EWADC11CZXL - Computer cooling system DAIKIN - Free user manual and instructions
Find the device manual for free EWADC11CZXL DAIKIN in PDF.
User questions about EWADC11CZXL DAIKIN
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Computer cooling system in PDF format for free! Find your manual EWADC11CZXL - DAIKIN and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. EWADC11CZXL by DAIKIN.
USER MANUAL EWADC11CZXL DAIKIN
MicroTech III ® Controller
MODBUS PROTOCOL INFORMATION SUMMARY
Application Software name: ACZC-ACZH-ADZ-ATLAS-AWS-EWWD-MNG-PFS
D-EOMOC002(19)12-14EN
Table of Contents
PREMISE....3
INTRODUCTION 4
Revision History 4
Reference Documents 4
BASIC INFORMATION ....5
Compatibility 5
Configuring the Microtech III for Modbus Network 5
Modbus Registers Addressing 5
MINIMUM INTEGRATION....6
DATA POINTS 7
Data Points for Chiller Models....7
Comprehensive Data Points List....9
ALARM POINTS ....18
Alarm Points for Chiller Models....18
Comprehensive Alarm Points List....19
APPENDIX A – ASCII CHARACTERS CONVERSION TABLE ......26
APPENDIX B - OVERALL REGISTERS TABLE 27
Premise
The Modbus protocol is a standardized Application Level (OSI Level 7) protocol used in interoperable Industrial Control networks. Modbus provides the communication infrastructure necessary to integrate products manufactured by different vendors and to integrate control services that are now independent.
This document describes the present status of Modbus communication profile for all MicroTech III application software, providing the necessary information to incorporate a MicroTech ^ III Chiller Unit Controller into a Building Automation System (BAS).
Modbus terms and principles are not defined. Refer to the appropriate specifications for definitions and details.
Revision History
1) D-EOMOC00011-14EN November 2014 Created
2) D-EOMOC002(17)12-14EN 17 December 2014 Improved
ADZ units
Upgraded
ATLAS Holding Registers 40025, 40026
3) D-EOMOC002(19)12-14EN 19 December 2014 Improved
ATLAS Holding Registers 40900, 40901, 40902
Improved
Appendix B
Upgraded
Holding Registers 40011, 40034
Upgraded
Revision History
Reference Documents
Ref.#1
www.Modbus.org
Compatibility
The MicroTech III Chiller Unit Controller conforms to the published Modbus standards. Controllers can communicate on standard Modbus networks using ASCII or RTU transmission mode. The MicroTech III Chiller Unit Controller uses the RTU mode only. Refer to Ref.#1 for more detailed information.
Configuring the Microtech III for Modbus Network
The MicroTech III Chiller Unit Controller can be configured in an interoperable Modbus network. The controller must have the corresponding Modbus Communication Module installed.
The MicroTech III Chiller Unit Controller and the Modbus Communication Module are shipped with default parameter values. Default values may be changed with the unit keypad. Parameters must be adjusted to accommodate your particular network. See the appropriate Operation Manual for default values and keypad operating instructions. See the MicroTech III Modbus Communication Module Installation Manual for details regarding network parameters available via the unit controller keypad/display.
Once communication module is set up and communication with network is established, in order to control the MicroTech III over the network, the Unit control source must be turned in "Network" (default is Local). From keypad/display set the Main Menu_View/Set Unit_Status/Settings_Control Source to "Network".
Modbus Registers Addressing
The Modbus Communication Module supports zero-based addressing. For example, holding register 40002 is addressed as 0001 in a Modbus message. The following tables assume 4xxxx addressing.
This section describes the information that assure compliance of Microtech III to the integration criteria for a Modbus network integration. The data/alarm points that represent the minimum integration data points are listed in Table 1 below and in boldface in Table 2 to Table 5.
Table 1. MicroTech III Chiller Unit Controller Registers for minimum integration
| Data/Alarm points |
| Actual Capacity |
| Chiller Enable Setpoint |
| Chiller Mode Setpoint - Network |
| Chiller Status |
| Clear Alarms - Network |
| Evaporator Entering Fluid Temperature |
| Evaporator Leaving Fluid Temperature |
| Capacity Limit Setpoint – Network |
| Cool Setpoint – Network |
| Problem Alarm Code |
| Fault Alarm Code |
| Warning Alarm Code |
Data Points for Chiller Models
Table 2 contains the list of Modbus data points available from the MicroTech III Chiller Unit Controller depending on the chiller model and corresponding unit controller application software. Application software name is available in the unit HMI: see in Main Menu, "About Chiller". The data points in boldface represent the minimum integration data points listed in Table 1.
Table 2. MicroTech III Unit Controller Data Points List for Chiller Model
| Data Point | ACZC | ACZH | ADZ | ATLAS | AWS | EWWD | MNG | PFS |
| Active Capacity Limit Output X X X X X X X X | ||||||||
| Active Energy | X | X | ||||||
| Active Setpoint X X X X X X X X | ||||||||
| Actual Capacity X X X X X X X X | ||||||||
| Alarm Digital Output X X X X X X X X | ||||||||
| Application Software Version X X X X X X X X | ||||||||
| Capacity Limit Setpoint - Network X X X X X X X X | ||||||||
| Chiller Capacity Limited X X X X X X X X | ||||||||
| Chiller Current X X X X X X X X | ||||||||
| Chiller Enable Output | X X | X X X | X X | X | ||||
| Chiller Enable Setpoint | X X | X X X | X X | X | ||||
| Chiller Local/Remote | X X | X X X | X X | X | ||||
| Chiller Location | X X | X X X | X X | X | ||||
| Chiller Mode Output | X X | X X X | X X | X | ||||
| Chiller Mode Setpoint – Network | X X | X X X | X X | X | ||||
| Chiller Model | X X | X X X | X X | X | ||||
| Chiller On/Off | X X | X X X | X X | X | ||||
| Chiller Status (Chiller Run Mode) | X X | X X X | X X | X | ||||
| Chiller Tons | X X | X X X | X X | X | ||||
| Chiller Voltage | X | X | ||||||
| Clear Alarms – Network | X X | X X X | X X | X | ||||
| Compressor Actual Capacity | X X | X X X | X X | X | ||||
| Compressor Current | X | X^1 | ||||||
| Compressor Discharge Refrigerant Temperature | X X | X X X | X X | X | ||||
| Compressor Full Load | X X | X X X | X X | X | ||||
| Compressor Off Auto | X X | X X X | X X | |||||
| Compressor Oil Feed Pressure | X X | X X X | X X | X | ||||
| Compressor Oil Level Status | X X | X X X | X X | |||||
| Data Point | ACZC | ACZH | ADZ | ATLAS | AWS | EMWD | MNG | PFS |
| Compressor Percent RLA X X | 1 | |||||||
| Compressor Power X X | 1 | |||||||
| Compressor Run Hours X X X X X X X X | ||||||||
| Compressor Starts X X X X X X X X | ||||||||
| Compressor Status X X X X X X X | ||||||||
| Compressor Suction Refrigerant Temperature X X X X X X X X X | ||||||||
| Compressor VFD Output | X | X | 1 | |||||
| Compressor Voltage X X | 1 | |||||||
| Condenser Approach Temperature X X X X X X X X X | ||||||||
| Condenser Ent Water Temperature | X | X | ||||||
| Condenser Leaving Water Temperature | X | X | ||||||
| Condenser Pump Run Hours | X | X | ||||||
| Condenser Pump Status | X | X | ||||||
| Condenser Refrigerant Pressure X X X X X X X X X | ||||||||
| Condenser Saturated Refrigerant Temperature | X X | X X | X X | X | ||||
| Cool Setpoint – Network | X X | X X | X X | X | ||||
| Date | X X | X X | X X | X | ||||
| Day of Week | X X | X X | X X | X | ||||
| Evaporator Approach Temperature | X X | X X | X X | X | ||||
| Evaporator Entering Water Temperature | X X | X X | X X | X | ||||
| Evaporator Flow Switch Status | X X | X X | X X | X | ||||
| Evaporator Leaving Water Temperature | X X | X X | X X | X | ||||
| Evaporator Pump #2 Status | X X | X X | X X | X | ||||
| Evaporator Refrigerant Pressure X X X X X X X X | ||||||||
| Evaporator Saturated Refrigerant Temperature | X X | X X | X X | X | ||||
| Evaporator SuperHeat Setpoint | X X | X X | X X | |||||
| Evaporator SuperHeat Temperature | X X | X X | X X | X | ||||
| EXV Position | X X | X X | X X | X | ||||
| Fault Alarm Code | X X | X X | X X | X | ||||
| Fault Alarm Index | X X | X X | X X | X | ||||
| Heat Recovery Enable - Network | X | |||||||
| Heat Recovery Ent Water Temperature | X | X | ||||||
| Heat Recovery Leaving Water Temperature | X | X | ||||||
| Heat Setpoint – Network | X | X X | X | X | ||||
| Hour | X X | X X | X X | X | ||||
| Ice Setpoint - Network | X X | X X | X X | X | ||||
| Liquid Temperature | X | |||||||
| Minute | X X | X X | X X | X | ||||
| Month | X X | X X | X X | X | ||||
| Noise Reduction Auto On | X X | X X | X | X | ||||
| Data Point | ACZC | ACZH | ADZ | ATLAS | AWS | EWD | MNG | PFS |
| Noise Reduction Status X X X X X | X | |||||||
| Number of Circuits X X X X X X X X | ||||||||
| Number of Compressors X X X X X X X X | ||||||||
| Outdoor Air Temperature X X X X X | X | |||||||
| Outdoor Fan Speed X X X X X X X | ||||||||
| Outdoor Fan Status X X X X X X X | ||||||||
| Power Factor | X | X | ||||||
| Power Input | X | X | ||||||
| Problem Alarm Code X X X X X X X X | ||||||||
| Problem Alarm Index X X X X X X X X | ||||||||
| Refrigerant Type X X X X X X X X | ||||||||
| Run Enabled X X X X X X X X | ||||||||
| Second X X X X X X X X | ||||||||
| Units X X X X X X X X | ||||||||
| Warning Alarm Code X X X X X X X X X | ||||||||
| Warning Alarm Index X X X X X X X X X | ||||||||
| Year X X X X X X X X |
Comprehensive Data Points List
Table 3 contains the complete list of Modbus data points available from the MicroTech III Chiller Unit Controller. The data points in boldface represent the minimum integration data points as identified in Table 1. Table 5 lists the available chiller alarm objects.
