TypeMiniature Circuit Breaker (MCB)
ModelHED401H
BrandHager
Number of Poles1
Rated Current (In)40 A
Tripping CharacteristicC-curve (5-10 In)
Rated Voltage (Ue)240/415 V AC
Rated Insulation Voltage (Ui)500 V
Rated Impulse Withstand Voltage (Uimp)4 kV
Breaking Capacity (Icn)6 kA (IEC 60898-1)
MountingDIN rail (TH35)
Width18 mm (1 module)
Depth78 mm
Height84 mm
Weight0.12 kg
Operating Temperature-25°C to +55°C
Terminal CapacitySolid: 1-25 mm², Stranded: 1-16 mm²
StandardsIEC 60898-1, EN 60898-1
Protection FunctionsOverload and short-circuit protection
MaintenanceNo periodic maintenance required; keep clean and dry.
SafetyIP20 protection (finger-safe terminals)
Spare PartsNot applicable; replace entire unit if defective.
RepairabilityNon-repairable; replacement recommended.

Frequently Asked Questions - HED401H HAGER

What does HED401H stand for?
HED is the series, 401 indicates 1-pole 40A, H likely denotes the breaking capacity or type.
What is the tripping curve of HED401H?
It has a C-curve tripping characteristic, meaning it trips at 5 to 10 times the rated current.
Can HED401H be used for both overload and short-circuit protection?
Yes, it provides both overload and short-circuit protection.
What is the maximum voltage for HED401H?
The rated voltage is 240/415 V AC.
How do I install HED401H on a DIN rail?
Snap it onto a 35 mm DIN rail (TH35). Ensure it clicks into place and is properly secured.
What is the breaking capacity of HED401H?
The rated breaking capacity is 6 kA according to IEC 60898-1.
Is HED401H suitable for residential use?
Yes, it is commonly used in residential and commercial distribution boards.
How do I clean the circuit breaker?
Use a dry cloth. Do not use water or solvents. Keep the surface clean and free from dust.
What should I do if the breaker keeps tripping?
Check for overload or short circuit in the connected circuit. If the problem persists, consult a qualified electrician.
Is the HED401H repairable?
No, it is a non-repairable device. If faulty, it must be replaced with a new one of the same ratings.

User questions about HED401H HAGER

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Circuit Breaker in PDF format for free! Find your manual HED401H - HAGER and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. HED401H by HAGER.

USER MANUAL HED401H HAGER

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : HAGER

Model : HED401H

Category : Circuit Breaker