Notice DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - page 4
View the manual : Français FR English EN
Pick your language and provide your email: we'll send you a specifically translated version.
Product typeMulti-split air conditioner
BrandDAIKIN
Models3MXM40N, 3MXM52N, 3MXM68N, 3MXS40K, 3MXS52E, 3MXS68G
RefrigerantR32
Power supply230 V ~ 50 Hz
Cooling capacity (min-max)2.5 - 6.8 kW
Heating capacity (min-max)3.0 - 7.7 kW
Number of connectable indoor unitsUp to 4
Outdoor unit dimensions (W x H x D)770 x 550 x 320 mm (approx.)
Outdoor unit weight40 - 55 kg depending on model
Main functionsCooling, heating, dehumidification, ventilation
FilterWashable air filter
Noise level (outdoor unit)48 - 52 dB(A)
Operating temperature rangeCooling: -10 °C to 46 °C; Heating: -15 °C to 18 °C
Energy efficiency class (cooling)A++ to A+
SEER / SCOPUp to 6.5 / 4.5
Remote controlInfrared wireless
Smart / programming function24-hour timer, auto shut-off
Maintenance and cleaningClean filters every 2 weeks; call a professional for annual maintenance
SafetyPower failure protection, refrigerant leak detection, safety shutdown in case of overheating
Spare parts and repairabilityParts available at DAIKIN authorized centers; repairability index above 8/10
Warranty2 years parts and labor (excluding installation conditions)
General informationUser and installation manual provided; compatible with Daikin Multi system

Frequently Asked Questions - 3MXM40N - 3MXM52N - 3MXM68N - 3MXS40K - 3MXS52E - 3MXS68G DAIKIN

What refrigerant is used in these models?
These multi-split air conditioners use the refrigerant R32, which is more environmentally friendly than older fluids.
How many indoor units can be connected?
These outdoor units allow connecting up to 4 indoor units depending on room needs.
How to clean the filters of the indoor unit?
Remove the filter by gently pulling it, wash it with warm water and a mild detergent, then dry it before putting it back. Repeat every 2 weeks.
What to do if the air conditioner does not turn on?
First check that the power supply is connected and the circuit breaker has not tripped. Make sure the remote control has valid batteries and point it at the unit. If the problem persists, contact a Daikin authorized technician.
What is the minimum operating temperature in heating mode?
Heating mode operates down to -15 °C outdoors. Below that, performance may be reduced.
How to reset the remote control?
Remove the batteries, wait 30 seconds, then put them back. Press the RESET button with a small screwdriver if necessary.
Can I install the outdoor unit myself?
Installation must be carried out by a qualified professional to ensure electrical and refrigeration compliance, as well as safety.
What does a flashing indicator light on the indoor unit mean?
Flashing codes are described in the manual. Generally, this indicates a sensor fault or a communication problem. Note the number of flashes and consult the troubleshooting section.
Is it normal for the outdoor unit to produce water or steam?
Yes, in heating mode, the outdoor unit may produce condensation or steam in cold weather. This is normal and does not indicate a malfunction.
Where to find the serial number of my unit?
The serial number is on a label on the side of the outdoor unit and on the front of the indoor unit (remove the grille to access).

User questions about 3MXM40N - 3MXM52N - 3MXM68N - 3MXS40K - 3MXS52E - 3MXS68G DAIKIN

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Multi-split air conditioner in PDF format for free! Find your manual 3MXM40N - 3MXM52N - 3MXM68N - 3MXS40K - 3MXS52E - 3MXS68G - DAIKIN and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. 3MXM40N - 3MXM52N - 3MXM68N - 3MXS40K - 3MXS52E - 3MXS68G by DAIKIN.

USER MANUAL 3MXM40N - 3MXM52N - 3MXM68N - 3MXS40K - 3MXS52E - 3MXS68G DAIKIN

Daikin Industries Czech Republic s.r.o.

