CBPAC59-W - Headphones CIARRA - Free user manual and instructions
Find the device manual for free CBPAC59-W CIARRA in PDF.
User questions about CBPAC59-W CIARRA
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Headphones in PDF format for free! Find your manual CBPAC59-W - CIARRA and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. CBPAC59-W by CIARRA.
USER MANUAL CBPAC59-W CIARRA
natural_image
Line drawing of a white rectangular electronic device with internal cooling fins and ventilation grilles (no text or symbols)Model Number:
CBPAC59-W
SPOT PORTABLE AIR CONDITIONER
MANUAL
CBPAC59-W
Please read this manual before use.
Reminder:
In high temperature or high humidity environments, there will be hot air behind. If used in small spaces, it is recommended to connect the exhaust pipe (optional) or open windows, doors, and exhaust fans.
ENGLISH | Instruction Manual | Page1-28 |
DEUTSCH | Gebrauchsanweisung | Seite29-56 |
FRANÇAIS | Manuel d'instruction | Page57-84 |
VERY IMPORTANT
Do not use your spot portable air conditioner before carefully reading this instruction manual.
Please keep this manual for product warranty and future reference.
CAUTION
- Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
- The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater.)
- Do not pierce or burn.
- Be aware that refrigerants may not contain an odor.
- Appliance shall be installed, operated and stored in a room with a floor area larger than 4m^2 .
- Servicing shall be performed only as recommended by the manufacturer.
- The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
- All working procedure that affects safety means shall only be carried by competent persons.
- "PLEASE MAKE SURE THE PRODUCTVENTILATES ALL THE TIME "! Please ensure that the inlet and outlet ventilation is never blocked.


natural_image
Illustration of an open book with a wrench resting on it (no text or symbols visible)

- Operate this unit on a horizontal surface to avoid water leakage.
- Do not operate this unit in an explosive or corrosive atmosphere.
- Operate this unit in an ambient of 38 degrees centigrade or less.
- Clean air filter periodically to enjoy the most efficient cooling.
- When the unit is shut off, please wait at least 3.5 minutes before restarting to prevent damage to the compressor.
- This unit needs at least 5 Amps of electricity to have its compressor operational. To avoid the household electricity block out, please do not use any extension cord for this unit.
- This unit provides indoor cooling, dehumidification, air fan, and optional air purification.
- When you turn on the unit, the fan will operate, but the compressor will start after the cooling alarm flashes for three minutes.
- When the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid hazard.
- In order to dispose the appliance safely, please remove the batteries from the unit before scrapping it.
- This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
-
The air-conditioner can be connected only to a supply with system impedance no more than 0.219Ω. In case necessary, please consult your supply authority for system impedance information.
-
The appliance shall be installed in accordance with national wiring regulations.
- Do not operate your air conditioner in a wet room such as a bathroom or laundry room. (Do not suitable for the model with window kit).
Transportation, marking and storage for units
- Transport of equipment containing flammable refrigerants Compliance with the transport regulations.
- Marking of equipment using signs Compliance with local regulations.
- Disposal of equipment using flammable refrigerants Compliance with national regulations.
- Storage of equipment/appliances the storage of equipment should be in accordance with the manufacturer's instructions.
- Storage of packed (unsold) equipment Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge. The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.
- The appliance shall be stored so as to prevent mechanical damage from occurring.
- General work area All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.
ATTENTION (Optional exhaust hose and hot air outlet connector, packaged separately)
For effective cooling function, please ensure that the following steps are undertaken:
1) Extend the exhaust hose to a length of not more than 400mm. The exhaust hose must be kept parallel and must not be bent up or down.
2) A distance of 500mm minimum must be kept between the filter side of the unit and wall or any other obstacles".
3) When this appliance starts to defrost, the word “⊕” will be displayed.
4) Please take down the hot air outlet connector and exhaust pipe (as fig 2).

