ENTES

MPR-60S-41 - Analyseur réseau ENTES - Free user manual and instructions

Find the device manual for free MPR-60S-41 ENTES in PDF.

📄 53 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice ENTES MPR-60S-41 - page 3
Pick your language and provide your email: we'll send you a specifically translated version.
Type de produit Analyseur de réseau électrique
Marque ENTES
Modèle MPR-60S-41
Dimensions (L x H x P) 96 x 96 x Profondeur (non spécifiée)
Poids 0.75 kg
Alimentation Voir étiquette sur l’appareil (typ. 100-240 V AC)
Consommation < 6 VA
Affichage Écran LCD 3,6 pouces avec rétroéclairage
Entrées de mesure Tension L-N : 1-300 V AC, L-L : 2-500 V AC ; Courant : 0,005-5,5 A
Précision Tension/Courant : 0,5 % ± 2 digit ; Puissance active : 1 % ± 2 digit
Communication RS-485 Modbus RTU (1200-38400 bps)
Sorties relais 2 x NO, 5 A, 1250 VA
Sorties impulsion énergie 2 sorties (active et réactive) jusqu'à 50 mA, 5-30 V DC
Entrées numériques 2 entrées (5-24 V DC, max 30 V DC)
Sortie analogique 0-20 mA ou 4-20 mA (MPR60S-41)
Mémoire interne 1 MB (jusqu'à 15 000 enregistrements de 28 paramètres)
Protection IP40 (face avant), double isolation classe II
Température de fonctionnement -5°C à +50°C
Normes EN 61000-6-2, EN 61000-6-4, EN 61010-1, etc.
Entretien et nettoyage Déconnecter l’alimentation, nettoyer avec un chiffon humide (pas de solvant)
Sécurité Consulter la notice avant installation ; réservé au personnel qualifié
Pièces détachées et réparabilité Contacter le fabricant ou un technicien agréé

Frequently Asked Questions - MPR-60S-41 ENTES

What is the MPR-60S-41 used for?
The MPR-60S-41 is a network analyzer that measures electrical parameters such as voltage, current, power, energy, and harmonics in three-phase systems. It also provides data logging and communication via Modbus RTU.
How do I configure the current transformer (CT) ratio?
Go to Setup > Network > CT and enter the primary current of your CT (1-5000). The display will show the measured current multiplied by this ratio.
How to set the voltage transformer (VT) ratio?
In Setup > Network > VT, enter the ratio (1.0 to 4000.0). For example, if using a 10 kV / 100 V PT, set VT to 100.0 (10 000/100 = 100).
What Modbus functions are supported?
The device supports functions 03H (read holding registers), 06H (write single register), 10H (write multiple registers), 14H (read log data), and 2BH (read device identification).
How to clear logged data?
Go to Info > Log.Rec. and select Clear to erase all parameter logs. For energy logs, go to Info > Eng.Rec. > Clear.
What is the maximum number of devices on the RS-485 bus?
Up to 31 devices can be connected without a repeater. With repeaters, up to 247 devices can be connected.
How to set a password to protect settings?
Go to Setup > Password > Set Psw and enter a 3-digit code. Then activate it. The default master password is 236.
What do the harmonic bars on the display represent?
The bars show the total harmonic distortion (THD) in % for voltage (THD V) or current (THD I) for each phase (L1, L2, L3). Each step equals 10%.
How to connect the device to a PC?
Use an RS-485 to RS-232 or RS-485 to USB converter. Configure the baud rate, parity, and address in Setup > RS-485. Then use MPR-SW software.
What should I do if the display shows a phase sequence error?
If the phase sequence indicator shows a problem, swap any two phase wires (L1-L2, L2-L3, or L1-L3) to correct the rotation.

User questions about MPR-60S-41 ENTES

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Analyseur réseau in PDF format for free! Find your manual MPR-60S-41 - ENTES and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. MPR-60S-41 by ENTES.

USER MANUAL MPR-60S-41 ENTES

ATTENTION : Consult the operating instructions before using the equipment.

If these precautions are not properly observed and carried out, it can cause physical accident or damage to the equipment or the installation.

The manufacturer or the authorized seller is not responsible for the consequences resulting from failure to comply with these precautions.

SAFETY PRECAUTIONS

This equipment has been manufactured and tested and it has left the factory in perfectly safe condition. To preserve this and ensure safe operation of the equipment the user should comply with the instruction which are mentioned in this manual.

Before installing, check that the operating and network voltages are the same!

Before carrying out any work on the equipment, check that it is disconnected from the electrical supply.

If the equipment is no longer completely safe to use, it should be taken out of service and protected against any accidental use.

Operator Safety

Read the following recommendations carefully before installing and operating the equipment.

The equipment described in this manual is designed only to be used by trained personnel.

Maintenance work must be carried out only by qualified, authorised personnel.

Personnel must observe the usual safety procedures for safe operation and during any maintenance work.

Breakdown Precautions

If you suspect that the equipment may no longer be safe (e.g. because of transport or operational damage), it must be taken out of service and protected against any accidental use.

The equipment should be handed over to authorised technicians for checking.

Cleaning Instructions

Disconnect the equipment from the electrical supply and only use a damp cloth to clean the external surfaces. Do not use any abrasive materials or solvents. Do not allow any moisture to reach the connection terminals.

Standards which are applied to the device:

EN 61000-6-2, EN 61000-6-4, EN 55016-2-1, EN 55016-2-3, EN 55011, EN 61000-3-2, EN 61000-3-3, EN 61010-1

EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11

Important note for system connection

①②③ indicators indicate the existence of the three phases. (See Figure 1)

If indicator (Phase sequence is not correct) is seen, you have to change any of the 2 phases before proceeding. (L1 - L2, L2 - L3 or L1 - L3)

THD 1 L1 235.8 V L2 225.6 V L3 223.7 V Voltage h

Figure 1: The existence of three phases on LCD.

SUMMARY

SAFETY PRECAUTIONS....1 IMPORTANT NOTE FOR SYSTEM CONNECTION....1

1. DESCRIPTION....3

1.1 Introduction....3
1.2 The front panel 4
1.3 Front panel properties....5
1.4 The rear panel....6

2. INSTALLATION 7

2.1 Mechanical assembly....7
2.2 Operating conditions....7
2.3 Electrical connection....8
2.4 PC Connection....9

3. MODBUS RTU PROTOCOL 10

3.1 Modbus functions....10
3.2 Features of connection cable....11
3.3 I/O Relay Status Register....11
3.4 Learning of device informations(2BH)....11
3.5 Reading and writing to data logs from device (14H)....11
3.6 File record information table....11
3.7 Energy log table....12
3.8 Error codes....12
3.9 MPR-SW (Interface Program)....12
3.10 Data register map (16 bit)....13
3.11 Data register map (32 bit)....14
3.12 Setup register map (16 bit) (MPR60S) 15
3.13 Setup register map (16 bit) (MPR60S -10) 16
3.14 Setup register map (16 bit) (MPR60S -20) 17
3.15 Setup register map (16 bit) (MPR60S -21) 18
3.16 Setup register map (16 bit) (MPR60S -40) 19
3.17 Setup register map (16 bit) (MPR60S-41) 20

4. GENERAL MENU 21

4.1 Setup....21
4.2 Network....21
4.3 Setting the date and time....22
4.4 PC Communication Settings (RS-485)....22
4.5 Datalog....23
4.6 Output Relays and Digital Outputs (Relay 1 and Relay 2)....24
4.7 Pulse Outputs (Pulse A and Pulse R) (MPR60S/MPR60S -21/41) 27
4.8 Digital Inputs (3. Input-1 / 4. Input-2) (MPR60S-10/20/40) 29
4.9 Display 30
4.10 Instantaneous Values....30
4.11 Energy....33
4.12 Demand 35
4.13 Observing the time and date....38
4.14 Info....40
4.15 Manufacturer-Product Information 41
4.16 Password....42
4.17 Parameter Table 43
4.18 Formulas....43
4.19 Current Analog Output (0/4-20mA) (MPR60S -40/41) 44
4.20 Voltage Analog Output (0/2-10V) (MPR60S-20/21) 45
4.21 Factory Settings....46
4.22 Technical Data 47

5. STANDART AND EXPLANATIONS......48

1. DESCRIPTION

1.1 INTRODUCTION

Device is a network analyser in 96x96 mm dimension with a non-flammable enclosure. It is designed for measuring all electrical parameters of an electric network with MODBUS-RTU Protocol on RS-485 communication port in order to communicate with the computer.

Device, based on DSP (Digital Signal Processor), is designed for the purpose of measuring all parameters in industry plants and recording these parameters to its memory. The measured parameters can be displayed on LCD screen which has dimension of 3.6 inch and can be read easily in dark environments by activating the Back-Light function.

Device contains a MODBUS serial interface option.

MPR60S Network Analyser RX 1 2 3 L1 2 12.3 V L2 2 20.6 V L3 2 17.8 V SETUP J E/VTES® ESC THD MENU

Figure 2: General view of the device.

MPR60S Network Analyser
THD V L1 123.2 λ L2 85.7 λ L3 93.4 λ Currents

ENTES MPR-60S-41 - INTRODUCTION - 3

ENTES MPR-60S-41 - INTRODUCTION - 4

ENTES MPR-60S-41 - INTRODUCTION - 5

ENTES MPR-60S-41 - INTRODUCTION - 6

ENTES MPR-60S-41 - INTRODUCTION - 7
Figure 3: Display and buttons.

Four buttons provide access to programming and measurement screens. The display is LCD and has a white backlight.

KEY FUNCTIONS

BUTTONFUNCTION
ESCExit from a menu any time (THD I and THD V can also be displayed)
Go to next menu or increase related value
Go to the previous menu or decrease related value
Enter to a menu or confirm the data entry

1.3 DISPLAY
MPR60S Network Analyser THD IV ▼▲ cap.ind. CosφP.F. L1-2 ▼▲ cap.ind. CosφP.F. L2-3 I/O 1 I/O 2 I/O 3 I/O 4 Exp. Imp. m- +H CurrentsMVArh ESC THD MENU ⑨ ⑩ ⑪ ⑫ ⑬ ⑭ 8.8.8.8 Mw 8.8.8.8 kW 8.8.8.8 W ⑦ ⑥ ⑧ ⑦ ②0 ②1 ②2 ②3 ⑤ ④ ③ ② ① EVTES®

1 ...... Menu (ENTER) button.

2 ...... Down button.

3 ...... Up button.

4 ...... ESC button. Exits from a menu or settings at any time. (THD I, THD V can also be displayed)

5 ...... Menu / Energy line : Shows the present menu. / It also shows the energy values.

6 ...... Shows whether the value in the Energy Menu is Export, Import, Inductive or capacitive.

7 ...... Active output is indicated.

8 ...... Harmonic bars: The total harmonics of the 3 phases are displayed in bar graphs. The columns represent L1, L2 and L3 phases. Each step indicate 10% increase / decrease V is for the voltages harmonics and I is for the currents harmonics.

9 ..... Indicates if the measure is phase to phase or phase to neutral.

10..... The Cosφ or PF (Power Factor) value of the related phase.

11 ..... Indicates if the measurement is capacitive or inductive.

12 ...... Min. and Max. symbols for the demand menu.

13 ..... Indicates that the harmonics are displayed on the screen.

14 .... Total symbol. Shows the total value of the related measurement.

15 ...... Phase sequence failure

16 .... Demand symbol. Shows the demand value of the related parameter.

17 ...... PC Communication indicator.

18 ...... Phase indication symbols.

19 ..... Shows the following measurement values with units. (V, kV, MV, A, kA, MA, W, kW, MW, VA, kVA, MVA, VAr, kVAr, MVAr %)

20 ..... 3.6" LCD Display.

21 ...... Backlight.

22 ..... Shows the unit of energy values. (kWh, kVArh, MWh, MVArh)

1.4 THE REAR PANEL

Network Analyser RS485 Iin :0.005-5.5A~(IL1,IL2,IL3) Un :1-300 VAC (L-N) ; 2-500 VAC (L-L) 1. Relay-1 2. Relay-2 3. Pulse-A 4. Pulse-R 21 22 23 24 Un 25 26

MPR60S

L1 L2 L3 1 2 3 4 5 6 CE CAT III Network Analyser RS485 7 8 9 10 L1 L2 L3 N I in :0.006-5.5A (IL1/L2,IL3) Vin :1-300 VAC (L-N); 2-500 VAC (L-L) 1,Relay-1 2,Relay-2 17 18 19 20 3.Input-1 4.Input-2 21 22 23 24 + - + - Un ~ 25 26

MPR60S-10

Network Analyser Analog Out RS485 1 2 3 4 5 6 7 8 9 10 L1 L2 L3 N In: 0.005-5.5Ain (L1, L2, L3) Vin: 1-300 VAC (L-N); 2-500 VAC (L-L) 1. Relay-1 2. Relay-2 17 18 19 20 3. Pulse-A 4. Pulse-R 21 22 23 24 Uo 25 26

MPR60S-21/41

L1 L2 L3 1 2 3 4 5 6 CE CAT III Network Analyser Analog Out RS485 7 8 9 10 L1 L2 L3 N I in: 0.005-5.5A, (IL1,IL2,IL3) Vin: 1-300 VAC (L-N): 2-500 VAC (L-L) 1.Reay-1 2.Reay-2 17 18 19 20 3.Input-1 4.Input-2 21 22 23 24 + - + - U_n ~ 25 26

MPR60S-20/40

Figure 4: The terminals on the rear panel.
ENTES MPR-60S-41 - THE REAR PANEL - 5

ENTES MPR-60S-41 - THE REAR PANEL - 6

ENTES MPR-60S-41 - THE REAR PANEL - 7

ENTES MPR-60S-41 - THE REAR PANEL - 8

ENTES MPR-60S-41 - THE REAR PANEL - 9

ENTES MPR-60S-41 - THE REAR PANEL - 10

ENTES MPR-60S-41 - THE REAR PANEL - 11

ENTES MPR-60S-41 - THE REAR PANEL - 12

Current monitoring terminals

Voltage monitoring terminals

Analog output / RS-485 output (Only for MPR60S-20/21/40/41)

RS-485 output

Digital output / Alarm

Energy pulse outputs (Only for MPR60S / MPR60S-21/41)

Digital inputs (Only for MPR60S-10/20/40)

Auxiliary supply terminals

2. INSTALLATION

2.1 MECHANICAL ASSEMBLY

The following drawings are the overall dimensions for the device and the panel cut-out.

ENTES MPR-60S-41 - MECHANICAL ASSEMBLY - 1
Figure 5: Dimension and the panel cut-out.

2.2 OPERATING CONDITIONS

CLIMATIC ENVIRONMENT

The device should be protected from water / dense moisture and be installed in a covered enclosure when used in a dusty environment. Ambient operating temperature is between -5^ and +50^

ELECTRICAL ENVIRONMENT

Although the device is protected against electrical current fluctuations, it is advisable to avoid the immediate proximity of equipment generating heavy drains (high power contactors, sets of busbars, etc.) The quality of communication obtained from the computer bus depends to a large extent on observing these precautions.

2.3 ELECTRICAL CONNECTION

Wire thickness for voltage terminals must be 2.5 mm^2 and 4.0 mm^2 for current terminals. For energy pulse outputs and digital inputs the required wire thickness is 1.5 mm^2 .

The fuse must be Type FF with 1A current limit.

3 Phase with neutral connection L1 L2 L3 Current Measurement Inputs Voltage Measurement Inputs Analog Out R8-485 External Supply L1 R8 R9 R10 RS-485 Analog Out RS-485 11 12 13 14 15 16 + GND A B TR RS-485 11 12 13 14 15 16 GND A B TR only for MPR60S MPR60S10 3. Input 1 4. Input 2 21 22 23 24 Input 1 Input 2 Max:30VDC 3. Pulse A 4. Pulse R 21 22 23 24 Pulse A Pulse R Max:30VDC only for MPR60S-10 MPR60S-20 MPR60S-40 only for MPR60S MPR60S-21 MPR60S-41

Figure 6: 3 phase with neutral connection

3 Phase without neutral connection L1 L2 L3 Current Measurement Inputs Voltage Measurement Inputs R3485 External Supply L1 N

Figure 7: 3 phase without neutral connection

ENTES MPR-60S-41 - ELECTRICAL CONNECTION - 3

Figure 8: ARON connection (3 phase without neutral connection)

2.4 PC CONNECTION

RS 485/232 Converter is necessary for communicating with computer.

ENTES MPR-60S-41 - PC CONNECTION - 1

flowchart
graph TD
    A["Max. 1200 mt."] --> B["RS-485/RS-232 or RS-485/USB CONVERTER"]
    B --> C["PC"]
    D["GNDTR B A"] --> E["GNDTR B A"]
    F["GNDTR B A"] --> G["GNDTR B A"]
    H["GNDTR B A"] --> I["GNDTR B A"]
    J["B A"] --> K["GND"]
    L["B A"] --> M["GND"]
    N["..."] --> O["..."]
    P["MPR60S-xx-1MPR60S-xx-2MPR60S-xx-31"]

Figure 9: 31 devices can be connected to the same line.

After 20 pieces of device, a repeater is advised for amplifying the data signal.

ENTES MPR-60S-41 - PC CONNECTION - 2

flowchart
graph TD
    A["MPR60S-xx-247."] --> B["REPEATER"]
    B --> C["PC"]
    D["RS-485/RS-232 or RS-485/USB CONVERTER"] --> E["PC"]
    F["Max. 1200 mt. MAX. 1200 mt."] --> G["PC"]
    H["Max. 1200 mt."] --> I["PC"]
    J["Max. 1200 mt."] --> K["PC"]
    L["Max. 1200 mt."] --> M["PC"]
    N["Max. 1200 mt."] --> O["PC"]
    P["Max. 1200 mt."] --> Q["PC"]
    R["Max. 1200 mt."] --> S["PC"]
    T["Max. 1200 mt."] --> U["PC"]
    V["Max. 1200 mt."] --> W["PC"]
    X["Max. 1200 mt."] --> Y["PC"]
    Z["Max. 1200 mt."] --> AA["PC"]

Figure 10: By using repeaters, 247 devices can be connected to the same line.

3. MODBUS RTU PROTOCOL

MODBUS RTU PROTOCOL

Standard message format of MODBUS RTU is as below :

TADDRESS8 BITSFUNCTION8 BITSDATAN x 8 BITSCRCH CRCL T

Starting and finishing of T times, which are as much as 3.5 characters time, are time periods of data lines which must be constant for evaluating by devices at the line if the message starts or finishes.

Address area, which is between 1 and 247, shows the serial address of device at the line.

Data area contains the data which is sent to device from slave to master or from master to slave.

