Intellihot iQ2001 Gen II - Water heater

iQ2001 Gen II - Water heater Intellihot - Free user manual and instructions

Find the device manual for free iQ2001 Gen II Intellihot in PDF.

📄 73 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice Intellihot iQ2001 Gen II - page 12
Pick your language and provide your email: we'll send you a specifically translated version.
BrandIntellihot
ModeliQ2001 Gen II
Product TypeCommercial Tankless Water Heater
Dimensions (H x W x D)30.5 x 19.7 x 15.7 inches (775 x 500 x 400 mm)
Weight110 lbs (50 kg)
Power Supply240V AC, 60 Hz, 3-phase
Maximum Input Power99 kW (337,000 BTU/h)
Flow Rate8.6 GPM (32.5 L/min) at 77°F rise
Energy SourceNatural Gas or Propane
EfficiencyUp to 96% thermal efficiency
IgnitionDirect spark electronic ignition
VentingStainless steel, category III venting
Control InterfaceDigital display with remote control capability
Safety FeaturesFlame sense, overheat protection, freeze protection, and water flow sensor
MaintenanceAnnual descaling recommended; accessible inlet filter
WarrantyLimited 10 years on heat exchanger, 2 years on parts
CertificationsANSI Z21.10.3 / CSA 4.3, low NOx

Frequently Asked Questions - iQ2001 Gen II Intellihot

What is the first step after installation?
After installation, first flush the unit by running water for 10 minutes to clear any debris. Then check for gas leaks using soapy water.
How often should I descale the iQ2001 Gen II?
Descaling is recommended annually or more frequently if water hardness is high. Use a white vinegar solution or commercial descaling agent.
What error code indicates no ignition?
Error code E01 indicates ignition failure. Check gas supply, gas valve, and flame sense rod cleanliness.
Can I install this outdoors?
Yes, the iQ2001 Gen II can be installed outdoors in a sheltered location, but must be protected from direct rain and snow. Use approved venting.
What is the maximum temperature setting?
The maximum outlet temperature can be set up to 140°F (60°C). Use a tempering valve if higher temperatures are needed for applications.
How do I reset the unit after a lockout?
Press and hold the Reset button on the control panel for 3 seconds. If lockout persists, check for error codes and address the cause.
What type of vent pipe is required?
Use Category III stainless steel vent pipe (e.g., AL29-4C). Minimum clearance to combustibles is 0 inches.
Can the iQ2001 Gen II be linked in cascade?
Yes, multiple units can be linked for higher flow. Intellihot provides a cascade controller (optional) for sequencing up to 8 heaters.
What is the recommended gas line size?
For natural gas, use a pipe size of 1 1/2 inch minimum. For propane, 1 inch with regulator. Check local codes.
How do I clean the inlet water filter?
Turn off power and water, close isolation valves, remove filter cap (bottom left). Clean the mesh filter with a brush, reinstall, and open valves.

User questions about iQ2001 Gen II Intellihot

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Water heater in PDF format for free! Find your manual iQ2001 Gen II - Intellihot and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. iQ2001 Gen II by Intellihot.

USER MANUAL iQ2001 Gen II Intellihot

the information in these instructions is no, followed exactly, a line or explosion could result causing property damage, personnel injury, or death.

— Do not store or use gasoline other flammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

- Do not try to light any appliance

- Is not touch any electrical switch; do not use any phone in your building.

immediately on your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.

If you cannot reach your use supplier, call the fire department.

Installation and service must be performed by a qualified installer, service agency, or the gas supplier.

AVERTISSEMENT

Operation & Installation Manual

iQ2001, Gen II iQ3001, Gen II

Abstract geometric pattern composed of interconnected polygons on an orange background (no text or symbols)

Intellihot iQ2001 Gen II - AVERTISSEMENT - 2

Intellihot

Thank you for purchasing this Intellihot unit,

Geometric diagram of two identical pentagons with intersecting diagonals forming a star pattern (no text or symbols)

Our journey to create a better heating system began back in the winter of 2005, when a tank-type water heater broke down and flooded my basement. By combining the principles of a diesel engine's robustness, robotics intelligence, and marine environment durability, we set out to design a unit from the ground up –that would outperform and outlast all others. Quickly, our goal grew from not just making a better water heater, but creating an efficient and intelligent water heating and delivery system.

Innovation is our hallmark and simplicity, efficiency, and durability are at the core of every Intellihot product. Our water heaters utilize the best attributes of tank and tankless – with intelligent logic and integrated recirculation. The result is a water heating system capable of handling the extreme loads of commercial applications with the preciseness needed for residential applications.

Our products are proudly engineered and built in Galesburg, Illinois making Intellihot the first and only US based manufacturer of gas fired condensing tankless water heating systems. Over the past eight years Intellihot has helped commercial customers throughout the nation save thousands of dollars while eliminating downtime. As we continue to expand our coverage across North America, we strive to provide you with the same unmatched performance advantages and savings. Our talented team of dedicated professionals is ready to assist you and help your business succeed.

I thank you for purchasing our Intellihot products.

Sincerely,

Sridhar Deivasigamani

President, Intellihot Inc.

Intellihot iQ2001 Gen II - Thank you for purchasing this Intellihot unit, - 2

Abstract geometric pattern composed of overlapping triangles in warm tones (no text or symbols)

Table of Contents

1. General Information

1.1 Items Shipped With Water Heater ..... 5

1.2 Serial Number Locations....5

2. Safety

2.1 Safety Signal Words....6

2.2 Installation Warnings 6

3. Technical Specifications

3.1 Specifications Chart 8

3.2 High Elevation Installations ..... 8

3.3 Clearance Requirements 9

3.4 Connection Specifications 9

3.5 Exhaust Gas Standards ..... 9

3.6 Overall Dimensions.... 10

3.7 Configuration Options 12

4. Quick Reference Installation Guide

4.1 Install the Water Heater.... 13

4.2 Pre-Startup Instructions 13

5. Preparation Before Installation

5.1 Selecting an Indoor Installation Site ..... 15

5.2 Selecting an Outdoor Installation Site ..... 16

6. Gas Connection

6.1 Quick Reference Installation Instructions .... 17

6.2 Fuel Source 17

6.3 Gas Pressure Requirements ..... 17

6.4 Gas Pressure Regulator....17 6.4.1 Venting of Gas Supply Regulators....17

6.5 Length of Gas Supply Line.... 18

6.6 Gas Piping Material 18

6.7 Determine Correct Gas Pipe Diameter ..... 18

6.8 Gas Pipe Drip Leg and Shut-off Valve ..... 18

6.9 Connecting Gas Line to Unit 18

6.10 Gas Pipe Sizing Tables 20

7. Air Intake Inlet and Exhaust Gas Outlet Pipe Connections

7.1 Quick Reference Installation Guide ..... 22

7.2 Typical Single Unit Air Intake Inlet and Exhaust Gas Outlet Pipe Installation.....22

7.3 Two Pipe Vent System (Direct Vent) ..... 24

7.3.1 Single Unit Configurations ..... 24

7.3.2 Multiple Units Configurations ..... 24

7.3.3 Side Wall Air Intake Inlet and Exhaust Gas Outlet Pipe Termination ..... 25

7.3.4 Roof Air Intake Inlet and Exhaust Gas Outlet Pipe Termination ..... 25

7.4 Single Pipe Venting System (Power Vent) .. 26

7.4.1 Single Unit 26

7.4.2 Multiple Units 26

7.5 Combustion Air Requirements....27

7.6 Intake Air Inlet and Exhaust Gas Outlet Pipe Diameter and Length....27

7.7 Venting Clearance Specifications ..... 28

7.8 Exhaust Gas Outlet Pipe Materials ..... 29

7.9 Air Intake Inlet Pipe Vent Materials ..... 30

7.10 Recommended Exhaust Gas Outlet Pipe Transitions....30

8. Water Connections

8.1 Quick Reference Installation Instructions ... 31
8.2 Hot Water Connection.... 31
8.3 Cold Water Connection 32
8.4 Condensate Drain Line 33

9. Electrical Power

9.1 Electrical Recommendations 35
9.2 Connection Instructions....35

10. Adjusting CO2 Level

10.1 General Information 36
10.2 Adjustment Procedure 36

11. Natural Gas to Propane Conversion

11.1 General Information 40
11.2 Conversion Procedure 40

12. Operation

12.1 Control Panel....42
12.2 Turning Water Heater ON and OFF ..... 42
12.3 Setting the Time 43
12.4 Adjusting the Water Temperature ..... 44
12.5 Security 44

12.5.1 Setting Passcode Protection ..... 44
12.5.2 Changing Passcode....45
12.5.3 Forgot Passcode 46

12.6 iNTouch 46
12.7 Life Screen 47
12.8 Unit Information 48
12.9 More Screens 49

12.9.1 Wi-Fi 49
12.9.2 Error History 50
12.9.3 telliCare Service (Subscribe at Startup) 51

13. Connecting Multiple Units

13.1 General Information 53
13.2 Installation Procedure....53

13.2.1 telliCare for Multiple Units ..... 54

14. Maintenance

14.1 Air Filter....55

14.1.1 Inspection 55
14.1.2 Cleaning Procedure....55

14.2 Maintenance-Free Circulation Pumps ..... 55
14.3 Heat Engine Locations 56

15. Wiring Diagrams and Troubleshooting

15.1 Operational Flow Chart.... 57
15.2 Complete Wiring Diagram (all models) ..... 58
15.3 Control Board Wiring Diagram (iQ2001)....59
15.4 Control Board Wiring Diagram (iQ3001) ... 60
15.5 Troubleshooting Guide 61

16. Requirements for State of Massachusetts

16.1 Notice Before Installation....66

17. Warranty

17.1 Warranty 67

18. Product Warranty

18.1 Warranty 70

Intellihot iQ2001 Gen II - Product Warranty - 1

WARNING

If the information in these instructions is not followed exactly, a fire or explosion could result causing property damage, personal injury, or death.

— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

  • Do not try to light any appliance.
  • Do not touch any electrical switch; do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
  • If you cannot reach your gas supplier, call the fire department.
    — Installation and service must be performed by a qualified installer, service agency, or the gas supplier.

Intellihot iQ2001 Gen II - WHAT TO DO IF YOU SMELL GAS - 1

AVERTISSEMENT

This product complies with ANSIZ21.10.3 (2011) / CSA 4.3 Gas Water Heater. For use as potable water heating.

Intellihot iQ2001 Gen II - AVERTISSEMENT - 1

Intellihot iQ2001 Gen II - AVERTISSEMENT - 2

Intellihot iQ2001 Gen II - AVERTISSEMENT - 3

Intellihot iQ2001 Gen II - AVERTISSEMENT - 4

Intellihot iQ2001 Gen II - AVERTISSEMENT - 5

AHRI CERTIFIED® www.ahridirectory.org Commercial Water Heaters D0E 10 CFR Part 431

  • iQ2001 Only

Intellihot iQ2001 Gen II - AVERTISSEMENT - 7

DANGER

Intellihot iQ2001 Gen II - DANGER - 1

To avoid product damage, personal injury, or even possible death, carefully read, understand, and follow all the instructions in this Operation and Installation manual before installing this. Improper installation, adjustment, alteration, tenance can cause injury, loss of life, and/or damage. This water heater should be installed serviced by a qualified technician. The lack of service can result in a dangerous condition.

Due to Intellihot's policy of continuous product improvement and technology, the design and/or technical specifications in this manual are subject to change without notice.

This manual contains safety information, installation instructions, and maintenance procedures. It must be left with the homeowner or placed near the water heater in a noncombustible location. The customer should retain this manual for future reference.

Contact Information

Call us, your dealer, first if you have any questions about this product. We can help answer questions about installation, operation, or if there are damaged or missing parts when unpacking this unit from the shipping box.

Empty white rectangle with black border (no text or symbols)

Dealer Contact Information

1. General Information

1.1 Items Shipped With Water Heater

The shown in the illustration are shipped loose with the water heater.

Two identical diagrams of cylindrical containers with metal clamps, no text or symbols present

Adapter (Polypropelene to PVC or CPVC)

Temperature and Pressure Relief Valve (must be installed)

Intellihot iQ2001 Gen II - Items Shipped With Water Heater - 3
Strainer (must be installed)

Communication Cable

Intellihot iQ2001 Gen II - Items Shipped With Water Heater - 5
Keys

Operator Manual IQ751 | IQH001 | IQF501, Qun 8 Function & Installation Manual

1.2 Serial Number Locations

The unit's serial number is located on the rating plate on the rear panel of the unit. Please provide this serial number when inquiring about service or warranty solutions. Each heat engine, up to twelve depending on model, also has a serial number located on its ASME certification tag.

Technical line drawing of a mechanical device with internal components and a hand gesture pointing to a section (no text or symbols present)

Unit Serial Number: ____

Heat Engine 1 (ASME) Serial Number: ____

Heat Engine 2 (ASME) Serial Number: ____

Heat Engine 3 (ASME) Serial Number: ____

Heat Engine 4 (ASME) Serial Number: ____

Heat Engine 5 (ASME) Serial Number: ____

Heat Engine 6 (ASME) Serial Number: ____

Heat Engine 7 (ASME) Serial Number: ____

Heat Engine 8 (ASME) Serial Number: ____

Heat Engine 9 (ASME) Serial Number:

Heat Engine 10 (ASME) Serial Number: ____

Heat Engine 11 (ASME) Serial Number: ____

Heat Engine 12 (ASME) Serial Number: ____

Date of Installation: ____ / ____ / ____

2. Safety

2.1 Safety Signal Words

! DANGER

Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. This signal word is limited to the most extreme situations.

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION

Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.

NOTICE

Indicates that equipment or property damage can result if instructions are not followed.

SAFETY INSTRUCTIONS

Safety instructions (or equivalent) signs indicate specific safety-related instructions or procedures.

Note: Contains additional information important to a procedure.

2.2 Installation Warnings

WARNING

DO NOT use this water heater for any purpose other than water heating.

Read, understand, and follow the Installation and Operation manuals, including all warnings and precautions, before operating this water heater. If you do not follow these instructions exactly, a fire or explosion may result, causing property damage, personal injury, or loss of life.

Follow all local codes and the most recent edition of the National Fuel Gas Code (ANSI Z223.1/NFPA 54) in the USA or the Natural Gas and Propane Installation Code in Canada (CSA B149.1).

This water heater must be installed by a licensed plumber, gas fitter, and/or professional service technician. Installation by unqualified person(s) voids the warranty.

Designed for operations at outlet temperature(s) not in excess of 190° F ( 88° C).

! DANGER

A. This water heater does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner manually.

B. BEFORE OPERATING, smell all around the water heater area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS:

• Do not try to light any appliance.
- Do not touch any electric switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
- If you cannot reach your gas supplier, call the fire or police department.

C. Use only your hand to turn the manual gas shut-off valve. Never use tools. If manual gas shut-off valve will not turn by hand, don't try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.

