Product TypeIndustrial Modbus Gateway
BrandMoxa
ModelMGate MB3170I-T
Dimensions (without ears)29 x 89.2 x 118.5 mm (1.14 x 3.51 x 4.67 in)
Dimensions (with ears)29 x 89.2 x 124.5 mm (1.14 x 3.51 x 4.9 in)
Power Input12 to 48 VDC
Power Consumption (max)555 mA @ 12-48 VDC
Operating Temperature-40 to 75°C (-40 to 167°F)
Storage Temperature-40 to 85°C (-40 to 185°F)
Operating Humidity5 to 95% RH (non-condensing)
Serial Ports1 RS-232/422/485 DB9 male + 2 terminal block (RS-422/485)
Ethernet Port1 RJ45 10/100 Mbps; optional fiber (100BaseFX)
Protocol ConversionModbus TCP to Modbus ASCII/RTU
Max TCP Connections32 (masters/slaves)
Max Serial Slaves31 (Modbus RTU/ASCII)
MountingDIN-rail or wall mounting
LED IndicatorsPWR1, PWR2, RDY, Ethernet (speed/link), P1/P2 (serial), FX (fiber)
Reset ButtonHold 5 seconds to load factory defaults
Relay Output1 digital relay alarm (NC), 1 A @ 30 VDC
Magnetic Isolation (serial)2 kV (for "I" models)
Hazardous Location CertificationsUL/cUL Class 1 Div 2, ATEX Zone 2, IECEx
Default IP Address192.168.127.254
Default Usernameadmin
Default Passwordmoxa

Frequently Asked Questions - MGate MB3170I-T Moxa

How do I reset the MGate MB3170I-T to factory defaults?
Use a pointed object (e.g., paper clip) to press and hold the Reset button for 5 seconds. Release when the Ready LED stops blinking. This restores factory settings.
What is the default IP address and login credentials?
Default IP: 192.168.127.254. Username: admin. Password: moxa.
Can this gateway be used in hazardous locations?
Yes, the MGate MB3170I-T is certified for ATEX Zone 2, IECEx, and UL/cUL Class 1 Div 2 hazardous locations. It must be installed in an enclosure with at least IP54 protection.
What serial protocols are supported?
The gateway supports Modbus RTU, Modbus ASCII, and Modbus TCP protocols. It converts between Modbus TCP and Modbus serial (RTU/ASCII).
How many Modbus slaves can be connected?
Up to 31 Modbus RTU/ASCII slaves can be connected via the serial port. Up to 32 Modbus TCP masters/slaves can be connected simultaneously.
What is the operating temperature range?
The -T model operates from -40°C to 75°C (-40°F to 167°F). Standard models operate from 0°C to 60°C.
How do I configure the MGate MB3170I-T?
Configuration can be done via a web browser (default IP above) or using MGate Manager or Device Search Utility (DSU) downloaded from Moxa's website.
What power supply is required?
The gateway requires a 12 to 48 VDC power source. Power consumption is 555 mA max. Connect to the terminal block power input (V1+/V1- and V2+/V2- for dual inputs).
What do the LED indicators mean?
PWR1/PWR2 (red): power on. RDY (green): normal operation; (red): booting/error. Ethernet (amber:10M, green:100M). P1/P2 (amber:rx, green:tx). FX (amber): fiber connection.
Is the MGate MB3170I-T repairable?
Moxa devices are designed for reliability. For repairs, contact Moxa technical support or an authorized service center. The device has no user-serviceable parts inside.

User questions about MGate MB3170I-T Moxa

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Industrial gangway in PDF format for free! Find your manual MGate MB3170I-T - Moxa and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. MGate MB3170I-T by Moxa.

USER MANUAL MGate MB3170I-T Moxa

MGate MB3170/MB3270 Series Quick Installation Guide

Version 8.2, January 2021

Technical Support Contact Information www.moxa.com/support

MOXA®

© 2021 Moxa Inc. All rights reserved.

P/N: 1802031700017

Moxa MGate MB3170I-T - MGate MB3170/MB3270 Series Quick Installation Guide - 1

Overview

The MGate MB3170 and MB3270 are 1 and 2-port advanced Modbus gateways that convert between Modbus TCP and Modbus ASCII/RTU protocols. They can be used to allow Ethernet masters to control serial slaves, or to allow serial masters to control Ethernet slaves. Up to 32 TCP masters and slaves can be connected simultaneously. The MGate MB3170 and MB3270 can connect up to 31 or 62 Modbus RTU/ASCII slaves, respectively.

