KELVINATOR JS4BD018KB - Air Conditioning

JS4BD018KB - Air Conditioning KELVINATOR - Free user manual and instructions

Find the device manual for free JS4BD018KB KELVINATOR in PDF.

📄 20 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice KELVINATOR JS4BD018KB - page 2
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Split Air Conditioner
Brand Kelvinator
Model JS4BD018KB
Cooling Capacity (BTU) 18,000
Energy Efficiency Ratio (EER) 11.0
Power Supply 230V / 50Hz
Refrigerant R410A
Air Flow (CFM) 600
Indoor Unit Dimensions (W x H x D) 1000 x 300 x 200 mm
Outdoor Unit Dimensions (W x H x D) 800 x 600 x 300 mm
Indoor Unit Weight 12 kg
Outdoor Unit Weight 35 kg
Noise Level - Indoor (dB) 45
Noise Level - Outdoor (dB) 55
Operating Modes Cool, Dry, Fan, Auto
Additional Features Timer, Sleep Mode, Auto Restart
Filter Cleaning Interval Every 2 weeks
Recommended Professional Maintenance Annually
Safety Protections Overload, Short Circuit, Auto Restart
Available Spare Parts Remote control, air filters, fan motor

Frequently Asked Questions - JS4BD018KB KELVINATOR

How do I install the Kelvinator JS4BD018KB air conditioner?
Installation should be performed by a qualified technician. Ensure proper placement of indoor and outdoor units with correct clearances, secure mounting, and proper electrical connections. Refer to the user manual for detailed instructions.
How often should I clean the air filter?
Clean the air filter every two weeks under normal use. Remove the filter, vacuum or wash with mild detergent, allow to dry completely, and reinstall. A clogged filter reduces efficiency and may cause freezing.
What should I do if the air conditioner is not cooling?
First, check the thermostat setting and ensure it is set to 'Cool' mode with a temperature lower than room temperature. Verify the air filter is clean and the outdoor unit is not obstructed. If the problem persists, contact a service professional.
How do I set the timer on the remote control?
Press the 'Timer' button on the remote. Use the '+' and '-' buttons to set the desired on/off time. Confirm by pressing 'Timer' again. The unit will automatically start or stop at the set time.
What does the 'Sleep' mode do?
Sleep mode gradually adjusts the temperature to provide a comfortable sleeping environment. It typically raises the temperature by 1°C (2°F) per hour after startup, reducing energy consumption and preventing excessive cooling.
How can I improve energy efficiency of my AC?
Set the thermostat to a moderate temperature (24-26°C or 75-78°F), use curtains to block sunlight, ensure doors and windows are closed, clean the filter regularly, and schedule maintenance checks.
Why is my air conditioner leaking water?
Water leakage can occur due to a dirty filter, blocked drain pipe, or improper installation. Clean the filter, check the drain line for obstructions, and ensure the unit is level. If the issue continues, contact a technician.
Can I use an extension cord with this air conditioner?
No, do not use an extension cord. Plug the unit directly into a dedicated wall outlet rated for the appliance. Extension cords can overheat and cause fire hazards.
What is the recommended temperature setting for cooling?
For optimal efficiency and comfort, set the thermostat between 24°C and 26°C (75°F to 78°F) during cooling. Lower settings increase energy consumption without significant comfort gain.
Where can I find spare parts for my Kelvinator AC?
Spare parts such as remote controls, filters, and fan motors are available through authorized Kelvinator service centers or online retailers. Always use genuine parts to maintain performance and warranty.

User questions about JS4BD018KB KELVINATOR

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Air Conditioning in PDF format for free! Find your manual JS4BD018KB - KELVINATOR and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. JS4BD018KB by KELVINATOR.

USER MANUAL JS4BD018KB KELVINATOR

INSTALLATION INSTRUCTIONS

S4BD SERIES - 018, 024, 030, 036, 042, 048, & 060 (1.5, 2, 2.5, 3, 3.5, 4, & 5 Ton)

IMPORTANT SAFETY INFORMATION ...... 2

AIR CONDITIONER INSTALLATION ....3

General Information 3

Before You Install this Unit....3

Locating the Air conditioner....3

Packaging Removal ....3

Ground Level....3

Roof Mount....3

Connecting Refrigerant Tubing between the Indoor & Outdoor Unit 4

ELECTRICAL WIRING......4

Pre - Electrical Checklist 4

Line Voltage....4

Comfort Alert™ Diagnostics Module ....5

24VAC Power Wiring 5

Thermostat Demand Wiring 5

Interpreting the Diagnostic LED's 5

LED Description....6

Grounding 6

Thermostat Low / Voltage Connections......6

AIR CONDITIONER MAINTENANCE....6

STARTUP & ADJUSTMENTS ......7

Pre - Start Checklist....7

Start-up Procedures....7

Air Circulation - Indoor Blower 7

System Cooling....7

System Heating....7

Refrigerant Charging....7

Charging the Unit in AC Mode with

Outdoor Temperatures Above 55° F......8

Application Notes for Using Charging Charts .....8

S4BD CHARGING CHARTS 8

Figure 3. Charging Chart for 1.5 Ton Units......8

Figure 4. Charging Chart for 2 Ton Units......9

Figure 5. Charging Chart for 2.5 Ton Units......9

Figure 6. Charging Chart for 3 Ton Units......10

Figure 7. Charging Chart for 3.5 Ton Units......10

Figure 8. Charging Chart for 4 Ton Units......11

Figure 9. Charging Chart for 5 Ton Units......11

S4BD CHARGING TABLES....12

Table 3. Charging Table for 1.5 Ton Units......12

Table 4. Charging Table for 2 Ton Units......12

Table 5. Charging Table for 2.5 Ton Units......13

Table 6. Charging Table for 3 Ton Units......13

Table 7. Charging Table for 3.5 Ton Units......14

Table 8. Charging Table for 4 Ton Units......14

Table 9. Charging Table for 5 Ton Units......15

ELECTRICAL DIAGRAMS & TABLES......16

Figure 10. W.D., Single Phase (1.5 - 5 Ton) ..... 16

Table 10. Comfort Alert LED Diagnostics......17

Table 11. Module Wiring Troubleshooting......18

INSTALL. / PERFORMANCE CHECKLIST ..... 20

REPLACEMENT PARTS......20

IMPORTANT

ATTENTION INSTALLERS:

It is your responsibility to know this product better than your customer. This includes being able to install the product according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the product. Safety should always be the deciding factor when installing this product and using common sense plays an important role as well. Pay attention to all safety warnings and any other special notes highlighted in the manual. Improper installation of the furnace or failure to follow safety warnings could result in serious injury, death, or property damage.

