REMKO

MKT 250 S-Line - Air Conditioning REMKO - Free user manual and instructions

Find the device manual for free MKT 250 S-Line REMKO in PDF.

📄 12 pages English EN Download 💬 AI Question
Notice REMKO MKT 250 S-Line - page 1
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about MKT 250 S-Line REMKO

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Air Conditioning in PDF format for free! Find your manual MKT 250 S-Line - REMKO and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. MKT 250 S-Line by REMKO.

USER MANUAL MKT 250 S-Line REMKO

Operation • Technology • Spare Parts

REMKO MKT 250 S-Line - 1

natural_image White portable air conditioner unit with control panel and German text label (no readable document content)

2 Safety Notices
2 Scope of Supply
3 Device Structure
3 Erecting the Device
3 Exhaust Air Conductance

4-5 Operation

4 Control Panel and Remote Control
4 "Mode" Selection
5 "Cool" Mode
5 "Dehumidify" Mode
5 "Fan" Mode
5 "Timer"

6 Functional Principle of the Cooling Process

5-7 Maintenance and Care

6 Cleaning the Filter
6 Draining the Condensate
7 Trouble Shooting

8 Taking the Device Out of Service
8 Warranty
9 Environment and Recycling

3-12 Technology

8 Electrical Wiring Diagram.
9 Installation Instructions for the Wall Bushing

10 Device Diagram
11 Spare Part List, Accessories
12 Technical Data

Safety Notices

Before delivery, this device was subjected to numerous material, function, and quality tests. Nevertheless, the device may present a danger if used by untrained personnel, improperly, or no according to regulation!

REMKO MKT 250 S-Line - Safety Notices - 1

Caution

Operation other than as described in these instructions is prohibited. Nonobservance leads to the extinguishment of any liability and warranty claims.

Observe the following notices:

The device is not suited for outdoor operation.
The device may not be set up and operated in rooms at risk of explosion and in atmospheres containing oil, sulphur, or salt

Make sure it is at a suffi cien security distance to infl ammable objects

Do not place any objects on the device.

- Observe the minimum clearances (Fig. 2)

Do not insert any objects into air inlets and outlets

Erect the device on an even, stable surface. Never place it on its side (Fig. 3).

Operate the device only when it is upright

Do not expose the device to direct water spray

Operate the device only within its permissible operating limits (16 to 35°C)

Do not pull on or bend the mains supply line

  • Protect all electrical lines of the device from damage, even from animals.
    Select the extension lines of the mains supply line depending on the connected load of the device, the line length, and the intended use.
    Do not lay lines under carpeting.
    Never operate the device without an air filter
  • Never direct the air flow at people.
    ■ Never open the device housing as there is a danger of an electrical shock.
    ■ Work on the cooling system and the electrical equipment may be carried out only by an authorised specialist.

Transporting the device

Before transport, switch off the device and pull the mains plug.
Transport the device only in an upright position
We recommended that any condensate be drained using the condensate drain spout on the back side of the device before transport.
After every transport of the device, wait at least 5 minutes before recommissioning it (Fig. 4).

REMKO MKT 250 S-Line - Transporting the device - 1

CAUTION

REMKO MKT 250 S-Line - Transporting the device - 2

TIP

REMKO MKT 250 S-Line - Transporting the device - 3

DANGER

Scope of Supply

1 MKT 240 air conditioner
1 Infrared remote control
2 Batteries (type AAA/1.5 V)
1 Air outlet hose with connection pipe adapter and window jet

REMKO MKT 250 S-Line - Scope of Supply - 1

text_image Control panel Infrared receiver Recessed grip Air directing plate fins Transport rollers

REMKO MKT 250 S-Line - Scope of Supply - 2

text_image Air inlet (circulation air) with air filter Exhaust air outlet Window jet Air outlet hose Connecting line with plug Air inlet (exhaust air) Condensate drain spout with plug Fig. 1 MKT 240

REMKO MKT 250 S-Line - Scope of Supply - 3

natural_image White portable air conditioner unit enclosed in a dashed bounding box, placed against a green curtain background (no text or symbols visible)

Fig.2

Minimum clearances

Side 500 mm

Front 500 mm

Rear 400 mm

10p 100 mn

Device Structure

Delivery

All devices are carefully packed before shipping. Please check the device immediately after delivery. Make a note of any damage or missing parts on the delivery note and inform the forwarding agent and your contractual partner. No warranty can be assumed for later complaints.

