ZB110L1 - Ventilation domestique BROAN - Free user manual and instructions
Find the device manual for free ZB110L1 BROAN in PDF.
User questions about ZB110L1 BROAN
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Ventilation domestique in PDF format for free! Find your manual ZB110L1 - BROAN and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. ZB110L1 by BROAN.
USER MANUAL ZB110L1 BROAN
READ AND SAVE THESE INSTRUCTIONS
Installer: leave this guide with homeowner.
Register your product online at www.broan.com/register.
ZB80L1 · ZB110L1
X2 | Multi-Speed Ventilation
Fan with Dimmable Light
INSTALLATION GUIDE

natural_image
Technical line drawing of a mechanical assembly with internal components and mounting brackets (no text or symbols)Easy installation in both new construction and retrofit
Table of Contents
Warnings and Cautions 2
Typical Installation 2
New Construction Installation 3
Retrofit Installation 7
Operation 12
Cleaning and Maintenance 12
Troubleshooting 12
Service Parts 13
Warranty 13
WARNING


TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
- Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed in the warranty.
- Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
- Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.
- Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer's guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
- When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
- Ducted fans must always be vented to the outdoors.
- Use only ON/OFF switch, mechanical timer or relay-switched control.
- Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch circuit.
- This unit must be grounded.
CAUTION

- For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
- This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up. DO NOT MOUNT THIS PRODUCT IN A WALL.
- To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
- Please read specification label on product for further information and requirements.
NOT FOR USE IN A COOKING AREA
Do not install above or inside this area

text_image
Floor 45°45° Cooking EquipmentTypical Installation
• Installation is the same for:

Joists

I-Joists

Trusses

• Fits in 2" x 8" ceiling construction.
- Infinitely adjust the fan position between joists from 14" to 24" on center.
- Do not install this fan in a ceiling thermally insulated to a value greater than R40.

text_image
INSULATION* (Place around and over Fan Housing.) FAN HOUSING POWER CABLE* Seal gaps around Housing. ROUND DUCT* *Purchase separately. Insulation* (Place around and over Fan Housing.) ROOF CAP* (with built-in damper) Keep duct runs short. OR Seal duct joints with tape. ROUND ELBOWS* WALL CAP* (with built-in damper)The ducting from this fan to the outside of the building has a strong effect on the air flow, noise and energy use of the fan. Use the shortest, straighest duct routing possible for best performance, and avoid installing the fan with smaller ducts than recommended. Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing ducts may not achieve their rated airflow.
6-inch round rigid metal duct is recommended for best performance.
New Construction Installation
Tools needed
• Power screwdriver with a Phillips bit
- Phillips screwdriver
- Flathead screwdriver
- Pliers
- Wire insulation stripper
- Wire cutter
Materials needed
- 6" round metal ducting recommended for best performance.
Use of other ducting is acceptable but may impact performance. - Roof cap or wall cap (built-in damper recommended)
- Tape to seal duct connections
• Electrical wiring and supplies per local code requirements
1 Remove Packaging

Parts Bag holds Knockout Plate and six (6) screws

text_image
Remove Instruction SheetPunch out Mask from packaging. See Step 6.

natural_image
Abstract geometric diagram with interlocking shapes and arrows, no text or symbols present2 Install Mounting Frame

text_image
II nting ne
text_image
Diagram showing a drill press setup with labeled components and directional arrows indicating movement or force.New Construction Installation
3 Snap-in and
Secure Housing

text_image
and sing 1 2 snap! 3 Screws from Parts Bag 4 Position Housing between joists and crimp channel on both sides of Mounting Frame to lock Housing in place. Do not crimp Housing.4 Attach Duct Connector and Ducting

text_image
Top and bottom flanges go outside Housing Insert tab into slot inside Housing 1
text_image
2 Screw from Parts Bag
text_image
6" Ducting Tape 3 4" Ducting Tape Tape 6" to 4" Reducer provided in select modelsNew Construction Installation
5 Connect Wires and Install Knockout Plate
- Run 120VAC electrical wiring to the installation location.
- Use proper UL-approved connectors to secure wiring to the Knockout Plate provided in Parts Bag.
- Connect wires as shown in wiring diagram.

