CARRIER Aquazone 50WT - Air conditioner

Aquazone 50WT - Air conditioner CARRIER - Free user manual and instructions

Find the device manual for free Aquazone 50WT CARRIER in PDF.

📄 68 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice CARRIER Aquazone 50WT - page 2
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Water Source Heat Pump
Brand Carrier
Model Aquazone 50WT
Cooling Capacity (BTU/h) 12,000
Heating Capacity (BTU/h) 14,000
Power Supply 208-230V, 1-phase, 60Hz
Dimensions (W x D x H) 21.5 x 21.5 x 18.5 inches
Weight 110 lbs (50 kg)
Refrigerant R-410A
Water Flow Rate 3 GPM
Sound Level (Low Speed) 48 dB
Control Type Microprocessor with remote thermostat
Safety Features Overload protection, freeze protection, high-pressure switch
Maintenance Clean or replace air filter monthly; inspect condensate drain annually
Key Components Hermetic compressor, coaxial water coil, air coil, expansion valve
Repairability Access panels for servicing compressor, fan motor, and control board
Warranty 5 years on compressor, 1 year on parts

Frequently Asked Questions - Aquazone 50WT CARRIER

What is the cooling capacity of the Carrier Aquazone 50WT?
The cooling capacity is 12,000 BTU/h under standard conditions.
What type of refrigerant does this unit use?
It uses R-410A refrigerant, which is environmentally friendly.
Can the Aquazone 50WT be installed in a closet?
Yes, it is designed for closet installation with proper clearances for airflow and service access.
How often should I clean the air filter?
Clean or replace the air filter monthly during peak usage to maintain efficiency.
What does the freeze protection feature do?
It prevents the water coil from freezing by shutting down the compressor if water temperature drops too low.
Is a condensate pump needed?
An optional condensate pump can be added if gravity drainage is not possible.
What is the typical water flow requirement?
The unit requires 3 GPM (gallons per minute) of water flow for proper operation.
How do I reset the unit after a safety shutdown?
Turn off power for 5 minutes, then restore power. The control board will automatically reset.
What is the warranty coverage?
Carrier offers 5 years on the compressor and 1 year on all other parts.
Where can I find replacement parts?
Contact your local Carrier distributor or visit the Carrier parts website using the model number.

User questions about Aquazone 50WT CARRIER

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Air conditioner in PDF format for free! Find your manual Aquazone 50WT - CARRIER and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. Aquazone 50WT by CARRIER.

USER MANUAL Aquazone 50WT CARRIER

Installation, Start-Up, and

Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS 2

GENERAL....3

PRE-INSTALLATION 3

• INSPECTION

- STORAGE

INSTALLATION 6

Step 1 — Check Jobsite ....6

• HORIZONTAL UNITS

• VERTICAL UNITS

• INSTALLATION GUIDELINES (ALL UNITS)

Step 2 — Check Unit ...... 6

• I N S P E C T U N I T

Step 3 — Locate Unit ..... 10

• PROTECTION

Step 4 — Mount the Unit ..... 10

- DUCT FLANGES

• HORIZONTAL UNITS

• VERTICAL UNITS

Step 5 — Check Duct System ..... 11

• HORIZONTAL SUPPLY AIR CONFIGURATION CONVERSION

Step 6 — Install Condensate Drain ..... 13

• HORIZONTAL UNITS

• VERTICAL UNITS

Step 7 — Pipe Connections ..... 13

• WATER QUALITY GUIDELINES

• INSTALLING SUPPLY AND RETURN HOSE KIT

• UNITS WITH BOILERLESS HEAT CONTROL

• UNITS WITH HOT WATER GENERATOR OPTION (HEAT RECOVERY PACKAGE/DESUPERHEATER)

• INITIAL START-UP

• UNITS WITH WATERSIDE ECONOMIZER

Step 8 — Wire Field Power Supply ..... 17

• HIGH VOLTAGE WIRING

• ELECTRIC HEATER

- LOW VOLTAGE, CONTROL WIRING

• ECM INTERFACE THERMOSTAT CONNECTIONS

• THERMOSTAT AND DDC SENSORS

• ADDITIONAL CONTROLS OPTIONS WIRING

Step 9 — Configure Unit Control Components ... 21

• UNIT PROTECTION MODULE (UPM)

UPM Standard Safeties and Alarms 22

• HI AND LOW REFRIGERANT PRESSURE PROTECTION

• WATER COIL FREEZE PROTECTION

• AIR COIL FREEZE PROTECTION

• HIGH CONDENSATE LEVEL SHUTDOWN

• INTELLIGENT ALARM RESET

• HARD LOCKOUT RESET

• OPTION CARD

PRE-START-UP 35

System Checkout 35

• CLEAN AIR COIL

• CONSTANT AIRFLOW (ECM) MOTOR

System Flushing and Filling .....38

System Flow....38

• FLOW VERIFICATION

• FLOW REGULATION

• ANTIFREEZE

- FREEZE PROTECTION SELECTION

• S T A R T - U P

Operating Limits 40

• ENVIRONMENT

• POWER SUPPLY

• UNIT STARTING CONDITIONS

Start-Up Procedure 41

• COOLING MODE START-UP

• HEATING MODE START-UP

OPERATION 45

Power Up Mode 45

Unit Protection Module (UPM) 45

Option Card 45

Sequence of Operation of Units Without DDC Controller 45

• STANDBY

• COOLING

• HOT GAS REHEAT WITH OPTION CARD (OPTIONAL)

- WATERSIDE ECONOMIZER WITH OPTION CARD (OPTIONAL)

• AUXILIARY ELECTRIC HEAT (OPTIONAL)

- TWO-POSITION MOTORIZED ISOLATION VALVE (2-WAY SOLENOID VALVE) (OPTIONAL)

- BOILERLESS HEAT WITH OPTION CARD (OPTIONAL)

- DIFFERENTIAL PRESSURE SWITCH / FLOW SWITCH (OPTIONAL)

- REFRIGERANT LEAK DETECTION SYSTEM (OPTIONAL)

• COMPRESSOR RELAY (OPTIONAL)

• PUMP/VALVE RELAY (OPTIONAL)

Sequence of Operation for Units with TruVu DDC Controller 47

• SCHEDULING

• INDOOR FAN

• COOLING OPERATION

• HEATING OPERATION

• WATERSIDE ECONOMIZER

Indoor Air Quality and Demand Control Ventilation . .50

• COMPRESSOR STATUS

• DEMAND LIMITING

  • REMOTE DISABLE
    • A L A R M S

SERVICE 53

Jobsite Check 53

• CHECKS TO THE AREA
• WORK PROCEDURE
- GENERAL WORK AREA
- CHECKING FOR PRESENCE OF REFRIGERANT
• PRESENCE OF FIRE EXTINGUISHER
• NO IGNITION SOURCES
• VENTILATED AREA

Electrical Devices 53

Repairs to Sealed Components 53

Repair to Intrinsically Safe Components ..... 53

Cabling 53

Filters 53

Condensate Drain Pans 54

Refrigerant System 54

• REFRIGERATING EQUIPMENT.
- DETECTION OF FLAMMABLE REFRIGERANTS

Compressor 54

Fan Motors 54

Condensate Drain Cleaning 54

Air Coil Cleaning 54

Condenser Cleaning 54

• GRAVITY FLOW METHOD
• FORCED CIRCULATION METHOD

Removal and Evacuation 55

Refrigerant Charging 55

• CHARGING PROCEDURES
- RECOVERY

Blower Assembly Service and Removal ..... 56

Vertical Configuration Units 56

Horizontal Configuration Units 58

Troubleshooting 59

• UNIT PROTECTION MODULE (UPM)
Thermostatic Expansion Valves 59
• TXV FAILURE

START-UP CHECKLIST CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when servicing or repairing this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the National Electrical Code (NEC) for special installation requirements.

Understand the signal words — DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage.

It is important to recognize safety information. These are the safety alert symbols. When you see these symbols on the unit and in instructions or manuals, be alert to the potential for personal injury.

CARRIER Aquazone 50WT - SAFETY CONSIDERATIONS - 1

Refrigerant Safety Group A2L

CARRIER Aquazone 50WT - SAFETY CONSIDERATIONS - 2

WARNING

WARNING: RISK OF FIRE

Flammable Refrigerant Used — To be repaired only by trained service personnel. DO NOT puncture refrigerant tubing.

WARNING

Do not use means to accelerate the defrosting process or to clean, unless recommended in these instructions.

WARNING

Do not pierce or burn refrigerant lines. Be aware that refrigerants may not contain an odor.

WARNING

WARNING: RISK OF FIRE

Flammable Refrigerant Used — Dispose of properly in accordance with federal or local regulations.

WARNING

The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater).

WARNING

Installation of auxiliary electric heaters in connecting ductwork must adhere to Carrier-approved models exclusively. Carrier bears no responsibility for the installation of any alternative auxiliary devices installed in the field.

CARRIER Aquazone 50WT - WARNING - 1

WARNING

Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Lockout/tagout all disconnect locations to alert others not to restore power until work is completed.

IMPORTANT: The installation of water source heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.

GENERAL

This Installation and Start-Up Instructions literature is for Aquazone™ water source heat pump systems. Water source heat pumps (WSHPs) are single-package horizontally and vertically mounted units with electronic controls designed for year-round cooling and heating.

See Fig. 1 for model number nomenclature details. See Table 1 for unit physical data.

IMPORTANT: Read the entire instruction manual before starting installation.

PRE-INSTALLATION

INSPECTION

Upon receipt of shipment, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the carton or crating of each unit, and inspect each unit for damage on both the interior and exterior. Ensure the shipping company makes proper notation of any shortages or damage on all copies of the freight bill.

Concealed damage not discovered during unloading must be reported to the shipping company within 5 days of receipt of shipment.

NOTE: It is the responsibility of the purchaser to file all necessary claims with the shipping company.

STORAGE

If the equipment is not needed for immediate installation upon its arrival at the job site, it should be left in its shipping carton and stored in a clean, dry area between 50 and 95°F. Units must only be stored or moved in the normal upright position as indicated by the UP arrows on each carton at all times. If unit stacking is required, stack units as follows: vertical units less than 6 tons, no more than two high; horizontal units less than 6 tons, no more than three high. Do not stack units larger than 6 tons.

CARRIER Aquazone 50WT - STORAGE - 1

other | Category | REFLECTIVE | REFLECTIVE | | :--- | :--- | :--- | | ORIENTATION | FILTER ACCESS | WATER CONNECTION | | Horizontal | Side Filter Access | Front Left | | Vertical | Side Filter Access | Front Right | | Nominal Capacity MBH (tons) (6-8) | 024 = 24 (2) | | | Nominal Capacity MBH (tons) (6-8) | 036 = 36 (3) | B | | Nominal Capacity MBH (tons) (6-8) | 048 = 48 (4) | C | | Nominal Capacity MBH (tons) (6-8) | 060 = 60 (5) | D | | Nominal Capacity MBH (tons) (6-8) | 070 = 70 (6) | F | | AIRFLOW CONFIGURATION (9) | | | | ORIENTATION | RETURN | DISCHARGE | | Horizontal | Right | Back | | Vertical | Right | Top | | Horizontal | Right | Left | | Vertical | Left | Back | | Vertical | Left | Right | | Vertical | Right | Top | | Horizontal | Bottom Filter Access | C | | Vertical | Bottom Filter Access | E | | Horizontal | Bottom Filter Access | F | Controls—Option/Transformer (10) B = UPM/75VA D = UPM + BE/75VAa E = UPM + TV DDC/100VA H = UPM + SR/75VA K = UPM + PR/75VA M = UPM + ER/75VA P = UPM + BE + PR/75VA* R = UPM + BE + SR/75VA* T = UPM + BE + SR + PR/75VA* V = UPM + SR + PR/75VA X = UPM + EMS + SR/75VA Z = UPM + EMS + PR/75VA LEGEND BE — Boilerless Electric Heat CA ECM — Constant Airflow ECM CB — Compressor Blanket CCF — Closed Cell Foam Insulation CO — Cooling Only DP — Differential Pressure Flow Switch ECM — Electronically Commutated Motor EMS — Energy Management Switch EQP — Extra Quiet Package HGBP — Hot Gas Bypass HGRH — Hot Gas Reheat HWG — Hot Water Generator LD — Leak Detection MHGRH — Modulating Hot Gas Reheat PR — Pump Relay REG — Auto Flow Regulator SCCR — Short Circuit Current Rating SR — Compressor Status Relay STD — Standard TV DDC — TruVu Direct Digital Controller ULL — Ultra Low Leak Cabinet UPM — Unit Protection Module VLV — 2-Way Solenoid Valve WSE — Water Side Economizer WSHP — Water Source Heat PumpDESIGN REVISION (16) A = Initial Release Miscellaneous Options (15) — = None A = Waterside Economizer (WSE)a B = A2L Leak Detection (LD) C = WSE + LDc Hydronic Options (14) OPTION | WATER COIL NoneAJ 2-Way Valve (VLV)BK Auto-Flow Reg. (REG)CL Flow Proving Switch (DP)DM VLV + REGEN VLV + DPFP VLV + REG + DPGQ REG + DPHR Sound and IAQ Options (13) A = None (Std Insulation) B = Closed Cell Foam Insulation (CCF) C = Extra Quiet Package (EQP) D = Ultra-Low-Leak Cabinet (ULL), CCF + 2 in. MERV 8b E = EQP, ULL, 2 in. MERV 8b F = 2 in. MERV 8 Filter, Std Insulation G = 2 in. MERV 8 Filter, CCF H = 2 in. MERV 13 Filter, Std Insulation J = 2 in. MERV 13 Filter, CCF K = 4 in. MERV 13 Filter, Std Insulation L = 4 in. MERV13 Filter, CCF M = ULL, CCF + 2 in. MERV 13b N = EQP, ULL, 2 in. MERV 13b P = ULL, CCF + 4 in. MERV 13b Q = EQP, ULL, 4 in. MERV 13b R = EQP, 2 in. MERV 8 S = EQP, 2 in. MERV 13 T = EQP, 4 in. MERV 13 U = Compressor Blanket (CB), Std Insulation V = Compressor Blanket (CB), CCF W = CB + 2 in. MERV 8, Std Insulation X = CB + 2 in. MERV 8, CCF Y = CB + 2 in. MERV 13, Std Insulation Z = CB + 2 in. MERV 13, CCF 1 = CB + 4 in. MERV 13, Std Insulation 2 = CB + 4 in. MERV 13, CCF 3 = ULL, CCF + CB + 2 in. MERV 8b 4 = ULL, CCF + CB + 2 in. MERV 13b 5 = ULL, CCF + CB + 4 in. MERV 13bElectrical Options (12) 3 = 208-230/1/60 G = 208-230/1/60, 65 kA SCCR 4 = 265/1/60 H = 208-230/3/60, 65 kA SCCR 5 = 208-230/3/60 J = 265/1/60, 65 kA SCCR 6 = 460/3/60 N = 208-230/1/60, 15 kW E-heat (dual-point power) B = 208-230/1/60 with Disc. C = 265/1/60 with Disc. D = 208-230/3/60 with Disc. E = 460/3/60 with Disc. Refrigerant Circuit Options (11) OPTION | NON-COATED AIR COIL | COATED AIR COIL NoneAB Hot Gas Reheat (HGRH)cCD Cooling Only (CO)EF Hot Gas Bypass (HGBP)GH HGRH + HGBPaNP Hot Water Generator (HWG)ST Modulating Hot Gas Reheat (MHGRH)12

Fig. 1 — 50WT Model Number Nomenclature

Table 1 — Physical Data — 50WT (024-070) Units

UNIT SIZE 024 036 048 060 070
Compressor Type (Qty 1) Scroll Scroll Scroll Scroll
Max Water Working Pressure (psig) ^a 400 400 400 400 400
ECM FAN MOTOR and BLOWER
Fan Motor TypeConstant AirflowConstant AirflowConstant AirflowConstant AirflowConstant Airflow
Fan Motor (hp)VT: 0.33HZ: 0.500.750.751.001.00
Blower Wheel Size (Dia. x W) (in.)10x811 x 911 x 9VT: 12 x 12HZ: 11 x 9VT: 12 x 12HZ: 11 x 9
WATER CONNECTION SIZE (INCLUDES ECONOMIZER OPTION)
FPT (in.)0.750.751.001.001.00
Coaxial Coil Volume (gal)0.280.460.461.091.09
VERTICAL CABINET
Refrigeration Charge (oz)33.545.056.589.089.0
Air Coil Dimensions (H x W) (in.)20 x 16.528 x 2136 x 2742 x 2742 x 27
Standard Filter - 1" Throwaway (L x H)19 x 2724 x 3018 x 3024 x 30 and 18 x 3024 x 30 and 18 x 30
Optional Filter - 2" MERV 8 or 13 (L x H)19 x 2724 x 3018 x 3024 x 30 and 18 x 3024 x 30 and 18 x 30
Optional Filter - 4" MERV 13 (L x H)19 x 2724 x 3018 x 3024 x 30 and 18 x 3024 x 30 and 18 x 30
Weight - Operating (lb)219 255 324 397 401
Weight - Shipping (lb)243 280 350 424 428
HORIZONTAL CABINET
Refrigeration Charge (oz)31.042.552.091.091.0
Air Coil Dimensions (H x W) (in.)15 x 2216 x 27.518 x 3120 x 5020 x 50
Standard Filter - 1" Throwaway (L x H)18 x 3020 x 3420 x 24 (Qty 2)20 x 25 (Qty 2)20 x 25 (Qty 2)
Optional Filter - 2" MERV 8 or 13 (L x H)18 x 3020 x 3420 x 24 (Qty 2)20 x 25 (Qty 2)20 x 25 (Qty 2)
Optional Filter - 4" MERV 13 (L x H)18 x 3020 x 3420 x 24 (Qty 2)20 x 25 (Qty 2)20 x 25 (Qty 2)
Weight - Operating (lb)213 263 319 366 414
Weight - Shipping (lb)237 288 345 393 441

NOTE(S):
a. 300 psig when unit is built with the factory installed 2-way solenoid valve option.
LEGEND
FPT — Female Pipe Thread

INSTALLATION

Step 1 — Check Jobsite

Installation, operation and maintenance instructions are provided with each unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check out the system before operation. Complete the inspections and instructions listed below to prepare a unit for installation. See Table 1 for unit physical data.

HORIZONTAL UNITS

Horizontal units are designed for indoor installation only. Be sure to allow adequate space around the unit for installation and servicing. See Fig. 2 for overall unit dimensions.

VERTICAL UNITS

Vertical units are designed for indoor installations only. Vertical units are typically installed in a floor-level closet or a small mechanical room, Be sure to allow adequate space around the unit for installation and servicing. See Fig. 3 for overall unit dimensions.

CAUTION

EQUIPMENT DAMAGE HAZARD

To avoid equipment damage, do not use these units as a source of heating or cooling during the construction process. The mechanical components and filters used in these units quickly become clogged with construction dirt and debris which may cause system damage.

INSTALLATION GUIDELINES (ALL UNITS)

  1. Be sure the location chosen for unit installation provides ambient temperatures maintained above freezing.
  2. Be sure the installation location is isolated from sleeping areas, private offices and other acoustically sensitive spaces.
  3. Be sure unit is mounted at a height sufficient to provide an adequate slope of the condensate lines. If an appropriate slope cannot be achieved, a field-supplied condensate pump may be required.
  4. On horizontal units, allow adequate room below the unit for condensate drain trap and do not locate the unit above supply piping.
  5. Provide sufficient space for duct connection. Do not allow the weight of the ductwork to rest on the unit.
  6. Provide adequate clearance for filter replacement and drain pan cleaning. Do not allow piping, conduit, etc. to block filter access. See Fig. 4.
  7. Provide sufficient access to allow maintenance and servicing of the blower and blower motor, compressor, refrigerant circuit, controls, and coils. See Fig. 4.
  8. For units with free return (non-ducted), provide adequate space for proper return airflow. For units installed in closets or mechanical rooms, provide sufficient return grill area for proper airflow.
  9. Provide ready access to water valves and fittings, and screwdriver access to unit side panels, discharge collar, and all electrical connections.
  10. Where access to side panels is limited, pre-removal of the control box side mounting screws may be necessary for future servicing.
  11. For units that are installed in enclosed spaces (such as furred in closets or behind finished ceilings), provide access panels

to allow for the installation, maintenance, service, and removal of the unit.

IMPORTANT: It is the installing contractor's responsibility to ensure that all equipment is installed with proper access for service, start-up, installation of accessories, configuration of control and other components, and equipment removal in accordance with Carrier's recommended service clearances and installation instructions. Please refer to the Carrier Commercial WSHP Warranty Statement (document number 04-570008-01) for details on warranty exclusions regarding equipment, access, removal and clearances.

Step 2 — Check Unit

Upon receipt of equipment at the jobsite, inspect the carton or crating of each unit, and inspect each unit for damage on both the interior and exterior. Note any damage and contact your local equipment sales office.

CAUTION

EQUIPMENT DAMAGE HAZARD

DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., at-tics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.

INSPECT UNIT

To prepare the unit for installation, complete the procedures listed below:

  1. Verify the correct unit has been received. Check the unit capacity (tonnage), voltage, orientation, and configuration.
  2. Compare the electrical data on the unit nameplate with to verify the jobsite power feed (voltage, amperage, MCA) and power protection (MOCP).
  3. Remove the unit packaging, keeping the unit attached to the shipping pallet. Do not destroy packaging. Save for re-installation on the unit if the unit will not be fully installed.
  4. Open a unit access panel. Verify the refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.
  5. Check the water piping and piping connections to make sure they are free from defects, kinks, dents, and appear to be water tight. Verify system operating water pressure.
  6. Inspect the blower assembly. Verify the blower has not come lose during shipping. Verify clearance between the blower wheel and the blower housing. Verify free blower rotation.
  7. Inspect all electrical connections. Be sure connections are clean and tight at the terminals.
  8. Check unit controls. If factory-installed TruVu controller is not provided, verify field provided thermostat is available. If TruVu DDC controller is provided, verify proper sensor has been provided and a commissioning interface will be available.
  9. Horizontal Units Only: Locate the hanging bracket kit located in the compressor compartment.
  10. Remove any shipping brackets from the unit.

CARRIER Aquazone 50WT - INSPECT UNIT - 1

MODELa.b.c.dHORIZONTAL DIMENSIONS (in.)e,f,g
ABCDEHJMNPRTUV
WidthDepthHeightDischarge HeightDischarge WidthWater InletbWater OutletR/A Duct WidthR/A Duct Flange HeightFilter Rack Heightkl,kCabinet Front to Filter RackCabinet End to Filter RackSide to Discharge (end)Top to Discharge (FLE & FRS)End to Discharge (straight)Top to Discharge (FRE & FLS)CONDENSER WATER CONNECTIONSRECOMMENDED REPLACEMENT NOMINAL FILTER SIZECONDENSATE DRAIN CONNECTION
2421.5047.0019.0011.2510.503.258.7529.2516.0018.0015.502.255.506.035.501.753/4" FPT18 x 303/4" FPT
3624.0054.0021.0012.5011.753.258.5033.2518.0020.0019.501.257.756.816.751.753/4" FPT20 x 343/4" FPT
4824.0065.0021.0012.5011.753.008.2543.5018.0020.5016.005.257.756.756.751.751" FPT20 x 24(2)3/4" FPT
6024.0075.2521.0012.5011.753.008.2549.5018.0020.2520.503.006.506.826.751.751" FPT20 x 25 (2)3/4" FPT
7024.0075.2521.0012.5011.753.008.2549.5018.0020.2520.253.006.506.826.751.751" FPT20 x 25 (2)3/4" FPT

NOTE(S):
a. Front of the unit is determined by the location of the control box panel.
b. When DDC controller is installed, control box panel extends 3.0 in. beyond the front of the unit.
c. When disconnect switch is installed, increase width by 2.0 in. beyond side of unit.
d. The local electric codes may require 36 in. or more clearance at the electrical control box.
e. Specifications subject to change without notice.
f. Overall unit dimensions do not include filter rack or duct flanges.
g. All dimensions within ± 0.125 in. Dimensions in inches.
h. Water In connection is by Return side of the unit via 3 way valve for units with selected Waterside economizer option.
i. The 1 in. filter rack extends 1.25 in. beyond the side of the unit (not including flange)
j. The 2 in. filter rack extends 3.0 in. beyond the side of the unit (not including flange). This filter rack is 4-sided with a filter access door on both ends (front/back) and
can accept either a 1 in. or 2 in. filter.
k. The 4 in. filter rack extends 4.75 in. beyond the side of the unit (not including flange). This filter rack is 4-sided with a filter access door on both ends (front/back) and can accept either a 2 in. or 4 in. filter.

Fig. 2 — 50WT 024-070 Horizontal Unit Dimensions

G E B F D

E Q D F B

A C Control Box Access Access Panels Refrigeration Access Water Out Condensate Drain H K J Water In

Left Hand Return Front Right Side Water Connections

M N P Electrical Connections

Return Air (Filter) View

Access Panels Refrigeration Access Water Out J K H Control Box Access Water In Condensate Drain A C

Right Hand Return Front Left Side Water Connections

MODELa,b,c,dVERTICAL UNIT DIMENSIONS (in.)e,f,g
ABCDEFGHJKMNPQCONDENSER WATER CONNECTIONSRECOMMENDED REPLACEMENT NOMINAL FILTER SIZECONDENSATE DRAIN CONNECTION
WidthDepthHeightDischarge DepthDischarge WidthCabinet Edge to DischargeCabinet Edge to Discharge (left hand return)Water InletWater OutletCondensate DrainR/A Duct WidthR/A Duct Flange HeightFilter Rack Heightb,JCabinet Edge to Discharge (right hand return)
2421.5026.0044.0011.2510.505.755.503.258.505.7518.2518.2527.255.503/4" FPT19 x 273/4" FPT
3624.0026.0044.0011.2510.505.006.753.258.505.7524.0024.0030.006.753/4" FPT24 x 303/4" FPT
4824.0033.0051.0013.5012.008.506.003.008.255.5030.0030.0037.256.003/4" FPT18 x 303/4" FPT
6025.0033.0058.0013.5014.759.006.003.008.255.5030.0030.0042.256.001" FPT24 x 30 and 18 x 303/4" FPT
7025.0033.0058.0013.5014.759.006.003.008.255.5030.0030.0042.756.001" FPT24 x 30 and 18 x 303/4" FPT

NOTE(S):
a. Front of the unit is determined by the location of the control box panel.
b. When DDC controller is installed, control box panel extends 3.0 in. beyond the front of the unit.
c. When disconnect switch is installed, increase width by 2.0 in. beyond side of unit.
d. The local electric codes may require 36 in. or more clearance at the electrical control box.
e. Specifications subject to change without notice.
f. Overall unit dimensions do not include filter rack or duct flanges.
g. All dimensions within ± 0.125 in. Dimensions in inches.
h. The 1 in. filter rack extends 1.25 in. beyond the side of the unit (not including flange).
i. The 2 in. filter rack extends 3.0 in. beyond the side of the unit (not including flange). This filter rack is 4-sided with a filter access door on both ends.
(front/back) and can accept either a 1 in. or 2 in. filter.
j. The 4 in. filter rack extends 4.75 in. beyond the side of the unit (not including flange). This filter rack is 4-sided with a filter access door on both ends (front/back) and can accept either a 2 in. or 4 in. filter.

Fig. 3 — 50WT 024-070 Vertical Unit Dimensions

Vertical Unit
Left Return, Top Discharge
CARRIER Aquazone 50WT - INSPECT UNIT - 7

natural_image Technical diagram of a mechanical assembly with internal components and mounting brackets (no visible text or labels)

Front View

Left Return, Top Discharge Blower Front Access 18 in. Minimum 24 in. Optimum Compressor and Electrical Front Access 24 in. Minimum 36 in. Optimum

Side View

Horizontal Unit
CARRIER Aquazone 50WT - INSPECT UNIT - 9

flowchart
graph TD
    A["Left Return, Back Discharge"] --> B["Top View"]
    C["Compressor and Electrical Front Access"] --> D["Top View"]
    E["Blower Access 18 in. Minimum 24 in. Optimum"] --> F["Top View"]
    G["Left Return, Right Discharge"] --> H["Top View"]
    style A fill:#f9f,stroke:#333
    style C fill:#f9f,stroke:#333
    style E fill:#f9f,stroke:#333
    style G fill:#f9f,stroke:#333

Fig. 4 — 50WT Service Clearance

Step 3 — Locate Unit

Locate the unit in an indoor area that allows easy removal of the filter and access panels, and has enough room for service personnel to perform maintenance or repair. Provide sufficient room to make fluid, electrical, and duct connection(s). If the unit is located in a confined space such as a closet, provisions must be made for return air to freely enter the space. See minimum service clearances in Fig. 6.

Horizontal units condensate drains are not internally trapped. Allow room below the unit base for horizontal models for an adequate condensate trap.

