USER MANUAL HRS400X1161 Envira-North
natural_image
Technical line drawing of an aircraft wing structure with truss framework and propeller (no text or symbols)Standard Web Truss Mount
Installation Instructions
ENVIRA-NORTH
SYSTEMS LIMITED
Tel: (519) 527-2198 Fax: (519) 527-2560
92 Railway St. P.O Box 668
Seaforth, ON Canada N0K 1W0
www.enviranorth.com
Standard Web Truss Mount Installation Guide
April 19, 2017
Table of Contents
Table of Contents 2
I. Before You Begin 2
11. Tools Required 2
III. Standard Web Truss Mount Components ....3
IV. Installation Instructions....4
Before You Begin
The Standard Web Truss Mount, when installed as directed, is designed and engineered to support up to a 24' Altra-Air Fan with a 4' drop and a 4' extension utilizing a multitude of beam length combinations.
The maximum span achievable across two web truss mounts without the need of additional hardware is 23' utilizing two 5" x 3.5" x 0.5" angles.
Consult a structural engineer before installation.

WARNING! Ignoring the following instructions can cause physical injury or death, or damage to the equipment.
NOTE: Illustrations/images may be changed without notice. All dimensions and specifications are approximate and drawings are not to scale.
Tools Required
- Ratchet or impact gun
- 7/16" and 3/4" Imperial socket to fit bolt heads and nuts
- 3/4" Imperial wrench to fit bolt heads and nuts
• Lifting device or scaffolding - Appropriate personal protective equipment
- Open end torque wrench with torques setting as low as 10 ft/lbs.
Standard Web Truss Mount Components

text_image
Web Truss Bracket EN400X1164 1/8" SS Cable (EN823X6952) 3/16" Cable Clamp (EN823X6952) ½" Flat Washer (EN823X6901) ½" Nylock Nut (EN823X6301) Torque to 18 ft/lbs ½" Threaded Rod (EN823X8331) mfd. Flat Bar w/ Welded Nuts (EN823X8327) mfd. Flat Bar w/o Nuts (EN823X8324) ½" Nut (EN823X6306) Torque to 12 ft/lbs mfd. I-Beam Clamp (EN823X8402) mfd. I-Beam Spacer (EN823X8401) ½" Nylock Nut (EN823X6301) Torque to 18 ft/lbs ½" X2½" Hex Head Cap Screw (EN823X6001) mfd. Bottom Plate (EN823X8324)Installation Instructions
-
Install 3" flat bar with welded nuts (EN823X8327) over the top chord of web truss. Ensure that flat bar is installed with the welded nuts facing upward.
-
Install both threaded rods (EN823X8331) into the 3" flat bar with welded nuts (EN823X8327), with a minimum of 2 thread pitches (1/4") of the threaded rod extended beyond the top surface of each welded nut.

natural_image
Line drawing of a wooden table support with two bolts and three legs (no text or symbols)- Install 3" flat bar without nuts (EN823X8324) through the holes onto threaded rod using 12 " nuts and flat washers (EN823X6306, EN823X6901) thus sandwiching top chord of truss. Torque nuts 12 ft/lbs (as per details)

natural_image
Line drawing of a structural support frame with two vertical posts and horizontal beams (no text or symbols)- Assemble I-beam clamps to bottom plate (EN823X8328) on both sides, by aligning the I-beam spacer (EN823X8401) and the I-beam clamp (EN823X8402) slotted holes on the bottom plate (EN823X8328) and fasten loosely using 12 " X 212 " hex head cap screw (EN823X6001), 12 " flat washers (EN823X6901) and 12 " nylock nuts (EN823X6301).
Note: I-Beam spacer only required for angle 3/8" thick or more.

natural_image
Technical line drawing of a mechanical assembly with two plates and four bolts (no text or symbols)- Install bottom plate (EN823X8328) with I-beam clamps assembled through center holes onto the two threaded rods using 12 " nylock nuts and flat washer(EN823X6301, EN823X6901) allowing enough space for web truss beam to slide through assembly easily.

natural_image
Technical line drawing of a structural support frame with columns and bolts (no text or symbols)- A minimum of two mounting points are required to carry the various lengths of web truss beam assemblies. Repeat step 1-5 as required.
Note: Web Truss Beam may be installed as one assembled component or separately as two angles to allow ease of installation, however; note that angles must be bolted together with 12 " X 212 " hex head cap screws (EN823X6001) and 12 " nylock nuts (EN823X6301) as many as required to complete the beam.

natural_image
Pure technical line drawing of a diagonal structural beam (no text or symbols)-
Insert one end of the web truss beam into the standard web truss bracket (EN400X1164) between the top of the bottom plate and the I-beam clamps and slide the web truss beam through the required assembled standard web truss bracket (EN400X1164) and repeat the procedure at the opposite end. Ensure a minimum of 6" of web truss beam extends past truss at each end.
-
Tighten the 12 " nylock nuts (EN823X6301) underneath the bottom plate (EN823X8328) to secure the web truss beam by sandwiching the assembly together. Torque nylock nuts to 18 ft/lbs.
Note: Increased torque limits the load capacity of the bracket.

natural_image
Technical line drawing of a structural framework with beams and supports (no text or symbols)- Thread safety cable (EN823X6950) around beam assembly and top chord of truss at each mounting point. Safety cable must be fastened by looping the cable ends together as shown in detail and clamping them together using 3/16" cable clamps (EN823X6952).

text_image
Technical diagram showing cable installation with three views: wire connection, switch mechanism, and warning symbol.The standard web truss mount installation is now complete and ready for fan installation.