text_image
Attach cable clamps to Knockout Plate. Knockout Plate mounts to outside of Housing and may be oriented as desired. Connect wires
text_image
③ ④ Screw from Parts Bag
flowchart
graph TD
A["Light SWITCH"] --> B["MANUAL ON"]
B --> C["14/2"]
C --> D["BLK BLU"]
D --> E["LIGHT WHT"]
F["FAN SWITCH"] --> G["BLK"]
G --> H["RED"]
H --> I["BLK BLK"]
I --> J["FAN WHT"]
K["LINE IN"] --> L["WHT"]
L --> M["GRD"]
M --> N["14/3"]
N --> O["GRD"]
O --> P["UNITSWITCH BOX"]
style A fill:#f9f,stroke:#333
style F fill:#f9f,stroke:#333
style K fill:#f9f,stroke:#333
style B fill:#ccf,stroke:#333
style G fill:#ccf,stroke:#333
style I fill:#ccf,stroke:#333
style L fill:#ccf,stroke:#333
style N fill:#ccf,stroke:#333
style P fill:#ccf,stroke:#333

flowchart
graph TD
A["MODE SELECT SWITCH"] --> B["FAN SWITCH"]
C["MASTER ON/OFF SWITCH"] --> D["DIMMER SWITCH"]
E["LINE IN"] --> F["BRK"]
G["GRD"] --> H["SWITCH BOX"]
I["14/2 BLK BLU"] --> J["LIGHT WHT"]
K["RED BLK RED"] --> L["FAN WHT"]
M["14/3 WHT"] --> N["GRD"]
O["14/3 WHT"] --> P["BRK"]
Q["14/3 WHT"] --> R["BRK"]
S["14/3 WHT"] --> T["BRK"]
U["14/3 WHT"] --> V["BRK"]
W["14/3 WHT"] --> X["BRK"]
Y["14/3 WHT"] --> Z["BRK"]
AA["14/3 WHT"] --> AB["BRK"]
AC["14/3 WHT"] --> AD["BRK"]
AE["14/3 WHT"] --> AF["BRK"]
New Construction Installation

Insert Mask and nish Ceiling
• Install ceiling material.
- Cut out around Housing.

text_image
d V/CONTROL DAMAGE: ver must be (UNC item 2) Mask pro duringcon Remov installinMask protects unit duringconstruction. Removebefore installingGrille.
CAUTION


IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE:
If the blower was unplugged, power must be disconnected (see page 2, WARNING item 2) before inserting motor plugs into control assembly.

Install Grille

text_image
Technical diagram showing a device with labeled parts and directional arrows indicating flow or movement.
natural_image
Illustration of a hand pressing down on a tray with abstract background elements (no text or symbols)Retrofit Installation
Tools needed
• Power screwdriver with a Phillips bit
- Phillips screwdriver
- Flathead screwdriver
- Pliers
- Wire insulation stripper
- Wire cutter
- Ruler
- Pencil
- Drywall saw
- Claw hammer or pry bar
- Utility knife
Materials needed
- Tape to seal duct connections
- Existing rigid duct will require the addition of a short length of flexible duct
• Electrical wiring and supplies per local code requirements
1 Remove Packaging

Parts Bag holds Knockout Plate and six (6) screws

text_image
Remove Instruction SheetPunch out Mask from packaging. See Step 12.

natural_image
Pure mechanical diagram showing a folded structure with arrows indicating direction, no text or symbols present2 Switch Off Power
WARNING

Before removing existing fan, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
3 Enlarge Ceiling Opening and Remove Existing Fan

text_image
12" (30.5 cm) 11" (27.9 cm) parallel with joists ①Existing ductwork and wiring left in place

text_image
ing ductwork and ②
natural_image
Technical line drawing of a mechanical assembly inside a transparent cube (no text or symbols)4 Examine Wiring Examine the existing wiring
Examine the existing wiring to make sure it is not damaged. If any damage is found, DO NOT CONTINUE INSTALLATION of this product. Contact a qualified person(s) for repair.
Retrofit Installation
5 Remove Blower Assembly

text_image
Remove Electron Assembly ① ② Both sides
text_image
Set aside Blower Assembly ③6 Remove Wiring Panel

text_image
1 Set aside screw 2
text_image
Set aside Wiring Panel ③7 Insert Mounting Frame

text_image
ing ① Remove screws from Mounting Frame and set aside ② Bend up four tabsRetrofit Installation
8 Secure Mounting Frame

text_image
Screws set aside in Step 7 using9 Snap-in Housing

text_image
1 2 snap! Pull existing wiring into Housing as it is inserted into Mounting Frame10 Attach Ducting and Duct Connector

text_image
Pull existing ductwork into Housing 1 2 4 Screw from Parts Bag 3 Insert tab into slot inside Housing
text_image
6" Ducting Tape 4" Ducting Tape Tape 6" to 4" Reducer provided in select modelsRetrofit Installation
11 Install Knockout Plate, Connect Wires and Reinstall Wiring Panel
- Use proper UL-approved connectors to secure wiring to the Knockout Plate provided in Parts Bag.
- Connect wires as shown in wiring diagram.