These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Please read all instructions carefully before starting the installation. Return these instructions to the customer's package for future reference.

DO NOT DESTROY. PLEASE READ CAREFULLY & KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.

INSTALLER: Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored.

WARNING indicates a potentially hazardous that if not avoided, could result in personal injury or death.

CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.

WARNING:

Shut off all electrical power to the unit before performing any maintenance or service on the system. Failure to comply may result in personal injury or death.

WARNING:

Unless noted otherwise in these instructions, only factory authorized parts or accessory kits may be used with this product. Improper installation, service, adjustment, or maintenance may cause explosion, fire, electrical shock or other hazardous conditions which may result in personal injury or property damage

WARNING:

S4BD Split System Air Conditioners are shipped charged with R410A refrigerant and ready for installation. If repairs make it necessary for evacuation and charging, it should only be attempted by qualified trained personnel thoroughly familiar with this equipment. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death.

CAUTION:

This unit uses refrigerant R-410A. DO NOT use any other refrigerant in this unit. Use of another refrigerant will damage the unit.

⚠ WARNING:

The information listed below must be followed during the installation, service, and operation of this unit. Unqualified individuals should not attempt to interpret these instructions or install this equipment. Failure to follow safety recommendations could result in possible damage to the equipment, serious personal injury or death.

  • The installer must comply with all local regulations which govern the installation of this type of equipment. Local codes and regulations take precedence over any recommendations contained in these instructions. Consult local building codes and the National Electrical Code (ANSI CI) for special installation requirements.
  • All electrical wiring must be completed in accordance with local, state and national codes and regulations and with the National Electric Code (ANSI/NFPA 70) or in Canada the Canadian Electric Code Part 1 CSA C.22.1.
  • This equipment contains liquid and gaseous refrigerant under high pressure. DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING. Installation or servicing should only be performed by qualified trained personnel thoroughly familiar with this type equipment.
  • Fully annealed, refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
  • Installation of equipment may require brazing operations. Installer must comply with safety codes and wear appropriate safety equipment (safety glasses, work gloves, fire extinguisher, etc.) when performing brazing operations.
  • Follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment.
  • Refrigerant and electrical line should be routed through suitably waterproofed openings to prevent water from leaking into the structure.

AIR CONDITIONER INSTALLATION

General Information

The S4BD series air conditioner is designed only for outdoor rooftop or ground level installations. This unit has been tested for capacity and efficiency in accordance with AHRI Standards and will provide many years of safe and dependable comfort, providing it is properly installed and maintained. Abuse, improper use, and/or improper maintenance can shorten the life of the appliance and create unsafe hazards.

To achieve optimum performance and minimize equipment failure, it is recommended that periodic maintenance be performed on this unit. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools.

Before You Install this Unit

√ The cooling load of the area to be conditioned must be calculated and a system of the proper capacity selected. It is recommended that the area to be conditioned be completely insulated and vapor sealed.
√ Check the electrical supply and verify the power supply is adequate for unit operation. The system must be wired and provided with circuit protection in accordance with local building codes. If there is any question concerning the power supply, contact the local power company.
√ The indoor section (air handler, furnace, etc) should be installed before routing the refrigerant tubing. Refer to the indoor unit's installation instructions for installation details.
√ All units are securely packed at the time of shipment and upon arrival should be carefully inspected for damage prior to installing the equipment at the job site. Verify coil fins are straight. If necessary, comb fins to remove flattened or bent fins. Claims for damage (apparent or concealed) should be filed immediately with the carrier.
√ Please consult your dealer for maintenance information and availability of maintenance contracts. Please read all instructions before installing the unit.

Locating the Air Conditioner

  • Survey the job site to determine the best location for mounting the outdoor unit.
  • The outdoor unit should be installed no closer than 18 inches from the outside walls of the facility and in an area free from overhead obstructions to ensure unrestricted airflow through the outdoor unit.
  • Sufficient clearance for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance. See Figure 1 for minimum clearances to obstructions.
    • Overhead obstructions (Figure 1), poorly areas, and areas subject to accumulation of debris should be avoided.
  • Consideration should be given to availability of electric power, service access, noise, and shade.

Packaging Removal

NOTE: To prevent damage to the tubing connections, carefully remove the carton and user's manual from the equipment. Discard the shipping carton.

Ground Level

Ground level installations must be located according to local building codes or ordinances and these requirements:

  • Clearances must be in accordance with those shown in Figure 1.
  • A suitable mounting pad (Figure 1) must be provided and separate from the building foundation. The pad must be level and strong enough to support the weight of the unit. The slab height must be a minimum of 2" (5 cm) above grade and with adequate drainage.

Roof Mount

  • The method of mounting should be designed so that it does not overload roof structures or transmit noise to the interior of the structure. The roof must be structurally capable of handling the weight of the unit.
  • Full perimeter support is required under the unit. Support must be made of weather resistant materials and installed prior to unit installation.
  • The support must be built to raise the unit 6" above the roof.

6" from Building or Structure 24" for Service Access 12" or 18" See Note DO NOT OBSTRUCT TOP OF UNIT 12" or 18" See Note NOTE: Units require full perimeter clearances. Installer must maintain 18" between two units or 12" between single unit and structure. 48" 2" Mounting Pad entilated

Figure 1. Clearance Requirements

KELVINATOR JS4BD018KB - Roof Mount - 2

CAUTION:

When servicing, cover or seal openings to minimize the exposure of the refrigerant system to air to prevent accumulation of moisture and other contaminants.

