MIM-E03DN - Heat pump SAMSUNG - Free user manual and instructions

Find the device manual for free MIM-E03DN SAMSUNG in PDF.

SAMSUNG MIM-E03DN - Heat pump
📄 60 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice SAMSUNG MIM-E03DN - page 4
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Wired Remote Controller
Compatible Systems Samsung DVM and air conditioning systems
Display LCD screen with backlight
Dimensions (W x H x D) 120 mm x 80 mm x 20 mm
Weight 0.15 kg
Power Supply 24 V AC/DC from indoor unit
Communication Interface RS-485
Maximum Cable Length 100 m
Number of Connectable Controllers Up to 1 per indoor unit (group control possible)
Supported Modes Cool, Heat, Fan, Dry, Auto
Temperature Setting Range 16°C – 30°C
Fan Speed Control Low, Medium, High, Auto
Timer Functions On/Off timer, weekly schedule
Wire Connection Terminals Screw terminals for power and communication
Mounting Wall-mounted with included bracket
Material Plastic (ABS)
Color White
Operating Temperature 0°C – 50°C
Storage Temperature -20°C – 60°C
Certifications CE, FCC

Frequently Asked Questions - MIM-E03DN SAMSUNG

How do I install the MIM-E03DN wired remote controller?
Installation requires connecting the controller to the indoor unit via a 4-wire cable. Use the provided mounting bracket to attach it to a wall. Connect the power (24V) and communication (RS-485) wires to the correct terminals. Refer to the wiring diagram in the manual.
What is the maximum cable length for the remote controller?
The maximum cable length is 100 meters for reliable communication. Use shielded twisted pair cable for best performance.
Can I control multiple indoor units with one MIM-E03DN?
Yes, the MIM-E03DN can control a group of indoor units in a Samsung DVM system. Group settings must be configured during installation.
How do I set the temperature on the controller?
Press the Up/Down arrows to adjust the desired temperature. The display shows the set temperature and room temperature. The allowable range is 16°C to 30°C.
Does the MIM-E03DN have a timer function?
Yes, it supports On/Off timers and a weekly schedule. Press the Timer button to access timer settings, then set the time and action.
What should I do if the display shows 'Err'?
An error code indicates a communication or system fault. Check wire connections between the controller and indoor unit. If the problem persists, consult the error code table in the manual or contact a technician.
Can I use the controller with non-Samsung air conditioners?
No, the MIM-E03DN is specifically designed for Samsung DVM and air conditioning systems. It uses a proprietary communication protocol and is not compatible with other brands.
How do I clean the remote controller?
Disconnect power before cleaning. Wipe the surface with a soft, dry cloth. Do not use water, solvents, or abrasive cleaners to prevent damage.
Can I replace the MIM-E03DN with a newer model?
Yes, but ensure compatibility with your system. The new controller should support the same communication protocol (RS-485) and power requirements. Consult the manual or Samsung support.
What is the warranty period for the MIM-E03DN?
The standard warranty is 2 years for manufacturing defects. Check your purchase documentation for specific terms.

User questions about MIM-E03DN SAMSUNG

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

Your email remains private: it is only used to notify you if someone answers your question.

No questions yet. Be the first to ask one.

Download the instructions for your Heat pump in PDF format for free! Find your manual MIM-E03DN - SAMSUNG and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. MIM-E03DN by SAMSUNG.

USER MANUAL MIM-E03DN SAMSUNG

Air to Water Heat Pump User Manual

Wired Remote Controller / Control Kit

Thank you for purchasing this product. Before operating this unit, please read this manual carefully and retain it for future reference.

Safety Information 4

Safety Information 4

At a Glance 6

Remote Controller Overview 6

Buttons Overview • Home Screen Overview • Zone Screen Overview •

DHW Screen Overview • Settings Screen Overview

Remote Controller Operation 9

Operating Basic Mode • Domestic Hot Water (DHW) Mode •

Adjusting Desired Temperature • Setting the Set Temperature

Power Smart Features 12

Power Smart Features 12

Operation Status • Quiet Mode • Outing Mode

Energy-Saving Operation 13

Energy-Saving Operation 13

Setting schedule • Energy • TDM (Time-Division Multi) Variables (TDM product Only)

Setting Options 16

Setting Options 16

How to set the Options • Current Time Setting (Example)

Installation/Service mode 19

Installation/Service mode 19

Additional functions of the Wired Remote Controller • Installation/Service mode •

How to upload or download field settings (example)

Set the FSV value by referring to the FSV label provided with the manual of the product, and then attach it on the control box's cover.

Field Setting Mode 27

Field setting mode 27

Field Setting Value (FSV) 10** •

Remote Controller Setting Range: Code 10** • Field Setting Value (FSV) 20** •

Water Law & Room Thermostat/ Wired remote controller: Code 20** •

Field Setting Value (FSV) 30** • DHW Heating: Code 30** • Field Setting Value (FSV) 40** •

Additional heating option: 40** • Field Setting Value (FSV) 50**/60** • Others: Code 50**/60** •

PV Control (Photovoltaics control) • Smart Grid Control

Appendix

49

Maintaining the Unit 49

Maintenance activities • Emergency heating / Emergency hot water supply

Troubleshooting tips 51

Communication • Water pump & Flow Sensor

Error codes 54

SAMSUNG MIM-E03DN - Appendix - 1

This marking on the product, accessories or literature indicates that the product and its electronic accessories (e.g. charger, headset, USB cable) should not be disposed of with other household waste.

(For India only)

For more information on safe disposal and recycling, visit our website www.samsung.com/in/support or contact our Helpline numbers - 1800 40 SAMSUNG (1800 40 7267864), 1800 5 SAMSUNG (1800 5 7267864).

For correct disposal of this product, please visit http://www.samsung.com/weee.pdf

For information on Samsung's environmental commitments and product regulatory obligations, e.g. REACH, visit our sustainability page available via www.samsung.com

SAMSUNG MIM-E03DN - Appendix - 2

This content is intended to protect the user's safety and prevent property damage. Please read it carefully for correct use of the product.

SAMSUNG MIM-E03DN - Appendix - 3

WARNING

Hazards or unsafe practices that may result in severe personal injury or death.

SAMSUNG MIM-E03DN - WARNING - 1

CAUTION

Hazards or unsafe practices that may result in minor personal injury or property damage.

SAMSUNG MIM-E03DN - CAUTION - 1

Follow directions. Do NOT attempt.

SAMSUNG MIM-E03DN - CAUTION - 2

SAMSUNG MIM-E03DN - CAUTION - 3

Make sure the machine is grounded to prevent electric shock.

SAMSUNG MIM-E03DN - CAUTION - 4

Unplug the appliance. Do NOT disassemble.

SAMSUNG MIM-E03DN - CAUTION - 5

FOR INSTALLATION

SAMSUNG MIM-E03DN - FOR INSTALLATION - 1

WARNING

SAMSUNG MIM-E03DN - WARNING - 1

The installation of this appliance must be performed by a qualified technician or service company.

- Failing to do so may result in electric shock, fire, explosion, problems with the product, or injury.

You must connect the product with rated power upon installation.

- Failing to do so may result in problems with the product, electric shock, or fire.

SAMSUNG MIM-E03DN - WARNING - 2

Do not install this appliance near a heater or inflammable material. Do not install this appliance in a humid, oily, or dusty location, in a location exposed to direct sunlight and water (rain drops). Do not install this appliance in a location where gas may leak.

- Failing to do so may result in electric shock or fire.

SAMSUNG MIM-E03DN - WARNING - 3

CAUTION

SAMSUNG MIM-E03DN - CAUTION - 1

Install the product on a hard and even place that can support its weight.

- If the place cannot support its weight, the product may fall down and it may cause product damage.

FOR POWER SUPPLY

SAMSUNG MIM-E03DN - FOR POWER SUPPLY - 1

WARNING

SAMSUNG MIM-E03DN - WARNING - 1

Do not bend or pull the power cord excessively. Do not twist or tie up the power cord.

- Failing to do so may result in electric shock or fire.

FOR OPERATION

SAMSUNG MIM-E03DN - FOR OPERATION - 1

WARNING

If the appliance generates a strange noise, a burning smell, or smoke, unplug the product immediately and contact your nearest service centre.

- Failing to do so may result in electric shock or fire.

To reinstall the product, please contact your nearest service centre.

  • Failing to do so may result in problems with the product, water leakage, electric shock, or fire.
  • A delivery service for the product is not provided. If you reinstall the product in another location, additional construction expenses and an installation fee will be charged.

If the malfunction diagnosis indicator appears or malfunctions, then stop operation immediately.

- If you detect any burning smells from the product or it malfunctions, then immediately turn off the product and power, and then contact the service centre. Continuing to use the device in this state can cause electrical shock, fire, or damage to the product.

SAMSUNG MIM-E03DN - WARNING - 1

Do not attempt to repair, disassemble, or modify the product yourself.

- Failing to do so may result in electric shock, fire, product malfunction, or injury.

SAMSUNG MIM-E03DN - WARNING - 2

CAUTION

SAMSUNG MIM-E03DN - CAUTION - 1

Do not allow water to enter the product.

- Failing to do so may result in fire or explosion.

SAMSUNG MIM-E03DN - CAUTION - 2

Do not operate the product with wet hands.

- Failing to do so may result in electric shock.

Do not spray volatile material such as insecticide onto the surface of the product.

• As well as being harmful to humans, it may also result in electric shock, fire, or product malfunction.

Do not give a strong impact to the product and do not disassemble the product.

Do not use this product for other purposes.

Do not press the buttons with any sharp objects.

- Failing to do so may result in electric shock or part damage.

FOR CLEANING

SAMSUNG MIM-E03DN - FOR CLEANING - 1

WARNING

SAMSUNG MIM-E03DN - WARNING - 1

Do not clean the product by spraying water directly onto it. Do not use benzene, thinner, alcohol or acetone to clean the product.

- Failing to do so may result in discoloration, deformation, damage, electric shock, or fire.

