HTW AHUKZ - Air conditioner

AHUKZ - Air conditioner HTW - Free user manual and instructions

Find the device manual for free AHUKZ HTW in PDF.

📄 64 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice HTW AHUKZ - page 35
View the manual : English EN Español ES
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Variable Refrigerant Flow (VRF) AHU Control Box Kit
Model Numbers AHUKZ-00D, AHUKZ-01D, AHUKZ-02D, AHUKZ-03D
Power Supply Single-phase 220-240V, 50/60Hz
Dimensions (Approx.) 124.8 mm (H) x 93 mm (W) x 36 mm (D)
Weight Not specified in manual; typically 1-2 kg
Installation Environment Ambient temperature -25°C to +52°C; IP20 protection
Control Options Return air temperature or outlet air temperature control; factory or third-party controller
Fan Speed Control 3-speed (Low, Middle, High) or single speed via DIP switch; 0-10V analog output available
Capacity Settings Via DIP switches (ENC1 and SW4-2); range from 0.8 HP (2.2 kW) to 20 HP (56 kW) depending on model
Parallel Connection Up to 4 control boxes in parallel for larger AHU capacities (up to 225 kW total)
Refrigerant Piping Seamless phosphorus-deoxidized copper piping; sizes from Φ6.35 to Φ54.0 mm depending on capacity
Temperature Sensors 5 sensors included (T1, TA, T2, T2A, T2B) with 9m extension wires
Communication P/Q/E for ODU; C1/C2/E for master-slave; X1/X2 for wired controller; D1/D2/E for optional controller
Error Codes Comprehensive error code system (e.g., E1, E2, H6, etc.) displayed on optional wired controller or display board
Safety Features Ground leakage breaker required; all-pole disconnection switch with ≥3 mm contact separation; overheat protection
Included Accessories Installation & owner's manual, wired controller, electronic expansion valve adapter cable, temperature sensors with wires, mounting screws and clips
Warranty Not specified; contact HTW or authorized dealer

Frequently Asked Questions - AHUKZ HTW

What is the AHUKZ control box used for?
The AHUKZ is a VRF control box kit that allows integration of a third-party Air Handling Unit (AHU) with a heat pump or heat recovery outdoor unit. It controls the electronic expansion valve, fan speed, and temperature regulation.
How do I set the capacity of the AHU control box?
Set the capacity using DIP switches ENC1 and SW4-2 on the main board. Refer to Table 4-1 in the manual for HP and kW values. After setting, power off and on to apply.
Can I connect multiple AHU control boxes to one AHU?
Yes, up to four AHU control boxes can be connected in parallel to control a single large AHU. You must set master/slave via SW2-3/SW2-4 and configure the number of slaves on the master unit via SW1-3/SW1-4.
How do I choose between return air and outlet air temperature control?
Set DIP switch SW4-1 to 0 for return air temperature control (default) or to 1 for outlet air temperature control. For outlet control, both T1 and TA sensors must be connected.
What does error code E9 mean?
Error code E9 indicates a communication error with the wired controller or that no address has been set. Use the wired controller to set the address or enable auto-addressing via SW2-1.
How do I set the address for the AHU control box?
Address can be set automatically via SW2-1 (set to 0 for auto-addressing) or manually using a wired controller. Press and hold ▲ and ▼ for 8 seconds to enter address settings.
What are the power supply requirements?
The unit requires a single-phase 220-240V, 50/60Hz power supply. Use separate circuits for ODU and control box. A ground leakage breaker and all-pole disconnection switch must be installed.
Can I use a third-party thermostat?
Yes. Set SW4-3/SW4-4 to 01 for capacity output mode or 10 for set temperature mode. Connect the third-party controller's 0-10V and dry contact signals to the appropriate terminals (see Figure 4-3/4-4). The factory controller will be ignored.
What temperature sensors are included and where are they installed?
Five sensors: T1 (inlet air), TA (outlet air, optional), T2A (evaporator inlet), T2 (evaporator intermediate), T2B (evaporator outlet). Mount T2A/T2/T2B on the copper pipes using welded sleeves.
How do I clean or maintain the control box?
The control box is sealed and requires no regular cleaning. Ensure the ventilation openings are free of dust. For repairs, contact qualified personnel. Disconnect power before any maintenance.

User questions about AHUKZ HTW

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Air conditioner in PDF format for free! Find your manual AHUKZ - HTW and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. AHUKZ by HTW.

USER MANUAL AHUKZ HTW

natural_image White rectangular electronic device with three ports and two copper-colored connectors (no visible text or symbols)

VRF CONTROL BOX KIT

AHUKZ

HTW-AHUKZ01D | HTW-AHUKZ02D | HTW-AHUKZ03D

ES

Owner's and Installation Manual

Please, read carefully before using the product.

HTW

QUALITY COMFORT EVERYWHERE

Imagen 3-1

natural_image Technical line drawing of an open electrical enclosure with internal components (no text or symbols)

HTW AHUKZ - HTW - 1

natural_image Technical line drawing of an electrical enclosure with internal components and wiring (no text or symbols)

HTW AHUKZ - HTW - 2

natural_image Technical line drawing of a mechanical device with internal components and mounting base (no text or symbols)

Imagen 3-3

Imagen 3-11

Imagen 3-12

natural_image Pure electrical circuit lines without any symbols

Imagen 3-13

Specifications are subject to change without notice.
Imagen 3-14

natural_image Pure electrical circuit lines without any symbols

Imagen 3-15

Nota:

Owner's and Installation Manual

HTW-AHUKZ01D | HTW-AHUKZ02D | HTW-AHUKZ03D

CONTENTS

1 PRECAUTIONS 01

2 INTRODUCTION 02

3 INSTALLATION

• 3.1 Before Installation 04
• 3.2 Choosing an Installation Site 05
• 3.3 Installation Methods and Size 05
• 3.4 Refrigerant Piping 07
• 3.5 Temperature Sensor Installation 10
• 3.6 Electrical Connection.... 11

4 FUNCTION SETTINGS

• 4.1 Capacity Settings 18
• 4.2 Setting the Master/Slave AHU Control Box 18
• 4.3 Address Settings of AHU Control Box 18
• 4.4 Selection of Control by Return Air Temperature or by Outlet Air Temperature …… 19
• 4.5 Selection of Controllers 20

5 DIP DEFINITION 23

6 ERROR CODE AND QUERY 26

1 PRECAUTIONS

Be sure to conform to local, national, and international laws and regulations.

Read "PRECAUTIONS" carefully before installation.

The following precautions include important safety items. Observe them and remember them at all times.

Keep this manual in a handy place for future reference.

Installation must be performed by authorized personnel, in accordance with NEC and CEC requirements.

The safety precautions listed here are divided into two categories. In both cases, important safety information which should be carefully read is provided.

CAUTION

Failure to observe a caution may result in injury or damage to the equipment.

After completing the installation, make sure that the unit operates properly during start-up. Please instruct the customer on how to operate the unit and keep it properly maintained. Also, inform customers that they should store this installation manual along with the owner's manual for future reference.

WARNING

Be sure that only trained and qualified service personnel are allowed to install, repair, or service the equipment.

Improper installation, repair, and maintenance may result in electric shock, short-circuiting, leaks, fire, or other damage to the equipment.

Install strictly according to these installation instructions.

If installation is defective, it will cause water leakage, electric shocks, and fire.

When installing the unit in a small room, take measures to keep the refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage.

Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency.

Use the included accessories parts and specified parts for installation.

If not, the unit could fall, or water leakage, electrical shock, or fire could occur.

Install at a strong and firm location which is able to withstand the unit's weight.

If the installation location is not strong enough or installation is not properly completed, the set could fall and cause injury.

The appliance must be installed 2.5 m above the floor. The appliance must not be installed in a laundry room.

Before obtaining access to terminals, all supply circuits must be disconnected.

The appliance must be positioned so that the plug is accessible.

The enclosure of the appliance shall be marked with words or symbols, and indicate the direction of the fluid flow.

For electrical work, follow the local national wiring standards, regulations and these installation instructions. An independent circuit and single outlet must be used.

If electrical circuit capacity is insufficient or there is a defect in the electrical work, it will cause an electrical fire to occur.

Use the specified cable, connect it tightly, and clamp the cable so that no external force will act on the terminal.

Improper connection or fixing could lead to overheating or fire at the connection.

Wiring routing must be properly arranged so that the control board cover is properly secured.

If the control board cover is not properly secured, it could lead to overheating at the connection point of the terminal, fire, or electrical shock.

If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard.

An all-pole disconnection switch with a contact separation of at least 3 mm should be connected in fixed wiring.

When carrying out piping connection, be careful to avoid air from entering the refrigeration cycle.

Otherwise, lower capacity, over-high pressure in the refrigeration cycle, explosion and injury could occur.

Do not modify the length of the power supply cord or use an extension cord, and do not share the single outlet with other electrical appliances.

Otherwise, fire or electrical shock may occur.

Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.

Improper installation may cause the equipment to fall and cause accidents.

If the refrigerant leaks during installation, ventilate the area immediately.

Toxic gas may be produced if the refrigerant comes into contact with fire.

After completing the installation, check that the refrigerant does not leak.

Toxic gas may be produced if the refrigerant leaks into the room and comes into contact with a source of flame, such as a fan heater, stove, or cooker.