text_image
>500mm 400mm ①
natural_image
Line drawing of a white air conditioner unit with ventilation grilles and a side panel (no text or symbols)
natural_image
Two technical diagrams showing a device with heat exchanger and a handle, both without any text or symbols.CONGRATULATIONS ON YOUR SELECTION OF A QUALITY SPOT PORTABLE AIR CONDITIONER
This Air Treatment Unit has been designed and manufactured to the highest standards of modern engineering.
Our product not only provides you a remote control to help user operate all the functions easily and conveniently but also has below benefits:
- Moves easily from room to room on easy glide castors.
- No installation required-just plug into any household power outlet.
- Powerful refrigerated air system cools down the ambience instantly whenever you want.
- Dehumidified and filtered air cycle improve breathing environments effectively.
- Besides the remote control, your one touch electronic pad also provides easy-identifying manual operation.
- 24 hours programmable timer that can be used with either the air conditioning or dehumidification setting.
- Unique sleep control function, dehumidification, humidification and air purification.
UNPACKING INSTRUCTIONS
- Place the machine in the correct direction before unpacking.
● Cut two packaging straps. - Open the carton.
- Remove the top packaging polylon.
- Lift the unit carefully to make it slides out of the foam base.
- Install the OPTIONAL hot air outlet connector and exhaust duct on the machine before using the machine (The OPTIONAL hot air outlet connector and exhaust duct are provided separately).
CONTENTS
1 / Air conditioner unit
2 / Remote control
3 / User manual
4/ Hot air outlet connector(optional)
5/ Exhaust pipe and connector(optional)
6/ Wheels (Not fixed in the machine, 4pcs)
Remarks: The wheel is placed under the machine. If
you need the wheel, please put the machine down and install them according to the following figure.



natural_image
Line drawing of a white industrial air conditioner unit with a side panel and ventilation grille (no text or symbols)

natural_image
Line drawing of a white industrial air conditioner unit with ventilation grilles and side panel (no text or symbols)NAME OF THE PARTS
- Control panel
- Top panel
- Front panel
- Cool air outlet and air blade
- Castors
- Hot air inlet
- Right panel
- Base

text_image
Technical diagram of an air conditioner unit with numbered components for identificationEN
- Back panel
- Hot air outlet and air blade
- Power cable protection ring
- Water tank
- Tank window piece
- Cold air inlet
- Left panel

text_image
Technical diagram of a portable air conditioner unit with numbered labels pointing to internal components.CONTROL PANEL & DESCRIPTION OF FUNCTION

text_image
SILENT TIMER SPEED MODE SWING ON/OFF1. POWER KEY ON/OFF
Press this button to turn the unit "ON" or "OFF"
2. FUNCTION MODE
Press this key to select cooling, dehumidifying, fan, or air purification (optional).
3. TEMPERATURE REGULATION KEY
During cooling function: This key raises the preset temperature by 1^ C each time it is pressed and the maximum limit is 30^ C .
During dehumidifying function: This key raises the preset humidity by 5% each time it is pressed and the maximum limit is 90%.
HUMIDITY SETTING:
“CO”→30%→35%→40%→45%→50%→55%→60%→65%→70%→75%→80% →85%→90%→“CO”.
4. TEMPERATURE REGULATION KEY

During cooling function: This key lowers the preset temperature by 1^ C each time it is pressed and the minimum limit is 16^ C.
During dehumidifying function: This key lowers the preset humidity by 5% each time and the minimum limit is 30%.
HUMIDITY SETTING:
“CO”→90%→85%→80%→75%→70%→65%→60%→55%→50%→45%→40%→35%→30%→“CO”.
5. DISPLAY

The display indicates the current setting temperature or the timer setting.
When the set temperature or the timer is adjusted, the new setting is shown then the display returns the current set temperature.
※ The display is also used to show error codes should a fault occur, see ERROR CODES.
6. SPEED