Buttons Overview

graph TD A["Zone1\nSet 30.0°\nHeat"] --> B["Zone2\nSet 24.0°\nHeat"] C["DHW\nSet 45.0°\nEconomic"] --> D["OK"] E["01"] --> F["02"] F --> G["03"] G --> H["04"] H --> I["05"] I --> J["06"] J --> K["07"]

01 Operation status display

- Displays the operation/function settings and statuses.

02 Operation On/Off button (LED display)

- Turns the Air to Water Heat Pump power On/Off.

03 Up/Down button

- Moves between items vertically or changes the set temperature.

04 Left/Right button

- Moves between items horizontally or changes the item value.

05 OK button

- Saves your new settings.

06 Save & Return button

- Saves your new settings and returns to the previous step.

07 Option button

- Selects the detailed setting function.

SAMSUNG MIM-E03DN - Buttons Overview - 2

NOTE

- The operation mode display on the remote controller changes depending on the selected language.

- Some functions may not be available, depending on the product specifications.

- You can see the operation status on the LED display.

- ON: Operating, Blinking: An error occurred, OFF: Turns off

Home Screen Overview

01 Zone1 Set 30.0° Heat Zone2 Set 24.0° Heat DHW Set 45.0° Domonic 02 03 04 < OK > -

01 Outdoor temperature display

• Displays outdoor temperature.

02 Date and time display

• Displays current date and time.

03 Zone 1 display

• Displays set temperature and operation modes for Zone 1.

04 Zone 2 display

• Displays set temperature and operation modes for Zone 2.

05 DHW display

• Displays set temperature and operation modes for DHW.

SAMSUNG MIM-E03DN - Home Screen Overview - 2

NOTE

- The Home screen may vary depending on whether Zone control is selected at the initial installation and whether DHW is supported.

Zone Screen Overview

08 07 06 05 04 Zone 1 Set Water Outlet 30.0° Current Water Outlet 28.2° Indoor 8.3° 03/28/2019 1:30 PM 02 03 05 Heat Water outlet

01 Set temperature display

• Displays the set temperature.

02 Current temperature display

• Displays current temperature for Water Outlet.

03 Current temperature display

• Displays current temperature for Indoor.

04 Operation mode display

• Displays any of Auto, Cool, and Heat.

05 Temperature sensor display

• Displays any of Water Law, Water Outlet, and Indoor.

06 Schedule indicator

- When you are setting a schedule.

- When you are setting the operation time limit.

07 Check indicator

08 Lock indicator

09 Central Control indicator

SAMSUNG MIM-E03DN - Zone Screen Overview - 2

NOTE

- Unavailable functions are marked inactive and they cannot be set.

- The locations of icons may differ depending on the function.

- When you do not press any button for 7 seconds, the function of the position is automatically selected.

DHW Screen Overview

06 05 04 07 DHW Set Current 84.0° -2.4° 01 Standard 02 03 OK

01 Set temperature display

• Displays the set temperature.

02 Current temperature display

• Displays current temperature for Water Outlet.

03 Operation mode display

• Displays any of Economic, Standard, Power, and Forced.

04 Schedule indicator

  • When you are setting a schedule.
  • When you are setting the operation time limit.

05 Check indicator

06 Lock indicator 07 Central Control indicator

SAMSUNG MIM-E03DN - DHW Screen Overview - 2

NOTE

  • Unavailable functions are marked inactive and they cannot be set.
  • The locations of icons may differ depending on the function.
  • When you do not press any button for 7 seconds, the function of the position is automatically selected.

Settings Screen Overview

Press the ⚙ button to enter the Setting screen and then select the desired function or option.

02 03 Operations Operation Status Qulet ON Cutting OFF Schedule 01 04 05 Energy Priority DHW Option ... 06 07 Option Button

01 Operation status display • Displays the operation status. 02 Quiet display • Displays the Quiet function. 03 Outing display • Displays the Outing function. 04 Schedule display - Displays any of Daily schedule, Weekly schedule, Yearly schedule, Holiday. 05 Energy display • Displays any of Energy Usage and Energy Setting. 06 Priority A2A display • Displays any of Priority A2A and Priority DHW. 07 Option display - Displays the Option.

SAMSUNG MIM-E03DN - Settings Screen Overview - 2

NOTE

  • Unavailable functions are marked inactive and they cannot be set.
  • In the menu with the > in the Option menu, you can select a menu with the > button.
  • When you do not press any button for 180 seconds with the option active, the settings are not saved and the Home screen appears.

Remote Controller Operation

Operate the product by using the remote controller.

Operating basic mode

Press the OK button to enter the Setting screen from the Home screen with the Zone 1 or Zone 2 activated. On each screen, press the OK and then press the ∧ or ∨ button to select any of Auto, Cool, and Heat modes.

Auto mode

Hydro unit will automatically adjust the temperature of discharge water with the Auto mode for indoor heating.

SAMSUNG MIM-E03DN - Auto mode - 1

NOTE

- When Water Law is active, the target supply water temperature will be determined automatically depending on the outdoor temperature: For the Heat mode, colder outdoor temperatures will result in warmer water.

Cool mode

You can adjust cooling temperature as you like with the Cool mode to cool indoor place.

- When selecting the Heat mode during the Cool mode, the Cool mode will be canceled.

Heat mode

Floor heating is available with the Heat mode by providing hot water in the spring, autumn and winter.

  • You can check the Defrost Operation on the operation status menu under Option.
  • When selecting the Cool mode during the Heat mode, the Heat mode will be canceled.

SAMSUNG MIM-E03DN - Heat mode - 1

NOTE

- When setting standard cooling & heating temperature as indoor temperature, the Auto mode cannot be selected.

Domestic Hot Water (DHW) mode

Press the OK button to enter the Setting screen from the Home screen with the DHW activated. On each screen, press the OK and then press the ∧ or ∨ button to select and use any of Economic, Standard, Power, and Forced modes.

SAMSUNG MIM-E03DN - Domestic Hot Water (DHW) mode - 1

NOTE

  • When the DHW mode is not supported, "Not Supported" appears.
  • To operate hot water mode, you need to set the hot water function 'Yes' in the field specification setting mode (#3011) of wired remote controller and connect the temperature sensor of hot water tank.
  • When the Cool/Heat mode and the DHW mode are selected at the same time, the Cool/Heat mode and the DHW mode will operate alternately.
  • (power) for the DHW mode cannot be used when the Booster heater is not in use.
  • If you want to enjoy a leisurely bath or need a lot of warm water urgently, select the Forced mode. When this mode is enabled, it is assured that the full capacity of the heat pump is only delivered for domestic water heating.

SAMSUNG MIM-E03DN - NOTE - 1

CAUTION

  • By default field setting value option, this function will not be turned off automatically.
  • If you want a Forced mode for a certain amount of duration time, change the field setting value of remote controller.

Adjusting desired temperature

On each screen, press the ∧ or ∪ button to adjust the temperature.

SAMSUNG MIM-E03DN - Adjusting desired temperature - 1

NOTE

- You can adjust the desired temperature by 0.1, 0.5, 1°C . (Default 0.5°C )

Setting the set temperature

On each screen, press the button to select a desired menu and then press the the OK button. You can adjust the set temperature by pressing the button.

SAMSUNG MIM-E03DN - Setting the set temperature - 1

NOTE

  • When the Reference temperature to control is Water Outlet, you can set the temperature only for Water Outlet.
  • When the Reference temperature to control is Indoor, you set the temperatures for Indoor and Water Outlet.
  • In the case of the model that can support both, you can set only the temperature for Indoor, but the temperature for Water Outlet is also affected together.
  • Depending on the Reference temperature set for cooling and heating, the controllable temperatures are restricted for each mode.
Auto Cool & Heat
Water Outlet Water Law Water Outlet
Indoor Temp - Indoor Temp

Power Smart Features

There is a variety of useful functionality provided by the product.

Operation status

Use this to display the operation status:

COMP operation, Back up heater, Booster heater, Solar, Back up boiler, Water pump, Water tank, Defrost operation, Freezing control, Water Tank Sterilization Operation, Indoor Thermostat Installation, Air to air operation, Solar PV, Smart grid, Eco Level, Demand Response.

Quiet mode

Noise from operation can be reduced with the Quiet mode.

SAMSUNG MIM-E03DN - Quiet mode - 1

NOTE

- When setting the Quiet mode through a contact from the outdoor unit or setting the Quiet Mode Automatic Time in the service mode using the wired remote controller, the mode cannot be controlled by user entry.

Outing mode

Heating can operate at low temperature while you are out with the Outing mode.

SAMSUNG MIM-E03DN - Outing mode - 1

NOTE

  • To cancel this mode, press any button on the remote controller.
  • When the Outing mode is On, the Home screen appears before entering the Setting.
  • When you press any key, the Outing mode is canceled. However, pressing the keys for switching between the Home and Main screen does not cancel this mode.
  • HOME: Directional button, OK button
  • Main Screen: Back button

Energy-Saving Operation

The product provides functions that allow you to reduce electricity consumption.

Setting schedule

Press the ⚙ button, press the ∧, ∨ or ⟨,⟩ button to select Schedule, and then press the OK button. When you select Add a schedule, you can configure settings for Daily schedule, Weekly schedule, Yearly Schedule, and Holiday.

Type Description
Daily scheduleCan set the Quiet mode or hot water status in the preset time.Can set up to 8 schedules.
Weekly scheduleCan set the operation for the desired units in the scheduled day and time.The scheduling is possible on the weekly basis. You can set the values for day, time, operation On/Off, scheduled units, operation state (operation mode, desired temperature).
Yearly ScheduleCan create a group for the month to schedule and assign scheduling to the group on the weekly basis.Yearly scheduling is possible and the scheduling can be assigned to up to 8 groups.
HolidayCan set not to run the weekly and yearly schedules on holidays.

SAMSUNG MIM-E03DN - Setting schedule - 1

NOTE

• Weekly and Yearly Schedule can cover settings up to 49.