Erecting the device

Make sure that all air intake and air outlet openings are free; observe the minimum clearances (Fig. 2).
Erect the device on a solid, even foundation (Fig. 3)
Make sure that people and sensitive objects such as plants are not directly affected by the emerging air.
Connect the device to a properly installed plug socket (230V/50Hz) (Fig. 5)
Insert the batteries into the remote control. To do so push up the cover on the back side of the remote control and insert the batteries while

observing the proper polarity. Observe the marking inside the compartment (Fig. 6).

Check whether the plug of the condensate drain spout has been provided and whether it has been properly inserted. There is otherwise a danger of water emerging.

Exhaust air conduction

During the operation of the air conditioner, the device creates humid exhaust air that must be conducted outside of the room so that the cooling effect can be maintained

Observe the following notices:

Plug the air outlet hose included in delivery onto the air outlet on the rear panel of the device.
- Lock both catches on the air outlet into both openings of the air outlet hose.
- Keep the air outlet hose as short as possible (max. length 1400 mm).
Always lay the air outlet hose with a constant upward incline from the device to the wall/window. Make sure it has

Fig. 8 Hanging the window jet into a pivot-hung
REMKO MKT 250 S-Line - Observe the following notices: - 1

natural_image Exterior view of a wall-mounted HVAC unit next to a wooden door opening, with a digital display nearby (no visible text or symbols)

Fig.9 Secure the double-wing window using a holding strap.
REMKO MKT 250 S-Line - Observe the following notices: - 2

natural_image Close-up of a white industrial piping bag attached to a wall-mounted device, with no visible text or symbols.

a wide curve radius (Fig. 7).

The air outlet hose may not be extended

Pivot-hung windows

- Connect the air outlet hose to the window jet and the device.

- Open the window and lay the fl at nozzle between the window trim and the window frame (Fig. 8..

Double-wing window

Lay the fl at nozzle between the wings, close the window as far as possible, and secure the wings with a holding strap (Fig. 9)

Wall bushing

In case of permanent installation (s. p. 9, Fig. 19), the exhaust air from the device is conducted outside the room through the wall bushing (Fig. 10)

Fig. 10 Permanent installation with a wall bushing (accessory, not included in supply schedule)
REMKO MKT 250 S-Line - Observe the following notices: - 3

natural_image Close-up of a white air purifier attached to a wall-mounted pipe, next to a wooden door (no visible text or symbols)

REMKO MKT 250 S-Line - Observe the following notices: - 4

natural_image White portable air purifier with red prohibition symbol on base, placed on wooden surface (no text or symbols)

Fig. 3 Vertical erection on solid, even foundation
REMKO MKT 250 S-Line - Observe the following notices: - 5

natural_image Close-up of a red analog clock face showing time with hour and minute hands (no text or symbols beyond numbers)

Fig. 4 Five-minute "wait"

REMKO MKT 250 S-Line - Observe the following notices: - 6

natural_image White electrical plug with a green arrow pointing to its side (no text or symbols visible)

Fig. 5 230 V / 50 Hz

REMKO MKT 250 S-Line - Observe the following notices: - 7

natural_image Interior view of a white cylindrical battery pack with two colored batteries and a power cord (no text or symbols visible)

Fig. € Remote control
REMKO MKT 250 S-Line - Observe the following notices: - 8

text_image Prohibition sign with red prohibition symbol over a pipe, indicating no smoking or anti-smoking

Abb. 7 Attach the air outlet hose with a constant upward incline

Operation

The device is operated comfortably using the control panel on the device or the infrared remote control. Keys with the same symbols have the same function.