3MXM40M2V1B, 3MXM52M2V1B, 3AMXM52M2V1B,

01** DIC2# is authorised to compile the Technical Construction File.07*** H DIC2# (e) viva e olivação do com a coprêne posito do olenho de compreis em 1985.13*** DIC2# on vivalutéu tain a mea a mea teleté do mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei meia mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei meii mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei mei meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meo meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meor meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meei meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meai meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoil meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meOI meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoa meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meovi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meori meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meosi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoci meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoui meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoi meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymeia meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoymei meoyme i Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoyme i Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei Meoymei MEO OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI OIOI 01 02*** DIC2# #hat die Berechtiguihe Diachicntionale Suazenmazienl.08* delirio ne l algevado in beo dolo;09* odo fio, 1000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000001 Directives, as amended.10* kato o dozao u o o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozAO CORTICATO DE ACGONDA EOCNOSOLARIAI11* Direkiv, med forstejng andrag.12* kato o dozao u o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o doz AO CORTICATO DE ACGONDA EOCNOSOLARIAI13* kato o dozao u o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o DOI ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLOGIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO ONGOLODIO 01 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.13*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.14* kato o dozao u o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o daitejng or ndar.15*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.16* kato o dozao u o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j odoceit.17* Spengy## yomogi naadaycnpchymo nongmnyo houy##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n###y##n### 18* kato o dozao u o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.18* kato o dozao u o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao oj 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.19* kato o dozao u o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o didra###y#### y## ### ## ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### 18* kato o dozao u o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.19* kato o dozao u o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao or 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.18* kato o dozao u o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao o j o dozao or 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.19* kato o dozao u o dozao o j o dozao o j o dozao o j o dozao or 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.18* kato o dozao u o dozao o j o dozao o j o dozao or 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.19* kato o dozao u o dozao o j o dozao o j o dozao or 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.19* kato o dozao u o dozao o j o dozao or 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.19* kato o dozao u o dozao or 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.19* kato o dozao u o dozao or 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.19* kato or 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.19* kato or 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.19* kato or 02*** DIC2# #hat die Bereeltiguiw chehichingie nolstcakse zusamniznustl.19* kato or 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.19* kato or 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakSE ZIOYON 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.19* kato or 02*** DIC2# #hat die Berechtiguiw chehichingie nolstcakse zusamniznustl.19* kato or 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse zusamniznustl.19* kato or 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse zusamniznustl.19* kato or 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DICZ 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC3 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC1 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC5 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC4 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC6 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC7 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC9 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC8 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC# 2#hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die Berechtimguiw chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die BerechtimguiW chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die BerechtimguiW chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die BerechtimguiW chehichingie nolstcakse ZIOYON 02*** DIC2# #hat die BerechtimguiW chehichingie nOLSTCAKSE ZIOYON 02*** DIC2# #hat die BerechtimguiW chehichingie nOLSTCAKSE ZIOYON 02*** DIC2# #hat die BerechtimguiW chehichingie nOLSTCAKSE ZIOYON 02*** DIC2# #hat die BerechtimguiW chehichingie nOLSTCAKSE ZIOYON 03*** DIC2# #hat die BerechtimguiW chehichingie nOLSTCAKSE ZIOYON 03*** DIC2# #hat die BerechtimguiW chehichingie nOLSTCAKSE ZIOYON 03*** DIC2# #hat die BerechtimguiW chehichingie nOLSTCAKSE ZIOYON 03*** DIC2# #Hat da rote s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat dore s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat derocn 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s sncs 03*** DIC2# #hat da roce s sncs 03*** DIC2# #hat da roce s sncs 03*** DIC2# #hat da roce s sncs 03*** DIC2# #hat da roce s sncs 03*** DIC2# #hat da roce s sncs 03*** DIC2# #hat da roze sncs 03*** DIC2# #hat da roce s sncs 03*** DIC2# #hat da roce s sncs 03*** DIC2# #hat da roce s sncs 03*** DIC2# #hat da roce s sncs 03*** DIC2# #hat da roce s sncs 03*** DIC2# #hat da rrcn 03*** DIC2# #hat da rrcn 03*** DIC2# #hat da rrcn 03*** DIC2# #hat da rrcn 03*** DIC2# #hat da rrcn 03*** DIC2# #hat da rrcn 03*** DIC2# #hat da rrcn 03*** DIC2# #hat da rrcn -13*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da rccn 03*** DIC2# #hat da rccn 03*** DIC2# #hat da rccn 03*** DIC2# #hat da rccn 03*** DIC2# #hat da rccn 03*** DIC2# #hat da rccn 03*** DIC2# #hat da rccn 03*** DIC2# #hat da rccn -13*** DIC2# #hat da roce s rncs 03*** DIC2# #hat da rccn 03*** DIC2# #hat da rccn 03*** DIC2# #hat da rccn 03*** DIC2# #hat da rccn 03*** DIC2# #hat da rccn 03*** DIC2# #hat da rccn
01• Maximum allowable pressure (PS) (bar) • Minimum maximum absolute pressure (TS) • Tmin: Minimum temperature of low pressure side: (℃) (T) • Tmax: Saturated temperature corresponding with the maximum absolute pressure (PS) (℃) (T) • Refrigerant (℃) • Setting of pressure safety device: (bar) • Manufacturing number and manufacturing year: refer to model number(s) (T) • Maxima maxima duty (PS) (bar) • Temporise minimum maximum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimumuty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty (TS) • Temporise minimum duty(PS) (℃) (T) • Refrigerant (℃) • Setting of pressure Schutzverbindung: (bar) (T) • Temperature minimum temperature of the uppermost layer of the duct (TS) • Temporise minimum temperature of the uppermost layer of the duct (Tmax: Temporise minimum in el aldo de bajo preso: (℃) (T) • Temporise minimum temperature of the uppermost layer of the duct (TS) • Temporise minimum temperature of the uppermost layer of the duct (Tmax: Temporise minimum temperature of the uppermost layer of the duct (Tmax: Temporise minimum temperature of the uppermost layer of the duct (Tmax: Temporise minimum temperature of the uppermost layer of the duct (Tmax: Temporise minimum temperature of the uppermost layer of the duct (Tmax: Temporise minimum temperature of the uppermost layer of the duct (Tmax: Temporise minimum temperature of the uppermost layer of the duct Tausend: aus dem befristetigungs- und der qualifizierungskomponente zu gewährt werden. Nenere zu fabrikation und arbeiten zu fabrikation corneale in das präsen de espocifacienzische teseile del model.02• Pressure maxima permissible (PS) (bar) • Minimal maximum absolute pressure (TS) • Tmin: Minimum temperature of low pressure side: (℃) (T) • Tmax: Saturated temperature corresponding with the maximum absolute pressure (PS) (℃) (T) • Refrigerant (℃) • Setting of pressure safety device: (bar) • Manufacturing number and manufacturing year: refer to model number(s) (T) • Maxima maxima duty (PS) (bar) • Temporise minimum maximum duty (TS) (T) • Temporise minimum maximum duty (TS) • Temporise minimum maximum duty (TS) • Temporise minimum maximum duty (TS) • Temporise minimum maximum duty (TS) • Temporise minimum maximum duty (TS) • Temporise minimum maximum duty (TS) • Temporise minimum maximum duty (TS) • Temporise minimum maximum duty (TS) • Temporise minimum maximum duty (TS) • Temporise minimum maximum duty (TS) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) Tausend: aus dem befristetigungs- und der qualifizierungskomponente zu gewährt werden. Nenere zu fabrikation und arbeiten zu fabrikation corneale in das präsen de espocifacienzische teseile del model.03• Pressure maxima permissible (PS) (bar) • Minimal maximum absolute pressure (TS) • Tmin: Minimum temperature of low pressure side: (℃) (T) • Tmax: Saturated temperature corresponding with the maximum absolute pressure (PS) (℃) (T) • Refrigerant (℃) • Setting of pressure safety device: (bar) • Manufacturing number and manufacturing year: refer to model number(s) (T) • Maxima maxima duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty(3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3 ℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃)04• Pressure maxima permissible (PS) (bar) • Minimal maximum absolute pressure (TS) • Tmin: Minimum temperature of low pressure side: (℃) (T) • Tmax: Saturated temperature corresponding with the maximum absolute pressure (PS) (℃) (T) • Refrigerant (℃) • Setting of pressure safety device: (bar) • Manufacturing number and manufacturing year: refer to model number(s) (T) • Maxima maxima duty (5℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃)05• Pressure maxima permissible (PS) (bar) • Minimal maximum absolute pressure (TS) • Tmin: Minimum temperature of low pressure side: (℃) (T) • Tmax: Saturated temperature corresponding with the maximum absolute pressure (PS) (℃) (T) • Refrigerant (℃) • Setting of pressure safety device: (bar) • Manufacturing number and manufacturing year: refer to model number(s) (T) • Maxima maxima duty (6℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) Tausend: aus dem befristetigungs- und der qualifizierungskomponente zu gewährt werden. Nenere zu fabrikation und arbeiten zu fabrikation corneale in das präsen de espocifacienzische teseile del model.06• Pressure maxima permissible (PS) (bar) • Minimal maximum absolute pressure (TS) • Tmin: Minimum temperature of low pressure side: (℃) (T) • Tmax: Saturated temperature corresponding with the maximum absolute pressure (PS) (℃) (T) • Refrigerant (℃) • Setting of pressure safety device: (bar) • Manufacturing number and manufacturing year: refer to model number(s) (T) • Maxima maxima duty (7℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • TemporISE minimum maximum duty (3℃) • TempORIS minimum maximum duty (3℃) • TempORIS minimum maximum duty (3℃) • TempORIS minimum maximum duty (3℃) • TempORIS minimum maximum duty (3℃) • TempORIS minimum maximum duty (3℃) • TempORIS minimum maximum duty (3℃) • TempORIS minimum maximum duty (3℃) • TempORIS minimum maximum duty (3℃) • TempORIS minimum maximum duty (3℃) • TempORIS minimall maximum duty (3℃) • TempORIS minimall maximum duty (3℃) • TempORIS minimall maximum duty (3℃) • TempORIS minimall maximum duty (3℃) • TempORIS minimall maximum duty (3℃) • TempORIS minimall maximum duty (3℃) • TempORIS minimall maximum duty (3℃) • TempORIS minimall maximum duty (3℃) • TempORIS minimall maximum duty (2℃) (T) • Temporise minimum maximum permissible (PS) (℃) (T) • Temporise minimum maximum permissible (PS) (℃) (T) • Temporise minimum maximum permissible (PS) (℃) (T) • TempORIS minimum maximum permissible (PS) (℃) (T) • TempORIS minimum maximum permissible (PS) (℃) (T) • TempORIS minimum maximum permissible (PS) (℃) (T) • TempORIS minimum maximum permissible (PS) (℃) (T) • TempORIS minimum maximum permissible (PS) (℃) (T) • TempORIS minimum maximum permissible (PS) (℃) (T) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der qualifizierungskomponente zu gewährt werden. Nenere zu fabrikation und arbeiten zu fabrikation corneale in das präsen de espocifacienzische teseile del model.07• Pressure maxima permissible (PS) (bar) • Minimal maximum absolute pressure (TS) • Tmin: Minimum temperature of low pressure side: (℃) (T) • Tmax: Saturated temperature corresponding with the maximum absolute pressure (PS) (℃) (T) • Refrigerant (℃) • Setting of pressure safety device: (bar) • Manufacturing number and manufacturing year: refer to model number(s) (T) • Maxima maxima duty (8℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • TempORIS minimum maximum permissible (PS) (℃) (T) • TempORIS minimum maximum permissible (PS) (℃) (T) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der qualifizierungskomponente zu gewährt werden. Nenere zu fabrikation und arbeiten zu fabrikation corneale in das präsen de espocifacienze schutzverbindung: (bar) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) • Temporise minimum maximum duty (3℃) • TempORIS minimum maximum permissible (PS) (℃) (T) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der qualifizierungskomponente zu gewährt werden. Nenere zu fabrikation und arbeiten zu fabrikation corneale in das präsen de espocifacienze schutzverbindung: (bar) • Temporise minimum maximum-duty: (℃) (T) • Temporise minimum maximum duty (3℃) (T) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der qualifizierungskomponente zu gewährt werden. Nenere zu fabrikation und arbeiten zu fabrikation corneale in das präsen de espocifacienze schutzverbindung: (bar) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der qualifizierungskomponente zu gewährt werden. Nenere zu fabrikation und arbeiten zu fabrikation corneale in das präsen de espocifacienze schutzverbindung: (bar) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und dazai: (℃) (T) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und dazai: (℃) (T) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und dazai: (℃) (T) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und dazai: (℃) (T) • TempORGILONATE INTERNATIONAL JAN OLIGELS LIGERLAN 1, 30 1900 VILVOORDE, BELGIUM08• Pressure maxima permissible (PS) (bar) • Minimal maximum absolute pressure (TS) • Tmin: Minimum temperature of low pressure side: (℃) (T) • Tmax: Saturated temperature corresponding with the maximum absolute pressure (PS) (℃) (T) • Refrigerant (℃) • Setting of pressure safety device: (bar) • Manufacturing number and manufacturing year: refer to model number(s) (T) • Maxima maxima duty (9℃) (T) • Temporise minimum maximum duty (3℃) (T) • Temporise minimum maximum duty (3℃) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der qualifizierungskomponente zu gewährt werden. Nenere zu fabrikation und arbeiten zu fabrikation corneale in das präsen de espocifacienze schutzverbindung: (bar) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und da zai: (℃) (T) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und da zai: (℃) (T) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und da zai: (℃) (T) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und da zai: (℃) (T) • TempORGILONATE INTERNATIONAL JAN OLIGELS LIGERLAN 1, 30 1900 VILVOORDE, BELGIUM09• Pressure maxima permissible (PS) (bar) • Minimal maximum absolute pressure (TS) • Tmin: Minimum temperature of low pressure side: (℃) (T) • Tmax: Saturated temperature corresponding with the maximum absolute pressure (PS) (℃) (T) • Refrigerant (℃) • Setting of pressure safety device: (bar) • Manufacturing number and manufacturing year: refer to model number(s) (T) • Maxima maxima duty: (3℃) (T) • Temporise minimum maximum duty (3℃) (T) • TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der qualifizierungskomponente zu gewährt werden. Nenere zu fabrikation und arbeiten zu fabrikation corneale in das präsen de espocifacienze schutzverbindung: (bar) • TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- und der qualifizierungskomponente zu gewährt werden. Nenere zu fabrikation und arbeiten zu fabrikation corneale in das präsen de espocifacienze schutzverbindung: (bar) • TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- und der quali: (3℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- und der quali: (3℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- und der quali: (3℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristETe: (3℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristETe: (3℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristETe: (3℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristETe: (3 ℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristETe: (3 ℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristETe: (3 ℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristETe: (3 ℃ ) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristETe: (3 ℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristETe: (3 ℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristETe: (3 ℃)07• Pressure maxima permissible (PS) (bar) • Minimal maximum absolute pressure (TS) • Tmin: Minimum temperature of low pressure side: (℃) (T) • Tmax: Saturated temperature corresponding with the maximum absolute pressure (PS) (℃) (T) • Refrigerant (℃) • Setting of pressure safety device: (bar) • Manufacturing number and manufacturing year: refer to model number(s) (T) • Maxima maxims yu fabrikation und arbeiten zu fabrikation corneale in das präsen de espocifacienze schutzverbindung: (bar) • TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- und der quali: (3℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- and der quali: (3℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- und der quali: (3 ℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- and der quali: (3 ℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- and der quali: (3 ℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- and der quali: (3 ℃) (T) • TempORIS minamalegul are and der quali: (3 ℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- and der quali: (3 ℃) (T) • TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- and der quali: (3 ℃) (T) • TempORIS minamalegULAREMICAL JAN OLIGELS LIGERLAN 1, 30 1900 VILVOORDE, BELGIUM08• Pressure maxima permissible (PS) (bar) • Minimal maximum absolute pressure (TS) • Tmin: Minimum temperature of low pressure side: (℃) (T) • Tmax: Saturated temperature corresponding with the maximum absolute pressure (PS) (℃) (T) • Refrigerant (℃) - Setting of pressure safety device: (bar) - Manufacturing number and manufacturing year: refer to model number(s) (T) - Maxima maxima duty: (3℃) (T) - Temporise minimum maximum duty (3℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der quali: (3 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der quali: (3 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der quali: (3 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der quali: (2 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der quali: (2 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der quali: (2 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der quali : (2 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der quali : (2 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der quali : (2 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der specifizierung des spezifizierenden Prozess (Tausend: aus dem befristetigungs- und der quali: (3 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der quali : (3 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der quali : (3 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der quali : (3 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der specifizierung des spezifizierenden Prozess (Tausend: aus dem befristetigungs- und der quali : (3 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der quali : (3 ℃) (T) - TempORIS minimum maximum permissible (Tausend: aus dem befristetigungs- und der quali : (3 ℃) (T) - TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- und der quali : (3 ℃) (T) - TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- und der quali : (3 ℃) (T) - TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- und der quali : (2 ℃) (T) - TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- und der quali : (2 ℃) (T) - TempORIS minamalegularey permissible (Tausend: aus dem befristetigungs- und der quali : (2 ℃) (T) - TempORIS minamalegularey permissible (TausEND: aus dem befristetigungs- und der quali : (2 ℃) (T) - TempORIS minamalegularey permissible (TausEND: aus dem befristetigungs- und der quali : (2 ℃) (T) - TempORIS minamalegularey permissible (TausEND: aus dem befristetigungs- und der quali : (2 ℃) (

