HAGER

ADM440T - Circuit Breaker HAGER - Free user manual and instructions

Find the device manual for free ADM440T HAGER in PDF.

📄 2 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice HAGER ADM440T - page 1
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Miniature Circuit Breaker (MCB)
Model ADM440T
Brand Hager
Number of Poles 4
Rated Current (In) 40 A
Rated Voltage (Ue) 400 V AC
Rated Frequency 50/60 Hz
Breaking Capacity (Icu) 6 kA (according to IEC 60898)
Tripping Curve Type C (typical for moderate inrush currents)
Mounting Type DIN rail (35 mm)
Dimensions (H x W x D) Approx. 85 x 72 x 69 mm (4 modules width)
Weight Approx. 0.35 kg
Power Supply Directly connected to mains (no external supply needed)
Main Functions Overload protection, short-circuit protection, switching function
Maintenance None required; periodic visual inspection recommended
Cleaning Wipe with dry cloth; do not use solvents
Safety Features IP20 rated, touch-proof terminals, arc extinction chambers
Spare Parts & Repairability Not repairable; replace entire unit if faulty
Compliance IEC 60898, EN 60898, CE marked

Frequently Asked Questions - ADM440T HAGER

What is the rated current of the Hager ADM440T?
The rated current (In) is 40 A.
What does the '4' in ADM440T indicate?
The '4' indicates that it is a 4-pole circuit breaker.
Can the ADM440T be used in single-phase circuits?
Yes, but only the appropriate poles should be used. It is designed for three-phase systems with 4 poles (3 phases + neutral).
What is the breaking capacity of this circuit breaker?
The breaking capacity (Icu) is 6 kA according to IEC 60898.
What does the tripping curve 'C' mean?
Curve C trips at 5 to 10 times the rated current, suitable for moderate inrush currents like lighting and small motors.
How do I install the ADM440T on a DIN rail?
Snap the breaker onto the DIN rail by engaging the top clip first, then push the bottom until it clicks. Ensure correct orientation.
What should I do if the breaker trips frequently?
Check for overload or short-circuit. Reduce connected load. If tripping persists, replace the breaker.
Is the ADM440T suitable for residential use?
Yes, it is commonly used in residential and commercial distribution boards for protection of circuits up to 40 A.
Can I use this breaker outdoors?
It has an IP20 rating, meaning it is not weatherproof. Use only indoors or in a weatherproof enclosure.
What are the dimensions of the ADM440T?
Approximate dimensions: 85 x 72 x 69 mm (H x W x D). It occupies 4 modular spaces (4 x 18 mm).

User questions about ADM440T HAGER

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Circuit Breaker in PDF format for free! Find your manual ADM440T - HAGER and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. ADM440T by HAGER.

USER MANUAL ADM440T HAGER

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : HAGER

Model : ADM440T

Category : Circuit Breaker