Table 3. MicroTech III Unit Controller Modbus Comprehensive Data Point List
| Data Point | Holding Register (4xxxx) | R/W | Range/Description |
| Active Capacity Limit Output | 14 | R | 0 - 100% |
| Active Energy | 1900 | R | Enabled whit Power meter optional |
| Active Setpoint | 12 | R | ACZC: 14.9° to 60.0 °F (-9.5 to 15.6°C) |
| ACZH: 14.9° to 131.0 °F (-9.5 to 55.0°C) | |||
| ADZ: 14.9° to 60.0 °F (-9.5 to 15.6°C) | |||
| ATLAS: 17.6° to 122.0°F (-8.0 to 50.0°C) | |||
| AWS: 17.6° to 122.0°F (-8.0 to 50.0°C) | |||
| EWWD: 15.0° to 140.0°F (-9.4° to 60.0°C) | |||
| MNG: 15.0° to 60.0 °F (-9.4° to 15.6°C) | |||
| PFS: 15.0° to 149.0°F (-9.4° to 65.0°C) | |||
| Actual Capacity | 13 | R | 0 - 100% |
| Alarm Digital Output | 5 | R | 0=No Alarm, 1=Alarm |
| Application Software Version^2 334 R | |||
| Application Software Version 338 R | |||
| Capacity Limit Setpoint - Network 38 RW 0 - 100% | |||
| Chiller Capacity Limited 4 R 0=Not Limited, 1=Limited | |||
| Chiller Current 25 R | |||
| Chiller Enable Output 2 R 0=Disable, 1=Enable | |||
| Chiller Enable Setpoint 9 RW 0=Disable, 1=Enable, 2=Null | |||
| Chiller Local/Remote | 1 R 0=Remote | 1=Local | |
| Chiller Location^3 | 318 | RW | |
| Chiller Location | 327 | RW | |
| Chiller Mode Output | 11 R | ACZC: 0=Null, 1= Ice, 2= Cool | |
| ACZH: 0=Null, 1= Ice, 2=Cool/Heat | |||
| ADZ: 0=Null, 1= Ice, 2=Cool | |||
| ATLAS: 0=Null, 1= Ice, 2=Cool | |||
| AWS: 0=Null, 1=Ice, 2=Cool | |||
| EWWD: 0=Null, 1=Ice, 2=Cool, 3=Heat | |||
| MNG: 0=Null, 1= Ice , 2=Cool, 3=Heat | |||
| PFS: 0=Null, 1=Cool, 2=Ice, 3=Heat | |||
| Chiller Mode Setpoint - Network | 34 RW | ACZC: 0=Null, 1= Ice, 2=Cool | |
| ACZH: 0=Null, 1= Ice, 2=Cool, 3=Heat | |||
| ADZ: 0=Null, 1= Cool, 2=Ice | |||
| ATLAS: 0=Null, 1= Ice, 2=Cool | |||
| AWS: 0=Null, 1= Ice, 2=Cool | |||
| EWWD: 0=Null, 1=Ice, 2 = Cool, 3 = Heat | |||
| MNG: 0=Null, 1=Cool , 2= Ice, 3=Heat | |||
| PFS: 0=Null, 1=Cool, 2=Ice, 3=Heat | |||
| Chiller Model | 317 R 0=Centrifugal, 1=Water Cooled, 2=Air Cooled, 3=Heat Pump, 9=Other | ||
| Chiller On/Off | 8 R 0=Off, 1=On | ||
| Chiller Status (Chiller Run Mode) | 15 R 1=Off, 2=Start, 3=Run, 4=Pre Shutdown, 5=Service | ||
| Chiller Tons | 1609 | R | |
| Chiller Voltage | 26 R Enabled whit Power meter optional | ||
| Circuit #1 Comp #1 - Actual Capacity | 1840 | R | |
| Circuit #1 Comp #1 - Current | 70 R 0 to10.000 Amps | ||
| Circuit #1 Comp #1 - Discharge Refrigerant Temp | 68 | R | -40°to 121°C (-40°to 250°F) |
| Circuit #1 Comp #1 - Full Load | 1842 | R | |
| Circuit #1 Comp #1 - Off Auto | 1841 | R | |
| Circuit #1 Comp #1 - Oil Feed Pressure | 1849 | R -5 | 801473 to 17.54946 psi(-40 to 121 kPa) |
| Circuit #1 Comp #1 - Oil Feed Pressure (PFS) | 1846 | R -5 | 801473 to 17.54946 psi(-40 to 121 kPa) |
| Circuit #1 Comp #2 - Oil Feed Pressure (PFS) | 1832 | R -5 | 801473 to 17.54946 psi(-40 to 121 kPa) |
| Circuit #1 Comp #1 - Oil Level Status | 1851 R | ||
| Circuit #1 Comp #1 - Percent RLA | 69 R 0 | 110% | |
| Circuit #1 Comp #1 - Power | 72 R 0 | 3500 kW | |
| Circuit #1 Comp #1 - Run Hours | 74 RW | 0-999.999 | (ACZC, ACZH, ADZ, ATLAS, AWS) |
| Circuit #1 Comp #1 - Run Hours | 74 R 0 | 999.999 | (EWWD, MNG, PFS) |
| Circuit #1 Comp #1 - Starts | 73 RW | 0 - 65.5 | 35 (ACZC, ACZH, ADZ, ATLAS, AWS) |
| Circuit #1 Comp #1 - Starts | 73 R 0 | - 65.535 | (EWWD, MNG, PFS) |
| Circuit #1 Comp #1 - Status | 1852 R | ||
| Circuit #1 Comp #1 - Suction Refrigerant Temp | 65 R | -40°-110° | C (-40-230° F) |
| Circuit #1 Comp #1 - VFD Output | 1845 R | ||
| Circuit #1 Comp #1 - Voltage | 71 R 0 | to 15.000 | V |
| Circuit #1 Comp #2 - Actual Capacity | 1826 R | ||
| Circuit #1 Comp #2 - Discharge Refrigerant Temp | 81 R | -40° to 12 | 1°C (-40°-250°F) |
| Circuit #1 Comp #2 - Full Load | 1828 R | ||
| Circuit #1 Comp #2 - Off Auto | 1827 R | ||
| Circuit #1 Comp #2 - Run Hours | 87 R 0 | 999,999 | |
| Circuit #1 Comp #2 - Starts | 86 R 0 | - 65,535 | |
| Circuit #1 Comp #2 - Status | 1838 R | ||
| Circuit #1 Comp #2 - Suction Refrigerant Temp | 78 R | -40°-110° | C (-40-230° F) |
| Circuit #1 Comp #3 - Off Auto | 1814 RW | ||
| Circuit #1 Comp #3 - Run Hours | 100 RW | 0-999.999 | |
| Circuit #1 Comp #3 - Starts | 99 R 0 | - 65,535 | |
| Circuit #1 Comp #3 - Status | 1825 R | ||
| Circuit #1 Condenser Approach Temp | 1987 R | 0 to 50 d°F (0 to10 d°C) | |
| Circuit #1 Condenser Refrigerant Pressure | 39 R 0 | to 410 psi (700 psi for R410A) - 0 to 2827 kPa (4826 kPa for R410A) | |
| Circuit #1 Condenser Saturated Refrigerant Temp | 40 R | -26.1 to 85°C (-14.98-185°F) | |
| Circuit #1 Evaporator Approach Temp | 1988 R | 0 to 50 d°F (0 to10 d°C) | |
| Circuit #1 Evaporator Refrigerant Pressure | 41 R | -349.97 to 349.97 psi (-2413 kPa to 2413 kPa) | |
| Circuit #1 Evaporator Saturated Refrigerant Temp | 42 R | -26.1 to 85°C (-14.98 to 185°F) | |
| Circuit #1 EXV Position | 1982 R | 0 to 110% | |
| Circuit #1 Outdoor Fan Speed | 1986 R | ||
| Circuit #1 Outdoor Fan Status | 1997 R | ||
| Circuit #2 Comp #1 - Actual Capacity 1800 R | |||
| Circuit #2 Comp #1 - Current | 109 R | 0 to 10.000 | |
| Circuit #2 Comp #1 - Discharge Refrigerant Temp | 107 R | -40° to 12 | 1°C (-40°-250°F) |
| Circuit #2 Comp #1 - Full Load | 1802 R | ||
| Circuit #2 Comp #1 - Off Auto | 1801 RW | ||
| Circuit #2 Comp #1 - Oil Feed Pressure | 1809 R | -5.80147 | 3 to 17.54946 psi(-40 to 121 kPA) |
| Circuit #2 Comp #1 - Oil Level Status | 1811 R | ||
| Circuit #2 Comp #1 - Percent RLA | 108 R | 0-110% | |
| Circuit #2 Comp #1 - Power | 111 R | 0-3500 kW | |
| Circuit #2 Comp #1 - Run Hours | 113 RW | 0-999.999 | (ACZC, ACZH, ADZ, ATLAS, AWS) |
| Circuit #2 Comp #1 - Run Hours | 113 R 0 | -999.999 | (EWWD,MNG) |
| Circuit #2 Comp #1 - Starts | 112 RW | 0 – 65.535 | (ACZC, ACZH, ADZ, ATLAS, AWS) |
| Circuit #2 Comp #1 - Starts | 112 R 0 | – 65.535 | (EWWD, MNG) |
| Circuit #2 Comp #1 - Status | 1812 R | ||
| Circuit #2 Comp #1 - VFD Output | 1805 R | ||
| Circuit #2 Comp #1 Suction Refrigerant Temp | 104 R -40°-110° | C (-40-230°F) | |
| Circuit #2 Comp #1 Voltage | 110 R 0 | -15,000 | |
| Circuit #2 Comp #2- Run Hours | 126 RW | 0-999.999 | |
| Circuit #2 Comp #2- Starts | 125 RW | 0 - 65.535 | |
| Circuit #2 Comp #2 - Off Auto | 1788 RW | ||
| Circuit #2 Comp #2 - Status | 1799 R | ||
| Circuit #2 Comp #3 - Off Auto | 1775 RW | ||
| Circuit #2 Comp #3 - Run Hours | 139 RW | 0-999.999 | |
| Circuit #2 Comp #3 - Starts | 138 RW | 0 – 65.535 | |
| Circuit #2 Comp #3 - Status | 1786 R | ||
| Circuit #2 Condenser Approach Temp | 1971 R | ||
| Circuit #2 Condenser Refrigerant Pressure | 43 R 0 | -410 psi | (700 psi for R410A) |
| Circuit #2 Condenser Saturated Refrigerant Temp | 44 R -26.1-85°C (-14.98-185°F) | ||
| Circuit #2 Evaporator Approach Temp | 1972 R | ||
| Circuit #2 Evaporator Refrigerant Pressure | 45 R -349.97–349.97 psi (-2413 kPa – 2413 kPa) | ||
| Circuit #2 Evaporator Saturated Refrigerant Temp | 46 R -26.1-85°C (-14.98-185°F) | ||
| Circuit #2 EXV Position | 1966 R | ||
| Circuit #2 Outdoor Fan Speed | 1970 R | ||
| Circuit #2 Outdoor Fan Status | 1981 R | ||
| Circuit #3 Comp #1 - Actual Capacity 1761 R | |||
| Circuit #3 Comp #1 - Current | 148 R 0 | -10.000 | |
| Circuit #3 Comp #1 - Discharge Refrigerant Temp | 146 R -40°– 121°C (-40°– 250°F) | ||
| Circuit #3 Comp #1 - Full Load | 1763 R | ||
| Circuit #3 Comp #1 - Off Auto | 1762 R | ||
| Circuit #3 Comp #1 - Oil Feed Pressure | 1770 R -5.801473 to 17.54946 psi(-40 to 121 kPA) | ||
| Circuit #3 Comp #1 - Oil Level Status | 1772 R | ||
| Circuit #3 Comp #1 - Percent RLA | 147 R 0 | -110% | |
| Circuit #3 Comp #1 - Power | 150 R 0 | -3500 kW | |
| Circuit #3 Comp #1 - Run Hours | 152 RW | 0-999.999 | (ACZC, ACZH, ADZ, ATLAS, AWS) |
| Circuit #3 Comp #1 - Run Hours | 152 R 0 | -999.999 | (EWWD, MNG) |
| Circuit #3 Comp #1 – Starts | 151 RW | 0 – 65.535 | (ACZC, ACZH, ADZ, ATLAS, AWS) |
| Circuit #3 Comp #1 – Starts | 151 R 0 | – 65.535 | (EWWD, MNG) |
| Circuit #3 Comp #1 - Status | 1773 R | ||
| Circuit #3 Comp #1 - Suction Refrigerant Temp | 143 R -40° to110°C (-40-230°F) | ||
| Circuit #3 Comp #1 - VFD Output | 1766 RW | ||
| Circuit #3 Comp #1 - Voltage | 149 R 0 | -15.000 | |
| Circuit #3 Condenser Approach Temp | 1955 RW | ||
| Circuit #3 Condenser Refrigerant Pressure | 47 RW | 0-410 psi (700 psi for R410A) | 0-2827 kPa, (4826 kPa for R410A) |
| Circuit #3 Condenser Saturated Refrigerant Temp | 48 RW | -26.1-85°C (-14.98-185°F) | |
| Circuit #3 Evaporator Approach Temp | 1956 RW | ||
| Circuit #3 Evaporator Refrigerant Pressure | 49 RW | -349.97 | -349.97 psi (-2413 kPa - 2413 kPa) |
| Circuit #3 Evaporator Saturated Refrigerant Temp | 50 RW | -26.1-85°C (-14.98-185°F) | |
| Circuit #3 EXV Position | 1950 R | ||
| Circuit #3 Outdoor Fan Speed | 1954 RW | ||
| Circuit #3 Outdoor Fan Status | 1965 RW | ||
| Clear Alarms - Network 10 RW 0=Normal, 1=Clear Alarms, 2=Null | |||
| Condenser Entering Water Temp 19 R -40-230°F (-40-1 10°C) | |||
| Condenser Leaving Water Temp 20 R -40-230°F (-40-11 0°C) | |||
| Condenser Pump Run Hours 297 R 0-999.999 | |||
| Condenser Pump Status | 299 R 0=Pump | Off Request, 1=Pump On Request | |
| Cool Setpoint - Network | 35 RW | ACZC: 14.9° to 60.08°F (-9.5 to 15.6 °C) | |
| ACZH: 14.9° to 60.08°F (-9.5 to 15.6 °C) | |||
| ADZ: 14.9° to 60.08°F (-9.5 to 15.6 °C) | |||
| ATLAS: 17.6° to 59.0 °F (-8.0 to 15.0 °C) | |||