CRC is a determination methode of error which is used at the MODBUS RTU Protocol and it has 2 bytes

3.1 Modbus Functions:

03H REGISTER READING14H LOG DATA RECORD READING
06H SINGLE REGISTER WRITING2BH DEVICE INFORMATION READING
10H MULTIPLE REGISTER WRITING

Register Reading (03H) function is used to read measured parameters and transformer ratios. If a register is tried to read except for values, device sends error message.

Example : This message must be sent to the device for reading the phase-neutral voltage of Phase 1;

01 Device address

03 Function

00 MSB address

00 LSB address

00 Register numbers MSB

01 Register numbers LSB

84 CRC MSB

0A CRC LSB

Single register writing command (06) is used to set the transformer ratios or clear any of min., max. or demand values. Current transformer ratio can be entered between 1 and 5000 and voltage transformer ratio can be entered between 1 and 4000. Only "0" (zero) value can be entered to the demand values.

For setting the CT ratio as 100;

01 Device address

06 Function

01 MSB address

00 LSB address

00 Data MSB

64 Data LSB

89 CRC MSB

DD CRC LSB

Multiple register writing command (10H) is used to change more than one register value. For setting the CT ratio as 100 and voltage transformer ratio as 2;

RESPONSE

01 Device address 01 Device address

10 Function 10 Function

01 MSB address 01 Register address (high)

00 LSB address 00 Register address (low)

00 Register number MSB 00 Number of registers (high)

02 Register number LSB 02 Number of registers (low)

04 Byte number 40 CRC (high)

00 Data MSB 34 CRC (low)

64 Data LSB

00 Data MSB

C8 Data LSB

BE CRC MSB

76 CRC LSB

Parameters are transmitted as 16 bit hexadecimal.

For example

- 230,6 V voltage value of the device is received as 2306 (0902H) and real value is obtained by multiplying to its multiplier (x0,1) and VT ratio

● 1,907A current value is received as 1907 (0773H) and it is multiplied by 0,001 and CT ratio

- -0,78 P.F. value is received as FCF4H. (16 bit signed integer)

● Energy values are sent as 2 words in 16 bit register table.

Energy value = (High x 10.000) + Low

Example

Low High

06237819 kWh = 1E8BH 026FH

3.2 Features of connection cable:

  • Screened
  • 24 AWG or more thickness
  • DC resistance : =<100 ohm/km
  • Characteristic impedance : 100 ohm for 100kHz
  • Capacitor between two conductors : =< 60 pF/m
  • Capacitor between one conductor and earth : =< 120 pF/m

3.3 I/O Relay Status Register.

I/O Relay Status register is used to observe the status of device outputs

1514131211109876543210
00000000000000Relay2Relay1
1314151211910876543120
0000000000000000Input2Input1Relay2Relay1(Only for MPR60S-10/20/40)
  • When Relay 1 is switched on, 0 (zero) bit of I/O Relay Status Register is read as 1 and when Relay 1 is not switched on it is read as 0.
  • When Relay 2 is switched on, 1st bit of I/O Relay Status Register is read as 1 and when Relay 2 is not switched on it is read as 0.
  • If Relay Functions (Setup register:011AH/012DH) is set to "1" then Relay 1/2 functions as "Digital Output 1/2".

For switch ON Relay 1 Example : 01 06 00 4C 00 01 CRC

For switch ON Relay 2 Example : 01 06 00 4C 00 02 CRC

For switch ON both relays Example : 01 06 00 4C 00 03 CRC

For switch OFF both relays Example : 01 06 00 4C 00 00 CRC

3.4 Learning of device informations (2BH)

Following data packet is sent to device to learn the device code, program version, manufacturer name and manufacturer web site :

01 2B 0E 01 00 70 77

3.5 Reading and writing to data logs from device (14H)

Modbus RTU 14H function is used to transmit measured parameters to the computer, when the device is not connected with computer.

01 14 07 06 00 00 00 02 00 01 99 24

01 Device address
14 Function
07 Byte number
06 Reference type
00 File number MSB0-15
00 File number LSB
00 Record number MSB0-999
02 Record number LSB
00 Record length MSB1
01 Record length LSB
99 CRC MSB
24 CRC LSB

Answer

01Device address
14Function
46Data length
20Record length
06Reference type
00Record number MSB
02Record number LSB
02Record date Day
10Record date Month
05Record date Year
19Record date Hour
07Record date Minute
23Record date Second
08Data 01 MSB
BCData 01 LSB
08Data 02 MSB
95Data 02 LSB
:: : : :
00Data 28 MSB
00Data 28 LSB
71CRC MSB
B0CRC LSB

ENTES MPR-60S-41 - Reading and writing to data logs from device (14H) - 1

Warning : Data logs must be deleted individually for each file.

For deleting the data logs at the File 0, below request must be sent.

Request: 01 06 04 01 00 00 D9 3A

Response : 01 06 04 01 00 00 D9 3A

record numbers

* Please refer to page 12 for energy log table.

Log formatTypeRange
1Index HiWord0..999
Index Lo
2Day HiWord1..31
Month Lo1..12
3Year HiWord00.99
Hour Lo00..23
4Minute HiWord00..59
Second Lo00..59
5Data 01 HiWord0..65535
Data 01 Lo
6Data 02 HiWord0..65535
Data 02 Lo
31Data 28 HiWord0..65535
Data 28 Lo
32CRCWordCRC16

3.6 File Record Information Table

It shows the number of records, open file and total number of recordings of the files which have data logs.

ADDRESSDESCRIPTION DIMENSION
0400HFile which is recorded now. (0-14)word
0401HRecord numbers at File 0word
0402HRecord numbers at File 1word
0410HRecord numbers at energy fileword
0411HTotal record numbersword

3.7 Energy Log

IndexEnergy Log Format Dimension Multiplier Range Unit
1 Index Word 0..999 -Data
2Day(Hi) 1..31WordDatad
Month(Lo) 1..12m
3Year(Hi) 00..99WordDatay
Hour (Lo) 00..23h
4Minute(Hi) 00..59WordDatam
Second (Lo) 00..59s
5Import Active Energy(Lo)WordData-kWh/MWh
6Import Active Energy(Hi)WordData x 1000099999999
7Export Active Energy (Lo)WordData-kWh/MWh
8Export Active Energy(Hi)WordData x 1000099999999
9Inductive Reactive Energy(Lo)WordData-kVArh/MVArh
10Inductive Reactive Energy(Hi)WordData x 1000099999999
11Capacitive Reactive Energy(Lo)WordData-kVArh/MVArh
12Capacitive Reactive Energy(Hi)WordData x 1000099999999
13Voltage High LN1WordData x VT x 0.10...VmaxV
14Voltage High LN2 Word 0...VmaxVData x VT x 0.1
15Voltage High LN3 Word 0...VmaxVData x VT x 0.1
16Current High Demand L1WordData x CT x 0.0010...ImaxA
17Current High Demand L2Word 0...ImaxData ACT x 0.001
18Current High Demand L3Word 0...ImaxData ACT x 0.001
19Current Demand L1WordData x CT x 0.0010...ImaxA
20Current Demand L2Word 0...ImaxData ACT x 0.001
21Current Demand L3Word 0...ImaxData ACT x 0.001
22Total Curent High DemandWordData x CT x 0.0010...ImaxA
23Energy Counter UnitWordData0:Kilo/1:Mega-
24Total Current DemandWord 0...ImaxData ACT x 0.001
25Total Active Power DemandSigned WordData x VT x CT0..±PtmaxW
26Total Reactive Power DemandSigned WordData x VT x CT0..±QtmaxVAr
27Total Appearnt Power DemandWord 0..StmaxData x VT x CTVA
28FrequencyWordData x 0.0145.00..65.00Hz
29Total Power FactorSigned WordData x 0.001 -1.000..1.000-
30Current Transformer RatioWordData1..2000-
31Voltage Transformer RatioWordData x 0.11..4000.0-
32Energy Pack CRCWordDataCRC 16-

3.8 ERROR CODES

If an inappropriate message is sent to device in MODBUS-RTU protocol, device sends an error message. Error codes are mentioned below :

01 Invalid Function

This message is received when a function is used which is not supported by device.

Example

Request 01 07 04 01 00 00 CRC

Response 01 Device address

87 80 h + 07h

constant invalid function code

01 Error code

82 CRC (high)

30 CRC (low)

02 Invalid Register

This message is received when an address is wanted to reach which is not found in register table of device.

Example

Request 01 06 50 00 00 CRC

Response 01 Device address

86 80 h + .06h

constant function code

02 Error code

C3 CRC (high)

A1 CRC (low)

03 Invalid Data :

This message is received when data is not found in required value intervals which is wanted to write.

Example

Request 01 03 00 00 00 FF CRC

Response 01 Device address

83 80 h + 03 h

constant function code

03 Error code

01 CRC (high)

31 CRC (low)

3.9 MPR-SW; Interface Program

MPR-SW is a recording and analysis program which is designed to use with all Entes products which has RS-485 outputs. MPR-SW Program records each parameter of the connected Entes products with programmable time intervals, draws graphics, billing for the energy consumption between adjustable dates, with 2 way communication. Maximum 247 devices can communicate with one software.

Device takes 64 samples in each period. For 50 Hz, it takes 3200 samples in one second and for 60 Hz, it takes 3840 samples in one second.

3.10 Data Register Map (16 bit)

ADDRESSDESCRIPTION UNITDIMENSION(16 bit)MULTIPLIERRANGE
0000HVoltage LN1WordData x VT x 0.10..VmaxV
0001HVoltage LN2WordData x VT x 0.10..VmaxV
0002HVoltage LN3WordData x VT x 0.10..VmaxV
0003HCurrent LN1WordData x CT x 0.0010..ImaxA
0004HCurrent LN2WordData x CT x 0.0010..ImaxA
0005HCurrent LN3WordData x CT x 0.0010..ImaxA
0006HTotal CurrentWordData x CT x 0.0010..ImaxA
0007HActive Power L1Signed IntData x VT x CT0..±PmaxW
0008HActive Power L2Signed IntData x VT x CT0..±PmaxW
0009HActive Power L3Signed IntData x VT x CT0..±PmaxW
000AHReactive Power L1Signed IntData x VT x CT0..±QmaxVAr
000BHReactive Power L2Signed IntData x VT x CT0..±QmaxVAr
000CHReactive Power L3Signed IntData x VT x CT0..±QmaxVAr
000DHApparent Power L1WordData x VT x CT0..SmaxVA
000EHApparent Power L2WordData x VT x CT0..SmaxVA
000FHApparent Power L3WordData x VT x CT0..SmaxVA
0010HPower Factor L1Signed IntData x 0.001-1.000..1.000-
0011HPower Factor L2Signed IntData x 0.001-1.000..1.000-
0012HPower Factor L3Signed IntData x 0.001-1.000..1.000-
0013HCos L1Signed IntData x 0.001-1.000..1.000-
0014HCos L2Signed IntData x 0.001-1.000..1.000-
0015HCos L3Signed IntData x 0.001-1.000..1.000-
0016HVoltage L12WordData x VT x 0.10..VmaxV
0017HVoltage L23WordData x VT x 0.10..VmaxV
0018HVoltage L31WordData x VT x 0.10..VmaxV
0019HVoltage LNWordData x VT x 0.10..VmaxV
001AHVoltage LLWordData x VT x 0.10..VmaxV
001BHFrequencyWordData x 0.0145.00..65.00Hz
001CHTotal Active PowerSigned IntData x VT x CT0..±Pt maxW
001DHTotal Reactive PowerSigned IntData x VT x CT0..±Qt maxVAr
001EHTotal Apparent PowerWordData x VT x CT0..St maxVA
001FHTHD V1WordData x 0.10..900%
0020HTHD V2WordData x 0.10..900%
0021HTHD V3WordData x 0.10..900%
0022HTHD V3PWordData x 0.10..900%
0023HTHD I1WordData x 0.10..900%
0024HTHD I2WordData x 0.10..900%
0025HTHD I3WordData x 0.10..900%
0026HTHD I3PWordData x 0.10..900%
0027H*Voltage High LN1WordData x VT x 0.10..VmaxV
0028H*Voltage High LN2WordData x VT x 0.10..VmaxV
0029H*Voltage High LN3WordData x VT x 0.10..VmaxV
002AH*Voltage Low LN1WordData x VT x 0.10..VmaxV
002BH*Voltage Low LN2WordData x VT x 0.10..VmaxV
002CH*Voltage Low LN3WordData x VT x 0.10..VmaxV
002DH*Demand Current High L1WordData x CT x 0.0010..ImaxA
002EH*Demand Current High L2WordData x CT x 0.0010..ImaxA
002FH*Demand Current High L3WordData x CT x 0.0010..ImaxA
0030H*Demand Current Low L1WordData x CT x 0.0010..ImaxA
0031H*Demand Current Low L2WordData x CT x 0.0010..ImaxA
0032H*Demand Current Low L3WordData x CT x 0.0010..ImaxA
0033H*Demand Current L1WordData x CT x 0.0010..ImaxA
0034H*Demand Current L2WordData x CT x 0.0010..ImaxA
0035H*Demand Current L3WordData x CT x 0.0010..ImaxA
0036H*Demand Total Current HighWordData x CT x 0.0010..ImaxA
0037H*Demand Total Current LowWordData x CT x 0.0010..ImaxA
0038H*Demand Total CurrentWordData x CT x 0.0010..ImaxA
0039H*Demand Total Active PowerSigned IntData x VT x CT0..Pt maxW
003AH*Demand Total Reactive PowerSigned IntData x VT x CT0..Qt maxVAr
003BH*Demand Total Apparent PowerWordData x VT x CT0..St maxVA
003CH*Import Active Energy LoWord(Data +--
003DH*Import Active Energy HiWord(Data x 10000)99999999kWh/MWh
003EH*Export Active Energy LoWord(Data +--
003FH*Export Active Energy HiWord(Data x 10000)99999999kWh/MWh
0040H*Inductive Reactive Energy LoWord(Data +--
0041H*Inductive Reactive Energy HiWord(Data x 10000)99999999kVArh/MVArh
0042H*Capacitive Reactive Energy LoWord(Data +--
0043H*Capacitive Reactive Energy HiWord(Data x 10000)99999999kVArh/MVArh
0044HHourWordData0..23h
0045HMinuteWordData0..59m
0046HSecondWordData0..59s
0047HDayWordData0..31day
0048HMonthWordData0..12month
0049HYearWordData00..99year
004AHCurrent Transformer RatioWordData1..5000-
004BHVoltage Transformer RatioWordData x 0.11.0..4000.0-
004CHIO Relay Status (only MPR60S/60S-2141)BinaryData & 0x0003b0:Relay1,b1:Relay2-
IO Relay and Control Status(only MPR60S-10/20/40)Data & 0x000Fb0:Relay1,b1:Relay2b2:Input1, b3:Input2
004DHTotal Power FactorSigned IntData x 0.001-1.000..1.000-
004EHNeutral CurrentWordData x CT x 0.0010..IN max.A
004FH*Demand Total Active Power HighSigned IntData x VT x CT0..+Pt maxW
0050H*Demand Total Reactive Power HighSigned IntData x VT x CT0..+Qt maxVAr
0051H*Demand Total Apparent Power HighWordData x VT x CT0..St maxVA
0052H*Demand Total Active Power LowSigned IntData x VT x CT0..+Pt maxW
0053H*Demand Total Reactive Power LowSigned IntData x VT x CT0..+Qt maxVAr
0054H*Demand Total Apparent Power LowWordData x VT x CT0..St maxVA

Word : 16bit Unsigned (0..65,535)
Signed Int : 16bit Signed (-32,768 .. 32,767)
* Writable registers (Only "0" (zero) value can be written)

3.11 Data Register Map (32 bit)

(Following values are multiplied by Voltage and Current Transformer Ratios)