These units are not approved for outdoor installation; therefore, they must be installed inside the structure being conditioned. Do not locate units in areas that are subject to freezing. Units must be installed in conditioned space that is not subject to extremes of temperature or humidity to avoid cabinet sweating and/or equipment damage.

PROTECTION

IMPORTANT: Care must be taken to prevent the introduction of dust, pain, debris, or chemicals into the unit, which can cause damage to the unit, delay start-up, and may impact unit longevity.

Do not use units for temporary heating, air conditioning or ventilation during construction or remodeling, especially when plastering, sanding or painting or when replacing carpet or flooring. Dust and debris can clog the coil and blower. Chemical vapors can lead to formicary corrosion and damage the coil. Ensure adequate ventilation and debris collection during construction or remodeling.

Once the units are properly positioned on the jobsite, cover them with either a shipping carton, vinyl film, or an equivalent protective covering. Cap open ends of pipes stored on the jobsite. This precaution is especially important in areas where painting, plastering, or spraying of fireproof material, etc. is not yet complete. Foreign material that accumulates within the units can prevent proper start-up and require costly clean-up operations. Before installing any of the system components, be sure to examine each pipe, fitting, and valve, and remove any dirt or foreign material found in or on these components.

Step 4 — Mount the Unit

DUCT FLANGES

The unit heat pumps feature foldout return and supply air duct flanges. These fold-out flanges allow the heat pumps to more easily fit through doorways and other tight spaces, and also prevent damage in shipping and handling.

It is recommended that all fold-out flanges be folded out once the heat pump is installed to ensure that return and supply airflow is not obstructed. These flanges can be easily folded using standard or duckbill pliers. Once folded out these flanges can be used to support light ductwork loads. See Fig. 5.

CARRIER Aquazone 50WT - DUCT FLANGES - 1

natural_image Exterior view of a large industrial air duct or chamber with a diamond-patterned mesh structure (no visible text or symbols)

Fig. 5 — Foldout Flanges

HORIZONTAL UNITS

While horizontal units may be installed on any level surface strong enough to hold their weight, they are typically suspended above a ceiling by threaded rods. All horizontal units come with a Hanging Bracket Kit to facilitate suspended unit mounting. Hanging brackets are installed as shown in Fig. 6.

Unit Front Bracket Can Be Mounted in Front or Side Location Rear Brackets

Fig. 6 — Hanging Bracket Locations

The hanging bracket kit includes the following:

• (5) brackets
• (5) rubber vibration isolators
• (8) screws no. 10 x 1/2 in.
• (10) bolts 1/4 - 28 x 1/2 in. hex bolt (not used on this model)

The following additional materials are needed and must be field supplied:

  • threaded rod (3/8 in. maximum diameter)
    • h e x n u t s
  • washers (1-3/4 in. minimum O.D.)

Hanging Bracket Installation

  1. Remove and discard factory-provided screws from location where hanging brackets will be installed. (see Fig. 7).

CARRIER Aquazone 50WT - Hanging Bracket Installation - 1

natural_image Technical line drawing of a structural support system with bolt holes and vertical supports (no text or symbols)

Fig. 7 — Removing Factory Screws

  1. Mount 4 brackets to unit corner post using the bolts provided in the kit, as shown in Fig. 8. DO NOT re-use the screws removed from the unit during Step 1 to mount the hanging brackets on the unit.

CARRIER Aquazone 50WT - Hanging Bracket Installation - 2

natural_image Technical line drawing of a mechanical bracket with mounting holes and a central hole (no text or symbols)

Fig. 8 — Mounting Brackets

  1. Install rubber grommet on the bracket as shown in Fig. 9.

  2. Hang the unit and assemble the field-provided threaded rod, nuts, and washers on the brackets as shown in Fig. 9.

CARRIER Aquazone 50WT - Hanging Bracket Installation - 3

natural_image Technical line drawing of a mechanical assembly with a spring-loaded component and a nut, mounted on a base (no text or symbols)

Fig. 9 — Hanging the Unit

IMPORTANT: Units larger than six tons include an integral angle iron frame with mounting holes present.

Horizontal units installed above the ceiling must conform to all local codes. An auxiliary drain pan, if required by code, should be at least 4 in. larger than the bottom of the heat pump.

Plumbing connected to the heat pump must not come in direct contact with joists, trusses, walls, etc. Some applications require an attic floor installation of the horizontal unit. In this case the unit should be set in a full size secondary drain pan on top of a vibration absorbing mesh.

The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing mesh. In both cases, a 3/4 in. drain connected to this secondary pan should be run to an eave at a location that will be noticeable.

CAUTION

If the unit is located in a crawl space, the bottom of the unit must be at least 4-in. above grade to prevent flooding of the electrical parts due to heavy rains.

VERTICAL UNITS

Vertical units should be mounted level on a vibration absorbing pad slightly larger than the unit base in order to minimize vibration transmission from the unit to the building structure (see Fig. 10). It is generally not necessary to anchor the unit unless required by local code.

Vibration Mounting Pad

Fig. 10 — Mounting Vertical Units

All major service access for the vertical models is from the front side of the unit. When installing the unit in a confined space such as a closet, ensure the service panel screws are accessible, that the filter can be replaced without damage and that water and electrical connections are accessible. For models with a unit-mounted disconnect switch, make sure the switch can be easily seen and operated.

To reduce sound transmission, units should be installed using flexible electrical conduit and hose kits. Care should be taken to ensure that no part of the unit cabinet is touching part of the building structure. For ducted return applications, a flexible duct connection should be used. Mount the unit on a vibration absorption pad slightly larger than the entire base to minimize vibration transmission. It is not necessary to mount the unit on the floor.

Step 5 — Check Duct System

All units are provided with a return air duct flange and supply air duct connections. Refer to unit dimensional drawings (Fig. 2 and 3) for physical dimensions of the collar and flange.

A flexible connector is recommended for supply and return air duct connections on metal duct systems. All metal ducting should be insulated with a minimum of 1 in. duct insulation to avoid heat loss or gain and prevent condensate from forming during the cooling operation. Application of the unit to uninsulated ductwork is not recommended as the unit's performance will be adversely affected.

CAUTION

Do not connect discharge ducts directly to the blower outlet. The factory filter rack should be left in place on a free return system.

If the unit will be installed in a new installation with new ductwork, the installation should be designed using current ASHRAE (American Society of Heating, Refrigerating, and Air-Conditioning Engineers) procedures for duct sizing. If the unit will be connected to an existing duct system, a check should be made to assure that the duct system has the capacity to handle the air required for the unit application. If the duct system is too small, larger ductwork must be installed. Be certain to check for existing leaks and repair. The duct system and all diffusers should be sized to handle the designed airflow quietly. To maximize sound attenuation of the unit blower, the supply and return air plenums should be insulated. There should be no direct straight air path through the air grille into the heat pump. The return air inlet to the heat pump must have at least one 90-degree turned away from the space return air grille. If air noise or excessive airflow are a problem, the blower speed can be changed to a lower speed to reduce airflow.

HORIZONTAL SUPPLY AIR CONFIGURATION CONVERSION

The supply air location can be field converted from end blow (back discharge) to straight through or vice-versa.

NOTE: Blower configuration changes should be done prior to unit being installed in the final location.

To convert the supply air direction, follow the steps below (Fig. 11-13):

  1. If the unit is connected to power, shut Off the unit and disconnect switch or circuit breaker.

  2. Locate the motor access panel (A). Remove the three screws at top and the three screws at the bottom of the panel. Remove the access panel and place it aside.

  3. Be careful not to damage the refrigerant coils or any other internal unit components.

  4. Locate blower panel (B). Remove the three screws from top and the three screws from bottom of the panel. Leave the blower panel in place on the base pan.

  5. Locate access panel corner post (C). Remove the four screws from top and the four screws from the bottom. Remove the corner post and set it aside.

  6. Locate blower support bracket (D). Remove the one screw and set it aside.

  7. Move blower panel (B) with blower to desired location, rotating it 180°. (See Fig. 13.) The motor power and control harness can be unplugged to facilitate blower relocation.

  8. Reinstall access panel corner post (C) using the eight screws previously removed.

  9. Fasten blower panel (B) using the six screws previously removed.

  10. Reinstall and fasten blower support bracket (D) using the one screw previously removed.

  11. Reattach the motor power and control harness if disconnected earlier.

  12. Reinstall and fasten motor access panel (A) using the six screws previously removed.

CARRIER Aquazone 50WT - HORIZONTAL SUPPLY AIR CONFIGURATION CONVERSION - 1

natural_image 3D diagram of a rectangular industrial or mechanical housing with labeled components A, B, and C, showing internal structure and an arrow indicating direction (no text or symbols beyond labels)

Fig. 11 — End Blow (back discharge) Orientation

CARRIER Aquazone 50WT - HORIZONTAL SUPPLY AIR CONFIGURATION CONVERSION - 2

natural_image 3D diagram of a mechanical device with labeled components A, B, and C, showing internal structure and mounting holes (no text or symbols beyond labels)

Fig. 12 — Straight Through Orientation

CARRIER Aquazone 50WT - HORIZONTAL SUPPLY AIR CONFIGURATION CONVERSION - 3

natural_image 3D mechanical assembly diagram showing internal components labeled B and D (no text or symbols beyond labels)

Straight Through End Blow

CARRIER Aquazone 50WT - HORIZONTAL SUPPLY AIR CONFIGURATION CONVERSION - 5

natural_image 3D rendering of a mechanical device with labeled components D and B, showing internal components and mounting brackets (no text or symbols beyond labels)

Fig. 13 — Blower Configuration

Step 6 — Install Condensate Drain

All units include a condensate drain pan under the evaporator coil. Units with waterside economizer have an additional condensate drain pan under the economizer coil.

HORIZONTAL UNITS

A drain line must be connected to each drain pain and pitched away from the unit a minimum of 1/8 in. per foot to allow the condensate to flow away from the unit.

This connection must be in conformance with local plumbing codes. A trap must be installed in the condensate line to ensure free condensate flow. (Heat pumps are not internally trapped.) A vertical air vent is sometimes required to avoid air pockets. See Fig. 14.

Condensate Drain Connection Vent (optional) Slope Down Min. 1/8" Per Foot Trap Down 2" Min.

Fig. 14 — Condensate Drain (Horizontal Units)

The depth of the trap depends on the amount of positive or negative pressure on the drain pan. A second trap must not be included. The horizontal unit should be pitched approximately 1/4 in. towards the drain in both directions, to facilitate condensate removal. See Fig. 15.

VERTICAL UNITS

Vertical configuration units are internally trapped from the factory. A second trap must NOT be included.

Step 7 — Pipe Connections

All WSHP units use female pipe thread fittings for water connections. Refer to Fig. 2 and 3 for connection sizes. When making piping connections, consider the following:

  • Use a backup wrench when making screw connections to unit to prevent internal damage to piping.
  • Insulation may be required on piping to avoid condensation in the case where fluid in loop piping operates at temperatures below dew point of adjacent air.
  • Flexible hoses should be used between the unit and the rigid system to avoid possible vibration.
  • Supply and return piping must be as large as the unit connections on the heat pump. Never use flexible hoses of a smaller inside diameter than that of the water connections on the unit.
  • Piping systems that contain steel pipes or fittings may be subject to galvanic corrosion. Dielectric fittings may be used to isolate the steel parts of the system to avoid galvanic corrosion.

  • Teflon tape thread sealant is recommended when connecting water piping connections to the units to ensure against leaks and possible heat exchanger fouling.

  • Balancing valve and supply/return manual isolation valves must be provided for unit isolation and water flow balancing.
  • Ensure unit receives the appropriate water flow during operation. To verify the correct water flow, utilize pressure/temperature ports positioned at the supply and return water lines. Refer to Fig. 35 and 36 for water pressure drop across water to refrigerant heat exchanger.
  • Avoid all plastic to metal threaded fittings due to the potential to leak. Use a flange fitted substitute.
  • Route piping to avoid service access areas to unit.
  • Flush the piping system prior to operation to remove dirt and foreign materials from the system.

Elevation Line When Mounted Level 1/4" [13] NOTE: Dimensions in [ ] are millimeters.

Fig. 15 — Pitched Unit

WATER QUALITY GUIDELINES

Units are supplied with either a copper or optional cupronickel coaxial water coil. Copper is adequate for ground water that is not high in mineral content.

Carrier recommends proper testing to assure the well water quality is suitable for use with water source equipment. In conditions anticipating moderate scale formation or in brackish water a cupronickel heat exchanger is recommended. Additional considerations are described below.

A secondary heat exchanger (plate frame between the unit and the open cooling tower or open loop ground water system) may also be used. It is imperative that all air is eliminated from the closed loop side of the heat exchanger to prevent condenser fouling.

In all applications, the quality of the water circulated through the heat exchanger must fall within the ranges listed in Table 2, Water Quality Guidelines. Consult a local water treatment firm, independent testing facility, or local water authority for specific recommendations to maintain water quality within the published limits

CAUTION

Water piping exposed to extreme, low ambient temperatures is subject to freezing.

Table 2 — Water Quality Guidelines

CONDITION HX MATERIALaCLOSED RECIRCULATINGbOPEN LOOP AND RECIRCULATING WELLc
Scaling Potential — Primary MeasurementAbove the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.
pH/Calcium Hardness MethodAll N/A pH< 7.5 and Ca Hardness, <100 ppm
Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.)
Scaling indexes should be calculated at 150°F for direct use and at 90°F for indirect HX use. A monitoring plan should be implemented.
Ryznar Stability Index AllN/A 6.0 to 7.5If >7.5 minimize steel pipe use.
Langelier Saturation IndexAll N/A -0.5 to +0.5If <=0.5 minimize steel pipe use.Based upon 150°F direct well, 85°F indirect well HX.
Iron Fouling
Iron Fe (Ferrous)(Bacterial Iron Potential)All N/A <0.2 ppm (Ferrous)If Fe^2+ (ferrous) >0.2 ppm with pH 6 to 8, O_2 <5 ppm, check for iron bacteria.
Iron FoulingAll N/A <0.5 ppm of OxygenAbove this level deposition will occur.
Corrosion Preventiond
pH All 6-8.5Monitor/treat as needed.6 to 8.5Minimize steel pipe below 7 and no open tanks with pH <8.
Hydrogen Sulfide ( H_2S )All N/A <0.5 ppmAt H_2S >0.2 ppm, avoid use of copper and cupronickel piping or HXs.Rotten egg smell appears at 0.5 ppm level.Copper alloy (bronze or brass) cast components are acceptable to <0.5 ppm.
Ammonia Ion as Hydroxide, Chloride, Nitrate and Sulfate CompoundsAll N/A <0.5 ppm
Maximum Chloride LevelsMaximum allowable at maximum water temperature.
50°F (10°C)75°F (24°C)100°F (38°C)
CopperN/A<20 ppmNRNR
CupronickelN/A <150 ppmNRNR
304 SSN/A<400 ppm<250 ppm<150 ppm
316 SSN/A<1000 ppm<550 ppm<375 ppm
TitaniumN/A>1000 ppm>550 ppm>375 ppm
Erosion and Clogging
Particulate Size and ErosionAll<10 ppm of particles and a maximum velocity of 6 fps. Filtered for maximum 800 micron size.<10 ppm (<1 ppm “s and free” for reinjection) of particles and a maximum velocity of 6 fps. Filtered for maximum 800 micron size. Any particulate that is not removed can potentially clog components.
BrackishAllN/AUse cupronickel heat exchanger when concentrations of calcium or sodium chloride are greater than 125 ppm are present. (Seawater is approximately 25,000 ppm.)

NOTE(S):
a. Heat exchanger materials considered are copper, cupronickel, 304 SS (stainless steel), 316 SS, titanium.
b. Closed recirculating system is identified by a closed pressurized piping system.
c. Recirculating open wells should observe the open recirculating design considerations.
d. If the concentration of these corrosives exceeds the maximum allowable level, then the potential for serious corrosion problems exists.
Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation occur as the sample is taken. Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate solution, allowing accurate sulfide determination up to 24 hours after sampling. A low pH and high alkalinity cause system problems, even when both values are within ranges shown. The term pH refers to the acidity, basicity, or neutrality of the water supply. Below 7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic. Neutral water registers a pH of 7.0.
To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.
LEGEND
HX — Heat Exchanger
N/A — Design Limits Not Applicable Considering Recirculating Potable Water
NR — Application Not Recommended
SS — Stainless Steel

INSTALLING SUPPLY AND RETURN HOSE KIT

Follow these piping guidelines:

  1. Install a drain valve at the base of each supply and return riser to facilitate system flushing.
  2. Install shutoff/balancing valves and unions at each unit to permit unit removal for servicing.
  3. Place strainers at the inlet of each system circulating pump.
  4. Select the proper hose length to allow slack between connection points. Hoses may vary in length by +2% to -4% under pressure.
  5. Do not exceed the minimum bend radius for the hose selected. Refer to Table 3. Exceeding the minimum bend radius may cause the hose to collapse, which reduces water flow rate. Install an angle adapter to avoid sharp bends in the hose when the radius falls below the required minimum.

NOTE: Piping must comply with all applicable codes.

Table 3 — Metal Hose Minimum Bend Radii

HOSE DIAMETER (in.)MINIMUM BEND RADII (in.)
1/23-9/16
3/43-9/16
14-3/8

Insulation is not required on loop water piping except where the piping runs through unheated areas or outside the building or when the loop water temperature is below the minimum expected dew point of the pipe ambient. Insulation is required if loop water temperature drops below the dew point.

IMPORTANT: Do not bend or kink supply lines or hoses.

Pipe joint compound is not necessary when Teflon threaded tape is pre-applied to hose assemblies or when flared-end connections are used. If pipe joint compound is preferred, use compound only in small amounts on the male pipe threads of the fitting adapters. Prevent sealant from reaching the flared surfaces of the joint.

NOTE: When anti-freeze is used in the loop, assure that it is compatible with Teflon tape or pipe joint compound employed.

Maximum allowable torque for brass fittings is 30 ft-lb. If a torque wrench is not available, tighten finger-tight plus one quarter turn. Tighten steel fittings as necessary.

Optional pressure-rated hose assemblies designed specifically for use with Carrier units are available. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fitted with swivel-joint fittings at one end to prevent kinking during installation.

CAUTION

Backup wrench is required when tightening water connections to prevent water line damage. Failure to use a backup wrench could result in equipment damage.

Male adapters secure hose assemblies to the unit and risers. Install hose assemblies properly and check them regularly to avoid system failure and reduced service life. See Fig. 16.

Rib Crimped Length (2 ft length standard) Swivel Brass Fitting Brass Fitting MPT

Fig. 16 — Supply/Return Hose Kit

UNITS WITH BOILERLESS HEAT CONTROL

Units with Boilerless Heat Control include entering water temperature sensor that is factory installed on the incoming water piping.

Refer to see Step 9 — “Configure Unit Control Components” on page 21 for boilerless control configuration for units with Option Card (units without factory installed TruVu™ controller).

Refer to the TruVu ^TM controller section of this manual for configuring the entering water temperature set point for boilerless control operation for units with TruVu ^TM controller.

UNITS WITH HOT WATER GENERATOR OPTION (HEAT RECOVERY PACKAGE/DESUPERHEATER)

The hot water generator (HWG) is a factory-installed option capable of providing hot water in the range of 110 to 120°F as a supplemental domestic hot water source. The HWG is a desuperheater that uses recovered heat from the hot discharge gas leaving the compressor. Included with the HWG is a vented, double wall coil, circulating pump, high water temperature limit switch (set at 120°F), discharge gas temperature limit switch, and an ON/OFF switch with built-in circuit breaker. The generator operates independently and is not factory wired to the unit controller.

NOTE: The HWG will reduce the amount of heat available to the space and it is recommended to deactivate the HWG in heating mode via the ON/OFF switch.

Water Tank Preparation

  1. Turn off electrical or fuel supply to the water heater.
  2. Attach garden hose to water tank drain connection and run other end of hose outdoors or to an open drain.
  3. Close cold water inlet valve to water heater tank.
  4. Drain tank by opening drain valve on the bottom of the tank, then open pressure relief valve or hot water faucet.
  5. Once drained the tank should be flushed with cold water until the water leaving the drain hose is clear and free of sediment.
  6. Close all valves and remove the drain hose.
  7. Install HWG water piping. All hot water piping should be a minimum of 3/8 in. OD copper tube to a maximum distance of fifteen feet. For distances beyond fifteen feet but not exceeding sixty feet use 1/2 in. copper tube. Separately insulate all exposed surface of both connecting water lines with 3/8 in. wall closed cell insulation. Install isolation valves on supply and return to the hot water generator. See Fig. 17.
    NOTE: Diagram is for illustration purposes only. Ensure access to heat pump is not restricted. All plumbing and piping connections must comply with local plumbing codes.

CARRIER Aquazone 50WT - Water Tank Preparation - 1

flowchart
graph TD
    A["WSHP"] --> B["Isolation Valves"]
    B --> C["Drain Valve"]
    C --> D["Storage DHW Heater"]
    D --> E["Cold Water In"]
    D --> F["Hot Water Out"]

Fig. 17 — Typical Hot Water Generator Installation

Water Tank Refill

  1. Open the cold water supply to the tank.
  2. Open a hot water faucet to vent air from the system until water flows from the faucet, then close.
  3. Depress the hot water tank pressure relief valve handle to ensure there is no air remaining in the tank.
  4. Carefully inspect all plumbing for water leaks. Correct as required.
  5. Purge all air from HWG by depressing the Schrader valve on the HR unit. Allow all air to bleed out until water appears at the valve.
  6. Before restoring the power or fuel supply to the water heater, adjust the temperature setting on the tank thermostat(s) to ensure maximum utilization of heat available from the refrigeration system and to conserve the most energy. On tanks with thermostats and both upper and lower elements, the lower element should be turned down to 100°F, while the upper element should be adjusted to 120°F. Depending upon the specific needs of the customer, you may need to adjust the upper element differently. On tanks with a single thermostat, lower the thermostat setting to 120°F or the "LOW" position. After thermostat adjustments are completed, replace access cover and restore electrical or fuel supply to water heater.

INITIAL START-UP

  1. Turn on the heat pump. The circulating pump should not run if the compressor is not running.
  2. Turn HWG switch to the "ON" position. The pump will operate if entering water temperature to HWG is below 120°F.

  3. Ensure the temperature difference between the water entering and leaving the heat recovery is 5 to 15°F.

  4. Allow the unit to operate for 20 to 30 minutes to ensure it is functioning properly. The pump should shut off when the water temperature entering the generator reaches 120^ F.

UNITS WITH WATERSIDE ECONOMIZER

The optional waterside economizer (pre-cooling coil) is factory installed and piped internally, in series with the condenser water circuit (see Fig. 18). A diverting 3-way motorized valve, entering water temperature sensor, drain pan with condensate overflow switch, and factory controls are included with the option.

The remote bulb (EWT sensor) is shipped internal to the unit and requires to be installed on straight incoming water line to the unit/3-way diverting valve (see Fig. 18). Care should be taken not to dent the bulb or mis-calibration may occur. The remote sensing bulb must be installed on a straight section of uninsulated pipe that provides a good measurement of the entering water temperature. It is recommended to insulate the sensing bulb after installation for better water temperature sensing.

When unit is shipped with economizer option, the economizer drain must be connected to a separate trap. Follow the same steps for the economizer drain as described for evaporator condensate drain Step 6 — “Install Condensate Drain” on page 13.

Refer to Step 9 — “Configure Unit Control Components” on page 21 for Economizer configuration for units with Option Card (units without factory installed TruVu™ controller).

Refer to the TruVu controller section of this manual for configuring the entering water temperature set point for economizer operation for units with TruVu DDC controller.

See Table 1 for connection sizes. Refer to the unit's performance report for economizer performance and additional water and air pressure drop.

CARRIER Aquazone 50WT - UNITS WITH WATERSIDE ECONOMIZER - 1

flowchart
graph LR
    A["EWT Sensor (field-installed)"] --> B["Fluid IN"]
    B --> C["N.O."]
    C --> D["N.C."]
    D --> E["WSE Coil"]
    E --> F["Condenser Coil"]
    F --> G["Isolation Valve (optional)"]
    G --> H["Fluid OUT"]

Fig. 18 — Waterside Economizer Diagram

Step 8 — Wire Field Power Supply

See Fig. 26-34 for typical wiring diagrams. See Tables 4-9 for additional electrical data. Please refer to the unit wiring diagram attached to the control panel for field installation.

WARNING

To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.

CAUTION

All power connections must be properly torqued to avoid the risk of overheating.

HIGH VOLTAGE WIRING

All field-installed wiring must comply with the National Electric Code as well as all applicable local codes. Refer to the unit electrical data on the unit nameplate for wire and branch circuit protection sizing. Supply power voltage and phasing should match the required voltage and phasing shown on the unit nameplate. Operating the unit below the minimum voltage, above the maximum voltage or with incorrect phasing can result in poor system performance or damage to the heat pump. All field wiring should be installed by qualified and trained personnel. Refer to the unit wiring diagram for field connection requirements.

Power wiring to the heat pump should be enclosed in flexible conduit to minimize the transmission of vibration from the unit cabinet to the building.

For heat pumps with unit mounted disconnect switches, field power should be connected to the marked terminals on the disconnect switch. For heat pumps without unit-mounted disconnect switches (except units with dual power supply), power is connected to the line (L) side of the compressor contactor and the ground lug in the unit electrical box.

For units with the 65 kA SCCR option, the power supply must be connected to the fuse block located in a dedicated fuse box.

460-v heat pumps with constant airflow motors require five power supply wires: the standard three high-voltage wires, the ground wire, and a neutral wire. These units employ a 265-v motor that requires power from one phase of the 460-v supply and the neutral wire.

CAUTION

The power supply ground wire should never be used as a neutral wire.

Transformer Settings for 208/230-v Units

As factory built, all 208/230-v units are wired for 230-v operation. For jobsites with a 208-v power supply, the primary leads on the unit transformer will need to be changed from 230-v to 208-v. Refer to the unit wiring diagram for details.

ELECTRIC HEATER

Factory-installed internal electric heater is available for selection with units. Two power supplies are required when electric heater is provided with the unit. The power supply for the electric heater (located in the electric heater package control box) provides power for the heater elements, the blower motor, and the control circuit for the unit. The power supply for the unit provides power for the compressor. This allows the electric heaters to continue to operate along with the blower motor in the case of unit compressor and/or compressor power supply failure. See data plates for minimum circuit capacities and maximum fuse/breaker sizing. See Tables 4-9 for additional electrical data.

