REMKO RVD 525 DC - Air conditioner

RVD 525 DC - Air conditioner REMKO - Free user manual and instructions

Find the device manual for free RVD 525 DC REMKO in PDF.

📄 84 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice REMKO RVD 525 DC - page 5
Pick your language and provide your email: we'll send you a specifically translated version.
Product TypeCeiling cassette air conditioner (cooling and heating)
ModelRVD 525 DC (indoor unit RVD 525 DC IT, outdoor unit RVD 525 DC AT)
Nominal Cooling Capacity (kW)5.3 (range 2.9 - 5.7)
Nominal Heating Capacity (kW)4.2 (range 2.4 - 6.1)
Energy Efficiency Ratio (SEER)6.1
SCOP (Heating)4.0
Power Supply230 V / 1 Ph / 50 Hz
Indoor Unit Dimensions (L x W x D) mm570 x 570 x 260
Indoor Unit Weight (kg)18.7
Outdoor Unit Dimensions (H x W x D) mm702 x 845 x 363
Outdoor Unit Weight (kg)33.7
Refrigerant Type / QuantityR32 / 1.15 kg (basic fill)
CO2 Equivalent (t)0.78
Sound Pressure Level Indoor (dB(A))36 / 39 / 43 (low / medium / high)
Air Flow Volume Indoor (m³/h)540 / 625 / 750 (low / medium / high)
Operating Range Cooling (°C)+5 to +50 (up to -15 with winter kit)
Operating Range Heating (°C)+5 to +24 (up to -15 with winter kit)
Condensate Pump Max Head (mm WS)500
FunctionsInverter technology, auto mode, cooling, heating, dehumidification, fan only, turbo, sleep, timer (on/off), follow me, swing, self-clean (optional)
ControlInfrared remote control (included); optional wired remote control
Filter Cleaning IntervalEvery 2 weeks (recommended)
Annual MaintenanceRecommended by specialist
Safety NotesFlammable refrigerant R32; ensure room area >4 m²; install by qualified personnel only
AccessoriesFloor console, wall bracket, winter fan speed control, fresh air kit (optional)

Frequently Asked Questions - RVD 525 DC REMKO

How often should I clean the air filter?
We recommend cleaning the air filter every 2 weeks. If the air is especially dirty, reduce this interval. To clean, disconnect power, open the air inlet guard, remove the filter, vacuum or wash with lukewarm water and mild detergent, let dry completely, then reinstall.
How do I set the timer to turn the unit on/off automatically?
Use the TIMER ON and TIMER OFF buttons on the remote. Press TIMER ON to set the switch-on delay (0.5 - 24 hours). Press TIMER OFF to set the switch-off delay. Each press increases time by 30 min (up to 10 hours) then by 1 hour (10-24 hours). The unit will automatically start/stop at the programmed time.
What does the ALARM LED mean?
A red ALARM LED indicates a malfunction. Check the flashing code on the indoor unit display (or use the remote to read error codes). Common errors include: F1 (indoor air temp sensor), F2 (evaporator sensor), F3 (condenser sensor), F4 (outdoor air temp sensor), F5 (fan motor), P1 (over/under voltage), P4 (inverter protection). Refer to the troubleshooting section in the manual for detailed corrective actions.
Can I use the air conditioner for cooling only?
Yes, the unit has cooling, heating, dehumidification, and fan-only modes. Press the MODE button on the remote to select the desired mode: Auto (automatic cooling/heating), Cool, Heat, Dry (dehumidification), and Fan.
What is the maximum refrigerant pipe length?
The maximum refrigerant piping length for the RVD 525 DC is 30 meters. For lengths over 5 meters, add additional refrigerant at 15 g/m. The maximum height difference between indoor and outdoor units is 20 meters.
How do I reset the remote control?
Remove the batteries from the remote control for at least 10 seconds, then reinsert them. This will clear all settings and reset to factory defaults (auto mode, 24°C, fan auto). If the remote still doesn't work, replace the batteries with new AAA alkaline batteries.
What is the minimum room size for installation?
The indoor and outdoor units must be installed in rooms with a floor area larger than 4 m². This is due to the flammable refrigerant R32. Ensure the installation room is well-ventilated and free from ignition sources.
How do I clean the condensate pump?
The condensate pump is maintenance-free but check the drainage line for dirt periodically. To access the pump, disconnect power, open the indoor unit, and clean the pump tray and hoses if needed. Use a soft brush and water. Do not use solvents.
Can I operate the unit without the remote control?
Yes, the indoor unit has a manual operation button on the receiver panel. Press it to start automatic mode (cooling at 24°C, fan auto). Press again for test mode (30 min high fan). A third press turns the unit off. Manual mode is limited; for full functions, use the remote.
What is the 'Follow Me' function?
The Follow Me function uses the temperature sensor on the remote control to measure room temperature at your location, not at the indoor unit. Press the FOLLOW ME key on the remote to activate. The remote sends temperature data every 3 minutes. If no signal for 7 minutes, it reverts to indoor unit sensor.

User questions about RVD 525 DC REMKO

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Air conditioner in PDF format for free! Find your manual RVD 525 DC - REMKO and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. RVD 525 DC by REMKO.

USER MANUAL RVD 525 DC REMKO

Operating and installation instructions

REMKO RVD series

Ceiling cassettes for cooling and heating

RVD 355 DC, RVD 525 DC, RVD 685 DC, RVD 1055 DC

REMKO RVD 525 DC - Operating and installation instructions - 1

natural_image Close-up of a white air vent grille with ventilation grilles (no text or symbols visible)

Read these operating instructions carefully before commissioning / using this device!

These instructions are an integral part of the system and must always be kept near or on the device.

Subject to modifications; No liability accepted for errors or misprints!

Translation of the original

Table of contents

1 Safety and usage instructions.... 5

1.1 General safety notes.... 5
1.2 Identification of notes.... 5
1.3 Personnel qualifications.... 5
1.4 Dangers of failure to observe the safety notes.... 5
1.5 Safety-conscious working.... 6
1.6 Safety instructions for the operator.... 6
1.7 Safety notes for installation, maintenance and inspection 6
1.8 Unauthorised modification and changes.... 7
1.9 Intended use.... 7
1.10 Warranty....7
1.11 Transport and packaging....7
1.12 Environmental protection and recycling.... 8

2 Technical data.... 9

2.1 Unit data....9
2.2 Unit dimensions, outdoor unit.... 12
2.3 Unit dimensions, indoor unit.... 13

3 Design and function.... 14

3.1 Unit description.... 14

4 Operation.... 15

4.1 General notes.... 15
4.2 Display on indoor unit.... 16
4.3 Keys on the remote control.... 17

5 Installation instructions for qualified personnel.... 23

5.1 Important notes prior to installation.... 23
5.2 Wall openings.... 23
5.3 Installation materials.... 23
5.4 Selection of installation location 24
5.5 Minimum clearances.... 25
5.6 Oil return measures.... 26

6 Installation.... 26

6.1 Unit installation.... 26
6.2 Connection of refrigerant piping.... 28
6.3 Leak testing.... 30
6.4 Adding refrigerant.... 31

7 Condensate drainage connection and safe drainage.... 31

8 Electrical wiring.... 33

8.1 General connection and safety instructions.... 33
8.2 Connecting the indoor unit.... 33
8.3 Outdoor unit connection.... 34
8.4 Electrical wiring diagram.... 35
8.5 Electrical drawings.... 39
8.6 Connection of a superordinate controller provided by the customer 47

9 Before commissioning.... 48

10 Commissioning.... 48

11 Shutdown......49

REMKO RVD series

12 Troubleshooting, customer service and fault analysis.... 50

12.1 Troubleshooting and customer service.... 50
12.2 Indoor unit fault analysis.... 54
12.3 Resistances of the temperature probes.... 65

13 Care and maintenance.... 68

14 Exploded view and spare parts lists.... 70

14.1 Exploded view - Indoor unit RVD 355-525 DC 70
14.2 Spare parts list - Indoor unit RVD 355-525 DC.... 71
14.3 Exploded view - Indoor unit RVD 685-1055 DC 72
14.4 Spare parts list - Indoor unit RVD 685-1055 DC.... 73

15 Exploded view - Outdoor unit RVD 355 DC....74

16 Spare parts list - Outdoor unit RVD 355 DC.... 75

17 Exploded view - Outdoor unit RVD 525 DC.... 76

18 Spare parts list - Outdoor unit RVD 525 DC.... 77

19 Exploded view - Outdoor unit RVD 685 DC.... 78

20 Spare parts list - Outdoor unit RVD 685 DC.... 79

21 Exploded view - Outdoor unit RVD 1055 DC....80

22 Spare parts list - Outdoor unit RVD 1055 DC....81

23 Index....83

1 Safety and usage instructions

1.1 General safety notes

Carefully read the operating manual before commissioning the units or their components for the first time. It provides useful tips and notes such as hazard warnings to prevent injury and material damage. Failure to follow the directions in this manual can endanger persons, the environment and the equipment itself or its components and will void any claims for liability.

Store this manual and the information required for the operation of this system (e.g. refrigerant data-sheet) in the vicinity of the unit.

The refrigerant used in the system is flammable. If applicable, observe the local safety conditions.

REMKO RVD 525 DC - General safety notes - 1

Warning of inflammable substances!

1.2 Identification of notes

This section provides an overview of all important safety aspects for proper protection of people and safe and fault-free operation. The instructions and safety notes contained within this manual must be observed in order to prevent accidents, personal injury and material damage.

Notes attached directly to the units must be observed in their entirety and be kept in a fully legible condition.

Safety notes in this manual are indicated by symbols. Safety notes are introduced with signal words which help to highlight the magnitude of the danger in question.

REMKO RVD 525 DC - Identification of notes - 1

DANGER!

Contact with live parts poses an immediate danger of death due to electric shock. Damage to the insulation or individual components may pose a danger of death.

REMKO RVD 525 DC - DANGER! - 1

DANGER!

This combination of symbol and signal word warns of a situation in which there is immediate danger, which if not avoided may be fatal or cause serious injury.

REMKO RVD 525 DC - DANGER! - 1

WARNING!

This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may be fatal or cause serious injury.

REMKO RVD 525 DC - WARNING! - 1

CAUTION!

This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause injury or material and environmental damage.

REMKO RVD 525 DC - CAUTION! - 1

NOTICE!

This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause material and environmental damage.

REMKO RVD 525 DC - NOTICE! - 1

This symbol highlights useful tips and recommendations as well as information for efficient and fault-free operation.

1.3 Personnel qualifications

Personnel responsible for commissioning, operation, maintenance, inspection and installation must be able to demonstrate that they hold a qualification which proves their ability to undertake the work.

1.4 Dangers of failure to observe the safety notes

Failure to observe the safety notes may pose a risk to people, the environment and the units. Failure to observe the safety notes may void any claims for damages.

REMKO RVD series

In particular, failure to observe the safety notes may pose the following risks:

The failure of important unit functions.
The failure of prescribed methods of maintenance and repair.
- Danger to people on account of electrical and mechanical effects.

1.5 Safety-conscious working

The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.

1.6 Safety instructions for the operator

The operational safety of the units and components is only assured providing they are used as intended and in a fully assembled state.

The units and components may only be set up, installed and maintained by qualified personnel.
- Protective covers (grills) over moving parts must not be removed from units that are in operation.
- Do not operate units or components with obvious defects or signs of damage.
- Contact with equipment parts or components can lead to burns or injury.
The units and components must not be exposed to any mechanical load, extreme levels of humidity or extreme temperatures.
Rooms in which refrigerant may escape shall be adequately aerated and ventilated. Otherwise, a risk of suffocation or fire exists.
- Do not leave children unsupervised when close to the system.
Commissioning must be performed by authorised specialists exclusively. Deficient commissioning may lead to water leaks, electric shocks or fire. Commissioning must take place as described in the user manual.
- Only instruct authorised specialist personnel to perform maintenance or servicing.
The system is filled with a flammable refrigerant. Never thaw any frozen unit components independently!
Do not operate any further devices that produce high heat or naked flames in the same room.

All housing parts and unit openings, e.g. air inlets and outlets, must be kept clear.
The units must be inspected by a service technician to ensure that they are safe to use and fully functional at least once yearly. Visual inspections and cleaning may be performed by the operator when the units are disconnected from the mains.

1.7 Safety notes for installation, maintenance and inspection

The refrigerant R32 used in the system is flammable. If applicable, observe the local safety conditions.
- Keep the cooling circuit clear of other gases and foreign substances. Only fill the cooling circuit with the refrigerant R32.
Only use the accessories, components and appropriately marked parts provided. The use of non-standardised components may result in water leaks, electric shocks and fire.
Only install and store the units in rooms larger than 4 m^2 . With a failure to comply, leaks may result in the room filling with a flammable mixture!
The minimum room size of 4 m^2 required for installation and storage pertains to the basic fill quantity of the unit. This varies according to the installation type and total fill quantity of the system. The calculation must take place in accordance with valid DIN standards. Make sure that the installation site is suitable for safe unit operation.
- Only mount the unit components on structurally suitable brickwork.
The units must not be installed in rooms in which further devices that produce heat are operated (heaters, open hearths).
■ Make sure the installation room is sufficiently ventilated.
Interventions in the cooling circuit are only possible after completely draining the refrigerant. Never solder or grind unit components!
Note that refrigerant may be odourless.
- Never operate the air conditioning unit in a humid room, such as a bathroom or laundry room. If the humidity is too high, this can cause short circuits on electrical parts.
The product must be correctly earthed at all times, otherwise it may induce electric shocks.
- Attach the condensate drain as described in the operating manual. The inadequate drainage of condensate can lead to water damage in your apartment.
All persons who intervene in the cooling circuit must hold a valid certificate from the chamber of industry and commerce, which confirms their ability to work with refrigerant.

■ Appropriate hazard prevention measures must be taken to prevent risks to people when performing installation, repair, maintenance or cleaning work on the units.
The setup, connection and operation of the units and its components must be undertaken in accordance with the usage and operating conditions stipulated in this manual and comply with all applicable regional regulations.
■ Regional regulations and laws as well as the Water Ecology Act must be observed.
The power supply should be adapted to the requirements of the units.
Units may only be mounted at the points provided for this purpose at the factory. The units may only be secured or mounted on stable structures, walls or floors.
The units and components should not be operated in areas where there is a heightened risk of damage. Observe the minimum clearances.
The units and components must be kept at an adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
■ Safety devices may not be modified or bypassed.
The connection of the indoor unit must be established as a permanent connection; a detachable, reusable connection is not permissible.

1.8 Unauthorised modification and changes

Modifications or changes to units and components are not permitted and may cause malfunctions. Safety devices may not be modified or bypassed. Original replacement parts and accessories authorised by the manufactured ensure safety. The use of other parts may invalidate liability for resulting consequences.

1.9 Intended use

Depending on the model, the units and the additional fittings with which they are equipped are only intended to be used as an air-conditioner for the purpose of cooling or heating the air in an enclosed space.

Any different or additional use is a non-intended use. The manufacturer/supplier assumes no liability for damages arising from a non-intended use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.

The threshold values specified in the technical data must not be exceeded.

1.10 Warranty

For warranty claims to be considered, it is essential that the ordering party or its representative complete and return the "certificate of warranty" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.

The warranty conditions are detailed in the "General business and delivery conditions". Furthermore, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.

1.11 Transport and packaging

The devices are supplied in a sturdy shipping container. Please check the equipment immediately upon delivery and note any damage or missing parts on the delivery and inform the shipper and your contractual partner. For later complaints can not be guaranteed.

REMKO RVD 525 DC - Transport and packaging - 1

WARNING!

Plastic films and bags etc. are dangerous toys for children!

Why:

  • Leave packaging material are not around.
  • Packaging material may not be accessible to children!

REMKO RVD series

1.12 Environmental protection and recycling

Disposal of packaging

All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved collection points.

REMKO RVD 525 DC - Disposal of packaging - 1

Disposal of equipment and components

Only recyclable materials are used in the manufacture of the devices and components. Help protect the environment by ensuring that the devices or components (for example batteries) are not disposed in household waste, but only in accordance with local regulations and in an environmentally safe manner, e.g. using certified firms and recycling specialists or at collection points.