text_image
1 Attach cable clamps to Knockout Plate. Knockout Plate mounts to inside of Housing and may be oriented as desired. 2 Screw from Parts Bag 3 Connect wires Light Fan
text_image
Screw set aside in Step 6 5 4
natural_image
Technical line drawing of a mechanical assembly with a numbered component (6), no visible text or symbols
flowchart
graph TD
A["Light SWITCH"] --> B["MANUAL ON"]
B --> C["14/2"]
C --> D["BLK BLU"]
D --> E["LIGHT WHT"]
F["FAN SWITCH"] --> G["BLK"]
G --> H["RED"]
H --> I["BLK"]
I --> J["FAN WHT"]
K["LINE IN"] --> L["WHT"]
L --> M["GRD"]
M --> N["14/3"]
N --> O["UNIT SWITCH BOX"]
style A fill:#f9f,stroke:#333
style F fill:#f9f,stroke:#333
style K fill:#f9f,stroke:#333
style N fill:#ccf,stroke:#333

flowchart
graph TD
A["MODE SELECT SWITCH"] --> B["FAN SWITCH"]
C["MASTER ON/OFF SWITCH"] --> D["BLK"]
E["LINE IN"] --> F["WHT"]
G["GRD"] --> H["SWITCH BOX"]
I["14/2 BLK BLU"] --> J["LIGHT WHT"]
K["14/3 RED"] --> L["BLK BLK"]
M["14/3 GRD"] --> N["BRIDGE"]
O["14/3 RED"] --> P["FAN WHT"]
Q["14/3 RED"] --> R["BRIDGE"]
S["14/3 RED"] --> T["BRIDGE"]
U["14/3 RED"] --> V["BRIDGE"]
W["14/3 RED"] --> X["BRIDGE"]
Y["14/3 RED"] --> Z["BRIDGE"]
AA["14/3 RED"] --> AB["BRIDGE"]
AC["14/3 RED"] --> AD["BRIDGE"]
AE["14/3 RED"] --> AF["BRIDGE"]
AG["14/3 RED"] --> AH["BRIDGE"]
AI["14/3 RED"] --> AJ["BRIDGE"]
AK["14/3 RED"] --> AL["BRIDGE"]
AM["14/3 RED"] --> AN["BRIDGE"]
AO["14/3 RED"] --> AP["BRIDGE"]
AQ["14/3 RED"] --> AR["BRIDGE"]
AS["14/3 RED"] --> AT["BRIDGE"]
AU["14/3 RED"] --> AV["BRIDGE"]
AW["14/3 RED"] --> AX["BRIDGE"]
AY["14/2"] --> AZ["WHT"]
style A fill:#f9f,stroke:#333
style C fill:#f9f,stroke:#333
style E fill:#f9f,stroke:#333
style Q fill:#f9f,stroke:#333
style AG fill:#f9f,stroke:#333
style AK fill:#f9f,stroke:#333
Retrofit Installation
12 Reinsert and Secure Blower Assembly CAUTION IN ORDER TO PREVENT
Power must be disconnected (see page 2, WARNING item 2) before inserting motor plugs into control assembly.

natural_image
Technical diagram of a mechanical assembly with internal components and a labeled section (1), no readable text or symbols present.
text_image
② ③ Screws from Parts BagIf ceiling repairs are needed, place Mask in Housing after Blower Assembly is secured. See New Construction Installation Step 6. Remove Mask before installing Grille.
13 Install Grille

