| Type de produit | Climatiseur mural/au sol |
| Marque | Daikin |
| Modèle | FVXS-F (FVXS25F, FVXS35F, FVXS50F) |
| Dimensions (HxLxP) | 600 x 700 x 210 mm |
| Poids net | 14 kg |
| Alimentation électrique | 220-240 V, 50 Hz, monophasé |
| Puissance frigorifique nominale | 2,5 kW (FVXS25F) / 3,5 kW (FVXS35F) / 5,0 kW (FVXS50F) |
| Puissance calorifique nominale | 2,5 kW (FVXS25F) / 3,5 kW (FVXS35F) / 5,0 kW (FVXS50F) |
| Classe énergétique | Non spécifiée |
| Réfrigérant | R-410A |
| Niveau sonore (mode silencieux) | À partir de 23 dBA |
| Fonctions principales | Froid, chaud, ventilateur seul, déshumidification, mode puissant, mode éco, nuit, commutation automatique, swing vertical, vitesse automatique |
| Filtre | Filtre à air lavable, amovible, antimoisissure + filtre photocatalytique au titane apatite |
| Programmateur | Programmateur hebdomadaire |
| Télécommande | Télécommande infrarouge fournie |
| Options | Contrôle en ligne, contrôle centralisé, horloge, passerelle KNX, etc. |
| Entretien | Nettoyage régulier du filtre à air ; accès facile |
| Garantie | Consulter la notice ou le vendeur |
| Autodiagnostic | Oui |
| Redémarrage automatique | Oui |
FOIRE AUX QUESTIONS - FVXS-F DAIKIN
Questions des utilisateurs sur FVXS-F DAIKIN
0 question sur cet appareil. Repondez a celles que vous connaissez ou posez la votre.
Poser une nouvelle question sur cet appareil
Téléchargez la notice de votre Climatiseur mural au format PDF gratuitement ! Retrouvez votre notice FVXS-F - DAIKIN et reprennez votre appareil électronique en main. Sur cette page sont publiés tous les documents nécessaires à l'utilisation de votre appareil FVXS-F de la marque DAIKIN.
MODE D'EMPLOI FVXS-F DAIKIN
Air Conditioning
Technical Data
Floor standing unit

EEDEN14-100
TABLE OF CONTENTS
FVXS-F
1 Features 2
2 Specifications 3
Technical Specifications 3
Electrical Specifications 4
3 Options 5
4 Dimensional drawings 6
5 Centre of gravity 7
6 Piping diagrams 8
7 Wiring diagrams 9
Wiring Diagrams - Single Phase 9
8 Sound data 10
Sound Pressure Spectrum - Cooling 10
Sound Pressure Spectrum - Heating 11
1 Features
- Its low height enables the unit to fit perfectly beneath a window
-
Can be installed against a wall or recessed
Vertical auto swing moves the discharge flaps up and down for efficient air and temperature distribution throughout the room -
Online controller (optional): control your indoor unit from any location via smartphone, laptop, pc, tablet or touch screen
- Weekly timer can be set to start heating or cooling anytime on a daily or weekly basis
Whisper quiet operation: down to 23dBA sound pressure level
1