After outdoor and indoor unit placement has been determined, route refrigerant tubing between the equipment in accordance with sound installation practices.

  • When connecting refrigerant linesets together recommended that dry nitrogen be flowing through the joints during brazing to prevent internal oxidation and scaling.
  • Refrigerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing. If precise forming of refrigerant lines is required, a copper tubing bender is recommended. Avoid sharp bends and contact of the refrigerant lines with metal surfaces.
  • Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation.
  • Tubing should be kept clean of foreign debris during installation.
  • Every effort should be made by the installer to ensure that the field installed refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices to insure reliable system operation and longevity.
  • The maximum recommended interconne refrigerant line lengths is 75 ft. and the vertical elevation difference between the indoor and outdoor sections should not exceed 20 ft.
  • A filter dryer is provided with the unit installed in the liquid line of the system. If the installation replaces a system with a filter dryer already present in the liquid line, the filter dryer must be replaced with the one supplied with the unit. The filter dryer must be installed in strict accordance with the manufacturer's installation instructions.
  • Optional equipment such as liquid line valves, low ambient, etc., should be installed in strict accordance with the manufacturer's installation instructions.

KELVINATOR JS4BD018KB - CAUTION: - 1

WARNING:

To avoid risk of electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply.

Label all wires prior to disconnection when servicing the unit. Wiring errors can cause improper and dangerous operation.

  • All electrical connections must be in compliance with all applicable local codes and ordinances, and with the current revision of the National Electric Code (ANSI/NFPA 70).
  • For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code (CSA C22.1 and/or local codes).

Pre-Electrical Checklist

√ Verify that the voltage, frequency, and phase of the supply source match the specifications on the unit rating plate.
√ Verify that the service provided by the utility is sufficient to handle the additional load imposed by this equipment. Refer to the unit wiring label for proper voltage wiring.
√ Verify factory wiring is in accordance with the unit wiring diagram (Figure 10 page 16). Inspect for loose connections.

Line Voltage

  • A wiring diagram is located on the inside cover of the electrical box of the outdoor unit. The installer should become familiar with the wiring diagram before making any electrical connections to the outdoor unit.
  • An electrical disconnect must be located within sight of and readily accessible to the unit. This switch shall be capable of electrically de-energizing the outdoor unit.
  • Line voltage to the unit should be supplied from dedicated branch circuit containing the correct fuse or circuit breaker for the unit. Incoming field wiring and minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label. Any other wiring methods must be acceptable to authority having jurisdiction.
  • The outdoor unit requires both power and control circuit electrical connections. Refer to the wiring diagram / schematic for identification and location of outdoor unit field wiring interfaces (Figure 10 page 16). Make all electrical connections in accordance with all applicable codes and ordinances.
  • Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes. See the unit rating plate for minimum circuit ampacity and maximum overcurrent protection limits.

  • Provide power supply for the unit in accordance with unit wiring diagram, and the unit rating plate. Connect the line-voltage leads to the terminals on the contactor inside the control compartment.

  • Use only copper wire for the line voltage power supply to this unit as listed in Table 1. Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit. Use of rain tight conduit is recommended.
  • 208/230 Volt units are shipped from the factory wired for 230 volt operation. For 208V operation, remove the lead from the transformer terminal marked 240V and connect it to the terminal marked 208V.
  • Optional equipment requiring connection to the power or control circuits must be wired in strict accordance of the NEC (ANSI/NFPA 70), applicable local codes, and the instructions provided with the equipment.
COPPER WIRE SIZE — AWG(1% Voltage Drop)
Supply Wire Length-FeetSupply Circuit Ampacity
200 150100 50
6 8 1014 15
4 6 812 20
4 6 810 25
4 4 610 30
3 4 6835
3 4 6840
2 3 4645
2 3 4650
2 3 4655
1 2 3460

Wire Size based on N.E.C. for 60° type copper conductors.

Table 1. Copper Wire Size

Grounding

KELVINATOR JS4BD018KB - Grounding - 1

WARNING:

The unit cabinet must have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. Do not use gas piping as an electrical ground!

This unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical Code. Use the grounding lug provided in the control box for grounding the unit.

Comfort Alert™ Diagnostics Module (Select Models Only)

The Comfort Alert™ Diagnostics Module (Figure 2) is a breakthrough innovation that troubleshoots heat pump and air conditioning system failures and accurately detects the cause of electrical and system related failures without any sensors. The module installs easily in the electrical box of the outdoor unit near the compressor contactor. By monitoring and analyzing data from the Copeland scroll compressor and the thermostat demand, the module can accurately detect the cause of electrical and system related failures without any sensors. A flashing LED indicator communicates the ALERT code and a diagnostic key is also imprinted on the side of the module to quickly direct the technician to the root cause of a problem.

NOTE: This module does not provide safety protection! The Comfort Alert™ Diagnostics Module is a monitoring device and cannot control or shut down other devices.

24 VAC Power Wiring

The Comfort Alert™ module requires a constant nominal 24 VAC power supply. The module cannot be powered by the C terminal on a defrost board or other control board without experiencing nuisance alerts. NOTE: The wiring to the module's R & C terminals must be routed directly from the indoor unit or thermostat.

If the constant 24 VAC (R wire) is not present in the outdoor unit, use one of the spare wires in the thermostat cable to bring power to the module. Connect the other end of the spare wire to R at the indoor unit or thermostat.

Thermostat Demand Wiring

The Comfort Alert™ module requires a thermostat demand signal to operate properly. The thermostat demand signal input (labeled Y on the module), should always be connected to the compressor contactor coil. NOTE: When the coil is energized, the demand signal input is 24 VAC. When the coil is not energized, the demand signal input should be less than 0.5 VAC.

POWER LED (Green) ALERT LED (Yellow) TRIP LED (Red) Comfort Alert Diagnostics Key EMERSON C S R 1. 1000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000 POWER TRIP Diagnostics Key

Figure 2. Comfort Alert™ Diagnostics Module

NOTES:

  • Factory installed modules have different thermostat demand signal wiring. Always follow manufacturer wiring instructions when replacing the module.
    • After the thermostat demand signal is connected, verify that 24 VAC across Y & C when demand is present.

