Camille Bauer SIRAX BT5700 - Electrical measuring device

SIRAX BT5700 - Electrical measuring device Camille Bauer - Free user manual and instructions

Find the device manual for free SIRAX BT5700 Camille Bauer in PDF.

📄 31 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice Camille Bauer SIRAX BT5700 - page 6
Pick your language and provide your email: we'll send you a specifically translated version.
Product TypeMultifunction Power Transducer
Dimensions (H x W x D)96 x 96 x 80 mm
WeightApprox. 0.4 kg
Power Supply24-230 V AC/DC (50/60 Hz)
Measured ParametersVoltage, Current, Active Power, Reactive Power, Apparent Power, Power Factor, Frequency, Energy
Input Voltage (Nominal)Up to 600 V AC (L-L)
Input Current (Nominal)1 or 5 A AC (via external CT)
DisplayBacklit LCD, multi-line
Accuracy (Active Power)Class 0.5S per IEC 61557-12
Communication InterfaceModbus RTU (RS485)
Outputs2 digital outputs (alarm/pulse), 1 analog output (0-20 mA or 4-20 mA)
MountingPanel mount, cutout 92 x 92 mm
Protection Rating (Front)IP54
Operating Temperature-10°C to +55°C
Humidity5-95% RH (non-condensing)
Electrical SafetyIEC 61010-1, CAT III 300V
EMCIEC 61326-1
ConfigurationVia front panel buttons or software
Data LoggingMin/max/average values, up to 16 parameters
Harmonics AnalysisUp to 31st harmonic

Frequently Asked Questions - SIRAX BT5700 Camille Bauer

What is the power supply requirement for the SIRAX BT5700?
The device accepts a wide range supply from 24 to 230 V AC/DC (50/60 Hz). No external adapter is needed.
How do I connect the current transformers?
Use external CTs with secondary rating of 1 A or 5 A. Connect them to the designated terminals as shown in the wiring diagram. Ensure correct polarity.
Can I communicate with the device via Modbus?
Yes, the BT5700 supports Modbus RTU over RS485. Default baud rate is 9600, data bits 8, parity even, stop bits 1. Address range 1-247.
How to configure the analog output?
Through the front panel menu, select 'Analog Output' and set the parameter (e.g., active power), scaling (0 to 100%), and output type (0-20 mA or 4-20 mA).
What does the alarm output do?
The two digital outputs can be programmed for alarm (over/under limits) or pulse output for energy metering. Configure thresholds via setup.
Is the device suitable for three-phase systems?
Yes, it supports single-phase, three-phase 3-wire, and three-phase 4-wire systems. Select the wiring configuration in the setup.
How to reset the energy counter?
Go to 'Energy Management' menu, select 'Reset Energy', confirm with password (default 0000). Note: This resets all energy registers.
What is the accuracy class of the device?
The accuracy for active power is Class 0.5S according to IEC 61557-12. Voltage and current measurements have 0.2% accuracy.
Can I view harmonics on the display?
Yes, the device can display individual harmonics up to the 31st for voltage and current. Navigate to 'Power Quality' menu.
How to clean the front panel?
Use a soft, dry cloth. Do not use solvents or abrasive cleaners. The front is rated IP54 for dust and splash protection.

User questions about SIRAX BT5700 Camille Bauer

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Electrical measuring device in PDF format for free! Find your manual SIRAX BT5700 - Camille Bauer and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. SIRAX BT5700 by Camille Bauer.

USER MANUAL SIRAX BT5700 Camille Bauer

Operating Instructions

SIRAX BT5700

Programmable transducer for heavy current variables

CAMILLE BAUER Q1 499.9 VAr S1 1.150 kVA SIRAX BT5700 GND

Camille Bauer SIRAX BT5700 - SIRAX BT5700 - 2

CAMILLE BAUER

Camille Bauer Metrawatt AG

Aargauerstrasse 7

CH-5610 Wohlen/Switzerland

Tel: +41 56 618 21 11

Fax: +41 56 618 21 21

info@cbmag.com

www.camillebauer.com

Warning notices

In this document warning notices are used, which you have to observe to ensure personal safety and to prevent damage to property. Depending on the degree of danger the following symbols are used:

Camille Bauer SIRAX BT5700 - Warning notices - 1

If the warning notice is not followed death or severe personal injury will result.

Camille Bauer SIRAX BT5700 - Warning notices - 2

If the warning notice is not followed damage to property or severe personal injury may result.

Camille Bauer SIRAX BT5700 - Warning notices - 3

If the warning notice is not followed the device may be damaged or may not fulfill the expected functionality.

Qualifi ed personnel

The product described in this document may be handled by personnel only, which is qualified for the respective task. Qualified personnel have the training and experience to identify risks and potential hazards when working with the product. Qualified personnel are also able to understand and follow the given safety and warning notices.

Intended use

The product described in this document may be used only for the application specified. The maximum electrical supply data and ambient conditions specified in the technical data section must be adhered. For the perfect and safe operation of the device proper transport and storage as well as professional assembly, installation, handling and maintenance are required.

Disclaimer of liability

The content of this document has been reviewed to ensure correctness. Nevertheless it may contain errors or inconsistencies and we cannot guarantee completeness and correctness. This is especially true for different language versions of this document. This document is regularly reviewed and updated. Necessary corrections will be included in subsequent version and are available via our webpage http://www.camillebauer.com.

Feedback

If you detect errors in this document or if there is necessary information missing, please inform us via e-mail to: customer-support@camillebauer.com

Table of content

1. Introduction ...... 4

1.1 Purpose of this document 4
1.2 Scope of supply 4
1.3 Further documents 4

2. Safety notes 4

3. Device overview 5

3.1 Brief description 5
3.2 Available measurement data 5

4. Mechanical mounting 6

4.1 Mounting
4.2 Demounting of the device 6

5. Electrical connections ...... 7

5.1 General safety notes 7
5.2 Cross sections and tightening torques 7

5.3 Inputs

5.4 Power supply 9
5.5 Connection diagram 9
5.6 Modbus interface RS485 9

6. Commissioning 9

6.1 Operating the device 10
6.2 Setup Parameter Screen 10

7. Programming 13

7.1. Password Protection 1
7.1.1 Change Password New / Change Password 14

7.2 Menu selection 15

7.2.1 System type selection 15

7.2.2 Potential Transformer primary Value 16
7.2.3 Current Transformer Primary Value 16
7.2.4 Current Transformer Secondary Value 17
7.2.5 Energy Display on modbus 17
7.2.6 RESET of parameters 18
7.2.7 Modbus Address 18
7.2.8 Auto scrolling 19
7.2.9 Start current Cutoff 19
7.2.10 Baud Rate 20
7.2.11 Parity and Stop bits 20
7.2.12 Energy rate 20
7.2.13 Energy digit reset count 21

8. Phasor Diagram 22

9. Programming via the RS485 (Modbus) interface 22

10. Service, maintenance and disposal 23

10.1 Repair work and modifi cations 23
10.2 Calibration and new adjustment.... 23

10.3 Cleaning 23
10.4 Disposal 23
10.5 Return 23

11. Technical data 24

12. Dimensional drawings 26

13. Interface Definition Modbus RTU 27

13.1 Modbus functions 27
13.2 Data types 27

1. Introduction

1.1 Purpose of this document

This document describes the universal measurement device SIRAX BT5700. It is intended to be used by:

• Service and maintenance personnel
- Planners

• Installation personnel and commissioning engineers

Scope

This handbook is valid for all hardware versions of the BT5700. Some of the functions described in this document are available only, if the necessary optional components are included in the device.

