RVD 525 DC - Air conditioner REMKO - Free user manual and instructions
Find the device manual for free RVD 525 DC REMKO in PDF.
| Product Type | Ceiling cassette air conditioner (cooling and heating) |
| Model | RVD 525 DC (indoor unit RVD 525 DC IT, outdoor unit RVD 525 DC AT) |
| Nominal Cooling Capacity (kW) | 5.3 (range 2.9 - 5.7) |
| Nominal Heating Capacity (kW) | 4.2 (range 2.4 - 6.1) |
| Energy Efficiency Ratio (SEER) | 6.1 |
| SCOP (Heating) | 4.0 |
| Power Supply | 230 V / 1 Ph / 50 Hz |
| Indoor Unit Dimensions (L x W x D) mm | 570 x 570 x 260 |
| Indoor Unit Weight (kg) | 18.7 |
| Outdoor Unit Dimensions (H x W x D) mm | 702 x 845 x 363 |
| Outdoor Unit Weight (kg) | 33.7 |
| Refrigerant Type / Quantity | R32 / 1.15 kg (basic fill) |
| CO2 Equivalent (t) | 0.78 |
| Sound Pressure Level Indoor (dB(A)) | 36 / 39 / 43 (low / medium / high) |
| Air Flow Volume Indoor (m³/h) | 540 / 625 / 750 (low / medium / high) |
| Operating Range Cooling (°C) | +5 to +50 (up to -15 with winter kit) |
| Operating Range Heating (°C) | +5 to +24 (up to -15 with winter kit) |
| Condensate Pump Max Head (mm WS) | 500 |
| Functions | Inverter technology, auto mode, cooling, heating, dehumidification, fan only, turbo, sleep, timer (on/off), follow me, swing, self-clean (optional) |
| Control | Infrared remote control (included); optional wired remote control |
| Filter Cleaning Interval | Every 2 weeks (recommended) |
| Annual Maintenance | Recommended by specialist |
| Safety Notes | Flammable refrigerant R32; ensure room area >4 m²; install by qualified personnel only |
| Accessories | Floor console, wall bracket, winter fan speed control, fresh air kit (optional) |
Frequently Asked Questions - RVD 525 DC REMKO
User questions about RVD 525 DC REMKO
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Air conditioner in PDF format for free! Find your manual RVD 525 DC - REMKO and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. RVD 525 DC by REMKO.
USER MANUAL RVD 525 DC REMKO
Operating and installation instructions
REMKO RVD series
Ceiling cassettes for cooling and heating
RVD 355 DC, RVD 525 DC, RVD 685 DC, RVD 1055 DC

natural_image
Close-up of a white air vent grille with ventilation grilles (no text or symbols visible)Read these operating instructions carefully before commissioning / using this device!
These instructions are an integral part of the system and must always be kept near or on the device.
Subject to modifications; No liability accepted for errors or misprints!
Translation of the original
Table of contents
1 Safety and usage instructions.... 5
1.1 General safety notes.... 5
1.2 Identification of notes.... 5
1.3 Personnel qualifications.... 5
1.4 Dangers of failure to observe the safety notes.... 5
1.5 Safety-conscious working.... 6
1.6 Safety instructions for the operator.... 6
1.7 Safety notes for installation, maintenance and inspection 6
1.8 Unauthorised modification and changes.... 7
1.9 Intended use.... 7
1.10 Warranty....7
1.11 Transport and packaging....7
1.12 Environmental protection and recycling.... 8
2 Technical data.... 9
2.1 Unit data....9
2.2 Unit dimensions, outdoor unit.... 12
2.3 Unit dimensions, indoor unit.... 13
3 Design and function.... 14
3.1 Unit description.... 14
4 Operation.... 15
4.1 General notes.... 15
4.2 Display on indoor unit.... 16
4.3 Keys on the remote control.... 17
5 Installation instructions for qualified personnel.... 23
5.1 Important notes prior to installation.... 23
5.2 Wall openings.... 23
5.3 Installation materials.... 23
5.4 Selection of installation location 24
5.5 Minimum clearances.... 25
5.6 Oil return measures.... 26
6 Installation.... 26
6.1 Unit installation.... 26
6.2 Connection of refrigerant piping.... 28
6.3 Leak testing.... 30
6.4 Adding refrigerant.... 31
7 Condensate drainage connection and safe drainage.... 31
8 Electrical wiring.... 33
8.1 General connection and safety instructions.... 33
8.2 Connecting the indoor unit.... 33
8.3 Outdoor unit connection.... 34
8.4 Electrical wiring diagram.... 35
8.5 Electrical drawings.... 39
8.6 Connection of a superordinate controller provided by the customer 47
9 Before commissioning.... 48
10 Commissioning.... 48
11 Shutdown......49
REMKO RVD series
12 Troubleshooting, customer service and fault analysis.... 50
12.1 Troubleshooting and customer service.... 50
12.2 Indoor unit fault analysis.... 54
12.3 Resistances of the temperature probes.... 65
13 Care and maintenance.... 68
14 Exploded view and spare parts lists.... 70
14.1 Exploded view - Indoor unit RVD 355-525 DC 70
14.2 Spare parts list - Indoor unit RVD 355-525 DC.... 71
14.3 Exploded view - Indoor unit RVD 685-1055 DC 72
14.4 Spare parts list - Indoor unit RVD 685-1055 DC.... 73
15 Exploded view - Outdoor unit RVD 355 DC....74
16 Spare parts list - Outdoor unit RVD 355 DC.... 75
17 Exploded view - Outdoor unit RVD 525 DC.... 76
18 Spare parts list - Outdoor unit RVD 525 DC.... 77
19 Exploded view - Outdoor unit RVD 685 DC.... 78
20 Spare parts list - Outdoor unit RVD 685 DC.... 79
21 Exploded view - Outdoor unit RVD 1055 DC....80
22 Spare parts list - Outdoor unit RVD 1055 DC....81
23 Index....83
1 Safety and usage instructions
1.1 General safety notes
Carefully read the operating manual before commissioning the units or their components for the first time. It provides useful tips and notes such as hazard warnings to prevent injury and material damage. Failure to follow the directions in this manual can endanger persons, the environment and the equipment itself or its components and will void any claims for liability.
Store this manual and the information required for the operation of this system (e.g. refrigerant data-sheet) in the vicinity of the unit.
The refrigerant used in the system is flammable. If applicable, observe the local safety conditions.

Warning of inflammable substances!
1.2 Identification of notes
This section provides an overview of all important safety aspects for proper protection of people and safe and fault-free operation. The instructions and safety notes contained within this manual must be observed in order to prevent accidents, personal injury and material damage.
Notes attached directly to the units must be observed in their entirety and be kept in a fully legible condition.
Safety notes in this manual are indicated by symbols. Safety notes are introduced with signal words which help to highlight the magnitude of the danger in question.

DANGER!
Contact with live parts poses an immediate danger of death due to electric shock. Damage to the insulation or individual components may pose a danger of death.

DANGER!
This combination of symbol and signal word warns of a situation in which there is immediate danger, which if not avoided may be fatal or cause serious injury.

WARNING!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may be fatal or cause serious injury.

CAUTION!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause injury or material and environmental damage.

NOTICE!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause material and environmental damage.

This symbol highlights useful tips and recommendations as well as information for efficient and fault-free operation.
1.3 Personnel qualifications
Personnel responsible for commissioning, operation, maintenance, inspection and installation must be able to demonstrate that they hold a qualification which proves their ability to undertake the work.
1.4 Dangers of failure to observe the safety notes
Failure to observe the safety notes may pose a risk to people, the environment and the units. Failure to observe the safety notes may void any claims for damages.
REMKO RVD series
In particular, failure to observe the safety notes may pose the following risks:
The failure of important unit functions.
The failure of prescribed methods of maintenance and repair.
- Danger to people on account of electrical and mechanical effects.
1.5 Safety-conscious working
The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.
1.6 Safety instructions for the operator
The operational safety of the units and components is only assured providing they are used as intended and in a fully assembled state.
The units and components may only be set up, installed and maintained by qualified personnel.
- Protective covers (grills) over moving parts must not be removed from units that are in operation.
- Do not operate units or components with obvious defects or signs of damage.
- Contact with equipment parts or components can lead to burns or injury.
The units and components must not be exposed to any mechanical load, extreme levels of humidity or extreme temperatures.
Rooms in which refrigerant may escape shall be adequately aerated and ventilated. Otherwise, a risk of suffocation or fire exists.
- Do not leave children unsupervised when close to the system.
Commissioning must be performed by authorised specialists exclusively. Deficient commissioning may lead to water leaks, electric shocks or fire. Commissioning must take place as described in the user manual.
- Only instruct authorised specialist personnel to perform maintenance or servicing.
The system is filled with a flammable refrigerant. Never thaw any frozen unit components independently!
Do not operate any further devices that produce high heat or naked flames in the same room.
All housing parts and unit openings, e.g. air inlets and outlets, must be kept clear.
The units must be inspected by a service technician to ensure that they are safe to use and fully functional at least once yearly. Visual inspections and cleaning may be performed by the operator when the units are disconnected from the mains.
1.7 Safety notes for installation, maintenance and inspection
The refrigerant R32 used in the system is flammable. If applicable, observe the local safety conditions.
- Keep the cooling circuit clear of other gases and foreign substances. Only fill the cooling circuit with the refrigerant R32.
Only use the accessories, components and appropriately marked parts provided. The use of non-standardised components may result in water leaks, electric shocks and fire.
Only install and store the units in rooms larger than 4 m^2 . With a failure to comply, leaks may result in the room filling with a flammable mixture!
The minimum room size of 4 m^2 required for installation and storage pertains to the basic fill quantity of the unit. This varies according to the installation type and total fill quantity of the system. The calculation must take place in accordance with valid DIN standards. Make sure that the installation site is suitable for safe unit operation.
- Only mount the unit components on structurally suitable brickwork.
The units must not be installed in rooms in which further devices that produce heat are operated (heaters, open hearths).
■ Make sure the installation room is sufficiently ventilated.
Interventions in the cooling circuit are only possible after completely draining the refrigerant. Never solder or grind unit components!
Note that refrigerant may be odourless.
- Never operate the air conditioning unit in a humid room, such as a bathroom or laundry room. If the humidity is too high, this can cause short circuits on electrical parts.
The product must be correctly earthed at all times, otherwise it may induce electric shocks.
- Attach the condensate drain as described in the operating manual. The inadequate drainage of condensate can lead to water damage in your apartment.
All persons who intervene in the cooling circuit must hold a valid certificate from the chamber of industry and commerce, which confirms their ability to work with refrigerant.
■ Appropriate hazard prevention measures must be taken to prevent risks to people when performing installation, repair, maintenance or cleaning work on the units.
The setup, connection and operation of the units and its components must be undertaken in accordance with the usage and operating conditions stipulated in this manual and comply with all applicable regional regulations.
■ Regional regulations and laws as well as the Water Ecology Act must be observed.
The power supply should be adapted to the requirements of the units.
Units may only be mounted at the points provided for this purpose at the factory. The units may only be secured or mounted on stable structures, walls or floors.
The units and components should not be operated in areas where there is a heightened risk of damage. Observe the minimum clearances.
The units and components must be kept at an adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
■ Safety devices may not be modified or bypassed.
The connection of the indoor unit must be established as a permanent connection; a detachable, reusable connection is not permissible.
1.8 Unauthorised modification and changes
Modifications or changes to units and components are not permitted and may cause malfunctions. Safety devices may not be modified or bypassed. Original replacement parts and accessories authorised by the manufactured ensure safety. The use of other parts may invalidate liability for resulting consequences.
1.9 Intended use
Depending on the model, the units and the additional fittings with which they are equipped are only intended to be used as an air-conditioner for the purpose of cooling or heating the air in an enclosed space.
Any different or additional use is a non-intended use. The manufacturer/supplier assumes no liability for damages arising from a non-intended use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.
The threshold values specified in the technical data must not be exceeded.
1.10 Warranty
For warranty claims to be considered, it is essential that the ordering party or its representative complete and return the "certificate of warranty" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The warranty conditions are detailed in the "General business and delivery conditions". Furthermore, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.
1.11 Transport and packaging
The devices are supplied in a sturdy shipping container. Please check the equipment immediately upon delivery and note any damage or missing parts on the delivery and inform the shipper and your contractual partner. For later complaints can not be guaranteed.

WARNING!
Plastic films and bags etc. are dangerous toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to children!
REMKO RVD series
1.12 Environmental protection and recycling
Disposal of packaging
All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved collection points.

Disposal of equipment and components
Only recyclable materials are used in the manufacture of the devices and components. Help protect the environment by ensuring that the devices or components (for example batteries) are not disposed in household waste, but only in accordance with local regulations and in an environmentally safe manner, e.g. using certified firms and recycling specialists or at collection points.