ADDRESSDESCRIPTIONDIMENSION(32 bit)RANGEUNITM
4000HVoltage LN1LongData x 0.010..Vmax x VTV
4002HVoltage LN2LongData x 0.010..Vmax x VTV
4004HVoltage LN3LongData x 0.010..Vmax x VTV
4006HCurrent LN1LongData x 0.0010..Imax x CTA
4008HCurrent LN2LongData x 0.0010..Imax x CTA
400AHCurrent LN3LongData x 0.0010..Imax x CTA
400CHTotal CurrentLongData x 0.0010..Imax x CTA
400EHActive Power L1Signed LongData x 0.010..±Pmax x VT x CTW
4010HActive Power L2Signed LongData x 0.010..±Pmax x VT x CTW
4012HActive Power L3Signed LongData x 0.010..±Pmax x VT x CTW
4014HReactive Power L1Signed LongData x 0.010..±Qmax x VT x CTVAr
4016HReactive Power L2Signed LongData x 0.010..±Qmax x VT x CTVAr
4018HReactive Power L3Signed LongData x 0.010..±Qmax x VT x CTVAr
401AHApparent Power L1LongData x 0.010..Smax x VT x CTVA
401CHApparent Power L2LongData x 0.010..Smax x VT x CTVA
401EHApparent Power L3LongData x 0.010..Smax x VT x CTVA
4020HPower Factor L1Signed LongData x 0.001-1.000..1.000-
4022HPower Factor L2Signed LongData x 0.001-1.000..1.000-
4024HPower Factor L3Signed LongData x 0.001-1.000..1.000-
4026HCos L1Signed LongData x 0.001-1.000..1.000-
4028HCos L2Signed LongData x 0.001-1.000..1.000-
402AHCos L3Signed LongData x 0.001-1.000..1.000-
402CHVoltage L12LongData x 0.010..Vmax x VTV
402EHVoltage L23LongData x 0.010..Vmax x VTV
4030HVoltage L31LongData x 0.010..Vmax x VTV
4032HVoltage LNLongData x 0.010..Vmax x VTV
4034HVoltage LLLongData x 0.010..Vmax x VTV
4036HFrequencyLongData x 0.0145.00..65.00Hz
4038HTotal Active PowerSigned LongData x 0.010..±Pt max x VT x CTW
403AHTotal Reactive PowerSigned LongData x 0.010..±Qt max x VT x CTVAr
403CHTotal Apparent PowerLongData x 0.010..ST max x VT x CTVA
403EHTHD V1LongData x 0.10..900%
4040HTHD V2LongData x 0.10..900%
4042HTHD V3LongData x 0.10..900%
4044HTHD V3PLongData x 0.10..900%
4046HTHD I1LongData x 0.10..900%
4048HTHD I2LongData x 0.10..900%
404AHTHD I3LongData x 0.10..900%
404CHTHD I3PLongData x 0.10..900%
404EH*Voltage High LN1LongData x 0.010..Vmax x VTV
4050H*Voltage High LN2LongData x 0.010..Vmax x VTV
4052H*Voltage High LN3LongData x 0.010..Vmax x VTV
4054H*Voltage Low LN1LongData x 0.010..Vmax x VTV
4056H*Voltage Low LN2LongData x 0.010..Vmax x VTV
4058H*Voltage Low LN3LongData x 0.010..Vmax x VTV
405AH*Demand Current High L1LongData x 0.0010..Imax x CTA
405CH*Demand Current High L2LongData x 0.0010..Imax x CTA
405EH*Demand Current High L3LongData x 0.0010..Imax x CTA
4060H*Demand Current Low L1LongData x 0.0010..Imax x CTA
4062H*Demand Current Low L2LongData x 0.0010..Imax x CTA
4064H*Demand Current Low L3LongData x 0.0010..Imax x CTA
4066H*Demand Current L1LongData x 0.0010..Imax x CTA
4068H*Demand Current L2LongData x 0.0010..Imax x CTA
406AH*Demand Current L3LongData x 0.0010..Imax x CTA
406CH*Demand Total Current HighLongData x 0.0010..Imax x CTA
406EH*Demand Total Current LowLongData x 0.0010..Imax x CTA
4070H*Demand Total CurrentLongData x 0.0010..Imax x CTA
4072H*Demand Total Active PowerSigned LongData x 0.010..Pt max x VT x CTW
4074H*Demand Total Reactive PowerSigned LongData x 0.010..Qt max x VT x CTVAr
4076H*Demand Total Apparent PowerLongData x 0.010..ST max x VT x CTVA
4078H*Import Active EnergyLongData99999999kWh/MWh
407AH*Export Active EnergyLongData99999999kWh/MWh
407CH*Inductive Reactive EnergyLongData99999999kVArh/MVArh
407EH*Capacitive Reactive EnergyLongData99999999kVArh/MVArh
4080HHourLongData0..23h
4082HMinuteLongData0..59m
4084HSecondLongData0..59s
4086HDayLongData0..31day
4088HMonthLongData0..12month
408AHYearLongData00..99year
408CHCurrent Transformer RatioLongData1..5000-
408EHVoltage Transformer RatioLongData x 0.11.0..4000.0-
4090HIO Relay Status (only MPR60S/60S-21/41)BinaryData & 0x0003b0:Relay1,b1:Relay2-
IO Relay and Control Status (only MPR60S-10/20/40)Data & 0x000Fb0:Relay1,b1:Relay2b2:Input1, b3:Input2
4092HTotal Power FactorSigned LongData x 0.001-1.000..1.000-
4094HNeutral CurrentLongData x 0.0010..IN max.A
4096H*Demand Total Active Power HighSigned LongData x 0.010..+Pt max x VT x CTW
4098H*Demand Total Reactive Power HighSigned LongData x 0.010..+Qt max x VT x CTVAr
409AH*Demand Total Apparent Power HighLongData x 0.010..ST max x VT x CTVA
409CH*Demand Total Active Power LowSigned LongData x 0.010..+Pt max x VT x CTW
409EH*Demand Total Reactive Power LowSigned LongData x 0.010..+Qt max x VT x CTVAr
40AOH*Demand Total Apparent Power LowLongData x 0.010..ST max x VT x CTVA

LTIPLIER

3.12 Setup Register Map (16 bit) (for MPR60S)

ADDRESS DESCRIPTIONDIMENSION(16bit)MULTIPLIERUNIT
0100HCurrent Transformer RatioWordData
0101HVoltage Transformer RatioWordData x 0.1
0102HNet TypeWord0:3P4W 1:3P3W 2:ARON
0103HReservedWordData
0104H3.Pulse-A Prm.WordDatakWh
0105H3.Pulse-A DurationWordDatams
0106H4.Pulse-R Prm.WordDatakVArh
0107H4.Pulse-R DurationWordDatams
0108HRelay1 Parameter1WordData
0109HRelay1 Hi1WordData
010AHRelay1 Lo1WordData
010BHRelay1 Delay1WordDatasec.
010CHRelay1 Hysteresis1WordData
010DHReservedWordData
010EHRelay1 Parameter2WordData
010FHRelay1 Hi2WordData
0110HRelay1 Lo2WordData
0111HRelay1 Delay2WordDatasec.
0112HRelay1 Hysteresis2WordData
0113HReservedWordData
0114HRelay1 Parameter3WordData
0115HRelay1 Hi3WordData
0116HRelay1 Lo3WordData
0117HRelay1 Delay3WordDatasec.
0118HRelay1 Hysteresis3WordData
0119HReservedWordData
011AHRelay1 FunctionWord0:Alarm / 1:Digital Output
011BHRelay2 Parameter1WordData
011CHRelay2 Hi1WordData
011DHRelay2 Lo1WordData
011EHRelay2 Delay1WordDatasec.
011FHRelay2 Hysteresis1WordData
0120HReservedWordData
0121HRelay2 Parameter2WordData
0122HRelay2 Hi2WordData
0123HRelay2 Lo2WordData
0124HRelay2 Delay2WordDatasec.
0125HRelay2 Hysteresis2WordData
0126HReservedWordData
0127HRelay2 Parameter3WordData
0128HRelay2 Hi3WordData
0129HRelay2 Lo3WordData
012AHRelay2 Delay3WordDatasec.
012BHRelay2 Hysteresis3WordData
012CHReservedWordData
012DHRelay2 FunctionWord0:Alarm / 1:Digital Output
012EHReservedWordData
012FHReservedWordData
0130HReservedWordData
0131HLog PeriodWordDatasec.
0132HLog EventWord0:Off / 1:On
0133HLog Energy PeriodWordDatasec.
0134HLog Par 1WordData
0135HLog Par 2WordData
:::Data
014FHLog Par 28WordData
:ReservedWordData
0156HDemand TimeWordDataminute
0157HHourWordDatah
0158HMinuteWordDatam
0159HSecondWordDatas
015AHReservedWordData
015BHDayWordDataday
015CHMonthWordDatamonth
015DHYearWordDatayear
015EHReservedWordData
015FHReservedWordData
0160HTotal Energy / SeparatelyWord0:Total/1:Separately
0161HSerial Number (1,2)Word (Hi/Lo)Char.1 / Char.2ASC II
0162HSerial Number (3,4)Word (Hi/Lo)Char.3 / Char.4ASC II
0163HSerial Number (5,6)Word (Hi/Lo)Char.5 / Char.6ASC II
0164HSerial Number (7,8)Word (Hi/Lo)Char.7 / Char.8ASC II
0165HReservedWordData
0166HReservedWordData
0167HReservedWordData
0168HReservedWordData
0169HReservedWordData
016AHReservedWordData
016BHReservedWordData
016CHEnergy Counter UnitWord0:Kilo / 1:Mega

3.13 Setup Register Map (16bit) (for MPR60S-10)

ADDRESS DESCRIPTIONDIMENSION(16bit)MULTIPLIERUNIT
0100HCurrent Transformer RatioWordData
0101HVoltage Transformer RatioWordData x 0.1
0102HNet TypeWord0:3P4W 1:3P3W 2:ARON
0103HReservedWordData
0104HReservedWordData
0105HReservedWordData
0106HReservedWordData
0107HReservedWordData
0108HRelay1 Parameter1WordData
0109HRelay1 Hi1WordData
010AHRelay1 Lo1WordData
010BHRelay1 Delay1WordDatasec.
010CHRelay1 Hysteresis1WordData
010DHReservedWordData
010EHRelay1 Parameter2WordData
010FHRelay1 Hi2WordData
0110HRelay1 Lo2WordData
0111HRelay1 Delay2WordDatasec.
0112HRelay1 Hysteresis2WordData
0113HReservedWordData
0114HRelay1 Parameter3WordData
0115HRelay1 Hi3WordData
0116HRelay1 Lo3WordData
0117HRelay1 Delay3WordDatasec.
0118HRelay1 Hysteresis3WordData
0119HReservedWordData
011AHRelay1 FunctionWord0:Alarm / 1:Digital Output
011BHRelay2 Parameter1WordData
011CHRelay2 Hi1WordData
011DHRelay2 Lo1WordData
011EHRelay2 Delay1WordDatasec.
011FHRelay2 Hysteresis1WordData
0120HReservedWordData
0121HRelay2 Parameter2WordData
0122HRelay2 Hi2WordData
0123HRelay2 Lo2WordData
0124HRelay2 Delay2WordDatasec.
0125HRelay2 Hysteresis2WordData
0126HReservedWordData
0127HRelay2 Parameter3WordData
0128HRelay2 Hi3WordData
0129HRelay2 Lo3WordData
012AHRelay2 Delay3WordDatasec.
012BHRelay2 Hysteresis3WordData
012CHReservedWordData
012DHRelay2 FunctionWord0:Alarm / 1:Digital Output
012EHReservedWordData
012FHReservedWordData
0130HReservedWordData
0131HLog PeriodWordDatasec.
0132HLog EventWord0:Off / 1:On
0133HLog Energy PeriodWordDatasec.
0134HLog Par 1WordData
0135HLog Par 2WordData
:::Data
014FHLog Par 28WordData
:ReservedWordData
0156HDemand TimeWordDataminute
0157HHourWordDatah
0158HMinuteWordDatam
0159HSecondWordDatas
015AHReservedWordData
015BHDayWordDataday
015CHMonthWordDatamonth
015DHYearWordDatayear
015EHReservedWordData
015FHReservedWordData
0160HTotal Energy / SeparatelyWord0:Total/1:Separately
0161HSerial Number (1,2)Word (Hi/Lo)Char.1 / Char.2ASC II
0162HSerial Number (3,4)Word (Hi/Lo)Char.3 / Char.4ASC II
0163HSerial Number (5,6)Word (Hi/Lo)Char.5 / Char.6ASC II
0164HSerial Number (7,8)Word (Hi/Lo)Char.7 / Char.8ASC II
0165HInput 1 FunctionWord0:Real Time / 1:Lacth
0166HInput 2 FunctionWord0:Real Time / 1:Lacth
0167HReservedWordWord
0168HReservedWordWord
0169HReservedWordData
016AHReservedWordData
016BHReservedWordData
016CHEnergy Counter UnitWord0:Kilo / 1:Mega

3.14 Setup Register Map (16 bit) (for MPR60S-20)

ADDRESS DESCRIPTIONDIMENSION(16bit)MULTIPLIERUNIT
0100HCurrent Transformer RatioWordData
0101HVoltage Transformer RatioWordData x 0.1
0102HNet TypeWord0:3P4W 1:3P3W 2:ARON
0103HReservedWordData
0104HReservedWordData
0105HReservedWordData
0106HReservedWordData
0107HReservedWordData
0108HRelay1 Parameter1WordData
0109HRelay1 Hi1WordData
010AHRelay1 Lo1WordData
010BHRelay1 Delay1WordDatasec.
010CHRelay1 Hysteresis1WordData
010DHReservedWordData
010EHRelay1 Parameter2WordData
010FHRelay1 Hi2WordData
0110HRelay1 Lo2WordData
0111HRelay1 Delay2WordDatasec.
0112HRelay1 Hysteresis2WordData
0113HReservedWordData
0114HRelay1 Parameter3WordData
0115HRelay1 Hi3WordData
0116HRelay1 Lo3WordData
0117HRelay1 Delay3WordDatasec.
0118HRelay1 Hysteresis3WordData
0119HReservedWordData
011AHRelay1 FunctionWord0:Alarm / 1:Digital Output
011BHRelay2 Parameter1WordData
011CHRelay2 Hi1WordData
011DHRelay2 Lo1WordData
011EHRelay2 Delay1WordDatasec.
011FHRelay2 Hysteresis1WordData
0120HReservedWordData
0121HRelay2 Parameter2WordData
0122HRelay2 Hi2WordData
0123HRelay2 Lo2WordData
0124HRelay2 Delay2WordDatasec.
0125HRelay2 Hysteresis2WordData
0126HReservedWordData
0127HRelay2 Parameter3WordData
0128HRelay2 Hi3WordData
0129HRelay2 Lo3WordData
012AHRelay2 Delay3WordDatasec.
012BHRelay2 Hysteresis3WordData
012CHReservedWordData
012DHRelay2 FunctionWord0:Alarm / 1:Digital Output
012EHAnalog Output ParametersWordData
012FHAnalog Output LowWordData
0130HAnalog Output HighWordData
0131HLog PeriodWordDatasec.
0132HLog EventWord0:Off / 1:On
0133HLog Energy PeriodWordDatasec.
0134HLog Par 1WordData
0135HLog Par 2WordData
Data
014FHLog Par 28WordData
ReservedWordData
0156HDemand TimeWordDataminute
0157HHourWordDatah
0158HMinuteWordDatam
0159HSecondWordDatas
015AHReservedWordData
015BHDayWordDataday
015CHMonthWordDatamonth
015DHYearWordDatayear
015EHReservedWordData
015FHReservedWordData
0160HTotal Energy / SeparatelyWord0:Total/1:Separately
0161HSerial Number (1,2)Word (Hi/Lo)Char.1 / Char.2ASC II
0162HSerial Number (3,4)Word (Hi/Lo)Char.3 / Char.4ASC II
0163HSerial Number (5,6)Word (Hi/Lo)Char.5 / Char.6ASC II
0164HSerial Number (7,8)Word (Hi/Lo)Char.7 / Char.8ASC II
0165HInput 1 FunctionWord0:Real Time / 1:Lacth
0166HInput 2 FunctionWord0:Real Time / 1:Lacth
0167HAnalog Output TypeWord0: 2-10V / 1: 0-10V
0168HReservedWordData
0169HReservedWordData
016AHReservedWordData
016BHReservedWordData
016CHEnergy Counter UnitWord0:Kilo / 1:Mega

3.15 Setup Register Map (16 bit) (for MPR60S-21)

ADDRESS DESCRIPTIONDIMENSION(16bit)MULTIPLIERUNIT
0100HCurrent Transformer RatioWordData
0101HVoltage Transformer RatioWordData x 0.1
0102HNet TypeWord0:3P4W 1:3P3W 2:ARON
0103HReservedWordData
0104H3.Pulse-A Prm.WordDatakWh
0105H3.Pulse-A DurationWordDatams
0106H4.Pulse-R Prm.WordDatakVArh
0107H4.Pulse-R DurationWordDatams
0108HRelay1 Parameter1WordData
0109HRelay1 Hi1WordData
010AHRelay1 Lo1WordData
010BHRelay1 Delay1WordDatasec.
010CHRelay1 Hysteresis1WordData
010DHReservedWordData
010EHRelay1 Parameter2WordData
010FHRelay1 Hi2WordData
0110HRelay1 Lo2WordData
0111HRelay1 Delay2WordDatasec.
0112HRelay1 Hysteresis2WordData
0113HReservedWordData
0114HRelay1 Parameter3WordData
0115HRelay1 Hi3WordData
0116HRelay1 Lo3WordData
0117HRelay1 Delay3WordDatasec.
0118HRelay1 Hysteresis3WordData
0119HReservedWordData
011AHRelay1 FunctionWord0:Alarm / 1:Digital Output
011BHRelay2 Parameter1WordData
011CHRelay2 Hi1WordData
011DHRelay2 Lo1WordData
011EHRelay2 Delay1WordDatasec.
011FHRelay2 Hysteresis1WordData
0120HReservedWordData
0121HRelay2 Parameter2WordData
0122HRelay2 Hi2WordData
0123HRelay2 Lo2WordData
0124HRelay2 Delay2WordDatasec.
0125HRelay2 Hysteresis2WordData
0126HReservedWordData
0127HRelay2 Parameter3WordData
0128HRelay2 Hi3WordData
0129HRelay2 Lo3WordData
012AHRelay2 Delay3WordDatasec.
012BHRelay2 Hysteresis3WordData
012CHReservedWordData
012DHRelay2 FunctionWord0:Alarm / 1:Digital Output
012EHAnalog Output ParametersWordData
012FHAnalog Output LowWordData
0130HAnalog Output HighWordData
0131HLog PeriodWordDatasec.
0132HLog EventWord0:Off / 1:On
0133HLog Energy PeriodWordDatasec.
0134HLog Par 1WordData
0135HLog Par 2WordData
Data
014FHLog Par 28WordData
ReservedWordData
0156HDemand TimeWordDataminute
0157HHourWordDatah
0158HMinuteWordDatam
0159HSecondWordDatas
015AHReservedWordData
015BHDayWordDataday
015CHMonthWordDatamonth
015DHYearWordDatayear
015EHReservedWordData
015FHReservedWordData
0160HTotal Energy / SeparatelyWord0:Total/1:Separately
0161HSerial Number (1,2)Word (Hi/Lo)Char.1 / Char.2ASC II
0162HSerial Number (3,4)Word (Hi/Lo)Char.3 / Char.4ASC II
0163HSerial Number (5,6)Word (Hi/Lo)Char.5 / Char.6ASC II
0164HSerial Number (7,8)Word (Hi/Lo)Char.7 / Char.8ASC II
0165HReservedWordData
0166HReservedWordData
0167HAnalog Output TypeWord0: 2-10V / 1: 0-10V
0168HReservedWordData
0169HReservedWordData
016AHReservedWordData
016BHReservedWordData
016CHEnergy Counter UnitWord0:Kilo / 1:Mega

