| Product Type | Multifunction Power Meter |
| Brand | Camille Bauer |
| Model | SIRAX BT5100 |
| Mounting Type | Panel mount (96x96 mm cutout) |
| Dimensions (H x W x D) | 96 x 96 x 60 mm |
| Weight | Approx. 0.3 kg |
| Power Supply | 85-265 V AC/DC (50/60 Hz) |
| Power Consumption | < 5 VA |
| Measurement Functions | Voltage, Current, Active/Reactive/Apparent Power, Power Factor, Frequency, Active/Reactive Energy, Harmonics up to 31st |
| Accuracy Class | Class 0.5 for power, Class 0.2 for energy |
| Display | Backlit LCD with multiple screens |
| Communication Interfaces | RS485 Modbus RTU, Pulse output |
| Measurement Inputs | 3-phase voltage (direct up to 480V L-N), 3-phase current (via CTs, secondary 1 or 5 A) |
| Operating Temperature | -10°C to +55°C |
| Storage Temperature | -25°C to +70°C |
| Protection Degree | IP20 (front panel) |
| Overvoltage Category | CAT III (300V) |
| Maintenance | Clean gently with a soft, dry cloth. Avoid liquids. |
| Safety Compliance | IEC 61010-1, EN 50470-1, EN 62052-11 |
| Spare Parts / Repairability | Contact Camille Bauer support for spare parts and repairs. Reparable by authorized service centers. |
| General Information | Multifunction power meter for sub-metering and monitoring in industrial and commercial applications. |
Frequently Asked Questions - SIRAX BT5100 Camille Bauer
What is the SIRAX BT5100 used for?
The SIRAX BT5100 is a multifunction power meter designed for measuring electrical parameters such as voltage, current, power, energy, and harmonics in three-phase systems.
How do I install the SIRAX BT5100?
Install the meter into a 96x96 mm panel cutout. Connect voltage inputs directly (up to 480V L-N) and current inputs via external current transformers (secondary 1A or 5A). Refer to the manual for wiring diagrams.
What communication protocols does it support?
It supports RS485 Modbus RTU for data communication. Additionally, it has a pulse output for energy consumption pulses.
What are the accuracy specifications?
The device offers Class 0.5 for power measurements and Class 0.2 for energy measurements, complying with IEC standards.
Can it measure harmonics?
Yes, it can measure individual harmonics up to the 31st order for both voltage and current.
What is the power supply requirement?
The meter operates on a universal power supply of 85-265 V AC/DC (50/60 Hz) with a consumption of less than 5 VA.
Is the device suitable for outdoor use?
No, the front panel is rated IP20, which is only splash-proof. It should be installed indoors or in a weatherproof enclosure.
How do I reset the energy counters?
Energy counters can be reset via the front panel buttons or through Modbus commands. Consult the manual for detailed instructions.
Where can I find the user manual?
The user manual is available for free download in PDF format from notice-facile.com or the Camille Bauer website.
What should I do if the display shows an error?
Check the wiring connections and power supply. Common errors include phase loss or overvoltage. If the problem persists, contact Camille Bauer support.
User questions about SIRAX BT5100 Camille Bauer