MTN6503-0201 - Uncategorized SCHNEIDER - Free user manual and instructions
Find the device manual for free MTN6503-0201 SCHNEIDER in PDF.
| Type | Industrial Control Module |
| Model | MTN6503-0201 |
| Brand | Schneider Electric |
| Dimensions (H x W x D) | 90 mm x 36 mm x 60 mm |
| Weight | 0.15 kg |
| Power Supply | 24 V DC, 5 VA |
| Rated Current | 16 A |
| Number of Poles | 2 |
| Mounting Type | DIN rail |
| Communication | Modbus RTU |
| Degree of Protection | IP20 |
| Operating Temperature | -25°C to +60°C |
| Storage Temperature | -40°C to +85°C |
| Relative Humidity | 5% to 95% (non-condensing) |
| Compliance | CE, RoHS |
| Terminal Capacity | 2.5 mm² solid/1.5 mm² stranded |
| Display | LED indicators for status |
| Functions | Switching, monitoring, remote control |
| Cleaning | Wipe with dry cloth; do not use solvents |
| Safety | Install by qualified personnel; disconnect power before maintenance |
| Spare Parts | Available from Schneider distributors |
Frequently Asked Questions - MTN6503-0201 SCHNEIDER
User questions about MTN6503-0201 SCHNEIDER
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Uncategorized in PDF format for free! Find your manual MTN6503-0201 - SCHNEIDER and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. MTN6503-0201 by SCHNEIDER.
USER MANUAL MTN6503-0201 SCHNEIDER
Application Metering Gateway 7602/1.0
Many parameters and their settings are dependent on the settings you have already made for other parameters. This means that some parameters will appear or disappear and the values available for selection will change according to settings you have already made. These dependencies have not been shown in the table for reasons of clarity. All settings are always shown.
Configurable times are set via the base and factor parameters. The actual time is given by the multiplication of the two values. Example:
Base = 1 second, Factor = 3
Actual time = 3 seconds
The bold values in a table are the values set during factory configuration.
Table of contents
- Function overview 1
• Behaviour of the application 1 - Modbus settings 2
- Metering device templates 3
- Metering device x 3
– Voltage and current monitor 4
-Power monitor 4
- Consumption monitor 5
-Template for SIM10M module 6
- Direct access to Modbus register 7
- Access to register X 7
-
Modbus register X 7
-
Diagnostic block 8
• Overview of parameters 9
• Overview of communication objects 11
Function overview
The KNX Metering Gateway is a device which connects meters via the Modbus open standard to KNX. The Modbus open standard allows you to receive a more in-depth analysis of consumption in all areas of your building.
You can connect up to 10 of the following types of meters based on Modbus remote terminal unit (RTU):
• Schneider Electric energy meters
• Schneider Electric power meters
- Schneider Electric Smart Interface Modules (SIM10M module)
- Non-Schneider Electric Modbus RTU devices (offering you greater flexibility)
With the information which the KNX Metering Gateway provides you can visualise energy or media consumption. This can also be used to reduce consumption through the use of control strategies within the KNX network.
You can choose from 17 different pre-prepared templates for the meters and devices in order to quickly connect to a KNX network. Each template contains the 20 most frequently needed Modbus values for simple configuration.
From each connected Modbus RTU device the KNX Metering Gateway can read up to an additional 40 Modbus register values and transfer this data to the KNX network.
You can read up to 10 meters using one KNX Metering gateway. This makes the Gateway very cost-efficient.
Integrating a SIM10 module makes it possible to determine and visualise gas and water consumption.
The KNX Metering Gateway is also suitable for retrofitting or for retroactive connection of existing Modbus systems to KNX because it is fully compatible with meters from other manufacturers.
Behaviour of the application
The application is influenced by the following events:
- ETS download
- Bus voltage failure
- Bus voltage recovery
The behaviour differs according to function and can influence the measuring and monitoring function. Therefore, you can set the behaviour using parameters at the corresponding point. Refer to the chapter in question for a precise description.
Modbus settings
The gateway always works in master mode and the connected Modbus devices work in slave mode. Communication from KNX bus to the Modbus is not possible.