3.16 Setup Register Map (16 bit) (for MPR60S-40)

ADDRESS DESCRIPTIONDIMENSION(16bit)MULTIPLIERUNIT
0100HCurrent Transformer RatioWordData
0101HVoltage Transformer RatioWordData x 0.1
0102HNet TypeWord0:3P4W 1:3P3W 2:ARON
0103HReservedWordData
0104HReservedWordData
0105HReservedWordData
0106HReservedWordData
0107HReservedWordData
0108HRelay1 Parameter1WordData
0109HRelay1 Hi1WordData
010AHRelay1 Lo1WordData
010BHRelay1 Delay1WordDatasec.
010CHRelay1 Hysteresis1WordData
010DHReservedWordData
010EHRelay1 Parameter2WordData
010FHRelay1 Hi2WordData
0110HRelay1 Lo2WordData
0111HRelay1 Delay2WordDatasec.
0112HRelay1 Hysteresis2WordData
0113HReservedWordData
0114HRelay1 Parameter3WordData
0115HRelay1 Hi3WordData
0116HRelay1 Lo3WordData
0117HRelay1 Delay3WordDatasec.
0118HRelay1 Hysteresis3WordData
0119HReservedWordData
011AHRelay1 FunctionWord0:Alarm / 1:Digital Output
011BHRelay2 Parameter1WordData
011CHRelay2 Hi1WordData
011DHRelay2 Lo1WordData
011EHRelay2 Delay1WordDatasec.
011FHRelay2 Hysteresis1WordData
0120HReservedWordData
0121HRelay2 Parameter2WordData
0122HRelay2 Hi2WordData
0123HRelay2 Lo2WordData
0124HRelay2 Delay2WordDatasec.
0125HRelay2 Hysteresis2WordData
0126HReservedWordData
0127HRelay2 Parameter3WordData
0128HRelay2 Hi3WordData
0129HRelay2 Lo3WordData
012AHRelay2 Delay3WordDatasec.
012BHRelay2 Hysteresis3WordData
012CHReservedWordData
012DHRelay2 FunctionWord0:Alarm / 1:Digital Output
012EHAnalog Output ParametersWordData
012FHAnalog Output LowWordData
0130HAnalog Output HighWordData
0131HLog PeriodWordDatasec.
0132HLog EventWord0:Off / 1:On
0133HLog Energy PeriodWordDatasec.
0134HLog Par 1WordData
0135HLog Par 2WordData
Data
014FHLog Par 28WordData
ReservedWordData
0156HDemand TimeWordDataminute
0157HHourWordDatah
0158HMinuteWordDatam
0159HSecondWordDatas
015AHReservedWordData
015BHDayWordDataday
015CHMonthWordDatamonth
015DHYearWordDatayear
015EHReservedWordData
015FHReservedWordData
0160HTotal Energy / SeparatelyWord0:Total/1:Separately
0161HSerial Number (1,2)Word (Hi/Lo)Char.1 / Char.2ASC II
0162HSerial Number (3,4)Word (Hi/Lo)Char.3 / Char.4ASC II
0163HSerial Number (5,6)Word (Hi/Lo)Char.5 / Char.6ASC II
0164HSerial Number (7,8)Word (Hi/Lo)Char.7 / Char.8ASC II
0165HInput 1 FunctionWord0:Real Time / 1:Lacth
0166HInput 2 FunctionWord0:Real Time / 1:Lacth
0167HAnalog Output TypeWord0:4-20mA / 1:0-20mA
0168HReservedWordData
0169HReservedWordData
016AHReservedWordData
016BHReservedWordData
016CHEnergy Counter UnitWord0:Kilo / 1:Mega

3.17 Setup Register Map (16 bit) (for MPR60S-41)

ADDRESS DESCRIPTIONDIMENSION(16bit)MULTIPLIERUNIT
0100HCurrent Transformer RatioWordData
0101HVoltage Transformer RatioWordData x 0.1
0102HNet TypeWord0:3P4W 1:3P3W 2:ARON
0103HReservedWordData
0104H3.Pulse-A Prm.WordDatakWh
0105H3.Pulse-A DurationWordDatams
0106H4.Pulse-R Prm.WordDatakVArh
0107H4.Pulse-R DurationWordDatams
0108HRelay1 Parameter1WordData
0109HRelay1 Hi1WordData
010AHRelay1 Lo1WordData
010BHRelay1 Delay1WordDatasec.
010CHRelay1 Hysteresis1WordData
010DHReservedWordData
010EHRelay1 Parameter2WordData
010FHRelay1 Hi2WordData
0110HRelay1 Lo2WordData
0111HRelay1 Delay2WordDatasec.
0112HRelay1 Hysteresis2WordData
0113HReservedWordData
0114HRelay1 Parameter3WordData
0115HRelay1 Hi3WordData
0116HRelay1 Lo3WordData
0117HRelay1 Delay3WordDatasec.
0118HRelay1 Hysteresis3WordData
0119HReservedWordData
011AHRelay1 FunctionWord0:Alarm / 1:Digital Output
011BHRelay2 Parameter1WordData
011CHRelay2 Hi1WordData
011DHRelay2 Lo1WordData
011EHRelay2 Delay1WordDatasec.
011FHRelay2 Hysteresis1WordData
0120HReservedWordData
0121HRelay2 Parameter2WordData
0122HRelay2 Hi2WordData
0123HRelay2 Lo2WordData
0124HRelay2 Delay2WordDatasec.
0125HRelay2 Hysteresis2WordData
0126HReservedWordData
0127HRelay2 Parameter3WordData
0128HRelay2 Hi3WordData
0129HRelay2 Lo3WordData
012AHRelay2 Delay3WordDatasec.
012BHRelay2 Hysteresis3WordData
012CHReservedWordData
012DHRelay2 FunctionWord0:Alarm / 1:Digital Output
012EHAnalog Output ParameterWordData
012FHAnalog Output LowWordData
0130HAnalog Output HighWordData
0131HLog PeriodWordDatasec.
0132HLog EventWord0:Off / 1:On
0133HLog Energy PeriodWordDatasec.
0134HLog Par 1WordData
0135HLog Par 2WordData
:::Data
014FHLog Par 28WordData
:ReservedWordData
0156HDemand TimeWordDataminute
0157HHourWordDatah
0158HMinuteWordDatam
0159HSecondWordDatas
015AHReservedWordData
015BHDayWordDataday
015CHMonthWordDatamonth
015DHYearWordDatayear
015EHReservedWordData
015FHReservedWordData
0160HTotal Energy / SeparatelyWord0:Total/1:Separately
0161HSerial Number (1,2)Word (Hi/Lo)Char.1 / Char.2ASC II
0162HSerial Number (3,4)Word (Hi/Lo)Char.3 / Char.4ASC II
0163HSerial Number (5,6)Word (Hi/Lo)Char.5 / Char.6ASC II
0164HSerial Number (7,8)Word (Hi/Lo)Char.7 / Char.8ASC II
0165HReservedWordData
0166HReservedWordData
0167HAnalog Output TypeWord0: 4-20mA / 1: 0-20mA
0168HReservedWordData
0169HReservedWordData
016AHReservedWordData
016BHReservedWordData
016CHEnergy Counter UnitWord0:Kilo / 1:Mega

4. GENERAL MENU

4.1 SETUP

In order for correct measurements and applications, make necessary configurations in the SETUP menu.

Sub-menus under the SETUP menu and settings are explained in detail below.

4.2 Network

In this menu, current transformer primary value, voltage transformer ratio and system connection type of device are set.

It has 5 sub-menus. "CT:......", "VT:......", "Net:......", "Eng:......", "E.Unit:......"

CT (Current Transformer Ratio)

The current transformer ratio is set between 1...5000.

ENTES MPR-60S-41 - CT (Current Transformer Ratio) - 1

flowchart
graph LR
    A["Energy Display"] --> B["Setup"]
    B --> C["Network"]
    C --> D["CT: 1"]

Figure 11: Setting the current transformer ratio

VT (Voltage Transformer Ratio)

The voltage transformer ratio can be adjusted between 1.0...4000.0

Please be careful that this value must be the voltage transformer ratio but not the value of the primary or secondary voltage.

ENTES MPR-60S-41 - VT (Voltage Transformer Ratio) - 1

flowchart
graph LR
    A["Energy Display"] --> B["Setup"]
    B --> C["Network Output"]

Figure 12: Setting the voltage transformer ratio

Net (Network Type)

The network type is set in this menu.

3P4W : 3 Phase + Neutral (Star connection)

3P3W : 3 Phase without Neutral (Delta connection)

ARON : ARON connection.

NOT: In 3P3W connections, as the neutral point is not connected, VLN voltages could be monitored different on unbalanced voltages.

ENTES MPR-60S-41 - Net (Network Type) - 1

flowchart
graph LR
    A["Energy Input"] --> B["Network Data Display"]
    B --> C["SETUP"]
    C --> D["Network Output"]
    D --> E["Net: 3P4W"]

Figure 13: Setting the type of system connection

Eng

If "Tol" menu is selected, device measures the reactive powers of the phases. If the total reactive power of the phases is inductive, it is recorded to the inductive area; If capacitive, it is recorded to the reactive area. If "Sprt" menu is selected, device measures the reactive powers of three phases for each phase separately. If it is in the inductive area, it is recorded to the inductive reactive area. If it is in the capacitive area, it is recorded to the capacitive reactive area.

Measurement for each phase separately can be done for 3P4W (3 Phase with Neutral) systems.

ENTES MPR-60S-41 - Eng - 1

flowchart
graph LR
    A["Energy Display"] --> B["Setup"]
    B --> C["Network"]
    C --> D["Ens: Tot"]

Figure 14: Setting the energy calculation type

E.Unit: (Energy Unit)

It is used for determine the units of energy counters. Counters can be chosen Mega or Kilo.

for example : If energy counter value is 12345678901 kWh

when "k" is chosen, 45678901 kWh will be displayed or

when "M" is chosen, 12345678 MWh will be displayed.

ENTES MPR-60S-41 - E.Unit: (Energy Unit) - 1

Warning :

You may quit all settings any time by ESC key.

You must record any change in the settings by menu key.

ENTES MPR-60S-41 - Warning : - 1

menu key.

4.3 Date and Time

It is essential to set the correct date and the time to obtain the right dates on the datalog menu Date (DD/MM/YYYY)

ENTES MPR-60S-41 - Date and Time - 1

flowchart
graph LR
    A["Energy Display"] --> B["Setup"]
    B --> C["Date"]

Figure 15: Setting the date

Time (Hour / Minute / Seconds)
ENTES MPR-60S-41 - Date and Time - 2

flowchart
graph LR
    A["Energy Display"] --> B["Setup"]
    B --> C["Time Measurement"]

Figure 16: Setting the time

4.4 RS-485 (PC Communication Settings)

All the measured parameters can be transferred to PC through the MPR-SW Software by MODBUS RTU Protocol. Device can be configured with PC through the MPR-SW Software.

It is necessary to set the Baud Rate, Address and Parity values to the device correctly.

RS-485 has 3 sub-menus "Addr: ...", "Bd: ...", "Prt: ..."

Addr (Address Information)

Address Information can be set between 1 and 247.

ENTES MPR-60S-41 - Addr (Address Information) - 1

flowchart
graph LR
    A["Energy Display"] --> B["Setup"]
    B --> C["RS-485"]
    C --> D["Addr: 1"]

Figure 17: Setting the address information

Bd (Baud Rate Value)

Baud rate is set between 1200 bps and 38400 bps.

ENTES MPR-60S-41 - Bd (Baud Rate Value) - 1

flowchart
graph LR
    A["Energy Display"] --> B["Setup"]
    B --> C["RS-485"]
    C --> D["Bd: 9600"]

Figure 18: Setting the baud rate value

ENTES MPR-60S-41 - Bd (Baud Rate Value) - 2

Warning :

You may quit all settings any time by ESC key.

You must record any change in the settings by

ENTES MPR-60S-41 - Warning : - 1

menu key.

Prt (Parity Settings)

Parity settings are set as none, even or odd.

ENTES MPR-60S-41 - Prt (Parity Settings) - 1

flowchart
graph LR
    A["Input"] --> B["MPR025 Network Analyzer"]
    B --> C["Energy Display with TWD I 142.8 L1 95.3 L2 127.9"]
    C --> D["Setup Display with TWD I 142.8 L1 95.3 L2 127.9"]
    D --> E["RS-485 Analyzer with TWD I 95.3 L2 127.9"]
    E --> F["Prt: None"]

Figure 19: Setting the Parity Settings
ENTES MPR-60S-41 - Prt (Parity Settings) - 2

IMPORTANT NOTE:

The "PARITY" should be selected as None in order to communicate with MPR-SW Software.

4.5 Datalog

Device records the chosen 28 parameters in its 1 MB memory with date and time stamp. The choice of the parameters and recording details are set in Datalog menu. These records can be monitored on the PC and not affected by energy cut off.

The "Datalog" menu has 30 sub-menus.

"Pr1:..." "Pr2:..." ...... "Pr28:...", "Per:", "Event:..."

"Pr1: ..." "Pr2: ..." ...... "Pr28:..." (Parameter Menus)

28 parameters can be associated with these sub menus with one parameter per each menu which will be recorded to memory

15.000 record lines can be stored in memory on the condition, where the total 28 parameters are called as one record line.

At 15.001st record, the first 1000 records are cleared automatically. And then, last record will be read as 14001th.

ENTES MPR-60S-41 - Datalog - 1

Note:

Even if less than 28 parameters are entered in sub menus, devices memory allocation is still for 28 parameters for each record line. So assigning less parameters do not increase memory capacity.

Parameter Settings
ENTES MPR-60S-41 - Note: - 1

flowchart
graph LR
    A["Energy Display"] --> B["Setup Display"]
    B --> C["Data Loss"]
    C --> D["Pr12 Q2 Output"]

Figure 20: Setting the "Pr12" Parameter

Per (Period Menu)

Period is the time interval between 2 consecutive records and can be set between 5 - 32.000 seconds.

If period is set to "off", then no parameters will be recorded.

ENTES MPR-60S-41 - Per (Period Menu) - 1

flowchart
graph LR
    A["Energy Input"] --> B["MFR025 Network Analyzer"]
    B --> C["SETUP"]
    C --> D["DataLos"]
    D --> E["Return to Data Loss"]

Figure 21: Setting the period time

ENTES MPR-60S-41 - Per (Period Menu) - 2

Warning :

You may quit all settings any time by ESC key.

You must record any change in the settings by → menu key.

ENTES MPR-60S-41 - Warning : - 1

Event

When "event" is on, the associated parameter array is recorded in case any of the output relays are switched on / off, regardless of period. So, the parameter values can be examined at the time of relay switching on.

ENTES MPR-60S-41 - Event - 1

flowchart
graph LR
    A["Energy Display"] --> B["Setup Display"]
    B --> C["DataLoss Event"]

Figure 22: Setting the event

4.6 1. Relay 1 and 2. Relay 2

Device has 2 relays (NO Normally open) for alarm outputs.

Any 3 parameters can be associated with any of the two relays at the same time. For each parameter, under, over, hysterisis and time delay values can be programmed. If the measured value of the set parameter exceeds the programmed values during the delay time, output relay switches on.

Relay 1 is switched on BPR015 Network Analyzer 235.4 236.5 223.7 VoltageA Relay 2 is switched on BPR015 Network Analyzer 235.4 236.5 223.7 VoltageA ESC ESC ESC ESC

Figure 23: Active relays are displayed on LCD.

The list of the parameters which can be associated with relays are marked with * on parameter table on page 41.

Relay 1 / (Relay 2) has 16 sub-menus.

Cfg: Configuration

Pr : Parameter

Hi : High (over)

Lo : Low (under)

Hs : Hysterisis

Dly : Time Delay

Menu of 1st Parameter

"Pr1:...", "Hi1:...", "Lo1:...", "Hs1:...", "Dly1:..."

Menu of 2nd Parameter

"Pr2:...", "Hi2:...", "Lo2:...", "Hs2:...", "Dly2:..."

Menu of 3rd Parameter

"Pr3:...", "Hi3:...", "Lo3:...", "Hs3:...", "Dly3:..."

Cfg (Configuration)

By this parameter, relays can be configured as "Alarm Output" (Cfg: Alarm) or as "Remote Control" (Cfg: DOut).

ENTES MPR-60S-41 - Cfg (Configuration) - 1

flowchart
graph LR
    A["Energy Display"] --> B["Setup"]
    B --> C["Relay1"]
    B --> D["Relay2"]
    C --> E["Cfs:Alrm"]
    D --> F["Cfs:DOut"]

Figure 24: Relay control type setting

ENTES MPR-60S-41 - Cfg (Configuration) - 2

ENTES MPR-60S-41 - Cfg (Configuration) - 3

flowchart
graph TD
    A["Pr1 (1st Parameter)"] --> B["Step 1: Setting of IL1 as the first parameter (Pr1) with 1.5 A < IL1 < 2.5 A having 20 mA hysteresis and 10 seconds delay time will be described. See Figure 25."]
    B --> C["Step 2: Setting of IL1 as the first parameter (Pr1) with 1.5 A < IL1 < 2.5 A having 20 mA hysteresis and 10 seconds delay time will be described. See Figure 25."]
    C --> D["Step 3: Setting of IL1 as the first parameter (Pr1) with 1.5 A < IL1 < 2.5 A having 20 mA hysteresis and 10 seconds delay time will be described. See Figure 25."]
    D --> E["Step 4: Setting of IL1 as the first parameter (Pr1) with 1.5 A < IL1 < 2.5 A having 20 mA hysteresis and 10 seconds delay time will be described. See Figure 25."]
    E --> F["Step 5: Setting of IL1 as the first parameter (Pr1) with 1.5 A < IL1 < 2.5 A having 20 mA hysteresis and 10 seconds delay time will be described. See Figure 25."]
    F --> G["Step 6: Setting of IL1 as the first parameter (Pr1) with 1.5 A < IL1 < 2.5 A having 20 mA hysteresis and 10 seconds delay time will be described. See Figure 25."]
    G --> H["Step 7: Setting of IL1 as the first parameter (Pr1) with 1.5 A < IL1 < 2.5 A having 20 mA hysteresis and 10 seconds delay time will be described. See Figure 25."]
    H --> I["Step 8: Setting of IL1 as the first parameter (Pr1) with 1.5 A < IL1 < 2.5 A having 20 mA hysteresis and 10 seconds delay time will be described. See Figure 25."]

Figure 25: Setting of IL1 as the first parameter with 1.5 A < IL1 < 2.5 A having 20 mA hysteresis and 10 seconds delay time.

ENTES MPR-60S-41 - Cfg (Configuration) - 4

Warning :

You may quit all settings any time by ESC key.

You must record any change in the settings by

ENTES MPR-60S-41 - Warning : - 1

menu key.

Hi1 (High / over value for the 1st parameter)

When the measured value is over the Hi1 value, Relay 1 (or Relay 2) is switched on complying with Hs1 (Hysterisis 1) and Dly1 (Delay 1) values.

ENTES MPR-60S-41 - Hi1 (High / over value for the 1st parameter) - 1

flowchart
graph LR
    A["(Hysterisis 1) and Dly1 (Delay 1) values."] --> B["Energy Display"]
    B --> C["Setup"]
    C --> D["Relay1 Output"]
    C --> E["Relay2 Output"]
    D --> F["Hi: ----"]
    E --> F

Figure 26: Setting the high (over) value for the 1st parameter

Lo1 (Low / under value for the 1st parameter)

When the measured value is under the Lo1 value, Relay 1 (or Relay 2) is switched on complying with Hs1 (Hysterisis 1) and Dly1 (Delay 1) values.

ENTES MPR-60S-41 - Lo1 (Low / under value for the 1st parameter) - 1

flowchart
graph LR
    A["(Hysterisis 1) and Dly1 (Delay 1) values."] --> B["Energy Display"]
    B --> C["Setup"]
    C --> D["Relay1 Output"]
    C --> E["Relay2 Output"]
    D --> F["Loi: ----"]

Figure 27: Setting the low (under) value for the 1st parameter

Hs1 (Hysteresis value for the 1st parameter)

This function is added to prevent system from unexpected oscillations during switch off.

When the switch off values of the associated parameters are over (or under) of Lo1 (or Hi1) values as the hysterisis value respectively, the Relay1 switches off.