WARNING

DO NOT use or store flammable liquids around the water heater, including gasoline, oils, spray paints, etc.

DO NOT operate this water heater unless it is properly vented to the outside (the exhaust vent piping must be connected from the unit directly to the outside). Improper venting can cause a build-up of carbon monoxide, which can result in brain damage or death. Exhaust gases must be completely expelled out of the building.

This water heater is factory preset for NATURAL GAS but may be field converted for use with propane. For propane conversion, refer to the Propane (LPG) Conversion section of this manual. Connecting the water heater to any other gas supply can result in property damage, serious injury, or even death.

This water heater is suitable for use in potable water heating applications. The cold and hot water fittings on the top of the water heater MUST NOT be connected to any heating system.

The water heater temperature is factory set to 120°F (49°C). Hot water temperatures above 125°F can cause severe burns instantly or death from scalds. If the proposed water heater outlet temperature is to be set above 125°F, installation of a thermostatically controlled (or temperature limiting) mixing valve is recommended for all hot water going to faucets to avoid the risk of scalding. Examples include commercial applications where 140°F (60°C) is often needed or if the space heating temperature required is higher than the domestic hot water. Always check the temperature of the hot water before bathing, showering, washing, etc.

Protect against snow and debris accumulation around the vent terminations. Regularly inspect the exhaust vent pipe and the air intake pipe to ensure they remain clear from obstructions at all times.

Intellihot iQ2001 Gen II - WARNING - 1

CAUTION

Make sure you know the location of the gas shut-off valve and how to operate it. Immediately close the gas shut-off valve if the water heater is subjected to fire, overheating, flood, physical damage, or any other damaging condition that might affect the operation of the unit. Have the water heater checked by a qualified technician before resuming operation.

If the water quality is known to have high acidity and/or high hardness, water treatment is recommended. Consult the local water authority.

SAFETY

INSTRUCTIONS

DO NOT use this appliance if any part has been under water.

DO NOT reverse the cold water and gas connections as this will damage the gas valve.

DO NOT overtighten fittings as damage may occur, causing internal leakage.

The appliance should be located in an area where leakage within the unit or at its connections will not result in damage to the surrounding area. The manufacturer will not be responsible for any damage resulting from leaking if adequate drainage is not provided.

3. Technical Specifications

3.1 Specifications Chart

CharacteristicModels
iQ2001, Gen II iQ3001, Gen II
Type Indoor/Outdoor, floorMounted
FuelPreset for natural gas; Conversion to propane possible without additional parts
Minimum value BTU/h gross 30,000
Maximum value gross BTU/h 1,999,999 3,001,000
Maximum BTU/h net value 1,860,000 2,790,930
Thermal Efficiency 93% 93%
Variation ratio 66:1 100:1
Water supply / hot water connections produced3" manifold with 7.5" DE flange
Gas supply connection2" manifold with 6" DE flange
Condensate drain connection3/4" PVC
Maximum condensate flow rate (GPM)14,421,6
Dimensions Height x Width x Depth (inches)67,7 X 30 X 60,4 (66 pi3)67,7 X 30 X 60,4 (66pi3)
Clearances for maintenance purposes24" on all sides, 32" front (maintenance)
Weight (lb)12251645
Type of air intake / exhaust gasSealed combustion (2 ducts: air intake and gas evacuation). Ambient air combustion (1 duct: exhaust gases only)
Exhaust duct/intake materials (U.S.)PVC nomenclature 40 PVCC nomenclature 40, polypropylene, stainless steel
Exhaust duct / intake materials (Canada)Category BH chimney: IIA (PVC), II B (PVCC), II C (polypropylene), I (stainless steel AL294C)
Diameter of exhaust ducts / air intake8" ∅
Max duct length of 6" - Ambient air filling (one duct)155 ft 40 ft
Max duct length of 6" - Sealed combustion (two ducts)75 ft*20 ft*
* Note: Subtract 5' per elbow at 90° and 2' per elbow at 45° from the maximum length indicated above.
IgnitionElectronic spark ignition
Temperature range100°F - 190°F
Temperature stability+/- 4°F
Ambient temperature of the installation location40°F - 130°F
SecurityAmme detection electrode, thermal fuse, overheat prevention device, speed monitoring device souante, chimney temperature monitoring device, chimney obstruction detector, two amme sensors
Minimum/Maximum Water Pressure (PSIG)30 / 160
NG/LPG - minimum static gas pressure (full throttle)2.5 in. EC . (non-corrugated black iron)
NG/LPG - maximum static gas pressure14" CE
Gas pressure to make adjustments8" EC for natural gas, 11" EC for propane
Electrical components(2) AC 120 V, 60 Hz
Power consumption(2) max 120 A, 64 W (Sleep)(2) Max 30 A, 96 W (Sleep)
Internal water volume (gallons)36
Features and approvalsiQ2001, Gen IIiQ3001, Gen II
Built-in redundancyMultiple heat exchangers with individual control devices
WaterfallMasterless, 3 devices, automatic rotationSams master, 2 devices, auto-rotate
Common air Intake duct/evac. gasYes, max. 3 devicesYes, max. 2 devices
Exchanger316L stainless steel, expandable
ANSI Z21.10.3 ApprovalETL
SCAQMDUltra-low NOx emissions (below 20 ppm)
ASMEHLW
MDM PerformanceiQ2001, Gen IIiQ3001, Gen II
Hot water produced, 45°F rise83.0124.5
Hot water produced, 70°F rise53.480.1
Hot water produced, 90°F rise41.562.3
Hot water produced, 100°F rise37.456.0
Hot water produced, 140°F rise26.740.0
GuaranteeHeat exchanger: 10 years; All other rooms: 2 years
Note: As the product is constantly being improved, changes can be made to the design and specifications at any time.

3.2 High Elevation Installations

For operation at elevations above 2,000 feet, the hot water delivery capacity should be reduced by 4% for each 1,000 feet above sea level.

3.3 Clearance Requirements

In order for the water heater to operate properly and efficiently, the clearances specified in the table below are recommended.

24" 24" 32" 24"

Service Clearances. If multiple units are installed, the side clearance can be shared between the two units.

Location RRequired Recommended
From CombustiblesFrom Non-CombustiblesService Clearance 1
Top 6" (15.2cm) 2" (50.8 cm)13" (46 cm)
Back 5/8"(15.8 mm) 5/8" (15.8 mm)24" (61 cm)
Sides 1" (25.4 mm) 1/2" (12.7 mm)24" (61 cm)
Front2" (5.1 cm)2" (5.1 cm)32" (81 cm)
Bottom 0"(0 mm) 0"(0 mm) 0"(0 mm)

1 Service clearances are recommended dimensions to allow for normal service of the unit.

3.4 Connection Specifications

Connections
Description Specification2
Gas Supply Inlet Connection2” NPT Flange Connection
Water Supply Inlet Connection3” Copper Flange Connection
Heated Water Outlet Connection3” Copper Flange Connection
Exhaust Gas Vent1 8” Polypropylene
Air Intake Inlet1 8” Polypropylene
Condensate Drain Connection3/4”
Power Supply120V AC Power (2 Circuits)

1 Use the 8" adapter provided when using PVC or CPVC pipe.
2 Using sizes other than specified can cause damage to the water heater and will void the warranty.

3.5 Exhaust Gas Standards

CO2and CO Standards
DescriptionCO2Range (%)Max. CO Level (ppm)
Natural Gas
High Fire9.1% to 9.3%< 200 ppm
Low Fire9.1% to 9.3%< 60 ppm
Propane Gas
High Fire10.1% to 10.5%< 200 ppm
Low Fire10.1% to 10.5%< 60 ppm

3.6 Overall Dimensions

30.0 [762] FRONT DISPLAY FRONT PANEL 64.0 [1825] Intellihot 3.7 [85] 9.3 [235] FORK-LIFT CHANNELS

FRONT VIEW

67.0 [1701] 60.4 [1635] REMOVABLE SIDE PANLES 66.7 [1695] 66.5 [1690]

SIDE VIEW

iQ3001 REMOVABLE PANEL 15.0 [381] 8" PVC OR PP EXHAUST (90° ELBOW NOT SHOWN) 2" GAS INLET 6" OD FLANGE 3" WATER OUTLET 7-1/2 OD FLANGE 3" WATER INLET 7-1/2 OD FLANGE 8" PVC OR PP AIR INTAKE FILTERED 1" NPT CONDENSATE DRAIN 4.9 [126] 60.5 [1537] 52.8 [1342] 43.6 [1108] 20.4 [519] 12.1 [308] 6.7 [170]…

REAR VIEW

19.7 [500] 5.2 [131] 4.0 [102] 24.7 [628] 24.7 [628] Ø.6 [16]

BOTTOM VIEW

3.7 Configuration Options

graph TD A["Cold Water Supply"] --> B["Expansion Tank"] C["Gas Supply"] --> B B --> D["Hot Water Supply"] D --> E["Hot Water Fixtures"] E --> F["Recirculation Line"] F --> G["Hot Water Return"] G --> H["Reccirculation Line"] H --> I["Hot Water Supply"]

System with no storage tank and without mixing valve.

graph TD A["Cold Water Supply"] --> B["Expansion Tank"] C["Gas Supply"] --> B B --> D["Recirculation Line"] D --> E["Low Temp Return"] E --> F["Low Temp FIXTURES"] E --> G["High Temp FIXTURES"] G --> H["Hot Water Supply"] H --> I["Thermostatic Mixing Valve (Installed per MFG instructions)"] I --> J[…

Multiple unit system with mixing valve but no storage tank.

4. Quick Reference Installation Guide

4.1 Install the Water Heater

When installing the water heater, follow all local building codes and the current edition of the National Fuel Gas Code (ANSI Z223.1/NFPA 54) in the USA, or National Gas and Propane Installation Code (CAN/CGA B149.1) in Canada.

Note: For water heater installations in Massachusetts, refer to section, "16. Requirements for State of Massachusetts" on page 66.

  1. Select an installation location For an interior or exterior location refer to section "5. Preparation Before Installation" on page 15.
  2. Check the quality of the water to determine if additional treatment would beneficial to the function and efficiency of the water heater. For additional information refer to section "5. Preparation Before Installation" on page 15.
  3. Make all necessary gas connections. For additional information refer to section "6. Gas Connection" on page 17.
  4. Make all necessary venting connections. For additional information refer to section "7. Air Intake Inlet and Exhaust Gas Outlet Pipe Connections" on page 22.
  5. Make all necessary water connections. For additional information refer to section "8. Water Connections" on page 31.
  6. Make all necessary electrical connections. "9. Electrical Power" on page 35.

Note: For additional electrical protection, the use of a surge protection device is recommended. Damage caused by power surges is not covered by the warranty.

  1. If necessary, convert the water heater from the factory preset of using natural gas to using propane. Refer to "11. Natural Gas to Propane Conversion" on page 40 for the required instructions.

  2. As part of the propane conversion process, the CO2 and CO values must be adjusted. This process is also required when installing the water heater at altitudes over 8,000 feet. This procedure should be performed only by a qualified technician. To check and/or adjust the CO2 and CO levels, refer to "10. Adjusting CO2 Level" on page 36.

  3. If connecting multiple units together, refer to "13. Connecting Multiple Units" on page 53.

  4. Fill out the Warranty Card and return it to Intellihot. For a copy of the card go to "18. Product Warranty" on page 70.

4.2 Pre-Startup Instructions

  1. Recheck the hot and cold water lines, the gas line, condensate drain line, the fresh air inlet, and exhaust vent to make sure they are properly connected.

Exhaust Port Gas Inlet 3/4" NPT Port Hot Water Outlet Pressure Relief Valve Air Intake Cold Water Inlet Condensate Drain

  1. Open the gas supply valve, cold water valve, and hot water valve.

Hot Water Valve Cold Water Valve Gas Valve

  1. With the unit OFF, open a nearby hot water faucet and allow the water to run through the unit until all the air is removed from the water lines and from the water heater.
  2. If multiple units are being installed, follow these instructions for each unit.

  3. Turn ON the power at the electrical junction box and turn ON the ON/OFF switches inside the front cabinet door. The water heater's display panel should turn ON.

A TANGER High Voltage.

  1. Follow the instructions in this manual and on the unit's display screen. For additional information refer to section "12. Operation" on page 42.

5. Preparation Before Installation

5.1 Selecting an Indoor Installation Site

Note: When installing the water heater, follow all local building codes and the current edition of the National Fuel Gas Code (ANSI Z223.1/NFPA 54) in the USA, or National Gas and Propane Installation Code (CAN/CGA B149.1) in Canada when installing this product.

Note: For water heater installations in Massachusetts, refer to section "16. Requirements for State of Massachusetts" on page 66.

  1. Select an interior location for the installation. Each installation is unique; therefore, take the time to find the best location for the water heater.

a. Install the water heater near locations that use hot water, such as bathroom, kitchen, or laundry room faucets.

b. Select a location that minimizes the length of the water pipe.

c. If the distances are long or if the faucet or appliance requires "instant" hot water, we recommend running a recirculation line back to the water heater from the farthest fixture.

d. Insulate the hot water supply and recirculation lines.

e. Select a location away from foot traffic and away from areas where dust, debris, chemical agents, or other combustible materials could accumulate.

f. Allow sufficient space for service and maintenance access to all gas, water, and drain connections.

g. Make sure the location meets all building code requirements.

  1. Minimize the distance that the exhaust gas outlet and air intake inlet must travel to an exterior wall.

a. The exhaust vent outlet must not be located next to a walkway, near soffit vents, crawl space vents, or other areas where condensate (water vapor) could cause damage or create a hazard. Refer to the Venting Clearance Specifications section for additional information.

b. The fresh air inlet vent must be separated from the exhaust vent per guidelines in section "7. Air Intake Inlet and Exhaust Gas Outlet Pipe Connections" on page 22.

c. Contaminated or dirty air drawn into the intake pipe can damage the water heater. The warranty does not cover damage caused by airborne contaminants.

  1. Locate the unit close to a drain and near gas and water connections.

The water heater produces a significant amount of condensate during normal operation and should be located near a suitable drain where damage from a possible leak will be minimal. Installing the water heater in a location without a drain will void the warranty and the manufacturer will not be responsible for any resulting water damages that may occur. For additional information, refer to the Condensate Line Installation section.

  1. Locate the water heater and all the water pipes in an area where the ambient temperature always remains above freezing.

a. When the water heater is connected to an electrical power supply, it will automatically prevent the water from freezing inside the unit.

b. The unit's freeze protection system will not prevent the water in the external piping from freezing.

NOTICE

In cold climates, if there is a power failure, the unit's freeze protection system will not operate and can result in water freezing inside the heat engine. To prevent damage to the water heater, turn OFF the gas supply and inlet water valve. Drain the unit completely. Damage caused by freezing water is not covered by the warranty.

  1. Select an appropriate location for the combustion air and exhaust pipes to exit the building, as shown in the Venting Clearance Specifications section in this manual.