Safety Precautions

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Safety Precautions - 1

Read the precautions in this manual carefully before operating the unit.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Safety Precautions - 2

This appliance is filled with R32.

  • The precautions described herein are classified as WARNING and CAUTION. They both contain important information regarding safety. Be sure to observe all precautions without fail.
  • Meaning of WARNING and CAUTION notices

WARNING .... Failure to follow these instructions properly may result in personal injury or loss of life.

CAUTION ....... Failure to observe these instructions properly may result in property damage or personal injury, which may be serious depending on the circumstances.

  • The safety marks shown in this manual have the following meanings:
Be sure to follow the instructions.Be sure to establish an earth connection.Never attempt.
  • After completing installation, conduct a trial operation to check for faults and explain to the customer how to operate the air conditioner and take care of it with the aid of the operation manual.
  • The original instructions are written in English. All other languages are translations of the original instructions.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Safety Precautions - 3

WARNING

  • Ask your dealer or qualified personnel to carry out installation work. Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage, electric shocks or fire.
  • Install the air conditioner in accordance with the instructions in this installation manual. Improper installation may result in water leakage, electric shocks or fire.
  • Be sure to use only the specified accessories and parts for installation work. Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.
  • Install the air conditioner on a foundation strong enough to withstand the weight of the unit. A foundation of insufficient strength may result in the equipment falling and causing injury.
  • Electrical work must be performed in accordance with relevant local and national regulations and with instructions in this installation manual. Be sure to use a dedicated power supply circuit only. Insufficiency of power circuit capacity and improper workmanship may result in electric shocks or fire.
  • Use a cable of suitable length. Do not use tapped wires or an extension lead, as this may cause overheating, electric shocks or fire.
    Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal connections or wires. Improper connections or securing of wires may result in abnormal heat build-up or fire.
  • When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires so that the control box lid can be securely fastened. Improper positioning of the control box lid may result in electric shocks, fire or over heating terminals.
  • If refrigerant gas leaks during installation, ventilate the area immediately. Toxic gas may be produced if the refrigerant comes into contact with fire.
    After completing installation, check for refrigerant gas leakage. Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
  • When installing or relocating the air conditioner, be sure to bleed the refrigerant circuit to ensure it is free of air, and use only the specified refrigerant (R32). The presence of air or other foreign matter in the refrigerant circuit causes abnormal pressure rise, which may result in equipment damage and even injury.
  • During installation, attach the refrigerant piping securely before running the compressor. If the refrigerant pipes are not attached and the stop valve is open when the compressor is run, air will be sucked in, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.
  • During pump-down, stop the compressor before removing the refrigerant piping. If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.
  • Be sure to earth the air conditioner. Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect earthing may result in electric shocks.
  • Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in electric shocks or fire.
  • Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
  • The appliance must be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater).
  • Do not pierce or burn.

  • Be aware that refrigerants may not contain an odour.

  • This appliance must be installed, operated and stored in a room larger than the minimum required floor area.
  • Comply with national gas regulations.

Safety Precautions

CAUTION
·Do not install the air conditioner at any place where there is a danger of flammable gas leakage. In the event of a gas leakage, build-up of gas near the air conditioner may cause a fire to break out.
·While following the instructions in this installation manual, install drain piping to ensure proper drainage and insulate piping to prevent condensation. Improper drain piping may result in indoor water leakage and property damage.
·Tighten the flare nut according to the specified method such as with a torque wrench. If the flare nut is too tight, it may crack after prolonged use, causing refrigerant leakage.
·Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals. Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
·The temperature of refrigerant circuit will be high, please keep the inter-unit wire away from copper pipes that are not thermally insulated.
·This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial and household use by lay persons.
·Sound pressure level is less than 70 dB(A).
·The following information shall be provided at an accessible place of the system: -instructions for shutting down the system in case of an emergency -name and address of fire department, police and hospital -name, address and day & night telephone numbers for obtaining service. In Europe, EN378 provides the necessary guidance for this logbook.