2 Technical data
2.1 Unit data
| Series RVD 355 DC RVD 525 DC RVD 685 DC RVD 1055 DC | |||||
| Operating mode | Inverter ceiling cassette-room air conditioner combination for cooling and heating | ||||
| Nominal cooling output1) | kW | 3.5(1.5-5.3) | 5.3(2.9-5.7) | 7.0(3.2-8.2) | 10.5(4.0-12.0) |
| Energy efficiency ratio SEER1) | 7.8 | 6.1 | |||
| Rated power consumption, elec-trical cooling1) | kW | 0.85 | 1.63 | 2.19 | 3.95 |
| Rated elec. curr. consump., cooling1) | A | 3.8 | 7.2 | 9.5 | 6.6 |
| Power consumption, annual, QCE3) | kWh | 157 | 304 | 402 | 602 |
| Energy efficiency ratio, cooling1) | A++ | ||||
| Nominal heat capacity2) | kW | 3.1(1.0-5.6) | 4.2(2.4-6.1) | 5.4(2.4-8.7) | 8.1(2.6-13.2) |
| Energy efficiency ratio SCOP4) | 4.6 | 4.0 | |||
| Rated power consumption, elec-trical heating2) | kW | 1.10 | 1.46 | 2.05 | 3.00 |
| Rated elec. curr. consump., heating2) | A | 5.0 | 6.4 | 8.9 | 5.0 |
| Power consumption, annual, QHE3) | kWh | 959 | 1435 | 1890 | 2835 |
| Energy efficiency ratio, heating2) | A++ | A+ | |||
| Max. power consumption | kW | 1.8 | 1.9 | 2.9 | 4.8 |
| Max. current consumption | A | 7.9 | 8.5 | 12.5 | |
| EDP no. | 1623845 | 1623855 | 1623865 | ||
1) Air inlet temp. TK 27 °C/FK 19 °C, outside temperature TK 35 °C, FK 24 °C, max. air flow volume, 5 m pipe length
2) Air inlet temp. TK 20 °C, outside temperature TK 7 °C, FK 6 °C, max. air flow volume, 5 m pipe length
3) The specified value is based on results from standard testing. The actual consumption depends on the use and location of the unit
4) The specified value is based on the average heating period
REMKO RVD series
| Associated indoor unit / series | RVD 355 DC IT | RVD 525 DC IT | RVD 685 DC IT | RVD 1055 DC IT | |
| Power supply V/Ph/Hz 230/1~/50 | |||||
| Application area (room volume), approx. | m^3 | 110 160 230 320 | |||
| Adjustment range room temperature | °C +17 to +30 | ||||
| Operating range °C/r.H.% +17 to +30 / 35-65 | |||||
| Air flow volume per stage | m^3/h | 416/504/617 | 540/625/750 | 1032/1200/1378 | 1438/1620/1775 |
| Sound pressure level per stage^5) | dB (A) 33/36/41 36/39/43 | 40/43/47 41/47/51 | |||
| Enclosure class IP X0 | |||||
| Refrigerant connection, liquid pipe | Inches (mm) | 1/4 (6.35) 3/8 (9.52) | |||
| Refrigerant connection, suction pipe | Inches (mm) | 3/8 (9.52) 1/2 (12.7) | 5/8 (15.9) | ||
| Condensate drainage connec-tion | mm | 25 | 32 | ||
| Condensate pump, flow rate, max. | mm WS | 500 | 750 | ||
| Dimensions: Length/width/depth | mm | 570/570/260 | 840/840/245 | ||
| Cover dimensions: Length/ width/depth | mm | 647/647/50 | 950/950/55 | ||
| Weight | kg | 18.7 | 28.0 | 32.5 | |
| EDP no. | 1623847 1623857 1623867 | 1623877 | |||
5) At distance of 1 m in the open air; specified values are maximum values
| Associated outdoor unit / series | RVD 355 DC AT | RVD 525 DC AT | RVD 685 DC AT | RVD 1055 DC AT | |
| Power supply V/Ph/Hz 230/1~/50 400/3~/50 | |||||
| Operating range, cooling °C | +5 to +507) | ||||
| Operating range, heating °C | +5 to +247) | ||||
| Air flow rate, max. m3/h 2000 2700 4000 | |||||
| Enclosure class IP 24 | |||||
| Sound power level max. dB (A) 63 64 68 | |||||
| Sound pressure level5) | dB (A) 56 | 55 | 62 64 | ||
| Refrigerant6) | R32 | ||||
| Refrigerant, basic quantity | kg | 0.87 | 1.15 | 1.50 | 2.40 |
| CO2equivalent | t 0.59 | 0.78 | 1.01 | 1.62 | |
| Operating pressure, max. | kPa | 4300/1700 | |||
| Refrigerant, additional quantity >5m | g/m | 15 | 30 | ||
| Refrigerant piping, max. length | m | 25 | 30 | 50 | 65 |
| Refrigerant piping, max. height | m | 10 | 20 | 25 | 30 |
| Refrigerant connection, liquid pipe | Inches (mm) | 1/4 (6.35) | 3/8 (9.52) | ||
| Refrigerant connection, suction pipe | Inches (mm) | 3/8 (9.52) | 1/2 (12.7) | 5/8 (15.9) | |
| Dimensions: Height / width / depth | mm | 554/800/333 | 702/845/363 | 810/946/410 | |
| Weight | kg | 34.7 | 33.7 | 49.4 | 81.5 |
| EDP no. | 1623846 | 1623856 | 1623866 | 1623876 | |
5) At distance of 1 m in the open air; specified values are maximum values
6) Contains greenhouse gas per the Kyoto protocol, GWP 675 (for further information, see chapter "Adding refrigerant")
7) Can be expanded up to -15^ with optional winter fan speed control
REMKO RVD series
2.2 Unit dimensions, outdoor unit


natural_image
Front view of a white air conditioner unit with a circular gauge and ventilation grille (no text or symbols visible)
Fig. 1: Dimensions RVD 355-1055 DC AT (all measurements in mm)
| Measurements (mm) A B C D E | ||||
| RVD 355-525 DC 800 554 333 514 340 | ||||
| RVD 685 DC 845 702 363 540 350 | ||||
| RVD 1055 DC 946 810 410 673 403 |
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
2.3 Unit dimensions, indoor unit




Fig. 2: Dimensions (all measurements in mm)
A: RVD 355-525 DC
B: RVD 685-1055 DC
1: Ceiling
2: Suspended ceiling
3: Floor
4: Condensate drainage connection
5: Injection pipe connection
6: Ceiling cut-out
7: Unit trim
8: Suction pipe connection
9: Refrigerant piping connections
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
3 Design and function
3.1 Unit description
The RVD 355-1055 DC room air conditioners have a REMKO RVD...AT outdoor unit as well as an RVD...IT indoor unit.
In cooling mode, the outdoor unit serves to output the heat extracted by the indoor unit from the room being cooled. In heating mode, the heat taken up by the outdoor unit can be discharged by the indoor unit into the room to be heated. In both operating modes, the output produced by the compressor precisely matches requirements, and thereby regulates the nominal temperature with minimal temperature deviations. This "inverter technology" results in energy savings over conventional split systems and also reduces noise emissions to a particularly low level. The outdoor unit can be installed in an outdoor area or, providing that certain requirements are met, an indoor area. The outdoor unit consists of a cooling cycle with compressor, fin condenser, condenser fan, reversing valve and throttle element. The outdoor unit is controlled by the regulation of the indoor unit.
The indoor unit is designed for indoor areas, for suspended ceilings with Euroraster dimensions. The cassette is hidden behind the suspended ceiling, only its cover is visible. It is operated by an infrared remote control. The indoor unit consists of a fin evaporator, evaporator fan, regulation system and condensate tray with condensate pump.
Floor consoles, wall consoles, refrigerant piping and winter fan speed control are available as accessories.
Refrigerant piping is used to connect the indoor unit to the outdoor unit.

Fig. 3: System layout RVD 355-1055 DC
A: Outdoor area
B: Indoor area
1: Indoor units
2: Outdoor unit
3: Condensate drainage line
4: Condenser fan
5: Power supply
6: Shut-off valve
7: Suction pipe
8: Injection pipe
9: Control lines

flowchart
graph TD
A["①"] --> B["M1"]
B --> C["M2"]
C --> D["M3"]
D --> E["FLT"]
E --> F["②"]
style A fill:#f9f,stroke:#333
style B fill:#ccf,stroke:#333
style C fill:#cfc,stroke:#333
style D fill:#fcc,stroke:#333
style E fill:#cff,stroke:#333
style F fill:#ffc,stroke:#333
Fig. 4: Cooling cycle schematic RVD 355-1055 DC
A: Outdoor area
B: Indoor area
1: RVD 355-1055 DC
M1: Condenser fan
M2: Compressor
M3: Evaporator fan IT
V1: Changeover valve C/H
EEV: Elec. Expansion valve
FLT: Filter
OEL: Oil return line
PSH: High pressure switch AT
PSL: Low pressure switch AT
T1: Probe, heat gas AT
T2: Probe, air inlet AT
T3: Probe, condenser AT
T4: Probe, air inlet IT
T5: Probe, evaporator IT
4 Operation
4.1 General notes
The indoor unit is easily operated using the standard infrared remote control. The indoor unit beeps to acknowledge the correct transmission of data. If it is not possible to program the indoor unit with the remote control, then it can also be manually operated. The indoor unit can also be operated via an optional cabled remote control.
Manual mode
The indoor units can be put into operation manually. Press the MANUAL key on the cover's receiver unit to first activate automatic mode and then test mode. Pressing the button a third time switches the unit off. Pressing the button again switches back to automatic mode.
The following settings apply for manual operation:
Cooling mode: 24 °C, fan speed: AUTO
Test mode: 30 minutes cooling, high fan speed, the IR remote control is deactivated, after 30 minutes the unit changes over to automatic mode
Infrared remote control
The infrared remote control sends the programmed settings a distance of up to 6 m to the receiver of the indoor unit. Data will only be received correctly if the remote control is pointed at the receiver and no objects are obstructing the transmission path.
Two AAA batteries must be inserted into the remote control in preparation. To do so, remove the flap from the battery compartment and insert the batteries the correct way around (see markings). Removing the batteries causes all stored data to be lost. The remote control will then access the default settings, which you are free to customise at any time.

Fig. 5: Maximum distance
! NOTICE!
Immediately replace flat batteries with a new set, otherwise there is a risk of leakage. It is recommended that the batteries are removed if the equipment is shut down for longer periods.
REMKO RVD series
Wired remote control
Connection of an optional wired remote control
The plug for connection of a wired remote control is located at the panel of the ceiling cassette (s. Fig. 6, [A]). The 5-core cable, coming from the display panel, is marked with the designations A-E (s. Fig. 6, [B]).

natural_image
Two technical diagrams: (A) a wall-mounted air vent with grid pattern, and (B) a cable with a blue connector (no text or symbols)Fig. 6: Wired remote control connection


4.2 Display on indoor unit
Display on indoor unit RVD 355-525 DC
The LED indicators illuminate to indicate the settings:
OPERATION LED green = unit switched on
TIMER LED yellow = timer programmed
DEF/FAN LED red = defrosting active/recirculation mode
ALARM LED red = alarm present

Fig. 7: Display on the unit RVD 355-525 DC
1: Unit for receiving signals from the remote control
2: Operation display
3: Timer indicator
4: Manual operation key
5: Defrosting fan
6: Malfunction indication
Display on indoor unit RVD 685-1055 DC
The LED indicators illuminate to indicate the settings:

Fig. 8: Display on the unit RVD 685-1055 DC
1: "Func" key
2: Operating lamp
3: "Timer" display activated / deactivated
4: Digital display
5: "Defrost phase" display
6: "Alarm" display
7: IR receiver
4.3 Keys on the remote control

Fig. 9: Keys on the remote control
① "ON/OFF" key
Press this key to switch the air conditioning unit on and off.
② Operating mode selection
This key is used to set the desired operating mode. The automatic, cooling, dehumidification, heating and recirculation modes are available.
③ Fan speed
Use this key to select the desired fan speed. The automatic, low, medium and high functions are available. Note: In the dehumidification mode, the fan speed cannot be set manually.
④ "SLEEP" key
Activates/deactivates the "SLEEP" function.
Pressing this key will automatically increase or decrease the target temperature by 1 °C within an hour in cooling and heating mode respectively. Press this key to maintain the most convenient temperature and save energy. This function is only available in "Cooling", "Heating" and "Auto" modes. If the unit is working in "SLEEP" mode, this activity is interrupted by pressing the "MODE", "FAN", "Speed" or "ON/OFF" keys.
⑤ "FRESH" key (no function)
⑥ "TURBO" key
Activation of the turbo function makes it possible to reach the setpoint in cooling or heating mode as fast as possible.
⑦ "SELF CLEAN" key (no function)
⑧ "ARROW UP" and "ARROW DOWN" keys
"ARROW UP" key
Press the key in order to increase the setpoint in 1°C steps to a maximum 30°C.
"ARROW DOWN" key
Press the key in order to reduce the setpoint in 1^ C steps to a minimum 17^ C.
⑨ "SILENCE/FP" key (no function)
⑩ "TIMER ON" key
Press this key to activate the unit start delay time. Each press of this key increases the delay time by 30 minutes. When the set time on the display exceeds 10.0, each press of the button increases the set time by 60 minutes. To deactivate the delay time, set the time to 0.0.
⑪ "TIMER OFF" key
This key can be used to program the delayed switch-off time. Each press of this key increases the switch-off time by 30 minutes. When the set time on the display exceeds 10.0, each press of the button increases the set time by 60 minutes. To deactivate the switch-off time, set the time to 0.0.
⑫ Swing mode
Press this key to start or stop the swing mode. With the 2-point key, you can change the fin settings on the left side. The right key has no function.
Press this key once to change the angle by 6 degrees. Pressing the key for 2 seconds stops the swing function.
REMKO RVD series
⑬ "FOLLOW ME" key
This key can be used to activate/deactivate the FOLLOW ME function. In this mode, the room temperature is measured on the remote control. This sends a signal to the indoor unit every 3 minutes. If the remote control does not send a signal to the indoor unit for 7 minutes, this mode is automatically deactivated.
⑭ "LED" key
This activates/deactivates the display on the indoor unit.
Indicators on the LCD

Fig. 10: Indicators on the LCD
1: Mode indicator - shows the current operating modes, including Auto ( ) Cooling ( ) Dehumidification ( ) Heating ( ) Fan ( ) and back to Auto ( ) mode.
2: Signal transmission symbol. This symbol appears when signals are being transmitted from the remote control to the indoor unit.
3: ON/OFF symbol. This symbol appears when the "ON/OFF" key is pressed. Pressing this key again causes the indicator to go out.
4: TIMER ON symbol. This symbol appears when TIMER ON is switched on.
5: ECO function (not available)
6: TIMER OFF symbol. This symbol appears when TIMER OFF is switched on.
7: Battery charge status (weak)
8: Sleep symbol. This symbol appears when the "Sleep" function is activated. Pressing this key again causes the indicator to go out.
9: Temperature/Timer symbol. Shows the temperature setting (-17°C\~30°C). If "FAN" mode is selected, the temperature setting is not displayed. In Timer mode, the ON and OFF settings appear for the TIMER.
10: FOLLOW ME symbol. This symbol appears when the "Follow me" function is activated.
11: Display of ion generator active (optional)
12: Fan speed symbol. This is where the selected fan speeds are displayed: AUTO (no indicator) and the three fan speed settings: ✕ (slow), ✕ (medium) and ✕ (fast). The fan speed is set to "Automatic" when either "Auto" or "Dehumidification" mode is activated.
13: Silent mode active (optional)

The illustration of the LCD with all of the symbols present is only intended to provide a clearer overview. During operation, only those symbols relevant to the respective functions appear on the display.
Key functions
A symbol is shown on the display to indicate that the settings are being transferred.
"Auto" mode (please observe notes!)
Make sure that the indoor unit is connected to the power supply, and is switched on.
The operating mode indicator on the display of the indoor unit begins to flash.
- Press the "MODE" key to select "Auto" mode.
- Press the "Arrow up/down" key to set the desired temperature. The temperature can be set between 17 and 30^ , in increments of 1^ .
- Press the "ON/OFF" key to switch on the air conditioning unit.

Fig. 11: "Auto" mode
"Cooling", "Heating" and "Recirculation" mode
Make sure that the indoor unit is connected to the power supply, and is switched on.
- Press the "MODE" key to select from operating modes "Cooling", "Heating" or "Recirculation".
- Press the "Arrow up/down" key to set the desired temperature. The temperature can be set between 17 and 30^ , in increments of 1^ .
- Press the "F AN" key to select from the four fan speeds (Auto, slow, medium and fast).
- Press the "ON/OFF" key to switch on the air conditioning unit.

Fig. 12: "Cooling", "Heating" and "Recirculation" mode
REMKO RVD series
"Dehumidification" mode
Make sure that the indoor unit is connected to the power supply, and is switched on.
The operating mode indicator on the display of the indoor unit begins to flash.
- Press the "MODE" key to select "Dehumidification" mode.
- The temperature setting on the remote control has no effect on unit operation.
- Press the "ON/OFF" key to switch on the air conditioning unit.