REMKO RVD 525 DC - Disposal of equipment and components - 1

2 Technical data

2.1 Unit data

Series RVD 355 DC RVD 525 DC RVD 685 DC RVD 1055 DC
Operating modeInverter ceiling cassette-room air conditioner combination for cooling and heating
Nominal cooling output1)kW3.5(1.5-5.3)5.3(2.9-5.7)7.0(3.2-8.2)10.5(4.0-12.0)
Energy efficiency ratio SEER1)7.86.1
Rated power consumption, elec-trical cooling1)kW0.851.632.193.95
Rated elec. curr. consump., cooling1)A3.87.29.56.6
Power consumption, annual, QCE3)kWh157304402602
Energy efficiency ratio, cooling1)A++
Nominal heat capacity2)kW3.1(1.0-5.6)4.2(2.4-6.1)5.4(2.4-8.7)8.1(2.6-13.2)
Energy efficiency ratio SCOP4)4.64.0
Rated power consumption, elec-trical heating2)kW1.101.462.053.00
Rated elec. curr. consump., heating2)A5.06.48.95.0
Power consumption, annual, QHE3)kWh959143518902835
Energy efficiency ratio, heating2)A++A+
Max. power consumptionkW1.81.92.94.8
Max. current consumptionA7.98.512.5
EDP no.162384516238551623865

1) Air inlet temp. TK 27 °C/FK 19 °C, outside temperature TK 35 °C, FK 24 °C, max. air flow volume, 5 m pipe length

2) Air inlet temp. TK 20 °C, outside temperature TK 7 °C, FK 6 °C, max. air flow volume, 5 m pipe length

3) The specified value is based on results from standard testing. The actual consumption depends on the use and location of the unit

4) The specified value is based on the average heating period

REMKO RVD series

Associated indoor unit / seriesRVD 355 DC ITRVD 525 DC ITRVD 685 DC ITRVD 1055 DC IT
Power supply V/Ph/Hz 230/1~/50
Application area (room volume), approx. m^3 110 160 230 320
Adjustment range room temperature°C +17 to +30
Operating range °C/r.H.% +17 to +30 / 35-65
Air flow volume per stage m^3/h 416/504/617540/625/7501032/1200/13781438/1620/1775
Sound pressure level per stage^5) dB (A) 33/36/41 36/39/4340/43/47 41/47/51
Enclosure class IP X0
Refrigerant connection, liquid pipeInches (mm)1/4 (6.35) 3/8 (9.52)
Refrigerant connection, suction pipeInches (mm)3/8 (9.52) 1/2 (12.7)5/8 (15.9)
Condensate drainage connec-tionmm2532
Condensate pump, flow rate, max.mm WS500750
Dimensions: Length/width/depthmm570/570/260840/840/245
Cover dimensions: Length/ width/depthmm647/647/50950/950/55
Weightkg18.728.032.5
EDP no.1623847 1623857 16238671623877

5) At distance of 1 m in the open air; specified values are maximum values

Associated outdoor unit / seriesRVD 355 DC ATRVD 525 DC ATRVD 685 DC ATRVD 1055 DC AT
Power supply V/Ph/Hz 230/1~/50 400/3~/50
Operating range, cooling °C+5 to +507)
Operating range, heating °C+5 to +247)
Air flow rate, max. m3/h 2000 2700 4000
Enclosure class IP 24
Sound power level max. dB (A) 63 64 68
Sound pressure level5)dB (A) 565562 64
Refrigerant6)R32
Refrigerant, basic quantitykg0.871.151.502.40
CO2equivalentt 0.590.781.011.62
Operating pressure, max.kPa4300/1700
Refrigerant, additional quantity >5mg/m1530
Refrigerant piping, max. lengthm25305065
Refrigerant piping, max. heightm10202530
Refrigerant connection, liquid pipeInches (mm)1/4 (6.35)3/8 (9.52)
Refrigerant connection, suction pipeInches (mm)3/8 (9.52)1/2 (12.7)5/8 (15.9)
Dimensions: Height / width / depthmm554/800/333702/845/363810/946/410
Weightkg34.733.749.481.5
EDP no.1623846162385616238661623876

5) At distance of 1 m in the open air; specified values are maximum values

6) Contains greenhouse gas per the Kyoto protocol, GWP 675 (for further information, see chapter "Adding refrigerant")

7) Can be expanded up to -15^ with optional winter fan speed control

REMKO RVD series

2.2 Unit dimensions, outdoor unit

D E

REMKO RVD 525 DC - Unit dimensions, outdoor unit - 2

natural_image Front view of a white air conditioner unit with a circular gauge and ventilation grille (no text or symbols visible)

C B

Fig. 1: Dimensions RVD 355-1055 DC AT (all measurements in mm)

Measurements (mm) A B C D E
RVD 355-525 DC 800 554 333 514 340
RVD 685 DC 845 702 363 540 350
RVD 1055 DC 946 810 410 673 403

We reserve the right to modify the dimensions and design as part of the ongoing technical development process.

2.3 Unit dimensions, indoor unit

A ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ 600 260 >290 >2000

B ① ② ③ ④ ⑤ 245 880 ⑥ ⑦ ⑧ >275 >2000

④ ⑨ 523 570 647 545 570 647

⑨ ④ 680 840 950 780 840 950

Fig. 2: Dimensions (all measurements in mm)

A: RVD 355-525 DC

B: RVD 685-1055 DC

1: Ceiling
2: Suspended ceiling
3: Floor
4: Condensate drainage connection

5: Injection pipe connection
6: Ceiling cut-out
7: Unit trim
8: Suction pipe connection
9: Refrigerant piping connections

We reserve the right to modify the dimensions and design as part of the ongoing technical development process.

3 Design and function

3.1 Unit description

The RVD 355-1055 DC room air conditioners have a REMKO RVD...AT outdoor unit as well as an RVD...IT indoor unit.

In cooling mode, the outdoor unit serves to output the heat extracted by the indoor unit from the room being cooled. In heating mode, the heat taken up by the outdoor unit can be discharged by the indoor unit into the room to be heated. In both operating modes, the output produced by the compressor precisely matches requirements, and thereby regulates the nominal temperature with minimal temperature deviations. This "inverter technology" results in energy savings over conventional split systems and also reduces noise emissions to a particularly low level. The outdoor unit can be installed in an outdoor area or, providing that certain requirements are met, an indoor area. The outdoor unit consists of a cooling cycle with compressor, fin condenser, condenser fan, reversing valve and throttle element. The outdoor unit is controlled by the regulation of the indoor unit.

The indoor unit is designed for indoor areas, for suspended ceilings with Euroraster dimensions. The cassette is hidden behind the suspended ceiling, only its cover is visible. It is operated by an infrared remote control. The indoor unit consists of a fin evaporator, evaporator fan, regulation system and condensate tray with condensate pump.

Floor consoles, wall consoles, refrigerant piping and winter fan speed control are available as accessories.

Refrigerant piping is used to connect the indoor unit to the outdoor unit.

Diagram of a HVAC system with labeled components including air conditioner, fan, and roof structure

Fig. 3: System layout RVD 355-1055 DC

A: Outdoor area
B: Indoor area
1: Indoor units
2: Outdoor unit
3: Condensate drainage line
4: Condenser fan
5: Power supply
6: Shut-off valve
7: Suction pipe
8: Injection pipe
9: Control lines

REMKO RVD 525 DC - Unit description - 2

flowchart
graph TD
    A["①"] --> B["M1"]
    B --> C["M2"]
    C --> D["M3"]
    D --> E["FLT"]
    E --> F["②"]
    style A fill:#f9f,stroke:#333
    style B fill:#ccf,stroke:#333
    style C fill:#cfc,stroke:#333
    style D fill:#fcc,stroke:#333
    style E fill:#cff,stroke:#333
    style F fill:#ffc,stroke:#333

Fig. 4: Cooling cycle schematic RVD 355-1055 DC

A: Outdoor area
B: Indoor area
1: RVD 355-1055 DC
M1: Condenser fan
M2: Compressor
M3: Evaporator fan IT
V1: Changeover valve C/H
EEV: Elec. Expansion valve
FLT: Filter
OEL: Oil return line
PSH: High pressure switch AT
PSL: Low pressure switch AT
T1: Probe, heat gas AT
T2: Probe, air inlet AT
T3: Probe, condenser AT
T4: Probe, air inlet IT
T5: Probe, evaporator IT

4 Operation

4.1 General notes

The indoor unit is easily operated using the standard infrared remote control. The indoor unit beeps to acknowledge the correct transmission of data. If it is not possible to program the indoor unit with the remote control, then it can also be manually operated. The indoor unit can also be operated via an optional cabled remote control.

Manual mode

The indoor units can be put into operation manually. Press the MANUAL key on the cover's receiver unit to first activate automatic mode and then test mode. Pressing the button a third time switches the unit off. Pressing the button again switches back to automatic mode.

The following settings apply for manual operation:

Cooling mode: 24 °C, fan speed: AUTO

Test mode: 30 minutes cooling, high fan speed, the IR remote control is deactivated, after 30 minutes the unit changes over to automatic mode

Infrared remote control

The infrared remote control sends the programmed settings a distance of up to 6 m to the receiver of the indoor unit. Data will only be received correctly if the remote control is pointed at the receiver and no objects are obstructing the transmission path.

Two AAA batteries must be inserted into the remote control in preparation. To do so, remove the flap from the battery compartment and insert the batteries the correct way around (see markings). Removing the batteries causes all stored data to be lost. The remote control will then access the default settings, which you are free to customise at any time.

max. 6 m

Fig. 5: Maximum distance

! NOTICE!

Immediately replace flat batteries with a new set, otherwise there is a risk of leakage. It is recommended that the batteries are removed if the equipment is shut down for longer periods.

REMKO RVD series

Wired remote control

Connection of an optional wired remote control

The plug for connection of a wired remote control is located at the panel of the ceiling cassette (s. Fig. 6, [A]). The 5-core cable, coming from the display panel, is marked with the designations A-E (s. Fig. 6, [B]).

REMKO RVD 525 DC - Wired remote control - 1

natural_image Two technical diagrams: (A) a wall-mounted air vent with grid pattern, and (B) a cable with a blue connector (no text or symbols)

Fig. 6: Wired remote control connection

Alarms are indicated by a code RVD 355-525 DC (see chapter Troubleshooting and customer service).

Help save on energy consumption in stand-by mode! If the device, system or component is not in use, we recommend disconnecting the power supply. Components with a safety function is excluded from our recommendation!

4.2 Display on indoor unit

Display on indoor unit RVD 355-525 DC

The LED indicators illuminate to indicate the settings:

OPERATION LED green = unit switched on

TIMER LED yellow = timer programmed

DEF/FAN LED red = defrosting active/recirculation mode

ALARM LED red = alarm present

①35 ② ④ ⑥

Fig. 7: Display on the unit RVD 355-525 DC

1: Unit for receiving signals from the remote control
2: Operation display
3: Timer indicator
4: Manual operation key
5: Defrosting fan
6: Malfunction indication

Display on indoor unit RVD 685-1055 DC

The LED indicators illuminate to indicate the settings:

① ② ③ ④ ⑤ ⑥ ⑦ FUNC

Fig. 8: Display on the unit RVD 685-1055 DC

1: "Func" key
2: Operating lamp
3: "Timer" display activated / deactivated
4: Digital display
5: "Defrost phase" display
6: "Alarm" display
7: IR receiver

4.3 Keys on the remote control

DOOLING SET TWP 21°C ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩ ⑪ ⑫ ⑬ ⑭ ⑮ TURNO SELF CLEAN LED POLLUM ME TURNO SELF CLEAN

Fig. 9: Keys on the remote control

① "ON/OFF" key

Press this key to switch the air conditioning unit on and off.

② Operating mode selection

This key is used to set the desired operating mode. The automatic, cooling, dehumidification, heating and recirculation modes are available.

③ Fan speed

Use this key to select the desired fan speed. The automatic, low, medium and high functions are available. Note: In the dehumidification mode, the fan speed cannot be set manually.

④ "SLEEP" key

Activates/deactivates the "SLEEP" function.

Pressing this key will automatically increase or decrease the target temperature by 1 °C within an hour in cooling and heating mode respectively. Press this key to maintain the most convenient temperature and save energy. This function is only available in "Cooling", "Heating" and "Auto" modes. If the unit is working in "SLEEP" mode, this activity is interrupted by pressing the "MODE", "FAN", "Speed" or "ON/OFF" keys.

⑤ "FRESH" key (no function)

⑥ "TURBO" key

Activation of the turbo function makes it possible to reach the setpoint in cooling or heating mode as fast as possible.

⑦ "SELF CLEAN" key (no function)

⑧ "ARROW UP" and "ARROW DOWN" keys

"ARROW UP" key

Press the key in order to increase the setpoint in 1°C steps to a maximum 30°C.

"ARROW DOWN" key

Press the key in order to reduce the setpoint in 1^ C steps to a minimum 17^ C.

⑨ "SILENCE/FP" key (no function)

⑩ "TIMER ON" key

Press this key to activate the unit start delay time. Each press of this key increases the delay time by 30 minutes. When the set time on the display exceeds 10.0, each press of the button increases the set time by 60 minutes. To deactivate the delay time, set the time to 0.0.

⑪ "TIMER OFF" key

This key can be used to program the delayed switch-off time. Each press of this key increases the switch-off time by 30 minutes. When the set time on the display exceeds 10.0, each press of the button increases the set time by 60 minutes. To deactivate the switch-off time, set the time to 0.0.

⑫ Swing mode

Press this key to start or stop the swing mode. With the 2-point key, you can change the fin settings on the left side. The right key has no function.

Press this key once to change the angle by 6 degrees. Pressing the key for 2 seconds stops the swing function.

REMKO RVD series

⑬ "FOLLOW ME" key

This key can be used to activate/deactivate the FOLLOW ME function. In this mode, the room temperature is measured on the remote control. This sends a signal to the indoor unit every 3 minutes. If the remote control does not send a signal to the indoor unit for 7 minutes, this mode is automatically deactivated.

⑭ "LED" key

This activates/deactivates the display on the indoor unit.

Indicators on the LCD
① AUTO SET TEMP. ECO COOL 8.8°F DRY % H HEAT FAN AUTO ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩ ⑪ ⑬ ⑭ ⑮

Fig. 10: Indicators on the LCD

1: Mode indicator - shows the current operating modes, including Auto ( ) Cooling ( ) Dehumidification ( ) Heating ( ) Fan ( ) and back to Auto ( ) mode.
2: Signal transmission symbol. This symbol appears when signals are being transmitted from the remote control to the indoor unit.
3: ON/OFF symbol. This symbol appears when the "ON/OFF" key is pressed. Pressing this key again causes the indicator to go out.
4: TIMER ON symbol. This symbol appears when TIMER ON is switched on.
5: ECO function (not available)
6: TIMER OFF symbol. This symbol appears when TIMER OFF is switched on.
7: Battery charge status (weak)
8: Sleep symbol. This symbol appears when the "Sleep" function is activated. Pressing this key again causes the indicator to go out.
9: Temperature/Timer symbol. Shows the temperature setting (-17°C\~30°C). If "FAN" mode is selected, the temperature setting is not displayed. In Timer mode, the ON and OFF settings appear for the TIMER.
10: FOLLOW ME symbol. This symbol appears when the "Follow me" function is activated.
11: Display of ion generator active (optional)
12: Fan speed symbol. This is where the selected fan speeds are displayed: AUTO (no indicator) and the three fan speed settings: ✕ (slow), ✕ (medium) and ✕ (fast). The fan speed is set to "Automatic" when either "Auto" or "Dehumidification" mode is activated.
13: Silent mode active (optional)

REMKO RVD 525 DC - ⑭ "LED" key - 2

The illustration of the LCD with all of the symbols present is only intended to provide a clearer overview. During operation, only those symbols relevant to the respective functions appear on the display.

Key functions

A symbol is shown on the display to indicate that the settings are being transferred.