text_image
Technical diagram showing a device with labeled parts and directional arrows indicating assembly or inspection steps.
natural_image
Illustration of a hand pressing down on a textured surface with directional arrows indicating movement (no text or symbols)WARNING ▲ More servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
Operation
To Turn Fan ON
Turn the master switch ON.
It is normal for this ventilation fan to take approximately 5 seconds to start running after it is turned on.
- Fan will run at the certified airflow rate if the mode select switch is ON.
- Fan will run at the user-adjustable airflow rate if the mode select switch is OFF.
To Use Fan Time Delay Airflow Rate Change
- Turn the master switch ON.
- Turn the mode select switch ON - fan will run at the certified airflow rate.
- When the mode select switch is turned OFF, fan will continue to run at the certified airflow rate until the user-adjustable time delay has elapsed, and then will automatically change to the user-adjustable airflow rate.
To Set the User-Adjustable Airflow Rate\*
Using a small, flat-blade screwdriver, carefully rotate the CFM adjustment until the arrow points to the desired airflow rate.
To Set the User-Adjustable Time Delay\*
Using a small, flat-blade screwdriver, carefully rotate the TIME adjustment until the arrow points to the desired time delay, shown in minutes.
* The user-adjustable controls are located in one corner of the Fan Housing, behind the Grille.

text_image
50 60 40 70 30 80 CFM TIME 15 5 30 45 60ZB80L User-adjustable controls

text_image
70 50 90 30 110 15 CFM TIME 30 45 5 60ZB110L User-adjustable controls
To Turn Fan OFF
Turn the master switch OFF.
To Operate Lights
The fan and light can be operated independently, using separate switches. The light may be operated with a dimmer switch. See wiring diagrams.
Cleaning and Maintenance
CAUTION
IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE:
DO NOT remove motor plug to stop spinning motor.
Power must be disconnected (see WARNING at top left of this page) before motor plug is removed or inserted into control assembly.
To Clean
For quiet and efficient operation, long life and attractive appearance, remove Grille and vacuum interior of unit with a dusting brush attachment.
The Motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noises, replace the Control Assembly and Motor.
Troubleshooting
Symptom: The fan does not run.
- Check for an open fuse or circuit breaker in the building's service panel.
- Check that the two (2) plug-in connections for the Motor and the Control are seated firmly in place.
- Check that the Blower Wheel spins freely.
Symptom: The fan runs erratically.
- Check that the Blower Wheel is firmly attached to the Motor shaft and both spin freely.
Symptom: The fan seems noisy.
- Check that the back draft damper in the fan's Duct Connector pivots freely. Screws used to attach the duct to the Duct Connector may be preventing the damper from opening.
- Check that the back draft damper in the wall or roof cap pivots freely. These dampers are sometimes mistakenly painted shut or obstructed by bird and insect debris.
Symptom: The fan does not properly ventilate the room.
- For spot ventilation, turn both the master switch and the mode select switch ON to enable the fan to run at the certified airflow rate.
- For spot ventilation followed by continuous ventilation, increase the “TIME” setting of the user-adjustable time delay.
- For continuous ventilation, increase the "CFM" setting of the user-adjustable airflow rate.