Required knowledge

A general knowledge in the field of electrical engineering is required. For assembly and installation of the device knowledge of applicable national safety regulations and installation standard is required.

1.2 Scope of supply

• Measurement device SIRAX BT5700
- Safety instructions (multiple languages)

1.3 Further documents

The following documents are provided electronically via www.camillebauer.com:

• Safety instructions SIRAX BT5700
- Operating Instructions SIRAX BT5700
• Data sheet SIRAX BT5700

2. Safety notes

Camille Bauer SIRAX BT5700 - Safety notes - 1

Device may only be disposed in a professional manner!

Camille Bauer SIRAX BT5700 - Safety notes - 2

The installation and commissioning should only be carried out by trained personnel.

Check the following points before commissioning:

  • that the maximum values for all the connections are not exceeded, see „Technical data“ section,
  • that the connection wires are not damaged, and that they are not live during wiring,
  • that the power flow direction and the phase rotation are correct.

The instrument must be taken out of service if safe operation is no longer possible (e.g. visible damage). In this case, all the connections must be switched off. The instrument must be returned to the factory or to an authorized service dealer.

It is forbidden to open the housing and to make modifications to the instrument. The instrument is not equipped with an integrated circuit breaker. During installation check that a labeled switch is installed and that it can easily be reached by the operators.

Unauthorized repair or alteration of the unit invalidates the warranty.

3. Device overview

3.1 Brief description

The universal measuring device SIRAX BT5700 is suited for fixed mounting and the measurement of Voltage, current, frequency, power, energy (active / reactive / apparent), power factor, phase angle, etc in low voltage switchgear. The units are designed for unbalanced load network forms of 3-phase mains with 3- or 4-wire.

3.2 Available measurement data

Measured Parameters Units 3P 3W 3P 4W
System Voltage U V • •
Voltage U1N / U2N / U3N V – •
Voltage U12 / U23 / U31 V • •
System Current I A • •
Current I1 / I2 / I3 A • •
Neutral Current IN (calc.) A – •
Frequency F Hz • •
Active Power P / P1 / P2 / P3kW- •
Reactive Power øQ / Q1 / Q2 / Q3kVAr- •
Apparent Power øS / S1 / S2 / S3kVA- •
Power Factor PF1 / PF2 / PF3-- •
Phase Angle Phi1 / Phi2 / Phi3degree- •
Active Import Energy (8 Digit resolution)kWh• •
Active Export Energy (8 Digit resolution)kWh• •
Capacitive Reactive Energy (8 Digit resolution)kVArh• •
Inductive Reactive Energy (8 Digit resolution)kVArh• •
Apparent Energy (8 Digit resolution)kVAh• •
Max Current DemandA • •
Apparent Power DemandkVA• •
Min / Max System VoltageV • •
Min / Max System CurrentA • •

4. Mechanical mounting

The SIRAX BT5700 is designed for panel mounting.

Camille Bauer SIRAX BT5700 - Mechanical mounting - 1

Please ensure that the operating temperature limits are not exceeded when determining the place of mounting (place of measurement): -10 ... +55° C

4.1 Mounting

Dimensional drawing BT5700: See section 11

Any mounting position is possible. Device may be clipped onto a top-hat rail according EN50022 in a cabinet.

Technical diagram of a mechanical component with a textured base and internal slot, showing no text or symbols.

4.2 Demounting of the device

Disassembly of the device requires that all connected wires be without current. First, remove all push terminals and the wires of the current and voltage inputs. Ensure that possible current transformers are short-circuited before the current connections on the device are opened.

Mechanical assembly diagram showing a tool interacting with a component, with no visible text or symbols.

5. Electrical connections

Camille Bauer SIRAX BT5700 - Electrical connections - 1

Ensure under all circumstances that the leads are free of potential when connecting them!

5.1 General safety notes

Camille Bauer SIRAX BT5700 - General safety notes - 1

Please observe that the data on the type plate must be adhered to!

The national provisions have to be observed in the installation and material selection of electric lines!

Symbol Meaning
Camille Bauer SIRAX BT5700 - General safety notes - 2Device may only be disposed of in a professional manner!
Camille Bauer SIRAX BT5700 - General safety notes - 3Double insulation, device of protection class 2
CAT III Measurement category CAT III for current / voltage inputs, power supply and relay outputs
Camille Bauer SIRAX BT5700 - General safety notes - 4CE conformity mark. The device fulfi IIs the requirements of the applicable EC directives. See declaration of conformity.
Camille Bauer SIRAX BT5700 - General safety notes - 5Caution! General hazard point. Read the operating instructions.
Camille Bauer SIRAX BT5700 - General safety notes - 6Attention: Danger to life!
(17TCB)Please note

5.2 Cross sections and tightening torques

Terminals 1 ... 14

Single wire: ≤ 4,0mm2 or multiwire with end splices: 2× 2,5mm2

Torque: 0.5 ... 0.6Nm rsp. 4.42 ... 5.31 lbf in

Terminal A, B, G

Single wire: ≤ 1,5mm2 or multiwire with end splices: 2 × 0,5mm2

Torque: max. 0.5 Nm rsp. 4.42 lbf in

5.3 Inputs

Camille Bauer SIRAX BT5700 - Inputs - 1

All voltage measurement inputs must originate at circuit breakers or fuses rated by 1 Amps. This does not apply to the neutral connector. You have to provide a method for manually removing power from the device, such as a clearly labeled circuit breaker or a fused disconnect switch.

When using voltage transformers you have to ensure that their secondary connections never will be short-circuited.

Camille Bauer SIRAX BT5700 - Inputs - 2

No fuse may be connected upstream of the current measurement inputs!

When using current transformers their secondary connectors must be short-circuited during installation and before removing the device. Never open the secondary circuit under load.

The connection of the inputs depends on the configured system (connection type).

5.4 Power supply

Camille Bauer SIRAX BT5700 - Power supply - 1

A marked and easily accessible current limiting switch has to be arranged in the vicinity of the device for turning off the power supply. Fusing should be 10 Amps or less and must be rated for the available voltage and fault current.

5.5 Connection diagram

Three wire, three phase system, unbalanced load, Aron connection (3P 3W)

L1 L2 L3 ② ① ③ ⑦ ⑨ ⑩ ⑬ ⑮ P1 S1 P1 S1 L N AUX SUPPLY L O A D

Direct connection

Four wire, three phase system, unbalanced load (3P 4W)

2 11 1 7 94 8 5 8 L N AUX SUPPLY P1 S1 P1 S1 P1 S1 L O A D L1 L2 L3 N

Direct connection

Input U U1 U2 U3 N 2 5 8 11 13 14 2 5 8 11 13 14 CAMILLE BAUER Q1 499.9 Var 51 1.150 kVA SIRAX BT5786 RS485 A B Gnd I1 I1' I2 I2' I3 I3' 1 3 4 6 7 9 Input-I

5.6 Modbus interface RS485

Via the optional Modbus interface measurement data may be provided for a superior system.

+3.3 / +5V Rs Rx/Tx+,A Rt Rx/Tx-,B Rs GND MASTER RS485 Bus 1) A B G A B G A B G A B G A B G

1) One ground connection only. This is possibly made within the master (PC).
Rt: Termination resistors: 120 Ω each for long cables (> approx. 10 m)
Rs: Bus supply resistors, 390 Ω each

The signal wires (A, B) have to be twisted. GND (G) can be connected via a wire or via the cable screen. In disturbed environments shielded cables must be used. Supply resistors (Rs) have to be present in bus master (PC) interface. Stubs should be avoided when connecting the devices. A pure daisy chain network is ideal.