Fig. 13: "Dehumidification" mode
In the "Dehumidification" mode, manual selection of the fan speed is not possible! Please note that temperature pre-selection is not possible and the dehumidified room can cool dramatically!
"Timer" mode
Press the "TIMER ON" key to set the "switch-on time" and the "TIMER OFF" key to set the "switch-off" time for the unit.
Setting the "switch-on time"
- Press the "TIMER ON" key . The remote control shows "TIMER ON", the last "switch-on time" setting and the symbol "H" appear on the display. The unit is now ready to reset the "switch-on time" and to start "TIMER ON" mode.
- Press the "TIMER ON" key again to set the desired "switch-on time". Each time the key is pressed, the time is increased by half an hour between 0 and 10 hours, and by an hour between 10 and 24 hours.
- Once these settings have been made, there is a one second delay before the remote control transmits the signal to the indoor unit. Then, after approx. two seconds, the "H" symbol disappears from the LCD display, and the set temperature appears again on the display.

Fig. 14: "Timer" mode
Setting the "switch-off time"
-
Press the "TIMER OFF" key . The remote control shows "TIMER OFF", the last "switch-off time" setting and the symbol "H" appear on the display. The unit is now ready to reset the "switch-off time" and to stop "TIMER OFF" mode.
-
Press the "TIMER OFF" key again to set the desired "switch-off time". Each time the key is pressed, the time is increased by half an hour between 0 and 10 hours, and by an hour between 10 and 24 hours.
-
Once these settings have been made, there is a one second delay before the remote control transmits the signal to the indoor unit. Then, after approx. two seconds, the "H" symbol disappears from the LCD display, and the set temperature appears again on the display.

- When T timer mode is selected, the remote control automatically transfers the timer signal to the indoor unit for the specified period of time. Therefore, you should hold the remote control in a location where it can transfer the signal to the indoor unit without interference.
The effective operation for the time settings by the remote control for the timer function is restricted to the following settings: 0.5, 1.0, 1.5, 2.0, 2.5, 3.0, 3.5, 4.0, 4.5, 5.0, 5.5, 6.0, 6.5, 7.0, 7.5, 8.0, 8.5, 9.0, 9.5, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23 and 24.
Example TIMER function settings
"TIMER ON" (Auto on mode)
Example:
You want the air conditioning unit to switch on 2 hours from the time it was programmed.
- Press the "TIMER ON" key . The last operating time setting for the timer, and the "H" symbols, appear on the display.
-
Press the "TIMER ON" key until the desired start time is shown in the "TIMER ON" area on the remote control.
-
W ait for 3 seconds and the temperature appears again in this area of the digital display. The "TIMER ON" indicator stays lit, and this function is activated.

Fig. 15: "TIMER ON" example
"TIMER OFF" (Auto off mode)
Example:
You want the air conditioning unit to switch off 4 hours from the time it was programmed.
- Press the "TIMER OFF" key . The last operating time setting for the timer, and the "H" symbols, appear on the display.
- Press the "TIMER OFF" key until "10H" is shown in the "TIMER OFF" area on the remote control.
- W ait for 3 seconds and the temperature appears again in this area of the digital display. The "TIMER OFF" indicator stays lit, and this function is activated.

Fig. 16: "TIMER OFF" example
REMKO RVD series
Combined TIMER (setting "TIMER ON" and "TIMER OFF" at the same time)
"TIMER OFF ⇒ "TIMER ON"
$$ (\text { On } \Rightarrow \text { Stop } \Rightarrow \text { Start }) $$
Example:
You want the air conditioning unit to switch off in two hours from the time it was programmed, and switch back on ten hours later.
- Press the "TIMER OFF" key.
- Press the "TIMER OFF" key again until the desired stop time is shown in the "TIMER OFF" area on the remote control.
- Press the "TIMER ON" key.
- Press the "TIMER ON" key again until "10H" is shown in the "TIMER ON" area on the remote control.
- Wait for 3 seconds and the temperature appears again in this area of the digital display. The "TIMER ON" and "TIMER OFF" indicators stay lit, and this function is activated.


Fig. 17: "TIMER OFF" / "TIMER ON" example
"TIMER ON "TIMER OFF"
$$ (\text { Off } \Rightarrow \text { Start } \Rightarrow \text { Stop }) $$
Example:
You want the air conditioning unit to switch on in two hours from the time it was programmed, and switch back off five hours later.
- Press the "TIMER ON" key.
- Press the "TIMER ON" key again until "2.0H" is shown in the "TIMER ON" area on the remote control.
- Press the "TIMER OFF" key.
- Press the "TIMER OFF" key again until "5.0H" is shown in the "TIMER OFF" area on the remote control.
- Wait for 3 seconds and the temperature appears again in this area of the digital display. The "TIMER ON" and "TIMER OFF" indicators stay lit, and this function is activated.


Fig. 18: "TIMER ON" / "TIMER OFF" example
5 Installation instructions for qualified personnel
5.1 Important notes prior to installation
Transport the unit in its original packaging as close as possible to the installation location. You avoid transport damage by doing so.
Check the contents of the packaging for completeness and check the unit for visible transport damage. Report any damage immediately to your contractual partner and the shipping company.
Lift the unit on the corners and not on the refrigerant or condensate drainage connections.
The refrigerant piping (injection and suction pipe), valves and connections must be insulated against vapour density. If necessary also insulate the condensate drainage line.
- Select an installation location which allows air to freely flow through the air inlet and outlet (see section "Minimum clearances").
Do not install the unit in the immediate vicinity of devices which generate intensive thermal radiation. Installation in the vicinity of thermal radiation reduces the unit output.
Only open the shut-off valves on the refrigerant piping after installation is complete.
Seal off open refrigerant piping with suitable caps or adhesive strips to prevent the infiltration of moisture and never kink or compress the refrigerant piping.
Avoid unnecessary bends. This minimises the pressure loss in the refrigerant piping and ensures that the compressor oil can flow back without obstruction.
Use the fastening materials provided in the scope of supply for the units.
Use four supports and the associated hooks to attach the ceiling cassette.
Use the insulated condensate hose in the scope of delivery as a junction piece to the continuing condensate drain. Secure the condensate drain with the supplied clamps.
5.2 Wall openings
A wall opening of at least 70mm diameter and 10mm incline from the inside to the outside must be created.
To prevent damage to the lines, the interior of the wall opening should be padded or, for example, lined with PVC pipe (see figure).
After installation has been completed, use a suitable sealing compound to close off the wall opening, taking account of fire protection regulations (responsibility of customer). Do not use cement or lime containing substances!

Fig. 19: Wall opening
1: Liquid line
2: Control line
3: Condensate drainage line
4: Suction pipe
5: PVC pipe
5.3 Installation materials
The indoor unit is attached using 4 threaded rods provided by the customer.
The outdoor unit is attached by 4 screws and a wall bracket to the wall or fixed by a floor bracket to the ground.
REMKO RVD series
5.4 Selection of installation location
Indoor unit
The indoor unit is designed for horizontal ceiling installation. The minimum distance from the floor should be 2 metres.
Outdoor unit
The outdoor unit is designed for horizontal installation on a base in outdoor areas. The installation site must be level, flat and firm. The unit should also be secured to prevent it from tipping over. The outdoor unit can be set up outside as well as inside a building. For external installation, please observe the following notes to protect the unit from the influence of the weather.
Rain
The unit should be at least 10 cm off the ground when mounted on the roof or ground. A floor bracket is available as an accessory.
Sun
The condenser on the outdoor unit emits heat. Exposure to sunlight further increases the temperature of the fins and reduces the heat released by the finned heat exchanger. The outdoor unit should be installed on to the north side of the building whenever possible. If necessary, take measures to provide sufficient shade (responsibility of customer). This could be a small roof. However, the discharging warm air flow must not be affected by the measures.
Wind
If the unit is being installed in windy areas, ensure that the warm outlet air is discharged in the prevailing wind direction. If this is not the possible, it may be necessary to install a windbreak (to be provided by the customer). Ensure that the windbreak does not adversely affect the air intake to the unit. Additional stabilisation is recommended. This can be realised with wire ropes or other constructions.

Fig. 20: Windbreak
1: Wind
Snow
The unit should be wall-mounted in areas of heavy snowfall. Installation should be at least 20 cm above the expected level of snow to prevent snow from entering the outdoor unit. An optional wall bracket is available as an accessory.

Fig. 21: Minimum clearance to snow
1: Snow
Installation inside buildings
■ Ensure that heat can dissipate adequately when placing the outdoor unit in cellars, lofts, adjoining rooms or halls (Fig. 22).
Install an additional fan with a rated flow comparative to that of the outdoor unit being installed in the room and which can compensate any additional pressure loss in ventilation ducts (Fig. 22).
Comply with any regulations and conditions affecting the statics of the building. If necessary, fit acoustic installation.

flowchart
graph TD
A["1"] --> B["2"]
B --> C["3"]
C --> D["3"]
D --> E["K"]
E --> F["W"]
F --> G["2"]
G --> H["3"]
H --> I["2"]
I --> J["3"]
J --> K["K"]
K --> L["2"]
L --> M["3"]
M --> N["W"]
N --> O["2"]
O --> P["K"]
P --> Q["2"]
Q --> R["W"]
R --> S["2"]
S --> T["K"]
Fig. 22: Installation inside buildings
K: Cold fresh air
W: Warm air
1: Outdoor unit
2: Additional fan
3: Air shaft
5.5 Minimum clearances
Observe the minimum clearances to allow access for maintenance and repair work and facilitate optimum air distribution.

Fig. 23: Minimum clearances, indoor unit and outdoor unit (all measurements in mm)
AT: Outdoor unit / IT: Indoor unit 1: Air inlet / 2: Air outlet
| ABCDE | |||||
| RVD 355-1055 DC | 300 | 2000 | 600 | 300 | 600 |
REMKO RVD series
5.6 Oil return measures
If the outdoor unit is installed at a higher level than the indoor unit, suitable oil return measures must be taken. Usually, an oil pump bend is installed for every 7 metres of height difference.

Fig. 24: Oil return measures
AT: Outdoor unit
IT: Indoor unit
1: 1 x oil pump bend in suction pipe to outdoor unit every 7 metres of height difference, radius: 50 mm
2: Max. 10-15 m
6 Installation
6.1 Unit installation
! NOTICE!
Installation should only be performed by authorised specialists.
The unit is mounted with the cover facing down on four threaded rods. Take into account the ceiling grid and any other installations.
-
Use the dimensions of the ceiling cassette to mark the fixing points for the threaded rods on structural parts approved to support the static load above the suspended ceiling (Fig. 25).
-
Fit the indoor unit onto the threaded rods and use the lower nuts to level the unit (Fig. 26).
-
Adhere to a ceiling clearance of at least 30 mm. Connect the refrigerant piping, electrical cables and condensate drainage line to the indoor unit as described below.
-
Check again that the unit is level.
-
The final task is to tighten the counternuts and attach the cover.

Fig. 25: Hooking in the unit
| Indoor units(all dimensions in mm) | Measurement A | Measurement B |
| RVD 355-525 DC 545 523 | ||
| RVD 685-1055 DC 780 680 |

Fig. 26: Hooking in the unit
1: Structural component
| Distance A | |
| RVD 355 DC IT 290 mm | |
| RVD 525 DC IT 290 mm | |
| RVD 685 DC IT 275 mm | |
| RVD 1055 DC IT 275 mm |

Fig. 27: Fastening the unit
A: Distance A
1: Ceiling
2: Suspended ceiling
3: Unit housing
| Indoor units | Distance A | Suspended unit |
| RVD 355-525 DC IT 23 mm 545x523 mm | ||
| RVD 685-1055 DC IT | 10-18 mm | 780x680 mm |
Fresh air connection
The unit is prepared for the intake of fresh air.

natural_image
3D rendering of a mechanical device with a labeled component (1) and no visible text or symbols on the main body.Fig. 28: Fresh air connection
1: Fresh air connection


Fresh air connection
The unit can also be employed to suck in and regulate the temperature of fresh air (outdoor air), in addition to room air. This is the preferred option for rooms with a high rate of air consumption.
- Observe the regional regulations concerning air treatment.
■ Fit a collar with a nominal diameter of 65 mm to the fresh air connection (Fig. 29).
REMKO RVD series

flowchart
graph TD
A["Chamber 1"] --> B["Flow Arrows"]
B --> C["Chamber 2"]
C --> D["Flow Arrows"]
D --> E["Chamber 3"]
E --> F["Flow Arrows"]
F --> G["Chamber 4"]
G --> H["Flow Arrows"]
H --> I["Chamber 5"]
I --> J["Flow Arrows"]
J --> K["Chamber 6"]
K --> L["Flow Arrows"]
L --> M["Chamber 7"]
M --> N["Flow Arrows"]
N --> O["Chamber 8"]
O --> P["Flow Arrows"]
P --> Q["Chamber 9"]
Q --> R["Flow Arrows"]
R --> S["Chamber 10"]
Fig. 29: Fresh air connection
1: Outdoor air intake
A: Outside
B: Inside
The fresh air content should not exceed 10% of the nominal air flow rate for the unit. The fresh air supply should be controlled by an additional speed-regulated fan.
The air at the outdoor air intake should be sucked in through a dust filter at a maximum rate of 2.5 m/s to prevent the ingress of rain water.
The fan should be connected to a separately protected electrical supply that is to be provided by the customer.

natural_image
Close-up of a mechanical component with a highlighted section and numbered marker (1), no readable text or symbols present.Fig. 30: Fresh air inlet
1: Fresh air inlet
6.2 Connection of refrigerant piping
The refrigerant piping connection provided by the customer takes place on one corner of the unit, inside the suspended ceiling. Once installed, the connections should be insulated to make them vapour diffusion proof.
! NOTICE!
Use only tools which are approved for use in an HVAC environment. (z. B.: bending pliers, pipe/tubing cutters, de-burrers and flaring tools). Do not cut refrigerant pipes with a saw.
! NOTICE!
All work must be carried out in a way that prevents dirt, particles, water etc. from entering, refrigerant lines!
! NOTICE!
A detachable connection may only be established outside the room. To connect the indoor units, use only the supplied, non-detachable union nuts or provide a firm connection.
Connection of the unit panel
The unit panel is bolted onto the ceiling cassette with the 4 screws supplied. Connect the connection cables between the unit panel and ceiling cassette together. When doing so, note that the connection cable of the swing motors must be connected directly to the control board of the ceiling cassette at contact CN14 (swing). A cable with connecting plug may have been plugged in at the factory. This must be removed for installation.
The following instructions describe the installation of the cooling cycle and the assembly of the indoor unit and the outdoor unit:
- The required pipe diameters are given in the table "Technical data".
-
Install the indoor unit and connect the refrigerant piping as described in the operating manual for the indoor unit.
-
Use the wall or floor brackets to fit the outdoor unit against structural parts approved to support the static load (refer to the installation instructions for the brackets).
-
Ensure that structure-borne sound is not transferred to parts of the building. Use vibration dampers to reduce the effects of structure-borne sound!
-
Lay the refrigerant piping from the indoor unit to the outdoor unit. Ensure that the fastenings are adequate and if necessary, take appropriate oil return measures!
-
Remove the factory-fitted protective caps and union nuts on the connections. These should be used later in the installation process.
-
Before flanging the refrigerant piping, ensure that the union nut is fitted on the pipe.
-
Prepare the laid refrigerant piping as shown below (Fig. 31 and Fig. 32).
-
V erify that the shape of the flange is correct (Fig. 33).
-
First connect and hand-tighten the refrigerant piping to ensure it is correctly seated.
-
Then tighten the fittings with 2 appropriately-sized open-ended spanners. Use a spanner to counter the force when tightening the fitting (Fig. 34).
-
Use insulation hoses which are designed for this temperature range and are diffusion proof.
-
Observe the permitted bending radius for the refrigerant piping during installation. Never bend a pipe twice in the same place. Brittleness and cracking can result.
-
Apply appropriate heat insulation to the installed refrigerant piping, including connector.
-
T ake the same action at the shut-off valves for all subsequent refrigerant piping.