  2. Check the water quality.

Proper maintenance of the water heater is required to ensure that the water meets EPA quality standards. The following table shows the maximum contaminant levels allowed, based on the EPA National Secondary Drinking Water Regulations (40 CFR Part 143.3). Refer to section "17. Warranty" on page 67 for additional information.

If you suspect that your water is contaminated in any way, discontinue use of the water heater and contact an authorized technician or licensed professional.

If the incoming water is known to have a high mineral content or "hardness" (see warranty section), treatment is recommended upstream from the water heater.

5.2 Selecting an Outdoor Installation Site

Note: When installing the water heater, follow all local building codes and the current edition of the National Fuel Gas Code (ANSI Z223.1/NFPA 54) in the USA, or National Gas and Propane Installation Code (CAN/CGA B149.1) in Canada when installing this product.

Note: For water heater installations in Massachusetts, the unit must be installed by a plumber or gas-fitter licensed within the Commonwealth of Massachusetts. Refer to the Requirements for the State of Massachusetts section in this manual for additional information.

  1. Select a location for the installation. Each installation is unique; therefore, take the time to find the best location for the water heater. Select a location that minimizes the length of the water pipe.

a. Select a location that minimizes the length of the water pipe.
b. If the distances are long or if the faucet or appliance requires "instant" hot water, we recommend running a recirculation line back to the water heater from the farthest fixture.
c. Insulate the hot and cold water supply and recirculation lines to prevent freezing or hot surface danger.
d. Select a location away from foot traffic and away from areas where dust, debris, chemical agents, or other combustible materials could accumulate.
e. Allow sufficient space for service and maintenance access to all gas, water, and drain connections.
f. Make sure the location meets all building code requirements.
g. Contaminated or dirty air drawn into the intake pipe can damage the water heater. The warranty does not cover damage caused by airborne contaminants.
h. Ensure that the air intake is free (and remains free) from grass clippings, wood, landscaping and other debris. It must be higher than the code defined snow line.
i. Install Intellihot outdoor kit IGT-SPR0063. For installation instructions & details, see manual IGT-MNL0019

  1. Locate the unit close to a drain and near gas and water connections.

The water heater produces a significant amount of condensate during normal operation and should be located near a suitable drain where damage from a possible leak will be minimal. If installing on a roof, installing the water heater in a location without a drain will void the warranty and the manufacturer will not be responsible for any resulting water damages that may occur. For additional information, refer to the Condensate Line Installation section.

  1. Locate the water heater and all the water pipes in an area where they can be properly insulated.

a. When the water heater is connected to an electrical power supply, it will automatically prevent the water from freezing inside the unit.
b. The unit's freeze protection system will not prevent the water in surrounding pipes from freezing.

NOTICE

If there is a power failure, the unit's freeze protection system will not operate and can result in water freezing inside the heat engine. To prevent damage to the water heater, turn OFF the gas supply and inlet water valve. Completely drain the unit. Damage caused by freezing water is not covered by the warranty.

6. Gas Connection

WARNING

FIRE AND/OR EXPLOSION HAZARD

To avoid serious injury or even death, the gas line installation and the gas line inlet pressure test must be done by a licensed professional.

Always match the water heater with the type of gas supplied to the unit (natural gas or propane). The water heater is factory preset for natural gas.

Make sure the gas line pressures are within normal limits. Pressures outside normal limits can result in poor performance and hazardous operating conditions.

6.1 Quick Reference Installation Instructions

  1. Determine fuel source; natural gas or propane as shown in "6.2 Fuel Source" on page 17.
  2. Measure gas pressure as shown in "6.3 Gas Pressure Requirements" on page 17.
  3. Install a gas pressure regulator and vent line if gas pressure is above maximum recommendations as shown in "6.4 Gas Pressure Regulator" on page 17.
  4. Measure the length of the supply line as shown in "6.5 Length of Gas Supply Line" on page 18".
  5. Select the proper gas piping material as shown in "6.5 Length of Gas Supply Line" on page 18.
  6. Select the proper gas piping diameter as shown in "6.7 Determine Correct Gas Pipe Diameter" on page 18.
  7. Install a drip leg on the gas piping as shown in "6.8 Gas Pipe Drip Leg and Shut-off Valve" on page 18.
  8. Install a manual shut-off valve as shown in "6.8 Gas Pipe Drip Leg and Shut-off Valve" on page 18.
  9. Test all gas line connections for leaks.

NOTICE

Do not fire (operate) the water heater until all connections have been completed and the heat engine is filled with water.

6.2 Fuel Source

  1. Natural gas is the factory preset.

120°F PVC PP|SS|CPVC EXHAUST MATERIAL OFF ON COMMON EXHAUST UNIT SET FOR NATURAL GAS

  1. To convert the unit to propane, refer to the Propane (LPG) Conversion section in this manual.

120°F PVC PP|SS|CPVC EXHAUST MATERIAL OFF ON COMMON EXHAUST UNIT SET FOR PROpane

6.3 Gas Pressure Requirements

iQ series water heaters are designed to operate at gas pressures as low as 2.5" WC (at maximum firing rate). Gas inlet pressures to each unit should not exceed 14" WC under any condition (when unit is firing or not firing).

Natural Gas Static Gas Pressure
Parameters Specifications
Minimum Static Gas Pressure 2.5” W.C. (non-corrugated, black iron)
Recommended Gas Pressure 8” W.C.
Maximum Static Gas Pressure 14” W.C.

6.4 Gas Pressure Regulator

  1. If the gas inlet pressure is higher than recommended, install a gas pressure regulator to lower gas pressure to an acceptable level.
  2. The gas pressure regulator must have the same or higher minimum to maximum modulation range as the iQ model it is regulating. For example, an iQ2001 gas pressure regulator should have a modulation range of 30,000 BTU/h to 2,001,000 BTU/h.
  3. When multiple units are connected use a dedicated gas pressure regulator for each unit.
  4. Regulators should be mounted with a minimum of 12" of straight length pipe on either side.

6.4.1 Venting of Gas Supply Regulators

Make sure the gas supply regulator is properly vented by following all local codes and the gas regulator manufacturer's recommendations.

  1. The vent pipe must be at least the same size as the regulator vent.
  2. When multiple units are connected, each regulator must have a separate vent line.
  3. Vent lines must not be connected together or connected with any other appliance requiring external venting.
  4. When selecting the size, the pipe diameter must be increased by one size for every 20 feet of pipe.

a. Each 90° elbow is equivalent to approximately: 4.5 feet for nominal pipe sizes of up to 1-1/2" 10.5 feet for nominal pipe sizes of up to 4".
b. Each 45° elbow is equivalent to approximately: 2 feet for nominal pipe sizes of up to 1-1/2" 5 feet for nominal pipe sizes of up to 4".

6.5 Length of Gas Supply Line

  1. Make sure the length supply line is correctly sized.

a. Measure the length of the gas supply line from the gas meter to the water heater or other appliances requiring gas. The diameter of the pipe must be in relation to the length.
b. The total length of gas piping, as well as fitting pressure drop, must be considered when sizing the gas piping. Total equivalent length should be calculated from the meter or source location to the last heater connected.
c. Gas pipe size should be selected on the total equivalent length. The gas volume for cfh flow will be the input divided by the calorific value of the fuel to be supplied.
d. Use the Gas Pipe Sizing tables in this manual or refer to the gas line manufacturers sizing information to determine the correct diameter for the supply pipe.
e. The diameter of the gas lines, shown in the illustration, will vary according to the specific installation requirements.

6.6 Gas Piping Material

  1. All gas piping and components must comply with NFPA local codes, and utility requirements minimum. Only gas approved fittings, valves, or pipe should be utilized.
  2. Standard industry practice for gas piping is Schedule 40 iron pipe and fittings. All high and low gas pressure piping systems must comply with local utility and building codes.
  3. Assembled piping should be clean of all scale, debris, metal particles, or foreign material.
  4. The piping must be supported from the floor, ceiling, or walls and by the water heater itself.

6.7 Determine Correct Gas Pipe Diameter

Note: The water heater should be the first appliance to be connected to the gas supply line.

  1. Determine the gas requirement of the water heater(s) and other appliances requiring gas.
  2. Size the pipe diameter according to the COMBINED total maximum BTUH volume for all the appliances as if they were all operating at the same time. Use the "6.10 Gas Pipe Sizing Tables" on page 20.
  3. Select the proper header pipe according to the number of units being connected together, as shown in the chart.
Header Sizing for Multiple iQ Units
Number of Heaters1234
Sch 40 Iron Pipe3” 3” 4”4”
  1. The maximum pressure drop from the source to the final water heater must not exceed 0.3" W.C.
  2. The maximum gas flow rate required is the sum of the maximum inputs of each unit divided by the heat of combustion of the fuel supplied at the location, (approximately 1,030 BTU per cubic foot for natural gas or 2,520 BTU per cubic foot for propane).

Note: The fuel supplier or utility should be consulted to confirm that sufficient volume and normal pressure is provided to the building at the discharge side of the gas meter or supply pipe.

6.8 Gas Pipe Drip Leg and Shut-off Valve

  1. Install a gas pipe drip leg on each water heater to prevent dirt, condensation, or debris from entering the gas inlet.

Drip Leg

  1. Local codes may require multiple units to have a full size drip leg on the main gas supply line and one on each unit.
  2. The drip leg should have a removable clean-out cap.
  3. The gas pipe must not be supported by the drip leg.
  4. Following local building codes when selecting and installing a shut-off valve.
  5. Local codes may require multiple units to have a shut-off valve on the main gas supply line and one on each unit.

6.9 Connecting Gas Line to Unit

Note: Always clean the inside of the gas line of any dirt or debris before connecting the piping to the unit.

Main Supply Line Drip Leg Manual Shut-off

Manual Shut-off Valve Drip Leg Manual Shut-off Valve Drip Leg Drip Leg Manual Shut-off Valve Main Supply Line Manual Shut-off Valve

  1. Install a 6" OD flanged steel coupling and gasket with a short piece of 2" NPT black pipe.

Technical line drawing of a mechanical assembly with pipes and a cylindrical component (no text or symbols)

  1. Install a manual shut-off valve as described in "6.8 Gas Pipe Drip Leg and Shut-off Valve" on page 18

Technical line drawing of a pipe fitting assembly with no visible text or symbols

Manual Shut-off Valve

  1. Install a drip leg in "6.8 Gas Pipe Drip Leg and Shut-off Valve" on page 18.
  2. Continue installing pipe to reach the main gas supply connection.
  3. Test all gas pipe connections.

a. All the gas pipe connections should be tested as prescribed in NFPA 54.
b. In multiple unit applications, each unit should be isolated before testing any piping system may exceed the allowable pressure of 14.0" W.C..

NOTICE

Do not fire (operate) the water heater until all connections have been completed and the heat engine is filled with water.

6.10 Gas Pipe Sizing Tables

This information is for reference only. Refer to gas pipe manufacturer specifications for actual delivery capacity. Contact the local gas supplier for actual BTU/ft 3 rating. This data copied from the National Fire Protection Association Article 54 (NFPA 54).

Pipe Sizes and BTU/h Capacity (NATURAL GAS). Use this table for static gas pressure LESS THAN 5" W.C.
Length including fittings (feet)1-1/2" 2" 2-1/2"3" 4"
10 2,090,0004,020,000 6,400,000 11,3000,000 23,100,000
20 1,430,0002,760,000 4,400,000 7,7800,000 15,900,000
30 1,150,0002,220,000 3,530,000 6,2500,000 12,700,000
40 985,0001,900,0005,020,000 5,350,000 10,900,000
50873,0001,680,0002,680,0004,740,0009,660,000
60 791,0001,520,0002,430,000 4,290,000 8,760,000
70728,0001,400,0002,230,0003,950,0008,050,000
80677,0001,300,0002,080,0003,670,0007,490,000
90635,0001,220,0001,950,0003,450,0007,030,000
100600,0001,160,0001,840,0003,260,0006,640,000
125532,0001,020,0001,630,0002,890,0005,890,000
150482,000928,0001,480,0002,610,0005,330,000
175443,000854,0001,360,0002,410,0004,910,000
200412,000794,0001,270,0002,240,0004,560,000
Note: BTU/h capacities are based on specific gravity of 0.6, pressure drop of 0.5" WC
Pipe Sizes and BTU/h Capacity (NATURAL GAS). Use this table for static gas pressure GREATER THAN 5" W.C.
Length including fittings (feet)1-1/4"1-1/2"2"2-1/2"3"4"
103,669,0005,497,00010,588,00016,875,00029,832,00043,678,000
202,522,0003,778,0007,277,00011,598,00020,503,00030,020,000
302,025,0003,034,0005,844,0009,314,00016,465,00024,107,000
401,733,0002,597,0005,001,0007,971,00014,092,00020,632,000
501,536,0002,302,0004,433,0007,065,00012,489,00018,286,000
601,392,0002,085,0004,016,0006,401,00011,316,00016,569,000
701,280,0001,919,0003,695,0005,889,00010,411,00015,243,000
801,191,0001,785,0003,437,0005,479,0009,685,00014,181,000
901,118,0001,675,0003,225,0005,140,0009,087,00013,305,000
1001,056,0001,582,0003,046,0004,856,0008,584,00012,568,000
125936,0001,402,0002,700,0004,303,0007,608,00011,139,000
150848,0001,270,0002,446,0003,899,0006,893,00010,093,000
175780,0001,169,0002,251,0003,587,0006,342,0009,285,000
200726,0001,087,0002,094,0003,337,0005,900,0008,638,000
Note: BTU/h capacities are based are based on specific gravity of 0.6, pressure drop of 3.0" WC
Pipe sizes and BTU/h capacity (PROPANE). Use this table for static gas pressure GREATER THAN 5" W.C.
Length including fittings (feet)1-1/4" 1-1/2"2" 2-1/2" 3" 4"
10 2,350,000 3,520,000 6,790,000 10,800,000 19,100,000 39,000,000
20 1,620,000 2,420,000 4,660,000 7,4300,000 13,100,000 26,800,000
30 1,300,000 1,940,000 3,750,000 5,970,00010,600,00021,500,000
401,110,0001,660,0003,210,0005,110,0009,030,00018,400,000
50 985,0001,480,000 2,840,000 4,530,000 8,000,00016,300,000
60892,0001,340,0002,570,0004,100,0007,250,00014,800,000
80821,0001,230,0002,370,0003,770,0006,670,00013,600,000
100763,0001,140,0002,200,0003,510,0006,210,00012,700,000
125716,0001,070,0002,070,0003,290,0005,820,00011,900,000
150677,0001,010,0001,950,0003,110,0005,500,00011,200,000
175600,000899,0001,730,0002,760,0004,880,0009,950,000
200543,000814,0001,570,0002,500,0004,420,0009,010,000
Note: The line BTU/h capacities are based on specific gravity of 1.5, pressure drop of 0.5" WC.

