AM216BXVGFR - Separator SAMSUNG - Free user manual and instructions
Find the device manual for free AM216BXVGFR SAMSUNG in PDF.
| Product Type | DVM S2 Heat Pump Outdoor Unit (Séparateur) |
| Model | AM216BXVGFR |
| Cooling Capacity | 216,000 Btu/h (63.3 kW) |
| Heating Capacity | 243,000 Btu/h (71.2 kW) |
| Refrigerant Type | R-410A |
| Power Supply | 230 V, 60 Hz, 3-phase (AM****XV*F* models) |
| Dimensions (W x D x H) | Approx. 1295 x 1155 x 2351 mm (51 x 45.5 x 92.6 in) |
| Refrigerant Pipe Connections | Liquid: 3/4 in (19.05 mm) OD; Gas: 1 5/8 in (41.28 mm) OD |
| Maximum Piping Length (Actual) | 200 m (656 ft) between outdoor and farthest indoor unit |
| Maximum Height Difference | Not specified; refer to manual for allowable limits |
| Maximum Number of Connectable Indoor Units | 37 (for AM216BXVG** series) |
| Indoor Unit Capacity Range | 50% to 130% of outdoor unit capacity |
| Basic Refrigerant Charge (Outdoor Unit) | 34.2 lb (15.5 kg) |
| Additional Refrigerant Calculation | Based on liquid pipe length and indoor unit type; see manual |
| Operating Temperature Range | Cooling: 5 to 43 °C (41 to 109 °F); Heating: -10 to 24 °C (14 to 75 °F) for auto trial |
| Protection Features | Overcurrent, overvoltage, refrigerant leakage detection, anti-corrosion treatment |
| Installation Requirements | Outdoor unit must be on a hard, level surface; sufficient ventilation space; base height ≥200 mm (8 in) |
| Electrical Wiring | Must comply with national wiring regulations; use dedicated circuit and ground |
| Maintenance | Periodic cleaning of condenser coils; check refrigerant pressure; inspect electrical connections |
| Warranty | Refer to Samsung warranty terms; standard limited warranty applies |
Frequently Asked Questions - AM216BXVGFR SAMSUNG
User questions about AM216BXVGFR SAMSUNG
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Separator in PDF format for free! Find your manual AM216BXVGFR - SAMSUNG and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. AM216BXVGFR by SAMSUNG.
USER MANUAL AM216BXVGFR SAMSUNG
- Thank you for purchasing this Samsung air conditioner.
- Before operating this unit, please read this manual carefully and retain it for future reference.
Safety Information 3
Safety Information 3
Installation Procedure 5
Preparations for Outdoor Unit 5
Choosing the installation location 7
Preparing materials and tools 9
Outdoor unit installation 9
Refrigerant pipe installation 14
Electrical wiring work 37
Air tightness test and vacuum drying 45
Pipe insulation 47
Basic segment display 50
Setting outdoor unit option switch and key function 51
Optional: Setting the MCU and Pipe Addresses (for HR Only) 59
Performing final checks and trial operation 61
Appendix 63
Inspection and trial operation 63
Automatic refrigerant amount detection function 65
California Proposition 65 Warning (US)

WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov.
Please follow the following safety information for the safety of the installer and the user.
• DVM S2 air conditioner uses R-410A refrigerant.
- When using R-410A, moisture or foreign substances may affect the performance and reliability of the product. Safety precautions must be obeyed when installing the refrigerant pipe.
- The designed maximum pressure of the system is 4.1MPa (594.6psi) and therefore select appropriate material and thickness according to the regulations.
- R-410A is a quasi-azeotrope of two refrigerants and it has to be charged in liquid phase when filling the refrigerant. (If you charge vapor refrigerant, it may change the blend of the refrigerant and cause product malfunction.)
- You must connect the indoor units for R-410A refrigerant. Refer to product catalog to find out the models names for connectable indoor units. (If you connect the indoor units that are not designed for R-410A, it cannot operate normally.)
- After completing the installation and trial operation, explain to the user how to use and maintain the product. Also, hand over this installation manual so that it can be stored by the user.
- The manufacturer is not responsible for incidents caused by improper installation. The installer is responsible for any installation-related claims from the user that arise from neglecting warnings and cautions stated in this manual. (The installer will be responsible for any service charges that may occur.)
- Generally, system air conditioners should not be relocated after installation. However, if relocation is necessary for unavoidable reasons, please contact Samsung's qualified dealers for system air conditioners.

WARNING
- Hazards or unsafe practices that may result in severe personal injury or death.

CAUTION
- Hazards or unsafe practices that may result in minor personal injury (to installer/user) or property damage.
General information

WARNING
- Consult a qualified installer or dealer for installation.
- If installation is done by an unqualified person, problems such as water leakage, electric shock, or fire may occur.
- Installation work must be done properly according to this installation manual.
- If installation is not done properly, it may cause water leakage, electric shock, or fire.
- When installing the unit in a small room, take measures to keep the refrigerant concentration from exceeding allowable safety limits in case of refrigerant leakage. Consult the dealer for precautionary measures before installation.
- If refrigerant leaks and exceeds dangerous concentration levels, it may cause suffocation accidents.
- If any gas or impurities, except R-410A refrigerant, come into the refrigerant pipe, serious problems may occur and it may cause injury.
- Use the supplied accessories, specified components, and tools for the installation.
- Do not use pipes and installation products used for refrigerants other than R-410A.
- Failure to use the specified components can cause product fall, water leakage, electrical shock, and fire. (Pipes and flare components used for refrigerants other than R-410A must not be used.)
• Install the outdoor unit on a hard and even place that can support its weight.
- If the place cannot support its weight, the outdoor unit may fall and cause injury.
- Check the following before installation and service work.
– Before welding, remove dangerous and flammable items that may cause explosion and fire around the work area. - Before welding, remove the refrigerant from inside the pipe or the product.
- If you perform welding while refrigerant is in the pipe, it may increase the pressure of the refrigerant and cause the pipe to burst. If the pipe bursts or explodes, it may cause severe injury to the installer.
- When welding, use nitrogen gas to eliminate oxidation inside the pipe.
- Do not modify the product on your own.
– Potential risk of electric shock, fire, product failure, or injury.
- Fix the outdoor unit securely on the foundation to resist strong wind or earthquake.
- If the outdoor unit is not properly fixed, it may tip over and accidents may occur.
- Electrical work must be done by qualified persons, complying with national wiring regulations and installed according to the instructions stated in the installation manual with a dedicated circuit.
– Capacity shortage on the leased circuit and improper installation may cause electric shock or fire.
- Make sure to perform grounding work.
- Do not connect the ground wire to a gas pipe, water pipe, lightning rod or telephone grounding. Improper grounding could cause electric shock.
- Wiring must be connected with the designated wires and it must be fixed securely so that it does not apply any external force to the connection part of the terminals.
- If connection for fixation is not properly done, it may cause heat generation or fire.
- Neatly arrange the wires in the electrical parts to make sure that electrical cover is closed securely without any gaps.
- If the cover is not properly closed, heat may generate on the electrical terminal and cause electric shock or fire.
- Exclusive circuit breaker (MCCB, ELB) must be installed to the power supply.
- When overcurrent or current leakage occurs with no circuit breaker installed, power will not be cut-off and it may cause electric shock or fire.
- Do not use damaged parts. It may cause fire or electric shock.
- You must cut-off the power before you work on, or adjust any power supply part for product installation, maintenance, repair or any other services.
– There is risk of electric shock. - Even when the power is off, it is dangerous when you come in contact with inverter PCB, fan PCB since high pressure DC voltage is charged to those parts.
- When replacing/repairing the PCB, cut-off the power and wait until the DC voltage is discharged before replacing/repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
- If the refrigerant gas leaks during the installation, you should ventilate the room.
- When the refrigerant gas gets in contact with flammable substance, it may generate toxic gas.
• Gas leakage must be checked after installation is completed.
- When the refrigerant gas gets in contact with flammable substance, it may generate toxic gas.
- You can get a frostbite if you get in contact with the leaked refrigerant gas.
- Supply power to the product during winter time since the product will operate in protection mode itself when the temperature decrease below 0°C (32°F).
- If you cut-off the power, compressor protection mode cannot be operated and may cause damage to the product.
- Wear protective equipment (such as safety gloves, goggles, and headgear) during installation and maintenance works. Installation/repair technicians may be injured if protective equipment is not properly equipped.
- This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
For use in Europe: This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.

CAUTION
- Do not install the drain pipe directly to the bottom part of the outdoor unit and built a proper drainage so that water drains out smoothly. If not, pipe may freeze or bursts during winter time and cause damage to the product or water leakage.
- When the draining work is not done properly, water leak may occur and cause property damage.
• Install the power cable and communication cable of the indoor and outdoor unit at least 1.5m (4.92ft) away from the electric appliances and install it at least 2m (6.56ft) away from the lightning conductor.
– Noise may be generated from the electronic devices, depending on the status of the electric wave.
• Install the outdoor unit within the angle stated in the table, according to the height of the building.
- Do not leave the refrigerant container under the hot sunlight. (There is risk of explosion.)
- You must use the appropriate pipes according to the standard since the pressure of the refrigerant is high.
- Make sure that the pipes do not get weaker by welding them too much.
- Make sure to install the product away from children's reach. (Sharp parts of the heat exchanger may cause personal injury, and when parts of the product get damaged, it may decrease the product's performance.)

| Height of the building Protection angle | |
| 20m(65.6 ft) or less 55° | |
| 40m(131.2 ft) or less 35° | |
| 60m(196.9 ft) or less 25° | |
- Install the indoor unit away from lighting apparatus that uses ballast stabilizers.
- If you use the wireless remote control, it may not operate normally due to ballast stabilizers.
- Do not install the product in the following places:
- Places where the outdoor unit's noise and warm air may disturb neighbors. (It may cause property loss.)
- Do not leave any obstacles around the inlet and outlet of the product. (It may cause damage or accidents.) – The place where there is mineral oil or arsenic acid.
– Those parts may get damaged due to burned resin and cause water leakage or the product may fall. – The efficiency of the heat exchanger may reduce or the product may break.
- The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet.
- The copper pipe or connection pipe may corrode and refrigerant may leak.
- The place where there is a machine that generates electromagnetic waves.
- The air conditioner may not operate normally due to problems in the control system.
- The place where there is a danger of combustible gas leakage or a place where thinner or gasoline is handled. – (There is a risk of fire or explosion.) – The place with carbon fiber or flammable dust.
- The place near the seashore or hot spring where there is a risk of outdoor unit corrosion.
- Changes in DVM S2 (inverter) compared to conventional models that must be noted when installing
- For optimal distribution of the refrigerant, you must use Y-joint as branch joint for connecting outdoor units. (Do not use T-joint)
- You cannot operate normally if you do not complete the trial operation through outdoor unit key mode. You must use KEY MODE to run trial operation.
- Check the compatibility of other products such as indoor unit, EEV kits etc. which will be connected to DVM S2.
- Make sure to note that outdoor unit combination is different from DVM PLUS III, IV and DVM S.
- The length of maximum piping, level difference, the quantity of connectable indoor units, the installation at the outdoor joints and the outdoor unit combinations are different from the conventional models.
- If the pipe length is over 2m (6.56ft) between outdoor units, make traps to prevent oil stagnation. Oil stagnation may occur when outdoor unit at the end of module stops while other outdoor units are still in operation.
Outdoor unit classification
| Classification | DVM S2 Small type | DVM S2 Large type | DVM S2 X-Large type |
| Appearance | ![]() | ![]() | ![]() |

CAUTION
Packaging material disposition
- Safely store or dispose the packaging materials.
- Sharp metals such as nails or wooden material packaging that may break into pieces become a cause for personal injury.
- Make sure to store or dispose the vinyl type packaging material to keep it out of reach of children. Children may put them over their face, which is very dangerous since it may lead them to suffocation.
Moving the outdoor unit
- Select the moving path in advance.
- Be sure that moving path can support weight of the outdoor unit.
- Do not slant the product more than 30° when carrying it. (Do not lay the product down in sideways.)
- Surface of the heat exchanger is sharp. Be careful not to get injured while moving the product.
- When transporting DVM S2 outdoor, be aware of the center of gravity of the outdoor (Please refer to the center of gravity label attached on the front panel, and remove it after installation.)

CAUTION
- You must use certain part of the product when moving the product.
When moving with a crane
- Fasten the wire rope as shown in the figure.
- To protect damage or scratches, insert a piece of cloth between the outdoor unit and the wire rope.

When moving with a forklift
- Carefully insert the forklift forks into the forklift holes at the bottom of the outdoor unit.
- Be careful with the forklift from damaging the product.

When moving the product without wooden pallet and the crane is not available for use
- Connect a wire rope to the outdoor unit as you would move it with a crane.
- Hang the wire rope to the forklift fork to move the outdoor unit.

Outdoor unit combination
- Make sure to use an indoor unit that is compatible with DVM S2.
- Indoor units can be connected within the range indicated in the following table.
- If the total capacity of the connected indoor units exceeds the indicated maximum capacity, the cooling and heating capacity of the indoor unit may decrease.
- The total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity. 0.5 × (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × (Outdoor unit capacity)
- Please contact your local Samsung representative or refer to the Technical Data Book for further details if the project requires you to design the project with a connection ratio greater than 130%.
- You can connect a maximum of 64 indoor units to the outdoor unit. The maximum quantity of connectable indoor units is set to 64 since the outdoor unit only supports up to 64 communication addresses. Indoor unit addresses can be assigned from 0 to 63. If the indoor unit address is assigned from 64 to 79, an E201 error will occur. • A maximum of 32 Wall-mount type indoor units with EEV (AM****NQD*, AM****NVD*) can be connected.
- Do not install 1st-generation MCU and 2nd-generation MCU together.
- 1st-generation MCU: MCU-S*NEE*N, MCU-S2NEK1N
- 2nd-generation MCU: MCU-S*NEK2N, MCU-S4NEK3N, MCU-S1NEK1N, MCU-S8NEK1N, MCU-S12NEK1N

CAUTION
- Use the following table to determine the size and number of outdoor units needed to achieve the capacity requirements.
Preparations for Outdoor Unit
Module combination for AM***BXVG* series
| Model name for combination | Number of individual outdoor units | Nominal Capacity | Rated Capacity | Total cooling capacity of the connected indoor units | Maximum number of connectable indoor units | Combined outdoor units | ||||||||||
| AM***BXVG** | ||||||||||||||||
| Cooling (Btu/h) | Heating (Btu/h) | Cooling (Btu/h) | Heating (Btu/h) | Minimum (Btu/h) | Maximum (Btu/h) | 072 (6Ton) | 096 (8Ton) | 120 (10Ton) | 144 (12Ton) | 168 (14Ton) | 192 (16Ton) | 216 (18Ton) | 240 (20Ton) | |||
| AM072BXVG** | 72000 81 | 000 69000 | 77000 360 | 00 93600 | 2 1 | |||||||||||
| AM096BXVG** | 1 | 96000 | 108000 | 92000 | 103000 | 48000 | 124800 | 16 | 1 | |||||||
| AM120BXVG** | 1 | 120000 | 135000 | 114000 | 129000 | 60000 | 156000 | 20 | 1 | |||||||
| AM144BXVG** | 1 | 144000 | 162000 | 138000 | 154000 | 72000 | 187200 | 25 | 1 | |||||||
| AM168BXVG** | 1 | 168000 | 189000 | 160000 | 180000 | 84000 | 218400 | 29 | 1 | |||||||
| AM192BXVG** | 1 | 192000 | 216000 | 184000 | 206000 | 96000 | 249600 | 33 | 1 | |||||||
| AM216BXVG** | 1 | 216000 | 243000 | 206000 | 232000 | 108000 | 280800 | 37 | 1 | |||||||
| AM240BXVG** | 1 | 240000 | 270000 | 228000 | 258000 | 120000 | 312000 | 41 | 1 | |||||||
| AM264BXVG** | 2 | 264000 | 297000 | 252000 | 282000 | 132000 | 343200 | 45 | 1 | 1 | ||||||
| AM288BXVG** | 2 | 288000 | 324000 | 274000 | 308000 | 144000 | 374400 | 49 | 1 | 1 | ||||||
| AM312BXVG** | 2 | 312000 | 351000 | 298000 | 334000 | 156000 | 405600 | 54 | 1 | 1 | ||||||
| AM336BXVG** | 2 | 336000 | 378000 | 320000 | 360000 | 168000 | 436800 | 58 | 1 | 1 | ||||||
| AM360BXVG** | 2 | 360000 | 405000 | 342000 | 386000 | 180000 | 468000 | 62 | 1 | 1 | ||||||
| AM384BXVG** | 2 | 384000 | 432000 | 366000 | 412000 | 192000 | 499200 | 64 | 2 | |||||||
| AM408BXVG** | 2 | 408000 | 459000 | 388000 | 438000 | 204000 | 530400 | 64 | 1 | 1 | ||||||
| AM432BXVG**1 | 3 | 432000 | 486000 | 412000 | 462000 | 216000 | 561600 | 64 | 2 | 1 | ||||||
| AM456BXVG** | 3 | 456000 | 513000 | 436000 | 488000 | 228000 | 592800 | 64 | 1 | 1 | 1 | |||||
Module combination for AM***BXVT** series
| Model name for combination | Number of Individual outdoor units | Nominal Capacity | Rated Capacity | Total cooling capacity of the connected indoor units | Maximum number of connectable indoor units | Combined outdoor units | |||||
| Cooling (Btu/h) | Heating (Btu/h) | Cooling (Btu/h) | Heating (Btu/h) | Minimum (Btu/h) | Maximum (Btu/h) | AM***BXVT** | |||||
| 072 (6Ton) | 096 (8Ton) | 120 (10Ton) | |||||||||
| AM072BXVT** | 1 | 72000 | 81000 | 69000 | 77000 | 36000 | 93600 | 12 | 1 | ||
| AM096BXVT** | 1 | 96000 | 108000 | 92000 | 103000 | 48000 | 124800 | 16 | 1 | ||
| AM120BXVT** | 1 | 120000 | 135000 | 114000 | 129000 | 60000 | 156000 | 20 | 1 | ||
| AM144BXVT** | 2 | 144000 | 162000 | 138000 | 154000 | 72000 | 187200 | 25 | 2 | ||
| AM168BXVT** | 2 | 168000 | 189000 | 161000 | 180000 | 84000 | 218400 | 29 | 1 | 1 | |
| AM192BXVT**1 | 2 | 192000 | 216000 | 184000 | 206000 | 96000 | 249600 | 33 | 2 | ||
| AM216BXVT**1 | 3 | 216000 | 243000 | 206000 | 232000 | 108000 | 280800 | 37 | 3 | ||
| AM240BXVT**1 | 3 | 240000 | 270000 | 228000 | 258000 | 120000 | 312000 | 41 | 2 | 1 | |
| AM264BXVT** | 3 | 264000 | 297000 | 252000 | 283000 | 132000 | 343200 | 45 | 2 | 1 | |
| AM288BXVT** | 3 | 288000 | 324000 | 275000 | 309000 | 144000 | 374400 | 49 | 1 | 1 | 1 |
Outdoor unit location requirements
Decide the installation location, with the consideration of the following conditions, under user's approval.
- Place where hot discharge air or noise from the outdoor unit may not disturb the neighbor (Especially in residential areas, keep the operation hours in mind.)
- Place where structure can bear the weight and vibration of the outdoor unit.
- Place with flat surface where rainwater does not settle or leak.
- Place where it is not exposed to strong wind.
- Well ventilated place with sufficient service place for repairs and maintenance. (Discharge duct must be purchased separately in your local market.)
- Place where you can connect the refrigerant pipes between indoor and outdoor units within allowable distance.
- Place where it allows easy waterproofing and draining work for the condensation water generated from the outdoor unit during heating operation.
- Place where there is no risk of inflammable gas leakage.
- Place where there is no direct influence of snow or rain.
- Place where a large amount of water generated by external environment does not directly affect the top of the outdoor unit.
Installation Guide at the seashore
Make sure to follow below guides when installing at the seashore.
1 Do not install the product in a place where it is directly exposed to sea water and sea breeze.
- Make sure to install the product behind a structure (such as a building) that can block sea breeze.
- Even when it is inevitable to install the product in a seashore area, make sure that the product is not directly exposed to sea breeze by installing a protection wall.