Fig. 31: Deburring the refrigerant piping
1: Refrigerant piping /2: Deburrer

natural_image
Close-up of hands using a mechanical clamp or tool to adjust a cable or hose component (no text or symbols visible)Fig. 32: Flanging the refrigerant piping
1: Flanging tool

Fig. 33: Correct flange shape
REMKO RVD series

Fig. 34: Tightening the fitting
1: Tighten with the first open-ended spanner
2: Counter with the second open-ended spanner
| Pipe dimension in inches | Tightening torque in Nm |
| 1/4" 15-20 | |
| 3/8" 33-40 | |
| 1/2" 50-60 | |
| 5/8" 65-75 | |
| 3/4" 95-105 |
6.3 Leak testing
Once all the connections have been established, the pressure gauge station is attached to the corresponding Schrader valve connection as follows:
blue = large valve = suction pressure
Once the connection has been made successfully, the leak test is carried out with dry nitrogen.
Leak testing involves spraying a leak detection spray onto the connections. If bubbles are visible, the connections have not been made properly. In that case, tighten the connection or, if necessary, create a new flange.
After completing a successful leak test, the excess pressure in the refrigerant piping is removed and a vacuum pump with an absolute final partial pressure of min. 10 mbar is used to remove all of the air and empty the pipes. Any moisture present in the pipes will also be removed.
! NOTICE!
A vacuum of at least 20 mbar must be produced!
The time required to generate the vacuum is dependent on the final pressure pipe volume of the indoor units and the length of the refrigerant piping. However, the process will take at least 60 minutes. Once any foreign gases and humidity have been completely extracted from the system, the valves on the pressure gauge station are closed and the valves on the outdoor unit are opened as described in the "Commissioning" section.
6.4 Adding refrigerant
The units contain a basic quantity of refrigerant. In addition, an additional amount of refrigerant must be added for refrigerant piping lengths exceeding 5 metres per circuit. Refer to the following chart:
| Up to and | incl. 5m | From 5m to max. length |
| RVD 355 DC | 0 g/m | 15 g/m |
| RVD 525 DC | ||
| RVD 685 DC | 30 g/m | |
| RVD 1055 DC |

CAUTION!
Wear protective clothing when handling refrigerant.

DANGER!
Only refrigerant in a liquid state may be used to fill the cooling cycle!

NOTICE!
Check the overheating to determine the refrigerant fill quantity.

NOTICE!
The escape of refrigerant contributes to climatic change. In the event of escape, refrigerant with a low greenhouse potential has a lesser impact on global warming than those with a high greenhouse potential.
This unit contains refrigerant with a greenhouse potential of 675. That means the escape of 1 kg of this refrigerant has an effect on global warming that is 675 times greater than 1 kg CO₂, based on 100 years. Do not conduct any work on the refrigerant circuit or dismantle the unit - always enlist the help of qualified experts.
7 Condensate drainage connection and safe drainage
Condensate drainage connection
If the temperature falls below the dew point, condensate will form on the cooling fins during cooling mode. A collection tray together with a condensate pump and liquid level switch are fitted as standard below the cooling fins. If the liquid level switch trips a protective shutdown due to inadequate removal of the condensate, the pump will switch on immediately and run on for approx. three minutes.
The condensate drainage line should have an incline of min. 2%. This is the responsibility of the customer. If necessary, fit vapour-diffusion-proof insulation.
If the level of the condensate drainage line on the unit is above that of the outlet, route the pipe vertically upwards and then with an incline to the drain.
Route the unit's condensate drainage line freely into the drain line. If the condensate runs directly into a sewer pipe, fit a trap to prevent any unpleasant odours.
When operating the unit at outside temperatures below 4 °C, ensure the condensate drainage line is laid to protect it against frost. If necessary, fit a pipe heater.
Following installation, check that the condensate run off is unobstructed and ensure that the line is durably leak tight.
Safe drainage in the event of leakages
Local regulations or environmental laws, for example the German Water Resource Act (WHG), can require suitable precautions to protect against uncontrolled drainage in case of leakage to provide for safe disposal of escaping air conditioning fluid or hazardous media.

NOTICE!
The max. pump pressure of the condensate pump is 500/750 mmWS. Capacity reductions can result from external influences such as air-side counter-pressure, soiling or wear. In order to guarantee safe functional operation, we recommend observing a maximum delivery height of 450/700 mm!
REMKO RVD series
! NOTICE!
If condensate is removed via a duct in accordance with DIN EN 1717, ensure that any microbiological contamination present on the wastewater side (bacteria, fungi, viruses) cannot enter the unit connected to it.

Fig. 35: Condensate drainage connection - incorrect!
A: Riser pipe too far away
B: Condensate drainage line too large/small
C: No incline
D: Cannot freely drain away

Fig. 36: Condensate drainage connection - correct!
8 Electrical wiring
8.1 General connection and safety instructions
A protected power supply cable is to be connected to the outdoor unit and a four-core control line with a minimum cross-section of 1.5mm^2 . To avoid EMC interference, only use shielded cable for this purpose and connect the shielding on both sides.

DANGER!
All electrical installation work is to be performed by specialist companies. Disconnect the power supply when connecting the electrical terminals.

NOTICE!
The electrical connection for the units must be made at a separate feedpoint with a residual current device in accordance with local regulations and should be laid out by an electrician.

We recommend using shielded wires for the control lines.
We recommend that a mains/repair switch be installed near the outdoor unit.
The terminal blocks for establishing the connections are located on the side of the unit. When the unit is installed, measurements can be made from the front by removing the cover.
If an optional condensate pump is used as an accessory in conjunction with the unit, it may be necessary to install an additional relay with a higher contact rating after the switch-off contact on the pump to switch off the compressor.
The control lines used should comprise shielded wire, if laid in areas exposed to strong magnetic fields.
Details concerning the electrical protection of the system are provided in the technical data.
8.2 Connecting the indoor unit
Make the connection as follows:
- Open the air inlet grill.
- Loosen the switch cabinet's cover ( Fig. 38).
- Feed the voltage-free cable through the edge protection rings on the control box and clamp the cable in the strain relief.
- Then connect the cable in accordance with the wiring diagram (see chapter "Electrical wiring diagram").
- Connect the electrical plugs on the cover to the mating connectors on the cassette. It is not possible to incorrectly connect these.
- Re-install all disassembled parts.

natural_image
Diagram of a microwave oven with airflow direction indicated by green arrow (no text or symbols)Fig. 37: Switch cabinet access
REMKO RVD series

Fig. 38: Connecting the indoor unit
1: Plastic cover
2: Electrical drawing
3: Power supply connection terminals
4: Strain relief
5: Communication line to outdoor unit
6: Plastic cover
7: Cable fastening possibility

Check all plugged and clamped terminals to verify that they are seated correctly and make permanent contact. Tighten as required.
8.3 Outdoor unit connection
Proceed as follows to connect the line:
- Remove the unit cover
- Remove the side panel at the connection.
- Choose the cable cross-section in accordance with the relevant specifications.
- Feed both cables through the edge protection rings on the fixed connection panel.
- Connect the lines as shown on the electrical connection diagram.
- Fix the line in the strain relief and re-assemble the unit.
8.4 Electrical wiring diagram
Connection RVD 355 DC

Fig. 39: Electrical wiring diagram RVD 355 DC
A: Outdoor unit RVD 355 DC AT
B: Indoor unit RVD 355 DC IT
1 Power supply
2: Communication lines
REMKO RVD series
Connection RVD 525 DC

Fig. 40: Electrical wiring diagram RVD 525 DC
A: Outdoor unit RVD 525 DC AT
B: Indoor unit RVD 525 DC IT
1 Power supply
2: Communication lines
Connection RVD 685 DC

flowchart
graph TD
subgraph_A["Configuration A"]
A1["1(L)"] --> A2["2(N)"]
A2 --> A3["L N"]
A3 --> A4["⊕"]
A4 --> A5["S1 S2"]
A5 --> A6["PE"]
A1 -->|1| A7["230V/1~50 Hz"]
A7 --> A8["PE"]
end
subgraph_B["Configuration B"]
B1["L N"] --> B2["S1"]
B2 --> B3["PE"]
B3 --> B4["S2"]
B4 --> B5["PE"]
end
A1 -->|2| B2
A2 -->|2| B3
A3 -->|2| B4
A4 -->|2| B5
A5 -->|2| B6
A6 -->|2| B7
A7 -->|2| B8
A8 -->|2| B9
A9 -->|2| B10
A10 -->|2| B11
A11 -->|2| B12
A12 -->|2| B13
A13 -->|2| B14
A14 -->|2| B15
A15 -->|2| B16
A16 -->|2| B17
A17 -->|2| B18
A18 -->|2| B19
A19 -->|2| B20
A20 -->|2| B21
A21 -->|2| B22
A22 -->|2| B23
A23 -->|2| B24
A24 -->|2| B25
A25 -->|2| B26
A26 -->|2| B27
A27 -->|2| B28
A28 -->|2| B29
A29 -->|2| B30
A30 -->|2| B31
A31 -->|2| B32
A32 -->|2| B33
A33 -->|2| B34
A34 -->|2| B35
A35 -->|2| B36
A36 -->|2| B37
A37 -->|2| B38
A38 -->|2| B39
A39 -->|2| B40
A40 -->|2| B41
A41 -->|2| B42
A42 -->|2| B43
A43 -->|2| B44
A44 -->|2| B45
A45 -->|2| B46
A46 -->|2| B47
A47 -->|2| B48
A48 -->|2| B49
A49 -->|2| B50
A50 -->|2| B51
A51 -->|2| B52
A52 -->|2| B53
A53 -->|2| B54
A54 -->|2| B55
A55 -->|2| B56
A56 -->|2| B57
A57 -->|2| B58
A58 -->|2| B59
A59 -->|2| B60
A60 -->|2| B61
A61 -->|2| B62
A62 -->|2| B63
A63 -->|2| B64
A64 -->|2| B65
A65 -->|2| B66
A66 -->|2| B67
A67 -->|2| B68
A68 -->|2| B69
A69 -->|2| B70
A70 -->|2| B71
A71 -->|2| B72
A72 -->|2| B73
A73 -->|2| B74
A74 -->|2| B75
A75 -->|2| B76
A76 -->|2| B77
A77 -->|2| B78
A78 -->|2| B79
A79 -->|2| B80
A80 -->|2| B81
A81 -->|2| B82
A82 -->|2| B83
A83 -->|2| B84
A84 -->|2| B85
A85 -->|2| B86
A86 -->|2| B87
A87 -->|2| B88
A88 -->|2| B89
A89 -->|2| B90
Fig. 41: Electrical wiring diagram RVD 685 DC
A: Outdoor unit RVD 685 DC AT
B: Indoor unit RVD 685 DC IT
1 Power supply
2: Communication lines
REMKO RVD series
Connection RVD 1055 DC

flowchart
graph TD
subgraph_Panel_A[" fan "]
L1["L1"] --> PE1["PE"]
L2["L2"] --> PE2["PE"]
L3["L3"] --> PE3["PE"]
N["N"] --> PE4["PE"]
PE1 --> 1["1"]
PE2 --> 1
PE3 --> 1
PE4 --> 1
PE5["PE"] --> 1
PE6["PE"] --> 1
end
subgraph_Panel_B[" fan "]
S1["S1"] --> PE7["PE"]
S2["S2"] --> PE8["PE"]
PE7 --> 2["2"]
PE8 --> 2
end
L1 --> 1
L2 --> 1
L3 --> 1
L3 --> 1
L1 --> 2
L2 --> 2
L3 --> 2
L3 --> 2
L1 --> 2
L2 --> 2
L3 --> 2
L3 --> 2
L1 --> 2
L2 --> 2
L3 --> 2
L1 --> 2
L2 --> 2
L3 --> 2
L3 --> 2
L1 --> 2
L2 --> 2
L3 --> 2
L1 --> 2
L2 --> 2
L3 --> 2
L1 --> 2
L2 --> 2
L3 --> 2
style Panel_A fill:#f9f,stroke:#333
style Panel_B fill:#bbf,stroke:#333
Fig. 42: Electrical wiring diagram RVD 1055 DC
A: Outdoor unit RVD 1055 DC AT
B: Indoor unit RVD 1055 DC IT
1 Power supply
2: Communication lines
8.5 Electrical drawings
Indoor unit RVD 355 DC IT

flowchart
graph TD
A["① M"] --> B["②"]
B --> C["③"]
C --> D["④"]
D --> E["⑤"]
E --> F["⑥"]
F --> G["⑦"]
G --> H["⑧"]
H --> I["⑨"]
I --> J["⑩"]
J --> K["⑪"]
K --> L["⑫"]
L --> M["⑬"]
M --> N["⑭"]
N --> O["⑮"]
O --> P["⑯"]
P --> Q["⑰"]
Q --> R["⑱"]
R --> S["⑲"]
S --> T["⑳"]
T --> U["㉑"]
U --> V["㉒"]
V --> W["㉓"]
W --> X["㉔"]
X --> Y["㉕"]
Y --> Z["㉖"]
Z --> AA["㉗"]
AA --> AB["㉘"]
AB --> AC["㉙"]
AC --> AD["㉚"]
AD --> AE["㉛"]
AE --> AF["㉜"]
AF --> AG["㉝"]
AG --> AH["㉟"]
AH --> AI["㉟A"]
AI --> AJ["①4"]
AJ --> AK["③"]
AK --> AL["④"]
AL --> AM["⑤"]
AM --> AN["⑥"]
AN --> AO["⑦"]
AO --> AP["⑧"]
AP --> AQ["㉑"]
AQ --> AR["㉒"]
AR --> AS["㉓"]
AS --> AT["㉔"]
AT --> AU["㉕"]
AU --> AV["㉖"]
Fig. 43: Electrical drawings RVD 355 DC IT
A: Control board
B: Display circuit board
1: DC fan motor (alternative)
2: Optional wired remote control
3: Connection of optional wired remote control
4: Potential-free alarm contact
5: External on/off
6: Connection possibility for fan motor provided by the customer
7: Transformer
8: Temperature probe, suction pipe
9: Temperature probe, evaporator
10: Temperature probe, indoor air
11: Swing motor
12: Connecting line to the outdoor unit
13: MCC-1 controller connection
14: DC fan motor
15: Condensate pump
16: Condensate pump liquid level switch
17: AC fan motor
REMKO RVD series
DIP switch setting possibilities
Address assignment MCC-1 (S2+S1)
| Switch | ||||
| S2 + S1 | ![]() | ![]() | ![]() | ![]() |
| Address 0~15 16~31 | ||||
| Factory setting | √ | |||
| S2 + S1 | ![]() | ![]() | ![]() | ![]() |
| Address 32~47 48~63 | ||||
| Factory setting | ||||
Anti-cold air function (SW1)
| Switch SW1 | Factory setting | |
| Fan motor stop temperature | ||
![]() | 24 | √ |
![]() | 15 | |
![]() | 8 | |
![]() | After EEPROM programming | |
Fan behaviour without demand (SW2)
| Switch SW2 Value | Factory setting | ||
| ON Setting | ![]() | Fan OFF | ✓ |
![]() | Fan ON | ||
Automatic restart after power failure (SW3)
| Switch SW3 Value | Factory setting | ||
| ON Setting | ![]() | Automatic restart in last operating mode | √ |
![]() | No automatic restart | ||
Mode priority (SW5)
| Switch SW5 | ||||
| ONSetting | ![]() | ![]() | ![]() | ![]() |
| Value Heating | Heating | Cooling | Cooling | |
| Factory setting | √ | |||
Temperature compensation (SW6)
| Switch SW6 | ||||
| ONSetting | ![]() | ![]() | ![]() | ![]() |
| Value | 6 | 4 | 2 | |
| Factory setting | √ | |||
Indoor units RVD 525-1055 DC