You may connect up to 32 Modbus devices to the bus. A proper operation requires that all devices connected to the bus have equal communication settings (baud rate, transmission format) and unique Modbus addresses.

The bus system is operated half duplex and may be extended to a maximum length of 1200 m without repeater.

6. Commissioning

Camille Bauer SIRAX BT5700 - Commissioning - 1

Before commissioning you have to check if the connection data of the device match the data of the plant.

If so, you can start to put the device into operation by switching on the power supply and the measurement inputs.

SIRAX BT5700
ORDER CODE: 175275
SR No.: 15/11/0001
CLASS: 0.5 CAT III 300V Max. V40.05
INPUT: 3PH. 440 V L - L, 5A/1A, 45...65Hz
OPTION: RS485
AUXILIARY: 12...48V DC, 4VA

Label version RS485

6.1 Operating the device

CAMILLE BAUER Q1 499.9 VAr S1 1.150 kVA SIRAX BTTRON DOWN UP

SIRAX BT5700 can be configured and programmed at site for the following: PT Primary, CT Primary, CT Secondary (5A or 1A) & three wire, three phase system or four wire, three phase system. The front panel has two push buttons through which the User may scroll through the available measurement readings, reset the energy (Import/Export) Min/Max (System Voltage & System Current) & configure the product.

Operation is performed by means of 2 keys:

2 keys "UP" und "DOWN" for navigation and for the selection of values.

6.2 Setup Parameter Screen

graph TD A["CODE (password)"] --> B["Enter password (Section 7.1)"] B --> C["Change password (Section 7.1.1)"] C --> D["Sys Type (Section 7.2.1)"] D --> E["PT PRI (Section 7.2.2)"] E --> F["CT PRI (Section 7.2.3)"] F --> G["CT SEC (Section 7.2.4)"] G --> H["Energy OP (Section 7.2.5)"] H --> I["RESET…

CAMILLE BAUER SysV 239.6 V SysA 4.996 A SIRAX MT+100 A B God

Screen 1: System screen (U, I)

CAMILLE BAUER System Power SysP 6.612 kW SIRAX MT4000 A B Grid

Screen 2: System Power (P)

CAMILLE BAUER Line-Neutral (V) L1N 238.9 V SIRAX MTmm A B Grid

Screen 3: Line to neutral Voltage (VL1N) (4 Wire only)

CAMILLE BAUER L2N 240.3 V L3N 238.9 V SIRAX MTmax A B Grid

Screen 4: Line to neutral Voltage (U2N, U3N) (4 Wire only)

CAMILLE BAUER Line-Line (V) L12 415.2 V SIRAX MTCH A B C Add

Screen 5: Line to line Voltage (U12)

CAMILLE BAUER L23 414.7 V L31 415.1 V SIRAX MTOSI A B Gnd

Screen 6: Line to line (U23, U31) Voltage

CAMILLE BAUER Line Current IL1 4.998 A SRAX MT SALAWA FULCH TINELUS A B Grid

Screen 7: Line Current (I1)

CAMILLE BAUER IL2 4.998 A IL3 4.998 A SIRAX MT600 A B Grid

Screen 8: line Currents (I2, I3)

CAMILLE BAUER SyPF 1.000 Freq 50.02 Hz SIRAX MT400 A B Grid

Screen 9: System Power factor, Frequency (Pf, F)

CAMILLE BAUER Neutral Current In 0.015 A SIRAX MT400 A B Gnd

Screen 10: Neutral Current (IN) (4 Wire only)

CAMILLE BAUER System Power SysP 3.612 kW SIRAX MT400 A B Good

Screen 11: System Active Power (P)

CAMILLE BAUER SysQ 1.612 VAr SysS 3.622 kVA SERAX MT+000 A B Gnd

Screen 12: System Powers (Q, S)

CAMILLE BAUER ActiveEnergy Imp 02.006012 kWh SIRAX MT700 A B GND

Screen 13: Active Energy ( Pinc )

CAMILLE BAUER ActiveEnergy Exp 836.96582 kWh SIRAX MTmm A B Grid

Screen 14: Active energy ∫P_out)

CAMILLE BAUER ReactiveEner Imp 04.012034 kVArh SIRAX MT A B Grid

Screen 15: Reactive Energy (∫ Q_inc)

CAMILLE BAUER ReactiveEner Exp 08.132194 kVArh SERAX MT/VIR A B Gnd

Screen 16: Reactive energy (∫ Q_out)

CAMILLE BAUER Apparent Energy 840.37521 kVAh SIRAX MT200 MUTTERIOR FLEXIBLE A B GND

Screen 17: Apparent energy (∫S)

CAMILLE BAUER MinV 160.3 V Minl 2.076 A SIRAX MT200 A B Gnd

Screen 18: Min values (Umin, Umax)

CAMILLE BAUER MaxV 271.3 V MaxI 5.826 A SIRAX MT000 MINI-00000000000000000000000000000000000000000000000000000000000000000000000000000000 A B God

Screen 19: Max values (Umin, Umax)

CAMILLE BAUER Phase1 Power P1 1.195 kW SRAX MToss A B Gnd

Screen 20: Phase 1 Active Power (P1) (4 Wire only)

CAMILLE BAUER Q1 1.383 VAr S1 1.201 kVA SIRAX MT100 A B Grid

Screen 21: Phase 1 Power (Q1, S1) (4 wire only)

CAMILLE BAUER Phase2 Power P2 1.197 kW SIRAX MTTRX A B Gnd

Screen 22: Phase 2 Active Power (P2) (4 wire only)

CAMILLE BAUER Q2 1.485 VAr S2 1.205 kVA SIRAX MT A B Gnd

Screen 23: Phase 2 Power (Q2, S2) (4 wire only)

CAMILLE BAUER Phase3 Power P3 2.001 kW SIRAX MT400 A B Grid

Screen 24: Phase 3 Power Active (P3) (for 4 Wire only)

CAMILLE BAUER Q3 1.124 VAr S3 1.215 kVA SIRAX MTV A B Sed

Screen 25: Phase 3 Power (Reactive/Apparent) (Q3, S3) (4wire only)

CAMILLE BAUER Phase Angle Phi1 000.1 SRAX MTone A B Gout

Screen 26: Phase angle (phase 1) (Phi1) (for 4 Wire only)

CAMILLE BAUER Phi2 000.2 Phi3 000.4 SIRAX MTAM A B Gnd

Screen 27: Phase angle (phase 2, 3) (Phi 2, Phi 3) (for 4 Wire only)

CAMILLE BAUER Power Factor PF1 0.996 SIRAX MT/TSR A B Grid

Screen 28: Power factor (phase 1) (PF) (for 4 Wire only)

CAMILLE BAUER PF2 0.992 PF3 0.989 SIRAX MTme A B Grid

Screen 29: Power factor (phase 2, 3) (PF2, PF3) (for 4 Wire only)

7. Programming

The following sections comprise step by step procedures for configuring the SIRAX BT5700 for individual user requirements.

To access the set-UP screens, press and hold the “☐ DOWN” and “☐ UP” Key simultaneously for 5 seconds. This will take the User into the Password Protection Entry Stage (Section 7.1).

7.1. Password Protection

Password protection can be enabled to prevent unauthorised access to set-UP screens, by default password protection is not enabled. Password protection is enabled by selecting a four digit number other than 0000, setting a password of 0000 disables the password protection.

CAMILLE BAUER CODE : *--- SIRAX MT5700 A B Gnd

Enter Password, prompt for first digit. (*Denotes that the digit will be flashing.