Accessories

Accessories supplied with the outdoor unit:

A Installation Manual + R32 Manual1B Drain plug It is on the bottom of the packing case.1
C Reducer assembly It is on the bottom of the packing case.1
E Refrigerant charge label Contains fluorinated greenhouse gases covered by the Kyoto Protocol R32 ①= kg ②= kg ①+②= kg1D Screw bag (For fixing electrical wire anchor bands) It is on the bottom of the packing case.1
F Multilingual fluorinated greenhouse gases label It is on the bottom of the packing case.1G Drain cap (1)6H Drain cap (2)3

Precautions for Selecting the Location

1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
2) Choose a location where the hot air discharged from the unit or the operation noise will not cause a nuisance to the neighbours of the user.
3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4) There must be sufficient spaces for carrying the unit into and out of the site.
5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6) The site must be free from the possibility of flammable gas leakage in a nearby place.
7) Install units, power cords and inter-unit wire at least 3m away from television and radio sets. This is to prevent interference to images and sounds. (Noises may be heard even if they are more than 3m away depending on radio wave conditions.)
8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air conditioner.
9) Since water will flow from the drain of the outdoor unit, do not place under the unit anything which must be kept away from moisture.

NOTE

Cannot be installed hanging from ceiling or stacked.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - NOTE - 1

CAUTION

When operating the air conditioner in a low outdoor ambient temperature, be sure to follow the instructions described below.

  • To prevent exposure to wind, install the outdoor unit with its suction side facing the wall.
  • Never install the outdoor unit at a site where the suction side may be exposed directly to wind.
  • To prevent exposure to wind, it is recommended to install a baffle plate on the air discharge side of the outdoor unit.
  • In heavy snowfall areas, select an installation site where the snow will not affect the unit.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - CAUTION - 1

Indoor/Outdoor Unit Installation Drawings

For installation of the indoor units, refer to the installation manual which was provided with the units.

(The diagram shows a wall-mounted indoor unit.)

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Indoor/Outdoor Unit Installation Drawings - 1

CAUTION

  • Do not connect the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the indoor unit in order to add another indoor unit later.
    Make sure no dirt or moisture gets into either side of the embedded branch piping.
    See "7 Refrigerant piping work" on page 9 for details.
  • It is impossible to connect the indoor unit for one room only. Be sure to connect at least 2 rooms.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - CAUTION - 1

Installation

Install the unit horizontally.
- The unit may be installed directly on a concrete verandah or a solid place if drainage is good.
- If the vibration may possibly be transmitted to the building, use a vibration-proof rubber (field supply).

1. Connections (connection port)

Install the indoor unit according to the table below, which shows the relationship between the class of indoor unit and the corresponding port.

The total indoor unit class that can be connected to this unit:

Heat pump type:

3MXM40M* - Up to 7.0kW

4MXM68M* - Up to 11.0kW

3MXM52M* - Up to 9.0kW

4MXM80M* - Up to 14.0kW

3AMXM52M* - Up to 9.0kW

5MXM90M* - Up to 15.5kW

3MXM68M* - Up to 11.0kW

Port3MXM40M*3MXM52M*3AMXM52M*
A15, 20, 25, 3515, 20, 25, 35, 42
B# 15, 20, 25, 35# 15, 20, 25, 35, 42, 50
C# 15, 20, 25, 35# 15, 20, 25, 35, 42, 50
Port3MXM68M*4MXM68M*
A15, 20, 25, 35, 4215, 20, 25, 35, 42
B# 15, 20, 25, 35, 42, 50, 6015, 20, 25, 35, 42
C# 15, 20, 25, 35, 42, 50, 60# 15, 20, 25, 35, 42, 50, 60
D# 15, 20, 25, 35, 42, 50, 60
Port4MXM80M*5MXM90M*
A15, 20, 25, 35, 4215, 20, 25, 35, 42
B# 15, 20, 25, 35, 42, 50, 6015, 20, 25, 35, 42
c# 15, 20, 25, 35, 42, 50, 60, 71# 15, 20, 25, 35, 42, 50, 60
D# 15, 20, 25, 35, 42, 50, 60, 71# 15, 20, 25, 35, 42, 50, 60, 71
E# 15, 20, 25, 35, 42, 50, 60, 71

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Connections (connection port) - 1

: Use a reducer to connect pipes.
:Use No.2 and 4 reducers.
: Use No. 5 and 6 reducers.
□ : Use No. 1 and 3 reducers.

Refer to "How to Use Reducers" on page 10 for information on reducer numbers and their shapes.

Precautions on Installation

  • Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed.
  • In accordance with the foundation drawing in fix the unit securely by means of the foundation bolts. (Prepare 4 sets of M8 or M10 foundation bolts, nuts and washers each which are available on the market.)
  • It is best to screw in the foundation bolts until their ends are 20mm from the foundation surface.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Precautions on Installation - 1

Outdoor Unit Installation Guideline

  • Where a wall or other obstacle is in the path of outdoor unit's inlet or outlet airflow, follow the installation guidelines below.
  • For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Outdoor Unit Installation Guideline - 1
Wall facing one side
Side view

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Outdoor Unit Installation Guideline - 2
Walls facing two sides

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Outdoor Unit Installation Guideline - 3
Top view

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Outdoor Unit Installation Guideline - 4
Walls facing three sides
More than 50
Top view
unit: mm

Selecting a Location for Installation of the Indoor Units

  • The maximum allowable length of refrigerant piping, and the maximum allowable height difference between the outdoor and indoor units, are listed below. (The shorter the refrigerant piping, the better the performance. Connect so that the piping is as short as possible. Shortest allowable length per room is 3m.)
Outdoor unit capacity class3MXM40M*3MXM52M* 3AMXM52M*3MXM68M*4MXM68M*4MXM80M*5MXM90M*
Piping to each indoor unit25m max.25m max.25m max.25m max.25m max.25m max.
Total length of piping between all units50m max.50m max.50m max.60m max.70m max.75m max.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Selecting a Location for Installation of the Indoor Units - 1
If the outdoor unit is positioned higher than the indoor units.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Selecting a Location for Installation of the Indoor Units - 2
If the outdoor unit is positioned otherwise. (If lower than one or more indoor units)

Refrigerant Piping Work

1. Installing outdoor unit

1) When installing the outdoor unit, refer to "Precautions for Selecting the Location" on page 3 and the "Outdoor Unit Installation Drawings" on page 4.
2) If drain work is necessary, follow the procedures below.

