| Product Type | Voltage Monitoring Relay |
| Brand | Hager |
| Model | VR10127011 |
| Dimensions (H x W x D) | 90 mm x 36 mm x 65 mm |
| Weight | 0.2 kg |
| Mounting Type | DIN Rail (35 mm) |
| Supply Voltage | 230 V AC, 50/60 Hz |
| Power Consumption | < 3 W |
| Overvoltage Threshold | Adjustable 250–300 V |
| Undervoltage Threshold | Adjustable 170–200 V |
| Output Contacts | 1 x Changeover (SPDT), 16 A / 250 V AC |
| Operating Temperature | -20°C to +60°C |
| Protection Class | IP20 |
| Certifications | CE, EN 60947-1 |
| Maintenance | Clean with a dry cloth; no lubrication required |
| Safety Instructions | Installation only by qualified electrician; disconnect power before servicing |
| Spare Parts Availability | Contact Hager customer service for replacement units |
| Warranty | 2 years |
Frequently Asked Questions - VR10127011 HAGER
What is the Hager VR10127011 used for?
The Hager VR10127011 is a voltage monitoring relay that protects electrical installations from overvoltage and undervoltage conditions.
How do I install the VR10127011?
Mount the relay on a 35 mm DIN rail, connect the supply voltage (230 V AC) according to the wiring diagram, and adjust the thresholds as needed. Only a qualified electrician should perform installation.
What are the adjustable voltage thresholds?
The overvoltage threshold can be set between 250 V and 300 V, and the undervoltage threshold between 170 V and 200 V.
What does the output contact do?
The relay has a single changeover contact (SPDT) rated 16 A / 250 V AC, which can be used to switch a load or signal when a voltage fault occurs.
What is the power consumption of the device?
The power consumption is less than 3 W.
Can the VR10127011 be used in outdoor applications?
No, the device has an IP20 rating, making it suitable for indoor use only in dry environments.
How do I reset the relay after a fault?
The relay automatically resets when the voltage returns to the normal range after a fault, provided the delay time (if adjustable) has elapsed.
What are the dimensions of the Hager VR10127011?
The dimensions are 90 mm (height) x 36 mm (width) x 65 mm (depth).
Is there a test function on the device?
Yes, most Hager voltage relays include a test button to simulate a fault condition and verify operation.
Where can I find spare parts or replacement?
For spare parts or replacement, contact Hager customer service or an authorized distributor.
User questions about VR10127011 HAGER
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
No questions yet. Be the first to ask one.
Download the instructions for your Electrical installation system in PDF format for free! Find your manual VR10127011 - HAGER and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. VR10127011 by HAGER.