Product Type Online double conversion UPS (ON-LINE)
Model E4 5000 VA (long autonomy version S available)
Dimensions (W x D x H) 260 x 570 x 717 mm
Net weight (E4 5000) 90 kg
Net weight (E4 5000S) 35 kg
Rated power 5 kVA / 3.5 kW
Input voltage Single phase, 176-276 VAC
Max input current 25 A
Input frequency 46-54 Hz
Output voltage 220 VAC (±1%)
Rated output current 23 A
Output frequency (battery mode) 50 Hz ±0.1%
Internal battery voltage (standard model) 240 VDC (20 batteries 12V in series)
Max charging current 20 A
Typical autonomy (full load) Not specified for this model, see full manual
Operating temperature 0°C to 40°C (optimal 20-25°C)
Relative humidity < 95%
Max altitude 1000 m (derating above)
Main functions Protection against power outages, overvoltages, undervoltages, filtering disturbances. Manual and static BY-PASS mode. RS232 communication, intelligent slot (AS400/SNMP). UPSurf-Control supervision software.
Maintenance and cleaning Recharge batteries every 3 months if stored. Do not block vents. Clean with a dry cloth.
Safety Input circuit breaker, overload and short circuit protection. Risk of internal electrocution. Intervention reserved for qualified personnel.
Spare parts and repairability No user-replaceable internal parts. Batteries replaceable by an authorized technician.
General information Brand INFOSEC. Warranty and after-sales service: hotline@infosec.fr / +33 (0)2 40 76 15 82. CE compliant.

Frequently Asked Questions - E4 5000 VA INFOSEC

How to connect the E4 5000 VA UPS to the mains?
The UPS is connected to a grounded wall outlet. It is recommended to use a 300 mA selective differential circuit breaker upstream. Connection must be carried out by qualified personnel.
Which devices can I connect to the UPS output?
Connect computer equipment (computers, servers) to the output sockets. Avoid inductive devices such as laser printers or heaters, which may cause overload.
How to start the UPS?
Ensure the input circuit breaker is in the ON position. Press the ON button (red) on the front panel for more than one second. The UPS performs a self-test then switches to normal mode.
What to do in case of a mains failure?
The UPS automatically switches to battery. A beep sounds every 4 seconds. You can silence the alarm by pressing the ON button. Save your data quickly; autonomy depends on the load.
How to completely shut down the UPS?
Press the OFF button (green) for more than one second. In mains mode, the UPS switches to BY-PASS. To cut the output, open the input circuit breaker or unplug the power cord.
How long do the batteries last and how to replace them?
Batteries last 3 to 5 years at 25°C. Replacement must be carried out by a qualified technician and only with batteries of the same type and in the same number.
Can I use a generator with this UPS?
Yes, provided the generator power is at least three times greater than that of the UPS. Start the generator first, wait for it to stabilize, then start the UPS.
How to monitor the UPS remotely?
The UPS is equipped with an RS232 interface and an intelligent slot for an AS400 or SNMP card. Use the provided UPSurf-Control software for monitoring and automatic shutdown of systems.
What do the indicators on the front panel mean?
The ON LINE indicator (green) indicates mains presence. INVERTER (green) indicates that the output is powered by the UPS. BAT. (orange) indicates battery mode. DEFAULT (red) indicates an anomaly. Indicators 2 to 6 indicate the load level or battery status.
Why is the audible alarm continuous?
A continuous alarm may indicate an overload, short circuit or internal fault. Refer to the incident table in the manual. If the DEFAULT indicator is on, contact after-sales service.

User questions about E4 5000 VA INFOSEC

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Inverter in PDF format for free! Find your manual E4 5000 VA - INFOSEC and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. E4 5000 VA by INFOSEC.

USER MANUAL E4 5000 VA INFOSEC

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : INFOSEC

Model : E4 5000 VA

Category : Inverter