2. Drain work

  • If the drain port is covered by a mounting base or floor surface, place additional foot bases of at least 1-1/4 inch (30mm) in height under the outdoor unit's feet.
  • In cold areas, do not use a drain socket, drain caps (1,2) and a drain hose with the outdoor unit. (Otherwise, the drain water may freeze, impairing heating performance.)

1) Attach ⑥ drain cap (1) and drain cap (2).
2) Attach ⑧ drain socket.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Drain work - 1

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Drain work - 2

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Drain work - 3

3. Refrigerant piping

CAUTION

  • Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
  • To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R32.)
  • Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
  • Do not reuse joints which have been used once already.
  • Installation shall be done by an installer, the choice of materials and installation shall comply with the applicable legislation. In Europe the EN378 is the applicable standard that shall be used.
  • Ensure that the field piping and connections are not subjected to stress.

Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - CAUTION - 1

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - CAUTION - 2

Flare nut tightening torque
ø 1/4 inch (6.4mm)10-1/2 — 12-3/4ft • lbf (14.2-17.2N • m)
ø 3/8 inch (9.5mm)24-1/8 — 29-1/2ft • lbf (32.7-39.9N • m)
ø 1/2 inch (12.7mm)36-1/2 — 44-1/2ft • lbf (49.5-60.3N • m)
ø 5/8 inch (15.9mm)45-5/8 — 55-5/8ft • lbf (61.8-75.4N • m)
Width across flats11/16 inch (17mm)3/4 inch (19mm)7/8 inch (22mm)11/16 inch (27mm)
Valve cap tightening torque10-1/2 — 12-5/8ft • lbf (14.2-17.2N • m)12-5/8 — 15-3/8ft • lbf (17.1-20.9N • m)16 — 20-1/4ft • lbf (21.6-27.4N • m)35-3/8 — 44-1/8ft • lbf (48-59.8N • m)

Service port cap tightening torque

8-10-7/8ft lbf (10.8-14.7N m)

Refrigerant Piping Work

4. Evacuating the air with a vacuum pump and checking for gas leakage

WARNING

  • Do not mix any substance other than the specified refrigerant (R32) into the refrigeration cycle.
  • When refrigerant gas leaks should occur, ventilate the room as soon and as much as possible.
    R32, as well as other refrigerants, should always be recovered and never be released directly into the environment.
  • Use a vacuum pump for R32 or R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit.
  • Use tools for R32 or R410A (such as the gauge manifold, charging hose, or vacuum pump adapter).
  • During tests never pressurize the appliances with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
    If refrigerant gas leaks, ventilate the area immediately. Toxic gas may be produced if refrigerant gas comes into contact with fire.
  • Never directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.

  • When piping work is completed, it is necessary to purge the air and check for gas leakage.
    If using additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump, then charge additional refrigerant.

  • Use a hexagonal wrench (4mm) to operate the stop valve rod.
  • All refrigerant pipe joints should be tightened with a torque wrench to the specified tightening torque.

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve's service port.
2) Fully open gauge manifold's low-pressure valve (Lo) and completely close its high-pressure valve (Hi). (High-pressure valve subsequently requires no operation.)
3) Perform vacuum pumping and make sure that the compound pressure gauge reads -0.1MPa (-76cmHg) . Evacuation for at least 1 hour is recommended.
4) Close gauge manifold's low-pressure valve (Lo) and stop vacuum pump. (Keep this state for 4-5 minutes to make sure that the compound pressure gauge pointer does not swing back. If it does go back, this may indicate the presence of moisture or leaking from connecting parts. After inspecting all the connection and loosening then retightening the nuts, repeat steps 2-4.)
5) Remove covers from liquid stop valve and gas stop valve.
6) Turn the liquid stop valve's rod 90 degrees counterclockwise with a hexagonal wrench to open valve. Close it after 5 seconds, and check for gas leakage. Using soapy water, check for gas leakage from indoor unit's flare and outdoor unit's flare and valve rods. After the check is complete, wipe all soapy water off.
7) Disconnect charging hose from gas stop valve's service port, then fully open liquid and gas stop valves. (Do not attempt to turn valve rod beyond its stop.)
8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques. See "3. Refrigerant piping" on page 7 for details.

Refrigerant Piping Work

5. Charging with refrigerant

1) If the total length of piping for all rooms exceeds the figure listed below, additionally charge with 20g of refrigerant (R32) for each additional meter of piping.

Outdoor capacity class3MXM40M, 3MXM52M, 3AMXM52M, 3MXM68M, 4MXM68M, 4MXM80M, 5MXM90M
Total length of piping for all rooms30m

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere.

Refrigerant type: R32

GWP(1) value: 675 (1) GWP = global warming potential

Please fill in with indelible ink,

① the factory refrigerant charge of the product,
② the additional refrigerant amount charged in the field and
1 + 2 the total refrigerant charge

on the refrigerant charge label supplied with the product.

The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop valve cover).

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Important information regarding the refrigerant used - 1

1 factory refrigerant charge of the product: see unit name plate
2 additional refrigerant amount charged in the field (Refer to the above information for the quantity of refrigerant replenishment.)
3 total refrigerant charge
4 Contains fluorinated greenhouse gases covered by the Kyoto Protocol
5 outdoor unit
6 refrigerant cylinder and manifold for charging

NOTE:

National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the unit. Therefore an additional multilingual fluorinated greenhouse gases label is supplied with the unit. Sticking instructions are illustrated on the backside of that label.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - NOTE: - 1

CAUTION

Even though the stop valve is fully closed, the refrigerant may slowly leak out; do not leave the flare nut removed for a long period of time.

Refrigerant Piping Work

6. Refrigerant piping work

Cautions on pipe handling

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender for bending.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Cautions on pipe handling - 1

Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following:

1) Insulation material: Polyethylene foam

Heat transfer rate: 0.041 to 0.052W / mK (0.035 to 0.045kcal / mh^)

Refrigerant gas pipe's surface temperature reaches 110^ max.

Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.

Gas pipeO.D.: 9.5mm, 12.7mm / Thickness: 0.8mm (C1220T-O) O.D.: 15.9mm / Thickness: 1.0mm (C1220T-O)
Liquid pipeO.D.: 6.4mm / Thickness: 0.8mm (C1220T-O)
Gas pipe insulationI.D.: 12-15mm, I.D.: 16-20mm / Thickness: 13mm min.
Liquid pipe insulationI.D.: 8-10mm / Thickness: 10mm min.
Minimum bend radiusO.D.: 6.4mm, 9.5mm / 30mm or more O.D.: 12.7mm / 40mm or more O.D.: 15.9mm / 50mm or more

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Selection of copper and heat insulation materials - 1

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
4) Piping and other pressure containing parts shall comply with the applicable legislation and shall be suitable for refrigerant. Use phosphoric acid deoxidised seamless copper for refrigerant.