Energy

Press the ⚙ button, press the ∧, ∨ or ⟨,⟩ button to select Energy, and then press the OK button. You can see and set any of Energy Usage and Energy Setting.

Classification Type Description
Energy Usage -Displays the Instantaneous Power, Weekly Energy Usage, Monthly Energy Usage, Yearly Energy Usage, Energy Usage over Last Year, and Operation Time in graph format. ⚪ NOTEFor accuracy of operation time, use the DMS time.The weekly display follows the ISO 8601 standards.
Energy SettingTarget Energy ConsumptionSets the target energy consumption.
Target Operation TimeSets the target operation time.
Alarm PopupSets whether or not to generate an alarm when the target energy consumption is reached.
Usage Data InitializationInitialises the entire energy function.

TDM (Time-Division Multi) Variables (TDM product Only)

Press the ⚙ button, press the ∧, ∨ or ⟨,⟩ button to select Priority A2A, and then press the OK button. Setting FSV #5033 to '0' becomes 'Priority A2A', and setting to '1' becomes 'Priority DHW'.

  • Under the installation of both A2A (Air-To-Air type air conditioner) and A2W (Air-To-Water type hydro unit) at the same time, our outdoor machine can supply its full capacity to the operating indoor machines (including A2A or A2W). If there are simultaneous operating demands from many A2A machines with A2W, the priority of controlling the outdoor machine (ex: compressor frequency) will be given to A2A, because of their fast response for user's comfort. Only the remaining capacity of outdoor machine will be given to A2W during A2A's normal operation. In this case, it might take very long time for A2W heating, so the outdoor machine will alternate the controlling priorities between A2A and A2W with time basis.
  • Priority maximum operation time (at FSV #5033=0): FSV #5031 (Default 30 min., Range 10 ~ 90 min.). After elapsing A2A maximum time, the outdoor machine will operate only for A2W to speed up the A2W's heating/cooling performance, even though there are A2A's continuous operation demands.
  • Non priority minimum operation time (at FSV #5033=0): FSV #5032 (Default 5 min., Range 3 ~ 60 min.). In this minimum time, the outdoor machine will operate only for A2W, even though there are no more A2W's continuous operation demands.
FSV settingA2A Cooling + A2W CoolingA2A Cooling + A2W HeatingA2A Heating + A2W CoolingA2A Heating + A2W Heating
A2A Priority(#5033=0)A2A CoolingA2W CoolingSame cooling ModeTDS ControlA2A CoolingA2W Cycle Off(The heater justoperates withoutheating.)Cooling OperationA2A HeatingA2W x (Not operation)Heating OperationA2A HeatingA2W HeatingSame heating ModeTDS Control
DHW Priority(#5033=1)Same with A2APriority settingA2W HeatingA2A Cooling(Heating + Cooling)TDS ControlSame with A2APriority settingSame with A2APriority setting

※ A2A : Air to Air, A2W : Air to Water

- When DHW Priority is enabled, hot water (heating) operation is given priority only if the A2A & A2W simultaneous operation is on. Other operations are the same as when A2A Priority is enabled.

SAMSUNG MIM-E03DN - TDM (Time-Division Multi) Variables (TDM product Only) - 1

CAUTION

  • While A2W is in operation, A2A does not operate. This is a normal operation.
  • While A2A or A2W is not in simultaneous operation, you can use any mode without operation mode restriction.

How to set the Options

1 Press the button. 2 Press the ↘ or button to select Option, and then press the button. 3 See the following pages to select the desired menu.

Step1 Step 2 Step 3 Step4 Step 5 Description Default
Button Lock ON/OFF OFF
Error List -
Indoor Unit Information--
User ModeLanguageDiffers depending on the languageFirst value for the language pack
Daylight Saving TimeDaylight Saving TimeON/OFF OFF
UnitDay/WeekWeek
MonthJanuary to DecemberMar
Week1st to 4th, F (final week)F (final week)
Day1 to 3122
LockAll LockON/OFF OFF
Lock of partial functionOperation LockON/OFF OFF
Operation Mode LockAll Mode LockON/OFF OFF
Auto Mode LockON/OFF OFF
Cool Mode LockON/OFF OFF
Heat Mode LockON/OFF OFF
Temperature LockON/OFF OFF
Schedule LockON/OFF OFF
Step 1 Step 2 Step 3 Step4 Step 5 Description Default
User ModeWired remote controllerLED ON/OFF ON
Button Mute ON/OFF OFF
Current TimeDateDate FormatYYYY/MM/DD, DD/MM/YYYY, MM/DD/YYYY
Year/Month/ Day2000 to 2099/1 to 12/1 to 31
TimeTime Format12-Hour/24-hour 12-Hour
Hour/ Minute/ AM/PM0 to 12/0 to 60/AM.PM
Reset Remote Controller-
Display SettingBrightness 10 to 100% 100%
Screen SaverTimer10 to 60 seconds
Brightness0, 10, 30, 50, 70%
Smart Reset--
Reset All User modes-
Service Time CheckService Call NumberService call number entered for Service mode
Last InspectionFinal control date entered for Service mode

SAMSUNG MIM-E03DN - How to set the Options - 1

NOTE

  • When two wired remote controllers are connected, the brightness can be set within 10 to 50%.
  • If the screen is on standby for an hour, in order to protect the screen it converts to screen protection mode for a minute before returning to the normal screen.

If the buttons are pressed after the screen protection is displayed it converts to the standby screen right away.

Current Time Setting (Example)

1 Press the button. 2 Press the ∧ ∨ or ( ) button to select Option, and then press the OK button. 3 Press the ∧ ∨ or ( ) button to select User mode, and then press the OK button. 4 Press the ∧ ∨ or ( ) button to select Wired remote controller, and then press the OK button. 5 Press the ∧ ∨ or ( ) button to select Current time, and then press the OK button. 6 Press the ∧ ∨ or ( ) button to select Time, and then press the OK button. 7 Press the ∧ ∨ or ( ) button to select Time format, Hour, Minute, and AM/PM, and then press the OK button.

Additional functions of the Wired Remote Controller

1. If you want to use the various additional functions for your Wired Remote Controller, press the ∧ and ∨ buttons at the same time for more than 3 seconds.

- The password entry screen appears.

2. Enter the password, 0202, and then press the OK button.

- The settings screen for installation/service mode appears.

3. See the list of additional functions for the Wired Remote Controller on the next page, and then select the desired menu.

- Once you have entered the setting screen, the current setting appears.

• Refer to the chart for data setting.

- Using the ∧/∨ buttons, change the settings and press the > button to move to the next setting.

- Press the OK button to save the new setting.

- Press the ⇔ button to move to the Home screen.

SAMSUNG MIM-E03DN - Additional functions of the Wired Remote Controller - 1

NOTE

- While setting the data, you can press the ⬆ button to move to the Home screen after checking the saving status at a pop-up screen.

Installation/Service mode

SAMSUNG MIM-E03DN - Installation/Service mode - 1

NOTE

  • Unavailable functions are marked inactive and cannot be set.
  • If communication initialization is needed after the setting, the system will reset automatically and communication will be initialized.
Step 1 Step 2Step 3 DescriptionDefault
Service TimerService Call Number16-digit phone numberInput: Blank, -, 0-9-
Last InspectionYear, Month, Day-
Installation DataYear, Month, Day-
Quiet Mode Automatic TimeEnable/Disable Disable
Entry time to Exit timePM 10:00 ~ AM 06:00
Indoor Zone OptionCool/Heat SelectionCool & Heat/Heat onlyCool & Heat
Main/Sub Wired RemoteMain/Sub Main
Zone Selection Zone 1/Zone 2Zone 1
Standard TemperatureWater Outlet/IndoorWater Outlet
Temperature UnitCelsius(°C):1°C/0.5°C/0.1°C0.5°C
Temperature Sensor SelectionWired Remote Controller/External Temperature SensorWired Remote Controller
Room Temperature CalibrationReference Temperature-9 to 40°C-
Calibration Value-9.9 to 9.9°C0°C
Indoor Zone OptionIndoor Zone Status InformationCentral : ON/OFF -
Normal Power : ON/OFF -
Mode : Heat/Cool/Auto -
DHW Power : ON/OFF -
DHW Mode :Economic/Standard/Power/Forced-
Water Pump : ON/OFF -
BUH : ON/OFF -
BSH : ON/OFF -
Flow sensor : lpm -
Inverter Pump :0% ~ 100%-
EEV Step :0~2000Step-
Thermostat 1 :ON/OFF -
Thermostat 2 :ON/OFF -
DHW Thermostat :ON/OFF -
Water pressure :0 ~ 00.0 bar-
Connection InformationNumber of Connection0 to 16-
View Master Indoor UnitAddress -
Master Indoor Zone InformationSerial No. :--
Indoor Unit Eva In Temp.(Teva_in) :Temperature-
Indoor Unit Eva Out Temp.(Teva_out) :Temperature-
Indoor Unit PHE IN(Tw1) :Temperature-
Indoor Unit PHE OUT(Tw2) :Temperature-
DHW Tank Temp. (Tt) :Temperature-
DHW Mode :Economic/Standard/Power/Forced-

Installation/Service mode

Step 1 Step 2Step 3 DescriptionDefault
Device InformationMicom Code : Micom code -
Program Version : Modified date -
Touch Code : Touch IC code -
Program Version : Modified date -
Graphic Image : Graphic image code -
Program Version : Modified date -
Reset All Service ModesErase All Service mode data--
Initialize a remote controller--
Power Master Reset 1)* --
ODU K3 Reset -
Field Setting Value10** --
20** --
30** --
40** --
50** --
Simple Setting--
FSV Upload/Download--
Self-Test ModeSelf-Test Mode DisplayWater Inlet Temp. :Temperature -
Water Outlet Temp. :Temperature -
Backup Heater Outlet Temp. :Temperature -
Mixing Valve Outlet Temp. :Temperature -
Tank Temp. : Temperature -
Indoor Ambient Temp. :Temperature -
Indoor Ambient Temp.(Zone 2) :Temperature -
Water Outlet Temp. (Zone 1) :Temperature -
Water Outlet Temp. (Zone 2) :Temperature -
Thermostat #1(Zone 1) :Heat/Cool -
Thermostat #2(Zone 2) :Heat/Cool -
Solar Panel ON/OFF -
Water Pump ON/OFF OFF
Booster Heater ON/OFF OFF
DHW Valve(3Way Valve)ON/OFF OFF
Zone 1 Valve ON/OFF OFF
Backup Heater 1 + Water PumpON/OFF OFF
Backup Heater 2 + Water PumpON/OFF OFF
Backup Boiler ON/OFF OFF
Zone 2 Valve ON/OFF OFF
Mixing Valve ON/OFF OFF
Indoor Unit OptionAddressMain address 00to 4F -
RMC address 00to FE -
Product Option 2)^* Refer to the installation manual of the connected indoor unit.-
Installation Option 1 2)^* -
Installation Option 2 2)^* -
MCU PortMCU address 00to 15 -
MCU Port A to F -

1)* Power Master Reset is a setting needed to supply optimized power to wired remote controller when multiple indoor units are connected to wired remote controller in a group. 2)* The total option codes are 24 digits. You can set six digits at a time and it is distinguished by page number. Press the OK button to move to the next page.