Baudrate setting
The Baudrate is set depending on the distance between Modbus RTU devices. For instance with a Baud rate of 9,600 bit/sec the maximum communication distance between 1 - 15 Modbus RTU devices is 1,200 metres. With the Baud rate of 19,200 bit/sec the maximum communication distance is 900 metres, as the table shows below:
| Baudrate setting Maximum communication distance for 1 to 15 Modbus RTU devices (Typical with Belden 3105A cables) | |
| 9,600 bit/sec 1,200 m | |
| 19,200 bit/sec 900 m | |
Parity refers to the technique of checking if transmission has been successful when transmitting between devices. It lets you know if some data has been lost during transmission.
Setting of parity
The Modbus supports only 11 bit frames. The ETS application sets stop bits automatically depending on the parity setting. "Parity" refers to the number of 1s in a given binary number. Odd parity means there are an odd number of 1s and even parity means that there are an even number of 1s. Parity bits are used as a means of error detection as digital data is transmitted and received. Both the Gateway and Meter must always be set to the same as one another, odd, even or none. The default parity mode of Modbus is "even" parity.

Make sure that all connected meters are always set to the same parity as one another, odd, even or one.
- Parity = None: choose between one and two stop bits
- Parity = Even: one stop bit is set
- Parity = Odd: one stop bit is set

When parity is set to „None“ it is necessary to pre-set meters PM2x0, PM7x0 and PM8x0 to one stop bit (all other meters require a setting of two stop bits here). This means that under „None“ parity PM2x0, Pm7x0 and PM8x0 meters cannot be combined with other meters. In their case it is necessary to work with „Odd“ or „Even“ parity.
Parameters
| Modbus settings | |
| Parameters Setting | |
| Baudrate setting (bit/sec) 1,200 | |
| 2,400 | |
| 4,800 | |
| 9,600 | |
| 19,200 | |
| Parity None | |
| Even | |
| Odd | |
| Stop bit One stop bit | |
| Two stop bits |
Delay between frames
Some devices require considerable time after end of response until they are ready to receive the following request from the master. In particular Schneider Electric SEPAM power devices and legacy slave devices. As they are slow in dealing with the original request they may miss the following request.
The time between requests should be less than 3.5 characters according to the Modbus specification. However, these legacy devices need more time. The parameter „Delay between frames“ solves this problem. The time is automatically adapted to 3.5 characters of the transmission speed, but you have the choice to increase this time if you need to support such slow legacy devices.
Parameters
| Modbus settings | |
| Parameters | Setting |
| Delay between frames1 ms* factor (50 .. 100) | Disabled50 - 100 adjustable in steps of 10 |
Start-up delay
The parameter „Start-up delay“ specifies from what point measured values are counted in the application. After an ETS download or bus voltage recovery, the device starts measuring the connected channels when the start-up delay is complete.
Parameters
| Modbus Settings | |
| Parameters | Setting |
| Start-up delay1 s * factor (1-250) | 5adjustable in single steps |
Metering device templates
Pre-installed ETS templates provide you with the 20 most frequently needed values which makes configuration much easier and quicker. This also means there is no need to map the Modbus register addresses to KNX.
The ETS application has special templates which you use to implement the Schneider Electric Modbus RTU based energy or power meters and SIM10M module.
These devices are outlined in the table below:
| Supported devices | ||
| Type | Name | Description |
| Energy/power meter | PM9C power | meter for the installation distributor (cabinet) for measurement with current transformers |
| Energy/power meter | PM210 current | , voltage, power and energy (each active/idle/apparent), frequency and power factor |
| Energy/power meter | PM710 slave | pointer (min/max), Total Harmonic Distortion (THD) I/THD U harmonic distortion |
| Energy/power meter | PM750 like | PM710 with alarm contact |
| Energy/power meter | PM810 like | PM750 with 4-quadrant measurement |
| Energy/power meter | PM820 like | PM810 with additional integrated memory for logging events and analysis of harmonics. |
| Energy/power meter | PM850 like | PM810 with harmonic content |
| Energy/power meter | PM870 like | PM850 with additional detection and logging of peaks of voltage and current |
| Energy/power meter | PM1200 like | PM210 with THD I/THD U harmonic distortion |
| Energy/power meter | DM6200 Ampere, volt, frequency meter | |
| Energy/power meter | iEM3150 | direct measurement to 63A, records energy |
| Energy/power meter | iEM3155 | like iEM3150 with alarm contact, MID compliant |
| Energy/power meter | iEM3250 | transformer measurement |
| Energy/power meter | iEM3255 | like iEM3250 with alarm contact, MID compliant |
| Energy/power meter | PM3250 4-quadrant measurement, THD I/THD U harmonic distortion | |
| Energy/power meter | PM3255 like | PM3250 with alarm |
| Smart Interface Module | SIM10M input module for pulse counting. | |
Metering device x
You can select the metering device you require from the parameter „Type of metering device“. These are the 17 devices from the previous table.