The protection wall should be constructed with a solid material that can block the sea breeze, and the height and width of the wall should be 1.5 times larger than the size of the outdoor unit. (You must secure more than 700mm (28 inches) of space between the protection wall and the outdoor unit for air circulation.)
2. Consider that the salinity particles clinging to the external panels should be sufficiently washed out. 3. Because the residual water at the bottom of the outdoor unit significantly promotes corrosion, make sure that the slope does not disturb drainage.
- Keep the floor level so that rain does not accumulate.
- Be careful not to block the drain hole due to foreign substances.
4. When the product is installed in a seashore area, periodically clean it with water to remove attached salinity.
5. Make sure to install the product in a place that provides smooth water drainage. Especially, ensure that the base part has good drainage. 6. If the product is damaged during installation or maintenance, make sure to repair it. 7. Check the condition of the product periodically.
- Check the installation site every 3 months and perform anti-corrosion treatment such as R-Pro supplied by SAMSUNG (Code: MOK-220SA) or commercial water repellent grease and wax, etc., based on the product condition.
- When the product is to be shut down for a long period of time, such as off-peak hours, take appropriate measures like covering the product.
8. If the product is installed within 500m (1640ft) of the seashore, special anti-corrosion treatment is required.
※ Please contact your local SAMSUNG representative for further details.
If you cannot find a proper location to install the outdoor unit, consult with an expert or specialty store.
![graph TD A["Sea"] --> B["Sea breeze"] B --> C["Outdoor unit"] D["Sea"] --> E["Sea breeze"] E --> F["Outdoor unit"] G["Sea"] --> H["Sea breeze"] H --> I["Outdoor unit"]](/content/2026/05/959055/images/dbe136bed674cc307795356d218a46795156e69db49b4724596cc5d1b47155c8.jpg)
CAUTION
- System air conditioner may cause static noise when listening to AM stations. Therefore, select an installation location for the indoor unit where electrical wiring can be done while keeping a certain distance from a radio, computer, and stereo equipment.
- Especially, keep the unit at least 3m (9.84ft) away from electrical equipment in an area with weak electromagnetic waves, and place the main power cable and communication cables in a separately installed protection tube.
- Make sure that there is no equipment that generates electromagnetic waves. If there is, electromagnetic waves may cause problems to the control systems, which may lead to air conditioner malfunction. (Example: The remote control sensor of the indoor unit may not receive the signal very well, due to the ballast stabilizer of the lighting equipment.)
- In regions with heavy snowfall, make sure to install the outdoor unit where there is no concern of direct snowfall on the outdoor unit. Also, build a higher base support so that accumulated snow does not block the air inlet or the heat exchanger.
- R-410A refrigerant is a safe, nontoxic, and nonflammable refrigerant. However, if there is any concern of exceeding dangerous levels of refrigerant concentration in case of leakage, extra ventilation is required.
Choosing the installation location
- When you install the outdoor unit in high places such as a roof, install a fence or guardrail around it. If there is no fence or guardrail, service personnel could fall.
- Do not install the product in places where corrosive gases such as sulfur oxides, ammonia, and sulfurous gas are produced. (e.g., toilet outlets, ventilation openings, sewage works, dyeing complexes, cattle sheds, sulfuric hot springs, nuclear power plants, ships, etc.) When installing the product in those places, contact an installation specialty store, as the copper pipe and brazing parts will need additional corrosion-proof or anti-rust additives to prevent corrosion.
- Make sure not to keep any inflammable materials (such as wooden materials, oil, etc.) around the outdoor unit. In case of fire, those inflammable materials will easily catch fire and may pass it on to the product.
- Depending on the condition of the power supply, unstable power or voltage may cause malfunction of the parts or control system. (At ships or places using power supply from electric generators, etc.)
- Make sure to install an MCU when using HR products.
- When selecting the location to install the MCU, choose a location far away from indoor rooms, because the refrigerant running of the MCU may create noise.
Outdoor unit space requirements
- Space requirement was decided based on the following conditions: cooling mode, outdoor temperature of 35°C (95°F). Larger space is required if the outdoor temperature is higher than 35°C (95°F) or if the place is easily heated by solar radiation.
- When securing installation space, consider the path for people and the direction of the wind.
- Secure installation space as shown in the illustration below, considering ventilation and service space.
- If the installation space is narrow, the installer or other workers may get injured during work, and it may also cause problems with the product.
- If you install multiple outdoor units in one space, make sure to secure enough ventilation space if there are any walls around the product that may disturb the air flow. If enough ventilation space is not secured, the product may malfunction.
- You may install the outdoor units with 20mm (0.78 inch) of space between them, but the product's performance may decrease depending on the installation environment.
Single installation

Module installation

- For or
- The height of the wall on the front side should not be higher than 1500mm (60 inches).
- The height of the wall on the air inlet side should not be higher than 500mm (20 inches).
- The height of the wall on the side is not limited.
- If the height of the wall exceeds a certain value (h1, h2), additional clearance [(h1)/2, (h2)/2: half of the exceeded height] should be added to the service space (S1, S2).

Preparing materials and tools
- You must keep the installation manual until the installation is finished.
- Hand over the installation manual to the customer after finishing the installation.
| Installation manual (1) Packing socket (1) | |
![]() | ![]() |
Note: Certain models are supplied with a packing socket. The socket type may differ, depending on the model.
Optional accessories
- The following optional accessories are needed for connecting pipes between the indoor and outdoor units.
| Classification Model Name | Specification | ||
| MBH kW | |||
| Y-Joint | MXJ-YA1509M 51 and below 15.0 and below | ||
| MXJ-YA2512M 52~136 15.1 ~40.0 | |||
| MXJ-YA2812M 137~154 40.1 ~45.0 | |||
| MXJ-YA2815M 165~240 45.1 ~70.3 | |||
| MXJ-YA3419M 241~336 | 70.4 ~98.4 | ||
| MXJ-YA4119M 337~461 | 98.5 ~135.2 | ||
| MXJ-YA4422M | Over 461 | Over135.2 | |
| Classification Model Name | Specification | ||
| MBH kW | |||
| Y-Joint(Only H/R) | MXJ-YA1500M 76 and below 22.4 and below | ||
| MXJ-YA2500M | 77~240 | 22.5 ~70.3 | |
| MXJ-YA3100M 241~461 | 70.4 ~135.2 | ||
| MXJ-YA3800M | Over 461 | Over135.2 | |
| Distribution header | MXJ-HA2512M | 154 and below(for 4 rooms) | 45.0 and below(for 4 rooms) |
| MXJ-HA3115M | 240 and below(for 8 rooms) | 70.3 and below(for 8 rooms) | |
| MXJ-HA3819M | 241 ~ 461(for 8 rooms) | 70.4 ~ 135.2(for 8 rooms) | |
| Y-Joint- Outdoor unit | MXJ-TA3819M | 461 and below | 135.2 andbelow |
| MXJ-TA4422M | Over 461 | Over135.2 | |
| Y-Joint(Only H/R)- Outdoor unit | MXJ-TA3100M | 461 and below | 135.2 andbelow |
| MXJ-TA3800M | Over 461 | Over135.2 | |
Note: If you use an indoor unit with no internal EEV (Electric Expansion Valve), you will need an EEV kit. Only use the genuine accessories listed in the above table and do not use imitated accessories.
Outdoor unit installation

WARNING
- Make sure to remove the wooden pallet before installing the outdoor unit. If you do not remove the wooden pallet, there is a risk of fire during welding the pipes. If the outdoor unit is installed with the wooden pallet on, and it was used for a long period of time, the wooden pallet may break and cause electrical hazards or high pressure may damage the pipes. Note: Fix the outdoor unit firmly on the base ground with anchor bolts. The manufacturer is not responsible for damage caused by not following the installation standards.
1. Make sure that the height of the base ground is 200mm (8 inches) or higher to protect the outdoor unit from rain water or other external conditions. Also, install a draining pit around the base ground and connect the drain pipe to the drainage. 2. Considering the vibration and weight of the outdoor unit, the strength of the base ground must be strong to prevent noise, and the top surface of it should be flat. 3. The base ground should be 1.5 times larger than the bottom of the outdoor unit. 4. The outdoor unit must be fixed firmly so that it can withstand a wind speed of 30m/s. If you cannot fix the outdoor unit on the base ground, fix it by the side or use extra structure.
5. In heating operation, defrost water may form, so you must really care about the drainage and waterproofing of the floor. To prevent defrost water from stagnating or freezing, construct a drainage with a slope of over 1/50. (Ice may form on the floor in winter season.) 6. It is necessary to add wire mesh or steel bars during concrete construction for the base ground to prevent damages or cracks. 7. When installing multiple outdoor units at the same place, construct an H beam or an anti-vibration frame on the base ground to install the outdoor unit. 8. After installing an H beam or an anti-vibration frame, apply corrosion protection and other necessary coatings. 9. When concrete construction for outdoor unit installation is completed, install an anti-vibration pad (t=20mm/0.78 inches or more) or an anti-vibration frame to prevent vibration of the outdoor unit from transferring to the base ground. 10. Place the outdoor unit on an H beam or an anti-vibration frame and fix it with the bolt, nut, and washer. (The bearing force has to be over 3.5kN)
Base ground construction
Outdoor unit installation
Outdoor unit base mount and anchor bolt position![Unit: mm (inch). Outdoor unit - Anti-vibration frame [4/8-Φ12(0.47)]. Anti-vibration - Base ground [4-Φ18(0.71)].](/content/2026/05/959055/images/4ad2b2ccdeb7bc63fbe5417f59b5c0073124674e76a195c0ff4eff84a38fc126.jpg)
Unit: mm (inch)
| Classification | DVM S2 Small type | DVM S2 Large type | DVM S2 X-Large type |
| A 930 (36.6) | 1295 (51) 1860 (73.2) | ||
| B 790 (31.1) | 1155 (45.5) 1720 (67.7) | ||
| C -- 150 (5.9) |
Note: Refer to the blueprints in the technical data book to make holes for connecting the anti-vibration pad.
Examples of draining work
- Construct the drainage ditch with reinforced concrete and ensure that waterproofing is done.
- For smooth draining of defrost water, make sure to apply a 1/50 slope.
- Construct drainage around the outdoor unit to prevent defrost water (from the outdoor unit) from stagnating, overflowing, or freezing near the installation space.
- When the outdoor unit is installed on the roof, check the strength and waterproof status of the roof.

Unit: mm (inch)
| Classification | DVM S2Small type | DVM S2Large type | DVM S2X-Large type |
| A | 1030 (40.6) | 1395 (54.9) | 1960 (77.2) |
| B 790 (31.1) | 1155 (45.5) | 1720 (67.7) |

CAUTION
- Cautions regarding connecting the anchor bolt
- Tighten the rubber washer to prevent the bolt connection part of the outdoor unit from corroding.

Rubber washer
- Anchor specification
| Size | Diameter of drill bit (a) | Anchor length (b) | Sleeve length (c) | Insert depth | Fastening torque |
| ∅10 | 14mm(1/2") | 75mm(3") | 40mm(1-1/2") | 50mm(2") | 30 N·m |
※ Use anchor bolts and nuts that are zinc plated or made of STS material. Regular anchor bolts or nuts may get damaged by corrosion.

- Cautions regarding connecting the pipe
- If you install the outdoor unit on the rooftop, check the strength and make sure to waterproof the rooftop.
- Construct a draining pit around the base construction and pay attention to the drainage around the outdoor unit. (Condensation or defrost water may form during outdoor unit operation.)
- If there is any possibility of small animals entering the pipe outlet, block the outlet as shown in the illustration.

Cautions regarding anti-vibration frame installation
- During installation, make sure there is no gap between the base ground and the supporting structures such as anti-vibration frame or H beam.
- The base ground must be constructed strongly to support the bottom part of the anti-vibration mount.

After installing the anti-vibration frame, untighten the fixing parts on the top and bottom of the frame.
Caution for installing discharge duct
- Static pressure of the discharge duct should be within the standard specification when installing the duct.
- If you remove the fan guard to install the discharge duct, make sure to install a safety net on the duct outlet. Foreign substances may enter the product and there could be a risk of personal injury.
- Wear protective equipment at all times when making galvanized sheet metal duct, since the worker may get injured by the sharp parts.
- When installing the outdoor unit under a tree or near a forest, leaves may get into the product and cause problems. Therefore, install a discharge duct to prevent foreign substance infiltration.

Installing the outdoor unit in various environments
Installing the outdoor unit around obstacles
It is necessary to install a discharge guide duct (field supply) to direct exhaust from the fan horizontally, when it is difficult to provide a minimum space of 2m (6.56ft) between the air outlet and a nearby obstacle.


WARNING
Should adopt bar type louver. Do not use a rain resistance louver.
[Bar type louver] [Rain resistance louver]


- Louver specifications.
- Angle criteria: less than 20°
- Opening ratio criteria: greater than 80%
Installing the outdoor unit in cold regions
- In cold regions with heavy snowfall, install a snow prevention duct as a sufficient countermeasure to prevent snow from accumulating on the outdoor unit. If the snow prevention duct is not installed, frost may accumulate on the heat exchanger and heating operation may not work normally. • The air outlet of the duct should not be directed into an enclosed space.

CAUTION
- Cautions regarding installing the frame and selecting the base ground
- The height (h) of the frame and the base ground should be higher than the "heaviest expected snowfall." – The area of the frame and the base ground should not be larger than the area of the outdoor unit. Snow may accumulate if the area of the frame or the base ground is larger.

Installing the outdoor unit in windy regions
- In windy regions such as near seashores, a protection wall or wind protection duct must be installed for normal operation of the outdoor unit. (Refer to the illustration of the snow prevention duct for installing the wind protection duct.) • Install the wind prevention duct with consideration of the prevailing wind direction. If the direction of the discharge part is the same as the prevailing wind direction, it could cause a decrease in product performance.

CAUTION
- Cautions regarding installing the frame and selecting the base ground
- The base ground must be solid, and the outdoor unit must be fixed with anchor bolts.
- Make sure to install the outdoor unit in a place strong enough to withstand its weight. If the place cannot withstand the weight of the outdoor unit, the outdoor unit may fall and cause personal injury.
- When installing on a rooftop subject to strong wind, countermeasures must be taken to prevent the unit from falling down.
- Use a frame that is resistant to corrosion.


WARNING
- When installing, make sure there is no leakage. When collecting the refrigerant, stop the compressor first before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works with the service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high which may lead to explosion and injury.
Refrigerant pipe work
- The length of refrigerant pipe should be as short as possible and the height difference between an indoor and outdoor unit should be minimized.
- Piping work must be done within allowable piping length, height difference, and the allowable length after branching.
- The pressure of the R-410A is high. Use only certified refrigerant pipe and follow the installation method.
- After installing the pipes, calculate the total length of the pipe to check if additional refrigerant is needed. When you need to charge the additional refrigerant, make sure to use R-410A refrigerant.
- Use clean refrigerant pipe and there shouldn't be any harmful ion, oxide, dust, iron content or moisture inside pipe.
- Use tools and accessories that fit on R-410A only.
| Tool | Installation process/purpose | Compatibility with conventional tool | |
| Pipe cutter | pe flaring | Pipe cutting | Compatible |
| Flaring tool P | |||
| Refrigerant machine oil | Refrigerant pipe installation | Apply refrigerant oil on flared part | Exclusive ether oil, ester oil, alkali benzene oil or synthetic oil |
| Torque wrench | Connect flare nut with pipe | Compatible | |
| Pipe bender | Pipe bending | ||
| Nitrogen gas | Air tightness test | Prevent oxidation within the pipe | |
| Welder | Pipe welding | ||
| Manifold gage | Air tightness test ~ additional refrigerant charging | Vacuuming, charging refrigerant and checking operation | Compatible |
| Refrigerant charging hose | Need exclusive one since there is risk of refrigerant leakage or inflow of impurities | ||
| Tool | Installation process/purpose | Compatibility with conventional tool |
| Vacuum pump | Pipe drying | Compatible (Use products which contain the check valve to prevent the oil from flowing backward into the outdoor unit.) Use the one that can be vacuumed up to -100.7kpa(5Torr). |
| Scale for refrigerant charging | Refrigerant charging Compatible | |
| Gas leak detector | Gas leak test | Need exclusive one (Ones used for R-134a is compatible) |
| Flare nut Must use the flare nut equipped with the product. | ||
Selecting refrigerant pipe