HTW AHUKZ - WARNING - 1

CAUTION

Ground the air conditioner.

Do not connect the ground wire to gas or water pipes, lightning rods or a telephone ground wire. Incomplete grounding may result in electrical shock.

Be sure to install a ground leakage breaker.

Failure to install a ground leakage breaker may result in electrical shock.

Connect the ODU wires first, and then connect the AHU control box wires.

You are not allowed to connect the air conditioner to a power source (including wiring and piping) until the air conditioner installation is completed.

While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate the piping in order to prevent condensation from occurring.

Improper drain piping may result in water leakage and property damage.

Install the AHU control box and ODUs, power supply wiring, and connecting wires at least 1 m away from televisions or radios in order to prevent image interference or noise.

Depending on the radio waves, a distance of 1 m may not be sufficient enough to eliminate the noise.

The appliance is not intended for use by young children or infirm persons without supervision.

Young children should be supervised to ensure that they do not play with the appliance.

2 INTRODUCTION

The AHU control box can be connected to the heat pump/heat recovery ODU and the third party AHU. Every third party AHU can be connected to one AHU control box or to several AHU control boxes in a parallel connection (up to four). This manual describes how to install and operate an AHU control box.

Using an AHU control box, a unit can be controlled by either return air temperature or by outlet air temperature.

  • When return air temperature control is selected, the connected AHU can be considered to be a standard IDU.
  • Users can opt to use the factory controller or a third party controller
  • The AHU control box has an input port of 0-10V. A third party controller is required to provide 0-10V of input. The system capacity requirement or temperature can be set based on 0-10V input. For details, refer to Section 5.2.2 Setting Capacity Output Mode via a Third Party Controller (Type 1) and Section 5.2.3 Setting Temperature Mode via a Third Party Controller (Type 2)

Exploded view diagram of an electronic device with numbered parts for identification

NO.Part and components
1Electric control box cover assembly
2E-part box assembly
3Electronic expansion valve assembly
4Electric control box welding assembly
5Clip
6Cable gland
7Rubber ring
8Fixing board,popes

3 INSTALLATION

Accessories

SHAPE USENAMEQUANTITY
Installation & owner's manualHTW AHUKZ - INSTALLATION - 11——
Wired controllerHTW AHUKZ - INSTALLATION - 21Wired controller
Electronic expansion valve adapter cable groupHTW AHUKZ - INSTALLATION - 31——
Fixed clamp of temperature sensorHTW AHUKZ - INSTALLATION - 43——
SleeveHTW AHUKZ - INSTALLATION - 53——
Screw ST3.9x25HTW AHUKZ - INSTALLATION - 64Secure the installation board
Plastic expanded tubeHTW AHUKZ - INSTALLATION - 74——
Temp.sensorHTW AHUKZ - INSTALLATION - 85——
Temp.sensor connecting wire groupHTW AHUKZ - INSTALLATION - 95——
Tie wrapHTW AHUKZ - INSTALLATION - 105——

Installation layout

Diagram of a server rack connected to an electronic device via cable, showing labeled components and connections.

Figure 3-1

Table 3-2 Names and functions

No.NameDescription
1ODUOutdoor units
2AHU control box-
3Air handling unit (AHU)Field supply
4Liquid pipeField supply
5Gas pipeField supply
6Wired controllerFactory controller
7Third party controllerField supply
8Temperature sensor wiring-

3.1 Before Installation

  • An AHU control box can be connected to a heat pump ODU or a heat recovery ODU.
  • When an AHU control box is connected to a heat recovery ODU, the system is not allowed to connect to AHU only. The IDU/ODU capacity ratio of common IDUs should be 50%-100%, that of the AHU control box should be 0%-50%, and that of the entire system should be 50%-100%.
  • When a heat pump ODU is employed and the AHU control box is connected to AHU indoors: If no common IDUs are also connected, the IDU/ODU capacity ratio should be 50%-100%; if common IDUs are also connected, the IDU/ODU capacity ratio should be 50%-100%, that of the AHU control box should be 0%-50%, and that of the entire system should be 50%-100%.
  • When a heat recovery ODU is employed and the AHU control box is connected to a FAPU, the unit can only be controlled by the outlet air temperature. The FAPU capacity of the entire system should not exceed 30% of the ODU capacity.
  • When a heat pump ODU is employed and the AHU control box is connected to a FAPU, the unit can only be controlled by the outlet air temperature. If no common IDUs are connected, the IDU/ODU capacity ratio should be 50%-100%; if common IDUs are also connected, the FAPU capacity of the entire system should not exceed 30% of the ODU capacity.

When an AHU control box is connected to a mini VRF ODU, only return air temperature control can be selected (outlet air temperature control cannot be selected)

Selecting an AHU control box that matches AHU:

The following parameters and restrictions stipulated in Table 3-3 and Table 3-4 must be considered when selecting the AHU control box. Otherwise, it may adversely affect the ODU's service life, operating range, and reliability.

NOTE

If the total capacity of IDUs exceeds the rated capacity of the ODU, the cooling and heating performance may be reduced when IDUs are in operation.

Table 3-3

ModelSetting Cooling Capacity (HP)AHU Capacity (kW)Internal volume of heat exchanger (dm3)Reference Air Volume (m3/h)Max. air Volume (m3/h)
AHUKZ -00D0.82.2-2.80.35~0.4500600
12.8~3.60.4~0.45550650
1.23.6~4.50.45~0.55600750
1.74.5~5.60.55~0.65750900
25.6~7.10.65~0.758501000
2.57.1~80.75~1.210001300
38~91.2~1.6613001800
AHUKZ -01D3.29~11.21.66-2.0614002400
411.2~142.06~2.5817003000
514~162.58~3.3221003800
616~203.32~3.6927004300
AHUKZ -02D820~253.69~4.6130005400
1025~304.61~5.5337006400
1230~365.53~6.6445007700
AHUKZ -03D1436~406.64~7.3754008600
1640~457.37~8.2960009700
2045~568.29~9.21750012000

Note: The evaporation temperature (cooling) is 6°C, the ambient temperature is 27°C DB/19°C WB, and the superheat degree is 5°C.

When the capacity of AHU exceeds 56 kW, up to four AHU control boxes can be connected in parallel to one AHU. See Table 3-4 for recommended parallel connection methods.

Table 3-4

Recommended Parallel CombinationsAHU Capacity (kW)Internal volume of heat exchanger (dm3)Reference Air Volume (m3/h)Max. air Volume (m3/h)
AHUKZ-02D+AHUKZ-02D56~659.63~11.56820014000
AHUKZ-02D+AHUKZ-03D65~7011.03~12.54940015100
AHUKZ-02D+AHUKZ-03D70~7611.90~13.301020016400
AHUKZ-02D+AHUKZ-03D76~8012.62~14.011080017200
AHUKZ-02D+AHUKZ-03D80~9013.40~15.261180019400
AHUKZ-03D+AHUKZ-03D90~10015.26~17.801340021600
AHUKZ-03D+AHUKZ-03D100~11217.51~19.611500024100
AHUKZ-02D+AHUKZ-02D+AHUKZ-03D112~12518.85~21.361670027000
AHUKZ-02D+AHUKZ-03D+AHUKZ-03D125~14021.19~24.071870030200
AHUKZ-03D+AHUKZ-03D+AHUKZ-03D140~15523.74~26.622100033400
AHUKZ-02D+AHUKZ-02D+AHUKZ-03D+AHUKZ-03D155~17526.20~29.362370037800
AHUKZ-02D+AHUKZ-03D+AHUKZ-03D+AHUKZ-03D175~19829.02~32.842620042700
AHUKZ-03D+AHUKZ-03D+AHUKZ-03D+AHUKZ-03D198~22533.17~37.153000048600

Perform checks upon completion of installation, and pay extra attention to the following items:

• Whether the temperature sensor is properly installed.
• Whether AHU control boxes are properly secured.
• Whether electrical connections meet specifications.
• Whether wires and pipes are correctly connected.
• Whether AHU control boxes are properly grounded.
• Whether capacity DIP switches are properly set.

3.2 Choosing an Installation Site

The following conditions must be met:

If the AHU control box is installed outdoors, take waterproofing measures to protect it from rainwater.

Avoid direct sunlight, as it will heat the AHU control box and shorten its service life, hence affecting operation.

Select a level, solid-mounting surface.

Do not install the AHU control box on or above the surface of the ODU.

Reserve some space in front of the AHU control box for future maintenance.

Ambient temperature: -25^ to +52^

Inlet air temperature range on AHU coil (T1):

Cooling: 17^ C - 43^ C

Heating: 5^ - 30^

IP Protection Degree: IP20 (after proper installation)

HTW AHUKZ - Choosing an Installation Site - 1

CAUTION

Do not install or operate AHU control boxes in the following indoor environments:

  • Places with fossil fuels (such as kitchens containing oil or natural gas)
  • Places containing sulphuric gas, such as a hot spring
  • Places exposed to strong electromagnetic fields
  • Places with large voltage fluctuations
  • Places where acidic or alkaline steam is present
  • Places with high concentrations of vapour or spray

3.3 Installation Methods and Size

For installation of the field supply AHU, refer to the AHU installation manual.