  • Point the infrared transmitter of the remote control at the infrared receiver on the control panel.
    n order for the signal to be received without interference, there should be

REMKO MKT 250 S-Line - Operation - 1

text_image 8 9 10 11 12 13 7 Cool Delhumidity High Med Low Room Temp Set temp Power Mode Fan Speed Timer Timer/Temp Adjust 18 2 3 4 5 6 Infrared receiver Fig. 11 Control panel* Control panel* 1 2 3 4 5 6

no objects between the remote control and the device (reach of approx. 5 m).

The proper reception of the signal is indicated acoustically.

REMKO MKT 250 S-Line - Operation - 2

text_image Infrared transmitter 1 2 3 4 5 6 7 14 12

Fig. 12 Infrared remote control

1 On/off "Power" buttor
2 "Mode" button
3 "Fan Speed" button
4 "Timer" button
b+6 Temperature/time setting buttons
"Timer/Temp. Adjust": 5 higher, 6 lower
7 Display
8 Red fault LED: Reservoir full (s. p. 7 Trouble Shooting;
An acoustic and an optical signal indicate that the float switch of the internal reservoir has shut down the operation of the device. The acoustic signal dies down after a short period of time, but the LED remains active.

9 Mode LED

Green: "Cool"

Orange: "Dehumidify"

Yellow: "Fan"

10 Orange LED for the fan speed, with high/medium/low speed "High"/"Med"/"Low"

11 Green LED for the time delay, "Timer

12 Green "Room Temp" LED

(If this LED lights up the current room temperature is shown in the display (7))

13 Green "Set Temp" LEL

14 "°C/°F" toggle button (only on the remote control)

"Mode" selection (2)

"Cool"

The device is used to cool the room. It filter and dehumidifi es the air and thus creates a pleasant room climate.

"Dehumidify"

n the "Dehumidify" mode, humidity is removed from the air.

“=an”

The device circulates the air, filters it, and creates an even air flow

"Cool" mode

  1. Attach the air outlet hose to the wall bushing or the window.
  2. Activate the device using the "Power" button (1).
  3. Press the "Mode" button (2) until the "Cool" LED (9) lights up.
  4. Select the fan setting using the "Fan Speed" button (3): "High" highest speed "Med" medium speed "Low" lowest speed
  5. If the "Room Temp." LED (12) lights up, the current room temperature is shown in the display (7).
  6. As soon as the (4/5/6) button is pressed, the display switches from the room temperature to the set temperature (LED 13 lights up) and shows the desired temperature for 15 seconds.
  7. Set the desired room temperature using the "Timer/Temp. Adjust" button (5/6). The up arrow (5) increases the set value shown in the display (7), while the down arrow (6) decreases it.

"Dehumidify" mode

  1. Attach the air outlet hose to the wall bushing or the window
  2. Activate the device using the "Power" button (1).
  3. Press the "Mode" button (2) until the "Dehumidify" LED (9) lights up; the fan is automatically switched to the "Med" or medium fan speed stage.

"Fan" mode

  1. Activate the device using the "Power" button (1).
  2. Press the "Mode" button (2) until the "Fan" LED (9) lights up.
  3. Select the fan setting using the "Fan Speed" button (3):
    "High" highest speed
    "Med" medium speed
    "Low" lowest speed
  4. The room temperature is not influenced and remains constant. For this reason, the temperature and time setting "Timer/Temp. Adjust" buttons (5/6) cannot be used.

REMKO MKT 250 S-Line - "Fan" mode - 1

"Timer" time delay (4)

You can turn the device on and off automatically using the timer. To do so, an activation/deactivation delay is programmed.

Automatic activation

  1. Activate the device using the "Power" button (1).
  2. Select the mode and make all settings for the desired mode.
  3. Deactivate the device using the "Power" button (1)
  4. Press the "Timer" button (4).
  5. Set the time using the "Timer/Temp. Adjust" button (5/6). Only whole hours can be entered.
  6. The LED (11) fl ashes
  7. The device activates automatically at the set time.