- Install the refrigerant pipe according to main pipe size of each outdoor unit capacity.
- When the pipe length (including elbow) between an outdoor unit and the farthest indoor unit exceeds 90m, you must increase the size of the pipe (main pipe) by one grade which connects between the outdoor unit to the first branch joint.
- For H/R model, When the pipe length (including elbow) between an outdoor unit and the farthest indoor unit exceeds 90m, you must increase the size of the liquid pipe by one grade among the pipes(main pipe) which connects between the outdoor unit to the first branch joint.
H/P
![graph LR A["16Ton"] --> B["Valve (A)"] C["12Ton"] --> D["Valve (B)"] E["6Ton"] --> F["Valve (C)"] G["Device"] --> H["Output (F)"] I["Valve (D)"] --> J["Switch"] K["Switch"] --> L["Switch"] M["Switch"] --> N["Switch"] O["Switch"] --> P["Switch"] Q["Switch"] --> R["Switch"] S["Switch"] --> T["Switch"]…](/content/2026/05/959055/images/74b1a71316a5777622c5c914680fd09b2ff4d20a97a869dfe40c3ec70a27c6bc.jpg)
Ex.) 34 Ton
| Ton No. | Pipe size (0.D) | ||||
| Liquid pipe Gas pipe | |||||
| mm inch | mm inch | ||||
| 16 (1) | 15.88 5/8 28.58 11/8 | ||||
| 28 (2) | 19.05 3/4 34.92 13/8 | ||||
| 34 (3) | 19.05 3/4 41.28 15/8 | ||||
Size of the pipe connected to the outdoor unit (A) Branch joint (C+E)
Select the size of the main pipe according to the table below.
| Outdoor unit capacity (MBH) (Cooling) | Outdoor unit capacity (kW) (Cooling) | *Maximum pipe length within 295ft (90m) | *Maximum pipe length over 295ft (90m) | ||||||
| Liquid Gas Liquid Gas | |||||||||
| inch | mm | inch | mm | inch | mm | inch | mm | ||
| Capacity ≤ 85 | Capacity ≤ 25 | ∅3/8 | ∅9.52 | ∅3/4 | ∅19.05 | ∅1/2 | ∅12.70 | ∅7/8 | ∅22.22 |
| 85 < Capacity ≤ 99 | 25 < Capacity ≤ 29 | ∅7/8 | ∅22.22 | ∅1 n### | ∅25.40 n### | ||||
| 99 < Capacity ≤ 120 | 29 < Capacity ≤ 35 | ∅1/2 | ∅12.70 | ∅11/8 | ∅28.58 | ∅5/8 | ∅15.88 | ∅11/8 | ∅28.58 |
| 120 < Capacity ≤ 140 | 35 < Capacity ≤ 41 | ||||||||
| 140 < Capacity ≤ 160 | 41 < Capacity ≤ 47 | ∅5/8 | ∅15.88 | ∅11/4 n### | ∅31.75 n### | ||||
| 160 < Capacity ≤ 181 | 47 < Capacity ≤ 53 | ∅3/4 | ∅19.05 | ||||||
| 181 < Capacity ≤ 222 | 53 < Capacity ≤ 65 | ||||||||
| 222 < Capacity ≤ 240 | 65 < Capacity ≤ 70 | ∅13/8 | ∅34.92 | ∅13/8 | ∅34.92 | ||||
| 240 < Capacity ≤ 336 | 70 < Capacity ≤ 98 | ∅3/4 | ∅19.05 | ∅7/8 | ∅22.22 | ∅11/2 n### | ∅38.10 n### | ||
| 336 < Capacity ≤ 467 | 98 < Capacity ≤ 137 | ∅15/8 | ∅41.28 | ∅15/8 | ∅41.28 | ||||
*Maximum pipe length: The pipe length between an outdoor unit and the farthest indoor unit. Note1) If ∅1" (25.40mm) pipe is not available on site, use ∅1 1/8" (28.58mm) pipe. Note2) If ∅1 1/4" (31.75mm) pipe is not available on site, use ∅1 3/8" (34.92mm) pipe. Note3) If ∅1 1/2" (38.10mm) pipe is not available on site, use ∅1 5/8" (41.28mm) pipe. For the case that the diameter of the default pipe of an outdoor unit does not match that of the pipe installed on the site, a socket is provided by default together with the outdoor unit.
Size of the pipe between branch joints (B)
Select the pipe size according to the sum of indoor unit capacity which will be connected after the branch.
✗ However, if the size of the pipe between branch joints (B) is bigger than the size of the pipe connected to the outdoor unit (A), apply the pipe size (A).
| Indoor unit capacity (MBH) | Indoor unit capacity (kW) | Branch pipe length within 148ft (45m) | Branch pipe length between 148ft~295ft (45~90m) | ||||||
| Liquid Gas Liquid Gas | |||||||||
| inch | mm | inch | mm | inch | mm | inch | mm | ||
| Capacity < 19 | Capacity < 5.7 | ∅1/4 | ∅6.35 | ∅1/2 | ∅12.70 | ∅3/8 | ∅9.52 | ∅5/8 | ∅15.88 |
| 19 ≤ Capacity < 55 | 5.7 ≤ Capacity < 16 | ∅3/8 | ∅9.52 | ∅5/8 | ∅15.86 | ∅1/2 | ∅12.70 | ∅3/4 | ∅19.05 |
| 55 ≤ Capacity < 79 | 16 ≤ Capacity < 23.2 | ∅3/4 | ∅19.05 | ∅7/8 | ∅22.22 | ||||
| 79 ≤ Capacity < 115 | 23.2 ≤ Capacity < 33.6 | ∅7/8 | ∅22.22 | ∅1 radell | ∅25.40 radell | ||||
| 115 ≤ Capacity < 133 | 33.6 ≤ Capacity < 39 | ∅1/2 | ∅12.70 | ∅11/8 | ∅28.58 | ∅5/8 | ∅15.88 | ∅11/8 | ∅28.58 |
| 133 ≤ Capacity < 150 | 39 ≤ Capacity < 44 | ||||||||
| 150 ≤ Capacity < 172 | 44 ≤ Capacity < 50.4 | ∅11/4 radell | ∅31.75 radell | ||||||
| 172 ≤ Capacity < 229 | 50.4 ≤ Capacity < 67.2 | ∅5/8 | ∅15.88 | ∅3/4 | ∅19.05 | ||||
| 230 ≤ Capacity < 248 | 67.2 ≤ Capacity < 72.8 | ∅13/8 | ∅34.92 | ∅13/8 | ∅34.92 | ||||
| 248 ≤ Capacity < 344 | 72.8 ≤ Capacity < 100.8 | ∅3/4 | ∅19.05 | ∅7/8 | ∅22.22 | ∅11/2 radell | ∅38.10 radell | ||
| 344 ≤ Capacity < 392 | 100.8 ≤ Capacity < 115 | ∅15/8 | ∅41.28 | ∅15/8 | ∅41.28 | ||||
| 392 ≤ Capacity < 592 | 115 ≤ Capacity < 173.6 | ∅13/4 radell | ∅44.45 radell | ||||||
| 592 ≤ Capacity < 676 | 173.6 ≤ Capacity < 198 | ∅7/8 | ∅22.22 | ∅13/4 radell | ∅44.45 radell | ∅1 radell | ∅25.40 radell | ∅21/8 | ∅53.98 |
| 676 ≤ Capacity < 860 | 198 ≤ Capacity < 252 | ∅21/8 | ∅53.98 | ||||||
| 860 ≤ Capacity | 252 ≤ Capacity | ∅1 radell | ∅25.40 radell | ∅11/8 | ∅28.58 | ||||
Note1) If ∅1" (25.40mm) pipe is not available on site, use ∅1 1/8" (28.58mm) pipe. Note2) If ∅1 1/4" (31.75mm) pipe is not available on site, use ∅1 3/8" (34.92mm) pipe. Note3) If ∅1 1/2" (38.10mm) pipe is not available on site, use ∅1 5/8" (41.28mm) pipe. Note4) If ∅1 3/4" (44.45mm) pipe is not available on site, use ∅2 1/8" (53.98mm) pipe.
Branch joint between outdoor units (C)
Select a branch joint according to the sum of the capacity of outdoor units connected to the branch joint.
| Classification | Outdoor unit capacity | Model name | |
| MBH | kW | ||
| Y-joint for outdoor unit (C) | Capacity ≤ 467 | Capacity ≤ 137 | MXJ-TA3819M |
| 467 < Capacity | 137 < Capacity MXJ-TA4422M | ||
First branch joint (D)
Select according to the sum of the capacity of the outdoor unit.
| Classification | Outdoor unit capacity | Model name | |
| MBH | kW | ||
| Y-joint (D) | Capacity ≤ 140 Capacity ≤ 41 | MXJ-YA2512M | |
| Capacity ≤ 160 Capacity ≤ 47 | MXJ-YA2812M | ||
| Capacity ≤ 239 | Capacity ≤ 70 | MXJ-YA2815M | |
| Capacity ≤ 336 | Capacity ≤ 98 | MXJ-YA3419M | |
| Capacity ≤ 467 | Capacity ≤ 137 | MXJ-YA4119M | |
| 467 < Capacity | 137 < Capacity MXJ-YA4422M | ||
Branch joint (E)
Select a branch joint according to the sum of indoor unit capacity which will be connected after the branch.
* However, if the branch joint (E) is larger than the first branch joint (D), use a branch joint of the same size as the first branch joint (D).
| Classification | Indoor unit capacity | Model name | |
| MBH | kW | ||
| Y-joint (E) | Capacity < 55 | Capacity < 16 | MXJ-YA1509M |
| 55 ≤ Capacity < 133.16 ≤ | Capacity < 39 MXJ-YA2512M | ||
| 133 ≤ Capacity < 172 | 39 ≤ Capacity < 50.4 | MXJ-YA2812M | |
| 172 ≤ Capacity < 248 | 50.4 ≤ Capacity < 72.8 | MXJ-YA2815M | |
| 248 ≤ Capacity < 344 | 72.8 ≤ Capacity < 100.8 | MXJ-YA3419M | |
| 344 ≤ Capacity < 478 | 100.8 ≤ Capacity < 140 | MXJ-YA4119M | |
| 478 < Capacity | 140 < Capacity | MXJ-YA4422M | |
| Distribution header (E) | Capacity < 172 (for 4 rooms) | Capacity < 50.4 (for 4 rooms) | MXJ-HA2512M |
| Capacity < 248 (for 8 rooms) | Capacity < 72.8 (for 8 rooms) | MXJ-HA3115M | |
| Capacity < 478 (for 8 rooms) | Capacity < 140 (for 8 rooms) | MXJ-HA3819M | |
Size of the pipe between the branch joint and the indoor unit (F)
Select according to the capacity of the indoor unit.
| Indoor unit capacity | Liquid | Gas | |||
| MBH | kW inch mm | inch mm | |||
| Capacity ≤ 20 | Capacity ≤ 6 | ∅1/4 | ∅6.35 | ∅1/2 | ∅12.7 |
| 20 < Capacity ≤ 54 | 6 < Capacity ≤ 16 | ∅3/8 | ∅9.52 | ∅5/8 | ∅15.88 |
| 54 < Capacity ≤ 78 | 16 < Capacity ≤ 23 | ∅3/8 | ∅9.52 | ∅3/4 | ∅19.05 |
| 78 < Capacity | 23 < Capacity | ∅3/8 | ∅9.52 | ∅7/8 | ∅22.22 |
* If the criteria for selecting the branch in the outdoor installation manual and the branch installation manual are different, please select the branch in accordance with the outdoor installation manual.
H/P
When all the following conditions are met, install the main liquid pipe that is one step smaller to reduce piping load and the amount of refrigerant.
Note that the refrigerant for the main liquid pipe must be added by the specified amount upon reduction.
Condition 1: The vertical piping length is less than 131 ft (40 m)
Condition 2: For BG units, allowable length A (ft) ≥ max. piping length (ft) / {1 - (vertical piping length (ft) * 0.0046)}
※ Max. piping length: The equivalent length (ft) of piping from the outdoor unit to the farthest indoor unit. For SI units, allowable length A (m) ≥ max. piping length (m) / {1 - (vertical piping length (m) * 0.015)}
※ Max. piping length: The equivalent length (m) of piping from the outdoor unit to the farthest indoor unit
※ If the conditions above are satisfied and one-size smaller piping has been installed, set the "liquid pipe (main pipe) size reduction" option.
- Length allowed to reduce the diameter of liquid pipe, A (equivalent length)
| Outdoor unit capacity (Ton) | Maximum pipe length within 90m (295.3ft) Maximum pipe length over 90m (295.3ft) | |||||||
| Pipe diameter Allowable length Pipe diameter Allowable length | ||||||||
| mm inch m ft mm inch m ft | ||||||||
| 6 | This capacity is not supported. | |||||||
| 8 This capacity is not supported. | ||||||||
| 10 | 9.52 | 3/8 | 50 | 164 | 12.7 | 1/2 | 200 | 656 |
| 12 | 9.52 | 3/8 | 30 | 98 | 12.7 | 1/2 | 160 | 525 |
| 14 | 12.7 | 1/2 | 90 | 295 | 15.88 | 5/8 | 200 | 656 |
| 16 | 12.7 | 1/2 | 90 | 295 | 15.88 | 5/8 | 200 | 656 |
| 18 | 12.7 | 1/2 | 80 | 262 | 15.88 | 5/8 | 200 | 656 |
| 20 | 12.7 | 1/2 | 60 | 197 | 15.88 | 5/8 | 190 | 623 |
| 22 | 15.88 | 5/8 | 90 | 295 | 19.05 | 3/4 | 200 | 656 |
| 24 | 15.88 | 5/8 | 90 | 295 | 19.05 | 3/4 | 200 | 656 |
| 26 | 15.88 | 5/8 | 90 | 295 | 19.05 | 3/4 | 200 | 656 |
| 28 | 15.88 | 5/8 | 90 | 295 | 19.05 | 3/4 | 200 | 656 |
| 30 | 15.88 | 5/8 | 90 | 295 | 19.05 | 3/4 | 200 | 656 |
| 32 | 15.88 | 5/8 | 80 | 262 | 19.05 | 3/4 | 200 | 656 |
| 34 | 15.88 | 5/8 | 70 | 230 | 19.05 | 3/4 | 200 | 656 |
| 36 | 15.88 | 5/8 | 60 | 197 | 19.05 | 3/4 | 190 | 623 |
| 38 | 15.88 | 5/8 | 60 | 197 | 19.05 | 3/4 | 170 | 558 |
| 40 | 15.88 | 5/8 | 50 | 164 | 19.05 | 3/4 | 150 | 492 |
E.g. 1: For a site with 18 tons (BG units), max. piping length of 460 ft (395 ft-long horizontal piping and 65 ft-long vertical piping) condition, allowable length A ≥ max. piping length / {1 - (vertical piping length * 0.0046)}
656ft ≥ 460ft / {1 - (65 * 0.0046)} = 460ft / 0.701 = 656ft
Accordingly, the max. piping length of 460 ft (395 ft-long horizontal piping and 65 ft-long vertical piping) is allowable.
E.g. 2: For a site with 18 tons (SI units), max. piping length of 140 m (120 m-long horizontal piping and 20 m-long vertical piping) condition, allowable length A ≥ max. piping length / {1 - (vertical piping length * 0.015)}
200m ≥ 140m / {1 - (20 * 0.015)} = 140m / 0.7 = 200m
Accordingly, the max. piping length of 140m (120m-long horizontal piping and 20m-long vertical piping) is allowable.
![graph LR A["16Ton 12Ton"] --> B["(1)"] A --> C["(2)"] A --> D["(3)"] E["6Ton"] --> F["(4)"] E --> G["(5)"] E --> H["(6)"] I["(A)"] --> J["(1)"] K["(B)"] --> L["(2)"] M["(C)"] --> N["(3)"] O["(D)"] --> P["(4)"] Q["(E)"] --> R["(5)"] S["(F)"] --> T["(6)"]](/content/2026/05/959055/images/e8ae993880e98474fe78fcc6d9ff0de0df3384e2d08cebd6d6e377a2da792061.jpg)
Size of the pipe connected to the outdoor unit (A) Branch joint (C+E)
Select the size of the main pipe according to the below table.
| Outdoor unit capacity (MBH) (Cooling) | Outdoor unit capacity (kW) (Cooling) | *Maximum pipe length within 295ft (90m) *Maximum pipe length over 295ft (90m) | |||||||||||
| Liquid | Low pressure gas | High pressure gas | Liquid | Low pressure gas | High pressure gas | ||||||||
| inch | mm | inch | mm | inch | mm | inch | mm | inch | mm | inch | mm | ||
| Capacity ≤ 85 | Capacity ≤ 25 | ∅5/6 | ∅9.52 | ∅3/4 | ∅19.05 | ∅5/8 | ∅15.83 | ∅1/2 | ∅12.70 | ∅5/4 | ∅79.05 | ∅5/8 | ∅15.66 |
| 85 < Capacity ≤ 99 | 25 < Capacity ≤ 29 | ∅9/8 | ∅67.27 | ∅34/10 | ∅9.05 | ∅9/6 | ∅97.27 | ∅5/4 | ∅19.05 | ||||
| 99 < Capacity ≤ 120 | 29 < Capacity ≤ 35 | ∅7/2 | ∅12.70 | ∅11/6 | ∅78.59 | ∅5/8 | ∅15.89 | ∅77/8 | ∅79.56 | ∅7/8 | ∅77.77 | ||
| 120 < Capacity ≤ 140 | 35 < Capacity ≤ 41 | ∅7/8 | ∅77.77 | ||||||||||
| 140 < Capacity ≤ 160 | 41 < Capacity ≤ 47 | ||||||||||||
| 160 < Capacity ≤ 181 | 47 < Capacity ≤ 53 | ∅5/8 | ∅10.68 | ∅5/4 | ∅79.05 | ||||||||
| 181 < Capacity ≤ 222 | 53 < Capacity ≤ 65 | ∅11/6 | ∅78.59 | ∅11/6 | ∅78.58 | ||||||||
| 222 < Capacity ≤ 240 | 65 < Capacity ≤ 70 | ∅15/8 | ∅54.92 | ∅15/6 | ∅54.92 | ||||||||
| 240 < Capacity ≤ 336 | 70 < Capacity ≤ 98 | ∅5/4 | ∅19.05 | ∅7/8 | ∅22.22 | ||||||||
| 336 < Capacity ≤ 457 | 98 < Capacity ≤ 137 | ∅15/8 | ∅41.28 | ∅15/8 | ∅54.92 | ∅15/8 | ∅41.28 | ∅15/8 | ∅54.92 | ||||
| 457 < Capacity ≤ 583 | 137 < Capacity ≤ 171 | ||||||||||||
*Maximum pipe length: The pipe length between an outdoor unit and the farthest indoor unit.
※ For HR model, only increase the size of the liquid pipe If pipe length exceeds 295ft (90m).
* For the case that the diameter of the default pipe of an outdoor unit does not match that of the pipe installed on the site, a socket is provided by default together with the outdoor unit
Size of the pipe between branch joints (B)
Select the pipe size according to the sum of indoor unit capacity which will be connected after the branch. However, if the size of the pipe between branch joints (B) is bigger than the size of the pipe connected to the outdoor unit (A), apply the pipe size (A).
| Indoor unit capacity (kW) | Indoor unit capacity (kW) | Branch pipe length within 148ft (45m) | Branch pipe length between 148ft-295ft (45~90m) | ||||||||||
| Liquid | Low pressure gas | High pressure gas | Liquid | Low pressure gas | High pressure gas | ||||||||
| inch | mm | inch | mm | inch | mm | inch | mm | inch | mm | inch | mm | ||
| Capacity<19 | Capacity<5.7 | ∅1/4 | ∅6.35 | ∅1/2 | ∅7.30 | ∅3/8 | ∅9.52 | ∅3/9 | ∅9.52 | ∅7/2 | ∅12.70 | ∅3/8 | ∅9.52 |
| 19 ≤ Capacity <55 | 5.7 ≤ Capacity <16 | ∅5/8 | ∅9.57 | ∅5/8 | ∅15.88 | ∅1/2 | ∅17.70 | ∅7/7 | ∅12.70 | ∅5/8 | ∅15.88 | ∅1/7 | ∅17.70 |
| 55 ≤ Capacity <79 | 16 ≤ Capacity <23.2 | ∅5/8 | ∅19.05 | ∅5/8 | ∅15.88 | ∅3/4 | ∅16.05 | ∅5/8 | ∅15.88 | ||||
| 79 ≤ Capacity <115 | 23.2 ≤ Capacity <33.6 | ∅7/8.69 | ∅7 | ∅5/8.69 | ∅7.05 | ∅5/8 | ∅17.77 | ∅5/4 | ∅19.05 | ||||
| 115 ≤ Capacity <133 | 33.6 ≤ Capacity <39 | ∅7/2 | ∅7.20 | ∅11/8 | ∅26.58 | ∅5/8 | ∅15.88 | ∅11/8 | ∅26.58 | ||||
| 133 ≤ Capacity <150 | 39 ≤ Capacity <44 | ∅7/8 | ∅22.22 | ∅7/8 | ∅22.22 | ||||||||
| 150 ≤ Capacity <172 | 44 ≤ Capacity <50.4 | ||||||||||||
| 172 ≤ Capacity <229 | 50.4 ≤ Capacity <67.2 | ∅5/8 | ∅10.88 | ∅7.78 | ∅26.38 | ∅5/4 | ∅19.05 | ∅11/8 | ∅28.58 | ||||
| 230 ≤ Capacity <248 | 67.2 ≤ Capacity <72.8 | ∅13/8 | ∅34.92 | ∅13/8 | ∅34.92 | ||||||||
| 248 ≤ Capacity <344 | 72.8 ≤ Capacity <100.8 | ∅5/4 | ∅19.05 | ∅7/8 | ∅22.22 | ||||||||
| 344 ≤ Capacity <392 | 100.8 ≤ Capacity <115 | ∅15/8 | ∅41.28 | ∅13/8 | ∅34.52 | ∅13/8 | ∅41.28 | ∅7.5/8 | ∅54.92 | ||||
| 392 ≤ Capacity <592 | 115 ≤ Capacity <173.6 | ||||||||||||
| 592 ≤ Capacity <676 | 173.6 ≤ Capacity <198 | ∅7/6 | ∅22.22 | ∅13/4mm-1 | ∅34.75mm-8 | ∅15/8 | ∅41.29 | ∅1 mm-1 | ∅75.40mm-1 | ∅7.5/4mm-8 | ∅30.45mm-8 | ∅15/8 | ∅41.28 |
| 676 ≤ Capacity <860 | 196 ≤ Capacity <252 | ∅27/8 | ∅53.98 | ∅21/8 | ∅53.98 | ||||||||
| 860 ≤ Capacity | 252 ≤ Capacity | ∅1mm-1 | ∅6.40mm-1 | ∅13/4mm-1 | ∅24.45mm-1 | ∅11/8 | ∅26.58 | ∅13/4mm-1 | ∅44.55mm-1 | ||||
Note1) If ø1" (25.40mm) pipe is not available on site, use ø1 1/8" (28.58mm) pipe. Note2) If ø1 1/4" (31.75mm) pipe is not available on site, use ø1 3/8" (34.92mm) pipe. Note3) If ø1 1/2" (38.10mm) pipe is not available on site, use ø1 5/8" (41.28mm) pipe. Note4) If ø1 3/4" (44.45mm) pipe is not available on site, use ø2 1/8" (53.98mm) pipe.
Ex.) 34 Ton
| Ton No. | Pipe size (O.D) | ||||||
| Liquid Gas High pressure Gas | |||||||
| mm inch mm inch mm inch | |||||||
| 10 | (1) | 15.88 | 5/8 | 28.58 | 11/8 | 28.58 | 11/8 |
| 28 | (2) | 19.05 | 3/4 | 34.92 | 13/8 | 28.58 | 11/8 |
| 34 | (3) | 19.05 | 3/4 | 41.28 | 15/8 | 34.92 | 13/8 |
Branch joint between outdoor units (C)
Select a branch joint according to the sum of the capacity of outdoor units connected to the branch joint.
| Classification | Outdoor unit capacity | Model name | |
| MBH | kW | ||
| Y-joint for liquid/low pressure gas pipe (C) | Capacity ≤ 467 | Capacity ≤ 137 | MXJ-TA3419M |
| 467 < Capacity | 137 < Capacity | MXJ-TA4122M | |
| Y-joint for high pressure gas pipe (C) | Capacity ≤ 467 | Capacity ≤ 137 | MXJ-TA3100M |
| 467 < Capacity | 137 < Capacity | MXJ-TA3800M | |
First branch joint (D)
Select according to the sum of the capacity of the outdoor unit.
| Classification | Outdoor unit capacity | Model name | |
| MBH | kW | ||
| Y-joint for liquid/low pressure gas pipe (D) | Capacity ≤ 140 | Capacity ≤ 41 | MXJ-YA2512M |
| Capacity ≤ 160 | Capacity ≤ 47 | MXJ-YA2812M | |
| Capacity ≤ 239 | Capacity ≤ 70 | MXJ-YA2815M | |
| Capacity ≤ 336 | Capacity ≤ 98 | MXJ-YA3419M | |
| Capacity ≤ 467 | Capacity ≤ 137 | MXJ-YA4119M | |
| 467 < Capacity | 137 < Capacity | MXJ-YA4422M | |
| Y-joint for high pressure gas pipe (D) | Capacity ≤ 85 | Capacity ≤ 25 | MXJ-YA1500M |
| Capacity ≤ 239 | Capacity ≤ 70 | MXJ-YA2500M | |
| Capacity ≤ 467 | Capacity ≤ 137 | MXJ-YA3100M | |
| 467 < Capacity | 137 < Capacity | MXJ-YA3800M | |
Branch joint (E)
Select a branch joint according to the sum of indoor unit capacity which will be connected after the branch.
※ However, if the branch joint (E) is bigger than the first branch joint (D), apply the branch joint of the same size as the first branch joint (D).
| Classification | Indoor unit capacity | Model name | |
| MBH | kW | ||
| Y-joint for liquid/low pressure gas pipe (E) | Capacity < 55 | Capacity < 16 | MXJ-YA1509M |
| 55 ≤ Capacity < 133 16 | ≤ Capacity < 39 MXJ | YA2512M | |
| 133 ≤ Capacity < 172 39 | ≤ Capacity < 50.4 MXJ | YA2812M | |
| 172 ≤ Capacity < 248 | 50.4 ≤ Capacity < 72.8 | MXJ-YA2815M | |
| 248 ≤ Capacity < 344 | 72.8 ≤ Capacity < 100.8 | MXJ-YA3419M | |
| 344 ≤ Capacity < 478 | 100.8 ≤ Capacity < 140 | MXJ-YA4119M | |
| 478 < Capacity | 140 < Capacity | MXJ-YA4422M | |
| Y-joint for high pressure gas pipe (E) | Capacity < 79 | Capacity < 23.2 | MXJ-YA1500M |
| 79 ≤ Capacity < 248 23 | 2 ≤ Capacity < 72.8 MXJ | -YA2500M | |
| 248 ≤ Capacity < 478 | 72.8 ≤ Capacity < 140 | MXJ-YA3100M | |
| 478 < Capacity | 140 ≤ Capacity | MXJ-YA3800M | |
Size of the pipe between the branch joint and the indoor unit (F)
Select according to the capacity of the indoor unit.
| Indoor unit capacity | Liquid | Gas | |||
| MBH | kW | inch | mm | inch | mm |
| Capacity ≤ 20 | Capacity ≤ 6 | ∅1/4 | ∅6.35 | ∅1/2 | ∅12.7 |
| 20 < Capacity ≤ 54 | 6 < Capacity ≤ 16 | ∅3/8 | ∅9.52 | ∅5/8 | ∅15.88 |
| 54 < Capacity ≤ 78 | 16 < Capacity ≤ 23 | ∅3/8 | ∅9.52 | ∅3/4 | ∅19.05 |
| 78 < Capacity | 23 < Capacity | ∅3/8 | ∅9.52 | ∅7/8 | ∅22.22 |
* If the criteria for selecting the branch in the outdoor installation manual and the branch installation manual are different, please select the branch in accordance with the outdoor installation manual.
H/R
When all the following conditions are met, install the main liquid pipe that is one step smaller to reduce piping load and the amount of refrigerant.
Note that the refrigerant for the main liquid pipe must be added by the specified amount upon reduction.
Condition 1: The vertical piping length is less than 131 ft (40 m)
Condition 2: For Imperial units, allowable length A (ft) ≥ max. piping length (ft) / {1 - (vertical piping length (ft) * 0.0046)}
※ Max. piping length: The equivalent length (ft) of piping from the outdoor unit to the farthest indoor unit For SI units, allowable length A (m) ≥ max. piping length (m) / {1 - (vertical piping length (m) * 0.015)}
※ Max. piping length: The equivalent length (m) of piping from the outdoor unit to the farthest indoor unit
If the conditions above are satisfied and one-size smaller piping has been installed, set the "liquid pipe (main pipe) size reduction" option.
Length allowed to reduce the diameter of liquid pipe, A (equivalent length)
| Outdoor unit capacity (Ton) | Maximum pipe length within 90m (295.3ft) Maximum pipe length over 90m (295.3ft) | |||||||
| Pipe diameter Allowable length Pipe diameter Allowable length | ||||||||
| mm inch m ft mm inch m ft | ||||||||
| 6 | This capacity is not supported. | |||||||
| 8 This capacity is not supported. | ||||||||
| 10 | 9.52 | 3/8 | 50 | 164 | 12.7 | 1/2 | 200 | 656 |
| 12 | 9.52 | 3/8 | 30 | 98 | 12.7 | 1/2 | 160 | 525 |
| 14 | 12.7 | 1/2 | 90 | 295 | 15.88 | 5/8 | 200 | 656 |
| 16 | 12.7 | 1/2 | 90 | 295 | 15.88 | 5/8 | 200 | 656 |
| 18 | 12.7 | 1/2 | 80 | 262 | 15.88 | 5/8 | 200 | 656 |
| 20 | 12.7 | 1/2 | 60 | 197 | 15.88 | 5/8 | 190 | 623 |
| 22 | 15.88 | 5/8 | 90 | 295 | 19.05 | 3/4 | 200 | 656 |
| 24 | 15.88 | 5/8 | 90 | 295 | 19.05 | 3/4 | 200 | 656 |
| 26 | 15.88 | 5/8 | 90 | 295 | 19.05 | 3/4 | 200 | 656 |
| 28 | 15.88 | 5/8 | 90 | 295 | 19.05 | 3/4 | 200 | 656 |
| 30 | 15.88 | 5/8 | 90 | 295 | 19.05 | 3/4 | 200 | 656 |
| 32 | 15.88 | 5/8 | 80 | 262 | 19.05 | 3/4 | 200 | 656 |
| 34 | 15.88 | 5/8 | 70 | 230 | 19.05 | 3/4 | 200 | 656 |
| 36 | 15.88 | 5/8 | 60 | 197 | 19.05 | 3/4 | 190 | 623 |
| 38 | 15.88 | 5/8 | 60 | 197 | 19.05 | 3/4 | 170 | 558 |
| 40 | 15.88 | 5/8 | 50 | 164 | 19.05 | 3/4 | 150 | 492 |
E.g. 1: For a site with 18 tons (BG units), max. piping length of 460 ft (395 ft-long horizontal piping and 65 ft-long vertical piping) condition, allowable length A ≥ max. piping length / {1 - (vertical piping length * 0.0046)}
656ft ≥ 460ft / {1 - (65 * 0.0046)} = 460ft / 0.701 = 656ft
Accordingly, the max. piping length of 460 ft (395 ft-long horizontal piping and 65 ft-long vertical piping) is allowable.
E.g. 2: For a site with 18 tons (SI units), max. piping length of 140 m (120 m-long horizontal piping and 20 m-long vertical piping) condition, allowable length A ≥ max. piping length / {1 - (vertical piping length * 0.015)}
Accordingly, the max. piping length of 140m (120m-long horizontal piping and 20m-long vertical piping) is allowable.
Additional refrigerant
H/PH/R![graph TD A["144MBH (12Ton)"] --> B["1/2" (5m/16.4')"] B --> C["12MBH"] B --> D["1/4" (5m/16.4')"] D --> E["24MBH"] D --> F["1/4" (10m/32.8')"] F --> G["24MBH"] F --> H["1/4" (15m/49.2)"] H --> I["18MBH"] H --> J["18MBH"] H --> K["18MBH"] H --> L["18MBH"] H --> M["12MBH"] C --> N[…](/content/2026/05/959055/images/4fd7fdeebcf5735c8c5c51cb9b7c4d59de99fec745139fd18f237eee9d88012c.jpg)
![graph TD A["MCU MCU"] -->|1/2" (10m/32.8')| B["216MBH (18Ton) [144MBH + 72MBH"]] A -->|1/2" (5m/16.4')| C["36MBH"] A -->|1/2" (10m/32.8')| D["12MBH"] A -->|1/2" (10m/32.8')| E["36MBH"] A -->|1/4" (15m/49.2')| F["36MBH"] A -->|1/4" (2m/6.6')| G["36MBH"] A -->|1/4" (18m/59.1')| H["24MBH"] A -->|3/8" (…](/content/2026/05/959055/images/42441d62e3595037eaa30a245e0f505fd93cc40dec2a4d9a035fad5312ad830b.jpg)
Refrigerant pipe installation
- Basic amount of refrigerant within the outdoor unit [lb(kg)]
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
| Classification AM072BXVG** AM096BXVG** AM120BXVG** AM144BXVG** | ||||
| Basic amount [lb(kg)] 13.7 (6.2) 17.6 (8) 17.6 (8) 23.1 (10.5) | ||||
| Classification AM168BXVG** AM192BXVG** AM216BXVG** AM240BXVG** | ||||
| Basic amount [lb(kg)] | 23.1 (10.5) | 27.6 (12.5) | 34.2 (15.5) | 34.2 (15.5) |
| Classification | AM072BXVT** AM096BXVT** AM120BXVT** | |||
| Basic amount [lb(kg)] | 17.6 (8) | 23.1 (10.5) | 23.1 (10.5) | |
• Amount of additional refrigerant depending on the pipe size (a)
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
| Size of liquid pipe[mm (inch)] | 1/4 ( 6.35 ) | 3/8 ( 9.52 ) | 1/2 ( 12.7 ) | 5/8 ( 15.88 ) | 3/4 ( 19.05 ) | 7/8 ( 22.22 ) | 1 ( 25.4 ) | 1\ 1/8 ( 28.58 ) |
| Additional amount[lb/ft (kg/m)] | 0.013(0.02) | 0.04(0.06) | 0.084(0.125) | 0.121(0.18) | 0.181(0.27) | 0.235(0.35) | 0.356(0.53) | 0.437(0.65) |
| Amount ofrefrigerant addedwhen the diameterof liquid pipe isreduced[kg/m (lb/ft)] | - | 0.054(0.08) | 0.087(0.13) | 0.131(0.195) | 0.188(0.28) | 0.282(0.42) | 0.356(0.53) | - |
- For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.0067lb/ft (0.01kg/m) regardless of the pipe size.
Refrigerant pipe installation
- Amount of additional refrigerant for each indoor unit ( ) b
Unit : lb(kg)
| Capacity Index (MBH) | 5 | 6 | 7 | 9 | 12 | 15 | 18 | 20 | 24 | 27 | 28 | 30 | 32 | 36 | 42 | 48 | 54 | 60 | 72 | 76 | 96 | 144 |
| 1way cassette (AM****N1DCH/**) | 0.55(0.25) | 0.55(0.25) | 0.55(0.25) | |||||||||||||||||||
| 1way cassette (AM****N1PCH/**) | 0.33(0.15) | 0.33(0.15) | 0.55(0.25) | 0.55(0.25) | 0.71(0.32) | 0.71(0.32) | 0.71(0.32) | |||||||||||||||
| 4way cassette S (600x600) (AM****NNDCH/**) | 0.64(0.29) | 0.64(0.29) | 0.64(0.29) | 0.64(0.29) | 0.82(0.37) | 0.82(0.37) | ||||||||||||||||
| 4way cassette S (AM***RN4DCH/**) | 0.99(0.45) | 0.99(0.45) | 0.99(0.45) | 1.26(0.57) | 1.26(0.57) | 2.20(1.00) | 2.20(1.00) | 2.20(1.00) | ||||||||||||||
| 4way cassette S (AM***BN4PCH/**) | 1.61(0.73) | 1.61(0.73) | 1.61(0.73) | 1.61(0.73) | 1.61(0.73) | 1.94(0.88) | 1.94(0.88) | 1.94(0.88) | ||||||||||||||
| 360 cassette (AM***KN4DCH/**) | 0.99(0.45) | 0.99(0.45) | 0.99(0.45) | 0.99(0.45) | 1.52(0.69) | 1.52(0.69) | 1.52(0.69) | |||||||||||||||
| LSP duct (AM****NLDCH/**) | 0.77(0.35) | 0.77(0.35) | 0.77(0.35) | 0.99(0.45) | 0.99(0.45) | 0.93(0.42) | 0.93(0.42) | 1.37(0.62) | ||||||||||||||
| MSP duct (AM***ANMDCH/**) | 0.99(0.45) | 0.99(0.45) | 0.99(0.45) | 0.99(0.45) | 0.99(0.45) | 1.50(0.68) | ||||||||||||||||
| HSP duct (AM***ANHDCH/**) | 1.50(0.68) | 1.50(0.68) | 1.50(0.68) | 1.85(0.84) | 1.85(0.84) | |||||||||||||||||
| HSP duct (AM***FNHDCH/**) (AM***JNHDCH/**) | 2.01(0.91) | 2.60(1.18) | 2.60(1.18) | |||||||||||||||||||
| OAP duct (AM****NE*CH/**) | 2.60(1.18) | 2.60(1.18) | ||||||||||||||||||||
| Floor Standing (AM****NFDCH/**) (AM****NGDCH/**) | 0.26(0.12) | 0.49(0.22) | 0.49(0.22) | 0.71(0.32) | 0.71(0.32) | |||||||||||||||||
| Ceiling (AM****NCDCH/**) | 0.86(0.39) | 0.86(0.39) | 1.23(0.56) | 2.09(0.95) | ||||||||||||||||||
| MPAHU(V-AHU) (AM****NZDCH/**) | 0.73(0.33) | 1.10(0.50) | 1.10(0.50) | 1.83(0.83) | 1.94(0.88) | 2.60(1.18) | 2.80(1.27) | 3.73(1.69) | 3.73(1.69) | |||||||||||||
| Wall mounted (with EEV) (AM****NVDCH/**) (AM****NQDCH/**) | 0.51(0.23) | 0.51(0.23) | 0.71(0.32) | 0.71(0.32) | 1.06(0.48) | 1.06(0.48) | 1.06(0.48) | 1.41(0.64) | 1.50(0.68) | |||||||||||||
| Hydro unit HE (AM****NBDCH/**) | 1.32(0.6) | 1.32(0.6) | 1.54(0.7) | 2.65(1.2) | ||||||||||||||||||
| Hydro unit HT (AM****NBFCB/**) | 1.32(0.6) | 1.32(0.6) | ||||||||||||||||||||
| MCU (MCU-S*NE**N) | 1.10 (0.50) | |||||||||||||||||||||
※ If there is no additional refrigerant value for the indoor unit in the above table, refer to the indoor unit installation manual.
- If AHU kit is included among the indoor units, you must add 0.018kg(0.04lb) of refrigerant for every1MBH of AHU capacity increase. Note1) In case the capacity conjunction of the Hydro Unit HT exceeds 50 % among the total indoor unit, please don't put the additional refrigerant.
• Method to calculate total amount of additional refrigerant
- Amount of additional refrigerant depending on the pipe length ( a)
- Amount of additional refrigerant for each indoor unit (b) = (Amount of additional refrigerant for each connected indoor unit) ※ Refer to the table
- Total amount of additional refrigerant = ⓐ+b
※ Sum of total amount of additional refrigerant and the basic amount of refrigerant should not exceed 100kg (220lb). If the refrigerant exceeds 100kg (220lb), separate the module so that weight of the refrigerant doesn't exceed 100kg (220lb).
Ex> If the outdoor unit's basic refrigerant amount is 8.7kg (19.1lb), the total amount of additional refrigerant(a+b) should not exceed 91.3kg (200.9lb).
• Example of refrigerant calculation for HP models
| Classification | Size of liquid pipe [mm (inch)] | Length [m (ft)] | Unit amount of refrigerant [kg/m (lb/ft)] | Amount of additional refrigerant [kg (lb)] | Total amount of additional refrigerant [kg (lb)] |
| 1 | 2 | 1 × 2 | (1 × 2) | ||
| Liquid pipe (a) | ∅6.35 (∅1/4) 35 (114.8) | 0.02 (0.013) 0.7 (1.49) | a 5.575 (12.19) | ||
| ∅9.52 (∅3/8) 50 (164.0) | 0.06 (0.040) 3.0 (6.56) | ||||
| ∅12.70 (∅1/2) 15 (49.2) | 0.125 (0.084) 1.875 (4.13) |
| Classification | Model name of indoor unit | Number of indoor units | Unit amount of refrigerant [kg/EA (lb/EA)] | Amount of additional refrigerant [kg (lb)] | Total amount of additional refrigerant [kg (lb)] |
| 1 | 2 | 1 × 2 | (1 × 2) | ||
| Indoor unit (b) | 4way cassette (AM018RN4DCH) | 4 0.57 (1.26) | 2.28 (4.92) | b 3.78 (8.22) | |
| LSP duct (AM024FNLDCH) | 2 0.45 (0.99) | 0.90 (1.98) | |||
| LSP duct (AM012FNLDCH) | 1 0.35 (0.77) | 0.35 (0.77) | |||
| 1way cassette (AM012AN1PCH) | 1 0.25 (0.55) | 0.25 (0.55) |
- Total amount of refrigerant (a+b) = 5.575 + 3.78 = 9.355 (kg) = 12.19 + 8.22 = 20.41 (lb)
• Example of refrigerant calculation for HR models
| Classification | Size of liquid pipe [mm (inch)] | Length [m (ft)] | Unit amount of refrigerant [kg/m (lb/ft)] | Amount of additional refrigerant [kg (lb)] | Total amount of additional refrigerant [kg (lb)] |
| 1 | 2 | 1×2 | Σ(1×2) | ||
| Liquid pipe (a) | ∅6.35 (∅1/4) 15 (49.2) | 0.02 (0.013) 0.3 (0.64) | a 11.965 (26.24) | ||
| ∅9.52 (∅3/8) | 112 (367.5) 0.06 (0) | 040) 6.72 (14.70) | |||
| ∅12.70 (∅1/2) 25 (82.0) | 0.125 (0.084) | 3.125 (6.89) | |||
| ∅15.88 (∅ 5/8) | 10 (32.8) | 0.18 (0.121) | 1.8 (3.97) | ||
| ∅ 6.35 (∅ 1/4) (EEV Kit ~ indoor unit) | 2 (6.6) | 0.01 (0.0067) | 0.02 (0.04) |
| Classification | Model name of indoor unit | Number of indoor units | Unit amount of refrigerant [kg/EA (lb/EA)] | Amount of additional refrigerant [kg (lb)] | Total amount of additional refrigerant [kg (lb)] |
| 1 | 2 | 1 × 2 | (1 × 2) | ||
| Indoor unit (b) | 4way cassette (AM024RN4DCH) | 4 | 0.73 (1.61) 2.92 (6.44) | b5.88 (12.97) | |
| 4way cassette (AM036RN4DCH) | 3 0.88 (1.94) 2.64 (5.82) | ||||
| Wall mounted (AM012TNVDCH) | 1 0.32 (0.71) | 0.32 (0.71) | |||
| MCU | 2 | 0.50 (1.10) | 1 (2.20) |
- Total amount of refrigerant (a+b) = 11.965 + 5.88 = 17.845 (kg) = 26.24 + 12.97 = 39.21 (lb)
Temper grade and minimum thickness of the refrigerant pipe
| Outer diameter Minimum thickness | Temper grade | |||
| mm inch | mm inch | |||
| 6.35 1/4 0 | 70 0.028 | Annealed | ||
| 9.52 3/8 0 | 70 0.028 | |||
| 12.70 1/2 0 | 80 0.031 | |||
| 15.88 5/8 1 | 00 0.039 | |||
| 19.05 3/4 0 | 90 0.035 | Drawn | ||
| 22.22 7/8 0 | 90 0.035 | |||
| 25.40 1 1.00 0 | 0.039 | |||
| 28.58 | 11/8 | 1.10 | 0.043 | |
| 31.75 | 11/4 | 1.10 | 0.043 | |
| 34.92 | 1 3/8 | 1.21 | 0.048 | |
| 38.10 | 11/2 | 1.35 | 0.053 | |
| 41.28 1 5/8 1 | 1.43 0.056 | |||
| 44.45 | 1 3/4 | 1.60 | 0.063 | |
| 50.80 | 2 | 2.00 | 0.079 | |
| 53.98 | 21/8 | 2.10 | 0.083 | |