The AHU control box can be installed in two ways:

  1. When the AHU control box's EEV remains with the AHU control box, the AHU control box must be installed vertically, as shown in Figure 3-2.
  2. When the AHU control box's EEV is split from the AHU control box, the AHU control box can be installed vertically or horizontally, but the split EEV must be vertical, as shown in Figure 3-2.

Units: mm

Wire passing-hole 65 65 65 124.8 93 36 Φ24 Φ39 95 135 Connect to outdoor unit Connect to DX AHU

HTW AHUKZ - Installation Methods and Size - 2
Figure 3-2

How to remove EEV from the AHU control box. The EEV may be removed from the AHU control box and positioned in an external location. Follow these steps to remove the EEV from the box.

HTW AHUKZ - Installation Methods and Size - 3

natural_image Technical line drawing of an open electrical enclosure with internal components (no text or symbols)

HTW AHUKZ - Installation Methods and Size - 4

natural_image Technical line drawing of an electrical enclosure with internal components and mounting brackets (no text or symbols)

HTW AHUKZ - Installation Methods and Size - 5

natural_image Technical line drawing of a mechanical device with internal components and mounting holes (no text or symbols)

Figure 3-3

3.4 Refrigerant Piping

3.4.1 Material and Size of the Piping

Only seamless phosphorus-deoxidized copper piping that complies with all applicable laws should be used. Temper grades and minimum thicknesses for different diameters of piping are specified in Table 3-5.

Table 3-5

Piping Outer Diameter (mm)TemperMin. Thickness (mm)
Φ6.35O (annealed)0.8
Φ9.530.8
Φ12.70.8
Φ15.91.0
Φ19.11.0
Φ22.21/2H (half hard)1.2
Φ25.41.2
Φ28.61.3
Φ31.81.5
Φ38.11.5
Φ41.31.5
Φ44.51.5
Φ54.01.8

Note: O: coiled piping; 1/2H: straight piping.

When the required pipe sizes (in inch) are not available, other diameters (in mm) may also be used, provided that the following is taken into account:

  • Select the pipe size nearest to the required size.
  • Use suitable adapters for the change-over from inch to mm pipes (field supply).

3.4.2 Pipe Limits

AHUKZ Liquid pipe AHU

Figure 3-4

  1. The connecting distance of each control box and AHU should not be more than 8 m. If the AHU control box and EEV are to be installed apart, the distance between them must be within 5 m.
  2. The maximum allowed piping length between the ODU and the AHU control box depends on the ODU model.

3.4.3 Welding Precautions

  1. Nitrogen must be applied before welding.

Failure to apply nitrogen in advance may result in a large amount of oxide residue on the interior surface of the copper tube, which will affect the normal operation of the valve body and compressor, and may damage the compressor in serious cases.

  1. When performing welding, use the pressure relief damper to keep the nitrogen pressure in the pipe at the range of 0.02-0.03 Mpa (as if the air is blowing gently on the skin).

1 2 3 4 5 6 6

Figure 3-5

1Refrigerant piping
2Part to be brazed
3Nitrogen connection
4Hand-operated valve
5Pressure relief damper
6Nitrogen

3.4.4 AHU Control Box Installation

  1. Drill four holes where you want to install the box, with the positions of the holes shown below. Secure the AHU control box using screws.

Liquid tube refrigerant inlet Liquid tube refrigerant outlet

Figure 3-6

  1. Remove seals from the inlet and outlet.
  2. Weld pipes on site

HTW AHUKZ - AHU Control Box Installation - 2

flowchart
graph LR
    A["Outdoor Unit"] -->|L3| B["Liquid pipe"]
    B -->|a1| C["A"]
    C -->|L1| D["B"]
    D -->|b1| E["C1"]
    E --> F["Gas pipe"]
    F --> G["N2"]
    G --> H["b2"]
    H --> I["B"]
    I --> J["L2"]
    J --> K["A"]
    K --> L["L4"]
    L --> M["Liquid pipe"]
    N["DX AHU"] --> O["PH19.1."]
    P["AHUKZ-03D(56kW)"] --> Q["N0"]
    R["AHUKZ-02D(28W)"] --> S["N1"]
    T["AHUKZ-01D(14kW)"] --> U["N2"]
    V["φ19.1."] --> W["PH19.1."]

HTW AHUKZ - AHU Control Box Installation - 3

NOTE

When welding pipes at the AHU control box, the valve body and filter should be cooled with a wet cloth to prevent damage to the EEV due to excessively high temperatures.

  1. After the pipes are installed, insulate the pipes.
  2. Pipe diameter requirements for the AHU control box are as follows:

Table 3-6

Control BoxAHUKZ-00DAHUKZ-00DAHUKZ-01DAHUKZ-02DAHUKZ-03D
Capacity A(×100W)A<5656≤A≤9090200360200360360≤560
Liquid Side (mm)Φ6.35Φ9.53Φ9.53Φ12.7Φ15.9

For installation of other piping and branch pipes, refer to the ODU installation manual.

3.4.5 Pipe classification

Table 3-7

Pipe nameCode(refer to Figure 3-7)
AHU Control box main pipeL1, L2,L3, L4
AHU Control box aux. pipea1,a2,b1,b2,c1,c2
AHU Control box branch joint assemblyA, B

Note:

The connecting distance of each control box and DX

AHU should not more than 8 m

a2+L4≤8m b2+L2+L4≤8m c2+L2+L4≤8m

3.4.6 Size of joint pipe for R410A DX AHU

Table 3-8

Capacity of AHU control box A(×100W)Size of main pipe(mm)
Liquid side(mm)Available branch joint
200< A≤450Φ12.7FQZHD-01
450< A<660Φ15.9FQZHD-02
660≤A<1350Φ19.1FQZHD-03
1350≤A<1800Φ22.2FQZHD-04
1800≤AΦ25.4FQZHD-04

e.x.1: Refer to Figure 3-7, the capacity of downstream controller box to L4 is 560+280+140=980, the pipe is Φ19.1.

Figure 3-7

3.4.7 Example

Take (56+28+14)kW that composed by three control boxes as an example to clarify the pipe selection.

Table 3-9

Controller box capacity A (×100W)AHUKZ-01D 90≤A≤200AHUKZ-02D 200AHUKZ-03D 360AHUKZ-03D 360
Liquid side(mm)Φ9.53Φ12.7Φ15.9

A. The branch pipe at the controll box.

There are a\~c branch pipe at the control box, the branch pipe diameter should be select as Table. 3-6. The pipe a1/a2 diameter is 15.9 , the pipe b1/b2 diameter is 12.7 , the pipe c1/c2 diameter is 9.53 .

B. Main pipe at the control box (Refer to Table. 3-8)

1) The main pipe L1/L2 with N1, N2 downstream control box that total capacity is 280+140=420 , the pipe L1 diameter is 12.7 , thus select FQZHD-01 for the branch joint B.
2) The main pipe L3/L4 with N0 N1 N2 downstream control box that total capacity is 560+280+140=980, the pipe L3/L4 diameter is Φ19.1, that select FQZHD-03 for the branch joint A.
3) The branch joint A with N_0 N_2 downstream control box that total capacity is 560 + 280 + 140 = 980 thus select FQZHD-03 for the branch joint A.

Note:

1) The pipe L3 diameter is still related to outdoor unit, take the large one for your selection.
2) The gas pipe should be confirmed according to the outdoor unit installation manul.

3.4.8 Other piping methods for example.

Single VRF DX AHU Control Box connect to one AHU

HTW AHUKZ - Single VRF DX AHU Control Box connect to one AHU - 1

flowchart
graph LR
    A["Outdoor Unit"] -->|Liquid/Gas pipe| B["Hybrid"]
    B --> C["Hybrid"]
    C --> D["HXU"]
    C --> E["HXU"]
    style A fill:#f9f,stroke:#333
    style B fill:#ccf,stroke:#333
    style C fill:#cfc,stroke:#333
    style D fill:#fcc,stroke:#333
    style E fill:#cff,stroke:#333

Piping to heat recovery outdoor unit.

HTW AHUKZ - Single VRF DX AHU Control Box connect to one AHU - 2

flowchart
graph TD
    A["outdoor unit"] --> B["MS"]
    B --> C["Liquid/Gas pipe"]
    B --> D["AHUKZ"]
    D --> E["Liquid pipe"]
    D --> F["Gas pipe"]
    B --> G["AHUKZ"]
    G --> H["Liquid pipe"]
    G --> I["Gas pipe"]
    B --> J["AHUKZ"]
    J --> K["Liquid pipe"]
    J --> L["Gas pipe"]
    B --> M["Liquid pipe"]
    M --> N["Gas pipe"]
    B --> O["DX AHU"]

Note: The maximum capacity of every AHU connected to MS box should not be exceed 28Kw.

3.5 Temperature Sensor Installation

There are five temperature sensors (T1, TA, T2A, T2, and T2B) and five extension wires in the accessories, as shown in Figure 3-8.

Temperature sensor Extension wire
T1 WhiteWhiteWhite TA White BlackBlack T2 Black BlackBlack T2A Blue BlueBlue T2B Red Red Red

HTW AHUKZ - Temperature Sensor Installation - 2

natural_image Two black cable connectors with white connectors and copper wires attached, placed on a green surface (no text or symbols visible)

Figure 3-8

Mounting location for temperature sensors:

T1 is an AHU inlet air temperature sensor; it should be installed at the air inlet of the AHU.

