CARRIER AquaEdge 23XRV - Compressor

AquaEdge 23XRV - Compressor CARRIER - Free user manual and instructions

Find the device manual for free AquaEdge 23XRV CARRIER in PDF.

📄 44 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice CARRIER AquaEdge 23XRV - page 1
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Centrifugal Compressor (for AquaEdge 23XRV Chiller)
Model AquaEdge 23XRV
Brand Carrier
Compressor Type Semi-hermetic centrifugal
Motor Drive Unit-mounted Variable Frequency Drive (VFD)
VFD Manufacturer Danfoss VLT FC102 series
Supply Voltage 380-480 V AC, 3-phase, 50/60 Hz
VFD Power Range 200 to 1000 kW (drive ratings N200 to N1M0)
Max Output Current (VFD) Up to 1670 A (parallel drive configuration)
Enclosure Protection IP54 (NEMA 12) for D and E sizes; IP00 for parallel drive modules
VFD Weight (D size) 135-275 lb (62-125 kg)
VFD Weight (E size) 650-700 lb (295-318 kg)
VFD Weight (PD size enclosure) Approx. 3000 lb (1361 kg)
Safety Features Lockout/tagout, DC bus capacitor discharge, Safe Torque Off (STO), ESD precautions
Commissioning Verify VFD parameters against chiller nameplate; check power wiring and grounding
Maintenance Periodic inspection of valves, fittings, piping for corrosion/leaks; static test of power modules
Repair Parts Use only Carrier or Danfoss approved replacement parts
VFD Cooling Air-cooled with fans (heat sink)
Operating Ambient Temp Max 40°C (104°F) standard, up to 55°C (131°F) with derating
Short Circuit Capacity 100 kA at 380-480 V (UL)
VFD Frame Sizes D (DD395-DD588), E (DE658-DE990), PD (DP1120-DP1670)
Communication Protocol LEN (Local Equipment Network) via RS-485, PIC6 HMI interface
Required Manuals Danfoss VLT FC102 manual, Carrier 19XR/19MV start-up and troubleshooting manuals

Frequently Asked Questions - AquaEdge 23XRV CARRIER

What are the safety precautions when servicing the AquaEdge 23XRV compressor VFD?
Always lock out and tag out all power sources. Wait for DC bus capacitors to discharge as per the discharge time table (20-40 minutes depending on drive size). Use a voltmeter to verify zero voltage before touching any internal components. Wear appropriate PPE including safety goggles and gloves.
How do I check the DC bus voltage on the VFD?
After power is removed and discharge time has elapsed, access the DC bus terminals. For D size drives, use extended probe tips on your voltmeter to reach the M5 studs (DC+ and DC-). For E size drives, terminals are similarly located. For parallel drives, check at the REGEN terminals or individual module DC fuses.
What should I do if the VFD displays a ground fault alarm?
First, disconnect the motor and run the VFD without load. If the alarm persists, there is likely a faulty current sensor inside the drive. If the alarm clears, use a megohmmeter to test the motor and cables for insulation breakdown. A manual initialization (power off, hold Status+Main Menu+OK, then power on) may zero the sensors, but will reset all parameters to default.
How often should I inspect the VFD and compressor components?
Periodically inspect all valves, fittings, and piping for corrosion, rust, leaks, or damage. Check the VFD enclosure for moisture, debris, and ensure vents are clear. During start-up, verify all configured parameters match the chiller nameplate. A thermal measurement of the capacitor bank and power connections should be taken before commissioning.
Can I use a torch to remove refrigerant components?
No. Do not use a torch to remove any component as the system contains oil and refrigerant under pressure. Instead, shut off power, recover refrigerant, displace traces of vapor with nitrogen, cut tubing with a cutter, and carefully unsweat remaining stubs. Oil can ignite when exposed to flame.
What is the procedure to replace a drive module in a parallel drive system?
Isolate the drive module by removing interlink connections and control cables. Use eye bolts to rig the individual module (each is similar to a D size drive). Ensure rigging angle is 65 degrees or larger. After replacement, verify the type code (parameter 14-23) is set correctly using a keypad, then power cycle and reset the alarm.
How do I enable LEN communication on a new or replacement VFD?
A keypad is required. Set parameter 14-29 to 00006100 to access hidden parameter 14-23. Change 14-23 from standard software (index 12) to special software S009 (index 12). Then change index 20 to 'Save to EEPROM'. A power cycle and reset will clear the alarm.
What is the correct lifting procedure for the VFD enclosure?
Use dedicated lifting eyes and appropriate weight-rated equipment. For D and E sizes, use eyebolts at the four corners. For parallel drive enclosures, use the four corner rigging lugs. Ensure lifting angle is 65 degrees or larger (or 45 degrees max for eyebolts). Never walk under suspended load.
What are the consequences of using power correction capacitors on the VFD output?
Power correction capacitors on the drive output can cause erratic motor operation, nuisance tripping, and permanent damage to the drive. Remove such capacitors before connecting the drive to the motor.
Where can I find the Danfoss VFD type code and serial number?
The Danfoss nameplate is located inside the VFD enclosure. It contains the Type Code (TC) starting with FC-102, Serial Number (S/N), and other ratings such as power, voltage, and enclosure type. This information is needed for technical support.

User questions about AquaEdge 23XRV CARRIER

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Compressor in PDF format for free! Find your manual AquaEdge 23XRV - CARRIER and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. AquaEdge 23XRV by CARRIER.

USER MANUAL AquaEdge 23XRV CARRIER

Failure to follow these procedures may result in personal injury or death.

DO NOT work on high-voltage equipment unless you are a qualified electrician.

DO NOT WORK ON electrical components, including control panels, switches, VFD, or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid-state components.

LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS INTERRUPTED, confirm that all circuits are de-energized before resuming work.

AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY GOGGLES. Wash any spills from the skin with soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a physician.

CARRIER AquaEdge 23XRV - 1

WARNING

DO NOT USE TORCH to remove any component. System contains oil and refrigerant under pressure.

To remove a component, wear protective gloves and goggles and proceed as follows:

a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from system using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen and the work area should be well ventilated. Refrigerant in contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter and remove component from unit. Use a pan to catch any oil that may come out of the lines and as a gauge for how much oil to add to the system.
e. Carefully un-sweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame.

Failure to follow these procedures may result in personal injury or death.

CARRIER AquaEdge 23XRV - WARNING - 1

WARNING

DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while chiller is under pressure or while chiller is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection.

CARRIER AquaEdge 23XRV - WARNING - 1

CAUTION

USE only repair or replacement parts that meet the code requirements of the original equipment.

PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks, or damage.

DO NOT re-use compressor oil or any oil that has been exposed to the atmosphere. Dispose of oil per local codes and regulations.

DO NOT leave refrigerant system open to air any longer than the actual time required to service the equipment. Seal circuits being serviced and charge with dry nitrogen to prevent oil contamination when timely repairs cannot be completed.

CARRIER AquaEdge 23XRV - CAUTION - 1

CAUTION

Failure to follow these procedures may result in personal injury or damage to equipment.

TO AVOID an electric shock hazard, verify that the voltage on the bus capacitors has discharged completely before servicing. Check the DC bus voltage at the power terminal block by measuring between the +DC and -DC terminals, between the +DC terminal and the chassis, and between the -DC terminal and the chassis. The voltage must be zero for all 3 measurements.

THE USER is responsible to conform with all applicable local, national, and international codes. Failure to observe this precaution could result in damage to, or destruction of, the equipment.

THIS DRIVE contains ESD (electrostatic discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. Typical ESD protections are ESD mat and grounded wrist strap.

DO NOT alter the setting of any jumper. Failure to observe this precaution could result in damage to, or destruction of, the equipment.

USE OF power correction capacitors on the output of the drive can result in erratic operation of the motor, nuisance tripping, and/or permanent damage to the drive. Remove power correction capacitors before proceeding. Failure to observe this precaution could result in damage to, or destruction of, the equipment.

MOST CODES require that upstream branch circuit protection be provided to protect input power wiring.

DO NOT route signal and control wiring with power wiring in the same conduit. This can cause interference with drive operation. Failure to observe this precaution could result in damage to, or destruction of, the equipment.

DISTRIBUTION SYSTEM short circuit capacity shall not exceed the rating of the drive. Failure to observe this precaution could result in damage to, or destruction of, the equipment.

DO NOT STEP on refrigerant lines. Broken lines can whip about and release refrigerant, causing personal injury.

DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow safe practices when using ladders.

USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if components are light, use mechanical equipment when there is a risk of slipping or losing your balance.

BE AWARE that certain automatic start arrangements CAN ENGAGE THE VFD, TOWER FAN, OR PUMPS. Open the disconnect ahead of the VFD, tower fans, or pumps.

INTRODUCTION

The Carrier VFD option Start-Up and Service Manual is intended for trained and qualified service personnel and is to be used during start-up, operation, and maintenance of Danfoss VLT FC102 series drives.

ABBREVIATIONS AND EXPLANATIONS

Frequently used abbreviations in this manual include:

DC — Direct Current

HMI — Human Machine Interface

IGBT — Insulated Gate Bipolar Transistor

I/O — Inputs/Outputs

IP — Internet Protocol

LCP — Local Control Panel

LEN — Local Equipment Network

MCB — Main Control Board

MDCIC — Multi-Drive Control Interface

MOV — Metal Oxide Varistor

PCB — Printed Circuit Board

PE — Protective Earthing Conductor

PIC — Product Integrated Control

PWM — Pulse Width Modulation

STO — Safe Torque Off

VFD — Variable Frequency Drive

Required Publications

The Carrier VFD option Start-Up and Service Manual must be used with the following manuals:

  • Latest version of the Danfoss VLT FC102 and VLT parallel AC Drives manuals as applicable.
  • Latest revision of the Start-Up, Operation, and Maintenance Instructions for the 19XR with PIC6 Controls.
  • Latest revision of the Controls Operation and Troubleshooting manual for 19XR with PIC6 Controls.

Getting Assistance from Danfoss

For technical support on drives, contact Technical Support experts: 1-888-Danfoss (1-888-326-3677).

Before calling, have the following information available. Type Code and Serial Number can be found on the Danfoss data nameplate. See Fig. 1.

• Image of drive nameplate including:
Carrier VFD Code (Carrier Part Number)
Danfoss Part Number / Type Code (T/C)
Danfoss Serial Number (S/N)

- Images of cable connections, filters, resistors, fuses, chokes, etc.

• Alarms/warnings experienced

• MCT 10 *.ssp file

For detailed repair procedures, refer to Danfoss VLT Drive Service Manual MG94A502.

Carrier P/N:

SEE NOTE: 1 T/C: FC-102N560T4E54H2TXC7CX5009XAXBXCXXXXDX P/N: 136L1239 S/N: 004902H121

560 kW / 750 HP

_IN: 3x380-480V 50/60Hz 954/858A

'LOUT: 3x0-Vin 0-590Hz 990/890A

CARRIER AquaEdge 23XRV - Carrier P/N: - 2

Type 12 / IP54 Tamb. 40°C/104°F

Max Tamb. 55°C/131°F w/Output Current Derating

SCCR 100 kA at UL Voltage range 380-480V

Danfoss A/S

6430 Nordborg, Denmark

danfoss.com

Assembled by Danfoss for Carrier

ASSEMBLED IN USA

CARRIER AquaEdge 23XRV - Carrier P/N: - 3

36UO E70524 IND. CONT. EQ.

UL Voltage range 380-480V

CARRIER AquaEdge 23XRV - Carrier P/N: - 4

CARRIER AquaEdge 23XRV - Carrier P/N: - 5

DANGER

See manual for special condition / mains fuse

  1. Identifies product group and drive series. This should always start with FC102.
  2. Drive Power Rating (N200, N250, N315, N355, N400, N450, N500, N560, N630, N710, N800, N1M0).
  3. Voltage Rating (T4 = 380-480V AC).
  4. Enclosure Type: E54: IP54 (NEMA 12).
  5. Drive type (H=6-pulse drive with RFI filter, P2=6-pulse parallel drive with RFI filter).
  6. S/N contains information related to Build date after the capital letter (wwy, where ww is the week and y is the year; for example, 121 = week 12, 2021.
  7. IN = input voltage; OUT = output voltage.
  8. Danger Electrical Symbol; 40 min indicates that for this size drive the internal capacitors will have discharged 40 minutes after power has been removed from the drive.