"Auto" mode (please observe notes!)

Make sure that the indoor unit is connected to the power supply, and is switched on.

The operating mode indicator on the display of the indoor unit begins to flash.

  1. Press the "MODE" key to select "Auto" mode.
  2. Press the "Arrow up/down" key to set the desired temperature. The temperature can be set between 17 and 30^ , in increments of 1^ .
  3. Press the "ON/OFF" key to switch on the air conditioning unit.

21°C ① ② ③ ①

Fig. 11: "Auto" mode

"Cooling", "Heating" and "Recirculation" mode

Make sure that the indoor unit is connected to the power supply, and is switched on.

  1. Press the "MODE" key to select from operating modes "Cooling", "Heating" or "Recirculation".
  2. Press the "Arrow up/down" key to set the desired temperature. The temperature can be set between 17 and 30^ , in increments of 1^ .
  3. Press the "F AN" key to select from the four fan speeds (Auto, slow, medium and fast).
  4. Press the "ON/OFF" key to switch on the air conditioning unit.

21°C ② ④ ① ③

Fig. 12: "Cooling", "Heating" and "Recirculation" mode

REMKO RVD series

"Dehumidification" mode

Make sure that the indoor unit is connected to the power supply, and is switched on.

The operating mode indicator on the display of the indoor unit begins to flash.

  1. Press the "MODE" key to select "Dehumidification" mode.
  2. The temperature setting on the remote control has no effect on unit operation.
  3. Press the "ON/OFF" key to switch on the air conditioning unit.

21°C ① ③ ②

Fig. 13: "Dehumidification" mode

In the "Dehumidification" mode, manual selection of the fan speed is not possible! Please note that temperature pre-selection is not possible and the dehumidified room can cool dramatically!

"Timer" mode

Press the "TIMER ON" key to set the "switch-on time" and the "TIMER OFF" key to set the "switch-off" time for the unit.

Setting the "switch-on time"

  1. Press the "TIMER ON" key . The remote control shows "TIMER ON", the last "switch-on time" setting and the symbol "H" appear on the display. The unit is now ready to reset the "switch-on time" and to start "TIMER ON" mode.
  2. Press the "TIMER ON" key again to set the desired "switch-on time". Each time the key is pressed, the time is increased by half an hour between 0 and 10 hours, and by an hour between 10 and 24 hours.
  3. Once these settings have been made, there is a one second delay before the remote control transmits the signal to the indoor unit. Then, after approx. two seconds, the "H" symbol disappears from the LCD display, and the set temperature appears again on the display.

COOLIC 21°C ① ②

Fig. 14: "Timer" mode

Setting the "switch-off time"

  1. Press the "TIMER OFF" key . The remote control shows "TIMER OFF", the last "switch-off time" setting and the symbol "H" appear on the display. The unit is now ready to reset the "switch-off time" and to stop "TIMER OFF" mode.

  2. Press the "TIMER OFF" key again to set the desired "switch-off time". Each time the key is pressed, the time is increased by half an hour between 0 and 10 hours, and by an hour between 10 and 24 hours.

  3. Once these settings have been made, there is a one second delay before the remote control transmits the signal to the indoor unit. Then, after approx. two seconds, the "H" symbol disappears from the LCD display, and the set temperature appears again on the display.

REMKO RVD 525 DC - "Timer" mode - 2

- When T timer mode is selected, the remote control automatically transfers the timer signal to the indoor unit for the specified period of time. Therefore, you should hold the remote control in a location where it can transfer the signal to the indoor unit without interference.

The effective operation for the time settings by the remote control for the timer function is restricted to the following settings: 0.5, 1.0, 1.5, 2.0, 2.5, 3.0, 3.5, 4.0, 4.5, 5.0, 5.5, 6.0, 6.5, 7.0, 7.5, 8.0, 8.5, 9.0, 9.5, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23 and 24.

Example TIMER function settings

"TIMER ON" (Auto on mode)

Example:

You want the air conditioning unit to switch on 2 hours from the time it was programmed.

  1. Press the "TIMER ON" key . The last operating time setting for the timer, and the "H" symbols, appear on the display.
  2. Press the "TIMER ON" key until the desired start time is shown in the "TIMER ON" area on the remote control.

  3. W ait for 3 seconds and the temperature appears again in this area of the digital display. The "TIMER ON" indicator stays lit, and this function is activated.

COOL SET TEMP. 2.0H FAN AUTO Start Off 2 hours laterSet time

Fig. 15: "TIMER ON" example

"TIMER OFF" (Auto off mode)

Example:

You want the air conditioning unit to switch off 4 hours from the time it was programmed.

  1. Press the "TIMER OFF" key . The last operating time setting for the timer, and the "H" symbols, appear on the display.
  2. Press the "TIMER OFF" key until "10H" is shown in the "TIMER OFF" area on the remote control.
  3. W ait for 3 seconds and the temperature appears again in this area of the digital display. The "TIMER OFF" indicator stays lit, and this function is activated.

COOL SET TEMP. 4.0H FAN AUTO OFF Stop On 4 hours laterSet time

Fig. 16: "TIMER OFF" example

REMKO RVD series

Combined TIMER (setting "TIMER ON" and "TIMER OFF" at the same time)

"TIMER OFF ⇒ "TIMER ON"

$$ (\text { On } \Rightarrow \text { Stop } \Rightarrow \text { Start }) $$

Example:

You want the air conditioning unit to switch off in two hours from the time it was programmed, and switch back on ten hours later.

  1. Press the "TIMER OFF" key.
  2. Press the "TIMER OFF" key again until the desired stop time is shown in the "TIMER OFF" area on the remote control.
  3. Press the "TIMER ON" key.
  4. Press the "TIMER ON" key again until "10H" is shown in the "TIMER ON" area on the remote control.
  5. Wait for 3 seconds and the temperature appears again in this area of the digital display. The "TIMER ON" and "TIMER OFF" indicators stay lit, and this function is activated.

REMKO RVD 525 DC - Example: - 1

REMKO RVD 525 DC - Example: - 2
Fig. 17: "TIMER OFF" / "TIMER ON" example

"TIMER ON "TIMER OFF"

$$ (\text { Off } \Rightarrow \text { Start } \Rightarrow \text { Stop }) $$

Example:

You want the air conditioning unit to switch on in two hours from the time it was programmed, and switch back off five hours later.

  1. Press the "TIMER ON" key.
  2. Press the "TIMER ON" key again until "2.0H" is shown in the "TIMER ON" area on the remote control.
  3. Press the "TIMER OFF" key.
  4. Press the "TIMER OFF" key again until "5.0H" is shown in the "TIMER OFF" area on the remote control.
  5. Wait for 3 seconds and the temperature appears again in this area of the digital display. The "TIMER ON" and "TIMER OFF" indicators stay lit, and this function is activated.

REMKO RVD 525 DC - Example: - 1

REMKO RVD 525 DC - Example: - 2
Fig. 18: "TIMER ON" / "TIMER OFF" example

5 Installation instructions for qualified personnel

5.1 Important notes prior to installation

Transport the unit in its original packaging as close as possible to the installation location. You avoid transport damage by doing so.
Check the contents of the packaging for completeness and check the unit for visible transport damage. Report any damage immediately to your contractual partner and the shipping company.
Lift the unit on the corners and not on the refrigerant or condensate drainage connections.
The refrigerant piping (injection and suction pipe), valves and connections must be insulated against vapour density. If necessary also insulate the condensate drainage line.
- Select an installation location which allows air to freely flow through the air inlet and outlet (see section "Minimum clearances").
Do not install the unit in the immediate vicinity of devices which generate intensive thermal radiation. Installation in the vicinity of thermal radiation reduces the unit output.
Only open the shut-off valves on the refrigerant piping after installation is complete.
Seal off open refrigerant piping with suitable caps or adhesive strips to prevent the infiltration of moisture and never kink or compress the refrigerant piping.
Avoid unnecessary bends. This minimises the pressure loss in the refrigerant piping and ensures that the compressor oil can flow back without obstruction.
Use the fastening materials provided in the scope of supply for the units.
Use four supports and the associated hooks to attach the ceiling cassette.
Use the insulated condensate hose in the scope of delivery as a junction piece to the continuing condensate drain. Secure the condensate drain with the supplied clamps.

5.2 Wall openings

A wall opening of at least 70mm diameter and 10mm incline from the inside to the outside must be created.
To prevent damage to the lines, the interior of the wall opening should be padded or, for example, lined with PVC pipe (see figure).
After installation has been completed, use a suitable sealing compound to close off the wall opening, taking account of fire protection regulations (responsibility of customer). Do not use cement or lime containing substances!

Cross-sectional diagram of a cable showing labeled components: outer sheath, middle sheath, and inner sheath with copper wires.

Fig. 19: Wall opening

1: Liquid line
2: Control line
3: Condensate drainage line
4: Suction pipe
5: PVC pipe

5.3 Installation materials

The indoor unit is attached using 4 threaded rods provided by the customer.

The outdoor unit is attached by 4 screws and a wall bracket to the wall or fixed by a floor bracket to the ground.

REMKO RVD series

5.4 Selection of installation location

Indoor unit

The indoor unit is designed for horizontal ceiling installation. The minimum distance from the floor should be 2 metres.

Outdoor unit

The outdoor unit is designed for horizontal installation on a base in outdoor areas. The installation site must be level, flat and firm. The unit should also be secured to prevent it from tipping over. The outdoor unit can be set up outside as well as inside a building. For external installation, please observe the following notes to protect the unit from the influence of the weather.

Rain

The unit should be at least 10 cm off the ground when mounted on the roof or ground. A floor bracket is available as an accessory.

Sun

The condenser on the outdoor unit emits heat. Exposure to sunlight further increases the temperature of the fins and reduces the heat released by the finned heat exchanger. The outdoor unit should be installed on to the north side of the building whenever possible. If necessary, take measures to provide sufficient shade (responsibility of customer). This could be a small roof. However, the discharging warm air flow must not be affected by the measures.

Wind

If the unit is being installed in windy areas, ensure that the warm outlet air is discharged in the prevailing wind direction. If this is not the possible, it may be necessary to install a windbreak (to be provided by the customer). Ensure that the windbreak does not adversely affect the air intake to the unit. Additional stabilisation is recommended. This can be realised with wire ropes or other constructions.

Diagram showing airflow direction with labeled arrows and a numbered annotation, likely illustrating a physics or engineering concept.

Fig. 20: Windbreak
1: Wind

Snow

The unit should be wall-mounted in areas of heavy snowfall. Installation should be at least 20 cm above the expected level of snow to prevent snow from entering the outdoor unit. An optional wall bracket is available as an accessory.

20 cm ①

Fig. 21: Minimum clearance to snow
1: Snow

Installation inside buildings

■ Ensure that heat can dissipate adequately when placing the outdoor unit in cellars, lofts, adjoining rooms or halls (Fig. 22).

Install an additional fan with a rated flow comparative to that of the outdoor unit being installed in the room and which can compensate any additional pressure loss in ventilation ducts (Fig. 22).

Comply with any regulations and conditions affecting the statics of the building. If necessary, fit acoustic installation.

REMKO RVD 525 DC - Snow - 2

flowchart
graph TD
    A["1"] --> B["2"]
    B --> C["3"]
    C --> D["3"]
    D --> E["K"]
    E --> F["W"]
    F --> G["2"]
    G --> H["3"]
    H --> I["2"]
    I --> J["3"]
    J --> K["K"]
    K --> L["2"]
    L --> M["3"]
    M --> N["W"]
    N --> O["2"]
    O --> P["K"]
    P --> Q["2"]
    Q --> R["W"]
    R --> S["2"]
    S --> T["K"]

Fig. 22: Installation inside buildings

K: Cold fresh air

W: Warm air

1: Outdoor unit

2: Additional fan

3: Air shaft

5.5 Minimum clearances

Observe the minimum clearances to allow access for maintenance and repair work and facilitate optimum air distribution.

ITAT 1000 1000 1000 1000 1000 ① E D A B C ②

Fig. 23: Minimum clearances, indoor unit and outdoor unit (all measurements in mm)

AT: Outdoor unit / IT: Indoor unit 1: Air inlet / 2: Air outlet

ABCDE
RVD 355-1055 DC3002000600300600

REMKO RVD series

5.6 Oil return measures

If the outdoor unit is installed at a higher level than the indoor unit, suitable oil return measures must be taken. Usually, an oil pump bend is installed for every 7 metres of height difference.

A ① ② B

Fig. 24: Oil return measures

AT: Outdoor unit

IT: Indoor unit

1: 1 x oil pump bend in suction pipe to outdoor unit every 7 metres of height difference, radius: 50 mm

2: Max. 10-15 m

6 Installation

6.1 Unit installation

! NOTICE!

Installation should only be performed by authorised specialists.

The unit is mounted with the cover facing down on four threaded rods. Take into account the ceiling grid and any other installations.

  1. Use the dimensions of the ceiling cassette to mark the fixing points for the threaded rods on structural parts approved to support the static load above the suspended ceiling (Fig. 25).

  2. Fit the indoor unit onto the threaded rods and use the lower nuts to level the unit (Fig. 26).

  3. Adhere to a ceiling clearance of at least 30 mm. Connect the refrigerant piping, electrical cables and condensate drainage line to the indoor unit as described below.

  4. Check again that the unit is level.

  5. The final task is to tighten the counternuts and attach the cover.

A B

Fig. 25: Hooking in the unit

Indoor units(all dimensions in mm)Measurement AMeasurement B
RVD 355-525 DC 545 523
RVD 685-1055 DC 780 680

Diagram illustrating a mechanical or electrical setup with labeled components and directional arrows, showing a device suspended from a platform.

Fig. 26: Hooking in the unit

1: Structural component

Distance A
RVD 355 DC IT 290 mm
RVD 525 DC IT 290 mm
RVD 685 DC IT 275 mm
RVD 1055 DC IT 275 mm

Technical diagram showing three labeled components (①, ②, ③) with structural elements and a dashed line marked A.

Fig. 27: Fastening the unit

A: Distance A

1: Ceiling
2: Suspended ceiling
3: Unit housing

Indoor unitsDistance ASuspended unit
RVD 355-525 DC IT 23 mm 545x523 mm
RVD 685-1055 DC IT10-18 mm780x680 mm

Fresh air connection

The unit is prepared for the intake of fresh air.

REMKO RVD 525 DC - Fresh air connection - 1

natural_image 3D rendering of a mechanical device with a labeled component (1) and no visible text or symbols on the main body.

Fig. 28: Fresh air connection

1: Fresh air connection

! NOTICE! Only use one fresh air connection

! NOTICE! The unit is factory filled with dry nitrogen for leak testing purposes. The pressurised nitrogen is released when the union nuts are undone.

Fresh air connection

The unit can also be employed to suck in and regulate the temperature of fresh air (outdoor air), in addition to room air. This is the preferred option for rooms with a high rate of air consumption.

  • Observe the regional regulations concerning air treatment.
    ■ Fit a collar with a nominal diameter of 65 mm to the fresh air connection (Fig. 29).

REMKO RVD series

REMKO RVD 525 DC - REMKO RVD series - 1

flowchart
graph TD
    A["Chamber 1"] --> B["Flow Arrows"]
    B --> C["Chamber 2"]
    C --> D["Flow Arrows"]
    D --> E["Chamber 3"]
    E --> F["Flow Arrows"]
    F --> G["Chamber 4"]
    G --> H["Flow Arrows"]
    H --> I["Chamber 5"]
    I --> J["Flow Arrows"]
    J --> K["Chamber 6"]
    K --> L["Flow Arrows"]
    L --> M["Chamber 7"]
    M --> N["Flow Arrows"]
    N --> O["Chamber 8"]
    O --> P["Flow Arrows"]
    P --> Q["Chamber 9"]
    Q --> R["Flow Arrows"]
    R --> S["Chamber 10"]

Fig. 29: Fresh air connection

1: Outdoor air intake

A: Outside
B: Inside

The fresh air content should not exceed 10% of the nominal air flow rate for the unit. The fresh air supply should be controlled by an additional speed-regulated fan.
The air at the outdoor air intake should be sucked in through a dust filter at a maximum rate of 2.5 m/s to prevent the ingress of rain water.
The fan should be connected to a separately protected electrical supply that is to be provided by the customer.