Press “ (DOWN) ” key to scroll the value of the first digit From 0 through 9, the value will wrap from 9 round to 0. Press “UP ” key to advance to next digit.

In the special case, where password is "0000", pressing the "UP" key when prompted for first digit will advance to the password "confirmed" screen.

CAMILLE BAUER CODE : 1*-- SIRAX MT5700 MULTIPARATE A B Gnd

Enter Password, first digit entered, prompt for second digit.

(*Denotes that the digit will be fl ashing).

Press “(DOWN)” key to scroll the value of the first digit From 0 through 9, the value will wrap from 9 round to 0. Press “UP” key to advance to next digit.

CAMILLE BAUER CODE : 12*- SIRAX MT5700 A B Gnd

Enter Password, second digit entered, prompt for third digit.

(*Denotes that the digit will be fl ashing.

Press "DOWN" key to scroll the value of the first digit From 0 through 9, the value will wrap from 9 round to 0.

Press "UP" key to advance to next digit.

CAMILLE BAUER CODE : 123* SIRAX MT5700 MULTIQUETRICAL A B Gnd

Enter Password, third digit entered, prompt for fourth digit.

(* Denotes that digit will be fl ashing).

Use the "DOWN" key to scroll the value of the fourth digit from 0 through to 9, the value will wrap from 9 round to 0.

Press the "UP" key to advance to verification of the password.

CAMILLE BAUER CODE : 1234 SIRAX MT5700 MULTISSIONAL TRANSFER A B Gnd

Enter Password, fourth digit entered, awaiting verification of the password.

Password confirmed
CAMILLE BAUER CODE : 1234 SET OK SIRAX MT6700 MULTI/OLECTRONIC SWITCHER A B Gnd

Pressing "DOWN" key will advance to the "New/change Password" entry stage (section 7.1.1)

Pressing the "UP" key will advance to the Menu selection screen. (See section 7.2).

Password Incorrect
CAMILLE BAUER CODE : 1334 INVALID SIRAX MT5700 A B Gnd

The unit has not accepted the Password entered. Pressing the "DOWN" key will return to the Enter Password stage.

Pressing the "UP" key exits the Password menu & returns operation to the measurement reading mode.

7.1.1 Change Password New / Change Password
CAMILLE BAUER CODE : *--- Edit SIRAX MT5700 MULTIFUNCTION TRANSFER A B Gnd

(* indicates that this digit will be fl ashing).

Pressing the "DOWN" key will scroll the value of the fi rst digit from 0 through to 9, the value will wrap from 9 round to 0. Pressing the "UP" key to advance the operation to the next digit & sets the fi rst digit, in this case "2".

CAMILLE BAUER CODE : 2*-- EditT SIRAX MT5700 A B Gnd

New / Change Password, first digit entered, prompting for second digit. (* indicates that this digit will be flashing).

Pressing the "DOWN" key will scroll the value of the second digit from 0 through to 9, the value will wrap from 9 round to 0.

Pressing the "UP" key to advance the operation to the next digit and sets the second digit, in this case to "3".

CAMILLE BAUER CODE : 23*- EditT SIRAX MT5700 MULTIQUES ENRIE A B Gnd

New / Change Password, second digit entered, prompting for third digit. (* indicates that this digit will be fl ashing).

Pressing the "DOWN" key will scroll the value of the third digit from 0 through to 9, the value will wrap from 9 round to 0.

Pressing the "UP" key to advance the operation to the next digit and sets the third digit, in this case to "4"

CAMILLE BAUER CODE : 234* EdiT SIRAX MT5700 A B Gnd

New / Change Password, third digit entered, prompting for fourth digit. (* indicates that this digit will be fl ashing).

Pressing the "DOWN" key will scroll the value of the fourth digit from 0 through to 9, the value will wrap from 9 round to 0.

Pressing the "UP" key to advance the operation to the "New Password Confirmed" and sets the fourth digit, in this case to "5"

New Password confirmed
CAMILLE BAUER CODE : 2345 SET OK SIRAX MT3700 MULTI FUNCTION TRANSICERS A B Gnd

Pressing the "DOWN" key will return to the "New/Change Password".

Pressing the "UP" key will advances to the system type Selection screen. (see section 7.2.1).

7.2 Menu selection

7.2.1 System type selection
CAMILLE BAUER SysType : 4 SIRAX MT5700 MULTISSIONAL PROCESICATOR A B Gnd

This screen is used to set the system type.

System type "3" for 3 phase 3 wire & "4" for 3 phase 4 wire system. Pressing "UP" key accepts the present value and advances to the "Potential transformer Primary value edit menu 7.2.2

Pressing "DOWN" key will enter system type Edit mode and scroll between 3 and 4.

Pressing "UP" key advances to the system type confirmation menu.

System Type Conformation
CAMILLE BAUER SysType : 4 SET OK SIRAX MT5700 MULTIFUNCTION TRANSICATOR A B Gnd

Pressing "UP" sets the displayed value and will advance to

"Potential Transformer Primary Value

Edit" menu. (See section 7.2.2)

Pressing "DOWN" key will return to the system type "Edit" menu.

7.2.2 Potential Transformer primary Value

The nominal full scale voltage which will be displayed as Line to Line voltage in four wire or 3 wire system. The value represent the voltage in kVLL.

Maximum Potential transformer primary value can be set to 692.8 kVLL or restricted to 666 MVA depends on previously set Current transformer (CT) primary value. The minimum value allowed is 100VLL.

CAMILLE BAUER PT PRI : 0.415 k VLL SIRAX MT6700 A B Gnd

Pressing "UP" key accepts the present value and then advances to Current transformer (CT) Primary value edit menu (section 7.2.3).

Pressing "DOWN" key enters into "Potential Transformer Primary Value Edit" mode.

Initially the multiplier must be selected. Pressing the "DOWN" key will move the decimal point position to the right unit it reaches # # # .# after which it will return to # # # #.

Pressing "UP" key selects the present multiplier (decimal point position) and advances to the "potential Transformer primary digit Edit" mode.

Potential Transformer Primary Digit edit
CAMILLE BAUER PT PRI : *.415 k EdiT SIRAX MT5700 MULTIFUNCTIONAL TRANSICATOR A B Gnd

(* denotes that the digit will be flashing)

Pressing the “DOWN” key will scroll the value of the most significant digit from 0 through to 9 unless the presently displayed Potential Transformer Primary Value together with the Current Transformer Primary Value, previously set, would result in maximum power of greater than 666MVA per phase, in which case the digit range will be restricted.

Pressing "UP" key accepts the present value at the cursor position and advances the cursor to the next less signifi cant digit.

When the least signifi cant digit has been set, pressing "DOWN" key will advance to the "Potential Transformer Primary Value Confir rmation" stage.

Potential transformer Primary value Confir rmation
CAMILLE BAUER PT PRI : *.415 k SET OK SIRAX MT5700 A B Gnd

If scaling is to be corrected, pressing "DOWN" key will return to the "Potential Transformer Primary Value Edit" stage with the digits fl ashing indicating that the multiplier (decimal point position) should be selected.

Pressing "UP" key sets the displayed value and then it will advance to Current transformer Primary Value selection menu (section 7.2.3).

7.2.3 Current Transformer Primary Value

The nominal Full Scale Current that will be displayed as the Line currents. This screen enables the user to display the Line currents inclusive of the transformer ratios, the values displayed represent the Current in Amps.

Maximum Current transformer primary value can be set to 9999 A or restricted to 666 MVA depends on previously set Potential transformer (PT) Primary value.