Fig. 1 — Sample Danfoss VFD Nameplate

IDENTIFYING DRIVE COMPONENTS

Chiller control, VFD Power Assembly and VFD schematics are included in Appendix A.

WARNING

DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power, wait the time specified in Table 1 or as specified on the Danfoss VFD nameplate for the DC bus capacitors to discharge. Always check the voltage with a voltmeter rated for the DC bus voltage to ensure the DC bus capacitors are discharged before touching any internal components. For parallel drive modules (N630 and larger) check voltage before and after the individual DC fuses. Failure to observe these precautions could result in severe bodily injury or loss of life.

An isolated multimeter with diode tester is needed to measure DC bus voltage and to make resistance and diode checks.

Table 1 — Discharge Time

VFD FRAMEDANFOSS POWER MODULE SIZECAPACITOR DISCHARGE TIME (MIN)
DD395-DD588 D2 0
DE658-DE990 E4 0
DP1120-DP1670 D2 0

The Danfoss VFD offering has a passive rectifier section and a six pulse inverter section. For Danfoss VFD frames DD and DE, chiller topology offering consists of a VFD power panel and a separate Danfoss drive mounted on the chiller condenser. The VFD power panel contains the required integration components for the VFD to operate with the chiller system. These components consist of the main circuit breaker, oil pump breaker and terminal block feed to power panel, terminal blocks, control power circuit breaker, control transformers, heater power terminal block feed, and fan relays.

The larger Danfoss DP frame size is used for multiple power modules to be used in parallel. The drive modules and the VFD power panel components are consolidated into a common enclosure.

The Danfoss VFD offering includes optional protective MOVs for VFD electrical surge protection and volt and ammeter options along with a line reactor offering. The drive is offered with no local control panel (LCP) keypad, and therefore if programming is required, a version of Danfoss' MCT-10 will need to be installed

on a laptop. For details of MCT-10, see Danfoss published literature VLT ^1 Motion Control Tools MCT 10 Setup Software Operating Instructions. Note that a keypad is required for some service functions such as enabling LEN on a non-Carrier configured Danfoss type code. (LEN is configured default on a Carrier type code.) A keypad is also required if a drive power card is being replaced.

WARNING

Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.

Refer to Fig. 2 for lockout/tagout details.

L1 L2 L3 Lockout/Tagout

Fig. 2 — Lockout/Tagout

When there is a need to access the VFD enclosure to do any troubleshooting, it is important to identify the type of drive prior to initiating any work.

The Carrier FC102 Danfoss product offering consists of three main configurations: D size, E size, and D size parallel drive (PD) modules. See details for the D size drive in Fig. 3, for the E size drive in Fig. 4, for 19MV size D/E drives see Fig. 5, and for the D size parallel drive modules in Fig. 6. The product range covers a drive range of 200 to 1000 kW. When any work or troubleshooting is required, it is critical to determine the type of drive since their design layouts vary. This can be done by locating the Carrier VFD label located on the outside of the drive or the Danfoss type code on the Danfoss VFD nameplate and matching up the appropriate VFD Power Rating in Table 2 and 3 or Table 4.

PIC6 HMI Incoming Power Access VFD Power Panel Service Circuit Breaker (Hidden) Fan (Hidden) Main Circuit Breaker Disconnect Handle Meter Option (Optional) Fan E-Stop D-Size Danfoss Air-Cooled Drive

Fig. 3 — D Size Drive — 19XRV

NOTE: Install Carrier-provided tophat to allow for adequate space for incoming power cables. Incoming Power Access Meter Option (Optional) VFD Power Panel Conduit Containing Drive Incoming and Leaving Motor Cables E-Stop Fan Main Circuit Breaker Disconnect Handle Service Circuit Breaker E-Size Danfoss Drive (Horizontal Installation)

Fig. 4 — E Size Drive — 19XRV

Second Stage Guide Vane Actuator Compressor Motor First Stage Guide Vane Actuator Tophat Evaporator Pressure Transducer and Charging Valve Relief Valves (Not All Shown) MBC Cavity Cover Evaporator Refrigerant Storage Tank / Vacuum Connection PIC6 HMI Touchscreen Panel Economizer (Option) Integrated Power and Control Panel Condenser Waterbox Return End Evaporator Waterbox Return End

Fig. 5 — D/E Size Drive — 19MV

NOTE: Install Carrier-provided tophat to allow for adequate space for incoming power cables. Incoming Power Cables Main Circuit Breaker Handle E-Stop PD Drive

Fig. 6 — Size PD Danfoss Drive (Integrated VFD and VFD Power Panel) — 19XR

Table 2 — VFD Type by Frame Size, D-E

CARRIER VFD FRAMEDANFOSSMAX DRIVE ENCLOSUREDANFOSS DRIVE
TypeEnclosure SizeDriveWeight lb (kg)HEIGHT in. (mm)WIDTH in. (mm)DEPTH in. (mm)
DD395 D D2h N200 135 (62)43.6 (1107) 12.8 (325)14.9 (379)
DD480 D D2h N250 135 (62)43.6 (1107) 12.8 (325)14.9 (379)
DD558 D D2h N315 275 (125)43.6 (1107) 12.8 (325)14.9 (379)
DE658 E1E1h N355 650 (295)80.4 (2043) 23.7 (602)20.2 (513)
DE745 E1E1h N400 650 (295)80.4 (2043) 23.7 (602)20.2 (513)
DE800 E1E1h N450 650 (295)80.4 (2043) 23.7 (602)20.2 (513)
DE880 E2E2h N500 700 (318)80.4 (2043) 27.5 (698)20.2 (513)
DE990 E2E2h N560 700 (318)80.4 (2043) 27.5 (698)20.2 (513)

Table 3 — VFD Power Panel for D and E Size Danfoss Drives

UNITVFD POWER PANEL
WEIGHTlb (kg)HEIGHTin. (mm)WIDTHin. (mm)DEPTHin. (mm)
19MV 531 (241)28.0 (711) 47.5 (1206) 28.75 (730)
19XRV 300 (136)40.5 (1030)37.25 (950) 19.0 (480)

Table 4 — VFD Type by Frame Size, PD

CARRIER VFD FRAMEDANFOSSMAX DRIVE ENCLOSUREDANFOSS DRIVEVFD ENCLOSURE
TypeEnclosure SizeDriveWeight lb (kg)HEIGHT in. (mm)WIDTH in. (mm)DEPTH in. (mm)WEIGHT lb (kg)HEIGHT in. (mm)WIDTH in. (mm)DEPTH in. (mm)
DP1120D ParallelDa4N630275 (125)88.7 (2254)63.3 (1608)25.0 (636)3000 (1361)65 (1652)110 (2800)24.6 (625)
DP1260D ParallelDa4N710275 (125)88.7 (2254)63.3 (1608)25.0 (636)3000 (1361)65 (1652)110 (2800)24.6 (625)
DP1460D ParallelDa4N800275 (125)88.7 (2254)63.3 (1608)25.0 (636)3000 (1361)65 (1652)110 (2800)24.6 (625)
DP1670D ParallelDa4N1M0275 (125)88.7 (2254)63.3 (1608)25.0 (636)3000 (1361)65 (1652)110 (2800)24.6 (625)

NOTE: Weight and dimensions for PD (parallel drive) for the Danfoss power module are for the combined VFD enclosure (both VFD and VFD power panel components).

Rigging

D, E SIZES

Drive enclosure and associated components are heavy. To avoid injury be sure to use appropriate equipment with appropriate weight ratings for lifting. Always use dedicated lifting eyes for lifting and never walk under suspended load. Wear PPE such as gloves, safety glasses and safety shoes to prevent injury. Ensure correct length of lifting cables so lifting angle is 65 degrees or larger with horizontal (Fig. 7). Always use lifting eye bolts (Fig. 8) to rig drive if it needs to be removed from the chiller. Note that E series drives are placed on the chiller in horizontal position and will need to be rigged from that orientation using rigging eyes in the four corners.

CARRIER AquaEdge 23XRV - D, E SIZES - 1

natural_image Line drawing of an industrial control cabinet with a crane hook above (no text or symbols)

Fig. 7 — Lifting Cables

CARRIER AquaEdge 23XRV - D, E SIZES - 2

natural_image Technical line drawing of an electronic device chassis with cooling fans and internal circuitry (no text or labels)

Fig. 8 — Installation of Eye Bolts

PARALLEL DRIVE MODULES

Parallel Drive Modules consist of four smaller D size modules installed in parallel configuration.

Install eye bolts and rig individual modules as a D series drive. Note that some component removal is necessary to gain access to remove an individual drive.

If the entire drive module enclosure is to be rigged, use dedicated rigging lugs. Use the 4 rigging lugs located in each corner of the drive enclosure.

The PD enclosure can be lifted by the 4 outside eyebolts. Lifting angle must never be more than a 45 degree pull (Fig. 9). See Fig. 10 for location of eyebolts.

X 45° Y

Fig. 9 — Lifting Angle for Eyebolts

Corner Rigging Eye Bolts Rig using a minimum of the 4 eye bolts located in the 4 corners of the drive.

Fig. 10 — Danfoss PD Drive Rigging

Components and Physical Data

19XRV Carrier Danfoss VFD Part Numbers are structured as shown in Fig. 11. 19MV Carrier Danfoss VFD Part Numbers are

structured as shown in Fig. 12. An example of Danfoss Type Code (TC) Breakdown is shown in Fig. 13.

CARRIER AquaEdge 23XRV - Components and Physical Data - 1

flowchart
graph TD
    A["19XRV — High Efficiency Semi-Hermetic Centrifugal Liquid Chiller with Unit-Mounted VFD"] --> B["Drive Code D — Danfoss"]
    A --> C["Maximum Amp Rating, VFD Frame Size 0588"]
    A --> D["Compressor Frame 3 — Single-Stage C, E — Two-Stage"]
    A --> E["Heat Exchanger Size 3"]
    A --> F["Line Voltage Code 3 — 380-400/60"]
    A --> G["Options A0 — 65 kA Breaker, 3% DC Choke"]
    A --> H["Options A1 — 100kA Breaker, 3% DC Choke"]
    A --> I["Options A2 — 65 kA Breaker, 3% DC Choke, Volt and Ammeter"]
    A --> J["Options A3 — 100kA Breaker, 3% DC Choke, Volt and Ammeter"]
    A --> K["Options B0 — 65 kA Breaker, 5% DC Choke"]
    A --> L["Options B1 — 100 kA Breaker, 5% DC Choke"]
    A --> M["Options B2 — 65 kA Breaker, 5% DC Choke, Volt and Ammeter"]
    A --> N["Options B3 — 100 kA Breaker, 5% DC Choke, Volt and Ammeter"]
    A --> O["Special Order Indicator — Standard"]
    A --> P["Front End Code F — Fixed Front End"]
    A --> Q["Special Order Indicator — Standard S — Special Order"]

Fig. 11 — Carrier Part Number for 19XRV Danfoss Drive

Description 19MV — High Efficiency 2-stage Semi-Hermetic back-to-back Centrifugal Liquid Chiller with unit-mounted VFD Drive Code D — Danfoss VFD Frame Size 0395 0480 0588 0658 0745 0880 0990 Compressor Frame 3 19MV D 0395 3 5 A0 F - Reserve Indicator - Presently this digit has no significance Front End Code F — Fixed Front End Options A0 — 100kA Fuse, 1.5% DC Choke A1 — 100 kA Fuse, 1.5% DC Chose, Volt and Ammeter Line Voltage Code 3 — 380-400/60 4 — 401-439/60 5 — 440-480/60 9 — 380-415/50

Fig. 12 — Carrier Part Number for 19MV Danfoss VFD

CARRIER AquaEdge 23XRV - Components and Physical Data - 3

flowchart
graph TD
    A["FC-102"] --> B["Product Group"]
    A --> C["Power Rating"]
    A --> D["Input Voltage"]
    A --> E["Enclosure Type"]
    A --> F["RFI Filter Option"]
    A --> G["Brake"]
    A --> H["Display (LCP)"]
    A --> I["PCB Options"]

    B --> J["FC-102 N560 T4 E54 H2 T X C 7 C X S009 X AX BX CX X XX DX"]
    C --> K["N315 N560"]
    C --> L["N355 N630"]
    C --> M["N400 N710"]
    C --> N["N450 N800"]
    C --> O["N500 N1M0"]

    D --> P["T4 — 380-480V AC"]
    D --> Q["T7 — 525-690V AC"]

    E --> R["E54 — IP54 (NEMA 12)"]
    E --> S["E00 — IP00 (Individual Module Drives for Parallel System)"]

    F --> T["H2 — RFI Filter, Class A2 (6-pulse)"]
    F --> U["P2 — Parallel Drive and RFI Filter, Class A2 (6-pulse)"]

    G --> V["X — No LCP"]

    H --> W["C — Coated PCB"]
    H --> X["X — Not Coated PCB"]

    I --> Y["Mains Option"]
    I --> Z["X — No Mains Option"]
    I --> AA["3 — Mains Disconnect and Fuse"]
    I --> AB["4 — Mains Contactor and Fuses"]
    I --> AC["7 — Fuse"]
    I --> AD["E — Mains Disconnect, Contactor, and Fuses"]
    I --> AE["J — Circuit Breaker and Fuses"]

Fig. 13 — Example of Danfoss Type Code (TC) Breakdown

D Size Drive

The D size FC102 drive and Carrier VFD control panel are positioned side by side off-center on top of the condenser shell.