■ Automatic deactivation

  1. The device is running in the previously set mode.
  2. Press the "Timer" button (4).
  3. Set the remaining run time using the "Timer/Temp. Adjust" button (5/6).
    Only whole hours can be entered.
  4. The LED (11) fl ashes
  5. The device deactivates automatically at the set time.

REMKO MKT 250 S-Line - ■ Automatic deactivation - 1

TIP

"Cool" mode

You can achieve a pleasant room climate by selecting a set temperature that is a maximum of 4 to 7°C below the outdoor temperature.

REMKO MKT 250 S-Line - "Cool" mode - 1

text_image Cooled circulation Fan (circulation air, air in the room) Evaporator Air inlet (circulation air) with air fi lte Warm exhaust air outside Ventilator (exhaust a Cooling circuit Air inlet (exhaust air) Condenser

Functional principle of the cooling process

The air conditioner cools the air by removing heat from it. The fan (circulation air) conducts cooled air into the room. The heat that the device has removed from the air is conducted outside via the air outlet hose.

Humidity is removed from the air and drips as condensate from the evaporator onto the hot condenser and evaporates. Excess condensate drips from the condenser into a collection tray and conducted from there to the condenser again using a rotor, evaporated, and then conducted away with the exhaust air flow

Fig.13 Functional principle of the cooling process

Maintenance and Care

REMKO MKT 250 S-Line - Maintenance and Care - 1

natural_image 3D rendering of a car air conditioner unit with airflow direction arrow (no text or symbols)

Fig.14 Removing the air fi lte upwards from the machine

REMKO MKT 250 S-Line - Maintenance and Care - 2

natural_image Close-up of a grid-patterned surface with a blue-handled tool extending from it (no text or symbols visible)

REMKO MKT 250 S-Line - Maintenance and Care - 3

natural_image Close-up of a metal pipe holding a transparent container with liquid, placed on a grid-patterned surface (no text or symbols visible)

Fig. 15/16 Cleaning the air fi lte

With low cleaning effort, you can guarantee malfunction-free operation and a long service life

Use only mild, environment-friendly cleaning agents.
Regularly clean the ventilation slots.
Clean the device as required, but at least once a year, with a moist cloth and lukewarm water
Do not expose the device to direct water spray

CAUTION

Always turn off the device and pull the mains plug before cleaning!

Never operate the device without the air fi lte,

Cleaning the air fi lte

Clean the air fi Iter regularly but at least every 100 operating hours. In case of strongly contaminated air, the period is reduced accordingly

  1. Switch off the device and pull the mains plug.
  2. Remove the filter from the device (Fig. 14).
  3. Clean the filter using a vacuum cleaner or, in case of heavy soiling, carefully using lukewarm water (Fig. 15/16).
  4. Let the filter air-dry and their reinsert it

Draining the condensate

The condensate evaporates during operation and is then conducted outside with the exhaust air via the air outlet hose.
In case of extreme humidity, the device collects condensate in a reservoir. If the permissible level is exceeded, the red fault LED lights up and the device shuts down.
The reservoir must be emptied via the condensate drain spout (Fig. 17).

REMKO MKT 250 S-Line - Draining the condensate - 1

natural_image Exterior view of a modern office building (no signage)

Fig.17 Draining the condensal

Trouble Shooting

The device is not functioning and the control panel remains dark.

Make sure that

  • the mains plug is properly inserted;
  • there is no power failure;
    • the mains voltage is present (fuse)

- Check the mains supply line for damage.

The device is not cooling properly.

  • Check the mode: the "Cool" LED must be lit.
    For an optimum cooling capacity, close the curtains and blinds. In addition, make sure the windows and doors are closed.

Make sure that

  • the air outlet hose has been properly attached. It may not be bent, declining, or laid in a tight curve;
  • no foreign bodies impair the exhaust or intake air supply (observe the minimum clearances);
  • the air directing plate fi ns are free of soiling or foreign objects
  • the set temperature is not too high (operating limits of the device: 16 to 35^ ).

REMKO MKT 250 S-Line - The device is not cooling properly. - 1

DANGER

Contact your dealer or contractual partner if the device cannot be commissioned.