ENTES MPR-60S-41 - Hs1 (Hysteresis value for the 1st parameter) - 1

flowchart
graph LR
    A["MPR005 Network Analyzer"] --> B["Energy Display"]
    B --> C["MPR005 Network Analyzer"]
    C --> D["SETUP"]
    D --> E["MPR005 Network Analyzer"]
    E --> F["Hs1: ----"]

Figure 28: Setting the hysteresis value for the 1st parameter

ENTES MPR-60S-41 - Hs1 (Hysteresis value for the 1st parameter) - 2

Warning :

You may quit all settings any time by ESC key.

You must record any change in the settings by menu key.

ENTES MPR-60S-41 - Warning : - 1

Dly1 (Delay time for the 1st parameter)

When the triggering signal is sent to the relay1, the relay1 will wait during the delay time before switching on. If the alarm signal is over during the delay time, the relay1 will not switch on.

ENTES MPR-60S-41 - Dly1 (Delay time for the 1st parameter) - 1

flowchart
graph LR
    A["NFR80S Network Analyzer"] --> B["NFR80S Network Analyzer"]
    B --> C["1. Relay1"]
    B --> D["2. Relay2"]
    C --> E["Dly1: ---"]
    D --> E

Figure 29: Setting the delay time for the 1st parameter.
ENTES MPR-60S-41 - Dly1 (Delay time for the 1st parameter) - 2

Warning

Where more than one parameter is associated with the output relay, and when the output relay is triggered by more than one measure, switch-off will be realized by the last remaining measure.

ENTES MPR-60S-41 - Warning - 1

flowchart
graph LR
    A["OR GATE"] --> B["Dly Time"]
    A --> C["Hys."]
    A --> D["Hold Reg."]
    E["Digital Output Control"] --> D
    B --> F["Output Relay"]
    C --> F
    D --> F

4.7 Pulse Outputs (3. Pulse A / 4. Pulse R) (MPR60S/MPR60S-21/41)

Device has 2 Pulse Outputs. It is possible to see, which one of these outputs generate pulse, from the LCD at any time.

A pulse has been generated from 3.Pulse A Output 23.2 95.7 73.4 Currents ESC A ▼ A pulse has been generated from 4.Pulse R Output 23.2 95.7 73.4 Currents ESC A ▼

Each time the consumed energy increases by an increment of "Prm", a pulse, as long as the "Dur" value entered (msec), is produced in the Pulse Outputs.

ENTES MPR-60S-41 - Pulse Outputs (3. Pulse A / 4. Pulse R) (MPR60S/MPR60S-21/41) - 2

line | Time (msec) | Energy | |-------------|--------| | 0 | 0 | | 3 | 1 | | 6 | 2 | | 9 | 3 | | 12 | 4 | | 15 | 5 | | 18 | 6 | | 21 | 7 | | 24 | 8 | | 27 | 9 | | 30 | 10 |

Figure 30: Energy - Pulse output graphic

ENTES MPR-60S-41 - Pulse Outputs (3. Pulse A / 4. Pulse R) (MPR60S/MPR60S-21/41) - 3

ENTES MPR-60S-41 - Pulse Outputs (3. Pulse A / 4. Pulse R) (MPR60S/MPR60S-21/41) - 4

Warning :

You may quit all settings any time by ESC key.

You must record any change in the settings by

ENTES MPR-60S-41 - Warning : - 1

menu key.

3. Pulse A (Import Active Energy Pulse Output) /

4. Pulse R (Inductive Reactive Energy Pulse Output)

A pulse is generated in 3. Pulse A relevant with the import active energy value or in 4. Pulse R relevant with the inductive reactive energy value. For example, a pulse for every increase of 10 kWh for 3. Pulse A or for every increase of 10 kVArh for 4. Pulse R.

  1. Pulse A (4. Pulse R) has 2 sub-menus. "Prm: ...", "Dur: ..."

Prm (Import Active / Inductive Reactive Energy Value to Set for 1 Pulse)

A pulse is generated from 3. Pulse A output for each increase of the Prm value by a desired amount (1 kWh...50.0 MWh / 1 kVArh...50.0 MVArh)

ENTES MPR-60S-41 - Prm (Import Active / Inductive Reactive Energy Value to Set for 1 Pulse) - 1

flowchart
graph LR
    A["Energy Input"] --> B["Energy Display"]
    B --> C["SETUP"]
    C --> D["Pulse A"]
    D --> E["Pulse R"]
    E --> F["Output: Prm: 1 kW"]

Figure 31: Setting the parameter value

Dur (Pulse Width in Miliseconds)

The pulse width is adjusted between 100 - 2500 msec.

ENTES MPR-60S-41 - Dur (Pulse Width in Miliseconds) - 1

flowchart
graph LR
    A["MFR02S Network Analyzer"] --> B["Energy"]
    B --> C["L1: 142.8, L2: 95.3, L3: 127.9"]
    C --> D["L1: 142.8, L2: 95.3, L3: 127.9"]
    D --> E["SETUP"]
    E --> F["L1: 142.8, L2: 95.3, L3: 127.9"]
    F --> G["3. Pulse A"]
    F --> H["4. Pulse R"]
    G --> I["Dur: 250"]
    H --> I

Figure 32: Setting the pulse width.

ENTES MPR-60S-41 - Dur (Pulse Width in Miliseconds) - 2

See page 33 for energy measurement.

Note : Even though the sub-menus under the 3. Pulse A and 4. Pulse R have the same names, these menus are independent of each other.

For Example:

It is possible to enter a specific parameter to the sub-menu "Prm" of 3. Pulse A and a different parameter to the sub-menu "Prm" of 4. Pulse R.

ENTES MPR-60S-41 - For Example: - 1

Warning :

You may quit all settings any time by ESC key.

You must record any change in the settings by

ENTES MPR-60S-41 - Warning : - 1

menu key.

4.8 Digital Inputs (3. Input-1 / 4. Input-2) (Only for MPR60S-10/20/40)

Device has 2 digital inputs. User can monitor the applied voltage to the input on the LCD display.

ENTES MPR-60S-41 - Digital Inputs (3. Input-1 / 4. Input-2) (Only for MPR60S-10/20/40) - 1

flowchart
graph LR
    A["MPR02S Network Analyzer"] --> B["Energy"]
    B --> C["MPR02S Network Analyzer"]
    C --> D["SETUP"]
    D --> E["MPR02S Network Analyzer"]
    E --> F["Fn:Real"]
    E --> G["MPR02S Network Analyzer"]
    G --> H["Fn:Latch"]

Figure 30: Setting the function value

- In order to configure Input-1 function, in 0165 H register:

- "0" has to be entered for Real Time and

- "1" has to be entered for Latch.

- In order to configure Input-2 function, in 0166 H register:

- "0" has to be entered for Real Time and

- "1" has to be entered for Latch.

ENTES MPR-60S-41 - Digital Inputs (3. Input-1 / 4. Input-2) (Only for MPR60S-10/20/40) - 2

line | Time | 3 Input-1 / 4 Input-2 Bits | Input: 5 24V DC max. 30V DC | |------|-----------------------------|------------------------------| | min | 0 | 0 | | 50 | 1 | 1 | | 1/4 | 1 | 1 | | 2/4 | 1 | 1 | | 3/4 | 1 | 1 | | max | 1 | 1 | | 30V | 1 | 1 | | max | 1 | 1 | | 50V | 1 | 1 | | max | 1 | 1 | | min | 0 | 0 |

Figure 31: Real Time function operation

- In order to reset input registers, which are set in latch function, "0" bit has to be written in I/O status register.

ENTES MPR-60S-41 - Digital Inputs (3. Input-1 / 4. Input-2) (Only for MPR60S-10/20/40) - 3

line | Input Event | I/O Status Register | Output Signal | |-------------|---------------------|---------------| | 3 Input-1 / 4 Input-2 Bits | 1 | 5 24V DC | | 3 Input-1 / 4 Input-2 Bits | 0 | 30V DC | | 3 Input-1 / 4 Input-2 Bits | 1 | min. 60 msec | | 3 Input-1 / 4 Input-2 Bits | 0 | Time |

Figure 32: Latch function type operation.

Addres: 004C H
131415 7891601152 4 3 2 1 0 0000000000 Input1 Relay2 Relay1

Input 1 and Input 2 register bits show inputs status.

ENTES MPR-60S-41 - Digital Inputs (3. Input-1 / 4. Input-2) (Only for MPR60S-10/20/40) - 5

Warning :

You may quit all settings any time by ESC key.

You must record any change in the settings by

ENTES MPR-60S-41 - Warning : - 1

menu key.

4.9 Display

In this menu, LCD display settings are configured. It has 3 sub-menus. "Loop: ...", "Cont: ...", "BL: ..."

Loop (Loop duration)

In this menu, the duration of displaying instantaneous value is adjusted automatically. The Loop duration can be adjusted as "No" or between 1...600 in terms of seconds.

For example; when the loop duration is set as 10sec. in the Instantaneous Values menu, if any button is not pressed during 10 sec. the Instantaneous values are displayed in sequence for 10 seconds periods.

By using this function all instantaneous values can be observed sequentially without pressing any buttons.

This function can be cancelled by selecting "No" option in the Loop Menu.

ENTES MPR-60S-41 - Loop (Loop duration) - 1

flowchart
graph LR
    A["Energy Input"] --> B["MPR05 Network Analyzer"]
    B --> C["Setup"]
    C --> D["Display"]
    D --> E["Loop: No"]

Figure 33: Setting the loop duration

Cont (Contrast - LCD Display Clarity Settings)

The value can be set between 1....6.

ENTES MPR-60S-41 - Cont (Contrast - LCD Display Clarity Settings) - 1

flowchart
graph LR
    A["Energy Input"] --> B["MPR025 Network Analyzer"]
    B --> C["SETUP"]
    C --> D["Display"]
    D --> E["Control: 6"]

Figure 34: Setting the contrast clarity

BL (Backlight)

Measured values can easily be read on the LCD screen even in dark environments with feature of the backlight function.

On : Backlight is On continuously.

Off : Backlight is Off continuously.

Auto : Backlight is switched on automatically when a button is pressed. It is switched off automatically at the end of 30 seconds if any button is not pressed again.

ENTES MPR-60S-41 - BL (Backlight) - 1

flowchart
graph LR
    A["Energy Input"] --> B["Energy Display"]
    B --> C["Display"]
    C --> D["Auto Output"]

Figure 35: Setting the contrast clarity

4.10 INSTANTANEOUS VALUES

This menu is the last menu that is reached by pressing ESC button while in any menu.

Also it is the main menu of device. If you wait a while without pressing any buttons in any menu, the Instantaneous value menu automatically comes back.

When device is energized for the first time, the device is in the Instantaneous values menu and shows the instantaneous values.

The display is seen as below.

MPRSS Network Analyzer L3 L2 L1 TND I L1 235.8 V L2 225.6 V L3 223.7 V Voltage h TND ESC VOUT

At the bottom of the screen, the active sub-menu is displayed. Each bar on the left indicates the ratio between total harmonic amount of current or voltage for each phase as a percentage value. Each step is 10%. It is possible to switch between "THD V" and "THD I" by ESC button. Also, it is possible to see the numerical values of the THD values by going to the Instantaneous Values Menu.

THD V : Total Harmonic Distortion of Voltage

THD I : Total Harmonic Distortion of Current

Note: When device's phase voltages exceed 330.0 V, phase-phase voltages exceed 530.0 V, phase currents exceed 5.500 A according to upper limits of measurement, "HIGH" is displayed on display.

By scrolling with ▲(UP), ▼(DOWN) buttons while in the Instantaneous Values Menu, the below parameters of the network are displayed.

Voltage_N^L - Voltage_L^L - Currents-P. Factor- Cosφ- Active (W)
Reactive (VAr)- Apparent (VA)- ΣPowers-Σ P.F.- THD V %- THD I %
Freq. Hz- Average_N^L - Average_L^L -ΣCurrent- In Neutral Current (A)

Voltager

VL1, VL2, VL3

Measured phase-neutral voltage value

MFROOS Network Analyzer L1 235.8 T L2 225.6 T L3 223.7 T Voltage h

Voltaget

VL1-2, VL2-3, VL3-1

Measured phase-phase voltage value

MFRGOS Network Analyzer L1-2 3834, L2-3 3812, L3-1 3860, Voltaget

Currents

IL1, IL2, IL3

Current measure of each phase

MPRSS Network Analyzer TWO 5 L1 123.2 1 L2 85.7 1 L3 93.4 1 Currents

P.Factor

PF L1, PF L2, PF L3

Power factor measure of all phases

MPRSS Network Analysis 0.98 0.97 0.95 P.Factor

Cosψ

Cosφ L1, Cosφ L2, Cosφ L3

MPFOS Network Analyzer 0.98 L1 0.96 L2 0.99 L3 Cosφ

Active

P L1, P L2, P L3

Active power measure of all phases

BPRGS Network Analyzer L1 175.3, L2 148.2, L3 95.7, Active

Reactive

Q L1, Q L2, Q L3

Reactive power measure of all phases

MPRSS Network Analyzer 112.8 kW 85.6 kW 73.4 kW Reactive

Apparent

S L1, S L2, S L3

Apparent power measure of all phases

ENTES MPR-60S-41 - Apparent power measure of all phases - 1

other BPRGS Network Analysis | Category | Value (%) | |---|---| | L1 | 10.2 | | L2 | 18.5 | | L3 | 22.3 | Apparent

ΣPowers ΣP, ΣQ, ΣS

Measured total active, total reactive and total apparent power values

ENTES MPR-60S-41 - ΣPowers ΣP, ΣQ, ΣS - 1

other MPPBOS Network Analyzer | Current (kW) | Power (kW) | | :--- | :--- | | 135.8 | 1 | | 873.0 | 1 | | 448.3 | 1 | ΣPowers

ΣP.F.

Total power factor values of all phases

MPRGS Network Analyzer Σ L1 L2 L3 100 ΣP . F . ESC A V W B

THD ∪%

The total harmonic values for voltages of each phase

MFR02 Network Analyzer THD V 25.7° L1 36.0° L2 14.5° L3 THD V%

THD 1%

The total harmonic values for currents of each phase

MFR02 Network Analyzer THD 23.1° L1 35.7° L2 11.5° L3 THD 1%

NOTES:

* If there is “-” symbol before the measured active power, it indicates the existence of active export power.
* When ARON connection is chose, "L2 ----" symbol is seen at the Currents. P.Factor, Cosφ. Active. Reactive. Placement THD I% DEMAND DEMAND DEMAND IL menus.
* The total current-voltage harmonic values are displayed in THD V% and THD I% menus as graphic bars on the left. Any time at the instantaneous values menu (except THD V% and THD I%), you can scroll between THD V and THD I with pressing ESC button. Harmonic menu can be used for watching the harmonic values detailed.

Freq. Hz

Frequency of the system.

(The frequency is measured from the L1 phase.)

MPEGOS Network Analyzer LY 50.1 Freq. Hz

Average

The average value of the measured phase-neutral voltages

KPROSS Network Analyzer L1 235.7 L2 L3 Average

Averaget

The average value of the measured phase-phase voltages

MPRSOS Network Analyzer L1-2 L2-3 385.4, L3-1 Averaget

ΣCurrent

The total current value of all phases

MPRGS Network Analyzer Σ L1 L2 L3 27.6μm ΣCurrent

MP60S Network Analyzer Σ L1 276 L2 L3 In:0.000

Watching the Values of the Other Parameters

Other parameters are grouped under the; ENERGY, DEMAND, TIME, DATE menus.

4.11 ENERGY

The Energy Values:

In this menu, below energy values are displayed and cleared.

Exp. Export Active Energy Imp. Import Active Energy

- Inductive Reactive Energy Capacitive Reactive Energy values

These energy values can be cleared one by one or all at once.

Imp. (Import Active Energy)
HP605 Network Analyzer 142.8 A 95.3 A 127.9 A ENERGY ESC ▲ ▼ ▼ ▼ BP605 Network Analyzer 225.8 A 227.3 A 218.6 A 00468173xW

Figure 36: Import Active Energy value

Clearing the Import Active Energy value
BPR05 Network Analyzer Th1 142.8 k L1 95.3 k L2 127.9 k L3 ENERGY BPR05 Network Analyzer Th1 225.8 k L1 227.3 k L2 218.6 k Imp 00468173:00 BPR05 Network Analyzer Th1 225.8 k L1 227.3 k L2 218.6 k Imp <-Clear? BPR05 Network Analyzer Th1 225.8 k L1 227.3 k L2 218.6 k Imp Clr?: Yes

Figure 37: Clearing the Import Active Energy value

Exp. (Export Active Energy value)
MFR05 Network Analyzer TND I 142.8 A LT 95.3 A L2 127.9 A L3 ENERGY MFR05 Network Analyzer TND I 225.8 A LT 227.3 A L2 218.6 A L3 00468173.0W MFR05 Network Analyzer TND I 225.8 A LT 227.3 A L2 218.6 A L3 00025342.0W

Figure 38: Export Active Energy value

Clearing the Export Active Energy value
MFR035 Network Analyzer THO 1 L1 L2 L3 142.8 95.3 127.9 ENERGY BFR035 Network Analyzer THO 1 L1 L2 L3 225.8 227.3 218.6 800253420W BFR035 Network Analyzer THO 1 L1 L2 L3 225.8 227.3 218.6 <-Clear? BFR035 Network Analyzer THO 1 L1 L2 L3 225.8 227.3 218.6 Cir?: Yes

Figure 39: Clearing the Export Active Energy value

Ind. (Inductive Reactive Energy)
EPR02S Network Analyzer TWO 1 L1 14.28 A L2 95.3 A L3 127.9 A ENERGY EPR02S Network Analyzer TWO 225.8 A L1 227.3 A L2 218.6 A L3 00468173 kW ESC ▲ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▶ EPR02S Network Analyzer TWO 225.8 A L1 227.3 A L2 218.6 A L3 00468173 kW ESC ▲ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ \u03b483276kWh

Figure 40: Inductive Reactive Energy value

ENTES MPR-60S-41 - The Energy Values: - 6
Warning :

You may quit all settings any time by ESC key.

You must record any change in the settings by

ENTES MPR-60S-41 - The Energy Values: - 7

menu key.