flowchart
graph TD
subgraph Section A
M1["① M"] -->|5| CN15
CN3["③ CN3"] -->|5| CN15
CN13["④ CN13"] -->|5| CN15
CN15 -->|4| CN40
CN15 -->|2| X59["X59"]
CN15 -->|3| XP9["XP9"]
CN15 -->|4| SWING_MOTOR["XSWING MOTOR"]
CN15 -->|5| XP10["XP10"]
end
subgraph Section B
CN8["② CN8"] -->|4| M["M"]
M -->|2| M["M"]
M -->|5| CN13
CN13 -->|10| B["B"]
B -->|5| 6["⑥"]
end
subgraph Section C
FAN1["FAN1"] -->|6| CAP1["CAP1"]
CAP1 --> braun["braun"]
braun --> schwarz["schwarz"]
schwarz --> CN66["CN66"]
CN66 --> CN55["CN55"]
CN55 --> E["Y"]
CN55 --> X["X"]
CN55 --> S2["S2"]
CN55 --> S1["S1"]
CN2["③"] --> CN3["④"]
CN2 --> CN4["P3"]
CN2 --> CN4
CN2 --> CN4
CN2 --> CN4
CN2 --> CN4
CN2 --> CN4
CN2 --> CN4
CN2 --> CN4
CN2 --> CN4
end
subgraph Section D
CX2["X2"] --> CAP1
CX2 --> shwarz["schwarz"]
end
subgraph Section E
CX2X2["X2"] --> CAP1
CX2X2 --> shwarz
end
subgraph Section F
CX2X2X2["X2"] --> CAP1
CX2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2A
end
subgraph Section G
CX7["T7B"] --> CN7["CN7"]
CX6["T7B"] --> CN6["CN6"]
CX5["T7B"] --> CN5["CN5"]
CX4["T7B"] --> CN4["CN4"]
CX3["T7B"] --> CN3["CN3"]
CX2["T7B"] --> CN2["CN2"]
CX1["T7B"] --> CN1["CN1"]
end
subgraph Section H
CX8["T8T"] --> CN8["CN8"]
CX7["T8T"] --> CN9["CN9"]
CX6["T8T"] --> CN10["CN10A"]
CX5["T8T"] --> CN10
CX4["T8T"] --> CN10
CX3["T8T"] --> CN10
end
subgraph Section I
CX9["T9T"] --> CN9
CX8["T9T"] --> CN10
CX7["T9T"] --> CN10
CX6["T9T"] --> CN10
CX5["T9T"] --> CN10
CX4["T9T"] --> CN10
end
subgraph Section J
CX10["T10A"] --> B["B"]
end
subgraph Section K
CX10["T10A"] --> B["B"]
end
subgraph Section L
CX10["T10A"] --> P4["P4"]
end
subgraph Section M
X9["X9"] --> SWING_MOTOR["XSWING MOTOR"]
X8["X8"] --> SWING_MOTOR["XSWING MOTOR"]
end
subgraph Section M_A
X9["X9"] --> SWING_MOTOR_X9["XSWING MOTOR_X9"]
end
subgraph Section M_B
X8["X8"] --> SWING_MOTOR_X8["XSWING MOTOR_X8"]
end
subgraph Section M_C
X9["X9"] --> SWING_MOTOR_X9["XSWING MOTOR_X9"]
end
subgraph Section M_D
X8["X8"] --> SWING_MOTOR_DW["XSWING MOTOR_DW"]
end
subgraph Section M_F
X9["X9"] --> SWING_MOTOR_FW["XSWING MOTOR_FW"]
end
subgraph Section M_G
X8["X8"] --> SWING_MOTOR_GW["XSWING MOTOR_GW"]
end
subgraph Section M_H
X9["X9"] --> SWING_MOTOR_HW["XSWING MOTOR_HW"]
end
subgraph Section M_H_A
X8["X8"] --> SWING_MOTOR_HW_A["XSWING MOTOR_HW"]
end
Fig. 44: Electrical drawings RVD 525-1055 DC
A: Control board
B: Display circuit board
1: DC fan motor (alternative)
2: Connection of optional wired remote control
3: Swing motors
4: Connection possibility for fan motor provided by the customer
5: Condensate pump
6: Optional wired remote control
7: Temperature probe, suction pipe
8: Temperature probe, evaporator
9: Temperature probe, indoor air
10: Condensate pump liquid level switch
11: Power supply
12: Communication line to outdoor unit
13: MCC-1 controller connection possibility
14: DC fan motor
15: Transformer
16: External on/off
17: Potential-free alarm contact
REMKO RVD series
DIP switch setting possibilities
Address assignment MCC-1 (S2+S1)
| Switch | ||||
| S2 + S1 | ![]() | ![]() | ![]() | ![]() |
| Address 0~15 16~31 | ||||
| Factory setting | √ | |||
| S2 + S1 | ![]() | ![]() | ![]() | ![]() |
| Address 32~47 48~63 | ||||
| Factory setting | ||||
Anti-cold air function (SW1)
| Switch SW1 | Factory setting | |
| Fan motor stop temperature | ||
| [YSAD] | 24 | √ |
![]() | 15 | |
![]() | 8 | |
![]() | After EEPROM programming | |
Fan behaviour without demand (SW2)
| Switch SW2 Value | Factory setting | ||
| ON Setting | ![]() | Fan OFF | ✓ |
![]() | Fan ON | ||
Automatic restart after power failure (SW3)
| Switch SW3 Value | Factory setting | ||
| ON Setting | ![]() | Automatic restart in last operating mode | √ |
![]() | No automatic restart | ||
Main / slave setting (SW5)
| Switch SW5 | ||||
| ONSetting | ![]() | ![]() | ![]() | ![]() |
| Value MAIN | NO SLAVE | MAIN | MAIN | SLAVE |
| Factory setting | √ | |||
Temperature compensation (SW6)
| Switch SW6 | ||||
| ON Setting | ![]() | ![]() | ![]() | ![]() |
| Value | 6 | 4 | 2 | |
| Factory setting | √ | |||
Power setting (ENC1)
| ENC1 | |||
| Switch no. | Power [W] | Switch no. | Power [W] |
| 4 | 4000-5300 | 8 | 9100-10500 |
| 5 | 5400-7100 | 9 | 12000-14000 |
| 6 | - | A | 14500-16000 |
| 7 | 7500-9000 | ||
Outdoor unit RVD 355 DC AT

flowchart
graph TD
A["1"] --> B["CN 50"]
B --> C["CN 21"]
C --> D["CN 7"]
D --> E["CN 31"]
E --> F["CN 25"]
F --> G["CN 60"]
G --> H["W 1(L) 2(N) SL N"]
H --> I["grün/gelb"]
H --> J["grün/gelb"]
H --> K["grün/gelb"]
H --> L["grün/gelb"]
C --> M["10"]
D --> N["5/6"]
E --> O["9"]
style A fill:#f9f,stroke:#333
style B fill:#ccf,stroke:#333
style C fill:#cfc,stroke:#333
style D fill:#fcc,stroke:#333
style E fill:#cff,stroke:#333
style F fill:#ffc,stroke:#333
style G fill:#fcf,stroke:#333
style H fill:#cff,stroke:#333
style I fill:#ffc,stroke:#333
style J fill:#cfc,stroke:#333
style K fill:#fcc,stroke:#333
style L fill:#ffc,stroke:#333
Fig. 45: Electrical drawings RVD 355 DC AT
A: Control board
1: Compressor
2: To indoor unit
3: Power supply
4: 4-way reversing valve
5: Crankcase heating
6: Condensate tray heating
7: Condenser
8: AC fan motor
9: Electronic E-valve
10: DC fan motor
11: Air inlet temperature probe
12: Temperature probe for condenser outlet
13: Temperature probe for heat gas line
REMKO RVD series
Outdoor unit RVD 525 DC AT

flowchart
graph TD
A["Control Panel"] --> B["CN 1A"]
B --> C["BNP"]
C --> D["BNP"]
D --> E["BNP"]
E --> F["BNP"]
F --> G["BNP"]
G --> H["BNP"]
H --> I["BNP"]
I --> J["BNP"]
J --> K["BNP"]
K --> L["BNP"]
L --> M["BNP"]
M --> N["BNP"]
N --> O["BNP"]
O --> P["BNP"]
P --> Q["BNP"]
Q --> R["BNP"]
R --> S["BNP"]
S --> T["BNP"]
T --> U["BNP"]
U --> V["BNP"]
V --> W["BNP"]
W --> X["BNP"]
X --> Y["BNP"]
Y --> Z["BNP"]
Z --> AA["BNP"]
AA --> AB["BNP"]
AB --> AC["BNP"]
AC --> AD["BNP"]
AD --> AE["BNP"]
AE --> AF["BNP"]
AF --> AG["BNP"]
AG --> AH["BNP"]
AH --> AI["BNP"]
AI --> AJ["BNP"]
AJ --> AK["BNP"]
AK --> AL["BNP"]
AL --> AM["BNP"]
AM --> AN["BNP"]
AN --> AO["BNP"]
AO --> AP["BNP"]
AP --> AQ["BNP"]
AQ --> AR["BNP"]
AR --> AS["BNP"]
AS --> AT["BNP"]
AT --> AU["BNP"]
AU --> AV["BNP"]
AV --> AW["BNP"]
AW --> AX["BNP"]
AX --> AY["BNP"]
Fig. 46: Electrical drawings RVD 525 DC AT
A: Control board
B: Auxiliary circuit board
1: Compressor
2: Communication line to indoor unit
3: Supply line to indoor unit
4: Power supply
5: 4-way reversing valve
6: Crankcase heating
7: Condensate tray heating
8: AC fan motor
9: Electronic E-valve
10: DC fan motor
11: Air inlet temperature probe
12: Temperature probe for condenser outlet
13: Temperature probe for heat gas line
Outdoor unit RVD 685 DC AT

Fig. 47: Electrical drawings RVD 685 DC AT
A: Control board
B: Inverter board
1: Klixon
2: Low pressure switch
3: High pressure switch
4: Air inlet temperature probe
5: Temperature probe for condenser outlet
6: Temperature probe for heat gas line
7: Condensate tray heating
8: Crankcase heating
9: 4-way reversing valve
10: Communication line to indoor unit
11: Power supply
12: Supply line to indoor unit
13: DC fan motor
14: Compressor
15: Transformer
REMKO RVD series
Outdoor unit RVD 1055 DC AT

flowchart
graph TD
subgraph_Component_A["Component A"]
A1["CN1"] --> A2["CN3"]
A1 --> A3["CN5"]
A2 --> A4["CN7"]
A3 --> A5["CN9"]
A4 --> A6["CN10"]
A5 --> A7["CN11"]
A6 --> A8["CN12"]
A7 --> A9["CN13"]
A8 --> A10["CN14"]
A9 --> A11["CN15"]
A10 --> A12["CN16"]
A11 --> A13["CN17"]
A12 --> A14["CN18"]
A13 --> A14a["CN15"]
A14 --> A14b["CN14"]
A14b --> A14c["CN13"]
end
subgraph_Component_B["Component B"]
B1["CN5CN6CN7"] --> B2["rot"]
B2 --> B3["weiss"]
B2 --> B4["blau"]
end
subgraph_Component_C["Component C"]
C1["CN3"] --> C2["CN3"]
C2 --> C3["FM1"]
C3 --> C4["CAP1"]
C4 --> C5["~"]
C5 --> C6["HEAT_Y"]
C6 --> C7["HEAT_D"]
C7 --> C8["SV"]
end
subgraph_Component_D["Component D"]
D1["CN34"] --> D2["CN35"] --> D3["CN11"] --> D4["CN7"]
D4 --> D5["CN20-NL2"]
D5 --> D6["CN30"]
D6 --> D7["orange"]
D7 --> D8["orange"]
D8 --> D9["orange"]
D9 --> D10["BLA"]
D10 --> D11["BLA"]
D11 --> D12["BLA"]
D12 --> D13["L-PRO H-PRO"]
end
subgraph_Component_E["Component_E"]
E1["PE2"] --> E2["PE1"]
end
subgraph_Component_F["Component_F"]
F1["N CN2"] --> F2["L1 CN4"] --> F3["L2 CN8CN6"] --> F4["PE3"] --> F5["CN21"]
F5 --> F6["SW"]
end
subgraph Component_G fill:#f9f,stroke:#333
end
subgraph Component_H fill:#ccf,stroke:#333
end
subgraph Component_I
I1["SW"] --> I2["BLA"]
I2 --> I3["BLA"]
I3 --> I4["BLA"]
I4 --> I5["BLA"]
I5 --> I6["BLA"]
I6 --> I7["BLA"]
I7 --> I8["BLA"]
I8 --> I9["BLA"]
I9 --> I10["BLA"]
I10 --> I11["BLA"]
I11 --> I12["BLA"]
I12 --> I13["BLA"]
I13 --> I14["L-PRO H-PRO"]
end
subgraph Component_J
J1["SW"] --> J2["BLA"] --> J3["BLA"] --> J4["BLA"] --> J5["BLA"] --> J6["BLA"] --> J7["BLA"] --> J8["BLA"] --> J9["BLA"] --> J10["BLA"] --> J11["BLA"] --> J12["BLA"] --> J13["L-PRO H-PRO"]
end
subgraph Component_K
K1["TP 10"] --> K2["T4 11"] --> K3["T3 12"]
end
subgraph Component_L
L1["TW 10"] --> L2["TW 10"] --> L3["TW 10"] --> L4["TW 10"] --> L5["TW 10"] --> L6["TW 10"] --> L7["TW 10"] --> L8["TW 10"] --> L9["TW 10"] --> L10["TW 10"] --> L11["TW 10"] --> L12["TW 10"] --> L13["TW 10"] --> L14["TW 10"] --> L15["TW 10"] --> L16["TW 10"] --> L17["TW 10"] --> L18["TW 10"] --> L19["TW 10"] --> L20["TW 10"] --> L21["TW 10"] --> L22["TW 10"] --> L23["TW 10"] --> L24["TW 10"] --> L25["TW 10"] --> L26["TW 10"] --> L27["TW 10"] --> L28["TW 10"] --> L29["TW 10"] --> L30["TW 10"] --> L31["TW 10"] --> L32["TW 10"] --> L33["TW 10"] --> L34["TW 10"] --> L35["TW 10"] --> L36["TW 10"] --> L37["TW 10"] --> L38["TW 10"] --> L39["TW 10"] --> L40["TW 10"] --> L41["TW 10"] --> L42["TW 10"] --> L43["TW 10"] --> L44["TW 10"] --> L45["TW 10"] --> L46["TW 10"] --> L47["TW 10"] --> L48["TW 10"] --> L49["TW 10"] --> L50["TW 10"] --> L51["TW 10"] --> L52["TW 10"] --> L53["TW 10"] --> L54["TW 10"] --> L55["TW 10"] --> L56["TW 10"] --> L57["TW 10"] --> L58["TW 10"] --> L59["TW 10"] --> L60["TW 10"]
subgraph Component_M
M["M 9"] --> N["MPTP ⑩"]
N["MPTP ⑪"]
N[MPTP ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪T MTPTP ⑫
N[MPTP ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT
N[MPTP ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT
N[MPTP ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪TMT ⑪CPTP
N[MPTP ⑪TMT
N[MPTP
N[MPTP
N[MPTP
N[MPTP
N[MPTP
N[MPTP
N[MPTP
N[MPTP
N[MPTP
N[MPTP
N[MPTP
N[MPTP
N[MPTP
N[MPTP
N[MPTP
N[MPTP
N[MPTP
NMPTP
NMPTP
NMPTP
NMPTP
NMPTP
NMPTP
NMPTP
NMPTP
NMPTP
NMPTP
NMPTP
end
Fig. 48: Electrical drawings RVD 1055 DC AT
A: Control board
B: Inverter board
C: Control board DC fan motor
1: Transformer
2: Magnetic ring
3: Compressor
4: DC fan motor
5: AC fan motor
6: Crankcase heating
7: Condensate tray heating
8: 4-way reversing valve
9: Electronic E-valve
10: Temperature probe for heat gas line
11: Temperature probe for condenser outlet
12: Air inlet temperature probe
13: Low pressure switch
14: High pressure switch
15: Communication line to indoor unit
16: Supply line to indoor unit
17: Power supply
8.6 Connection of a superordinate controller provided by the customer
Units of type RVD can be switched on and off by a superordinate controller. In order to utilise the potential-free contact for externally switching the unit on and off, it is first necessary to remove the jumper (JR6) at the indoor unit control board. The contacts are then available.