Press to select either LOW, HIGH or Medium fan speed.
7. PROGRAMMABLE TIMER

TIMER-ON: The timer-on is used to turn on the unit automatically after the set time is over.
- Press the "TIMER" key at stand-by status to set the time you desired.
- Once the set hour has come to an end, the unit will turn on automatically.
- Press the "POWER" key before time out, the setting time will be canceled and the unit will turn on.
- You can set the function and fan speed while setting the timer.
TIMER-OFF: The timer-off is used to turn off the unit automatically after the setting time is over.
- Press the "TIMER" key at operating status to set the time you desired.
- Once the set hour has come to an end, the unit will turn off automatically.
- Press the "POWER" key before the time out, the setting time will be canceled and the unit will turn off.
8. Fan
During this mode, the unit only runs for the fan without involved the operation of compressor & water pump. The fan speed can be set from the fan speed button.
9. DEHUMIDIFICATION
After the dehumidification function is enabled, the ambient air humidity can be reduced.
10. SILENT FUNCTION
A. While in cooling mode, press the SILENT key to set the temperature.
B. Press the SILENT key again can cancel the setting.
C. In silent mode, the fan speed defaults to low speed and can be set to high, medium, or low speed.
11. SWING
Press this key and the outlet will oscillating, and it will stop when this key is pressed again. The outlet will close to the middle position automatically when the unit stops working.
12. ALARM
When the water tank is full, the full water lamp will light up. Please empty the water tank, reinstall the tank, and press the power button to restart the unit.
13. ADD WATER
When the water filling light of the display board is on, the water tank can be pumped out and added to the water level, and the machine can be restarted.
※Warm tip: Before starting the machine, please make sure to keep the water tank above 1 liter and below 3 litres (the water quantity shall not exceed the full line). Please stop the machine for at least 3 minutes before draining and refilling the water tank, otherwise the residual water from the machine will drip onto the ground.

natural_image
Line drawing of a white industrial air conditioner unit with cooling fins and a side drawer (no text or symbols)16. Defrost indicator
When the defrost indicator light is on, it means that the defrost action has started, the compressor stops running, and the fan continues to run; after 10 minutes of defrost, the defrost indicator light is off, the defrost action ends, and the compressor restarts.
Remote Control Introduction

natural_image
Gray remote control interface with various function icons (clock, pie chart, crescent moon, document, starburst, plus, power button) on a gray background.- POWER
- FUNCTION
- TIMER
- HI
- MED
- LOW
- SLEEP
- TEMP.
- SWING
On/Off switch
Function "MODE" selector
Hourly programming
High fan speed
Medium fan speed
Low fan speed
Silent operation selector
Temperature selector
Swing
NOTICE
Before assembling the water tank, gently pull out the pumping pipe and then push the assembly tank inside, and place the pumping pipe into the reserved opening of the water tank cover to ensure that the water tank does not clamp or press the pipe, and then release it, then gently push the water tank inside until the assembly is in place.

natural_image
Technical line drawing of a mechanical assembly with mounting holes and internal components (no text or symbols)
text_image
Water tank cover reserved connectorMAINTENANCE
PLEASE DISCONNECT THE POWER CORD BEFORE CLEANING.
AIR FILTER.
The filter frame and filter on both sides of the machine can be easily removed by gently pressing down the frame.
Wash the filter with cool water (cooler than 40^ C) every two weeks, and put filter back after it air-dried naturally.

natural_image
Diagram showing a device transitioning from a fan-shaped opening to a closed air vent (no text or symbols present)CONDENSER/EVAPORATOR
Please use a vacuum cleaner with a brush connector.
Casing
Wipe with a damp cloth and polish with a soft cloth.
When cleaning the filter, please remove it as the picture.
POWER SUPPLY
(1) Confirm the correct power.
(2) Insert the plug into the outlet firmly In order to prevent any dangerous leakage.
(3) Don't pull power wire by force because it will cause damage to power wire.

natural_image
Cartoon illustration showing a smiling refrigerator, a plunger with a 'OK!' sign, and a hand holding a plug (no text or symbols)PLACE FOR USE
(1) Because the machine distributes hot air, please don't place or operate in a narrow place.
(2) In case of dangerous leak, don't work the machine in a humid place.
(3) Don't place the machine in a sunlit corner otherwise the unit might shut down due to the overheat and the color of the machine may soon fade out.
HELPFUL HINTS
The unit is fitted with a special thermal cut off device.
Please ensure the unit is not placed against objects which will obstruct air intake e.g. furniture or curtains as this will affect it's performance dramatically.
Hot air connector installation method (optional accessories)
● Prepare the machine stand and hot air connector.
- Fasten the lower edge of the hot air connector aligned with the hole, and gently push the hot air connector forward, as shown in the following figure.

