| Product Type | Circuit Breaker |
| Brand | Hager |
| Model | AED216B |
| Number of Poles | 2 |
| Rated Current | 16 A |
| Tripping Curve | B |
| Rated Voltage | 230/400 V AC |
| Breaking Capacity | 6 kA |
| Dimensions (H x W x D) | 85 x 36 x 68 mm |
| Weight | 150 g |
| Mounting Type | DIN rail |
| Enclosure Protection | IP20 |
| Operating Temperature | -25°C to +55°C |
| Main Functions | Overcurrent protection, short-circuit protection |
| Maintenance | No regular maintenance required |
| Cleaning | Wipe with dry cloth; do not use solvents |
| Safety Features | Touch-proof terminals, IP20 protection |
| Spare Parts Availability | Available from authorized distributors |
| Repairability | Not user-serviceable; replace if faulty |
| Certifications | CE, EN 60898-1 |
Frequently Asked Questions - AED216B HAGER
What is the rated current of the Hager AED216B?
The Hager AED216B circuit breaker has a rated current of 16 A.
What does the 'B' in AED216B mean?
The 'B' indicates the tripping curve for overcurrent protection, designed for resistive and lighting loads with low inrush currents.
How do I install the AED216B on a DIN rail?
Clip the breaker onto a 35 mm DIN rail until it locks. Ensure the terminals are connected with appropriate torque (typically 2-3 Nm).
Why does my AED216B keep tripping?
Tripping may occur due to overload (exceeding 16A), short circuit, or a faulty appliance. Check connected load and wiring. If persistent, consult an electrician.
Can I use the AED216B for motor protection?
No, the B-curve is not suitable for motors. For motors, use a C- or D-curve breaker or a motor protection circuit breaker.
What is the breaking capacity of this circuit breaker?
The AED216B has a breaking capacity of 6 kA at 230/400 V AC.
Is the AED216B compatible with Hager's modular range?
Yes, it is part of the Hager modular system and fits standard enclosures and distribution boards.
How do I test the AED216B for proper functioning?
Press the test button (T) to simulate a trip condition. The breaker should switch off. Reset by moving the lever to ON.
What is the recommended wire size for terminals?
Use 1.5 mm² to 16 mm² copper wire. Strip insulation to 12 mm and tighten to 2 Nm.
Can the AED216B be used in a DC circuit?
No, it is designed for AC circuits only. Using it on DC may cause failure or fire.