WGCT2RJ6NM - Network Socket HAGER - Free user manual and instructions
Find the device manual for free WGCT2RJ6NM HAGER in PDF.
| Product Type | RJ45/RJ11 Data Outlet (Uncategorized) |
| Brand | Hager |
| Model | WGCT2RJ6NM |
| Application | Data transmission in local area networks and telephone/data applications |
| Installation | Flush-mounted in standard wall boxes (recommended depth ≥ 35 mm), indoor use only |
| Environmental Protection | Indoor areas with no drip or spray water |
| RJ45 Voltage Proof (Contact-to-Contact) | 1000 V DC or AC peak |
| RJ45 Current Rating | 0.75 A |
| RJ45 Insulation Resistance | ≥ 500 MΩ at 100 V DC |
| RJ45 Signal Contact Resistance | ≤ 20 mΩ |
| RJ45 Connection Type | IDC terminals |
| RJ45 Design Standard | IEC 60603-7 |
| RJ45 Color Code | TIA/EIA 568-B.2 (A and B) |
| RJ45 Cat.5e Bandwidth | Max. 100 MHz |
| RJ45 Cat.5e Conductor Diameter | 0.51 ... 0.64 mm (AWG 24-22), solid |
| RJ45 Cat.5e Standard | ISO/IEC 11801 (UTP) |
| RJ45 Cat.6 Bandwidth | Max. 250 MHz |
| RJ45 Cat.6 Conductor Diameter | 0.51 ... 0.64 mm (AWG 24-22), solid |
| RJ45 Cat.6 Standard | ISO/IEC 11801, 2nd edition (UTP) |
| RJ45 Cat.6A Bandwidth | Max. 500 MHz |
| RJ45 Cat.6A Conductor Diameter | 0.41 ... 0.64 mm (AWG 26-22), solid |
| RJ45 Cat.6A Standard | ISO/IEC 11801, edition 2.2 (UTP) |
| RJ11 Compliance | YD/T 577 |
| Safety Installation | Must be installed by qualified electrician according to local standards |
Frequently Asked Questions - WGCT2RJ6NM HAGER
User questions about WGCT2RJ6NM HAGER
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Network Socket in PDF format for free! Find your manual WGCT2RJ6NM - HAGER and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. WGCT2RJ6NM by HAGER.
USER MANUAL WGCT2RJ6NM HAGER
Electrical equipment must only be installed and assembled by a qualified electrician in accordance with the relevant installation standards, regulations, directives and safety and accident prevention directives of the country.
Failure to comply with these installation instructions may result in damage to the device, fire or other hazards.
Function
The RJ45 outlets are used for data transmission in local area networks. The RJ11 outlets are designed for telephone and data applications. Each jack is equipped with a dust protection slider.
Correct use
- For the flush-mounted installation in standard wall boxes (recommended wall box depth ≥ 35 mm).
- Only suitable for use in indoor areas with no drip and no spray water.
Technical data
RJ45 outlets
Voltage proof (contact-to-contact): 1000 V DC or AC peak
Current rating: 0.75 A
Insulation resistance: ≥ 500 M at 100 V DC
Signal contact resistance: ≤ 20 m
Type of connection: IDC terminals
Design: according to IEC 60603-7
Colour code A and B: according to TIA/EIA 568-B.2
RJ45 Cat.5e modules
Transmission bandwidth: max. 100 MHz
Conductor ∅ (solid): 0.51 ... 0.64 mm (AWG 24-22)
Cat.5e, unshielded (UTP): according to ISO/IEC 11801
RJ45 Cat.6 modules
Transmission bandwidth: max. 250 MHz
Conductor ∅ (solid): 0.51 ... 0.64 mm (AWG 24-22)
Cat.6, unshielded (UTP): according to ISO/IEC 11801, 2nd edition
RJ45 Cat.6A modules
Transmission bandwidth: max. 500 MHz
Conductor ∅ (solid): 0.41 ... 0.64 mm (AWG 26-22)
Cat.6A, unshielded (UTP): according to ISO/IEC 11801, edition 2.2
RJ11 outlet
Compliance: YD/T 577
Information for electricians
Installation and electrical connection
Preparing the device for installation
(for example "RJ11 + RJ45 outlet")
1A

Hager Muse
Hager Inspire1B

- Carefully loosen the frame on the notches with a flat-blade screwdriver. Lift up and remove the frame (1A/1B).
■ Hager Inspire: Remove the cover plate also with a flat-blade screwdriver (1B).
Connecting the RJ45 data module
■ Remove the cover plate of the data module with a flat-blade screwdriver.
2A

- Strip 30 mm of cable jacket (2A).
■ Position and terminate first pair according to colour code A or B:
RJ45 pin assignment TIA/EIA 568B TIA/EIA 568A
![]() | 1 white/orange white/green | |
| 2 orange green | ||
| 3 white/green white/orange | ||
| 4 blue blue | ||
| 5 white/blue white/blue | ||
| 6 green orange | ||
| 7 white/brown white/brown | ||
| 8 brown brown |
As with the first pair position and terminate each subsequent pair one at a time until termination is complete.
- Fix the cover plate back to the module.
Connecting the RJ11 telephone module
3A

- Strip 10 mm of cable jacket (3A).
■ Position first pair according to colour code:
RJ11 pin assignment
![]() | 2 blue/white |
| 3 white/blue | |
| 4 white/red | |
| 5 red/white |
- Fix the cover plate back to the module.

Checking of the installation:
A functional test of the installation should be made for each data or telephone outlet.
Installing the device into the wall box
(for example "RJ11 + RJ45 outlet")
4

natural_image
Technical diagram of a mechanical assembly with a bracket and tool, showing no text or symbols■ After wiring, fix the device with the two screws attached into the wall box (4).
Assembling the covers
(for example "RJ11 + RJ45 outlet")
5A

Hager Muse
5B

Hager Inspire
■ Hager Muse: Snap the frame onto the device (5A).
■ Hager Inspire: Place the cover plate in the correct position and fix with frame (5B).
2-5gang frames are available for multiple combinations.