Table 4 — 50WT without Electric Heat — Constant Airflow ECM Blower Motor Electrical Data

50WT UNIT SIZEVOLTAGE/HZ/PHASEVOLTAGE MIN/MAXCOMPRESSOR BLOWER MOTORTOTAL UNIT FLAMCA MOP
Quantity RLA LRA FLA Hp
024208-230/1/60 197/253 1 10.362.04.4 0.33 14.7 17.225.0
265/1/60 238/292 1 7.8 5204.7 0.3312.514.5 20.0
208-230/3/60 197/253 1 6.356.04.4 0.3310.712.3 15.0
460/3/60 414/506 1 3.8 2904.7 0.338.59.715.0
036208-230/1/60 197/253 1 14.690.08.4 0.7523.026.640.0
265/1/60 238/292 1 12.6 799.07.5 0.7520.123.2 35.0
208-230/3/60 197/253 1 9.932.08.4 0.7518.320.7 30.0
460/3/60 414/506 1 4.8 4437.5 0.7512.314.2 20.0
048208-230/1/60 197/253 1 18.3138.08.40.7526.731.3 45.0
208-230/3/60 197/253 1 11.9112.08.40.7520.323.3 35.0
460/3/60 414/506 1 6.8 6187.5 0.7514.316.220.0
060208-230/1/60 197/253 1 25.2147.39.11.0034.340.660.0
208-230/3/60 197/253 1 13.8161.09.11.0022.926.340.0
460/3/60 414/506 1 6.9 5809.11.0016.018.225.0
070208-230/1/60 197/253 1 28.0166.09.11.0037.144.170.0
208-230/3/60 197/253 1 18.9162.39.11.0028.032.750.0
460/3/60 414/506 1 9.1 7089.11.0018.220.525.0

LEGEND

Hp — Horsepower

FLA — Full Load Amps

LRA — Locked Rotor Amp

RLA — Rated Load Amps

MCA — Minimum Circuit Amp

MOCP — Maximum Overcurrent Protection

Table 5 — First Data Plate for Units with Electric Heater (EH) Option — Compressor Power Connection

50WT UNIT SIZEVOLTAGE/HZ/ PHASEVOLTAGE MIN/MAXCOMPRESSORFLA MCAMOP
Quantity RLA LRA
024 208-2301/60 197/253 1 10.3 62.0 10.3 12.8 20.0
036 208-2301/60 197/253 1 14.6 90.0 14.6 18.2 30.0
048 208-2301/60 197/253 1 18.3 138.0 18.3 22.940.0
060 208-2301/60 197/253 1 25.2 147.3 25.2 31.550.0
070 208-2301/60 197/253 1 28.0 166.0 28.0 35.060.0

Table 6 — Second Data Plate for Units 5 kW Electric Heater (EH) Option and Constant Airflow ECM Motor

50WT UNIT SIZEVOLTAGE/ HZ/ PHASEVOLTAGE MIN/MAXBLOWER MOTOR5 kW ELECTRIC HEATER
Heater Element Unit Data Plate Values
FLA HpWattsAmpsMCAMOP
208-v240-v208-v240-v208-v240-v208-v240-v
024208-230/1/60197/2534.40.333.6 K4.8 K17.32027.230.52530
036208-230/1/60197/2538.40.753.6 K4.8 K17.32032.235.53035
048208-230/1/60197/2538.40.753.6 K4.8 K17.32032.235.53035
060208-230/1/60197/2539.11.003.6 K4.8 K17.32033.036.43035
070208-230/1/60197/2539.11.003.6 K4.8 K17.32033.036.43035

Table 7 — Second Data Plate for Units 10 kW Electric Heater (EH) Option and Constant Airflow ECM Motor

50WT UNIT SIZEVOLTAGE/ HZ/ PHASEVOLTAGE MIN/MAXBLOWER MOTOR10 kW ELECTRIC HEATER
Heater ElementUnit Data Plate Values
FLA HpWattsAmpsMCAMOP
208-v240-v208-v240-v208-v240-v208-v240-v
024208-230/1/60197/2534.40.337.2 K9.6 K34.74048.855.54550
036208-230/1/60197/2538.40.757.2 K9.6 K34.74053.860.55060
048208-230/1/60197/2538.40.757.2 K9.6 K34.74053.860.55060
060208-230/1/60197/2539.11.007.2 K9.6 K34.74054.761.45060
070208-230/1/60197/2539.11.007.2 K9.6 K34.74054.761.45060

Table 8 — Second Data Plate for Units 15 kW Electric Heater (EH) Option and Constant Airflow ECM Motor

50WT UNIT SIZEVOLTAGE/ HZ/ PHASEVOLTAGE MIN/MAXBLOWER MOTOR15 kW ELECTRIC HEATER
Heater ElementUnit Data Plate Values
FLAHpWattsAmpsMCAMOP
208-v240-v208-v240-v208-v240-v208-v240-v
036208-230/1/60197/2538.40.7510.8 K14.4 K52.06075.585.57080
048208-230/1/60197/2538.40.7510.8 K14.4 K52.06075.585.57080
060208-230/1/60197/2539.11.0010.8 K14.4 K52.06076.486.47080
070208-230/1/60197/2539.11.0010.8 K14.4 K52.06076.486.47080

Table 9 — Second Data Plate for Units 20 kW Electric Heater (EH) Option and Constant Airflow ECM Motor

50WT UNIT SIZEVOLTAGE/ HZ/ PHASEVOLTAGE MIN/MAXBLOWER MOTOR20 kW ELECTRIC HEATER
Heater ElementUnit Data Plate Values
FLA HpWattsAmpsMCAMOP
208-v240-v208-v240-v208-v240-v208-v240-v
048208-230/1/60197/2538.40.7514.4 K19.2 K69.38097.2110.590110
060208-230/1/60197/2539.11.0014.4 K19.2 K69.38098.0111.490110
070208-230/1/60197/2539.11.0014.4 K19.2 K69.38098.0111.490110

LOW VOLTAGE, CONTROL WIRING

WARNING

To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.

CAUTION

Never route control wiring through the same conduit as power supply wiring. Electrical noise and transients from the power wiring can cause communication issues or damage to the control wiring and connected control components.

Units without factory installed TruVu DDC controller can be controlled using the included thermostat inputs (R, O, Y1, C, G) for single stage heat pump thermostat or field-installed DDC (Direct Digital Controls) controls. Note that the reversing valve on the unit is energized when the unit is in the cooling mode. See Fig. 19 for typical thermostat connections.

COYRG

Fig. 19 — Typical Thermostat Connections

Control wiring for units with constant airflow ECM blower motors is routed through a constant airflow ECM interface board. Thermostat input wiring is connected to the 10-pin screw type terminal block on the lower center portion of the ECM Interface Board. In addition to providing a connecting point for thermostat wiring, the interface board also translates thermostat inputs into control commands for the Electronic Commutated Motor (ECM) DC fan motor and displays an LED indication of operating status. Refer to the unit wiring diagrams for complete details. See Fig. 20. The thermostat connections and their functions are as follows.

ECM INTERFACE THERMOSTAT CONNECTIONS

• Y1 First Stage Compressor Operation
• Y2 Second Stage Compressor Operation
• G Fan

  • O Reversing Valve (energized in cooling)
    • W1 Auxiliary Electric Heat (runs with compressor)
    • EM/W2 Emergency Heat (electric heat only)
    • NC Transformer 24 vac Common (extra connection)
    • C1 Transformer 24 vac Common (primary connection)
    • R Transformer 24 vac Hot
    • H Dehumidification Mode

10 R C1 R C2 EM W1 O Y2 Y1 G H C W2 W1 O Y2 Y1 G H 6 9 8 7 5 2 4 3 J01 CFM H A B C D NORM [+] TEST CFM ADJUST YES NO HGRH R C G O Y1 Y2 W1 W2 H C 11

LEGEND

1 Motor harness plug

2 Blower CFM Adjustment

3 Motor Settings

4 Dehumidification Indication

5 Thermostat Digital Contact Inputs

6 Cfm Count Indicator

7 Thermostat Input Status Indication

8 Reheat digital outputs

9 Thermostat Outputs

10 24 Vac

11 Dehumidification Method Selector

Fig. 20 — ECM Interface Board Physical Layout

THERMOSTAT AND DDC SENSORS

Thermostats or DDC space sensors should be located on an interior wall away from supply ducts. Avoid locations subject to direct sunlight or drafts, or external walls. Thermostat wiring should be 18 AWG (American Wire Gauge). Refer to the installation instructions for the thermostat for further details.

IMPORTANT: Exceptionally long runs of thermostat wire should be avoided to prevent voltage drops in the control circuit.

ADDITIONAL CONTROLS OPTIONS WIRING

Hot Gas Reheat Control

Units with hot gas reheat (HGRH) will include an additional H terminal on the input terminal board for dehumidification control. To enable a call for dehumidification, a 24-v signal must be sent to the H terminal with no voltage applied to the Y1 or O terminals. Any call for cooling (Y1 and O) will override the dehumidification call.

Pump Relay

Units with selected Pump Relay option can be field wired to enable a field provided loop pump or solenoid valve when there is a call for compressor operation. Represented as AUX relay on Wiring Diagrams (see Fig. 26-34).

Energy Management Switch

Units with selected energy management switch (EMS) can be field wired to disable unit operation when a 24-v signal is removed from the relay. Removing the 24-v signal causes the relay to open, which cuts 24-v power to the unit control circuit. All unit components will be disabled at when the EMS is deactivated. Represented as EMS relay on Wiring Diagrams (see Fig. 26-34).

Alarm Output (All Units)

If the unit is being connected to a thermostat or DDC control with an alarm indicator, this connection is made at the unit malfunction output on the Unit Protection Module (UPM). See the Unit Protection Module heading in Step 9 — “Configure Unit Control Components” on page 21 section for further details.

TruVu DDC Controller

TruVu is a factory installed DDC control that requires the use of Carrier ZS or non-communicating sensors or the Carrier TruVu Equipment touch interface for space temperature sensing. TruVu DDC is not compatible with thermostats.

All units equipped with TruVu DDC controller include factory-installed EWT, LWT, SAT, and RAT sensors. Additional field-installed sensors should be provided and wired as needed. Please refer to the Operation section of the Installation, Operation, and Maintenance (IOM) manual for available inputs for optional field-installed components.

IMPORTANT: Relocate the factory installed supply air temperature sensor (SAT) when using a field-installed electric heater. The Supply Air Temperature (SAT) sensor should be downstream of any external heating device for effective control.

All TruVu wiring is completed at the TruVu control board. See Fig. 34 for details.

Control Transformer

All units without factory installed TruVu DDC include 75VA transformer. All units with TruVu™ DDC controller include a 100VA transformer.

CAUTION

Exceeding the transformer capacity can result in low control voltage, erratic unit operation or damage to the heat pump.

The VA capacity of the transformer should be considered when applying low voltage accessories, such as shut off valves, thermostats, or DDC controls. Table 10 shows the VA draw of factory-mounted components in the low voltage heat pump.

The total VA draw of the heat pump internal components plus any attached accessories must be lower than the VA capacity of the unit control transformer.

Table 10 — Low Voltage VA Draw

STANDARD CONSTRUCTION
Component VA
Reversing Valve Solenoid 12
Compressor Contactor Single Phase10
UPM Board5
Total VA Draw27
OPTION CARD
Component VA
Total from ‘Standard’27
Option Card5
Hot Gas Reheat Solenoid9
Economizer Valve3
Total VA Draw44
OPTIONAL COMPONENTS
Component VA
Compressor Monitor Relay4
Blower Monitor Relay4
Energy Management Relay4
Fire Alarm Relay4
Heater Contactor10
AUX Relay10
Electric Heating/Blower Relay4
683 TruVuTM DDC37
CA ECM Board1
Leaving Water Valve7
Compressor Contactor 3 Phase10

Step 9 — Configure Unit Control Components

WARNING

To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.

UNIT PROTECTION MODULE (UPM)

The Unit Protection Module (UPM) as shown in Fig. 21 is a printed circuit board (PCB) included in all units, that interfaces with the thermostat or the digital direct controller.

The main purpose of this device is to protect the compressors by monitoring the different states of switches and sensors of each refrigerant circuit. This device provides time delays and protects the unit against freezing of the water and refrigerant heat exchangers as well as condensate overflow when the appropriate sensors are installed.

ICM LPR-BG1707 P/Na 8733827069 OUT ALR/COM G_OUT F1 JN1 R C 14 13 12 11 10 1 2 3 4 5 6 7 8 9 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 LPC HPC Y CC HPC SPCB-2 R61 R62 R63 R64 R65 R66 R67 R68 R69 R70 R71 R72 R73 R74 R75 R76 R77 R78 R79 R80 R81 R82 R83 R84 R85 R86 R87 R88 R89 R90 R91 R92 R93 R94 R95 R96 R97 R98 R99 R100 PSCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SPCB-2 SFC

LEGEND

1 — Compressor Contact Output
2 — High-Pressure Switch Connection
3 — Call for Compressor (Y1)
4 — Low Pressure Switch Connection
5 — Water Coil Freeze Connection (Freeze 1)
6 — UPM Status LED Indicator (Fault Status)
7 — Air Coil Freeze Connection (Freeze 2)
8 — Condensate Overflow Sensor Connection
9 — Ground
10 — UPM Settings DIP Switch (SW1)
11 — A2L Sensor
12 — 24 vac Power Common
13 — 24 vac Power Input
14 — UPM Standoff
15 — Power LED
16 — Fan
17 — Dry Contact

Fig. 21 — Unit Protection Module (UPM)

UPM Standard Safeties and Alarms

HI AND LOW REFRIGERANT PRESSURE PROTECTION

  • High-pressure switch located in the refrigerant discharge line and wired across the HPC (High-Pressure Switch Connection) terminals on the UPM.
  • Low-pressure switch located in the unit refrigerant suction line and wired across the LPC (Low-Pressure Switch Connection) terminals (LPC1 and LPC2) on the UPM.

WATER COIL FREEZE PROTECTION

Waterside freeze protection sensor, mounted close to condensing water coil, monitors refrigerant temperature between condensing water coil and thermal expansion valve (see Fig. 22.)

If temperature drops below or remains at freeze limit trip for 120 seconds, the controller will shut down the compressor and enter into a soft-lockout condition. The default freeze limit trip is 25^ F; however, this can be changed to 15^ F by flipping DIP switch SW1 (see Fig. 21, Item 10, Fig. 24, and Table 11).

NOTE: The UPM Board Dry Contacts are Normally Open (NO).

IMPORTANT: The freeze sensor will not guard against the loss of water. A flow switch is recommended to prevent the unit from running if water flow is lost or reduced.

IMPORTANT: If the unit is employing a fresh water system (no anti-freeze protection), it is extremely important to have the Freeze 1 set to 25°F (DIP Switch SW1 set to Off) in order to shut down the unit at the appropriate leaving water temperature and protect your heat pump from freezing if a freeze sensor is included.

AIR COIL FREEZE PROTECTION

Air coil freeze protection sensor, mounted between the thermal expansion device and the evaporator, monitors refrigerant temperature between the evaporator coil and thermal expansion valve (see Fig. 23). If temperature drops below or remains at the freeze limit trip for 30 seconds, the controller will shut down the compressor

and enter into a soft-lockout condition. The default freeze limit trip is 25°F, this can be changed to 15°F by flipping DIP switch SW1 (see Fig. 21, Item 10, Fig. 24, and Table 11.)

CARRIER Aquazone 50WT - AIR COIL FREEZE PROTECTION - 1

natural_image Mechanical diagram showing a pipe connection with a black coiled tube and a mechanical assembly (no text or symbols)

Fig. 22 — Waterside Freeze Sensor Location (FREEZE 1) — Vertical Configuration Shown

CARRIER Aquazone 50WT - AIR COIL FREEZE PROTECTION - 2

natural_image Technical diagram of a mechanical assembly with pipes and a valve, no visible text or symbols

Fig. 23 — Air Coil Freeze Sensor Location (FREEZE 2) — Vertical Configuration Shown

HIGH CONDENSATE LEVEL SHUTDOWN

The condensate overflow protection sensor is located in the drain pan of the unit and connected to the "COND" terminal on the UPM board (see Fig. 21, item 8).

Anti-Short Cycle Timer

Five minute delay on break timer to prevent compressor short cycling.

Random Start Time Delay

Each controller has an unique random start delay ranging from 270 to 300 seconds on initial power up to reduce the chance of multiple units simultaneously starting at the same time after power up or after a power interruption, in order to avoid creating a large electrical spike.

Low-Pressure Bypass Timer

If the compressor is running and the low pressure switch opens, the controller will keep the compressor On for 120 seconds. After two minutes if the low-pressure switch remains open, the controllers will shut down the compressor and enter a soft lockout. The compressor will not be energized until the low-pressure switch closes and the anti-short cycle time delay expires. If the low-pressure switch opens two or four times in one hour, the unit will enter a hard lockout. In order to exit hard lockout power to the unit would need to be reset. The reset signal is either a Y or R signal depending on the position of the DIP switch as shown in Table 11. If the reset is set to R, the board must be manually powered off and powered back on to exit the hard lock out.

Brownout/Surge/Power Interruption Protection

The brownout protection in the UPM board will shut down the compressor if the incoming power falls below 18 vac. The compressor will remain Off until the voltage is above 18 vac and Anti-Short Cycle Timer (300 seconds) times out. The unit will not go into a hard lockout.

Alarm Output

Alarm output is Normally Open (NO) dry contact. If pulse is selected the alarm output will be pulsed. The fault output will depend on the DIP switch setting for "Alarm". If it is set to "CONST", a constant signal will be produced to indicate a fault has occurred and the unit re-quires inspection to determine the type of fault. If it is set to "PULSE" a pulse signal is produced and a fault code is detected by a remote device indicating the fault. (For blink code explanation, see Table 12). The remote device must have a analog input with malfunction detection capability to interpret PULSE signal when the UPM board is set to "PULSE".

IMPORTANT: If 24 vac output is needed R must be wired to ALR-COM terminal; 24 vac will be available to the ALR-OUT terminal when the unit is in the alarm condition.

Test Mode

A test DIP switch is provided to reduce all time delays settings to 10 seconds during troubleshooting or verification of unit operation.

IMPORTANT: Operation of unit in test mode can lead to accelerated wear and premature failure of components. The "TEST" switch must be set back to "NO" after troubleshooting/servicing.

INTELLIGENT ALARM RESET

If a fault condition is initiated, the five minute delay on break time period is initiated and the unit will restart after these delays expire. During this period the fault LED will indicate the cause of the fault. If the fault condition still exists or occurs two or four times (depending on "2" or "4" settings for Lockout DIP Switch) before 60 minutes, the unit will go into a hard lockout and requires a manual lockout reset. See Fig. 24.

HARD LOCKOUT RESET

A hard lockout can be reset by turning the unit thermostat off and then back on when the "RESET" DIP switch is set to "Y" or by shutting off unit power at the circuit breaker when the "RESET" DIP switch is set to "R".

NOTE: The blower motor will remain active during a lockout condition.

Table 11 — UPM DIP Switch Selectable Positions

TOGGLEFUNCTIONONOFFFACTORY DEFAULT
1Lockout422
2ResetRYY
3AlarmContPulsePulse
4TestYesNoNo
5Freeze 115°F25°F25°F
6Freeze 215°F25°F25°F
7PumpONOFFOFF

Table 12 — UPM Fault Blink Codes

BLINKSFAULTFAULT CRITERIA
NoneNoneAll fault conditions normal.
1High PressureRefrigerant discharge pressure has exceeded 600 psig.
2Low PressureRefrigerant suction pressure has fallen below 40 psig.
3Water Coil Freeze ConditionRefrigerant temperature to the water coil has fallen below 25°F for 120 seconds.
4Condensate OverflowCondensate levels in the unit drain pan are too high.
5Brown OutControl voltage has fallen below 18 VAC
6Air Coil Freeze ConditionRefrigerant temperature to the air coil has fallen below 25°F for 120 seconds.
7Refrigerant Leak FaultRefrigerant LFL% is more than 15%.

ON OFF CTS 208-7 T126

Fig. 24 — UPM Settings DIP Switch (SW1)

OPTION CARD

Units ordered with the water side economizer or hot gas reheat factory installed options and no factory installed DDC controller will include the Option Card as standard (see Fig. 25).

The card has three primary functions:

"Boilerless" Electric Heat Control

Boilerless heat control is a means to control an auxiliary electric heater on units that are connected to a water loop without a reliable heat injection source. The option card features a potentiometer to configure a water loop heat setpoint (Item 2, Fig. 25, Heat Set Point Potentiometer). When the water loop (EWT) drops below the specified setpoint and there is a call for heating the compressor will be disabled and the option card sends a 24-v output to enable the electric heater.

On/Off Hot Gas Reheat Control

Hot gas reheat control is an active means of dehumidification control. HGRH is enabled when the space temperature is satisfied but the space humidity is above the desired setpoint. The Option card energizes the fan, reversing valve, HGRH valve and compressor.

Water Side Economizer Control

Water side economizer control allows for cooling directly with the source water when the source water temperature is below a configurable setpoint. The expansion card features a potentiometer to configure a water loop cool setpoint (Item 1, Fig. 25, Cool Set Point Potentiometer). When the water loop drops below the specified setpoint and there is a call for cooling the WSE diverting valve will divert water through the water side economizer coil. If a cooling call remains for a period of >10 min the compressor will be enabled to assist the WSE in meeting the cooling demand.

See Fig. 26-34 for wiring diagrams.

4.350+/-.010 3.800 3.750 +/-.010 3.000 T2 R T1 T8 T9 G_OUT P.N: 8733827071 B344-12 PC31697-1A SPC9-2 .475 B/C T10 T11 0.895 W_OUT H_OUT E_OUT 0.512 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

1 Cool Set Point Potentiometer
2 Heat Set Point Potentiometer
3Operating Mode Dip Switch
4Entering Water Temperature
5H Signal Input
6O Signal Input
7Y Call Input
8LED Input Status
9Economizer Output "E_OUT"
10Hot Gas Reheat Output "H_OUT"
11Boilerless Control "W_OUT"
12Reversing Valve Output "O_OUT"
13Option Card Standoff
14LED Output Status
15FAN Output "G_OUT"
16Y Call Output "Y_OUT"
1724 VAC Power Input
1824 VAC Power Common

Fig. 25 — Option Card

CARRIER Aquazone 50WT - Water Side Economizer Control - 2

COLOR CHART LEGEND
ABBREVIATIONCOLOR
BKBLACK
BLBLUE
BNBROWN
GNGREEN
ORORANGE
RDRED
VTVIOLET
WTWHITE
YLYELLOW
GYGREY
UPM STATUS LED - BLINK CODES
1HIGH PRESSURE FAULT
2LOW PRESSURE FAULT
3CONDENSER FREEZE CONDITION
4CONDENSATE OVERFLOW FAULT
5BROWN OUT FAULT
6EVAPORATOR FREEZE CONDITION
7REFRIGERANT LEAKAGE

FACTORY WIRE FIELD WIRE

STANDARD COMPONENTS LEGEND: BM - BLOWER MOTOR CAP - COMPRESSOR CAPACITOR CBR - 24V CIRCUIT BREAKER CC - COMPRESSOR CONTACTOR
HPS - HIGH PRESSURE SWITCH LPS - LOW PRESSURE SWITCH
RV - REVERSING VALVE (HEAT PUMPS)

CS - CONDENSATE SENSOR (IN DRAIN PAN)

OPTIONAL COMPONENTS LEGEND:

[ ] A2L - AIR TO LIQUID REFRIGERANT LEAK SENSOR
[ ] AUX - AUXILIARY RELAY (FOR LOOP RUMP
[ ] CMR - COMPRESSOR MONITOR
[ ] DPS - DIFFERENTIAL PRESSURE SWITCH
[ ] DS = DISCONNECT SWITCH [ ] EMS = ENERGY MGMT SYSTEM RELAY
[ ] FB - FUSE BLOCK (FOR 100KA SCCR RATING) [ ] HRP - HEAT RECOVERY PACKAGE: HRPM- HEAT RECOVERY PUMP MOTOR HWL - HOT WATER LIMIT (120F) LGL - LOW GAS TEMPERATURE LIMIT (100F) SWT - ON/OFF SWITCH AND OVERLOAD [ ] HSL - HIGH TEMPERATURE SUCTION LIMIT (WITH HOT GAS BYPASS ONLY) [ ] LWV - LEAVING WATER VALVE

NOTES: 1. SEE UNIT NAME PLATE FOR ELECTRICAL RATING. 2. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH

N.E.C.-N.F.P.A. #70, COPPER CONDUCTORS ONLY - CONDUCTEURS EN CUIVRE SEULEMENT. 3. 208/230V. UNITS ARE FACTORY WIRED FOR 230V. OPERATION FOR 208V. OPERATION

REMOVE PRIMARY LEAD FROM 240 TERMINAL AND CONNECT IT TO 208. CAP ALL UNUSED TERMINALS.

  1. FOR ALTERNATE EMS COIL VOLTAGES CONSULT FACTORY.
  2. UHM-L INCLUDES BUILT IN: 270-300 SECOND RANDOM START

300 SECOND DELAY ON BREAK

120 SECOND LOW PRESSURE BYPASS

  1. TEST DIP SWITCH REDUCES DELAYS TO 10 SEC WHEN SET TO YES. MUST BE SET TO NO FOR NORMAL OPERATION
  2. "FREEZE SENSOR" ON CONDENSER WILL BE SET TO 25°F OPERATION BY DEFAULT, IF 15°F OPERATION IS REQUIRED,
    MOVE DIP SWITCH SLIDER TO THE 15F POSITION.
  3. "ALARM OUTPUT" DIR SWITCH MUST BE SET TO "RULSE" IF PLINKING T-STAT SERVICE LIGHT IS DESIRED OR IF
    DDC CONNECTION IS AVAILABLE. CONT FOR NON BLINKING THERMOSTAT CONNECTION.
  4. DEFAULT SETTINGS FOR UPM BOARD FROM FACTORY SHOWN. ALSO SEE INSTALLATION MANUAL.
  5. ALARM OUTPUT IS NORMALLY OPEN (NO) DRY CONTACT, IF 24 VAC IS NEEDED CONNECT R FROM TERMINAL
    BLOCK TO ALR-COM TERMINAL, 24VAC WILL BE SENSED ON THE ALR-OUT WHEN THE UNIT IS IN ALARM
    CONDITION. OUTPUT WILL BE PULSED IF PULSE IS SELECTED. 11 REVERSING VALVE NOT PRESENT ON UNITS WITH STRAIGHT COOL
  6. UNIT WILL HAVE OPTIONAL DISCONNECT SWITCH OR FUSE PROTECTION, UNIT WILL NOT HAVE BOTH.

Fig. 26 — Single Phase, Constant Airflow ECM Motor, Standard Unit

CARRIER Aquazone 50WT - Water Side Economizer Control - 3

COLOR CHART LEGEND
ABBREVIATIONCOLOR
BKBLACK
BLBLUE
BNBROWN
GNGREEN
ORORANGE
RDRED
VTVIOLET
WTWHITE
YLYELLOW
GYGREY
UPM STATUS LED - BLINK CODES
1HIGH PRESSURE FAULT
2LOW PRESSURE FAULT
3CONDENSER FREEZE CONDITION
4CONDENSATE OVERFLOW FAULT
5BROWN OUT FAULT
6EVAPORATOR FREEZE CONDITION
7REFRIGERANT LEAKAGE

FACTORY WIRE FIELD WIRE

STANDARD COMPONENTS LEGEND: BM - BLOWER MOTOR CAP - COMPRESSOR CAPACITOR CBR - 24V CIRCUIT BREAKER CC - COMPRESSOR CONTACTOR CS1 - CONDENSATE SENSOR (IN FS - FREEZE SENSOR HPS - HIGH PRESSURE SWITCH LPS - LOW PRESSURE SWITCH RV - REVERSING VALVE (HEAT F Y2S - COMPRESSOR 2ND STAGE

OPTIONAL COMPONENTS LEGEND: [ ] A2L - AIR TO LIQUID REFRIGERANT LEAK SENSOR [ ] AUX - AUXILIARY RELAY (FOR LOOP PUMP, ETC) [ ] CMR - COMPRESSOR MONITOR RELAY [ ] CS2 - CONDENSATE SENSOR (IN ECONOMIZER DRAIN PAN) [ ] DPS - DIFFERENTIAL PRESSURE SWITCH [ ] DS - DISCONNECT SWITCH [ ] EMS - ENERGY MGMT SYSTEM RELAY [ ] FB - FUSE BLOCK (FOR 100KA SCCR RATING) [ ] HGR - HOT GAS REHEAT RELAY [ ] HGV - HOT GAS VALVE SOLENOID [ ] HRP - HEAT RECOVERY PACKAGE: HRPM- HEAT RECOVERY PUMP MOTOR HWL - HOT WATER LIMIT (120F) LGL - LOW GAS TEMPERATURE LIMIT (100F) SWT - ON/OFF SWITCH AND OVERLOAD [ ] HSL - HIGH TEMPERATURE SUCTION LIMIT (WITH HOT GAS BYPASS ONLY) [ ] LWV - LEAVING WATER VALVE [ ] MBV - MOTORIZED BALL VALVE

NOTES:

  1. SEE UNIT NAME PLATE FOR ELECTRICAL RATING.
  2. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH

N.E.C.-N.F.P.A. #70, COPPER CONDUCTORS ONLY - CONDUCTEURS EN CUIVRE SEULEMENT.

  1. 208/230V UNITS ARE FACTORY WIRED FOR 230V OPERATION. FOR 208V OPERATION, REMOVE PRIMARY LEAD FROM 240 TERMINAL AND CONNECT IT TO 208 CAR ALL UNUSED TERMINALS

  2. FOR ALTERNATE EMS COIL VOLTAGES CONSULT FACTORY.

  3. UPM-I INCLUDES BUILT IN: 270-300 SECOND RANDOM START

300 SECOND DELAY ON BREAK 120 SECOND LOW PRESSURE BYPASS

  1. "TEST" DIP SWITCH REDUCES DELAYS TO 10 SEC WHEN SET TO YES. MUST BE SET TO "NO" FOR NORMAL OPERATION.

  2. "FREEZE SENSOR" ON CONDENSER WILL BE SET TO 25°F OPERATION BY DEFAULT, IF 15°F OPERATION IS REQUIRED, SWITCH SLIDER TO THE 15°F POSITION

  3. "ALARM OUTPUT" DIP SWITCH MUST BE SET TO "PULSE" IF BLINKING T-STAT SERVICE LIGHT IS DESIRED OR IF DDC

CONNECTION IS AVAILABLE. CONT FOR NON BLINKING THERMOSTAT CONNECTION. 8. DEFAULT SETTINGS FOR LIRM BOARD FROM FACTORY SHOWN, ALSO SEE INSTALLATION MANUAL

  1. ALARM OUTPUT IS NORMALLY OPEN (NO) DRY CONTACT. IF 24 VAC IS NEEDED, CONNECT R FROM TERMINAL BLOCK TO ALR-COM TERMINAL, 24VAC WILL BE SENSED ON THE ALR-OUT WHEN THE UNIT IS IN ALARM CONDITION. OUTPUT WILL BE

PULSED IF PULSE IS SELECTED. 11. REVERSING VALVE NOT PRESENT ON UNITS WITH STRAIGHT COOL

  1. UNIT WILL HAVE OPTIONAL DISCONNECT SWITCH OR FUSE PROTECTION, UNIT WILL NOT HAVE BOTH.
  2. HOT GAS REHEAT RELAY WILL ONLY BE USED WHEN HOT GAS REHEAT AND ECONOMIZER OPTIONS ARE SELECTED.