| AWS: 17.6° to 59.0 °F (-8.0 to 15.0 °C) | |||
| EWWD: 24.98° to 60.08 °F (-3.9 to 15.6 °C) | |||
| MNG: 24.98° to 60.08 °F (-3.9 to 15.6 °C) | |||
| PFS: 24.98° to 60.08 °F (-3.9 to 15.6 °C) | |||
| Date | 311 | RW | |
| Day of Week | 312 | RW | 0 (Monday) - 6 (Sunday).Calculated by the controller. |
| Evaporator Entering Fluid Temp | 16 R -40-230°F | (-40-110°C) | |
| Evaporator Flow Switch Status | 6 | R 0=No Flow, 1=Flow | |
| Evaporator Leaving Fluid Temp | 17 R -40-230°F | (-40-1 10°C) | |
| Evaporator Pump #1 Run Hours | 303 | RW | 0-999.999(ACZC, ACZH, ADZ, ATLAS, AWS) |
| Evaporator Pump #1 Run Hours | 303 R 0-999.999 | (EWWD, MNG, PFS) | |
| Evaporator Pump #1 Status | 305 R 0=Pump | Off Request, 1=Pump On Request | |
| Evaporator Pump #2 Run Hours | 306 | RW | 0-999.999 (ACZC, ACZH, ADZ, ATLAS, AWS) |
| Evaporator Pump #2 Run Hours | 306 R 0-999.999 | (EWWD, MNG, PFS) | |
| Evaporator Pump #2 Status | 308 R 0=Pump | Off Request, 1=Pump On Request | |
| Evaporator SuperHeat Setpoint 1897 R | |||
| Evaporator SuperHeat Temp | 1899 R | ||
| Fault Alarm Code | 33 R | 0=No Alarms32551=COMP SHUTDOWN-Low pressure ratio Circuit #1, Comp #132583=COMP SHUTDOWN - Low pressure ratio Circuit #2, Comp #132615=COMP SHUTDOWN-Low pressure ratio Circuit #3, Comp #132771=COMP SHUTDOWN-Outside Air Temp Sensor Fault,33063=COMP SHUTDOWN-Current Overload Circuit #1, Comp #133095=COMP SHUTDOWN-Current Overload Circuit #2, Comp #133127=COMP SHUTDOWN-Current Overload Circuit #3, Comp #134087=COMP SHUTDOWN-Motor Protector Circuit #1 Comp #134119=COMP SHUTDOWN-Motor Protector Circuit #2 Comp #134599=COMP SHUTDOWN-Motor Temp High Circuit #1, Comp #134631=COMP SHUTDOWN-Motor Temp High Circuit #2, Comp #134663=COMP SHUTDOWN-Motor Temp High Circuit #3, Comp #134855=COMP SHUTDOWN-Motor Temp Sensor Fault Circuit #1, Comp #134887=COMP SHUTDOWN-Motor Temp Sensor Fault Circuit #2, Comp #1 | |
| 34919=COMP SHUTDOWN-Motor Temp Sensor Fault Circuit #3, Comp #136387=CIRCUIT SHUTDOWN-Condenser Pressure Sensor Circuit #1 Fault36391=COMP SHUTDOWN-Condenser Pressure Sensor Fault Circuit #1, Comp #136419=CIRCUIT SHUTDOWN-Condenser Pressure Sensor Circuit #2 Fault36423=COMP SHUTDOWN-Condenser Pressure Sensor Fault Circuit #2, Comp #136455=COMP SHUTDOWN-Condenser Pressure Sensor Fault Circuit #3, Comp #137155=CIRCUIT SHUTDOWN-Condenser Pressure High Circuit #1 Fault37159=COMP SHUTDOWN-Condenser Pressure High Circuit #1, Comp #137187=CIRCUIT SHUTDOWN-Condenser Pressure High Circuit #2 Fault37191=COMP SHUTDOWN-Condenser Pressure High Circuit #2, Comp #137223=COMP SHUTDOWN-Condenser Pressure High Circuit #3, Comp #137671=COMP SHUTDOWN-Discharge Temp Sensor Fault Circuit #1, Comp #137703=COMP SHUTDOWN-Discharge Temp Sensor Fault Circuit #2, Comp #137735=COMP SHUTDOWN-Discharge Temp Sensor Fault Circuit #3, Comp #137927=COMP SHUTDOWN-Discharge Temp High Circuit #1, Comp #137959=COMP SHUTDOWN-Discharge Temp High Circuit #2, Comp #137991=COMP SHUTDOWN-Discharge Temp High Circuit #3, Comp #138403=UNIT SHUTDOWN-Evaporator Water Flow Loss, 38659=UNIT SHUTDOWN-Evaporator Leaving Water Temp Low (Freeze)38915=COMP SHUTDOWN-Evaporator Pressure Low 39203=CIRCUIT SHUTDOWN-Low Evaporator Pressure Circuit #1 Fault39207=COMP SHUTDOWN-Evaporator Pressure Low Circuit #1, Comp #139235=CIRCUIT SHUTDOWN-Low Evaporator Pressure Circuit #2 Fault39239=COMP SHUTDOWN-Evaporator Pressure Low Circuit #2, Comp #139271=COMP SHUTDOWN-Evaporator Pressure Low Circuit #3, Comp #139715=CIRCUIT SHUTDOWN-Evaporator Pressure Sensor Circuit #1 Fault39719=COMP SHUTDOWN-Evaporator Pressure Sensor Fault Circuit #1, Comp #139747=CIRCUIT SHUTDOWN-Evaporator Pressure Sensor Circuit #2 Fault39751=COMP SHUTDOWN-Evaporator Pressure Sensor Fault Circuit #2, Comp #139783=COMP SHUTDOWN-Evaporator Pressure Sensor Fault Circuit #3, Comp #141255=COMP LOCKOUT-Number of Allowed Re-Starts Exceeded Circuit #1, Comp #141287=COMP LOCKOUT-Number of Allowed Re-Starts Exceeded Circuit #2, Comp #141319=COMP LOCKOUT-Number of Allowed Re-Starts Exceeded Circuit #3, Comp #141475=UNIT SHUTDOWN-Evaporator Leaving Water Temp Sensor Fault41731=UNIT SHUTDOWN-Evaporator Entering Water Temp Sensor Failure42535=COMP SHUTDOWN-Mechanical High Pressure Circuit #1, Comp #142567=COMP SHUTDOWN-Mechanical High Pressure Circuit #2, Comp #142599=COMP SHUTDOWN-Mechanical High Pressure Circuit #3, Comp #144327=COMP SHUTDOWN-Oil Feed Pressure Sensor Fault Circuit #1, Comp #144359=COMP SHUTDOWN-Oil Feed Pressure Sensor Fault Circuit #2, Comp #144391=COMP SHUTDOWN-Oil Feed Pressure Sensor Fault Circuit #3, Comp #145059=SHUTDOWN-Phase Voltage Protection45351=COMP SHUTDOWN-Starter Fault Comp Circuit #1, Comp #145383=COMP SHUTDOWN-Starter Fault Comp Circuit #2, Comp #145415=COMP SHUTDOWN-Starter Fault Comp Circuit #3, Comp #146887=COMP SHUTDOWN-Suction Temp Sensor Fault Circuit #1, Comp #146919=COMP SHUTDOWN-Suction Temp Sensor Fault Circuit #2, Comp #146951=COMP SHUTDOWN-Suction Temp Sensor Fault Circuit #3, Comp #147911=COMP SHUTDOWN-Mechanical Low Pressure Circuit #1, Comp #147943=COMP SHUTDOWN-Mechanical Low Pressure Circuit #2, Comp #147975=COMP SHUTDOWN-Mechanical Low Pressure Circuit #3, Comp #148131=Unit Controller offline48163=Controller board offline Circuit #148195=Controller board offline Circuit #248227=Controller board offline Circuit #348419=COMP SHUTDOWN-No Pressure Change After Start Circuit #148451=COMP SHUTDOWN-No Pressure Change After Start Circuit #248483=COMP SHUTDOWN-No Pressure Change After Start Circuit #348675=COMP SHUTDOWN-No Pressure at Startup Circuit #148707=COMP SHUTDOWN-No Pressure at Startup Circuit #248739=COMP SHUTDOWN-No Pressure at Startup Circuit #348935=COMP SHUTDOWN-Slide position sensor fault Circuit #1, Comp#148967=COMP SHUTDOWN-Slide position sensor fault Circuit #2, Comp#148999=COMP SHUTDOWN-Slide position sensor fault Circuit #3, Comp#149155=UNIT STOP-Emergency Stop Alarm49411=UNIT STOP-Evaporator Water Temps Inverted 49667=UNIT STOP-External Alarm49923=Evaporator Leaving Water Temp 1 Sensor Fault50179=Evaporator Leaving Water Temp 2 Sensor Fault50435=CIRCUIT SHUTDOWN-Evaporator 1 Freeze Protection50691=CIRCUIT SHUTDOWN-Evaporator 2 Freeze Protection50983=COMP SHUTDOWN-COMP VFD Fault Circuit #1, Comp #151015=COMP SHUTDOWN-COMP VFD Fault Circuit #2, Comp #151047=COMP SHUTDOWN-COMP VFD Fault Circuit #3, Comp #151239=COMP SHUTDOWN-COMP VFD Over Heat Fault Circuit #1, Comp #151271=COMP SHUTDOWN-COMP VFD Over Heat Fault Circuit #2, Comp #151303=COMP SHUTDOWN-COMP VFD Over Heat Fault Circuit #3, Comp #151495=COMP SHUTDOWN-COM ERROR With COMP VFD Circuit #1, Comp #151527=COMP SHUTDOWN-COM ERROR With COMP VFD Circuit #2, Comp #151559=COMP SHUTDOWN-COM ERROR With COMP VFD Circuit #3, Comp #151755 = COMP SHUTDOWN -Low Discharge Superheat Circuit #1, Comp #151783 = COMP SHUTDOWN -Low Discharge Superheat Circuit #2, Comp #151815 = COMP SHUTDOWN -Low Discharge Superheat Circuit #3, Comp #158371= UNIT STOP - PVM GFP Fault58403= CIRCUIT SHUTDOWN- PVM GFP Circuit #1 Fault58435= CIRCUIT SHUTDOWN- PVM GFP Circuit #2 Fault58915=COMP SHUTDOWN-Refrig Charge Circuit #158947=COMP SHUTDOWN-Refrig Charge Circuit #258979==COMP SHUTDOWN-Refrig Charge Circuit #3 | |||
| Fault Alarm Index 30 R | 0=No Alarms127=COMP SHUTDOWN-Low pressure ratio #n128=COMP SHUTDOWN-Outside Air Temp Sensor Fault129=COMP SHUTDOWN-Current Overload Circuit #n, Comp #n135=COMP SHUTDOWN-Motor Temp High Circuit #n 136=COMP SHUTDOWN-Motor Temp Sensor Fault #n142=COMP SHUTDOWN-Condenser Pressure Sensor Fault #n 145=COMP SHUTDOWN-Condenser Pressure High #n,147=COMP SHUTDOWN-Discharge Temp Sensor Fault #n148=COMP SHUTDOWN-Discharge Temp High #n150=UNIT SHUTDOWN-Evaporator Water Flow Loss151=UNIT SHUTDOWN-Evaporator Leaving Water Temp Low (Freeze)153=COMP SHUTDOWN-Evaporator Pressure Low #n, 155=COMP SHUTDOWN-Evaporator Pressure Sensor Fault #n 161=COMP LOCKOUT-Number of Allowed Re-Starts Exceeded #n162=UNIT SHUTDOWN-Evaporator Leaving Water Temp Sensor Fault163=UNIT SHUTDOWN-Evaporator Entering Water Temp Sensor Failure166=COMP SHUTDOWN-Mechanical High Pressure #n172=COMP SHUTDOWN-Oil Delta Pressure High Circuit #1, Comp #1173=COMP SHUTDOWN-Oil Feed Pressure Sensor Fault #n176=SHUTDOWN-Phase Voltage Protection177=COMP SHUTDOWN-Starter Fault Comp #n183=COMP SHUTDOWN-Suction Temp Sensor Fault #n 187=COMP SHUTDOWN-Mechanical Low Pressure #n 188=Controller board offline Circuit #n189=COMP SHUTDOWN-No Pressure Change After Start 190=COMP SHUTDOWN-No Pressure at Startup 191=CIRCUIT SHUTDOWN-Evaporator Freeze Protection 192=UNIT STOP-Emergency Stop Alarm193=UNIT STOP-Evaporator Water Temps Inverted194=UNIT STOP-External Alarm195=Evaporator Leaving Water Temp 1 Sensor Fault 196=Evaporator Leaving Water Temp 2 Sensor Fault 197=CIRCUIT SHUTDOWN-Evaporator 1 Freeze Protection 198=CIRCUIT SHUTDOWN-Evaporator 2 Freeze Protection199=COMP SHUTDOWN-COMP VFD Fault Circuit #n, Comp #n200=COMP SHUTDOWN-COMP VFD Over Heat Fault Circuit #n, Comp #n201=COMP SHUTDOWN-COM ERROR With COMP VFD Circuit #n, Comp #n202 = COMP SHUTDOWN-Low Discharge Superheat Circuit #n, Comp #n230-COMP SHUTDOWN-Refrig Charge Circuit #n | ||
| Heat Recovery Enable - Network 18 RW 0=Disable, 1=Enable | |||
| Heat Recovery Entering Water Temp 22 R Enabled | whit Heat Recovery option | ||
| Heat Recovery Leaving Water Temp 23 R Enabled | whit Heat Recovery option | ||