Each connected device has a unique address, between 1 and 247, as per the Modbus addressing protocol. To identify the device, you need to set its address at the parameter „Address of metering device“.
The template allows you to monitor different kinds of values. To achieve this it has three monitoring functions which you can enable by parameter. These are:
• „Voltage and current monitor“
• „Power monitor“
- "Consumption monitor"
With the parameter „Sending behaviour“ you can specify how all values of the monitors are sent. For a cyclical sending, you can set the parameter „Time base“ to either 1 second or 1 minute. The chosen setting applies to all values of the whole template.
Parameters
| Metering device x | |
| Parameters | Setting |
| Type of metering device | Disabled |
| PM9C | |
| PM210 | |
| PM710/PM750 | |
| PM8x0 | |
| DM1200 | |
| DM6200 | |
| iEM3150 | |
| iEM3155 | |
| iEM3250 | |
| iEM3255 | |
| PM3250/PM3255 | |
| SIM10M | |
| Address of metering device | 1 ..247 |
| Read Modbus values after start | Enabled |
| Disabled | |
| Voltage and current monitor | Enabled |
| Disabled | |
| Power monitor | Enabled |
| Disabled | |
| Consumption monitor | Enabled |
| Disabled | |
| Sending behaviour | Cyclically (as configured time) |
| If value was changed | |
| Time base | 1 sec |
| 1 min |
Voltage and current monitor
You can set the parameter „Voltage and current monitor“ to read Modbus values after start. Values for voltage and current are available for each phase (1-3) separately. When you enable the voltage or current of phase x you can then set their cyclic sending with integers of 1 second or 1 minute, with a base as configured in previous parameter „Time base“.
Parameters
| Voltage and current monitor | |
| Parameters Setting | |
| Voltage unit Millivolt (DPT 9.020) | |
| Volt (DPT 9.*) | |
| Voltage of phase x Enabled | |
| Disabled | |
| Cyclic voltage sending Time base * factor (1-250) | 2, 1 .. 250 |
| Current unit Milliampere (DPT 9.021) | |
| Current of phase x Enabled | |
| Cyclic current sending Time base * factor (1-250) | 2, 1 .. 250 |
| Frequency Enabled | |
| Disabled | |
| Cyclic frequency sending Time base * factor (1-250) | 2, 1 .. 250 |
Power monitor
The power monitor allows you to enable parameters as follows:
• Power factor (power factor in cosΦ)
• Active power x, for each phase 1-3
- Reactive power x , for each phase 1-3
- Total active power (total power in kW), sum of phases 1-3
- Total reactive power (total power in kVAr), sum of phases 1-3
- Total apparent power (total power in kVA), sum of phases 1-3
With each of these you can then set their cyclic sending with integers of 1 second or 1 minute, with a base as configured in previous parameter „Time base“.
Parameters
| Power monitor | |
| Parameters Setting | |
| Power factor (cos phi) Enabled | |
| Disabled | |
| Cyclic power factor sending Time base * factor (1-250) | 2, 1 .. 250 |
| Active power x | Enabled |
| Disabled | |
| Cyclic active power factor sending Time base * factor (1-250) | 2, 1 .. 250 |
| Power datapoint | Power kW (DPT 9.024), 2 Byte |
| Value power W (DTP 14.056), 4 Byte | |
| Reactive power x | Enabled |
| Disabled | |
| Cyclic reactive power factor sending Time base * factor (1-250) | 2, 1 .. 250 |
| Power datapoint | Power kW (DTP 9.024), 2 Byte |
| Value power W (DTP 14.056), 4 Byte | |
| Total active power Total reactive power Total apparent power | Enabled |
| Disabled | |
| Cyclic total active / reactive / aparent power factor sending Time base * factor (1-250) | 2, 1 .. 250 |
| Power datapoint | Power kW (DTP 9.024), 2 Byte |
| Value power W (DTP 14.056), 4 Byte |
Consumption monitor
With the consumption monitor you can enable the following:
• Active energy counter (total energy - active in kWh)
- Reactive energy counter (total energy - reactive - in kVArh)
- Apparent energy counter (total energy - apparent - in kVAh)
These monitor energy consumption within the period.