CAUTION
- For pipes larger than ∅ 3/4" (∅ 19.05mm), drawn type (C1220T-1/2H or C1220T-H) copper pipe must be used. If an annealed type (C1220T-O) copper pipe is used, the pipe may break due to its low pressure resistance and cause personal injury.
Keeping refrigerant pipe
To prevent foreign materials or water from entering the pipe, storing and sealing methods (especially during installation) are very important. Apply the correct sealing method depending on the environment.
| Exposure place | Exposure time | Sealing type |
| Outdoor | Longer than one month | Pipe pinch |
| Shorter than one month | Taping | |
| Indoor | - | Taping |
Refrigerant pipe welding and safety information

CAUTION
- Important information for refrigerant pipe work.
– Make sure there is no moisture inside the pipe. - Make sure there are no foreign substances and impurities in the pipe. – Make sure there is no leakage. - Make sure to follow the instructions when welding or storing the pipe.
Nitrogen flushing welding
- When welding the refrigerant pipes, flush them with nitrogen gas as shown in the picture.
- If you do not perform nitrogen flushing when welding the pipes, oxide may form inside the pipe. It can cause damage to important parts such as the compressor and valves, etc.
- Adjust the flow rate of the nitrogen flushing with a pressure regulator to maintain 0.05 m2/h ( 0.54ft2/h ) or less.

Direction of the pipe when welding
- The direction of the pipe should be headed downward or sideways when welding.
- Avoid welding the pipe with the pipe direction heading upward.

CAUTION
- When you test for gas leakage after welding the pipes, use a designated solution for gas leakage detection. If you use a detection solution that includes sulfuric ingredients, it may cause corrosion to the pipes.
Cutting or flaring the pipes
1. Make sure that you have prepared the required tools: pipe cutter, deburring tool, flaring tool, and pipe holder, etc. 2. If you want to shorten the pipe, cut it with a pipe cutter, ensuring that the cut edge remains at 90° with the side of the pipe. - Refer to the illustrations below for correct and incorrect examples of cut edges.

3. To prevent a gas leak, remove all burrs at the cut edge of the pipe using a deburring tool. 4. Carry out flaring work using a flaring tool as shown below.
![[Flaring tools] Clutch type Wing nut type A Flaring bar Pipe Flare nut Yoke Flaring bar Pipe](/content/2026/05/959055/images/da7bb7a5ea124a03477152f35c783145af079b9f74e968ab6cd74fee39195698.jpg)
|  | Pipe diameter [D, mm (inch)] | Depth of flaring part [A, mm (inch)] | ||
| Using flaring tool for R-410A | Using conventional flaring tool | |||
| Clutch type | Wing nut type | |||
| φ 6.35(ø1/4) | 0~0.5 (0~0.02) | 1.0~1.5 (0.04~0.06) | 1.5~2.0 (0.06~0.08) | |
| φ 9.52(ø3/8) | ||||
| φ 12.70(ø1/2) | ||||
| φ 15.88(ø5/8) | ||||
5. Check that you have flared the pipe correctly.
– Refer to the illustrations below for correct and incorrect examples of flared pipe.

CAUTION
- If foreign matters or burrs are not removed after cutting the pipe, refrigerant gas may leak.
- If foreign matters enter inside the pipe, important interior parts of the unit may get damaged or product efficiency will be reduced. So, the direction of the pipe should be downward during pipe cutting or flaring.
Connecting the flared pipes
- Check if the flaring is properly done according to the standard size.
- Align the center of the piping and tighten the flare nut with your hands. Then, tighten the flare nut with a torque wrench in the direction of the arrow indicated in the illustration below.
- Make sure to use ester oil to coat the flare connection section.

| Outer diameter (D) | Torque | Flare dimension (L) | Flare shape (mm) | |||
| mm inch N·m | lbf·ft mm inch | R0.4~0.8(0.016~0.032) | ||||
| 6.35 1/4 | 14 ~ 18 | 10.3 ~ 13.3 | 8.7 ~ 9.1 | 0.34 ~ 0.36 | ||
| 9.52 3/8 | 34 ~ 42 | 25.1 ~ 31.0 | 12.8 ~ 13.2 | 0.50 ~ 0.52 | ||
| 12.7 1/2 | 49 ~ 61 | 36.1 ~ 45.0 | 16.2 ~ 16.6 | 0.64 ~ 0.65 | ||
| 15.88 5/8 | 68 ~ 82 | 50.2 ~ 60.5 | 19.3 ~ 19.7 | 0.76 ~ 0.78 | ||
CAUTION
- Blowing nitrogen gas should be done when welding the pipe. Make sure to use the provided flare nut.
- Make sure that there are no cracks or twisted parts when bending the pipe.
- Do not fasten the flare nut with excessive strength.
- R-410A is a high-pressure refrigerant, and there is a risk of refrigerant leakage if the flare connection is not coated with ester oil. Therefore, apply ester oil to coat the flare connection area.
Refrigerant pipe installation
Pipe installation for an outdoor unit
1. Direction of the pipe
Refrigerant pipe can be withdrawn from the front, left, and right sides. Take the necessary method to install the pipes according to the conditions of the installation site.