SAMSUNG MIM-E03DN - Installation/Service mode - 1

NOTE

- Address is displayed in hexadecimal. Please refer to the following table.

Hexadecimal Decimal Hexadecimal Decimal Decimal
00 0 10 16 20 32
01 1 11 17 2133
022 1218 2234
033 13 1923 35
04414202436
05515212537
06616222638
07717232739
08818242840
099 19 25 2941
0A101A262A42
0B111B27 2B 43
0C 121C28 2C 44
0D131D292D45
0E 141E30 2E46
0F151F312F47
Hexadecimal Decimal Hexadecimal Decimal
30484064
31494165
32 504266
3351 4367
34 52 4468
35 53 4569
36 54 4670
37554771
38 56 4872
39574973
3A 584A74
3B59 4B75
3C604C76
3D 61 4D77
3E 62 4E78
3F 63 4F79

How to upload or download field settings (example)

1 Insert an SD card into the Sub PBA SD Card slot on the Hydro unit. 2 Select Field Setting Value in the Service mode. 3 Press the or button to select FSV Upload/Download.

SAMSUNG MIM-E03DN - How to upload or download field settings (example) - 1

NOTE

  • Upload: Uploads the FSV data of the Hydro unit to the SD card.
  • Download: Downloads the FSV data of the SD card to the Hydro unit.
  • The upper-level controllers excluding Wi-Fi kit (2.0) and MWR-WW10** wired remote controller cannot use the 2-zone control and energy monitoring.
  • When connecting between the MWR-WW10** wired remote controller and an upper-level controller, the settings for FSV (4061) must be changed not to use the 2-zone control.

Field setting mode

SAMSUNG MIM-E03DN - Field setting mode - 1

CAUTION

- Set the FSV value of the product other than the specified models by referring to the FSV label provided with the manual of the product, and then attach it on the control box's cover. The FSV values in the table are applied to the specified models.

SAMSUNG MIM-E03DN - CAUTION - 1

NOTE

- Be sure to reset the power when changing the FSV (#3041 to 3046) of disinfection operation and the FSV (#5011 to 5019) of setting the outing mode.

Field Setting Value (FSV) 10**

Code 10** : Upper and lower temperature limits of each operation mode of wired remote controller Heating(Water Out, Room), Cooling(Water Out, Room), DHW(Tank)

- The values in the following table are just examples for your understanding.

Main Menu & CodeMenuFunctionSub CodeMODEL CODE: AE200(260)RNW***/ AE200(260)CNW***MODEL CODE: MIM-E03DN/ AE***CXYB*G
Setting Standard Setting Standard
ItemStepUnitDefaultMin.Max.DefaultMin.Max.
Remote Controller Setting Range Code 10**CoolingWater Out Temperature for CoolingMax1 °C101125 1825 25 1825
Min1°C10121651816518
Room Temperature for CoolingMax1°C1021302830302830
Min1°C1022181828181828
HeatingWater Out Temperature for HeatingMax1 °C1031 65/70/751* 37 65/70/751* 65/70/751* 37 65/70/751*
Min1°C1032251537251537
Room Temperature for HeatingMax1°C1041301830301830
Min1°C1042161618161618
DHWDHW tank TemperatureMax1 °C1051 55/63/701* 5070 55/63/701* 5070
Min1°C1052403040403040
Hysteresis for Thermo ONWater Out Hysteresis for Heat0.5°C1061007007
Water Out Hysteresis for Cool0.5°C1062117117
Room Hysteresis for Heat0.5°C1063007007
Room Hysteresis for Cool0.5°C1064117117

SAMSUNG MIM-E03DN - Field Setting Value (FSV) 10** - 1

NOTE

- The FSV #3011 in the wired remote controller should be set to 1 or 2 to use the DHW mode.

• 1)*The value is determined according to the type of outdoor unit.

Remote Controller Setting Range: Code 10**

Space Cooling

  • Target water outlet temperature : Upper limit(#1011, Default 25°C, Range : 18 ~ 25°C), Lower limit(#1012, Default 16°C, Range : 5 ~ 18°C)
  • With this default FSV settings, user can change the target water outlet temperature within the range of 16 ~ 25°C for cooling.
  • Target room temperature : Upper limit(#1021, Default 30°C), Lower limit(#1022, Default 18°C)
  • With this default FSV settings, user can change the target room temperature within the range of 18 ~ 30°C for cooling.

Space Heating

  • Target water outlet temperature: Upper limit (#1031, Default 65/70/75°C, Range: 37 ~ 65/70/75°C), Lower limit (#1032, Default 25°C, Range: 15 ~ 37°C)
  • With these default FSV settings, the user can change the target water outlet temperature within the range of 25 ~ 65/70/75°C for heating.
  • Target room temperature: Upper limit (#1041, Default 30°C), Lower limit (#1042, Default: 16°C)
  • With these default FSV settings, the user can change the target room temperature within the range of 16 ~ 30°C for heating.

DHW Heating

  • Target DHW tank temperature: Upper limit (#1051, Default 55/63/70°C, Range: 50 ~ 70°C), Lower limit (#1052, Default 40°C, Range: 30 ~ 40°C)
  • With these default FSV settings, the user can change the target tank temperature within the range of 40 ~ 55/63/70°C for DHW heating.

Hysteresis

If the value of the FSV is large, it takes longer to thermo on.

• Water outlet temperature control by hysteresis (heating) Ex) When target water outlet temperature is 55°C, thermo off temperature is 57°C and thermo on temperature is 55°C - FSV#1061 (Default 0°C, Range 0~7°C) • Water outlet temperature control by hysteresis (cooling) Ex) When target water outlet temperature is 7°C, thermo off temperature is 7°C and thermo on temperature is 7°C + FSV#1062 (Default 1°C, Range 1~7°C) • Room temperature control by hysteresis (heating) Ex) When target room temperature is 30°C, thermo off temperature is 32°C and thermo on temperature is 30°C - FSV#1063 (Default 0°C, Range 0~7°C) • Room temperature control by hysteresis (cooling) Ex) When target room temperature is 18°C, thermo off temperature is 18°C and thermo on temperature is 18°C + FSV#1064 (Default 1°C, Range 1~7°C)

Field Setting Value (FSV) 20**

Code 20** : Water law design and external room thermostat Heating (2 WL's for floor & FCU), Cooling (2 WL's for floor & FCU), WL & Thermostat types

- The values in the following table are just examples for your understanding.

Main Menu & CodeMenuFunctionSub CodeMODEL CODE: AE200(260)RNW***/ AE200(260)CNW***MODEL CODE: MIM-E03DN/ AE***CXYB*G
Setting Standard Setting Standard
Item Step Unit Default Min. Max.Default Min. Max.
Water Law Code 20**HeatingOutdoor Temperature for Heating Water LawMax (Point 1)1°C2011-10-205-10-205
Min (Point 2)1°C2012151020151020
Water out Temperature for WL1 Heating (UFHs)Max (Point 1)1°C20214017 65/70/751* 4017 65/70/75 *
Min (Point 2)1 °C2022 2517 65/70/751* 2517 65/70/75 *
Water out Temperature for WL2 Heating (FCUs)Max (Point 1)1 °C2031 5017 65/70/751* 5017 65/70/75 *
Min (Point 2)1°C20323517 65/70/751* 3517 65/70/75 *
Heating Water Law SelectionWL Type--20411(WL1)121(WL1)12
CoolingOutdoor Temperature for Cooling Water LawMax (Point 1)1°C2051302535302535
Min (Point 2)1°C2052403545403545
Water out Temperature for WL1 Cooling (UFHs)Max (Point 1)1°C20612552525525
Min (Point 2)1°C20621852518525
Water out Temperature for WL2 Cooling (FCUs)Max (Point 1)1°C20711852518525
Min (Point 2)1°C207255255525
Cooling Water Law SelectionWL Type--20811(WL1)121(WL1)12
External ControlExternal Room Thermister#1 (UFHs)1-20910(No)040(No)04
#2 (FCUs)1-20920(No)040(No)04
Remote ControllerRemote Controller Room Temp. Control1-2093414414

SAMSUNG MIM-E03DN - Field Setting Value (FSV) 20** - 1

NOTE

• 1)* The value is determined according to the type of outdoor unit.

Water Law & Room Thermostat/ Wired remote controller: Code 20**

| Time Period | Temperature (Ta) | Location | # | | :--- | :--- | :--- | :--- | | #2011 | 2 | Heating WL | 1 | | #2012 | 2 | Cooling WL | 1 | | #2051 | 2 | Heating WL | 1 | | #2052 | 2 | Cooling WL | 1 | | #2061 | 2 | Cooling WL | 1 | | #2062 | 2 | Cooling WL | 1 | | #2062/2072 | 2 | Cooling WL | 1…

Water Law for Heating

- Outdoor air temperature range: Lower limit 1 (#2011, Default -10°C, Range: -20 ~ 5°C), Upper limit 2 (#2012, Default 15°C, Range: 10 ~ 20°C) - With these default settings, the water outlet temperature by heating water law can be changed within the outdoor temperature range of -10 ~ 15°C.