7. Air Intake Inlet and Exhaust Gas Outlet Pipe Connections

! DANGER

Improper venting of the water heater will result in excessive levels of carbon monoxide, which can lead to severe personal injury or death. This water heater must be vented in accordance with the "Venting of Equipment" section of the latest edition of the ANSI Z223.1 / NFPA 54 (Natural Fuel Gas Code) in the USA, or in Canada refer to the "Venting Systems and Air Supply for Appliances" section in the latest version of CAN/CGA B149.1 (Natural Gas and Propane Installation Code), and all applicable local building codes. Vent installation should be performed only by a licensed professional.

WARNING

Intellihot iQ2001 Gen II - WARNING - 1

BREATHING HAZARD CARBON MONOXIDE GAS

  • Do not operate flood damaged water heaters.
    • Install venting system according to the required codes and material manufacturers specifications.
  • Do not obstruct fresh air intakes or exhaust outlets. Adequately support all vent system piping.
  • Do not place vapor emitting products near water heater or air intake.
  • Place working carbon monoxide detectors outside each sleeping area.
  • Do not operate the water heater before properly installing the exhaust outlet.
  • Visually inspect the vent system and eliminate any possible area where condensation could create a blockage of intake or exhaust air.

Breathing concentrated levels of carbon monoxide, even for a short period of time, will cause brain damage and can even lead to death.

Note: This water heater falls into the Category IV appliance.

7.1 Quick Reference Installation Guide

  1. Select the desired type of venting system: Two Pipe Vent System (Direct) or Single Pipe Vent System (Power).
    "7.3 Two Pipe Vent System (Direct Vent)" on page 24.
    "7.4 Single Pipe Venting System (Power Vent)" on page 26.
  2. Select the desired termination of the air intake inlet and exhaust gas outlet pipe; outside wall or roof.
    "7.3.3 Side Wall Air Intake Inlet and Exhaust Gas Outlet Pipe Termination" on page 25.
    "7.3.4 Roof Air Intake Inlet and Exhaust Gas Outlet Pipe Termination" on page 25.

  3. Determine the straight line distance and the number of elbows required to route the air intake inlet and exhaust gas outlet pipes to their termination point.
    "7.6 Intake Air Inlet and Exhaust Gas Outlet Pipe Diameter and Length" on page 27.

  4. Determine the diameter of pipe required to properly bring in intake air and vent exhaust gas.
    "7.6 Intake Air Inlet and Exhaust Gas Outlet Pipe Diameter and Length" on page 27.
  5. Verify the location of the air intake inlet and exhaust gas outlet terminations are within state and local codes.
    "7.7 Venting Clearance Specifications" on page 28.
  6. Select an approved material for the air intake inlet piping.
    "7.8 Exhaust Gas Outlet Pipe Materials" on page 29.
  7. Select an approved material for the exhaust gas outlet piping. "7.9 Air Intake Inlet Pipe Vent Materials" on page 30.

7.2 Typical Single Unit Air Intake Inlet and Exhaust Gas Outlet Pipe Installation

  1. Select one of the two venting configurations: two pipes (direct vent) configuration or with one pipe (power vent) configuration.

Exhaust Air Intake

  1. Select the desired termination location and make sure each pipe terminates within all local and state codes.
  2. Select the desired material for the air intake inlet and exhaust gas outlet pipes.

CAUTION

This water heater has a factory preset control to limit the exhaust gas temperature to 149°F (65°C) when the PVC is selected in the "Flue Type" programming section. As a result, the water heater can be vented with Schedule 40 PVC. If the incoming (or recirculation return) water temperature does not exceed 150°F (66°C), the exhaust gas temperature will not exceed 149°F (65°C).

WARNING

When the unit is set for CPVC (polypropylene pipe), flue temperatures can reach 190°F (88°C). PVC pipe will melt at temperatures above 149°F (65°C) and could therefore result in a fire. Make sure the setting and the type of material being used for the flue are compatible.

For this application use Schedule 80 CPVC or Approved Polypropylene in the USA or Type BH Special Gas Vent Class IIB (CPCV) or Class IC (Polypropylene) that conforms to ULC-S636 in Canada.

Note: If PVC or CPVC pipe is being used, the included polypropylene-to-PVC adapters must be installed.

Technical line drawing of two cylindrical mechanical components with clamps, no text or symbols present

SAFETY INSTRUCTIONS

On multiple unit installations, the air intake inlet and exhaust gas outlet piping from each water heater must be connected into the properly-sized common piping. Use the table in "7.6 Intake Air Inlet and Exhaust Gas Outlet Pipe Diameter and Length" on page 27 to determine the diameter of the common connecting piping between each individual water heater.

  1. Determine the length and corresponding diameter for the air inlet pipe and route the pipe to the desired termination location.

a. For termination of the pipe to the outside, continue installing the required pipe to a suitable outside location. Glue all connections, making sure the joints are sealed airtight.

b. Install suitable pipe support hangers every 4 to 5 feet, or as local building codes require.

IH-39

c. To configure the unit for power vent, insert a 3' section of 8" pipe.

  1. Determine the length and corresponding diameter for the exhaust gas outlet pipe and route it to a suitable outside location.
    a. Glue all connections, making sure the joints are sealed airtight.
    b. Install all horizontal exhaust gas outlet piping with a minimum 2 degree (1/4" per foot) slope back toward the water heater. This allows any condensate that accumulates in the exhaust gas outlet pipe to properly drain back into the unit.
    c. Install suitable pipe support hangers every 4 to 5 feet, or as local building codes require.

SAFETY INSTRUCTIONS

Do not connect any other appliance vents to the water heater inlet or outlet pipes.

  1. If multiple units are installed, make sure the diameter of the connecting exhaust gas outlet pipe is properly sized for the number of units being installed.

7.3 Two Pipe Vent System (Direct Vent)

7.3.1 Single Unit Configurations

The water heater can be directly vented without any modification using a 8 inch diameter pipe.

The following diagrams represent some typical direct venting configurations and are included to assist in designing the vent system. Possible configurations are not limited to the following diagrams.

MAKE UP AIR MAKE UP AIR MAKE UP AIR

7.3.2 Multiple Units Configurations

When more than one unit is installed, refer to "7.6 Intake Air Inlet and Exhaust Gas Outlet Pipe Diameter and Length" on page 27.

Connecting multiple units together requires proper sizing of the air intake inlet and exhaust gas outlet pipes. Up to two (iQ3001) or three (iQ2001) water heaters can be connected (cascading) together. Units which share a common vent must be connected together in a cascading configuration, as described in "13. Connecting Multiple Units" on page 53"13. Connecting Multiple Units" on page 53.

The following diagrams represent some typical direct venting configurations and are included to assist in designing the vent system. Possible configurations are not limited to the following diagrams.

MAKE UP AIR MAKE UP AIR MAKE UP AIR

7.3.3 Side Wall Air Intake Inlet and Exhaust Gas Outlet Pipe Termination

  1. Terminate the air intake inlet pipe with a 90° elbow (angled down). Use a flange and PVC screen (not supplied).
  2. Terminate the exhaust gas outlet pipe on the exterior wall at least 12" above ground and at least 18" away from the air intake inlet pipe, or as required by local building codes. In areas of high snow fall, protect the vent terminations from blockage. Use a flange and PVC guard.

18" - 36" or over 72" Exhaust Intake Air IQ-020

Single unit.

See Note A Exhaust Intake Air IQ-020a

Multiple units.

Note A: The distance between any exhaust gas outlet and air intake inlet pipe should be between 18 and 36 inches apart. If this minimum specification cannot be met, the air intake inlet and exhaust gas outlet pipes should be 72 inches apart or more.

  1. To avoid moisture and frost build-up to openings on adjacent homes, use 45° elbows, 90° elbows, or tees for the vent termination to direct the exhaust gas fumes away from the building.

7.3.4 Roof Air Intake Inlet and Exhaust Gas Outlet Pipe Termination

Venting the unit through the roof is also an option. With this installation method, the terminations must extend at least 12" over maximum potential snow levels, or as required by local building codes. In areas of high snow fall, protect the vent terminations from blockage.

Terminate the air intake inlet pipe with a 90° elbow (angled down). A suitable roof flashing and vent cap (not supplied) should be installed.

12" USA or 18" Canada over maximum snow level or as required by local code 3' Minimum 12" Minimum 12" USA or 18" Canada over maximum snow level or as required by local code Exhaust Intake Air

Single unit.
Exhaust See Note A Intake Air

Multiple units.

Note A: The distance between any exhaust gas outlet and air intake inlet pipe should be between 18 and 36 inches apart. If this minimum specification cannot be met, the air intake inlet and exhaust gas outlet pipes should be 72 inches apart or more.

7.4 Single Pipe Venting System (Power Vent)

7.4.1 Single Unit

The following illustrations represent some typical power venting configurations and are included to assist in designing the vent system. Possible configurations are not limited to these designs.

MAKE UP AIR MAKE UP AIR MAKE UP AIR MAKE UP AIR MAKE UP AIR MAKE UP AIR MAKE UP AIR MAKE UP AIR MAKE UP AIR MAKE UP AIR

7.4.2 Multiple Units

When installing multiple units, refer to "7.6 Intake Air Inlet and Exhaust Gas Outlet Pipe Diameter and Length" on page 27.

Connecting multiple units together requires proper sizing of the air intake inlet and exhaust gas outlet pipes. Up to two (iQ3001) or three (iQ2001) water heaters can be connected (cascading) together. Units which share a common vent must be connected together in a cascading configuration, as described in "13. Connecting Multiple Units" on page 53"13. Connecting Multiple Units" on page 53.

MAKE UP AIR MAKE UP AIR MAKE UP AIR MAKE UP AIR MAKE UP AIR MAKE UP AIR DECOMMISSIONED AIR INTAKE AND EXHAUST

7.5 Combustion Air Requirements

When using the single exhaust gas outlet pipe or power vent method, the following table outlines the required opening sizes for the combustion and ventilation air coming into the room and the required CFM requirements per water heater:

SAFETY INSTRUCTIONS

Do not operate the unit in an area that will draw in outside air contaminated with high levels of dust, sawdust, aerosols such as paint, or other airborne contaminants.

If necessary, purchase and install appropriate air screens and follow a regular cleaning program to ensure an adequate supply of clean, outside combustion air.

Required Combustion & Ventilation Air Opening Sizes (sq. in) Per Heater Per Boiler Room:
Model InputAir TypeRequired CFMAir is drawn directly from outside into the mechanical roomAir is drawn from another interior space inside the building
through two openings*, direct or verticalthrough one opening**through two horizontal ducts
iQ2001, Gen II 1,999,999Combustion Air360 5006661,000 2000
Ventilation Air360 500 1,0002000
iQ3001, Gen II 3001,000Combustion Air540 75010001,500 3001
Ventilation Air540 750 1,5003001
*Where two openings are used, one must be within 12 inches of the floor and the other opening must be within 12 inches of the ceiling of the mechanical room.**Where one opening is required, it must be located within 12 inches of the ceiling.

7.6 Intake Air Inlet and Exhaust Gas Outlet Pipe Diameter and Length

The iQ2001 and iQ3001 come factory installed with 8 inch polypropylene (PP) venting. The following chart outlines the maximum length of venting allowable for each model.

A vent system's length is calculated by adding the length of all straight runs used (both horizontal and vertical) and then adding the equivalent lengths of each turn (90° or 45° elbow) used in the system.

SAFETY INSTRUCTIONS

A vent system's length must not exceed the maximum length outlined in the chart below.

Maximum Pipe Length in Feet
Number of UnitsVenting Type
8" Diameter10" Diameter12" Diameter
iQ2001iQ3001iQ2001iQ3001iQ2001iQ3001
11 pipe - PV15570460220500220
2 pipe - DV7535230110250110
21 pipe - PV4013060315150
2 pipe - DV20653015575
31 pipe - PV6015070
2 pipe - DV307535
PV = Power VentDV = Direct VentNote: Reduce the maximum equivalent length above by 5 feet per 90° elbow used and by 2 feet per 45° elbow used. Do not exceed the above set limits.

7.7 Venting Clearance Specifications

G D E B Operable Fixed Closed V A Inside Corner Detail A J H I C Fixed Closed Operable V F B O M V K Gas Meter/Regulator Air Inside Inlet Vent Terminal Area Where Terminal is Not Permitted IQ-010

Venting Clearance Specifications
Item DescriptionClearance Distance
USA 1 Canada 2
A Clearances above grade, veranda, porch, deck, or balcony 1 foot 1 foot
B Clearances to window or door that may be opened 1 foot** 3 feet
C Clearances to permanently closed window **
D Vertical clearance to a ventilated soffit, eves, or overhang **
E Clearances to unventilated soffit, eves, or overhang **
F Clearances to outside corner **
G Clearances to inside corner **
HClearances to each side of centerline extended from meter/regulator*3 feet within a height 15 feet above meter/regulator assembly
IClearances to gas meter regulator vent outlet*3 feet
JClearances to non-mechanical air supply inlet or combustion air inlet to any other appliance1 foot**3 feet
KClearances to mechanical air supply inlet3 feet above if within 10 feet horizontally6 feet
LClearances to above paved sidewalk or paved driveway on public property*7 feet
MClearances under veranda, porch, deck, or balcony*1 foot
*Per local/gas supplier codes. Use clearances in accordance with local building codes and local gas supplier.** For single vent pipe/direct 4 feet (1.2 m) below or to the side of opening and 1 foot above opening.1 In accordance with Z223.12 In accordance with CSA B149.1

Note: The vent for this appliance shall not terminate;
Over public walkways; or
Near soffit vents or crawl space vents or other areas where condensate or vapor could create a nuisance or hazard or cause property damage; or
Where condensate vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other equipment.

7.8 Exhaust Gas Outlet Pipe Materials

SAFETY INSTRUCTIONS

For Canadian installations, plastic exhaust gas outlet piping must comply with CAN/CGA B149.1 and be certified to the Standard For Type BH Gas Venting Systems, ULC-S636. Components of this listed system must not be interchanged with other vent systems or unlisted pipes or fittings. All plastic components and specified primers and glues must be from a single system manufacturer and must not be intermixed with another system manufacturer's products.

All units come factory installed with 8 inch polypropylene (PP) venting. A polypropylene to PVC adapter is included with each unit to enable the use of PVC exhaust gas outlet pipe. The maximum allowable venting distances are the same regardless of vent material selected.

The materials listed in the tables below outline the acceptable exhaust gas outlet pipe materials:

United States Exhaust Gas Outlet Pipe Standards
Material Description*
Exhaust Gas Outlet PipePVC Schedule 40 (ASTM D1785)
CPVC Schedule 40, 80
Approved Polypropylene
AL29-4C Stainless Steel
Canadian Exhaust Gas Outlet Pipe Standards
Material Description (approved to ULC-S636)**
Exhaust Gas Outlet PipeType BH Special Gas Vent Class IIA (PVC)
Type BH Special Gas Vent Class IIB (CPVC)
Type BH Special Gas Vent Class IIC (Polypropylene)
Type BH Special Gas Vent Class I (AL29-4C Stainless Steel)
*Note: Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel (polyphenylsulfone) in nonmetallic venting systems is prohibited. Covering non-metallic vent pipe and fittings with thermal insulation is prohibited.**Note: The components (pipe, fittings, primers, and glues) must be from a single manufacturer; do not interchange. Follow the vent manufacturer's certified instructions.

