INFOSEC X4 SINUS 1500 RT - Inverter

X4 SINUS 1500 RT - Inverter INFOSEC - Free user manual and instructions

Find the device manual for free X4 SINUS 1500 RT INFOSEC in PDF.

📄 35 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice INFOSEC X4 SINUS 1500 RT - page 6
View the manual : Français FR English EN
Pick your language and provide your email: we'll send you a specifically translated version.
BrandINFOSEC
ModelX4 SINUS 1500 RT
Product TypePure Sine Wave UPS (Double Conversion)
Power1500 VA
Input VoltageSingle Phase 110-240 V
Output VoltageConfigurable: 110, 120, 208, 220, 230, 240 V
Frequency50/60 Hz (Auto-sensing)
BatteriesInternal, Lead-Acid, Hot-swappable
RuntimeVaries by load (full recharge 5h)
ProtectionAVR (Boost/Buck), Surge Arrest, Surge Suppression
OutletsEssential and Programmable
CommunicationsUSB, RS-232, SNMP Slot
DisplayLCD Status Screen
Audible AlarmsBattery Mode, Low Battery, Overload, Fault
EPO FunctionEmergency Power Off via Connector
SoftwareInfoPower (Included)
SafetyCE Compliance, Electric Shock Protection
MaintenanceDisconnect before cleaning, damp cloth
RepairabilityUser Replaceable Batteries
MountingRack (2U) or Tower
WeightApprox. 12 kg

Frequently Asked Questions - X4 SINUS 1500 RT INFOSEC

How to start the INFOSEC X4 SINUS 1500 RT UPS?
Press the ON/MUTE button for at least 2 seconds to turn on the UPS. The LCD screen lights up and the UPS switches to normal mode if mains power is present.
How to configure the output voltage?
Set the UPS to standby mode (off). Press Select for 5 seconds to enter Configuration mode. Use the Up and Down buttons to navigate to '01' (output voltage) and press Enter. Choose the desired value (110, 120, 208, 220, 230, or 240 V) and confirm with Enter. To exit, select '00' and press Enter. Disconnect and reconnect the AC input to apply.
What to do in case of UPS overload?
If the OVERLOAD icon flashes and the alarm sounds twice per second, the UPS is overloaded. Immediately remove non-essential loads from the outlets to reduce power consumption. If fault code 43 appears, the UPS has shut down: remove excess loads and restart.
How to replace the UPS batteries?
The UPS supports hot-swap battery replacement. Remove the front panel, disconnect the battery cables, remove the battery compartment by unscrewing the two front screws. Open the compartment cover, replace the batteries with identical models. Reinstall the compartment, reconnect the cables, and replace the front panel. Follow safety instructions: wear gloves, use insulated tools.
What does error code 01 on the LCD screen mean?
Code 01 indicates a BUS-DC startup failure. This is an internal fault requiring a qualified technician. Contact your dealer or after-sales service.
How to activate the programmable outlets on the UPS?
In Configuration mode, navigate to parameter '02' using the Up button. Press Enter, then select 'ENA' with Up and confirm with Enter. Next, set the runtime of programmable outlets via parameter '03' by adjusting the value in minutes (0-999). To finalize, exit by selecting '00' then Enter, and restart the UPS.
How to disable the audible alarm in battery mode?
When the UPS is running on battery and the alarm sounds every 4 seconds, press the ON/MUTE button for at least 5 seconds to mute the alarm. This does not disable alarms for critical warnings (low battery, overload).
How to install the InfoPower software provided with the UPS?
Insert the provided CD into your computer. Connect the UPS to the computer via a USB or RS-232 cable. Launch the InfoPower software installation and follow the instructions. After restart, an orange icon appears in the taskbar. You can then monitor and configure the UPS from the computer.
Can I connect a laser printer to the UPS?
No, it is not recommended to connect laser printers as they consume excessive power and may cause overload. The UPS is designed to power computer equipment like computers, monitors, and peripherals.
How to store the UPS for a long period?
Before storage, charge the batteries for 5 hours. Place the UPS covered, upright, in a cool and dry place. If the temperature is between -25°C and 40°C, recharge the batteries every 3 months for 1-2 hours. Between 40°C and 45°C, recharge every 2 months.

User questions about X4 SINUS 1500 RT INFOSEC

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Inverter in PDF format for free! Find your manual X4 SINUS 1500 RT - INFOSEC and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. X4 SINUS 1500 RT by INFOSEC.

USER MANUAL X4 SINUS 1500 RT INFOSEC

1. SAFETY INSTRUCTIONS - Security

IMPORTANT!