T2A is an AHU evaporator inlet temperature sensor; it should be installed at the inlet pipe of the evaporator.

T2 is an AHU evaporator intermediate temperature sensor; it should be installed at the intermediate pipe of the evaporator.

T2B is an AHU evaporator outlet sensor; it should be installed at the outlet pipe of the evaporator.

TA is an outlet air temperature sensor and therefore does not need to be installed if outlet air temperature control is not selected.

Mounting location of T2A, T2, and T2B tube temperature sensors

T2 T2B T2A Gas pipe Liquid pipe

Figure 3-9

Installation of tube temperature sensors T2A, T2 and T2B

  1. Weld the sleeves of the temperature sensors at the designated mounting location.

1 2 Welding 1 2 45

Figure 3-10

  1. Insert the temperature sensor into the sleeve after inserting the buckle.

Technical diagram showing two mechanical assembly steps with labeled components and a magnified detail view

Figure 3-11

  1. Apply insulation materials and secure with cable ties.

Technical diagram showing labeled components of a pipe or cable assembly with numbered parts 1 to 6.

Figure 3-12

Mounting location of indoor temperature sensors T1 and TA

Return Air Exhaust Air Outdoor Air Supply Air A : Inlet air temperature T1 B : Outlet air temperature TA (optional)

HTW AHUKZ - Temperature Sensor Installation - 8

natural_image Pure technical line drawings of U-shaped pipe fittings without any text, numbers, or symbols

Figure 3-13

Using an extension cord with the temperature sensor to allow long distance connection

The attached extension cord of the temperature sensor is 9 m long. If an extension cord is required, connect one end of the cord to the AHU control box and the other end to temperature sensor mounted on the AHU.

3.6 Electrical Connection

CAUTION

  1. The ODU and AHU control box should use separate power supplies with rated voltage. However, the AHU control box and other AHUs in the same system should use the same power.
  2. The external power supply to the air conditioner should have ground wiring, which is linked to the ground wiring of the AHU control box and ODU.
  3. The wiring work should be completed by qualified persons according to circuit drawing.
  4. The fixed connecting lines must be equipped with at least 3 mm of electric shock spacing.
  5. A leakage protector should be installed in accordance with the local electrical standard.
  6. Be sure to properly locate the power wiring and the signal wirings to avoid causing cross-disturbance and their contact with the connecting pipe or stop value body. Generally, do not twist two wirings together unless the joint is well-soldered and covered with insulator tape.
  7. Do not turn on the power until the electrical wiring have been correctly completed.

3.6.1 Circuit Diagram

Please refer to the circuit diagram for wiring.

Circuit diagram

HTW AHUKZ - Circuit Diagram - 1

flowchart
graph TD
    subgraph Main Board
        CN31["CN31"] -->|ENC1 ENC2 ENC3 ENC4| SW1["SW1"]
        CN33["CN33"] -->|POWER LOW MIDDLE HIGH| SW2["SW2"]
        CN30["CN30"] -->|M-smart| CN25["CN25"]
        CN2["CN2"] --> L["L"]
        CN2 --> N["N"]
        CN2 --> NHIGH["HIGH"]
        CN2 --> LOW["MIDDLE[LOW"]]
        CN2 --> L'N' [L']
        CN2 --> AUX["AUX"]
        CN2 --> COM["COM"]
        CN2 --> Alarm["Alarm Defrost"]
        CN2 --> Run["Run"]
        CN2 --> DisplayBoard["Display board"]
        CN2 --> XP12["XP12"]
        CN2 --> XP11["XP11"]
        CN2 --> EEV["EEV"]
        CN2 --> Switch["CN31-ON/CN35 ON/OFF/COOL/HEAT/FAN COM 0-10V output 0-10V input"]
        CN2 --> Switch --> Water["ON/OFF switch"]
        CN2 --> Switch --> Third-party["Third party controller"]
        CN2 --> Switch --> MagnetRing["Magnet ring"]
        CN2 --> Switch --> Factory["To wired controller (factory)"]
        CN2 --> Switch --> AHUControlBox["To master/slave AHU control box comm.bus"]
        CN2 --> Switch --> WaterLevelSwitch["Water level switch if the drain-age pump is available"]
    end

    subgraph Single-phase AC motor
        CN31 -->|P Q E| ToOutdoorMSUnit["To Outdoor/MS units comm.bus"]
        CN33 -->|D1 D2 E| ToWiredController["To wired controller (optional)"]
        CN30 -->|X1 X2| ToMasterSlaveAHU
        CN26 -->|ON/OFF switch| Water
        CN25 -->|ON/OFF switch| Water
        CN24 -->|ON/OFF switch| Water
        CN23 -->|ON/OFF switch| Water
        CN22 -->|ON/OFF switch| Water
        CN21 -->|ON/OFF switch| Water
        CN15 -->|T2B T1 T2A TA| RedRed["RED XS1 XP1 XS2 XP2 WHITE XS3 XP3 XS4 XP4 BLACK XS5 XP5 XS6 XP6 BLUE XS7 XP7 XS8 XP8 YELLOW XS9 XP9 XS10 XP10 TA"]
    end

    style Main Board fill:#f9f,stroke:#333
    style Single-phase AC motor fill:#ccf,stroke:#333
    style Main Board fill:#cfc,stroke:#333
    style Single-phase AC motor fill:#fcc,stroke:#333
    style Main Board fill:#ffc,stroke:#333
    style Single-phase AC motor fill:#cff,stroke:#333

Figure 3-14Specifications are subject to chang

3.6.2 Wiring Inside the Electric Control Box

For connections to the AHU control box : Pull the wires inside through the screw nut and fasten the nut firmly to ensure a good pull relief and water protection.

The cables require an additional pull relief. Strap the cable with the installed tie wrap.

HTW AHUKZ - Wiring Inside the Electric Control Box - 1

natural_image Technical diagram of a mechanical assembly with no visible text or symbols

Figure 3-15

Note:

The connection with the terminal block must be secure. Failure to do so may result in heating due to poor contact, and even fire in serious cases.

The power cable and the communication cable should be separated by at least 50 mm to prevent electromagnetic interference.

Connect the cables to the main board in accordance with the circuit diagram shown in Figure 3-14.

Connect cables in accordance with the following table.

Table 3-10

Description Connected ToCross Section (mm2)Max. Length (m)Specification
L, NPower supplyPower supply*-220-240V 1Ph50/60hz
LOW/MIDDLE/HIGH, NFan speed signalAHU fan#-220-240V 1Ph50/60hz
EEVElectronic expansion valveElectronic expansion valve-50-12VDC
T1Inlet air temperatureAHU100-5VDC
TAOutlet air temperatureAHU heat exchanger100-5VDC
T2AHeat exchanger inlet temperatureAHU heat exchanger100-5VDC
T2Heat exchanger intermediate temperatureAHU heat exchanger100-5VDC
T2BHeat exchanger outlet temperatureAHU100-5VDC
P, Q, ECommunication cable connected to ODU/MSODU / MS0.7512000-5VDC
X1, X2Wired controllerFactory controller20018VDC
D1, D2, EWired controller (optional)Factory controller12000-5VDC
C1, C2, EComunicate with AHU control boxMaster/slave AHU control box12000-5VDC
ON/OFFRemote on/offThird party controller0-12VDC
coolCooling signalThird party controller0-12VDC
heatHeating signalThird party controller**0-12VDC
fanFan statusThird party controller0-12VDC
alarmAlarm signalThird party controller0-24VDC/AC
defrostDefrosting/anti-cold wind signalThird party controller0-24VDC/AC
runOperating StatusThird party controller0-24VDC/AC
AUXElectric auxiliary heater signalElectric auxiliary heater0-12VDC

*Refer to Cross section of main power cable

Refer to Fan wiring

**The maximum length depends on the external device that is connected (controller, relay ...).

3.6.3 Temperature Sensor Wiring 3.6.4 Cross section of main power cable

The temperature sensors come with two wiring methods, by dialling DIP switch SW9-2.

TypeSW9
1HTW AHUKZ - Temperature Sensor Wiring 3.6.4 Cross section of main power cable - 1SW9-2 is 0: One or more AHU control boxes are connected in parallel to one AHU; one coil is connected to multiple control boxes; (shielding faults from slave unit's temperature sensors T1, T2, T2A, TA and T2B) (factory default)
HTW AHUKZ - Temperature Sensor Wiring 3.6.4 Cross section of main power cable - 2
2HTW AHUKZ - Temperature Sensor Wiring 3.6.4 Cross section of main power cable - 3SW9-2 is 1: Multiple AHU control boxes are connected in parallel. In the event of multiple coils, one coil is connected to one control box; (shielding faults from slave unit's temperature sensor T1, TA)
1 2 3 SW9

Type 1: One or more AHU control boxes are connected in parallel to one AHU, and the T2A, T2 and T2B sensors of any coil of AHU are connected to the master AHU control box. The T1 and TA sensor is connected to the main board of the master AHU control box.