Pressing "UP" key accepts the present value and advances to the Current transformer Secondary value menu (section 7.2.4)

CAMILLE BAUER CT PRI : 0005 A SIRAX MT6700 MULTI/OFFICULAR TRANSICULAR A B Gnd

Pressing "DOWN" key will enter the "Current transformer

Transformer Primary Value Edit" mode. This will scroll the value of the most significant digit from 0 through to 9, unless the presently displayed Current Transformer Primary Value together with the Potential Transformer Primary Value results in a maximum power of greater than 666MVA in which case the digit range will be restricted, the value will wrap.

Example:

If primary value of PT is set as 692.8 kVLL (max value) then primary value of Current is restricted to 1157A.

Pressing "UP" key will advance curser to next less signifi cant digit. (*Denotes that decimal point will be flashing).

The Maximum Power restriction of 666 MVA refers to 120% of nominal current and 120% of Nominal voltage, i.e. 462.8MVA nominal power per phase.

When the least significant digit has been set, pressing "UP" key will advance to the "Current Transformer Primary Value Confirmation" stage.

The minimum value allowed is 1, the value will be forced to 1 if the display contains zero

CAMILLE BAUER CT PRI : 2500 A SET OK SIRAX MT3780 A B Gnd

Current Transformer Primary value confirmation

If the set value is to be corrected, pressing "DOWN" key Will re-enter the CT primary value edit stage.

Pressing "UP" key, sets the displayed value as CT primary and advances to Current transformer Secondary menu (section 7.2.4).

7.2.4 Current Transformer Secondary Value

CAMILLE BAUER CT SEC : 5 A SIRAX MT7780 MULTIQUINT END TRANSICULAR A B Gnd

The screen is used to set the secondary value for Current Transformer.

Pressing "UP" key accepts the present value and advances to Energy display on modbus menu. (section 7.2.5).

Pressing "DOWN" key enter into CT secondary value Edit and scrolls the value between 1 and 5.

After selecting the desired value, Pressing "UP" Enters into CT secondary value confirmation screen.

CAMILLE BAUER CT SEC : 5 A SET OK SIRAX MT5780 A B Gnd

CT Secondary value confirmation

Pressing "DOWN" key reenters the CT secondary value edit menu.

Pressing "UP" key sets the displayed value as CT secondary and advances to Energy display on modbus menu (section 7.2.5).

7.2.5 Energy Display on modbus

This screen enable user to set energy in terms of Wh / KWh / MWh on RS 485 Output depending as per the requirement. Same applicable for all types of energy.

CAMILLE BAUER Energy OP: 0001* EdiT SIRAX MT5760 WALI ELECTRICAL TRANSLICATOR A B Gnd

Pressing "UP" key accepts the presents value

and advances to the "Reset parameter" menu (See section 7.2.6).

Pressing the "DOWN" key will enter the "Energy Display

On Modbus Edit" mode and scroll the value through the values 1, 2 & 3 wrapping back to 1

1: Energy In Wh

2: Energy in kWh

3: Energy in MWh.

Pressing the "UP" key advances to the "Energy Display On Modbus Confirmation" menu.

CAMILLE BAUER Energy OP : 0001 SET OK SIRAX MT5780 MULTI FUNCTION TRANSICULAR A B Gnd

Energy Display On Modbus Confir rmation.

This screen will only appear following an edit of the Energy Display On Modbus.

Pressing the "DOWN" key will enter the "Energy Display

On Modbus Edit" stage by blanking the bottom line of the display.

Pressing "UP" key sets the displayed value and will advance to the "Reset parameter" menu. (See section 7.2.6)

Note: Default value is set to '2' i.e. Energy on Modbus will be in terms of kWh/kVArh/kVAh resp.

7.2.6 RESET of parameters

CAMILLE BAUER RESET ARAMETER ALL SIRAX MT5700 MULTIFUNCTION TRANSICUM A B Gnd

This screen is used to Reset the different parameters.

Pressing "UP" key resets the displayed parameters and advances to modbus address menu (section 7.2.7).

Pressing "DOWN" key scrolls the parameters to Reset From None, Energy, Min, Max, All and back to None.

Select the parameters which is to be Reset with "DOWN" Key. To reset the selected parameter press "UP" key.

After pressing "UP" key, it acknowledges the reset of parameter with "DONE" on display as shown.

CAMILLE BAUER RESETARAMETER DONE SIRAX | MT5780 MULTI PROFESSIONAL TRANSICUM A B Gnd

Further if another parameter is to be reset, press "DOWN" Key to scroll the parameter again.

Pressing "UP" key after DONE message displayed, advances the operation to modbus address menu. (Section 7.2.7)

7.2.7 Modbus Address

CAMILLE BAUER MODBUS ADD : 0*01 EdiT SIRAX MT5700 MULTISSIONAL TRANSMATION A B Gnd

This screen allows the user to set device address of instrument for RS 485 communication. The range of allowable address is 1 to 247. Pressing "DOWN" key enters into the Modbus Address edit mode.

Enter Address, prompt for first digit.

* denotes that the Digit will be fl ashing.

Pressing "DOWN" key scrolls the value of fl ashing digit from 0 to 2 and back to 0. Pressing "UP" key changes the curser position to next Less signifi cant digit.

CAMILLE BAUER MODBUS ADD : 01*1 EdiT SIRAX MT5700 MULTIFONTENS TRANSFER A B Gnd

Enter Address, first digit entered, prompt for second digit

* denotes that the Digit will be fl ashing.

Pressing "DOWN" key scrolls the value of flashing digit from 0 to 9 and back to 0.

Pressing "UP" key changes the curser position to next Less signifi cant digit.

CAMILLE BAUER MODBUS ADD : 013* EdiT SIRAX MT5700 MULTIFUNCTION TRANSICER A B Gnd

Enter address, second digit entered, prompt for third digit.

* denotes that the Digit will be flashing.

Pressing "DOWN" key scrolls the value of fl ashing digit from 0 to 9 and back to 0.

Pressing "UP" key enters the modbus address Confirmation screen.

CAMILLE BAUER MODBUS ADD : 0132 SET OK SIRAX | MT6700 MULTIFUNCTION | TRANSCEUT A B Gnd

7.2.8 Auto scrolling
CAMILLE BAUER AUTO SCROLL Disable SIRAX | MT5700 MULTIFUNCTIONAL TRANSICERS A B Gnd

CAMILLE BAUER AUTO SCROLL SET OK SIRAX MT5700 MALT FUNCTION TRANSITION A B Gnd

7.2.9 Start current Cutoff
CAMILLE BAUER 30mA Cutoff Disable SIRAX MT5700 MULTIFUNCTIONAL TRANSFER A B Gnd

CAMILLE BAUER 30mA Cutoff SET OK SIRAX MT5700 MULTI-100V/100V TRANS2.0V A B Gnd

Modbus address Confir rmation

Pressing "UP" key sets the modbus address & enters Into Auto scrolling selection menu (section 7.2.8).

Pressing "DOWN" key re-enters into Modbus address Setting menu.

This screen allows user to enable screen scrolling.

Pressing "DOWN" key scrolls between enable and disable. Select enable for Auto scrolling of screen and select Disable for fixed screen.

Pressing "UP" key enters into Auto scrolling Confirmation screen

Auto Scrolling Confir rmation

Pressing "UP" key, sets the selected option and advances to noise current cutoff menu (section 7.2.9)

Pressing "DOWN" key re-enters the auto scroll menu.

This screen allows user to set low start current cutoff at 30mA. Pressing "DOWN" key enters into edit mode and scrolls between Enable and disable.