SAFETY INSTRUCTIONS

Do not use cellular foam core pipe to vent exhaust gases.

This water heater has a built-in exhaust gas outlet temperature control that limits the exhaust gas temperature to a maximum of 149° F ( 65° C) for PVC pipe. In commercial applications which require higher water temperatures, exhaust gas temperature can reach 190° F ( 88° C) and require materials such as polypropylene (PP), stainless steel (SS), or CPVC.

If the temperature approaches the upper limit, the burner will turn off automatically to protect the vent pipe. Once the exhaust gas temperature has dropped to a normal operating level, the unit will automatically restart.

If the inlet/return water temperature will exceed 150° F ( 66° C), do not use PVC pipe. Follow the display prompts to set the maximum water temperature for the exhaust gas outlet pipe material being used.

120°F PVC PP/SS/CPVC Are you sure you would like to change exhaust material? PVC pipe will lose integrity at temps above 149°F. Pipe setting and material must be compatible. OFF ON YES NO UNIT SET FOR COMMON EXHAUST NATURAL GAS

120°F PVC PP | SS | CPVC Are you sure you would like to change exhaust material? In this setting exhaust temp can reach 190 °F. Ensure suitable vent materials are used. YES NO UNIT SET FOR COMMON EXHAUST NATURAL GAS

7.9 Air Intake Inlet Pipe Vent Materials

The air intake inlet pipe can be of any plastic or metal vent material available. ABS, PVC, polypropylene, galvanized steel, and/or flexible corrugated ducting are all examples. When using a corrugated material, ensure there is no inadvertent crimping or blockage to the air intake inlet pipe.

Refer to the table below for a list of approved materials.

United States Vent Pipe Standards
Material Description
Vent PipePVC Schedule 40
CPVC Schedule 80
Approved Polypropylene
Canadian Vent Pipe Standards
Material Description
Vent PipeType BH Special Gas Vent Class IIA (PVC)
Type BH Special Gas Vent Class IIB (CPVC)
Type BH Special Gas Vent Class IIC (Polypropylene)

Note: In addition to these charts, it is recommended to consult the most recent edition of ANSI Z223.1/NFPA 54 or CAN/CGA B149.1, as well as all applicable local codes and regulations when selecting vent pipe materials.

Intellihot iQ2001 Gen II - Recommended Exhaust Gas Outlet Pipe Transitions - 1

Do not direct exhaust gas from opposite directions. Use a 45 degree transition, as shown.

Simple line drawing of a scroll with arrows indicating direction (no text or symbols)

graph TD A["Input Arrow"] --> B["Process Step"] B --> C["Output Arrow"]

Diagram showing a hand holding a device with directional arrows and a prohibition symbol below.

Simple line drawing of a mechanical or fluidic component with directional arrows (no text or symbols)

Do not transition into a reducer or use a t-fitting. Transitions should always be directed into a straight run of pipe.

Simple line drawing of a device with two scroll panels and a prohibition symbol (no text or labels)

Do not use 90 degree transition into a reducer or a straight pipe.

1/4" Rise Per Foot Run Condensate Drain 1/4" Rise Per Foot Run Condensate Drain

Diagram showing a vehicle with a prohibition symbol, indicating no restriction or prohibition.

Do not use reducers in a straight run of pipe.

8. Water Connections

Note: For flow rate changes faster than 10 gpm in one second, a water hammer arrester must be installed to prevent damage to the water heater.

8.1 Quick Reference Installation Instructions

  1. Install the hot water piping.

NOTICE

When tightening any fittings to the connections on the water heater, care should be exercised not to overtighten these joints and damage the unit.

  1. Install the cold water piping.
  2. Make sure the pressure relief valve is installed. If necessary, install a customer supplied relief valve.
  3. Install a condensate drain line.
  4. After installation has been completed, test the water heater for proper flow and inspect for leaks.
  5. Run the hot water for a few minutes and then clean the inlet water strainer located on the cold water inlet fitting. This strainer must be cleaned periodically to maintain proper water flow.

8.2 Hot Water Connection

Install and connect the hot water lines. Keep the hot water pipes as short as possible to deliver hot water to the fixtures quickly. If an optional hot water storage tank is required, connect the hot water lines to this tank also.

Since each installation is different, it is up to the installer to route the water lines using the most efficient routing. The drawings shown here are only suggestions indicating the items needed for the installation.

CAUTION

To prevent adverse health issues, only materials (pipes, fittings, valves, solder, etc.) that are approved for use in potable water systems should be used.

  1. Connect a short section of 3" copper water line to the water heater's hot water connection.
    a. The incoming flange, flange gasket, and stainless steel flange bolts must be supplied by the installer.
    b. The flange connection uses a 7.5" OD, four-bolt flanged assembly.
    c. The gasket material specs are an EPDM material with a minimum rating of 210° F continuous service or higher.
    d. The flange bolts are a 3/4" diameter stainless steel. Also install stainless steel washers on both sides of the flange.

e. Route the water lines from the water heater to the connection with the building's water pipes in the most efficient manner.

Technical line drawing of a mechanical assembly with no visible text or symbols

WARNING

To prevent serious personal injury, do not install any shut-off device between the water heater and the pressure relief valve. This valve is designed to release abnormally high pressure within the water heater in the event of a system problem.

  1. If not factory installed, install a 1" 150 psi maximum pressure relief valve, as required by your local code into the port on the outlet piping of the unit.

Technical line drawing of a mechanical assembly with pipes and housing (no text or symbols)

NOTICE

The pressure relief valve must be rated at 150 psi, the maximum btu/h input of the unit, and comply with all local building codes and standards. Do not install any restrictions or other valves in the pressure relief line.

  1. Install and route a discharge pipe from pressure relief valve to within 6 inches of the floor and directed away from walkways or other appliances.

a. Route the relief valve to within 6 inches of the floor to prevent injury in the event of a discharge.
b. The diameter of the pipe from the relief valve must be equal to the outlet size of the relief valve.
c. Do not use reducers in the outlet piping.
d. Do not install any valves, restrictions, or other blockages in the outlet piping.
e. For multiple unit installations, the outlet piping must not be connected together. Each line must be separately routed to a suitable drain.

Technical line drawing of a mechanical assembly with pipes and housing (no text or symbols)

  1. Following local building codes, install a manual shut-off valve.

Technical line drawing of a mechanical assembly with pipes and a valve (no text or symbols)

  1. Connect the unit to the building's hot water lines. If multiple water heaters are being installed, the diameter of both the main cold water lines and the main hot water lines need to be sized appropriately.
  2. To conserve energy, insulate all hot water piping.

SAFETY INSTRUCTIONS

Do not insulate the pressure relief valve.

  1. With the unit OFF, open a nearby hot water faucet and allow the water to run through the unit until all the air is exhausted from the water lines and from the water heater.
  2. Leak test the water piping. Repair any leaks immediately.

Note: For energy conservation, the hot water pipes should be insulated. Also insulate any recirculation water lines.

8.3 Cold Water Connection

Install and connect the cold water lines.

Note 1: If the incoming water is known to have a high mineral content or "hardness" (see warranty section), treatment is recommended upstream from the water heater.

Note 2: A water inlet stainer must be installed prior to use. This strainer must be inspected and cleaned after initial operation of 3 hours. Subsequently inspect the strainer at least every 3 months to establish a cleaning schedule.

When the water heater is installed in a closed loop recirculation system, and if the cold water supply line has a back flow preventer, then an expansion tank should be installed to allow for water expansion.

CAUTION

To prevent adverse health issues, only materials (pipes, fittings, valves, solder, etc.) that are approved for use in potable water systems should be used.

  1. Connect a short section of 3" copper water line to the water heater's cold water connection.

a. The incoming flange, flange gasket, and stainless steel flange bolts must be supplied by the installer.

b. The flange connection uses a 7.5" OD, four-bolt brass flanged assembly.

c. The gasket material specs are an EPDM material with a minimum rating of 210° F continuous service or higher.

d. The flange bolts are a 3/4" diameter stainless steel. Also install stainless steel washers on both sides of the flange.

e. Route the water lines from the water source to the water heater connection in the most efficient manner.

Technical line drawing of a mechanical assembly with mounting flanges and housing (no text or symbols)

  1. Following local building codes, install a manual shut-off valve.

Technical line drawing of a mechanical device with pipes and housing (no text or symbols)

  1. Connect the unit to the building's cold water lines. If multiple water heaters are being installed, the diameter of the main cold water line needs to be sized appropriately.

Note: Isolation valve kits can be used if incoming water treatment is anticipated (such as a water softener) due to hardness levels or heavy usage of the unit.

  1. With the unit OFF, open a nearby cold water faucet and allow the water to run through the unit until all the air is exhausted from the water lines and from the water heater.

  2. Leak test the water lines. Repair any leaks immediately.

8.4 Condensate Drain Line

Due to its efficient design, the water heater produces condensate (water) as a normal by-product of heating the water.

This condensate is acidic, with a pH level between 3 and 4. Local building codes may require an in-line neutralizer to be installed (not included) to treat this water.

The maximum condensate flow rate is 21.6 GPH.

  1. Install a 3/4" flexible hose to the hose connection on the water heater.

a. If a floor drain is used to remove the discharge, route the drain hose over or into the drain.

b. Long drain lines should contain a union to facilitate servicing the unit or cleaning the drain line.

Technical line drawing of a mechanical device with internal components and a circular component at the bottom (no text or symbols)

  1. If required, install an in-line neutralizer to treat the acidic condensate. Follow all the installation instructions included with the neutralizer.

Technical line drawing of a mechanical device with mounting base and wiring (no text or symbols)

iB3001 telliBot Condensate Neutralizer

Note: Whenever a condensate neutralizer is required, it is suggested that a iB3001 telliBot Condensate Neutralizer be used. When used in a cascading application, use one telliBot unit per water heater.

1" Min. tallitot

A 1 inch minimum distance is required between the condensate outlet of the water heater and the outlet of the condensation neutralizer, as shown. This minimum distance is also required when using a condensate pump.

  1. If a floor drain is not available, a condensate pump can be used to pump the condensate to the drain.

Technical line drawing of a mechanical device with a power outlet and wiring (no text or symbols)

a. If a condensate pump is being used, the water heater may need to be raised off the floor to accommodate the height of the pump.

b. Route the hose from the condensate pump to a nearby floor drain or drain pipe.

c. The condensate pump must be supported by the floor or other means; it cannot be supported by the connecting pipes.

9. Electrical Power

9.1 Electrical Recommendations

WARNING

To avoid serious injury or even death, follow all applicable local, state, and national regulations, mandates, and building codes for guidelines to install the electrical power supply.

Electrical code requirements are different in the USA and Canada. Refer to and follow the local building codes, the latest edition of the National Electrical Code (NFPA 70) in the USA, or the CGA C22.1 Canadian Electrical Code - Part 1.

For a single iQ2001 water heater, the circuit breakers should be at least 20 amps per circuit. Please follow the local electrical code in determining the appropriate breaker size.

A minimum 30 Amp circuit breaker, per circuit, should be installed for the iQ3001. Please follow the local electrical code in determining the appropriate breaker size.

For multiple units, install an adequately sized breaker. Installing a separate circuit breaker for each unit is required to isolate units during service or repair.

20 (30) Amp Single Circuit Multiple Units

Note: For an electrical wiring schematic, refer to "15.2 Complete Wiring Diagram (all models)" on page 58 for additional information.

NOTICE

The electrical connections for the water heaters are polarity sensitive. Before connecting the water heater to the power source, test the polarity of the electrical circuit.

9.2 Connection Instructions

  1. On single unit installations, make sure the electrical circuit being used is wired with appropriately sized wire (or at least 10 gauge) wire and grounded with an appropriately sized circuit breaker. Please note that the wire size varies based on the breaker size. The electrical power required for the water heater is 120V AC at 60 Hz (multiple circuits).

  2. Remove the four cover screws and open the cover.

DANGER High Voltage.

WARNING

To avoid serious injury or even death from electrical hazards, an additional ON/OFF electrical junction box should be installed near the water heater. This switch will allow power to be removed from the water heater prior to service or in the case of an emergency.

  1. Route a customer-supplied appropriately-sized, wire with ground from an electrical junction box with an ON/OFF switch through the back panel of the water heater. Route the wire through the cabinet to the junction box.
  2. On the opposite side of the block from the factory installed wiring, connect the white wire to the white terminal, the black wire to the black terminal, and the green ground wire to the green terminal (for each circuit).

Diagram of a mechanical or electrical component with multiple connectors and arrows indicating assembly or connection (no text or symbols present)

  1. If multiple units are being installed, install each with a dedicated, appropriately sized circuit breaker. For installing multiple units, refer to "13. Connecting Multiple Units" on page 53 for additional information.

10. Adjusting CO2 Level

10.1 General Information

This procedure is required:

1) only during installation in a high-altitude location over 8,000 feet, or
2) when converting the unit from natural gas to propane.

This procedure should be performed only by a qualified technician.

! DANGER

A concentration of carbon monoxide (CO) as small as 0.04% (400 parts per million) in the air can be fatal. When making High Fire and/or Low Fire adjustments, CO levels must be monitored using a flue gas analyzer and must not exceed 400 ppm of CO at any time during the operation.

Adjusting the “Low Fire screw” or the “High Fire screw” even in small increments can result in a significant increase in CO concentration. To avoid serious injury or death, DO NOT make any adjustments to the gas valve without monitoring the exhaust gases with a functional and calibrated flue gas analyzer.

CO2and CO Standards
Description CORange (%) Max.CO Level (ppm)
Natural Gas
High Fire 9.1% to9.3% < 200 ppm
Low Fire 9.1% to9.3% < 60 ppm
Propane
High Fire 10.1% to10.5% < 200 ppm
Low Fire 10.1% to10.5% < 60 ppm

NOTICE

The values listed in the table are for nominal conditions. Variables such as gas pressure, heating value of the gas, humidity, and temperature of combustion air can impact CO and CO2 values. Changes in these variables can result in different CO and CO2 values on the same water heater.

A qualified service technician must use a calibrated flue gas analyzer to adjust the gas valve to achieve the desired CO₂ and CO values.

Before any adjustments are made, the service technician must confirm the static gas pressure meets these minimum requirements. Natural Gas - 8" W.C. Propane - 11" W.C.

10.2 Adjustment Procedure

  1. Remove the side covers.
  2. Locate the gas valve on each heat engine. There are eight heat engines in iQ2001 and twelve in iQ3001.