Fig. 49: Removing the jumper
The building controller is now connected via the two outer contacts of the plug labelled ON - OFF. If the connection between the two contacts is open, the system is in stand-by mode. The "Operation LED" and the "Timer LED" blink alternately. The unit can no longer be switched on using the remote control.

Fig. 50: Open contact
1: Stand-By
If the connection between the two contacts is closed, the unit is reactivated and switches to the last operating mode used.

Fig. 51: Closed contact
2: Operation
REMKO RVD series
9 Before commissioning
After leak testing has been successfully completed, connect the vacuum pump via the pressure gauge station to the valve connections on the outdoor unit (see chapter "Leak testing") and create a vacuum.
Perform the following checks prior to putting the unit into operation for the first time and after any work on the cooling cycle. Record the results in the commissioning report:
- Check all refrigerant piping and valves for leak-tightness using leak detection spray or soapy water.
- Check the refrigerant piping and insulation for damage.
- Check the electrical connection between the indoor unit and the outdoor unit for correct polarity.
- Check that all fastenings, mountings, etc. are firm and at the correct level.
10 Commissioning
! NOTICE!
Commissioning should only be performed by specially trained personnel and documented after the certificate has been issued. Observe the operating manuals for the indoor unit and outdoor unit when commissioning the entire system.
Once all the components have been connected and tested, the system can be put into operation. A functional check should be performed to verify its correct function and identify any unusual operating behaviour prior to handing it over to the operator.
! NOTICE!
Check that the shut-off valves and valve caps are tight after carrying out any work on the cooling cycle. Use appropriate sealant products as necessary.
Functional checks and test run
Check the following points:
- Leak-tightness of the refrigerant piping.
■ Compressor and fan running smoothly.
In cooling mode, cold air output by the indoor unit, and warm air output by the outdoor unit.
■ Function test of the indoor unit and all program sequences.
Check of the surface temperature of the suction pipe and that the vaporiser is not overheating. To measure the temperature, hold the thermometer to the suction pipe and subtract the boiling point temperature reading on the pressure gauge from the measured temperature. - Record the measured temperatures in the commissioning report.
Function test of the cooling and heating modes
- Remove the protective caps from the valves.
- Start the commissioning procedure by briefly opening the shut-off valves on the outdoor unit until the pressure gauge indicates a pressure of approx. 2 bar.
- Check all connections for leaks with leak detection spray and suitable leak detectors.
- If no leaks are found, fully open the shut-of f valves by turning them anti-clockwise using a spanner. If leaks are found, remedy the faulty connection. It is imperative that the vacuum creation and drying steps are repeated.
- Activate the main circuit breaker or fuse.
- Use the remote control to switch on the unit and select the cooling mode, maximum fan speed and lowest target temperature.
- Check the overheating, outside, inside, outlet and vaporisation temperatures and record the measured values in the commissioning report. Check the correct function and settings of all regulation, control and safety devices.
- Check the unit control system using the functions described in the chapter "Operation". Timer, temperature setting, fan speeds and switching to ventilation or dehumidification mode.
- Check the correct function of the condensate drainage line by pouring distilled water into the condensate tray. A bottle with a spout is recommended for pouring the water into the condensate tray.
- Switch the indoor unit to heating mode.
- During the test run, check the functionality of all of the previously described safety devices.
- Record the measured values into the commissioning report and familiarise the operator with the system.
- Remove the pressure gauge. Check that seals have been fitted in the sealing caps.
- Re-install all disassembled parts.
11 Shutdown
Temporary shutdown
- Let the indoor unit run for 2 to 3 hours in recirculation mode, or in cooling mode at maximum temperature, to extract any residual humidity from the unit.
- Shut down the system using the remote control.
- Switch of unit. f the electrical power supply to the
- Cover the unit as far as possible with plastic foil in order to protect it from the influences of weather.
Permanent shutdown
Ensure that units and components are disposed of in accordance with local regulations, e.g. through authorised disposal and recycling specialists or at collection points.
REMKO GmbH & Co. KG or your contractual partner will be pleased to provide a list of certified firms in your area.
12 Troubleshooting, customer service and fault analysis
12.1 Troubleshooting and customer service
The unit and components are manufactured using state-of-the-art production methods and tested several times to verify their correct function. However, if malfunctions should occur, please check the functions as detailed in the list below. For systems with an indoor unit and outdoor unit, refer to the chapter "Troubleshooting and customer service" in both operating manuals. Please inform your dealer if the unit is still not working correctly after all function checks have been performed!
Operational malfunctions
| Malfunction Possible causes | Checks Remedial measures | ||
| The unit does not start or switches itself off | Power failure, under-voltage, defective mains fuse / main switch in OFF position | Does all other electrical equipment function correctly? | Check the voltage and if necessary, wait for it to come back on |
| Damaged power supply Does all other elec. equipment function correctly? | Repair by specialist firm | ||
| Wait time after switching on is too short | Have approx. 5 minutes elapsed since the restart? | Schedule longer wait times | |
| Temperature outside operating range | Are the fans in the indoor unit and outdoor unit working correctly? | Observe temperature ranges of indoor unit and outdoor unit | |
| Electrical surges caused by thunderstorms | Have there been lightning strikes in the area recently? | Switch off the mains breaker and switch it back on. Have it inspected by a specialist | |
| Malfunction of the external condensate pump | Has the pump shut down due to a malfunction? | Check and if necessary clean the pump | |
| High-pressure / low-pressure switches have triggered | Check refrigerant pressure and look for leaks if necessary | Rectify leakage and re-start | |
| The unit does not respond to the remote control | Transmission distance too far / receiver affected by interference | Does the indoor unit beep when pressing a key? | Reduce the distance to less than 6 m or change position |
| Defective remote control Is the unit running in manual mode? | Replace the remote control | ||
| Receiver or transmitter unit exposed to excessive solar radiation | Does it function correctly in the shade? | Place the receiver and/or transmitter unit in the shade | |
| Electromagnetic fields are interfering with transmission | Does it function after removing potential sources of interference? | Signal is not transmitted when interference sources are operational | |
| Key in remote control jammed / two buttons pressed at same time | Does the “Transmitting” symbol appear on the display? | Release the key / only press one key | |
| Batteries in remote control are flat | Have new batteries been inserted? Is the display incomplete? | Insert new batteries | |
| Malfunction Possible causes | Checks Remedial measures | ||
| The unit is running but only provides reduced or no cooling or heating capacity | Filter is dirty / air inlet / outlet opening is blocked by debris | Have the filters been cleaned? | Clean the filters |
| Windows and doors open. Heating / cooling load has increased | Have structural / usage modifications been made? | Close windows and doors / install additional units | |
| Neither cooling nor heating mode has been set | Does the cooling symbol appear on the display? | Correct the settings for the unit | |
| Fins on outdoor unit blocked by foreign objects | Is the fan on the outdoor component running? Are the fins unobstructed? | Check the fan or winter fan speed control, reduce the air resistance | |
| Leaking cooling cycle Are there signs of frost on the exchanger fins of the indoor unit? | Repair by specialist | ||
| Outdoor unit iced up Check outdoor unit. Has the cassette probe on the outdoor unit been correctly positioned? | De-ice and fit the probe at the point where the most ice forms | ||
| Condensate discharge on unit | Drainage pipe on collection container clogged / damaged | Can the condensate drain off without any obstruction? | Clean the drainage pipe and collection container |
| Faulty external condensate pump or float | Is the collection tray full of water and the pump not running? | Call out a specialist to replace the pump | |
| Condensate has not drained away and has collected in the condensate drainage line | Is there an incline on the condensate drainage line? Check there is no blockage in the pipe. | Route the condensate drainage line with an incline and clean it. | |
| Condensate does not drain off | Are the condensate drainage lines unblocked and is there a steady incline? Are the condensate pump and liquid level switch functioning correctly? | Route the condensate drainage line with an incline and clean it. If the liquid level switch or the condensate pump is defective, have them replaced | |
| Float is stuck or jammed due to excessive dirt | Are the LEDs on the receiver unit of the indoor unit flashing? | Should be cleaned by specialist firm | |

NOTE
If the outdoor unit makes noises at low outside temperatures, even although it is switched off, this is not a malfunction. This is the winding of the compressor being run briefly in order to heat up the oil within it and also to guarantee the viscosity at low ambient temperatures. If you do not use the unit in the winter then you can switch off the breaker. Switch it back on again at least 12 hours before the next time that the unit will be required!
REMKO RVD series
Malfunction indicated by flashing code RVD 355-525 DC
| Error description | Number of flashes per second) 1) | LED timer 2) | Error code |
| EEPROM error, indoor unit 1 OFF E0 | |||
| Communication error between indoor unit and outdoor unit 2 OFF E1 | |||
| Evaporator fan motor speed control not OK 4 OFF E3 | |||
| Room air temperature probe faulty 5 OFF E4 | |||
| Evaporator temperature probe faulty 6 OFF E5 | |||
| No cooling capacity after 30 minutes 7 OFF EC | |||
| Condensate pump liquid level switch triggered 8 OFF EE | |||
| Safety shut-down due to increased power consumption 1 ON F0 | |||
| Outdoor unit air inlet temperature probe faulty 2 ON F1 | |||
| Condenser outlet temperature probe faulty | 3 ON F2 | ||
| Temperature probe for heat gas line faulty | 4 ON F3 | ||
| EEPROM error, outdoor unit | 5 ON F4 | ||
| Condenser fan speed control not OK | 6 ON F5 | ||
| Suction pipe temperature probe in AT faulty | 7 ON F6 | ||
| Fin motor defective or not connected | F7 | ||
| Inverter error | 1 | FLASHES | P0 |
| Over/undervoltage error | 2 | FLASHES | P1 |
| Safety shut-down compressor excess temperature | 3 | FLASHES | P2 |
| Safety shut-down due to low outside temperature | 4 | FLASHES | P3 |
| Compressor control faulty | 5 | FLASHES | P4 |
| Mode conflict | 6 | FLASHES | P5 |
| Low pressure alarm | 7 | FLASHES | P6 |
^1) LED [1] in the bottom figure
2) LED [2] in the bottom figure

Fig. 52: Malfunction indicated by flashing code RVD 355-525 DC
Malfunction indicated by flashing code RVD 685-1055 DC
| Error description | Number of flashes per second) 1) | LED timer 2) | Error code 3) |
| EEPROM error, indoor unit 1 OFF E0 | |||
| Communication error between indoor unit and outdoor unit 2 OFF E1 | |||
| Evaporator fan motor speed control not OK 4 OFF E3 | |||
| Room air temperature probe faulty 5 OFF E4 | |||
| Evaporator temperature probe faulty 6 OFF E5 | |||
| No cooling capacity after 30 minutes 7 OFF EC | |||
| Condensate pump liquid level switch triggered 8 OFF EE | |||
| Safety shut-down due to increased power consumption 1 ON F0 | |||
| Outdoor unit air inlet temperature probe faulty 2 ON F1 | |||
| Condenser outlet temperature probe faulty | 3 ON F2 | ||
| Temperature probe for heat gas line faulty | 4 ON F3 | ||
| EEPROM error, outdoor unit | 5 ON F4 | ||
| Condenser fan speed control not OK | 6 ON F5 | ||
| Temperature probe suction pipe in outdoor unit faulty | 7 ON F6 | ||
| Fin motor defective or not connected | F7 | ||
| Inverter error | 1 | FLASHES | P0 |
| Over/undervoltage error | 2 | FLASHES | P1 |
| Safety shut-down compressor excess temperature | 3 | FLASHES | P2 |
| Safety shut-down due to low outside temperature | 4 | FLASHES | P3 |
| Compressor control faulty | 5 | FLASHES | P4 |
| Mode conflict | 6 | FLASHES | P5 |
| Low pressure alarm | 7 | FLASHES | P6 |
^1) LED [1] in the bottom figure
2) LED [2] in the bottom figure
^3) LED [3] in the bottom figure