REMKO RVD 525 DC - REMKO RVD series - 2

natural_image Close-up of a mechanical component with a highlighted section and numbered marker (1), no readable text or symbols present.

Fig. 30: Fresh air inlet

1: Fresh air inlet

6.2 Connection of refrigerant piping

The refrigerant piping connection provided by the customer takes place on one corner of the unit, inside the suspended ceiling. Once installed, the connections should be insulated to make them vapour diffusion proof.

! NOTICE!

Use only tools which are approved for use in an HVAC environment. (z. B.: bending pliers, pipe/tubing cutters, de-burrers and flaring tools). Do not cut refrigerant pipes with a saw.

! NOTICE!

All work must be carried out in a way that prevents dirt, particles, water etc. from entering, refrigerant lines!

! NOTICE!

A detachable connection may only be established outside the room. To connect the indoor units, use only the supplied, non-detachable union nuts or provide a firm connection.

Connection of the unit panel

The unit panel is bolted onto the ceiling cassette with the 4 screws supplied. Connect the connection cables between the unit panel and ceiling cassette together. When doing so, note that the connection cable of the swing motors must be connected directly to the control board of the ceiling cassette at contact CN14 (swing). A cable with connecting plug may have been plugged in at the factory. This must be removed for installation.

The following instructions describe the installation of the cooling cycle and the assembly of the indoor unit and the outdoor unit:

  1. The required pipe diameters are given in the table "Technical data".
  2. Install the indoor unit and connect the refrigerant piping as described in the operating manual for the indoor unit.

  3. Use the wall or floor brackets to fit the outdoor unit against structural parts approved to support the static load (refer to the installation instructions for the brackets).

  4. Ensure that structure-borne sound is not transferred to parts of the building. Use vibration dampers to reduce the effects of structure-borne sound!

  5. Lay the refrigerant piping from the indoor unit to the outdoor unit. Ensure that the fastenings are adequate and if necessary, take appropriate oil return measures!

  6. Remove the factory-fitted protective caps and union nuts on the connections. These should be used later in the installation process.

  7. Before flanging the refrigerant piping, ensure that the union nut is fitted on the pipe.

  8. Prepare the laid refrigerant piping as shown below (Fig. 31 and Fig. 32).

  9. V erify that the shape of the flange is correct (Fig. 33).

  10. First connect and hand-tighten the refrigerant piping to ensure it is correctly seated.

  11. Then tighten the fittings with 2 appropriately-sized open-ended spanners. Use a spanner to counter the force when tightening the fitting (Fig. 34).

  12. Use insulation hoses which are designed for this temperature range and are diffusion proof.

  13. Observe the permitted bending radius for the refrigerant piping during installation. Never bend a pipe twice in the same place. Brittleness and cracking can result.

  14. Apply appropriate heat insulation to the installed refrigerant piping, including connector.

  15. T ake the same action at the shut-off valves for all subsequent refrigerant piping.

Diagram showing two hands operating a tool with labeled parts, including a copper connector and red tool.

Fig. 31: Deburring the refrigerant piping

1: Refrigerant piping /2: Deburrer
REMKO RVD 525 DC - Connection of the unit panel - 2

natural_image Close-up of hands using a mechanical clamp or tool to adjust a cable or hose component (no text or symbols visible)

Fig. 32: Flanging the refrigerant piping

1: Flanging tool
90° Ø A

Fig. 33: Correct flange shape

REMKO RVD series

Diagram of a wrench tool with labeled parts ① and ②, showing mechanical assembly.

Fig. 34: Tightening the fitting

1: Tighten with the first open-ended spanner
2: Counter with the second open-ended spanner

Pipe dimension in inchesTightening torque in Nm
1/4" 15-20
3/8" 33-40
1/2" 50-60
5/8" 65-75
3/4" 95-105

6.3 Leak testing

Once all the connections have been established, the pressure gauge station is attached to the corresponding Schrader valve connection as follows:

blue = large valve = suction pressure

Once the connection has been made successfully, the leak test is carried out with dry nitrogen.

Leak testing involves spraying a leak detection spray onto the connections. If bubbles are visible, the connections have not been made properly. In that case, tighten the connection or, if necessary, create a new flange.

After completing a successful leak test, the excess pressure in the refrigerant piping is removed and a vacuum pump with an absolute final partial pressure of min. 10 mbar is used to remove all of the air and empty the pipes. Any moisture present in the pipes will also be removed.

! NOTICE!

A vacuum of at least 20 mbar must be produced!

The time required to generate the vacuum is dependent on the final pressure pipe volume of the indoor units and the length of the refrigerant piping. However, the process will take at least 60 minutes. Once any foreign gases and humidity have been completely extracted from the system, the valves on the pressure gauge station are closed and the valves on the outdoor unit are opened as described in the "Commissioning" section.

6.4 Adding refrigerant

The units contain a basic quantity of refrigerant. In addition, an additional amount of refrigerant must be added for refrigerant piping lengths exceeding 5 metres per circuit. Refer to the following chart:

Up to andincl. 5mFrom 5m to max. length
RVD 355 DC0 g/m15 g/m
RVD 525 DC
RVD 685 DC30 g/m
RVD 1055 DC

REMKO RVD 525 DC - Adding refrigerant - 1

CAUTION!

Wear protective clothing when handling refrigerant.

REMKO RVD 525 DC - CAUTION! - 1

DANGER!

Only refrigerant in a liquid state may be used to fill the cooling cycle!

REMKO RVD 525 DC - DANGER! - 1

NOTICE!

Check the overheating to determine the refrigerant fill quantity.

REMKO RVD 525 DC - NOTICE! - 1

NOTICE!

The escape of refrigerant contributes to climatic change. In the event of escape, refrigerant with a low greenhouse potential has a lesser impact on global warming than those with a high greenhouse potential.

This unit contains refrigerant with a greenhouse potential of 675. That means the escape of 1 kg of this refrigerant has an effect on global warming that is 675 times greater than 1 kg CO₂, based on 100 years. Do not conduct any work on the refrigerant circuit or dismantle the unit - always enlist the help of qualified experts.

7 Condensate drainage connection and safe drainage

Condensate drainage connection

If the temperature falls below the dew point, condensate will form on the cooling fins during cooling mode. A collection tray together with a condensate pump and liquid level switch are fitted as standard below the cooling fins. If the liquid level switch trips a protective shutdown due to inadequate removal of the condensate, the pump will switch on immediately and run on for approx. three minutes.

The condensate drainage line should have an incline of min. 2%. This is the responsibility of the customer. If necessary, fit vapour-diffusion-proof insulation.
If the level of the condensate drainage line on the unit is above that of the outlet, route the pipe vertically upwards and then with an incline to the drain.
Route the unit's condensate drainage line freely into the drain line. If the condensate runs directly into a sewer pipe, fit a trap to prevent any unpleasant odours.
When operating the unit at outside temperatures below 4 °C, ensure the condensate drainage line is laid to protect it against frost. If necessary, fit a pipe heater.
Following installation, check that the condensate run off is unobstructed and ensure that the line is durably leak tight.

Safe drainage in the event of leakages

Local regulations or environmental laws, for example the German Water Resource Act (WHG), can require suitable precautions to protect against uncontrolled drainage in case of leakage to provide for safe disposal of escaping air conditioning fluid or hazardous media.

REMKO RVD 525 DC - Safe drainage in the event of leakages - 1

NOTICE!

The max. pump pressure of the condensate pump is 500/750 mmWS. Capacity reductions can result from external influences such as air-side counter-pressure, soiling or wear. In order to guarantee safe functional operation, we recommend observing a maximum delivery height of 450/700 mm!

REMKO RVD series

! NOTICE!

If condensate is removed via a duct in accordance with DIN EN 1717, ensure that any microbiological contamination present on the wastewater side (bacteria, fungi, viruses) cannot enter the unit connected to it.

A B C D

Fig. 35: Condensate drainage connection - incorrect!

A: Riser pipe too far away
B: Condensate drainage line too large/small
C: No incline
D: Cannot freely drain away

min. 2% 16-20 mm max. 500 mmWS

Fig. 36: Condensate drainage connection - correct!

8 Electrical wiring

8.1 General connection and safety instructions

A protected power supply cable is to be connected to the outdoor unit and a four-core control line with a minimum cross-section of 1.5mm^2 . To avoid EMC interference, only use shielded cable for this purpose and connect the shielding on both sides.

REMKO RVD 525 DC - General connection and safety instructions - 1

DANGER!

All electrical installation work is to be performed by specialist companies. Disconnect the power supply when connecting the electrical terminals.

REMKO RVD 525 DC - DANGER! - 1

NOTICE!

The electrical connection for the units must be made at a separate feedpoint with a residual current device in accordance with local regulations and should be laid out by an electrician.

REMKO RVD 525 DC - NOTICE! - 1

We recommend using shielded wires for the control lines.

We recommend that a mains/repair switch be installed near the outdoor unit.
The terminal blocks for establishing the connections are located on the side of the unit. When the unit is installed, measurements can be made from the front by removing the cover.
If an optional condensate pump is used as an accessory in conjunction with the unit, it may be necessary to install an additional relay with a higher contact rating after the switch-off contact on the pump to switch off the compressor.
The control lines used should comprise shielded wire, if laid in areas exposed to strong magnetic fields.
Details concerning the electrical protection of the system are provided in the technical data.

8.2 Connecting the indoor unit

Make the connection as follows:

  1. Open the air inlet grill.
  2. Loosen the switch cabinet's cover ( Fig. 38).
  3. Feed the voltage-free cable through the edge protection rings on the control box and clamp the cable in the strain relief.
  4. Then connect the cable in accordance with the wiring diagram (see chapter "Electrical wiring diagram").
  5. Connect the electrical plugs on the cover to the mating connectors on the cassette. It is not possible to incorrectly connect these.
  6. Re-install all disassembled parts.

REMKO RVD 525 DC - Connecting the indoor unit - 1

natural_image Diagram of a microwave oven with airflow direction indicated by green arrow (no text or symbols)

Fig. 37: Switch cabinet access

REMKO RVD series

Technical diagram of a device internal structure with numbered components and exploded view, showing assembly steps.

Fig. 38: Connecting the indoor unit

1: Plastic cover
2: Electrical drawing
3: Power supply connection terminals
4: Strain relief

5: Communication line to outdoor unit
6: Plastic cover
7: Cable fastening possibility

REMKO RVD 525 DC - REMKO RVD series - 2

Check all plugged and clamped terminals to verify that they are seated correctly and make permanent contact. Tighten as required.

8.3 Outdoor unit connection

Proceed as follows to connect the line:

  1. Remove the unit cover
  2. Remove the side panel at the connection.
  3. Choose the cable cross-section in accordance with the relevant specifications.
  4. Feed both cables through the edge protection rings on the fixed connection panel.
  5. Connect the lines as shown on the electrical connection diagram.
  6. Fix the line in the strain relief and re-assemble the unit.

8.4 Electrical wiring diagram

Connection RVD 355 DC
A 2(N) 1(L) W PE PE B 2(N) 1(S) W L N S PE 1 230V/1~/50 Hz

Fig. 39: Electrical wiring diagram RVD 355 DC

A: Outdoor unit RVD 355 DC AT

B: Indoor unit RVD 355 DC IT

1 Power supply

2: Communication lines

REMKO RVD series

Connection RVD 525 DC
A L N 1(L) 2(N) S L N PE PE PE B S 1 230V/1~/50 Hz

Fig. 40: Electrical wiring diagram RVD 525 DC

A: Outdoor unit RVD 525 DC AT

B: Indoor unit RVD 525 DC IT

1 Power supply

2: Communication lines

Connection RVD 685 DC
REMKO RVD 525 DC - REMKO RVD series - 2

flowchart
graph TD
    subgraph_A["Configuration A"]
        A1["1(L)"] --> A2["2(N)"]
        A2 --> A3["L N"]
        A3 --> A4["⊕"]
        A4 --> A5["S1 S2"]
        A5 --> A6["PE"]
        A1 -->|1| A7["230V/1~50 Hz"]
        A7 --> A8["PE"]
    end
    subgraph_B["Configuration B"]
        B1["L N"] --> B2["S1"]
        B2 --> B3["PE"]
        B3 --> B4["S2"]
        B4 --> B5["PE"]
    end
    A1 -->|2| B2
    A2 -->|2| B3
    A3 -->|2| B4
    A4 -->|2| B5
    A5 -->|2| B6
    A6 -->|2| B7
    A7 -->|2| B8
    A8 -->|2| B9
    A9 -->|2| B10
    A10 -->|2| B11
    A11 -->|2| B12
    A12 -->|2| B13
    A13 -->|2| B14
    A14 -->|2| B15
    A15 -->|2| B16
    A16 -->|2| B17
    A17 -->|2| B18
    A18 -->|2| B19
    A19 -->|2| B20
    A20 -->|2| B21
    A21 -->|2| B22
    A22 -->|2| B23
    A23 -->|2| B24
    A24 -->|2| B25
    A25 -->|2| B26
    A26 -->|2| B27
    A27 -->|2| B28
    A28 -->|2| B29
    A29 -->|2| B30
    A30 -->|2| B31
    A31 -->|2| B32
    A32 -->|2| B33
    A33 -->|2| B34
    A34 -->|2| B35
    A35 -->|2| B36
    A36 -->|2| B37
    A37 -->|2| B38
    A38 -->|2| B39
    A39 -->|2| B40
    A40 -->|2| B41
    A41 -->|2| B42
    A42 -->|2| B43
    A43 -->|2| B44
    A44 -->|2| B45
    A45 -->|2| B46
    A46 -->|2| B47
    A47 -->|2| B48
    A48 -->|2| B49
    A49 -->|2| B50
    A50 -->|2| B51
    A51 -->|2| B52
    A52 -->|2| B53
    A53 -->|2| B54
    A54 -->|2| B55
    A55 -->|2| B56
    A56 -->|2| B57
    A57 -->|2| B58
    A58 -->|2| B59
    A59 -->|2| B60
    A60 -->|2| B61
    A61 -->|2| B62
    A62 -->|2| B63
    A63 -->|2| B64
    A64 -->|2| B65
    A65 -->|2| B66
    A66 -->|2| B67
    A67 -->|2| B68
    A68 -->|2| B69
    A69 -->|2| B70
    A70 -->|2| B71
    A71 -->|2| B72
    A72 -->|2| B73
    A73 -->|2| B74
    A74 -->|2| B75
    A75 -->|2| B76
    A76 -->|2| B77
    A77 -->|2| B78
    A78 -->|2| B79
    A79 -->|2| B80
    A80 -->|2| B81
    A81 -->|2| B82
    A82 -->|2| B83
    A83 -->|2| B84
    A84 -->|2| B85
    A85 -->|2| B86
    A86 -->|2| B87
    A87 -->|2| B88
    A88 -->|2| B89
    A89 -->|2| B90

Fig. 41: Electrical wiring diagram RVD 685 DC

A: Outdoor unit RVD 685 DC AT

B: Indoor unit RVD 685 DC IT

1 Power supply

2: Communication lines

REMKO RVD series

Connection RVD 1055 DC
REMKO RVD 525 DC - REMKO RVD series - 1

flowchart
graph TD
    subgraph_Panel_A[" fan "]
        L1["L1"] --> PE1["PE"]
        L2["L2"] --> PE2["PE"]
        L3["L3"] --> PE3["PE"]
        N["N"] --> PE4["PE"]
        PE1 --> 1["1"]
        PE2 --> 1
        PE3 --> 1
        PE4 --> 1
        PE5["PE"] --> 1
        PE6["PE"] --> 1
    end
    subgraph_Panel_B[" fan "]
        S1["S1"] --> PE7["PE"]
        S2["S2"] --> PE8["PE"]
        PE7 --> 2["2"]
        PE8 --> 2
    end
    L1 --> 1
    L2 --> 1
    L3 --> 1
    L3 --> 1
    L1 --> 2
    L2 --> 2
    L3 --> 2
    L3 --> 2
    L1 --> 2
    L2 --> 2
    L3 --> 2
    L3 --> 2
    L1 --> 2
    L2 --> 2
    L3 --> 2
    L1 --> 2
    L2 --> 2
    L3 --> 2
    L3 --> 2
    L1 --> 2
    L2 --> 2
    L3 --> 2
    L1 --> 2
    L2 --> 2
    L3 --> 2
    L1 --> 2
    L2 --> 2
    L3 --> 2
    style Panel_A fill:#f9f,stroke:#333
    style Panel_B fill:#bbf,stroke:#333