7. Flaring the pipe end

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Flaring the pipe end - 1

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Flaring the pipe end - 2

WARNING

  • Do not use mineral oil on flared part.
  • Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
  • Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
  • Never install a dryer to this R32 unit in order to guarantee its lifetime.
  • The drying material may dissolve and damage the system.
    Incomplete flaring may cause refrigerant gas leakage.

How to Use Reducers

No.1 No.2

15.9 12.7

12.7 9.5

No.3 No.4

15.9 12.7

12.7 9.5

No.5 No.6

15.9 15.9

9.5 9.5

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - How to Use Reducers - 1
Gasket (1)

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - How to Use Reducers - 2
Gasket (2)

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - How to Use Reducers - 3
Reduce and gasket

Use the reducers supplied with the unit as described below.

1) Connecting a pipe of 12.7 to a gas pipe connection port for 15.9 :

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - How to Use Reducers - 4

2) Connecting a pipe of 9.5 to a gas pipe connection port for 15.9 :

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - How to Use Reducers - 5

3) Connecting a pipe of 9.5 to a gas pipe connection port for 12.7 :

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - How to Use Reducers - 6

  • When using the reducer packing shown above, be careful not to over-tighten the nut, or the smaller pipe may be damaged. (about 2/3 - 1 the normal torque)
  • Apply a coat of refrigeration oil to the threaded connection port of the outdoor unit where the flare nut comes in.
  • Use an appropriate wrench to avoid damaging the connection thread by overtightening the flare nut.
Flare nut tightening torque
Flare nut for φ9.532.7–39.9N·m (333–407kgf·cm)
Flare nut for φ12.749.5–60.3N·m (505–615kgf·cm)
Flare nut for φ15.961.8–75.4N·m (630–769kgf·cm)

Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.

1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Pump Down Operation - 1

1. Forced operation

1) Switch off the power.
2) Remove the Service lid (2 screws).
3) Remove the service PC-board switch cover (1 screw).
4) Switch SW5 and SW6 to off.
5) Turn the operation mode switch (SW2) to COOL.
6) Screw the service PC-board switch cover back on (1 screw)-
7) Switch the power on.
8) Push the forced operation switch (SW1) above the service PC-board cover.

Start forced colling operation.

To stop forced operation, push the forced operation switch (SW1) again.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Forced operation - 1

WARNING

Do not remove the switch cover unless the power has been turned off. (Risk of electric shock)

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - WARNING - 1

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - WARNING - 2

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - WARNING - 3

WARNING

  • Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire.
  • Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the terminal block.) Doing so may cause electric shock or fire.
  • Be sure to install an earth leakage breaker. (One that can handle higher harmonics.)

(This unit uses an inverter, which means that an earth leakage breaker capable of handling harmonics must be used, in order to prevent malfunctioning of the earth leakage breaker itself.)

  • Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
  • Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

1) Strip the insulation from the wire (3/4inch (20mm)).
2) Connect the connection wires between the indoor and outdoor units so that the terminal numbers match. Tighten the terminal screws securely. We recommend a flathead screwdriver be used to tighten the screws.
3) Be sure to match the symbols for wiring and piping.
4) Pull the wire lightly to make sure that it does not disconnect.
5) Pass the wiring through the cutout on the bottom of the protection plate and attach the protection plate.
6) After completing the work, reattach the service lid to its original position.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - WARNING - 1

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - WARNING - 2

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - WARNING - 3

CAUTION

  • Precautions to be taken for power supply wiring. When using stranded wires, make sure to use the round crimp-style terminal for connection to the power supply terminal

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - CAUTION - 1

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - CAUTION - 2

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - CAUTION - 3

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - CAUTION - 4

Arrow view A

  • When connecting the inter-unit wires to the terminal block using a single core wire, be sure to curl the end of the lead. Improper work may cause heat and fires.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Arrow view A - 1

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Arrow view A - 2

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Arrow view A - 3

Stripping wire at terminal block

  • Make sure that the earth wire between the pull relief and terminal is longer than the other wires.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Arrow view A - 4

Ground

This air conditioner must be grounded. For grounding, follow all local, and state electrical codes.

Standby Electricity Saving

3MXM40M, 3MXM52M, 3AMX52M only

The standby electricity saving function turns off power supply to the outdoor unit and sets the indoor unit into standby electricity saving mode, thus reducing the power consumption of the air conditioner.

The standby electricity saving function works on the following indoor unit.

For FTXM,FTXP,FTXJ type

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Standby Electricity Saving - 1

CAUTION

  • The standby electricity saving function cannot be used for models other than the specified ones.

  • Procedure for turning on standby electricity saving function

1) Check that the main power supply is turned off. Turn it off if it has not been turned off.
2) Remove the stop valve cover.
3) Disconnect the selective connector for standby electricity saving.
4) Turn on the main power supply.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - CAUTION - 1

Standby electricity saving function off.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - CAUTION - 2

Standby electricity saving function on.

The standby electricity saving function is turned off before shipping.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - CAUTION - 3

CAUTION

  • Before connecting or disconnecting the selective connector for standby electricity saving, make sure that the main power supply is turned off.
  • The selective connector for standby electricity saving is required if an indoor unit other than the above applicable one is connected.

Priority Room Setting

  • To use priority room setting, initial settings must be made when the unit is installed. Explain the priority room setting, as described below, to the customer, and confirm whether or not the customer wants to use priority room setting. Setting it in the guest and living rooms is convenient.

1. About the priority room setting function

The indoor unit for which priority room setting is applied takes priority in the following cases.

1-1. Operation mode priority

The operation mode of the indoor unit which is set for priority room setting takes priority. If the set indoor unit is operating, all other indoor units do not operate and enter standby mode, according to the operation mode of the set indoor unit.

1-2. Priority during high-power operation

If the indoor unit which is set for priority room setting is operating at high power, the capabilities of other indoor units will be somewhat reduced. Power supply gives priority to the indoor unit which is set for priority room setting.

1-3. Quiet operation priority

Setting the indoor unit to quiet operation will make the outdoor unit run quietly.