CAUTION
- Caution for using knock-out hole

- Make sure to prevent any damage to the exterior of the outdoor unit.
- Remove all burrs around the knock-out hole and apply varnish on the cross-section and edges of the knock-out hole to prevent rust.
- Use a cable protection tube and bushing to prevent a cable from being damaged when passing through a knock-out hole.
2. Connecting refrigerant pipe for outdoor unit
| Classification Front side connection Right/left (and bottom) side connection | |
| Working process | First, remove the piping cover from the outdoor unit.Separate the knock-out hole that you are going to use. Ifyou separate the knock-out hole that is going to be unused,small animals such as squirrels and rats may get into the unitthrough the hole.Fix the bottom side of the piping cover first and then fix thetop part of it. |
| H/P | —— Liquid side pipe Gas side pipe |
| H/R | —— High pressuregas pipe—— Liquid side pipe |

CAUTION
- Caution for welding the pipe to an outdoor unit
- When welding the pipe, the unit may get damaged by the heat and flame from welding. Use a flame proofing cloth to protect the unit from a welding fire or flame. The sensor for detecting outside temperature is located on the left side of the welding part, so be extra careful not to damage the sensor when welding.
- The O-ring and Teflon packing inside the service valve may get damaged by the heat from welding. Wrap the bottom side of the service valve with a wet cloth and weld it as shown in the illustration. Also, water dripping from the wet cloth may interrupt the welding. Make sure the water does not drip from the wet cloth.
- Make sure that connected pipes do not interrupt each other or make contact with the product. (Vibration may cause damage to the pipes.)
- When removing the sealed pipe on the bottom side of the service valve, cut it with a pipe cutter first and then start the welding. When the sealed pipe is welded without cutting, you may get injured by the refrigerant within the pipe.


3 Pipe installation between the outdoor units
- You will need branch joints, which are optional accessories, for connecting between outdoor units in order to combine outdoor units in a module. ※ For optimal distribution of the refrigerant, you must use a Y-joint as the branch joint for connecting outdoor units. (Do not use a T-joint)
- When you install the outdoor units in a module, there is no restriction on the installation order among outdoor units. • The height of the connection pipe should be the same or lower than the ones connected to the outdoor units.
- Check the changes in comparison with the DVM II, III, and IV.
| Caution Correct installation Incorrect installation | ||
| Refrigerant pipes should be connected at the same or lower level than the ones connected to the outdoor unit. | ![]() | ![]() |
| Refrigerant pipes must be connected by the side of the product. | (12inch) or more | ![]() |
| Branch joint between outdoor units must be installed horizontally. | ![]() | ![]() |
| Install a vertical trap in following cases as shown in the figure :Case1. Pipe length between outdoor unit branches exceeds 2.5m(8.20ft).Case2. Pipe length between outdoor unit and its branch exceeds 2.5m(8.20ft). | ![]() [IMAGE] | ![]() ![]() |
Refrigerant pipe installation
Examples of refrigerant pipe installation
H/P
1 Using Y-joint
2 Using distribution header![graph TD A["Input Data"] --> B["Device 1"] A --> C["Device 2"] A --> D["Device 3"] B --> E["Output Device 1"] C --> F["Output Device 2"] D --> G["Output Device 3"]](/content/2026/05/959055/images/e3c38d94a394ca7e835a26ea2215c1e2fe5ae0412d94dd11c8bd9b575a96c786.jpg)
![graph TD A["Central Server"] --> B["Client Module 1"] A --> C["Client Module 2"] A --> D["Client Module 3"] A --> E["Client Module 4"] A --> F["Client Module 5"] A --> G["Client Module 6"]](/content/2026/05/959055/images/929432895d0af69907ca9a4a37ed03ed9ff6b25c06a2c4702a605e4c6996ba86.jpg)
H/R
Using Y-joint![graph TD A["Server 1"] --> B["MCU"] B --> C["MCU"] C --> D["Server 2"] D --> E["MCU"] E --> F["MCU"] F --> G["Server 3"] G --> H["MCU"] H --> I["Server 4"] I --> J["MCU"] J --> K["Server 5"] K --> L["MCU"] L --> M["Server 6"] M --> N["MCU"] N --> O["Server 7"] O --> P["MCU"] P --> Q["Server 8"] Q --…](/content/2026/05/959055/images/18c003498744b5c9b39ff8fdafc24b2c569b59da467297f9bc989f5ea07f8975.jpg)
Note 1) Direct-connected indoor unit without MCU (for HR only) - This indoor unit can only be used for cooling operation. (Heating operation is not possible.) - Connect indoor unit to liquid and low pressure gas pipe. - Change the installation option for direct-connected indoor unit without MCU. (refer to the indoor unit installation manual)
Allowable length of the refrigerant pipe and the installation examples
H/P
| Classification Single Installation Module installation | ||
| Installing only with Y-joint | Outdoor unit![]() | Outdoor unit![]() |
| Installing with Y-joint and distribution header | Outdoor unit![]() | Outdoor unit![]() |
| Installing only with distribution header | Outdoor unit![]() | Outdoor unit![]() |
| Classification | Example | Remarks | ||||
| Maximum allowable length of pipe | Outdoor unit ~ Indoor unit | Actual length (Equivalent length) | 200 m(656') and below [220 m(722') and below] | Installing only with Y-joint | a+b+c+d+e+f+g+p ≤ 200 m(220 m)/656'(722') | Equivalent length Y-joint: 0.5 m (1.64'), Distribution header: 1 m(3.28') |
| Installing with Y-joint and distribution header | a+b+h ≤ 200m (220m), a+i+k ≤ 200 m(220 m)/656'(722') | |||||
| Installing only with distribution header | a+i ≤ 200 m(220 m)/656(722') | |||||
| Total length of pipe (m) | 1000 m(3281') or less | Installing only with Y-joint | a+b+c+d+e+f+g+h+i+j+k+l+m+n+p ≤ 1000 m (3281') | - | ||
| Installing with Y-joint and distribution header | a+b+c+d+e+f+g+h+i+j+k ≤ 1000 m (3281') | - | ||||
| Installing only with distribution header | a+b+c+d+e+f+g+h+i ≤ 1000 m (3281') | - | ||||
| Outdoor unit ~ Outdoor unit (Module installation) | Pipe length | 10 m (33') or less | x ≤ 10 m (33'), y ≤ 10 m (33'), z ≤ 10 m (33') | ![]() | ||
| Equivalent length | 13 m (43') or less | x ≤ 13 m (43'), y ≤ 13 m (43'), z ≤ 13 m (43') | ||||
| Maximum allowable height difference of pipe | Outdoor unit ~ Indoor unit | 110/110 m(361'/361')Note 2) | H1 ≤ 110/110 m(361/361') | |||
| Indoor unit ~ Indoor unit | 50 m (164') or less | H2 ≤ 50 m (164') | ||||
| But, when wall-mount type indoor units with EEV(AM****NQD* / AM****NVD*) is installed, H2 is 15 m(49') or less. | ||||||
Refrigerant pipe installation
| Classification Example Remarks | ||||||
| Maximum allowable length after branch joint | First branch joint ~ Farthest Indoor unit | Pipe length | 45 m (148') or less | Installing only with Y-joint | b+c+d+e+f+g+p ≤ 45 m (148') | - |
| Installing with Y-joint and distribution header | i+k ≤ 45 m (148') | |||||
| Installing only with distribution header | i ≤ 45 m (148') | |||||
| 45 m~90 m (148'~295') Note 1) | Required conditions must be satisfied | - | ||||
| EEV kit Model name Remarks | |||||
| EEV kit ~ Indoor unit Actual pipe length | Actual pipe length | 2 m (6.6') | MEV-E24SA | 1 indoor | Apply to products without EEV (Wall mount & ceiling) |
| MEV-E32SA | |||||
| 20 m (66') or less | MXD-E24K132A | 2 indoorMXD-E24K200A | |||
| MXD-E32K200A | |||||
| MXD-E24K232A | 3 indoor | ||||
| MXD-E24K300A | |||||
| MXD-E32K224A | |||||
| MXD-E32K300A | |||||
※ Please refer to the EEV Kit manual. Note 1) Required condition
| Classification Condition Example | ||
| First branch joint ~ Farthest Indoor unit | 45m(148') ≤ b+c+d+e+f+g+p ≤ 90m (295'): branch pipes (b, c, d, e, f, g) size must be increased by 1 grade | ![]() |
| Total length of extended pipe | If the size of pipe (main pipe), between the first branch joint and the outdoor unit, is not increased by 1 grade, a+(b+c+d+e+f+g)×2 +h+i+j+k+l+m+n+p ≤ 1000 m (3281') | |
| If the size of pipe (main pipe), between the first branch joint and the outdoor unit, is increased by 1 grade, (a+b+c+d+e+f+g)×2 +h+i+j+k+l+m+n+p ≤ 1000 m (3281') | ||
| Each Y-joint ~ Each indoor unit | h, i, j, ... p ≤ 45 m (148') | |
| Difference between the distance of the outdoor unit to the farthest indoor unit and nearest | ||
| indoor unit ≤ 45m(148'), (a+b+c+d+e+f+g+p)-(a+h) ≤ 45m (148') | ||
Note 2) When indoor unit is located at higher level than outdoor unit, allowable height difference is 110m(361'), (If the height difference is over 40m(131'), contact your local dealer for more information.) but when the indoor unit is located at lower level than outdoor unit, allowable height difference is 110m(361') (If the height difference is over 50m(164'), need to decide whether to install PDM kit or not.) Model name of the PDM kit : MXD-A38K2A, MXD-A12K2A, MXD-A58K2A
H/R
| Classification Installation with Y-joint | |
| Installing with MCU only | ![]() |
| Installing with MCU and Y-joint | Direct-connected indoor unit without MCU (Cooling only) (Connecting Only Low Pressure Gas Pipe / Liquid Pipe note3)![]() |
| Classification Example Remarks | ||||||
| Maximum allowable pipe length | Outdoor unit ~ Indoor unit | Actual pipe length (Equivalent length) | 200 m or less (220 m or less)/656'(722') | Installing only with MCU | a+g+j ≤ 200 m (220 m)/656'(722') | Equivalent length Y-joint: 0.5 m(1.64') Distribution header: 1 m(3.28') MCU: 1 m(3.28') |
| Installing with MCU and Y-joint | a+b+h+k ≤ 200 m (220 m)/656'(722') | |||||
| Total length of pipe | 1000 m (3281') or less | Installing only with MCU | a+b+c+d+e+f+g+h+i+j ≤ 1000 m(3281') | |||
| Installing with MCU and Y-joint | a+b+c+...+r ≤ 1000 m(3281') | |||||
| Outdoor unit | Pipe length | 10 m(33') or less | x ≤ 10 m (33'), y ≤ 10 m (33'), z ≤ 10 m (33') | ![]() | ||
| ~ Outdoor unit (Module installation) | Equivalent length | 13 m(43') or less | x ≤ 13 m (43'), y ≤ 13 m (43'), z ≤ 13 m (43') | |||
| MCU ~ Indoor unit | Pipe length | 45 m(148') or less | Installing only with MCU | b+c ≤ 45 m(148'), b+d ≤ 45 m(148'), b+e ≤ 45 m(148'), f≤ 45 m(148'), g+h ≤ 45 m(148'), g+i ≤ 45 m(148'), g+j ≤ 45 m(148') | ||
| Installing with MCU and Y-joint | c+d, c+e, c+f, g, h+i, h+j, h+k, n, o, p, q, r ≤ 45 m(148') | |||||
| Maximum allowable height difference | Outdoor unit ~ Indoor unit | Pipe length | 110 m / 110 m(361'/361') Note1 | H1 ≤ 110 m / 110 m(361'/361') | ||
| Indoor unit ~ Indoor unit | 40 m(131') or less | H2 ≤ 40 m(131') | ||||
| But, when AM****NQD* / AM****NVD* is installed, H2 is 15 m(49') or less. | ||||||
| Indoor unit ~ Indoor unit (in one MCU) | 15 m(49') or less | H3 ≤ 15 m(49') | ||||
| MCU ~ MCU | 30 m(98') or less | H4 ≤ 30 m(98') | ||||
| Maximum allowable length after branch joint | First branch joint ~ Farthest Indoor unit | Pipe length | 45 m(148') or less | Installing only with MCU | g+j ≤ 45 m(148') | |
| Installing with MCU and Y-joint | b+h+k ≤ 45 m(148') l+m+q ≤ 45 m(148') l+r ≤ 45 m(148') | |||||
| 45 ~ 90 m (148'~295') Note2 | Required conditions must be satisfied | |||||
Refrigerant pipe installation
| EEV Kit Model name Remarkers | |||||
| EEV kit - Indoor unit Actual pipe length | Actual pipe length | 2 m (6.6') | MEV-E24SA | 1 indoor | Apply to products without EEV (Wall mount & ceiling) |
| MEV-E32SA | |||||
| 20 m (66') or less | MXD-E24K132A | 2 indoorMXD-E24K200A | |||
| MXD-E32K200A | |||||
| MXD-E24K232A | 3 indoor | ||||
| MXD-E24K300A | |||||
| MXD-E32K224A | |||||
| MXD-E32K300A | |||||
※ Please refer to the EEV Kit manual. Note 1) When indoor unit is located at higher level than outdoor unit, allowable height difference is 110m(361'), (If the height difference is over 40m(131'), contact your local dealer for more information.) but when the indoor unit is located at lower level than outdoor unit, allowable height difference is 110m(361') (If the height difference is over 50m(164'), need to decide whether to install PDM kit or not.) Model name of the PDM kit : MXD-A38K2A, MXD-A12K2A, MXD-A58K2A Note 2) Required condition
| Classification Condition Example | ||
| First branch joint ~ Farthest Indoor unit | 45m(148') ≤ b+h+k, l+m+q, l+r ≤ 90m(295') : Size of the branch liquid and low pressure gas pipes (b, l, m) must be increased by 1 grade. | ![]() |
| Total length of extended pipe | If the size of pipe (main pipe), between the first branch joint and the outdoor unit, is not increased by 1 grade, a+(b+l+m) x2+c+d+e+f+g+h+l+j+k+n+o+p+q+r ≤ 1000m(3281') | |
| If the size of pipe (main pipe), between the first branch joint and the outdoor unit, is increased by 1 grade, (a+b+l+m) x2+c+d+e+f+g+h+i+j+k+n+o+p+q+r ≤ 1000m(3281') | ||
| MCU ~ Each indoor unit | c+d, c+e, c+f, g, h+i, h+j, h+k, n, o, p, q, r ≤ 45 m(148') | |
| Difference between the distance of the outdoor unit to the farthest indoor unit and nearest indoor unit ≤ 45m(148') (a+b+h+k) - (a+b+c+d) ≤ 45m(148') | ||
Note 3) For indoor units to which no MCU is connected, be sure to set their options to "Cooling only indoor unit," and then connect them to a low pressure gas pipe and a liquid pipe. Be sure to combine the cooling only indoor units so that their total capacity becomes 50% or less of the total capacity of all indoor units. Note 4) In case of connecting more than one indoor unit in one MCU Port, the below indoor units cannot be combined. ERV plus(AM****NK*C**), OAP duct (AM****NE*C*), Hydro Unit HE (AM****NBDC*), Hydro Unit HT (AM****NBFC*), AHU kit (MXD-K***AN, MCM-D***N) Note 5) In case of connecting two MCU ports with Y-joint, the indoor units cannot be combined to more than one.
Installing the branch joints
Branch joints must be installed 'horizontally' or 'vertically'.
Horizontal installation
Vertical installation


NOTE
- For A~J type branch joints: Connect the branch joint to the connection pipe with the provided reducer.
- For K~Z type branch joints: Cut the connection part of the branch joint or the provided socket, according to the diameter of the connection pipe, before connecting them.


CAUTION
• Install the branch joint within ±15° of the horizon or vertical line. - Make sure that the pipe is not bent at where it is connected to the branch joint. - Keep a minimum straight line distance of 500mm (20inch) or more before connecting branch joint.

※ Install within ±15° of the horizon or vertical line.
Installing the distribution header
1 Select the reducer that fits the diameter of the pipe.
![Pipe* to outdoor unit. Socket. Provided item. Socket. Pipe* to indoor unit. [Liquid side]. Pipe* to outdoor unit. Socket. Socket. Pipe* to indoor unit. [Gas side].](/content/2026/05/959055/images/51d0a6d71260ca2acaf459d9d187b407f8d445ffeb418af34a0e9add999dcb22.jpg)
※ Pipe : Separately purchased item 2 If the number of connected indoor unit is fewer than ports on the distribution header, block the unused ports with caps.



NOTE
- For A~J type distribution header: Connect the distribution header to the connection pipe with the provided reducer.
- For K~Z type distribution headers: Cut the provided socket, according to the diameter of the connection pipe, before connecting it.

Refrigerant pipe installation

CAUTION
- Connect the indoor units in order, while respecting the direction of the arrow shown in the illustration.
- When indoor units are connected to the same distribution head, they must be connected in order of their capacity, from largest to smallest.
- Keep unused port ① to avoid oil trap.
3. Install the distribution header horizontally.
- Install the distribution header horizontally so that its ports do not face down.

Installing the branch joint between outdoor units
Installation of outdoor joints
※ High pressure gas pipe only applies to the H/R product.

※ Use the attached reducer according to the selected pipe size.

NOTE
- Connect the outdoor joint to the pipe by cutting the outlet of the outdoor joint or provided reducer properly.

Installing the MCU
MCU specification
| Model MCU-S12NEK1N MCU-S8NEK1N MCU-S6NEK2N | |||
| Exterior of MCU | ![]() | ![]() | ![]() |
| Number of connectable indoor units at one port Up to 8 units Up to 8 units Up to 8 units | |||
| Maximum number of indoor units (Total) | 64 64 32 | ||
| The maximum capacity of the connectable indoor units at one port | 16 kW(54MBH) | 16 kW(54MBH) | 16 kW(54MBH) |
| The maximum capacity of the connectable indoor units at one port (with Y-JOINT) | 32.0 kW(108 MBH) | 32.0 kW(108 MBH) | 32.0 kw(108 MBH) |
| The maximum capacity of the connectable indoor units | 85.0 kW(290MBH) | 85.0 kW(290MBH) | 61.6 kW(216MBH) |
| Internal EEV | Not includedCannot connect indoor unit without internal EEV | ||
| Model MCU-S4NEK3N MCU-S2NEK2N MCU-S1NEK1N | |||
| Exterior of MCU | ![]() | ![]() | ![]() |
| Number of connectable indoor units at one port Up to 8 units Up to 8 units Up to 8 units | |||
| Maximum number of indoor units (Total) 32 16 8 | |||
| The maximum capacity of the connectable indoor units at one port | 16 kW(54MBH) | 16 kW(54MBH) | 16 kW(54MBH) |
| The maximum capacity of the connectable indoor units at one port (with Y-JOINT) | 32.0 kw(108 MBH) | 32.0 kw(108 MBH) | - |
| The maximum capacity of the connectable indoor units | 61.6 kW(216MBH) | 32.0 kW(108MBH) | 16 kW(54MBH) |
| Internal EEV | Not includedCannot connect indoor unit without internal EEV | ||