Schematic diagram:

HTW AHUKZ - Temperature Sensor Wiring 3.6.4 Cross section of main power cable - 4

flowchart
graph TD
    A["Master AHU"] --> B["Signal wire (C1/C2/E)"]
    A --> C["Signal wire (C1/C2/E)"]
    A --> D["Signal wire (C1/C2/E)"]
    B --> E["L1"]
    C --> F["L2"]
    D --> G["N# slave AHU(Ns3)"]

Figure 3-16

Type 2: Multiple AHU control boxes are connected in parallel. Each coil is connected to an AHU control box. The T2A, T2 and T2B sensors of each coil are connected to the main board of the corresponding AHU control box. The T1 and TA sensor only needs to be connected to the master AHU control box.

Schematic diagram:

HTW AHUKZ - Temperature Sensor Wiring 3.6.4 Cross section of main power cable - 5

flowchart
graph TD
    A["Factory controller"] --> B["Master AHU"]
    B --> C["Signal wire (C1/C2/E)"]
    B --> D["N# slave AHU(N≤3)"]
    E["2# AHU"] --> F["T1,T2,T2A,T2B,TA"]
    E --> G["T2,T2A,T2B"]
    style A fill:#f9f,stroke:#333
    style E fill:#ccf,stroke:#333

Figure 3-17

Please select the main power cable. Refer to Table 3-11 and Table 3-12.

Table 3-11

AHUKZ-00D~01DModel
PowerPhaseSingle-phase
Voltage and Frequency220-240V - 50/60Hz
AHU Control Box Power Wire (mm ^2 )2.0 (<50 m)

Table 3-12

AHUKZ-02D~03DModel
PowerPhaseSingle-phase
Voltage and Frequency220-240V - 50/60Hz
AHU Control Box Power Wire (mm2)4.0 (<50 m)

CAUTION

  1. Specific wiring requirements must adhere to local wiring regulations.
  2. Use only copper wires.
  3. Be sure to use specified wires for connections and ensure that no external force is imparted to terminal connections. If connections are not firmly secured, overheating or fires may result.
  4. The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter. Make sure the power-supply voltage does not drop by more than 10%.
  5. Power must be unified supply to all AHU control boxes in the same system.
  6. A breaker for current leakage must be attached to the power supply. If no ground leakage breaker is installed, it may cause electrical shock.
  7. Never connect the main power source to a terminal block of the communication line. If connected, electrical parts will burn out.

3.6.5 Fan Wiring

Fan signal:

The AHU control box has two output modes to control fan speed: an analog signal output LOW/MIDDLE/HIGH and an output of 0-10V, respectively. The output mode is selected based on the actual on-site needs of the AHU.

Table 3-13

Fan SignalLOW/ MIDDLE/HIGH0-10V output
LowLOW#
MiddleMIDDLE#
HighHIGH#

: Refer to 0-10V output control

0-10V Output control

The DIP switch numbers of ENC2, ENC3 and ENC4 correspond to different voltage outputs. Depending on the DIP switch numbers of SW1-2, there are two control modes available, which are gear 1 and gear 3 fan speeds, respectively.

  1. SW1-2 dialled to "OFF" (factory default)

ENC2, ENC3 and ENC4 are respectively defined as low, middle and high voltage output signals. By default, ENC2 is set to 2V, ENC3 is set to 7V, and ENC4 is set to A (A is 10V). See the table below for their corresponding relations:

Table 3-14
0-10V output Voltage

HTW AHUKZ - 0-10V Output control - 1 (2V Factory Default)HTW AHUKZ - 0-10V Output control - 2 (7V Factory Default)HTW AHUKZ - 0-10V Output control - 3 (10V Factory Default)
Fan output voltage of Low speed Fanoutput voltage of Middle speed Fan output voltage of High speed
Dial code 0123456789ABCDEF
Voltage(V)1123456789101010101010

Note: ENC2<ENC3<ENC4. If not satisfied, fault H9 is reported.

2. SW1-2 dialled to "ON"

This indicates that the fan has only one fan speed. In this case, ENC2 indicates the fan speed while ENC3 indicates a 0-10V output voltage for the corresponding gear. ENC4 is not defined.

Table 3-15

ENC2 DIPFan SpeedLOW/MIDDLE/HIGH0-10V output
0Low onlyLOW outputENC3 voltage
1Middle onlyMIDDLE outputENC3 voltage
2 (by default)High onlyHIGH outputENC3 voltage
3-FHigh onlyHIGH outputENC3 voltage

Corresponding voltage for the ENC3 DIP switch:

Table 3-16

Dial code 0123456789ABCDEF
Voltage(V)1123456789101010101010

Wiring between the terminal block and fan

The sum current of the drainage pump and fan motor should not be greater than 3.5A in models AHUKZ-00D and AHUKZ-01D. The sum current of the drainage pump and fan motor should not be greater than 15A in models AHUKZ-02D and AHUKZ-03D.

The unit should be equipped with molded case circuit breaker, refer to Table 3-17.

The AHU control box has a control port for single-phase AC motor; refer to Figure 3-18 and Figure 3-19. It has three different speeds (high, medium, and low), the output voltage will also be the same as the input power of the box. Figure 3-18 and Figure 3-19 show the wiring diagram. Figure 3-18 is the recommended wiring in these two ways. In Figure 3-18, the AHU control box is not directly connected to the fan motor. Always use it as a motor driving the relay contacts. Otherwise, the product could be damaged or a fire could occur.

CN2 CN3 CN4 L N HIGH MIDDLE LOW mixed case circuit breaker single-phase power fan motor single-phase AC motor Figure 3-18 single-phase power

CN2 CN3 CN4 L N N HIGH MIDDLE LOW molded case circuit breaker single-phase power fan motor single-phase AC motor Figure 3-

If wiring as shown in Figure 3-19, the maximum current of the fan motor must not exceed the value shown in Table 3-17. Table 3-17

ModelMax. Current of AC Motor and Drainage pumpMolded case circuit breaker
AHUKZ-00D~01D3.5A6A
AHUKZ-02D~03D15A20A

If the fan motor is a 3-Phase AC motor, SW1-2 must be set to "ON", and the ENC2 must be dialled to "2". The fan terminal block only supports high-speed output. When wiring the motor, refer to Figure 3-20.

SW1, ENC2
ONHTW AHUKZ - Wiring between the terminal block and fan - 3HTW AHUKZ - Wiring between the terminal block and fan - 4Only high-speed is available

Note:

  1. The rated current of the contactor must be greater than the current of the motor.
  2. The control power of the contactor must be the same as the input power of the AHU control box.
  3. SW1-2 must be set to "ON".
  4. ENC2 must be dialled to "2".
  5. The product do not include the breaker and contactor.

CN2 CN3 CN4 L N HIGH molded case circuit breaker single-phase power External 3-Phase power Contactor control A1 A2 Contactor fan motor 3-phase AC motor

Figure 3-20

3.6 Signal Cable Connection

The following figure displays the signal cable connection diagram:

HTW AHUKZ - Signal Cable Connection - 1

flowchart
graph TD
    CN10["CN10"] -->|P Q E| CN19["CN19"]
    CN19 -->|D1 D2 E| CN5["CN5"]
    CN5 -->|C1 C2 E| CN23["CN23"]
    CN23 -->|X1 X2| CN8["WATER"]
    CN8 -->|Magnet ring| CN10
    CN10 -->|P Q E| ToOutdoor["To Outdoor/MS units comm.bus"]
    CN19 -->|D1 D2 E| ToWired["To Wired Controller (optional)"]
    CN5 -->|C1 C2 E| ToMaster["AHU control box comm.bus"]
    CN23 -->|X1 X2| ToWired
    CN8 -->|Water level switch| WaterLevelSwitch["Water level switch to the water level switch if the drainage pump is available"]

Figure 3-21

Note:

The connecting terminals of the water level switch are connected by default. When connecting the AHU with the drainage pump, remove the connecting wire and connect to the water level switch.

X1 and X2 are ports for connecting to a standard wired controller, while D1,D2 and E are ports for connecting to the optional wired controller. For specific models, consult the manufacturer's technical support personnel or a local dealer.

When a third party controller is used, communication between the AHU control box and third party controller is achieved via dry contacts. See the signal cable connection diagram below:

HTW AHUKZ - Note: - 1

flowchart
graph TD
    A["CN17"] --> B["Alarm"]
    A --> C["Defrost"]
    A --> D["Run status"]
    E["CN18"] --> F["0-10V signal"]
    G["CN62"] --> H["Fan status"]
    G --> I["Heat mode"]
    G --> J["Cool mode"]
    K["CN9CN32CN61"] --> L["On/off"]
    style A fill:#f9f,stroke:#333
    style E fill:#f9f,stroke:#333
    style K fill:#f9f,stroke:#333
    style B fill:#ccf,stroke:#333
    style F fill:#ccf,stroke:#333
    style H fill:#ccf,stroke:#333
    style I fill:#ccf,stroke:#333
    style J fill:#ccf,stroke:#333

Figure 3-22

Example of signal wiring(Heat pump)