Industrial machinery setup with yellow and blue pipes, hoses, and a copper pipe (no visible text or symbols)

Technical line drawing of an electric motor assembly with no visible text or symbols

  1. Remove the plug from the test port on the exhaust manifold. Insert a calibrated flue gas analyzer into the test port.
  2. Follow the display screens.

120 °F

120°F USAGE ANALYSIS FLOW/TEMP SETTINGS LIFE UNIT INFO MORE

120°F TIME/DATE SECURITY COMBUSTION CASCADING iNTouch ADV. SETTINGS

NOTICE

Do NOT change the blower speed settings. This adjustment MUST be performed by factory personnel ONLY. Changing this setting WILL VOID the warranty!

  1. Create a hot water flow of at least 8.0 GPM as shown on the display screen.

120°F LOW FIRE HIGH FIRE COMBUSTION - 420 + UNIT DETAILS Inner Zone: 01 °F Cooled Zone: 131°F Inner Zone: 78 °F New Area: 6.25 mV Field Area: 147 MPU BLOWER SPEED ... RPM LEFT RIGHT

Note: If flow rate is inadequate, a pop-up message will notify to increase the flow.

120°F LOW FIRE HIGH FIRE Flow rate inadequate. Increase flow to the water heater and please wait, or press exit to leave combustion mode. EXIT UNIT DETAILS OFF: 81 °F HWP: 131°F OFF: 78 °F OFF: 1.2 mmH HWP: 147 mmH BLOWER SPEED ... RPM LEFT RIGHT

  1. At at a flow rate of 8.0 GPM, Heat Engine 1 (H1) will start.
  2. Allow three minutes of operation at High Fire.
  3. Record "initial output" in Hire Fire Recorded Values table.

  4. If the CO2 values are within appropriate range, proceed to Step 10, otherwise continue.

a. Use a flat blade screwdriver to turn the High Fire screw clockwise to decrease and counterclockwise to increase the CO2 value.
b. Adjust in 1/4 turn increments.
c. Wait three minutes to stabilize flue gas readings and recheck values.
d. Adjust until values fall with specified range.

HIGH FIRE SCREW

  1. Once the desired values are achieved, record the new High Fire CO 2 “adjusted values” in the table.
CO2and CO Standards
Description CO2Range MaxCO Level
Natural Gas High Fire 9.1%to 9.3% < 200 ppm
Propane High Fire 10.1% to10.5% < 200 ppm
High Fire Recorded Values
Date ____ / ____ / ____
Heat Engine (1)Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (2)Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine 3)Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (4)Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (5)Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (6)Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (7)Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (8)Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (9)Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (10)Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (11)Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (12)Initial Output Adjusted Value
CO2 Value %
Max CO ppm
  1. From the display screen, press Heat Engine 2 (H2) and repeat the High Fire procedure for all heat engines.

  2. Press LOW FIRE on the display screen.

120°F LOW FIRE UNIT DETAILS Inner Temp: 83 °F Outer Temp: 131°F Flue Temp: 76 °F Flue Size: 0.25 GPa Flue Pin: 147 wgs BLower Speed LEFT FRONT

  1. Record "initial output" in Low Fire Recorded Values table.
CO2 and CO Standards
Description CO2 Range Max.CO Level
Natural Gas Low Fire 9.1% to 9.3% < 60 ppm
Propane Low Fire 10.1% to 0.5% < 60 ppm
Low Fire Recorded Values
Date ____ / ____ / ____
Heat Engine (1) Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (2) Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine 3) Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (4) Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (5) Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (6) Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (7) Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (8) Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (9) Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (10)initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (11)Initial Output Adjusted Value
CO2 Value %
Max CO ppm
Heat Engine (12)initial Output Adjusted Value
CO2 Value %
Max CO ppm
  1. Adjust the Low Fire screw while the burner operates at low fire using a 2mm hex wrench. Turn clockwise to increase CO2 and counterclockwise to decrease CO2 .

LOW FIRE SCREW

  1. Once the desired values are achieved, record the new Low Fire CO, "adjusted values" in the table.

  2. From the display screen, press Heat Engine 2 (H2) and repeat the Low Fire procedure for all heat engines.

120°F LOW FIRE HIGH FIRE Please wait... Finishing heat exch. 1 setup. Starting heat exch. 2 setup... BLOWER SPEED ... RPM INT DETAILS Temp: 81 °F Temp: 131°F Temp: 78 °F Temp: 1.2 mW Temp: 147 mW LEFT RIGHT

  1. When all heat engines have been properly adjusted, turn off water flow.

  2. Remove the flue gas analyzer probe and plug the test port.

  3. Press the back button to return to the main screen.

120°F Do you want to exit Combustion Mode? YES NO INT DETAILS 81 °F 131°F 70 °F 6.2 GPM 147 MHTV BLOWER SPEED ... RPM LEFT RIGHT

  1. Check for gas leaks using a leak detector.

  2. Install side panel covers. If converting to propane, proceed to section "11. Natural Gas to Propane Conversion" on page 40.

11. Natural Gas to Propane Conversion

SAFETY

INSTRUCTIONS

A qualified service technician MUST make the required changes to convert the water heater from Natural Gas to Propane.

11.1 General Information

Note: This conversion process also requires the CO2 levels to be adjusted. Refer to “10. Adjusting CO2 Level” on page 36 for instructions.

Before converting the unit for propane, verify the current gas inlet pressure meets the recommended pressure and record it in the space below.

Propane Static Gas Pressure
Parameters Specifications
Minimum Static Gas Pressure 8” W.C. (non-corrugated, black iron)
Recommended Gas Pressure 11” W.C.
Maximum Static Gas Pressure 13” W.C.

Current Static Propane Gas Pressure ____W.C.

Date ____

Note: This conversion process also requires the CO2 levels to be adjusted. Refer to "10. Adjusting CO2 Level" on page 36 for instructions.

11.2 Conversion Procedure

  1. Follow these steps before repositioning the DIP switches.

a. Turn the water heater OFF using the display screen.

≡ 120 °F

b. Place the circuit breaker for the water heater at the main electrical panel in the OFF position. Verify there is no power to the unit(s).

OFF N

c. Locate DIP Switch 1 on each circuit board (located on each engine).

Note: Eight control boards in iQ2001 and twelve control boards in iQ3001.

120°F TO CONVERT TO PROPANE 1. Shut off all hot water. 2. Shut off power. 3. Shut off gas supply. 4. Remove side panels. 5. Locate circuit boards. 6. Locate DIP switch 1 (SW1). 7. Change the position of SW1 on all control boards. 8. Adjust combustion per manual to compete setup. DIP Switch Settings…

d. Move each DIP switch downward into the Propane position.

DIP Switch Settings (Réglages des commutateurs DIP)
SW1 PropaneON ONNatural Gas(Gaz naturel)

e. Reset the circuit breaker to the ON position. Turn the water heater ON using the display screen.

POWER

  1. Follow the display screens to check if the unit is now set to propane.

120 °F

120°F USAGE ANALYSIS FLOW/TEMP SETTINGS LIFE UNIT INFO MORE

120°F TIME/DATE SECURITY COMBUSTION CASCADING iNTouch ADV. SETTINGS

120°F PVC PP/SS/CPVC EXHAUST MATERIAL OFF ON COMMON EXHAUST UNIT SET FOR NATURAL GAS

  1. Refer to section "10. Adjusting CO2 Level" on page 36 in this manual for instructions to adjust CO₂ levels.

12. Operation

12.1 Control Panel
OFF MENU 120 °F CURRENT SET POINT TEMPERATURE ADJUST SLIDER

Main Menu Screen

120°F USAGE ANALYSIS FLOW/TEMP SETTINGS LIFE UNIT INFO MORE

Selecting the Menu button brings up this screen.

Black background with a glowing red hexagon at the center (no text or symbols)

A sleep mode screen will appear after a period of inactivity.

12.2 Turning Water Heater ON and OFF

  1. When power is applied to the water heater or the electrical switches are turned ON, the Main Menu screen will automatically appear.

A MANGER High Voltage.

Intellihot iG2001

  1. To turn the water heater OFF, press and hold the Power button in the upper left of the screen.

≡ 120 °F

  1. Press the Power button to turn the unit ON.

POWER

WARNING

Turning the unit OFF does not disconnect it from the power source. Whenever working around electrical components within the water heater, turn off the power at its source. Touching live electrical components can cause serious injury or death.

12.3 Setting the Time
120°F USAGE ANALYSIS FLOW/TEMP SETTINGS LIFE UNIT INFO MORE

120°F TIME/DATE SECURITY COMBUSTION CASCADING INTouch ADV SETTINGS

145°F DATE > 1 2 0 0 A M hour minute an/pe

145°F 0 7 21 2016 month day year

Press the Up/Down arrows to make adjustments. Press the Back button to return to the main screen.

12.4 Adjusting the Water Temperature

Note: The outlet water temperature is factory preset to 120°F, however these commercial water heaters are capable of heating water to 190°F.

! DANGER

DANGER
Intellihot iQ2001 Gen II - ! DANGER - 1

Hot water temperature over 125°F (52°C) can cause severe burns instantly or death from scalding. Children, the disabled, and the elderly are at the highest risk of being scalded. Do not leave children or the infirm unsupervised. Check temperature of hot water before taking a shower or

bath. To control water temperature to a particular faucet, temperature limiting valves can be installed by your service professional.

All water faucets must be closed before changing the temperature setting. The unit must not be operating.

  1. Firmly press the slider and slide it to the right to increase the temperature or to the left to decrease. Firmly hold the icon until the display reaches the desired temperature.

≡ 120°

Change Temperature? Temperature above 140 °F can cause severe burns. CONFIRM CANCEL

  1. For finer temperature adjustments, use the (+) and (−) icons.

≡ 120 °F - +

  1. Follow any prompts shown on the screen.

12.5 Security

12.5.1 Setting Passcode Protection

It is not necessary to set a passcode for the water heater to function properly. This feature is available to help prevent unauthorized access to the unit.

If a passcode is set, it must be entered prior to accessing the main screen.

120°F USAGE ANALYSIS FLOW/TEMP SETTINGS LIFE UNIT INFO MORE

120°F TIME/DATE SECURITY COMBUSTION CASCADING iT much ADV. SETTINGS

Press ON/OFF and follow the prompts.
120°F OFF ON PASSCODE SET PASSCODE 1 2 3 4 5 6 7 8 9 0 Done 145°F Choose a 2-digit passcode 1 2 3 4 5 6 7 8 9 0 Done 145°F RE-ENTER PASSCODE TO CONFSER 1 2 3 4 5 6 7 8 9 0 Done 120°F RE-ENTER PASSCODE TO CONFSER 1 2 3 NEW PASSCODE HAS BEEN SAVED. 6 9 Done ≡ 120°F

12.5.2 Changing Passcode
< 120°F OFF ON PASSCODE CHANGE PASSCODE < 145°F ENTER CURRENT PASSCODE 1 2 3 4 5 6 7 8 9 ← 0 Done < 145°F ENTER NEW 4-DIVIT PASSCODE 1 2 3 4 5 6 7 8 9 ← 0 Done < 145°F RE-ENTER PASSCODE TO CONFIRM 1 2 3 4 5 6 7 8 9 ← 0 Done < 120°F WRONG PASSCODE TRY AGAIN 1 2 3 4 5 6 7 8 9 ← 0 Done

120°F HE-ENTER PASSCODE TO CON NEW PASSCODE HAS BEEN SAVED. 1 2 3 6 9 Done

≡ 120 °F

12.5.3 Forgot Passcode

If the unit passcode is lost or forgotten, press the "?" icon and call technical support.

145°F ENTER CURRENT PASSLOAD 1 2 3 4 5 6 7 8 9 ← X 0 Done

120°F PASSCODE DIS NOT MATCH PLEASE SET-START 1 2 3 4 5 6 7 8 9 Done

150°F Technical Support: 1-877-835-1705 support@intellihot.com Model Number: iQ3001 Serial Number: 080818iQ30124 Please have the following information ready: Date installed, location, application, and error code (if any)

12.6 iNTouch

If equipped, the iNTouch icon will be active.

120°F TIME/DATE SECURITY COMBUSTION CASCADING iNTouch ADV. SETTINGS

120°F iN Touch N/A Manifold Temp 120°F Set by Display Louvre Power: OFF Remote Enabled: OFF Louvre Feedback: OFF Pump Relay: OFF Runtime Relay: OFF Alarm Relay: OFF

12.7 Life Screen

These screens provide a visual indication of the remaining life of various components.

Note: Parts can be ordered by contacting technical support.

120°F USAGE ANALYSIS FLOW/TEMP SETTINGS LIFE UNIT INFO MORE

120°F All serviceable parts okay – No service required. UNIT OVERVIEW WATER VALVE ELOWER ELECTROPE GAS VALVE O-RINGS WATER RAMP

120°F All serviceable parts okay – No service required. HEAT EXCH. 1 WATER VALVE LOWER ELECTRODE SAS VALVE ORINGS 100% 50% LEFT RIGHT

Press the (+) button to show the details of the various heat engines.

120°F Service recommended. UNIT OVERVIEW BLONER H6 H9 H2 H1 ELECTROCK GAO VALVE WATER VALVE O-RINGS WATER PUMP

Service recommended. Press and hold part name to reset. HEAT EXCH. 1 | Component | Value (A) | Value (B) | |---|---|---| | WATER VALVE | 100 | 5 | | ORINGS | 60 | 40 | | BLower | 70 | 30 | | GAS VALVE | 80 | 20 | | ELECTRODE | 90 | 10 | LEAF | 100 | 5 RIGHT 120°F

Service recommended: Order appropriate replacement part as soon as possible. To reset life, press and hold the appropriate bar and follow the prompts.

Service required. UNIT OVERVIEW | Component | Total (kW) | |---|---| | ELECTROSE | 100 | | BLower | 100 | | Gas Valve | 100 | | WATER Valve | 20 | | Overhang | 60 | | WATER PUMP | 100 |

Service required. Press and hold part name to reset. HEAT EXCR. 1 | Component | Value | |---|---| | WATER VALVE | 100K | | ORANGES | 70K | | BLower | 80K | | GAS VALVE | 85K | | ELECTRODE | 95K |

Service required: Take IMMEDIATE action when this screen appears because the part life is critical. To reset life, press and hold the appropriate bar and follow the prompts.

When a part is replaced, the screens will provide replacement part information and a screen to reset the service meter for the part being replaced.

Service required. Press and hold part name to reset: HEAT EXCH. 1 To service the inlet water valve use spare parts kit: SPRO003 CONTINUE CANCEL 120°F 120°F Service required. Press and hold part name to reset: HEAT EXCH. 1 Enter 4-digit Replacement Code Cancel Done 1 2 3 4 5 6 7 8 9 0 Done 120°F Serv…

12.8 Unit Information

This screen provides the model, software version, serial number, and a link to the contact us screen for the water heater.