The Carrier VFD power panel is where the customer runs unit incoming power; the panel contains all required components to interface with the VFD, control panel, and power panel (as applicable). See Fig. 14-16.

NOTE: Items preceded by an asterisk (*) are options. Circuit Breaker 1 (Oil Pump Supply) Fuse 4; 2 Amp Fuse Circuit Breaker 2 Fuse 3; 25 Amp Fuse(Oil Heater Supply) Analog Control Relay (ACR) Terminal Block (TB8) Terminal Block (TB5) * Surge Protective Device (SPD) * Fuses for SPD (FU8) Service Circuit Breaker TCB FU3, FU4 CB2 TB8 TSB5 SPD MCB Main Circuit Breaker * Meter Kit Terminal Blocks and Fuse 9-14 Power Terminals for Motor Cables * Meter Kit Current Transformers Incoming Power Busbar Leads (R, S, T) Drive Output Busbars (U, V, W to Motor) * PT (Potential Transformer) for Voltage Meter Kit Transformer 1: 4 kVA 380V/480V to 115V (50/60 Hz)

Fig. 14 — D Size FC102 Drive and Carrier VFD Power Panel (19XRV Shown)

Incoming Power Option: Meter Kit (Ammeter and Voltmeter) Display and Switches Main Circuit Breaker Disconnect Handle

Fig. 15 — Carrier 19XRV VFD Power Panel for D and E Size Drives (19XRV D Size Panel Shown)

10 11 1 8 9 16 1 15 13 (IP 21/54 NEMA 1/12) 12 13 (IP 20/Chassis) 6 7 2 5 3 4 8 9 Detail of Control Shelf

1 LCP (Local Control Panel) — not provided
2 RS-485 Serial Bus Connector
3 Digital I/O and 24V Power Supply
4 Analog I/O Connector
5 USB Connector
6 Serial Bus Terminal Switch
7 Analog Switches (A53), (A54)
8 Relay (01, 02, 03)
9 Relay 2 (04, 05, 06)
10 Lifting Ring
11 Mounting Slot
12 Cable Clamp (PE)
13 Ground
14 Motor Output Terminals 96 (U), 97 (V), 98 (W)
15 Line Power Input Terminals 91 (R), 92 (S), 93 (T)
16 TB5 (IP21/54 only) Terminal block for anti-condensation heater.

Fig. 16 — D Size Control Shelf Components

To check DC bus voltage check voltage between terminal 1 and 2 as depicted below. To reach the DC bus location a voltmeter with safety probe tip extenders must be utilized since the DC bus studs are located far back in the drive. See Fig. 17 and static checks later in this manual.

1 2 + W -704F20-FR 07799905 B- cu

1 DΦ (+) Bus

2 DC (-) Bus

Fasteners are M5 studs.

Fig. 17 — DC Bus Location in D1h–D8h Drives

E Size Drive

The E size FC102 drives have higher amperage capacity compared to the D size. Like the D size, the E size drive is positioned on the condenser in conjunction with the VFD power panel. The E size drives are mounted in horizontal position. The E size drives are mounted on a VFD bracket arrangement supported and suspended between the condenser tubesheets.

For the smaller D size drives, customer incoming power is terminated in the VFD Power Panel; power leads are run from the VFD Power Panel to the VFD and from the VFD to the motor. The main power panel is detailed in Fig. 18-20. For an interior view of the E drive enclosure, see Fig. 21; Fig. 22 details control shelf elements.

Circuit Breaker 1 (Oil Pump Supply) Main Circuit Breaker T88 T85 SPD T2 T1 Fuse 4; 2 Amp Fuse Fuse 3; 25 Amp Fuse Circuit Breaker 2 (Oil Heater Supply) Terminal Block (TB8) Terminal Block (TB5) Analog Control Relay (ACR) Option: Surge Protective Device Option: Meter Kit Terminal blocks and Fuse 9-14 Service Circuit Breaker Option: Fuses for Surge Protective Device (FU8) Transformer 1: 4 kVA 380V/480V to 115V (50/60 Hz) Option: PT (Potential Transformer) for Voltage Meter Kit

Fig. 18 — 19XRV Main Power Panel (MPP), E Size

IOB2 and Optional IOB3 and IOB4 (See Individual IOB Figures) Fan Breaker Lugs Modem SIOB 5TB Power Converter Ethernet Switch CB1 and CB2 Controls Circuit Breakers T1 - 120v:24v Transformer (100va) PS4 - MBC Power Supply T2 - 120v:24v Transformer (200va) Ground Lug MCB Breaker L1, L2, L3 Bus Bars To VFD

Fig. 19 — 19MV Power Panel - Front View (D and E Size Drive)

TB3 TB4 3CT 240V:120V (1500 VA) EMI Filter MCB - Main Breaker 1CT - Step-down Transformer (4 KVA) UPS

NOTE: Field Wiring Connections Are All on Terminal Blocks TB3 and TB4 (Located on Floor of Low Voltage Section)

Fig. 20 — 19MV Power Panel - Top View (D and E Size Drive)

1 2 3 4 5 6 7 8 9 10 11 12

1 Control Shelf
2 Local Control Panel (LCP) cradle
3 RFI Filter (optional)
4 Mains fuses (required for UL compliance, but otherwise optional)
5 Mains Terminal
6 FRI Shield Termination
7 Fan Power Card
8 Space Heater (optional)
9 Mains Disconnect (optional)
10 Brake/Regeneration Terminals (optional)
11 Motor Terminals
12 Ground Terminals

Fig. 21 — Interior View of Enclosures, E Size Drive DE658 through DE990
1 2 3 4 5 6 7 8 9 10 11 12 13

1 LCP Cradle (LCP not shown or provided)
2 Bus Terminal Switch
3 Serial Communication Terminals
4 Digital Input/Output Terminals
5 Cable/EMC Clamps
6 Relay 1 and Relay 2
7 Control Card (underneath LCP and Control Terminals)
8 Control Shelf
9 USB Port
10 Analog Input Switches A53/A54
11 Analog Input/Output Terminals
12 Brake Resistor Terminals, 104-106 (on power card underneath control shelf)
13 Power Card (underneath the control shelf)

Fig. 22 — Control Shelf Details

For static checks an isolated multimeter with diode tester is needed to measure DC bus voltage and to make diode checks. DC+ and DC- terminals are identified in Fig. 23 for E sized drives.

1 DC (+) Bus 2 DC (-) Bus

Fig. 23 — DC Bus Location in E1h–E4h Drives, Shown in Upright Position

D and E Size VFD Power Panel Schematics — 19XRV

See Fig. 24 and 25 for detailed drawings.
CUSTOMER POWER SUPPLY 380-415/480-3-60HZ SERVICE POWER SUPPLY 380-415/480-3-60HZ NOTE FOR SERVICE ONLY + REDUCT LUMPES FOR UPS OPTION + REQUIRED RACKED CONTRACTOR WITH UPS OPTION TO COMPRESSOR PUMP PANEL C2 C1 GROUND SCTMP RUNSTOP OE PUMP RUNNING SIGNAL CABLE TB-50 TB-51 TO VFD RELAT 2 RUNNING SIGNAL CABLE CONNECT TO CONTROL PANEL 30CB, 39B-27, 28 RUN 33A1 TB5 ACR XK1 TBS 102C AUX1 LARY CONTACT NOTE CB TO TRIPPED: MCB-NO-, AUX-ST* CHANGES STATE TO CLOSE CB TO TRIPPED: MCB-NC, AUX-ST* CHANGES STATE TO OPEN TO VFD POWERTRONIX TRANSFORMER N/A N/A N/A MICRON TRANSFORMER P/N: 32VS15021501LC N/A N/A P/N: HT01M1380 PRIMARY WINDING(50/60HZ) H3.0 X3 Primary H1-H2 = 380VAC or 480VAC H2.380 WINDING(50/60HZ) H1-H3 = 480VAC H2.380 H1.480 H3.480 H2.380 H1.480 H3.480 H2.380 H1.480 H3.480 H2.380 H1.480 H3.480 H2.380 H1.480 H3.480 H2.380 H1.480 H3.480 H2.380 H1.5VAC H3.480 H2.380 H1.5VAC H3.480 H2.380 H1.5VAC H3.480 H2.380 H1.5VAC H3.480 H2.380 H1.5VAC H3.480 H2.380 H1.5VAC H3.480 H2.4VAC H1.5VAC H3.480 H2.4VAC H1.5VAC H3.480 H2.4VAC H1.5VAC H3.480 H2.4VAC H1.5VAC H3.480 H2.4VAC H1.5VAC H3.480 H2.4VAC H1.5VAC H3.5VAC H1.5VAC H3.5VAC H1.5VAC H3.5VAC H1.5VAC H3.5VAC H1.5VAC H3.5VAC H1.5VAC H3.5VAC H1.5VAC H3.5VAC H1.5VAC H3.5VAC H1.5VAC H3.5VAC H2.5VAC TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TBI TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII TII

Fig. 24 — Danfoss D and E Size VFD Power Panel Wiring Diagram

MTB L1 L2 L3 PE STUD 3 1L2 1L3 LEMOND ACR: ANALOG CONTROL RELAY MCB: MASTER CIRCUIT BREAKER SCB: SERVICE CIRCUIT BREAKER TB: TERMINAL BLOCK 23 "0.0" 26 A 25 24 100 200 201 2A (3) 2F FU10 2F RF 208 209 204 203 202 100 100 (2L1) (2L2) (2L3) 100A GL BLK BLK (1AWG) 114AWG (1.4AWG) 100 (1.4AWG) (1.4AWG) (1.4AWG) (1.4AWG) (1.4AWG) (1.4AWG) (1.4AWG) (1.4AWG) (1.4AWG) (1.4AWG) (1.4AWG) (1.4AWG) (1.4AWG) (1.4AWG) (1.4AWG) (2L1) (2L2) (2L3) 100A GL TO VFD NOTES: ALL WIRES USE BVR TYPE. UNMARKED WIRE DIAMETERS ARE ALL 2.5MM2. 19XR04048000 REV.D

Fig. 25 — Danfoss D and E Size VFD Power Panel Schematic (Ammeter, Voltmeter, and Surge Protective Device Options)

NOTE: See Appendix A for the 19MV controls and power panel wiring diagram. See Appendix A for the 19XR controls and compressor power panel wiring.