You can then set their cyclic sending with integers of 1 second or 1 minute, with a base as configured in the previous parameter „Time base“.
The energy counters each have 3 possible consumption object types which you can set to Active energy, Active energy kWh or Active energy V64.
Parameters
| Consumption monitor | |
| Parameters Setting | |
| Active energy counter Enabled | |
| Disabled | |
| Cyclic active consumption sending Time base * factor (1-250) | 2, 1 .. 250 |
| Consumption object type Active energy (DPT 13.010) | |
| Active energy kWh (DPT 13.013) | |
| Active energy V64 (DPT 29.010) | |
| Reactive energy counter Enabled | |
| Disabled | |
| Cyclic reactive consumption sending Time base * factor (1-250) | 2, 1 .. 250 |
| Consumption object type Reactive energy (DPT 13.012) | |
| Reactive energy kVArh (DPT 13.015) | |
| Reactive energy V64 (DPT 29.012) | |
| Apparent energy counter Enabled | |
| Disabled | |
| Cyclic apparent consumption sending Time base * factor (1-250) | 2, 1 .. 250 |
| Consumption object type Apparent energy (DPT 13.011) | |
| Apparent energy kVAh (DPT 13.014) | |
| Apparent energy V64 (DPT 29.011) | |
Application Example
Requirements
• measure and visualise how much energy is used lighting an office building
• measure the gas and water consumption in the building
• monitor the quality of the network to ensure the operational safety of IT equipment
Solution
- install an iEM3150 meter to record the energy consumed by the lighting
- install an iEM3255 meter to determine the network quality
• install a SIM10M module to measure gas and water consumption via impulse - connect the devices to each other via Modbus
By connecting the KNX Metering Gateway to the Modbus line, the data can be configured easily using the templates supplied and then transmitted to the KNX bus. The consumption data is then conveniently displayed for facility management in their offices on a touch panel. Incoming alarms triggered by fluctuations in the network quality are also displayed.
Communication objects
The following communication objects can be selected:
| Function Object name Type | Prio Flags Behaviour | ||||
| Metering device x | Voltage of phase x | 2 Byte | Low CTR | Send/read | |
| Metering device x | Current phase x | 2 Byte | Low | CTR | Send/read |
| Metering device x | Frequency | 4 Byte | Low CTR | Send/read | |
| Metering device x | Power factor | 4 Byte | Low CTR | Send/read | |
| Metering device x | Active power kW x | 2/4 Byte | Low CTR | Send/read | |
| Metering device x | Reactive power kVAr x | 2/4 Byte | Low CTR | Send/read | |
| Metering device x | Total active power kW x | 2/4 Byte | Low CTR | Send/read | |
| Metering device x | Total reactive power kVAr x | 2/4 Byte | Low CTR | Send/read | |
| Metering device x | Total apparent power kVA x | 2/4 Byte | Low CTR | Send/read | |
| Metering device x | Active energy counter kWh | 4/8 Byte | Low CTR | Send/read | |
| Metering device x | Reactive energy counter kVArh | 4/8 Byte | Low CTR | Send/read | |
| Metering device x | Apparent energy counter kVAh | 4/8 Byte | Low CTR | Send/read | |
Template for SIM10M
Within the KNX Metering Gateway you can also connect to a SIM10M module allowing you to:
- read energy consumption
- read the buildings' pulse meters that measure gas and water consumption
- visualise these values
The SIM10M module offers you two different functions:
- six logic counters with pulse acquisition and on/off detection by internal 3.6 V DC power and pull-up resistors.
- two analogue inputs with a range of 0-10 V DC externally powered.
The SIM10M module is able to control and count the pulses of up to six simple meters with pulse or relay output.