Package Checklist

Before installing the MGate MB3170 or MB3270, verify that the package contains the following items:

• MGate MB3170 or MB3270 Modbus gateway
• Quick installation guide (printed)
- Warranty card

Optional Accessories:

• DK-35A: DIN-rail mounting kit (35 mm)
• Mini DB9F-to-TB Adaptor: DB9 female to terminal block adapter
- DR-4524: 45W/2A DIN-rail 24 VDC power supply with universal 85 to 264 VAC input
- DR-75-24: 75W/3.2A DIN-rail 24 VDC power supply with universal 85 to 264 VAC input
- DR-120-24: 120W/5A DIN-rail 24 VDC power supply with 88 to 132 VAC/176 to 264 VAC input by switch

NOTE Please notify your sales representative if any of the above items is missing or damaged.

Hardware Introduction

LED Indicators

NameColorFunction
PWR1RedPower is being supplied to the power input
PWR2RedPower is being supplied to the power input
RDYRedSteady: Power is on and the unit is booting up
Blinking: IP conflict, DHCP or BOOTP server did not respond properly, or a relay output occurred
GreenSteady: Power is on and the unit is functioning normally
Blinking: Unit is responding to locate function
OffPower is off or power error condition exists
EthernetAmber10 Mbps Ethernet connection
Green100 Mbps Ethernet connection
OffEthernet cable is disconnected or has a short
P1, P2AmberSerial port is receiving data
GreenSerial port is transmitting data
OffSerial port is not transmitting or receiving data
FXAmberSteady on: Ethernet fiber connection, but port is idle.
Blinking: Fiber port is transmitting or receiving data.
OffFiber port is not transmitting or receiving data.

Reset Button

Press the Reset button continuously for 5 sec to load factory defaults:

The reset button is used to load factory defaults. Use a pointed object such as a straightened paper clip to hold the reset button down for five seconds. Release the reset button when the Ready LED stops blinking.

Panel Layouts

The MGate MB3170 has a male DB9 port and a terminal block for connecting to serial devices. The MGate MB3270 has two DB9 connectors for connecting to serial devices.

Moxa MGate MB3170I-T - Panel Layouts - 1

Hardware Installation Procedure

STEP 1: After removing the MGate MB3170/3270 from the box, connect the MGate MB3170/3270 to a network. Use a standard straight-through Ethernet (fiber) cable to connect the unit to a hub or switch. When setting up or testing the MGate MB3170/3270, you might find it convenient to connect directly to your computer's Ethernet port. In this case, use a crossover Ethernet cable.

STEP 2: Connect the serial port(s) of the MGate MB3170/3270 to a serial device.

STEP 3: The MGate MB3170/3270 is designed to be attached to a DIN rail or mounted on a wall. The two sliders on the MGate MB3170/3270 rear panel serve a dual purpose. For wall mounting, both sliders should be extended. For DIN-rail mounting, start with one slider pushed in, and the other slider extended. After attaching the MGate MB3170/3270 on the DIN rail, push the extended slider in to lock the device server to the rail. The two placement options are illustrated in the accompanying figures.

STEP 4: Connect the 12 to 48 VDC power source to terminal block power input.

Wall or Cabinet Mounting

Mounting the MGate MB3170/3270 Series on to a wall requires two screws. The heads of the screws should be 5 to 7 mm in diameter, the shafts should be 3 to 4 mm in diameter, and the length of the screws should be more than 10.5 mm.

5 - 7 mm 3 - 4 mm 10.5 mm

NOTE Wall mounting is certified for use in maritime applications.

Wallmount
Moxa MGate MB3170I-T - Wall or Cabinet Mounting - 2

natural_image Vertical line drawing of a device with ports and connectors (no text or symbols)

DIN Rail
Moxa MGate MB3170I-T - Wall or Cabinet Mounting - 3

natural_image Pure technical line drawing of a rectangular frame with mounting brackets (no text or symbols)

Moxa MGate MB3170I-T - Wall or Cabinet Mounting - 4

natural_image Pure technical line drawing of a rectangular electronic component or enclosure (no text or symbols)

Moxa MGate MB3170I-T - Wall or Cabinet Mounting - 5
Push here to lock to the DIN-Rail

Software Installation Information

ou can download the MGate Manager, User's Manual, and Device Search Utility (DSU) from Moxa's website: www.moxa.com. Please refer to the User's Manual for additional details on using the MGate Manager and DSU.

The MGate MB3170/3270 also supports login via a web browser.