Never open the device housing.

Never perform work on the cooling circuit or the electrical equipment.

REMKO MKT 250 S-Line - DANGER - 1

The device is not functioning and the "Timer" time de ay LED is fl asling.

- "Timer" time delay is programmed. Delete the timer setting.

REMKO MKT 250 S-Line - The device is not functioning and the "Timer" time de ay LED is fl asling. - 1

The device is not functioning and

"E1" is being shown in the display.

The room temperature lies outside the operating range of 16 to 35°C. Wait until the room temperature lies in the working range (reduce the incident of sunlight and close windows and doors, if necessary).

The device does not react to the remote control.

Make sure that

  • the batteries are functioning; change them if necessary;
  • the batteries are inserted with the correct polarity (cf. the marking);
  • there are no objects between the remote control and the device (reach of approx. 5 m).

REMKO MKT 250 S-Line - The device does not react to the remote control. - 1

The device deactivates automatically. The fault LED fl ashes and a signal sounds (reservoir full).

To drain the reservoir, proceed as follows

  1. Switch off the device and pull the mains plug.
  2. Place a fl at tray under the condensate drain spout and remove the plug (Fig. 17).
  3. After the condensate has drained, reinsert the plug firmly

Condensate is emerging.

Make sure that

  • the device is on a horizontal foundation;
  • the air outlet hose is properly attached;
  • the plug is firmly inserted in the condensate drain spout.

REMKO MKT 250 S-Line - Condensate is emerging. - 1

text_image Electrical wiring diagram Control panel Evaporator fan White Red Orange Yellow Condenser Mains plug Hi Med Lo JU7 L RL7U1 Brown I N F L COMF Red Red Red Blue Blue Blue Blue Condenser Compressor Evaporator fan Reservoir motor Microswitch Temperature sensor Technical dimensions and design subject to alteration

Fig. 18 Electrical wiring diagram.

Taking out of service

To take the device out of service, deactivate it first by pressing the "Power" button. Then pull the mains plug.

If the device must be shut down for a longer period of time, for example, for storage during the winter, observe the following:

  1. Let the machine run for about two hours in the "Fan" mode to dry the surface of the evaporator plate fi ns. In this way, the residual moisture is removed from the device and you can prevent unpleasant smells during recommissioning.
  2. Switch off the device, pull the mains plug, and roll up the mains supply line
  3. Drain the condensate (s. p. 6).

Warranty

The function of the device was precisely checked several times at the factory. If malfunctions that are not described in the "Trouble Shooting" chapter (s. p. 7) still appear, contact your dealer or contractual partner
In order for REMKO to assume the warranty, the "Warranty Certifi cate" included in delivery must be completely filled out and sent to REMKO GmbH & CO KG immediately after purchasing or commissioning

CAUTION

The manufacturer is not liable for damage that occurs due to nonobservance of manufacturer instructions or the legal requirements or due to unauthorised changes to the device.

Fig. 19

Installation diagram for the wall bushing

REMKO MKT 250 S-Line - CAUTION - 1

text_image JAHWELTREUNDOLICH JAHWELTREUNDOLICH KALTEMITIEL

REMKO MKT 250 S-Line - CAUTION - 2

natural_image Abstract green recycling symbol composed of three interlocking arrows forming a circular design (no text or symbols)

REMKO MKT 250 S-Line - CAUTION - 3

text_image Telescopic pipe Protective grille Sealing cap Trap min. 450 mm max. 480 mm

Environment and Recycling

■ Dispose of the packaging in an eco-friendly manner
Do not dispose of the device in domestic rubbish
Both the refrigerant and the plant parts are subject to special disposal conditions
The refrigerant used belongs to the chlorofl uorocarbon refrigerant group. It is released into the air due to damage to the cooling circuit, injury to the respiratory organs of people and animals will not occur

Installation Instructions for the Wall

■ Create a core hole in the outside wall (max.- wall thickness of 480 mm) with a diameter of at least 135 mm.
Take the minimum distance of 430 mm between the floor (mounting surface of the device) and the centre of the wall bushing into consideration.
- Insert the telescopic pipe into the wall bushing
To prevent cold bridges, insulate the telescopic pipe with suitable insulating material.
■ Wall the telescopic pipe into the core hole in such a way that it is fl ush to both sides of the wall.