Fig. 42: Electrical wiring diagram RVD 1055 DC

A: Outdoor unit RVD 1055 DC AT

B: Indoor unit RVD 1055 DC IT

1 Power supply

2: Communication lines

8.5 Electrical drawings

Indoor unit RVD 355 DC IT
REMKO RVD 525 DC - Electrical drawings - 1

flowchart
graph TD
    A["① M"] --> B["②"]
    B --> C["③"]
    C --> D["④"]
    D --> E["⑤"]
    E --> F["⑥"]
    F --> G["⑦"]
    G --> H["⑧"]
    H --> I["⑨"]
    I --> J["⑩"]
    J --> K["⑪"]
    K --> L["⑫"]
    L --> M["⑬"]
    M --> N["⑭"]
    N --> O["⑮"]
    O --> P["⑯"]
    P --> Q["⑰"]
    Q --> R["⑱"]
    R --> S["⑲"]
    S --> T["⑳"]
    T --> U["㉑"]
    U --> V["㉒"]
    V --> W["㉓"]
    W --> X["㉔"]
    X --> Y["㉕"]
    Y --> Z["㉖"]
    Z --> AA["㉗"]
    AA --> AB["㉘"]
    AB --> AC["㉙"]
    AC --> AD["㉚"]
    AD --> AE["㉛"]
    AE --> AF["㉜"]
    AF --> AG["㉝"]
    AG --> AH["㉟"]
    AH --> AI["㉟A"]
    AI --> AJ["①4"]
    AJ --> AK["③"]
    AK --> AL["④"]
    AL --> AM["⑤"]
    AM --> AN["⑥"]
    AN --> AO["⑦"]
    AO --> AP["⑧"]
    AP --> AQ["㉑"]
    AQ --> AR["㉒"]
    AR --> AS["㉓"]
    AS --> AT["㉔"]
    AT --> AU["㉕"]
    AU --> AV["㉖"]

Fig. 43: Electrical drawings RVD 355 DC IT

A: Control board
B: Display circuit board
1: DC fan motor (alternative)
2: Optional wired remote control
3: Connection of optional wired remote control
4: Potential-free alarm contact
5: External on/off
6: Connection possibility for fan motor provided by the customer
7: Transformer

8: Temperature probe, suction pipe
9: Temperature probe, evaporator
10: Temperature probe, indoor air
11: Swing motor
12: Connecting line to the outdoor unit
13: MCC-1 controller connection
14: DC fan motor
15: Condensate pump
16: Condensate pump liquid level switch
17: AC fan motor

REMKO RVD series

DIP switch setting possibilities

Address assignment MCC-1 (S2+S1)

Switch
S2 + S1REMKO RVD 525 DC - DIP switch setting possibilities - 1REMKO RVD 525 DC - DIP switch setting possibilities - 2REMKO RVD 525 DC - DIP switch setting possibilities - 3REMKO RVD 525 DC - DIP switch setting possibilities - 4
Address 0~15 16~31
Factory setting
S2 + S1REMKO RVD 525 DC - DIP switch setting possibilities - 5REMKO RVD 525 DC - DIP switch setting possibilities - 6REMKO RVD 525 DC - DIP switch setting possibilities - 7REMKO RVD 525 DC - DIP switch setting possibilities - 8
Address 32~47 48~63
Factory setting

Anti-cold air function (SW1)

Switch SW1Factory setting
Fan motor stop temperature
REMKO RVD 525 DC - DIP switch setting possibilities - 924
REMKO RVD 525 DC - DIP switch setting possibilities - 1015
REMKO RVD 525 DC - DIP switch setting possibilities - 118
REMKO RVD 525 DC - DIP switch setting possibilities - 12After EEPROM programming

Fan behaviour without demand (SW2)

Switch SW2 ValueFactory setting
ON SettingREMKO RVD 525 DC - DIP switch setting possibilities - 13Fan OFF
REMKO RVD 525 DC - DIP switch setting possibilities - 14Fan ON

Automatic restart after power failure (SW3)

Switch SW3 ValueFactory setting
ON SettingREMKO RVD 525 DC - DIP switch setting possibilities - 15Automatic restart in last operating mode
REMKO RVD 525 DC - DIP switch setting possibilities - 16No automatic restart

Mode priority (SW5)

Switch SW5
ONSettingREMKO RVD 525 DC - DIP switch setting possibilities - 17REMKO RVD 525 DC - DIP switch setting possibilities - 18REMKO RVD 525 DC - DIP switch setting possibilities - 19REMKO RVD 525 DC - DIP switch setting possibilities - 20
Value HeatingHeatingCoolingCooling
Factory setting

Temperature compensation (SW6)

Switch SW6
ONSettingREMKO RVD 525 DC - DIP switch setting possibilities - 21REMKO RVD 525 DC - DIP switch setting possibilities - 22REMKO RVD 525 DC - DIP switch setting possibilities - 23REMKO RVD 525 DC - DIP switch setting possibilities - 24
Value642
Factory setting

Indoor units RVD 525-1055 DC

REMKO RVD 525 DC - Indoor units RVD 525-1055 DC - 1

flowchart
graph TD
    subgraph Section A
        M1["① M"] -->|5| CN15
        CN3["③ CN3"] -->|5| CN15
        CN13["④ CN13"] -->|5| CN15
        CN15 -->|4| CN40
        CN15 -->|2| X59["X59"]
        CN15 -->|3| XP9["XP9"]
        CN15 -->|4| SWING_MOTOR["XSWING MOTOR"]
        CN15 -->|5| XP10["XP10"]
    end

    subgraph Section B
        CN8["② CN8"] -->|4| M["M"]
        M -->|2| M["M"]
        M -->|5| CN13
        CN13 -->|10| B["B"]
        B -->|5| 6["⑥"]
    end

    subgraph Section C
        FAN1["FAN1"] -->|6| CAP1["CAP1"]
        CAP1 --> braun["braun"]
        braun --> schwarz["schwarz"]
        schwarz --> CN66["CN66"]
        CN66 --> CN55["CN55"]
        CN55 --> E["Y"]
        CN55 --> X["X"]
        CN55 --> S2["S2"]
        CN55 --> S1["S1"]
        CN2["③"] --> CN3["④"]
        CN2 --> CN4["P3"]
        CN2 --> CN4
        CN2 --> CN4
        CN2 --> CN4
        CN2 --> CN4
        CN2 --> CN4
        CN2 --> CN4
        CN2 --> CN4
        CN2 --> CN4
    end

    subgraph Section D
        CX2["X2"] --> CAP1
        CX2 --> shwarz["schwarz"]
    end

    subgraph Section E
        CX2X2["X2"] --> CAP1
        CX2X2 --> shwarz
    end

    subgraph Section F
        CX2X2X2["X2"] --> CAP1
        CX2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2A
    end

    subgraph Section G
        CX7["T7B"] --> CN7["CN7"]
        CX6["T7B"] --> CN6["CN6"]
        CX5["T7B"] --> CN5["CN5"]
        CX4["T7B"] --> CN4["CN4"]
        CX3["T7B"] --> CN3["CN3"]
        CX2["T7B"] --> CN2["CN2"]
        CX1["T7B"] --> CN1["CN1"]
    end

    subgraph Section H
        CX8["T8T"] --> CN8["CN8"]
        CX7["T8T"] --> CN9["CN9"]
        CX6["T8T"] --> CN10["CN10A"]
        CX5["T8T"] --> CN10
        CX4["T8T"] --> CN10
        CX3["T8T"] --> CN10
    end

    subgraph Section I
        CX9["T9T"] --> CN9
        CX8["T9T"] --> CN10
        CX7["T9T"] --> CN10
        CX6["T9T"] --> CN10
        CX5["T9T"] --> CN10
        CX4["T9T"] --> CN10
    end

    subgraph Section J
        CX10["T10A"] --> B["B"]
    end

    subgraph Section K
        CX10["T10A"] --> B["B"]
    end

    subgraph Section L
        CX10["T10A"] --> P4["P4"]
    end

    subgraph Section M
        X9["X9"] --> SWING_MOTOR["XSWING MOTOR"]
        X8["X8"] --> SWING_MOTOR["XSWING MOTOR"]
    end

    subgraph Section M_A
        X9["X9"] --> SWING_MOTOR_X9["XSWING MOTOR_X9"]
    end

    subgraph Section M_B
        X8["X8"] --> SWING_MOTOR_X8["XSWING MOTOR_X8"]
    end

    subgraph Section M_C
        X9["X9"] --> SWING_MOTOR_X9["XSWING MOTOR_X9"]
    end

    subgraph Section M_D
        X8["X8"] --> SWING_MOTOR_DW["XSWING MOTOR_DW"]
    end

    subgraph Section M_F
        X9["X9"] --> SWING_MOTOR_FW["XSWING MOTOR_FW"]
    end

    subgraph Section M_G
        X8["X8"] --> SWING_MOTOR_GW["XSWING MOTOR_GW"]
    end

    subgraph Section M_H
        X9["X9"] --> SWING_MOTOR_HW["XSWING MOTOR_HW"]
    end

    subgraph Section M_H_A
        X8["X8"] --> SWING_MOTOR_HW_A["XSWING MOTOR_HW"]
    end

Fig. 44: Electrical drawings RVD 525-1055 DC

A: Control board
B: Display circuit board
1: DC fan motor (alternative)
2: Connection of optional wired remote control
3: Swing motors
4: Connection possibility for fan motor provided by the customer
5: Condensate pump
6: Optional wired remote control
7: Temperature probe, suction pipe

8: Temperature probe, evaporator
9: Temperature probe, indoor air
10: Condensate pump liquid level switch
11: Power supply
12: Communication line to outdoor unit
13: MCC-1 controller connection possibility
14: DC fan motor
15: Transformer
16: External on/off
17: Potential-free alarm contact

REMKO RVD series

DIP switch setting possibilities

Address assignment MCC-1 (S2+S1)

Switch
S2 + S1REMKO RVD 525 DC - DIP switch setting possibilities - 1REMKO RVD 525 DC - DIP switch setting possibilities - 2REMKO RVD 525 DC - DIP switch setting possibilities - 3REMKO RVD 525 DC - DIP switch setting possibilities - 4
Address 0~15 16~31
Factory setting
S2 + S1REMKO RVD 525 DC - DIP switch setting possibilities - 5REMKO RVD 525 DC - DIP switch setting possibilities - 6REMKO RVD 525 DC - DIP switch setting possibilities - 7REMKO RVD 525 DC - DIP switch setting possibilities - 8
Address 32~47 48~63
Factory setting

Anti-cold air function (SW1)

Switch SW1Factory setting
Fan motor stop temperature
[YSAD]24
REMKO RVD 525 DC - DIP switch setting possibilities - 915
REMKO RVD 525 DC - DIP switch setting possibilities - 108
REMKO RVD 525 DC - DIP switch setting possibilities - 11After EEPROM programming

Fan behaviour without demand (SW2)

Switch SW2 ValueFactory setting
ON SettingREMKO RVD 525 DC - DIP switch setting possibilities - 12Fan OFF
REMKO RVD 525 DC - DIP switch setting possibilities - 13Fan ON

Automatic restart after power failure (SW3)

Switch SW3 ValueFactory setting
ON SettingREMKO RVD 525 DC - DIP switch setting possibilities - 14Automatic restart in last operating mode
REMKO RVD 525 DC - DIP switch setting possibilities - 15No automatic restart

Main / slave setting (SW5)

Switch SW5
ONSettingREMKO RVD 525 DC - DIP switch setting possibilities - 16REMKO RVD 525 DC - DIP switch setting possibilities - 17REMKO RVD 525 DC - DIP switch setting possibilities - 18REMKO RVD 525 DC - DIP switch setting possibilities - 19
Value MAINNO SLAVEMAINMAINSLAVE
Factory setting

Temperature compensation (SW6)

Switch SW6
ON SettingREMKO RVD 525 DC - DIP switch setting possibilities - 20REMKO RVD 525 DC - DIP switch setting possibilities - 21REMKO RVD 525 DC - DIP switch setting possibilities - 22REMKO RVD 525 DC - DIP switch setting possibilities - 23
Value642
Factory setting

Power setting (ENC1)

ENC1
Switch no.Power [W]Switch no.Power [W]
44000-530089100-10500
55400-7100912000-14000
6-A14500-16000
77500-9000

Outdoor unit RVD 355 DC AT

REMKO RVD 525 DC - Outdoor unit RVD 355 DC AT - 1

flowchart
graph TD
    A["1"] --> B["CN 50"]
    B --> C["CN 21"]
    C --> D["CN 7"]
    D --> E["CN 31"]
    E --> F["CN 25"]
    F --> G["CN 60"]
    G --> H["W 1(L) 2(N) SL N"]
    H --> I["grün/gelb"]
    H --> J["grün/gelb"]
    H --> K["grün/gelb"]
    H --> L["grün/gelb"]
    C --> M["10"]
    D --> N["5/6"]
    E --> O["9"]
    style A fill:#f9f,stroke:#333
    style B fill:#ccf,stroke:#333
    style C fill:#cfc,stroke:#333
    style D fill:#fcc,stroke:#333
    style E fill:#cff,stroke:#333
    style F fill:#ffc,stroke:#333
    style G fill:#fcf,stroke:#333
    style H fill:#cff,stroke:#333
    style I fill:#ffc,stroke:#333
    style J fill:#cfc,stroke:#333
    style K fill:#fcc,stroke:#333
    style L fill:#ffc,stroke:#333

Fig. 45: Electrical drawings RVD 355 DC AT

A: Control board
1: Compressor
2: To indoor unit
3: Power supply
4: 4-way reversing valve
5: Crankcase heating
6: Condensate tray heating

7: Condenser
8: AC fan motor
9: Electronic E-valve
10: DC fan motor
11: Air inlet temperature probe
12: Temperature probe for condenser outlet
13: Temperature probe for heat gas line

REMKO RVD series

Outdoor unit RVD 525 DC AT
REMKO RVD 525 DC - REMKO RVD series - 1

flowchart
graph TD
    A["Control Panel"] --> B["CN 1A"]
    B --> C["BNP"]
    C --> D["BNP"]
    D --> E["BNP"]
    E --> F["BNP"]
    F --> G["BNP"]
    G --> H["BNP"]
    H --> I["BNP"]
    I --> J["BNP"]
    J --> K["BNP"]
    K --> L["BNP"]
    L --> M["BNP"]
    M --> N["BNP"]
    N --> O["BNP"]
    O --> P["BNP"]
    P --> Q["BNP"]
    Q --> R["BNP"]
    R --> S["BNP"]
    S --> T["BNP"]
    T --> U["BNP"]
    U --> V["BNP"]
    V --> W["BNP"]
    W --> X["BNP"]
    X --> Y["BNP"]
    Y --> Z["BNP"]
    Z --> AA["BNP"]
    AA --> AB["BNP"]
    AB --> AC["BNP"]
    AC --> AD["BNP"]
    AD --> AE["BNP"]
    AE --> AF["BNP"]
    AF --> AG["BNP"]
    AG --> AH["BNP"]
    AH --> AI["BNP"]
    AI --> AJ["BNP"]
    AJ --> AK["BNP"]
    AK --> AL["BNP"]
    AL --> AM["BNP"]
    AM --> AN["BNP"]
    AN --> AO["BNP"]
    AO --> AP["BNP"]
    AP --> AQ["BNP"]
    AQ --> AR["BNP"]
    AR --> AS["BNP"]
    AS --> AT["BNP"]
    AT --> AU["BNP"]
    AU --> AV["BNP"]
    AV --> AW["BNP"]
    AW --> AX["BNP"]
    AX --> AY["BNP"]