| Heat Setpoint - Network 37 RW | ACZH: 77.0° to 131°F (25.0 to 55.0 °C) | ||
| ATLAS: 86.0 to 122 °F(30.0 to 50.0°C) | |||
| AWS: 77.0° to 131°F (25.0 to 55.0 °C) | |||
| EWWD: 77.0 to 140 °F (25.0 to 60.0 °C) | |||
| PFS: 77.0° to 149°F (25.0° to 65.0 °C) | |||
| Hour 313 RW 0-23 | |||
| Ice Setpoint - Network 36 RW | ACZC: 14.9° to 39.9°F (-9.5 to 4.4 °C) | ||
| ACZH: 14.9° to 39.9°F (-9.5 to 4.4 °C) | |||
| ADZ: 14.9° to 39.9°F (-9.5 to 4.4 °C) | |||
| ATLAS: 17.6° to 39.2 °F (-8.0 to 4.0 °C) | |||
| AWS: 17.6° to 39.2 °F (-8.0 to 4.0 °C) | |||
| EWWD: 15.08° to 38.12 °F (-9.4° to 3.4 °C) | |||
| MNG: 15.08° to 38.12 °F (-9.4° to 3.4 °C) | |||
| PFS: 15.08° to 38.12 °F (-9.4° to 3.4 °C) | |||
| Liquid Temp 1984 R | |||
| Minute 314 RW 0-59 | |||
| Month 310 RW 1-12 | |||
| Noise Reduction Auto On 1998 RW | |||
| Noise Reduction Status | 2000 R | ||
| Number of Circuits | 1607 R | ||
| Number of Comps | 1608 R | ||
| Outdoor Air Temp | 24 | R | -40-230°F (-40-110°C) |
| Power Factor | 1902 R | Enabled with Power meter optional | |
| Power Input | 27 | R | Enabled with Power meter optional |
| Problem Alarm Code | 32 | R | 0=No Alarms,16418=RESTART DELAYED - Power Loss While Running Circuit #116450=RESTART DELAYED - Power Loss While Running Circuit #216482=RESTART DELAYED - Power Loss While Running Circuit #316642=START INHIBITED - Ambient Temp Low 16898=INHIBIT LOAD - Condenser Pressure High 17186=INHIBIT LOAD - Condenser Pressure High Circuit #1 17218=INHIBIT LOAD - Condenser Pressure High Circuit #217250=INHIBIT LOAD - Condenser Pressure High Circuit #3 17282=INHIBIT LOAD - Condenser Pressure High Circuit #1 17730=UNLOAD Condenser Pressure High Circuit #3 17794=UNLOAD LOAD - Evaporator Pressure Low Circuit #119522=INHIBIT LOAD - Evaporator Pressure Low Circuit #2 19554=INHIBIT LOAD - Evaporator Pressure Low Circuit #3 19586=INHIBIT LOAD - Evaporator Pressure Low Circuit #1 20034=UNLOAD - Evaporator Pressure Low Circuit #2 20066=UNLOAD - Evaporator Pressure Low Circuit #3 20098=UNLOAD - Evaporator20262=UNLOAD-Comp Motor Current High Circuit #1, Comp #120294=UNLOAD-Comp Motor Current High Circuit #2, Comp #120326=UNLOAD-Comp Motor Current High Circuit #3, Comp #120738=PUMP #2 START ATTEMPTED - Evaporator Pump #1 Failure20994=PUMP #1 START ATTEMPTED - Evaporator Pump #2 Failure21542=INHIBIT LOAD-Comp Motor Current High Circuit #1, Comp #121574=INHIBIT LOAD-Comp Motor Current High Circuit #2, Comp #121606= INHIBIT LOAD-Comp Motor Current High Circuit #3, Comp #1 |
| Problem Alarm Index | 29 | R | 0=No Alarms64=RESTART DELAYED-Power Loss While Running Circuit #n65=START INHIBITED - Ambient Temp Low67=INHIBIT LOAD - Condenser Pressure High Circuit #n69=UNLOAD - Condenser Pressure High Circuit #n76=INHIBIT LOAD - Evaporator Pressure Low Circuit #n 78=UNLOAD - Evaporator Pressure Low Circuit #n79=UNLOAD - Comp Motor Current High Circuit #n, Comp #n81=PUMP #2 START ATTEMPTED - Evaporator Pump #1 Failure82=PUMP #1 START ATTEMPTED - Evaporator Pump #2 Failure84= INHIBIT LOAD-Comp Motor Current High Circuit #n, Comp #n |
| Refrigerant Type 1606 R | |||
| Run Enabled 3 R 0=Off, 1= Run Allowed | |||
| Second 315 RW 0-59 | |||
| Units 316 RW 0=English, 1=Metric | |||
| Warning Alarm Code 31 R | 0=No Alarms513=Evaporator Entering Water Temp Sensor Failure 2049=Bad setpoint override input2305=Bad demand limit input2817=Unit power restore3105=Circuit 1 failed pumpdown3137=Circuit 2 Failed pumpdown3169=Circuit 3 failed pumpdown3201=Circuit 4 failed pumpdown3329=External Event3585=Bad Current Limit Input3841=Option Controller Communication Failed4128=Circuit 1 Low Refrigerant Charge4160=Circuit 2 Low Refrigerant Charge4192=Circuit 3 Low Refrigerant Charge4352=Chiller Network Communication Failure | ||
| Warning Alarm Index 28 R | 0=No Alarms8=Bad setpoint override input9=Bad demand limit input11=Unit power restore12=Circuit failed pumpdown13=External Event14 = Bad Current Limit Input15=Option Controller Communication Failed16=Low Refrigerant Charge17=Chiller Network Communication Failure | ||
| Year 309 RW - | |||
Alarm Points for Chiller Models
Table 4 contains the list of Modbus alarm points available from the MicroTech III Chiller Unit Controller depending on the chiller model and corresponding unit controller application software. Application software name is available in the unit HMI: see in Main Menu, "About Chiller".
Table 4. MicroTech III Unit Controller Alarm Points List for Chiller Model
| Alarm Point | ACZC | ACZH | ADZ | ATLAS | AWS | EWWD | MNG | PFS |
| Bad Current Limit Input Warning | X X | X X X | ||||||
| Bad demand limit input Warning X X X X X X X X | ||||||||
| Bad setpoint override input Warning X X X X X X X X X | ||||||||
| Circuit Failed pumpdown Warning X X X X X X X X | ||||||||
| Circuit Fan Warning X | ||||||||
| Circuit INHIBIT LOAD - High Current Problem X X X X X X X X | ||||||||
| Circuit INHIBIT LOAD - High Pressure Problem X X X X X X X X X | ||||||||
| Circuit INHIBIT LOAD - Low Pressure Problem | X | X X X | X | |||||
| Circuit SHUTDOWN - Evap Pressure Sensor Fault | X X | X X X | X X | |||||
| Circuit SHUTDOWN - Low Evap Pressure Fault | X X | X X X | X X | |||||
| Circuit SHUTDOWN - No Pressure at Startup Fault | X X | X X X | X X | |||||
| Circuit SHUTDOWN - No Pressure Change After Start | X X | X X X | X X X | |||||
| Circuit SHUTDOWN - Phase Voltage Protection Fault | X X | X X X | X X | |||||
| CIRCUIT UNLOAD - High Pressure Problem | X | X X X | ||||||
| CIRCUIT UNLOAD - Low Pressure Problem | X | X X X | ||||||
| Comp LOCKOUT - Allowed Re-Starts Exceeded Fault | X X | X X X | X X | |||||
| Comp SHUTDOWN - COM ERROR With VFD Fault | X X | X X X | X X | |||||
| Comp SHUTDOWN - Discharge Temp High Fault | X X | X X X | X X X | |||||
| Comp SHUTDOWN - Discharge Temp Sensor Fault | X X | X X X | X X X | |||||
| Comp SHUTDOWN - Low pressure ratio Fault | X X | X X X | X X X | |||||
| Comp SHUTDOWN - Mechanical High Pressure Fault | X X | X X X | X X X | |||||
| Comp SHUTDOWN - Mechanical Low Pressure Fault | X X | X X X | X X X | |||||
| Comp SHUTDOWN - Motor Protector Fault | X X | X | ||||||
| Comp SHUTDOWN - Motor Temp High Fault | X X | X X X | X X X | |||||
| Comp SHUTDOWN - Motor Temp Sensor Fault | X X | X X X | X X X | |||||
| Comp SHUTDOWN - Oil Delta Pressure High Fault | X X | X X X | X X X | |||||
| Comp SHUTDOWN - Oil Feed Pressure Sensor Fault | X X | X X X | X X X | |||||
| Comp SHUTDOWN - Slide position Sensor Fault | X | X X X | X | |||||
| Comp SHUTDOWN - Starter Fault | X X | X X X | X X X | |||||
| Comp SHUTDOWN - Suction Temp Sensor Fault | X X | X X X | X X X | |||||
| Comp SHUTDOWN - VFD Fault | X X | X X X | X X | |||||
| Comp SHUTDOWN - VFD Over Heat Fault | X X | X X X | X X | |||||
| Comp SHUTDOWN -Current Overload Fault X X X X X X X | ||||||||
| Comp SHUTDOWN-Low Discharge Superheat Fault | X | X X X | X | |||||
| Condenser Ent Water Temp Sensor Fault | X | X | ||||||
| Condenser Leav Water Temp Sensor Fault | X | X | ||||||
| Controller board offline Fault X X X X X X X X | ||||||||
| Evap Ent Water Temp Sensor Fault X X X | ||||||||
| Evap Leav Water Temp Sensor Fault X X X X X X X | ||||||||
| Evap Pump #1 Failure - Pump #2 Start Attempted Problem X X X X X | ||||||||
| Evap Pump #2 Failure - Pump #1 Start Attempted Problem X X X X X | ||||||||
| External event Warning X X X X X X X X | ||||||||
| Option Fan Alarm Controller Communication Failed Warning X | ||||||||
| Option Controller Communication Failed Warning | X | X X X | X | |||||
| RESTART DELAYED - Power Loss While Running Problem X X X X X X X X | ||||||||
| SHUTDOWN - Condenser Pressure High Fault X X X X X X X | ||||||||
| CIRCUIT SHUTDOWN - Condenser Pressure Sensor Fault X X X X X X X | ||||||||
| START INHIBITED - Ambient Temp Low Problem X X X X X X X | ||||||||
| Unit Power Restore Warning | X | X X X | X | |||||
| UNIT SHUTDOWN - Condenser Flow Loss | X | |||||||
| UNIT SHUTDOWN - Condenser High Pressure | X | |||||||
| UNIT SHUTDOWN - Discharge High Temp | X | |||||||
| UNIT SHUTDOWN - Evap Ent Water Temp Sensor Fault | X | X X X | X | |||||
| UNIT SHUTDOWN - Evap Freeze Protection Fault | X X | X X X | X X | |||||
| UNIT SHUTDOWN - Evap Leav Water Temp Low | X X | X X X | X X X | |||||
| UNIT SHUTDOWN - Evap Leav Water Temp Sensor Fault | X X | X X X | X X X | |||||
| UNIT SHUTDOWN - Evap Low Pressure | X | |||||||
| UNIT SHUTDOWN - Evap Pressure Sensor Fault | X | |||||||
| UNIT SHUTDOWN - Evap Water Flow Loss | X X | X X X | X X X | |||||
| UNIT SHUTDOWN - Outside Air Temp Sensor Fault | X X | X X X | X X | |||||
| UNIT SHUTDOWN - Phase Voltage Protection Fault | X X | X X X | X X X | |||||
| UNIT STOP - Emergency Stop Alarm | X X | X X X | X X X | |||||
| UNIT STOP - Evap Water Temps Inverted | X X | X X X | X X X | |||||
| UNIT STOP - External Alarm | X X | X X X | X X X | |||||
| UNIT UNLOAD - High Pressure Problem | X | |||||||
| UNIT UNLOAD - Low Pressure Problem | X | |||||||
| UNIT UNLOAD - Hi Current Problem | X X | X X X | X X | |||||
| UNIT SHUTDOWN - Condenser Pressure Sensor Fault | X |
Comprehensive Alarm Points List
Table 5 contains the complete list of Modbus Alarm points available from the MicroTech III Chiller Unit Controller. Detailed description of all Microtech III Alarms available to the network will be included in next release of this document.