HTW AHUKZ - Example of signal wiring(Heat pump) - 1

flowchart
graph TD
    A["Signal wire(P/Q/E)"] --> B["The signal wire between outdoor and master AHU control box"]
    C["Signal wire(C1/C2/E)"] --> D["The signal wire between master AHU control box and slave AHU control box"]
    E["Centralized controller"] --> F["L1"]
    F --> G["L2"]
    G --> H["L3"]
    H --> I["L4"]
    I --> J["L5"]
    J --> K["T1,T2,T2A,T2B,TA"]
    K --> L["Factory controller"]
    K --> M["The third party controller"]
    N["Signal wire(P/Q/E)"] --> O["L7"]
    O --> P["Master AHU"]
    Q["Signal wire(C1/C2/E)"] --> R["L4"]
    R --> S["Signal wire (C1/C2/E)"]
    T["N# slave AHU(N≤3)"] --> U["L5"]
    U --> V["1# AHU"]
    W["The third party controller"] --> X["L8"]
    X --> Y["Master AHU"]
    Z["2# AHU"] --> AA["L6"]
    AA --> AB["T2,T2A,T2B (optional)"]
    AC["Factory controller"] --> AD["OR"]
    AE["The third party controller"] --> AF["L8"]

Figure 3-23

HTW AHUKZ - Example of signal wiring(Heat pump) - 2

flowchart
graph TD
    A["Outdoor unit signal wire (X/Y/E)"] -->|L1| B["Signal wire(P/Q/E)"]
    B -->|L9| C["MS BOX"]
    C -->|L10| D["Signal wire (P/Q/E)"]
    D --> E["T1,T2,T2A,T2B,TA"]
    E --> F["The third party controller"]
    F --> G["OR"]
    G --> H["1# AHU"]
    D --> I["L7"]
    I --> J["MS BOX"]
    J --> K["Signal wire(P/Q/E)"]
    K --> L["L11"]
    L --> M["MS BOX"]
    M --> N["L7"]
    N --> O["The third party controller"]
    O --> P["OR"]
    P --> Q["2# AHU"]
    O --> R["T1,T2,T2A,T2B,TA"]

Figure 3-24
Note:
1. The diameter of the signal wire should be greater than or equal to 0.75 mm², and the C1C2E and PQE signal wire should be 3-core shielding wire.
2. Maximum wiring length: L1<1200m; L2+L3<1200m; L4+L5<1200m; L6<1200m; L7<200m; L8<200m; L9,L10,L11<1200m;
3. If the third party controller is selected to control the AHU box, the centralized controller cannot be connected to the system. The system can only connect to the centralized controller if a factory controller is selected to control the AHU control box.
4. Connect the centralized controller to the ODU XYE terminal block. Do not connect the centralized controller to the C1C2E terminal block of the AHU control box.

4 FUNCTION SETTINGS

4.1 Capacity Settings

The capacity DIP switches for the AHU control box should be set after the box is installed.

The capacity can be set through ENC1 and SW4-2. After completing the settings, power off and then power on the unit to apply the settings.

NOTE

Each AHU control box in parallel connection should undergo capacity settings.

Table 4-1 Capacities of SW4-2 and ENC1

HTW AHUKZ - NOTE - 1ENC1Capacity (hp)Capacity (KW)
000.8 hp2.2AHUKZ-00D
11.0 hp2.8
21.2 hp3.6
31.7 hp4.5
42.0 hp5.6
52.5 hp7.1
63.0 hp8.0
73.2 hp9.0AHUKZ-01D
83.6 hp10.0
94.0 hp11.2
A4.5 hp12.0
B5.0 hp14.0
C6.0 hp16.0
D6.5hp18.0
E7.0hp20.0AHUKZ-02D
F8.0 hp22.4
1010.0 hp28.0
112.0 hp33.5
214.0 hp40.0AHUKZ-03D
316.0 hp45.0
420.0 hp56.0

4.2 Setting the Master/Slave AHU Control Box

  1. If multiple AHU control boxes are connected in parallel, the master/slave AHU control box needs to be set through SW2-3 and SW2-4
HTW AHUKZ - Setting the Master/Slave AHU Control Box - 1SW2-3 and SW2-4 are 00: master AHU control box(factory default)
HTW AHUKZ - Setting the Master/Slave AHU Control Box - 2SW2-3 and SW2-4 are 01: slave AHU control box 1
...HTW AHUKZ - Setting the Master/Slave AHU Control Box - 3SW2-3 and SW2-4 are 10: slaveAHU control box 2
HTW AHUKZ - Setting the Master/Slave AHU Control Box - 4SW2-3 and SW2-4 are 11: slaveAHU control box 3
  1. When AHU control boxes are connected in parallel, the number of slave AHU control boxes must be set via SW1-3 and SW1-4.

Note: The number of slave AHU control boxes connected in parallel can only be set from the main board of the master AHU control box.

[W5AS]Valid for the master unit onlySW1-3 and SW1-4 are 00: the number of slave AHU control boxes connected in parallel is 0 (factory default)
HTW AHUKZ - Setting the Master/Slave AHU Control Box - 5Valid for the master unit onlySW1-3 and SW1-4 are 01: the number of slave AHU control boxes connected in parallel is 1
HTW AHUKZ - Setting the Master/Slave AHU Control Box - 6Valid for the master unit onlySW1-3 and SW1-4 are 10: the number of slave AHU control boxes connected in parallel is 2
HTW AHUKZ - Setting the Master/Slave AHU Control Box - 7Valid for the master unit onlySW1-3 and SW1-4 are 11: the number of slave AHU control boxes connected in parallel is 3

4.3 Address Settings of AHU Control Box

When powering-on for the first time, If the address is not set, the wired controller will display fault E9.

The ODU can use auto-addressing to set the address for an AHU control box which does not have an address.

If using manual setting, a wired controller is required to set the address of the AHU control box.

Only the master AHU control box communicates with the ODU. Therefore, only the address of master AHU control box needs to be set via the wired controller.

Press and hold ▲ and ▼ on the wired controller for 8s to enter the Address Settings page. If the AHU control box has an address, the page displays the current address. Otherwise, press ▲ and ▼ to change the address and press Ⓐ to confirm and send the current address to the AHU control box.

COOL 27°C 6.0 Therm Off ▲ ○ ↓ ⊗

Figure 4-1

Note:

The address of the same system cannot be repeated.

When the AHU control box is set to have a capacity of over 18 kW and the capacity DIP switch is greater than D, a virtual address will be generated. The virtual address is equivalent to the actual address and occupies the address bit. When setting the address, do not set the actual address to a virtual address that is already occupied.

The master AHU control box calculates the total number of addresses occupied by AHU control boxes (represented by the letter N) based on the capacity of each AHU control box, and generates N-1 virtual addresses based on the set addresses.

Table 4-2

ENC1SW4-2Corresponding Virtual AddressesQty of Occupied Addresses
00~DNo virtual address1
0E-FActual address +1////2
10-1Actual address +1////2
12-4Actual address +1Actual address +2Actual address +3//4

4.3.1 Single AHU Control Box Controlling One AHU

  1. If the ODU is V5X, the address quantity of the AHU control box detected by the ODU will be the sum of the actual address quantity and the virtual address quantity. For example, if the capacity code of an AHU control box is E, and the actual setting address is 5, a virtual address 6 will be generated based on Table 4-2, and the quantity of IDUs detected by the ODU will be 2. If the ODU is not a V5X ODU, the address quantity of the AHU control box detected by the ODU will be the sum of the actual address quantity.
  2. When the AHU control box system connects to the centralized controller, the actual address and the virtual address will be displayed for V5X ODUs. For example, if the capacity code of an AHU control box is E, and the actual setting address is 5, both the actual address 5 and the virtual address 6 will be displayed on the centralized controller. If the ODU is not a V5X ODU, only the actual address will be displayed.
  3. The network address is the same as the AHU control box address, so there is no need to set them separately.
  4. Each individual AHU control box controls one AHU. Each individual AHU control box is the main AHU control box.

4.3.2 Several AHU Control Boxes in a Parallel Connection Controlling One AHU

For this product, several AHU control boxes are allowed to connect in parallel to control one AHU. In this case, three steps must be completed.

  • Set the master AHU control box, slave 1 AHU control box, slave 2 AHU control box, and slave 3 AHU control box by using SW2-3 and SW2-4.
  • Set the quantity of slave AHU control boxes by using SW1-3 and SW1-4 on the master AHU control box.
  • Set an address on the master AHU control box by a wired controller. This address is an actual address. Virtual addresses will be generated in the parallel connection system.

If there are several parallel AHU control boxes systems in one refrigerant system, take figure 3-23 for example, calculate the number of occupied virtual addresses for each parallel AHU control box system, and set the actual address of each parallel AHU control box system to avoid repetition of actual addresses and virtual addresses.

4.4 Selection of Control by Return Air Temperature or by Outlet Air Temperature

AHU control box can select the control by either return air temperature or by outlet air temperature via SW4-1.

HTW AHUKZ - Selection of Control by Return Air Temperature or by Outlet Air Temperature - 1Valid for the master unit onlySW4-1 is 0: return air temperature control (factory default)
HTW AHUKZ - Selection of Control by Return Air Temperature or by Outlet Air Temperature - 2Valid for the master unit onlySW4-1 is 1: outlet air temperature control

When return air temperature control is selected, a inlet air temperature sensor must be connected to AHU control box;

when outlet air temperature control is selected, both the return air temperature sensor and outlet air temperature sensor must be connected to AHU control box.

When outlet air temperature control is selected, AHU control box must use T1 coming from AHU instead of wired controller. At this time, wired controller should turn off the function of "Follow Me". Please refer to wired controller manual for more information.