120°F USAGE ANALYSIS FLOW/TEMP SETTINGS LIFE UNIT INFO MORE 120°F ABOUT YOUR WATER HEATER MODEL: iQ3001 Software: 93€7.201.000 Serial #: 080B18iQ300121 CONTACT US 150°F Technical Support: 1-877-835-1705 support@intellihot.com Model Number: iQ3001 Serial Number: 080B18iQ30124 Please have the followin…

12.9 More Screens
120°F USAGE ANALYSIS FLOW/TEMP SETTINGS LIFE UNIT INFO MORE

12.9.1 Wi-Fi

Intellihot Gen II water heaters are Wi-Fi capable with the factory installed IGT-SPR0085 Wi-Fi module. This feature also allows the units to be monitored and controlled from a mobile device.

120°F Wi-Fi CONTACT ERROR HISTORY telliCARE

120°F Wi-Fi Wi-Fi Connection is not available on this water heater. CONTINUE tellZERO ERROR HISTORY

120°F This water heater has lost connection to the buildings Wi-Fi Network. To setup connection, please press the button below and follow the on screen instructions. BEGIN SETUP

120°F The setup was not complete to allow this unit to be monitored and controlled remotely through the app on your mobile phone. To setup connection, please press the button below and follow the on screen instructions.

120°F Wi-Fi: IGTI-Galesburg Connection: Connected Strength: 73% Last Ping: Two minutes ago FORGET W-FI NETWORK

Status of Wi-Fi connection screens.

Whenever software updates are being made, the following screens will appear.

The software on this water heater is being updated. Engine 1 of 8 is currently being updated. Other engines will continue to operate and provide hot water.

The software on this water heater is being updated. Engine 1 of 12 is currently being updated. Other engines will continue to operate and provide hot water.

120°F Are you sure you would like to continue? This will reset the Wi-Fi Network. YES NO IGTI-Galesburg Connected 73% Two minutes ago TARGET Wi-Fi NETWORK

120°F Clearing WiFi credentials... IGTI-Galesburg Connected 73% Two minutes ago FORGET WiFi NETWORK

120°F Wi-Fi reset successful. IGTI-Galesburg Connected 73% Two minutes ago FORGET Wi-Fi NETWORK

12.9.2 Error History
120°F Wi-Fi CONTACT ERROR HISTORY telliZero

There are several error history screens. One screen provides an overview of the entire unit. Pressing the (+) icon provides more detailed error information.

UNIT ERROR HISTORY No errors

120°F HEAT EXCH. ERROR HISTORY No errors LEFT RIGHT

120°F HEAT EXCH. ERROR HISTORY No errors LEFT RIGHT

Left and Right bank error history screens.

UNIT ERROR HISTORY 10 Dec,2019 1:17 AM H1 Ignition Fault 31 Dec,2018 8:12 AM H8 Blocked Flue Fault

This unit comes equipped with telliCare, the industry's only Wi-Fi predictive maintenance service which allows your Intelihot water heater to be monitored and controlled remotely through an app on your mobile device. PREVIOUS NEXT

HEAT EXCH. ERROR HISTORY 10 Dec, 2019 1:17 AM H10 Blower Speed Fault LEFT RIGHT

STEP 1 Download telliCare from the App Store and create an account. PREVIOUS NEXT

12.9.3 telliCare Service (Subscribe at Startup)

telliCare is a Wi-Fi enabled, prognostics and predictive maintenance service for Gen II water heaters. This service allows water heaters to be monitored and controlled remotely via an app on a mobile device.

On Startup:

Hi!

STEP 2 Add this unit to your account by pressing the "+" in the top right hand corner. The app will ask you to connect to the Wi-Fi broadcasted from this unit (telliCare-AB43). For reference, MAC Address: 12:34:RE:32:05:FF PREVIOUS NEXT

If setup is not complete:

Tap anywhere on the screen to continue.

Congrats on purchasing the most intelligent water heater on the planet!

Oops... setup is not complete for this unit to connect to the tellCare app on your mobile device. Not to worry, this can be completed at a later time.

Warranty To register this unit, please scan the GR Code below using the tellCare app. Once complete, the app will provide a 4-digit code. Enter the code below. 1 2 3 4 5 6 7 8 9 ← 0 Done PREVIOUS FINISHED

If telliCare setup is skipped, register the unit by scanning the QR Code via the App.

Note: Each individual unit must be registered and each unit can only be registered once.

120°F Wi-Fi CONTACT ERROR HISTORY tellicARE

120°F telliCare Service: not subscribed Subscribe Today! Install the telliCare app on your mobile device.

Subscribe to this service by downloading the telliCare app from iTunes App Store and following the prompts on the app.

Two status screens provide the expiration date of the service and if it is on an auto renewal schedule.

120°F telliCare Service: subscribed Expires: 22 NOV.2019

120°F telliCare Service: subscribed Auto Renewal: 22 NOV, 2018

13. Connecting Multiple Units

13.1 General Information

Multiple units can be connected together to supply large demands of hot water.

The water heaters communicate through a cable connection between each water heater. The benefits of connecting the units are:

  • When demand for hot water is low, fewer units will operate.
  • If one unit has an error code, the others will continue to operate.
  • Changing the settings (temperature, time, etc.) on one unit changes settings on all the units.
  • It allows shut down of one unit for maintenance while the others continue to operate.

13.2 Installation Procedure

  1. Connect all the units to a gas supply pipe. Make sure the pipe is properly sized in accordance with the BTU draw and number of units being operated. Refer to "6. Gas Connection" on page 17 for additional information.
  2. Connect all the units to the power supply. Refer to "9. Electrical Power" on page 35 for additional information.

Manual Shut-off Valve Drip Leg Manual Shut-off Valve Drip Leg Main Supply Line Manual Shut-off Valve Drip Leg Manual Shut-off Valve

  1. Install the combustion (fresh) air intake and exhaust outlet pipes. Refer to "7. Air Intake Inlet and Exhaust Gas Outlet Pipe Connections" on page 22 for additional information.
  2. Install and connect the hot water lines. If an optional hot water storage tank is required, connect the hot water lines to this tank. Make sure the water pipe is properly sized in accordance with the number of units being operated.
  3. Install and connect the cold water lines. Make sure the water line is properly sized in accordance with the number of units being operated.
  4. Connect and route the condensate drain lines to a suitable discharge location. Refer to "8. Water Connections" on page 31 for additional information.
  5. Do Not connect communication cables at this time.

  6. Power up all the units and assign a unique number, one through four to each unit. Set the STAGING to ON.

120°F USAGE ANALYSIS FLOW/TEMP SETTINGS LIFE UNIT INFO MORE

120°F TIME/DATE SECURITY COMBUSTION CASCADING iNTouch ADV. SETTINGS

120°F Multi-Unit Setup Select a number to assign this unit - 1 + OFF ON STAGING

Note: Different size floor-standing water heaters (iQ751, iQ1001, iQ1501, iQ2001, or iQ3001) can be connected. When assigning unit numbers, start with the smallest unit and progress to the largest. A maximum of two iQ3001 water heaters or three iQ2001 water can be connected.

WARNING

Before making any adjustments or connections inside the water heater cabinet, make sure the power is disconnected. Unplug the water and/or turn the circuit breaker OFF.

  1. If necessary, press the Power button to turn OFF each water heater in the system and disconnect power from all the units in the system.

  2. Open the side panels and locate the main circuit boards.

Industrial equipment setup with copper pipes, wiring, and electronic components (no visible text or symbols)

iQ2001 with Eight Circuit Boards. iQ3001 with Twelve Circuit Boards.

  1. Connect the included communication cable from an open jack on the circuit board in one unit to an open jack in the next unit. Repeat this step as required by the number of water heaters being connected.
  2. On the first water heater, locate DIP Switch 3 on circuit board 1. Position the switch in the ON position (left) as shown in the table below.
  3. Position all other switches on the circuit boards in the unit to the OFF position (right).
  4. On any water heater unit between the first and last unit, the position of all DIP SW3 switches should be in the OFF position (right).
  5. On the last water heater, locate DIP Switch 3 as shown in the table below.
  6. Once the communication cables are routed and connected and the DIP switches are correctly positioned, close and lock the front door.
  7. Reconnect the power and turn the water heater ON. The water heaters, should now be ready to communicate with each other and operate as a single system.

Note: Whenever a change is made to any one water heater, all the other units in the system will be automatically updated to the new settings.

13.2.1 telliCare for Multiple Units

If cascading multiple units, the Wi-Fi module on all units besides "Unit 1" in the sequence need to be disconnected to make room for cascade communication cables. Remove the attached cable at each end from the referenced jacks and set aside.

Close-up of a green printed circuit board with electronic components and wiring, no visible text or symbols

Cascade Termination DIP Switch 3 Setting (Single Unit)
Board Number
Model 1 23 4 5 6 7 89 10 11 12
iQ2001ONOFFOFFOFFOFFOFFOFFOFFONN/A
iQ3001ONOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFON
Cascade Termination DIP Switch 3 Setting (Multiple Units)
Board Number
Model 123456789101112
iQ2001Unit 1ONOFFOFFOFFOFFOFFOFFOFFOFFN/A
Unit 2OFFOFFOFFOFFOFFOFFOFFOFFOFF
Unit 3OFFOFFOFFOFFOFFOFFOFFOFFON
iQ3001Unit 1ONOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFF
Unit 2OFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFON

14. Maintenance

14.1 Air Filter

14.1.1 Inspection

Check the filter every six months for dirt and dust build-up. Clean and re-oil the filter annually. If the filter is dirty, follow the cleaning procedure.

Note: The air filter is manufactured by K&N. Contact K&N at 800-858-3333 or online at www.knfilters.com for the necessary supplies to clean the filter.

  1. Loosen the band clamp and remove the air filter.

Close-up of a mechanical device with purple filter array and white frame, showing internal components and wiring (no text or symbols visible)

  1. Inspect the inside of the filter for dirt and dust build-up. Clean the filter, if needed.
  2. After inspection and/or cleaning, replace the air filter and snugly tighten the band clamp.

14.1.2 Cleaning Procedure

  1. Liberally spray K&N Air Filter Cleaner and Degreaser (99-0606) onto both sides of filter and allow to soak for 10 minutes to loosen the dirt. Do not allow cleaner to dry on air filter.

NOTICE

K&N Air Filter Cleaner is the only cleaner formulated to safely clean K&N air filters with cotton media. The use of any other cleaning solution could damage the cotton material.

  1. Rinse the air filter with cool low-pressure water applied from the outside inward in order to flush the dirt out of the filter. Continue to rinse the filter until all traces of cleaner are gone. It may be necessary to repeat Steps 1 and 2.
  2. After rinsing, gently shake off the excess water and air dry the filter.

NOTICE

Do not use compressed air to dry the filter. Do not apply oil to the filter until it is completely dry.

  1. Spray K&N Aerosol Air Filter Oil (99-0504) evenly along the crown of each pleat holding nozzle about 3" away. Allow oil to wick for approximately 20 minutes. Touch up any light areas on either side of the filter until there is a uniform red color at all areas.

14.2 Maintenance-Free Circulation Pumps

The circulation pumps are maintenance-free and therefore does not require any servicing. The only adjustment is the speed setting, which must be set to Speed 3 (III).

Industrial machine setup with pipes and a red motor, no visible text or symbols

14.3 Heat Engine Locations

Use the following diagrams to identify the location of the heat engines.

120°F UNIT OVERVIEW 755 MBTU FIRING RATE 77 °F FLUPE TEMP 137 °F WATER OUT 73 °F WATER IN 25.1 GPM FLOW RATE

120°F HEAT EXCH.1 147 MBTU FIRING RATE 78 °F FLUE TEMP 131 °F WATER OUT 81 °F WATER IN 6.2 GPM FLOW RATE LEFT RIGHT

iQ2001 Left status.

120°F HEAT EXCH. 5 147 MBTU FIRING RATE 78 °F FLUE TEMP 131 °F WATER OUT 81 °F WATER IN 6 . 2 GPM FLOW RATE LEFT RIGHT

iQ2001 Right status.

120°F HEAT EXCH. 7 147 MBTU FIRING RATE 78 °F BLUE TEM 131 °F WATER OUT 81 °F WATER IN 6 . 2 GPM FLOW RATE LEFT RIGHT

iQ3001 Right status.

120°F HEAT EXCH. 1 147 MBTU FIRING RATE 78 °F FLUE TEMP 131 °F WATER OUT 81 °F WATER IN 6 . 2 GPM FLOW RATE LEFT RIGHT

iQ3001 Left status.

15. Wiring Diagrams and Troubleshooting

15.1 Operational Flow Chart

graph TD A["Wait"] --> B{Is Flow On} B -->|Yes| C["Energize Ignition Module"] B -->|No| D{Is Temp. Within Limits} D -->|Yes| E["De-energize Ignition Module"] D -->|No| F["Maintain Temperature Module"] C --> G{Successful Ignition} G -->|Yes| H["Set Modulation"] G -->|No| I["Error Handler"] H --> J{Sa…

IH-56

15.2 Complete Wiring Diagram (all models)
POWER DISTRIBUION BLOCK BN-GROUND WT-NEUTRAL BK-LINE BN-LINE BL-NEUTRAL GN/YL-GROUND BL-NEUTRAL BN-LINE GN/YL-GROUND BD WT BL BK 194°F THERMAL FUSE BN 390°F THERMAL FUSE BN 390°F THERMAL FUSE GN/YL-GROUND DIRECT SPARK IGNITION SWEER TRANSFORMER ON NG LP OFF RED LED (BURNER ON) GREEN LED (POWER) FUSE…

15.3 Control Board Wiring Diagram (iQ2001)
graph TD A["CONTROL MODULE 1"] --> B["COMUNICATION CABLE"] B --> C["DISPLAY"] D["PUMP"] --> E["FUSE"] E --> F["GN'YL RN BL"] F --> G["LOAD BK WT GN LINE"] G --> H["POWER SWITCH (LOWER)"] H --> I["LINE"] I --> J["CONTROL MODULE 2"] K["CONTROL MODULE 5"] --> L["COMMUNICATION CABLE"] L --> M["CONJECUTR…

15.4 Control Board Wiring Diagram (iQ3001)
graph TD A["CONTROL MODULE 1"] --> B["DISPLAY"] C["CONTROL MODULE 2"] --> D["COMMUNICATION CABLE CABLE"] E["CONTROL MODULE 3"] --> F["COMMUNICATION CABLE CABLE"] G["PUMP"] --> H["GN-YL FUSE"] I["CONTROL MODULE 4"] --> J["COMMUNICATION CABLE"] K["CONTROL MODULE 5"] --> L["COMMUNICATION CABLE"] M["CON…