PD Size Drive

PARALLEL DRIVE SYSTEMS - DP1120 - DP1670

Parallel drive (PD) systems consist of four D size FC102 drives mounted in a common enclosure, creating a larger PD size with greater ampacity than D and E size drives. As per Table 4 the Carrier PD size drives offering yields a range up to 1670 amp.

The PD size drive enclosure includes both the drive components and the VFD Power Panel components which were separated in its own enclosure for the D and E drive size offering. See Fig. 26-28. NOTE: Enclosure does not represent Carrier application.

NOTE: Install Carrier-provided tophat to allow for adequate space for incoming power cables.

Fig. 26 — Parallel Drive Isometric View
Bar (GND) and Micro Switch (Typical) (Parallel Connections) Motor Busbars (U, V, W) Main Circuit Breaker (MCB) Service Circuit Breaker (SCB) Optional Line Reactor Control Section D Size Drives (4 Drive Module Design) Control Shelf Location

Fig. 27 — Parallel Drive Overall Layout

GND FU8, FU10, FU11 (Option) SPD (Option) FU8 (Option) CB1 FU1, FU2, FU3 ACR Relay CR1 Relay TB4, TB5, TB8

Fig. 28 — Control Section Component Identification

Control Shelf

The control shelf contains the MDCIC (multi-drive control interface card), and control card. The MDCIC is connected to each of the drive modules via a ribbon cable and communicates to the control card. The control card controls the operation of the drive modules. See Fig. 29.

Technical diagram of an electronic device with numbered components for identification

1 Control ShelfInterfaces with, and controls, the various drive system components. Allows connection of an external control device.
2 LCP CradleCradle where the LCP may optionally be installed, but is not provided by factory.
3 Control Terminal BlocksTerminal blocks for connecting control wiring.
4 Top Level Drive System Label Label describing the drive system at the top-level.
5 Relay Terminal BlocksTerminal blocks for connecting the relay cable from the relay connector on the top plate of drive module 1.
6 Ferrite core Reduces high frequency electromagnetic noise.
7 44-Pin Ribbon Cable Connects the individual drive module with MDCIC.
8 MDCIC Multi-drive control interface card (MDCIC) with cover plate removed.
9 SMPS Switched mode power supply
10 Pilz relay Relay
11 DIN rail Mounting
12 Terminal block Mounted on DIN rail

Fig. 29 — Control Shelf

PD Module

Each drive module has an IP00 protection rating. Four modules are connected in parallel to create a drive system. See Fig. 30-31. The parallel drive modules contain 2 DC fuses per drive module.

1 DC-link terminal and DE fuse 2 MDCIC plug 3 Microswitch to DC fuse connector 4 Relay 1 and 2 connector 5 Brake fault jumper and connector 6 Mains input terminals (inside the unit) 7 Terminal cover 8 Ground terminals 9 Top fan 10 Drive module label 11 Motor output terminals (inside the unit) 12 Heat sink and heat sink fan 13 Ground plate

Fig. 30 — View of Parallel Drive Module

1 2 DC Fuse

Fig. 31 — DC Fuse and Microswitch Connector

1 DC Fuse

2 Microswitch Connector

DC Bus

When testing parallel drive systems do the following:

  • To access the DC bus voltage, use the REGEN terminals at the top of one of the modules.
  • When testing DC bus voltage for the entire system, it is not necessary to remove the interlink connections between the individual drives.
  • When testing DC bus voltage for an individual drive, the module must be isolated by removing interlink connections and the control cable connections of the module.

For DC bus location, see Fig. 32. For more details, see the PD VFD module wiring schematic (Fig. 33).

1 2 + W FC-0F20-FR- 17703905 CU CU

1 DC (+) Bus
2 DC (-) Bus

Fasteners are M5 studs.

Fig. 32 — DC Bus Location in Parallel Drive Systems

FUSE REPLACEMENT FOR METERING KIT OPTION DESIGNATION TYPE RATED VOLTAGE RATED CURRENT FU9, FU10, FU11 CLASS CC 250VAC 2A FUSE REPLACEMENT FOR SPD KIT OPTION DESIGNATION TYPE RATED VOLTAGE RATED CURRENT FUB GL 500VAC 100A LIO LIO LIO NO FU4 FU3 FU2 FU1 4 VFD POWER MODELS CONNECTION VFD DRIVE External REF ONLY M T1-117 MOTOR CONNECTION PE PFE RFLAT1 RFLAT2 RUNNING SWEAL CABLE RELAY1 RELAY2 SPEED REFERENCE 0-16V/0-20mA ON OFF HIGH PRESSURE SWITCH SHORTDOWN INTERFACE RS 485 INTERFACE RS 485 INTERFACE T8.4 T8.5VY-T8.5I RUNSTOR OIL PUMP COMPRESSION POWER PANEL OUTPUT(50/60Hz) 220V(850VA) 115V(350VA) COMPRESSOR POWER PANEL FROM FIPS CONTROL PANEL 17 43 HIGH PRESSURE SWITCH 11 14 SWITCHER INTERFACE R12 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.38 T8.4 T8.5VY-T8.5I RUNSTOR OIL PUMP COMPRESSION POWER PANEL OUTPUT(50/60Hz) 220V(850VA) 115V(350VA) COMPRESSOR POWER PANEL FROM FIPS CONTROL PANEL 17 43 HIGH PRESSURE SWITCH 11 14 SWITCHER INTERFACE R12 0.37 0.37 0.37 0.37 0.37 0.37 0.37 115V/16.0 R12 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.38 T8.4 T8.5VY-T8.5I RUNSTOR OIL PWP COMPRESSION POWER PANEL OUTPUT(50/60Hz) 220V(850VA) 115V(350VA) COMPRESSOR POWER PANEL FROM FIPS CONTROL PANEL 17 43 HIGH PRESSURE SWITCH 11 14 SWITCHER INTERFACE R12 0.37 0.37 0.37 0.37 0.37 0.37 115V/16.0 R12 0.37 0.37 0.37 0.37 0.37 115V/16.0 T8.4 T8.5VY-T8.5I RUNSTOR OIL PWP COMPRESSION POWER PANEL OUTPUT(50/60Hz) 220V(850VA) 115V(350VA) COMPRESSOR POWER PANEL FROM FIPS CONTROL PANEL 17 43 HIGH PRESSURE SWITCH 11 14 SWITCHER INTERFACE R12 0.37 R12 0.37 0.37 0.37 0.37 115V/16.0 R12 0.37 0.37 0.37 0.37 115V/16.0 T8.4 T8.5VY-T8.5I RUNSTOR OIL PWP COMPRESSION POWER PANEL OUTPUT(50/60Hz) 220V(850VA) 115V(350VA) COMPRESSOR POWER PANEL FROM FIPS POWER PANEL 17 43 HIGH PRESSURE SWITCH 11 14 SWITCHER INTERFACE R12 0.37 R12 0.37 0.37 0.37 115V/16.0 R12 0.37 0.37 0.37 115V/16.0 T8.4 T8.5VY-T8.5I RUNSTOR OIL PWP COMPRESSION POWER PANEL OUTPUT(50/60Hz) 220V(850VA) 115V(350VA) COMPRESSOR POWER PANEL FROM FIPS POWER PANEL 17,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44,44, FUS REPLACEMENT FOR STANDARD OPTION LEGENDS ACE: ANALOG CONTROL RELAY HCD: MASTER CIRCUIT BREAKER SCR: SERVICE CIRCUIT BREAKER TB: TERMINAL BLOCK OS3 / OS2 / OS1 / OIL PUMP POWER SUPPLY N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A TO CONTROL PULC + WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTR : WTF | MUTRON TRANSFORMER PIR: RISOMARID BRI: PRINATE MOLD (S/O/69HZ) RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: RJ: SUECKEER SUECKEER (S/O/69HZ) SUECKEER SUECKEER (S/O/69HZ) SUECKEER SUECKEER (S/O/69HZ) SUECKEER SUECKEER (S/O/69HZ) SUECKEER SUECKEER (S/O/69HZ) SUECKEER SUECKEER (S/O/69HZ) SUECKEER SUECKEERA LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCl : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : LCL : FAN AND VFD CONTROL POWER SUPPLY FUS MODULE CONTROL POWER VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE Board VFD DRIVE BOARD VFD DRIVE BOARD VFD DRIVE BOARD VFDINEVECS A/C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D EFS DESECE C D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S D A/S T8X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X2X

Fig. 33 — Danfoss PD VFD Module Wiring Schematic

START-UP Alternate Wire Lugs

DANGER

Internal components and circuit boards of the drive are live when the drive is connected to incoming power. Coming into contact with this voltage is extremely dangerous and will result in severe personal injury or death.

The motor terminals U, V, W and the DC bus (DC+ and DC-) are live when the drive is connected to incoming power, even if the motor is not running.

Do not make any connections when the drive is connected to the incoming power.

After having disconnected the drive, if any service work is to be performed wait for the capacitors to fully discharge. The minimum waiting time is specified on the drive label.

Prior to performing any repair work measure DC bus voltage with a volt meter. For drives in parallel ensure to measure DC bus voltage before and after the individual DC fuses.

Before connecting the drive to the incoming power, make sure that the enclosure is closed.

WARNING

The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O terminals may have a dangerous control voltage present even when the drive is disconnected from incoming power. Coming into contact with this voltage could result in severe personal injury.

If the incoming power wire size in the VFD power panel does not fit the standard lug, alternate lugs may be available. Please contact the circuit breaker manufacturer for availability. Note that lugs rated for a higher current than the circuit breaker may be used. See Table 5 or 6 for wire lug specifications.

Verify Installation

Record the following job information:

  1. Job Name
  2. Job Number
  3. City
  4. State
  5. Zip Code

Record the following nameplate information, it is suggested to take a picture of the appropriate nameplates for future reference.

  1. From the Danfoss nameplate (Fig. 1) located inside the VFD enclosure:

a. Danfoss Type Code (TC) Number
b. Danfoss Serial Number

  1. From the machine nameplate (Fig. 34) located on the VFD enclosure:

a. Chiller Serial Number
b. Chiller Model
c. Motor rated load amps
d. Motor nameplate rpm
e. Motor nameplate kW
f. Motor nameplate voltage
g. Voltage

Grounding bar hole size:

DD/DE size 14 mm (0.55 in.)

PD size 18 mm (0.71 in.)

Table 5 — 19XRV Wire Lugs

VOLTAGE VFDMAX RATED OUTPUT AMPBREAKER AMP SIZEABB LUGLUG CABLE RANGE
380-439VDD588570800A1SDA113095R1(3) 2/0-400 kcmil
DE658638800A1SDA113095R1(3) 2/0-400 kcmil
DE745722800A1SDA113095R1(3) 2/0-400 kcmil
DE800776800A1SDA113095R1(3) 2/0-400 kcmil
DE8808531000A1SDA104758R1(4) 4/0-500 kcmil
DE9909601000A1SDA104758R1(4) 4/0-500 kcmil
DP112010861600AK8TM(4) 1/0-750 kcmil
DP126012221600AK8TM(4) 1/0-750 kcmil
DP146014162000AK8TM(4) 1/0-750 kcmil
DP167016192000AK8TM(4) 1/0-750 kcmil
440-480VDD588518800A1SDA113095R1(3) 2/0-400 kcmil
DE658572800A1SDA113095R1(3) 2/0-400 kcmil
DE745658800A1SDA113095R1(3) 2/0-400 kcmil
DE800708800A1SDA113095R1(3) 2/0-400 kcmil
DE8807571000A1SDA104758R1(4) 4/0-500 kcmil
DE9908631000A1SDA104758R1(4) 4/0-500 kcmil
DP112010191600AK8TM(4) 1/0-750 kcmil
DP126011251600AK8TM(4) 1/0-750 kcmil
DP146013392000AK8TM(4) 1/0-750 kcmil
DP167014842000AK8TM(4) 1/0-750 kcmil