- Water outlet temperature range for floor/FCU applications respectively: Upper limit 1 (#2021/2031, Default 40/50°C, Range: 17 ~ 65/70/75°C), Lower limit 2 (#2022/2032, Default 25/35°C, Range: 17 ~ 65/70/75°C)

- With these default settings, the water outlet temperature by heating water law can be changed within the range of 25/35 ~ 40/50°C.

- In case that 2 zone control is not used (FSV# 4061 = 0) and the external room thermostat is not used (FSV#2091 = 0, #2092 = 0). Type of water law according to heating devices (floor/FCU): #2041 (Default 1 (WL1 for floor), 2 (WL2 for FCU or radiator))

Water Law for Cooling

- Outdoor air temperature range: Lower limit 1 (#2051, Default 30°C, Range: 25 ~ 35°C), Upper limit 2 (#2052, Default 40°C, Range: 35 ~ 45°C). With these default settings, the water outlet temperature by cooling water law can be changed within the outdoor temperature range of 30 ~ 40°C.

- Water outlet temperature range for floor/FCU applications respectively: Upper limit 1 (#2061/2071, Default 25/18°C), Lower limit 2 (#2062/2072, Default 18/5°C) - With these default settings, the water outlet temperature by cooling water law can be changed within the range of 5/18 ~ 18/25°C.

- In case that 2 zone control is not used (FSV# 4061 = 0) and the external room thermostat is not used (FSV# 2091 = 0, #2092 = 0). Type of water law according to cooling devices (floor/FCU): #2081 (Default 1 (WL1 for floor), 2 (WL2 for FCU or radiator))

- Do not set WL1 below 16 degrees to prevent floor condensation when using underfloor cooling.

External Room Thermostat (Field Option)

- Terminal #1 (#2091, Default 0 for no usage), #2 (#2092, Default 0 for no usage)

  • To use wired remote controller for heating/cooling operation, both of the above settings should be set to 0 simultaneously. If not, thermostat controls system.
  • To use the External Room Thermostat option, set the 2-zone control option (FSV #4061) to "0" to disable it.
  • If set to #2091/#2092 1, the compressor can be turned on or off only by the thermostat.

- If set to #2091/#2092 2~4, the compressor can be turned on or off by the thermostat or according to the WL discharged water temperature. (#2092 2: WL Thermo off → Water pump off, #2092 3: WL Thermo off → Water pump on, #2092 4: WL Thermo off → Water pump 7 min off → 3 min on → ...).

#20922, Water pump ON ON OFF OFF Time Water law Thermo 1 0 1min Time

| Time | Water pump | Water law Thermo | |------|------------|------------------| | 0 | 1 | 0 | | 1 | 1 | 0 | | 0 | 1 | 0 |

| Time | ON | OFF | | ------------- | ---- | --- | | 0 | 1 | 0 | | 3min | 0 | 1 | | 7min | 1 | 0 | | 3min | 0 | 1 |

- During thermostat operation, the user can shift the target water temperature up or down within the range of -5 to +5 °C.

  • When the Room thermostat is used, the floor valve should be connected to 2-way valve #1, and the FCU valve should be separately connected to 2-way valve #2 of the Hydro Unit PBA.
  • When only floor cooling/heating is installed and if the Water Law or outlet water temperature is too low, the 2-way valve may close and E911 error may occur.
  • When the floor and FCU units are installed together and operating in cooling mode, the floor valve may close and E911 may occur to prevent floor condensation when the outlet water temperature is below 16 °C. Therefore, the FCU should secure a minimum value for the flow rate.
  • Thermostat #2, which controls the FCU, has priority for operation modes and discharge water temperature.
  • Samsung is not responsible for accidents such as floor condensation that can occur by not connecting the valve to the zone #1 port of the Hydro Unit PBA.

Remote controller room temperature control

• Control by room temperature sensor (Service mode) - If set to #2093 1, the compressor can be turned on or off only by the room temp sensor. - If set to #2093 2~4, the compressor can be turned on or off by the room temp sensor or according to the WL discharged water temperature. (#2093 2: WL Thermo off → Water pump off, #2093 3: WL Thermo off → Water pump on, #2093 4: WL Thermo off → Water pump 7 min off → 3 min on → ...).

Field Setting Value (FSV) 30**

Code 30**: User's options for Domestic Hot Water (DHW) tank heating

• The values in the following table are just examples for your understanding.

Main Menu & CodeMenuFunctionSub CodeMODEL CODE: AE200(260)RNW***/ AE200(260)CNW***MODEL CODE: MIM-E03DN/ AE***CXYB*G
Setting Standard Setting Standard
Item Step Unit DefaultMin. Max.Defaultt Min. Max.
Domestic Hot Water Tank Code 30**DHWDHW mode activateDHW mode--3011102002
Heat PumpMax. Temp. 1°C302155/63/70 °*4555/63/70 °*55/63/70 °*4555/63/70 °*
Stop1°C302200102010
Start1°C302355305530
Min. Operating Time1min302451205120
Max. Operating Time5min30253059530595
Operation Interval0.5hour302630.51030.510
Booster HeaterOn/Off--30311 (On)0 (Off)10 (Off)0 (Off)1
Delay Time5min3032202095202095
Overshoot1°C3033004004
DisinfectionOn/Off--30411 (On)0 (Off)11 (On)0 (Off)1
Interval1day3042Fri (5)Sun (0)All (7) Fri (5)Sun (0)All (7)
Start Time1 o'clock 304323 (AE***RNW***)02314023
14 (AE***CNW***)
Target Temp.5°C3044704070704070
Duration5min30451056010560
Max time1hour304681248124
Forced DHW OperationTimer OFF Function--30510 (No)01 (Yes)0 (No)01 (Yes)
Time Duration1(x10)min305263306330
Solar Panel/ DHW ThermostatH/P Combination1-30610 (No)020 (No)02
3-way ValveDefalut Direction--30710 (Room)01 (Tank)0 (Room)01 (Tank)
Domestic Hot Water Tank Code 30**Addition FunctionEnergy meteringBackup Heater 1step capacity1kW3081216216
Backup Heater 2step capacity1kW3082206206
Booster Heater capacity1kW3083316316

SAMSUNG MIM-E03DN - Field Setting Value (FSV) 30** - 1

NOTE

• 1)* The value is determined according to the type of outdoor unit.

The FSV #3011 in the wired remote controller should be set to 1 or 2 to use the DHW function.

If FSV #3011 is set to 1, the DHW operation starts based on the thermo-on temperature. If FSV #3011 is set to 2, the DHW operation starts based on the thermo-off temperature.

(For example, when the current temperature becomes 45°C under the conditions that the thermo-on temperature is 43°C and the thermo-off temperature is 48°C, the DHW turns off if FSV #3011 is set to 1 and DHW turns on if FSV #3011 is set to 2.)

Heat Pump Variables for Controlling DHW Tank

  • Maximum DHW tank temperature with heat pump operation: FSV #3021, Default 55/63/70°C, Range: 45 ~ 55/63/70°C.
  • Temperature difference determining the heat pump OFF temperature: FSV #3022, Range: 0 ~ 10°C.
  • Temperature difference determining the heat pump ON temperature: FSV #3023, Default 5°C, Range: 5 ~ 30°C.

[DHW Tank water temperature thermo on/off control]| Label | Value | | ----------- | ----- | | Tc > THP MAX | #3021 | | Tc ON | #3023 | | Tc OFF | #3022 |

Tc < THP MAX T(C) #3021 Tc MAX TU=THP OFF THP ON #3023 TU T(

Tu: User set temp. T(C): Temp. (Celsius)

- DHW heating mode timer: Mode timer manages the operation terms when there are simultaneous requests of space heating/cooling and DHW.

  • FSV #3024 (minimum Space heating operating time, Default 5 min., Range 1 ~ 20 min.), #3025 (maximum DHW time, Default 30 min., Range 5 ~ 95 min.), #3026 (maximum space heating operation time, Default 3 hour, Range 0.5 ~ 10 hour)
  • Maximum operation time is applied only when both DHW and Space heating request operation. DHW or Space heating operates continuously until reaching the target temperature without time limitation in the single operation.

[Time variation control of DHW and space heating mode]| Event | Time Label | | ------------------- | -------------- | | Space heating request | 1 | | DHW request | 0 | | DHW operation | 1 | | Space heating operation | 0 |

[Time variation control of Heat pump and booster heater of DHW]| Event Type | Value | | ------------------ | ----- | | Heating request | 1 | | DHW request | 1 | | H/P Operation | 1 | | Booster Operation | 1 |

SAMSUNG MIM-E03DN - Heat Pump Variables for Controlling DHW Tank - 5

NOTE

  • The FSV #4022 for booster heater priority should be set to "0 (both)" or "2" (booster) to use booster heater.
  • If not (backup heater priority), the booster heater can be operated in case of no backup heater demand.

Booster Heater Variables for Controlling DHW Tank

  • The FSV #3031 should be set to "1(On)" (Default) to use booster heater as an additional heat source for DHW tank.
  • Booster heater startup delay timer: In case of DHW request, this timer will delay the operation of booster heater compared to heat pump.
  • FSV #3032 (Default 20 min., Range 20 \~ 95 min.), In "Power/Forced" DHW mode, the delay timer will be neglected, and the booster starts immediately.
  • In "Economic" DHW mode, the DHW heating will be conducted only with heat pump.
  • 3032 should be smaller than the maximum H/P time (#3025). If the delay time is set too high, it might take very long time for DHW heating.