Fig. 27 — Single Phase, Constant Airflow ECM Motor, Option Card (WSE, HGRH, Boilerless Heat)

CARRIER Aquazone 50WT - Fig. 27 — Single Phase, Constant Airflow ECM Motor, Option Card (WSE, HGRH, Boilerless Heat) - 1

COLOR CHART LEGEND
ABBREVIATIONCOLOR
BKBLACK
BLBLUE
BNBROWN
GNGREEN
ORORANGE
RDRED
VTVIOLET
WTWHITE
YLYELLOW
GYGREY
UPM STATUS LED - BLINK CODES
1HIGH PRESSURE FAULT
2LOW PRESSURE FAULT
3CONDENSER FREEZE CONDITION
4CONDENSATE OVERFLOW FAULT
5BROWN OUT FAULT
6EVAPORATOR FREEZE CONDITION
7REFRIGERANT LEAKAGE

FACTORY WIRE FIELD WIRE

STANDARD COMPONENTS LEGEND:
APS - AIR PRESSURE SWITCH
BM - BLOWER MOTOR
CAP - COMPRESSOR CAPACITOR
CBR - 24V CIRCUIT BREAKER
CC - COMPRESSOR CONTACTOR
CS - CONDENSATE SENSOR (IN D
FS - FREEZE SENSOR
HR1 - HEATING RELAY
HE1 - HEATING ELEMENT
HLS1 - HEATING LIMIT SWITCH
HPS - HIGH PRESSURE SWITCH
LPS - LOW PRESSURE SWITCH
RV - REVERSING VALVE (HEAT P
YZS - COMPRESSOR 2ND STAGE
OPTIONAL COMPONENTS LEGENDS
[ ] AZL - AIR TO LIQUID REFRIGERANT LEAK SENSOR
[ ] AUX - AUXILIARY RELAY(FOR LOOP PUMP, ETC)
[ ] CBR1- CIRCUIT BREAKERS (1 - 2)
[ ] CBR2
[ ] CMR - COMPRESSOR MONITOR RELAY
[ ] DPS - DIFFERENTIAL PRESSURE SWITCH
[ ] EMS - ENERGY MGMT SYSTEM RELAY
[ ] HR2 - HEATING RELAY 2,3,4
[ ] HR3,HR4
[ ] HE2 - HEATING ELEMENT (2 - 4)
[ ] HE3,HE4
[ ] HLS2- HEATING LIMIT SWITCH
[ ] HLS3,HLS4
[ ] HRP - HEAT RECOVERY PACKAGE:
[ ] HRPM- HEAT RECOVERY PUMP MOTOR
[ ] HWL - HOT WATER LIMIT (120F)
[ ] LGL - LOW GAS TEMPERATURE LIMIT (100F)
[ ] SWT - ON/OFF SWITCH AND OVERLOAD
[ ] HSL - HIGH TEMPERATURE SUCTION LIMIT(WITH HOT GAS BYPASS ONLY)
[ ] LWV - LEAVING WATER VALVE
[ ] TB1 - POWER TERMINAL BLOCK

NOTES: 1. SEE UNIT NAME PLATE FOR ELECTRICAL RATING.
2. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH
N.E.C.-N.F.P.A. #70, COPPER CONDUCTORS ONLY - CONDUCTEURS EN COIVRE SEOLEMENT. 3. 208/230V UNITS ARE FACTORY WIRED FOR 230V OPERATION FOR 208V OPERATION
REMOVE PRIMARY LEAD FROM 240 TERMINAL AND CONNECT IT
4. FOR ALTERNATE EMS COIL VOLTAGES CONSULT FACTORY. 5. UBM-L INCLUDES BUILT IN: 270-300 SECOND RANDOM START
3. OPM=1 INCLUDES BUILT IN: 270=300 SECOND RANDOM START 300 SECOND DELAY ON BREAK
120 SECOND LOW PRESSURE BYPASS

  1. "TEST" DIP SWITCH REDUCES DELAYS TO 10 SEC WHEN SET TO YES. MUST BE SET TO "NO" FOR NORMAL OPERATION.

  2. FREEZE SENSOR ON CONDENSER WILL BE SET TO 20F OPERATION BY DEFAULT, IF 15F OPERATION IS REQUIRED, MOVE DIP SWITCH SLIDER TO THE 15F POSITION

  3. "ALARM OUTPUT" DIP SWITCH MUST BE SET TO "PULSE" IF BLINKING T-STAT SERVICE LIGHT IS DESIRED OR IF DDC CONNECTION IS AVAILABLE. CONT

FOR NON BLINKING THERMOSTAT CONNECTION.

  1. DEFAULT SETTINGS FOR OPM BOARD FROM FACTORY SHOWN. ALSO SEE INSTALLATION MANUAL.
  2. ALARM OUTPUT IS NORMALLY OPEN (NO) DRY CONTACT. IF 24 VAC IS NEEDED. CONNECT R FROM TERMINAL BLOCK TO ALR-COM TERMINAL. 24VAC

WILL BE SENSED ON THE ALR-OUT WHEN THE UNIT IS IN ALARM CONDITION. OUTPUT WILL BE PULSED IF PULSE IS SELECTED.

  1. REVERSING VALVE NOT PRESENT ON UNITS WITH STRAIGHT COOL.
  2. ELVINOL (ELV) NIAL RESET DRYABY CONTACTS WILL OPEN AT 1955 / / 55 AND CLOSE AT 1955 / / 75 BACK UP CONTACTS WILL OPEN AT

  3. SKEJUKWLSKW, DUAL RESET PRIMARY CONTACTS WILL OPEN AT 135F (+/-3F) AND CLOSE AT 125F (+/-7F). BACK UP CONTACTS WILL OPEN AT 180F (+/-8F). BACK-UP CONTACTS WILL NOT RESET.

20KW: DUAL RESET PRIMARY CONTACTS WILL OPEN AT 140°F (+/-5°F) AND CLOSE AT 110°F (+/-7°F). BACK UP CONTACTS WILL OPEN AT 180°F

(+/-8F). BACK-UP CONTACTS WILL NOT RESET.

  1. ONLY HEATERS 15 - 20 KW HAVE CIRCUIT BREAKERS.
  2. TERMINAL BLOCK USED ON 5KW/10KW UNITS ONLY

  3. THERMOSTATS USING W2/E AS EMERGENCY HEAT SIGNAL MUST TERMINATE GREY W2 WIRE ON HC1 COIL FOR 5KW UNITS.

  4. AIR PRESSURE SWITCH IS NORMALLY OPEN AND WILL CLOSE WHEN THE FAN IS ON.

USE CLASS II FIELD WIRING SET MOTOR TERMINAL CONNECTIONS BELOW BK RD GN/YL BM TRANSFORMER BLK (COM) LINE VOLTAGE 1 UNIT GROUND LUG L1 L2 CC BK RD YL COMP HRPM BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY BY HY GY RL R0 R1 C1 C2 TO FCS MOTOR CN0 ADJUS1 LDW 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5V 1.5M BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BL BRD30000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000

N.E.C.-N.F.P.A. #70, COPPER CONDUCTORS ONLY - CONDUCTEURS EN CUIVRE SEULEMENT. 3. 208/230V UNITS ARE FACTORY WIRED FOR 230V OPERATION. FOR 208V OPERATION, REMOVE PRIMARY LEAD FROM 240 TERMINAL AND CONNECT IT TO 208. CAP ALL UNUSED TERMINALS.
4. FOR ALTERNATE EMS COIL VOLTAGES CONSULT FACTORY. 5. UPM-I INCLUDES BUILT IN: 270-300 SECOND RANDOM START
300 SECOND DELAY ON BREAK 120 SECOND LOW PRESSURE BYRASS
6. "TEST" DIP SWITCH REDUCES DELAYS TO 10 SEC WHEN SET TO YES, MUST BE SET TO "NO" FOR NORMAL OPERATION. 7. "LEFT SWITCH" ON CONSTRUCTION WILL BE SET TO SET OPERATION ON OUTPUT. IF ASST OPERATION IS REQUIRED, LEFT SWITCH CURED TO THE
7. FREEZE SENSOR ON CONDENSER WILL BE SET TO 25F OPERATION BY DEFAULT, IF 15F OPERATION IS REQUIRED, MOVE DIP SWITCH SIDER TO THE 15F POSITION.
8. "ALARM OUTPUT" DIP SWITCH MUST BE SET TO "PULSE" IF BLINKING T-STAT SERVICE LIGHT IS DESIRED OR IF DDC CONNECTION IS AVAILABLE, CONT FOR NON-BLINKING THERMOSTAT CONNECTION
9. DEFAULT SETTINGS FOR UPM BOARD FROM FACTORY SHOWN. ALSO SEE INSTALLATION MANUAL.
10. ALARM OUTPUT IS NORMALLY OPEN (NO) DRY CONTACT. IF 24 VAC IS NEEDED, CONNECT R FROM TERMINAL BLOCK TO ALR-CUM TERMINAL, 24VAC WILL BE SENSED ON THE ALR-OUT WHEN THE UNIT IS IN ALARM CONDITION. OUTPUT WILL BE PULSED IF PULSE IS SELECTED.
11. REVERSING VALVE NOT PRESENT ON UNITS WITH STRAIGHT COOL. 12. 5kW 10kW 15kW DUAL RESET PRIMARY CONTACTS WILL OPEN AT 155°E (+/-5°E) AND CLOSE AT 125°E (+/-7°E). BACK UP CONTACTS WILL OPEN AT
180°F (+/-8°F). BACK-UP CONTACTS WILL NOT RESET. 2611RVAL RESET PRIMARY CONTACTS WILL OPEN AT 400°F (+/-5°F) AND CLOSE AT 410°F (+/-7°F). BACK UP CONTACTS WILL OPEN AT 180°F.
20KW: DUAL RESET PRIMARY CONTACTS WILL OPEN AT (+/-8F). BACK-UP CONTACTS WILL NOT RESET.
13. ONLY HEATERS 15 - 20 KW HAVE CIRCUIT BREAKERS. 14. TERMINAL BLOCK USED ON 5KW/10KW UNITS ONLY
15. THERMOSTATS USING W2/E AS EMERGENCY HEAT SIGNAL MUST TERMINATE GRAY W2 WIRE ON HC1 COIL FOR 5KW UNITS.
16. HOT GAS REHEAT RELAY WILL ONLY BE USED WHEN HOT GAS REHEAT AND ECONOM 17. AIR PRESSURE SWITCH IS NORMALLY OPEN AND WILL CLOSE WHEN THE FAN IS ON.

Fig. 29 — Single Phase, Constant Airflow ECM Motor, E-Heat, Dual Point Power, Option Card (WSE, HGRH, Boilerless Heat)
LINE VOLTAGE 2 UNIT GROUND LUG L1 L2 TB1 L1 BLACK L3 RED RED L1 BLACK L2 CBR1 CBR2 HEATER PACKAGE WIRE HARNESS PLUS CONNECTED TO MAIN CONTROL BOX NOTE - L1 AND L2 PONIDE POWER TO CONTROL TRANSFORMER AND BLOWER MOTOR C5 RED L2 BLACK HL31 HE1 HL32 HE2 HL34 HE1 HL35 HE4 HL36 HE3 HL37 HE2 HL38 HE1 HL39 HE4 HL40 HE3 HL41 HE2 HL42 HE1 HL43 HE4 HL44 HE3 HL45 HE2 HL46 HE1 HL47 HE4 HL48 HE3 HL49 HE2 HL50 HE1 HL51 HE4 HL52 HE3 HL53 HE2 HL54 HE1 HL55 HE4 HL56 HE3 HL57 HE2 HL58 HE1 HL59 HE4 HL60 HE3

COLOR CHART LEGEND
ABBREVIATIONCOLOR
BKBLACK
BLBLUE
BNBROWN
GNGREEN
ORORANGE
RDRED
VTVOLET
WTWHITE
YLYELLOW
GYGREY
UPM STATUS LED - BLINK CODES
1HIGH PRESSURE FAULT
2LOW PRESSURE FAULT
3CONDENSER FREEZE CONDITION
4CONDENSATE OVERFLOW FAULT
5BROWN OUT FAULT
6LAVORATOR FREEZE CONDITION
7REFRIGERANT LEAKAGE

FACTORY WIRE FIELD WIRE

STANDARD COMPONENTS LEGEND:
APS - AIR PRESSURE SWITCH
BM - BLOWER MOTOR
CAP - COMPRESSOR CAPACITOR
CBR - 24V CIRCUIT BREAKER
CC - COMPRESSOR CONTACTOR
CS1 - CONDENSATE SENSOR (IN
FS - FREEZE SENSOR
HR1 - HEATING RELAY
HE1 - HEATING ELEMENT
HLS1 - HEATING LIMIT SWITCH
HPS - HIGH PRESSURE SWITCH
LPS - LOW PRESSURE SWITCH
RV - REVERSING VALVE (HEAT F
YZS - COMPRESSOR 2ND STAGE
OPTIONAL COMPONENTS LEGEND:
[ ]A2L - AIR TO LIQUID REFRIGERANT LEAK SENSOR
[ ]AUX - AUXILIARY RELAY(FOR LOOP PUMP, ETC)
[ ]CBR1- CIRCUIT BREAKERS (1 - 2)CBR2
[ ]CS2 - CONDENSATE SENSOR (IN ECONOMIZER DRA
[ ]CMR - COMPRESSOR MONITOR RELAY
[ ]DPS - DIFFERENTIAL PRESSURE SWITCH
[ ]EMS - ENERGY MOMT SYSTEM RELAY
[ ]HR2 - HEATING RELAY 2.3.4HR3,HR4
[ ]HE2 - HEATING ELEMENT (2 - 4)HE3,HE4
[ ]HLS2 - HEATING LIMIT SWITCHHLS3,HLS4
[ ]HDR - HOT GAS REHEAT RELAY
[ ]HDY - HOT GAS VALVE SOLENOID
[ ]HRP - HEAT RECOVERY PACKAGE:HRPM- HEAT RECOVERY PUMP MOTORHWL - HOT WATER LIMIT (120F)LQL - LOW GAS TEMPERATURE LIMIT (100F)SWT - ON/OFF SWITCH AND OVERLOAD
[ ]HSL - HIGH TEMPERATURE SUCTION LIMIT(WTH HOT GAS BYPASS ONLY)
[ ]LWV - LEAVING WATER VALVE
[ ]MBV - MOTORIZED BALL VALVE
[ ]TB1 - POWER TERMINAL BLOCK

NOTES:
1. SEE UNIT NAME PLATE FOR ELECTRICAL RATING. 2. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH
N.E.C.-N.F.P.A. #70, COPPER CONDUCTORS ONLY - CONDUCTEURS EN CUIVRE SEULEMENT.
3. 208/230V UNITS ARE FACTORY WIRED FOR 230V OPERATION. FOR 208V OPERATION, REMOVE PRIMARY LEAD FROM 240 TERMINAL AND CONNECT IT TO 208. CAP ALL UNUSED TERMINALS.
4. FOR ALTERNATE EMS COIL VOLTAGES CONSULT FACTORY. 5. UPM-I INCLUDES BUILT IN: 270-300 SECOND RANDOM START
300 SECOND DELAY ON BREAK 100 SECOND LOW PRESSURE DYPA
120 SECOND LOW PRESSURE BYPASS 6. "TEST" DIP SWITCH REDUCES DELAYS TO 10 SEC WHEN SET TO YES, MUST BE SET TO "NO" FOR NORMAL OPERATION.
7. "FREEZE SENSOR" ON CONDENSER WILL BE SET TO 25F OPERATION BY DEFAULT, IF 15F OPERATION IS REQUIRED, MOVE DIP SWITCH SLIDER TO THE
8. "ALARM OUTPUT" DIP SWITCH MUST BE SET TO "PULSE" IF BLINKING T-STAT SERVICE LIGHT IS DESIRED OR IF DDC CONNECTION IS AVAILABLE. CONT
FOR NON BLINKING THERMOSTAT CONNECTION. 9. DEFAULT SETTINGS FOR LUPM BOARD FROM FACTORY SHOWN, ALSO SEE INSTALLATION MANUAL.
10. ALARM OUTPUT IS NORMALLY OPEN (NO) DRY CONTACT. IF 24 VAC IS NEEDED, CONNECT R FROM TERMINAL BLOCK TO ALR-COM TERMINAL, 24VAC
WILL BE SENSED ON THE ALR-OUT WHEN THE UNIT IS IN ALARM CONDITION. OUTPUT WILL BE PULSED IF PULSE IS SELECTED. 11. REVERSING VALVE NOT PRESENT ON UNITS WITH STRAIGHT COOL.
12. 5kW.10kW.15kW DUAL RESET PRIMARY CONTACTS WILL OPEN AT 155F (+/-5F) AND CLOSE AT 125F (+/-7F). BACK UP CONTACTS WILL OPEN AT
180°F (+/-8°F). BACK-UP CONTACTS WILL NOT RESET. 20kW: DUAL RESET PRIMARY CONTACTS WILL OPEN AT 140°F (+/-5°F) AND CLOSE AT 110°F (+/-7°F). BACK UP CONTACTS WILL OPEN AT 180°F
(+/-8°F). BACK-UP CONTACTS WILL NOT RESET.
13. ONLY HEATERS 15 - 20 KW HAVE CIRCUIT BREAKERS. 14. TERMINAL BLOCK USED ON 5KW/10KW UNITS ONLY.
15. THERMOSTATS USING W2/E AS EMERGENCY HEAT SIGNAL MUST TERMINATE GRAY W 16. HOT CAS REHEAT RELAY WILL ONLY BE USED WHEN HOT CAS REHEAT AND ECONOM
16. HOT GAS REHEAT RELAY WILL ONLY BE USED WHEN HOT GAS REHEAT AND ECONOR 17. AIR PRESSURE SWITCH IS NORMALLY OPEN AND WILL CLOSE WHEN THE FAN IS ON.

CARRIER Aquazone 50WT - Fig. 27 — Single Phase, Constant Airflow ECM Motor, Option Card (WSE, HGRH, Boilerless Heat) - 4

flowchart
graph TD
    A["Common"] --> B["C"]
    B --> C["OR"]
    C --> D["RV"]
    D --> E["10A"]
    E --> F["OR"]
    F --> G["BL"]
    G --> H["CLV"]
    H --> I["OR"]
    I --> J["BL"]
    J --> K["CLV"]
    K --> L["OR"]
    L --> M["BL"]
    M --> N["CLV"]
    N --> O["OR"]
    O --> P["BL"]
    P --> Q["CLV"]
    Q --> R["OR"]
    R --> S["BL"]
    S --> T["CLV"]
    T --> U["OR"]
    U --> V["BL"]
    V --> W["CLV"]
    W --> X["OR"]
    X --> Y["BL"]
    Y --> Z["CLV"]
    Z --> AA["OR"]
    AA --> AB["BL"]
    AB --> AC["CLV"]
    AC --> AD["OR"]
    AD --> AE["BL"]
    AE --> AF["CLV"]
    AF --> AG["OR"]
    AG --> AH["BL"]
    AH --> AI["CLV"]
    AI --> AJ["OR"]
    AJ --> AK["BL"]
    AK --> AL["CLV"]
    AL --> AM["OR"]
    AM --> AN["BL"]
    AN --> AO["CLV"]
    AO --> AP["OR"]
    AP --> AQ["BL"]
    AQ --> AR["CLV"]
    AR --> AS["OR"]
    AS --> AT["BL"]
    AT --> AU["CLV"]
    AU --> AV["OR"]

UNIT GROUND LUG WT BK GN/YL BM CC DP BP RD CAP YL COMP TJL TJH SMT HRPM L1 L2 DS FB RD TRANSFORMER BLK (COM) 3

COLOR CHART LEGEND
ABBREVIATIONCOLOR
BKBLACK
BLBLUE
BNBROWN
GNGREEN
ORORANGE
RDRED
VTVIOLET
WTWHITE
YLYELLOW
GYGREY
UPM STATUS LED - BLINK CODES
1HIGH PRESSURE FAULT
2LOW PRESSURE FAULT
3CONDENSER FREEZE CONDITION
4CONDENSATE OVERFLOW FAULT
5BROWN OUT FAULT
6EVAPORATOR FREEZE CONDITION
7REFRIGERANT LEAKAGE

FACTORY WIRE FIELD WIRE ----

STANDARD COMPONENTS LEGEND: BM - BLOWER MOTOR

CAP - COMPRESSOR CAPACITOR CRR - 24V CIRCUIT BREAKER

CC - COMPRESSOR CONTACTOR

CS1 - CONDENSATE SENSOR (IN UNIT DRAIN PAN)

PS - FREEZE SENSOR HPS - HIGH PRESSURE SWITCH

LPS - LOW PRESSURE SWITCH

RV - REVERSING VALVE (HEAT PUMPS)

123 - COMPRESSOR 2ND STAGE OPTIONAL COMPONENTS LEGEND:

[ ] A2L - AIR TO LIQUID REFRIGERANT LEAK SENSOR

[ ] A2R - A2L BLOWER RELAY

CS2 - CONDENSATE SENSOR (IN ECONOMIZER DRAIN PAN)

[ ] DPS - DIFFERENTIAL PRESS [ ] DS - DISCONNECT SWITCH

[ ] FB - FUSE BLOCK (FOR 65KA SCCR RATING)

[ ] HGV - HOT GAS VALVE SOL

[ ] HRP - HEAT RECOVERY PACKAGE: HRPM - HEAT RECOVERY PUMP MOTO

HWL - HOT WATER LIMIT (120F)

LGL - LOW GAS TEMPERATURE LIMIT (100F)

SWT - ON/OFF SWITCH AND OVERLOAD

[ ] HSL - HIGH TEMPERATURE SOCTION L (WITH HOT GAS BYPASS ONLY)

[ ] LWV - LEAVING WATER VALVE

[ ] LWR - LEAVING WATER RELAY

[ ] MEV - MOTORIZED BALL VALVE

NOTES: 1. SEE UNIT NAME PLATE FOR ELECTRICAL RATING

  1. SEE UNITS NAME PLET FOR ELECTRICAL RATINGS.
  2. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH

N.E.C.-N.F.P.A. #70, COPPER CONDUCTORS ONLY - CONDUCTEURS EN CUIVRE SEULEMENT.

  1. 208/230V UNITS ARE FACTORY WIRED FOR 230V OPERATION. FOR 208V OPERATION, REMOVE PRIMARY LEAD FROM 240 TERMINAL AND CONNECT IT TO 208. CAP ALL UNUSED TERMINALS.

  2. UPM-I INCLUDES BUILT IN: 270-300 SECOND RANDOM START

300 SECOND DELAY ON BREAK 120 SECOND LOW PRESSURE BYPASS

  1. "TEST" DIP SWITCH REDUCES DELAYS TO 10 SEC WHEN SET TO YES. MUST BE SET TO "NO" FOR NORMAL

  2. "FREEZE SENSOR" ON CONDENSER WILL BE SET TO 25°F OPERATION BY DEFAULT, IF 15°F OPERATION IS REQUIRED, MOVE DID SWITCH SHED TO THE 15°F POSITION

MOVE DIP SWITCH SLIDER TO THE TSP POSITION. 7. "ALARM OUTPUT" DIP SWITCH MUST BE SET TO "PULSE" IF BLINKING T-STAT SERVICE LIGHT IS DESIRED OR IF DDC

CONNECTION IS AVAILABLE. CONT FOR NON BLINKING THERMOSTAT CONNECTION.

  1. DEFAULT SETTINGS FOR UPM BOARD FROM FACTORY SHOWN. ALSO SEE INSTALLATION MANUAL.
  2. ALARM OUTPUT IS NORMALLY OPEN (NO) DRY CONTACT, IE 24 VAC IS NEEDED CONNECT R FR

TO ALR-COM TERMINAL, 24VAC WILL BE SENSED ON THE ALR-OUT WHEN THE UNIT IS IN ALARM CONDITION.

OUTPUT WILL BE PULSED IF PULSE IS SELECTED. 10. REVERSING VALVE NOT PRESENT ON UNITS WITH STRAIGHT COOL

  1. REVERSING VALVE NOT PRESENT ON UNITS WITH STRAIGHT COOL.
  2. UNIT WILL HAVE OPTIONAL DISCONNECT SWITCH OR FUSE PROTECTION, UNIT WILL NOT HAVE BOTH.

Fig. 30 — Single Phase, Constant Airflow ECM Motor, TruVu™ DDC

CARRIER Aquazone 50WT - Fig. 30 — Single Phase, Constant Airflow ECM Motor, TruVu™ DDC - 1

UPM STATUS LED - BLINK CODESCOLOR CHART LEGEND
1HIGH PRESSURE FAULTABBREVIATIONCOLOR
2LOW PRESSURE FAULTBKBLACK
3CONDENSER FREEZE CONDITIONBLBLUE
4CONDENSATE OVERFLOW FAULTBNBROWN
5BROWN OUT FAULTGNGREEN
6EVAPORATOR FREEZE CONDITIONORORANGE
7REFRIGERANT LEAKAGERDRED
VTVIOLET
WTWHITE
YLYELLOW
GYGREY

STANDARD COMPONENTS LEGEND:
BM - BLOWER MOTOR CBR - 24V CIRCUIT BREAKER
CC - COMPRESSOR CONTACTOR
CS - CONDENSATE SENSOR (IN DRAIN PAN)
HPS - FREEZE SENSOR HPS - HIGH PRESSURE SWITCH
LPS - LOW PRESSURE SWITCH
RV - REVERSING VALVE (HEAT PUMPS) Y2S - COMPRESSOR 2ND STAGE

OPTIONAL COMPONENTS LEGEND:

A2L - AIR TO LIQUID REFRIGERANT LEAK SENSOR

[ ] AUX - AUXILIARY RELAY (FOR LOOP BUMP, ETC)

[ ] CMR - COMPRESSOR MONITOR RELAY

[ ] DPS - DIFFERENTIAL PRESSURE SWITCH

[ ] DS - DISCONNECT SWITCH

EMS - ENERGY MGMT SYSTEM RELAY ED - EUSE BLOCK (FOR SEKA SOOR RATING)

1 HP - FUSE DESIGN (FOR USDA SGR RATING) 2 HRP - HEAT RECOVERY PACKAGE:

HRPM-HEAT RECOVERY PUMP MOTOR

HWL - HOT WATER LIMIT (120F)

LGL = LOW GAS TEMPERATURE LIMIT (TOOF) SWT = ON/OFF SWITCH AND OVERLOAD

[ ] HSL - HIGH TEMPERATURE SUCTION LIMIT

(WITH HOT GAS BYPASS ONLY)

[ ] LWV - LEAVING WATER VALVE

TB2 = MAIN TERMINAL BLOCK (460V UNITS ONLY) TB3 = TERMINAL BLOCK DISCONNECT SWITCH

(460V UNITS ONLY)

NOTES:

  1. SEE UNIT NAME PLATE FOR ELECTRICAL RATING.

  2. ALL FIELD WIRING MUST BE IN ACCORDANCE WI

N.E.C.-N.F.P.A. #70, COPPER CONDUCTORS ONLY - CONDUCTEURS EN COIVRE SEOLEMENT. 3. 208/230V. UNITS ARE FACTORY WIRED FOR 230V OPERATION FOR 208V OPERATION

REMOVE PRIMARY LEAD FROM 240 TERMINAL AND CONNECT IT TO 208. CAP ALL UNUSED TERMINALS.

  1. FOR ALTERNATE EMS COIL VOLTAGES CONSULT FACTORY.

  2. OFM-T INCLUDES BOLT IN: 270-300 SECOND RANDOM START 300 SECOND DELAY ON BREAK

120 SECOND LOW PRESSURE BYPASS

  1. "TEST" DIP SWITCH REDUCES DELAYS TO 10 SEC WHEN SET TO YES. MUST BE SET TO "NO" FOR NORMAL OPERATION.
  2. "FREEZE SENSOR" ON CONDINGER WILL BE SET TO SET OPERATION ON DEFAULT IF LEFT OPERATION IS REQUIRED.

  3. FREEZE SENSOR ON CONDENSER WILL BE SET TO 25F OPERATION BY DEFAULT, IF 15F OPERATION IS REQUIRED, DIP SWITCH SLIDER TO THE 15F POSITION

B. "ALARM OUTPUT" DIP SWITCH MUST BE SET TO "PULSE" IF BLINKING T-STAT SE

CONNECTION IS AVAILABLE. CONT FOR NON BLINKING THERMOSTAT CONNECTION.