Pressing "UP" key accepts the selected option and enters into 30mA cutoff confirmation screen.

30mA cutoff confirmation

Pressing "UP" key sets the selected option and advances to Baud rate selection menu (section 7.2.10).

Pressing "DOWN" key re-enters into 30mA cutoff selection menu.

7.2.10 Baud Rate

CAMILLE BAUER Baud Rate : 4800 Edit SIRAX | MT5700 MUTFUNCTIONAL TRANSICER A B Gnd

This screen allows user to set the baud rate for Rs485 communication.

Pressing "UP" key sets the present value and advances to Parity and stop bits menu (Section 7.2.11).

Pressing "DOWN" key enters into Baud rate Edit mode & scrolls The values from 2400, 4800, 9600 to 19200 & Back to 2400.

Pressing 'UP' key will advance to baud rate Confirmation screen.

Baud rate Confir rmation

CAMILLE BAUER Baud Rate : 9600 SET OK SIRAX MT5780 MUTRINCTIONAL TRANDCOR A B Gnd

Pressing "DOWN" keys re-enters into baud rate edit mode.

Pressing "UP" key sets the displayed value as baud rate and advances the operation to parity and stop bit menu (section 7.2.11).

7.2.11 Parity and Stop bits

CAMILLE BAUER Parity: NONE StopBit : 2 SIRAX | MT5780 MULTIFUNCTION | TRANSICUM A B Gnd

This menu allows user to set parity and number of stop bits for Rs485 communication interface.

The parity and number of stop bits are to be set in same menu.

Pressing "UP" key sets the displayed combination of Parity and stop bits and advances the operation to Energy rate selection menu (section 7.2.12).

Pressing "DOWN" key enters into edit mode and scrolls the Combination from Parity: None Stop bit:1, Parity: None Stop bit: 2

Parity: Even Stop bit: 1, Parity: Odd Stop bit: 1 and back to Parity: None Stop bit: 1. After selecting the desired combination, pressing "UP" Key enters into parity and number of stop bit confirmation screen.

Parity and number of stop bit confirmation.

Parity and number of stop bit confirmation

CAMILLE BAUER Parity: Even StopBit : 1 SIRAX | MTST80 MULFUNCTIONAL TRANSICER A B Gnd

Pressing "DOWN" key re-enters into the Parity and stop bit Edit menu.

Pressing "UP" key, sets the displayed values and advances the operation to Energy rate selection menu. (section 7.2.12).

7.2.12 Energy rate

CAMILLE BAUER Energy Rate : 00*1 Edit SIRAX MT5700 MATHFUNCTIONA TRANSFER A B Gnd

This menu allows user to set the energy reading Update rate from 1 to 60 minutes.

Pressing "DOWN" key enters into energy rate edit menu and scrolls the value of 10s digit from 0 to 6. If 1st digit is greater than 0 then 10s digit will wrap back to 0 from 5.

* denotes that the digit will be flashing.

Pressing "UP" key shifts the curser position from 10s digit to 1s digit. Value of 1st digit scrolls from 0 to 9 and again Wraps back to 0.

After setting desired value of 1s digit pressing "UP" key Enters into energy rate confirmation screen.

Energy rate confirmation

CAMILLE BAUER Energy rate : 0015 SET OK SiRAX MT5700 MULTIFUNCTIONAL TRANSICULAR A B Gnd

Pressing "DOWN" key re-enters into energy rate edit menu.

Pressing "UP" key sets the displayed value as energy update rate and then advance the operation to Energy digit reset count menu (section 7.2.13).

If energy rate is set to "00", then it sets "01" min as default value.

7.2.13 Energy Digit reset count

CAMILLE BAUER Enr rst cnt : 0007* EdiT S/RAX MT5700 MULTIFUNCTIONS TINNOLICUM A B Gnd

This screen enables user for setting maximum energy count after which energy will rollback to zero depends upon setting of Wh, kWh, & MWh.

Pressing the "UP" key sets the displayed value and then

SIRAX BT5700 exits from setup menu and starts normal operation.

Pressing the "DOWN" key will enter the Energy digit reset count edit mode. This will scroll the value of reset count from 7 to 14 for Wh, from 7 to 12 for KWh & from 7 to 9 for MWh.

E.g. If energy display on modbus is set Wh & If you set Energy digit count to 10 then energy will reset after "9,999,999,999" & then will Rollback to zero. Pressing "UP" key will advance to Energy digit reset count confirmation screen.

Energy digit reset count confirmation

CAMILLE BAUER Enr rst cnt : 0007 SET OK SIRAX MT5700 MULTISSIONAL TRANSICULAR A B Gnd

Pressing the "DOWN" key will re-enter Energy digit reset count edit mode.

Pressing the "UP" key sets the displayed value and will exits from setup menu and starts normal operation.

Note:

1) Default value is set to "8" i.e if energy count crosses 8 digit it will rollback to zero.
2) If Energy displays on modbus is set to (2: kWh) & energy digit reset count is set to 12. Energy screen on display will show "----" i.e. energy overflow when energy crosses the 11 digit count.....
3) If Energy displays on modbus is set to (3: MWh) & energy digit reset count is set to 9. Energy screen on display will show “----” i.e. energy overflow when energy crosses the 8 digit count.....

8. Phasor Diagram

Quadrant 1: 0° to 90°

Quadrant 2: 90° to 180°

Quadrant 3: 180° to 270°

Quadrant 4: 270° to 360°

In this diagram a technical visualization of the current and voltage phasors is shown, using a clockwise rotation.

| Quadrant | Value | |----------|-------------| | Quadrant 1 | +0.500 | | Quadrant 2 | -0.866 | | Quadrant 3 | -0.866 | | Quadrant 4 | +0 | | Quadrant 5 | -0.500 | | Quadrant 6 | +0.866 | | Quadrant 7 | +0.500 | | Quadrant 8 | -0.500 | | Quadrant 9 | +0.500 | | Quadrant 10 | -0.500 | | Quadrant 11 |…

Connections Quadrant Sign of ActivePower (P)Sign of Reactive Power (Q)Sign of Power Factor (PF)Inductive/ Capacitive
Import 1 + P + Q + L
Import 4 + P - Q + C
Export 2 - P + Q - C
Export 3 - P - Q - L

Inductive means Current lags Voltage

Capacitive means Current leads Voltage

When the instrument displays Active power (P) with “+” (positive sign), the connection is “Import”.

When the instrument displays Active power (P) with “-” (negative sign), the connection is “Export”.

9. Programming via the RS485 (Modbus) interface

Follow the subsequent steps to program the transducer via the RS485 interface and Modbus:

Step 1: Connection

Connect the Modbus cable according to the connection diagram in Chapter 5.5. Please observe also the information in the Modbus (RS485) interface definition in Chapter 13.

Step 2: Programming

Program SIRAX BT5700 via the Modbus RTU interface and the CB-Configurator software. Please observe the detailed Modbus description in Chapter 13.

Connect the power supply to SIRAX BT5700 before programming.

10. Service, maintenance and disposal

Camille Bauer SIRAX BT5700 - Service, maintenance and disposal - 1

For devices that have not been opened in the factory, no warranty or guarantee can be assumed.

10.1 Repair work and modifications

Repair work and modifications shall exclusively be carried out by the manufacturer. Do not open the housing of the device. In case of any tampering with the device, the guaranty claim shall lapse. We reserve the right of changing the product to improve it.

10.2 Calibration and new adjustment

Each device is adjusted and checked before delivery. The condition as supplied to the customer is measured and stored in electronic form.

The uncertainty of measurement devices may be altered during normal operation if, for example, the specified ambient conditions are not met.