Table 6 — 19MV Wire Lug Table

VOLTAGE VFDMAX RATED OUTPUT AMPBREAKER AMP SIZEABB LUGLUG CABLE RANGE
380-439DD395 427 800 1SDA113095R1 (3)2/0-400 kcmil
DD480 518 800 1SDA113095R1 (3)2/0-400 kcmil
DD588 635 800 1SDA113095R1 (3)2/0-400 kcmil
DE658 711 800 1SDA113095R1 (3)2/0-400 kcmil
DE745 80512001SDA104758R1 (4) 4/0-500 kcmil
DE800 86412001SDA104758R1 (4) 4/0-500 kcmil
DE880 95012001SDA104758R1 (4) 4/0-500 kcmil
DE990106912001SDA104758R1(4) 4/0-500 kcmil
440-480DD395 390 800 1SDA113095R1 (3)2/0-400 kcmil
DD480 478 800 1SDA113095R1 (3)2/0-400 kcmil
DD588 578 800 1SDA113095R1 (3)2/0-400 kcmil
DE658 637 800 1SDA113095R1 (3)2/0-400 kcmil
DE745 73212001SDA104758R1 (4) 4/0-500 kcmil
DE800 78812001SDA104758R1 (4) 4/0-500 kcmil
DE880 84212001SDA104758R1 (4) 4/0-500 kcmil
DE990 96112001SDA104758R1 (4) 4/0-500 kcmil

Carrier MODEL NUMBER SERIAL NUMBER MACHINE NAMEPLATE SUPPLY DATA VOLTS/PHASE/HERTZ LOCKED MOTOR AMPS OVERLOAD TRIP AMPS MAX FUSE/CIRCUIT BREAKER SIZE MIN SUPPLY CIRCUIT AMPACITY MACHINE ELECTRICAL DATA MOTOR NAMEPLATE VOLTAGE COMPRESSOR 100% SPEED RATED LINE VOLTAGE RATED LINE AMPS RATED LINE RILOWATIS MOTOR RATED LOAD KW MOTOR RATED LOAD AMPS MOTOR NAMEPLATE AMPS MOTOR NAMEPLATE RPM MOTOR NAMEPLATE KW INVERTER PWM FREQUENCY SCCR KA SAFETY CODE CERTIFICATION THE COMPRESSOR MOTOR CONTROLS AND HENDER PROTECTION MUST BE IN ACCORDANCE WITH CARRIER SPECIFICATION 2-49. INFORMATION KEY 3 Carrier MODEL NUMBER SERIAL NUMBER MACHINE NAMEPLATE SUPPLY DATA VOLTS/PHASE/HERTZ VFD INPUT AMPS OVERLOAD TRIP AMPS MAX FUSE/CIRCUIT BREAKER SIZE MIN SUPPLY CIRCUIT AMPACITY MACHINE ELECTRICAL DATA MOTOR NAMEPLATE VOLTAGE COMPRESSOR 100% SPEED Hz RATED LINE VOLTAGE RATED LINE AMPS RATED LINE RILOWATIS MOTOR RATED LOAD KW MOTOR RATED LOAD AMPS MOTOR NAMEPLATE AMPS MOTOR NAMEPLATE RPM MOTOR NAMEPLATE KW INVERTER PWM FREQUENCY IN: STATOR WINDING RESISTANCE ONKS MOTOR D-AXIS INDUCTANCE IN MOTOR G-AXIS INDUCTANCE IN MOTOR BACK EMF VOLTS SCCR KA MOTOR RATED TORQUE N m SAFETY CODE CERTIFICATION THE COMPRESSOR MOTOR CONTROLS AND HENDER PROTECTION MUST BE IN ACCORDANCE WITH CARRIER SPECIFICATION 2-49. INFORMATION KEY 3

Fig. 34 — 19XRV/19MV Machine Nameplate

Configure the VFD

All configurations required by the VFD are supplied by the HMI through the VFD Gateway. The Danfoss Std Tier VFD can operate with PIC6 via LEN. Any configuration changes necessary and possible are made on the HMI screens. A complete set of configurations is transmitted to the VFD each time the controls are powered up.

Table 7 shows parameters in the Unit Mounted VFD Configuration menu for PIC6. Parameters in italics are to be entered or confirmed at start-up.

Table 7 — VFD Configuration (PIC6/UM VFD Configuration) CFGUMVFD - UM VFD Configuration

PARAMETER ^a DEFAULT VALUE
COMPRESSOR 100% SPEED60
RATED LINE VOLTAGE460
MOTOR NAMEPLATE CURRENT200
MOTOR RATED LOAD CURRENT200
MOTOR NAMEPLATE VOLTAGE ^b 460
MOTOR NAMEPLATE RPM3000
MOTOR NAMEPLATE KW1500
INCREASE RAMP TIME ^b 30
DECREASE RAMP TIME ^b 30
MOTOR RATED TORQUE (NM) ^c 1500
SWITCH FREQUENCY (kHz) ^c 5
STATOR RESISTANCE (Rs) ^c 0.001
D-AXIS INDUCTANCE (Ld) ^c 0.010
Q-AXIS INDUCTANCE (Lq) ^c 0.010
BACK EMF AT 1000 RPM ^c 10

NOTE(S):
a. Parameters in italics are to be entered or confirmed at start-up.
b. 19XRV only
c. 19MV only

Commissioning the Unit

The commission procedure is as follows:

  1. If the chiller has been stored outdoors, allow at least 24 hours room temperature stabilization prior to commissioning. Ensure any condensation that occurs as a result of the ambient temperature is allowed to evaporate.
  2. Verify parameters in the VFD_CONF UM VFD Config (CFGUMVFD) screen against chiller nameplate.
  3. Install surge suppression devices if required.
  4. Review the power wiring and grounding to ensure that it has been properly connected.
  5. Visually examine the inside of the drive enclosure to:

a. Look for signs of corrosion or moisture residue.
b. Remove any dirt or debris.
c. Make sure all vents are clear.

  1. Apply power to the drive and take thermal measurements of the capacitor bank and power connections. Do this again before start-up.

©

©

©

Table 8 — Typical Fault Code Descriptions and Corrective Actions* (cont)

DANFOSS ALARM/WARNING CODEDANFOSS ALARMPIC6 ALARM CODEPIC6 - DESCRIPTIONPIC6 DISPLAY DANFOSS VFD ALARM IN MAINTENANCE MENUDESCRIPTION AND POSSIBLE CORRECTIVE ACTION
33 Inrushfault 449 VFD FaultInrush FaultExcessive power-ups have occurred within a short time period. Allow unit to cool. Check DC bus voltage.
34Fieldbus communication fault449 VFD FaultField Bus FaultThe fieldbus on the communication option card is not working. Verify that the wiring is correct. In addition, verify parameter 8.01 = 0 Digital and ctrl.word and 8.02 = 1 FC Port.
36 Mainsfailure 454VFD Fault - Main Power FailureMains failure Check fuses to drive and supply power to the chiller.
38 Internalfault 449 VFD FaultInternal FaultWhen an internal fault occurs, a code number is shown. This fault occurs when there is a communication error between the control card and the power card. Try the following: Cycle power, check that any options are installed correctly, check for loose or missing wires. It may be necessary to contact Danfoss Technical Support.
39 Heat sink sensor449 VFD FaultFault —No feedback from the heat sink temperature sensor. The power card does not sense the IGBT thermal sensor. Problem could be the power card, the gatedrive card or the ribbon cable connection between the power card and gatedrive card.
40Warning - overload of digital output terminal 27.449 VFD Fault —Check the load connection to terminal 27 and remove the short-circuit connection.
45Earth Fault While Ramping449VFD FaultThere is current from the output phase to ground, either in the cable between the drive and the motor, or in the motor itself. The current transducers detect the ground fault by measuring current going out from the drive and current going into the drive from the motor. Ground fault is issued if the deviation of the two currents is too large. The current going out of the drive must be the same as the current going into the drive. Troubleshoot as follows: Remove AC power from the drive and disconnect the motor. Power the drive back on and reset the fault by pressing the "Reset" key. Run the VFD with no motor to see if the fault appears or if the drive runs without tripping. Observe the motor current in the display. It should be very close to zero with no motor connected. Reconnect the motor and attempt to run the drive again. If the drive trips on an "Alarm 14" with the motor disconnected, then the problem is inside the drive. A bad current sensor is most likely the cause of this type of fault. If the drive runs without the motor connected, but the current shown in the display is greater than 0.3 amps then it has a faulty current sensor. If the drive runs with no motor connected and the current shown in the display is less than 0.3 amps, then the ground fault is likely in the connecting cables or the motor. Check the motor and connected cables with a megohmmeter to find out which has the short. May need to check motor internal lugs with a megohmmeter to find out if short is in the motor terminal. reconnect the motor. In the event that there is current shown in the display with no motor connected, performing a "manual initialization" of the drive might help in zeroing out the current sensors. With power off, press and hold the "Status", "Main Menu" and "OK" keys on the keypad (not provided). Power the drive back on while holding the keys for 5 seconds. The drive will power up in an alarm 80 "Drive Initialization" if successful. WARNING: A manual initialization will cause the drive to revert back to factory default settings, wiping out all parameter changes, any fault log data, and any personal menu settings that have been made, so ensure the drive parameter file with MCT 10 has been downloaded prior to doing this reset.
46Power card supply449VFD FaultThe supply on the power card is out of range. Check for a defective power card, control card, option card, 24 V DC power supply, defective heat sink fan.
4724 V supply low449VFD Fault24V Supply FaultThe supply on the power card is out of range. Check for a defective power card.
481.8 V supply low449VFD Fault1.8V Supply FaultThe 1.8 V DC supply used on the control card is outside of the allowable limits. The supply is measured on the control card. Check for a defective control card. If an option card is present, check for overvoltage.
57AMA internal fault449VFD FaultAMA Not OKNot relevant; Carrier default has AMA =0 [off].
59Current Limit449VFD FaultCurrent is higher than the value in P4-18 Current Limit. Verify configured motor data.
65Control card over temperature449 VFD FaultCtrl Card overtempThe cutout temperature of the control card is 85^ C( 185^ F) . Check the following: Ambient temperature, clogged filters, fan operation, control card.
67Option module configuration has changed449 VFD FaultOption ChangeOne or more options have either been added or removed since the last power-down. Check that the configuration change is intentional and reset the unit.

Table 8 — Typical Fault Code Descriptions and Corrective Actions* (cont)

DANFOSS ALARM/WARNING CODEDANFOSS ALARMPIC6 ALARM CODEPIC6 - DESCRIPTIONPIC6 DISPLAY DANFOSS VFD ALARM IN MAINTENANCE MENUDESCRIPTION AND POSSIBLE CORRECTIVE ACTION
68 Safe Stop activated 449 VFD Fault Safe StopSafe Torque Off (STO) has been activated. To resume normal operation, apply 24 V DC to terminal 37, then send a reset signal (via bus, digital I/O, or by pressing [Reset]).
69Power card temperature449 VFD FaultThe power card temperature sensor is either too cold or too hot. Verify ambient operating temperature, check filters, verify fans are operating, check power card.
70Illegal FC configuration449 VFD FaultControl and power cards are incompatible. Verify type code from unit nameplate and part numbers of cards with supplier of the parts.
71 PTC 1Safe Stop 449 VFD Fault PTC1 Safe StopSafe Torque Off (STO) has been activated from the VLT PTC Thermistor Card MCB 112 because the motor is too warm. Once the motor cools and the digital input from the MCB 112 is deactivated, normal operation can resume when the MCB 112 applies 24 V DC to terminal 37 again. When the motor is ready for normal operation, a reset signal is sent (via serial communication, digital I/O, or by pressing [Reset] on the LCP). If automatic restart is enabled, the motor can start when the fault is cleared.
72 Dangerous failure 449 VFD Fault Dangerous FailureSafe Torque Off (STO) with trip lock. Unexpected signal levels on safe torque off and digital input from the VLT PTC Thermistor Card MCB 112.
79Illegal power section configuration449 VFD FaultThe power card scaling card is incorrect or is not installed.
80Drive initialized to default value449 VFD FaultDrive InitializedParameter settings are initialized to default settings after a manual reset. To clear alarm, reset unit.
94End of curve449VFD FaultEnd of Curve22-50=[0]Off
95Broken belt449VFD FaultBroken Belt22-60=[0]Off
99Locked rotor449VFD FaultAn overload condition was detected. This can indicate a locked compressor/motor. Further inspection is required.
243Brake IGBT449VFD FaultBrake IGBT FaultNot relevant; no brake IGBT.
245Heat Sink Sensor449VFD FaultNo feedback from the heat sink sensor. See Alarm 39.
250New spare part449VFD FaultN/AParameter 14-23 type code (T/C) must be set correctly. Will occur when power or switch mode supply has been replaced and the drive type code must be set correctly in EEPROM in accordance with the drive label. At index number 20 in parameter 14-23 enter Save to EEPROM and press the OK key. Alarm will change to Alarm 251. To reset alarm 251 remove power to the unit and reapply power and press the Reset key to clear the alarm. Important: A keypad is required to enter the type code.
251New type code449VFD FaultService Trip, Type codeThe power card or other components have been replaced and the type code has been changed. Cycle power and reset the drive to remove the warning and to resume normal operation.
N/AN/A311N/ALoss Communication with Danfoss VFDLEN Communication error with VFD is lost. Check wiring. Note that for new drive not factory configured for Carrier or after software upgrade LEN must be enabled. Set parameter 14-29 to 00006100. This gives access to hidden parameter 14-23. Change this parameter using a field-provided keypad With keypad: Press OK once. You should now have a cursor on the value [00] just below the parameter number and name. Increase this by pressing the UP key until the value [12] and you see this on the line below: "[nnn] SXXX (std. sw)". Press OK and change to "[nnn] S009 (Special sw)", with the UP and DOWN buttons. Press OK again. You should have the cursor in the same place as on the previous step. Press UP until the value is [20]; press OK; change to [1] Save to EEPROM; press OK. You should now get a trip lock alarm A251 New Type Code. Do a power cycle and reset the alarm. It should be okay now. Check parameter 8-30; change it to [20] LEN if necessary.