text_image
1 2 3 4 5 6 7 8 9 10 11 12 Order replacement arts by Part No., t by Key No. No. Part No. DescriptionKey No. Part No. Description
1 97018349 Mounting Frame
2 97018721 Knockout Plate & Screws
3 97018382 Housing
4 97020893 Wiring Panel/Harness Assembly
5 97020846 Control Assembly & Motor (ZB80L1)
97020845 Control Assembly & Motor (ZB110L1)
6 97018331 Duct Connector - 6"
7 99111513 6" to 4" Reducer (model ZB80L1 only)
8 99020301 Blower Wheel
9 97018768 Scroll Assembly (ZB110L1)
97019371 Scroll Assembly (ZB80L1)
10 97020827 Grille Assembly (includes 11, 12)
11 99140208 Grille Spring (2 req'd)
12 99111711 Lens (2 req'd)
13 99271625 LED Driver
WarrantyService Parts
Broan Ventilation Fan/Lights Limited Warranty
WARRANTY PERIOD: Broan warrants to the original consumer purchaser of its Broan Ventilation Fan/Light (the "Fan") that your Fan (excluding lamps/bulbs) will be materially free from defects in materials or workmanship for a period of three (3) years from the date of original purchase. The warranty on the lamps/bulbs provided with the Fan is one (1) year and does not cover lamp/bulb breakage. This warranty does not cover accessories, such as speed controls, that may be purchased separately and installed with the Fan. The limited warranty period for replacement parts, and for Fans repaired or replaced under this limited warranty, shall continue for the remainder of the original warranty period.
NO OTHER WARRANTIES: THE FOREGOING WARRANTIES ARE EXCLUSIVE AND IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED. BROAN DISCLAIMS AND EXCLUDES ALL OTHER EXPRESS WARRANTIES, AND DISCLAIMS AND EXCLUDES ALL WARRANTIES IMPLIED BY LAW, INCLUDING WITHOUT LIMITATION THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. TO THE EXTENT THAT APPLICABLE LAW PROHIBITS THE EXCLUSION OF IMPLIED WARRANTIES, THE DURATION OF ANY APPLICABLE IMPLIED WARRANTY IS LIMITED TO THE PERIOD SPECIFIED FOR THE EXPRESS WARRANTY. Some states do not allow limitations on how long a implied warranty lasts, so the above limitation may not apply to you. Any oral or written description of the Fan is for the sole purpose of identifying it and shall not be construed as an express warranty.
REMEDY: During the applicable limited warranty period, Broan will, at its option, provide replacement parts for, or repair or replace, without charge, any Fan or part thereof, to the extent Broan finds it to be covered by and in breach of this limited warranty. Broan will ship the repaired or replaced Fan or replacement parts to you at no charge. You are responsible for all costs for removal, reinstallation and shipping, insurance or other freight charges incurred in the shipment of the Fan or part to Broan. This warranty does not cover (a) normal maintenance and service, (b) normal wear and tear, (c) any Fans or parts which have been subject to misuse, abuse, abnormal usage, negligence, accident, improper or insufficient maintenance, storage or repair (other than repair by Broan), (d) damage caused by faulty installation, or installation or use contrary to recommendations or instructions, (e) any Fan that has been moved from its original point of installation, (f) damage caused by environmental or natural elements, (g) damage in transit, (h) natural wear of finish, (i) Fans in commercial or nonresidential use, or (j) damage caused by fire, flood or other act of God. This warranty covers only Fans sold in the United States or through U.S. distributors authorized by Broan.
EXCLUSION OF DAMAGES: BROAN'S OBLIGATION TO PROVIDE REPLACEMENT PARTS, OR REPAIR OR REPLACE, AT BROAN'S OPTION, SHALL BE YOUR SOLE AND EXCLUSIVE REMEDY UNDER THIS LIMITED WARRANTY AND BROAN'S SOLE AND EXCLUSIVE OBLIGATION. BROAN SHALL NOT BE LIABLE FOR INCIDENTAL, INDIRECT, CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR IN CONNECTION WITH THE FAN, ITS USE OR PERFORMANCE. Incidental damages include but are not limited to such damages as loss of time and loss of use. Consequential damages include but are not limited to the cost of repairing or replacing other property which was damaged if the Fan does not work properly.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights, which vary from state to state.
This warranty supersedes all prior warranties and is not transferable from the original consumer purchaser.
BROAN SHALL NOT BE LIABLE TO YOU, OR TO ANYONE CLAIMING UNDER YOU, FOR ANY OTHER OBLIGATIONS OR LIABILITIES,
INCLUDING, BUT NOT LIMITED TO, OBLIGATIONS OR LIABILITIES ARISING OUT OF BREACH OF CONTRACT OR WARRANTY,
NEGLIGENCE OR OTHER TORT OR ANY THEORY OF STRICT LIABILITY, WITH RESPECT TO THE FAN OR BROAN'S ACTS OR OMISSIONS OR OTHERWISE.
This warranty covers only replacement or repair of defective Fans or parts thereof at Broan's main facility and does not include the cost of field service travel and living expenses.
Any assistance Broan provides to or procures for you outside the terms, limitations or exclusions of this limited warranty will not constitute a waiver of such terms, limitations or exclusions, nor will such assistance extend or revive the warranty.
Broan will not reimburse you for any expenses incurred by you in repairing or replacing any defective Fan, except for those incurred with Broan's prior written permission.
HOW TO OBTAIN WARRANTY SERVICE: To qualify for warranty service, you must (a) notify Broan at the address or telephone number stated below within seven (7) days of discovering the covered defect, (b) give the model number and part identification and (c) describe the nature of any defect in the Fan or part. At the time of requesting warranty service, you must present evidence of the original purchase date.
Broan, 926 West State Street, Hartford, WI 53027
(1-800-637-1453)
www.broan.com
If you must send the Fan or part to Broan, as instructed by Broan, you must properly pack the Fan or part—Broan is not responsible for damage in transit.
LEA Y CONSERVE ESTAS INSTRUCCIONES
natural_image
Technical line drawing of a mechanical assembly with a central fan and mounting bracket (no text or symbols)natural_image
Abstract geometric diagram with interlocking shapes and arrows, no text or symbols presenttext_image
Diagram showing a drill press setup with labeled components and directional arrows indicating movement or force.text_image
Technical diagram showing a mechanical assembly with labeled components and directional arrows indicating motion or force.
natural_image
Illustration of a hand pressing down on a tray with arrows indicating movement (no text or symbols)natural_image
Pure mechanical assembly diagram showing two connected components with arrows indicating motion direction (no text or symbols)natural_image
Technical line drawing of a mechanical assembly inside a transparent box (no text or symbols)natural_image
Technical line drawing of a mechanical assembly with no visible text or symbols
flowchart
graph TD
A["INTERRUPTOR DE LUZ"] --> B["ENCENDIDO MANUAL"]
B --> C["14/2 NEG WHT"]
C --> D["AZL"]
D --> E["LUZ"]
E --> F["BLC"]
G["INTERRUPTOR DE VENT."] --> H["14/3"]
H --> I["ROJ"]
I --> J["ROJ"]
J --> K["VENT."]
K --> L["BLC"]
M["LINEA DE ENTRADA"] --> N["BLC"]
N --> O["TRA"]
O --> P["TRA"]
P --> Q["TRA"]
Q --> R["TRA"]
R --> S["TRA"]
S --> T["TRA"]
T --> U["TRA"]
U --> V["TRA"]
V --> W["TRA"]
W --> X["TRA"]
X --> Y["TRA"]
Y --> Z["TRA"]
Z --> AA["TRA"]
AA --> AB["TRA"]
AB --> AC["TRA"]
AC --> AD["TRA"]
AD --> AE["TRA"]
AE --> AF["TRA"]
AF --> AG["TRA"]
AG --> AH["TRA"]
AH --> AI["TRA"]
AI --> AJ["TRA"]
AJ --> AK["TRA"]
AK --> AL["TRA"]
AL --> AM["TRA"]
AM --> AN["TRA"]
AN --> AO["TRA"]
AO --> AP["TRA"]
AP --> AQ["TRA"]
AQ --> AR["TRA"]
AR --> AS["TRA"]
AS --> AT["TRA"]
AT --> AU["TRA"]
AU --> AV["TRA"]
AV --> AW["TRA"]
AW --> AX["TRA"]
AX --> AY["TRA"]
AY --> AZ["TRA"]
AZ --> BA["TRA"]
BA --> BB["TRA"]
BB --> BC["TRA"]
BC --> BD["TRA"]
BD --> BE["TRA"]
BE --> BF["TRA"]
BF --> BG["TRA"]
BG --> BH["TRA"]
BH --> BI["TRA"]
BI --> BJ["TRA"]
BJ --> BK["TRA"]
BK --> BL["TRA"]
BL --> BM["TRA"]
BM --> BN["TRA"]
BN --> BO["TRA"]
BO --> BP["TRA"]
BP --> BQ["TRA"]
BQ --> BR["TRA"]
BR --> BS["TRA"]
BS --> BT["TRA"]
BT --> BU["TRA"]
BU --> BV["TRA"]
BV --> BW["TRA"]
BW --> BX["TRA"]
BX --> BY["TRA"]
BY --> BZ["TRA"]