text_image
① a bInstallation method of hot exhaust duct (optional accessories)
Take out the joint tube from the exhaust pipe(see picture①) and fix a part and b part together.
- Rotate the joint tube counterclockwise and fix it with the exhaust pipe(see arrow①).
● Fit the pipe on the unit as arrow②. - Rotate the exhaust pipe counterclockwise and fix it with the unit (see arrow③)
- Rotate the exhaust pipe clockwise and take it out. (see arrow④)

natural_image
Four technical line drawings of industrial air purifiers with labeled parts (no text or symbols on the devices themselves)Troubleshooting
1. Information on servicing
1) Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.
2) Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed.
3) Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
4) Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
5) No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion.
All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking” signs shall be displayed.
6) Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
7) Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If in doubt consult the manufacturer's technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
- The charge size is in accordance with the room size within which the refrigerant containing parts are installed;
- The ventilation machine and outlets are operating adequately and are not obstructed;
- If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;
- Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;
- Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
8) Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used.
This shall be reported to the owner of the equipment so all parties are advised.
Initial safety checks shall include:
- That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
- That there no live electrical components and wiring are exposed while charging, recovering or purging the system;
• That there is continuity of earth bonding.
2. Repairs to sealed components
1) During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
2) Particular attention shall be paid to the following to ensure that by
working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that the apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer's specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them.
3. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
4.Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
5. Detection of flammable refrigerants
Under no circumstances shall potentially sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
6. Leak detection methods
The following leak detection methods are deemed acceptable for all refrigerant systems.
Electronic leak detectors may be used to detect refrigerant leaks but, in the case of FLAMMABLE REFRIGERANTS, the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed, and the appropriate percentage of gas (25% maximum) is confirmed.
Leak detection fluids are also suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked flames shall be removed /extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.
7. Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures shall be used. However, for flammable refrigerants it is important that best practice be followed, since flammability is a consideration. The following procedure shall be adhered to:
a) safely remove refrigerant following local and national regulations;
b) purge the circuit with inert gas;
c) evacuate;
d) purge with inert gas;
e) open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders.
The system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.
This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.
8. Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed.
- Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
- Cylinders shall be kept in an appropriate position according to the instructions.
- Ensure that the REFRIGERATING SYSTEM is earthed prior to charging the system with refrigerant
- Label the system when charging is complete (if not already).
• Extreme care shall be taken not to overfill the REFRIGERATING SYSTEM.
Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak-tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
9.Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant. It is essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure, ensure that:
- mechanical handling equipment is available, if required, for handling refrigerant cylinders;
- all personal protective equipment is available and being used correctly;
• the recovery process is supervised at all times by a competent person; - recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with instructions.
h) Do not overfill cylinders (no more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another REFRIGERATING SYSTEM unless it has been cleaned and checked.
10. Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. For appliances containing FLAMMABLE REFRIGERANTS, ensure that there are labels on the equipment stating the equipment contains FLAMMABLE REFRIGERANT.
11.Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i. e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants including, when applicable, FLAMMABLE REFRIGERANTS. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that FLAMMABLE REFRIGERANT does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.
Fuse parameters of the machine
Type: 524 or 5H Voltage: 250V Current: 3.15 A
TROUBLE SHOOTING
| Problem | Cause | Trouble shooting |
| E1 | Electrical short on both temperature sensor and PCB(environment) | Contact an electrician for repair |
| E2 | Electrical short of temperature sensor copper tube and PCB wiring(coil) | Contact an electrician for repair |
| E4 | Indicates water tank full | Drain the water from the tank and return it to its original position |
| E8 | Machine tilting | Place the machine upright |
| H1 | In dehumidification mode, the ambient humidity is above 90% | Normal phenomenon, humidity below 90% returns to normal |
SPECIFICATION
| ModelSpecification | CBPAC59-WPCX5R-18MB |
| Power Source 220-240V~ 50Hz | |
| COOLING POWER(DB/WB35/24°C) | 200W |
| RATED POWER INPUT 300W | |
| Cooling Capacity | 500W |
| Moisture Removed 15 Liters/day | |
| Refrigerant R290,56g | |
| Permissible Excessive Operating Pressure | |
| Suction: | 0.6MPa |
| Discharge: | 2.5MPa |
| Maximum Allowable Pressure | 4.0MPa |
Dimensions(mm)
W215XD343xH590mm