CAUTION
- Indoor units without internal EEV (AM****NCDCH*) cannot be connected directly to the MCU.
- Please connect these indoor units using the EEV kit (MEV-E**SA, MXD-E**K***A).
- If the sum of the connected indoor unit capacity connected to the MCU is greater than 67.2kW (228MBH), performance may vary depending on operating conditions.
- The incoming pipe diameters supplying refrigerant to the MCU are determined based on the sum of the connected indoor units. If these pipe diameters are different from the MCU pipe diameters, use the provided reducers to connect to the MCU. If the provided reducers are not the correct size, field-supplied reducers must be used.
Refrigerant pipe installation
Installing the indoor units
| Model MCU-S12NEK1N MCU-S8NEK1N MCU-S6NEK2N | |||
| Example installing (Each port connection) | ![]() | ![]() | ![]() |
| MCU-S4NEK3N MCU-S2NEK2N MCU-S1NEK1N | |||
![]() | ![]() | ![]() | |
| Example installing (MCU series connection) | MCU series connection![]() | ||
| Installing indoor units | Under 16.0 kW indoor unit : Don't use Y-connector16.0 kW ~ 32.0 kW indoor unit : Use Y-connector at the Gas & Liquid lineIf you want to continuous cooling operation under -5 °C, set outdoor 'Expand operational temperature range for cooling operation (HR only)', and use Y-connector on 5.0 ~ 16 kW Indoor unitIn case of MCU connection in series, the maximum capacity of indoor units in MCU series connection is the larger value of MCU which are connected in series.(Example> MCU-S12NEK1N + MCU-S6NEK2N → 85.0 kW (290 MBH)) | ||
| Using Y-connector | [MCU-S6*, MCU-S4*, MCU-S2*, MCU-S1*]In case of using Y-connector, it is only connectable for port combination at below connectable port combination for Y-connector : A + B port, C + D port, E + F portNon-connectable port combination for Y-connector : B + C port, D + E port, non-continuous portSet Dip Switch option for using Y-connectorS/W Option S/W Option S/W Option S/W Option![]() ![]() ![]() Default Combination of A+B port Combination of C+D port Combination of E+F port | ||
![[MCU-S12*, MCU-S8*] In case of using Y-connector, it is only connectable for port combination at below connectable port combination for Y-connector : [#1-A] + [#1-B] port, [#1-C] + [#1-D] port, [#1-E] + [#1-F] port [#2-A] + [#2-B] port, [#2-C] + [#2-D] port, [#2-E] + [#2-F] port Non-connectable port…](/content/2026/05/959055/images/524e07bd87b1e486fbb5e6c1eeb4a759879b6e22989c02e8b70bfcceeef2ffe2.jpg)
Electric Characteristics
1 [AM***BXVGF* series] Heat Pump / Heat Recovery (208\~230V)| Nom. Ton | Model | Units | Module #1 Module #2 Module #3 | ||||||||||||||||||
| RLA | FLA | Power Supply | RLA | FLA | Power Supply | RLA | FLA | Power Supply | |||||||||||||
| Hz | Volts | Comp1 | Comp2 | FAN1 | FAN2 | MCA | MOP | Comp1 | Comp2 | FAN1 | FAN2 | MCA | MOP | Comp1 | Comp2 | FAN1 | FAN2 | MCA | MOP | ||
| 6Ton | AM072BXVGF* | 60 | 208~230 | 18.7 | - | 4.6 | - | 28.0 | 35.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 8Ton | AM096BXVGF* | 60 | 208~230 | 12.2 | 12.2 | 4.2 | 4.2 | 36.0 | 40.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 10Ton | AM120BXVGF* | 60 | 208~230 | 14.4 | 14.4 | 4.2 | 4.2 | 40.8 | 45.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 12Ton | AM144BXVGF* | 60 | 208~230 | 19.6 | 19.6 | 4.2 | 4.2 | 52.6 | 60.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 14Ton | AM168BXVGF* | 60 | 208~230 | 20.4 | 20.4 | 4.2 | 4.2 | 54.4 | 60.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 16Ton | AM192BXVGF* | 60 | 208~230 | 22.5 | 22.5 | 4.6 | 4.6 | 60.0 | 70.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 18Ton | AM216BXVGF* | 60 | 208~230 | 24.3 | 24.3 | 4.6 | 4.6 | 64.0 | 80.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 20Ton | AM240BXVGF* | 60 | 208~230 | 26.1 | 26.1 | 4.6 | 4.6 | 68.0 | 80.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 22Ton | AM264BXVGF* | 60 | 208~230 | 12.2 | 12.2 | 4.2 | 4.2 | 36.0 | 40.0 | 20.4 | 20.4 | 4.2 | 4.2 | 54.4 | 60.0 | - | - | - | - | - | - |
| 24Ton | AM288BXVGF* | 60 | 208~230 | 12.2 | 12.2 | 4.2 | 4.2 | 36.0 | 40.0 | 22.5 | 22.5 | 4.6 | 4.6 | 60.0 | 70.0 | - | - | - | - | - | - |
| 26Ton | AM312BXVGF* | 60 | 208~230 | 12.2 | 12.2 | 4.2 | 4.2 | 36.0 | 40.0 | 24.3 | 24.3 | 4.6 | 4.6 | 64.0 | 80.0 | - | - | - | - | - | - |
| 28Ton | AM336BXVGF* | 60 | 208~230 | 12.2 | 12.2 | 4.2 | 4.2 | 36.0 | 40.0 | 26.1 | 26.1 | 4.6 | 4.6 | 68.0 | 80.0 | - | - | - | - | - | - |
| 30Ton | AM360BXVGF* | 60 | 208~230 | 14.4 | 14.4 | 4.2 | 4.2 | 40.8 | 45.0 | 26.1 | 26.1 | 4.6 | 4.6 | 68.0 | 80.0 | - | - | - | - | - | - |
| 32Ton | AM384BXVGF* | 60 | 208~230 | 22.5 | 22.5 | 4.6 | 4.6 | 60.0 | 70.0 | 22.5 | 22.5 | 4.6 | 4.6 | 60.0 | 70.0 | - | - | - | - | - | - |
| 34Ton | AM408BXVGF* | 60 | 208~230 | 22.5 | 22.5 | 4.6 | 4.6 | 60.0 | 70.0 | 24.3 | 24.3 | 4.6 | 4.6 | 64.0 | 80.0 | - | - | - | - | - | - |
| 36Ton | AM432BXVGF*1 | 60 | 208~230 | 14.4 | 14.4 | 4.2 | 4.2 | 40.8 | 45.0 | 14.4 | 14.4 | 4.2 | 4.2 | 40.8 | 45.0 | 22.5 | 22.5 | 4.6 | 4.6 | 60.0 | 70.0 |
| 38Ton | AM456BXVGF* | 60 | 208~230 | 14.4 | 14.4 | 4.2 | 4.2 | 40.8 | 45.0 | 19.6 | 19.6 | 4.2 | 4.2 | 52.6 | 60.0 | 22.5 | 22.5 | 4.6 | 4.6 | 60.0 | 70.0 |
| Nom. Ton | Model | Units | Module #1 | Module #2 | Module #3 | ||||||||||||||||
| RLA | FLA | Power Supply | RLA | FLA | Power Supply | RLA | FLA | Power Supply | |||||||||||||
| Hz | Volts | Comp1 | Comp2 | FAN1 | FAN2 | MCA | MOP | Comp1 | Comp2 | FAN1 | FAN2 | MCA | MOP | Comp1 | Comp2 | FAN1 | FAN2 | MCA | MOP | ||
| 6Ton | AM072BXVGJ* | 60 | 460 | 10.0 | - | 2.3 | - | 15.0 | 20.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 8Ton | AM096BXVGJ* | 60 | 460 | 6.0 | 6.0 | 2.1 | 2.1 | 18.0 | 20.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 10Ton | AM120BXVGJ* | 60 | 460 | 6.6 | 6.6 | 2.1 | 2.1 | 19.4 | 25.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 12Ton | AM144BXVGJ* | 60 | 460 | 9.6 | 9.6 | 2.1 | 2.1 | 26.2 | 35.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 14Ton | AM168BXVGJ* | 60 | 460 | 11.0 | 11.0 | 2.1 | 2.1 | 29.0 | 35.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 16Ton | AM192BXVGJ* | 60 | 460 | 13.0 | 13.0 | 2.3 | 2.3 | 34.0 | 40.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 18Ton | AM216BXVGJ* | 60 | 460 | 14.8 | 14.8 | 2.3 | 2.3 | 38.0 | 50.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 20Ton | AM240BXVGJ* | 60 | 460 | 15.6 | 15.6 | 2.3 | 2.3 | 40.0 | 50.0 | - | - | - | - | - | - | - | - | - | - | - | - |
| 22Ton | AM264BXVGJ* | 60 | 460 | 6.0 | 6.0 | 2.1 | 2.1 | 18.0 | 20.0 | 11.0 | 11.0 | 2.1 | 2.1 | 29.0 | 35.0 | - | - | - | - | - | - |
| 24Ton | AM288BXVGJ* | 60 | 460 | 6.0 | 6.0 | 2.1 | 2.1 | 18.0 | 20.0 | 13.0 | 13.0 | 2.3 | 2.3 | 34.0 | 40.0 | - | - | - | - | - | - |
| 26Ton | AM312BXVGJ* | 60 | 460 | 6.0 | 6.0 | 2.1 | 2.1 | 18.0 | 20.0 | 14.8 | 14.8 | 2.3 | 2.3 | 38.0 | 50.0 | - | - | - | - | - | - |
| 28Ton | AM336BXVGJ* | 60 | 460 | 6.0 | 6.0 | 2.1 | 2.1 | 18.0 | 20.0 | 15.6 | 15.6 | 2.3 | 2.3 | 40.0 | 50.0 | - | - | - | - | - | - |
| 30Ton | AM360BXVGJ* | 60 | 460 | 6.6 | 6.6 | 2.1 | 2.1 | 19.4 | 25.0 | 15.6 | 15.6 | 2.3 | 2.3 | 40.0 | 50.0 | - | - | - | - | - | - |
| 32Ton | AM384BXVGJ* | 60 | 460 | 13.0 | 13.0 | 2.3 | 2.3 | 34.0 | 40.0 | 13.0 | 13.0 | 2.3 | 2.3 | 34.0 | 40.0 | - | - | - | - | - | - |
| 34Ton | AM408BXVGJ* | 60 | 460 | 13.0 | 13.0 | 2.3 | 2.3 | 34.0 | 40.0 | 14.8 | 14.8 | 2.3 | 2.3 | 38.0 | 50.0 | - | - | - | - | - | - |
| 36Ton | AM432BXVGJ*1 | 60 | 460 | 6.6 | 6.6 | 2.1 | 2.1 | 19.4 | 25.0 | 6.6 | 6.6 | 2.1 | 2.1 | 19.4 | 25.0 | 13.0 | 13.0 | 2.3 | 2.3 | 34.0 | 40.0 |
| 38Ton | AM456BXVGJ* | 60 | 460 | 6.6 | 6.6 | 2.1 | 2.1 | 19.4 | 25.0 | 9.6 | 9.6 | 2.1 | 2.1 | 26.2 | 35.0 | 13.0 | 13.0 | 2.3 | 2.3 | 34.0 | 40.0 |
| Nom.Ton | Model | Units | Module #1 Module #2 Module #3 | ||||||||||||||||||
| RLA | FLA | Power Supply | RLA | FLA | Power Supply | RLA | FLA | Power Supply | |||||||||||||
| Hz | Volts | Comp1 | Comp2 | FAN1 | FAN2 | MCA | MOP | Comp1 | Comp2 | FAN1 | FAN2 | MCA | MOP | Comp1 | Comp2 | FAN1 | FAN2 | MCA | MOP | ||
| 6Ton | AM072BXVTF* | 60 | 208~230 | 18 | 18 | 4.2 | 4.2 | 50 | 60 | - | - | - | - | - | - | - | - | - | - | - | - |
| 8Ton | AM096BXVTF* 60 | 208~230 | 22 | 22 | 4.2 | 4.2 | 62 | 70 | - | - | - | - | - | - | - | - | - | - | - | - | |
| 10Ton | AM120BXVTF* 60 | 208~230 | 28 | 28 | 4.2 | 4.2 | 76 | 90 | - | - | - | - | - | - | - | - | - | - | - | - | |
| 12Ton | AM144BXVTF* 60 | 208~230 | 18 | 18 | 4.2 | 4.2 | 50 | 60 | 18 | 18 | 4.2 | 4.2 | 50 | 60 | - | - | - | - | - | - | |
| 14Ton | AM168BXVTF* 60 | 208~230 | 18 | 18 | 4.2 | 4.2 | 50 | 60 | 22 | 22 | 4.2 | 4.2 | 62 | 70 | - | - | - | - | - | - | |
| 16Ton | AM192BXVTF*1 | 60 | 208~230 | 22 | 22 | 4.2 | 4.2 | 62 | 70 | 22 | 22 | 4.2 | 4.2 | 62 | 70 | - | - | - | - | - | - |
| 18Ton | AM216BXVTF*1 | 60 | 208~230 | 18 | 18 | 4.2 | 4.2 | 50 | 60 | 18 | 18 | 4.2 | 4.2 | 50 | 60 | 18 | 18 | 4.2 | 4.2 | 50 | 60 |
| 20Ton | AM240BXVTF*1 | 60 | 208~230 | 18 | 18 | 4.2 | 4.2 | 50 | 60 | 18 | 18 | 4.2 | 4.2 | 50 | 60 | 22 | 22 | 4.2 | 4.2 | 62 | 70 |
| 22Ton | AM264BXVTF* 60 | 208~230 | 18 | 18 | 4.2 | 4.2 | 50 | 60 | 18 | 18 | 4.2 | 4.2 | 50 | 60 | 28 | 28 | 4.2 | 4.2 | 76 | 90 | |
| 24Ton | AM288BXVTF* | 60 | 208~230 | 18 | 18 | 4.2 | 4.2 | 50 | 60 | 22 | 22 | 4.2 | 4.2 | 62 | 70 | 28 | 28 | 4.2 | 4.2 | 76 | 90 |
| Nom. Ton | Model | Units | Module #1 Module #2 Module #3 | ||||||||||||||||||
| RLA | FLA | Power Supply | RLA | FLA | Power Supply | RLA | FLA | Power Supply | |||||||||||||
| Hz Volts | Comp1 | Comp2 | FAN1 | FAN2 | MCA | MOP | Comp1 | Comp2 | FAN1 | FAN2 | MCA | MOP | Comp1 | Comp2 | FAN1 | FAN2 | MCA | MOP | |||
| 6Ton | AM072BXVTJ* | 60 | 460 | 9.2 | 9.2 | 2.1 | 2.1 | 25 | 30 | - | - | - | - | - | - | - | - | - | - | - | - |
| 8Ton | AM096BXVTJ* | 60 | 460 | 11 | 11 | 2.1 | 2.1 | 31 | 35 | - | - | - | - | - | - | - | - | - | - | - | - |
| 10Ton | AM120BXVTJ* | 60 | 460 | 14 | 14 | 2.1 | 2.1 | 38 | 45 | - | - | - | - | - | - | - | - | - | - | - | - |
| 12Ton | AM144BXVTJ* | 60 | 460 | 9.2 | 9.2 | 2.1 | 2.1 | 25 | 30 | 9.2 | 9.2 | 2.1 | 2.1 | 25 | 30 | - | - | - | - | - | - |
| 14Ton | AM168BXVTJ* | 60 | 460 | 9.2 | 9.2 | 2.1 | 2.1 | 25 | 30 | 11 | 11 | 2.1 | 2.1 | 31 | 35 | - | - | - | - | - | - |
| 16Ton | AM192BXVTJ*1 | 60 | 460 | 11 | 11 | 2.1 | 2.1 | 31 | 35 | 11 | 11 | 2.1 | 2.1 | 31 | 35 | - | - | - | - | - | - |
| 18Ton | AM216BXVTJ*1 | 60 | 460 | 9.2 | 9.2 | 2.1 | 2.1 | 25 | 30 | 9.2 | 9.2 | 2.1 | 2.1 | 25 | 30 | 9.2 | 9.2 | 2.1 | 2.1 | 25 | 30 |
| 20Ton | AM240BXVTJ*1 | 60 | 460 | 9.2 | 9.2 | 2.1 | 2.1 | 25 | 30 | 9.2 | 9.2 | 2.1 | 2.1 | 25 | 30 | 11 | 11 | 2.1 | 2.1 | 31 | 35 |
| 22Ton | AM264BXVTJ* | 60 | 460 | 9.2 | 9.2 | 2.1 | 2.1 | 25 | 30 | 9.2 | 9.2 | 2.1 | 2.1 | 25 | 30 | 14 | 14 | 2.1 | 2.1 | 38 | 45 |
| 24Ton | AM288BXVTJ* | 60 | 460 | 9.2 | 9.2 | 2.1 | 2.1 | 25 | 30 | 11 | 11 | 2.1 | 2.1 | 31 | 35 | 14 | 14 | 2.1 | 2.1 | 38 | 45 |
NOTE
- RLA is based on AHRI 1230 Cooling Standard Condition (Indoor Temp : 26.7°C/80°F(DB) / 19.46°C/67°F(WB), Outdoor Temp : 35°C/95°F(DB)) • Voltage Tolerance is ±10% • Maxium allowable voltage between phases is 2% • Refer to module combination table for independent units information Symbols: \- RLA : Rated Load Ampere \- FLA : Full Load Ampere \- MCA : Minimum Circuit Ampere (A) \- MOP: Maxium Overcurrent Protective Device(A)" CAUTION
\- Caution for electrical work - You must install ELCB or MCCB + ELB - ELCB: Earth leakage breaker - MCCB: Molded case circuit breaker - ELB: Earth leakage breaker - Do not operate the outdoor unit before completing the refrigerant pipe work. - Do not disconnect or change the cable inside the product. It may cause damage to the product. - Specification of the power cable is selected based on following installation condition; culvert installation/ ambient temperature 30°C (86°F)/ single multi conductor cables. If the condition is different from the ones stated, please consult an electrical installation expert and re-select the power cable. - If the length of power cable exceed 50m (164.04ft), re-select the power cable considering the voltage drop. \- Use a power cable made out of incombustible material for the insulator (inner cover) and the sheath (outer cover). \- Do not use the power cable with the core wire exposed due to insulator damage occurred during removal of the sheath. When the core wire is exposed, it may cause fire. Power and communication cable configuration
- Main power and the ground cable must be withdrawn through the knock-out hole on the bottom-right or right side of the cabinet. - Withdraw the communication cable from the designated knock-out hole on the bottom-right side of the front part. • Install the power and communication cable using separate cable protection tube. - Fix a protection tube to the knock-out hole on the outdoor unit by using a CD connector or bushing. Make sure to use insulating bushing. Specification of the protection tube
| Name Temper grade Applicable conditions | ||
| Flexible PVC conduit | PVC | When the protection tube is installed indoor and not exposed to outside, because it is embedded in concrete structure |
| Class 1 flexible conduit | Galvanized steel sheet | When the protection tube is installed indoor but exposed to outside so there are risk of damage to the protection tube |
| Class 1 PVC coated flexible conduit | Galvanized steel sheet and Soft PVC compound | When the protection tube is installed outdoor and exposed to outside so there are risk of damage to the protection tube and extra waterproof is needed |
CAUTION
- Caution for perforating the knock-out hole - Perforate a knock-out hole by punching it with a hammer. • After perforating the knock-out hole, apply rust resisting paint around the hole. - When you need to pass the cables through the knock-out hole, remove burrs on the hole and protection the cable with a protection tape or bushing etc. - Caution for installing communication cable - When you connect the cable, it may sag and pressed by other parts. Therefore cables should be fixed to a clamp highlighted with a box on the illustration.  Path for arranging external communication cable Fixing location of the external communication cablePower wiring diagram
 - Connect a power cable of the outdoor unit after checking that R-S-T (3 phase 3 wire) is properly connected. - Malfunction may occur if one or more of the wires among R-S-T phases (3 Phases-3 Wires) are not connected properly. (*Malfunction: Turning on/off, occurrence of error, consecutive reset) • Communication cable between indoor and outdoor units and communication cable between outdoor units has no polarity. - Arrange the cables with a cable tie. ※ ELCB and ELB must be installed since there is risk of electric shock or fire when they are not installed.Selecting solderless ring terminal
- Select a solderless ring terminal for a power cable according to the nominal dimensions for cable. - Apply insulation coating to the connection part of the solderless ring terminal and the power cable.   | Nominal dimensions for cable[mm2 (inch2)] | 4/6 (0.006/0.009) 10 | (0.01) 16 (0) | 02) 25 (0.03) | 35 (0.05) 50 (0.07) 70 (0.10) | |||||||
| Nominal dimensions for screw[mm (inch)] | 4 (3/8) 8 | 3/16) 8 (3/16) | 8 (3/16) 8 | 3/16) 8 (3/16) | 8 (3/16) 8 | 3/16) 8 (3/16) | 8 (3/16) | ||||
| B | Standard dimension[mm (inch)] | 9.5 (3/8) 15 | (9/16) 15 | (9/16) 16 (10/16) | 12 (1/2) | 16.5(10/16) | 16 (10/16) | 22 (7/8) 22 (7/8) | 24 (1) | ||
| Allowance[mm (inch)] | ±0.2 (±0.007) | ±0.2(±0.007) | ±0.2(±0.007) | ±0.3 (±0.011) ±0.3 | (±0.011) | ±0.3(±0.011) | ±0.4(±0.015) | ||||
| D | Standard dimension[mm (inch)] | 5.6 (1/4) | 7.1 (1/4) | 9 (3/8) | 11.5 (7/16) | 13.3 (1/2) | 13.5 (1/2) | 17.5 (1/2) | |||
| Allowance[mm (inch)] | +0.3 (+0.011)-0.2 (-0.007) | +0.3(+0.011)-0.2(-0.007) | +0.3(+0.011)-0.2(-0.007) | +0.5 (+0.019)-0.2 (-0.007) | +0.5 (+0.019)-0.2 (-0.007) | +0.5(+0.019)-0.2(-0.007) | +0.5(+0.019)-0.4(-0.015) | ||||
| d1 | Standard dimension[mm (inch)] | 3.4 (1/8) | 4.5 (3/16) | 5.8 (1/4) | 7.7 (5/16) | 9.4 (3/8) | 11.4 (7/16) | 13.3 (1/2) | |||
| Allowance[mm (inch)] | ±0.2 (±0.007) | ±0.2(±0.007) | ±0.2(±0.007) | ±0.2 (±0.007) | ±0.2 (±0.007) | ±0.3(±0.011) | ±0.4(±0.015) | ||||
| E | Min. [mm (inch)] | 6 (1/4) | 7.9 (5/16) | 9.5 (5/16) | 11 (3/8) | 12.5 (1/2) | 17.5 (11/16) | 18.5 (3/4) | |||
| F | Min. [mm (inch)] | 5 (3/16) | 9 (3/8) | 9 (3/8) | 13 (1/2) | 15 (5/8) | 13 (1/2) | 13 (1/2) | 13 (1/2) | 14 (9/16) | 20 (3/4) |
| L | Max. [mm (inch)] | 20 (3/4) | 28.5 (1-1/8) | 30 (1-3/16) | 33 (1-5/16) | 34 (1-3/8) | 38 (1-1/2) | 43 (1-11/16) | 50 (2) | 51 (2) | |
| d2 | Standard dimension[mm (inch)] | 4.3 (3/16) | 8.4 (1-3/16) | 8.4 (1-3/16) | 8.4 (1-3/16) | 8.4 (1-3/16) | 8.4 (1-3/16) | 8.4 (1-3/16) | 8.4 (1-3/16) | 8.4 (1-3/16) | 8.4 (1-3/15) |
| Allowance [mm (inch)] | +0.2(+0.007)0 (0) | +0.4(+0.015)0 (0) | +0.4(+0.015)0 (0) | +0.4(+0.015)0 (0) | +0.4 (+0.015)0 (0) | +0.4 (+0.015)0 (0) | +0.4(+0.015)0 (0) | +0.4(+0.015)0 (0) | |||
| t | Min. [mm (inch)] | 0.9 (0.03) | 1.15 (0.04) | 1.45 (0.05) | 1.7 (0.06) | 1.8 (0.07) | 1.8 (0.07) | 2.0 (0.078) | |||
Connecting the power terminal
- Connect the cables to the terminal board with solderless ring terminals. - Properly connect the cables by using certified and rated cables and make sure to fix them properly so that external force is not applied to the terminal. - Use a driver and wrench that can apply the rated torque when tightening the screws on the terminal board. - Tighten the terminal screws by complying rated torque value. If the terminal is loose, fire can occur due to arc heat generation and if the terminal is too tight, terminal board could get damaged. 1 Front connection  2 Closing the cover | Screw | Tightening torque for terminal | Remarks | |
| N·m lbf ft | |||
| M3.5 0.78~1.18 0.6~0.9 communication cable | |||
| M4 | 1.2~1.8 | 0.9~1.3 | Single phase 208~230V power cable |
| M8 5.5~7.3 4.1~5.4 3 phase 208~230V / 460V power cable | |||
CAUTION
- When removing the outer sheath of the power supply cable, be careful not to scratch the inner sheath of the cable. - Make sure that more than 20mm (0.79 inch) of the outer sheath of the indoor unit power and communication cable are inside the electrical component box. • Install the communication cable separately from power cable and other communication cables. - There is a risk of electric shock when power is applied. Close the cover of the control box before proceeding to work. - To inspect the compressor or PBA, first make sure to turn off the system. Electricity may flow even in a compressor that has not been used recently. Exercise caution to protect yourself from an electric shock.Examples of how to use the cable stripper
Fixing the power cable
3 phase 3wires 208-230V [AM****XV*F*] 3 phase 3wires 460V [AM****XV*J*]  CAUTION
- Do not let the power cable come into contact with the pipes inside the outdoor unit. If the power supply cable touches the pipes, the vibration of the compressor is transferred to the pipes and can damage the power supply cables or pipes, creating the danger of fire or explosion. - Make sure that the place where the sheath of power supply cable is removed is inside the power supply box. If it is impossible, you should connect the protection tube for power cable to the power supply box. • After arranging the power cable into the power supply box, tighten the cover.Connect the ring terminal of the 3-phase cable
1 Cut the power cable to an appropriate length and connect it with the solderless terminal. 2 After connecting the power cable to the terminal as seen in the illustration, fix it with cable tie. 3 Fix the housing, which has an insulator, to the terminal board. Fixing the ground cable
\- Connect the ground cable to the grounding hole inside the power supply box. Withdrawing the power cable