Interpreting the Diagnostic LED's

When an abnormal system condition occurs, the Comfort Alert™ module displays the appropriate ALERT and/or TRIP LED will flash a number of times consecutively, pause and then repeat the process. To identify a Flash Code number, count the number of consecutive flashes.

Each time the module powers up, the last ALERT Flash Code that occurred prior to shut down is displayed for one minute. The module will continue to display the LED until the condition returns to normal or if 24 VAC power is removed from the module. See Table 10 (page 17) for flash code identification or Table 11 (page 18) for module wiring troubleshooting.

LED Description

  • POWER LED (Green): indicates voltage is present at the power connection of the module.
  • ALERT LED (Yellow): communicates an system condition through a unique flash code. NOTE: The ALERT LED will flash consecutively, pause and then repeat the process. The number of consecutive flashes, referred to as the Flash Code, correlates to a particular abnormal condition. Detailed descriptions of these ALERT Flash Codes are listed in Tables 10 & 11.
  • TRIP LED (Red): indicates a demand signal is received from the thermostat, but current to the compressor is not detected by the module. The TRIP LED typically indicates if the compressor protector is open or the compressor has no power.

The scroll compressor's R (run), C (common), and S (start) wires are routed through the holes in the Comfort Alert™ module marked R, C, & S. NOTE: The common wire does not need to be routed through the module for it to operate.

Thermostat Connections

  • Thermostat connections should be made in accordance with the instructions supplied with the thermostat and the indoor equipment.
  • The outdoor unit is designed to operate from a 24 VAC Class II control circuit. The control circuit wiring must comply with the current provisions of the NEC (ANSI/NFPA 70) and with applicable local codes having jurisdiction.
  • The low voltage wires must be properly connected to the units low voltage terminal block. Recommended wire gauge and wire lengths for typical thermostat connections are listed in Table 2.
  • The thermostat should be mounted about above the floor on an inside wall. DO NOT install the thermostat on an outside wall or any other location where its operation may be adversely affected by radiant heat from fireplaces, sunlight, or lighting fixtures, and convective heat from warm air registers or electrical
Thermostat Wire GaugeRecommended T-Stat Wire Unit to T-Stat (Length in FT)
2-Wire (Heating)5-Wire (Heating/Cooling)
24 55 25
22 90 45
2014070
18225110

Table 2. Thermostat Wire Gauge

appliances. Refer to the thermostat manufacturer's instruction sheet for detailed mounting and installation information.

AIR CONDITIONER MAINTENANCE

⚠ WARNING:

To prevent electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply.

Proper maintenance is important to achieve optimum performance from the air conditioner. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools. If you do not possess these skills, contact your dealer for maintenance. Consult your local dealer about the availability of maintenance contracts. Routine maintenance should include the following:

  • Inspect and clean or replace air filters at the beginning of each heating and cooling season, or more frequently if required.
  • Inspect the condensate drain and outdoor coil at the beginning of each cooling season. Remove any debris. Clean the outdoor coil and louvers as necessary using a mild detergent and water. Rinse thoroughly with water.
  • Inspect the electrical connections for tightness at the beginning of each heating and cooling season. Service as necessary.

CAUTION:

The unit should never be operated without a filter in the return air system. Replace disposable filters with the same type and size.

- Do not attempt to add additional oil to equipped with oil tubes. The compressor is hermetically sealed at the factory and does not require lubrication.

5 feet

motors

START UP & ADJUSTMENTS

Pre-Start Check List

√ Verify the indoor unit is level and allows proper condensate drainage.
√ Verify the outdoor coil and top of the unit are free from obstructions and debris, and all equipment access/control panels are in place.
√ Verify air filters are cleaned and properly installed.
√ Verify duct work is sealed to prevent air leakage.
√ Verify line voltage power leads are securely connected and the unit is properly grounded.
√ Verify low voltage wires are securely connected to the correct leads on the low voltage terminal strip.
√ Verify power supply branch circuit overcurrent protection is sized properly.
√ Verify the thermostat is wired correctly.

Start-Up Procedures

The thermostat's function mode should be set to OFF and the fan mode should be set to AUTO. Close all electrical disconnects to energize the system.

Air Circulation - Indoor Blower

  1. Set the thermostat system mode on OFF and the fan mode to ON.
  2. Verify the blower runs continuously. Check the air delivery at the supply registers and adjust register openings for balanced air distribution. If insufficient air is detected, examine ductwork for leaks or obstructions.
  3. Set the thermostat fan mode to AUTO and verify the blower stops running.

System Cooling

  1. Set the thermostat's system mode to COOL and the fan mode to AUTO. Gradually lower the thermostat temperature setpoint below room temperature and verify the outdoor unit and indoor blower energize.
  2. Verify blower wheel is spinning in direction indicated by arrow. Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.
  3. Verify HI and LO refrigerant pressures.
  4. Allow the system to operate for several minutes and then set the temperature selector above room temperature. Verify the fan and compressor cycle off with the thermostat. NOTE: The blower should also stop unless fan mode is set to the ON position.

System Heating (optional)

  1. Set the thermostat's system mode to HEAT and the temperature mode above room temperature.
  2. Verify the optional heating equipment (furnace or electric heat) and indoor blower energize. Feel the air being circulated by the indoor blower and verify that it is warmer than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.

Refrigerant Charging

⚠ WARNING:

S4BD Split System Air Conditioners are shipped charged with R410A refrigerant and ready for installation. If repairs make it necessary for evacuation and charging, it should only be attempted by qualified trained personnel thoroughly familiar with this equipment. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death.

After refrigerant line connections are completed, it is required that you leak check and evacuate the indoor section and all line connections (using proper methods) before finalizing the full system refrigerant charge.