Clearing the Inductive Reactive Energy value
MPRSS Network Analyzer THC: 225.8 - 227.3 - 218.6 ENERGY MPRSS Network Analyzer THC: 225.8 - 227.3 - 218.6 02483276µm MPRSS Network Analyzer THC: 225.8 - 227.3 - 218.6 <-Clear? MPRSS Network Analyzer THC: 225.8 - 227.3 - 218.6 Clr?: Yes

Figure 41: Clearing the Inductive Reactive Energy value

Cap. (Capacitive Reactive Energy)
BFR025 Network Analyzer THO 1 L1 225.8 L2 227.3 L3 218.6 ENERGY BFR025 Network Analyzer THO 1 L1 225.8 L2 227.3 L3 218.6 00468173kW X 2 BFR025 Network Analyzer THO 1 L1 225.8 L2 227.3 L3 218.6 000 12278kW ESC A V S THO S W ESC A V S

Figure 42: Capacitive Reactive Energy value.

Clearing the Capacitive Reactive Energy value
MFR05 Network Analyzer TND 225.8 L1 227.3 L2 218.6 ENERGY X2 MFR05 Network Analyzer TND 225.8 L1 227.3 L2 218.6 -000 12278 kW MFR05 Network Analyzer TND 225.8 L1 227.3 L2 218.6 Imp: <-Clear? MFR05 Network Analyzer TND 225.8 L1 227.3 L2 218.6 Imp: Clr?: Yes

Figure 43: Clearing the Capacitive Reactive Energy value

Clearing all energy values (Exp, Imp, Ind, Cap)
MFR025 Network Analyzer TND 1 225.8, L1 227.3, L2 218.6, ENERGY MFR025 Network Analyzer TND 1 225.8, L1 227.3, L2 218.6, Imp. 00468173iW! MFR025 Network Analyzer TND 1 225.8, L1 227.3, L2 218.6, Imp. <-Clear?? MFR025 Network Analyzer TND 1 225.8, L1 227.3, L2 218.6, Imp. Clr ?: Yes MFR025 Network Analyzer TND 1 225.8, L1 227.3, L2 218.6, Imp. Clr ?: Yes MFR025 Network Analyzer TND 1 225.8, L1 227.3, L2 218.6, Clr ?: Yes

Figure 44: Clearing all energy values

ENTES MPR-60S-41 - The Energy Values: - 12

Warning :

You may quit all settings any time by ESC key.

You must record any change in the settings by menu key.

ENTES MPR-60S-41 - Warning : - 1

menu key.

4.13 DEMAND

Observing Demand, min. and max. Values

Demand : It shows the averages which arise on power and current during demand time.

min. value : It shows the min. value different from zero that measured on voltages.

max. value : It shows the max. value that measured on voltages.

*max.VL-N (max. voltage values between Phase-Neutral)

*min.VL-N (min. voltage values between Phase-Neutral)

*max. Demand IL (Max. demand values of phase currents)

*min. Demand IL (Min. demand values of phase currents)

*Demand IL (Demand values of phase currents)

*max. Demand ΣI and min. Demand ΣI (Total max. and min. demand values of phase current)

*Demand Σ IL (Demand value of total phase current)

*Demand ΣP, Demand ΣQ and Demand ΣS (Demand values of total power values)

max. Demand P , max. Demand Q and max. Demand S (Max. demand values of total powers)

min. Demand P , min. Demand Q and min. Demand S (Min. demand values of total powers)

Minimum, maximum and demand values can be cleared one by one or all at once.

MPR025 Network Analyzer L1 225.8 r L2 233.0 r L3 23.1.2 r ENERGY MPR025 Network Analyzer L1 225.8 r L2 233.0 r L3 23.1.2 r DEMAND MURPHY TWO SUNION TWO SUNION

Figure 45: Demand values

max. VLN (Max. values of the phase-neutral voltages)

MPRGS Network Analyzer 225.8 233.0 23.12 ENERGY MPRGS Network Analyzer 225.8 233.0 23.12 DEMAND MPRGS Network Analyzer 245.8 253.0 25.12 DEMAND

Figure 46: Max. VLN

Clearing the max. VLN (Max. values of the phase-neutral voltages)

MPROS Network Analyzer 225.8, 233.0, 231.2, ENERGY MPROS Network Analyzer 245.8, 253.0, 251.2, DEMAND MPROS Network Analyzer 245.8, 253.0, 251.2, Clear? MPROS Network Analyzer 245.8, 253.0, 251.2, Clr?: Yes

Figure 47: Clearing the max. VLN

Observing the min. VLN (Min. values of the phase-neutral voltages)

MPRGS Network Analyzer 225.8 233.0 231.2 ENERGY MPRGS Network Analyzer 245.8 253.0 251.2 DEMAND MPRGS Network Analyzer 205.3 212.5 198.6 DEMAND

Figure 48: Min. VLN value

ENTES MPR-60S-41 - Observing Demand, min. and max. Values - 5
Warning :
You may quit all settings any time by

You must record any change in the settings by
ENTES MPR-60S-41 - Observing Demand, min. and max. Values - 6
menu key.

Clearing the min. VLN (Min. values of the phase-neutral voltages)
MFRGS Network Analyzer 225.8, 233.0, 231.2, ENERGY MFRGS Network Analyzer 205.3, 212.5, 198.6, DEMAND MFRGS Network Analyzer 205.3, 212.5, 198.6, Clear? MFRGS Network Analyzer 205.3, 212.5, 198.6, Clr?: Yes

Figure 49: Clearing the min. V LN value

max. Demand IL (Max values of phase currents)
MFR025 Network Analyzer 225.8 233.0 231.2 ENERGY EKC TND MFR025 Network Analyzer 225.8 233.0 231.2 DEMAND EKC TND MFR025 Network Analyzer 245.8 253.0 251.2 DEMAND EKC TND MFR025 Network Analyzer 145.6 137.5 138.4 DEMAND

Figure 50: Max. Demand IL value

Clearing the max. Demand IL (Max values of phase currents)
MPR025 Network Analyzer THO 1 142.8 A L1 95.3 A L2 127.9 A ENERGY MPR025 Network Analyzer THO 145.6 A L1 137.5 A L2 138.4 A DEMAND MPR025 Network Analyzer THO 145.6 A L1 137.5 A L2 138.4 A Clear? MPR025 Network Analyzer THO 145.6 A L1 137.5 A L2 138.4 A Clear?: Cir?: Yes

Figure 51: Clearing the max. Demand II. value

min. Demand IL (Min values of phase currents)
MPR05 Network Analyzer 225.8, 233.0, 231.2, ENERGY MPR05 Network Analyzer 225.8, 233.0, 231.2, DEMAND MPR05 Network Analyzer 245.8, 253.0, 251.2, DEMAND MPR05 Network Analyzer 25.8, 33.6, 19.7 DEMAND

Figure 52: Min. Demand IL value

Clearing the min. Demand IL (Min values of phase currents)
MFR025 Network Analyzer THO 1 142.8 L1 95.3 L2 127.9 ENERGY MFR025 Network Analyzer THO 25.8 L1 33.6 L2 19.7 DEMAND MFR025 Network Analyzer THO 25.8 L1 33.6 L2 19.7 Clear? MFR025 Network Analyzer THO 25.8 L1 33.6 L2 19.7 Clr?: Yes

Figure 53: Clearing the min. Demand IL value

ENTES MPR-60S-41 - Observing Demand, min. and max. Values - 12
Warning :

You may quit all settings any time by ESC key.

You must record any change in the settings by menu key.

ENTES MPR-60S-41 - Observing Demand, min. and max. Values - 13

menu key.

Demand IL (Demand values of the currents)
MPR605 Network Analyzer 2258 2330 2312 ENERGY MPR605 Network Analyzer 2258 2330 2312 DEMAND MPR605 Network Analyzer 2458 2530 2512 DEMAND MPR605 Network Analyzer 956 874 1086 DEMAND

Figure 54: Demand IL

Clearing the Demand IL (Demand values of the currents)
MFP80S Network Analyzer Energy 142.8 95.3 127.9 MFP80S Network Analyzer Demand 95.6 87.4 108.6 Clear? 95.6 87.4 108.6 Clear?: 95.6 87.4 108.6 C1r?: Yes

Figure 55: Clearing the demand IL

Demand I , Min. / Max. Demand I (Demand, Min and max demand values of total phase currents)
MFR025 Network Analyzer Energy 142.8 95.3 127.9 TBD EPC A V MEAN MFR025 Network Analyzer Demand 95.6 87.4 108.6 TBD EPC A V MEAN MFR025 Network Analyzer Demand 245.8 253.0 251.2 TBD EPC A V MEAN MFR025 Network Analyzer Demand 42.15 79.1

Figure 56: Min. Demand / Demand Max. Σ |

Clearing Demand I , Min. / Max. Demand I (Demand, Min and max demand values of total phase currents)
MFR025 Network Analyzer THU 1 142.8 L1 95.3 L2 127.9 ENERGY MFR025 Network Analyzer THU 42.15 L1 79.1 DEMAND MFR025 Network Analyzer THU 42.15 L1 79.1 Clear? MFR025 Network Analyzer THU 42.15 L1 79.1 C1r?: Yes

Figure 57: Clearing the Min. Demand / Max. Demand Σ I

Demand Powers (Demand values of total powers)
Active (P), Reactive (Q) and Apparent (S) Powers
MPR025 Network Analyzer L1 142.8 A L2 95.3 A L3 127.9 A ENERGY MPR025 Network Analyzer L1 95.6 A L2 87.4 A L3 108.6 A DEMAND MPR025 Network Analyzer L1 245.8 A L2 253.0 A L3 251.2 A DEMAND MPR025 Network Analyzer L1 765.1 A L2 154.1 A L3 986.1 A DEMAND

Figure 58: Demand Σ Powers

Clearing the Demand Powers (Demand values of total powers)
MPR60S Network Analyzer 142.8 95.3 127.9 ENERGY MFR60S Network Analyzer 76.5 15.4 98.6 DEMAND MFR60S Network Analyzer 76.5 15.4 98.6 Clear? MFR60S Network Analyzer 76.5 15.4 98.6 Clr?: Yes

Figure 59: Clearing the Demand Σ Powers

Clearing All Demand values and Min. / Max. Values at Once
ENTES MPR-60S-41 - Observing Demand, min. and max. Values - 20

flowchart
graph LR
    A["Energy Conversion"] --> B["Energy Conversion"]
    B --> C{Clear?}
    C --> D["Energy Conversion"]
    D --> E{All!}
    E --> F["Energy Conversion"]

Figure 60: Clearing all demand values and min. / max. values at once

Max. Demand Powers (Max. demand values of total powers)
MPR05 Network Analyzer TWD 1 142.8 A L1 95.3 A L2 127.9 A ENERGY MPR05 Network Analyzer TWD 95.6 A L1 87.4 A L2 108.6 A L3 DEMAND MPR05 Network Analyzer TWD 245.8 A L1 253.0 A L2 251.2 A DEMAND MPR05 Network Analyzer TWD 76.5 A L1 15.4 A L2 98.6 A DEMAND

Figure 61: Max. demand value of Σ Powers

Max. Demand Powers (Clearing max. demand values of total powers)
MPROGS Network Analyzer Energy 142.8 95.3 127.9 ↑ MPROGS Network Analyzer Demand 76.5 15.4 98.6 ↑ MPROGS Network Analyzer Clear? 76.5 15.4 98.6 ↑ MPROGS Network Analyzer Clr?: Yes

Figure 62: Clearing max. demand values of Σ Powers

Min. Demand Powers (Min. demand values of total powers)
MFRGS Network Analyzer 142.8 A 95.3 A 127.9 A ENERGY MFRGS Network Analyzer 95.6 A 87.4 A 108.6 A DEMAND MFRGS Network Analyzer 245.8 A 253.0 A 251.2 A DEMAND MFRGS Network Analyzer 76.5 A 15.4 A 98.6 A DEMAND

Figure 63: Max. demand value of Σ Powers

Min. Demand Powers (Clearing min. demand values of total powers)
MPRGS Network Analyzer 142.8 95.3 127.9 ENERGY MPRGS Network Analyzer 76.5 15.4 98.6 DEMAND MPRGS Network Analyzer 76.5 15.4 98.6 Clear? MPRGS Network Analyzer 76.5 15.4 98.6 Clr?: Yes

Figure 64: Clearing max. demand values of Σ Powers

Clearing All Demand values and Min. / Max. Values at Once
ENTES MPR-60S-41 - Observing Demand, min. and max. Values - 25

flowchart
graph LR
    A["Energy Consumption"] --> B["Data Output"]
    B --> C{Clear?}
    C --> D["Output: MPRGS Network Analysis"]
    D --> E{Clr All!}
    E --> F{Clr?: Yes}

Figure 65: Clearing all demand values and min. / max. values at once

4.13 TIME AND DATE

Time and Date Menus

Time and Date, which are configured from the SETUP menu, are kept in the memory.

Even if the power is switched off, the informations of time and date are saved into the memory.

TIME (Menu for observing the time)
RF003 Network Analysis THB I L1 95.3 L2 127.9 ENERGY → RF003 Network Analysis THB I L1 95.3 L2 127.9 12:40:31 ESC ESC THD ISC

Figure 66: Time

Date (Menu for observing the date)
BFP605 Network Analysis TWD 1 142.8 A L1 95.3 A L2 127.9 A L3 ENERGY → BFP605 Network Analysis TWD 1 142.8 A L1 95.3 A L2 127.9 A L3 14/02/06 ESC A V B ESC A V B

Figure 67: Date

4.14 INFO

INFO

The information about the memory of the device and the manufacturer are seen in this menu.

Information menu has three sub-menus.

Log.Rec..... Eng. Rec.....Producer-Production Information.....

Log. Rec.:

This menu gives us information about the quantity of record lines of the parameters from Pr1 to Pr28 at the top line and indicates the occupied memory.

MPR025 Network Analyzer THD 1 142.8 A L1 L2 95.3 A L3 127.9 A ENERGY MPR025 Network Analyzer THD 1 142.8 A L1 L2 95.3 A L3 127.9 A INFO MPR025 Network Analyzer THD 1 14.76 A L1 L2 98.4 A L3 127.9 A LOA. Rec. EIG A V NEM

Figure 68: Info

Above, 14760 record lines are memorised and 98.4% of the memory is used.

See page 23 for Datalog Menu

Clearing all recorded parameters from Pr1 to Pr28 in Log. Rec. permanent memory
MFR025 Network Analysis 142.8 95.3 127.9 ENERGY 14.76 98.4* Los.Rec. MFR025 Network Analysis 14.76 98.4* Clr All! MFR025 Network Analysis 14.76 98.4* Clr?: Yes

Figure 69: Clearing all recorded parameters

Eng. Rec. (Energy recording)

Device records all energy values ( Export Active, Import Active, Inductive Reactive, Capacitive Reactive) in the permanent memory for energy values in every 15 minutes.

1.000 record lines are allocated for energy values. When this area is filled, all energy recordings are cleared to enable further records.

ENTES MPR-60S-41 - Eng. Rec. (Energy recording) - 1

Note: Allocated areas for parameter and energy values are independent from each others. The permanent memory is not affected from power cuts.

BPRSOS Network Analyzer THD I 142.8 A L1 95.3 L2 127.9 ENERGY THD I 142.8 A L1 95.3 L2 127.9 INFO THD I 142.8 A L1 95.3 L2 127.9 INFO THD I 142.8 A L1 95.3 L2 127.9 INFO THD I 142.8 A L1 95.3 L2 127.9 INFO THD I 142.6 A L1 95.3 L2 127.9 INFO THD I 142.6 A L1 95.3 L2 127.9 INFO THD I 142.6 A L1 95.3 L2 127.9 INFO THD I 142.6 A L1 95.3 A L2 127.9 A INFO THD I 142.6 A L1 95.3 A L2 127.9 A INFO THD I 142.6 A L1 95.3 A L2 127.9 A INFO THD I 142.6 A L1 95.3 A L2 127.9 A INFO Thd I 142.6 A L1 95.3 A L2 127.9 A INFO Thd I 142.6 A L1 95.3 A L2 127.9 A INFO Thd I 142.6 A L1 95.3 A L2 127.9 A INFO Thd I 13 A L1 95.3 A L2 127.9 A INFO Thd I 13 A L1 95.3 A L2 127.9 A INFO Thd I 13 A L1 95.3 A L2 127.9 A INFO Thd I 13 A L1 95.3 A L0 Rec. BPRSOS Network Analyzer THD I 147.6 A L1 95.3 A L2 127.9 A INFO THD I 147.6 A L1 95.3 A L2 127.9 A INFO THD I 147.6 A L0 Rec. BPRSOS Network Analyzer THD I 113 A L1 95.3 A L2 127.9 A INFO THD I 113 A L0 Rec. BPRSOS Network Analyzer

Figure 70: Energy records

Above, 113 record lines are memorised and 11.3% of the memory is used.

Clearing all recorded parameters from Pr1 to Pr28 in the Eng. Rec. permanent memory
MFR05 Network Analyzer 142.8 95.3 127.9 ENERGY 113 11.3* Ens.Rec. MFR05 Network Analyzer 113 11.3* Clr All! MFR05 Network Analyzer 113 11.3* Clr? Yes

Figure 71: Clearing all recorded parameters in the Eng. Rec. permanent memory

ENTES MPR-60S-41 - Eng. Rec. (Energy recording) - 4

Note : If data records, which are saved in to the permanent memory for every 15 minutes in Eng.Rec. Menu, are cleared, energy values are not affected from this event.

4.15 Manufacturer - Product Information

Information about manufacturer, the version number of the device, company contact information and serial number (8 digit) are on this menu.

MFR025 Network Analyzer TND I 142.8 L1 95.3 L2 127.9 L3 ENERGY MFR025 Network Analyzer TND I 142.8 L1 95.3 L2 127.9 L3 INFO MFR025 Network Analyzer 14.76k 98.4* Los.Rec. MFR025 Network Analyzer TND I 142.8 L1 95.3 L2 127.9 L3 ENTES.AS

Figure 72: Manufacturer - Product Information

4.16 PASSWORD

User password is set and activated in this menu.

In order to prevent the device's SETUP, DEMAND and ENERGY menus from unauthorized access, it is necessary to set up a 3 digit user password and then activate it.

Set Psw (Menu for setting up a user password)

ENTES MPR-60S-41 - Set Psw (Menu for setting up a user password) - 1

flowchart
graph LR
    A["Start"] --> B["UPR60S Network Analyzer"]
    B --> C["UPR60S Network Analyzer"]
    C --> D["UPR60S Network Analyzer"]
    D --> E["Set Psw"]
    E --> F["UPR60S Network Analyzer"]
    F --> G["New 000"]

Figure 73: Setting the password

Chg Psw (Menu for changing the user password)

The new password is saved to the SETUP, DEMAND and ENERGY menus.

ENTES MPR-60S-41 - Chg Psw (Menu for changing the user password) - 1

flowchart
graph TD
    A["Energy"] --> B["Setup"]
    B --> C["Psw: 000"]
    C --> D["New: 999"]

Figure 74: Changing the password

Main Password: 236

4.17 PARAMETER TABLE

The parameters, that can be set, are marked with an * symbol in the parameter table.