- Temperature difference determining the booster heater OFF temperature (T_BH OFF = Tu + #3033): FSV #3033, Default 0°C, Range: 0 \~ 4°C.

- Temperature difference determining the booster heater ON temperature (T_BH ON = T_BH OFF - 2)

Case 1) When set temperature is 70° C

BSH is ON at less than 68 degrees, OFF at more than 70°C.

Case 2) When setting temperature is 50°C (FSV 3022 = 0 condition)

Heat pump and BHS are ON at less than 45 degrees, OFF at more than 50°C

(Thermo off / on operation temperature is used together)

[Thermo on/off control of Heat pump and Booster Heater]

Case 1: When set temperature(Tu) > ThpMAX(FSV #3021) 1)*| Phase | Temperature (°C) | |-------|------------------| | Off | 2°C | | ON | 3022 | | ON | 3033 |

Case 2: When set temperature(Tu) ≤ ThpMAX(FSV #3021) 1)*| Time Point | HP & BH | | :--- | :--- | | 1 | 0 | | 2 | High peak | | 3 | Low peak | | 4 | High peak | | 5 | Low peak | | 6 | High peak | | 7 | Low peak | | 8 | High peak | | 9 | Low peak | | 10 | High peak | | 11 | Low peak | | 12 | High peak | | 13 | Low peak | | 14 | High peak | | 15 | Low peak…

SAMSUNG MIM-E03DN - [Thermo on/off control of Heat pump and Booster Heater] - 3

NOTE

• 1)* The value is determined according to the type of outdoor unit.

- "Power/Forced/Standard" DHW mode operation without booster heater installed, DHW mode operates as a heat pump only.

Disinfection Function

1) "Booster heater" Disinfection

- The FSV #3041 should be set to "1 (On)" (Default) to use disinfection function.

- Scheduling : Day (#3042, Default "Friday"), starting time [#3043, Default "23:00" (AE***RNW***)], target tank temp. (#3044, Default "70°C"), duration (#3045, Default 10 min.)

[Time variation control of Heat pump and booster heater of DHW]| Time (t) | T_H (T_H) | T_U (T_U) | | :--- | :--- | :--- | | 00:00 | T_H | T_U | | 23:00 | T_H | T_U | | 24:00 | T_H | T_U | #3044 | T_H | T_U | #3045 | T_H | T_U | #3043 | T_H | T_U |

2) "R290 Heat Pump" Disinfection

- The FSV #3041 should be set to "1 (On)" (Default) to use the disinfection function.

- When FSV#3031 is set to "0 (Off)", the disinfection function is performed only by the heat pump to reach the target tank temperature.

- Scheduling: Day (#3042, Default "Friday"), starting time (#3043, Default "14:00"), target tank temp. 60°C, duration 60 min.

[Time variation control of heat pump of DHW]| t | T_H | T_U | | -------------- | ----- | ----- | | 00:00:01:0013:0014:0015:00 | TH | TU | | 00:00:01:0013:3043:0015:00 | 60min | 3043 |

3) "R290 Heat Pump + Booster Heater" Disinfection

- The FSV #3041 should be set to "1 (On)" (Default) to use the disinfection function.

- When FSV#3031 is set to "1 (On)", the disinfection function is performed by the heat pump to reach a target tank temperature of 60°C. After that, the booster heater is activated and the disinfection function continues until it reaches the target tank temperature (#3044, default 70°C), for a duration specified by (#3045, default 10 min).

- Scheduling: Day (#3042, Default "Friday"), starting time (#3043, Default "14:00"), target tank temp. (Default "70°C"), duration (Default 10 min.)

[Time variation control of heat pump of DHW]| Time | Temperature | | ----------------- | ----------- | | 00.0014:0015:00 | T_H | | | 60°C | | | T_U | | | 60°C | | | T_H | | | 3044 | | | 3045 | | | 3043 |

SAMSUNG MIM-E03DN - Disinfection Function - 4

NOTE

  • The disinfection function is available only when a booster heater is connected. (However, AE***CXY*** is also capable of Heat Pump Disinfection.)
  • R290 Mono Outdoor Unit (AE***CXYD*G) and Hydro Unit (AE***CNW**), Control Kit (MIM-E03DN) combination or R290 Mono Outdoor Unit (AE***CXYB*G) standalone model can be operated in disinfection mode without a booster heater.
  • Hydro Unit (AE***RNW***) can only be operated for disinfection with a Booster Heater.
  • During disinfection operation of heat pumps, regardless of settings, PV/smart grid/solar interlocking/boiler interlocking control do not work.
  • Check tank capacity, booster heater capacity, and booster heater for issues if disinfection operation does not work normally over the maximum operation time (E919 error).

Forced DHW by User's Input

  • Forced mode can be activated by changing setting the FSV #3011 to 1/2 (USE).
  • Forced mode shall be working depending on Timer setting (#3051, #3052).

Additional Solar panel/DHW thermostat Installation for DHW with Heat Pump (Field Option)

  • Solar panel and heat pump are able to operate simultaneously by setting value. (FSV #3061, "1")
  • When using DHW thermostat, set the FSV #3061, "2".
  • There is one minute delay of 2-way / 3-Way valve closing whereas no delay of valve opening.
  • Individual zone control is only available with external thermostat. • FSV 3071 determines a 3-way direction.

Energy metering

- To accurately indicate energy consumption, the capacity of the backup heater and booster heater must be set using FSV #3081 / 3082 / 3083.

SAMSUNG MIM-E03DN - Energy metering - 1

NOTE

- Energy metering measurements are made by the product and can differ from actual energy consumption.

Field Setting Value (FSV) 40**

Code 40** : User's options for heating devices including internal backup heater and external boiler

- The values in the following table are just examples for your understanding.

Main Menu & CodeMenuFunctionSub CodeMODEL CODE: AE200(260)RNW***/ AE200(260)CNW***MODEL CODE: MIM-E03DN/ AE***CXYB*G
Setting Standard Setting Standard
Item Step Unit Default Min. Max. Default Min. Max.
Heating Code 40**HeatingHeat PumpHeating / DHW priority- -4011 0 (DHW)01 (Heating)0 (DHW)01 (Heating)
Low Outdoor Temp. for Heating Priority1°C40120-15200-1520
Heating Off Temp.1°C4013 35/451 * 14 35/451 * 35/451 * 14 35/451 *
Backup HeaterOn/Off--40210 (No)020 (No)02
BUH/BSH Priority 1- 40222 (BSH)0 (Both)2 (BSH)0 (Both)0 2(BSH)
Cold weather compensation--40231 (Yes)0 (No)11 (Yes)0 (No)1
Threshold Temp.1°C40240-25350-2535
Defrost Backup Temp.5°C4025151055151055
Backup BoilerBack-up Boiler On/Off--40310 (No)01 (Yes)0 (No)01 (Yes)
Boiler Priority--40320 (No)01 (Yes)0 (No)01 (Yes)
Threshold Condition1°C4033-15-205-15-205
Mixing valveApplication1-40410 (No)020 (No)02
Target ΔT (Heating)1°C40421051510515
Target ΔT (Cooling)1°C40431051510515
Control factor1-4044215215
Control interval1min404521302130
Running Time3(x10) min404696249624
Inverter PumpApplication--4051102102
Target ΔT 1°C4052528528
Control factor1-4053213213
PWM minimum output1(10)%40540 (25%)0 (25%)3 (55%)0 (25%)0 (25%)3 (55%)
Addition FunctionZone controll1-40610 (No)01 (Yes)N/AN/AN/A

SAMSUNG MIM-E03DN - Field Setting Value (FSV) 40** - 1

NOTE

• 1)* The value is determined according to the type of outdoor unit.

Additional heating option : 40**

Heat Pump Variables for Space Heating

  • FSV #4011 for DHW priority is set to "O(DHW)" (Default) as a default. Space heating gets a priority by setting FSV #4011 "1", but this is only valid when the outdoor temperature is lower than the specified temperature defined by FSV #4012.
  • When priority is on DHW, DHW mode (FSV #3025, default 30 mins) and space heating (FSV#3026, default 180 mins) alternately operate, and when priority is on space heating, they operate as space heating mode.
  • Space heating off temperature(FSV #4013, Default "35/45°C", Range 14 ~ 35/45°C): At high outdoor temperature above this value, the space heating will be turned off, to avoid overheating.

Backup Heater Variables for Space Heating

  • The FSV #4021 should be set to 1(Yes) to use 2-stage electric backup heater in hydro unit as an additional heat source. (If FSV # 4021 is 2, a 1-stage electric backup heater is used) • To configure the backup heater's operating conditions by setting FSV #4023 and FSV #4024.
  • When FSV #4023 is set to 0, the backup heater operates regardless of the outdoor temperature.
  • When FSV #4023 is set to 1(Default), the backup heater operates when the outdoor temperature is below FSV #4024 (Default "0") to save energy; its operation is restricted at FSV #4024 or higher.
  • The FSV #4022 for backup heater priority should be set to "0 (both)" (Default) or "1" (backup) to use backup heater. If not (booster heater priority), the backup heater can be operated in case of no booster heater demand.
  • The threshold temperature for backup heater operation during defrost mode to prevent cold draft because of chilled water can be controlled by adjusting FSV #4025. Under FSV #4025 of water outlet temperature, backup heater Will be turned on.

SAMSUNG MIM-E03DN - Backup Heater Variables for Space Heating - 1

NOTE

- To use both backup heater and booster heater together at the same time as set FSV#4022="0", please check the capacity of the power circuit breaker of your house before use.

External Backup Boiler for Space Heating (Field Option)

  • The FSV #4031 should be set to "1 (Yes)" to use a backup boiler as an additional heat source. (default: "0 (No installation)")
  • Priority of backup boiler and heat pump is defined by FSV #4032 (default: "0 (OFF)")
  • To compensate the lowered heat pump heating performance under very cold weather conditions, the backup boiler operates instead of heat pump under the threshold temperature (FSV #4033, Default "-15°C", Range -20 \~ 5°C).