NOTE: This is not a complete list of Danfoss FC102 codes. If a warning/alarm is present which is not included in this table refer to the Danfoss manual.

Checking Power Modules and Motor Input with Input Power Off — Static Test

Use the following procedure to check the drive's power module circuitry with power off:

  1. Turn off and lock out input power. Wait appropriate time as per Danfoss VFD nameplate.
  2. Verify there is no voltage at the drive's input power terminals.
  3. Using a voltmeter, check the DC bus potential as described in the section Verifying That DC Bus Capacitors Are Discharged to ensure the DC bus capacitors are discharged.
  4. Disconnect the motor from the drive.
  5. Check all AC line and DC bus fuses.
  6. Use a multimeter to perform a static check on the input diodes and output IGBTs. See Table 9. For parallel drives this test will have to be done for each individual drive module, so in addition to removing the input and motor busbars for parallel drives the DC link connection will have to be removed for the individual drives.
  7. Check motor impedance.
  8. Reconnect the motor to the drive.
  9. Reapply input power.

WARNING

DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power, wait the time specified in Table 1 or as specified on the Danfoss VFD nameplate. For the DC bus capacitors to discharge and then check the voltage with a voltmeter rated for the DC bus voltage to ensure the DC bus capacitors are discharged before touching any internal components. For parallel drive modules (N630 and larger) check voltage before and after the individual DC fuses. Failure to observe this precaution could result in severe bodily injury or loss of life.

An isolated multimeter will be needed to measure DC bus voltage and to make resistance checks.

Table 9 — Diode Checks

METER LEADMETER READING
(+) (-)
RDC+ Infinite (OV)
DC-Infinite (OV)
SDC+Infinite (OV)
DC- Infinite (OL)
TDC+Infinite (OV)
DC-Infinite (OV)
UDC+0.3 to 0.7 v
DC- Infinite (OL)
VDC+0.3 to 0.7 v
DC- Infinite (OL)
WDC+0.3 to 0.7 v
DC- Infinite (OL)
DC+RInfinite (OL)
S
T
U
V
W
DC-R0.3-0.7v
S
T
U
V
W

Digital meters require a special diode check function because the current sourced by the meter during a normal resistance (Ohms) test is too low to accurately test a diode. Make sure the meter is set to the diode test function. Voltage readings may not be exact as shown in above table, but look for consistency during each of the 4 tests. When performing a test that should return infinity (OL) as shown in above table, you should see a value slowly climbing toward infinity. This is a result of the meter charging a capacitor and is normal.

If an incorrect reading is observed associated with U, V, W (outputs) this indicates a failed inverter IGBT module. Replace the shorted IGBT modules. Similarly if an incorrect reading is observed associated with R, S, T (inputs) this indicates a shorted SCR. Replace the shorted SCR module.

Servicing the Drive

WARNING

To guard against possible personal injury and/or equipment damage:

  1. Inspect all lifting hardware for proper attachment before lifting drive.
  2. Do not allow any part of the drive or lifting mechanism to make contact with electrically charged conductors or components.
  3. Do not subject the drive to high rates of acceleration or deceleration while transporting to the mounting location or when lifting.
    Do not allow personnel or their limbs directly underneath the drive when it is being lifted and mounted.

WARNING

DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power, wait the time specified in Table 1 or as specified on the Danfoss VFD nameplate. For the DC bus capacitors to discharge and then check the voltage with a voltmeter rated for the DC bus voltage to ensure the DC bus capacitors are discharged before touching any internal components. For parallel drive modules (N630 and larger) check voltage before and after the individual DC fuses. Failure to observe this precaution could result in severe bodily injury or loss of life.

An isolated multimeter will be needed to measure DC bus voltage and to make resistance checks.

Refer to Fig. 35 for location of DC bus terminals.

1 L1 L2 L3 Lockout/Tagout 2 DC Bus Test Terminals Located Inside Access Door DC+ DC- 0V Multimeter

Fig. 35 — Check DC Bus Terminals

For FC102 service guide lines, refer to Danfoss Manuals; the latest Service Guide for VLT FC Series is MG94A502.

APPENDIX A — WIRING SCHEMATICS
DIP SWITCH LEGEND SWITCH ON SWITCH OFF ON BLACK IS RAISED PORTION OF SWITCH 210B COMPRESSOR POWER PANEL WIRING PART CONTROL PANEL WIRING PART HMI COMMER ETHERNET SWITCH MODEM ETHERNET FIELD INSTALLATION

19XR05044702 REV L

Fig. A - 19XRV Chiller Control Schematic (PIC6)

APPENDIX A — WIRING SCHEMATICS (CONT)
CARRIER AquaEdge 23XRV - WARNING - 3

flowchart
graph TD
    subgraph Sensor1
        A["310B Module"] --> B["Max"]
        A --> C["OR"]
        A --> D["Input"]
        A --> E["Output"]
    end

    subgraph Sensor2
        F["410B Module"] --> G["Max"]
        F --> H["OR"]
        F --> I["Input"]
        F --> J["Output"]
    end

    subgraph Control
        K["MINI OF EXAP_LWP"] --> L["MINI OF EXAP_LWP"]
        M["MINI OF EXAP_LWP"] --> N["MINI OF EXAP_LWP"]
        O["MINI OF EXAP_LWP"] --> P["MINI OF EXAP_LWP"]
        Q["MINI OF EXAP_LWP"] --> R["MINI OF EXAP_LWP"]
        S["MINI OF EXAP_LWP"] --> T["MINI OF EXAP_LWP"]
        U["MINI OF EXAP_LWP"] --> V["MINI OF EXAP_LWP"]
        W["MINI OF EXAP_LWP"] --> X["MINI OF EXAP_LWP"]
        Y["MINI OF EXAP_LWP"] --> Z["MINI OF EXAP_LWP"]
        AA["MINI OF EXAP_LWP"] --> AB["MINI OF EXAP_LWP"]
        AC["MINI OF EXAP_LWP"] --> AD["MINI OF EXAP_LWP"]
        AE["MINI OF EXAP_LWP"] --> AF["MINI OF EXAP_LWP"]
        AG["MINI OF EXAP_LWP"] --> AH["MINI OF EXAP_LWP"]
        AI["MINI OF EXAP_LWP"] --> AJ["MINI OF EXAP_LWP"]
        AK["MINI OF EXAP_LWP"] --> AL["MINI OF EXAP_LWP"]
        AM["MINI OF EXAP_LWP"] --> AN["MINI OF EXAP_LWP"]
        AO["MINI OF EXAP_LWP"] --> AP["MINI OF EXAP_LWP"]
        AQ["MINI OF EXAP_LWP"] --> AR["MINI OF EXAP_LWP"]
        AS["MINI OF EXAP_LWP"] --> AT["MINI OF EXAP_LWP"]
        AU["MINI OF EXAP_LWP"] --> AV["MINI OF EXAP_LWP"]
        AW["MINI OF EXAP_LWP"] --> AX["MINI OF EXAP_LWP"]
        AY["MINI OF EXAP_LWP"] --> AZ["MINI OF EXAP_LWP"]
        BA["MINI OF EXAP_LWP"] --> BB["MINI OF EXAP_LWP"]
        BC["MINI OF EXAP_LWP"] --> BD["MINI OF EXAP_LWP"]
        BE["MINI OF EXAP_LWP"] --> BF["MINI OF EXAP_LWP"]
        BG["MINI OF EXAP_LWP"] --> BH["MINI OF EXAP_LWP"]
        BI["MINI OF EXAP_LWP"] --> BJ["MINI OF EXAP_LWP"]
        BK["MINI OF EXAP_LWP"] --> BL["MINI OF EXAP_LWP"]
        BM["MINI OF EXAP_LWP"] --> BN["MINI OF EXAP_LWP"]
        BO["MINI OF EXAP_LWP"] --> BP["MINI OF EXAP_LWP"]
        BQ["MINI OF EXAP_LWP"] --> BR["MINI OF EXAP_LWP"]
        BS["MINI OF EXAP_LWP"] --> BT["MINI OF EXAP_LWP"]
        BU["MINI OF EXAP_LWP"] --> BV["MINI OF EXAP_LWP"]
        BW["MINI OF EXAP_LWP"] --> BX["MINI OF EXAP_LWP"]
        BYD["MINI OF EXAP_LWP"] --> BZ["MINI OF EXAP_LWP"]
        CA["MINI OF EXAP_LWP"] --> CB["MINI OF EXAP_LWP"]
        CC["MINI OF EXAP_LWP"] --> CD["MINI OF EXAP_LWP"]
        CE["TTR_HIGH"] --> CF["TTR_LOW"]
    end

    subgraph Control
    G
    H
    I
    J
    K
    L
    M
    N
    O
    P
    Q
    R
    S
    T
    U
    V
    W
    X
    Y
    Z
    AA
    AB
    AC
    AD
    AE
    AF
    AG
    AH
    AI
    AJ
    AK
    AL
    AM
    AN
    AO
    AP
    AQ
    AR
    AS
    AT
    AU
    AV
    AW
    AX
    AY
    AZ
    BA
    BB
    BC
    BD
    BE
    BF
    BG
    BH
    BI
    AJ
    AK
    AL
    AM
    AN
    AO
    AP
    AQ
    AW
    AX
    AY
    AZ
    BA
    BB
    BC
    BD
    BE
    BF
    BG
    BH
    BI
    AJ
    AK
    AL
    AM
    AN
    AO
    AP
    AQ
    AW
    AX
    AY
    AZ
    BA
    BB
    BC
   BD
    BE
    BF
    BG
    BH
    BI
    AJ
    AK
    AL
    AM
    AN
    AO
    AP
    AQ
    AW
    AX
    AY
    AZ
    BA
    BB
    BC
   BD
    BE
    BF
    BG
    BH
    BI
    AJ
    AK
    AL
    AM
    AN
    AO
    Ap

POWER CONNECTION NOTE: TE-1 AND TE-2 ARE FOR EXTERNAL ZAIC POWER SUPPLY CONNECTION LIMITED TO 105/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40/40 CONTROL RELAY CONTACT 3TB 3.213 RES_STOP NOTE: THE DIGITAL INPUT LOOP IS PONFED BY EXTERNAL POWER SUPPLY EACH DISCRETE INPUT SHALL DETECT WHIPER IN EXTERNAL SWITCH ON CONTRACTOR IS OPEN OR CLOSED OR SPINED. FOR VFD INTERLOCK CONTROL ROCKWELL VFD CONNECTION WITH THE CONTROL PANEL 3TB 3.212 ALE 4TB 4.212 TFP_HIGH TFP_LOW NOTE: EACH DIGITAL OUTPUT LOOP SHALL BE LIMITED TO A MAXIMUM OF 16 NC MNC. STANDARD AND 16 NMR, LIGHT LOAD RELAY IS RECOMMENDED AND THE COIL VOLTAGE OF RELAY IS ZAIC. DIGITAL INPUT ANALOG OUTPUT 3TB 3.213 6P ANALOG INPUT NOTE: THE ANALOG INPUTS SUPPORT SETTOR THERMISTOR, 2-3NNA SENSOR AND SOC SENSOR. 3TB 3.216 8.375 RJ_INT RJ_INT R.HISIT AUTO.NES AUTO.TEN AUTO.DEN AUTO.T RF.LEA4 ANALOG INPUT NOTE: THE ANALOG INPUTS SUPPORT SETTOR THERMISTOR, 2-3NNA SENSOR AND SOC SENSOR.

