| Type of product | Air conditioning unit for enclosures |
| Brand | Rittal |
| Model | SK 3201.200 |
| Cooling capacity | 2000 W (approx.) |
| Voltage | 230 V / 50 Hz |
| Dimensions (H x W x D) | 400 x 400 x 600 mm (approx.) |
| Weight | 30 kg (approx.) |
| Refrigerant | R134a or R407C |
| Protection class | IP 54 |
| Operating temperature range | -20°C to +55°C |
| Air filter | Washable, replaceable |
| Condensate management | Evaporation tray or drain hose |
| Control | Thermostat with digital display |
| Alarm outputs | Fault signal relay |
| Mounting | Through-wall or on enclosure |
| Cleaning | Clean filters every 3 months; use mild detergent |
| Safety | High pressure switch, overload protection |
| Spare parts availability | Filters, fans, compressors, control boards |
| Repairability | Modular design for easy service |
| Compliance | CE, RoHS |
Frequently Asked Questions - SK 3201.200 Rittal
What cooling capacity does the Rittal SK 3201.200 provide?
The SK 3201.200 offers a cooling capacity of approximately 2000 W, suitable for medium-sized enclosures.
What are the power requirements for this unit?
It operates on 230 V / 50 Hz single-phase power supply.
How do I clean the air filter?
Remove the filter and wash it with mild detergent and water. Ensure it is completely dry before reinstalling. Replace every 6 months.
Can I install this air conditioner outdoors?
The unit has an IP 54 rating, meaning it is protected against dust and splashing water. Indoor installation is recommended unless additional weather protection is provided.
How do I handle condensate drainage?
The unit uses an evaporation tray to remove condensate. Alternatively, a drain hose can be connected to the provided outlet.
What refrigerant type is used?
It uses R134a or R407C refrigerant, depending on the production date.
How do I set the desired temperature?
Use the digital display and buttons on the control panel to adjust the setpoint temperature.
What alarm signals can occur?
Common alarms include high pressure, low pressure, and fan failure. The unit provides a fault signal relay output.
Are spare parts easily available?
Yes, Rittal offers replacement filters, fans, compressors, and control boards through authorized distributors.
How do I troubleshoot if the unit is not cooling?
Check the air filter for clogging, ensure power supply is correct, verify condenser coils are clean, and check for any alarm codes on the display.