Installing and connecting UPSs in a way that does not comply with accepted practices releases Infosec Communication from any liability.

1.1 Risk of electric shock:

The UPS unit uses potentially hazardous voltages. Do not attempt to disassemble this equipment as it does not contain accessible components that can be repaired by users.
All repairs should be performed by qualified technicians only.
The utility power outlet shall be near the equipment and easily accessible. To isolate the UPS from AC input, turn it off and then remove the plug from the utility power outlet.
The UPS has its own internal power supply (battery). There is a risk that output sockets may still be live after the UPS has been disconnected from the mains power supply.
In an emergency situation, switch the UPS to the "Off" position and disconnect the unit from the AC power supply.
When the UPS is out of order, please refer to section: "trouble shooting" and call the hot line.

1.2 Connected products:

Combined UPS and connected equipment leakage current should not exceed 3.5mA .
Make sure that the connected load does not exceed UPS capabilities. To ensure improved backup time and longer battery life, we recommend a load equivalent to 1/3 of nominal power.
Do not plug the UPS input into its own output socket.
Do not plug the UPS into a power strip or surge suppressor.
The UPS has been designed for personal computers. It should not be used with electrical or electronic equipment with inductive loads such as motors or fluorescent lights.
Do not connect any household appliances such as microwaves, vacuum cleaners, hair dryers or life-support systems to the UPS.
Due to excessive consumption, laser printers should not be connected to the UPS.
Please replace the fuse only with the same type and amperage in order to avoid fire hazards.

1.3 Good disposals of the device:

The mains outlet that supplies the UPS shall be located near the UPS and shall be easily accessible.
Install the UPS in a temperature and humidity-controlled indoor area free of conductive interference.
It should not be exposed to direct sunlight or sources of heat. Do not cover the ventilation slots.
Disconnect the UPS from AC power before cleaning with a damp cloth (no cleaning products).
Do not leave any recipients containing liquid on or near the UPS.

1.4 About batteries:

It is recommended that a qualified technician change the battery.
Do not dispose of the battery in a fire as it may explode.
Do not open or damage the battery! The electrolyte, fundamentally sulphuric acid, can be toxic and harmful to the skin and eyes. If you come into contact with it, wash thoroughly with water and clean dirtied clothes.
Do not throw the battery into a fire. It may explode. It has to be disposed of separately at the end of its useful life. Refer to local legislation and regulations.
The UPS contains large-capacity batteries. To avoid any danger of electric shock do not open it/them. If a battery needs servicing or has to be replaced, please contact the distributor.
Servicing should be performed or supervised by competent personnel who take the necessary precautions. Keep unauthorized personnel away from batteries.
A battery can present a risk of electric shock and cause short circuits. The following precautions should be observed by the qualified technician:

Remove watches, rings or other metal objects from hands.
Use tools with insulated handles.
Disconnect the charging source prior to connecting or disconnecting battery terminals.
- When replacing batteries, use the same type and number of sealed lead-acid batteries.

1.5 CE conformity (IEC model):

INFOSEC X4 SINUS 1500 RT - CE conformity (IEC model): - 1

This logo means that the IEC product answers to the EMC and LVD standards (regarding to the regulation associated with the electric equipment voltage and the electromagnetic fields).

IMPORTANT

INFOSEC X4 SINUS 1500 RT - IMPORTANT - 1

An UPS belongs to the electronic and electrical equipment category. At the end of its useful life it must be disposed of separately and in an appropriate manner.

This symbol is also affixed to the batteries supplied with this device, which means they too have to be taken to the appropriate place at the end of their useful life.

Contact your local recycling or hazardous waste centre for information on proper disposal of the used battery.

2. INSTALLATION AND SETUP

NOTE: Before the installation of the unit, please inspect it. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use.

2.1 Rear panel view

INFOSEC X4 SINUS 1500 RT - Rear panel view - 1
X4 SINUS RT IEC 1500/2000 VA

INFOSEC X4 SINUS 1500 RT - Rear panel view - 2
X4 SINUS RT IEC 3000 VA

INFOSEC X4 SINUS 1500 RT - Rear panel view - 3
X4 SINUS RT NEMA 1500 VA

INFOSEC X4 SINUS 1500 RT - Rear panel view - 4
X4 SINUS RT NEMA 2000 VA

INFOSEC X4 SINUS 1500 RT - Rear panel view - 5
X4 SINUS RT NEMA 3000 VA

1 - Programmable outlets: connect to non-critical loads.
2 - Output receptacles: connect to mission-critical loads.
3 - AC input.
4 - Input circuit breaker.
5 - Network/Fax/Modem surge protection.
6 - Emergency Power Off function connector (EPO).
7 - USB communication port.
8 - RS-232 communication port.
9 - SNMP intelligent slot.
10 - Input terminal.
11 - Output terminal.