Table 5. MicroTech III Unit Controller Modbus Comprehensive Alarm Point List
| Alarm Point | Holding Register (4xxxx) | R/W Range |
| Bad Current Limit Input Warning 814 R 0=Normal, 1=Alarm | ||
| Bad demand limit input Warning 378 R 0=Normal, 1=Alarm | ||
| Bad setpoint override input Warning 377 R 0=Normal, 1=Alarm | ||
| Circuit #1 Comp #1 - LOCKOUT - Number of Allowed Re-Starts Exceeded Fault 583 R 0=Normal, 1=Alarm | ||
| Circuit #1 Comp #1 - SHUTDOWN - COM ERROR With VFD Fault 774 R 0=Normal, 1=Alarm | ||
| Circuit #1 Comp #1 - SHUTDOWN - Condenser Pressure Sensor Fault 509 R 0=Normal, 1=Alarm | ||
| Circuit #1 Comp #1 - SHUTDOWN - Current Overload Fault 447 R 0=Normal, 1=Alarm | ||
| Circuit #1 Comp #1 - SHUTDOWN - Discharge Temp High Fault 535 R 0=Normal, 1=Alarm | ||
| Circuit #1 Comp #1 - SHUTDOWN - Discharge Temp Sensor Fault 529 R 0=Normal, 1=Alarm | ||
| Circuit #1 Comp #1 - SHUTDOWN - Low pressure ratio Fault 440 R 0=Normal, 1=Alarm | ||
| Circuit #1 Comp #1 - SHUTDOWN - Mechanical High Pressure Fault 601 R 0=Normal, 1=Alarm | ||
| Circuit #1 Comp #1 - SHUTDOWN - Mechanical Low Pressure Fault 717 R 0=Normal, 1=Alarm | ||
| Circuit #1 Comp #1 - SHUTDOWN - Motor Protector Fault | 466 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #1 - SHUTDOWN - Motor Temp High Fault | 478 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #1 - SHUTDOWN - Motor Temp Sensor Fault | 734 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #1 - SHUTDOWN - Oil Delta Pressure High Fault | 637 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault | 643 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault (PFS) | 649 | R 0=Normal, 1=Alarm |
| Circuit #1 Comp #1 - SHUTDOWN - Starter Fault | 662 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #1 - SHUTDOWN - Suction Temp Sensor Fault 698 R 0=Normal, 1=Alarm | ||
| Circuit #1 Comp #1 - SHUTDOWN - VFD Fault | 762 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #1 - SHUTDOWN - VFD Over Heat Fault | 768 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #1 - SHUTDOWN -Slide position Sensor Fault | 756 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #1 - SHUTDOWN-Low Discharge Superheat Fault | 808 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #1 - UNLOAD - Hi Current Problem | 420 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #2 - SHUTDOWN - Discharge Temp High Fault (PFS) | 536 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #2 - SHUTDOWN - Discharge Temp Sensor Fault (PFS) | 530 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #2 - SHUTDOWN - Low Discharge SuperHeat Fault (PFS) | 809 | R 0=Normal, 1=Alarm |
| Circuit #1 Comp #2 - SHUTDOWN - Mechanical High Pressure Fault (PFS) | 602 | R 0=Normal, 1=Alarm |
| Circuit #1 Comp #2 - SHUTDOWN - Mechanical Low Pressure Fault 718 R 0=Normal, 1=Alarm | ||
| Circuit #1 Comp #2 - SHUTDOWN - Motor Protector Fault | 467 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #2 - SHUTDOWN - Motor Temp High Fault (PFS) | 479 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #2 - SHUTDOWN - Motor Temp Sensor Fault | 735 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #2 - SHUTDOWN - Oil Delta Pressure High Fault (PFS) | 638 | R 0=Normal, 1=Alarm |
| Circuit #1 Comp #2 - SHUTDOWN - Oil Feed Pressure Sensor Fault (PFS) | 650 | R 0=Normal, 1=Alarm |
| Circuit #1 Comp #2 - SHUTDOWN - Slide position Sensor Fault | 757 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #2 - SHUTDOWN - Starter Fault (PFS) | 663 R 0=Normal, 1=Alarm | |
| Circuit #1 Comp #2 - SHUTDOWN - Suction Temp Sensor Fault (PFS) | 699 R 0=Normal, 1=Alarm | |
| Circuit #1 Controller board offline Fault | 723 R 0=Normal, 1=Alarm | |
| Circuit #1 Failed pumpdown Warning | 741 R 0=Normal, 1=Alarm | |
| Circuit #1 Option Fan Alarm Warning | 901 R 0=Normal, 1=Alarm |
| Alarm Point | Holding Register (4xxxx) | R/W | Range |
| Circuit #1 INHIBIT LOAD - High Current Problem 780 R 0=Normal, 1=Alarm | |||
| Circuit #1 INHIBIT LOAD - High Pressure Problem 390 R 0=Normal, 1=Alarm | |||
| Circuit #1 INHIBIT LOAD - Low Pressure Problem 411 R 0=Normal, 1=Alarm | |||
| Circuit #1 RESTART DELAYED - Power Loss While Running Problem 384 R 0=Normal, 1=Alarm | |||
| Circuit #1 SHUTDOWN - Condenser Pressure High Fault 517 R 0=Normal, 1=Alarm | |||
| Circuit #1 SHUTDOWN - Evaporator Pressure Sensor Fault 552 R 0=Normal, 1=Alarm | |||
| Circuit #1 SHUTDOWN - Low Evaporator Pressure Fault 545 R 0=Normal, 1=Alarm | |||
| Circuit #1 SHUTDOWN - No Pressure at Startup Fault 711 R 0=Normal, 1=Alarm | |||
| Circuit #1 SHUTDOWN - No Pressure Change After Start 747 R 0=Normal, 1=Alarm | |||
| Circuit #1 SHUTDOWN - Phase Voltage Protection Fault (ACZC, ACZH, ADZ) 817 R 0=Normal, 1=Alarm | |||
| Circuit #1 SHUTDOWN - Phase Voltage Protection Fault (ATLAS, AWS, EWWD, MNG) 751 R 0=Normal, 1=Alarm | |||
| Circuit #1 SHUTDOWN- Motor ProtectorFault 466 R 0=Normal, 1=Alarm | |||
| Circuit #1 UNLOAD - High Pressure Problem | 395 R 0=Normal, 1=Alarm | ||
| Circuit #1 UNLOAD - Low Pressure Problem | 416 R 0=Normal, 1=Alarm | ||
| Circuit #2 Comp #1 - SHUTDOWN - COM ERROR With VFD Fault | 776 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - Condenser Pressure Sensor Fault | 511 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - Discharge Temp High Fault | 537 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - Discharge Temp Sensor Fault | 531 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - Low Discharge SuperHeat Fault | 810 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - Low pressure ratio Fault | 442 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - Mechanical High Pressure Fault | 603 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - Mechanical Low Pressure Fault | 719 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - Motor Temp High Fault | 480 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - Motor Temp Sensor Fault | 736 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - Oil Delta Pressure High Fault | 639 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault | 645 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - Slide position Sensor Fault | 758 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - Starter Fault | 664 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - Suction Temp Sensor Fault | 700 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - VFD Fault | 764 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN - VFD Over Heat Fault | 770 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN -Current Overload Fault | 449 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - SHUTDOWN- Motor Protector Fault | 468 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #1 - UNLOAD - Hi Current Problem | 422 R 0=Normal, 1=Alarm | ||
| Circuit #2 Comp #1 -LOCKOUT - Number of Allowed Re-Starts Exceeded Fault | 585 | R | 0=Normal, 1=Alarm |
| Circuit #2 Comp #2 - SHUTDOWN - Motor Protector Fault | 469 | R | 0=Normal, 1=Alarm |
| Circuit #2 Controller board offline Fault | 724 R 0=Normal, 1=Alarm | ||
| Circuit #2 Failed pumpdown Warning | 742 R 0=Normal, 1=Alarm | ||
| Circuit #2 Option Fan Alarm Warning | 902 R 0=Normal, 1=Alarm | ||
| Circuit #2 INHIBIT LOAD - High Current Problem 782 R 0=Normal, 1=Alarm | |||
| Circuit #2 INHIBIT LOAD - High Pressure Problem | 391 R 0=Normal, 1=Alarm | ||
| Circuit #2 INHIBIT LOAD - Low Pressure Problem 412 R 0=Normal, 1=Alarm | |||
| Circuit #2 RESTART DELAYED - Power Loss While Running Problem 385 R 0=Normal, 1=Alarm | |||
| Circuit #2 SHUTDOWN - Condenser Pressure HighFault 519 R 0=Normal, 1=Alarm | |||
| Circuit #2 SHUTDOWN - Evaporator Pressure Sensor Fault 554 R 0=Normal, 1=Alarm | |||
| Circuit #2 SHUTDOWN - Low Evaporator Pressure Fault 547 R 0=Normal, 1=Alarm | |||
| Circuit #2 SHUTDOWN - No Pressure at Startup Fault 712 R 0=Normal, 1=Alarm | |||
| Circuit #2 SHUTDOWN - No Pressure Change After Start 748 R 0=Normal, 1=Alarm | |||
| Circuit #2 SHUTDOWN - Phase Voltage Protection Fault (ACZC, ACZH, ADZ) 818 R 0=Normal, 1=Alarm | |||
| Circuit #2 SHUTDOWN - Phase Voltage Protection Fault (ATLAS, AWS, EWWD, MNG) 752 R 0=Normal, 1=Alarm | |||
| Circuit #2 UNLOAD - High Pressure Problem 396 R 0=Normal, 1=Alarm | |||
| Circuit #2 UNLOAD - Low Pressure Problem 417 R 0=Normal, 1=Alarm | |||
| Circuit #3 Comp #1 - SHUTDOWN - COM ERROR With VFD Fault 778 R 0=Normal, 1=Alarm | |||
| Circuit #3 Comp #1 - SHUTDOWN - Condenser Pressure High Fault 521 R 0=Normal, 1=Alarm | |||