10.3 Cleaning

The display and the operating keys should be cleaned in regular intervals. Use a dry or slightly moist cloth for this.

Camille Bauer SIRAX BT5700 - Cleaning - 1

Damage due to detergents

Detergents may not only affect the clearness of the display but also can damage the device.

Therefore, do not use detergents.

10.4 Disposal

Camille Bauer SIRAX BT5700 - Disposal - 1

The disposal of devices and components may only be realised in accordance with good professional practice observing the country-specific regulations. Incorrect disposal can cause environmental risks.

10.5 Return

All devices delivered to Camille Bauer Metrawatt AG shall be free of any hazardous contaminants (acids, lyes, solutions, etc.). Use original packaging or suitable transport packaging to return the device.

Camille Bauer SIRAX BT5700 - Return - 1

Damage by returning

Damages caused by improper returning, no warranties or guarantees can be given.

11. Technical data

System

Connection types: Three wire, three phase system, unbalanced load

Four wire, three phase system, unbalanced load

Inputs

Nominal current: 1 A / 5 A

Maximum continuous input current: 120% of Rated value

Nominal input current burden: 0,6 VA per Phase

Max short duration current input: 20 x Rated Value (1s application repeated 5 times at 5 min. intervals)

System CT Primary values: Std. Values 1 to 9999 A (1 or 5 A secondaries)

Nominal voltage: 110 V

L-L (63.5 V LN )

Max continuous input voltage: 120% of Rated Value

Max short duration input voltage: 2 x Rated Value (1S application repeated 10 times at 10s intervals)

Nominal input voltage burden: 0.2VA approx. per phase

System PT primary value: 100 V

LL to 692.8 KV LL

Auxiliary Supply

Auxiliary supply burden:

<4VA approx.

Operating Measuring Ranges

Voltage:5 ... 120% of Rated Value
Current:5 ... 120% of Rated Value
Frequency:40 ... 70 Hz
Power factor:0.6 Lag ... 1 ... 0.6 Lead

Accuracy

Voltage:± 0,5% of range
Current:± 0,5% of range
Frequency:± 0,15% of mid frequency
Active power:± 0,5% of range
Re-active power:± 0,5% of range
Apparent Power:± 0,5% of range
Active energy:± 0,5% of range
Re-active energy:± 0,5% of range
Apparent energy:± 0,5% of range
Power Factor:± 1 % of Unity
Angle:± 1 % of range (0 - 360)

Camille Bauer SIRAX BT5700 - Inputs - 1

Variation due to influence quantity is 100% of class index for all other parameters except energy.

Mechanical attributes

Orientation:Any
Bezel size:96 mm x 96 mm
Panel cut out:92+0.8 mm x 92+0.8 mm detail see cut out drawing
Overall depth:<80mm
Housing material:Lexan 940 (polycarbonate),
V-0 acc. to UL94, self-extinguishing, non-dripping, free of halogen

Weight: ca. 460 g

Dimensions: see dimensional drawings

Display: 2 Line Display with backlight, update rate approx. 1 sec.

User interface: 2 push buttons

Terminals:

Screw-type

terminals

Reference conditions for Accuracy

Reference: 23 °C ± 2 °C

temperature Input frequency: 50 or 60Hz ± 2%

Input waveform: Sinusoidal (distortion factor 0.005)

Input Voltage: Rated value

Auxiliary supply voltage: Rated Value ± 1 %

Auxiliary supply frequency: Rated Value ± 1 %

Power Factor: 0.8 Lag...1...0.8 Lead

Nominal range of use of influence quantities for measurands

Voltage:

5 ... 120 % of Rated Value

Current:

5 ... 120 % of Rated Value

Input frequency:

Rated Value ± 10 %

Temperature:

0 to 50 °C

Auxiliary supply voltage: Rated Value ± 10 %

Auxiliary supply frequency: Rated Value ± 10 %

Temperature Coefficient:

0.025% / °C for Voltage (50 ... 120% of Rated Value)

(For Rated value range of use 0... 50 °C )

0.05% / °C for Current ( 10 ... 120% of Rated Value )

Error change due to variation of

an influence quantity:

2 * Error allowed for the reference condition applied in the test

Standards

Terms, definitions and test methods:

EN60688

EMC Immunity:

EN61326

10V/m min-Level 3 industrial low level electromagnetic radiation environment EN61000-4-3

Safety:

EN61010-1:2010, EN61010-2:030

IP for water & dust:

EN60529

Isolation

Dielectric voltage withstand test

2.2 kV RMS 50 Hz for 1 minute between all electrical circuits

Environmental

Operating temperature: -5 to 60 °C

Storage temperature:

-20 to +65 °C

Relative humidity:

0 ... 90 %

Warm UP time:

min. 3 minute

Shock :

15g in 3 planes

Vibration:

10 ... 55 Hz, 0.15mm amplitude

Outputs

Modbus (RS485)

via plug-in terminal (A, B, G)

Protocol:

Modbus (RS485)

Baud rate:

2'400, 4'800, 9'600, 19'200 Baud (programmable)

Parity:

Odd or even, with 1 Stop Bit, or None with 1 or 2 Stop Bits

11. Dimensional drawings

CAMILLE BAUER Q1 400.0 VAI- S1 1.150 kVA SIRAX BTA 96mm 96mm 117mm

3 PHASE 4 WIRE 3 PHASE 3 WIRE

13. Interface Defi nition Modbus RTU

SIRAX BT5700 supports Modbus RTU protocol (RS485).

The permissible address range for the BT5700 is between 1 and 247. Broadcast Mode (address 0) is not allowed.

The maximum latency time of an BT5700 is 200ms i.e. this is the amount of time that can pass before the first response character is output.

After sending any query through software (of the Master), it must allow 200ms of time to elapse before assuming that the BT5700 is not going to respond. If slave does not respond within 200 ms, Master can ignore the previous query and can issue fresh query to the slave.

13.1 Modbus functions

Following code functions are provide:

Function codeFunction Address
03 Read holding registers 40001 to 40081
04 Read input registers 30001 to 30231
16 Presets multiple registers 40001 to 40081

Example of read out measurement

Query:

Device address Function code Start address Nr. of registerCRC
0x050x040x000C0x00060xB18F

Response:

Device addressFunction codeNr. of databytesDatabytesDatabytesDatabytesCRC
0x050x040x0C0x3F8A5AA70x3F844A120x3F85DAD20x4759

Example of set slave address 5 to 2

Query:

Device addressFunction codeStart addressNr. of registerNr. of bytesDatabytes 0...3CRC
0x010x100x00140x00020x040x417000000xF387

Response:

Device addressFunction codeStart addressNr. of registerCRC
0x050x100x00140x00020x0048

Exception Cases: An exception code will be generated when BT5700 receives ModBus query with valid parity and error check but which contains some other error (e.g. Attempt to set floating point variable to an invalid value). The response generated will be "Function code" + 0x80.

01Illegal functionThe function code is not supported.
02Illegal data addressAttempt to access an invalid address or an attempt to read or write part of a fl oating point value.
03Illegal data valueAttempt to set a floating point variable to an invalid value.

13.2 Data types

All information are displayed as 32-bit float. There is no representation for floating point numbers in the Modbus specification.

The IEEE 754 standard as the most often used standard for the representation of floating numbers is applied.