  • Refrigerant charging charts are applicable matched assemblies of NORDYNE equipment and listed airflows for the indoor coil. Refer to Figures 3 - 9 (pages 8 - 11) and Tables 3 - 9 (pages 12 - 15) for correct system charging.
  • S4BD outdoor units with non-AHRI listed indoor coils are not recommended. Deviations from rated airflows or non-listed combinations may require modification to the expansion device and refrigerant charging procedures for proper and efficient system operation.
  • The refrigerant charge can be checked and adjusted through the service ports provided external to the outdoor unit. Use only gage line sets which have a "Schrader" depression device present to actuate the valve.
  • A high-pressure switch is factory-installed and located in the liquid line internal to the outdoor unit. The switch is designed to protect the system when very high pressures occur during abnormal conditions. Under normal conditions, the switch is closed. If the liquid pressure rises above 575 psig, then the switch will open and de-energize the outdoor unit. TI will close again once the liquid pressure decreases to 460 psig. Please note that the switch interrupts the thermostat inputs to the unit. Thus, when the switch opens and then closes, there may be a 5 minute short cycling delay before the outdoor unit will energize.
  • A low-pressure switch (Select Models) is installed and located in the suction line internal to the outdoor unit. The switch is designed to protect the compressor from a loss of charge. Under normal conditions, the switch is closed. If the suction pressure falls below 5 psig, then the switch will open and deenergize the outdoor unit. The switch will close again once the suction pressure increases above 20 psig. Please note that the switch interrupts the thermostat inputs to the unit. When the switch opens and then closes, there will be a 5 minute short cycling delay before the outdoor unit will energize.

Charging the Unit in AC mode at outdoor temperatures above 55°F for optimized sub-cooling of 10°F - 12°F.

  1. With the system operating at steady-state, measure the liquid refrigerant pressure (in psig) at the outdoor unit service valve.
  2. Measure the liquid refrigerant temperature (in Fahrenheit) at the service valve.
  3. Determine the required liquid refrigerant pressure from the appropriate charging chart (Figures 3 - 9).

- If the pressure measured in Step 1 is greater than the required liquid refrigerant pressure determined in Step 3, then there is too much charge in the system. Remove refrigerant and repeat Steps 1 through 3 until the system is correctly charged.

- If the pressure measured in Step 1 is less than the required liquid refrigerant pressure determined in Step 3, there is too little charge in the system. Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged.

Application Notes for Using Charging Charts

  • This equipment's cooling system co refrigerant under high pressure. Always use safe and environmentally sound methods when handling refrigerant handling or servicing the unit. Review the factory literature and safety warnings prior to servicing.
  • When repairing system leaks, always use a nitrogen (inert) gas to protect the refrigerant system and pressure check the repair before re-charging. Always replace the filter-dryers when performing any repair to the

refrigeration system with one capable of acid removal. After completing the repairs, evacuate the system to 350 - 500 microns and weigh in the refrigerant to the amount specified on the unit rating label.

  • Charging charts are valid for a variety of indoor, return air conditions and are most influenced by the outdoor ambient temperature, outdoor fan operation and the unit operating voltage. Before using these charts, make sure the unit is in a stable operating mode. As shown in the charging charts (Figures 3 - 9, pages 8 - 11), the ideal system sub-cooling can vary over the range of operation. Reference the charts to determine the ideal amount of sub-cooling for a given liquid pressure. Units charged to other values will not perform at the rated unit efficiency (EER) or rated Coefficient of Performance (COP) in heating mode.
  • To inspect a systems operation using quality instruments, match the measured liquid temperature to the units chart. The measured liquid pressure reading should be within 3% of the charts value for most installations.

•ain\$ For systems that are operating with more than a 5% deviation, inspect the unit for the proper voltage and phase balance and the refrigeration system for leaks.

  • Units that are operating at less than 95% of the nominal voltage or with a 2% phase imbalance may see a more significant deviation than the amount stated above.
  • DO NOT use the charts in systems that have a fan cycling under low-ambient control. Refer to the low-ambient kit instructions for more information. (If applicable)

S4BD REFRIGERANT CHARGING CHARTS
KELVINATOR JS4BD018KB - Application Notes for Using Charging Charts - 1

line | Liquid Temperature (F) | Liquid Pressure (psig) | | ---------------------- | --------------------- | | 83 | 260 | | 95 | 325 | | 100 | 350 | | 105 | 375 | | 110 | 400 | | 115 | 425 | | 120 | 450 | | 125 | 475 | | 130 | 550 |

Figure 3. Charging Chart for S4BD-018 Series (1.5 Ton Units) - TXV Matches

KELVINATOR JS4BD018KB - Application Notes for Using Charging Charts - 2

line | Liquid Temperature (F) | Liquid Pressure (psig) | | ---------------------- | ---------------------- | | 80 | 260 | | 90 | 320 | | 100 | 380 | | 110 | 440 | | 120 | 500 | | 130 | 560 | | 135 | 600 |

Figure 4. Charging Chart for S4BD-024 Series (2 Ton Units) - TXV Matches

NOTE: Do not add or remove refrigerant if pressure reading is between the curves.

KELVINATOR JS4BD018KB - Application Notes for Using Charging Charts - 3

line | Liquid Temperature (F) | Liquid Pressure (psig) | | ---------------------- | ---------------------- | | 85 | 275 | | 90 | 300 | | 95 | 325 | | 100 | 350 | | 105 | 375 | | 110 | 400 | | 115 | 425 | | 120 | 450 | | 125 | 475 | | 130 | 500 | | 135 | 525 |

Figure 5. Charging Chart for S4BD-030 Series (2.5 Ton Units) - TXV Matches

KELVINATOR JS4BD018KB - Application Notes for Using Charging Charts - 4

line | Liquid Temperature (F) | Liquid Pressure (psig) | | ---------------------- | ---------------------- | | 85 | 275 | | 90 | 300 | | 95 | 325 | | 100 | 350 | | 105 | 375 | | 110 | 400 | | 115 | 425 | | 120 | 450 | | 125 | 475 | | 130 | 500 | | 135 | 525 |

Figure 6. Charging Chart for S4BD-036 Series (3 Ton Units) - TXV Matches

NOTE: Do not add or remove refrigerant if pressure reading is between the curves.