2.2 Install the UPS

For safety consideration, the X4 SINUS RT is shipped without connecting battery wires. Before installing the UPS, please follow the steps below to re-connect battery wires.

INFOSEC X4 SINUS 1500 RT - Install the UPS - 1
- Step 1
Remove front panel.

INFOSEC X4 SINUS 1500 RT - Install the UPS - 2
Step 2
Connect the AC input and re-connect battery wires.

INFOSEC X4 SINUS 1500 RT - Install the UPS - 3
- Step 3
Put the front panel back to the unit.

Rack-mount installation

INFOSEC X4 SINUS 1500 RT - Rack-mount installation - 1
Step 1

INFOSEC X4 SINUS 1500 RT - Rack-mount installation - 2

Tower installation

INFOSEC X4 SINUS 1500 RT - Tower installation - 1
Step 1

INFOSEC X4 SINUS 1500 RT - Tower installation - 2
Step 2

INFOSEC X4 SINUS 1500 RT - Tower installation - 3
Step 3

2.3 Setup the UPS

- Step 1 - UPS input connection

Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.

Avoid using extension cords.

- Step 2 - UPS output connection

For socket-type outputs, there are two kinds of outputs: programmable outlets and general outlets. Please connect non-critical devices to the programmable outlets and critical devices to the general outlets. During power failure, you may extend the backup time to critical devices by setting shorter backup time for non-critical devices.

- Step 3 - Communication connection

Communication ports:

INFOSEC X4 SINUS 1500 RT - Communication ports: - 1
USB port

INFOSEC X4 SINUS 1500 RT - Communication ports: - 2
RS-232 port

INFOSEC X4 SINUS 1500 RT - Communication ports: - 3
Intelligent slot

To allow unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.

The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring options.

PS: USB port and RS-232 port can't work at the same time.

- Step 4 - Network connection

Network/Fax/Phone surge port

INFOSEC X4 SINUS 1500 RT - Network/Fax/Phone surge port - 1

Connect the modem/phone/fax line into surge-protected "IN" outlet on the back panel of the UPS unit. Connect from "OUT" outlet to the equipment with another modem/fax/phone line cable.

- Step 5 - Disable and enable EPO function

Keep the pin 1 and pin 2 closed for UPS normal operation. To activate EPO function, cut the wire between pin 1 and pin 2.

INFOSEC X4 SINUS 1500 RT - - Step 5 - Disable and enable EPO function - 1

- Step 6 - Turn on the UPS

Press the ON/MUTE button on the front panel for two seconds to power on the UPS.

Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period.

- Step 7 - Install software

For optimal computer system protection, refer to the InfoPower software CD to fully configure UPS shutdown.

2.4 Battery replacement

NOTICE: This UPS is equipped with internal batteries and user can replace the batteries without shutting down the UPS or connected loads (hot-swappable battery design). Replacement is a safe procedure, isolated from electrical hazards.

CAUTION! Consider all warnings, cautions, and notes before replacing batteries.

Note: Upon battery disconnection, equipment is not protected from power outages.

INFOSEC X4 SINUS 1500 RT - Battery replacement - 1
Remove front panel.

INFOSEC X4 SINUS 1500 RT - Battery replacement - 2
Disconnect battery wires.

INFOSEC X4 SINUS 1500 RT - Battery replacement - 3
Pull out the battery box by removing two screws on the front panel.

INFOSEC X4 SINUS 1500 RT - Battery replacement - 4

INFOSEC X4 SINUS 1500 RT - Battery replacement - 5
Remove the top cover of battery box and replace the inside batteries.
After replacing the batteries, put the battery box back to original location and screw it tightly.

INFOSEC X4 SINUS 1500 RT - Battery replacement - 6
Re-connect the battery wires.

INFOSEC X4 SINUS 1500 RT - Battery replacement - 7

Put the front panel back to the unit.