The binary counters each have a scale, multiple and divide factor implemented. This is because the ETS application does not support decimal points, so in each case there needs to be a multiple and divide factor to achieve the required value, e.g. when scale factor = 18.32, multiple factor is 1832 and divide factor is 100.
Typical use case of SIM10M module and setting of ETS application
When connecting the SIM10M module and the power and pulse meters, you must set the amount of pulses which are defined for 1kWh (or m^3 for gas and water). Those constants are set in the ETS application (preset to 3,200 pulses and 1,000 imp/kWh). The result is sent to the KNX bus via the communication object.
Reset of binary counter
The reset datapoint reacts only to a „true“ telegram. A “false” telegram is ignored.
Communication objects
The following communication objects can be selected:
| Function Object name Type | Prio Flags Behaviour | ||||
| SIM10M module x | Binary counter x 4 | Byte Low CTR | Send/read | ||
| SIM10M module x | Analogue input x | 2 Byte Low CTR | Send/read | ||
| SIM10M module x | Reset of binary counter x | 1 bit | Low CW | Send | |
Parameters
| SIM10M module 1 | |
| Parameter | Setting |
| Address of SIM10M | 1 .. 247 |
| Read input values after start | Enabled |
| Disabled | |
| Binary counter 0 .. 5 | Enabled |
| Disabled | |
| Cyclic object sending Time base * factor (1 .. 250) | 2, 1 .. 250 |
| Multiplication factor | 1, 1 .. 10,000 |
| Division factor (Data*multi / div factor) | 1, 1 .. 10,000 |
| Voltage unit | Millivolt (DPT 9.020) |
| Volt (DPT 9.0*) | |
| Analogue input 0, 1 | Enabled |
| Disabled | |
| Cyclic object sending Time base * factor (1 .. 250) | 2, 1 .. 250 |
| Sending behaviour | Cyclically (as configured time) |
| If value was changed | |
| Time base | 1 sec |
| 1 min |
Direct access to Modbus register
The KNX Metering Gateway is only able to read basic Modbus register values. For access to other Modbus registers you must use an additional functionality, „Access to Register x“. Within this parameter you can select which registers you wish to access. The registers are grouped in five groups with eight registers each.
| Direct access to Modbus register | |
| Parameters Setting | |
| Access to Modbus register 1 - 8 | Disabled |
| Enabled | |
| Access to Modbus register 9-16 | Disabled |
| Enabled | |
| Access to Modbus register 17 - 24 | Disabled |
| Enabled | |
| Access to Modbus register 25 - 32 | Disabled |
| Enabled | |
| Access to Modbus register 33-40 | Disabled |
| Enabled |
Access to Modbus register x
By enabling or disabling groups of registers, you can then disable or enable access to individual registers.
| Access to Modbus register x | |
| Parameters Setting | |
| Access to Modbus register x Disabled | |
Modbus register x
You can set parameter „Register type“ to either „Read holding register“ (set as default) or „Read input register“.
With the Read input register you can read from 1 to 125 contiguous input registers in a remote device. The Request protocol date unit (PDU) specifies the starting register address and the number of registers. In the PDU addresses start from zero, therefore registers numbered 1 - 16 are addressed as 0 - 15.
You can set parameter „Modbus data is“ to Unsigned, to Float or to Float (words are swapped).
You can set the Modbus value to convert to 2, 4 or 8 Byte. Within this datapoint the object type can be set to „unsigned“, „signed“ or „float“. You must be careful when setting the Modbus value as each datapoint has a set range. If the value falls out of this range the sending of the value will be blocked and will not reach the KNX bus.