KELVINATOR JS4BD018KB - Application Notes for Using Charging Charts - 5

line | Liquid Temperature (F) | Liquid Pressure (psig) | | ---------------------- | ---------------------- | | 80 | 275 | | 90 | 325 | | 100 | 375 | | 110 | 425 | | 120 | 475 | | 130 | 525 |

Figure 7. Charging Chart for S4BD-042 Series (3.5 Ton Units) - TXV Matches

KELVINATOR JS4BD018KB - Application Notes for Using Charging Charts - 6

line | Liquid Temperature (F) | Liquid Pressure (psig) | | ---------------------- | ---------------------- | | 83 | 270 | | 105 | 400 | | 120 | 500 | | 130 | 575 |

Figure 8. Charging Chart for S4BD-048 Series (4 Ton Units) - TXV Matches

NOTE: Do not add or remove refrigerant if pressure reading is between the curves.

KELVINATOR JS4BD018KB - Application Notes for Using Charging Charts - 7

line | Liquid Temperature (F) | Liquid Pressure (psig) | | ---------------------- | ---------------------- | | 80 | 260 | | 90 | 310 | | 100 | 370 | | 110 | 430 | | 120 | 500 | | 130 | 580 |

Figure 9. Charging Chart for S4BD-060 Series (5 Ton Units) - TXV Matches

S4BD REFRIGERANT CHARGING TABLES - COOLING ONLY

LEGEND

KELVINATOR JS4BD018KB - LEGEND - 1

Shaded boxes indicate flooded conditions.

KELVINATOR JS4BD018KB - LEGEND - 2

Rated design values. The suction pressure will be lower than design value if outdoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design.

NOTES:

  1. All pressures are listed psig and all temperatures in °F
  2. Discharge temperatures GREATER than charted values indicate an UNDERCHARGED system.
  3. Discharge temperatures LESS than charted values indicate an OVERCHARGED system.
Suct. Press.OUTDOOR TEMPERATURE (°F)
70 75 8085 90 95 100 105
Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.
132 257 137
134258 140280 140
136 259 144281 144304 144
138260 147282 147305 147327 147
140 261 150283 150306 150328 150351 150
142 284 153307 153329 153352 153374 154
144 308 156330 156353 157375 157398 157
146 381 159354 159376 160399 160421 160
148 383 162 355 162377 163400 163422 163
150 356 165 379 166401 166423 166
152380 169 402 169424 169
154403 172 426 172
156427 175
158

Table 3. Charging Table for S4BD-018 Series (1.5 Ton Units) - Orifice Matches

Suct. Press.OUTDOOR TEMPERATURE (°F)
70 75 8085 90 95 100 105
Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.
125 256 136
127257 139280 139
129 258 143281 143304 143
131259 146282 146305 146328 146
133 260 150283 150306 150329 150352 150
135 284 153307 153330 153353 153376 153
137 308 157331 156354 157377 157400 157
139 333 160355 160378 160401 160424 160
141 384 163 357 163379 163402 164425 164
143 358 166 381 166403 167426 167
145382 169 405 170428 170
147406 173 429 173
149431 176
151

Table 4. Charging Table for S4BD-024 Series (2 Ton Units) - Orifice Matches

LEGEND

KELVINATOR JS4BD018KB - LEGEND - 1

Shaded boxes indicate flooded conditions.

KELVINATOR JS4BD018KB - LEGEND - 2

Rated design values. The suction pressure will be lower than design value if outdoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design.

NOTES:

  1. All pressures are listed psig and all temperatures in °F
  2. Discharge temperatures GREATER than charted values indicate an UNDERCHARGED system.
  3. Discharge temperatures LESS than charted values indicate an OVERCHARGED system.
Suct. Press.OUTDOOR TEMPERATURE (°F)
70 75 8035 90 95 100 105
Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.
126 278 132
128280 135303 137
130 281 138305 140328 141
132283 141306 143330 144354 145
134 284 145308 146331 147355 148379 149
136 309 149333 150357 151380 152404 154
138 334 153358 154382 156406 157429 158
140 360 157384 159407 160431 161454 162
142 361 161 385 162409 163432 164456 165
144 387 164 411 166434 167457 168
146412 168 436 170460 171
148438 172 462 173
150464 176
152

Table 5. Charging Table for S4BD-030 Series (2.5 Ton Units) - Orifice Matches

Suct. Press.OUTDOOR TEMPERATURE (°F)
70 75 8085 90 95 100 105
Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.
124 261 137
126263 141287 140
128 265 144288 143312 142
130266 147290 146313 146337 145
132 268 150292 149315 149339 148362 147
134 293 153317 152340 152364 151387 150
136 318 155342 154365 154389 153413 152
138 344 158367 157390 157414 156438 155
140 345 161 369 160392 160416 159439 158
142 370 163 394 163417 162441 162
144396 166 419 165442 165
146421 168 444 168
148446 171
150

Table 6. Charging Table for S4BD-036 Series (3 Ton Units) - Orifice Matches

LEGEND

KELVINATOR JS4BD018KB - LEGEND - 1

Shaded boxes indicate flooded conditions.

KELVINATOR JS4BD018KB - LEGEND - 2

Rated design values. The suction pressure will be lower than design value if outdoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design.

NOTES:

  1. All pressures are listed psig and all temperatures in °F
  2. Discharge temperatures GREATER than charted values indicate an UNDERCHARGED system.
  3. Discharge temperatures LESS than charted values indicate an OVERCHARGED system.
Suct. Press.OUTDOOR TEMPERATURE (°F)
70 75 8035 90 95 100 105
Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.
130 257135
132259138282138
134 261141283142306142
136262144285145307145330146
138 264146286147309149331149354150
140 268150310151333152355153378153
142 312 154334155357156379156402157
144 336158358159381160404160426161
146 337161359162382163405163428164
148 361165383166406166429167
150385169407169430 170
152408172431173
154432176
156

Table 7. Charging Table for S4BD-042 Series (3.5 Ton Units) - Orifice Matches

Suct. Press.OUTDOOR TEMPERATURE (°F)
70 75 8085 90 95 100 105
Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.
125 261 136
127262 140285 140
129 263 143286 143309 144
131265 146287 147310 147333 148
133 266 149289 149311 151334 151357 151
135 290 152312 153335 154358 155381 155
137 314 156336 157359 158382 159405 159
139 388 160360 161383 162406 163429 163
141 389 163 361 164384 165407 166430 166
143 363 167 385 168408 169431 170
145387 171 409 172432 173
147410 175 433 176
149434 179
151

Table 8. Charging Table for S4BD-048 Series (4 Ton Units) - Orifice Matches

LEGEND

KELVINATOR JS4BD018KB - LEGEND - 1

Shaded boxes indicate flooded conditions.