Mount the protection grill on the outside of the wall (make sure it is protected from rain)
Fix the trap to the inside.
The "top" label on the trap must be legible from the inside
When taking the device out of service, for example, at the beginning of winter, close the opening of the trap using the sealing cap to prevent air circulation

REMKO MKT 250 S-Line - Installation Instructions for the Wall - 1

text_image Device Diagram Technical dimensions and design subject to alteration Fig 20. Device diagram of the MKT 240

Fig.20 Device diagram of the MKT 240

Spare Part List

Fig. no. DesignationRef. no.
1 Unit bottom1106850
2 Transport roller1106851
3 Condensate motor with rotor1106852
4 Condenser 2.5 μF (evaporator fan)1106853
5 Float regulator (reservoir)1106854
6 Cover (reservoir)1106855
7 Microswitch (reservoir)1106856
8 Compressor, cpl.1106857
9 Condenser 2.5 μF (compressor)1106858
10 Evaporator1106859
11 Fan housing (exhaust air)1106860
12 Fan wheel (exhaust air)1106862
13 Fan motor (exhaust air)1106863
14 Condensate tray1106864
15 Exhaust air pipe adapter1106315
16 Condenser 1.5 μF1106316
17 Evaporator1106317
18 Fan housing, 3-pc. (circulation air)1106318
19 Fan wheel, left (circulation air)1106869
20 Fan wheel, right (circulation air)1106870
21 Fan motor (circulation air)1106871
22 Side wall, right1106872
23 Circuit board1106873
24 Mains supply line with plug1106874
25 Front wall1106875
26 Back wall1106876
27 Air outlet segment1106877
28 Side wall, left1106878
29 PCB with control1106879
30 Control panel1106880
31 Entry circuit1106881
32 Air fi liter1106883
Air outlet hose, cpl. (Nos. 33, 34, 35)1106885
33 Air outlet hose1106886
34 Connection pipe adapter1106887
35 Window jet1106888
Not shown Condensate drain spout with plug1106882
Not shown Sensor (circulation air1106889
Not shown Remote contrc1106884

Accessories

DesignationRef. no.
Wall bushing1613115
(incl. telescopic pipe, protective grille, trap, sealing cap)

When ordering spare parts, enter the serial of the device on the rating plate in addition to the Ref. no

REMKO GmbH & Co. KG

Air-conditioning and heating technology

Im Seelenkamp 12 · 32791 Lage, Germany

P.O. Box 1827 · 32777 Lage, Germany

Phone +49-5 2 32-606-130

Fax +49-5 232-606-260

E-mail export@remko.de

URL www.remko.de

Technical Data
REMKC MKT 240

Device typeMKT 24C
Nominal cooling capacity * kW 2.30
Energy effi ciency class, cooling B
Energy effi ciency variable 2.42
Dehumidifi cation capacity Max. l/h1.60
Application range (room air volume) Approx. n^3 70
Temperature setting range °C16 bis 32
Temperature operating limits °C16 bis 35
RefrigerantR 407 C
Refrigerant quantity kg0.77C
Circulation air volume flow rate n^3/h 230/260/300
Exhaust air volume flow rate Max. n^3/h 36C
Sound pressure level ** dB (A)49/51/55
Voltage supply V/Ph/Hz 230/1~/50
Type of protectionIP 20
Power consumption kW 0.95
Current consumption A 4.43
Air outlet hose, length mm1400
Air outlet hose, diameter mm 125
Dimensions, height mm 450
Dimensions, width mm 770
Dimensions, depth mm 430
Weight kg27.00
Ref. no.1612240

* Room temperature dry-bulb 35°C / wet-bulb 24°C
** Distance 1 m

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : REMKO

Model : MKT 250 S-Line

Category : Air Conditioning