| Datapoint Range | |
| 2 Byte unsigned 0 .. 65 535 | |
| 2 Byte signed -32 768 .. 32 767 | |
| 2 Byte float -670 760.. 670 760 | |
| 4 Byte unsigned 0 .. 4 294 967 295 | |
| 4 Byte signed -2 147 483 648.. 2 147 483 647 | |
| 4 Byte float Object_x Byte | |
| 8 Byte unsigned 0 .. 18 446 744 073 709 551 615 |
Parameters
| Modbus register x - Modbus side | |
| Parameters Setting | |
| Address of modbus device | 1 .. 247 |
| Register address | 1,000 .. 50,000 |
| Register type | Read holding register |
| Read input register | |
| Modbus data is | Unsigned |
| Float | |
| Float (words are swapped) | |
| Multiplication factor | 1, 1 .. 10,000 |
| Division factor (data*multi/div factor) | 1, 1 .. 10,000 |
| Modbus register x - KNX side | |
| Parameters Setting | |
| Quantity of coils (Modbus datapoint) | 1 |
| 2 | |
| 4 | |
| Modbus value convert to | 2 Byte |
| 4 Byte | |
| 8 Byte | |
| Type of object | 2/4 Byte unsigned |
| 2/4 Byte signed | |
| 2/4 Byte float | |
| Time base | 1 sec |
| 1 min | |
| Cyclic sending Time base * factor (1 .. 250) | 2, 1 .. 10,000 |
| Sending behaviour Cyclically (as | configured time) |
| If value was changed |
Communication objects
The following communication objects can be selected:
| Function | Object name | Type | Prio | Flags | Behaviour |
| Access to register x | Object_x Byte | 2/4/8Byte | Low | CTR S | send/read |
Diagnostic block
The Metering Gateway supports two different communication objects for the diagnostics of modbus devices. These are „Active Modbus status“ and „Passive Modbus status“.
The „Active Modbus status“ object sends an error code to the KNX bus after recognising that a problem exists on the Modbus. The sending of this status is controlled by the parameter „Sending behaviour“. The status will either be sent every time after reading of register (minimum 20 times per device template) or it will only be sent if Modbus exception code is changed. The range of exception codes is 0 - 6. All information about errors is stored in external FRAM memory.
The last reported status of a slave can be forced to be sent by the "Active Modbus status" object by sending the slave ID to the "Passive Modbus status object.
When you enable the parameter „Reset“, a reset telegram is sent and the gateway will stop reading all Modbus registers and make a restart. If the parameter "Reset" is enabled it is possible to restart the gateway with a "1"-telegram on object "Reset of gateway".
The table of error codes is listed below:
| Exception code | Name Description | |
| 0 hex No | error(slave is ok) | |
| 01 hex Illeg | gal function | The function code received in the query is not an allowable action for the slave. This may be because the function code is only applicable to newer devices, and was not implemented in the unit selected.It could also indicate that the slave is in the wrong state to process a request of this type, for example because it is unconfigured and is being asked to return register values, If a Poll Program Complete command was issued, this code indicates that no program function proceeds |
| 02 hex Illeg | gal data address | The data address received in the query is not an allowable address for the slave. The combination of reference number and transfer length is invalid. |
| 03 hex Illeg | gal data value | A value contained in the query data field is not an allowable value for the slave. This indicates a fault in the structure of remainder of a complex request, e.g. that the implied length is incorrect.It specifically does NOT mean that a data item submitted for storage in a register has a value outside the expectation of the application program since the Modbus protocol is unaware of the significance of any particular value of any particular register. |
| 04 hex Slave device failure | An unrecoverable error occurred while the slave was attempting to perform the requested action. | |
| Exception code | Name Description | |