*VL1, L2, L3(Phase Voltage)
*VL12, L23, L31(Phase-Phase Voltage)
*VN (Average)(Total Phase Voltage Average)
*VL (Average)(Total Phase-Phase Voltages Average)
*Freq.Hz(Frequency)
*IL1, L2, L3(Phase Currents)
*ΣI(Total Phase Currents)
*PL1, L2, L3(W)(Acive Power)
*QL1, L2, L3(VAr)(Reactive Power)
*SL1, L2, L3(VA)(Apparent Power)
*ΣP. (W)(Total Active Power)
*ΣQ. (VAr)(Total Reactive Power)
*ΣS. (VA)(Total Apparent Power)
*COSφL1, L2, L3(Displacement Power Factor)
*PFL1, L2, L3(Power Factor)
ΣP. F(Total Power Factor)
Exp.(KWh)(Export Active Energy)
Imp.(KWh)(Import Active Energy)
Ind. (KVArh)(Inductive Reactive Energy)
Cap.(KVArh)(Capacitive Reactive Energy)
*H-VL1, L2, L3(Harmonic Values for Voltages)
*H-IL1, L2, L3(Harmonic Values for Currents)
*Max.VLN(Maksimum Phase Voltage)
*Min. VIN(Minimum Phase Voltage)
*Max. Demand IL(Max. Demand of Phase Currents)
*Min. Demand IL(Min. Demand of Phase Currents)
*Max. Demand ΣI(Max. Demand of Total Phase Currents)
*Min. Demand ΣI(Min. Demand of TotalPhase Currents)
*Demand IL(Demand of Phase Currents)
*Demand ΣIL(Demand of Total Phase Currents)
*Demand ΣW(Demand of Total Active Powers)
*Demand ΣVAr(Demand of Total Reactive Powers)
*Demand ΣVA(Demand of Total Apparent Powers)
Hr.(Hour)
Min.(Minute)
Sec.(Second)
Day(Day)
Mo.(Month)
Year(Year)
CTR(Current Transformer Ratio)
VTR(Voltage Transforemr Ratio)
IOS(Relay Position)
*In(Neutral Current)
Max. Demand ΣW(Max. Demand of Total Active Powers)
Max. Demand ΣVAr(Max. Demand of Total Reactive Powers)
Max. Demand ΣVA(Max. Demand of Total Apparent Powers)
Min. Demand ΣW(Min. Demand of Total Active Powers)
Min. Demand ΣVAr(Min. Demand of Total Reactive Powers)
Min. Demand ΣVA(Min. Demand of Total Apparent Powers)

4.18 FORMULAS

RMS Values for Voltages V_rms = 1N_i=0^Nv^2 RMS Values for Currents I_rms = 1N_i=0^Nt_i^2
Total Active Power P = 1N_i=0^Np_i Total Reactive Power Q = 1N_i=0^Nq_i
Apparent Power S = P^-2 + Q^2 Total Power Factor P.F = P S
Total Harmonic Distortion for Voltages V_THD% = _i=2^31V_i^2V_i × 100
Total Harmonic Distortion for Currents I_THD% = _i=2^31I_i^2I_i × 100

4.19 Current Analog Output (0/4-20mA) (Only for MPR60S-40/41)
ENTES MPR-60S-41 - FORMULAS - 1

flowchart
graph LR
    A["Energy Display"] --> B["Setup"]
    B --> C["Anls.Out"]
    C --> D["Output: Type0-20"]

In device, this feature gives the possibility that observing the measured values by other devices with converting these values in to 0-20 mA or 4-20 mA current data. The below parameters can be set as analog output in device.

The below parameters can be set as analog output :

VL1, L2, L3 (V) (Phase Voltage)

VL12, L23, L31 (V) (Phase-Phase Voltage)

V. (Average) (Average of the total phase voltages)

V. (Average) (Average of the total phase-phase voltages)

Frequency (Hz) (Frequency)

L1, L2, L3 (A) (Phase Currents)

THD %VL1, L2, L3 (Total Harmonic Values for Voltages)

THD %| L1, L2, L3 (Total Harmonic Values for Currents)

PL1, L2, L3 (W) (Active Power)

QL1, L2, L3 (VAr) (Reactive Power)

SL1, L2, L3 (VA) (Apparent Power)

Σl. (A) (Total Phase Currents)

ΣP. (W) (Total Active Power)

ΣQ. (VAr) (Total Reactive Power)

ΣS. (VA) (Total Apparent Power)

For example

Below settings should be fulfilled as like :

Type : 0-20 mA

After above settings are completed;

Analog current output's value will be 0 mA when VL1 value is 0 V,

Analog current output's value will be 20 mA when VL1 value is 300 V.

When VL1 is 220 V analog voltage output value will be;

$$ \mathrm{Iout} = \frac {(2 0 - 0) \times (2 2 0 - 0)}{(3 0 0 - 0)} = 1 4, 6 7 \mathrm{mA} $$

For example

Below settings should be fulfilled as like :

Type : 0-20 mA

After above settings are completed;

Analog current output's value will be 0 mA when PL1 value is -650 W,

Analog current output's value will be 20 mA when PL1 value is 350 W

When PL1 is -300 W analog voltage output value will be;

$$ \text { lout } = \frac {(2 0 - 0) \times [ - 3 0 0 - (- 6 5 0) ]}{[ 3 5 0 - (- 6 5 0) ]} = 7 \mathrm{mA} $$

MFTRECS Network Analyzer Prms VL1

MIPRESS Network Analyzer Lo : 0 v

MFPRESS Network Analyzer Hi : 300 V

3 Phase with neutral connection Current Measurement Inputs Voltage Measurement Inputs Analog Out RS-485 1 2 3 4 5 6 L1 L2 L3 L4 L5 L6 L1 L2 L3 L4 L5 L6 1. Relay 1. Relay 2 2. Pulse 4. Pulse 5 External Supply L1 N Analog Out RS-485 11 12 13 14 15 16 - + GND A B TR

4.20 Voltage Analog Output (0/2-10V) (Only for MPR60S-20/21)

ENTES MPR-60S-41 - Voltage Analog Output (0/2-10V) (Only for MPR60S-20/21) - 1

flowchart
graph LR
    A["Energy Display"] --> B["Setup"]
    B --> C["Analysis Setup"]
    C --> D["Type 2-10 Analyzer"]

In device, this feature gives the possibility that observing the measured values by other devices with converting these values in to 0-10 V or 2-10 V voltage data. The below parameters can be set as analog output in device.

The below parameters can be set as analog output :

V_L1, L2, L3 (V) (Phase Voltage)

VL12, L23, L31 (V) (Phase-Phase Voltage)

V. 1N (Average) (Average of the total phase voltages)

V. E (Average) (Average of the total phase-phase voltages)

Frequency (Hz) (Frequency)

L1, L2, L3 (A) (Phase Currents)

THD %VL1, L2, L3 (Total Harmonic Values for Voltages)

THD %I L1, L2, L3 (Total Harmonic Values for Currents)

PL1, L2, L3 (W) (Active Power)

QL1, L2, L3 (VAr) (Reactive Power)

SL1, L2, L3 (VA) (Apparent Power)

Σl. (A) (Total Phase Currents)

ΣP. (W) (Total Active Power)

ΣQ. (VAr) (Total Reactive Power)

ΣS. (VA) (Total Apparent Power)

For example

Below settings should be fulfilled as like :

Type : 2-10 V

After above settings are completed;

Analog voltage output's value will be 2 V when L1 value is 100mA,

Analog voltage output's value will be 10 V when IL1 value is 5 A.

When IL1 is 3.5 A analog voltage output value will be;

$$ \text { I o u t } = \frac {(1 0 - 2) \times (3 . 5 - 0 . 1)}{(5 - 0 . 1)} + 2 = 7. 5 5 1 \mathrm{V} $$

For example

Below settings should be fulfilled as like :

Type : 0-10 V

Prm (Parameter) : SQ

Lo(Low value) : -250 VAr

Hi (High value) : 750 VAr

After above settings are completed;

Analog voltage output's value will be 0 V when SQ value is -250 VAr,

Analog voltage output's value will be 10 V when SQ value is 750 VAr.

When SQ is 400 VAr analog voltage output value will be;

$$ \text { I o u t } = \frac {(1 0 - 0) \times [ 4 0 0 - (- 2 5 0) ]}{[ 7 5 0 - (- 2 5 0) ]} = 6. 5 \mathrm{V} $$

3 Phase with neutral connection L1 L2 L3 L4 L5 L6 Current Measurement Inputs Voltage Measurement Inputs Analog Out RS-485 External Supply Analog Out RS-485 11 12 13 14 15 16 - + GND A B TR L1 L2 L3 L4 L5 L6 1.0V/1.2 V/2.1 2.0V/2.2 V/3.1 2.0V/2.3 V/4.1 2.0V/2.5 V/6.1 K N

4.21 FACTORY SETTINGS

Network

CT (Current transformer) : 10
VT ( Voltage transformer): 1.0
Net (System Connection) : 3P4W
Eng (Energy): Tot.
E.Unit (Energy Unit): k

Display

Loop (Loop duration): No
Cont (Contrast): 6
BL. (Backlight): Auto

RS-485

Addr (Address): 1
Bd (Baud rate value): 9600 bps
Prt (Parity): None

Datalog

Per (Period): 900 sec.
Event: No
Pr1(Parameter 1): VL1
Pr2(Parameter 2): VL2
Pr3(Parameter 3): VL3
Pr4(Parameter 4): IL1
Pr5(Parameter 5): IL2
Pr6(Parameter 6): IL3
Pr7(Parameter 7): ΣI
Pr8(Parameter 8): P1
Pr9(Parameter 9): P2
Pr10(Parameter 10): P3
Pr11(Parameter 11): Q1
Pr12(Parameter 12): Q2
Pr13(Parameter 13): Q3
Pr14(Parameter 14): S1
Pr15(Parameter 15): S2
Pr16(Parameter 16): S3
Pr17(Parameter 17): PF1
Pr18(Parameter 18): PF2
Pr19(Parameter 19): PF3
Pr20(Parameter 20): Cos1
Pr21(Parameter 21): Cos2
Pr22(Parameter 22): Cos3
Pr23(Parameter 23): V12
Pr24(Parameter 24): V23
Pr25(Parameter 25): V31
Pr26(Parameter 26): VN
Pr27(Parameter 27): VL
Pr28 (Parameter 28): Freq.

1.Relay1

Cfg: Digital Output
Pr1,Pr2,Pr3 (Parameters): Off
Hi1,Hi2,Hi3 (High): - - - -
Lo1,Lo2,Lo3 (Low): - - - -
Hs1,Hs2,Hs3 (Hysterisis): - - - -
Dly1,Dly2,Dly3 (Delay): - - - -

2.Relay 2

Cfg: Digital Output
Pr1,Pr2,Pr3 (Parameters) : Off
Hi1,Hi2,Hi3 (High) : - - - -
Lo1,Lo2,Lo3 (Low) : - - - -
Hs1,Hs2,Hs3 (Hysterisis) : - - - -
Dly1,Dly2,Dly3 (Delay) : - - - -
  1. Pulse A (only for MPR60S/MPR60S-21/41)
Prm(Energy value to set for 1 pulse) : 1 kWh
Dur ( Pulse width) : 250 msec.
  1. Pulse R (only for MPR60S/MPR60S-21/41)
Prm(Energy value to set for 1 pulse) : 1 kVArh Dur (Pulse width) : 250 msec.
  1. Input-1 (only for MPR60S-10/20/21)
Fn : Real Time
  1. Input-2 (only for MPR60S-10/20/21)
Fn : Real Time

Current Analog Output (only for MPR60S-40/41)

Voltage Analog Output (only for MPR60S-20/21)

Set Psw (Setting up the password) : None (000)

4.22 TECHNICAL DATA

Operating Voltage (Un) : Please look behind the device.

Frequency:50760Hz

Power Consumption : < 6 VA

Burden : < 1 VA (Current Burden)

: < 0.5 VA (Voltage Burden)

Measurement Input

Voltage

: 1,0 - 300,0 V AC (L-N)

: 2,0 - 500,0 V AC (L-L)

Current : 0,005 - 5.5 A

Measurement Ranges

Frequency : 45,0 - 65,0 Hz

Power:0-4000 M (W, VAr, VA)

Energy : 0 - 99 999 999 kWh, kVArh or MWh, MVArh

Measurement Category: CAT III

Accuracy

Voltage, Current : 0.5%±2digit

Active Power : 1%±2digit

Reactive, Apparent Power : 2%±2digit

Voltage Transformer Ratio : 1,0...4000,0

Current Transformer Ratio:1...5000

Connection Type: 3P-4W, 3P-3W, ARON

Relay Outputs (2 pcs.)

Demand Time

Communication Interface

Baud Rate

Address

Parity

Data Logging

Parameters

Record Size

Log Duration

(time interval between 2 records)

Energy Record

Event

Memory

Digital Inputs (2 pcs.)

Functions

Input Pulse Width

Operation Voltage

Energy Pulse Outputs (2 pcs.)

Switch Period

Pulse Width

Operation Current

Operation Voltage

Analog Voltage Output

Load Resistance

Response Perriod

Analog Current Output

Load Resistance

Response Perriod

Real Time Clock

Ambient Temperature

Display

Dimensions

Equipment Protection Class

Box Protection Class

Terminal Block Protection Class

Box Material

Installation

Wire Thickness for Voltage Connection

Wire Thickness for Current Connection

Wire Thickness for Pulse or

Digital Input Connection

RS-485 Connection

Weight

Installation Category

Type

Package Dimensions

Package Weight

Pcs për Package

2 NO, 5A, 1250 VA

15 min.

MODBUS RTU (RS-485)

1200 - 38400 bps

1 - 247

None, Even, Odd Parity

Choosen 28 parameters with date and time

15000 record lines

No, 5 - 32.000 seconds

1000 record lines (1 record in every 15 minutes)

Yes, No

1 MB Internal Memory

Real Time / Latch

Min. 50 ms

5...24 V DC, max. 30 V DC

Min. 1 sec.

100-2500 ms

Max. 50 mA

5-24 V DC max. 30 V DC

0-10 V or 2-10 V

≥5 kΩ

1 sec

0-20 mA or 4-20 mA

≤500 Ω

1 sec.

3,6" LCD with Backlight

PR19

Double Insulation-Class II (☐)

IP 40

IP 00

Non-flammable

Flush mounting with rear terminals

2,5 mm²

4.0 mm²

1.5 mm²

Category 5 Cable (Shielded Twisted Pair)

0.75 kg

Class II

PR 19

280x280x265 mm

6 kg

8 pcs

5. Standarts and Explanations

EN 61000-6-2 : Electromagnetic compatibility (EMC). Generic standards. Immunity for industrial environments.

EN 61000-6-4 : Electromagnetic compatibility (EMC). Generic standards. Emission standard for industrial environments.

EN 55016-2-1 : Specification for radio disturbance and immunity measuring apparatus and methods. Methods of measurement of disturbances and immunity. Conducted disturbance measurements.

EN 55016-2-3 : Specification for radio disturbance and immunity measuring apparatus and methods. Methods of measurement of disturbances and immunity. Radiated disturbance measurements.

EN 55011 : Limits and methods of measurement of radio disturbance characteristics of industrial, scientific and medical (ISM) radio-frequency equipment.

EN 61000-3-2 : Electromagnetic compatibility (EMC). Limits for harmonic current emissions (equipment input current < 16A per phase)

EN 61000-3-3 : Electromagnetic compatibility (EMC) - Part 3-3: Limits - Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems, for equipment with rated current = 16 A per phase and not subject to conditional connection.

EN 61010-1 : Safety requirements for electrical equipment for measurement, control, and laboratory use - Part 1: General requirements.

EN 61000-4-2 : Elektrostatic discharge immunity test.

EN 61000-4-3 : Radiated RF electromagnetic field immunity test.

EN 61000-4-4 : Electrical fast transient/burst immunity test.

EN 61000-4-5 : Surge immunity test.

EN 61000-4-6 : Immunity to RF conducted disturbances.

EN 61000-4-8 : Power frequency magnetic field immunity test.

EN 61000-4-11 : Voltage dips, short interruptions and voltage variations immunity test.