Fig. 46: Electrical drawings RVD 525 DC AT

A: Control board
B: Auxiliary circuit board
1: Compressor
2: Communication line to indoor unit
3: Supply line to indoor unit
4: Power supply
5: 4-way reversing valve
6: Crankcase heating

7: Condensate tray heating
8: AC fan motor
9: Electronic E-valve
10: DC fan motor
11: Air inlet temperature probe
12: Temperature probe for condenser outlet
13: Temperature probe for heat gas line

Outdoor unit RVD 685 DC AT

rot (braun) blau CN4 CN5 CN2 CN3 blau blau CN1 U V W CN14 V(S) W(C) 15 14 3/5 3/5 5/13 6/13 CN14 L-OUT RY2 ON(4) COM3 CN29 CN12 CN14 CN7 CN17 CN7 CN18 VALVE-A 4/T4 T3 ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩ ⑪ ⑫ ⑬ ⑭ ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ ㉑ ㉒ ㉓ ㉔ ㉕ ㉖ ㉗ ㉘ ㉙ ㉚ ㉛ ㉜ ㉝ ㉞ ㉟ ㉳ ㉴ ㉵ ㉜ ㉝ ㉞ ㉟ ㉞ ㉟ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞ ㉞

Fig. 47: Electrical drawings RVD 685 DC AT

A: Control board
B: Inverter board
1: Klixon
2: Low pressure switch
3: High pressure switch
4: Air inlet temperature probe
5: Temperature probe for condenser outlet
6: Temperature probe for heat gas line
7: Condensate tray heating

8: Crankcase heating
9: 4-way reversing valve
10: Communication line to indoor unit
11: Power supply
12: Supply line to indoor unit
13: DC fan motor
14: Compressor
15: Transformer

REMKO RVD series

Outdoor unit RVD 1055 DC AT
REMKO RVD 525 DC - REMKO RVD series - 1

flowchart
graph TD
    subgraph_Component_A["Component A"]
        A1["CN1"] --> A2["CN3"]
        A1 --> A3["CN5"]
        A2 --> A4["CN7"]
        A3 --> A5["CN9"]
        A4 --> A6["CN10"]
        A5 --> A7["CN11"]
        A6 --> A8["CN12"]
        A7 --> A9["CN13"]
        A8 --> A10["CN14"]
        A9 --> A11["CN15"]
        A10 --> A12["CN16"]
        A11 --> A13["CN17"]
        A12 --> A14["CN18"]
        A13 --> A14a["CN15"]
        A14 --> A14b["CN14"]
        A14b --> A14c["CN13"]
    end

    subgraph_Component_B["Component B"]
        B1["CN5CN6CN7"] --> B2["rot"]
        B2 --> B3["weiss"]
        B2 --> B4["blau"]
    end

    subgraph_Component_C["Component C"]
        C1["CN3"] --> C2["CN3"]
        C2 --> C3["FM1"]
        C3 --> C4["CAP1"]
        C4 --> C5["~"]
        C5 --> C6["HEAT_Y"]
        C6 --> C7["HEAT_D"]
        C7 --> C8["SV"]
    end

    subgraph_Component_D["Component D"]
        D1["CN34"] --> D2["CN35"] --> D3["CN11"] --> D4["CN7"]
        D4 --> D5["CN20-NL2"]
        D5 --> D6["CN30"]
        D6 --> D7["orange"]
        D7 --> D8["orange"]
        D8 --> D9["orange"]
        D9 --> D10["BLA"]
        D10 --> D11["BLA"]
        D11 --> D12["BLA"]
        D12 --> D13["L-PRO H-PRO"]
    end

    subgraph_Component_E["Component_E"]
        E1["PE2"] --> E2["PE1"]
    end

    subgraph_Component_F["Component_F"]
        F1["N CN2"] --> F2["L1 CN4"] --> F3["L2 CN8CN6"] --> F4["PE3"] --> F5["CN21"]
        F5 --> F6["SW"]
    end

    subgraph Component_G fill:#f9f,stroke:#333
    end

    subgraph Component_H fill:#ccf,stroke:#333
    end

    subgraph Component_I
        I1["SW"] --> I2["BLA"]
        I2 --> I3["BLA"]
        I3 --> I4["BLA"]
        I4 --> I5["BLA"]
        I5 --> I6["BLA"]
        I6 --> I7["BLA"]
        I7 --> I8["BLA"]
        I8 --> I9["BLA"]
        I9 --> I10["BLA"]
        I10 --> I11["BLA"]
        I11 --> I12["BLA"]
        I12 --> I13["BLA"]
        I13 --> I14["L-PRO H-PRO"]
    end

    subgraph Component_J
        J1["SW"] --> J2["BLA"] --> J3["BLA"] --> J4["BLA"] --> J5["BLA"] --> J6["BLA"] --> J7["BLA"] --> J8["BLA"] --> J9["BLA"] --> J10["BLA"] --> J11["BLA"] --> J12["BLA"] --> J13["L-PRO H-PRO"]
    end

    subgraph Component_K
        K1["TP 10"] --> K2["T4 11"] --> K3["T3 12"]
    end

    subgraph Component_L
        L1["TW 10"] --> L2["TW 10"] --> L3["TW 10"] --> L4["TW 10"] --> L5["TW 10"] --> L6["TW 10"] --> L7["TW 10"] --> L8["TW 10"] --> L9["TW 10"] --> L10["TW 10"] --> L11["TW 10"] --> L12["TW 10"] --> L13["TW 10"] --> L14["TW 10"] --> L15["TW 10"] --> L16["TW 10"] --> L17["TW 10"] --> L18["TW 10"] --> L19["TW 10"] --> L20["TW 10"] --> L21["TW 10"] --> L22["TW 10"] --> L23["TW 10"] --> L24["TW 10"] --> L25["TW 10"] --> L26["TW 10"] --> L27["TW 10"] --> L28["TW 10"] --> L29["TW 10"] --> L30["TW 10"] --> L31["TW 10"] --> L32["TW 10"] --> L33["TW 10"] --> L34["TW 10"] --> L35["TW 10"] --> L36["TW 10"] --> L37["TW 10"] --> L38["TW 10"] --> L39["TW 10"] --> L40["TW 10"] --> L41["TW 10"] --> L42["TW 10"] --> L43["TW 10"] --> L44["TW 10"] --> L45["TW 10"] --> L46["TW 10"] --> L47["TW 10"] --> L48["TW 10"] --> L49["TW 10"] --> L50["TW 10"] --> L51["TW 10"] --> L52["TW 10"] --> L53["TW 10"] --> L54["TW 10"] --> L55["TW 10"] --> L56["TW 10"] --> L57["TW 10"] --> L58["TW 10"] --> L59["TW 10"] --> L60["TW 10"]

    subgraph Component_M
        M["M 9"] --> N["MPTP ⑩"]
        N["MPTP ⑪"]
        N[MPTP ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪T MTPTP ⑫
        N[MPTP ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT
        N[MPTP ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT
        N[MPTP ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪CPTP
        N[MPTP ⑪TMT
        N[MPTP
        N[MPTP
        N[MPTP
        N[MPTP
        N[MPTP
        N[MPTP
        N[MPTP
        N[MPTP
        N[MPTP
        N[MPTP
        N[MPTP
        N[MPTP
        N[MPTP
        N[MPTP
        N[MPTP
        N[MPTP
        N[MPTP
        NMPTP
        NMPTP
        NMPTP
        NMPTP
        NMPTP
        NMPTP
        NMPTP
        NMPTP
        NMPTP
        NMPTP
        NMPTP
    end

Fig. 48: Electrical drawings RVD 1055 DC AT

A: Control board
B: Inverter board
C: Control board DC fan motor
1: Transformer
2: Magnetic ring
3: Compressor
4: DC fan motor
5: AC fan motor
6: Crankcase heating
7: Condensate tray heating

8: 4-way reversing valve
9: Electronic E-valve
10: Temperature probe for heat gas line
11: Temperature probe for condenser outlet
12: Air inlet temperature probe
13: Low pressure switch
14: High pressure switch
15: Communication line to indoor unit
16: Supply line to indoor unit
17: Power supply

8.6 Connection of a superordinate controller provided by the customer

Units of type RVD can be switched on and off by a superordinate controller. In order to utilise the potential-free contact for externally switching the unit on and off, it is first necessary to remove the jumper (JR6) at the indoor unit control board. The contacts are then available.

ON—OFF JR6

Fig. 49: Removing the jumper

The building controller is now connected via the two outer contacts of the plug labelled ON - OFF. If the connection between the two contacts is open, the system is in stand-by mode. The "Operation LED" and the "Timer LED" blink alternately. The unit can no longer be switched on using the remote control.

① ON—OFF JR6

Fig. 50: Open contact

1: Stand-By

If the connection between the two contacts is closed, the unit is reactivated and switches to the last operating mode used.

② ON—OFF JR6

Fig. 51: Closed contact

2: Operation

REMKO RVD series

9 Before commissioning

After leak testing has been successfully completed, connect the vacuum pump via the pressure gauge station to the valve connections on the outdoor unit (see chapter "Leak testing") and create a vacuum.

Perform the following checks prior to putting the unit into operation for the first time and after any work on the cooling cycle. Record the results in the commissioning report:

  • Check all refrigerant piping and valves for leak-tightness using leak detection spray or soapy water.
  • Check the refrigerant piping and insulation for damage.
  • Check the electrical connection between the indoor unit and the outdoor unit for correct polarity.
  • Check that all fastenings, mountings, etc. are firm and at the correct level.

10 Commissioning

! NOTICE!

Commissioning should only be performed by specially trained personnel and documented after the certificate has been issued. Observe the operating manuals for the indoor unit and outdoor unit when commissioning the entire system.

Once all the components have been connected and tested, the system can be put into operation. A functional check should be performed to verify its correct function and identify any unusual operating behaviour prior to handing it over to the operator.

! NOTICE!

Check that the shut-off valves and valve caps are tight after carrying out any work on the cooling cycle. Use appropriate sealant products as necessary.

Functional checks and test run

Check the following points:

  • Leak-tightness of the refrigerant piping.
    ■ Compressor and fan running smoothly.
    In cooling mode, cold air output by the indoor unit, and warm air output by the outdoor unit.
    ■ Function test of the indoor unit and all program sequences.
    Check of the surface temperature of the suction pipe and that the vaporiser is not overheating. To measure the temperature, hold the thermometer to the suction pipe and subtract the boiling point temperature reading on the pressure gauge from the measured temperature.
  • Record the measured temperatures in the commissioning report.

Function test of the cooling and heating modes

  1. Remove the protective caps from the valves.
  2. Start the commissioning procedure by briefly opening the shut-off valves on the outdoor unit until the pressure gauge indicates a pressure of approx. 2 bar.
  3. Check all connections for leaks with leak detection spray and suitable leak detectors.
  4. If no leaks are found, fully open the shut-of f valves by turning them anti-clockwise using a spanner. If leaks are found, remedy the faulty connection. It is imperative that the vacuum creation and drying steps are repeated.
  5. Activate the main circuit breaker or fuse.
  6. Use the remote control to switch on the unit and select the cooling mode, maximum fan speed and lowest target temperature.
  7. Check the overheating, outside, inside, outlet and vaporisation temperatures and record the measured values in the commissioning report. Check the correct function and settings of all regulation, control and safety devices.
  8. Check the unit control system using the functions described in the chapter "Operation". Timer, temperature setting, fan speeds and switching to ventilation or dehumidification mode.
  9. Check the correct function of the condensate drainage line by pouring distilled water into the condensate tray. A bottle with a spout is recommended for pouring the water into the condensate tray.
  10. Switch the indoor unit to heating mode.
  11. During the test run, check the functionality of all of the previously described safety devices.
  12. Record the measured values into the commissioning report and familiarise the operator with the system.
  13. Remove the pressure gauge. Check that seals have been fitted in the sealing caps.
  14. Re-install all disassembled parts.

11 Shutdown

Temporary shutdown

  1. Let the indoor unit run for 2 to 3 hours in recirculation mode, or in cooling mode at maximum temperature, to extract any residual humidity from the unit.
  2. Shut down the system using the remote control.
  3. Switch of unit. f the electrical power supply to the
  4. Cover the unit as far as possible with plastic foil in order to protect it from the influences of weather.

Permanent shutdown

Ensure that units and components are disposed of in accordance with local regulations, e.g. through authorised disposal and recycling specialists or at collection points.

REMKO GmbH & Co. KG or your contractual partner will be pleased to provide a list of certified firms in your area.

12 Troubleshooting, customer service and fault analysis

12.1 Troubleshooting and customer service

The unit and components are manufactured using state-of-the-art production methods and tested several times to verify their correct function. However, if malfunctions should occur, please check the functions as detailed in the list below. For systems with an indoor unit and outdoor unit, refer to the chapter "Troubleshooting and customer service" in both operating manuals. Please inform your dealer if the unit is still not working correctly after all function checks have been performed!

Operational malfunctions

Malfunction Possible causesChecks Remedial measures
The unit does not start or switches itself offPower failure, under-voltage, defective mains fuse / main switch in OFF positionDoes all other electrical equipment function correctly?Check the voltage and if necessary, wait for it to come back on
Damaged power supply Does all other elec. equipment function correctly?Repair by specialist firm
Wait time after switching on is too shortHave approx. 5 minutes elapsed since the restart?Schedule longer wait times
Temperature outside operating rangeAre the fans in the indoor unit and outdoor unit working correctly?Observe temperature ranges of indoor unit and outdoor unit
Electrical surges caused by thunderstormsHave there been lightning strikes in the area recently?Switch off the mains breaker and switch it back on. Have it inspected by a specialist
Malfunction of the external condensate pumpHas the pump shut down due to a malfunction?Check and if necessary clean the pump
High-pressure / low-pressure switches have triggeredCheck refrigerant pressure and look for leaks if necessaryRectify leakage and re-start
The unit does not respond to the remote controlTransmission distance too far / receiver affected by interferenceDoes the indoor unit beep when pressing a key?Reduce the distance to less than 6 m or change position
Defective remote control Is the unit running in manual mode?Replace the remote control
Receiver or transmitter unit exposed to excessive solar radiationDoes it function correctly in the shade?Place the receiver and/or transmitter unit in the shade
Electromagnetic fields are interfering with transmissionDoes it function after removing potential sources of interference?Signal is not transmitted when interference sources are operational
Key in remote control jammed / two buttons pressed at same timeDoes the “Transmitting” symbol appear on the display?Release the key / only press one key
Batteries in remote control are flatHave new batteries been inserted? Is the display incomplete?Insert new batteries
Malfunction Possible causesChecks Remedial measures
The unit is running but only provides reduced or no cooling or heating capacityFilter is dirty / air inlet / outlet opening is blocked by debrisHave the filters been cleaned?Clean the filters
Windows and doors open. Heating / cooling load has increasedHave structural / usage modifications been made?Close windows and doors / install additional units
Neither cooling nor heating mode has been setDoes the cooling symbol appear on the display?Correct the settings for the unit
Fins on outdoor unit blocked by foreign objectsIs the fan on the outdoor component running? Are the fins unobstructed?Check the fan or winter fan speed control, reduce the air resistance
Leaking cooling cycle Are there signs of frost on the exchanger fins of the indoor unit?Repair by specialist
Outdoor unit iced up Check outdoor unit. Has the cassette probe on the outdoor unit been correctly positioned?De-ice and fit the probe at the point where the most ice forms
Condensate discharge on unitDrainage pipe on collection container clogged / damagedCan the condensate drain off without any obstruction?Clean the drainage pipe and collection container
Faulty external condensate pump or floatIs the collection tray full of water and the pump not running?Call out a specialist to replace the pump
Condensate has not drained away and has collected in the condensate drainage lineIs there an incline on the condensate drainage line? Check there is no blockage in the pipe.Route the condensate drainage line with an incline and clean it.
Condensate does not drain offAre the condensate drainage lines unblocked and is there a steady incline? Are the condensate pump and liquid level switch functioning correctly?Route the condensate drainage line with an incline and clean it. If the liquid level switch or the condensate pump is defective, have them replaced
Float is stuck or jammed due to excessive dirtAre the LEDs on the receiver unit of the indoor unit flashing?Should be cleaned by specialist firm

REMKO RVD 525 DC - Troubleshooting and customer service - 1

NOTE

If the outdoor unit makes noises at low outside temperatures, even although it is switched off, this is not a malfunction. This is the winding of the compressor being run briefly in order to heat up the oil within it and also to guarantee the viscosity at low ambient temperatures. If you do not use the unit in the winter then you can switch off the breaker. Switch it back on again at least 12 hours before the next time that the unit will be required!