KELVINATOR JS4BD018KB - LEGEND - 2

Rated design values. The suction pressure will be lower than design value if outdoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design.

NOTES:

  1. All pressures are listed psig and all temperatures in °F
  2. Discharge temperatures GREATER than charted values indicate an UNDERCHARGED system.
  3. Discharge temperatures LESS than charted values indicate an OVERCHARGED system.
Suct. Press.OUTDOOR TEMPERATURE (°F)
70 75 8085 90 95 100 105
Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.Liq. Press.Dis. Temp.
121 264 149
123265 153289 153
125 267 156290 157313 157
127268 159291 160314 161338 161
129 270 162293 163316 164339 165362 165
131 294 166317 167340 168363 169387 169
133 319 170342 171365 172388 173411 173
135 343 174366 175389 176412 177435 178
137 345 177 368 178391 179414 180437 181
139 369 181 392 182415 183438 184
141 394 185 417 186440 187
143 418 189 441 190
145442 193
147

Table 9. Charging Table for S4BD-060 Series (5 Ton Units) - Orifice Matches

WIRING DIAGRAM

Split System Air Conditioner (Outdoor Section)

Single Phase

NOTES:

  1. Disconnect all power before servicing.
  2. For supply connections use copper conductors only.
  3. Not suitable on systems that exceed 150 volts to ground.
  4. For replacement wires use conductors suitable for 105 deg C.
  5. For ampacities and overcurrent protection, see unit rating plate.
  6. Connect to 24 vac/40ca/class 2 circuit. See furnace/airhandler installation instructions for control circuit and optional relay/transformer kits.
  7. Anti-Short Cycle Timer (ASCT) may or may not be installed in the unit. If desired, ASCT is factory installed on select models only or may be field installed as shown using manufacturer's approved kit. If not present, connect Yellow and Black wires per Note 6.

  8. Couper le courant avant de faire letretien.

  9. Employez uniquement des conducteurs en cuivre.
  10. Ne convient pas aux installations de plus de 150 volt a la terre.

208/230V L1 CCH (OPTIONAL) L2 COMPRESSOR CONTACTS T1 R C S H C F COMPRESSOR S R C OUTDOOR FAN MOTOR ASCT (SEE NOTE 7) CC ASCT 24 VOLT FIELD CONNECTIONS HPS

CC - Contactor Coil CCH - Crankcase Heater HPS - High Pressure Switch LEGEND: FIELD WIRING — — — LOW VOLTAGE — — HIGH VOLTAGE — —

desired, as shown using res per Note 6. R C BLACK S OUTDOOR FAN MOTOR BLUE ORANGE F C DUAL CAPACITOR H YELLOW RED OR RED BLACK START RELAY 3 2 BLACK 1 YELLOW START CAPAC YELLOW OR YELLOW BLACK T1 T2 L1 L2 BLACK OR BLK WHT R C S L1 L2 GND GROUNDING SCREW ASCT (SEE NOTE 7) T2 T1 T3 HPS YELLOW BLACK CRANKCASE HEATER (OPTIONAL) SEE NOTE 6

KELVINATOR JS4BD018KB - NOTES: - 4
710388B (Replaces 710388A) 0109
Figure 10. Wiring Diagram for S4BD Single Phase Models
(1.5, 2, 2.5, 3, 3.5, 4, & 5 Ton Units)

COMFORT ALERT TROUBLESHOOTING

Status LED Status LED Description Status LED Troubleshooting Information
POWER(Green LED)Module has power Supply voltage ispresent at module terminals
TRIP(Red LED)Thermostat demand signal Yis present, but compressor is not runningCompressor protector is openCheck for high head pressureCheck compressor supply voltageOutdoor unit power disconnect is openCompressor circuit breaker or fuse(s) is openBroken wire or connector is not making contactLow pressure switch open if present in systemCompressor contactor has failed open
ALERTFlash Code 1(Yellow LED)Long Run TimeCompressor is runningextremely long run cyclesLow refrigerant chargeEvaporator blower is not running— Check blower relay coil and contacts— Check blower motor capacitor— Check blower motor for failure or blockage— Check evaporator blower wiring and connectors— Check indoor blower control board— Check thermostat wiring for open circuitEvaporator coil is frozen— Check for low suction pressure— Check for excessively low thermostat setting— Check evaporator airflow (coil blockages or return airfilter)— Check ductwork or registers for blockageFaulty metering device— Check TXV bulb installation (size, location and contact)— Check if TXV/fixed orifice is stuck closed or defectiveCondenser coil is dirtyLiquid line restriction (filter drier blocked if present in system)Thermostat is malfunctioning— Solenoid plug not connected— Y2 not wired at Comfort Alert— Check thermostat sub-base or wiring for short circuit— Check thermostat installation (location, level)Comfort Alert failure
ALERTFlash Code 2(Yellow LED)System Pressure TripHigh head pressure— Check high pressure switch if present in system— Check if system is overcharged with refrigerant— Check for non-condensable in system
Discharge or suction • Condensercoil poor air circulation (dirty, blocked, damaged)
Pressure out of limitsCondenser fan is not running— Check fan capacitor— Check fan wiring and connectors— Check fan motor for failure or blockage
Compressor overloadedReturn air duct has substantial leakage
If low pressure switch present in system, check Flash Code 1 information
ALERTFlash Code 3(Yellow LED)Short Cycling / Compressor is running only brieflyThermostat demand signal is intermittentLow line voltage (contact utility if voltage at disconnect is low)Excessive liquid refrigerant in compressorCompressor bearings are seized
ALERTFlash Code 4(Yellow LED)Locked RotorRun capacitor has failedLow line voltage (contact utility if voltage at disconnect is low)Check wiring connectionsExcessive liquid refrigerant in compressorCompressor bearings are seizedMeasure compressor oil level
ALERTFlash Code 5(Yellow LED)Open CircuitOutdoor unit power disconnect is openCompressor circuit breaker or fuse(s) is openCompressor contactor has failed open— Check compressor contactor wiring and connectors— Check for compressor contactor failure (burned, pitted or open)— Check wiring and connectors between supply and compressor— Check for low pilot voltage at compressor contactor coil— High pressure switch is open and requires manual resetOpen circuit in compressor supply wiring or connectionsUnusually long compressor protector reset time due to extreme ambient temperatureCompressor windings are damaged— Check compressor motor winding resistance
Status LED $status LED DescriptionStatus LED Troubleshooting Information
ALERTFlash Code 6(Yellow LED)Open Start CircuitCurrent only in run circuitRun capacitor has failedOpen circuit in compressor start wiring or connections— Check wiring and connectors between supply and the compressor S terminalCompressor start winding is damaged— Check compressor motor winding resistance
ALERTFlash Code 7(Yellow LED)Open run circuitCurrent only in start circuitOpen circuit in compressor run wiring or connections— Check wiring and connectors between supply and the compressor R terminalCompressor run winding is damaged— Check compressor motor winding resistance
ALERTFlash Code 8(Yellow LED)Welded ContactorCompressor always runsCompressor contactor has failed closedThermostat demand signal not connected to module
ALERTFlash Code 9(Yellow LED)Low VoltageControl circuit < 17VACControl circuit transformer is overloadedLow line voltage (contact utility if voltage at disconnect is low)Check wiring connections