| Circuit #3 Comp #1 - SHUTDOWN - Condenser Pressure Sensor Fault | 513 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - Current Overload Fault | 451 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - Discharge Temp High Fault | 539 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - Discharge Temp Sensor Fault 533 R 0=Normal, 1=Alarm | |||
| Circuit #3 Comp #1 - SHUTDOWN - Evaporator Pressure Low Fault | 549 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - Evaporator Pressure Sensor Fault | 556 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - Low pressure ratio Fault | 444 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - Mechanical High Pressure Fault | 605 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - Mechanical Low Pressure Fault | 721 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - Motor Temp High Fault | 482 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - Motor Temp Sensor Fault | 738 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - Oil Delta Pressure High Fault | 641 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault 647 R 0=Normal, 1=Alarm | |||
| Circuit #3 Comp #1 - SHUTDOWN - Slide position Sensor Fault | 760 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - Starter Fault | 666 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - Suction Temp Sensor Fault | 702 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - VFD Fault | 766 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN - VFD Over Heat Fault | 772 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - SHUTDOWN-Low Discharge Superheat Fault | 812 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 - UNLOAD - Hi Current Problem | 424 R 0=Normal, 1=Alarm | ||
| Circuit #3 Comp #1 -LOCKOUT - Number of Allowed Re-Starts Exceeded Fault | 587 | R | 0=Normal, 1=Alarm |
| Circuit #3 Controller board offline Fault | 725 R 0=Normal, 1=Alarm | ||
| Circuit #3 Failed pumpdown Warning | 743 R 0=Normal, 1=Alarm | ||
| Circuit #3 INHIBIT LOAD - High Current Problem | 784 R 0=Normal, 1=Alarm | ||
| Circuit #3 INHIBIT LOAD - High Pressure Problem | 392 R 0=Normal, 1=Alarm | ||
| Circuit #3 INHIBIT LOAD - Low Pressure Problem | 413 R 0=Normal, 1=Alarm | ||
| Circuit #3 RESTART DELAYED - Power Loss While Running Problem | 386 R 0=Normal, 1=Alarm | ||
| Circuit #3 SHUTDOWN - No Pressure at Startup Fault 713 R 0=Normal, 1=Alarm | |||
| Circuit #3 SHUTDOWN - No Pressure Change After Start 749 R 0=Normal, 1=Alarm | |||
| Circuit #3 SHUTDOWN - Phase Voltage Protection Fault 753 R 0=Normal, 1=Alarm | |||
| Circuit #3 SHUTDOWN - PVM GFP Fault | 819 R 0=Normal, 1=Alarm | ||
| Circuit #3 UNLOAD - High Pressure Problem 397 R 0=Normal, 1=Alarm | |||
| Circuit #3 UNLOAD - Low Pressure Problem 418 R 0=Normal, 1=Alarm | |||
| Condenser Entering Water Temp Sensor Fault (EWWD) 365 R 0=Normal, 1=Alarm | |||
| Condenser Entering Water Temp Sensor Fault (PFS) 541 R 0=Normal, 1=Alarm | |||
| Condenser Leaving Water Temp Sensor Fault 368 R 0=Normal, 1=Alarm | |||
| Controller board offline Fault 746 R 0=Normal, 1=Alarm | |||
| Evaporator Entering Water Temp Sensor Fault 366 R 0=Normal, 1=Alarm | |||
| Evaporator Leaving Water Temp Sensor Fault 590 R 0=Normal, 1=Alarm | |||
| Evaporator Pump #1 Failure - Pump #2 Start Attempted Problem 430 R 0=Normal, 1=Alarm | |||
| Evaporator Pump #2 Failure - Pump #1 Start Attempted Problem 431 R 0=Normal, 1=Alarm | |||
| External event Warning 745 R 0=Normal, 1=Alarm | |||
| Option Fan Alarm Controller Communication Failed Warning 900 R 0=Normal, 1=Alarm | |||
| Option Controller Communication Failed Warning 815 R 0=Normal, 1=Alarm | |||
| RESTART DELAYED - Power Loss While Running Problem 379 R 0=Normal, 1=Alarm | |||
| START INHIBITED - Ambient Temp Low Problem 388 R 0=Normal, 1=Alarm | |||
| UNIT INHIBIT LOAD - High Pressure Problem 389 R 0=Normal, 1=Alarm | |||
| UNIT INHIBIT LOAD - High Pressure Problem 389 R 0=Normal, 1=Alarm | |||
| UNIT INHIBIT LOAD - Low Pressure Problem | 410 R 0=Normal, 1=Alarm | ||
| UNIT INHIBIT LOAD - Low Pressure Problem | 410 R 0=Normal, 1=Alarm | ||
| Unit Power Restore Warning | 740 R 0=Normal, 1=Alarm | ||
| UNIT RESTART DELAYED - Power Loss While Running Problem | 379 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Condenser Flow Loss | 515 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Condenser High Pressure | 516 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Condenser Pressure Sensor Fault (PFS) | 508 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Evaporator Entering Water Temp Sensor Fault | 755 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Evaporator Freeze Protection Fault | 592 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Evaporator Leaving Water Temp Low (Freeze) | 543 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Evaporator Leaving Water Temp Sensor Fault | 589 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Evaporator Low Pressure | 544 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Evaporator Pressure Sensor Fault | 551 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Evaporator Water Flow Loss 542 R 0=Normal, 1=Alarm | |||
| UNIT SHUTDOWN - Low Pressure Ratio | 441 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Mechanical High Pressure Switch | 602 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Mechanical Low Pressure Switch | 718 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Motor Temp High | 479 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - No Pressure Change After Start (PFS) | 747 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Oil Delta Pressure High | 638 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Outside Air Temp Sensor Fault | 446 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Phase Voltage Protection (ACZC, ACHZ, ADZ) | 816 R 0=Normal, 1=Alarm | ||
| UNIT SHUTDOWN - Phase Voltage Protection (ATLAS, AWS, EWWD, MNG, PFS) | 661 | R | 0=Normal, 1=Alarm |
| UNIT STOP - Emergency Stop Alarm | 798 R 0=Normal, 1=Alarm | ||
| UNIT STOP - Evaporator Water Temps Inverted | 799 R 0=Normal, 1=Alarm | ||
| UNIT STOP - External Alarm | 800 R 0=Normal, 1=Alarm | ||
| UNIT STOP - PVM GFP Fault | 816 R 0=Normal, 1=Alarm |
| Alarm Point | Holding Register (4xxxx) | R/W Range |
| UNIT UNLOAD - High Pressure Problem 394 R 0=Normal, 1=Alarm | ||
| UNIT UNLOAD - Low Pressure Problem 415 R 0=Normal, 1=Alarm |
Appendix A – ASCII Characters Conversion Table
This table lists the ASCII characters and their decimal and hexadecimal numbers. The MicroTech III Chiller Unit Controller does not support the characters in boldface type. Also, non-printing characters, with the exception of the (Space) character, are not listed in this table and are not supported. Characters not supported are translated to a space.
Table 6. ASCII Characters Conversion Table
| Char Decimal Hexadecimal Char Decimal Hexadecimal Char Decimal Hexadecimal | ||||||||
| (Space) 32 0x20 @ 64 0x40 | ` | 96 0x60 | ||||||
| ! | 33 | 0x21 | A | 65 | 0x41 | a | 97 | 0x61 |
| “ | 34 0x22 | B | 66 | 0x42 b | 98 0x62 | |||
| # | 35 0x23 C 67 | 0x43 | c 99 0x63 | |||||
| $ | 36 0x24 | D | 68 | 0x44 d | 100 0x64 | |||
| % | 37 | 0x25 | E | 69 | 0x45 | e | 101 | 0x65 |
| & | 38 | 0x26 | F | 70 | 0x46 | f | 102 | 0x66 |
| ‘ | 39 | 0x27 | G | 71 | 0x47 | g | 103 | 0x67 |
| ( | 40 | 0x28 | H | 72 | 0x48 | h | 104 | 0x68 |
| ) | 41 | 0x29 | I | 73 | 0x49 | l | 105 | 0x69 |
| * | 42 0x2a J 74 0x4a j | 106 0x6a | ||||||
| + | 43 | 0x2b | K | 75 | 0x4b | k | 107 | 0x6b |
| ‘ | 44 | 0x2c | L | 76 | 0x4c | l | 108 | 0x6c |
| - | 45 | 0x2d | M | 77 | 0x4d | m | 109 | 0x6d |
| . | 46 | 0x2e | N | 78 | 0x4e | n | 110 | 0x6e |
| / | 47 | 0x2f | O | 79 | 0x4f | o | 111 | 0x6f |
| 0 | 48 | 0x30 | P | 80 | 0x50 | p | 112 | 0x70 |
| 1 | 49 | 0x31 | Q | 81 | 0x51 | q | 113 | 0x71 |
| 2 | 50 | 0x32 | R | 82 | 0x52 | r | 114 | 0x72 |
| 3 | 51 | 0x33 | S | 83 | 0x53 | s | 115 | 0x73 |
| 4 | 52 | 0x34 | T | 84 | 0x54 | t | 116 | 0x74 |
| 5 | 53 | 0x35 | U | 85 | 0x55 | u | 117 | 0x75 |
| 6 | 54 | 0x36 | V | 86 | 0x56 | v | 118 | 0x76 |
| 7 | 55 | 0x37 | W | 87 | 0x57 | w | 119 | 0x77 |
| 8 | 56 | 0x38 | X | 88 | 0x58 | x | 120 | 0x78 |
| 9 | 57 | 0x39 | Y | 89 | 0x59 | y | 121 | 0x79 |
| : | 58 | 0x3a | Z | 90 | 0x5a | z | 122 | 0x7a |
| ; | 59 | 0x3b | [ | 91 | 0x5b | { | 123 | 0x7b |
| < | 60 | 0x3c | \ | 92 | 0x5c | | | 124 | 0x7c |
| = | 61 | 0x3d | ] | 93 | 0x5d | } | 125 | 0x7d |
| > | 62 | 0x3e | ^ | 94 | 0x5e | ~ | 126 | 0x7e |
| ? | 63 | 0x3f | 95 | 0x5f | ||||
This section summarizes all Data/Alarm Points Registers discussed above in the document and listed by Holding Register address.