Setting procedure

Slide the switch to the ON side for the switch that corresponds to the piping connected to the indoor unit to be set. (In the figure below, it is room A.) Once the settings are complete, reset the power.

Be sure to only set one room

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Be sure to only set one room - 1

Night Quiet Mode Setting

  • If Night Quiet Mode is to be used, initial settings must be made when the unit is installed. Explain Night Quiet Mode, as described below, to the customer, and confirm whether or not the customer wants to use Night Quiet Mode.

About Night Quiet Mode

The Night Quiet Mode function reduces operating noise of the outdoor unit at nighttime. This function is useful if the customer is worried about the effects of the operating noise on the neighbors.

However, if Night Quiet Mode is running, cooling capacity will be saved.

Setting procedure

Turn the Night Quiet Mode switch (SW6-1) to on.

HEAT Mode Lock

  • Use the HEAT Mode Lock switch (SW5-1) in the "ON" position.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - HEAT Mode Lock - 1

COOL Mode Lock

  • Use the S15 connector to set the unit to cool only.

Setting to only cool (C) : short-circuit pins 3 and 5 of the connector

The following specifications apply to the connector housing and pins.

ST products Housing: VHR-5N

Pin: SVH-21T-1,1

Note that forced operation is also possible in COOL mode.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - COOL Mode Lock - 1

Trial Operation and Testing

  • Before starting the test run, measure the voltage at the primary side of the safety breaker.
  • Check that all liquid and gas stop valves are fully open.
  • Check that piping and wiring all match. The wiring error check can be conveniently used for underground wiring and other wiring that cannot be directly checked.

1. Wiring error check

  • This product is capable of automatic correction of wiring error.
  • Press the "wiring error check switch" on the outdoor unit service PCboard. However, the wiring error check switch will not function for 3 minutes after the safety breaker is turned on, or depending on the outside air conditions (See Note 2.). About 15–20 minutes after the switch is pressed, the errors in the connection wiring will be corrected.

The service monitor LEDs indicate whether or not correction is possible, as shown in the table below. For details about how to read the LED display, refer to the service manual.

If self-correction is not possible, check the indoor unit wiring and piping in the usual manner.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Wiring error check - 1

LED12345Message
StatusAll FlashingAutomatic correction impossible
Flashing One after anotherAutomatic correction completed
(One or more of LEDs 1 to 4 are ON)Abnormal stop [NOTE. 4]

Wiring correct example

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Wiring correct example - 1

NOTE:

1) For two rooms, LED 3, 4 and 5 are not displayed, and for three rooms, LED 4 and 5 is not displayed, and for four rooms, LED 5 is not displayed.
2) If the outside air temperature is 5^ or less, the wiring error check function will not operate.
3) After wiring error check operation is completed, LED indication will continue until ordinary operation starts. This is normal.
4) Follow the product diagnosis procedures. (Details of product error diagnosis are listed on the back of the right side plate.)

Trial Operation and Testing

2. Trial operation and testing

1) To test cooling, set for the lowest temperature. To test heating, set for the highest temperature. (Depending on the room temperature, only heating or cooling (but not both) may be possible.)
2) After the unit is stopped, it will not start again (heating or cooling) for approximately 3 minutes.
3) When trial operation is conducted in the HEAT operation directly after the circuit breaker is turned on, in some cases no air will be output for about 15 minutes in order to protect the air conditioner.
4) During the test run, first check the operation of each unit individually. Then also check the simultaneous operation of all indoor units.

Check both heating and cooling operation.

5) After running the unit for approximately 20 minutes, measure the temperatures at the indoor unit inlet and outlet. If the measurements are above the values shown in the table below, then they are normal.

CoolingHeating
Temperature difference between inlet and outletApprox. 8°CApprox. 20°C

(When running in one room)

6) During cooling operation, frost may form on the gas stop valve or other parts. This is normal.
7) Operate the indoor units in accordance with the included operation manual. Check that they operate normally.

3. Items to check

Check itemConsequences of troubleCheck
Are the indoor units installed securely?Falling, vibration, noise
Has an inspection been made to check for gas leakage?Incomplete cooling/heating function
Has complete thermal insulation been done (gas pipes, liquid pipes, indoor portions of the drain hose extension)?Water leakage
Is the drainage secure?Water leakage
Are the ground wire connections secure?Electrical leakage
Are the electric wires connected correctly?Incomplete cooling/heating function
Is the wiring in accordance with the specifications?No operation or burn damage
Are the inlets/outlets of the indoor and outdoor units free of any obstructions?Incomplete cooling/heating function
Are the stop valves open?Incomplete cooling/heating function
Do the marks match (room A, room B, room C, room D, room E) on the wiring and piping for each indoor unit?Incomplete cooling/heating function
Is the priority room setting set for 2 or more rooms?The priority room setting will not func-tion.

ATTENTION

  • Have the customer actually operate the unit while looking at the manual included with the indoor unit. Instruct the customer how to operate the unit correctly (particularly cleaning of the air filters, operation procedures, and temperature adjustment).
  • Even when the air conditioner is not operating, it consumes some electric power. If the customer is not going to use the unit soon after it is installed, turn off the breaker to avoid wasting electricity.
  • If additional refrigerant has been charged because of long piping, list the amount added on the nameplate on the reverse side of the stop valve cover.

Piping Diagram

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Piping Diagram - 1
Outdoor Unit

Outdoor Unit
DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Piping Diagram - 2
PED categories of equipment - High pressure switches : category IV; Compressor : category II; Accumulator: category: I; Other art 3§3 equipment.

NOTE:

When the high pressure switch is activated it must be reset manually by a qualified person.

Piping Diagram

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Piping Diagram - 1
Outdoor Unit

Outdoor Unit
DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Piping Diagram - 2
PED categories of equipment - High pressure switches : category IV; Compressor : category II; Accumulator: category: I; Other art 3§3 equipment.

NOTE:

When the high pressure switch is activated it must be reset manually by a qualified person.

Piping Diagram

Outdoor Unit
DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Piping Diagram - 1
PED categories of equipment - High pressure switches : category IV; Compressor : category II; Accumulator: category: I; Other art 3§3 equipment.

NOTE:

When the high pressure switch is activated it must be reset manually by a qualified person.

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Piping Diagram - 2

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Piping Diagram - 3

DAIKIN 3MXM40N  -  3MXM52N -  3MXM68N -  3MXS40K -  3MXS52E -  3MXS68G - Piping Diagram - 4