Econo mode

Night set mode

Fan only

Powerful mode

Auto cooling-heating changeover

Whisper quiet

Indoor unit silent operation

Vertical auto swing

Auto fan speed

Fan speed steps

Dry programmeTitanium apatite photocatalytic air purification filter

Titanium apatite photocatalytic air purification filter

Weekly timer Infrared remote control

Auto_restart

Self diagnosis

Multi model application

VRV for residential application
2 Specifications
| 2-1 Technical Specifications | FVXS25F | FVXS35F | FVXS50F | ||||
| Power input - 50Hz | Cooling | Nom. | kW | 0.015 | 0.027 | ||
| Heating | Nom. | kW | 0.017 | 0.034 | |||
| Casing | Colour | White | |||||
| Dimensions | Unit | Height/Width/Depth | mm | 600/700/210 | |||
| Packed unit | Height/Width/Depth | mm | 696/786/286 | ||||
| Weight | Unit | kg | 14 | ||||
| Packed unit | kg | 18 | |||||
| Heat exchanger | Length | mm | 510 | ||||
| Rows | Quantity | 2 | |||||
| Fin pitch | mm | 1.2 | |||||
| Stages | Quantity | 22 | |||||
| Tube type | ø6.35 Hi-XU | ||||||
| Fin | Type | Multi slit fin | |||||
| Fan | Type | Turbo fan | |||||
| Quantity | - | 1 | |||||
| Air flow rate | Cooling | High | m³/min | 8.2 | 8.5 | 10.7 | |
| cfm | 290 | - | |||||
| Nom. | m³/min | 8.2 | 8.5 | 10.7 | |||
| cfm | 290 | - | |||||
| Low | m³/min | 4.8 | 4.9 | 7.8 | |||
| cfm | 169 | - | |||||
| Silent operati on | m³/min | 4.1 | 4.5 | 6.6 | |||
| cfm | 145 | - | |||||
| Heating | High | m³/min | 8.8 | 9.4 | 11.8 | ||
| cfm | 311 | - | |||||
| Nom. | m³/min | 6.9 | 7.3 | 10.1 | |||
| cfm | 244 | - | |||||
| Low | m³/min | 5.0 | 5.2 | 8.5 | |||
| cfm | 177 | - | |||||
| Silent operati on | m³/min | 4.4 | 4.7 | 7.1 | |||
| cfm | 155 | - | |||||
| Fan motor | Quantity | - | 1 | ||||
| Model | D48D-28 | ||||||
| Speed | Steps | 5 + silent, + auto | 5 | ||||
| Cooling | High/ Mediu m/Low/ Silent operati on | rpm | 640/520/400/360 | 650/530/410/380 | 800/700/600/520 | ||
| Heating | High/ Mediu m/Low/ Silent operati on | rpm | 680/550/420/380 | 700/560/420/390 | 850/740/630/540 | ||
| Output | High | W | 48 | ||||
| Sound power level | Cooling | dBA | 52 | 60 | |||
| Heating | dBA | 52 | 60 | ||||
| Sound pressure level | Cooling | High/Nom./Low/ Silent operation | dBA | 38/32/26/23 | 39/33/27/24 | 44/40/36/32 | |
| Heating | Super high/High/ Nom./Low/Silent operation | dBA | -/38/32/26/23 | -/39/33/27/24 | -/45/40/36/32 | ||
| Refrigerant | Type | R-410A | |||||
2 Specifications
| 2-1 Technical Specifications | FVXS25F | FVXS35F | FVXS50F | ||
| Piping connections | Liquid | OD | 6.35 | ||
| Gas | OD | 9.5 | 9.52 | 12.7 | |
| Drain | 20 | ||||
| Heat insulation | Both liquid and gas pipes | ||||
| Temperature control | Microcomputer control | ||||
| Air direction control | Right, Left, Horizontal, Downward | ||||
| Air filter | Type | Removable / washable / mildew proof | |||
Standard Accessories : Wireless remote control; Quantity : 1 ;
Standard Accessories : Air purification filter; Quantity : 2 ;
Standard Accessories : Batteries; Quantity : 2 ;
Standard Accessories : Remote control holder; Quantity : 1 ;
Standard Accessories : Thermal insulation tape; Quantity : 2 ;
Standard Accessories : Installation manual; Quantity : 1 ;
Standard Accessories : Drain hose; Quantity : 1 ;
Standard Accessories : Operation manual; Quantity : 1 ;
Standard Accessories : Air supply filter ; Quantity : 1 ;
| 2-2 Electrical Specifications | FVXS25F | FVXS35F | FVXS50F | |||
| Power supply | Name | V1 | ||||
| Phase | 1~ | |||||
| Frequency | Hz | 50 | ||||
| Voltage | V | 220-240 | ||||
| Current | Nominal running current (RLA) - 50Hz | Cooling | A | 0.14 / 0.13 / 0.12 | 0.17 | |
| Heating | A | 0.15 / 0.14 / 0.13 | 0.19 | |||
| Current - 50Hz | Zmax | List | - | No requirements | ||
| Maximum running current | A | - | 0.20 | |||
| Wiring connections - 50Hz | For power supply | Quantity | - | 3 | ||
| Remark | 3 for power supply, 4 for interunit wiring (Earth wire included) | 4 for interunit wiring (earth wire included) | ||||
Notes
(1) 220 ~V
(2) 230 V
(3) 240 ~V
(4) When connected with multi-system outdoor unit, refer to the specifications of the multi outdoor unit to be connected.
3 Options
3-1 Options
FVXS-F
Indoor Units - Control systems
| PVX525F | PVX535F | PVX550F | ||
| Wiring adapter normal open contact / normal open pulse contact | KRF413A15 (1) | |||
| Centralised control board | Up to 5 rooms | KRC72 (2) | ||
| Central remote controller | DC302C51 | |||
| Unified ON/OFF control | DC301B51 | |||
| Schedule timer | DST301B51 | |||
| Interface adapter for DIII-net | KRF928A25 | |||
| Online controller | KKRP01A | |||
| External mounting kit for online controller | KKRPW01A | |||
| Will power cable for online controller | KKRPW01A | |||
| Touch LCD wall controller (3) | KBCRC01A | |||
| Simple wall controller (3) | KBCRC501A | |||
| KNX gateway | KUC-DD | |||
(1) Wiring adapter supplied by Daikin. Time clock and other devices: to be purchased locally.
(2) Wiring adapter is also required for each indoor unit.
(3) Can only be used in combination with online controller KRRPO1A.
4 Dimensional drawings
4-1 Dimensional Drawings