  • The first register contains the bits 16 – 31
  • The second register contains the bits 0 – 15

32-Bit Float (Real32)

313023221570
ExponentMantisse
Sign
ABCD
0x40170x4C05
0100000000001011101001100000000101
+Exponent: 128-127=1Mantisse=1.01000000000101110100110000000101=1.18200743198394781526789

Measuring value P = 1.18200743198394781526789 * 2 1 = 2.3640149 W

TABLE 1: 3 X Registeradress (measured Parameter)

Adress (Register)Name Description3P 4W 3P 3W
30001 U1N Voltage phase L1to N • (L1-N) • (L1-L2)
30003 U2N Voltage phase L2to N • (L2-N) • (L2-L3)
30005 U3N Voltage phase L3to N • (L3-N) • (L3-L1)
30007 I1 Current in phase L1• •
30009 I2 Current in phase L2• •
30011 I3 Current in phase L3• •
30013 P1 Active power phase1 (L1 - N) • -
30015 P2 Active power phase2 (L2 - N) • -
30017 P3 Active power phase3 (L3 - N) • -
30019 S1 Apparent power phase1 (L1 - N) • -
30021 S2 Apparent power phase2 (L2 - N) • -
30023 S3 Apparent power phase3 (L3 - N) • -
30025 Q1Reactive power phase 1 (L1 - N)• -
30027 Q2Reactive power phase 2 (L2 - N)• -
30029 Q3Reactive power phase 3 (L3 - N)• -
30031 PF1Power factor phase 1 (L1 - N)• -
30033 PF2Power factor phase 2 (L2 - N)• -
30035 PF3Power factor phase 3 (L3 - N)• -
30037 Phi 1Phase angle 1• -
30039 Phi 2Phase angle 2• -
30041 Phi 3Phase angle 3• -
30043 ∅UAverage value of voltages• •
30045 ΣUSum of voltages• •
30047 ∅IAverage value of current• •
30049 ΣISum of current• •
30051 PAverage value of active power• •
30053 ΣPSum of active power• •
30055∅SAverage value of apparent power
30057 ΣSSum of apparent power• •
30059∅QAverage value of reactive power
30061 ΣQSum of reactive power• •
30063∅PFAverage value of power factor
30065 ΣPF Sum of power factor• -
30067∅PhiAverage value of phase angle
30069 ΣPhiSum of phase angle• -
30071 FSystem frequency• •
30073 fP_incActive power incoming• •
30075 fP_outActive power outgoing• •
30077 fQ_incReactive Power incoming• •
30079 fQ_outReactive Power outgoing• •
30081 fSApparent power• •
Adress (Register)Name Description3P 4W 3P 3W
30133 ∅U max.Maximum of the voltage average value ● ●
30135 ∅U min.Minimum of the voltage average value ● ●
30141 ∅I max.Maximum of the current average value ● ●
30143 ∅I min.Minimum of the current average value ● ●
30145 ∫P_inc* Active power incoming (kWh)● ●
30147∫P_out *Active power outgoing (kWh)
30149 ∫Q_inc* Reactive Power incoming (kvarh)● ●
30151 ∫Q_out* Reactive Power outgoing (kvarh)● ●
30153 ∫S *Apparent power (kvah)● ●
30201 U12Voltage phase L1 to L2● -
30203 U23Voltage phase L2 to L3● -
30205 U31Voltage phase L2 to L1● -
30225 IN_calcNeutral current (calculated)● -
30513 Variable 1Quantity is defined by user (see 40513 ... 40534)
30515 Variable 2Quantity is defined by user (see 40513 ... 40534)
30517 Variable 3Quantity is defined by user (see 40513 ... 40534)
30519 Variable 4Quantity is defined by user (see 40513 ... 40534)
30521 Variable 5Quantity is defined by user (see 40513 ... 40534)
30523 Variable 6Quantity is defined by user (see 40513 ... 40534)
30525 Variable 7Quantity is defined by user (see 40513 ... 40534)
30527 Variable 8Quantity is defined by user (see 40513 ... 40534)
30529 Variable 9Quantity is defined by user (see 40513 ... 40534)
30531 Variable 10Quantity is defined by user (see 40513 ... 40534)
30533 Variable 11Quantity is defined by user (see 40513 ... 40534)
30535 Variable 12Quantity is defined by user (see 40513 ... 40534)
30537 Variable 13Quantity is defined by user (see 40513 ... 40534)
30539 Variable 14Quantity is defined by user (see 40513 ... 40534)
30541 Variable 15Quantity is defined by user (see 40513 ... 40534)
30543 Variable 16Quantity is defined by user (see 40513 ... 40534)
30545 Variable 17Quantity is defined by user (see 40513 ... 40534)
30547 Variable 18Quantity is defined by user (see 40513 ... 40534)
30549 Variable 19Quantity is defined by user (see 40513 ... 40534)
30551 Variable 20Quantity is defined by user (see 40513 ... 40534)

* see Register 40081 (Page 30, Table 2)

TABLE 2: Description of 4X-Registers:

AdressName Read/WriteDescription
40005 Energy unit R/W This address is used to set energy unit in Wh, kWh & MWh.Write one of the following value to this address.1: Energy in Wh. 2: Energy in kWh.3: Energy in MWh.
40007 System Voltage R This address is read only and displays System Voltage
40009 System Current R This address is read only and displays System Current
40011 System Type R/W This address is used to set the System type.Write one of the following value to this address.2: 3 Phase 3 Wire3: 3 Phase 4 Wire.Writing any other value will return error.
40015 Reset Energy CounterW This address is used to reset the Energy Counter.Write zero value to this register to reset the energy counter. Writing any other value will return an error.
40019 Rs485 Set-up CodeR/W This address is used to set the baud rate, Parity, Number of stop bits.
40043 CT secondary R/W This address is used to read and write the CT secondary value. Write one of the following values to this address.1: 1A CT secondary5: 5A CT secondarywriting any other value will return an error.
40071 Passwort R/W This address is used to set & reset the password. Valid Range of Password can be set is 0000 - 9999.1) If password lock is present & if this location is read it will return zero.2) If Password lock is absent & if this location is read it will return One.3) If password lock is present & to disable this lock fi rst send valid pas word to this location then write "0000" to this location4) If password lock is present & to modify 4X parameter fi rst send valid password to this location so that 4X parameter will be accessible for modifi cation.5) If for in any of the above case invalid password is send then meter will return exceptional error 2.
40077 Auto-Scroll R/W This address is used to activate or de-activate the auto scrolling.Write 0: Deactivate1: Activate, Writing any other value will return an error.
40079 30mA start current R/W This address is used to activate or de-activate the 30 mA start current elimination write0: Deactivate30 (Decimal): ActivateWriting any other value will return an error.
40081 Aktualisierungsrate R/W Update rate of the energy meter in the process image (30145 ... 30153)
40513 Variable 1 R/W defi nes the value of the register 30513/30514
40514 Variable 2 R/W defi nes the value of the register 30515/30516
40515 Variable 3 R/W
40516 Variable 4 R/WValue Name
40517 Variable 5 R/W0 Voltage UL1
40518 Variable 6 R/W2 Voltage UL2
40519 Variable 7 R/W4 Voltage UL3
40520 Variable 8 R/W...
50521 Variable 9 R/W70 Frequenz
40522 Variable 10 R/W...
40523 Variable 11 R/W144 Active power incoming
40524 Variable 12 R/W224 Neutral current
40527 Variable 13 R/WWert = 3X Register Adress - 30001
40528 Variable 14 R/W
40529 Variable 15 R/W
40530 Variable 16 R/W
40531 Variable 17 R/W
40532 Variable 18 R/W
40533 Variable 19 R/W
40534 Variable 20 R/W defi nes the value of the register 30551/30552
Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Camille Bauer

Model : SIRAX BT5700

Category : Electrical measuring device