BMM500 - Measuring equipment Megger - Free user manual and instructions
Find the device manual for free BMM500 Megger in PDF.
Pick your language and provide your email: we'll send you a specifically translated version.
| Product type | Digital megohmmeter |
| Brand | Megger |
| Model | BMM500 |
| Dimensions (L x W x H) | Approximately 270 x 250 x 150 mm |
| Weight | Approximately 3 kg |
| Power supply | Rechargeable NiMH battery or alkaline batteries (6 x LR14) |
| Test voltage | 250 V, 500 V, 1000 V, 2500 V, 5000 V, 10000 V |
| Insulation measurement range | Up to 10 TΩ |
| Resolution | 1 kΩ to 1 GΩ depending on scale |
| Main functions | Insulation resistance measurement, DC/AC voltage, frequency, resistance, continuity test, PI, DAR |
| Display | Backlit LCD screen with bargraph |
| Internal memory | Up to 1500 results with timestamp |
| Communication interface | USB and Bluetooth (optional) |
| Safety category | CAT IV 600 V / CAT III 1000 V |
| Standards | IEC 61010-1, IEC 61557 |
| Operating temperature | -10 °C to +55 °C |
| Humidity | 90% RH non-condensing |
| Protection rating | IP54 |
| Maintenance and cleaning | Clean with a slightly damp cloth, without solvent. Check the cords regularly. |
| Spare parts and repairability | Contact Megger after-sales service. Repair must be carried out by an authorized technician. |
Frequently Asked Questions - BMM500 Megger
How to turn on the Megger BMM500?
Press the ON/OFF button on the front panel. The device turns on and performs a self-test.
What types of batteries to use?
Use 6 LR14 (C) alkaline batteries or rechargeable NiMH batteries. Do not use lithium batteries.
How to perform an insulation test?
Select the desired test voltage (250 V to 10 kV) using the rotary switch, connect the test leads to the equipment and press the TEST button. Hold it down until the test is complete.
What do PI and DAR mean?
PI (Polarization Index) and DAR (Dielectric Absorption Ratio) are automatically calculated ratios to assess insulation quality. They are measured from tests of a determined duration.
How to download measurement data?
Connect a USB cable to the PC and the device. Use PowerDB software or a terminal emulator to download the records.
The battery does not hold charge, what to do?
Check that the batteries are properly installed. If the problem persists, replace the batteries with new ones. If the device does not turn on, contact technical support.
What is the accuracy of the BMM500?
The accuracy is ±5% of reading ±2 units for insulation resistances and ±2% for voltages.
How to clean the device?
Use a soft, dry cloth or slightly dampened with water. Do not use solvents or abrasive products.
Where to find the complete user manual?
The complete manual is available for free download on the website notice-facile.com in the section dedicated to the Megger BMM500.
How to calibrate the device?
Calibration must be performed by an accredited laboratory. Megger recommends a calibration interval of 12 months. Consult your authorized service center.
User questions about BMM500 Megger
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
No questions yet. Be the first to ask one.
Download the instructions for your Measuring equipment in PDF format for free! Find your manual BMM500 - Megger and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. BMM500 by Megger.