Table 7. Overall Registers Table
| Data/Alarm Point | Holding Register (4xxxx) | R/W |
| Chiller Local/Remote 1 R | ||
| Chiller Enable Output 2 R | ||
| Run Enabled 3 R | ||
| Chiller Capacity Limited 4 R | ||
| Alarm Digital Output 5 R | ||
| Evaporator Flow Switch Status 6 R | ||
| Chiller On/Off 8 R | ||
| Chiller Enable Setpoint 9 RW | ||
| Clear Alarms – Network 10 RW | ||
| Chiller Mode Output | 11 | R |
| Active Setpoint | 12 | R |
| Actual Capacity | 13 | R |
| Active Capacity Limit Output | 14 | R |
| Chiller Status (Chiller Run Mode) | 15 | R |
| Evaporator Entering Fluid Temp | 16 | R |
| Evaporator Leaving Fluid Temp | 17 | R |
| Heat Recovery Enable - Network | 18 RW | |
| Condenser Entering Water Temp | 19 | R |
| Condenser Leaving Water Temp | 20 | R |
| Heat Recovery Entering Water Temp | 22 | R |
| Heat Recovery Leaving Water Temp | 23 | R |
| Outdoor Air Temp | 24 | R |
| Chiller Current | 25 | R |
| Chiller Voltage | 26 | R |
| Power Input | 27 | R |
| Warning Alarm Index | 28 | R |
| Problem Alarm Index | 29 | R |
| Fault Alarm Index | 30 | R |
| Warning Alarm Code | 31 | R |
| Problem Alarm Code | 32 | R |
| Fault Alarm Code | 33 | R |
| Chiller Mode Setpoint – Network | 34 RW | |
| Cool Setpoint – Network | 35 RW | |
| Ice Setpoint - Network | 36 RW | |
| Heat Setpoint – Network | 37 RW | |
| Capacity Limit Setpoint - Network | 38 RW | |
| Circuit #1 Condenser Refrigerant Pressure | 39 | R |
| Circuit #1 Condenser Saturated Refrigerant Temp | 40 | R |
| Circuit #1 Evaporator Refrigerant Pressure | 41 | R |
| Circuit #1 Evaporator Saturated Refrigerant Temp | 42 | R |
| Circuit #2 Condenser Refrigerant Pressure | 43 | R |
| Circuit #2 Condenser Saturated Refrigerant Temp | 44 | R |
| Circuit #2 Evaporator Refrigerant Pressure | 45 | R |
| Circuit #2 Evaporator Saturated Refrigerant Temp | 46 | R |
| Circuit #3 Condenser Refrigerant Pressure | 47 RW | |
| Circuit #3 Condenser Saturated Refrigerant Temp | 48 RW | |
| Circuit #3 Evaporator Refrigerant Pressure | 49 RW | |
| Circuit #3 Evaporator Saturated Refrigerant Temp 50 RW | ||
| Circuit #1 Comp #1 - Suction Refrigerant Temp 65 R | ||
| Circuit #1 Comp #1 - Discharge Refrigerant Temp 68 R | ||
| Circuit #1 Comp #1 - Percent RLA 69 R | ||
| Circuit #1 Comp #1 - Current 70 R | ||
| Circuit #1 Comp #1 - Voltage 71 R | ||
| Circuit #1 Comp #1 - Power 72 R | ||
| Circuit #1 Comp #1 - Starts 73 RW | ||
| Circuit #1 Comp #1 - Starts 73 R | ||
| Circuit #1 Comp #1 - Run Hours 74 RW | ||
| Circuit #1 Comp #1 - Run Hours 74 R | ||
| Circuit #1 Comp #2 - Suction Refrigerant Temp 78 R | ||
| Circuit #1 Comp #2 - Discharge Refrigerant Temp 81 R | ||
| Circuit #1 Comp #2 - Starts 86 R | ||
| Circuit #1 Comp #2 - Run Hours 87 R | ||
| Circuit #1 Comp #3 - Starts 99 R | ||
| Circuit #1 Comp #3 - Run Hours 100 RW | ||
| Circuit #2 Comp #1 Suction Refrigerant Temp | 104 | R |
| Circuit #2 Comp #1 - Discharge Refrigerant Temp | 107 | R |
| Circuit #2 Comp #1 - Percent RLA | 108 | R |
| Circuit #2 Comp #1 - Current 109 R | ||
| Circuit #2 Comp #1 Voltage 110 R | ||
| Circuit #2 Comp #1 - Power 111 R | ||
| Circuit #2 Comp #1 - Starts | 112 RW | |
| Circuit #2 Comp #1 - Starts | 112 | R |
| Circuit #2 Comp #1 - Run Hours | 113 RW | |
| Circuit #2 Comp #1 - Run Hours | 113 | R |
| Circuit #2 Comp #2- Starts | 125 RW | |
| Circuit #2 Comp #2- Run Hours 126 RW | ||
| Circuit #2 Comp #3 - Starts | 138 RW | |
| Circuit #2 Comp #3 - Run Hours 139 RW | ||
| Circuit #3 Comp #1 - Suction Refrigerant Temp | 143 | R |
| Circuit #3 Comp #1 - Discharge Refrigerant Temp | 146 | R |
| Circuit #3 Comp #1 - Percent RLA | 147 | R |
| Circuit #3 Comp #1 - Current 148 R | ||
| Circuit #3 Comp #1 - Voltage | 149 | R |
| Circuit #3 Comp #1 - Power 150 R | ||
| Circuit #3 Comp #1 - Starts 151 RW | ||
| Circuit #3 Comp #1 - Starts | 151 | R |
| Circuit #3 Comp #1 - Run Hours | 152 RW | |
| Circuit #3 Comp #1 - Run Hours | 152 | R |
| Condenser Pump Run Hours | 297 | R |
| Condenser Pump Status | 299 | R |
| Evaporator Pump #1 Run Hours 303 RW | ||
| Evaporator Pump #1 Run Hours | 303 | R |
| Evaporator Pump #1 Status 305 R | ||
| Evaporator Pump #2 Run Hours | 306 RW | |
| Evaporator Pump #2 Run Hours | 306 | R |
| Evaporator Pump #2 Status 308 R | ||
| Year | 309 RW | |
| Month | 310 RW | |
| Date | 311 RW | |
| Day of Week | 312 RW | |
| Hour | 313 RW | |
| Minute | 314 RW | |
| Second | 315 RW | |
| Units 316 RW | ||
| Chiller Model 317 R | ||
| Chiller Location[2] 318 RW | ||
| Chiller Location 327 RW | ||
| Application Software Version[1] 334 R | ||
| Application Software Version 338 R | ||
| Condenser Entering Water Temp Sensor Fault (EWWD) 365 R | ||
| Evaporator Entering Water Temp Sensor Fault 366 R | ||
| Condenser Leaving Water Temp Sensor Fault 368 R | ||
| Bad setpoint override input Warning 377 R | ||
| Bad demand limit input Warning 378 R | ||
| RESTART DELAYED - Power Loss While Running Problem 379 R | ||
| UNIT RESTART DELAYED - Power Loss While Running Problem | 379 R | |
| Circuit #1 RESTART DELAYED - Power Loss While Running Problem | 384 R | |
| Circuit #2 RESTART DELAYED - Power Loss While Running Problem | 385 R | |
| Circuit #3 RESTART DELAYED - Power Loss While Running Problem | 386 R | |
| START INHIBITED - Ambient Temp Low Problem | 388 R | |
| UNIT INHIBIT LOAD - High Pressure Problem 389 R | ||
| UNIT INHIBIT LOAD - High Pressure Problem 389 R | ||
| Circuit #1 INHIBIT LOAD - High Pressure Problem | 390 R | |
| Circuit #2 INHIBIT LOAD - High Pressure Problem | 391 R | |
| Circuit #3 INHIBIT LOAD - High Pressure Problem | 392 R | |
| UNIT UNLOAD - High Pressure Problem | 394 R | |
| Circuit #1 UNLOAD - High Pressure Problem | 395 R | |
| Circuit #2 UNLOAD - High Pressure Problem | 396 R | |
| Circuit #3 UNLOAD - High Pressure Problem | 397 R | |
| UNIT INHIBIT LOAD - Low Pressure Problem | 410 R | |
| UNIT INHIBIT LOAD - Low Pressure Problem | 410 R | |
| Circuit #1 INHIBIT LOAD - Low Pressure Problem | 411 R | |
| Circuit #2 INHIBIT LOAD - Low Pressure Problem | 412 R | |
| Circuit #3 INHIBIT LOAD - Low Pressure Problem | 413 R | |
| UNIT UNLOAD - Low Pressure Problem | 415 R | |
| Circuit #1 UNLOAD - Low Pressure Problem | 416 R | |
| Circuit #2 UNLOAD - Low Pressure Problem | 417 R | |
| Circuit #3 UNLOAD - Low Pressure Problem | 418 R | |
| Circuit #1 Comp #1 - UNLOAD - Hi Current Problem | 420 R | |
| Circuit #2 Comp #1 - UNLOAD - Hi Current Problem | 422 R | |
| Circuit #3 Comp #1 - UNLOAD - Hi Current Problem | 424 R | |
| Evaporator Pump #1 Failure - Pump #2 Start Attempted Problem | 430 R | |
| Evaporator Pump #2 Failure - Pump #1 Start Attempted Problem | 431 R | |
| Circuit #1 Comp #1 - SHUTDOWN - Low pressure ratio Fault | 440 R | |
| UNIT SHUTDOWN - Low Pressure Ratio | 441 R | |
| Circuit #2 Comp #1 - SHUTDOWN - Low pressure ratio Fault | 442 R | |
| Circuit #3 Comp #1 - SHUTDOWN - Low pressure ratio Fault | 444 R | |
| UNIT SHUTDOWN - Outside Air Temp Sensor Fault | 446 R | |
| Circuit #1 Comp #1 - SHUTDOWN - Current Overload Fault | 447 R | |
| Circuit #2 Comp #1 - SHUTDOWN -Current Overload Fault | 449 R | |
| Circuit #3 Comp #1 - SHUTDOWN - Current Overload Fault | 451 R | |
| Circuit #1 Comp #1 - SHUTDOWN - Motor Protector Fault | 466 R | |
| Circuit #1 SHUTDOWN- Motor ProtectorFault | 466 R | |
| Circuit #1 Comp #2 - SHUTDOWN - Motor Protector Fault | 467 R | |
| Circuit #2 Comp #1 - SHUTDOWN- Motor Protector Fault | 468 R | |
| Circuit #2 Comp #2 - SHUTDOWN - Motor Protector Fault | 469 R | |
| Circuit #1 Comp #1 - SHUTDOWN - Motor Temp High Fault | 478 R | |
| Circuit #1 Comp #2 - SHUTDOWN - Motor Temp High Fault (PFS) | 479 R | |
| UNIT SHUTDOWN - Motor Temp High | 479 R | |
| Circuit #2 Comp #1 - SHUTDOWN - Motor Temp High Fault 480 R | ||
| Circuit #3 Comp #1 - SHUTDOWN - Motor Temp High Fault 482 R | ||
| UNIT SHUTDOWN - Condenser Pressure Sensor Fault (PFS) 508 R | ||
| Circuit #1 Comp #1 - SHUTDOWN - Condenser Pressure Sensor Fault 509 R | ||
| Circuit #2 Comp #1 - SHUTDOWN - Condenser Pressure Sensor Fault 511 R | ||
| Circuit #3 Comp #1 - SHUTDOWN - Condenser Pressure Sensor Fault 513 R | ||
| UNIT SHUTDOWN - Condenser Flow Loss 515 R | ||
| UNIT SHUTDOWN - Condenser High Pressure 516 R | ||
| Circuit #1 SHUTDOWN - Condenser Pressure High Fault 517 R | ||
| Circuit #2 SHUTDOWN - Condenser Pressure HighFault 519 R | ||
| Circuit #3 Comp #1 - SHUTDOWN - Condenser Pressure High Fault 521 R | ||
| Circuit #1 Comp #1 - SHUTDOWN - Discharge Temp Sensor Fault 529 R | ||
| Circuit #1 Comp #2 - SHUTDOWN - Discharge Temp Sensor Fault (PFS) 530 R | ||
| Circuit #2 Comp #1 - SHUTDOWN - Discharge Temp Sensor Fault 531 R | ||
| Circuit #3 Comp #1 - SHUTDOWN - Discharge Temp Sensor Fault 533 R | ||
| Circuit #1 Comp #1 - SHUTDOWN - Discharge Temp High Fault 535 R | ||
| Circuit #1 Comp #2 - SHUTDOWN - Discharge Temp High Fault (PFS) 536 R | ||
| Circuit #2 Comp #1 - SHUTDOWN - Discharge Temp High Fault 537 R | ||
| Circuit #3 Comp #1 - SHUTDOWN - Discharge Temp High Fault 539 R | ||
| Condenser Entering Water Temp Sensor Fault (PFS) | 541 R | |
| UNIT SHUTDOWN - Evaporator Water Flow Loss | 542 R | |
| UNIT SHUTDOWN - Evaporator Leaving Water Temp Low (Freeze) | 543 R | |
| UNIT SHUTDOWN - Evaporator Low Pressure | 544 R | |
| Circuit #1 SHUTDOWN - Low Evaporator Pressure Fault | 545 R | |
| Circuit #2 SHUTDOWN - Low Evaporator Pressure Fault | 547 R | |
| Circuit #3 Comp #1 - SHUTDOWN - Evaporator Pressure Low Fault | 549 R | |
| UNIT SHUTDOWN - Evaporator Pressure Sensor Fault | 551 R | |