flowchart
graph TD
A["INTERRUPTOR DE SELECCIÓN DE MODO"] --> B["INTERRUPTOR DE VENTILATOR"]
B --> C["REGULADOR DE INTENSIDAD"]
C --> D["14/2 NEG AZL BLC"]
D --> E["LUZ"]
E --> F["BLC"]
G["INTERRUPTOR PRINCIPAL DE ENCENDIDO/APAGADO"] --> H["INTERRUPTOR DE VENTILATOR"]
H --> I["REGULADOR DE INTENSIDAD"]
I --> J["ROJ"]
J --> K["NEG"]
K --> L["UNIDAD"]
M["LINEA DE ENTRADA"] --> N["CAJA DE INTERRUPTORES"]
N --> O["14/3 BLC"]
O --> P["TRA"]
Q["UNIDAD"] --> R["VENT."]
R --> S["BLC"]
T["UNIDAD"] --> U["TRA"]
V["UNIDAD"] --> W["RETURANT"]
X["UNIDAD"] --> Y["RETURANT"]
natural_image
Technical diagram of a mechanical device with internal components and a black arrow pointing to a feature (no text or symbols present)
text_image
Technical diagram of an air conditioner unit with labeled components and wiring connectionstext_image
Technical diagram showing a device with labeled parts and directional arrows indicating assembly or operation.