  1. DEFAULT SETTINGS FOR UPM BOARD FROM FACTORY SHOWN. ALSO SEE INSTALLATION MANUAL.
  2. ALARM OUTPUT IS NORMALLY OPEN (NO) DRY CONTACT IF 24 VAC IS NEEDED CONNECT R FROM TERMINAL BLOCK TO

ALR-COM TERMINAL, 24VAC WILL BE SENSED ON THE ALR-OUT WHEN THE UNIT IS IN ALARM CONDITION. OUTPUT WILL BE

PULSED IF PULSE IS SELECTED.

  1. REVERSING VALVE NOT PRESENT ON UNITS WITH STRAIGHT COOL.
  2. TERMINAL BLOCK TB3 LOCATED IN SIDE DISCONNECT SWITCH BOX

  3. EON MOTOR IS WIRED BETWEEN LINE AND NEUTRAL FOR 380-460VAC UNITS. FOR 208/230VAC UNITS EON MOTOR IS

WIRED BETWEEN LINES. 14. UNIT WILL HAVE OPTIONAL DISCONNECT SWITCH OR FUSE PROTECTION. UNIT WILL NOT HAVE BOTH

  1. UNIT WILL HAVE OPTIONAL DISCONNECT SWITCH.
  2. SCCR OPTION IS NOT AVAILABLE ON 460 UNITS.

CARRIER Aquazone 50WT - Fig. 30 — Single Phase, Constant Airflow ECM Motor, TruVu™ DDC - 2

COLOR CHART LEGEND
ABBREVIATIONCOLOR
BKBLACK
BLBLUE
BNBROWN
GNGREEN
ORORANGE
RDRED
VTVIOLET
WTWHITE
YLYELLOW
GYGREY
UPM STATUS LED - BLINK CODES
1HIGH PRESSURE FAULT
2LOW PRESSURE FAULT
3CONDENSER FREEZE CONDITION
4CONDENSATE OVERFLOW FAULT
5BROWN OUT FAULT
6EVAPRORATOR FREEZE CONDITION
7REFRIGERANT LEAKAGE

FACTORY WIRE—
FIELD WRE ----
STANDARD COMPONENTS LEGEND: BM - BLOWER MOTOR
CBR - 24V CIRCUIT BREAKER
CC - COMPRESSOR CONTACTOR CS1 CONDENSATE SENSOR (IN
CSF - CONDENSATE SENSOR (IN FS - FREEZE SENSOR
HPS - HIGH PRESSURE SWITCH
LPS - LOW PRESSURE SWITCH RV - REVERSING VALVE (HEAT PUMPS)
Y2S - COMPRESSOR 2ND STAGE

OPTIONAL COMPONENTS LEGEND:

[ ] A2L - AIR TO LIQUID REFRIGERANT LEAK SENSOR

[ ] AUX = AUXILIARY RELAT (FOR LOOP PUMP, ETIC)

( ) CHP - COUPRESSOR MONITOR RELAY

[ ] CMR = COMPRESSOR MONITOR RELAY [ ] CS2 = CONDENSATE SENSOR (IN ECONOMIZER DRA

[ ] DPS - DIFFERENTIAL PRESSURE SWITCH

[ ] DS - DISCONNECT SWITCH

EMS - ENERGY MGMT SYSTEM RELAY FR - FUSE BLOCK (FOR 65KA SCCR RATING)

HGB - HOSE BLOCK (FOR OSRA SLAIR RATING) HGR - HOT GAS REHEAT RELAY

[ ] HGV - HOT GAS VALVE SOLENOID

[ ] HRP - HEAT RECOVERY PACKAGE: URRM - HEAT RECOVERY PLUMB MOTOR

HWL - HOT WATER LIMIT (120F)

LGL - LOW GAS TEMPERATURE LIMIT (100F)

SWT - ON/OFF SWITCH AND OVERLOAD [ ] HSL - HIGH TEMPERATURE SUCTION LIMIT

(WITH HOT GAS BYPASS ONLY)

[ ] LWV - LEAVING WATER VALVE

[ ] MBV - MOTORIZED BALL VALVE

[ ] TB2 = MAIN TERMINAL BLOCK (460V UNITS ONLY) [ ] TB3 = TERMINAL BLOCK DISCONNECT SWITCH

NOTES: (460V UNITS ONLY)

  1. SEE UNIT NAME PLATE FOR ELECTRICAL RATING.

  2. ALL FIELD WRING MUST BE IN ACCORDANCE WITH

N.E.C.-N.F.P.A. #70, COPPER CONDUCTORS ONLY - CON 3. 208/230V. UNITS ARE FACTORY WIRED FOR 230V OF

REMOVE PRIMARY LEAD FROM 240 TERMINAL AND C

  1. FOR ALTERNATE EMS COIL VOLTAGES CONSULT FACT
  2. UBM-L INCLUDES BUILT IN: 270-300 SECOND RAND

S. SPM-T INCLUDES BOLET IN: 270-300 SECOND RAND 300 SECOND DELAY ON

120 SECOND LOW PRESSURE BYPASS 6. "TEST" DID SWITCH REDUCES DELAYS TO 10 SEC WHEN SET TO YES, MUST BE SET TO "NO" FOR NORMAL OPERATION

  1. TEST DIP SWITCH REDUCES DEETS TO 10 SEC WHEN SET TO YES. MUST BE SET TO NO FOR NORMAL OPERATION.
  2. "FREEZE SENSOR" ON CONDENSER WILL BE SET TO 25'E OPERATION BY DEFAULT. IF 15'E OPERATION IS REQUIRED. MOVE DIP

SWITCH SLIDER TO THE 15'F POSITION

  1. "ALARM OUTPUT" DIP SWITCH MUST BE SET TO "PULSE" IF BLINKING T-STAT SERVICE LIGHT IS DESIRED OR IF DDC CONNECTION IS AVAILABLE CONT FOR NON-BLINKING THERMOSTAT CONNECTION

  2. DEFAULT SETTINGS FOR UPM BOARD FROM FACTORY SHOWN. ALSO SEE INSTALLATION MANUAL.

  3. ALARM OUTPUT IS NORMALLY OPEN (NO) DRY CONTACT. IF 24 VAC IS NEEDED, CONNECT R FROM TERMINAL BLOCK TO ALR-COM

TERMINAL, 24VAC WILL BE SENSED ON THE ALR-OUT WHEN THE UNIT IS IN ALARM CONDITION. OUTPUT WILL BE PULSED IF PULSE IS SELECTED

  1. REVERSING VALVE NOT PRESENT ON UNITS WITH STRAIGHT COOL.

  2. TERMINAL BLOCK TB3 LOCATED IN SIDE DISCONNECT SWITCH BOX.

  3. FON MOTOR IS WIRED BETWEEN LINE AND NEUTRAL FOR 380,460VAC UNITS FOR 208/270VAC UNITS FON MOTOR IS WIRED

  4. EON MOTOR IS WIRED BETWEEN LINE AND NEUTRAL FOR 380-400VAC UNITS. FOR 208/250VAC UNITS EON MOTOR IS WIRED BETWEEN LINES.

  5. HOT GAS REHEAT RELAY WILL ONLY BE USED WHEN HOT GAS REHEAT AND ECONOMIZER OPTIONS ARE SELECTED.

  6. UNIT WILL HAVE OPTIONAL DISCONNECT SWITCH OR FUSE PROTECTION, UNIT WILL NOT HAVE BOTH.

  7. SCCR OPTION IS NOT AVAILABLE ON 460 UNITS

Fig. 32 — Three Phase, Constant Airflow ECM Motor, Option Card (WSE, HGRH, Boilerless Heat)

CARRIER Aquazone 50WT - Fig. 30 — Single Phase, Constant Airflow ECM Motor, TruVu™ DDC - 3

flowchart
graph TD
    A["Common"] --> B["C"]
    B --> C["OR"]
    C --> D["RV"]
    D --> E["SPS"]
    E --> F["Grid"]
    F --> G["O"]
    G --> H["Y"]
    H --> I["Y2"]
    I --> J["W1"]
    J --> K["H"]
    K --> L["EC"]
    L --> M["R"]
    M --> N["UO-1"]
    N --> O["AC-2"]
    P["BL"] --> Q["BL"]
    Q --> R["BL"]
    R --> S["BL"]
    S --> T["BL"]
    T --> U["BL"]
    U --> V["BL"]
    V --> W["LWR"]
    W --> X["LWV"]
    X --> Y["OR"]
    Y --> Z["OR"]
    Z --> AA["OK"]
    AA --> AB["MDY"]
    AB --> AC["RD"]
    AC --> AD["WT"]
    AD --> AE["PINK"]
    AE --> AF["MRV"]
    AF --> AG["RD"]
    AG --> AH["BY"]
    AH --> AI["BL"]
    AI --> AJ["BL"]
    AJ --> AK["BL"]
    AK --> AL["BL"]
    AL --> AM["BL"]
    AM --> AN["BL"]
    AN --> AO["BL"]
    AO --> AP["BL"]
    AP --> AQ["BL"]
    AQ --> AR["BL"]
    AR --> AS["BL"]
    AS --> AT["BL"]
    AT --> AU["BL"]
    AU --> AV["BL"]
    AV --> AW["BL"]
    AW --> AX["BL"]
    AX --> AY["BL"]
    AY --> AZ["BL"]
    AZ --> BA["BL"]
    BA --> BB["BL"]
    BB --> BC["BL"]
    BC --> BD["BL"]
    BD --> BE["BL"]
    BE --> BF["BL"]
    BF --> BG["BL"]
    BG --> BH["BL"]
    BH --> BI["BL"]
    BI --> BJ["BL"]
    BJ --> BK["BL"]
    BK --> BL
    BL --> BM["BL"]
    BM --> BN["BL"]
    BN --> BO["BL"]
    BO --> BP["BL"]
    BP --> BQ["BL"]
    BQ --> BR["BL"]
    BR --> BS["BL"]
    BS --> BT["BL"]
    BT --> BU["BL"]
    BU --> BV["BL"]
    BV --> BW["BL"]
    BW --> BX["BL"]
    BX --> BY["BL"]
    BY --> BZ["BL"]
    BZ --> CA["BL"]
    CA --> CB["BL"]
    CB --> CC["BL"]
    CC --> CD["BL"]
    CD --> CE["BL"]
    CE --> CF["BL"]
    CF --> CG["BL"]
    CG --> CH["BL"]

UNIT GROUND LUG L1 L2 L3 N D5 FB TB3 TB2 480V CONNECTION WT BK ON/YL BM WT BK ON/YL BM CC RK YL RD COMP RW TWH 70° SWT HRPM TRANSFORMER BK (COM) RD

COLOR CHART LEGEND
ABBREVIATIONCOLOR
BKBLACK
BLBLUE
BNBROWN
GNGREEN
ORORANGE
RDRED
VTVIOLET
WTWHITE
YLYELLOW
GYGREY
UPM STATUS LED - BLINK CODES
1HIGH PRESSURE FAULT
2LOW PRESSURE FAULT
3CONDENSER FREEZE CONDITION
4CONDENSATE OVERFLOW FAULT
5BROWN CUT FAULT
6EVAPORATOR FREEZE CONDITION
7REFRIGERANT LEAKAGE

Fig. 33 — Three Phase, Constant Airflow ECM Motor, TruVu™ DDC

Optional Smart Source Water Valve and/or DCV Dampper To BACnet IP Network USB Service Port Dip Switch to configure UO-1 as an analog (CA ECM or VHD) or binary (PSC & CT ECM) output Power 24V NC Data Grid AOC03 CC ACO3 10/100 Base-TX Service Comm Eth0 Eth1 UO-01 Analog Dry Contact Carrier TruVu I-VuReady End of Net7 Yes No Net . Shield Port S1 Next . Shield Port S2 Gnd Rnet + Rnet + 2V IN-01 Grid IN-02 IN-03 Grid IN-04 24 Vdc 24 Vdc IN-05 Grid IN-06 IN-07 Grid IN-08 DSc TO MODBUS CARD Open for Optional Field Inputs RATS EWTS LWTS SATS 8733837662

Fig. 34 — TruVu™ DDC Controller Wiring Diagram
TERMINATION DETAIL IN-7-B: DRY CONTACT (N/C) DPS Grid IN 7-B TERMINATION DETAIL IN 1-2-3-6: TEMP SENSOR (7/8/25C @ 10k OHM) TEMP SENSOR IN 1-2-3-6 Grid TERMINATION DETAIL Rnet ZS SENSOR GREEN Gnd WHITE Rnet + BLACK Rnet - RED 12V EQUIPMENT TOUCH DEVICE WHITE Gnd BLACK Rnet + 12V FACTORY WIRE ———— FIELD WIRE ———— A EQUIPMENT TOUCH DEVICE OR ZS COMBINATION WALL SENSOR OF TEMPERATURE, HUMIDITY, A READINGS. B OPTIONAL MODULATING REHEAT 3 TWO STAGE/SPEED UNITS: BO-4 AVAILABLE FOR OUTPUT SIGNAL SINGLE STAGE/SPEED UNITS: B- AVAILABLE FOR WSE 4 H SIGNAL IS USED ON REHEAT A 5 TWO STAGE/SPEED UNITS: BO-6 FOR WSE OUTPUT SIGNAL SINGLE STAGE/SPEED UNITS: B- AVAILABLE FOR FAN ON G2 OUT 6 IN-07 UTILIZED FOR OPTIONAL R INSTALLED DIFFERENTIAL PRES SWITCH WHEN EQUIPPED

FACTORY INSTALLED COMPONENTS (OUTPUTS) UO-1 - UNIVERSAL OUTPUT 1: [ ] G1 - FAN ON (PSC & CT ECM) [ ] ECM - FAN MODULATION (CA ECM PWM) [ ] VFD - FAN MODULATION (VFD 0-10VDC) AO-2 - ANALOG OUTPUT 2: [ ] MRV - MODULATING REHEAT VALVE BO-2 - BINARY OUTPUT 2: [ ] Y1 - COMPRESSOR BO-3 - BINARY OUTPUT 3: [ ] O - REVERSING VALVE BO-4 - BINARY OUTPUT 4: [ ] Y2 - COMPRESSOR (TWO STAGE/SPEED) [ ] WSE - WATER-SIDE ECONOMIZER VALVE (SINGLE STAGE) [ ] W1 - AUX HEAT 1ST STAGE (SINGLE STAGE) BO-5 - BINARY OUTPUT 5: [ ] H - DEHUMIDIFICATION (HGRH) [ ] W1 - AUX HEAT 1ST STAGE (SINGLE OR TWO STAGE/SPEED) BO-6 - BINARY OUTPUT 6: [ ] G2 - FAN ON (CT ECM) [ ] WSE - WATER-SIDE ECONOMIZER VALVE (TWO STAGE) [ ] W2 - AUX HEAT 2ND STAGE (TWO STAGE/SPEED) BO-7 - BINARY OUTPUT 7: [ ] G3 - FAN ON (CT ECM) [ ] VFD - VFD ENABLE/DISABLE STANDARD FACTORY INSTALLED COMPONENTS (INPUTS): IN-2 - UNIVERSAL INPUT 2: [ ] LWTS - LEAVING WATER TEMPERATURE SENSOR IN-3 - UNIVERSAL INPUT 3: [ ] EWTS - ENTERING WATER TEMPERATURE SENSOR STANDARD FACTORY PROVIDED COMPONENTS (INPUTS): IN-1 - UNIVERSAL INPUT 1: [ ] SATS - SUPPLY AIR TEMPERATURE SENSOR IN-6 - UNIVERSAL INPUT 6: [ ] RATS - RETURN AIR TEMPRETURE SENSOR OPTIONAL FACTORY INSTALLED COMPONENTS (INPUTS): IN-7 - UNIVERSAL INPUT 7: [ ] DPS - DIFFERENTIAL PRESSURE SWITCH OPTIONAL FIELD INSTALLED COMPONENTS (INPUTS): IN-6 - UNIVERSAL INPUT 8: [ ] SPT - SPACE TEMPRETURE SENSOR IN-7 OR 8 - UNIVERSAL INPUT 7 OR 8: [ ] EMSD - EMERGENCY SHUTDOWN [ ] OCC - REMOTE OCCUPANCY [ ] SCO - SECONDARY CONDENSATE OVERFLOW [ ] FS - FLOW SWITCH [ ] FM - WATER FLOW METER

PRE-START-UP

System Checkout

After completing the installation, and before energizing the unit, the following system checks should be made prior to initial start-up:

  1. Verify the supply voltage to the heat pump is in accordance with the nameplate ratings.
  2. Verify the control transformer is set to the correct voltage for 208/230-v units (factory setting is 230-v).
  3. Make sure that all electrical connections are tight and secure.
  4. Check the electrical fusing/breaker and wiring for the correct size.
  5. Verify the low voltage wiring between the thermostat or DDC controls and the unit is correct.

  6. Verify the water piping is complete and correct.

  7. Verify there are no leaks in the external piping or in the internal unit piping. Correct as necessary.

  8. Verify the isolation or flow control valves are open and that any automatic flow control valve or balancing valve are set to the correct setting.

  9. Check the water flow is correct and adjust if necessary.

  10. Check the blower for free rotation, and that it is secured to the shaft.

  11. Verify the foam blower shipping support has been removed.

  12. Vertical Units Only - Verify vibration isolation has been provided and that the unit has been installed on a solid structure.

  13. Horizontal Units Only - Verify the hanging brackets have been installed and that the unit is secured to an adequate support structure.

  14. Verify the unit has proper service clearance. Be certain that all access panels are secured in place.

  15. Verify ductwork has been properly fastened to supply and return duct collars.

  16. Verify the ductwork is free from obstruction and that all dampers or registers are open.

  17. Make sure return air filters are positioned correctly in the filter rack if removed during installation.

  18. Verify the unit is not in TEST mode.

  19. Verify all control components have been properly configured and that all control components have been wired.
  20. For units with TruVu DDC controller, verify a space temperature input is provided via ZS sensor, or non-communication zone sensor (10K thermistor), or over the network and that a commissioning interface is available.

CLEAN AIR COIL

To obtain maximum performance, clean the air coil before starting the unit. A ten percent solution of dishwasher detergent and water is recommended for both sides of the coil. Rinse thoroughly with water.

CONSTANT AIRFLOW (ECM) MOTOR

The 50WT units in 208/230-v, 265-v, or 460-v are available with a constant airflow ECM blower motor. These motors dynamically adjust their power output to precisely match the desired airflow on a pre-programmed fan curve. See Tables 13-14 for blower performance by speed setting, and for the factory default motor setting. These motors include the following features:

  1. Three Speed Settings: Units are factory set to "NORM" but can be field adjusted to "+" to increase CFM by 15% or to "-" to reduce CFM by 15%. See the constant airflow ECM motor blower performance table for complete details on available CFM for each unit size (refer to the Wire Control Connections section of this manual).
  2. Low CFM Ventilation: Units circulate air at 70% of full airflow rate when there is a call for fan only.
  3. Passive Dehumidification: Reduces airflow during a cooling call when dehumidification is also required. This reduces the sensible heat ratio of the cooling coil and extends cooling run time to dehumidify more effectively (refer to the Wire Control Connections section of this manual).
  4. Test Mode: Operates the motor at a 70% torque setting. This setting can be used to diagnose programming problems in the motor itself (refer to the Wire Control Connections section of this manual).
  5. CFM Indicator Light: indicator light blinks for each 100 CFM of air delivered.
    NOTE: This blink code is approximate and should not replace test and balance.

Table 13 — 50WT Vertical Units — Constant Airflow Motor Performance ^a,b,c

UNIT SIZE FAN SPEEDDEFAULT FACTORY MOTOR SETTINGAIRFLOW (cfm) AT EXTERNAL STATIC PRESSURE (in. wg)
0.10 020 0.300.40 0.500.60 0.700.80 0.901.001.10 1.20
024 Full LoadA - 680680 680 680680 680680 680— — — —
A Norm (Full)X 800 800 800 800 800 800 800 800 — —— —
A + 920920 920 920920 920920 920— — — —
024 Part LoadA - 553553 553 553553 553553 553— — — —
A Norm (Part)X 650 650 650 650 650 650 650 650 — —— —
A + 748748 748 748748 748748 748— — — —
036 Full LoadA - 1,1051,105 1,1051,105 1105 1,1051,105 1,1051,105 1,105— —
A Norm (Full)X 1,3001,300 1300 1,3001,300 1,3001,300 1,3001,300 1,3001,300 1,300
A + 1,4951,495 1,4951,495 1495 1,4951,495 1,4951,495 1,495— —
036 Part LoadA - 829829 829 829829 829829 829829 829— —
A Norm (Part)X 975 975 975 975 975 975 975 975 975 975 — —
A + 1,1211,121 1,1211,121 1121 1,1211,121 1,1211,121 1,121— —
048 Full LoadA - 1,4451,445 1,4451,445 1445 1,4451,445 1,4451,445 1,445— —
A Norm (Full)X 1,7001,700 1700 1,7001,700 1,7001,700 1,7001,700 1,7001,700 1,700
A + 1,9551,955 1,9551,955 1955 1,9551,955 1,9551,955 1,955— —
048 Part LoadA - 1,1051,105 1,1051,105 1105 1,1051,105 1,1051,105 1,105— —
A Norm (Part)X 1,3001,300 1300 1,3001,300 1,3001,300 1,3001,300 1,3001,300 1,300
A + 1,4951,496 1,4961,495 1495 1,4951,495 1,4951,495 1,495— —
060 Full LoadA - 1,7001,700 1,7001,700 1700 1,7001,700 1,7001,700 1,7001,700 1,7001,700 1,700
A Norm (Full)X 2,0002,000 2000 2,0002,000 2,0002,000 2,0002,000 2,0002,000 2,0002,000
A + 2,3002,300 2,3002,300 2300 2,3002,300 2,3002,300 2,3002,300 2,3002,300 2,300
060 Part LoadA - 1,3601,360 1,3601,360 1360 1,3601,360 1,3601,360 1,3601,360 1,3601,360 1,360
A Norm (Part)X 1,6001,600 1600 1,6001,600 1,6001,600 1,6001,600 1,6001,600 1,6001,600
A + 1,8401,840 1,8401,840 1840 1,8401,840 1,8401,840 1,8401,840 1,8401,840 1,840
070 Full LoadA - 1,8281,828 1,8281,828 1828 1,8281,828 1,8281,828 1,8281,828 1,8281,828 1,828
A Norm (Full)X 2,1502,150 2150 2,1502,150 2,1502,150 2,1502,150 2,1502,150 2,1502,150
A +2,4732,4732,4732,4732,4732,4732,4732,4732,4732,4732,4732,473
070 Part LoadA - 1,5301,530 1,5301,530 1530 1,5301,530 1,5301,530 1,5301,530 1,5301,530 1,530
A Norm (Part)X 1,8001,800 1800 1,8001,800 1,8001,800 1,8001,800 1,8001,800 1,8001,800
A + 2,0702,070 2,0702,070 2070 2,0702,070 2,0702,070 2,0702,070 2,0702,070 2,070

NOTE(S):
a. During fan only operation air flow is 70% of tabulated value.
b. When passive dehumidification mode is enabled, air flow is 85% of tabulated value.
c. Cfm airflow is based on wet coil and 1 in. disposable MERV 5 filter.

Table 14 — 50WT Horizontal Units — Constant Airflow Motor Performance ^a,b,c

UNIT SIZEFAN SPEEDDEFAULT FACTORY MOTOR SETTINGAIRFLOW (cfm) AT EXTERNAL STATIC PRESSURE (in. wg)
0.10 020 0.300.40 0.500.60 0.700.80 0.901.00 1.101.20
024 Full LoadA - 808808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 808 80
A Norm (Full)X 950 950 950 950 950 950 950 950 950 950 950 950 950 950 950 950 950 950 950 950 950 950 950 950 950 953 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 11,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,093 1,080 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 8—— — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — ——— — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — ———————————————————
024 Part LoadA - 680680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 68080 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 920 920 920 920 920 920 920 920 920 920 920 920 920 920 920 920 920 920 920 920 920 920 920 920 920 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 974 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 973 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 972 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 971 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 970 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 965 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 960 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 945 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 940 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 965 970 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 975 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 945 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 935 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 925 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 915 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 955 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 970 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 962 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 960 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 972 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 973 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 963 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 965 963 965 965 963 965 965 963 965 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 942 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 942 963 963 963 963 962 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 963 942 963 963 963 963 963 962 963 963 963 963 963 963 963 963 963 963 963 942 963 963 963 963 963 963 963 963 963 963 963 942 963 963 963 963 963 963 963 963 963 963 963 963 942 963 963 963 963 963 963 963 963 942 963 963 963 963 963 963 963 963 942 963 963 963 963 963 963 962 963 963 963 963 963 963 963 963 963 942 963 963 963 963 963 963 963 963 942 963 963 963 963 963 962 963 963 963 963 963 963 963 963 942 963 963 963 963 963 963 942 963 963 963 963 942 963 963 942 963 942 942 942 942 942 942 942 942

NOTE(S):
a. During fan only operation air flow is 70% of tabulated value.
b. When passive dehumidification mode is enabled, air flow is 85% of tabulated value.
c. Cfm airflow is based on wet coil and 1 in. disposable MERV 5 filter.

System Flushing and Filling

Once the piping is complete, units require final purging and loop charging. A flush cart pump of at least 1.5 hp is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop. Flush the loop in both directions with a high volume of water at a high velocity. Follow the steps below to properly flush the loop:

  1. Verify power is off.
  2. Fill loop with water from hose through flush cart before using flush cart pump to ensure an even fill. Do not allow the water level in the flush cart tank to drop below the pump inlet line to prevent air from filling the line.

  3. Maintain a fluid level in the tank above the return tee to avoid air entering back into the fluid.

  4. Shutting off the return valve that connects into the flush cart reservoir will allow 50 psig surges to help purge air pockets. This maintains the pump at 50 psig.

  5. To purge, keep the pump at 50 psig until maximum pumping pressure is reached.

  6. Open the return valve to send a pressure surge through the loop to purge any air pockets in the piping system.

  7. A noticeable drop in fluid level will be seen in the flush cart tank. This is the only indication of air in the loop. NOTE: If air is purged from the system while using a 10 in. PVC flush tank, the level drop will only be 1 to 2 in. since liquids are incompressible. If the level drops more than this, flushing should continue since air is still being compressed in the loop. If level is less than 1 to 2 in., reverse the flow.

  8. Repeat this procedure until all air is purged.

  9. Restore power.

Antifreeze may be added before, during or after the flushing process. However, depending on when it is added in the process, it can be wasted. Refer to the Antifreeze section on page 39 for more detail.

Loop static pressure will fluctuate with the seasons. Pressures will be higher in the winter months than during the warmer months.

This fluctuation is normal and should be considered when charging the system initially. Run the unit in either heating or cooling for several minutes to condition the loop to a homogeneous temperature.

When complete, perform a final flush and pressurize the loop to a static pressure of 40 to 50 psig for winter months or 15 to 20 psig for summer months.

After pressurization, be sure to remove the plug from the end of the loop pump motor(s) to allow trapped air to be discharged and to ensure the motor housing has been flooded. Be sure the loop flow center provides adequate flow through the unit by checking pressure drop across the heat exchanger. Compare the results to the data in Fig. 35 and 36.

System Flow

FLOW VERIFICATION

The 50WT WSHP units ordered without a factory-installed water flow switch as standard. It is recommend to provide field-installed water flow switch or order the unit with factory-installed water flow switch to prevent the compressor from operating without loop flow.

IMPORTANT: It is recommended to have a flow switch to prevent the unit from running if water flow is lost.

FLOW REGULATION

Flow regulation can be accomplished by two methods. Most water control valves have a flow adjustment built into the valve. By measuring the pressure drop through the unit heat exchanger, the flow rate can be determined. Adjust the water control valve until the desired flow rate is achieved. Since the pressure constantly varies, two pressure gauges may be needed in some applications. See Fig. 35 and 36 for waterside pressure drop.

An alternate method of flow regulation is to install an automatic flow control valve. These valves feature a removable cartridge that controls the maximum flow through the valve assembly. Verify that the water flow control cartridge matches the application flow requirement.

CARRIER Aquazone 50WT - FLOW REGULATION - 1

line | Flow Rate (gpm) | 024 036 048 060 070 | Dotted Line | Dash-Dot Line | | --------------- | ------------------- | ----------- | ------------- | | 8.0 | 1.0 | 1.0 | 1.0 | | 12.0 | 2.0 | 1.5 | 1.5 | | 16.0 | 3.0 | 2.0 | 2.0 | | 20.0 | 6.0 | 2.5 | 2.5 | | 24.0 | - | 3.5 | 3.5 | | 26.0 | - | 4.0 | 4.0 |

Fig. 35 — Water Pressure Drop Curve for Units without 2-Way Valve

CARRIER Aquazone 50WT - FLOW REGULATION - 2
Fig. 36 — Water Pressure Drop Curve for Units with 2-Way Valve

ANTIFREEZE

In areas where leaving water temperatures drop below 40^ F or where piping will be routed through areas subject to freezing, anti-freeze is needed.