4.5 Selection of Controllers

The factory controller or a third party controller can be selected for the AHU control box. The type of controllers can be selected through SW4-3 and SW4-4.

SW4-3, SW4-4

HTW AHUKZ - Selection of Controllers - 1SW4-3 and SW4-4 are 00: factory controller mode (factory default)
HTW AHUKZ - Selection of Controllers - 2SW4-3 and SW4-4 are 01: capacity output mode of a third party controller
[G4BX]SW4-3 and SW4-4 are 10: set temperature control mode of third party controller

Note:

After DIP switches on main board are set, remember to power off and then power on the main board to apply the settings. Otherwise, the settings will be invalid.

When a third party controller is used, two control modes are available: capacity output control mode and set temperature control mode.

4.5.1 Factory Controller

When the factory controller is selected, the AHU control box can be controlled by the factory wired controller.

The factory wired controller in the accessories is connected to X1 and X2 ports on the main board.

Only the master AHU control box communicates with the ODU. As a result, when AHU control boxes are connected in parallel, only the factory wired controller of master AHU control box can communicate with ODU.

COOL HIGH 混 Sed Temp. 27°C 6.0h Timer Off L ▲ F D ▼

Factory wired controller
Figure 4-2

For detailed instructions for the wired controller, refer to the wired controller installation & owner's manual.

Note:

When the factory controller mode is applied, the main board of the AHU control box will not respond to the control signal from a third party controller.

4.5.2 Setting Capacity Output Mode via a Third Party Controller (Type 1)

When capacity setting with a third party controller mode has been selected, only the third party controller can be used to control the AHU control box. The signal from the factory controller will not respond except to the address setting and inquiring signal.

Even if capacity setting with third party controller mode has been selected, a factory remote controller or wired controller is needed to set the address for the AHU control box, because the third party controller does not have this function.

Third party controller wiring

For the wiring figure, refer to Figure 4-3. Pay careful attention to the following three things:

  1. The distance between the third party controller and the AHU control box depends on the external device that is connected (controller/relay...)
  2. If several AHU control boxes in a parallel connection control one AHU, the third party controller only needs to be connected with the master AHU control box.
  3. One third party controller cannot control two or more AHU at the same time.

Terminal block of AHU control box
HTW AHUKZ - Third party controller wiring - 1

flowchart
graph TD
    A["CN17"] --> B["Alarm"]
    C["CN18"] --> D["Defrost Run status"]
    E["CN62"] --> F["V-"]
    G["Fan status"] --> H["Heat mode"]
    I["On/off"] --> J["Cool mode"]
    K["The third party controller"] --> L["On/off"]
    M["0-10V signal"] --> N["V+"]

Figure 4-3

The definition of signals between the third party controller and AHU control box.

  1. Signals from the third party controller to the AHU control box.

Table 4-3

SignalSignal TypeSpecification Port
Capacity setAnalog voltage0-10VDC0-10V input
ON/OFFDry contactClose: ON Disconnect: OFF
Cool modeDry contactClose: cool mode Disconnect: no cool signalCOOL
Heat modeDry contactClose: heat mode Disconnect: no heat signalHEAT
Fan statusDry contactClose: fan ON Disconnect: fan OFFFAN

Note:

(1) The analog voltage must be between the maximum and the minimum value.

(2) Don't close the heat mode contact and cool mode contact at the same time if it needs to run the AHU control box.

  1. Signals from the AHU control box to the third party controller.

Table 4-4

SignalSignal TypeSpecification Port
AlarmDry contactClose: alarmDisconnect: no alarmAlarm
DefrostDry contactClose: defrostingDisconnect: no defrost
Run statusDry contactClose: runningDisconnect: offRun

Note:

All signals between the third party controller and AHU control box must be in accordance with the definition specified in Table 4-3 and Table 4-4. It will not work correctly if the definition of the signal in the third party controller is not correct.

Operation at 0-10V capacity output

This control mode requires a third party controller equipped with a temperature sensor that is used to control the following temperatures:

  1. Return air temperature of the AHU
  2. Outlet air temperature of the AHU

The AHU control box will interpret the 0–10 V signal according to 10 steps. The correlation between the voltage output and the system capacity is shown in the table below.

Capacity setting requirement table(same in heating and cooling)

Analog input 0-10V DCCapacity setting requiment
Normal (V)Range (V)
0U<0.50%
10.5≤U<1.510%
21.5≤U<2.520%
32.5≤U<3.530%
43.5≤U<4.540%
54.5≤U<5.550%
65.5≤U<6.560%
76.5≤U<7.570%
88.5≤U<9.580%
98.5≤U<9.590%
109.5≤U≤10100%

Operation instruction

When the third party controller has been selected, AHU control box will operate according to the control signal from the third party controller and output alarm, defrost and run status signal.

4.5.3 Setting Temperature Mode via a Third Party Controller (Type 2)

When setting temperature control mode via third party controller has been selected, the AHU control box does not respond to instructions from the factory controller except for address setting and query.

Even if temperature control by a third party controller is applied, a factory controller is still needed to set the address because the third party controller cannot do so Third party controller wiring

Please refer to Figure 4-4 for the wiring diagram. Pay careful attention to the following three things:

  1. The distance between the third party controller and the AHU control box depends on the external device that is connected (controller/relay...)
  2. If several AHU control boxes in parallel connection control one AHU, the third party controller only needs to be connected with the master AHU control box.

Terminal block of AHU control box
HTW AHUKZ - Setting Temperature Mode via a Third Party Controller (Type 2) - 1

flowchart
graph TD
    A["CN17"] --> B["Alarm"]
    C["CN18"] --> D["Defrost"]
    C --> E["Run status"]
    F["CN62"] --> G["Vc"]
    H["CN9CN32CN61"] --> I["Fan status"]
    H --> J["Heat mode"]
    H --> K["Cool mode"]
    L["0-10V signal"] --> M["On/off"]
    style A fill:#f9f,stroke:#333
    style C fill:#f9f,stroke:#333
    style F fill:#f9f,stroke:#333
    style H fill:#f9f,stroke:#333
    style L fill:#ccf,stroke:#333
    style B fill:#fff,stroke:#333
    style D fill:#fff,stroke:#333
    style E fill:#fff,stroke:#333
    style G fill:#fff,stroke:#333
    style I fill:#fff,stroke:#333
    style K fill:#fff,stroke:#333

Figure 4-4

  1. One third party controller can't control two or more AHUs at the same time.

Definition of signals between the third party controller and the AHU control box

  1. Signals from the third party controller to the AHU control box.

Table 4-7

SignalSignal TypeSpecification Port
Temp. setAnalog voltage0~10VDC refer to Table 6-30-10V input
ON/OFFDry ON/OFF contactClose: ON Disconnect: OFF
Cool modeDry contactClose: cool mode Disconnect: no cool signalCOOL
Heat modeDry contactClose: heat mode Disconnect: no heat signalHEAT
Fan statusDry contactClose: fan ON Disconnect: fan OFFFAN

Note:

(1) The analog voltage must be between the maximum and the minimum value.
(2) Don't close the heat mode contact and cool mode contact at the same time if it needs to run the AHU control box.

  1. Signals from the AHU control box to the third party controller

Table 4-8

SignalSignal TypeSpecification Port
AlarmDry contactClose: alarmDisconnect: no alarmAlarm
DefrostDry defrost contactClose: defrostingDisconnect: no defrost
Run statusDry contactClose: runningDisconnect: offRun

Note:

The definition of signals between the third party controller and AHU control box must comply with those shown in Table 4-7 and Table 4-8. If the signal is incorrectly defined, the system will not operate properly.

Operation at 0-10V temperature output

  • The AHU control box needs to be connected to the return air temperature sensor T1, and to be connected to the outlet air temperature sensor TA if the outlet air temperature control is selected.
  • The third party controller sends a voltage signal of 0-10V to the AHU control box. The AHU control box converts the voltage of 0-10V into the target temperature TS according to Table 4-9 or Table 4-10, and calculates the temperature difference between the target temperature and the return temperature T1 or the outlet temperature TA detected by the AHU control box. The temperature difference is used to regulate the system output.

1 0-10V 2 1 Third party controller 2 AHU control box Figure 4

Third party controller - return air temperature control setting

Table 4-9

NormalVoltage RangeCooling Set Temperature (°C)Heating Set Temperature (°C)
Min.Max.
0.500.75Not availableNot available
10.851.151717
1.41.251.551717
1.81.651.951717
2.22.052.351717
2.62.452.751717
32.853.151717
3.43.253.551717
3.83.653.951717
4.24.054.351818
4.64.454.751919
54.855.152020
5.45.255.552121
5.85.655.952222
6.26.056.352323
6.66.456.752424
76.857.152525
7.47.257.552626
7.87.657.952727
8.28.058.352828
8.68.458.752929
98.859.153030
9.49.2510Not availableNot available

Third party controller - outlet air temperature control setting

Table 4-10

NormalVoltage RangeCooling Set Temperature (°C)Heating Set Temperature (°C)
Min.Max.
0.500.75Non settableNon settable
10.851.151010
1.41.251.551111
1.81.651.951212
2.22.052.351313
2.62.452.751414
32.853.151515
3.43.253.551616
3.83.653.951717
4.24.054.351818
4.64.454.751919
54.855.152020
5.45.255.552121
5.85.655.952222
6.26.056.352323
6.66.456.752424
76.857.152525
7.47.257.552626
7.87.657.952727
8.28.058.352828
8.68.458.752929
98.859.153030
9.49.2510Non settableNon settable

Note:

The analog voltage must be between maximum and minimum value.