This marking indicates that this product should not be disposed with other household wastes throughout the EU. To prevent possible hazards to the environment or human health from uncontrolled waste disposal, please recycle it to prove the sustainable reuse of material resources. Please ask return and collection systems or contact the retailer where the product was purchased to return your used device, they can recycle products safely.
SPOT PORTABLE AIR CONDITIONER
MANUAL
CBPAC59-W
natural_image
Illustration of an open book with a wrench resting on it (no text or symbols visible)

text_image
400mm >500mm ①
natural_image
Line drawing of a white air conditioner unit with ventilation grilles and a side panel (no text or symbols)
natural_image
Two technical diagrams showing a device with heat exchanger and a handle, one marked with a checkmark (no text or symbols present)natural_image
Illustration of a white industrial air conditioner unit with ventilation grilles and a side panel (no text or symbols visible)

natural_image
Line drawing of a rectangular electronic device with ventilation grilles and a side view of four small circular components (no text or symbols)
natural_image
Line drawing of a small electronic device with a fan and ventilation grille (no text or symbols)
natural_image
Line drawing of a white industrial air conditioner unit with ventilation grilles and side panel (no text or symbols)text_image
Technical diagram of an air conditioner unit with numbered components for identification
text_image
Technical diagram of a portable air conditioner unit with numbered labels pointing to internal components.TIMER-OFF: The timer-off is used to turn off the unit automatically after the setting time is over.
When the water tank is full, the full water lamp will light up. Please empty the water tank, reinstall the tank, and press the power button to restart the unit.
13. WASSER ZUFÜLLEN
natural_image
Line drawing of a white industrial air purifier with fan and control panel (no text or symbols)14. Abtauanzeige

natural_image
Gray remote control with various function icons (clock, pie chart, moon, document, starburst, plus, power) arranged in a grid on a gray background.- POWER
- FUNKTION
- TIMER
- HI
- MED
- NIEDRIG
- SCHLAFEN
- TEMP.
- SCHWINGEN
Ein/Aus-Schalter
text_image
Diagram showing airflow or ventilation system transformation from a single air conditioner unit to a multi-chambered air conditioner unit.VERFLÜSSIGER/VERDAMPFER
natural_image
Cartoon illustration showing a smiling refrigerator, a phone with an 'OK!' sign, and a hand inserting a plug into a socket (no text or symbols)EINSATZBEREICH
text_image
Diagram illustrating a mechanical assembly process with labeled steps a and b, showing transformation from a cylindrical component to a final basket.natural_image
Four technical line drawings of industrial air purifiers with labeled parts (no text or symbols on devices)Fehlersuche
MANUEL DU CLIMATISEUR
PORTABLE SPOT
CBPAC59-W
natural_image
Illustration of an open book with a double-headed wrench on the cover (no text or symbols)

text_image
400mm >500mm ①
natural_image
Line drawing of a white industrial air conditioner unit with internal cooling fins and ventilation slots (no text or symbols)
natural_image
Two technical diagrams showing a device with heat sinks and a checkmark indicating selection (no text or symbols present)FÉLICITATIONS POUR VOTRE CHOIX D'UN CLIMATISEUR PORTABLE SPOT DE QUALITÉ
natural_image
Line drawing of a white industrial air conditioner unit with a side panel and vent, showing internal airflow or cooling zones (no text or symbols)
SOMMAIRE
natural_image
Line drawing of a white industrial air conditioner unit with ventilation grilles and side panel (no text or symbols)natural_image
Illustration of a white industrial air conditioner unit with ventilation grilles and a side panel (no text or symbols)

natural_image
Line drawing of a rectangular electronic device with ventilation grilles and a side view of four small circular components (no text or symbols)NOM DES PIÈCES
text_image
Technical diagram of an air conditioner unit with numbered components for identification
text_image
Technical diagram of a portable air conditioner unit with numbered labels pointing to different components.PANNEAU DE CONTRÔLE ET DESCRIPTION DES FONCTIONS

text_image
SILENT TIMER SPEED MODE SWING ON/OFF1. TOUCHE POWER

natural_image
Line drawing of a white industrial air conditioner unit with cooling fins and a side drawer (no text or symbols)natural_image
Gray remote control with various function icons (clock, pie chart, moon, document, starburst, plus, power) arranged in a grid on a gray background.- POWER
- FONCTION
- IMINUTERIE
- HI
- MED
- LOW
- SLEEP
- TEMP.
- SWING
ENGLISH
DEUTSCH
FRANÇAIS