19XR05044703 REV L

Fig. A - 19XRV Chiller Control Schematic (PIC6) (cont)

APPENDIX A — WIRING SCHEMATICS (CONT)
LEGEND △ DENOTES OIL PUMP TERMINAL ○ DENOTES POWER PANEL TERMINAL □ DENOTES CONTROL PANEL TERMINAL ○ DENOTES COMPONENT TERMINAL • WIRE SPlice —— OPTION WIRING —— DENOTES NALE/FEMALE O.C. + DENOTES HACH. CONTROL PANEL CONN. ** DENOTES MOTOR STARTER PANEL CONN. ABBREVIATION LISTING HGBP HOT GAS BYPASS GVA GUIDE VANE ACTUATOR C CONTACTOR IOS INPUT OUTPUT BOARD CB CIRCUIT BREAKER TB TERMINAL BOARD FU FUSE 115V 22 12 (BLK) (BLK) COMM 23 1C 13 (WHT) (WHT) TO GVA L1 BLK 75kA 84 (WHT) TO GVA L2 (WHT) TO GVA L2 (WHT) TO GVA L1 (BLK) TO IOB2 J12-10* (WHT) TO TB5-51** (RED) TO TB5-50** (ORN) TO TB5-43** (BRN) TO TB5-17** (BLK) TO VFD (CLR) B TO VFD (BLK) TO VFD (RBD) SHIELD A 1TB A B C 19KR05045002 REV E COMPRESSOR POWER PANEL WIRING SCHEMAIC COMPR OIL PUMP MOTOR WINDING HIGH TEMPERATURE WHT COMP R OIL PUMP MOTOR C1 C2 COMPR OIL PUMP C1 C2 C2 (WHT) HGBP (BRN) 3C 3 (OPTIONAL) (BLU) IORN) TO IOB2 J12-2* TO IOB2 J12-1* TO S24V** TO SOV* TO TO 24V** TO 1TB PS-L PS-N PS-GND TO 24VAC (BLK) (WHT) (BLK) (WHT) T1 24VAC (BRN) (BRN) (RED) (GRN) TO 524V** TO TO 24V** TO 1TB PS-L PS-N PS-GND T1 24VAC (BLK) (WHT) (BLK) (WHT) T2 24VAC (BRN) (BRN) (RED) (GRN) TO 524V** TO TO 24V** TO 1TB PS-L PS-N PS-GND HGBP SOLINOID 115V WIRING HOT GAS BYPASS OPTION FOR FR. 1, 2, 3, 4, 5 & 6 WT. EXCH. FUSE REPLACEMENT 1FU(SA) HT10KB153 2FU(LGA) HT10KB160 3FU(DSA) HT10KB135 GROUNDS LUG GROUNDS CREM HGBP OPTION (BLK) (RED) (BRN) (BRN) (RED) (GRN) (RED) (BRN) (RED) (BRN) (RED) (BRN) (RED) (BRN) (RED) (BRN) (RED) (BRN) (RED) (BRN) (RED) (BRN) (RED) (BRN) (RED) (BRN) (RED) (BRN) (RED) (BRN) (RED) (BRN) (RED) (BRN) (RED) (BRN)

Fig. B — 19XRV Compressor Power Panel Schematic

36
APPENDIX A — WIRING SCHEMATICS (CONT)
TO 3108-JA LEN/485-IN (ICE (MOYA) K) 2 J2-3 RED 16 2 J2-3 VIO 16 2 J2-3 WNT 16 2 J2-3 GND C2 20 L12 LEN/485-IN J12 POWER IN 3 J15-1 RED 16 CB1 CB1,1 RED 16 47.8 5 J15-2 GNT 16 ECP ESTOP,3 STATUS CONF.FS L12 EVAF.FS OPTIONAL ICE,CON SWI,STOP REN,CON OPTIONAL SEM,LOCH ECON,P SV EVAF,P SV CONO,P SV EVAF,T LCW ECW ECN OPTIONAL AUTO,THW 7 J2-3 VIO 16 7 J2-3 VIO 16 7 J2-3 VIO 16 7 J2-3 VIO 16 7 J2-3 VIO 16 7 J2-3 VIO 16 7 J2-3 VIO 16 7 J2-3 VIO 16 7 J2-3 VIO 16 7 J2-3 VIO 16 EOP SWITCH LEO/NO Switch ON Switch OFF SN1 ADDRESS:0000 4321 TIRLE 5 J2-3 GNT 16 5 J2-3 BLU 16 5 J2-3 VIO 16 5 J2-3 VIO 16 5 J2-3 VIO 16 ICR,A1 VIO 16 ICR,A2 GNT 16 ACR,A1 VIO 16 ACR,A2 GNT 16 NOT USED EXP.COL.SYS.VLT ATR INT,RON,STAT ECONJER ECV ECON,EV,2 GNT 20 ECON,EV,3 HDT 20 ECON,EV,4 SEL 20 ECON,EV,4 RIN 20 CONDENSER ECV CONDENSER ECV TO MTI [SEE SHEET MTI] J1.5 LEN/485-OUT J2.4 POWER OUT J1.9 LEN/485-OUT J2.4 POWER OUT

2001503201 REV. 0

SYMBOL LEGEND
TERMINAL BLOCK
FEMALE CONNECTOR
MALE CONNECTOR
......OPTIONAL WIRING
NORMALLY OPEN
NORMALLY CLOSED
CONTACT (N O.)
CONTACT (N C.)
THERMOSTAT
THERMISTOR
COIL
CARLE
TPRESSURE SWITCH
TPRESSURE TRANSDUCER
FUSE
CIRCUIT BREAKER
FLOW SWITCH
GROUND

Fig. C — 19MV SIOB

APPENDIX A — WIRING SCHEMATICS (CONT)

Fig. D — 19MV IOB2

APPENDIX A — WIRING SCHEMATICS (CONT)

Fig. E — 19MV IOB3

APPENDIX A — WIRING SCHEMATICS (CONT)
39 FOM 120V-12 120V-120V 120V SHEET M1 FOM 220V-12 120V-220V-12 120V SHEET M1 FOM 220V-12 120V-220V-12 120V SHEET M1 FOM 220V-12 120V-220V-12 120V SHEET M1 FOM 220V-12 120V-220V-12 (OUT) FOM 220V-12 120V-220V-12 (OUT) FOM 220V-12 120V SHEET M1 FOM 220V-12 120V SHEET M1 FOM 220V-12 120V SHEET M1 FOM 220V-12 120V SHEET M1 FOM 220V-12 120V SHEET M1 FOM 220V-12 120V SHEET M1 FOM 165A-17 165A-17 165A-17 165A-17 165A-17 165A-17 165A-17 165A-17 165A-17 165A-17 165A-17 165A-17 165A-17 165B-18 18 FOM 435A-435A-435A-435A-435A-435A-435A-435A-435A-435A-435A-435A-435A-435A-435A-435A-435A-435A-435A-435A-435A- CONJ-EW CONJ-LW CONJ-MW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJLW CONJ-LW CONJ-MW CONJ-MW CONJ-EW CONJ-LW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-FW CONJ-LW CONJ-MW CONJ-MW CONJ-EW CONJ-LW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-SW CONJ-LW CONJ-MW CONJ-MW CONJ-EW CONJ-LW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-LW CONJ-EW CONJ-KS WTR SOUT 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5x 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5t 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.5s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.6s 3.7s 3.7s 3.7s 3.7s 3.7s 3.7s 3.7s 3.7s 3.7s 3.7s 3.7s 3.7s 3.7s 4. FOM 480A-480A-480A-480A-480A-480A-480A-480A-480A-480A-480A-480A-480A-480A-480A-480A-480A-480A-480A-480A-480A - FOM ENIEN IOB ADDRESS SWI ICU SWITCH LECOOL INCH ON INCH OFF BLACK SWITCH IF TRE SWITCH PORTION SE SWITCH STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG STG ITC+AT ORC INR ITC+AT ORC INR ITC+AT ORC INR ITC+AT ORC INR ITC+AT ORC INR ITC+AT ORC INR ITC+AT ORC INR ITC+AT ORC INR ITC+AT ORC INR ITC+AT ORC INR ITC+AT ORC INR ITC+AT ORC INR ITA + A B C D E F G H I N T I O P R S T E S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S T S< img src="boxc"sf">a">b">c">d">e">f">g">h">i">j">k">l">m">m">n">o">p">q">r">z">a">b">c">d">e">f">g">g">h">i">j">k">l">m">m">n">o">p">q">r">z">a">b">c">d">e">f">g">g">h">i">j">k">l">m">m">n">o">p">q">r">z">a">b">c">d">e">f">g">g">h">i">j">k">l">m">n">m">n">o">p">q">r">z">a">b">c">d">e">f">g">g">h">i">j">k">l">m">m">n">o">p">q">r">z">a">b">c">d">e">f">g">g">h">i">j">k">l">m">n">m">n">o">p">q">r">Z">a">b">c">d">e">f">g">g">h">i">j">k">l">m">n">m">

Fig. F — 19MV IOB4

APPENDIX A — WIRING SCHEMATICS (CONT)
CUSTOMER POWER SUPPLY 380/480V -2F-50/60M7 POWER,AND RLK DLOT-1.0 DANTOS VFD DC BUS INVERTER MOTOR,ORR RLE DLOT-1 TBT 1 2 3 4 5 MCB 1 2 3 4 5 BUS BAR TBT, AND FLT STD. Q247 MT. 5A MT. LOCK 1. STOP,1 PCR-2,21 BLD 1A 10V1,200 CL 1A 10V1,200 CL 2A 10V1,200 CL 3A 10V1,200 CL 4A 10V1,200 CL 5A 10V1,200 CL 6A 10V1,200 CL 7A 10V1,200 CL 8A 10V1,200 CL 9A 10V1,200 CL 10A 10V1,200 CL 11A 10V1,200 CL 12A 10V1,200 CL 13A 10V1,200 CL 14A 10V1,200 CL 15A 10V1,200 CL 16A 10V1,200 CL 17A 10V1,200 CL 18A 10V1,200 CL 19A 10V1,200 CL 20A 10V1,200 CL 21A 10V1,200 CL 22A 10V1,200 CL 23A 10V1,200 CL 24A 10V1,200 CL 25A 10V1,200 CL 26A 10V1,200 CL 27A 10V1,200 CL 28A 10V1,200 CL 29A 10V1,200 CL 30A 10V1,200 CL 31A 10V1,200 CL 32A 10V1,200 CL 33A 10V1,200 CL 34A 10V1,200 CL 35A 10V1,200 CL 36A 10V1,200 CL 37A 10V1,200 CL 38A 10V1,200 CL 39A 10V1,200 CL 40A 10V1,200 CL 41A INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT INT FILTER FLT

SYMBOL LEGEND
TERMINAL BLOCK
FEMALE CONNECTOR
MALE CONNECTOR
OPTIONAL WIRING
NORMALLY OPEN
NORMALLY CLOSED
CONTACT (V.O.)
CONTACT (V.C.)
THERMOSTAT
THERWISTOR
COIL
CABLE
PRESSURE SWITCH
PRESSURE TRANSDUCER
FUSE
CIRCUIT BREAKER
FLOW SWITCH
GROUND