- Withdrawing from the front side - Connect the power cable protection tube into the power supply box as shown picture. - Be sure that the power supply cable is not damaged by burr on the knock-out hole. Installing the Solution device
\- When the number of indoor units installed with the outdoor unit is 16 or less | F1 F2 OF1 OF2 R1 | R2 | |||
| Terminal block with indoor unit | Terminal block with outdoor unit sub module | Terminal block with solution device | ||
Where to install the interface module
 • Install the interface module in location (A), considering the installation conditions. - For details on how to install, refer to the interface module installation manual. Connecting the MCU (MCU-S6NEK2N, MCU-S4NEK3N, MCU-S2NEK2N, MCU-S1NEK1N, MCU-S8NEK1N, MCU-S12NEK1N) Example   • (A) Power must be supplied to the MCU separately from the outdoor unit. • (B) Connect the communication cable of the outdoor unit (F1, F2) to the communication cable of the MCU (F1, F2) CAUTION
\- Power cable connection should be done with the solderless ring terminal.  \- When installing the MCU, communication cable can be connected as shown above.Grounding work
Grounding must be done by a qualified installer for your safety.Grounding the power cable
• The standard of grounding may vary according to the rated voltage and installation place of the air conditioner. • Ground the power cable according to the following table.| Installation place\Power condition | Voltage to ground is lower than 150V Voltage | to ground is over 150V |
| High humidity Must perform the grounding work 3. Note1 (Including the case where earth leakage breaker is installed) | ||
| Average humidity Perform grounding work 3. Note1) | Must perform the grounding work 3. Note1) (Including the case where earth leakage breaker is installed) | |
| Low humidity | Perform grounding work 3, if possible, for your safety. Note2) | |
Performing the grounding work
• Use a rated grounding cable by referring to the specification of the electric cable for the outdoor unit. ※ When using the exclusive grounding terminal (When the grounding terminal is already built on the house) ※ When using grounding of the switch board  Air tightness test and vacuum drying
Air tightness test
• Use tools for R-410A to prevent the inflow of foreign substances and resist against the internal pressure. - Do not remove the core of filling port. - Use dry nitrogen gas for air tightness test as shown in the illustration. H/PH/R  CAUTION
- Perform a Nitrogen gas leak test with the service valve of the outdoor unit closed. - When charging the nitrogen gas, charge it from the both (high-low pressure) sides. - If the pipe is filled in a short time with a highly excessive pressure of Nitrogen gas, the pipes may get damaged. Make sure to use a regulator to prevent the high pressure Nitrogen gas, over 4.1MPa (594.6psi), from entering into the pipe.Air tightness test and vacuum drying
Vacuum drying pipes and indoor units
• Use tools for R-410A to prevent the inflow of foreign substances and resist against the internal pressure. - Use vacuum pump that allows vacuuming under -100.7kPa (5 Torr). • Use the vacuum pump with the check valve to prevent pump oil from flowing backward while the vacuum pump is stopped. - Completely close the liquid gas side service valve of the outdoor unit.  ※ If the pressure rises in an hour, either water is remaining inside the pipe or there is a leakage. When the ambient temperature of vacuuming pipe is low (less than 0° C ( 32° F)), moisture might remain within the pipe. Therefore, pay special attention to the pipe sealing in the winter.Insulating the refrigerant pipes and branch joints
- Check for gas leakage before completing (the hose and pipe insulation) and if there is no sign of leakage, make sure to insulate the pipes and hoses. - Use EPDM material insulator that meets the following conditions.| Test item Unit Standard | ||
| Density g/cm | 3 | 0.048~0.096 |
| Dimensional change rate by heat | % Below -5 | |
| Absorption rate g/cm | 3 | Below 0.005 |
| Thermal conduction rate W/m·K Below 0.037 | ||
| Moisture transpiration factor | ng/(m2·s·Pa) Below 15 | |
| Moisture transpiration grade | g/(m2·24h) Below 15 | |
| Formaldehyde dispersion mg/L | There should be none | |
| Oxygen rate % Over | 25 | |
Selecting the refrigerant pipe insulator
• Insulate the gas pipe and liquid pipe by referring to the thickness of insulator for each pipe size. - The standard condition is; temperature at 30°C (89.6°F), humidity less than 85%. If case if the humidity is higher, you must increase the size by one grade as stated in below table.| Pipe | Diameter of refrigerant pipe | Insulator (Cooling·Heating) | Remarks | ||||
| General 1) [30 °C, 85 %] | High humidity 2) [30 °C, over 85 %] | ||||||
| EPDM, NBR | |||||||
| mm inch mm inch mm inch | |||||||
| Liquid | 6.35~9.52 | 1/4~3/8 | 9 | 3/8 | 9 | 3/8 | Heat resisting temperature over 120°C |
| 12.7~50.8 | 1/2~2 | 13 | 1/2 | 13 | 1/2 | ||
| Gas | 6.35 | 1/4 | 13 | 1/2 | 19 | 3/4 | |
| 9.52~25.4 | 3/8~1 | 19 | 3/4 | 25 | 1 | ||
| 28.58~44.45 | 11/8~13/4 | 19 | 3/4 | 32 | 11/4 | ||
| 50.8 | 2 | 25 | 1 | 38 | 11/2 | ||
Insulate the refrigerant pipe
- Make sure to insulate the refrigerant pipe, branch joint, distribution header, and the connection part of the pipes. • If you insulate the pipes, condensed water will not fall from the pipes. - Check if there are any cracks on the insulation at the bent part of the pipe.  Insulating pipes
- The insulation of the gas and liquid pipes can be in contact with each other but they should not press excessively against each other. - When the gas side and liquid side pipes are contacting each other, increase the thickness of the insulation by one grade. Insulating pipes connected behind the EEV kit
- When installing the gas side and liquid side pipes, leave at least 10mm of space. - When the gas side and liquid side pipes are contacting each other, increase the thickness of the insulation by one grade. 10mm (0.4inch)10mm (0.4inch) 10mm (0.4inch)  CAUTION
• Install the insulation without any gaps or cracks and use adhesive on the connection part of it to prevent moisture from entering. - Bind the refrigerant pipe with insulation tape if it is exposed to outside sunlight. (When binding the pipe with finishing tape, be careful not to reduce the thickness of the insulation.) • Install the refrigerant pipe respecting that the insulation does not get thinner on the bent part or hanger of pipe. - When the thickness of insulation is reduced, reinforce the reduced thickness with additional insulation. Insulate the distribution header
- Fix the distribution header with a cable tie and cover the connected part. • Insulate the distribution header and the welded part and wrap the connected part with an adhesive insulation tape to prevent dew formation.   - Fix the distribution header with a hanger after insulating it.  Insulating the branch joint
- Tightly attach the insulator, provided with the branch joint, to the separately purchased insulator. Wrap the connected part with an insulator (separately purchased item) that has thickness of at least 10mm (0.4inch). - Use an insulator that resist heat up to 120°C (248°F). Wrap the branch joint with an insulation that has thickness of at least 10mm (0.4inch).  Insulation tape (Separately purchased item)  Pipe insulator (Separately purchased item) ※ Attach the adhesive insulation tape to the pipe, as shown in the picture, after insulating the pipe.Insulating the pipe located inside of the outdoor unit
- With a pipe insulator, insulate the pipe up to whole service valve located inside of the outdoor unit. - Seal the gap between the outdoor unit pipe and the insulator. Rainwater and dewdrops may soak through the gap between the pipe and the insulation of the outdoor unit installed on the outside. - Separate the cover of the pipe and close it after insulation work. Only remove a knock-out hole cover where the pipe will be installed. If the knock-out hole is open unnecessarily, it must be closed. If not, small animals such as squirrels and rats may get into the unit through the hole and the unit may be damaged. H/P  H/R  CAUTION
\- The filled-out label must be adhered in the proximity of the product charging port. (ex. onto the inside of the stop valve cover.)Single installation
- Open the manifold gauge valve connected to the liquid side service valve and add the liquid refrigerant. - If you cannot add the whole quantity of the refrigerant while the outdoor unit is stopped, open the gas side and liquid side service valve. Then, add remaining refrigerant by pressing the refrigerant adding button of the outdoor PCB. Module installation
- Open the manifold gauge valve connected to the liquid side service valve and add the liquid refrigerant. - If you cannot add the whole quantity of the refrigerant while the outdoor unit is stopped, open the gas side and liquid side service valve. Then, add remaining refrigerant by pressing the refrigerant adding button of the outdoor PCB. - If you use the refrigerant charging function from the PCB, outdoor unit will operate and charge the refrigerant. At this time, you must use gas side manifold gauge for cooling operation and use charging port for heating at the manifold gauge for heating operation.  CAUTION
- Open the gas side and liquid side service valve completely after charging the refrigerant. (If you operate the air conditioner with the service valve closed, the important parts may be damaged.) - Put on safety equipment when charging refrigerant. - Do not charge the refrigerant when you adjust or control other product such as indoor units or EEV kits. - If you charge the refrigerant with the front cabinet open, be very careful with the fan on the top of the product to prevent personal injury. - When the ambient temperature is low in winter time, do not heat the refrigerant container to speed up the charging process. There is risk of explosion. - Beware for possibility of refrigerant leakage when you connect the manifold gauge to the charging port for heating. - Close the valve of the refrigerant container immediately after charging the refrigerant. If not, there might be a change in entire amount of refrigerant.Using service valve for gas
• After charging the refrigerant, close all caps as shown in the illustration. - Tightening torque for the cap of refrigerant charging port 10\~12N·m (7.4 \~ 8.9 lbf·ft) - Tightening torque for the cap of control part 20\~25N·m (14.8 \~ 18.4lbf·ft) - Opening/closing torque for the valve - ∅19.05mm (∅3/4inch) : 10 N·m (7.4 lbf·ft) Cap for the control part  Cap for the refrigerant charging portBasic segment display
| Step Display content Display | ||||
| At initial power input Checking segment display | SEG 1 SEG 2 | SEG 3 SEG 4 | ||
| "8" "8" "8" "8" | ||||
| While setting communication between indoor and outdoor unit (Addressing) | Number of connected indoor units | SEG 1 SEG 2 | SEG 3 SEG 4 | |
| "A" "d" | Number of communicated unitsRefer to "View Mode" for communication address | |||
| After communication setting (usual occasion) | MCU, Indoor unit address | SEG 1 SEG 2 | SEG 3 SEG 4 | |
| I/U: "A"MCU: "C" | I/U: "0"MCU: "1" | Reception address (in decimal number) | ||
Setting outdoor unit option switch and key function
Setting outdoor unit option switches
\- Setting outdoor install option| Step Button Display Description | Note | |||
| Outdoor unit address | ||||
| Step1 Outdoor unit display | od nd | Setting required - | ||
| Step2 | Press (K1+K2) for 2 seconds | od 00 | Unit address for module combination | 00: Main unit |
| K4 x 1 time | od 01 | 01: Sub1 unit | ||
| K4 x 2 times | od 02 | 02: Sub2 unit | ||
| K4 x 3 times | od 03 | 03: Sub3 unit | ||
| Step3 | If it is main unit, go to step4. Otherwise, press K2 button for 2 seconds to save & exit (system will be reset) | |||
| Quantity of indoor units | ||||
| Step4 Press K1 | -td 00 | Ready to set - | ||
| Step5 | K2 x n times | -td x0 | Tens digit (0 ~ 6) | Ex) 03: 3 units64: 64 units |
| K4 x n times | -td0x | Ones digit (0 ~ 9) | ||
| * K4: Press for 2 seconds - automatic detection of indoor units' quantity | ||||
| Step6 | If it is heat recovery model, go to step 7. Otherwise, press K2 button for 2 seconds to save & exit (system will be reset) | |||
| Quantity of MCUs * Heat recovery model only | ||||
| Step7 Press K1 | NC 00 | Ready to set - | ||
| Step8 | K2 x n times | NC x0 | Tens digit (0 ~ 1) | Ex) 03: 3 units16: 16 units |
| K4 x n times | nCOx | Ones digit (0 ~ 9) | ||
| * K4: Press for 2 seconds - automatic detection of MCUs' quantity | ||||
| Step9 K2: long | Rd 00 | Save Restart | ||
| * Press K1 for 2 seconds to exit without save regardless of setting step. | ||||
Setting outdoor unit option switch and key function
Installing and setting the option with tact switch and explanation of the functions
Setting the option
1 Press and hold K2 to enter the option setting. (Only available when the operation is stopped) \- If you enter the option setting, display will show the following. (If you have set the 'Emergency operation for compressor malfunction', 1 or 2 will be displayed on Seg 4.)  – Seg 1 and Seg 2 will display the number for selected option. - Seg 3 and Seg 4 will display the number for set value of the selected option. 2 If you have entered option setting, you can shortly press the K1 switch to adjust the value of the Seg 1, Seg 2 and select the desired option. Example)  3 If you have selected desired option, you can shortly press the K2 switch to adjust the value of the Seg 3, Seg 4 and change the function for the selected option. Example)  4 After selecting the function for options, press and hold the K2 switch for 2 seconds. Edited value of the option will be saved when entire segments blinks and tracking mode begins. CAUTION
- Edited option will not be saved if you do not end the option setting as explained in above instruction. ※ While you are setting the option, you may press and hold the K1 button to reset the value to previous setting. ※ If you want to restore the setting to factory default, press and hold the K4 button while you are in the option setting mode. \- If you press and hold the K4 button, setting will be restored to factory default but it doesn't mean that restored setting is saved. Press and hold the K2 button. When the segments shows that tracking mode is in progress, setting will be saved.| Optional item | Input unit | SEG1 | SEG2 | SEG3 | SEG4 | Function of the option | Remarks |
| Emergency operation for compressor malfunction | Individual 0 0 | 0 0 Disabled (Factory default) | E560 will occur when all the compressors are set as malfunction state. | ||||
| 0 | 1 | Set compressor 1 as malfunction state | |||||
| 0 | 2 | Set compressor 2 as malfunction state | |||||
| Capacity correction for cooling | Main 0 1 | 0 0 7 9 | Targeted evaporation temperature [°C].(When low temperature value is set, discharged air temperature of the indoor unit will decrease) | ||||
| 0 1 5-7 (Factory default) | |||||||
| 0 2 | 9-11 | ||||||
| 0 3 | 10-12 | ||||||
| 0 4 | 11-13 | ||||||
| 0 5 | 12-14 | ||||||
| 0 6 | 13-15 | ||||||
| Capacity correction for heating | Main 0 2 | 0 0 | 3.0 (Factory default) | Targeted high pressure [MPa].(When low pressure value is set, discharged air temperature of the indoor unit will decrease) | |||
| 0 1 | 2.5 | ||||||
| 0 2 | 2.6 | ||||||
| 0 3 | 2.7 | ||||||
| 0 4 | 2.8 | ||||||
| 0 5 | 2.9 | ||||||
| 0 6 | 3.1 | ||||||
| 0 7 | 3.2 | ||||||
| 0 8 | 3.3 | ||||||
| Current restriction rate | Individual 0 3 | 0 0 | 100% (Factory default) | When restriction option is set, cooling and heating performance may decrease. | |||
| 0 1 | 95 % | ||||||
| 0 2 | 90 % | ||||||
| 0 3 | 85 % | ||||||
| 0 4 | 80 % | ||||||
| 0 5 | 75 % | ||||||
| 0 6 | 70 % | ||||||
| 0 7 | 65 % | ||||||
| 0 8 | 60 % | ||||||
| 0 9 | 55 % | ||||||
| 1 0 | 50 % | ||||||
| 1 1 | No restriction | ||||||
| Oil collection interval | Main 0 4 | 0 0 | Factory default | ||||
| 0 1 | Shorten the interval by 1/2 | ||||||
| Temperature to trigger defrost operation | Main 0 5 | 0 0 | Factory default | ||||
| 0 | 1 | Apply setting when the product is being installed in humid area such as near river or lake | |||||
| Fan speed correction for outdoor unit | Individual 0 6 | 0 0 | Factory default | ||||
| 0 1 | Increase fan speed | Increase the outdoor unit's fan speed to maximum value | |||||
Setting outdoor unit option switch and key function
| Optional item | Input unit | SEG1 | SEG2 | SEG3 | SEG4 | Function of the option | Remarks |
| Silent mode Main 07 | 00 Disabled (Factory default) | Enables the silent mode for night-time in cooling mode (It operates automatically depending on the temperature.)However, if the external contact interface module (MIM-B14) is used, entering the silent mode is available with contact signal in cooling and heating mode. | |||||
| 01 LEVEL 1 / Auto | |||||||
| 02 | LEVEL 2 / Auto | ||||||
| 03 | LEVEL 3 / Auto | ||||||
| 04 LEVEL 1 / External contact | |||||||
| 05 | LEVEL 2 / External contact | ||||||
| 06 | LEVEL 3 / External contact | ||||||
| 07 | LEVEL 1 | ||||||
| 08 | LEVEL 2 | ||||||
| 09 | LEVEL 3 | ||||||
| High-head condition setting | Main 08 | 00 Disabled (Factory default) | |||||
| 0 | 1 | Level 1 of height difference type 1 (Indoor unit is lower than outdoor unit) | When outdoor unit is located 40~80m above the indoor unit | ||||
| 0 | 2 | Level 2 of height difference type 1 (Indoor unit is lower than outdoor unit) | When outdoor unit is located over 80m above the indoor unit | ||||
| 0 | 3 | Height difference type 2 (Outdoor unit is lower than indoor unit) | When indoor unit is over 30 m above the outdoor unit | ||||
| Long-piping condition setting | Main 09 | 00 Disabled (Factory default) | |||||
| 01 | LEVEL 1 | When equivalent length of farthest indoor unit from the outdoor unit is between 100~170m | |||||
| 02 | LEVEL 2 | When equivalent length of farthest indoor unit from the outdoor unit is over 170m | |||||
| Energy control operation | Main | 10 | 00 | Basic (Factory default) | Energy control option of designated operation sequenceOperating in energy saving mode, capacity might decrease compared to normal operation mode | ||
| 01 | Energy saving | ||||||
| 02 | Power | ||||||
| Rotation defrost (HR only) | Main | 11 | 00 Disabled (Factory default) | ||||
| 01 | Enabled | When enabled, continuous heating operation is possible but heating performance will decrease during rotation defrost operation | |||||
| Expand operational temperature range for cooling operation (HR only) | Main | 1 | 2 | 00 Disabled (Factory default) | |||
| 01 | Enabled | When enabled, continuous cooling operation is possible even in low temperature condition up to -15°C, but noise of the MCU will increase | |||||
| Channel address | Main | 1 | 3 | A | U | Automatic setting (Factory default) | Address for classifying the product from upper level controller (DMS, S-NET 3, etc.) |
| 0~15 | Manual setting for channel 0~15 | ||||||
| Snow accumulation prevention control | Main | 1 | 4 | 00 | Enabled (Factory default) | During snow accumulation, the fan may spin even when the unit is not in operation | |
| 01 | Disabled | ||||||
| Unused option | Main | 1 | 5 | 0 | 0 | Unused option | Unused option by this model |
| Unused option | Main | 1 | 6 | 0 | 0 | Unused option | Unused option by this model |
| Speed operation Main 17 | 0 0 Disabled (Factory default) | Enabling this setting will command the air conditioner to cool/heat faster at initial start-up.However, this function will not work when High-head condition setting or Long-piping condition setting is enabled. | |||||
| 0 1 Enabled | |||||||
| Max. capacity restriction | Main 18 | 0 0 Enabled (Factory default) Restrict excessive capacity | city increasewhen operating indoor units with small capacity | ||||
| 0 1 | Disabled | ||||||
| Unused option | Main | 1 | 9 | 0 | 0 | Unused option | Unused option by this model |