| Circuit #1 SHUTDOWN - Evaporator Pressure Sensor Fault | 552 R | |
| Circuit #2 SHUTDOWN - Evaporator Pressure Sensor Fault | 554 R | |
| Circuit #3 Comp #1 - SHUTDOWN - Evaporator Pressure Sensor Fault 556 R | ||
| Circuit #1 Comp #1 - LOCKOUT - Number of Allowed Re-Starts Exceeded Fault | 583 R | |
| Circuit #2 Comp #1 -LOCKOUT - Number of Allowed Re-Starts Exceeded Fault | 585 R | |
| Circuit #3 Comp #1 -LOCKOUT - Number of Allowed Re-Starts Exceeded Fault | 587 R | |
| UNIT SHUTDOWN - Evaporator Leaving Water Temp Sensor Fault | 589 R | |
| Evaporator Leaving Water Temp Sensor Fault | 590 R | |
| UNIT SHUTDOWN - Evaporator Freeze Protection Fault | 592 R | |
| Circuit #1 Comp #1 - SHUTDOWN - Mechanical High Pressure Fault | 601 R | |
| Circuit #1 Comp #2 - SHUTDOWN - Mechanical High Pressure Fault (PFS) | 602 R | |
| UNIT SHUTDOWN - Mechanical High Pressure Switch | 602 R | |
| Circuit #2 Comp #1 - SHUTDOWN - Mechanical High Pressure Fault | 603 R | |
| Circuit #3 Comp #1 - SHUTDOWN - Mechanical High Pressure Fault | 605 R | |
| Circuit #1 Comp #1 - SHUTDOWN - Oil Delta Pressure High Fault | 637 R | |
| Circuit #1 Comp #2 - SHUTDOWN - Oil Delta Pressure High Fault (PFS) | 638 R | |
| UNIT SHUTDOWN - Oil Delta Pressure High | 638 R | |
| Circuit #2 Comp #1 - SHUTDOWN - Oil Delta Pressure High Fault | 639 R | |
| Circuit #3 Comp #1 - SHUTDOWN - Oil Delta Pressure High Fault | 641 R | |
| Circuit #1 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault | 643 R | |
| Circuit #2 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault 645 R | ||
| Circuit #3 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault 647 R | ||
| Circuit #1 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault (PFS) | 649 R | |
| Circuit #1 Comp #2 - SHUTDOWN - Oil Feed Pressure Sensor Fault (PFS) | 650 R | |
| UNIT SHUTDOWN - Phase Voltage Protection (ATLAS, AWS, EWWD, MNG, PFS) | 661 R | |
| Circuit #1 Comp #1 - SHUTDOWN - Starter Fault | 662 R | |
| Circuit #1 Comp #2 - SHUTDOWN - Starter Fault (PFS) | 663 R | |
| Circuit #2 Comp #1 - SHUTDOWN - Starter Fault | 664 R | |
| Circuit #3 Comp #1 - SHUTDOWN - Starter Fault | 666 R | |
| Circuit #1 Comp #1 - SHUTDOWN - Suction Temp Sensor Fault 698 R | ||
| Circuit #1 Comp #2 - SHUTDOWN - Suction Temp Sensor Fault (PFS) 699 R | ||
| Circuit #2 Comp #1 - SHUTDOWN - Suction Temp Sensor Fault 700 R | ||
| Circuit #3 Comp #1 - SHUTDOWN - Suction Temp Sensor Fault 702 R | ||
| Circuit #1 SHUTDOWN - No Pressure at Startup Fault 711 R | ||
| Circuit #2 SHUTDOWN - No Pressure at Startup Fault 712 R | ||
| Circuit #3 SHUTDOWN - No Pressure at Startup Fault 713 R | ||
| Circuit #1 Comp #1 - SHUTDOWN - Mechanical Low Pressure Fault 717 R | ||
| Circuit #1 Comp #2 - SHUTDOWN - Mechanical Low Pressure Fault 718 R | ||
| UNIT SHUTDOWN - Mechanical Low Pressure Switch 718 R | ||
| Circuit #2 Comp #1 - SHUTDOWN - Mechanical Low Pressure Fault 719 R | ||
| Circuit #3 Comp #1 - SHUTDOWN - Mechanical Low Pressure Fault 721 R | ||
| Circuit #1 Controller board offline Fault 723 R | ||
| Circuit #2 Controller board offline Fault 724 R | ||
| Circuit #3 Controller board offline Fault 725 R | ||
| Circuit #1 Comp #1 - SHUTDOWN - Motor Temp Sensor Fault 734 R | ||
| Circuit #1 Comp #2 - SHUTDOWN - Motor Temp Sensor Fault 735 R | ||
| Circuit #2 Comp #1 - SHUTDOWN - Motor Temp Sensor Fault 736 R | ||
| Circuit #3 Comp #1 - SHUTDOWN - Motor Temp Sensor Fault 738 R | ||
| Unit Power Restore Warning 740 R | ||
| Circuit #1 Failed pumpdown Warning 741 R | ||
| Circuit #2 Failed pumpdown Warning 742 R | ||
| Circuit #3 Failed pumpdown Warning 743 R | ||
| External event Warning 745 R | ||
| Controller board offline Fault 746 R | ||
| Circuit #1 SHUTDOWN - No Pressure Change After Start 747 R | ||
| UNIT SHUTDOWN - No Pressure Change After Start (PFS) 747 R | ||
| Circuit #2 SHUTDOWN - No Pressure Change After Start 748 R | ||
| Circuit #3 SHUTDOWN - No Pressure Change After Start 749 R | ||
| Circuit #1 SHUTDOWN - Phase Voltage Protection Fault (ATLAS, AWS, EWWD, MNG) | 751 R | |
| Circuit #2 SHUTDOWN - Phase Voltage Protection Fault (ATLAS, AWS, EWWD, MNG) | 752 R | |
| Circuit #3 SHUTDOWN - Phase Voltage Protection Fault | 753 R | |
| UNIT SHUTDOWN - Evaporator Entering Water Temp Sensor Fault | 755 R | |
| Circuit #1 Comp #1 - SHUTDOWN -Slide position Sensor Fault | 756 R | |
| Circuit #1 Comp #2 - SHUTDOWN - Slide position Sensor Fault | 757 R | |
| Circuit #2 Comp #1 - SHUTDOWN - Slide position Sensor Fault | 758 R | |
| Circuit #3 Comp #1 - SHUTDOWN - Slide position Sensor Fault | 760 R | |
| Circuit #1 Comp #1 - SHUTDOWN - VFD Fault | 762 R | |
| Circuit #2 Comp #1 - SHUTDOWN - VFD Fault | 764 R | |
| Circuit #3 Comp #1 - SHUTDOWN - VFD Fault | 766 R | |
| Circuit #1 Comp #1 - SHUTDOWN - VFD Over Heat Fault | 768 R | |
| Circuit #2 Comp #1 - SHUTDOWN - VFD Over Heat Fault | 770 R | |
| Circuit #3 Comp #1 - SHUTDOWN - VFD Over Heat Fault | 772 R | |
| Circuit #1 Comp #1 - SHUTDOWN - COM ERROR With VFD Fault | 774 R | |
| Circuit #2 Comp #1 - SHUTDOWN - COM ERROR With VFD Fault | 776 R | |
| Circuit #3 Comp #1 - SHUTDOWN - COM ERROR With VFD Fault | 778 R | |
| Circuit #1 INHIBIT LOAD - High Current Problem | 780 R | |
| Circuit #2 INHIBIT LOAD - High Current Problem | 782 R | |
| Circuit #3 INHIBIT LOAD - High Current Problem | 784 R | |
| UNIT STOP - Emergency Stop Alarm | 798 R | |
| UNIT STOP - Evaporator Water Temps Inverted | 799 R | |
| UNIT STOP - External Alarm | 800 R | |
| Circuit #1 Comp #1 - SHUTDOWN-Low Discharge Superheat Fault | 808 R | |
| Circuit #1 Comp #2 - SHUTDOWN - Low Discharge SuperHeat Fault (PFS) | 809 R | |
| Circuit #2 Comp #1 - SHUTDOWN - Low Discharge SuperHeat Fault | 810 R | |
| Circuit #3 Comp #1 - SHUTDOWN-Low Discharge Superheat Fault | 812 R | |
| Bad Current Limit Input Warning 814 R | ||
| Option Controller Communication Failed Warning 815 R | ||
| UNIT SHUTDOWN – Phase Voltage Protection (ACZC, ACHZ, ADZ) 816 R | ||
| UNIT STOP - PVM GFP Fault 816 R | ||
| Circuit #1 SHUTDOWN – Phase Voltage Protection Fault (ACZC, ACZH, ADZ) 817 R | ||
| Circuit #2 SHUTDOWN – Phase Voltage Protection Fault (ACZC, ACZH, ADZ) 818 R | ||
| Circuit #3 SHUTDOWN - PVM GFP Fault 819 R | ||
| Option Fan Alarm Controller Communication Failed Warning 900 R | ||
| Circuit #1 Option Fan Alarm Warning 901 R | ||
| Circuit #2 Option Fan Alarm Warning 902 R | ||
| Refrigerant Type 1606 R | ||
| Number of Circuits 1607 R | ||
| Number of Comps 1608 R | ||
| Chiller Tons 1609 R | ||
| Circuit #3 Comp #1 - Actual Capacity | 1761 R | |
| Circuit #3 Comp #1 - Off Auto | 1762 R | |
| Circuit #3 Comp #1 - Full Load | 1763 R | |
| Circuit #3 Comp #1 - VFD Output | 1766 | RW |
| Circuit #3 Comp #1 - Oil Feed Pressure | 1770 R | |
| Circuit #3 Comp #1 - Oil Level Status | 1772 R | |
| Circuit #3 Comp #1 - Status | 1773 R | |
| Circuit #2 Comp #3 - Off Auto | 1775 | RW |
| Circuit #2 Comp #3 - Status | 1786 R | |
| Circuit #2 Comp #2 - Off Auto | 1788 | RW |
| Circuit #2 Comp #2 - Status | 1799 R | |
| Circuit #2 Comp #1 - Actual Capacity | 1800 R | |
| Circuit #2 Comp #1 - Off Auto | 1801 | RW |
| Circuit #2 Comp #1 - Full Load | 1802 R | |
| Circuit #2 Comp #1 - VFD Output | 1805 R | |
| Circuit #2 Comp #1 - Oil Feed Pressure | 1809 R | |
| Circuit #2 Comp #1 - Oil Level Status | 1811 R | |
| Circuit #2 Comp #1 - Status | 1812 R | |
| Circuit #1 Comp #3 - Off Auto | 1814 | RW |
| Circuit #1 Comp #3 - Status | 1825 R | |
| Circuit #1 Comp #2 - Actual Capacity | 1826 R | |
| Circuit #1 Comp #2 - Off Auto | 1827 R | |
| Circuit #1 Comp #2 - Full Load | 1828 R | |
| Circuit #1 Comp #2 - Oil Feed Pressure (PFS) | 1832 R | |
| Circuit #1 Comp #2 - Status | 1838 R | |
| Circuit #1 Comp #1 - Actual Capacity | 1840 R | |
| Circuit #1 Comp #1 - Off Auto | 1841 R | |
| Circuit #1 Comp #1 - Full Load | 1842 R | |
| Circuit #1 Comp #1 - VFD Output | 1845 R | |
| Circuit #1 Comp #1 - Oil Feed Pressure (PFS) | 1846 R | |
| Circuit #1 Comp #1 - Oil Feed Pressure | 1849 R | |
| Circuit #1 Comp #1 - Oil Level Status | 1851 R | |
| Circuit #1 Comp #1 - Status | 1852 R | |
| Evaporator SuperHeat Setpoint | 1897 R | |
| Evaporator SuperHeat Temp | 1899 R | |
| Active Energy | 1900 R | |
| Power Factor | 1902 R | |
| Circuit #3 EXV Position | 1950 R | |
| Circuit #3 Outdoor Fan Speed | 1954 | RW |
| Circuit #3 Condenser Approach Temp | 1955 | RW |
| Circuit #3 Evaporator Approach Temp | 1956 | RW |
| Circuit #3 Outdoor Fan Status | 1965 | RW |
| Circuit #2 EXV Position 1966 R | ||
| Circuit #2 Outdoor Fan Speed 1970 R | ||
| Circuit #2 Condenser Approach Temp 1971 R | ||
| Circuit #2 Evaporator Approach Temp 1972 R | ||
| Circuit #2 Outdoor Fan Status 1981 R | ||
| Circuit #1 EXV Position 1982 R | ||
| Liquid Temp 1984 R | ||
| Circuit #1 Outdoor Fan Speed 1986 R | ||
| Circuit #1 Condenser Approach Temp 1987 R | ||
| Circuit #1 Evaporator Approach Temp 1988 R | ||
| Circuit #1 Outdoor Fan Status 1997 R | ||
| Noise Reduction Auto On 1998 RW | ||
| Noise Reduction Status 2000 R |
The present publication is drawn up by of information only and does not constitute an offer binding upon Daikin Applied Europe S.p.A.. Daikin Applied Europe S.p.A. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content, and the products and services presented therein. Specification are subject to change without prior notice. Refer to the data communicated at the time of the order. Daikin Applied Europe S.p.A. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Applied Europe S.p.A..