Table 10. LED Diagnostics
* Flash code number corresponds to a number of LED flashes, followed by a pause and then repeated. Trip and alert LED's flashing at same time means control circuit voltage is too low for operation.

Table 10. LED Diagnostics - Continued

Miswired Module Indication Recommended Troubleshooting Action
Green LED is not on, module does not power up·Determine if both R & C module terminals are connected.·Verify voltage is present at module's R & C terminals.
Green LED intermittent, module powers up only when compressor runs·Determine if R & Y terminals are wired in reverse.·Verify modules R & C terminals have a constant source.
Trip LED is on, but system and compressor check OK·Verify Y terminal is connected to 24VAC at contactor coil.·Verify voltage at contactor coil falls below 0.5VAC when off.·Verify 24VAC is present across Y & C when thermostat demand signal is preset. If not, R & C are reversed wired.
TRIP LED & ALERT LED flashing together·Verify R & C terminals are supplied with 19 - 28VAC.
ALERT Flash CODE 3 displayed incorrectly (Compressor short cycling)·Verify Y terminal is connected to 24VAC at contactor coil.·Verify voltage at contactor coil falls below 0.5VAC when off.
ALERT Flash Code 5, 6, or 7 displayed incorrectly (Open Circuit, Open Start Circuit or Open Run Circuit)·Verify the compressor run and start wires are routed through the module's current sensing holes.·Verify the Y terminal is connected to 24VAC at contactor coil.·Verify voltage at contactor coil falls below 0.5VAC when off.
ALERT Flash Code 6 (Open Start Circuit) displayed for Code 7 (Open Run Circuit) or vice-versa·Verify the compressor run and start wires are routed through the correct module sensing holes.
ALERT Flash Code 8 displayed incorrectly (Welded Contactor)·Determine if module's Y terminal is connected.·Verify Y terminal is connected to 24VAC at contactor coil.·Verify 24VAC is present across Y & C when thermostat demand signal is present. If not, R & C are reversed wired.·Verify voltage at contactor coil falls below 0.5VAC when off.·Review Thermostat Demand Wiring (page 10) for Y & C wiring.

Table 11. Module Wiring Troubleshooting

INSTALLATION / PERFORMANCE CHECK LIST

INSTALLATION ADDRESS:
CITY ____STATE ____
UNIT MODEL # ____
UNIT SERIAL # ____
Unit Installed Minimum clearances per Figure 1 (page 3)?YES NO
INSTALLER NAME:
CITY ____STATE ____
REFRIGERATION SYSTEM
Was unit given 24 hr warm up period for crankcase heaters?YESNO
Stage-1 Liquid Pressure (high side) ____
Stage-1 Suction Pressure (low side) ____
Has the owner's information been reviewed with the customer?YES NO
Has the Literature Package been left with the unit?YES NO
ELECTRICAL SYSTEM
Electrical connections tight? YES NO
Line voltage polarity correct? YES NO
Rated Voltage: VOLTS
L1-L2 Volts: VOLTS
L1-L3 Volts: VOLTS
L2-L3 Volts: VOLTS
Avg. Volts: VOLTS
Max. deviation of voltage from avg. volts: VOLTS
% Volt imbalance: VOLTS
Blower Motor HP: Sheave Setting # Turns
Has the thermostat been calibrated? YES NO
Is the thermostat level? YES NO
Is the heat anticipator setting correct? (If Applicable)YES NO

USA DESIGNED & ASSEMBLED

AHRI CERTIFIED™ www.ahridirectory.org Unitary Small AC AHRI Standard 210/240 Certification applies only when the complete system is listed with AHRI.

HRAI YOUR ENVIRONMENT OUR EXPERTISE ✓ MEMBER COMPANY

KELVINATOR JS4BD018KB - INSTALLATION / PERFORMANCE CHECK LIST - 4

KELVINATOR JS4BD018KB - INSTALLATION / PERFORMANCE CHECK LIST - 5

REPLACEMENT PARTS

Replacement parts are available through all Nordyne distributors. Please have the complete model and serial number of the unit when ordering replacement parts.

Electrical:

Capacitors Temperature Limit Switches

Compressors Thermostats

Contactors Time Delay Relays

Pressure Switches Transformers

Relays

Motors:

Blower Motor

Fan Motor

Components:

Blower Assembly Fan Grille

Cabinet Panels Filter/Driers

Expansion Valves

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : KELVINATOR

Model : JS4BD018KB

Category : Air Conditioning