Fig. 53: Malfunction indicated by flashing code RVD 685-1055 DC
REMKO RVD series
12.2 Indoor unit fault analysis
| Error code: E0 / F4 | |
| Reason: The control board of the outdoor unit or indoor unit cannot read the unit memory (EEPROM) | |
| Cause: | Installation errorControl boards of outdoor unit or indoor unit defective |
| Switch off voltage, switch on again 2 minutes later. Is the error still present? | |
![]() | |
| Replace the circuit boards of the outdoor unit and indoor unit in turn, in order to locate the defective EEPROM | |
| Error code: E1 | ||
| Reason: The indoor unit does not receive a signal from the outdoor unit within 110 seconds. | ||
| Cause: | Electrical connection not configured correctlyControl boards outdoor unit or indoor unit defective | |
| Switch off voltage, switch on again 2 minutes later. Is the error still present? | ||
![]() | ||
| Measure the voltage between the “S” and “N” terminals of the outdoor unit. Is the measured value positive? | NO→ | Check electrical connections in the indoor unit.Are they OK? |
![]() | ↓YES | |
| Check electrical connections in the outdoor unit. Are they OK? | Replace the control boards of the indoor unit. Is the fault remedied? | |
![]() | ↓NO | |
| Is the transformer OK? | Replace the control boards of the outdoor unit | |
| NO→ | Replace the transformer | |
![]() | ||
| Replace the control boards of the outdoor unit.Is the fault remedied? | ||
![]() | ||
| Replace the control boards of the indoor unit | ||
REMKO RVD series
| Error code: E3 / F5 | ||
| Reason: If the fan speed of the indoor unit/outdoor unit falls below 300 rpm, the unit switches off and the display shows error code E3 or E5 | ||
| Cause: | Electrical connection faultyEvaporator fan wheel defectiveEvaporator fan motor defectiveControl board faulty | |
| Switch off voltage, switch on again 2 minutes later. Is the error still present? | ![]() | The unit operates normally. |
| ↓YES | ||
| De-energise the unit and attempt to turn the fan wheel by hand. Does it rotate freely? | ![]() | Check the motor and the fan wheel bearing, and replace the defective parts. |
| ↓YES | ||
| Check the electrical connections.Are these correctly implemented? | ![]() | Correctly establish the electrical connection |
| ↓YES | ||
| Measure the voltage at the corresponding connector plug on the control board (see section & 'Procedure' on page 57). Does the measured voltage lie within the tolerance range? | ![]() | Replace the control board. |
| ↓YES | ||
| Replace the fan motor. Is the fault remedied? | ![]() | |
Procedure
DC fan motor of the indoor unit (control chip is installed in the motor):
Switch on the voltage to the unit. In standby mode, measure the unit between terminals 1-3 and 4-3 of the connector plug. Check the measured values against those listed in the table below. If these differ, there is a problem with the control board and it must be replaced.

natural_image
Technical line drawing of a 13456 connector pinout (no text or symbols on the diagram itself)Fig. 54: Motor measurements
| Terminal Colour Voltage | ||
| 1 Red 280V~380 V | ||
| 2 --- --- | ||
| 3 Black 0 V | ||
| 4 White 17-17.5V | ||
| 5 Yellow | 0~5.6V | |
| 6 | Blue | 17-17.5V |
DC fan motor of the outdoor unit (control chip is installed in the motor):
Measure the resistance between terminals 1-3 and 4-3. This should be roughly identical. If the resistance deviates significantly, assume that the motor is defective and must be replaced.
REMKO RVD series
| Error code: EC | ||
| Reason: The evaporator probe T2 measures the actual value with the compressor start and takes this as the reference value T_Start . If, 5 minutes after the compressor start, the value T_Start has not dropped by 2 °C for at least 4 seconds then the system assumes that the refrigerant is low. The measurement is performed a total of 3 times before the display shows the error code "EC". | ||
| Cause: | Refrigerant low or cooling circuit blockedEvaporator probe T2 defectiveIndoor unit control board defective | |
| Switch off voltage, switch on again 2 minutes later. Is the error still present? | ||
![]() | ||
| Check whether the indoor unit blows out cold air. | YES→ | Check the position and function of the evaporator probe T2. Is it correctly seated and with the correct resistance? |
![]() | ↓YES | |
| Check the cooling circuit for leaks. Leaks found? | Exchange the control boards of the indoor unit. | |
| YES→ | Remedy leaks and put the unit back into operation. | |
![]() | ||
| Check the cooling circuit for any blockages. Are the shut-off valves on the outdoor unit open? | ||
| Error code: E4 / E5 / F1 / F2 / F3 | ||
| Reason: If the test voltage of the probes is lower than 0.06 V or higher than 4.94 V then the display shows the error code of the corresponding probe. | ||
| Cause: | Electrical connection faultyTemperature probe defectiveControl board defective | |
| Check the connecting cable between the control board and the temperature probe. Is it OK and correctly connected? | NO→ | Establish a proper connection. |
| ↓YES | ||
| Check the probe for correct resistance, depending on the temperature (see resistance table) | NO→ | Replace the probe. |
| ↓YES | ||
| Replace the corresponding control board. | ||

Fig. 55: Check the probes
REMKO RVD series
| Error code: F0 | |||
| Reason: Safety shutdown due to overly high current consumption of individual unit components | |||
| Cause: | Faulty power supplyCooling circuit blockedFaulty control boardElectrical connections faultyCompressor defective | ||
| Check the supply voltage. Is this correct? | NO→ | Switch the unit off and ensure correct supply voltage. | |
| ↓YES | |||
| Check the cooling circuit for any blockages. Is the cooling circuit OK? | NO→ | Remove the blockage (shut-off valve open?) | |
| ↓YES | |||
| Check the winding resistances of the compressor. Are they OK? | NO→ | Replace the compressor. | |
| ↓YES | |||
| Check the electrical connections. Are these correctly implemented? | NO→ | Replace or correct the electrical connections. | |
| ↓YES | |||
| Does the transformer operate fault-free? | NO→ | Replace the transformer or control boards of the outdoor unit. | |
| ↓YES | |||
| Replace the outdoor unit. | |||
| Error code: P0 | ||
| Reason: If the power supply to the compressor controller is faulty, the display shows the error code “P0” and the unit switches off | ||
| Cause: | External enabling contact openElectrical connection faultyFaulty control boardCondenser fan motor defective or blockedCompressor defective | |
| Check the external enabling contact CN23 and the jumper JR6. Are both contacts open? (See Chapter 8.6 ‘Connection of a superordinate controller provided by the customer’ on page 47) | YES→ | Close the external enabling contact CN23 or the jumper JR6. |
| ↓NO | ||
| Check the connecting cables between the control board and compressor? Are they faulty? | YES→ | Establish a correct connection between the control board and compressor. |
| ↓NO | ||
| Check the inverter controller (see section ‘‘Check the inverter controller’ on page 62). Fault eliminated? | NO→ | Replace the control board. |
| ↓YES | ||
| Check the condenser fan motor. Is it working correctly? | NO→ | See troubleshooting fault F5 |
| ↓YES | ||
| Check the winding resistances of the compressor. Are they OK? | NO→ | Replace the compressor. |
| ↓YES | ||
| Exchange the control boards of the outdoor unit. | ||
REMKO RVD series
Check the inverter controller
Switch off the power supply to the unit. Wait until the capacitors are fully discharged and disconnect the compressor from the control board.
Check the resistances at the outputs of the control board with the aid of a digital voltmeter as follows:
| Voltmeter Normal resistance | ||
| (+) Red (-) Black | ||
| U | N | ∞(multiple MΩ) |
| V | ||
| W | ||
| (+) Red | ||
| Error code: P1 | |
| Reason: Overvoltage or undervoltage protection has tripped | |
| Cause: | ■ Faulty supply voltage■ Refrigerant low or cooling circuit blocked■ Faulty control board |
| Check the power supply. Is the supply voltage correct? | NO→ | Switch the unit off and have the power supply checked/corrected. |
| ↓YES | ||
| Check the electrical connections. Are they OK? | NO→ | Replace the electrical connections. |
| ↓YES | ||
| Switch the power on and put the unit into standby mode. Measure the voltage on the board, at contacts "P" and "N". This should be approx. 310 V, 340 V or 380 V DC. Now start the unit. The voltage between "P" and "N" should now be between 220-400V. Is the correct voltage applied? | NO→ | Replace the control board. |
| ↓YES | ||
| Check the transformer. Is a defect present? | NO→ | Replace the control board. |
| ↓YES | ||
| Replace the transformer. | ||
| Error code: P2 (with units with a thermal contact) | |||
| Reason: If the test voltage of the thermal contact does not lie at 5 V, then the display shows the error message “P2” | |||
| Cause: | Faulty supply voltageRefrigerant low or cooling circuit blockedFaulty control board | ||
| Check the air flow volumes of the indoor unit and outdoor unit. Are they blocked or dirty? | ![]() | Clean the filter or heat exchanger and ensure a sufficient air flow volume. | |
![]() | |||
| Switch off the power supply to the unit and switch it on again after 10 mins.Does the unit start up? | |||
![]() | |||
| Check the temperature of the compressor. Has it heated up? | NO→ | Check the thermal contact. Is it correctly connected? | |
| ↓YES | ↓NO | ||
| Measure the resistance of the thermal contact.Is it 0? | Connect it correctly. | ||
![]() | ↓YES | NO→ | |
| Check the cooling circuit. Is it OK? | ![]() | Replace the control board of the outdoor unit. | |
REMKO RVD series
| Error code: P4 | ||
| Reason: Safety shutdown of inverter controller. Internal system monitoring triggered (e.g. communication problem between board and compressor, the compressor speed is not OK) | ||
| Cause: | ■ Faulty electrical connections■ Inverter regulation on board defective■ Condenser fan motor defective■ Compressor defective■ Control board defective | |
| Check the electrical connection between the control board and compressor. Are these correctly implemented? | YES→ | Establish a proper connection. |
| ↓NO | ||
| Check the inverter controller. Is this functional? | NO→ | Replace the control board. |
| ↓YES | ||
| Check the condenser fan motor. Is it OK? | NO→ | Follow the instructions for troubleshooting fault F5 |
| ↓YES | ||
| Check the winding resistances of the compressor. Are they OK? | NO→ | Replace the compressor |
| ↓YES | ||
| Replace the control boards of the outdoor unit. | ||
Check individual components
Check the temperature probes
Disconnect the temperature probe from the control board and measure the resistance on the plug's contacts.

1: Multimeter
| Error code: dF |
| Reason: The unit is in heating mode and the outdoor unit is being defrosted. After the defrost phase, the indoor unit automatically switches back to the last operating mode. |
12.3 Resistances of the temperature probes
Probe T1, T2, T3 and T4
| Temp. (°C) | Resistance (kΩ) | Temp. (°C) | Resistance (kΩ) |
| -20 115.27 12 18.72 | |||
| -19 108.15 13 17.80 | |||
| -18 101.52 14 16.93 | |||
| -17 96.34 15 16.12 | |||
| -16 89.59 16 15.34 | |||
| -15 84.22 17 14.62 | |||
| -14 79.31 18 13.92 | |||
| -13 74.54 19 13.26 | |||
| -12 70.17 20 12.64 | |||
| -11 66.09 21 12.06 | |||
| -10 62.28 22 11.50 | |||
| -9 58.71 23 10.97 | |||
| -8 56.37 24 10.47 | |||
| -7 52.24 25 10.00 | |||
| -6 49.32 26 9.55 | |||
| -5 46.57 27 9.12 | |||
| -4 44.00 28 8.72 | |||
| -3 41.59 29 8.34 | |||
| -2 39.82 30 7.97 | |||
| -1 37.20 31 7.62 | |||
| 0 35.20 32 7.29 | |||
| 1 33.33 33 6.98 | |||
| 2 31.56 34 6.68 | |||
| 3 29.91 35 6.40 | |||
| 4 28.35 36 6.13 | |||
| 5 26.88 37 5.87 | |||
| 6 25.50 38 5.63 | |||
| 7 24.19 39 5.40 | |||
| 8 22.57 40 5.18 | |||
| 9 21.81 41 4.96 | |||
| 10 20.72 42 4.76 | |||
| 11 19.69 43 4.57 |
| Temp. (°C) | Resistance (kΩ) | Temp. (°C) | Resistance (kΩ) |
| 44 4.39 | 79 1.21 | ||
| 45 4.21 | 80 1.17 | ||
| 46 4.05 | 81 1.14 | ||
| 47 3.89 | 82 1.10 | ||
| 48 3.73 | 83 1.06 | ||
| 49 3.59 | 84 1.03 | ||
| 50 3.45 | 85 1.00 | ||
| 51 3.32 | 86 0.97 | ||
| 52 3.19 | 87 0.94 | ||
| 53 3.07 | 88 0.91 | ||
| 54 2.96 | 89 0.88 | ||
| 55 2.84 | 90 0.85 | ||
| 56 2.74 | 91 0.83 | ||
| 57 2.64 | 92 0.80 | ||
| 58 2.54 | 93 0.78 | ||
| 59 2.45 | 94 0.75 | ||
| 60 2.36 | 95 0.73 | ||
| 61 2.27 | 96 0.71 | ||
| 62 2.19 | 97 0.69 | ||
| 63 2.11 | 98 0.67 | ||
| 64 2.04 | 99 0.65 | ||
| 65 1.97 | 100 0.63 | ||
| 66 1.90 | 101 0.61 | ||
| 67 1.83 | 102 0.59 | ||
| 68 1.77 | 103 0.58 | ||
| 69 1.71 | 104 0.56 | ||
| 70 1.65 | 105 0.54 | ||
| 71 1.59 | 106 0.53 | ||
| 72 1.54 | 107 0.51 | ||
| 73 1.48 | 108 0.50 | ||
| 74 1.43 | 109 0.48 | ||
| 75 1.39 | 110 0.47 | ||
| 76 1.34 | 111 0.46 | ||
| 77 1.29 | 112 0.45 | ||
| 78 1.25 | 113 0.43 |
REMKO RVD series
| Temp. (°C) | Resistance (kΩ) | Temp. (°C) | Resistance (kΩ) |
| 114 0.42 | 127 0.30 | ||
| 115 0.41 | 128 0.29 | ||
| 116 0.40 | 129 0.28 | ||
| 117 0.39 | 130 0.28 | ||
| 118 0.38 | 131 0.27 | ||
| 119 0.37 | 132 0.26 | ||
| 120 0.36 | 133 0.26 | ||
| 121 0.35 | 134 0.25 | ||
| 122 0.34 | 135 0.25 | ||
| 123 0.33 | 136 0.24 | ||
| 124 0.32 | 137 0.23 | ||
| 125 0.32 | 138 0.23 | ||
| 126 0.31 | 139 0.22 |
Probe T5
| Temp. (°C) | Resistance (kΩ) | Temp. (°C) | Resistance (kΩ) |
| -20 542.7 -2 200.7 | |||
| -19 511.9 -1 190.5 | |||
| -18 483.0 0 180.9 | |||
| -17 455.9 1 171.9 | |||
| -16 430.5 2 163.3 | |||
| -15 406.7 3 155.2 | |||
| -14 384.3 4 147.6 | |||
| -13 363.3 5 140.4 | |||
| -12 343.6 6 133.5 | |||
| -11 325.1 7 127.1 | |||
| -10 307.7 8 121.0 | |||
| -9 291.3 9 115.2 | |||
| -8 275.9 10 109.8 | |||
| -7 261.4 11 104.6 | |||
| -6 247.8 12 99.69 | |||
| -5 234.9 13 95.05 | |||
| -4 222.8 14 90.66 | |||
| -3 211.4 15 86.49 |
| Temp. (°C) | Resistance (kΩ) | Temp. (°C) | Resistance (kΩ) |
| 16 82.54 51 18.96 | |||
| 17 78.79 52 18.26 | |||
| 18 75.24 53 17.58 | |||
| 19 71.86 54 16.94 | |||
| 20 68.66 55 16.32 | |||
| 21 65.62 56 15.73 | |||
| 22 62.73 57 15.16 | |||
| 23 59.98 58 14.62 | |||
| 24 57.37 59 14.09 | |||
| 25 54.89 60 13.59 | |||
| 26 52.53 61 13.11 | |||
| 27 50.28 62 12.65 | |||
| 28 48.14 63 12.21 | |||
| 29 46.11 64 11.79 | |||
| 30 44.17 65 11.38 | |||
| 31 42.33 66 10.99 | |||
| 32 40.57 67 10.61 | |||
| 33 38.89 68 10.25 | |||
| 34 37.30 69 9.90 | |||
| 35 35.78 70 9.57 | |||
| 36 34.32 71 9.25 | |||
| 37 32.94 72 8.94 | |||
| 38 31.62 73 8.64 | |||
| 39 30.36 74 8.36 | |||
| 40 29.15 75 8.08 | |||
| 41 28.00 76 7.82 | |||
| 42 26.90 77 7.57 | |||
| 43 25.86 78 7.32 | |||
| 44 24.85 79 7.09 | |||
| 45 23.89 80 6.86 | |||
| 46 22.89 81 6.64 | |||
| 47 22.10 82 6.43 | |||
| 48 21.26 83 6.23 | |||
| 49 20.46 84 6.03 | |||
| 50 19.69 85 5.84 | |||
| 86 5.66 | 109 2.86 | ||
| 87 5.49 | 110 2.78 | ||
| 88 5.32 | 111 2.70 | ||
| 89 5.16 | 112 2.63 | ||
| 90 5.00 | 113 2.56 | ||
| 91 4.85 | 114 2.49 | ||
| 92 4.70 | 115 2.42 | ||
| 93 4.56 | 116 2.36 | ||
| 94 4.43 | 117 2.29 | ||
| 95 4.29 | 118 2.23 | ||
| 96 4.17 | 119 2.17 | ||
| 97 4.05 | 120 2.12 | ||
| 98 3.93 | 121 2.06 | ||
| 99 3.81 | 122 2.01 | ||
| 100 3.70 | 123 1.96 | ||
| 101 3.60 | 124 1.91 | ||
| 102 3.49 | 125 1.86 | ||
| 103 3.39 | 126 1.81 | ||
| 104 3.30 | 127 1.76 | ||
| 105 3.20 | 128 1.72 | ||
| 106 3.11 | 129 1.67 | ||
| 107 3.03 | 130 1.63 | ||
| 108 2.94 |
REMKO RVD series
13 Care and maintenance
Regular care and observation of some basic points will ensure trouble-free operation and a long service life.