Mixing valve Installation (Field Option)

- The FSV #4041 should be set to "1 or 2" to use mixing valve.

※ 4041 = 1 : Controlled based on the temperature difference (4042, 4043)

※ 4041 =2 : Controlled based on the temperature difference of the WL value

ex) Heating <#4041=1> <#4041=2>

| Ta | Tw2 | | ---- | ---- | | 4042 | 4042 |

| Ta | FCU WL | Floor WL | | --- | --- | --- | | Low | High | Low | | High | Low | Low |

  • FSV #4042 / #4043 is for adjusting temperature difference between Tw3 (Tw2) and Tw4.
  • FSV #4044 determines the amount of the opening/closing degree of the valve per operation, and the larger the set number, the greater the opening/closing degree per operation. It operates every FSV #4045 set interval.
  • When using mixing valve, FSV #4046 should be matched with mixing valve running time characteristic.

Inverter Pump Installation (Field Option)

  • FSV #4051=1 (Default) : Inverter pump use + Output 100%, FSV #4051=2 : Inverter pump use + Output 70%, FSV #4051=0 : Inverter pump Not use.
  • FSV #4052 is for adjusting the temperature difference between Tw2 and Tw1.
  • FSV #4053 determines the amount of change in PWM output during pump operation; the larger the set value, the greater the change in PWM output per operation.
  • Pump PWM minimum output is limited to 25% to 55% according to FSV #4054. (Setting "0": 25%, "1": 35%, "2": 45%, "3": 55%)

SAMSUNG MIM-E03DN - Inverter Pump Installation (Field Option) - 1

NOTE

- Tw1 (Inlet Water Temp), Tw2 (Discharge Water Temp), Tw3 (Backup Heater Outlet Water Temp), Tw4 (Mixing Valve Temp.)

Zone Control (Field Option)

- For zone control using a wired remote control (install option), FSV #4061 should be set to "1 (Yes)".

SAMSUNG MIM-E03DN - Zone Control (Field Option) - 1

NOTE

- The MIM-E03DN (MONO Control Kit) model does not support this zone control function.

Field Setting Value (FSV) 50**/60**

Code 50**/60**: User's options for extra functions

- The values in the following table are just examples for your understanding.

Main Menu & CodeMenuFunctionSub CodeMODEL CODE : AE200 (260)RNW***/ AE200(260)CNW***MODEL CODE : MIM-E03DN/ AE***CXYB*G
Setting Standard Setting
Item Step Unit Default Min. Max.DefaultMin. Max.
Others Code 50**/60**Outing ModeWater Out Temperature for Cooling1°C50112552525525
Room Temperature for Cooling1°C5012301830301830
Water Out Temperature for Heating1°C5013151555151555
Room Temperature for Heating1°C5014161630161630
Cooling WL1 Temp.1°C50152552525525
Cooling WL2 Temp.1°C50162552525525
Heating WL1 Temp.1°C5017151555151555
Heating WL2 Temp.1°C5018151555151555
DHW tank Temp.1°C5019303070303070
DHW SavingDHW Saving Temp1°C502150405040
DHW Saving Mode1-5022001001
DHW Saving Thermo on Temp.1°C50232504025040
Power Peak ControlApplication--50410 (No)01 (Yes)0 (No)01 (Yes)
Select forced off parts1-50420 (All)030 (All)03
Using input voltage--50431 (High)0 (Low)11 (High)0 (Low)1
Frequency Ratio Control--50510 (No)01 (Yes)0 (No)01 (Yes)
Others Code 50**/60**Additional FunctionPV ControlApplication 1 - 5081 0 (No)01 (Yes)0 (No)01 (Yes)
Setting Temp Shift Value (Cooling)1°C508221202120
Setting Temp Shift Value (Heating)1°C508321502150
Smart Grid ControlApplication1-50910 (No)01 (Yes)N/AN/AN/A
Setting Temp Shift Value (Heating)1°C50922150N/AN/AN/A
Setting Temp Shift Value (DHW)1°C50935140N/AN/AN/A
DHW Mode (Target Tank Temp.)1-5094001N/AN/AN/A
Outdoor UnitHeating Outdoor Unit ControlMinimum Thermo ON operating time limit1min602255305530
Optional Thermo On/Off1-60311 (Yes)0 (No)1 (Yes)1 (Yes)0 (No)1 (Yes)
Thermostat ControlType"0": 2 way valve "1": Water pump1-6041001001

Others: Code 50**/60**

Outing Mode

- Under holiday mode, all target temperatures – space heating and cooling, water law, DHW, and room temperature – are set to the values defined in the above table.

SAMSUNG MIM-E03DN - Outing Mode - 1

NOTE

- With the lowered target temperatures (FSV #5011 \~ #5019), the system operates normally.

- DHW heating only by the heat pump to save energy (Operated in Eco mode of wired remote control) Target DHW temperature is lower than the temperature set by user. The temperature difference is defined by FSV #5021. (default: 5°C) If user sets the temperature 45°C, the system sets the target temperature 40°C with the default setting.

  • If user want additional energy saving, use a "Saving mode" (#5022, default: 0, OFF)
  • The user can set the "Thermo On" temperature during "Saving mode" using FSV #5023

Peak Power Control

  • If users make contracts with local electric power company for limiting the amount of power consumption when a surge in power usage, users can set FSV of "Forced off".
  • According to FSV (#5041), Default is Non-usage. And According to FSV (#5042), If input is "0 (default)", Back up heater (BUH) is unavailable while external contact is high. If input is "1", Only Compressor(Heat Pump) is available. If input is "2", Only Booster Heater (BSH) is available. If input is "3", nothing is available.
[D-00] Compressor Back up heater Booster heater
0 (Default) Permitted Forced off Permitted
1 Permitted Forced off Forced off
2 Forced off Forced off Permitted
3 Forced off Forced off Forced off
  • Applying the control when power voltage of input contact is high is default. According to FSV (#5043), it is available to adopt this logic in low condition exceptionally.
  • When Peak power control is applied, the system is subject to "Forced OFF" according to the set value. Therefore, appropriate measures such as antifreeze are necessary to prevent freezing at low temperatures.

FR Control(Frequency ratio control) - Display "DR" on wired remote control

  • This is to limit the maximum frequency of the outdoor unit compressor. (if #5051 = 1 "use")
  • Method 1: External DC signal Control uses a DC voltage of 0 10V ( 0v = 50% , 10v = 150% )
  • Method 2: Demand ratio (DR) control through Modbus communication.

Outdoor Unit Control

• Minimum Thermo ON operating time limit (FSV#6022): Minimum operating time after outdoor unit starts. - Heating Optional Thermo On/Off Function (FSV#6031): Function to induce an increase in efficiency during operation by stopping the outdoor unit when the outdoor unit is continuously operated at a low operating frequency during heating operation.

Thermostat Control Type (FSV #6041)

- When external room thermostat setting (FSV #2091, #2092) is set to use, it is applied as follows.

FSV #6041 TypeOutput when all thermostat contact is OFF
0 2way valve ControlOpen
1Secondary Pump ControlOFF

- When external room thermostat setting (FSV #2091, #2092), 2Zone Control (FSV #4061) are set to unuse, it is applied as follows.

FSV #6041DWH modeNot DWH mode
0CloseOpen
1CloseOpen for Thermo ON, Close for Thermo Off

PV Control (Photovoltaics control)

This is for energy saving by using the solar energy.

The FSV #5081 should be set to "1(Yes)" for PV control. (However, Peak power control can not be used at the same time.)

FSV 0 1
#5081 Disable (Default) Activation

SAMSUNG MIM-E03DN - PV Control (Photovoltaics control) - 1

NOTE

  • Except for how water mode, This function is activated only for the outing mode. • Cooling mode (FSV #5082 = 2°C, Default)
  • Room sensor setting: Current setting value - FSV #5082 (Min = FSV #1022)
  • Water outlet setting: Current setting value - FSV #5082 (Min = FSV #1012)
  • Water law setting: Current setting value - FSV #5082 (Min = FSV #2061, #2062, #2071, #2072)

- Heating mode (FSV #5083 = 2°C, Default)

– Room sensor setting: Current setting value + FSV #5083 (Max = FSV #1041) - Water outlet setting: Current setting value + FSV #5083 (Max = FSV #1031) - Water law setting: Current setting value + FSV #5083 (Max = FSV #2021, #2022, #2031, #2032)

- Hot water mode

- Thermo on operation regardless of outing mode: Setting temperature = Max temperature of hot water mode (FSV #1051)

Smart Grid Control

SAMSUNG MIM-E03DN - Smart Grid Control - 1

NOTE

- MIM-E03DN (MONO Control Kit) model does not support this Smart grid function.

The FSV #5091 should be set to "1(Yes)" for Smart Grid control.

FSV 0 1
#5091 Disable (Default) Activation

Operation mode for Smart Grid

Operation Mode Terminal1 Terminal 2
Mode 1 Short Open
Mode 2 Open Open
Mode 3 Open Short
Mode 4 Short Short
  • Mode 1: Forced thermo off operation of all system
  • Mode 2: Normal operation It is equally applied both heating and hot water mode.

- Mode 3: Normal operation (FSV #5092 = 2°C, FSV #5093 = 5°C, Default) The heating and hot water setting temperature are set by the FSV setting value.

  • Heating mode (Room sensor setting) : Current setting value + FSV #5092
  • Heating mode (Water outlet setting): Current setting value + FSV #5092
  • Heating mode (Water law setting) : Current setting value + FSV #5092
  • Hot water mode : Current setting value + FSV #5093

- Mode 4: When operating, the set temperature is reflected as follows.

Hot water mode

  • 5094=0: Target set temperature is 55/63/70°C. FSV #3021 (Maximum DHW tank temperature with heat pump operation)
  • 5094=1: Target set temperature is 70°C. [If FSV #3031 is 0 (no use of booster heater) or DHW mode is economic mode, the booster heater is not activated.]