Alcohols and glycols are commonly used as antifreeze agents. Freeze protection should be maintained to 15^ F below the lowest expected entering loop temperature. For example, if the lowest expected entering loop temperature is 30^ F, the leaving loop temperature would be 22 to 25^ F. Therefore, the freeze protection should be at 15^ F ( 30^ F - 15^ F = 15^ F).

NOTE: All alcohols should be pre-mixed and pumped from a reservoir outside of the building or introduced under water level to prevent fuming.

Calculate the total volume of fluid in the piping system (see Table 15). Use the percentage by volume in Table 16 to determine the amount of antifreeze to use. Antifreeze concentration should be checked from a well-mixed sample using a hydrometer to measure specific gravity.

Table 15 — Approximate Fluid Volume (gal.) per 100 Ft of Pipe ^a

PIPEDIAMETER (in.)VOLUME (gal.)
Copper1.004.1
1.256.4
1.509.2
Rubber Hose13.9
Polyethylene3/4 IPS SDR112.8
1 IPS SDR114.5
1-1/4 IPS SDR118.0
1/2 IPS SDR1110.9
2 IPS SDR1118.0
1-1/4 IPS SCH408.3
1-1/2 IPS SCH4010.9
2 IPS SCH 4017.0

NOTE(S):
a. Volume of heat exchanger is approximately 1.0 gallon.

LEGEND

IPS — Internal Pipe Size

SCH — Schedule

SDR — Standard Dimensional Ratio

Table 16 — Antifreeze Percentages by Volume

ANTIFREEZEMINIMUM TEMPERATURE FOR FREEZE PROTECTION (°F)
10152025
Methanol (%)25211610
100% USP Food Grade Propylene Glycol (%)38302215
Ethanol (%)29252014

FREEZE PROTECTION SELECTION

The 25°F FP1 factory setting (water) should be used to avoid freeze damage to the unit.

Once antifreeze is selected, refer to the Step 9 — “Configure Unit Control Components” on page 21 of this manual for FREEZE Protection settings on the UPM board.

START-UP

Use the procedure outlined below to initiate proper unit start-up.

Operating Limits

ENVIRONMENT

This equipment is designed for indoor installation only. Extreme variations in temperature, humidity and corrosive water or air will adversely affect the unit performance, reliability and service life.

NOTE: Two factors determine the operating limits of a unit: entering-air temperature and water temperature. Whenever any of these factors are at a minimum or maximum level, the other factor must be at a normal level to ensure proper unit operation. See Tables 18-22.

POWER SUPPLY

A voltage variation of ± 10% of nameplate utilization voltage is acceptable.

UNIT STARTING CONDITIONS

Depending on the model, units should start and operate with entering water temperature temperatures between 20 and 110°F and entering air temperatures between 45 and 95°F. Water flow rates should be between 1.5 and 3.0 gpm/nominal cooling ton.

NOTE: These operating limits are not normal or continuous operating conditions. Assume that such a start-up is for the purpose of bringing the building space up to occupancy temperature. See Table 17 for operating limits.

Table 17 — Operating Limits

FLUID TYPELIMITCOOLINGHEATING
AirMinimum Ambient (°F)5040
Maximum Ambient (°F)10085
Rated Ambient (°F)8068
Minimum Entering (°F db/wb)65/5745
Maximum Entering (°F db/wb)95/8580
Rated Entering (°F)80/6768/57
LiquidMinimum Entering (°F)a4520
Max Entering (°F)11080
Typical Entering Range (F)Water Loop
Ground Loop50-8025-50
Ground Water50-7040-60
Rated Entering (F)Water Loop8668
Ground Loop7732
Ground Water5950
Anti-Freeze Requirement (LWT / EWT °F)<40 / <50
Maximum operating water pressure (PSI/kPa)400 psi/2,758 kPa(Standard unit)300 psi/2,068 kPa (with water valve option)
Minimum operating Flow Rate (GPM/Ton)1.5

NOTE(S):
a. Units with waterside economizer options can operate with EWT < 45°F.
LEGEND
DB — Dry Bulb
EWT — Entering Water Temperature
LWT — Leaving Water Temperature
WB — Wet Bulb

Start-Up Procedure

WARNING

When the disconnect switch is closed, high voltage is present in some areas of the electrical panel. Exercise caution when working with the energized equipment. Failure to heed this warning could lead to personal injury.

  1. Restore power to system.
  2. Turn thermostat blower position to ON or use the DDC interface to enable the unit blower. The blower should start.
  3. Balance airflow at diffusers/dampers.
  4. Adjust all water valves to the full open position.
  5. Use the thermostat or DDC control to enable the compressor by placing the unit in cooling mode.
  6. Verify compressor operation. If scroll compressor, verify compressor rotation direction.

SCROLL COMPRESSOR ROTATION

It is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction:

  1. Connect service gauges to suction and discharge pressure fittings.
  2. Energize the compressor by using the thermostat or DDC control to put the unit in cooling mode.
  3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge pressure does not rise to normal levels:

  1. Turn off power to the unit. Install disconnect tag.
  2. Reverse any two of the unit power leads.
  3. Reapply power to the unit and verify pressures are correct. The suction and discharge pressure levels should now move to their normal start-up levels.

When the compressor is rotating in the wrong direction, the unit makes more noise and does not provide cooling.

After a few minutes of reverse operation, the scroll compressor internal overload protection will open, thus activating the unit lockout. This requires a manual reset. To reset the lockout, turn the thermostat on and then off or power cycle the unit power feed.

NOTE: There is a 5-minute time delay before the compressor will restart.

COOLING MODE START-UP

  1. Using the thermostat or DDC control, operate the unit in the cooling cycle. Refer to Table 17 for operating limits. Allow the unit to run for a minimum of five minutes and record the operating data.
  2. Check for water leaks and vibration.
  3. Check for cool air delivery at unit grille a few minutes after the unit has begun to operate.
  4. Verify that the compressor is on and that the water flow rate is correct by measuring pressure drop through the heat exchanger using P/T plugs. Check the elevation and cleanliness of the condensate lines; any dripping could be a sign of a blocked line. Be sure the condensate trap includes a water seal.
  5. Check the temperature of both supply and discharge water. Compare to Tables 18-22. If temperature is within range, proceed. If temperature is outside the range, check the cooling refrigerant pressures in Tables 18-22.
  6. Check air temperature drop across the coil when compressor is operating. Air temperature drop should be between 15 and 25°F.
  7. Disable cooling mode and wait a period of 5 minutes to allow system pressures to equalize.

HEATING MODE START-UP

  1. After waiting for a period of 5 minutes after the cooling cycle, use the thermostat or DDC control to operate the unit in the heating cycle. Refer to Table 17 for operating limits. Allow the unit to run for a minimum of five minutes and record the operating data.
  2. Check for water leaks and vibration.
  3. Check for warm air delivery at unit grille a few minutes after the unit has begun to operate.
  4. Verify that the compressor is on and that the water flow rate is correct by measuring pressure drop through the heat exchanger using P/T plugs.
  5. Check the temperature of both supply and discharge water. Compare to Tables 18-22. If temperature is within range, proceed. If temperature is outside the range, check the cooling refrigerant pressures in Tables 18-22.
  6. Check air temperature rise across the coil when compressor is operating. Air temperature rise should be between 20^ F and 30^ F.
  7. Disable heating mode.

Table 18 — 50WT024 Typical Unit Operating Pressures and Temperatures

ENTER FLUID TEMP (°F)WATER FLOW (gpm)COOLING HEATING
Suction Pressure (psig)Discharge Pressure (psig)Water Temp Rise (°F)Air Temp Drop (°F)Suction Pressure (psig)Discharge Pressure (psig)Water Temp Drop (°F)Air Temp Rise (°F)
303607
6677
403 114-131180-198 20-2318-22 72-82251-271 10-111 17-21
6 113-130153-171 9-1219-23 80-90257-277 5-619-23
503 116-133209-227 19-2218-22 85-95262-282 11-112 20-24
6 114-131180-198 9-1218-22 95-105270-290 6-721-25
603 117-134240-258 19-2218-22 99-109274-294 13-114 22-26
6 116-133210-228 9-1218-22 112-122285-305 7-824-28
703 119-136274-292 19-2218-22 115-125 287-30715-16 25-29
6 117-134244-262 9-1218-22 131-141 301-321 8-928-32
803 120-137312-330 19-2217-21 133-143 302-32217-18 28-32
6 119-136281-299 9-1218-22 152-162 319-339 9-1031-35
903 122-139354-372 18-2117-21 152-162 318-33819-20 31-35
6 121-138322-340 9-1217-21 176-186 339-359 11-1235-39
1003 124-141400-418 18-2117-21 —
6 122-139368-386 9-1217-21 —

Table 19 — 50WT036 Typical Unit Operating Pressures and Temperatures

ENTER FLUID TEMP (°F)WATER FLOW (gpm)COOLING HEATING
Suction Pressure (psig)Discharge Pressure (psig)Water Temp Rise (°F)Air Temp Drop (°F)Suction Pressure (psig)Discharge Pressure (psig)Water Temp Drop (°F)Air Temp Rise (°F)
304558
9065
404.5109-125182-20620-2320-2469-79271-29111-1221-25
9.0108-124157-18110-1320-2478-88279-2996-722-26
504.5111-127210-23420-2319-2382-92284-30412-1323-27
9.0109-125 184-208 10-1320-2493-103 295-315 7-8 25-29
604.5112-128242-26620-2319-2396-106299-31914-1526-30
9.0111-127215-2399-1219-23110-120313-3338-929-33
704.5114-130277-30119-2219-23112-122316-33616-1729-33
9.0113-129 249-273 9-12 19-23129-139 334-3549-10 33-37
804.5115-131316-34019-2218-22129-139334-35418-1933-37
9.0114-130288-3129-1219-23150-160356-37610-1137-41
904.5117-133358-38219-2218-22148-158355-37521-2236-40
9.0116-132330-3549-1218-22174-184382-40211-1241-45
1004.5119-135404-42818-2118-22
9.0118-134377-4019-1218-22

Table 20 — 50WT048 Typical Unit Operating Pressures and Temperatures

ENTER FLUID TEMP (°F)WATER FLOW (gpm)COOLING HEATING
Suction Pressure (psig)Discharge Pressure (psig)Water Temp Rise (°F)Air Temp Drop (°F)Suction Pressure (psig)Discharge Pressure (psig)Water Temp Drop (°F)Air Temp Rise (°F)
306507
1257
406 108-124175-195 20-2320-24 61-81251-271 10-1119-23
12 106-122156-176 10-1320-24 69-89259-279 5-621-25
506 110-126202-222 20-2320-24 74-94263-283 11-1222-26
12 108-124179-199 9-1220-24 84-104273-2936-7 24-28
606 111-127232-252 19-2219-23 88-108277-29713-14 25-29
12 110-126209-229 9-1220-24 100-120289-309 7-827-31
706 113-129266-286 19-2219-23 103-123292-312 15-1628-32
12 112-128242-262 9-1219-23 119-139306-326 8-931-35
806 115-131304-324 19-2219-23 121-141308-328 17-1831-35
12 114-130279-299 9-1219-23 140-160326-346 9-1035-39
906 116-132346-366 18-2118-22 139-159326-346 19-2035-39
12 115-131321-341 9-1218-22 163-183348-368 11-1239-43
1006118-134391-41118-2118-22
12117-133366-3869-1218-22

Table 21 — 50WT060 Typical Unit Operating Pressures and Temperatures

ENTER FLUID TEMP (°F)WATER FLOW (gpm)COOLING HEATING
Suction Pressure (psig)Discharge Pressure (psig)Water Temp Rise (°F)Air Temp Drop (°F)Suction Pressure (psig)Discharge Pressure (psig)Water Temp Drop (°F)Air Temp Rise (°F)
307.553-69225-2828-1019-23
15.060-76231-2895-620-25
407.5104-129170-20919-2521-2564-82234-29610-1122-26
15.0103-127149-1859-1221-2572-91242-3055-624-29
507.5105-131195-24118-2420-2475-96245-31112-1325-30
15.0104-129172-2159-1220-2586-108255-3236-726-32
607.5106-133223-27618-2419-2489-112257-32813-1527-33
15.0105-130199-2499-1320-24101-126269-3427-830-36
707.5107-134253-31418-2420-24103-130270-34615-1731-37
15.0106-132229-2869-1320-24119-147286-3649-1034-41
807.5108-136288-35618-2419-23119-148286-36617-2034-41
15.0108-134264-3279-1219-23138-169304-3879-1138-45
907.5110-138326-40217-2319-23137-169301-38719-2237-45
15.0109-136302-3729-1219-23160-194325-41211-1342-50
1007.5111-140368-45117-2218-22
15.0111-138344-4219-1218-22

Table 22 — 50WT070 Typical Unit Operating Pressures and Temperatures

ENTER FLUID TEMP (°F)WATER FLOW (gpm)COOLING HEATING
Suction Pressure (psig)Discharge Pressure (psig)Water Temp Rise (°F)Air Temp Drop (°F)Suction Pressure (psig)Discharge Pressure (psig)Water Temp Drop (°F)Air Temp Rise (°F)
309 — — —— 53-69 230287 8-10 21-25
18 — — —— 60-76 237295 4-5 22-27
409 100-126171-211 18-221-26 64-82241-303 10-111 24-28
18 99-12450-188 8-1321-26 71-90 249-312 5-6 25-30
509 101-128194-242 18-220-25 75-96253-319 11-112 27-32
18 100-126173-218 9-1221-26 85-107263-331 6-729-35
609 103-130221-277 17-220-24 89-112 266-337 13-115 30-36
18 101-128199-251 8-1321-25 100-125279-352 7-833-39
709 104-132252-314 17-220-25 103-130 281-357 14-16 33-39
18 103-130229-288 8-1220-25 118-146298-376 8-936-43
809 105-133286-356 17-220-24 119-148 299-379 16-19 37-44
18 104-132263-329 8-1119-24 138-169319-402 9-1141-48
909 107-136324-402 17-219-23 137-169 317-403 18-21 41-49
18 106-134301-373 8-1119-23 160-194343-430 10-1245-53
1009 108-138366-450 16-219-23 —
18 108-137343-422 8-1119-23 —

OPERATION

Power Up Mode

The unit will not operate until all the inputs, terminals and safety controls are checked for normal operation.

NOTE: The compressor will have a 5-minute anti-short cycle upon power up.

Unit Protection Module (UPM)

All Carrier WSHP units feature an advanced UPM which implements all the critical equipment safeties and allows for continuous safe and reliable operation. Fig. 37 shows the UPM sequence of operations for units safeties. Refer to Step 9 — “Configure Unit Control Components” on page 21 for detailed information about Safeties and Alarms.

Option Card

An optional expansion card is provided on units that are intended to be controlled by a thermostat. The card supplements the primary thermostat control by controlling auxiliary devices that a thermostat is not typically capable of controlling. Refer to Step 9 — “Configure Unit Control Components” on page 21 for information.

Sequence of Operation of Units Without DDC Controller

STANDBY

Y and W terminals are not active in Standby mode; however, the O and G terminals may be active, depending on the application. The compressor will be off.

COOLING

Y and O terminals are active in Cooling mode. After power up, the first call to the compressor will initiate a 270 to 300 second random start delay and a 5-minute anti-short cycle protection time delay. After both delays are complete, the compressor is energized.

NOTE: On all subsequent compressor calls the random start delay is omitted.

HEATING STAGE 1

Terminal Y is active in heating stage 1. After power up, the first call to the compressor will initiate a 270 to 300 second random start delay and a 5-minute anti-short cycle protection time delay. After both delays are complete, the compressor is energized.

NOTE: On all subsequent compressor calls the random start delay is omitted.

HOT GAS REHEAT WITH OPTION CARD (OPTIONAL)

Terminal H is active in dehumidification mode with hot gas reheat. After a call for H, the reversing valve (O), compressor (Y), and fan (G) are also enabled.

NOTE: Any call for cooling (Y), heating (Y or W), or reversing valve (O) will override dehumidification mode (H).

WATERSIDE ECONOMIZER WITH OPTION CARD (OPTIONAL)

Y and O terminals are active in Cooling mode. When the entering water temperature drops below the configured entering water temperature set point specified on the Option Card, the compressor and reversing valve are disabled and the waterside economizer is enabled. The waterside economizer three way control valve will divert water to the economizer coil for free cooling. If a cooling call remains for a period of >10 min the compressor will be enabled to assist the WSE in meeting the cooling demand. When the entering water temperature rises above the configured on the Option card board set point, the waterside economizer is disabled and the compressor and reversing valve are enabled.

AUXILIARY ELECTRIC HEAT (OPTIONAL)

The output provided on the controller shall be able to control single stage of electric heat. The sequence of operation of the electrical heat is an alternative/emergency heat. When the terminal W is energized, it will enable Electric heater and disable compressor (Y).

TWO-POSITION MOTORIZED ISOLATION VALVE (2-WAY SOLENOID VALVE) (OPTIONAL)

The two way water flow control valve is enabled anytime there is a call for cooling (Y), heating (Y), or dehumidification (H) and allows water to flow through the unit. When there is no call for cooling, heating, or dehumidification, the water flow control valve is disabled, stopping flow through the unit.

BOILERLESS HEAT WITH OPTION CARD (OPTIONAL)

When the entering water temperature is below the configured set point on the Option Card (refer to Step 9 — “Configure Unit Control Components” on page 21) and there is a call for heating (Y), the compressor is disabled and the auxiliary heat output is enabled (W). When the entering water temperature is above the configured EWT set point, the auxiliary heat out-put is disabled and the compressor is enabled.

DIFFERENTIAL PRESSURE SWITCH / FLOW SWITCH (OPTIONAL)

The flow switch monitors the pressure difference between two points on the waterside. The unit will be shut down if flow is not met.

REFRIGERANT LEAK DETECTION SYSTEM (OPTIONAL)

The A2L sensor continually samples the air and if the concentration of refrigerant detected is higher than the preset threshold (15% LFL), it sends a signal to the UPM which then switches off the compressor and turns on the blower. The compressor will remain off until saturation level is within acceptable range (12% LFL). The A2L sensor is connected to the UPM, it must always remain connected. If communication is lost, the UPM will enter refrigerant leak hard lockout fault and energize the alarm contact. To test that the communication between the sensor and board is active, the sensor can be disconnected from the UPM, which should simulate a fault. The A2L sensor for the refrigerant leak detection system shall only be replaced with the part specified on the spare parts list.

WARNING

When refrigerant leak detection system installed, unit must be powered except for service.

WARNING

Continuous air circulation required for proper functioning.

COMPRESSOR RELAY (OPTIONAL)

Optional relay providing compressor status via a normally open set of dry contacts.

PUMP/VALVE RELAY (OPTIONAL)

The pump/valve relay is enabled anytime there is a call for cooling (Y), heating (Y), or dehumidification (H) and can be used to enable/disable field installed 2 way solenoid valve or circulator pumps. When there is no call for cooling, heating, or dehumidification, pump/valve relay is disabled.

CARRIER Aquazone 50WT - PUMP/VALVE RELAY (OPTIONAL) - 1

flowchart
graph TD
    A["START"] --> B{V > 18VAC}
    B -->|NO| C["FLAMMABILITY > 15%"]
    B -->|YES| D["A2L SENSOR EXISTS?"]
    D -->|YES| E{CON > 0}
    D -->|NO| F["SENSOR DISCONNECT?"]
    E -->|NO| G["CON > 0"]
    E -->|YES| H{Y1 = ON}
    H -->|YES| I["HPC = CLOSED"]
    H -->|NO| J["LPC = CLOSED"]
    I -->|YES| K["INITIAL POWER UP?"]
    I -->|NO| L["START TIMER"]
    J -->|YES| M["FRZ > TEMP LIMIT"]
    J -->|NO| N["START TIMER"]
    K -->|YES| O["START ANTIs SHORT CYCLE"]
    K -->|NO| P["START RANDOM START UP"]
    L --> Q["START TIMER"]
    M --> R["T > ASC OR RS SEC"]
    N --> R
    O --> R
    P --> R
    Q --> S["CC OUTPUT = OFF"]
    R --> T["CC OUTPUT = ON"]
    U["CLEAR Faults"] --> V{R = 24VAC}
    V -->|NO| W["RESET ON R"]
    V -->|YES| X{RESET ON Y}
    X -->|NO| Y["Clear Faults"]
    X -->|YES| Z{HPC = CLOSED}
    Z -->|YES| AA["LPC = CLOSED"]
    AA -->|NO| AB["START TIMER"]
    AB --> AC{TIME > 120 SEC}
    AC -->|YES| AD["BLINK CODE ON STATUS LED RECORD ALARM START COUNTER (IF APPLICABLE)"]
    AC -->|NO| AE["CONTURER NEEDED?"]
    AE -->|YES| AF["COUNT = 2 OR COUNT = 4"]
    AF -->|YES| AG["BLINK CODE ON STATUS LED"]
    AG --> AH{HARD LOCKOUT}
    AH -->|NO| AI["BLINK CODE ON STATUS LED DISPLAY OUTPUT = PULSE ALR OUTPUT = ON/PULSE"]
    AH -->|YES| AJ["CC OUTPUT = OFF"]
    AI --> AK["CC OUTPUT = ON"]
    AJ --> AK

Fig. 37 — UPM Sequence of Operations

Sequence of Operation for Units with TruVu DDC Controller

Units with TruVu ^TM DDC controller still feature a UPM board for unit operation, so the operation will be similar to the sequence for units without DDC controller. TruVu ^TM does feature advanced functionality, such as automatic fan speed control

and intelligent alarming, which will differ from the units with UPM board only. Below is an overview of the different features for the TruVu™ controls. See Fig. 38 for TruVu™ Control Board overview.

UPM Communication Factory-Installed Modbus Card Accesses RNET (ZS sensors, TruVu ET display) Universal Inputs Factory-Installed: SAT, LWT, EWT, Compressor Status, Fan Status 24 vdc Terminal Optional Factory-Installed: Differential Pressure Flow Switch Universal Inputs Optional Field-Installed: RAT, SPT, Emergency Shutdown, Remote Occupancy, secondary Condensate Overflow Flow Switch End of Net? No Yes Port S1 Net + Net - Shield I/O Bus Gnd Rnet + Rnet - +12V SAT Gnd LWT EWT Gnd COMP 24 Vdc 24 Vdc FAN Gnd RAT/T55 IN-07 Gnd IN-08 DSC Sys Net Prog I/O - Rx S1 - Rx I/O - Rx Airflow Low Comm. Cr.lock Power 24V AC/DC+ Act Net Gnd Data Pwr Network Communication BACnet/IP, BACnet/Ethernet, vlodbus TCP/IP Carrier i-Vu® Ready Heat Pump Controller TV-WSHP683-E2 PN 8733844145 ETH0 Eth1 Service Analog Binary Control Common FAN AO-02 Gnd AO-03 R Y1 O/W1 BO-04 R BO-05 BO-06 BO-07 Universal Output Factory -Installed: Fan On G1 / PWM ECM Fan Modulation / 0-10 VDC VFD Modulation Analog Outputs Optional Factory-Installed Dehumidification (MHGRH). Optional Field-Installed: Auxiliary Heat, Waterside Economizer, Outdoor Air Damper, Dehumidification, Source Water Valve Binary Outputs Factory-Installed: Compressor, Reversing Valve, Auxiliary Heat, Waterside Economizer, FanOn (G2/G3), Dehumidification (on/off) HGRH), Cycle with Fan/Compressor

Fig. 38 — TruVu Control Board

SCHEDULING

Time periods can be configured to schedule the transitions from occupied to unoccupied operation. The time periods control the space temperature to occupied heating and cooling setpoints. The unit operates continuously in the Occupied mode until a time schedule is configured by using either the TruVu Equipment Touch, Field Assistant, the i-Vu® application, or a third-party control system enables/disables the BAS On/Off point. The local time and date for these functions must be set to operate properly.

The occupancy source can be changed to one of the following:

Occupancy Schedules

The controller is occupied 24/7 until you configure a time schedule using either the TruVu Equipment Touch, Field Assistant, the i-Vu® application, or a third party Enables/Disables the BAS On/Off point. You can disable this by going to Configuration > Unit Configuration > Occupancy Schedules, changing the point from Enable to Disable and clicking OK.

NOTE: You must Enable this point in order for the TruVu™ ET Touch, Field Assistant, or the i-Vu® application to assign a time schedule to the controller.

Schedule Schedule

The unit operates according to the schedule configured and stored in the unit. The schedule is accessible via the TruVu ET, the i-Vu® application, or Field Assistant. The daily schedule consists of a start and stop time (standard or 24-hour mode) and 7 days of the week, starting with Monday and ending on Sunday.

CARRIER Aquazone 50WT - Schedule Schedule - 1

CAUTION

Scheduling can only be controlled from one source.

Occupancy Input Contact (Option)

If configured for remote occupancy control (default), the TruVu can use an external dry contact closure to determine the occupancy status of the unit. You must disable the Occupancy Schedules in order to use the occupancy contact input. The unit enters an occupied mode when it senses the abnormal input. After the input returns to its normal state, the unit stays in the occupied mode for the configured OCC Override Delay period (15 minutes default).

BAS (Building Automation System) On/Off

For use with a Building Automation System that supports network scheduling, you must disable the Occupancy Schedules so the BAS system can control the unit through a network communication and the BAS scheduling function.

Global Occupancy Scheduling

The TruVu can read the occupancy status from another unit so that a group of WSHP's can be controlled from a single occupancy schedule. The local Occupancy Schedules must be disabled in order to use the global occupancy input.

BACnet Network Occupancy Input

The TruVu can accept an external BACnet Binary Network Input for occupancy control. This function is only compatible with units used in BACnet systems. You need to configure the System Occupancy BACnet network input point to locate the device and point name where the external occupancy point information resides. You must also disable Occupancy Schedules in order to use this input.

INDOOR FAN

Fan Modes

You can configure the indoor fan to operate in any one of 3 fan modes:

- Auto - intermittent operation during both occupied and unoccupied periods

  • Continuous (default) - intermittent operation during unoccupied periods and continuous during occupied periods
  • Always on - operates the fan continuously during both occupied and unoccupied periods

In the continuous default mode, the fan is turned on when any one of the following is true:

  • It is in occupied mode, which is determined by the occupancy status.
  • There is a demand for cooling or heating in unoccupied mode.
  • There is a call for dehumidification (optional).

Auto Fan Speed Control

The TruVu can control up to 3 fan speeds using the ECM (Electronically Commutated Motor). The motor operates at the lowest speed possible to provide quiet and efficient fan operation with the best latent capability. The motor increases speed if additional cooling or heating is required to reach the desired space temperature setpoint. The control increases the motor's speed as the space temperature rises above the cooling or below the heating setpoint. The amount of space temperature increase above or below the setpoint required to increase the fan speed is configurable in the setpoint. Also, the control increases the fan speed as the Supply Air Temperature approaches the configured minimum or maximum limits.

  • Heating Max SAT Control - When heat is required and active, the control continuously monitors the supply air temperature to verify it does not rise above the configured Maximum Heating SAT Limit (110° default). As the SAT approaches this value, the control increases the fan speed as required to ensure the SAT remains within the limit. This provides the most quiet and efficient operation by running the fan at the lowest speed possible.

- Cooling Min SAT Control - When mechanical cooling is required and active, the control continuously monitors the supply air temperature to verify it does not fall below the configured Minimum Cooling SAT Limit (50° default). As the SAT approaches this value, the control increases the fan speed as required to ensure the SAT will remain within the limit. Fan operates at the lowest speed during dehumidification to maximize latent capacity during cooling.

Fan Delay

When power is reapplied after a power outage, there is a configurable delay of 5 - 600 seconds (default 60) before starting the fan. You must configure the fan delay:

  • The Fan On Delay defines the delay time (0 - 30 seconds, default 10) before the fan begins to operate after heating or cooling is started.
  • The Fan Off Delay defines the delay time (0 - 180 seconds, default 45) the fan continues to operate after heating or cooling is stopped.

NOTE: The fan continues to run as long as the compressors, heating stages, or the dehumidification relays are on. If the SPT failure alarm, ZS Sensor failure alarm, or condensate overflow alarm is active, the fan is shutdown immediately, regardless of occupancy state or demand.

Fan Status

You can configure an optional input as either an occupancy input contact or a fan status input. If configured as fan status, the controller compares the status of the fan to the desired commanded state. When the fan is commanded to run (ON), the fan status is checked and verified to match the commanded state. If the fan status is not on, then a fan status alarm is generated after 1 minute and the equipment's compressor(s) and auxiliary heat is disabled and the optional OA damper closes.