DANGER!
Prior to performing any work, ensure the equipment is disconnected from the voltage supply and secured to prevent accidental switch-on!

Contact Remko GmbH & Co. KG to sign up for a maintenance contract
Care
- Ensure that the indoor unit and outdoor unit are free of dirt, mould and other deposits.
Only clean the units with a damp cloth. Do not use any caustic, abrasive or solvent-based cleaning products. Do not use a jet of water.
- Clean the fins on the indoor unit and outdoor unit prior to long shutdown periods.
Maintenance
It is recommended that you take out a maintenance contract with an annual service from an appropriate specialist firm.
For systems which operate year-round (e.g. in server rooms), the maintenance intervals must be reduced accordingly.

This enables you to ensure the operational reliability of the plant at all times!
| Type of task Checks / maintenance / inspection | Commis-sioning | Monthly Half-yearly | Yearly |
| General | ● | ● | |
| Check voltage and current | ● | ● | |
| Check function of compressor / fans | ● | ● | |
| Dirt on condenser / evaporator | ● | ● | |
| Check the refrigerant volume | ● | ● | |
| Check condensate drainage | ● | ● | |
| Check insulation | ● | ● | |
| Check moving parts | ● | ● | |
| Sealing test for cooling cycle | ● | ●1) |
1) see note below
Cleaning the cover on the indoor unit
- Disconnect the power supply to the unit.
- Open and fold down the air inlet guard on the cover. The filter is held in place by the flaps screwed in at the side of the guard (Fig. 56).
- Clean the grill and cover with a soft, damp cloth.
- Switch the power supply back on.
Air filter for indoor unit
We recommend cleaning the air filter at intervals of no more than 2 weeks. Reduce this interval if the air is especially dirty.

NOTICE!
Statutory regulations require an annual leak test for the cooling cycle dependant on the refrigerant quantity. Inspection and documentation of the work performed is to be carried out by specialist technicians.
Cleaning the filter
- Disconnect the power supply to the unit.
- Open and fold down the air inlet guard on the cover. The filter is held in place by the flaps screwed in at the side of the guard (Fig. 56).
- T ilt the filter and lift it out (Fig. 56).
- Clean the filter with a commercially available vacuum cleaner (Fig. 57). To do so, turn the dirty side so it is facing upwards.
- Dirt can also be removed by carefully cleaning with lukewarm water and mild cleaning agents. The dirty side should be face down (Fig. 58).
- If water is used, let the filter dry out properly in the air before fitting it back into the unit.
- Carefully insert the filter . Ensure that it locates correctly.
- Close the cover as described above but in reverse order.
- Switch the power supply back on.
- Switch the unit back on.
Cleaning the condensate pump
The indoor unit includes a built-in condensate pump for pumping the condensate to a drain at a higher level.
The pump is more or less maintenance-free. The condensate drainage lines should be checked for dirt at regular intervals. Clean them as required.
If an external pump is also used, observe the maintenance and care instructions in the separate operating instructions.

natural_image
3D rendering of a square metal enclosure with internal grid structure (no text or symbols)Fig. 56: Pull out the filter

natural_image
Illustration of a pen tip touching a grid-patterned surface (no text or symbols)Fig. 57: Cleaning with a vacuum cleaner

natural_image
3D rendering of a metal pipe inserted into a grid-patterned surface (no text or symbols visible)Fig. 58: Cleaning with lukewarm water
REMKO RVD series
14 Exploded view and spare parts lists
14.1 Exploded view - Indoor unit RVD 355-525 DC

Fig. 59: Exploded view of the unit RVD 355-525 DC IT
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
14.2 Spare parts list - Indoor unit RVD 355-525 DC

IMPORTANT!
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)
No. Designation
| 1 Infrared remote control |
| 2 Condensate pump liquid level switch |
| 3 Condensate pump |
| 4 Condensate pump mounting plate |
| 5 Condensate hose |
| 6 Condensate connection |
| 7 Unit trim |
| 8 Display board |
| 9 Condensate tray |
| 10 Temperature probe, evaporator |
| 11 Evaporator |
| 12 Evaporator housing |
| 13 Unit housing |
| 14 Terminal block cover |
| 15 Control board |
| 16 Temperature probe, indoor air |
| 17 Air inlet nozzle |
| 18 Fan wheel |
| 19 Fan motor |
| 20 Fan motor mounting plate |
REMKO RVD series
14.3 Exploded view - Indoor unit RVD 685-1055 DC

Fig. 60: Exploded view of the unit RVD 685-1055 DC IT
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
14.4 Spare parts list - Indoor unit RVD 685-1055 DC

IMPORTANT!
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)
No. Designation
| 1 Infrared remote control |
| 2 Condensate pump liquid level switch |
| 3 Condensate pump |
| 4 Condensate pump mounting plate |
| 5 Condensate hose |
| 6 Condensate connection |
| 7 Unit trim |
| 8 Display board |
| 9 Air filter |
| 10 Liquid level switch mounting plate |
| 11 Condensate tray |
| 12 Evaporator |
| 13 Casing part, left |
| 14 Unit housing |
| 15 Casing part, front |
| 16 Temperature probe, indoor air |
| 17 Condensate tray sealing cap |
| 18 Temperature probe, evaporator |
| 19 Casing part, rear |
| 20 Casing part, right |
| 21 Control board |
| 22 Transformer |
| 23 Air inlet nozzle |
| 24 Fan wheel |
| 25 Fan motor |
| 26 Housing floor |
REMKO RVD series
15 Exploded view - Outdoor unit RVD 355 DC

Fig. 61: Exploded view of the unit RVD 355 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
16 Spare parts list - Outdoor unit RVD 355 DC

IMPORTANT!
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)
No. Designation
| 1 Cover panel |
| 2 Protection grid, front wall |
| 3 Front panel |
| 4 Fan blade |
| 5 Fan motor |
| 6 Fan motor mounting plate |
| 7 Corner panel, left |
| 8 Condenser |
| 9 Air inlet temperature probe |
| 10 Electronic injection valve |
| 11 Shut-off valve, injection pipe |
| 12 4-way reversing valve |
| 13 Shut-off valve, suction pipe |
| 14 Partitioning panel |
| 15 Temperature probe for heat gas line |
| 16 Compressor |
| 17 Floor panel |
| 18 Side panel, right |
| 19 Refrigerant connections cover |
| 20 Terminal block cover |
| 21 Control board |
| 22 Temperature probe for condenser outlet |
| 23 Condensate tray heating |
| 24 Crankcase heating |
| 25 Mounting plate for refrigerant connections |
REMKO RVD series
17 Exploded view - Outdoor unit RVD 525 DC

Fig. 62: Exploded view of the unit RVD 525 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
18 Spare parts list - Outdoor unit RVD 525 DC

IMPORTANT!
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)
No. Designation
| 1 Cover panel |
| 2 Protection grid, front wall |
| 3 Front panel |
| 4 Fan blade |
| 5 Fan motor |
| 6 Fan motor mounting plate |
| 7 Corner panel, left |
| 8 Condenser |
| 9 Air inlet temperature probe |
| 10 Electronic injection valve |
| 11 Shut-off valve, injection pipe |
| 12 4-way reversing valve |
| 13 Shut-off valve, suction pipe |
| 14 Partitioning panel |
| 15 Temperature probe for heat gas line |
| 16 Compressor |
| 17 Floor panel |
| 18 Side panel, right |
| 19 Refrigerant connections cover |
| 20 Control board |
| 21 Auxiliary circuit board |
| 22 Temperature probe for condenser outlet |
| 23 Condensate tray heating |
| 24 Crankcase heating |
REMKO RVD series
19 Exploded view - Outdoor unit RVD 685 DC

Fig. 63: Exploded view of the unit RVD 685 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
20 Spare parts list - Outdoor unit RVD 685 DC

IMPORTANT!
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)
No. Designation
| 1 Cover panel |
| 2 Protection grid, front wall |
| 3 Front panel |
| 4 Fan blade |
| 5 Fan motor |
| 6 Fan motor mounting plate |
| 7 Corner panel, left |
| 8 Condenser |
| 9 Air inlet temperature probe |
| 10 Electronic injection valve |
| 11 Shut-off valve, injection pipe |
| 12 4-way reversing valve |
| 13 Shut-off valve, suction pipe |
| 14 Partitioning panel |
| 15 Temperature probe for heat gas line |
| 16 Compressor |
| 17 Floor panel |
| 18 Side panel, right |
| 19 Refrigerant connections cover |
| 20 Terminal block cover |
| 21 Control board |
| 22 Inverter board |
| 23 Cooling fins |
| 24 Temperature probe for condenser outlet |
| 25 Mounting plate for refrigerant connections |
| 26 Transformer |
| 27 Condensate tray heating |
| 28 Crankcase heating |
REMKO RVD series
21 Exploded view - Outdoor unit RVD 1055 DC

Fig. 64: Exploded view of the unit RVD 1055 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
22 Spare parts list - Outdoor unit RVD 1055 DC

IMPORTANT!
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)
No. Designation
| 1 Cover panel |
| 2 Protection grid, front wall |
| 3 Front panel |
| 4 Fan blade |
| 5 Fan motor |
| 6 Fan motor mounting plate |
| 7 Side panel, left |
| 8 Recessed grip side panel, left |
| 9 Condenser |
| 10 Temperature probe for condenser outlet |
| 11 Temperature probe for heat gas line |
| 12 Air inlet temperature probe |
| 13 4-way reversing valve |
| 14 Shut-off valve, suction pipe |
| 15 Inverter board |
| 16 Control board |
| 17 Liquid separator |
| 18 Transformer |
| 19 Side panel, right |
| 20 Terminal block cover |
| 21 Shut-off valve cover |
| 22 Recessed grip front panel, right |
| 23 Front panel, right |
| 24 Low pressure switch |
| 25 Electronic injection valve |
| 26 Shut-off valve, injection pipe |
| 27 High pressure switch |
| 28 Compressor |
| 29 Partitioning panel |
| 30 Floor panel |
REMKO RVD series
No. Designation
31 Shut-off valve mounting plate
32 Condensate tray heating
33 Crankcase heating
23 Index
C
Care and maintenance 68
Cleaning
Air filter for indoor unit 68
Condensate pump 69
Cover on the indoor unit 68
Condensate drainage connection 31
Customer service 50
D
Display on indoor unit 16
Disposal of equipment 8
E
Electrical drawings ..... 39, 41, 43, 44, 45, 46
Electrical wiring 33
Electrical wiring diagram ..... 35, 36, 37, 38
Environmental protection 8
Exploded view of the unit . . . 70, 72, 74, 76, 78, 80
F
Flashing code, fault display 52, 53
Fresh air connection 27
Fresh air inlet 28
Function test of the cooling and heating modes 49
Functional checks 48
|
Infrared remote control 15
Installation location, selection 24
Installation materials 23
Intended use 7
K
Keys on the remote control 17
M
Maintenance 68
Malfunction indicated by flashing code .... 52, 53
Malfunctions
Checks 50
Possible causes 50
Remedial measures 50
Manual mode 15
Minimum clearances 25
0
Oil return measures 26
Ordering spare parts ..... 71, 73, 75, 77, 79, 81
R
Remote control Keys 17
Resistances Temperature probes 65
S
Safe drainage in the event of leakages ..... 31
Safety
Dangers of failure to observe the safety notes 5
General 5
Identification of notes 5
Instructions for the operator 6
Note for inspection work 6
Note for installation work 6
Note for maintenance work 6
Personnel qualifications 5
Safety-conscious working 6
Unauthorised modification 7
Unauthorised replacement part manufacture . 7
Selection of installation location 24
Setting of
Address assignment MCC-1 ..... 40, 42
Anti-cold air function 40, 42
Automatic restart after power failure . . . . 40, 42
DIP switch 40, 42
Fan behaviour without demand ..... 40, 42
Main / slave 42
Mode priority 40
Power 42
Temperature compensation ..... 40, 42
Shutdown
Permanent 49
Temporary 49
Spare parts list ..... 71, 73, 75, 77, 79, 81
Superordinate controller, connection ..... 47
T
Temperature probes Resistances 65
Test run 48
Troubleshooting and customer service ..... 50
U
Unit installation 26
W
Wall opening 23
Warranty 7
Wired remote control 16
REMKO QUALITY WITH SYSTEMS
Air-Conditioning | Heating | New Energies
REMKO GmbH & Co. KG
Hotline within Germany
+49 (0) 5232 6 06-0
Hotline International

































