Fig. G — 19MV Customer Power Supply and Danfoss VFD Wiring

41
CARRIER AquaEdge 23XRV - APPENDIX A — WIRING SCHEMATICS (CONT) - 3

flowchart
graph TD
    A["Motor Bearing Control Board (MBC)"] --> B["AT 21G"]
    B --> C["CONOC DEMOS"]
    C --> D["30V 24VDC SET"]
    D --> E["Switched 24VDC"]
    E --> F["75V 218.3"]
    F --> G["RESUM/REF"]
    G --> H["RESUM/REF"]
    H --> I["RESUM/REF"]
    I --> J["RESUM/REF"]
    J --> K["TX 200VA"]
    K --> L["TX 200VA"]
    L --> M["TX 200VA"]
    M --> N["TX 200VA"]
    N --> O["TX 200VA"]
    O --> P["TX 200VA"]
    P --> Q["TX 200VA"]
    Q --> R["TX 200VA"]
    R --> S["TX 200VA"]
    S --> T["TX 200VA"]
    T --> U["TX 200VA"]
    U --> V["TX 200VA"]
    V --> W["TX 200VA"]
    W --> X["TX 200VA"]
    X --> Y["TX 200VA"]
    Y --> Z["TX 200VA"]
    Z --> AA["TX 200VA"]
    AA --> AB["TX 200VA"]
    AB --> AC["TX 200VA"]
    AC --> AD["TX 200VA"]
    AD --> AE["TX 200VA"]
    AE --> AF["TX 200VA"]
    AF --> AG["TX 200VA"]
    AG --> AH["TX 200VA"]
    AH --> AI["TX 200VA"]
    AI --> AJ["TX 200VA"]
    AJ --> AK["TX 200VA"]
    AK --> AL["TX 200VA"]
    AL --> AM["TX 200VA"]
    AM --> AN["TX 200VA"]
    AN --> AO["TX 200VA"]
    AO --> AP["TX 200VA"]
    AP --> AQ["TX 200VA"]
    AQ --> AR["TX 200VA"]
    AR --> AS["TX 200VA"]
    AS --> AT["TX 200VA"]
    AT --> AU["TX 200VA"]
    AU --> AV["TX 200VA"]
    AV --> AW["TX 200VA"]
    AW --> AX["TX 200VA"]
    AX --> AY["TX 200VA"]
    AY --> AZ["TX 200VA"]
    AZ --> BA["TX 200VA"]
    BA --> BB["TX 200VA"]
    BB --> BC["TX 200VA"]
    BC --> BD["TX 200VA"]
    BD --> BE["TX 200VA"]
    BE --> BF["TX 200VA"]
    BF --> BG["TX 200VA"]
    BG --> BH["TX 200VA"]
    BH --> BI["TX 200VA"]
    BI --> BJ["TX 200VA"]
    BJ --> BK["TX 200VA"]
    BK --> BL["TX 200VA"]
    BL --> BM["TX 200VA"]
    BM --> BN["TX 200VA"]
    BN --> BO["TX 200VA"]
    BO --> BP["TX 200VA"]
    BP --> BQ["TX 200VA"]
    BQ --> BR["TX 200VA"]
    BR --> BS["TX 200VA"]
    BS --> BT["TX 200VA"]
    BT --> BU["TX 200VA"]
    BU --> BV["TX 200VA"]
    BV --> BW["TX 200VA"]
    BW --> BX["TX 200VA"]
    BX --> BY["TX 200VA"]
    BY --> BZ["TX 200VA"]

Fig. H — 19MV Motor Bearing Control Board Wiring

APPENDIX A — WIRING SCHEMATICS (CONT)
UNIT-MOUNTED VHD MODES COMM HI-THR VID RED 18 RHT RHL 18 CU 20 CONTROL PANEL OND CCN JN J14 USB JN-3-DND CU 20 HMI THERNET SWITCH FROM S105-J15 LENS/405-OUT ISEE SHRT 41 ATR WMT,AVAC+6 BLK 16 WMT,24VAC+5 RED 18 A27L,913C+970T, ETHERNET TO BASTROGHD (ICRA CA) (REF:550+017) (ISEE SHEET 41) MODEM ANTenna CELLS POWER SOURCE:PDS FROM DTR-IN FSS,IN MNT 14 FROM IFSI FSS,IL BLK 14 1TB RED 18 30B GRY 18 FROM I7P CSKI SHRT 41 A27L,913C+970T, ETHERNET TO BASTROGHD (ICRA CA) (REF:550+017) (ISEE SHEET 41) GROUND CONNECTIONS DOOR,NV OHD BUSBAR OHD,BUSBAR GRN,YEL 16 DOOR,LN DOOR,LV GRN,YEL 16 ENCL FRAME,MV ENCL FRAME,LV EXCEL Pressure SWITCH CONNECTION 4TB ST,N ZCR,42 GRY 18 RCH,AL ZCR,41 HLU 18 DTS 2014 GMT 18 2018 +/- 18 MP,SW R1 R2 EXPANSION CONTROL SYSTEM VALVE CONNECTIONS: EXCEL B: EXCEL-6 ORY 18 B: EXCEL-6 PM 18 B: EXCEL-7 RND 18 B: EXCEL-7 BLK 18 ECBY_8 GRY 18 ECBY_9 PNK 18 ECBY_1 RED 18 ECBY_2 SLK 18 ECBY_3 BLK 22 ECBY_4 BLK 22 ECBY_5 BLK 22 ECBY_6 BLK 22 ECBY_7 BLK 22 ECBY_8 GRY 18 ECBY_9 PNK 18 ECBY_1 RED 18 ECBY_2 SLK 18 ECBY_3 BLK 22 ECBY_4 BLK 22 ECBY_5 BLK 22 ECBY_6 BLK 22 ECBY_7 BLK 22 ECBY_8 BLK 22 ECBY_9 BLK 22 ECBY_10 BLK 22 ECBY_11 BLK 22 ECBY_12 BLK 22 ECBY_13 BLK 22 ECBY_14 BLK 22 ECBY_15 BLK 22 ECBY_16 BLK 22 ECBY_17 BLK 22 ECBY_18 BLK 22 ECBY_19 BLK 22 ECBY_20 BLK 22 ECBY_21 BLK 22 ECBY_22 BLK 22 ECBY_23 BLK 22 ECBY_24 BLK 22 ECBY_25 BLK 22 ECBY_26 BLK 22 ECBY_27 BLK 22 ECBY_28 BLK 22 ECBY_29 BLK 22 ECBY_30 BLK 22 ECBY_31 BLK 22 ECBY_32 BLK 22 ECBY_33 BLK 22 ECBY_34 BLK 22 ECBY_35 BLK 22 ECBY_36 BLK 22 ECBY_37 BLK 22 ECBY_38 BLK 22 ECBY_39 BLK 22 ECBY_40 BLK 22 ECBY_41 BLK 22 ECBY_42 BLK 22 ECBY_43 BLK 22 ECBY_44 BLK 22 ECBY_45 BLK 22 ECBY_46 BLK 22 ECBY_47 BLK 22 ECBY_48 BLK 22 ECBY_49 BLK 22 ECBY_50 BLK 22 ECBY_51 BLK 22 ECBY_52 BLK 22 ECBY_53 BLK 22 ECBY_54 BLK 22 ECBY_55 BLK 22 ECBY_56 BLK 22 ECBY_57 BLK 22 ECBY_58 BLK 22 ECBY_59 BLK 22 ECBY_60 BLK 22 ECBY_61 BLK 22 ECBY_62 BLK 22 ECBY_63 BLK 22 ECBY_64 BLK 22 ECBY_65 BLK 22 ECBY_66 BLK 22 ECBY_67 BLK 22 ECBY_68 BLK 22 ECBY_69 BLK 22 ECBY_70 BLK 22 ECBY_71 BLK 22 ECBY_72 BLK 22 ECBY_73 BLK 22 ECBY_74 BLK 22 ECBY_75 BLK 22 ECBY_76 BLK 22 ECBY_77 BLK 22 ECBY_78 BLK 22 ECBY_79 BLK 22 ECBY_80 BLK 22

2001503201 REV D

SYMBOL LEGEND
TERMINAL BLOCK
FEMALE CONNECTOR
MALE CONNECTOR
OPTIONAL WIRING
NORMALLY OPEN
NORMALLY CLOSED
CONTACT (N.O.)
CONTACT (N.C.)
THERMOSTAT
THERMISTOR
COIL
CABLE
PRESSURE SWITCH
PRESSURE TRANSDUCER
FUSE
CIRCUIT BREAKER
FLOW SWITCH
GROUND

Fig. I — 19MV HMI and Ethernet Switch Wiring

43
APPENDIX A — WIRING SCHEMAICS (CONT) CT1 CT2 AMETER SWITCH AMETER ANALOG AMP,POS, RLE 16 AMP,NIS, RLE 16 AMP,POS, RLE 16 AMP,POS, RLE 16 AMP,POS, RLE 16 AMP,POS, RLE 16 AMP,POS, RLE 16 AMP,POS, RLE 16 AMP,POS, RLE 16 AMP,POS, RLE 16 AMP,POS, RLE 16 AMP,POS, RLE 16 AMP,POCK, RLE 16 AMP,POCK, RLE 16 AMP,POCK, RLE 16 AMP,POCK, RLE 16 AMP,POCK, RLE 16 AMP,POCK, RLE 16 AMP,POCK, RLE 16 AMP,POCK, RLE 16 AMP,POCK, RLE 16 AMP,POCK,RLE 16 AMP,POCK,RLE 16 AMP,POCK,RLE 16 AMP,POCK,RLE 16 AMP,POCK,RLE 16 AMP,POCK,RLE 16 AMP,POCK,RLE 16 AMP,POCK,RLE 16 AMP,POCK,RLE 16 AMP,POCK,RLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,tLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,tSLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,TLE 16 AMP,POCK,TLE 16 AMP,POCK,SLE 16 AMP,POCK,tSLE 40000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000

Fig. J — 19MV Ammeter Switch and Voltmeter Switch Wiring

APPENDIX A — WIRING SCHEMATICS (CONT)

CARRIER AquaEdge 23XRV - APPENDIX A — WIRING SCHEMATICS (CONT) - 1DIGITAL INPUT4TB2J13 47 SPARE,SAFETYFS.LOCI3TB4J13 POW.FDBCUS.ALENOT USEDFC.05NOTE THE DIGITAL INPUT LOOP ISPOWERED BY INTERNAL ZAVAC POWERSUPPLY. EACH DISCRETE INPUT SMALL DETECTWHETHER AN EXTERNAL SWITCH ORCONTRACTOR IS OPEN OR CLOSE B OR OPENED.ANALOG INPUT4TB2J16 47 CHWR.T4TB2J15 47 REF.LEAK4TB2J15 47 AUTO.RES4TB5J9 47 CHWS.T4TB5J11 47 AUTO.DEW4TB5J16 47 EVAP.CAP4TB5J15 47 R,RESET4TB5J16 47 EVAP.FL4TB5J11 47 COND.FLMOTE THE ANALOG INPUTS SUPPORT SW/10R THERMISTOR, 4-20MA SENSOR AND SVDC SENSOR.
ANALOG OUTPUTNOTE EACH ANALOG OUTPUT LOOP SUPPORT 0/4-20MA OR0/7-10VDC VOLTAGE OUTPUT THE ANALOG OUTPUT LOOP ISPOWERED BY BOARD DO NOT SUPPLY EXTERNAL POWER.POWER CONNECTIONNOTE: TH-1 AND TH-2 ARE FOR EXTERNALZAVAC POWER SUPPLY CONNECTION.LIMITED TO 10VAP ZAVAC.
WATER PUMP CONTROL RELAY CONTACTCHWP11 PACDWPP11 PA

Fig. K — 19MV Field Wiring

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : CARRIER

Model : AquaEdge 23XRV

Category : Compressor