MPR60S MENU MAP

INSTANT VALUES
ENTES MPR-60S-41 - MPR60S MENU MAP - 1

flowchart
graph TD
    A["Voltage"] --> B["Energy"]
    C["Voltage"] --> B
    D["Current"] --> B
    E["P.Factor"] --> B
    F["Cose"] --> B
    G["Active"] --> B
    H["Reactive"] --> B
    I["Apparent"] --> B
    J["F.Powers"] --> B
    K["SPF"] --> B
    L["THD V%"] --> M["DEMAND"]
    N["THD P%"] --> M
    O["Freq. Hz"] --> P["SETUP"]
    Q["AverageS"] --> P
    R["AverageI"] --> P
    S["Current"] --> P
    T["Energy"] --> U["DET"]
    U --> V["SETUP"]
    V --> W["TIME"]
    W --> X["INFO"]
    X --> Y["Display"]
    Y --> Z["RS-485"]
    Z --> AA["Setup"]
    AA --> AB["Reset2"]
    AB --> AC["Reset2"]
    AC --> AD["Reset2"]
    AD --> AE["Reset2"]
    AE --> AF["Reset2"]
    AF --> AG["Reset2"]
    AG --> AH["Reset2"]
    AH --> AI["Reset2"]
    AI --> AJ["Reset2"]
    AJ --> AK["Reset2"]
    AK --> AL["Reset2"]
    AL --> AM["Reset2"]
    AM --> AN["Reset2"]
    AN --> AO["Reset2"]
    AO --> AP["Reset2"]
    AP --> AQ["Reset2"]
    AQ --> AR["Reset2"]
    AR --> AS["Reset2"]
    AS --> AT["Reset2"]
    AT --> AU["Reset2"]
    AU --> AV["Reset2"]
    AV --> AW["Reset2"]
    AW --> AX["Reset2"]
    AX --> AY["Reset2"]
    AY --> AZ["Reset2"]
    AZ --> BA["Reset2"]
    BA --> BB["Reset2"]
    BB --> BC["Reset2"]
    BC --> BD["Reset2"]
    BD --> BE["Reset2"]
    BE --> BF["Reset2"]
    BF --> BG["Reset2"]
    BG --> BH["Reset2"]
    BH --> BI["Reset2"]
    BI --> BJ["Reset2"]
    BJ --> BK["Reset2"]
    BK --> BL["Reset2"]
    BL --> BM["Reset2"]
    BM --> BN["Reset2"]
    BN --> BO["Reset2"]
    BO --> BP["Reset2"]
    BP --> BQ["Reset2"]
    BQ --> BR["Reset2"]
    BR --> BS["Reset2"]
    BS --> BT["Reset2"]
    BT --> BU["Reset2"]
    BU --> BV["Reset2"]
    BV --> BW["Reset2"]
    BW --> BX["Reset2"]
    BX --> BY["Reset2"]
    BY --> BZ["Reset2"]
    BZ --> CA["Reset2"]
    CA --> CB["Reset2"]
    CB --> CC["Reset2"]
    CC --> CD["Reset2"]
    CD --> CE["Reset2"]
    CE --> CF["Reset2"]
    CF --> CG["Reset2"]
    CG --> CH["Reset2"]
    CH --> CI["Reset2"]
    CI --> CJ["Reset2"]
    CJ --> CK["Reset2"]
    CK --> CR["Reset2"]
    CR --> CS["Reset2"]
    CS --> CT["Reset2"]
    CT --> CU["Reset2"]
    CU --> CV["Reset2"]
    CV --> CW["Reset2"]
    CW --> CX["Reset2"]
    CX --> CY["Reset2"]
    CY --> CZ["Reset2"]
    CZ --> DA["Reset2"]
    DA --> DB["Reset2"]
    DB --> DC["Reset2"]
    DC --> DD["Reset2"]
    DD --> DE["Reset2"]
    DE --> DF["Reset2"]
    DF --> DG["Reset2"]
    DG --> DH["Reset2"]
    DH --> DI["Reset2"]
    DI --> DJ["Reset2"]
    DJ --> DK["Reset2"]
    DK --> DL["Reset2"]
    DL --> DV["Reset2"]
    DV --> DW["Reset2"]
    DW --> DX["Reset2"]
    DX --> DXB["Reset2"]
    DXB --> DXC["Reset2"]
    DXC --> DXD["Reset2"]
    DXD --> DXE["Reset2"]
    DXE --> DXF["Reset2"]
    DXF --> DXG["Reset2"]
    DXG --> DXH["Reset2"]
    DXH --> DXI["Reset2"]
    DXI --> DXJ["Reset2"]
    DXJ --> DXK["Reset2"]
    DXK --> DXL["Reset2"]
    DXL --> DXM["Reset2"]
    DXM --> DXN["Reset2"]
    DXN --> DXO["Reset2"]

INSTANT VALUES
ENTES MPR-60S-41 - MPR60S MENU MAP - 2

flowchart
graph TD
    A["Voltage k"] --> B["Energy"]
    C["Voltage l"] --> B
    D["Currents"] --> B
    E["P. Factor"] --> B
    F["Cose"] --> B
    G["Active"] --> B
    H["Reactive"] --> B
    I["Apparent"] --> B
    J["L. Powers"] --> B
    K["ΔP.F."] --> L["SETUP"]
    M["THD V%"] --> L
    N["THD 1%"] --> L
    O["Freq. Hz"] --> P["TIME"]
    Q["Everage k"] --> P
    R["Average t"] --> P
    S["Current"] --> P
    T["Energy"] --> U["Demand"]
    U --> V["SETUP"]
    V --> W["Time"]
    W --> X["INFO"]
    X --> Y["Log Rec"]
    X --> Z["Ver."]
    Y --> AA["Log Rec"]
    Y --> AB["Clear"]
    Y --> AC["Clear"]
    U --> AD["Password Defined"]
    U --> AE["Password Defined"]
    U --> AF["Password Defined"]
    U --> AG["Password Defined"]
    U --> AH["Password Defined"]
    U --> AI["Password Defined"]
    U --> AJ["Password Defined"]
    U --> AK["Password Defined"]
    U --> AL["Password Defined"]
    U --> AM["Password Defined"]
    U --> AN["Password Defined"]
    U --> AO["Password Defined"]
    U --> AP["Password Defined"]
    U --> AQ["Password Defined"]
    U --> AR["Password Defined"]
    U --> AS["Password Defined"]
    U --> AT["Password Defined"]
    U --> AU["Password Defined"]
    U --> AV["Password Defined"]
    U --> AW["Password Defined"]
    U --> AX["Password Defined"]
    U --> AY["Password Defined"]
    U --> AZ["Password Defined"]
    U --> BA["Password Defined"]
    U --> BB["Password Defined"]
    U --> BC["Password Defined"]
    U --> BD["Password Defined"]
    U --> BE["Password Defined"]
    U --> BF["Password Defined"]
    U --> BG["Password Defined"]
    U --> BH["Password Defined"]
    U --> BI["Password Defined"]
    U --> BJ["Password Defined"]
    U --> BK["Password Defined"]
    U --> BL["Password Defined"]
    U --> BM["Password Defined"]
    U --> BN["Password Defined"]
    U --> BO["Password Defined"]
    U --> BP["Password Defined"]
    U --> BQ["Password Defined"]
    U --> BR["Password Defined"]
    U --> BS["Password Defined"]
    U --> BT["Password Defined"]
    U --> BU["Password Defined"]
    U --> BV["Password Defined"]
    U --> BW["Password Defined"]
    U --> BX["Password Defined"]
    U --> BY["Password Defined"]
    U --> BZ["Password Defined"]
    U --> CA["Password Defined"]
    U --> CB["Password Defined"]
    U --> CC["Password Defined"]
    U --> CD["Password Defined"]
    U --> CE["Password Defined"]
    U --> CF["Password Defined"]
    U --> CG["Password Defined"]
    U --> CH["Password Defined"]
    U --> CI["Password Defined"]
    U --> CJ["Password Defined"]
    U --> CK["Password Defined"]
    U --> CR["Password Defined"]
    U --> CS["Password Defined"]
    U --> CT["Password Defined"]
    U --> CU["Password Defined"]
    U --> CV["Password Defined"]
    U --> CW["Password Defined"]
    U --> CX["Password Defined"]
    U --> CY["Password Defined"]
    U --> CZ["Password Defined"]

ENTES MPR-60S-41 - MPR60S MENU MAP - 3

flowchart
graph TD
    A["Voltage 1"] --> B["Currents"]
    B --> C["P. Factor"]
    C --> D["Cos"]
    D --> E["Active"]
    E --> F["Reactive"]
    F --> G["Apparent"]
    G --> H["L. Powers"]
    H --> I["L.P.F."]
    I --> J["THD V%"]
    J --> K["THD 1%"]
    K --> L["Freq. Hz"]
    L --> M["Average s"]
    M --> N["Averaget"]
    N --> O["C. Current"]

    P["ENERGY"] --> Q["EXP."]
    Q --> R["Clear"]
    R --> S["PSW"]
    S --> T["Imp."]
    T --> U["Clear"]
    U --> V["PSW"]
    V --> W["JML"]
    W --> X["Clear"]
    X --> Y["PSW"]
    Y --> Z["Clear"]
    Z --> AA["PSW"]
    AA --> AB["Password Defined"]

    AC["DEMAND"] --> AD["v"]
    AD --> AE["Clear"]
    AE --> AF["PSW"]
    AF --> AG["A"]
    AG --> AH["Clear"]
    AH --> AI["PSW"]
    AI --> AJ["A"]
    AJ --> AK["Clear"]
    AK --> AL["PSW"]
    AL --> AM["RS-485"]

    AN["SETUP"] --> AO["Password Defined"]

    AP["Network"] --> AQ["CT."]
    AQ --> AR["VT."]
    AR --> AS["Nc."]
    AS --> AT["E.C.T."]
    AT --> AU["E.Uric."]

    AV["Display"] --> AW["Loop."]
    AW --> AX["C.unit"]
    AX --> AY["BL"]

    AZ["RS-485"] --> BA["Addr."]
    BA --> BB["Bd."]
    BB --> BC["Pn"]

    BD["Catalog"] --> BE["1. Roten"]
    BE --> BF["Clp."]
    BF --> BG["P1.1"]
    BG --> BH["H1.1"]
    BH --> BI["Lc1.1"]
    BI --> BJ["H1.1"]
    BJ --> BK["Dc1.1"]
    BK --> BL["P2.1"]
    BL --> BM["H2.1"]
    BM --> BN["Lc7.1"]
    BN --> BO["H2.1"]
    BO --> BP["Dy2.1"]
    BP --> BQ["P3.1"]
    BQ --> BR["H3.1"]
    BR --> BS["Lc3.1"]
    BS --> BT["Hck.1"]
    BT --> BU["Dy2.1"]

    BV["2. Relay2"] --> BW["Cip."]
    BW --> BX["P1.1"]
    BX --> BY["H1.1"]
    BY --> BZ["Lc1.1"]
    BZ --> CA["H1.1"]
    CA --> CB["Dc1.1"]
    CB --> CC["P2.1"]
    CC --> CD["H2.1"]
    CD --> CE["Lc7.1"]
    CE --> CF["P3.1"]
    CF --> CG["H3.1"]
    CG --> CH["Lc3.1"]
    CH --> CI["Hck.1"]
    CI --> CJ["Dy2.1"]

    CK["3. Update"] --> CL["Fn."]

    CM["Address"] --> CN["Frc."]
    CN --> CO["Time."]
    CO --> CP["8hmm(y)"]
    CP --> CQ["Date."]
    CQ --> CR["8hmm(y)"]
    CR --> CS["Set Pow."]
    CS --> CT["Password Undefined"]
    CT --> CU["Chg Pow."]
    CU --> CV["Password Defined"]
    CV --> CW["Antic Out."]

    CX["Type"] --> CY["Fpn."]
    CY --> CZ["Lc1.1"]
    CZ --> DA["H2.1"]

    DB["LogRec"] --> DBa["Clear"]
    DBa --> DBb["LogRec"]
    DBb --> DBc["LogRec"]

    DBc --> DBd["Var."]


    style A fill:#f9f,stroke:#333
    style P fill:#ccf,stroke:#333

ENTES MPR-60S-41 - MPR60S MENU MAP - 4

flowchart
graph TD
    A["Voltage L"] --> B["Voltage I"]
    B --> C["Currents"]
    C --> D["P Factor"]
    D --> E["Cosφ"]
    E --> F["Active"]
    F --> G["Reactive"]
    G --> H["Apparent"]
    H --> I["S Powers"]
    I --> J["ΔP.F."]
    J --> K["THD V%"]
    K --> L["THD I%"]
    L --> M["Freq. Hz"]
    M --> N["Average k"]
    N --> O["Average L"]
    O --> P["Current"]

    Q["ENERGY"] --> R["Exp. Clear PSW"]
    Q --> S["Imp Clear PSW"]
    Q --> T["mm Clear PSW"]
    Q --> U["Clear PSW"]
    Q --> V["Password Defined"]

    W["DEMAND"] --> X["V Clear PSW"]
    W --> Y["V Clear PSW"]
    W --> Z["V Clear PSW"]
    W --> AA["V Clear PSW"]
    W --> AB["V Clear PSW"]
    W --> AC["V Clear PSW"]
    W --> AD["V Clear PSW"]
    W --> AE["V Clear PSW"]
    W --> AF["V Clear PSW"]
    W --> AG["V Clear PSW"]

    AH["SETUP"] --> AI["PSW Password Defined"]
    AH --> AJ["Network CT"]
    AH --> AK["Display Loop"]
    AH --> AL["RSC-182 Addr"]
    AH --> AM["Datakey 1. Rosay"]

    AN["TIME"] --> AO["Log Rec Clear"]
    AN --> AP["Eng Rec Clear"]
    AN --> AQ["Var."]

    AR["INFO"] --> AS["Log Rec Clear"]
    AR --> AT["Eng Rec Clear"]
    AR --> AU["Var."]

    AV["Datakey"] --> AW["Op Part1: Hit: Lo1: Hx1: Op1: P2: Hx2: Op2: Hx3: Op3: Op4: Op5: Op6: Op7: Op8: Op9: Op10: Op11: Op12: Op13: Op14: Op15: Op16: Op17: Op18: Op19: Op20: Op21: Op22: Op23: Op24: Op25: Op26: Op27: Op28: Op29: Op30: Op31: Op32: Op33: Op34: Op35: Op36: Op37: Op38: Op39: Op40: Op41: Op42: Op43: Op44: Op45: Op46: Op47: Op48: Op49: Op50: Op51: Op52: Op53: Op54: Op55: Op56: Op57: Op58: Op59: Op60: Op61: Op62: Op63: Op64: Op65: Op66: Op67: Op68: Op69: Op70: Op71: Op72: Op73: Op74: Op75: Op76: Op77: Op78: Op79: Op80: Op81: Op82: Op83: Op84: Op85: Op86: Op87: Op88: Op89: Op90: Op91: Op92: Op93: Op94: Op95: Op96: Op97: Op98: Op99: Op100: OpenRecord"]

    AX["Datakey"] --> AY["Op Part1: Hit: Lo1: Hx1: Lo1: Hx1': Op1': Hx2': Op2': Hx3': Op3': Hx4': Op4': Hx5': OpenRecord"]

    AZ["Datakey"] --> BA["Op Part2: Hit, Lc1, Lc2, Lc3, Lc4, Lc5, Lc6, Lc7, Lc8, Lc9, Lc10, Lc11, Lc12, Lc13, Lc14, Lc15, Lc16, Lc17, Lc18, Lc19, Lc20, Lc21, Lc22, Lc23, Lc24, Lc25, Lc26, Lc27, Lc28, Lc29, Lc30, Lc31, Lc32, Lc33, Lc34, Lc35, Lc36, Lc37, Lc38, Lc39, Lc40, Lc41, Lc42, Lc43, Lc44, Lc45, Lc46, Lc47, Lc48, Lc49, Lc50, Lc51, Lc52, Lc53, Lc54, Lc55, Lc56, Lc57, Lc58, Lc59, Lc60, Lc61, Lc62, Lc63, Lc64, Lc65, Lc66, Lc67, Lc68, Lc69, Lc70, Lc71, Lc72, Lc73, Lc74, Lc75, Lc76, Lc77, Lc78, Lc79, Lc80, Lc81, Lc82, Lc83, Lc84, Lc85, Lc86, Lc87, Lc88, Lc89, Lc90, Lc91, Lc92, Lc93, Lc94, Lc95, Lc96, Lc97, Lc98, Lc99, Lp100"]    
    AM --> AN
    AN --> AO
    AN --> AP
    AN --> AQ
    AN --> AR

ENTES MPR-60S-41 - MPR60S MENU MAP - 5

flowchart
graph TD
    A["Voltage"] --> B["Currents"]
    B --> C["P Factor"]
    C --> D["Cosφ"]
    D --> E["Active"]
    E --> F["Reactive"]
    F --> G["Apparent"]
    G --> H["S_Powers"]
    H --> I["≥P.F."]
    I --> J["THD V%"]
    J --> K["THD 1%"]
    K --> L["Freq. Hz"]
    L --> M["Average"]
    M --> N["Averaget"]
    N --> O["L_Current"]

    P["Voltage"] --> Q["Currents"]
    Q --> R["P Factor"]
    R --> S["Cosφ"]
    S --> T["Active"]
    T --> U["Reactive"]
    U --> V["Apparent"]
    V --> W["S_Powers"]
    W --> X["≥P.F."]
    X --> Y["THD V%"]
    Y --> Z["THD 1%"]
    Z --> AA["Freq. Hz"]
    AA --> AB["Average"]
    AB --> AC["L_Current"]

    AD["ENERGY"] --> AE["Expt. Clear PSW Imp. Clear PSW 2ML Clear PSW Clear Password Defined"]
    AF["DEMAND"] --> AG["V Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW Clear PSW All"]
    AH["SETUP"] --> AI["PSW Password Defined"]
    AJ["TIME"] --> AK["Display Loop C_ort BL: Addr Bal: Prt"]
    AL["INFO"] --> AM["Log Rec: Clear Eng Rec: Clear Ver."]

    AN["Data og"] --> AO["T Relay1"]
    AP["Ver"] --> AQ["Event Prt: Prt1: Prt2: Prt3: Prt4: Prt5: Prt6: Prt7: Prt8: Prt9: Prt10: Prt11: Prt12: Prt13: Prt14: Prt15: Prt16: Prt17: Prt18: Prt19: Prt20: Prt21: Prt22: Prt23: Prt24: Prt25: Prt26: Prt27: Prt28:"]

    AO --> AP
    AO --> AN
    AP --> AO
    AN --> AO
    AO --> AN
    AO --> AO
    AO --> AO

ENTES MPR-60S-41 - MPR60S MENU MAP - 6

flowchart
graph TD
    A["Voltage L"] --> B["Energy"]
    C["Voltage I"] --> B
    D["Currents"] --> E["Demand"]
    F["P Factor"] --> E
    G["Cos"] --> E
    H["Active"] --> E
    I["Reactive"] --> E
    J["Apparent"] --> E
    K["L Powers"] --> E
    L["ΔP.F."] --> M["SETUP"]
    N["THD V%"] --> M
    O["THD 1%"] --> M
    P["Freq. Hz"] --> Q["TIME"]
    R["Average k"] --> S["DATE"]
    T["Average L"] --> S
    U["Current"] --> S
    V["Energy"] --> W["Detection"]
    X["Demand"] --> Y["Setup"]
    Z["SETUP"] --> AA["Network"]
    AB["Time"] --> AC["DATE"]
    AD["INFO"] --> AE["Information"]

    subgraph Blue Symbols
        direction TB
        E --> AF["Clear"]
        AF --> AG["PSW"]
        AF --> AH["Password Defined"]
        AF --> AI["Imp."]
        AF --> AJ["IPML"]
        AF --> AK["Clear"]
        AF --> AL["Clear"]
        AF --> AM["PSW"]
        AF --> AN["PSW"]
        AF --> AO["PSW"]
        AF --> AP["Clear"]
        AF --> AQ["PSW"]
        AF --> AR["Clear"]
        AF --> AS["PSW"]
        AF --> AT["Clear"]
        AF --> AU["PSW"]
        AF --> AV["Clear"]
        AF --> AW["PSW"]
        AF --> AX["Clear"]
        AF --> AY["PSW"]
        AF --> AZ["Clear"]
        AF --> BA["PSW"]
        AF --> BB["Clear"]
        AF --> BC["PSW"]
        AF --> BD["Clear"]
        AF --> BE["PSW"]
        AF --> BF["Clear"]
        AF --> BG["PSW"]
        AF --> BH["Clear"]
        AF --> BI["PSW"]
        AF --> BJ["Clear"]
        AF --> BK["PSW"]
    end

    subgraph Blue Symbols
        direction TB
        AA --> BL["Display"]
        BL --> BM["RS-485"]
        BM --> BN["Dialog"]
        BN --> BO["Event"]
        BO --> BP[Pm: Event, Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1:Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt1: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2: Pt2a, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pc, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm, Pm,
    end
Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : ENTES

Model : MPR-60S-41

Category : Analyseur réseau