COOLING OPERATION

Space Temperature Control

The TruVu operates 1 or 2 stages of compression to maintain the desired cooling setpoint. The compressor outputs are controlled by the PI (Proportional-integral) cooling loop and cooling stages capacity algorithm. The algorithm calculates the desired number of stages needed to satisfy the space by comparing the control temperature (return air or space) to the appropriate cooling setpoint.

NOTE: The waterside economizer, if applicable, is used for first stage cooling, in addition to the compressor(s). The following conditions must be true for the cooling algorithm to run:

  • Cooling is set to Enable.
  • The Fire/Smoke Input and Shutdown modes are inactive.
  • Heat mode is not active and the compressor time guard(s) have expired.
  • Condensate overflow alarm status is Normal.
  • Fan Status is True (if option is enabled).
  • If occupied, the control temperature is greater than the occupied cooling setpoint.

• Control temperature reading is valid.

- If unoccupied, the control temperature is greater than the unoccupied cooling setpoint.

- If economizer cooling is available and active, and the economizer alone is insufficient to provide enough cooling.

- OAT > Cooling Lockout Temperature if OAT is available.

- Source water pump is on (if source water linkage is active).

- Water Flow Switch Status is True (if option is enabled).

If all of the above conditions are met, the compressors' relays are energized as required. Otherwise, they will be de-energized. If cooling is active and if the SAT approaches the minimum SAT limit, the fan will be indexed to the next higher speed. If this is insufficient, and if the SAT falls further (equal to the minimum SAT limit), the fan will be indexed to the maximum speed. If the SAT still continues to falls 5°F below the minimum SAT limit, all cooling stages will be disabled.

During Cooling, the reversing valve output is held in the cooling position (either B or O type, as configured), even after the compressor is stopped. The valve does not switch position until the heating mode is required.

The configuration screens contain the Min SAT parameter as well as Cooling Lockout based on outdoor air temperature (OAT). Both can be adjusted to meet various specifications.

Passive Dehumidification

When the unit is configured for auto fan speed control the TruVu will use the lowest fan speed setting possible to meet the setpoint and stay within the maximum SAT limits. Using the lowest fan speed possible in cooling operation will provide a method of passive dehumidification allowing for enhanced latent capacity.

Hot Gas Reheat Dehumidification

The TruVu provides occupied and unoccupied dehumidification only on units that are equipped with the reheat option. This function requires an accessory hardwired space relative humidity sensor. When using a relative humidity sensor to control dehumidification during occupied or unoccupied times, the dehumidification setpoints are used accordingly. Also, you may use a ZS Humidity Sensor or a network input point System Space RH in place of the hardwired RH sensor.

When the indoor relative humidity becomes greater than the dehumidification setpoint, a dehumidification demand is acknowledged. Once acknowledged, the dehumidification output is energized, bringing on the supply fan (medium speed), mechanical cooling, and the integral reheat coil. The controls engage cooling mode and the waste heat from the compressor cooling cycle is returned to the reheat coil simultaneously, meaning that the reversing valve causes the compressor to operate in the cooling mode. NOTE: During cooling mode, the unit cools and dehumidifies, and disables the reheat coil. However, once the call for cooling has been satisfied and there is still a call for dehumidification, the unit continues to operate in the reheat mode.

HEATING OPERATION

Space Temperature Control (Reverse Cycle Heating)

The TruVu operates 1 or 2 stages of compression to maintain the desired heating setpoint. The compressor outputs are controlled by the heating PI (Proportional-integral) loop and heating stages capacity algorithm. The algorithm calculates the desired number of stages needed to satisfy the space by comparing the control temperature (return air or space) to the appropriate heating setpoint.

The following conditions must be true for the heating algorithm to run:

  • Heating is set to Enable.
  • The Fire/Smoke Input and Shutdown modes are inactive.
  • Cool mode is not active and the compressor time guard has expired.

- Condensate overflow alarm status is Normal.

- Fan Status is True (if option is enabled).

- If occupied, the control temperature is less than the occupied heating setpoint.

• Control temperature reading is valid.

- If unoccupied, the control temperature is less than the unoccupied heating setpoint.

- OAT > < Heating Lockout Temperature if OAT is available.

- Source Water Pump is on (if Source Water Linkage active).

- Water Flow Switch Status is True (if option is enabled).

If all the above conditions are met, the heating outputs are energized as required, otherwise they are de-energized. If heating is active and the SAT approaches the maximum SAT limit, the fan is indexed to the next higher speed. If this is insufficient, and if the SAT rises further and reaches the Maximum Heating SAT limit, the fan is indexed to the maximum speed. If the SAT still continues to rise 5°F above the maximum limit, all heating stages are disabled.

Space Temperature Control (Reverse Cycle Heating and Auxiliary Heat)

The TruVu can control a 2-position or modulating water or steam valve, connected to a coil on the discharge side of the unit and supplied by a boiler, or a single stage ducted electric heater, in order to maintain the desired heating setpoint. If the compressor capacity is insufficient, or a compressor failure occurs, the auxiliary heat is used. Unless the compressor fails, the auxiliary heat only operates to supplement the heat provided by the compressor, if the space temperature falls more than 1°F below the desired heating setpoint. (This amount is configurable.) The heat is controlled so the SAT does not exceed the Maximum Heating SAT limit.

The same conditions required for Reverse Cycle Heating must be true in order for the Auxiliary Heat algorithm to run.

Auxiliary Modulating Hot Water / Steam Heating

The control can modulate a hot water or steam valve connected to a coil on the discharge side of the unit, and supplied by a boiler in order to maintain the desired heating setpoint, if the compressor capacity is insufficient, or a compressor failure occurs. Unless a compressor fault condition exists, the valve only operates to supplement the heat provided by the compressor if the space temperature falls more than 1^ F below the desired heating setpoint. The valve is controlled so the SAT does not exceed the Maximum Heating SAT limit.

2-Position Hot Water / Steam Heating

The control can operate a 2-position, NO or NC, hot water or steam valve, connected to a coil on the discharge side of the unit and supplied by a boiler, in order to maintain the desired heating setpoint, if the compressor capacity is insufficient or a compressor

failure occurs. Unless a compressor fault condition exists, the valve only opens to supplement the heat provided by the compressor, if the space temperature falls more than 1^ F below the desired heating setpoint. The valve is controlled so the SAT does not exceed the Maximum Heating SAT limit and is subject to a 2-minute minimum OFF-time to prevent excessive valve cycling.

Electric Auxiliary Heat

The control can operate a factory or field-installed single or two stage of electric heat that is installed on the discharge side of the unit, in order to maintain the desired heating setpoint, if the compressor capacity is insufficient or a compressor failure occurs. Unless a compressor fault condition exists, the heat stage only operates to supplement the heat provided by the compressor if the space temperature falls more than 1^ F below the desired heating setpoint. The heat stage is controlled so the SAT does not exceed the Maximum Heating SAT limit and is subject to a 2-minute minimum OFF-time to prevent excessive cycling.

"Boilerless" Control (Auxiliary Heat)

The TruVu can be configured to control the auxiliary heat source for “boilerless” types of systems or system with no means for heat injection into the source water loop. Compressor will be disabled, and the auxiliary heat source will be enabled when the entering water temperature drops below the configurable boilers electric heat setpoint.

WATERSIDE ECONOMIZER

The TruVu can provide modulating, or 2-position waterside economizer operation (for a factory or field-installed economizer coil mounted to the return air side of the unit and connected to the source water loop), in order to provide free cooling or preheating, when water conditions are optimal. Waterside economizer settings can be accessed on Properties > Equipment > Status.

The following conditions must be true for economizer operation:

  • SAT reading is available.
  • EWT reading is available.
  • If occupied, the control temperature is greater than the occupied cooling setpoint or less than the occupied heating setpoint and the source water is suitable.
  • Space temperature reading is valid.
  • If unoccupied, the SPT or ZS is greater than the unoccupied cooling setpoint, or less than the unoccupied heating setpoint, and the source water is suitable.

Modulating Waterside Economizer Control

Modulates a water valve to control source water flowing through a coil on the entering air side of the unit

Cooling

Provides an economizer cooling function by using the source water loop when the entering water loop temperature is at least 5^ F below space temperature. If the water loop conditions are suitable, the valve modulates open to maintain a Supply Air Temperature that meets the load conditions. If the economizer coil capacity alone is insufficient for a period greater than 5 minutes, or if a high humidity condition occurs, then the compressor starts, in order to satisfy the load. If the SAT approaches the Minimum Cooling SAT limit (HOME > CONFIG > UNIT), the economizer valve modulates closed during compressor operation.

Heating

In addition, the control modulates the water valve if the entering source water loop temperature is suitable for heating (at least 5^ F above space temperature) and heat is required. The valve is controlled in a similar manner, except to satisfy the heating requirement. If the coil capacity alone is insufficient to satisfy the space load conditions for more than 5 minutes, then the compressor starts in order to satisfy the load. If the SAT approaches the Maximum Heating SAT limit, the economizer valve modulates closed during compressor operation.

2-position Waterside Economizer Control

2-Position Waterside Economizer Control has the capability to control a NO or NC, 2-position water valve to control source water flow through a coil on the entering air side of the unit.

Cooling

The purpose is to provide a cooling economizer function directly from the source water loop when the entering water loop temperature is at least 5^ F below space temperature. If the optional coil is provided and the water loop conditions are suitable, then the valve opens to provide cooling to the space, when required. If the capacity is insufficient for a period greater than 5 minutes, or if a high humidity condition occurs, the compressor is started in order to satisfy the load. If the SAT reaches the Minimum Cooling SAT limit, the economizer valve closes during compressor operation.

Heating

In addition, the economizer control opens the water valve, if the entering water loop temperature is suitable for heating (at least 5^ F above space temperature) and heat is required. The valve is controlled in a similar manner, except to satisfy the heating requirement. If the coil capacity is insufficient to satisfy the space load for more than 5 minutes, then the compressor is started to satisfy the load. If the SAT reaches the Maximum Heating SAT limit, the economizer valve closes during compressor operation.

Indoor Air Quality and Demand Control Ventilation

If the optional hardwired indoor air quality sensor is installed, ZS CO₂ (IAQ), or the System Space AQ network input point is used, the TruVu maintains indoor air quality with a modulating OA damper, which provides demand controlled ventilation. The control operates the modulating OA damper during occupied periods, monitors the CO₂ level, compares it to the configured setpoints, and adjusts the ventilation rate, as required. The control provides proportional ventilation to meet the requirements of ASHRAE specifications by providing a base ventilation rate and then increasing the rate as the CO₂ level increases. The control proportionally increases ventilation when the CO₂ level rises above the start ventilation setpoint and reaches the full ventilation rate when the CO₂ level is at or above the maximum setpoint.

Configure the minimum damper position to ensure that proper base ventilation is delivered when occupants are not present. Access the IAQ configurations through the configuration screen.

The following conditions must be true in order for this algorithm to run:

  • Damper Control is configured for DCV.
  • The Fire/Smoke Input and Shutdown modes are inactive.
  • Fan status is True (if option is enabled).
  • The unit is in an occupied mode.
  • IAQ sensor reading is greater than the DCV start CTRL setpoint.

The control has the following 4 adjustable setpoints:

  • DCV Start Ctrl Setpoint.
  • DCV Max Ctrl Setpoint.
    • Minimum Damper POS.
    • DCV Max Vent Damper POS.

NOTE: For the damper to maintain proper base ventilation, you must configure the fan as Continuous or Always On.

2-Position OA Damper

Alternatively, the controller can be configured to operate as a ventilation damper in a 2-position ventilation mode to provide the minimum ventilation requirements during occupied periods.

Differential pressure switch / water flow switch

The flow switch monitors the pressure difference between two points on the waterside. An optional input can be configured as condenser water flow status input. If configured, the flow status must be ON for 3 seconds to enable the compressors.

COMPRESSOR STATUS

The TruVu provides a status input to monitor the compressor operation. The status is monitored to determine if the compressor status matches the commanded state. This input is used to determine if a refrigerant safety switch or other safety device has tripped and caused the compressor to stop operating normally. If this occurs, an alarm is generated to indicate the faulted compressor condition.

DEMAND LIMITING

The TruVu can accept 3 levels of demand limit from the BACnet network. In response to a demand limit, the unit decreases its heating setpoint and increases its cooling setpoint to widen the range, in order to immediately lower the electrical demand. You can configure the temperature adjustment for both heating and cooling and for each demand level. You can also set the response to a particular demand level to 0.

REMOTE DISABLE

Fire/Smoke Detector Input

The TruVu can read the status of a normally closed FSD contact input to determine if a fire or smoke detector alarm is present. If the controller determines an alarm condition is present, all heating, cooling, and the fan are disabled. The switch is factory-set to Normally Closed and cannot be changed.

Shutdown Input

The TruVu controller has a shutdown input (software point) which, when set to its Active mode causes the WSHP to safely shutdown in a controlled fashion. Heating and cooling is disabled after any minimum runtime conditions expire and the fan is disabled after the fan-off timer expires. All alarms are reset but any active alarm remains active. After the shutdown input transitions from Active mode to Inactive, the TruVu restarts after the configured power fail restart delay expires.

ALARMS

High Discharge Pressure (UPM Alarm)

The TruVu WSHP monitors the status of a high discharge pressure fault condition via the serial port (S1). The fault condition is determined by the Unit Protection Module (UPM) included on all WSHPs. The UPM monitors a high-pressure switch input and establishes a high-pressure fault when the discharge pressure exceeds 600 PSIG. Upon fault a 5-minute break is initiated (soft lockout) and the compressor is disabled. The unit will automatically restart after this time period. If the fault occurs 2 times (configurable on UPM) within 60 minutes the UPM will put the unit into hard lockout requiring manual reset. Manual reset can be accomplished remotely when the UPM is configured for the reset method "Y" by remotely disabling the unit via the TruVu WSHP.

Low Suction Pressure (UPM Alarm)

The TruVu WSHP monitors the status of a low suction pressure fault condition via the serial port (S1). The fault condition is determined by the Unit Protection Module (UPM) included on all WSHPs. The UPM monitors a low-pressure switch input and establishes a high-pressure fault when the discharge pressure drops below 40 PSIG. Upon fault a 5-minute break is initiated (soft lockout) and the compressor is disabled. The unit will automatically restart after this time period. If the fault occurs 2 times (configurable on UPM) within 60 minutes the UPM will put the unit into hard lockout requiring manual reset. Manual reset can be accomplished remotely when the UPM is configured for the reset method "Y" by remotely disabling the unit via the TruVu WSHP.

Air Coil Freeze Alarm (UPM Alarm)

The TruVu WSHP monitors the status of an air coil freeze fault condition via the serial port (S1). The fault condition is determined by the Unit Protection Module (UPM) included on all WSHPs. The UPM monitors the heating liquid line refrigerant temperature and establishes a high-pressure fault if the temperature drops below 26°F (configurable on UPM) for 30 seconds. Upon fault a 5-minute break is initiated (soft lockout) and the compressor is disabled. The unit will automatically restart after this time period. If the fault occurs 2 times (configurable on UPM) within 60 minutes the UPM will put the unit into hard lockout requiring manual reset. Manual reset can be accomplished remotely when the UPM is configured for the reset method "Y" by remotely disabling the unit via the TruVu WSHP.

Water Coil Freeze Alarm (UPM Alarm)

The TruVu WSHP monitors the status of a water coil freeze fault condition via the serial port (S1). The fault condition is determined by the Unit Protection Module (UPM) included on all WSHPs. The UPM monitors the cooling liquid line refrigerant temperature and establishes a high-pressure fault if the temperature drops below 26°F (configurable on UPM) for 30 seconds. Upon fault a 5-minute break is initiated (soft lockout) and the compressor is disabled. The unit will automatically restart after this time period. If the fault occurs 2 times (configurable on UPM) within 60 minutes the UPM will put the unit into hard lockout requiring manual reset. Manual reset can be accomplished remotely when the UPM is configured for the reset method "Y" by remotely disabling the unit via the TruVu WSHP.

Condensate Overflow Alarm (UPM Alarm)

The TruVu WSHP monitors the status of a condensate overflow fault condition via the serial port (S1). The fault condition is determined by the Unit Protection Module (UPM) included on all WSHPs. The UPM monitors a condensate overflow switch and upon fault puts the unit in a hard lockout condition, disabling the compressor. The hard lockout condition requires manual reset. Manual reset can be accomplished remotely when the UPM is configured for the reset method "Y" by remotely disabling the unit via the TruVu WSHP.

Brownout Alarm (UPM Alarm)

The TruVu WSHP monitors the status of a brownout fault condition via the serial port (S1).

Fire/Smoke Detector Alarm

The control monitors the voltage input to J1-9 to detect if a smoke detector or fire detector NC contact has opened, indicating an alarm condition. The control verifies the presence of 24 vac on this input. If the input opens at any time, an alarm is generated after 3 seconds and the equipment (fan, compressor, aux heat, and damper) immediately shuts down.

Space Temperature Alarms

The control provides the ability to generate an alarm when the space temperature exceeds the alarm setpoint. A separate occupied hysteresis and fixed unoccupied high and low alarm setpoints are provided. The control provides a 5-minute alarm delay during unoccupied periods. During occupied periods, the control uses the occupied temperature setpoint and applies the hysteresis value to determine the alarm setpoints. When occupancy transitions from unoccupied to occupied or the occupied temperature setpoints are changed, causing an alarm condition to occur, the control automatically calculates an alarm delay (equivalent to the configured delay time in minutes/°F, multiplied by the temperature error, +15 minutes). This prevents nuisance alarms when an occupancy change occurs and allows time for the unit to correct an alarming temperature condition.

Source Water Temperature Alarm

The control has 4 configurable alarm limits for source water temperature. The control verifies that the water temperature is within operating range (between high and low limits) for the specific operating mode (heating or cooling) before energizing the compressor. Once the compressor is started, the source water temperature is further monitored to verify that it is within limits to insure sufficient water is flowing through the coil. If the leaving water temperature rises above or falls below the appropriate limits, and lasts for more than 15 seconds, an alarm is generated and the compressor shuts down.

Supply Air Temperature Alarm

The control has 2 configurable alarm limits for supply air temperature. The control verifies that the supply air temperature is within operating range (between high and low limits) when the compressor or auxiliary heat is operating. If the air temperature rises above or falls below the appropriate limits, and this lasts for more than 5 minutes, an alarm is generated.

Fan Status Alarm

The control generates a fan status alarm if the fan status input detects the fan is OFF after any fan speed output has been enabled. A 30-second alarm delay is used to allow the fan to start operation before an alarm condition is detected. The control monitors the fan output and if the fan is operating at any speed, the fan status must detect the fan is operating.

Compressor Status Alarm

The control generates a compressor failure alarm if the compressor status input detects the compressor is OFF after the compressor output has been energized. A 6-minute alarm delay is used to allow the compressor to start (prevents alarms due to timeguard operation) before an alarm condition is detected. The control monitors the compressor output and if the compressor output is energized, the compressor status input must detect the compressor operation.

Filter Status Alarm

The control provides the ability to generate a dirty filter alarm after the number of fan run hours exceeds a configurable filter alarm timer limit. The control monitors the fan output and if the fan is operating at any speed, it accumulates run time. If the fan run time hours exceed the configurable limit, an alarm is generated. To reset the alarm timer after the alarm has been generated, a Reset Filter Alarm input is provided. You can disable the filter alarm by setting the Filter Alarm Timer Delay to 0 (factory default).

Indoor Air Quality Alarm

The control provides the ability to generate a high CO_2 level alarm during occupied periods when the CO_2 sensor value exceeds the adjustable limit. When a transition from unoccupied to occupied occurs, or the occupied alarm limit is changed to a value that causes an alarm condition to occur, the control will automatically calculate an alarm delay (equivalent to the configured delay time in minutes/ppm, times the error that occurred, +15 minutes). This prevents nuisance alarms from occurring when occupancy changes or the setpoint is changed. You can disable the IAQ alarm by setting Occupied High IAQ Alarm Limit to 0.

Relative Humidity Alarm

The control provides the ability to generate an alarm when the space relative humidity exceeds the alarm setpoint. Separate occupied and unoccupied high humidity alarm setpoints are provided. The control provides a 5-minute alarm delay during unoccupied periods. During occupied periods, the controller uses the occupied high RH alarm limit. When an occupancy transition from unoccupied to occupied occurs, or the occupied high alarm limit is lowered, causing an alarm condition to occur, the control automatically calculates an alarm delay (equivalent to the configured delay time in minutes/% RH, times the humidity error condition that occurred, +15 minutes). This prevents nuisance alarms when an occupancy change occurs and allows time for the unit to correct an alarming humidity condition.

Source Water Linkage Failure Alarm (if Source Water Linkage was active)

The control generates a Source Water Linkage failure alarm if Linkage fails after once being active. The Linkage status is monitored and if it fails to be updated from the Loop controller, then a Source Water Linkage alarm is generated. There is a 6-minute alarm delay to prevent false alarms.

NOTE: You can reset this alarm only by re-establishing Linkage and correcting the condition that caused the Linkage failure, or by momentarily setting the Shutdown point to Active.

Airside Linkage Failure Alarm (if Airside Linkage was active)

The control generates an Airside Linkage failure alarm if Linkage fails after once being active. The Linkage status is monitored and if it fails to be updated from the master zone controller, then an Airside Linkage alarm is generated. There is a 6-minute alarm delay to prevent false alarms.

NOTE: You can reset this alarm only by re-establishing Linkage and correcting the condition that caused the Linkage failure, or by momentarily setting the Shutdown point to Active.

OAT Sensor Alarm (if Network OA Temperature was active)

The control generates an OAT Sensor failure alarm if the value of OAT fails to be updated through the network after once being active. The update status is monitored and if it fails to be updated, then an OAT sensor alarm is generated. There is an alarm delay (approximately 1 hour) to prevent false alarms, while minimizing the required update rate for OAT.

NOTE: You can reset this alarm by momentarily setting the Shutdown point to Active.

SPT Sensor Alarm (if SPT sensor was active)

The control generates an SPT sensor failure alarm if the SPT sensor fails to communicate with the control for 5 minutes or greater. The update status is monitored and if it fails to be updated, then an SPT sensor alarm is generated.

ZS Sensor Alarm (if ZS sensor was active)

The control generates a ZS sensor failure alarm if the ZS sensor fails to communicate with the control for 5 minutes or greater. The update status is monitored and if it fails to be updated, then a ZS sensor alarm is generated.

UPM Alarm - Hard lockout status

The control generates Alarm when Hard lockout Alarm is active on UPM board. Configurable 2 or 4 soft lockout alarms on UPM board before unit enters to hard lock out. Soft lockout alarm history is available via controller.

Low Water Flow Alarm

The control monitors differential pressure switch (water flow switch), and generates alarm if water flow is not met.

Air Side Delta T Alarm

The control has 4 configurable alarm limits for Air Side Delta T.

The control verifies that the calculates delta T based on Return and Supply Air temperatures reading and verifies if it operates within configured ranged (between high and low limits) for the specific operating mode (heating or cooling) before energizing the compressor.

Source Water Valve Alarm

The control generates alarm if communication with Act Net device is lost.

Water Side Delta T Alarm

The control has 4 configurable alarm limits for Source water Delta T.

The control verifies that the calculates delta T based on Entering and Leaving water temperatures reading and verifies if it operates within configured ranged (between high and low limits) for the specific operating mode (heating or cooling) before energizing the compressor.

Entering Water Temperature Alarm

The control has 4 configurable alarm limits for Entering Water temperature.

The control verifies that the entering water temperature is within operating range (between high and low limits) for the specific operating mode (heating or cooling) before energizing the compressor. Once the compressor is started, the entering water temperature is further monitored to verify that it is within limits to insure sufficient water is flowing through the coil. If the entering water

temperature rises above or falls below the appropriate limits, and lasts for more than 15 seconds, an alarm is generated and the compressor shuts down.

Return Air Temperature Alarm (if RAT sensor is field provided)

The control has 2 configurable alarm limits for return air temperature. The control verifies that the return air temperature is within operating range (between high and low limits) when unit is operating. If the air temperature rises above or falls below the appropriate limits, and this lasts for more than 5 minutes, an alarm is generated.

SERVICE

Perform the procedures outlined below periodically, as indicated. An annual “checkup” is recommended by a licensed refrigeration mechanic. Recording the performance measurements of volts, amps, and water temperature differences (both heating and cooling) is recommended. This data should be compared to the information on the unit’s data plate and the data taken at the original start-up of the equipment.

Periodic lockouts almost always are caused by air or water flow problems. The lockout (shutdown) of the unit is a normal protective measure in the design of the equipment. If continual lockouts occur call a qualified technician immediately and have them check for water flow problems, water temperature problems, airflow problems or air temperature problems. Use of the pressure and temperature charts for the unit may be required to properly determine the cause.

Jobsite Check

CHECKS TO THE AREA

Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating system the following precautions shall be completed prior to conducting work on the system.

WORK PROCEDURE

Work shall be undertaken under a controlled procedure to minimize the risk of a flammable gas or vapor being present while the work is being performed.

GENERAL WORK AREA

All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided.

CHECKING FOR PRESENCE OF REFRIGERANT

The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with R-454B refrigerant, i.e. non-sparking, adequately sealed or intrinsically safe.

PRESENCE OF FIRE EXTINGUISHER

If any hot work is to be conducted on the refrigerating equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO_2 fire extinguisher adjacent to the charging area.

NO IGNITION SOURCES

No person carrying out work in relation to a refrigerating system which involves exposing any pipe work shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which refrigerant can possibly be released to the possible ignition sources. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no

flammable hazards or ignition risks. "No Smoking" signs shall be displayed.

VENTILATED AREA

Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.

WARNING

To avoid injury and the discharge of refrigerant into the environment, all refrigerant discharged from this unit must be recovered without exception. Technicians must follow industry accepted guidelines and all local, state and federal statutes for the recovery and disposal of refrigerants.

WARNING

To avoid injury and the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must only be serviced by technicians who meet local, state and federal proficiency requirements.

WARNING

To prevent injury or death due to electrical shock or contact with moving parts, lockout/tagout disconnect switch before servicing unit.

Electrical Devices

Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily repaired. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner so all parties are advised.

Initial safety checks shall include:

  • that capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
  • that no live electrical components and wiring are exposed while charging, recovering or purging the system;
    • that there is continuity of earth bonding

Repairs to Sealed Components

Sealed electrical components shall be replaced.

Repair to Intrinsically Safe Components

Intrinsically safe components must be replaced.

Cabling

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or other adverse environmental effects. During the check take into account the effects of aging or continual vibration from sources such as compressors or fans.

Filters

Filter changes or cleanings are required at regular intervals. The time period between filter changes will depend upon type of environment the equipment is used in. In a single family home, that is not under construction, changing or cleaning the filter every 60 days may be sufficient. In other applications such as motels, where daily vacuuming produces a large amount of lint, filter changes may be need to be as frequent as biweekly. See Fig. 2 and 3 for replacement filter sizes. Note that horizontal units

containing two filters are taped together at the factory to facilitate removal. This should be done by end user as new filters are installed.

IMPORTANT: Units should never be operated without a filter.

CAUTION

Equipment should never be used during construction or renovation due to possibility of contaminants entering the air coil of the equipment which permanently affects the performance and may shorten the life of the equipment.

Condensate Drain Pans

The condensate drain should be checked quarterly by cleaning and flushing to ensure proper drainage.

Refrigerant System

Verify air and water flow rates are at proper levels before servicing. To maintain sealed circuitry integrity, do not install service gauges unless unit operation appears abnormal. Check to see that unit is within the superheat and subcooling temperature ranges shown in Tables 18-22. If the unit is not within these ranges, recover and reweigh in refrigerant charge.

REFRIGERATING EQUIPMENT.

Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer's maintenance and service guidelines shall be followed.

The following checks shall be applied to installations using flammable refrigerants:

  • the actual refrigerant charge is in accordance with the room size within which the refrigerant containing parts are installed;
  • the ventilation machinery and outlets are operating adequately and are not obstructed;
  • if an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;
  • signs on the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;
  • refrigerating pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.

DETECTION OF FLAMMABLE REFRIGERANTS

Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

The following leak detection methods are deemed acceptable for all refrigerant systems:

Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable refrigerants, the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL gas (25% maximum) and it is confirmed.

Leak detection fluids are also suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.

NOTE: Examples of leak detection fluids are the bubble method and fluorescent dye method. If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak.

Compressor

IMPORTANT: When a compressor is removed from this unit, system refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, the refrigerant lines of the compressor must be sealed after it is removed.

Conduct annual amperage checks to ensure that amp draw is no more than 10% greater than indicated on the serial plate data.