3. OPERATIONS

3.1 Buttons operation

INFOSEC X4 SINUS 1500 RT - Buttons operation - 1

ButtonsFunctions
ON/MUTE buttonTurn on the UPS: Press and hold ON/MUTE button for at least 2 seconds to turn on the UPS.Mute the alarm: When the UPS is turned on in battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system. This is not applied to the situations when warnings or errors occur.Up selection key: Press this button to display previous selection in UPS setting mode.Switch to UPS self-test mode: Press and hold ON/MUTE buttons for 5 seconds to enter UPS self-testing while in AC mode.
OFF/ENTER buttonTurn off the UPS: Press and hold this button at least 2 seconds to turn off the UPS.Confirm selection key: Press this button to confirm selection in UPS setting mode.
SELECT buttonSwitch LCD message: Press this button to change the LCD message for input voltage, input frequency, battery voltage, output voltage and output frequency.Setting mode: Press and hold this button for 5 seconds to enter UPS setting mode only when UPS is off.Down election key: Press this button to display next selection in UPS setting mode.

3.2 LCD panel

1) Rack display

INFOSEC X4 SINUS 1500 RT - 1) Rack display - 1

2) Tower display

INFOSEC X4 SINUS 1500 RT - 2) Tower display - 1

DisplayFunctions
Backup time information
Indicates the backup time in pie chart.
Indicates the backup time in numbers. H: hours; M: minute.
Warning & fault information
Indicates that warning and fault occur.
Indicates the warning and fault codes (codes are listed in details page 12).
Setting operation
Indicates the setting operation.
Input/Output & battery information
INPUT BATT. OUTPUT V HzIndicates the input/output voltage, input/output frequency or battery voltage. V: voltage; Hz: frequency.
Load information
LOAD 25% 50% 75% 100%Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
OVER LOADIndicates overload.
SHORTIndicates that the load or the UPS output is short circuited.
UPS status
Indicates that programmable management outlets are working.
Indicates that the UPS alarm is disabled.
Indicates the UPS powers the output directly from the mains (See details page 13).
Indicates that the battery charger is working (See details page 13).
Indicates that the UPS is working in boost mode (See details page 13).
Indicates that the UPS is working in buck mode (See details page 13).
Battery information
25% 50% 75% 100% BATTERYIndicates the battery level by 0-25%, 26-50%, 51-75% and 76-100%.
LOW BATTIndicates low battery.
+Indicates a problem with the battery.

3.3 Audible alarms

Battery modeSounding every 4 seconds.
Low batterySounding every second.
OverloadSounding twice every second.
FaultContinuously sounding.

3.4 LCD display wording index

AbbreviationsDisplay contentMeaning
ENAENREnable
DISDISDisable
ESCESCEscape
EPEPEPO
FAFAFan
TPTPTemperature
CHCHCharger
RACRACRack display
TOETOETower display
SFSFSite Fault

3.5 UPS setting

There are two parameters to set up the UPS:

Parameter 1 – Program alternatives. There are 4 programs to set up: output voltage setting, programmable outlets enable/disable, programmable outlets setting, LCD display direction and exit.

Parameter 2 - Setting figures.

INFOSEC X4 SINUS 1500 RT - UPS setting - 1

1) Output voltage setting

InterfaceSetting figures
LOAD OUTPUT BATTERYFor 110/120/208/220/230/240 VAC models, you may choose the following output voltage: 110: presents output voltage is 110 VAC. 120: presents output voltage is 120 VAC. 208: presents output voltage is 208 VAC. 220: presents output voltage is 220 VAC. 230: presents output voltage is 230 VAC. 240: presents output voltage is 240 VAC.

2) Programmable outlets enable/disable

InterfaceSetting figures
LOAD BATTERY ERA 02ENA: Programmable outlets enable. DIS: Programmable outlets disable.

3) Programmable outlets setting

InterfaceSetting figures
LOAD BATTERY 999 0-999 for programmable outlets which connect to non-critical devices on battery mode.Setting the backup time limits in minutes from 0-999 for programmable outlets which connect to non-critical devices on battery mode.

4)LCD display direction setting

InterfaceSetting figures
LOAD BATTERY HAC 04RAC: The LCD display is horizontal. TOE: The LCD display is vertical.

5) Exit

Examples of steps to follow for setting the parameters:

Step 1 - Before entering setting mode, make sure that the UPS is in Stand-by mode (off-charging) and that the battery is connected. The LCD display is shown as right.
Step 2 - Press and hold the "Selection" button for 5 seconds to enter Setting mode.
Step 3 - Press the "Up" button (ON/MUTE) to switch to "02" of program list. Then press "Enter" button to enter value setting of parameter 2. Press the "Up" button to change the value to "ENA" to enable the programmable outlet function. Then press "Enter" button again to confirm the setting.
Step 4 - Press the "Up" button (ON/MUTE) again to switch to "03" of program list. Then press "Enter" button for setting programmable outlet time. Push "Up" button to change the value of backup time according your demand. Then press "Enter" to confirm the setting.
Step 5 - Press "Up" button (ON/MUTE) to switch to "00" of program list. Then press "Enter" button to exit setting menu.
Step 6 - Disconnect AC input and wait until the LCD display is off. The new setting will be activated when turning on the UPS again.