REMKO RVD series

Malfunction indicated by flashing code RVD 355-525 DC

Error descriptionNumber of flashes per second) 1)LED timer 2)Error code
EEPROM error, indoor unit 1 OFF E0
Communication error between indoor unit and outdoor unit 2 OFF E1
Evaporator fan motor speed control not OK 4 OFF E3
Room air temperature probe faulty 5 OFF E4
Evaporator temperature probe faulty 6 OFF E5
No cooling capacity after 30 minutes 7 OFF EC
Condensate pump liquid level switch triggered 8 OFF EE
Safety shut-down due to increased power consumption 1 ON F0
Outdoor unit air inlet temperature probe faulty 2 ON F1
Condenser outlet temperature probe faulty3 ON F2
Temperature probe for heat gas line faulty4 ON F3
EEPROM error, outdoor unit5 ON F4
Condenser fan speed control not OK6 ON F5
Suction pipe temperature probe in AT faulty7 ON F6
Fin motor defective or not connectedF7
Inverter error1FLASHESP0
Over/undervoltage error2FLASHESP1
Safety shut-down compressor excess temperature3FLASHESP2
Safety shut-down due to low outside temperature4FLASHESP3
Compressor control faulty5FLASHESP4
Mode conflict6FLASHESP5
Low pressure alarm7FLASHESP6

^1) LED [1] in the bottom figure
2) LED [2] in the bottom figure

Diagram showing labeled components of a device with numbered annotations

Fig. 52: Malfunction indicated by flashing code RVD 355-525 DC

Malfunction indicated by flashing code RVD 685-1055 DC

Error descriptionNumber of flashes per second) 1)LED timer 2)Error code 3)
EEPROM error, indoor unit 1 OFF E0
Communication error between indoor unit and outdoor unit 2 OFF E1
Evaporator fan motor speed control not OK 4 OFF E3
Room air temperature probe faulty 5 OFF E4
Evaporator temperature probe faulty 6 OFF E5
No cooling capacity after 30 minutes 7 OFF EC
Condensate pump liquid level switch triggered 8 OFF EE
Safety shut-down due to increased power consumption 1 ON F0
Outdoor unit air inlet temperature probe faulty 2 ON F1
Condenser outlet temperature probe faulty3 ON F2
Temperature probe for heat gas line faulty4 ON F3
EEPROM error, outdoor unit5 ON F4
Condenser fan speed control not OK6 ON F5
Temperature probe suction pipe in outdoor unit faulty7 ON F6
Fin motor defective or not connectedF7
Inverter error1FLASHESP0
Over/undervoltage error2FLASHESP1
Safety shut-down compressor excess temperature3FLASHESP2
Safety shut-down due to low outside temperature4FLASHESP3
Compressor control faulty5FLASHESP4
Mode conflict6FLASHESP5
Low pressure alarm7FLASHESP6

^1) LED [1] in the bottom figure

2) LED [2] in the bottom figure

^3) LED [3] in the bottom figure

① ② ③ FUNC

Fig. 53: Malfunction indicated by flashing code RVD 685-1055 DC

REMKO RVD series

12.2 Indoor unit fault analysis

Error code: E0 / F4
Reason: The control board of the outdoor unit or indoor unit cannot read the unit memory (EEPROM)
Cause:Installation errorControl boards of outdoor unit or indoor unit defective
Switch off voltage, switch on again 2 minutes later. Is the error still present?
REMKO RVD 525 DC - Indoor unit fault analysis - 1
Replace the circuit boards of the outdoor unit and indoor unit in turn, in order to locate the defective EEPROM
Error code: E1
Reason: The indoor unit does not receive a signal from the outdoor unit within 110 seconds.
Cause:Electrical connection not configured correctlyControl boards outdoor unit or indoor unit defective
Switch off voltage, switch on again 2 minutes later. Is the error still present?
REMKO RVD 525 DC - Indoor unit fault analysis - 2
Measure the voltage between the “S” and “N” terminals of the outdoor unit. Is the measured value positive?NO→Check electrical connections in the indoor unit.Are they OK?
REMKO RVD 525 DC - Indoor unit fault analysis - 3↓YES
Check electrical connections in the outdoor unit. Are they OK?Replace the control boards of the indoor unit. Is the fault remedied?
REMKO RVD 525 DC - Indoor unit fault analysis - 4↓NO
Is the transformer OK?Replace the control boards of the outdoor unit
NO→Replace the transformer
REMKO RVD 525 DC - Indoor unit fault analysis - 5
Replace the control boards of the outdoor unit.Is the fault remedied?
REMKO RVD 525 DC - Indoor unit fault analysis - 6
Replace the control boards of the indoor unit

REMKO RVD series

Error code: E3 / F5
Reason: If the fan speed of the indoor unit/outdoor unit falls below 300 rpm, the unit switches off and the display shows error code E3 or E5
Cause:Electrical connection faultyEvaporator fan wheel defectiveEvaporator fan motor defectiveControl board faulty
Switch off voltage, switch on again 2 minutes later. Is the error still present?REMKO RVD 525 DC - REMKO RVD series - 1The unit operates normally.
↓YES
De-energise the unit and attempt to turn the fan wheel by hand. Does it rotate freely?REMKO RVD 525 DC - REMKO RVD series - 2Check the motor and the fan wheel bearing, and replace the defective parts.
↓YES
Check the electrical connections.Are these correctly implemented?REMKO RVD 525 DC - REMKO RVD series - 3Correctly establish the electrical connection
↓YES
Measure the voltage at the corresponding connector plug on the control board (see section & 'Procedure' on page 57). Does the measured voltage lie within the tolerance range?REMKO RVD 525 DC - REMKO RVD series - 4Replace the control board.
↓YES
Replace the fan motor. Is the fault remedied?REMKO RVD 525 DC - REMKO RVD series - 5

Procedure

DC fan motor of the indoor unit (control chip is installed in the motor):

Switch on the voltage to the unit. In standby mode, measure the unit between terminals 1-3 and 4-3 of the connector plug. Check the measured values against those listed in the table below. If these differ, there is a problem with the control board and it must be replaced.

REMKO RVD 525 DC - Procedure - 1

natural_image Technical line drawing of a 13456 connector pinout (no text or symbols on the diagram itself)

Fig. 54: Motor measurements

Terminal Colour Voltage
1 Red 280V~380 V
2 --- ---
3 Black 0 V
4 White 17-17.5V
5 Yellow0~5.6V
6Blue17-17.5V

DC fan motor of the outdoor unit (control chip is installed in the motor):

Measure the resistance between terminals 1-3 and 4-3. This should be roughly identical. If the resistance deviates significantly, assume that the motor is defective and must be replaced.

REMKO RVD series

Error code: EC
Reason: The evaporator probe T2 measures the actual value with the compressor start and takes this as the reference value T_Start . If, 5 minutes after the compressor start, the value T_Start has not dropped by 2 °C for at least 4 seconds then the system assumes that the refrigerant is low. The measurement is performed a total of 3 times before the display shows the error code "EC".
Cause:Refrigerant low or cooling circuit blockedEvaporator probe T2 defectiveIndoor unit control board defective
Switch off voltage, switch on again 2 minutes later. Is the error still present?
REMKO RVD 525 DC - REMKO RVD series - 1
Check whether the indoor unit blows out cold air.YES→Check the position and function of the evaporator probe T2. Is it correctly seated and with the correct resistance?
REMKO RVD 525 DC - REMKO RVD series - 2↓YES
Check the cooling circuit for leaks. Leaks found?Exchange the control boards of the indoor unit.
YES→Remedy leaks and put the unit back into operation.
REMKO RVD 525 DC - REMKO RVD series - 3
Check the cooling circuit for any blockages. Are the shut-off valves on the outdoor unit open?
Error code: E4 / E5 / F1 / F2 / F3
Reason: If the test voltage of the probes is lower than 0.06 V or higher than 4.94 V then the display shows the error code of the corresponding probe.
Cause:Electrical connection faultyTemperature probe defectiveControl board defective
Check the connecting cable between the control board and the temperature probe. Is it OK and correctly connected?NO→Establish a proper connection.
↓YES
Check the probe for correct resistance, depending on the temperature (see resistance table)NO→Replace the probe.
↓YES
Replace the corresponding control board.

PILLIKE 178 DIGITAL MULTIMETER 09.10 Amm. Mangan HOLE RANGE REL Hz %

Fig. 55: Check the probes

REMKO RVD series

Error code: F0
Reason: Safety shutdown due to overly high current consumption of individual unit components
Cause:Faulty power supplyCooling circuit blockedFaulty control boardElectrical connections faultyCompressor defective
Check the supply voltage. Is this correct?NO→Switch the unit off and ensure correct supply voltage.
↓YES
Check the cooling circuit for any blockages. Is the cooling circuit OK?NO→Remove the blockage (shut-off valve open?)
↓YES
Check the winding resistances of the compressor. Are they OK?NO→Replace the compressor.
↓YES
Check the electrical connections. Are these correctly implemented?NO→Replace or correct the electrical connections.
↓YES
Does the transformer operate fault-free?NO→Replace the transformer or control boards of the outdoor unit.
↓YES
Replace the outdoor unit.
Error code: P0
Reason: If the power supply to the compressor controller is faulty, the display shows the error code “P0” and the unit switches off
Cause:External enabling contact openElectrical connection faultyFaulty control boardCondenser fan motor defective or blockedCompressor defective
Check the external enabling contact CN23 and the jumper JR6. Are both contacts open? (See Chapter 8.6 ‘Connection of a superordinate controller provided by the customer’ on page 47)YES→Close the external enabling contact CN23 or the jumper JR6.
↓NO
Check the connecting cables between the control board and compressor? Are they faulty?YES→Establish a correct connection between the control board and compressor.
↓NO
Check the inverter controller (see section ‘‘Check the inverter controller’ on page 62). Fault eliminated?NO→Replace the control board.
↓YES
Check the condenser fan motor. Is it working correctly?NO→See troubleshooting fault F5
↓YES
Check the winding resistances of the compressor. Are they OK?NO→Replace the compressor.
↓YES
Exchange the control boards of the outdoor unit.

REMKO RVD series

Check the inverter controller

Switch off the power supply to the unit. Wait until the capacitors are fully discharged and disconnect the compressor from the control board.

Check the resistances at the outputs of the control board with the aid of a digital voltmeter as follows:

Voltmeter Normal resistance
(+) Red (-) Black
UN∞(multiple MΩ)
V
W
(+) Red
Error code: P1
Reason: Overvoltage or undervoltage protection has tripped
Cause:■ Faulty supply voltage■ Refrigerant low or cooling circuit blocked■ Faulty control board
Check the power supply. Is the supply voltage correct?NO→Switch the unit off and have the power supply checked/corrected.
↓YES
Check the electrical connections. Are they OK?NO→Replace the electrical connections.
↓YES
Switch the power on and put the unit into standby mode. Measure the voltage on the board, at contacts "P" and "N". This should be approx. 310 V, 340 V or 380 V DC. Now start the unit. The voltage between "P" and "N" should now be between 220-400V. Is the correct voltage applied?NO→Replace the control board.
↓YES
Check the transformer. Is a defect present?NO→Replace the control board.
↓YES
Replace the transformer.
Error code: P2 (with units with a thermal contact)
Reason: If the test voltage of the thermal contact does not lie at 5 V, then the display shows the error message “P2”
Cause:Faulty supply voltageRefrigerant low or cooling circuit blockedFaulty control board
Check the air flow volumes of the indoor unit and outdoor unit. Are they blocked or dirty?REMKO RVD 525 DC - REMKO RVD series - 1Clean the filter or heat exchanger and ensure a sufficient air flow volume.
REMKO RVD 525 DC - REMKO RVD series - 2
Switch off the power supply to the unit and switch it on again after 10 mins.Does the unit start up?
REMKO RVD 525 DC - REMKO RVD series - 3
Check the temperature of the compressor. Has it heated up?NO→Check the thermal contact. Is it correctly connected?
↓YES↓NO
Measure the resistance of the thermal contact.Is it 0?Connect it correctly.
REMKO RVD 525 DC - REMKO RVD series - 4↓YESNO→
Check the cooling circuit. Is it OK?REMKO RVD 525 DC - REMKO RVD series - 5Replace the control board of the outdoor unit.

REMKO RVD series

Error code: P4
Reason: Safety shutdown of inverter controller. Internal system monitoring triggered (e.g. communication problem between board and compressor, the compressor speed is not OK)
Cause:■ Faulty electrical connections■ Inverter regulation on board defective■ Condenser fan motor defective■ Compressor defective■ Control board defective
Check the electrical connection between the control board and compressor. Are these correctly implemented?YES→Establish a proper connection.
↓NO
Check the inverter controller. Is this functional?NO→Replace the control board.
↓YES
Check the condenser fan motor. Is it OK?NO→Follow the instructions for troubleshooting fault F5
↓YES
Check the winding resistances of the compressor. Are they OK?NO→Replace the compressor
↓YES
Replace the control boards of the outdoor unit.

Check individual components

Check the temperature probes

Disconnect the temperature probe from the control board and measure the resistance on the plug's contacts.

① Ω

1: Multimeter

Error code: dF
Reason: The unit is in heating mode and the outdoor unit is being defrosted. After the defrost phase, the indoor unit automatically switches back to the last operating mode.