Fan Motors

All units have lubricated fan motors. Fan motors should never be lubricated unless obvious, dry operation is suspected. Periodic maintenance oiling is NOT recommended as it will result in dirt accumulating in the excess oil and cause eventual motor failure. Conduct annual dry operation check and amperage check to ensure amp draw is no more than 10% greater than indicated on serial plate data and remove any build up on the blower assembly.

Condensate Drain Cleaning

Clean the drain line and unit drain pan at the start of each cooling season. Check flow by pouring water into drain. Be sure trap is filled to maintain an air seal.

Air Coil Cleaning

Remove dirt and debris from evaporator coil as required by condition of the coil. A 10% solution of dishwasher detergent and water is recommended for cleaning both sides of the coil, followed by a thorough water rinse. Clean coil with a stiff brush, vacuum cleaner, or compressed air. Use a fin comb of the correct tooth spacing when straightening mashed or bent coil fins.

Condenser Cleaning

Water-cooled condensers may require cleaning of scale (water deposits) due to improperly maintained closed-loop water systems. Sludge build-up may need to be cleaned in an open water tower system due to induced contaminants.

Local water conditions may cause excessive fouling or pitting of tubes. Condenser tubes should therefore be cleaned at least once a year, or more often if the water is contaminated.

Proper water treatment can minimize tube fouling and pitting. If such conditions are anticipated, water treatment analysis is recommended. Refer to the Carrier System Design Manual, Part 5, for general water conditioning information.

CAUTION

Follow all safety codes. Wear safety glasses and rubber gloves when using inhibited hydrochloric acid solution. Observe and follow acid manufacturer's instructions.

Clean condensers with an inhibited hydrochloric acid solution. The acid can stain hands and clothing, damage concrete, and, without inhibitor, damage steel. Cover surroundings to guard against splashing. Vapors from vent pipe are not harmful, but take care to prevent liquid from being carried over by the gases.

Warm solution acts faster, but cold solution is just as effective if applied for a longer period.

GRAVITY FLOW METHOD

Do not add solution faster than vent can exhaust the generated gases.

When condenser is full, allow solution to remain overnight, then drain condenser and flush with clean water. Follow acid manufacturer's instructions (see Fig. 39).

See Note Pail Funnel 1" Pipe Vent Pipe 5'Approx Condenser 3' to 4' Pail

NOTE: Fill condenser with cleaning solution. Do not add solution more rapidly than vent can exhaust gases caused by chemical action.

Fig. 39 — Gravity Flow Method

FORCED CIRCULATION METHOD

Fully open vent pipe when filling condenser. The vent may be closed when condenser is full and pump is operating. See Fig. 40.

Regulate flow to condenser with a supply line valve. If pump is a non-overloading type, the valve may be fully closed while pump is running.

For average scale deposit, allow solution to remain in condenser overnight. For heavy scale deposit, allow 24 hours. Drain condenser and flush with clean water. Follow acid manufacturer's instructions.

Pump Suction Pump Support Tank Fine Mesh Screen Priming Conn. Gas Vent Globe Va Ives Supply 1" Pipe Condenser Remove Wa ter Regulating Va Iv Return

Fig. 40 — Forced Circulation Method

Removal and Evacuation

When breaking into the refrigerant circuit to make repairs, or for any other purpose, conventional procedures shall be used. However, for flammable refrigerants it is important that best practice be followed, since flammability is a consideration. The following procedure shall be adhered to:

  • safely remove refrigerant following local and national regulations
  • evacuate
    • purge the circuit with inert gas (optional for A2L)
    • evacuate (optional for A2L)

• continuously flush or purge with inert gas when using flame to open circuit; and
- open the circuit.

The refrigerant charge shall be recovered into the correct recovery cylinders if venting is not allowed by local and national codes. For appliances containing flammable refrigerants, the system shall be purged with oxygen-free nitrogen to render the appliance safe for flammable refrigerants. This process might need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant systems.

For appliances containing flammable refrigerants, refrigerant purging shall be achieved by breaking the vacuum in the system with oxygen-free nitrogen and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum (optional for A2L). This process shall be repeated until no refrigerant is within the system (optional for A2L). When the final oxygen-free nitrogen charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.

The outlet for the vacuum pump shall not be close to any potential ignition sources, and ventilation shall be available.

Refrigerant Charging

WARNING

To prevent personal injury, wear safety glasses and gloves when handling refrigerant. Do not overcharge system — this can cause compressor flooding.

NOTE: Do not vent or depressurize unit refrigerant to atmosphere. Remove and recover refrigerant following accepted practices.

CHARGING PROCEDURES

In addition to conventional charging procedures, the following requirements shall be followed.

  • Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
  • Cylinders shall be kept in an appropriate position according to the instructions.
  • Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.
  • Label the system when charging is complete (if not already).
  • Extreme care shall be taken not to overfill the refrigerating system.

Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak-tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.

RECOVERY

When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.

When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labeled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.

The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of the flammable refrigerant. If in doubt, the manufacturer should be consulted. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition.

The recovered refrigerant shall be processed according to local legislation in the correct recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.

If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The compressor body shall not be heated by an open flame or other ignition sources to accelerate this process. When oil is drained from a system, it shall be carried out safely.

Blower Assembly Service and Removal

CAUTION

Before attempting to remove fan motors or motor mounts, place a piece of plywood over evaporator coils to prevent coil damage.

Vertical Configuration Units

For the vertical configuration, the blower assembly is designed to slide out to facilitate access and servicing of the blower/motor assembly. If removal of the blower assembly is required, such as when installation constraints prevent the use of the slide-out feature, follow these steps:

  1. Disconnect the motor power wires from the motor terminals before removing the motor from the unit.
  2. Shut off the main power supply to the unit and apply lock-out/tag-out procedures.
  3. Remove the three screws positioned above the motor. See Fig. 41.
  4. Drop down and slide off the welded pins situated on the opposite side from the motor. See Fig. 42.

Ensure all steps are followed for safe and efficient removal of the blower assembly.

CARRIER Aquazone 50WT - Vertical Configuration Units - 1
Fig. 41 — Evaporator Coil Service on Vertical Units

Weld Pins are Located on the Side Opposite to Motor Screws are Located Above Motor

Fig. 42 — Vertical Units Blower Assembly

Horizontal Configuration Units

For horizontal configurations, if removal of the blower assembly becomes necessary, follow these steps:

  1. Disconnect the motor power wires from the motor terminals before removing the motor from the unit.

  2. Shut off the main power supply to the unit and apply lock-out/tag-out procedures.

  3. Remove the three screws located on the motor side of the blower assembly. See Fig. 43.

  4. Twist and pull blower back from welded pins located on opposite side to the motor, near the evaporator. See Fig. 43.

Ensure all steps are followed for safe and efficient removal of the blower assembly.

Screws are Located on the Motor Side Weld Pins are Located on Side Opposite to Motor

Fig. 43 — Horizontal Units Blower Assembly

Troubleshooting

When troubleshooting problems with a WSHP, consider the following.

UNIT PROTECTION MODULE (UPM)

All Carrier WSHPS are equipped with a 24-v low voltage control circuit. Units are selectable to be provided with no controls for control via a field installed thermostat or third party DDC or to be provided with a factory installed Carrier i-Vu DDC for advanced equipment control and monitoring. Regardless of the selection all units will be equipped with a unit protection module. The UPM board should be one of the first areas to start with troubleshooting an equipment issue. See Fig. 21. Refer to Step 9 — “Configure Unit Control Components” on page 21, UPM Configuration and Alarms.

Thermostatic Expansion Valves

Thermostatic expansion valves (TXV) are used as a means of metering the refrigerant through the evaporator to achieve a preset superheat at the TXV sensing bulb. Correct superheat of the refrigerant is important for the most efficient operation of the unit and for the life of the compressor. Refer to Fig. 44 for refrigerant diagram.

Packaged heat pumps typically use one bi-flow TXV to meter refrigerant in both modes of operation. When diagnosing possible TXV problems it may be helpful to reverse the refrigerant flow to assist with the diagnosis.

Geothermal and water source heat pumps are designed to operate through a wide range of entering-water temperatures that will have a direct effect on the unit refrigerant operating pressures. Therefore, diagnosing TXV problems can be difficult.

TXV FAILURE

The most common failure mode of a TXV is when the valve fails while closed. Typically, a TXV uses spring pressure to close the valve and an opposing pressure, usually from a diaphragm, to open the valve. The amount of pressure exerted by the diaphragm will vary, depending on the pressure inside of the sensing bulb. As the temperature of and pressure within the bulb decreases, the valve will modulate closed and restrict the refrigerant flow through the valve. The result is less refrigerant in the evaporator and an increase in the superheat. As the temperature at the bulb increases the diaphragm pressure will increase, which opens the valve and allows more refrigerant flow and a reduction in the superheat.

If the sensing bulb, connecting capillary, or diaphragm assembly are damaged, pressure is lost and the spring will force the valve to a closed position. Often, the TXV will not close completely so some refrigerant flow will remain, even if there is inadequate flow for the heat pump to operate.

The TXV sensing bulb must be properly located, secured, and insulated as it will attempt to control the temperature of the line to which it is connected. The sensing bulb must be located on a dedicated suction line close to the compressor. On a packaged heat pump, the bulb may be located almost any place on the tube running from the compressor suction inlet to the reversing valve. If the bulb is located on a horizontal section, it should be placed in the 10:00 or 2:00 position for optimal performance.

CAUTION

Use caution when tightening the strap. The strap must be tight enough to hold the bulb securely but caution must be taken not to over-tighten the strap, which could dent, bend, collapse or otherwise damage the bulb.

The bulb must be secured to the pipe using a copper strap. The use of heat transfer paste between the bulb and the pipe will also help ensure optimum performance.

The bulb must also be properly insulated to eliminate any influence on valve operation by the surrounding conditions. Cork tape is the recommended insulation as it can be molded tight to the bulb to prevent air infiltration.

Causes of TXV Failure

The most common causes of TXV failure are:

  1. A cracked, broken, or damaged sensing bulb or capillary can be caused by excessive vibration of the capillary during shipping or unit operation.

If the sensing bulb is damaged or if the capillary is cracked or broken, the valve is considered failed and must be replaced. Replacement of the TXV "power head" or sensing bulb, capillary, diaphragm assembly is possible on some TXVs. The power head assembly screws onto most valves, but not all are intended to be replaceable. If the assembly is not replaceable, replace the entire valve.

  1. Particulate debris within the system can be caused by several sources including contaminated components, tubing, and service tools, or improper techniques used during brazing operations and component replacement.

Problems associated with particulate debris can be compounded by refrigerant systems that use POE (polyester oil). POE oil has solvent-like properties that will clean the interior surfaces of tubing and components. Particulates can be released from interior surfaces and may migrate to the TXV strainer, which can lead to plugging of the strainer.

  1. Corrosive debris within the system may happen after a failure, such as a compressor burn out, if system was not properly cleaned.

  2. Non-condensables may be present in the system. Non-condensables includes any substance other than the refrigerant or oil such as air, nitrogen, or water. Contamination can be the result of improper service techniques, use of contaminated components, and/or improper evacuation of the system.

Symptoms

The symptoms of a failed TXV can be varied and will include one or more of the following:

• Low refrigerant suction pressure.
• High refrigerant superheat.
• High refrigerant subcooling.
• TXV and/or low pressure tubing frosting.
- Equalizer line condensing and at a lower temperature than the suction line or the equalizer line frosting.
- FP1 faults in the heating mode in combination with any of the symptoms listed above.
- FP2 faults in the cooling mode in combination with any of the symptoms listed above. Some symptoms can mimic a failed TXV but may actually be caused by another problem.

Before conducting an analysis for a failed TXV the following must be verified:

  • Confirm that there is proper water flow and water temperature in the heating mode.
  • Confirm that there is proper airflow and temperature in the cooling mode.
  • Ensure coaxial water coil is clean on the inside; this applies to the heating mode and may require a scale check.
  • Refrigerant may be undercharged. To verify, subcooling and superheat calculations may be required.

Diagnostics

Several tests may be required to determine if a TXV has failed. The following tools may be required for testing:

  1. Refrigerant gauge manifold compatible with the refrigerant in the system.
  2. Digital thermometer, preferably insulated, with wire leads that can be connected directly to the tubing.
  3. Refrigerant pressure-temperature chart for the refrigerant used.

To determine that a TXV has failed, verify the following:

  • The suction pressure is low and the valve is non-responsive.
  • The TXV sensing bulb can be removed from the suction line and warmed by holding the bulb in your hand. This action should result in an increase in the suction pressure while the compressor is operating. The sensing bulb can also be chilled by immersion in ice water, which should result in a decrease in the suction pressure while the compressor is operating. No change in the suction pressure would indicate a nonresponsive valve.
  • Simultaneous LOW suction pressure, HIGH refrigerant subcooling and HIGH superheat.
  • LOW suction pressure, LOW subcooling and HIGH superheat may indicate an undercharge of refrigerant. HIGH subcooling and LOW superheat may indicate an overcharge of refrigerant. The suction pressure will usually be normal or high if there is an overcharge of refrigerant.
  • LOW suction pressure and frosting of the valve and/or equalizer line may indicate a failed valve. However, these symptoms may also indicate an undercharge of refrigerant. Calculate the subcooling and superheat to verify a failed valve or refrigerant charge issue.

Repair

CARRIER Aquazone 50WT - Repair - 1

WARNING

Most TXVs are designed for a fixed superheat setting and are therefore considered non-adjustable. Removal of the bottom cap will not provide access for adjustment and can lead to damage to the valve or equipment, unintended venting of refrigerant, personal injury, or possibly death.

CARRIER Aquazone 50WT - WARNING - 1

CAUTION

Always recover the refrigerant from the system with suitable approved tools, recovery equipment, and practices prior to attempting to remove or repair any TXV.

IMPORTANT: Repair of any sealed refrigerant system requires training in the use of refrigeration tools and procedures. Repair should only be attempted by a qualified service technician. A universal refrigerant handling certificate will be required. Local and/or state license or certificate may also be required.

CARRIER Aquazone 50WT - CAUTION - 1

CAUTION

Disconnect power from unit before removing or replacing connectors, or servicing motor. Wait 5 minutes after disconnecting power before opening motor.

Figure 44 illustrates the typical refrigerant diagram for 50WT units.

CARRIER Aquazone 50WT - CAUTION - 1

flowchart
graph LR
    A["Refrigerant to Air HX"] --> B["Fan"]
    B --> C["Filter Drier"]
    C --> D["TXV"]
    D --> E["Compressor"]
    E --> F["Refrigerant to Water HX"]
    F --> G["Equalizer Line"]
    G --> H["HL"]
    H --> I["HT"]
    I --> J["CL"]
    J --> K["HT LT"]
    K --> L["CS"]
    G --> M["SB"]
    M --> N["HPS"]
    N --> O["AP"]
    O --> P["Reversing Valve"]
    P --> Q["LPS"]
    Q --> R["AP"]
    R --> S["Compressor"]
    style A fill:#f9f,stroke:#333
    style B fill:#ccf,stroke:#333
    style C fill:#cfc,stroke:#333
    style D fill:#fcc,stroke:#333
    style E fill:#cff,stroke:#333
    style F fill:#ffc,stroke:#333
    style G fill:#fcf,stroke:#333
    style H fill:#cff,stroke:#333
    style I fill:#cfc,stroke:#333
    style J fill:#cfc,stroke:#333
    style K fill:#cfc,stroke:#333
    style L fill:#cfc,stroke:#333
    style M fill:#cfc,stroke:#333
    style N fill:#cfc,stroke:#333
    style O fill:#cfc,stroke:#333
    style P fill:#cfc,stroke:#333
    style Q fill:#cfc,stroke:#333
    style R fill:#cfc,stroke:#333
    style S fill:#cfc,stroke:#333

LEGEND

AP — Access Port

CL LT — Cooling Liquid Line Temperature / Water Side Freeze 1

HT LT — Heating Liquid Line Temperature / Air Coil Freeze 2

HPS — High Pressure Switch

LPS — Low Pressure Switch

SB — TXV Sensing Bulb

NOTE(S):

  1. Filter Drier only present on units equipped with scroll compressor 2 tons and up.
  2. All Pilot and Equalizer Lines 1/4" OD.

Fig. 44 — Typical Refrigerant Diagram - 50WT Units

See Table 23 for compressor characteristics and Table 24 for additional troubleshooting information.
Table 23 — Compressor Characteristics

50WT MODEL VOLTAGE CODECOLD WINDING RESISTANCE VALUES (+/- 7%)RUN CAPACITOR (μF/V)
Single Phase Three Phase
R-C S-C T1-T2 T2-T3 T3-T1
24208-230/1/60 1.071.65 — — — 30μF/370-v
265/1/60 1.49 1.57 — — — 30μF/370-v
208-230/3/60 — —1.412 —
460/3/60— — 7.6387.6386.041 —
36208-230/1/600.7281.471 — —— 45μF/370-v
265/1/60 0.96 1.39 — — — 45μF/370-v
208-230/3/60 — —1.150 —
460/3/60— — 4.484 —
48208-230/1/600.4361.660 — —— 40μF/440-v
208-230/3/60 — —0.979 —
460/3/60— — 3.907 —
60208-230/1/600.3491.394 — —— 40μF/440-v
208-230/3/60 — —0.5250.6780.678 —
460/3/60— — 0.8643.1653.165 —
70208-230/1/600.3291.398 — —— 55μF/440-v
208-230/3/60 — —0.561 —
460/3/60— — 2.5493.12.549 —

Table 24 — Troubleshooting

FAULT COOLING HEATING CHECK POSSIBLE CAUSE SOLUTION
No Compressor Operation but Fan RunsXIs Fault LED Blinking 1 time?High Pressure Fault - No or Low Water FlowCheck water valves and/or pumps for proper operation. Check for water coil blockage.
High Pressure Fault - High Water TemperatureCheck water temperature - is it in range?
High Pressure Fault - Fouled or Scaled Water CoilCheck for proper flow rate and water temperature, but low waterside temp rise in cooling.
XHigh Pressure Fault - No or Low AirflowCheck fan motor for proper operation.
Check air filter.
Inspect air coil for dirt/debris.
Check ductwork - are dampers closed or blocked?
XIs Fault LED Blinking 2 Times?Low Pressure Fault - No or Low AirflowCheck fan motor for proper operation.
Check air filter.
Inspect air coil for dirt/debris.
Check ductwork - are dampers closed or blocked?
Low Pressure Fault - Low RefrigerantCheck refrigerant pressure with gauge set.
XLow Pressure Fault - No or Low Water FlowCheck water valves and/or pumps for proper operation. Check for water coil blockage.
Low Pressure Fault - Low RefrigerantCheck for proper flow rate and water temperature, but low waterside temp drop in heating.
XIs Fault LED Blinking 3 times?Freeze Fault, Water Coil - No or Low Water FlowCheck water valves and/or pumps for proper operation. Check for water coil blockage.
Freeze Fault - Low Water TemperatureCheck water temperature - is it below 40°F entering? If heat pump is connected to a closed loop with antifreeze check that the "FREEZE 1" resistor on the UPM board has been cut to set the unit to antifreeze mode.
Freeze Fault - Low RefrigerantCheck refrigerant pressure with gauge set.
XIs Fault LED Blinking 4 Times?Condensate Fault - Poor DrainageCheck condensate pan for high water level. Check drain line for blockages, double trapping or inadequate trapping.
Condensate Fault - Blocked Return AirCheck condensate pan for high water level. Check air filter and return air ductwork for blockage. Check that there is adequate space between the return air opening and walls or other obstructions on free return applications.
XXIs Fault LED Blinking 5 Times?Brown Out Fault - Low Supply VoltageCheck primary voltage - ensure it is within the limits listed on the unit data plate.
Brown Out Fault - Overloaded Control CircuitCheck control voltage - if it is below 18 V check accessories connected to the unit and ensure that they do not exceed the VA draw shown on page 21.
Brown Out Fault - Bad Thermostat ConnectionCheck that thermostat wiring is proper gauge and length, that it is not damaged and that all connections at the thermostat and heat pump are secure.
XIs Fault LED Blinking 6 Times?Freeze Fault, Air Coil - No or Low AirflowCheck fan motor for proper operation.
Check air filter.
Inspect air coil for dirt/debris.
Check ductwork - are dampers closed or blocked?
Freeze Fault, Air Coil - Blocked Return AirCheck that there is adequate space between the return air opening and walls or other obstructions on free return applications.
Freeze Fault, Air Coil - Low RefrigerantCheck refrigerant pressure with gauge set.
XXNo fault LED - Contactor not EnergizedThermostat Not Calling for Compressor OperationEnsure that the thermostat is on and calling for "Y".
Bad Thermostat ConnectionCheck "Y" connection from thermostat. Ensure that there is 24 vac between "Y" and "C".
Loose Wire To Contactor CoilCheck wiring - ensure that there is 24 vac across the contactor coil.
Burned Out Contactor CoilTest contactor with 24 vac (between "R" and "C"). Ohm contactor coil - an open circuit indicates a burned coil.
XXNo fault LED - Contactor EnergizedOpen Compressor OverloadCheck for supply voltage at the load side of the contactor. For 3 phase models check phase rotation and voltage at all 3 phases.
Poor Wiring ConnectionsLook for signs of heat on the wiring insulation. Check that all wiring connections are secure and properly torqued.
Burned Out CompressorDoes compressor hum when power is applied? If not check the resistance of the compressor windings using the values shown in the compressor characteristics chart. Note that the compressor must be cool (70°F) when checking the windings.
No Compressor or Fan OperationXXPower LED OnBad Thermostat Connection / Faulty ThermostatCheck thermostat and wiring. Check unit terminal block for 24 vac between "Y" and "C" and "G" and "C".
Power LED OffLow or No Supply PowerEnsure that the supply voltage to the unit is with in the range shown on the unit data plate.
Faulty Control TransformerCheck for 24 vac between "R" and "C" on the unit terminal block. For 75 and 100 VA transformers, check that the transformer circuit breaker has not tripped. Check low voltage circuit for overload conditions or short circuits before replacing the transformer.

Table 24 — Troubleshooting (cont)

FAULTCOOLINGHEATINGCHECKPOSSIBLE CAUSESOLUTION
No Fan Operation (constant airflow motor)XXNo Fan Operation SignalCheck for 24 vac between "G" and "C". Check all wiring connections. Make sure that the thermostat connection plug is securely connected.
Loose WiringCheck all wiring connections at motor and control box. Check that power and control harnesses are securely connected.
Interface Board ProblemsMake sure that the interface board is not damaged and that all DIP switches are in the proper configuration (refer to the blower performance tables).
Faulty MotorCheck supply voltage to the motor. Check that all motor wires are secure. Move the "TEST" DIP switch to "ON" and the other switches to "OFF" on the "ADJUST" switch block on the interface board - the motor should run at 70% torque when "G" is called. With power off spin the motor shaft - noise, resistance or uneven motion can be signs of motor failure.
Unit Not Shifting into CoolingXReversing Valve Solenoid EnergizedFaulty SolenoidCheck that the reversing valve solenoid is receiving 24 vac. If so, check the resistance of the solenoid - an open circuit may indicate a burned out solenoid.
Reversing Valve Solenoid Not EnergizedMiswired / Faulty ThermostatCheck that the reversing valve thermostat wire is connected to the "O" terminal of the thermostat. Check for a contact closure between "O" and "R".
Loose Wire on "O" TerminalCheck that the wires from the thermostat to the unit are securely connected and that the wires from the electrical box to the reversing valve are connected.
Excessively Cold Supply Air Temperature in Cooling or Excessively Hot Supply Air Temperature in HeatingXX Reduced AirflowDirty Filter Replace filter.
Fan Speed Too LowConsult blower performance table and increase fan speed if possible.
Excessive Duct Pressure DropConsult blower performance table and increase fan speed if possible.
Excessively Warm Supply Air Temperature in Cooling and/or Excessively Cool Air In HeatingXXAirflow Too High FanSpeed Setting Too HighConsult blower performance table and reduce fan speed if possible.
High or Low Water TemperatureInlet Water Temperature Out Of RangeCheck unit capacity vs. water temperature.
Air Leakage LeakyDuctwork Inspect ductwork.
Loss of Refrigeration CapacityLow Refrigerant Check refrigerant pressures with gauge set.
High Humidity XAirflow Too HighFan Speed Setting Too HighConsult blower performance table and reduce fan speed if possible.
Loss of Refrigeration CapacityLow Refrigerant Check refrigerant pressures with gauge set.
Short CyclingUnit Oversized Check unit performance against building load calculations.
Poor Thermostat Location Make sure that thermostat is not located by a supply- air duct.
Objectionable Noise LevelsXXAir NoisePoor Ductwork/grille Design Ensure ductwork and grilles are properly sized for unit airflow.
Fan Speed Setting Too HighConsult blower performance table and reduce fan speed if possible.
Structure Bourne NoiseUnit Not Mounted on Full Vibration PadMount unit on a vibration pad.
Unit Not Connected with Flexible Conduit, Water Lines and/or DuctworkInstall unit in accordance with instructions.
Unit Cabinet Touching Wall or Other Building ComponentAdjust unit location to avoid unit touching structure.
XCompressor NoiseHigh Water Temperature or Low Water Flow Rate Elevating Head PressureIncrease water flow rate and/or reduce water temperature if possible.
Scaled or Fouled Water Coil Elevating Heat PressureClean/descale water coil.
XLow Airflow Elevating Head PressureCheck filter.
Increase fan speed.
XXWater HammerFast Closing Valves InstalledChange valves to slow-close type.

50WT START-UP CHECKLIST (REMOVE AND USE FOR JOB FILE.)

NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sections of this Installation, Start-Up, and Service Instructions document.

CUSTOMER: ____ JOB NAME: ____

MODEL NO.: ____ SERIAL NO.: ____ DATE: ____

I.PRE-START-UP

Does the unit voltage correspond with the supply voltage available? (Y/N) ____

Have the power and control wiring connections been made and terminals tight? (Y/N) ____

Have water connections been made and is fluid available at heat exchanger? (Y/N) ____

Has pump been turned on and are isolation valves open? (Y/N) ____

Has condensate connection been made and is a trap installed? (Y/N) ____

Is an air filter installed? (Y/N) ____

II. START-UP

Is fan operating when compressor operates? (Y/N) ____

If 3-phase scroll compressor is present, verify proper rotation per instructions. (Y/N) ____

Is control voltage above 21.6 volts? (Y/N) ____.

If not, check for proper transformer connection.

TEMPERATURES

Fill in the analysis chart attached.

COAXIAL HEAT COOLING CYCLE:

EXCHANGER FLUID IN ____ F FLUID OUT ____ F ____ PSI ____ FLOW

HEATING CYCLE: FLUID IN ____ F FLUID OUT ____ F ____ PSI ____ FLOW

AIR COIL COOLING CYCLE: AIR IN ____ F AIR OUT ____ F

HEATING CYCLE: AIR IN ____ F AIR OUT ____ F

HEATING CYCLE ANALYSIS
CARRIER Aquazone 50WT - TEMPERATURES - 1

flowchart
graph LR
    A["Air Coil"] -->|°F| B["Expansion Valve"]
    B --> C["COAX"]
    C --> D["Suction"]
    C --> E["Compressor"]
    C --> F["Discharge"]
    D --> G["PSI"]
    E --> H["PSI"]
    F --> I["PSI Water Out Water In"]
    I --> J["Look Up Pressure Drop in Waterside Pressure Drop Table to Determine Flow Rate."]
    style A fill:#f9f,stroke:#333
    style B fill:#ccf,stroke:#333
    style C fill:#cfc,stroke:#333
    style D fill:#fcc,stroke:#333
    style E fill:#fcc,stroke:#333
    style F fill:#fcc,stroke:#333
    style G fill:#fff,stroke:#333
    style H fill:#fff,stroke:#333
    style I fill:#fff,stroke:#333
    style J fill:#fff,stroke:#333

COOLING CYCLE ANALYSIS
CARRIER Aquazone 50WT - TEMPERATURES - 2

flowchart
graph LR
    A["Air Coil"] -->|°F| B["Expansion Valve"]
    B --> C["Liquid Line"]
    C --> D["COAX"]
    D --> E["Suction"]
    D --> F["Compressor"]
    D --> G["Discharge"]
    E --> H["PSI"]
    F --> I["PSI"]
    G --> J["PSI"]
    H --> K["Water In"]
    I --> L["Water Out"]
    J --> M["Look Up Pressure Drop in Waterside Pressure Drop Table to Determine Flow Rate."]

HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =

____ FLOW RATE (GPM) x ____ TEMP. DIFF. (DEG. F) x ____ FLUID FACTOR* = ____(Btu/hr)

SUPERHEAT = SUCTION TEMPERATURE - SUCTION SATURATION TEMPERATURE = ____(DEG F)

SUBCOOLING = DISCHARGE SATURATION TEMPERATURE - LIQUID LINE TEMPERATURE = ____(DEG F)

*Use 500 for water, 485 for antifreeze.

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : CARRIER

Model : Aquazone 50WT

Category : Air conditioner