| 05 hex Acknowledge | Specialized use in conjunction with programming commands.The slave has accepted the request and is processing it, but a long duration of time will be needed for it to do so. This response is returned to prevent a timeout error from occurring in the master. The master can issue a Poll Program Complete message to determine if programming is complete. | |
| 06 hex Slave device busy | Specialized use in conjunction with programming commands. The slave is engaged in processing a long-duration program command. The master should re-transmit the message later when the slave is free. | |
Communication objects
The following communication objects can be selected:
| Function Object name Type | Prio Flags Behaviour | ||||
| Diagnostic block | Active Modbus status | 2 Byte | Low CRT | Send/read | |
| Diagnostic block | Passive Modbus status | 1 Byte | Low CRT | W | Receive/read |
| Diagnostic block | Reset of gateway | 1 bit | Low CW | Receive | |
Parameters
| Diagnostic block | |
| Parameters | Setting |
| Diagnostic block | Disabled |
| Enabled | |
| Active status | Disabled |
| Enabled | |
| Sending behaviour | Evey time |
| If value was changed | |
| Passive status | Disabled |
| Enabled | |
| Reset | Disabled |
| Enabled |
Overview of parameters
| Modbus settings | |
| Parameters Setting | |
| Baudrate setting (bit/sec) 1,200 | |
| 2,400 | |
| 4,800 | |
| 9,600 | |
| 19,200 | |
| Parity None | |
| Even | |
| Odd | |
| Stop bits One stop bit | |
| Delay between frames1 msec * factor (50..100) | Disabled |
| 50 | |
| 60 | |
| 70 | |
| 80 | |
| 90 | |
| 100 | |
| Start-up delay1s * factor (1 .. 250) | 5, 1 .. 250 |
| Metering device templates | |
| Parameters Setting | |
| Metering device x Enabled | |
| Disabled |
| Metering device x | |
| Parameters Setting | |
| Type of metering device Disabled | |
| PM9C | |
| PM210 | |
| PM710/PM750 | |
| PM8x0 | |
| PM1200 | |
| DM6200 | |
| iEM3150 | |
| iEM3155 | |
| iEM3250 | |
| iEM3255 | |
| PM3250/PM3255 | |
| SIM10M | |
| Address of metering device/ SIM10 module | 1 .. 247 |
| Read Modbus values after start En abled | |
| Voltage and current monitor Enabled | |
| Power monitor Enabled | |
| Consumption monitor Enabled | |
| Metering device x | |
| Parameters Setting | |
| Sending behaviour Cyclically (as | configured time) |
| If value was changed | |
| Time base | 1 sec |
| 1 min |
| Voltage and current monitor | |
| Parameters Setting | |
| Voltage unit | Millivolt (DPT 9.020) |
| Volt (DPT 9.*) | |
| Voltage of phase 1, 2, 3 | Enabled |
| Disabled | |
| Cyclic voltage sending Time base * factor (1 . 250) | 2, 1 .. 250 |
| Current unit | Milliampere (DPT 9.021) |
| Ampere (DPT 9.*) | |
| Current of phase x | Enabled |
| Disabled | |
| Cyclic current sending Time base * factor(1 . 250) | 2, 1 .. 250 |
| Frequency | Enabled |
| Disabled | |
| Cyclic frequency sending Time base * factor(1 . 250) | 2, 1 .. 250 |
| Power monitor | |
| Parameters | Setting |
| Power factor (cos phi) | Enabled |
| Disabled | |
| Cyclic power factor sending Time base * factor (1 .. 250) | 2, 1 .. 250 |
| Active power x | Enabled |
| Disabled | |
| Cyclic active power sending Time base * factor (1 .. 2500) | 2, 1 .. 250 |
| Power datapoint | Power kW (DTP 9.024), 2 Byte |
| Value power W (DTP14.056), 4 Byte | |
| Reactive power x | Enabled |
| Disabled | |
| Cyclic reactive power sending Time base * factor (1 .. 250) | 2, 1 .. 250 |
| Power datapoint | Power kW (DTP 9.024), 2 Byte |
| Value power W (DTP 14.056), 4 Byte | |
| Total active power Total reactive power Total apparent power | Enabled |
| Disabled | |
| Cyclic total x power sending Time base * factor (1 .. 2500) | 2, 1 .. 250 |
| Power datapoint | Power kW (DTP 9.024), 2 Byte |
| Value power W (DTP 14.056), 4 Byte | |
| Consumption monitor | |
| Parameters Setting | |
| Active energy counter Enabled | |
| Disabled | |
| Cyclic active consumption sending Time base * factor (1 .. 2500) | 2, 1 .. 250 |
| Consumption object type Active energy | (DPT 13.010) |
| Active energy kWh(DPT 13.013) | |
| Active energy V64 (DPT 29.010) | |
| Reactive energy counter Enabled | |
| Disabled | |
| Cyclic reactive consumption sending Time base * factor (1 .. 2500) | 2, 1 .. 250 |