5 Centre of gravity
5-1 Centre of Gravity

FVXS-F

4D056197D
6 Piping diagrams
6-1 Piping Diagrams

FVXS25-35F
Refrigerant flow


4D056137B

FVXS50F
Refrigerant flow


4D056138D
7 Wiring diagrams
7 - 1 Wiring Diagrams - Single Phase

FVXS25-50F
3D055953A
8 Sound data
8 - 1 Sound Pressure Spectrum - Cooling
8

| NOTES | |||
| 1 | Overall (dB): (B,G,N is already rectified) | ||
| A | 38 | 26 | |
| 2 | Measuring place: Measured in an anechoic room | ||
| 3 | Operation noise differs with operation and ambient conditions. | ||
| 4 | Operating conditions: Power source 220-240V, 50Hz Standard external static pressure ○-○ 50Hz 220-240v (H) ○-○○ 50Hz 220-240V (L) | ||
| 5 | Location of microphone. JSC9612 The operation noise measuring method is in accordance with JSC9612 | ||

| NOTES | |||
| 1 | Overall (dB): (B,G,N is already rectified) | ||
| 2 | Measuring place: Measured in an anechoic room | ||
| 3 | Operation noise differs with operation and ambient conditions. | ||
| 4 | Operating conditions: Power source 220-240V, 50Hz Standard external static pressure ○-50Hz 220-240v (H) ○-50Hz 220-240V (L) | ||
| 5 | Location of microphone. JSC9612 The operation noise measuring method is in accordance with JSC9612 | ||

FVXS50F
NOTES
Overall (dB)
| 50Hz 230V (0) | 50Hz 230V (L) |
| 44 | 36 |
(B.G.N is already rectified).
2 Measuring place: Measure in anechoic room
3 Operation noise differs with operation and ambient conditions.
4 Operating conditions: Power source 220-240V 50Hz
JIS Standard
5 Standard external static pressure
O—O 50 Hz 220-240V (H)
0-50Hz220-240V(L)
Cooling
5 Location of microphone 1562643
JSC9612 The operation noise measuring method is in accordance with JSC9612.

3D056238C
8 Sound data
8 - 2 Sound Pressure Spectrum - Heating

FVXS25F (Heating)
NOTES
1 Overall (dB):
(B,G,N is already rectified)
2 Measuring place: Measured in an anechoic room
3 Operation noise differs with operation and ambient conditions.
4.Operating conditions:Power source 220-240V,50Hz
Standard external static pressure
50Hz 220-240v (H) O---O 50Hz 220-240V (L)
5 Location of microphone.
JSC9612
The operation noise measuring
method is in accordance with JISC9612
| Scale | 50Hz 230V(H) | 50Hz 230V(L) |
| A | 38 | 26 |


FVXS50F
HEATING
NOTES
1 Overall (dB)
| Scale | 50Hz 230V(H) | 50Hz 230V(L) |
| A | 45 | 36 |
(B.G.N is already rectified)
2 Measuring place: Measure in anechoic room
3 Operation noise differs with operation and ambient conditions.
4 Operating conditions: Power source 220-240V 50Hz
JIS Standard
5 Standard external static pressure
O-50Hz220-240V(H)O---O,50Hz,220-240V(1)
Heating
6 Location of microphone
JSC9612 The operation noise measuring method is in accordance with JSC9612.

3D056238C

FVXS35F (Heating)
NOTES
Overall (dB)
(B,G,N is already rectified)
Measuring place: Measured in an anechoic room
Operation noise differs with operation and ambient conditions.
Operating conditions: Power source 220-240V, 50Hz
Standard external static pressure
50Hz220-240v(H) 50Hz220-240V(L)
Location of microphone.
JISC9612
The operation noise measuring
method is in accordance with JSC9612
| Scale | 50Hz 230V(H) | 50Hz 230V(L) |
| A | 39 | 27 |




Daikin Europe N.V. participates in the Eurorent Certification programme for Liquid Chilling Packages (LCP), Air handling units (AHU) and Fan coil units (FCU). Check ongoing validity of certificate online: www.eurorent-certification.com or using: www.certiflash.com
The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V., Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.