| Unused option | Main | 2 | 0 | 0 | 0 | Unused option | Unused option by this model |
| LA KIT option | Main | 2 | 1 | 0 0 Disabled (Factory default) Set when LA KIT is installed. | In case of using LA KIT option, AI High Pressure Control is restricted. | ||
| 0 1 Enabled | |||||||
| Emergency operation for indoor unit communication error | Main | 2 2 | 0 0 Disabled (Factory default) | When set, emergency operation is possible even if an indoor communication error occurs. | |||
| 0 | 1 | Indoor high humidity condition (operating for up to 12hours) | |||||
| 0 | 2 | Indoor low humidity condition (operating for up to 24hours) | |||||
| Base Heater | Main 2 3 | 0 0 Disabled (Factory default) | Set when Base Heater is installed. | ||||
| 0 1 Enabled | |||||||
| Inverter Carrier Frequency | Main | 2 4 | 0 0 | Disabled (default) | Set inverter carrier frequency | ||
| 0 1 | 8kHz | ||||||
| Aux Heater's interworking control for cycle heating (cooling priority control) | Main | 2 5 | 0 0 | Not applied | When using the Aux Heating, set the delay time for Switching from cooling to heating.※ Unused by the cooling only models | ||
| 0 1 | Switching delay to heating (30 mins.) | ||||||
| 0 2 | Switching delay to heating (15 mins.) | ||||||
| 0 3 | Switching delay to heating (10 mins.) | ||||||
| 0 4 | Switching delay to heating (5 mins.) | ||||||
| 0 5 | Not switching delay | ||||||
| Auto Change Over | Main | 2 | 6 | 0 0 | Not applied | When Thermo off for all running indoor units, change the operation mode.※ Unused by the cooling only models | |
| 0 1 | Applied | ||||||
| Emergency defrost operation | Main | 2 7 | 0 0 | Disable (default) | You can enable this fuction, if the ice on the outdoor Heat exchanger is not removed even after continuous defrost operation, emergency defrosting operation is performed, but defrost operation can take a long time. | ||
| 0 1 | Enable | ||||||
| Reduction of the diameter of liquid pipe | Main | 2 8 | 0 0 | Disable (default) | Set when piping is installed with Reduction of the diameter of liquid pipe. | ||
| 0 1 | Enable | ||||||
| View Mode Unit Option | Main | 2 9 | 0 | 0 | Temperature: °CPressure: MPa | Converts the temperature, pressure units in the view mode(K4 switch) | |
| 0 | 1 | Temperature: °FPressure: psi | |||||
Setting outdoor unit option switch and key function
Setting key operation and checking the view mode with tact switch | K1 control KEY operation Display on segment | |
| Press and hold 1 time Auto trial operation | "K" "K" "BLANK" "BLANK"Display can be changed into "K" "9" "X" "X"(Last two digits display the progress.) |
| K1 (Number of press) KEY operation Display on segment | ||
| 1 time | Refrigerant charging in Heating mode | “K”“1”“BLANK”“BLANK” |
| 2 times Trial operation in Heating mode "K" “2” "BLANK" "BLANK" | ||
| 3 times | Pump out in Heating mode (Outdoor unit address 1) | “K”“3”“BLANK”“1” |
| 4 times | Pump out in Heating mode (Outdoor unit address 2) | “K”“3”“BLANK”“2” |
| 5 times | Pump out in Heating mode (Outdoor unit address 3) | “K”“3”“BLANK”“3” |
| 6 times | Pump out in Heating mode (Outdoor unit address 4) | “K”“3”“BLANK”“4” |
| 7 times | Vacuuming (Outdoor unit address 1) | “K”“4”“BLANK”“1” |
| 8 times | Vacuuming (Outdoor unit address 2) | “K”“4”“BLANK”“2” |
| 9 times | Vacuuming (Outdoor unit address 3) | “K”“4”“BLANK”“3” |
| 10 times | Vacuuming (Outdoor unit address 4) | “K”“4”“BLANK”“4” |
| 11 times | Vacuuming (All outdoor units) | “K”“4”“BLANK”“A” |
| 12 times | Inverter Fault Detection (Comp#1) | “K”“5”“1”“1” |
| 13 times | Inverter Fault Detection (Comp#2) | “K”“5”“1”“2” |
| 14 times | Inverter Fault Detection (Fan#1) | “K”“5”“F”“1” |
| 15 times | Inverter Fault Detection (Fan#2) | “K”“5”“F”“2” |
| 16 times | End Key operation | - |
WARNING
- After installing the product, be sure to perform leak tests on the piping connections. After pumping down refrigerant to inspect or relocate the outdoor unit, be sure to stop the compressor and then remove the connected pipes. - Do not operate the compressor while a valve is open due to refrigerant leakage from a pipe or an unconnected or incorrectly connected pipe. Failure to do so may cause air to flow into the compressor and too a high pressure to develop inside the refrigerant circuit, leading to an explosion or product malfunction.| K2 (Number of press) KEY operation Display on segment | ||
| 1 time | Refrigerant charging in Cooling mode | "K" "5" "BLANK" "BLANK" |
| 2 times Trial operation in Cooling mode "K" "6" "BLANK" "BLANK" | ||
| 3 times | Pump down all units in Cooling mode | "K" "7" "BLANK" "BLANK" |
| 4 times | H/R: Checking the pipe connectionH/P: Automatic setting of operation mode (Cooling/Heating) for trial operation | "K" "8" "BLANK" "BLANK" |
| 5 times Checking the amount of refrigerant | "K" "9" X X (Display of last two digits may differ depending on the progress) | |
| 6 times Discharge mode of DC link voltage "K" "A" "BLANK" "BLANK" | ||
| 7 times Forced defrost operation "K" "B" "BLANK" "BLANK" | ||
| 8 times | Forced oil collection | "K" "C" "BLANK" "BLANK" |
| 9 times | Inverter compressor 1 check | "K" "D" "BLANK" "BLANK" |
| 10 times | Inverter compressor 2 check | "K" "E" "BLANK" "BLANK" |
| 11 times | Fan 1 check | "K" "F" "BLANK" "BLANK" |
| 12 times | Fan 2 check | "K" "G" "BLANK" "BLANK" |
| 13 times | H/R : Auto pipe pairingH/P : Unused | "K" "H" X X (Display of last two digits may differ depending on the progress) |
| 14 times | Baseheater testing mode | "K" "I" "BLANK" "BLANK" |
| 15 times | Unused | "K" "J" "BLANK" "BLANK" |
| 16 times | End Key operation | - |
| K3 (Number of press) KEY operation Display on segment | |||
| 1 time | Initialize (Reset) setting | Same as initial state | |
| K4 (Number of press) KEY operation | Display on segment | ||
| SEG1 | SEG2, 3, 4 | ||
| 1 time | Capacity of Outdoor unit Model | 1 | (a) Capacity → Off, 1, 6 |
| 2 times | Order frequency of the compressor1 | 2 | 120 Hz → 1, 2, 0 |
| 3 times | Order frequency of the compressor2 | 3 | 120 Hz → 1, 2, 0 |
| 4 times | High pressure (MPa) | 4 | 1.52 MPa → 1, 5, 2 |
| 5 times | Low pressure (MPa) | 5 | 0.43 MPa → 0, 4, 3 |
| 6 times | Discharge temperature (Compressor 1) | 6 | 87 °C → 0, 8, 7 |
| 7 times | Discharge temperature (Compressor 2) | 7 | 87 °C → 0, 8, 7 |
| 8 times | IPM temperature (Compressor 1) | 8 | 87 °C → 0, 8, 7 |
| 9 times | IPM temperature (Compressor 2) | 9 | 87 °C → 0, 8, 7 |
| 10 times | CT sensor value (Compressor 1) | A | 2 A → 0, 2, 0 |
| 11 times | CT sensor value (Compressor 2) | B | 2 A → 0, 2, 0 |
Setting outdoor unit option switch and key function
| K4 (Number of press) KEY operation | Display on segment | ||
| SEG1SE | G2, 3, 4 | ||
| 12 times | Suction temperature | C | -42 °C → -, 4, 2 |
| 13 times | COND OUT temperature | D | -42 °C → -, 4, 2 |
| 14 times | Temperature of liquid pipe | E | -42 °C → -, 4, 2 |
| 15 times | TOP temperature (Compressor 1) | F | -42 °C → -, 4, 2 |
| 16 times | TOP temperature (Compressor 2) | G | -42 °C → -, 4, 2 |
| 17 times | Outdoor temperature | H | -42 °C → -, 4, 2 |
| 18 times | EVI inlet temperature | I | -42 °C → -, 4, 2 |
| 19 times | EVI outlet temperature | J | -42 °C → -, 4, 2 |
| 20 times | Main EEV1 step | K | 2000 steps → 2, 0, 0 |
| 21 times | Main EEV2 step | L | 2000 steps → 2, 0, 0 |
| 22 times | EVI EEV step | M | 300 steps → 3, 0, 0 |
| 23 times | HR EEV step | N | 300 steps → 3, 0, 0 |
| 24 times | Fan step (SSR or BLDC) | O | 13 steps → 0, 1, 3 |
| 25 times | Current frequency (Compressor 1) | P | 120 Hz → 1, 2, 0 |
| 26 times | Current frequency (Compressor 2) | Q | 120 Hz → 1, 2, 0 |
| 27 times | Suction 2 temperature | R | -42 °C → -, 4, 2 |
| 28 times | Main indoor unit address S | Main indoor unit not selected → BLANK, N, DIf indoor unit No.1 is selected as the main unit → 0, 0, 1 | |
| 29 times | unused | T | - |
| 30 times | Suction 3 temperature | U | -42°C → -, 4, 2 |
| 31 times | COND OUT 2 temperature | V | -42°C → -, 4, 2 |
| 32 times | End key operation | ||
| Model Display on segment | |
| AM072*** Off, 0, 8 | |
| AM096*** Off,1,0 | |
| AM120*** | Off, 1, 2 |
| AM144*** | Off, 1, 4 |
| AM168*** | Off, 1, 8 |
| AM192*** Off, 2, 0 | |
| AM216*** | Off, 2, 2 |
| AM240*** | Off, 2, 4 |
| K4 (Number of press)Press and hold the K4 to enter the setting | Displayed content | Display on segment | |||
| page1 | page2 | ||||
| 1 time | Main version | MAIN | Version (ex. 1412) | ||
| 2 times | Hub version | HUB | Version (ex. 1412) | ||
| 3 times | Inverter1 version | INV1 | Version (ex. 1412) | ||
| 4 times | Inverter 2 version | INV2 | Version (ex. 1412) | ||
| 5 times | Fan 1 version | FAN1 | Version (ex. 1412) | ||
| 6 times | Fan 2 version | FAN2 | Version (ex. 1412) | ||
| 7 times | EEP version | EEP | Version (ex. 1412) | ||
| 8 times | Automatically assigned address of the units | AUTO | SEG1 | SEG2 | SEG3, 4 |
| Indoor unit: "A"MCU: "C" | Indoor unit: "0"MCU: "1" | Address(ex: 07) | |||
| 9 times | Manually assigned address of the units | MANU | SEG1 | SEG2 | SEG3, 4 |
| Indoor unit: "A" | Indoor unit: "0" | Address(ex: 15) | |||
Optional: Setting the MCU and Pipe Addresses (for HR Only)
You can set the MCU address, the MCU ports to use, and the address for each MCU port connected to each indoor unit. It is for 2nd-generation MCU only. (MCU-S*NEK2N, MCU-S4NEK3N, MCU-S1NEK1N, MCU-S8NEK1N, MCU-S12NEK1N)Setting the MCU address and the MCU ports to use
You can set the MCU address and the MCU ports on the MCU PBA.  1 Set the MCU address switch to a value. If two or more MCUs are installed, be sure to set a unique value for each MCU. For the MCU address, you can set a value from 0 to 15. * When counting the quantity of MCUs, one MCU is one. However, in the case of MCU-S12NEK1N and MCU-S8NEK1N, even one MCU must be counted as two MCUs. 2 For each MCU ports that are connected to an indoor unit through piping, set their DIP switch to ON. For other MCU ports, set their DIP switches to OFF. You can find the address (A to F) of an MCU port on the indoor unit piping connection. 3 If two MCU ports are connected to an indoor unit through a Y-joint, set the relevant S/W option DIP switch to the settings given in the following table:| S/W optionDIP switchNo. | ON(Individual connection) | OFF(Shared connection) |
| 1 Each of | ports A and B Both ports A and B | |
| 2 Each of | ports C and D Both ports C and D | |
| 3 Each of | ports E and F Both ports E and F |
CAUTION
- If the following models are connected, set the pipe addresses manually by referring to Setting the Pipe Addresses Manually. - ERV plus (AM****NKDE*), OAP duct (AM****NEPE*), Hydro Unit (AM****NBDE*, AM****NBF**), AHU kit (MXD-K***AN, MCM-D***N) - If 1st-generation MCU (MCU-S*NEE*N, MCU-S2NEK1N) is installed, refer to the corresponding install manual.Setting the Pipe Addresses Manually
You can use the wired or wireless remote control or the S-NET Pro 2 to set the pipe addresses for each indoor unit.Setting by using the wired or wireless remote control (For how to operate the remote control buttons, see the remote control user manual.)
1 Turn on both the indoor unit and the remote control. 2 Enter the "Option setting mode" on the remote control. 3 Set the address of each MCU port that is connected to an indoor unit by referring to the following table. (You can also set the address of each indoor unit.)| Option | SEG1 | SEG2 | SEG3 | SEG4 | SEG5 | SEG6 |
| Value | 0 | A: Address setting mode | 0: The address of the indoor unit will not be set.1: The address of the indoor unit will be set. | 0 to 9: Hundreds digit of the indoor unit address | 0 to 9: Tens digit of the indoor unit address | 0 to 9: Units digit of the indoor unit address |
| Option | SEG7 | SEG8 | SEG9 | SEG10 | SEG11 | SEG12 |
| Value | 1 | 0 | 0: The RMC address will not be set.1: The RMC address will be set. | 0 | 0 to F: RMC group channel | 0 to F: RMC group address |
| Option | SEG13 | SEG14 | SEG15 | SEG16 | SEG17 | SEG18 |
| Value | 2 | 0 | 0: The MCU address will not be set.1: The MCU address will be set. | 0 to 1: Tens digit of the MCU address | 0 to 9: Units digit of the MCU address | A to F: MCU port address |
| Option | SEG19 | SEG20 | SEG21 | SEG22 | SEG23 | SEG24 |
| Value | 3 | 0 | 0 | 0 | 0 | 0 |
Setting by using S-NET Pro 2
\- Set the pipe addresses by using Add-on > Change address on S-NET Pro 2. (For more information, see the S-NET Pro 2 Help.)Optional: Setting the MCU and Pipe Addresses (for HR Only)
Setting the Pipe Addresses Automatically (Auto pipe pairing operation)
You can use the Automatic pipe-address setting operation to automatically set the address of each MCU port that is connected to an indoor unit. If an MCU port is set incorrectly or a pipe between an MCU and an indoor unit is connected incorrectly, that indoor unit is indicated.Check items before running the Auto pipe pairing operation
1 Ensure that the service valve of the outdoor unit is open. 2 Ensure that the power cables and communication cables of the indoor and outdoor units are correctly connected. 3 Turn on the indoor and outdoor units 6 hours before running the Automatic pipe-address setting operation to warm up both units sufficiently. 4 Before turning on the power, check whether the voltages and phases are correct by using a voltmeter and a phase tester. - Check for the R, S, T, and N terminals: ensure that 380-415V is read between lines (R-S, S-T, T-R) and 200-240V (R-N, S-N, T-N) between phases. 5 After the power is turn on, set the devices (indoor unit, MCU, and others) that are connected to the outdoor unit, and set the options. Note that, before the MCU port addresses are set, MCU port setting errors (E216, 217, 218) may occur. You can run the Automatic pipe-address setting operation regardless of MCU port setting errors. 6 If the OAP(Outdoor Air Processing) Duct or Hydro unit is connected, set the pipe addresses manually referring to [Setting the Pipe Addresses Manually]. 7 Check the operating temperature for the Automatic pipe-address setting operation: If this operation is run at a temperature out of the operating temperature range, the addresses set automatically may be incorrect. Set the pipe addresses manually by referring to Setting the Pipe Addresses Manually. 8 Auto pipe-pairing operation does not work within 3 minutes after power on and reset due to communication check.  [Operating temperature for the Auto pipe pairing operation] \- Before running the Auto pipe pairing operation, be sure to close the front cabinet. If this operation is run with the front cabinet open, the product may be damaged and the pipe addresses cannot be correctly recognized.    To run the Auto pipe pairing operation, take the following steps:
1 Press the K2 button 13 times on the main PBA of the outdoor unit to start the Auto pipe pairing operation. (Display : Hh)| Outdoor temperature < 24°C (75°F) | 24°C (75°F) ≤ Outdoor temperature < 30°C(86°F) | 30°C(86°F) ≤ Outdoor temperature | |
| Indoor temperature < 24°C (75°F) | Main heating operation | Main heating operation | Main cooling operation |
| Indoor temperature ≥ 24°C (75°F) | Main heating operation | Main cooling operation | Main cooling operation |
| Result | Outdoor unit display | Description |
| Setting completed | End | |
| Setting error | E191 ↔ Indoor unit data (displayed alternately) | Indoor unit data• SEG 1,2 = indoor unit address / SEG 3,4 = error status00: An MCU port is not disabled, or a pipe is not connected.01: Cooling only indoor unit is connected to MCU.02: The shared setting for two ports is incorrect.Example) When the MCU port connected to the indoor unit 12 is disabled, E191 and 1200 are displayed alternately• If two or more indoor units have setting errors, the data about the next indoor unit is displayed each time you press the K2 switch. |
CAUTION
- If the MCU ports to use are set incorrectly, the Auto pipe pairing operation may stop due to high-pressure or low-pressure protection control or the data about the indoor unit that has a MCU port setting error may be incorrect. Ensure that the MCU ports to use are set correctly. - Depending on the indoor and outdoor temperatures, the Auto pipe pairing operation may stop due to protection control. - If an error occurs while the Auto pipe pairing operation is running, check the error code and take actions. - If you cannot finish the Auto pipe pairing operation because of the previous reasons, set the pipe addresses manually by referring to Setting the Pipe Addresses Manually.Performing final checks and trial operation
1 Before supplying the power, use DC 500V (AM****XV*J*) or DC 600 V (AM****XV*F*) insulation resistance tester to measure the power (3 phase: R, S, T/1 phase: L, N) terminal and the outdoor unit grounding. \- Measurement should be over 30MΩ. 2 Before supplying the power, use a voltmeter and phase tester to check the voltage and the phase. \- R, S, T terminal: Check the 460V (AM****XV*J*) or 230V (AM****XV*F*) between wires (R-S, S-T, T-R) CAUTION
- Never measure the communication terminal since communication circuit may get damaged. - Check for short-circuit of the communication terminal with a general circuit tester.   3 Check if the R-410A indoor units are connected. 4 When N phase is not correctly connected to R, S and T phase, over-voltage protection control will be in effect and it will cut-off the power of the PCB. Check the power cable connection of the N phase if the PCB is not turned on. 5 Check the following after the installation is completed.| Installation work | Outdoor unit | Have you checked the external surface and the inside of the outdoor unit?Is there any possibility of short-circuit caused by the heat of an outdoor unit?Is the place well-ventilated and ensures space for service?Is the outdoor unit fixed securely to withstand any external force? |
| Indoor unit | Have you checked the external surface and the inside of the indoor unit?Is there enough space for service?Have you checked if the center of the indoor unit is ensured and it is installed horizontally? | |
| Refrigerant pipe work | Have you selected correct pipes?Are the liquid and gas valve open?Is the total number of connected indoor units within the allowable range?Are the length and the height difference between the refrigerant pipes within the allowable range?Are the branch joints properly installed?Did you check the connection of liquid and gas pipes?Have you selected correct insulator for pipes and insulated them correctly?Did you insulate the pipes and connection part correctly?Is the quantity of the additional refrigerant correctly weighed in? (You must record the amount of additional refrigerant on the service record paper placed inside of the outdoor unit.) | |
| Drain pipe work | Have you checked if the drain pipes of the indoor and outdoor unit are connected together?Have you completed the drain test?Is the drain pipe properly insulated? | |
| Electrical wiring work | Are the power cable and communication cable tightened firmly on the terminal board within the range of rated tightening torque?Have you checked for cross-connection of the power and communication cables?Have you performed the earthing work 3 to the outdoor unit?Did you make sure to use 2-core cable (not multi-core cable) for the communication cable?Is the length of the wire within allowed range?Is the wiring route correct? | |
| Setting address | Did you set the address of the indoor and outdoor units properly?Did you set the address of the indoor and outdoor units properly? (When using multiple remote controllers) | |
| Option | If there is a possibility of the outdoor unit from vibrating, check whether the anti-vibration frame is correctly installed. | |





—— Liquid side pipe Gas side pipe
—— High pressuregas pipe—— Liquid side pipe

(12inch) or more



[IMAGE]





























Default Combination of A+B port Combination of C+D port Combination of E+F port