15.5 Troubleshooting Guide

Description Possible CauseRemedy
BlowerSpeed FaultIntellihot iQ2001 Gen II - Troubleshooting Guide - 1Blower noisy / impeller jammed.Disconnected signal wire.Wiring faulty.Inspect blower / impeller. Clean and remove any obstructions.Check PWN signal. Check for loose wires / pins, and repair.If the problem persists, turn control panel OFF, shut gas valve, disconnect power from unit, and contact an authorized service technician.
IgniterIgnition FailureIntellihot iQ2001 Gen II - Troubleshooting Guide - 2Water over-heat switch tripped.Faulty DSI, faulty igniter wire, faulty ignition connection, faulty PCB, bad igniter.Low gas pressure.Wiring faulty.Check pump, check cross-over solenoid. Electrical noise (DSI).Replace part.Adjust gas pressure at regulator, check / increase size of gas line, check for gas line blockage.If the problem persists, turn control panel OFF, shut gas valve, disconnect power from unit, and contact an authorized service technician.
Open SensorsInlet / Outlet SensorsIntellihot iQ2001 Gen II - Troubleshooting Guide - 3Intellihot iQ2001 Gen II - Troubleshooting Guide - 4Unplugged connectors.Faulty sensor wiring.Faulty sensor.Heat engine water outlet temperature sensor.Flue temperature sensor.Inlet water temperature sensor.Faulty controller.Check connectors and ensure they are securely connectedCheck for nicked or broken sensor wiring or connectors. Also check for corroded or wet connectorsMeasure resistance of sensor at connector (18 kΩ at 50°F, 10 kΩ at 77°F, 3 kΩ at 140°F).Replace controller.
Faulty SensorsInlet / Outlet SensorsIntellihot iQ2001 Gen II - Troubleshooting Guide - 5Intellihot iQ2001 Gen II - Troubleshooting Guide - 6Faulty sensor wiring or faulty sensor.Inlet water temperature sensor.Heat engine water outlet temperature sensor.Faulty controller.Check for nicked or broken sensor wiring or connectors. Also check for corroded or wet connectors.Measure resistance of sensor at connector (18 kΩ at 50°F, 10 kΩ at 77°F, 3 kΩ at 140°F).Replace controller
Heat EngineOutlet temperature exceeded set limitIntellihot iQ2001 Gen II - Troubleshooting Guide - 7Flow rate changes excessive.Faulty sensor wiring.Faulty sensor.Faulty controller.Ensure the water flow rate does not change faster than 2 GPM every 5 seconds.Check for nicked or broken sensor wiring or connectors. Also check for corroded or wet connectors.Measure resistance of sensor at connector (18 kΩ at 50°F, 10 kΩ at 77°F, 3 kΩ at 140°F).Replace controller.
FlueTemperature Exceeded Set LimitIntellihot iQ2001 Gen II - Troubleshooting Guide - 8Incorrect vent set up.High inlet temperature.Faulty sensor wiring.Faulty sensor.Faulty controller.If vent pipe material is CPVC or polypropylene, ensure that CPVC is selected in the vent material screen.Ensure inlet temperature is lower than 150°F if vent pipe material is PVC or lower than 190°F if vent pipe material is CPVC or polypropylene.Check for nicked or broken sensor wiring and connectors. Also check for corroded or wet connectors.Measure resistance of sensor at connector (18 kΩ at 50°F, 10 kΩ at 77°F, 3 kΩ at 140°F).Replace controller
Blocked Flue Fault(c).Intellihot iQ2001 Gen II - Troubleshooting Guide - 9Backed up condensate.Wiring loose (switch open).Check exhaust termination. Check exhaust connection at water heater. Install screens to prevent blockage.Check slope of drain. Check for double loops, air locks, or debris in loop.Check wiring.
Flue sensorIntellihot iQ2001 Gen II - Troubleshooting Guide - 10Unplugged connectors.Faulty sensor wiring.Faulty sensor.Flue temperature sensor.Inlet water temperature sensor.Faulty controller.Check connectors and ensure they are securely connectedCheck for nicked or broken sensor wiring or connectors. Also check for corroded or wet connectorsMeasure resistance of sensor at connector (18 kΩ at 50°F, 10 kΩ at 77°F, 3 kΩ at 140°F).Replace controller.
CascadingFaultIntellihot iQ2001 Gen II - Troubleshooting Guide - 11AlertIntellihot iQ2001 Gen II - Troubleshooting Guide - 12Loss of communication between units.Check for broken or nicked communication cable or loose connector.Ensure that the communication cable is not bundled or tied to any high voltage lines.Ensure dip switch (SW3) is ON in first and last units and OFF in all other units.Ensure each unit numbering is unique.
Water ValveIntellihot iQ2001 Gen II - Troubleshooting Guide - 13Faulty sensor wiring.Water valve clogged or damaged.Check for nicked or broken sensor wiring or connectors. Also check for corroded or wet connectors.Replace water valve.
Description Possible Cause Remedy
PumpIntellihot iQ2001 Gen II - Troubleshooting Guide - 14Intellihot iQ2001 Gen II - Troubleshooting Guide - 15Intellihot iQ2001 Gen II - Troubleshooting Guide - 16·Faulty pump wiring.·Pump fuse blown.·Faulty pump.·Faulty controller.·Check for nicked or broken sensor wiring or connectors. Also check for corroded or wet connectors.·Replace fuse (5 Amp)·Replace pump.·Replace controller.
Fuel TypeIntellihot iQ2001 Gen II - Troubleshooting Guide - 17·DIP switches mismatched (SW1) ·Check switches on all boards to make sure they are all set to the same gas type.
SoftwareIntellihot iQ2001 Gen II - Troubleshooting Guide - 18Intellihot iQ2001 Gen II - Troubleshooting Guide - 19·Incorrect settings.·Incompatible settings.·Incorrect software version.·Faulty wiring.·Review and correct settings.·Review and correct settings.·Update software version.·Check for nicked or broken sensor wiring or connectors. Also check for corroded or wet connectors.
Air FilterIntellihot iQ2001 Gen II - Troubleshooting Guide - 20Intellihot iQ2001 Gen II - Troubleshooting Guide - 21Intellihot iQ2001 Gen II - Troubleshooting Guide - 22·Blocked inlet.·Over six months in service·Dirty or damaged filter.·Remove blockage and install screens to prevent future blockage·Remove and inspect filter. Clean or replace as needed.
Manifold SensorsIntellihot iQ2001 Gen II - Troubleshooting Guide - 23Intellihot iQ2001 Gen II - Troubleshooting Guide - 24Intellihot iQ2001 Gen II - Troubleshooting Guide - 25Intellihot iQ2001 Gen II - Troubleshooting Guide - 26Intellihot iQ2001 Gen II - Troubleshooting Guide - 27Intellihot iQ2001 Gen II - Troubleshooting Guide - 28Blocked inlet.Dirty or damaged filter.Unplugged connectors.Faulty sensor wiring.Faulty sensor.Faulty controller..Remove blockage and install screens to prevent future blockage.Remove and inspect filter. Clean or replace as needed.Check connectors and ensure they are securely connectedCheck for nicked or broken sensor wiring or connectors. Also check for corroded or wet connectorsMeasure resistance of sensor at connector (18 kΩ at 50°F, 10 kΩ at 77°F, 3 kΩ at 140°F).Replace controller.
System AlertIntellihot iQ2001 Gen II - Troubleshooting Guide - 29A system alert is present (main menu screen).Malfunction of monitored part or system.Refer to the remedy for indicated part or system.
FaultIntellihot iQ2001 Gen II - Troubleshooting Guide - 30A fault or error is present (main menu screen).Malfunction of monitored part or system.Refer to the remedy for indicated part or system.
Description Possible CauseRemedy
Alert / Error / FaultIntellihot iQ2001 Gen II - Troubleshooting Guide - 31Intellihot iQ2001 Gen II - Troubleshooting Guide - 32Intellihot iQ2001 Gen II - Troubleshooting Guide - 33· An alert, fault, or error is present(active screen).· Malfunction of monitored part or system.· Refer to the remedy for indicated part or system.
AliveIntellihot iQ2001 Gen II - Troubleshooting Guide - 34Intellihot iQ2001 Gen II - Troubleshooting Guide - 35Intellihot iQ2001 Gen II - Troubleshooting Guide - 36Intellihot iQ2001 Gen II - Troubleshooting Guide - 37Intellihot iQ2001 Gen II - Troubleshooting Guide - 38· Shows status of water heater.· Sleep mode.· Sleep mode passcode protected.· Indicates a service problem exists within the monitored parts.· Indicates an alert exists within the monitored systems.· Indicates a fault exists within the monitored parts or system.· Touch display screen to awake.· Touch display screen to awake and enter passcode.· Refer to the remedy for indicated part or system.· Refer to the remedy for indicated part or system.· Refer to the remedy for indicated part or system.

16. Requirements for State of Massachusetts

16.1 Notice Before Installation

This appliance must be installed by a licensed plumber or gas fitter in accordance with the Massachusetts Plumbing and Fuel Gas Code 248 CMR Sections 2.00 and 5.00.

IMPORTANT: In the State of Massachusetts (248 CMR 4.00 & 5.00)

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE DETECTORS.

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery backup is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building, or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision cannot be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS.

Each carbon monoxide detector, as required in accordance with the above provisions, shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3. SIGNAGE.

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".

4. INSPECTION.

The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

17. Warranty

17.1 Warranty

General

This unit is warranted by Intellihot Inc., and covers defects in materials and workmanship, subject to the applicable time periods and terms below. The warranty effective start date begins on the date of commissioning.

This warranty is extended to the original purchaser and any subsequent owner at the original install location, and applies only when properly installed by a licensed contractor and operated in accordance with the instruction manuals. This warranty is limited to repairs or replacement of parts, at Intellihot's option that are proven to be defective under normal use and connected only to potable water systems.

Warranty Period

Commercial Domestic Hot Water (DHW) Warranty: Heat Engine coil - 10 years, Other Parts - 2 years.

Heat Engine Coil

The warranty period for a heat engine coil failure, when installed in a Commercial DHW application is ten (10) years from the effective start date.

All Other Parts and Components

The warranty period for any original parts (excluding the heat engine coil) against failure, is two (2) years from the effective start date. A replacement part will be warranted for the unexpired term of the original warranty. Defective parts submitted may not be returned. No returns will be accepted without prior authorization from Intellihot.

Definition of Potable water

Potable water is defined as drinkable water supplied from utility or well water in compliance with EPA secondary maximum contaminant levels (40 CFR part 143.3) as shown in the table.

Contaminant Level
Aluminum 0.05 to 0.2 mg/l
Chloride 250 mg/l
Color 15 color units
Copper 1.0 mg/l
Corrosivity Non-corrosive
Fluoride 2.0 mg/l
Foaming Agents 0.5 mg/l
Iron 0.3 mg/l
Manganese0.05 mg/l
Odor3 threshold odor number
pH6.5-8.5 mg/l
Silver0.1 mg/l
Sulfate250 mg/l
Total dissolved solids (TDS)500 mg/l
Zinc5 mg/l

Shipping Costs

If a replacement part is supplied under the terms of this warranty, Intellihot will provide ground service delivery for the part free of charge. Any expedited shipping expense will be paid by the customer.

Water Hardness Criteria

This warranty applies only when the water quality and supply meets the parameters outlined in the table below.

To use the table, locate the desired unit setpoint temperature on the left side of the table. Then locate the incoming water pressure across the top. The corresponding value in the table is the maximum allowable hardness in grains per gallon (gpg).

Maximum Allowable Hardness (grains per gallon, gpg)
Unit Setpoint(°F)Incoming Water Pressure (psi)
3040506080100
100-120°81520253030
120-140°51115202730
140-160°4511131820
160-190°3410121517

Not Covered by this Warranty

This warranty does not cover failures or problems due to:

  • Failure to install in accordance with applicable building codes, ordinances, normal plumbing, or electrical trade practices.
  • Improper installation, improper use, improper maintenance, improperly made replacements or repairs, accidents or abuse.

- Sediment deposits, fire, flood, lightning, freezing, and acts of God, or any causes other than defects in materials and workmanship.

- The unit is installed without consideration for an adequate drain to accommodate leaks,

- The unit installed where the leakage could result in damage to the area adjacent to the water heater or to the lower floors of the building.

- Damages due to improper/inadequate water hardness treatment or damages from scale formation due to water hardness.

- Water heater's usage flow rate required a water hammer arrestor, but water hammer arrestor not installed.

- Electrical failures due to Inadequately sized electrical breaker or inadequately sized wire

• Not performing recommended maintenance.

- Not properly electrically grounding the unit or not following the electrical grounding requirements.

This warranty will be void and have no effect if:

  • The unit is modified or altered in any way.
  • Appliance(s) or equipment are attached to the unit that have not been approved by Intellihot Inc.
  • If the unit is used exclusively as a booster heater for a commercial dishwasher, or if the water from a reverse osmosis or deionized process is run directly through the unit.
  • The serial number is altered, defaced, or discarded.

Warranty Limitations

This warranty applies only when the unit is used in the United States or Canada. Except for the limited warranties provided above, Intellihot Inc. disclaims any and all other warranties, including but not limited to warranties of merchantability and fitness for a particular purpose; provided however, that implied warranties of merchantability and fitness for a particular purpose are not disclaimed during the 1-year period from the effective date. Intellihot shall not be liable for indirect, special, incidental, consequential, or other similar damages, including lost profits, arising from or relating to the unit. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

How to Make a Claim

The warranty claim can be submitted online at https://www.intellihot.com/warranty-claim/

or

by calling (877) 835-1705. Proof of purchase in the form of a dated sales receipt or warranty registration should be included with your claim. The product owner should submit the warranty claim directly to Intellihot at the following address:

Intellihot Inc.

Attn: Warranty Claims

2900 W. Main St.

Galesburg, IL 61401

All parts claimed to be defective may be requested to be returned to Intellihot for examination prior to full claim settlement. Please include the following information on your warranty claim:

  • Model number and serial number of the unit.
  • Date of original purchase.
  • Owner's name and address.
  • A description of the problem with the part and unit.

NOTES

18. Product Warranty

18.1 Warranty

To register via the telliCare app, refer to "12.9.3 telliCare Service (Subscribe at Startup)" on page 51.

Warranty Registration Intellihot Inc. 2900 W. Main Street Galesburg, IL 61401

Or fill out the information in the form below and mail to the following address:

Make a copy or cut here to remove page.

Model:

Serial Numbers (up to 12):

Owner Information: Name: ____ Address: ____ City, State, Postal Code: ____ Phone Number: ____

Dealer Information: Sold By: ____ Address: ____ City, State, Postal Code: ____ Phone Number: ____

Geometric diagram of interconnected polygons with no text or symbols

Endless water. Zero waste. TM

Abstract geometric pattern composed of interlocking triangles in shades of purple, orange, and yellow (no text or symbols)

Geometric line drawing of interconnected polygons (no text or symbols)

Intellihot

12-2022

Par1#:IGT-MNL0044

Intellihot iQ2001 Gen II - Intellihot - 1

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Intellihot

Model : iQ2001 Gen II

Category : Water heater