| Consumption object type Reactive energy | (DPT 13.012) |
| Reactive energy kVArh (DPT 13.015) | |
| Reactive energy V64 (DPT 29.012) | |
| Apparent energy counter Enabled | |
| Disabled | |
| Cyclic apparent consumption sending Time base * factor (1 .. 2500) | 2, 1 .. 250 |
| Consumption object type Apparent energy | (DPT 13.011) |
| Apparent energy kVAh (DPT 13.014) | |
| Apparent energy V64 (DPT 29.011) |
| Direct access to Modbus register | |
| Parameters Setting | |
| Access to Modbus register 1 - 8 Enabled | Disabled |
| Disabled | |
| Access to Modbus register 9 - 16 Enabled | Disabled |
| Disabled | |
| Access to Modbus register 17 - 24 Enabled | Disabled |
| Disabled | |
| Access to Modbus register 25 - 32 Enabled | Disabled |
| Disabled | |
| Access to Modbus register 33 - 40 Enabled | Disabled |
| Disabled | |
| Access to Modbus register x | |
| Parameters Setting | |
| Access to Modbus register x Enabled | |
| Disabled |
| Modbus register x - Modbus side | |
| Parameters Setting | |
| Address of Modbus device 1 .. 247 | |
| Register address | 1 .. 50,000 |
| Register type | Read holding register |
| Read input register | |
| Modbus data is | Unsigned |
| Float | |
| Float (words are swapped) | |
| Multiplication factor | 1, 1 .. 10,000 |
| Division factor(Data*multi/div factor) | 1, 1 .. 10,000 |
| Modbus register x - KNX side | |
| Parameters Setting | |
| Quantity of coils (Modbus datapoint) | 1 |
| 2 | |
| 4 | |
| Modbus value convert to | 2 Byte |
| 4 Byte | |
| 8 Byte | |
| Type of object | 2/4 Byte Unsigned |
| 2/4 Byte signed | |
| 2/4 Byte Float | |
| Time base | 1 sec |
| 1 min | |
| Cyclic sending Time base * factor (1 .. 250) | 2, 1 .. 250 |
| Sending behaviour | Cyclically (as configured time) |
| If value was changed |
| Diagnostic block | |
| Parameters Setting | |
| Diagnostic block | Disabled |
| Enabled | |
| Active status | Disabled |
| Enabled | |
| Sending behaviour | Every time |
| If value was changed | |
| Passive status | Disabled |
| Enabled | |
| Reset | Disabled |
| Enabled |
Overview of communication objects
Metering Device x
| Function Object name Type | Prio Flags Behaviour | |||
| Metering device x | Voltage phase x 2 | Byte Low CTR | Send/read | |
| Metering device x | Current phase x 2 | Byte Low CTR | Send/read | |
| Metering device x | Frequency 4 Byte | Low CTR Send/read | ||
| Metering device x | Power factor 4 Byte | Low CTR Send/read | ||
| Metering device x | Active power kW x | 2/4 Byte | Low CTR Send/read | |
| Metering device x | Reactive power kVAr x | 2/4 Byte | Low CTR Send/read | |
| Metering device x | Total active power kW x | 2/4 Byte | Low CTR Send/read | |
| Metering device x | Total reactive power kVAr x | 2/4 Byte | Low CTR Send/read | |
| Metering device x | Total apparent power kVA x | 2/4 Byte | Low CTR Send/read | |
| Metering device x | Active energy counter kWh | 4/8 Byte | Low CTR Send/read | |
| Metering device x | Reactive energy counter kVArh | 4/8 Byte | Low CTR Send/read | |
| Metering device x | Apparent energy counter kVAh | 4/8 Byte | Low CTR Send/read | |
SIM10M module x
| Function Object name Type | Prio | Flags B | Behaviour | |
| SIM10M module x | Binary counter x | 4 Byte | Low CTR | Send/read |
| SIM10M module x | Analogue input x | 2 Byte | Low CTR | Send/read |
| SIM10M module x | Reset of binary counter x | 1 bit | Low CW | Send |
Access to Register x
| Function Object name | Type Prio | Flags | Behaviour |
| Access to register x | Object_2 Byte | 2 Byte Low CTR | Send/read |
| Access to register x | Object_4 Byte | 4 Byte Low CTR | Send/read |
| Access to register x | Object_8 Byte | 8 Byte Low CTR | Send/read |
Diagnostic block
| Function Object name Type | Prio Flags Behaviour | ||||
| Diagnostic block | Active Modbus status | 2 Byte | Low CRT | Send/read | |
| Diagnostic block | Passive Modbus status | 1 Byte | Low CRT | W | Receive/read |
| Diagnostic block | Reset of gateway | 1 bit | Low CW | Receive | |
Schneider Electric Industries SAS
If you have technical questions, please contact the Customer Care Centre in your country.
www.schneider-electric.com