3.6 Operating mode and description

Operating modeDescriptionLCD display
ECO modeWhen the input voltage is within voltage acceptable range, UPS will power the output directly from the mains.LOAD 25° 50° 75° 25° 50° 75° 100° OUTPUT 220V OK BATTERY OK
Buck mode when AC is normalWhen the input voltage is higher than the voltage regulation range but lower than high loss point, the buck AVR will be activated.LOAD 25% 50% 25% 75% 220 V BATTERY
Boost mode when AC is normalWhen the input voltage is lower than the voltage regulation range but higher than low loss point, the boost AVR will be activated.LOAD 25% 50% 25% 75% 220 V BATTERY
Battery modeWhen the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 seconds, UPS will backup power from battery.LOAD 25% 50% 25% 75% 220 V BATTERY
Standby modeUPS is powered off, there is no output supply power, but the batteries can be charged.LOAD 25% 50% 25% 75% 220 V BATTERY

3.7 Faults reference code

Fault eventFault codeIconFault eventFault codeIcon
Bus start fail01xInverter output short14SHORT
Bus over02xBattery voltage too high27x
Bus under03xBattery voltage too low28+
Inverter soft start fail11xOver temperature41x
Inverter voltage high12xOver load43OVER LOAD
Inverter voltage high13x

3.8 Warning indicators

WarningsIcons (flashing)Alarms
Low batteryLOW BATT!Sounding every second.
OverloadOVER LOAD!Sounding twice every second.
Battery is not connected1 +1!Sounding every second.
Overcharge25% 50% 75% 100%Sounding every second.
Site wiring fault5F!Sounding every second.
EPO enableEP!Sounding every second.
Fan failureFA!Sounding every second.
Over temperatureEP!Sounding every second.
Charger failureCH!Sounding every second.
Battery fault+!Sounding every second.

4. TROUBLESHOOTING

If the UPS system does not operate correctly, please solve the problem by using the table below.

SymptomsPossible causesRemedy
No indication and alarm even though the main is normal.The AC input power is not correctly connected.Check if input power cord firmly connected to the mains.
The AC input is connected to the UPS output.Plug AC input power cord to AC input correctly.
The icon flashing on LCD display and alarm is sounding every second.EPO function is activated.Set the circuit in close position to disable EPO function.
The icon flashing on LCD display and alarm is sounding every second.Line and neutral conductors of UPS input are reversed.Rotate mains power socket by 180° and then connect to UPS system.
The icon andThe external or internal battery is incorrectly connected.Check if all batteries are connected well.
flashing on LCD display and alarm is sounding every second.
Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously sounding.Battery voltage is too high or problem with the charger.Contact your dealer.
Fault code is shown as 28 and the icon is lighting on LCD display and alarm is continuously sounding.Battery voltage is too low or problem with the charger.Contact your dealer.
The icon and the icon OVER LOAD are flashing on LCD display and alarm is sounding twice every second.UPS is overloaded.Remove excess loads from UPS output.
Fault code is shown as 43 and The icon OVERLOAD is lighting on LCD display and alarm is continuously sounding.The UPS shut down automatically because of an overload at the UPS output.Remove excess loads from UPS output and restart it.
Fault code is shown as 14 and alarm is continuously sounding.The UPS shut down automatically because short circuit occurs on the UPS output.Check output wiring and if connected devices are in short circuit status.
Fault code is shown as 1, 2, 3, 11 and 41 on LCD display and alarm is continuously sounding.A UPS internal fault has occurred.Contact your dealer
Battery backup time is shorter than nominal valueBatteries are not fully charged.Charge the batteries for at least 5 hours and then check capacity. If the problem still persists, consult your dealer.
Batteries defect.Contact your dealer to replace the battery.
The icon and the warning code flashing on LCD display and alarm is sounding every second.Fan is locked or doesn't working properly.Check fans and notify dealer.

5. STORAGE AND MAINTENANCE

5.1 Warning indicator

The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25^ ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.

5.2 Storage

Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:

Storage TemperatureRecharge FrequencyCharging Duration
-25°C - 40°CEvery 3 months1-2 hours
40°C - 45°CEvery 2 months1-2 hours

INFOSEC X4 SINUS 1500 RT - Storage - 1

Version française

1. INSTRUCTIONS DE SECURITE

IMPORTANT!

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : INFOSEC

Model : X4 SINUS 1500 RT

Category : Inverter