PSR-SPP-24DC/TS/S - Uncategorized Phoenix Contact - Free user manual and instructions
Find the device manual for free PSR-SPP-24DC/TS/S Phoenix Contact in PDF.
Pick your language and provide your email: we'll send you a specifically translated version.
| Product Type | Safety Relay |
| Brand | Phoenix Contact |
| Model | PSR-SPP-24DC/TS/S |
| Supply Voltage | 24 V DC |
| Dimensions (W x H x D) | 22.5 x 99 x 114.5 mm |
| Weight | Approx. 150 g |
| Housing Material | Plastic, polyamide |
| Protection Rating | IP20 |
| Operating Temperature | -25 °C to +60 °C |
| Main Functions | Monitoring of safety circuits, emergency stop, protection of people and machines |
| Number of Channels | 1 safety channel |
| Contact Type | Forced-guided output contacts |
| Inputs | For safety sensors (pushbuttons, light curtains) |
| Outputs | 2 NC (normally closed) output contacts |
| Diagnostics | Green LED for operating status, red LED for fault |
| Maintenance and Cleaning | Check connections regularly, clean housing with a dry, lint-free cloth |
| Safety | Compliant with EN ISO 13849-1 (PL e, Cat. 4) |
| Spare Parts and Repairability | Device not field-repairable, must be replaced if defective |
| General Information | Designed for automation and safety applications in industry |
Frequently Asked Questions - PSR-SPP-24DC/TS/S Phoenix Contact
What is the supply voltage of the PSR-SPP-24DC/TS/S?
The supply voltage is 24 V DC (direct current).
How to wire this safety relay?
Connect the safety sensors to the inputs (terminals S11, S12, etc.) and the contactors to the NC outputs (terminals 13-14, 23-24). Refer to the wiring diagram in the manual.
What do the LEDs on the device mean?
The green LED indicates that the relay is active (operating status). The red LED signals a fault or safety interruption.
Can I use this module with light curtains?
Yes, it is compatible with light curtains and other safety sensors such as emergency stop buttons.
What is the achieved performance level (PL)?
This relay can achieve PL e according to EN ISO 13849-1, depending on wiring and choice of external components.
How to perform diagnostics on the device?
Check the LEDs, perform periodic safety tests by simulating a fault (opening the safety circuit). Use a multimeter to check the output contacts.
What are the exact dimensions?
The dimensions are 22.5 mm width, 99 mm height, and 114.5 mm depth.
How to clean the housing?
Use a dry, lint-free cloth. Do not use solvents or abrasive products.
What to do if a fault is detected?
The device must be replaced immediately. It is not repairable on site. Check the wiring and sensors before ordering a new module.
Is this module suitable for category 4 applications?
Yes, it allows the realization of category 4 applications according to EN ISO 13849-1, provided redundant wiring and appropriate structure.
User questions about PSR-SPP-24DC/TS/S Phoenix Contact
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
No questions yet. Be the first to ask one.
Download the instructions for your Uncategorized in PDF format for free! Find your manual PSR-SPP-24DC/TS/S - Phoenix Contact and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. PSR-SPP-24DC/TS/S by Phoenix Contact.