5 DIP DEFINITION

NOTE

0 means DIP switch is dialled to "OFF" 1 means DIP switch is dialled to "ON"

1) Definitions of each bit of SW1:

HTW AHUKZ - NOTE - 1Valid for the master unit onlySW1-1 is 0: shutdown compensation temperature (cooling) is 0^ (factory default)SW1-1 is 1: shutdown compensation temperature (cooling) is 2^ (outlet air temperature control is invalid)
HTW AHUKZ - NOTE - 2Valid for the master unit onlySW1-2 is 0: AHU control box provides three fan speeds (factory default)SW1-2 is 1: only one fan speed
HTW AHUKZ - NOTE - 3Valid for the master unit onlySW1-3 and SW1-4 are 00: the number of slave AHU control boxes connected in parallel is 0 (factory default); valid for the master unit
HTW AHUKZ - NOTE - 4Valid for the master unit onlySW1-3 and SW1-4 are 01: the number of slave AHU control boxes connected in parallel is 1
HTW AHUKZ - NOTE - 5Valid for the master unit onlySW1-3 and SW1-4 are 10: the number of slave AHU control boxes connected in parallel is 2
HTW AHUKZ - NOTE - 6Valid for the master unit onlySW1-3 and SW1-4 are 11: the number of slave AHU control boxes connected in parallel is 3

2) Definitions of each bit of SW2:

HTW AHUKZ - NOTE - 7SW2-1 is 0: automatic addressing (factory default)SW2-1 is 1: clearing AHU control box address
HTW AHUKZ - NOTE - 8SW2-2 is 0: no self-check (factory default)SW2-2 is 1: self-check
HTW AHUKZ - NOTE - 9SW2-3 and SW2-4 are 00: master AHU control box(factory default)
HTW AHUKZ - NOTE - 10SW2-3 and SW2-4 are 01: slave AHU control box 1
HTW AHUKZ - NOTE - 11SW2-3 and SW2-4 are 10: slave AHU control box 2
HTW AHUKZ - NOTE - 12SW2-3 and SW2-4 are 11: slave AHU control box 3

3) Definitions of each bit of SW3:

Return Air Temperature Control (SW4-1 is 0) OutletAir Temperature Control (SW4-1 is 1)
HTW AHUKZ - NOTE - 13Valid for the master unit onlySW3-1 and SW3-2 are 00: anti-cold air temperature value in heating mode is 15^ (factory default)SW3-1 and SW3-2 are 00: anti-cold air temperature value in heating mode is 14^
HTW AHUKZ - NOTE - 14Valid for the master unit onlySW3-1 and SW3-2 are 01: anti-cold air temperature value in heating mode is 20^ SW3-1 and SW3-2 are 01: anti-cold air temperature value in heating mode is 12^
HTW AHUKZ - NOTE - 15Valid for the master unit onlySW3-1 and SW3-2 are 10: anti-cold air temperature value in heating mode is 24^ SW3-1 and SW3-2 are 10: anti-cold air temperature value in heating mode is 16^
HTW AHUKZ - NOTE - 16Valid for the master unit onlySW3-1 and SW3-2 are 11: anti-cold air temperature value in heating mode is 26^ SW3-1 and SW3-2 are 11: anti-cold air temperature value in heating mode is 18^
HTW AHUKZ - NOTE - 17Valid for the master unit onlySW3-3 and SW3-4 are 00: temperature compensation in heating mode is 6^ (factory default)SW3-3 and SW3-4 are 00: Outlet air temperature control is invalid
HTW AHUKZ - NOTE - 18Valid for the master unit onlySW3-3 and SW3-4 are 01: temperature compensation in heating mode is 2^ SW3-3 and SW3-4 are 01: Outlet air temperature control is invalid
HTW AHUKZ - NOTE - 19Valid for the master unit onlySW3-3 and SW3-4 are 10: temperature compensation in heating mode is 4^ SW3-3 and SW3-4 are 10: Outlet air temperature control is invalid
HTW AHUKZ - NOTE - 20Valid for the master unit onlySW3-3 and SW3-4 are 11: temperature compensation in heating mode is 0^ (Follow Me function)SW3-3 and SW3-4 are 11: No temperature compensation for outlet air temperature control by default

4) Definitions of each bit of SW4:

HTW AHUKZ - NOTE - 21Valid for the master unit onlySW4-1 is 0: return air temperature control (factory default)SW4-1 is 1: outlet air temperature controlON1234Valid for the master unit onlySW4-2 indicates high bit (ON indicates + 16)
HTW AHUKZ - NOTE - 22Valid for the master unit onlySW4-3 and SW4-4 are 00: factory controller mode (factory default)ON1234Valid for the master unit onlySW4-3 and SW4-4 are 01: capacity output mode of a third party controller
HTW AHUKZ - NOTE - 23Valid for the master unit onlySW4-3 and SW4-4 are 10: set temperature control mode of a third party controllerON1234Valid for the master unit onlySW4-3 and SW4-4 are 11: set temperature control mode of a third party controller (reserved)

5) Definitions of each bit of SW9:

[2327]Valid for the master unit onlySW9-1 is 0: 2-digit digital display panel (factory default)SW9-2 is 1: 3-digit digital display panel
HTW AHUKZ - NOTE - 24Valid for the master unit onlySW9-2 is 0: One or more AHU control boxes are connected in parallel to one AHU; one coil is connected to multiple control boxes; (shielding faults from the slave unit's temperature sensors T1, T2, T2A, TA and T2B) (factory default)SW9-2 is 1: Multiple AHU control boxes are connected in parallel. In the event of multiple coils, one coil is connected to one control box; (shielding faults from the slave unit's temperature sensor T1,TA)
HTW AHUKZ - NOTE - 25Valid for the master unit onlySW9-3 is 0: no swing control (factory default)SW9-3 is 1: swing control

6) Definitions of each bit of SW10:

00: AHUKZ-00D model
01: AHUKZ-01D model
10: AHUKZ-02D model
11: AHUKZ-03D model

7) Definitions of J1:

Without jumper; no short circuit indicates a power failure memory function (factory default)
With jumper, short circuit indicates no power failure memory function

6 ERROR CODE AND QUERY

Error Code

PriorityDefinitionDisplayed content
1Rcfrigerant leak errorA1
2Emergency shut downA0
3No address is setFE (only displayed on the display board)
4IDU address code repeated→ F7+repeated address, displayed alternately every 1sF7+repeated address
5Mode conflict errorE0
6Communication error between IDU and ODUE1
7T1 sensor errorE2
8T2 sensor errorE3
9T2B sensor errorE4
10T2A sensor errorE5
11IDU fan errorE6 (reserved)
12EEPROM errorE7
13TA sensor errorE8 (the error is not reported when return air temperature control is applied)
14 E9Communication error with the wired controller, (only for wired controller) or no address is setted
15Error of electronic expansion valve coilsEb (restore after power on again)
17 EdODU error
18Water level alarm errorEE
19Low temperature alarmH2
20High temperature alarmH3
21The number of detected AHU control boxes and the number of dialing units are inconsistent, or Master-slave communication is not availableH6
22Capacity DIP switch of the AHU control box is inconsistent with modelH8 (restore after power on again)
23(ENC2,ENC3,ENC4)incorrect DIP switch for 0-10V fan signal.The DIP switch value ensures ENC2 < ENC3 < ENC4 .H9 (restore after power on again)
24 P1(Persessured)sensor error
25MS error modeF8
26MS self-check errorU4 (restore after power on again)
27 Slave unit error Hb

Query

Wired controller query

No.No. Parameter displayed on the wired controller during control box check
1Control box communication address
2Capacity (HP) of control box
3Control box network address (the same as the communication address)
4Set temperature Ts
5Room temperature T1
6Actual T2 AHU temperature
7Actual T2A AHU temperature
8Actual T2B AHU temperature
9TA temperature
10Compressor discharge temperature (show high discharge temperature)
11Target superheat degree (reserved)
12EEV position/8
13Software version No.
14Error Code

HTW

QUALITY COMFORT EVERYWHERE

HTW AHUKZ - QUALITY COMFORT EVERYWHERE - 1

GROUP

make your life easy

info@htwspain.com - www.htwspain.com

FRANCE

info@htwfrance.com

PORTUGAL

info@htw.pt

ITALIA

info.it@htwspain.com

HTW AHUKZ - QUALITY COMFORT EVERYWHERE - 2

IMPORTANT INFORMATION FOR CORRECT DISPOSAL OF THE PRODUCT IN ACCORDANCE WITH EC DIRECTIVE 2002/96/EC. At the end of its working life, the product must not be disposed of as urban waste. It must be taken to a special local authority deifferentiated waste collection centre or to a dealer providing this service. Disposing of a household appliance separately avoids possible negative consequences for the environment and health deriving from inappropriate disposal and enables the constituent materials to be recovered to obtain significant savings in energy and resources. As a reminder of the need to dispose of household appliances separately, the product is marked with a crossed-outwheeled dustbin.

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : HTW

Model : AHUKZ

Category : Air conditioner