12.3 Resistances of the temperature probes

Probe T1, T2, T3 and T4

Temp. (°C)Resistance (kΩ)Temp. (°C)Resistance (kΩ)
-20 115.27 12 18.72
-19 108.15 13 17.80
-18 101.52 14 16.93
-17 96.34 15 16.12
-16 89.59 16 15.34
-15 84.22 17 14.62
-14 79.31 18 13.92
-13 74.54 19 13.26
-12 70.17 20 12.64
-11 66.09 21 12.06
-10 62.28 22 11.50
-9 58.71 23 10.97
-8 56.37 24 10.47
-7 52.24 25 10.00
-6 49.32 26 9.55
-5 46.57 27 9.12
-4 44.00 28 8.72
-3 41.59 29 8.34
-2 39.82 30 7.97
-1 37.20 31 7.62
0 35.20 32 7.29
1 33.33 33 6.98
2 31.56 34 6.68
3 29.91 35 6.40
4 28.35 36 6.13
5 26.88 37 5.87
6 25.50 38 5.63
7 24.19 39 5.40
8 22.57 40 5.18
9 21.81 41 4.96
10 20.72 42 4.76
11 19.69 43 4.57
Temp. (°C)Resistance (kΩ)Temp. (°C)Resistance (kΩ)
44 4.3979 1.21
45 4.2180 1.17
46 4.0581 1.14
47 3.8982 1.10
48 3.7383 1.06
49 3.5984 1.03
50 3.4585 1.00
51 3.3286 0.97
52 3.1987 0.94
53 3.0788 0.91
54 2.9689 0.88
55 2.8490 0.85
56 2.7491 0.83
57 2.6492 0.80
58 2.5493 0.78
59 2.4594 0.75
60 2.3695 0.73
61 2.2796 0.71
62 2.1997 0.69
63 2.1198 0.67
64 2.0499 0.65
65 1.97100 0.63
66 1.90101 0.61
67 1.83102 0.59
68 1.77103 0.58
69 1.71104 0.56
70 1.65105 0.54
71 1.59106 0.53
72 1.54107 0.51
73 1.48108 0.50
74 1.43109 0.48
75 1.39110 0.47
76 1.34111 0.46
77 1.29112 0.45
78 1.25113 0.43

REMKO RVD series

Temp. (°C)Resistance (kΩ)Temp. (°C)Resistance (kΩ)
114 0.42127 0.30
115 0.41128 0.29
116 0.40129 0.28
117 0.39130 0.28
118 0.38131 0.27
119 0.37132 0.26
120 0.36133 0.26
121 0.35134 0.25
122 0.34135 0.25
123 0.33136 0.24
124 0.32137 0.23
125 0.32138 0.23
126 0.31139 0.22

Probe T5

Temp. (°C)Resistance (kΩ)Temp. (°C)Resistance (kΩ)
-20 542.7 -2 200.7
-19 511.9 -1 190.5
-18 483.0 0 180.9
-17 455.9 1 171.9
-16 430.5 2 163.3
-15 406.7 3 155.2
-14 384.3 4 147.6
-13 363.3 5 140.4
-12 343.6 6 133.5
-11 325.1 7 127.1
-10 307.7 8 121.0
-9 291.3 9 115.2
-8 275.9 10 109.8
-7 261.4 11 104.6
-6 247.8 12 99.69
-5 234.9 13 95.05
-4 222.8 14 90.66
-3 211.4 15 86.49
Temp. (°C)Resistance (kΩ)Temp. (°C)Resistance (kΩ)
16 82.54 51 18.96
17 78.79 52 18.26
18 75.24 53 17.58
19 71.86 54 16.94
20 68.66 55 16.32
21 65.62 56 15.73
22 62.73 57 15.16
23 59.98 58 14.62
24 57.37 59 14.09
25 54.89 60 13.59
26 52.53 61 13.11
27 50.28 62 12.65
28 48.14 63 12.21
29 46.11 64 11.79
30 44.17 65 11.38
31 42.33 66 10.99
32 40.57 67 10.61
33 38.89 68 10.25
34 37.30 69 9.90
35 35.78 70 9.57
36 34.32 71 9.25
37 32.94 72 8.94
38 31.62 73 8.64
39 30.36 74 8.36
40 29.15 75 8.08
41 28.00 76 7.82
42 26.90 77 7.57
43 25.86 78 7.32
44 24.85 79 7.09
45 23.89 80 6.86
46 22.89 81 6.64
47 22.10 82 6.43
48 21.26 83 6.23
49 20.46 84 6.03
50 19.69 85 5.84
86 5.66109 2.86
87 5.49110 2.78
88 5.32111 2.70
89 5.16112 2.63
90 5.00113 2.56
91 4.85114 2.49
92 4.70115 2.42
93 4.56116 2.36
94 4.43117 2.29
95 4.29118 2.23
96 4.17119 2.17
97 4.05120 2.12
98 3.93121 2.06
99 3.81122 2.01
100 3.70123 1.96
101 3.60124 1.91
102 3.49125 1.86
103 3.39126 1.81
104 3.30127 1.76
105 3.20128 1.72
106 3.11129 1.67
107 3.03130 1.63
108 2.94

REMKO RVD series

13 Care and maintenance

Regular care and observation of some basic points will ensure trouble-free operation and a long service life.

REMKO RVD 525 DC - Care and maintenance - 1

DANGER!

Prior to performing any work, ensure the equipment is disconnected from the voltage supply and secured to prevent accidental switch-on!

REMKO RVD 525 DC - DANGER! - 1

Contact Remko GmbH & Co. KG to sign up for a maintenance contract

Care

- Ensure that the indoor unit and outdoor unit are free of dirt, mould and other deposits.

Only clean the units with a damp cloth. Do not use any caustic, abrasive or solvent-based cleaning products. Do not use a jet of water.
- Clean the fins on the indoor unit and outdoor unit prior to long shutdown periods.

Maintenance

It is recommended that you take out a maintenance contract with an annual service from an appropriate specialist firm.
For systems which operate year-round (e.g. in server rooms), the maintenance intervals must be reduced accordingly.

REMKO RVD 525 DC - Maintenance - 1

This enables you to ensure the operational reliability of the plant at all times!

Type of task Checks / maintenance / inspectionCommis-sioningMonthly Half-yearlyYearly
General
Check voltage and current
Check function of compressor / fans
Dirt on condenser / evaporator
Check the refrigerant volume
Check condensate drainage
Check insulation
Check moving parts
Sealing test for cooling cycle●1)

1) see note below

Cleaning the cover on the indoor unit

  1. Disconnect the power supply to the unit.
  2. Open and fold down the air inlet guard on the cover. The filter is held in place by the flaps screwed in at the side of the guard (Fig. 56).
  3. Clean the grill and cover with a soft, damp cloth.
  4. Switch the power supply back on.

Air filter for indoor unit

We recommend cleaning the air filter at intervals of no more than 2 weeks. Reduce this interval if the air is especially dirty.

REMKO RVD 525 DC - Air filter for indoor unit - 1

NOTICE!

Statutory regulations require an annual leak test for the cooling cycle dependant on the refrigerant quantity. Inspection and documentation of the work performed is to be carried out by specialist technicians.

Cleaning the filter

  1. Disconnect the power supply to the unit.
  2. Open and fold down the air inlet guard on the cover. The filter is held in place by the flaps screwed in at the side of the guard (Fig. 56).
  3. T ilt the filter and lift it out (Fig. 56).
  4. Clean the filter with a commercially available vacuum cleaner (Fig. 57). To do so, turn the dirty side so it is facing upwards.
  5. Dirt can also be removed by carefully cleaning with lukewarm water and mild cleaning agents. The dirty side should be face down (Fig. 58).
  6. If water is used, let the filter dry out properly in the air before fitting it back into the unit.
  7. Carefully insert the filter . Ensure that it locates correctly.
  8. Close the cover as described above but in reverse order.
  9. Switch the power supply back on.
  10. Switch the unit back on.

Cleaning the condensate pump

The indoor unit includes a built-in condensate pump for pumping the condensate to a drain at a higher level.

The pump is more or less maintenance-free. The condensate drainage lines should be checked for dirt at regular intervals. Clean them as required.

If an external pump is also used, observe the maintenance and care instructions in the separate operating instructions.

REMKO RVD 525 DC - Cleaning the condensate pump - 1

natural_image 3D rendering of a square metal enclosure with internal grid structure (no text or symbols)

Fig. 56: Pull out the filter

REMKO RVD 525 DC - Cleaning the condensate pump - 2

natural_image Illustration of a pen tip touching a grid-patterned surface (no text or symbols)

Fig. 57: Cleaning with a vacuum cleaner

REMKO RVD 525 DC - Cleaning the condensate pump - 3

natural_image 3D rendering of a metal pipe inserted into a grid-patterned surface (no text or symbols visible)

Fig. 58: Cleaning with lukewarm water

REMKO RVD series

14 Exploded view and spare parts lists

14.1 Exploded view - Indoor unit RVD 355-525 DC

Exploded view diagram of a device with numbered parts, showing internal components and assembly steps

Fig. 59: Exploded view of the unit RVD 355-525 DC IT
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.

14.2 Spare parts list - Indoor unit RVD 355-525 DC

REMKO RVD 525 DC - Spare parts list - Indoor unit RVD 355-525 DC - 1

IMPORTANT!

To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)

No. Designation

1 Infrared remote control
2 Condensate pump liquid level switch
3 Condensate pump
4 Condensate pump mounting plate
5 Condensate hose
6 Condensate connection
7 Unit trim
8 Display board
9 Condensate tray
10 Temperature probe, evaporator
11 Evaporator
12 Evaporator housing
13 Unit housing
14 Terminal block cover
15 Control board
16 Temperature probe, indoor air
17 Air inlet nozzle
18 Fan wheel
19 Fan motor
20 Fan motor mounting plate

REMKO RVD series

14.3 Exploded view - Indoor unit RVD 685-1055 DC

Exploded view diagram of a device with numbered components for identification

Fig. 60: Exploded view of the unit RVD 685-1055 DC IT

We reserve the right to modify the dimensions and design as part of the ongoing technical development process.

14.4 Spare parts list - Indoor unit RVD 685-1055 DC

REMKO RVD 525 DC - Spare parts list - Indoor unit RVD 685-1055 DC - 1

IMPORTANT!

To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)

No. Designation

1 Infrared remote control
2 Condensate pump liquid level switch
3 Condensate pump
4 Condensate pump mounting plate
5 Condensate hose
6 Condensate connection
7 Unit trim
8 Display board
9 Air filter
10 Liquid level switch mounting plate
11 Condensate tray
12 Evaporator
13 Casing part, left
14 Unit housing
15 Casing part, front
16 Temperature probe, indoor air
17 Condensate tray sealing cap
18 Temperature probe, evaporator
19 Casing part, rear
20 Casing part, right
21 Control board
22 Transformer
23 Air inlet nozzle
24 Fan wheel
25 Fan motor
26 Housing floor

REMKO RVD series

15 Exploded view - Outdoor unit RVD 355 DC
Exploded view diagram of a household air conditioner system with numbered components

Fig. 61: Exploded view of the unit RVD 355 DC AT

We reserve the right to modify the dimensions and design as part of the ongoing technical development process.

16 Spare parts list - Outdoor unit RVD 355 DC

REMKO RVD 525 DC - Spare parts list - Outdoor unit RVD 355 DC - 1

IMPORTANT!

To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)

No. Designation

1 Cover panel
2 Protection grid, front wall
3 Front panel
4 Fan blade
5 Fan motor
6 Fan motor mounting plate
7 Corner panel, left
8 Condenser
9 Air inlet temperature probe
10 Electronic injection valve
11 Shut-off valve, injection pipe
12 4-way reversing valve
13 Shut-off valve, suction pipe
14 Partitioning panel
15 Temperature probe for heat gas line
16 Compressor
17 Floor panel
18 Side panel, right
19 Refrigerant connections cover
20 Terminal block cover
21 Control board
22 Temperature probe for condenser outlet
23 Condensate tray heating
24 Crankcase heating
25 Mounting plate for refrigerant connections

REMKO RVD series

17 Exploded view - Outdoor unit RVD 525 DC
Exploded view diagram of a household air conditioner unit with numbered parts for identification

Fig. 62: Exploded view of the unit RVD 525 DC AT

We reserve the right to modify the dimensions and design as part of the ongoing technical development process.

18 Spare parts list - Outdoor unit RVD 525 DC

REMKO RVD 525 DC - Spare parts list - Outdoor unit RVD 525 DC - 1

IMPORTANT!

To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)

No. Designation

1 Cover panel
2 Protection grid, front wall
3 Front panel
4 Fan blade
5 Fan motor
6 Fan motor mounting plate
7 Corner panel, left
8 Condenser
9 Air inlet temperature probe
10 Electronic injection valve
11 Shut-off valve, injection pipe
12 4-way reversing valve
13 Shut-off valve, suction pipe
14 Partitioning panel
15 Temperature probe for heat gas line
16 Compressor
17 Floor panel
18 Side panel, right
19 Refrigerant connections cover
20 Control board
21 Auxiliary circuit board
22 Temperature probe for condenser outlet
23 Condensate tray heating
24 Crankcase heating

REMKO RVD series

19 Exploded view - Outdoor unit RVD 685 DC
Exploded view diagram of a device with numbered components for identification

Fig. 63: Exploded view of the unit RVD 685 DC AT

We reserve the right to modify the dimensions and design as part of the ongoing technical development process.

20 Spare parts list - Outdoor unit RVD 685 DC

REMKO RVD 525 DC - Spare parts list - Outdoor unit RVD 685 DC - 1

IMPORTANT!

To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)

No. Designation

1 Cover panel
2 Protection grid, front wall
3 Front panel
4 Fan blade
5 Fan motor
6 Fan motor mounting plate
7 Corner panel, left
8 Condenser
9 Air inlet temperature probe
10 Electronic injection valve
11 Shut-off valve, injection pipe
12 4-way reversing valve
13 Shut-off valve, suction pipe
14 Partitioning panel
15 Temperature probe for heat gas line
16 Compressor
17 Floor panel
18 Side panel, right
19 Refrigerant connections cover
20 Terminal block cover
21 Control board
22 Inverter board
23 Cooling fins
24 Temperature probe for condenser outlet
25 Mounting plate for refrigerant connections
26 Transformer
27 Condensate tray heating
28 Crankcase heating

REMKO RVD series

21 Exploded view - Outdoor unit RVD 1055 DC
Exploded view diagram of household appliances with numbered parts for identification

Fig. 64: Exploded view of the unit RVD 1055 DC AT

We reserve the right to modify the dimensions and design as part of the ongoing technical development process.

22 Spare parts list - Outdoor unit RVD 1055 DC

REMKO RVD 525 DC - Spare parts list - Outdoor unit RVD 1055 DC - 1

IMPORTANT!

To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)

No. Designation

1 Cover panel
2 Protection grid, front wall
3 Front panel
4 Fan blade
5 Fan motor
6 Fan motor mounting plate
7 Side panel, left
8 Recessed grip side panel, left
9 Condenser
10 Temperature probe for condenser outlet
11 Temperature probe for heat gas line
12 Air inlet temperature probe
13 4-way reversing valve
14 Shut-off valve, suction pipe
15 Inverter board
16 Control board
17 Liquid separator
18 Transformer
19 Side panel, right
20 Terminal block cover
21 Shut-off valve cover
22 Recessed grip front panel, right
23 Front panel, right
24 Low pressure switch
25 Electronic injection valve
26 Shut-off valve, injection pipe
27 High pressure switch
28 Compressor
29 Partitioning panel
30 Floor panel

REMKO RVD series

No. Designation

31 Shut-off valve mounting plate
32 Condensate tray heating
33 Crankcase heating

23 Index

C

Care and maintenance 68

Cleaning

Air filter for indoor unit 68

Condensate pump 69

Cover on the indoor unit 68

Condensate drainage connection 31

Customer service 50

D

Display on indoor unit 16

Disposal of equipment 8

E

Electrical drawings ..... 39, 41, 43, 44, 45, 46

Electrical wiring 33

Electrical wiring diagram ..... 35, 36, 37, 38

Environmental protection 8

Exploded view of the unit . . . 70, 72, 74, 76, 78, 80

F

Flashing code, fault display 52, 53

Fresh air connection 27

Fresh air inlet 28

Function test of the cooling and heating modes 49

Functional checks 48

|

Infrared remote control 15

Installation location, selection 24

Installation materials 23

Intended use 7

K

Keys on the remote control 17

M

Maintenance 68

Malfunction indicated by flashing code .... 52, 53

Malfunctions

Checks 50

Possible causes 50

Remedial measures 50

Manual mode 15

Minimum clearances 25

0

Oil return measures 26

Ordering spare parts ..... 71, 73, 75, 77, 79, 81

R

Remote control Keys 17

Resistances Temperature probes 65

S

Safe drainage in the event of leakages ..... 31

Safety

Dangers of failure to observe the safety notes 5

General 5

Identification of notes 5

Instructions for the operator 6

Note for inspection work 6

Note for installation work 6

Note for maintenance work 6

Personnel qualifications 5

Safety-conscious working 6

Unauthorised modification 7

Unauthorised replacement part manufacture . 7

Selection of installation location 24

Setting of

Address assignment MCC-1 ..... 40, 42

Anti-cold air function 40, 42

Automatic restart after power failure . . . . 40, 42

DIP switch 40, 42

Fan behaviour without demand ..... 40, 42

Main / slave 42

Mode priority 40

Power 42

Temperature compensation ..... 40, 42

Shutdown

Permanent 49

Temporary 49

Spare parts list ..... 71, 73, 75, 77, 79, 81

Superordinate controller, connection ..... 47

T

Temperature probes Resistances 65

Test run 48

Troubleshooting and customer service ..... 50

U

Unit installation 26

W

Wall opening 23

Warranty 7

Wired remote control 16

REMKO QUALITY WITH SYSTEMS

Air-Conditioning | Heating | New Energies

REMKO GmbH & Co. KG

Hotline within Germany

+49 (0) 5232 6 06-0

Hotline International

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : REMKO

Model : RVD 525 DC

Category : Air conditioner