Heating mode

  • Heating mode (Room sensor setting): Current set value + FSV #5092 + 3°C (Max = FSV #1041)
  • Heating mode (Water outlet setting): Current set value + FSV #5092 + 5°C (Max = FSV #1031)
  • Heating mode (Water law setting): Current set value + FSV #5092 + 5°C (Max = FSV #2021, #2022, #2031, #2032)

Maintenance activities

- To ensure optimal availability of the unit, a number of checks and inspections on the unit and the field wiring must be carried out at regular intervals, preferably yearly. This maintenance should be performed by a local technician. Besides keeping the remote controller clean with a soft damp cloth, no maintenance is required by the operator.

SAMSUNG MIM-E03DN - Maintenance activities - 1

WARNING

  • During longer periods of standstill, e.g., during summer with a heating-only application, it is very important NOT TO SWITCH OFF THE POWER SUPPLY to the unit.
  • Switching off the power supply stops the automatic repetitive movement of the motor, which prevents it from getting jammed.

Emergency heating / Emergency hot water supply

  • Heating function is performed only by the backup heater if the outdoor unit malfunctions (available only when a backup heater is connected).
  • Enabling the function: Turn off the Control kit Dip S/W #1, and then turn the power off and on.
  • Disabling the function: Turn on the Control kit Dip S/W #1, and then turn the power off and on.
  • Default operation: Automatic heating is performed at a set temperature of 45°C.

  • Hot water is supplied only by the booster heater if the outdoor unit malfunctions.
  • Enabling the function: Turn off the Control kit Dip S/W #2, and then turn the power off and on.
  • Disabling the function: Turn on the Control kit Dip S/W #2, and then turn the power off and on.
  • Default operation: Automatic hot water supply is performed at a set temperature of 50°C. • Emergency hot water supply is available only when a booster heater is connected.

LOW VOLTAGE AREA HIGH VOLT ICE AREA HDDI WED SHEB PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC PDC

Troubleshooting tips

If the unit has some problem to work properly, error codes will be displayed on the wired remote controller. The following table describes the explanation of the error codes.

Display Explanation
120Short- or open-circuit error of the room temperature sensor of the Zone 2 indoor unit (detected only when the room thermostat is used)
121Short- or open-circuit error of the room temperature sensor of the Zone 1 indoor unit (detected only when the room thermostat is used)
653Wired remote controller thermistor SHORT or OPEN
899Zone1 Water Outlet Themistor SHORT or OPEN
900Zone2 Water Outlet Themistor SHORT or OPEN
901Water Inlet thermistor SHORT or OPEN
902PHE Outlet thermistor SHORT or OPEN
903Water Outlet thermistor SHORT or OPEN
904Water TANK thermistor SHORT or OPEN
916Mixing Valve thermistor SHORT or OPEN

graph TD A["Manometer"] --> B["T_w3"] B --> C["E902"] C --> D["T_w2"] D --> E["T_eva out"] E --> F["T_eva in T_w1"] F --> G["E901"] G --> H["PWM Pump"] H --> I["Expansion Vessel(8L)"] I --> J["Flow sensor"] J --> K["Booster heater (3kW)"] K --> L["3-Way V/V 3"] L --> M["Pressure Relief v/v"] M --> N…

Troubleshooting tips

Communication

Display Explanation
601Communication error between remote controller and the Hydro unit
604Tracking error between remote controller and the Hydro unit
654Memory(EEPROM) Read/Write Error(Wired remote controller data error)

E601, E604graph TD A["Room Layout"] --> B["Control Panel"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333

E654

- MEMORY(EEPROM) Read/Write Error (Wired controller data error)

Download connector Micro SD card EEPROM Thermistor Connector F3/F4 Terminal Block

Water pump & Flow Sensor

Display Explanation
911Low flow rate error• in case of low flow rate in 30 sec during water pump signals is ON(Starting)• in case of low flow rate in 15 sec during water pump signals is ON(After starting)
912Normal flow rate error• in case of normal flow rate in 10min during water pump signal is OFF

E911

• Water pump ON (Low flow rate): NOT enough water flow

Water flow < 12LPM (Outdoor unit capacity > 9kW) Water flow < 7LPM (Outdoor unit capacity ≤ 9kW) Water flow < 7LPM (AE080/120/140BXYD**) Water flow < 7LPM (AE050/080/120/160CXYD**)

E912

• Water pump OFF (Normal flow rate)

Water flow > 12LPM (Outdoor unit capacity > 9kW) Water flow > 7LPM (Outdoor unit capacity ≤ 9kW) Water flow < 7LPM (AE080/120/140BXYD**) Water flow > 7LPM (AE050/080/120/160CXYD**)

Display Explanation Error Source
101 Hydro Unit / Outdoor Unit communication connection error Hydro Unit
120Short- or open-circuit error of the room temperature sensor of the Zone 2 indoor unit (detected only when the room thermostat is used)Hydro Unit
121Short- or open-circuit error of the room temperature sensor of the Zone 1 indoor unit (detected only when the room thermostat is used)Hydro Unit
122 EVAInlet temp sensor SHORT or OPEN Hydro Unit
123 EVAOutlet temp sensor SHORT or OPEN Hydro Unit
162 EEPROM Error Hydro Unit
198 Error of Terminal Block's Thermal Fuse(Open) Hydro Unit
201 Hydro Unit / Outdoor Unit communication error(Matching error)Hydro Unit/Ourdoor Unit
202 Hydro Unit / Outdoor Unit communication error(3 min)Hydro Unit/Ourdoor Unit
203 Communication error between INVERTER and MAIN MICOM (4 min) Outdoor Unit
221 Outdoor Unit air temperature sensor error Outdoor Unit
231 Condenser temperature sensor error Outdoor Unit
251 Discharge temperature sensor error Outdoor Unit
320 OLP sensor errorOutdoor Unit
403Plate heat exchanger freeze detection (During cooling operation)Outdoor Unit
404Protection of Outdoor Unit when it is overload (during Safety Start, Normal operation state)Outdoor Unit
407 Comp down due to high pressure sensorOutdoor Unit
416Discharge of a compressor is overheatedOutdoor Unit
419 OUTDOOR UNIT EEV operation errorOutdoor Unit
425Power source line missing error (only for 3-phase model)Outdoor Unit
436Plate heat exchanger freeze detection (During heating operation)Outdoor unit
440Heating operation blocked (outdoor temperature over 35 °C)Outdoor Unit
441Cooling operation blocked (outdoor temperature under 9 °C)Outdoor Unit
458 OUTDOOR UNIT fan1 errorOutdoor Unit
461 [Inverter] Compressor startup errorOutdoor Unit
462 [Inverter] Total current error/PFC over current errorOutdoor Unit
463 OLP is overheated Outdoor Unit
464 [Inverter] IPM over current error Outdoor Unit
465 Compressor overload error Outdoor Unit
466 DC LINK over/low voltage error Outdoor Unit
467 [Inverter] Compressor rotation error Outdoor Unit
468 [Inverter] Current sensor error Outdoor Unit
469 [Inverter] DC LINK voltage sensor error Outdoor Unit
470 Outdoor unit EEPROM Read/Write Error Outdoor Unit
471 Outdoor unit EEPROM Read/Write Error(OTP error) Outdoor Unit
474IPM(IGBT Module) or PFCM temperature sensor ErrorOutdoor Unit
475Outdoor Unit Fan2 errorOutdoor Unit
484 PFC Overload ErrorOutdoor Unit
485 Input current sensor errorOutdoor Unit
500IPM is overheatedOutdoor Unit
507Comp down due to high pressure switchOutdoor unit
536 PHE refrigerant leak errorOutdoor unit
554 Gas leak errorOutdoor Unit
590 Inverter EEPROM Checksum errorOutdoor Unit
601Communication error between the Hydro Unit and wired remote controllerHydro Unit
604Communication tracking error between the Hydro Unit and wired remote controllerHydro Unit
653 Wired remote controller temp sensor SHORT or OPENHydro Unit, Wired Remote Controller
654Memory(EEPROM) Read/Write Error(Wired remote Controller data error)Hydro Unit, Wired Remote Controller
897 Water Tank in sensor error (open/short)Hydro unit
899Short- or open-circuit error of the Zone 1 water-out temperature sensorHydro Unit
900Short- or open-circuit error of the Zone 2 water-out temperature sensorHydro Unit
901Water inlet (PHE) temperature sensor error(open/short)Hydro Unit
902 Water outlet (PHE) temperature sensor error(open/short) Hydro Unit
903 Water outlet (backup heater) temperature sensor error Hydro Unit
904 DHW tank temperature sensor error Hydro Unit
906 Refrigerant gas inlet (PHE) temperature sensor (open/short) Outdoor Unit
907Error due to pipe rupture protection Hydro Unit
908Error due to freeze prevention (Re-operation is possible) Hydro Unit
909Error due to freeze prevention (Re-operation is impossible) Hydro Unit
910Water temperature sensor on water outlet pipe is detached Hydro Unit
911Flow Switch Off Error, When Water pump is running Hydro Unit
912Normal flow rate error• in case of normal flow rate in 10min during water pump signal is OFFHydro Unit
913Six times detection for Flow Switch Error (Re-operation is possible)Hydro Unit
914Error due to incorrect thermostat connectionHydro Unit
915Error on DC fan (Non-operating)Hydro Unit
916Mixing valve sensor errorHydro Unit
917Water Tank Sensor configuration errorHydro Unit
919Error that the set temperature for disinfection operation is not reached, or, after reaching, the temperature fails to continue for the requested timeHydro Unit
973Water pressure error(open/short)Outdoor Unit

This product is India RoHS compliant

SAMSUNG MIM-E03DN - E912 - 2

SAMSUNG MIM-E03DN - E912 - 3

SAMSUNG MIM-E03DN - E912 - 4

SAMSUNG MIM-E03DN - E912 - 5

This appliance is filled with R-32.

DB68-09088A-06

SAMSUNG MIM-E03DN - E912 - 6

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : SAMSUNG

Model : MIM-E03DN

Category : Heat pump