Default IP address: 192.168.127.254

Default account: admin

Default password: moxa

Pin Assignments

Ethernet Port (RJ45)
Moxa MGate MB3170I-T - Pin Assignments - 1

PinSignal
1Tx+
2Tx-
3Rx+
6Rx-

Serial Port (DB9 Male)
9 8 7 6 5 4 3 2 1

PinRS-232RS-422/RS-485 (4W)RS-485 (2W)
1DCDTxD--
2RxDTxD+-
3TxDRxD+Data+
4DTRRxD-Data-
5GNDGNDGND
6DSR--
7RTS--
8CTS--
9---

NOTE For the MB3170 Series, the DB9 male port can only be used for RS-232.

Terminal Block Female Connector on the MGate (RS-422, RS-485)
5 4 3 2 1

PinRS-422/RS-485 (4W)RS-485 (2W)
1TxD+-
2TxD--
3RxD+Data+
4RxD-Data-
5GNDGND

Power Input and Relay Output Pinouts
V2+ V2- V1+ V1-

V2+ V2-V1+ V1-
Shielded GroundDC Power Input 1DC Power Input 1Relay OutputRelay OutputDC Power Input 2DC Power Input 2

Optical Fiber Interface

100BaseFX
Multi-modeSingle-mode
Fiber Cable Type OM150/125 μmG.652
800 MHz*km
Typical Distance4 km5 km40 km
Wave-lengthTypical (nm)13001310
TX Range (nm)1260 to 13601280 to 1340
RX Range (nm)1100 to 16001100 to 1600
Optical PowerTX Range (dBm)-10 to -200 to -5
RX Range (dBm)-3 to -32-3 to -34
Link Budget (dB)1229
Dispersion Penalty (dB)31
Note: When connecting a single-mode fiber transceiver, we recommend using an attenuator to prevent damage caused by excessive optical power.Note: Compute the "typical distance" of a specific fiber transceiver as follows: Link budget (dB) > dispersion penalty (dB) + total link loss (dB).

Specifications

Power Requirements
Power Input12 to 48 VDC
Power Consumption (Input Rating)MGate MB3170, MGate MB3170-T, MGate MB3270, MGate MB3270-T:12 to 48 VDC, 435 mA (max.)MGate MB3270I, MGate MB3270I-T, MGate MB3170-M-ST, MGate MB3170-M-ST-T, MGate MB3170-M-SC, MGate MB3170-M-SC-T:12 to 48 VDC, 510 mA (max.)MGate MB3170I, MGate MB3170I-T, MGate MB3170-S-SC, MGate MB3170-S-SC-T, MGate MB3170I-S-SC, MGate MB3170I-S-SC-T, MGate MB3170I-M-SC, MGate MB3170I-M-SC-T:12 to 48 VDC, 555 mA (max.)
Operating Temperature0 to 60°C (32 to 140°F),-40 to 75°C (-40 to 167°F) for -T model
Storage Temperature-40 to 85°C (-40 to 185°F)
Operating Humidity5 to 95% RH
Magnetic Isolation Protection (serial)2 kV (for "I" models)
DimensionsWithout ears:With ears extended:29 x 89.2 x 118.5 mm (1.14 x 3.51 x 4.67 in)29 x 89.2 x 124.5 mm (1.14 x 3.51 x 4.9 in)
Relay Output1 digital relay output to alarm (normal close):current carrying capacity 1 A @ 30 VDC
Hazardous LocationUL/cUL Class 1 Division 2 Group A/B/C/D, ATEX Zone 2, IECEx

This device complies with Part 15 of the FCC rules.

Operation is subject to the following conditions:

  1. This device may not cause harmful interference.
  2. This device must accept any interference received, including interference that may cause undesired operation.

ATEX and IECEx Information

Moxa MGate MB3170I-T - ATEX and IECEx Information - 1

Moxa MGate MB3170I-T - ATEX and IECEx Information - 2

MB3170/3270 Series

  1. Certificate number: DEMKO 18 ATEX 2168X
  2. IECEx number: IECEx UL 18.0149X
  3. Certification string: Ex nA IIC T4 Gc

Ambient Range : 0°C ≤ Tamb ≤ 60°C (For suffix without -T)

Ambient Range : -40^ ≤ Tamb ≤ 75^ (For suffix with -T)

  1. Standards covered:

ATEX: EN 60079-0:2012+A11:2013, EN 60079-15:2010

IECEx: IEC 60079-0 Ed.6; IEC 60079-15 Ed.4

  1. The conditions of safe usage:

  2. The equipment shall only be used in an area of at least pollution degree 2, as defined in IEC/EN 60664-1.

  3. The equipment shall be installed in an enclosure that provides a minimum ingress protection of IP4 in accordance with IEC/EN 60079-0.
  4. Conductors suitable for Rated Cable Temperature ≥ 100^
  5. Input conductor with 28-12 AWG (max. 3.3 mm ^4 ) to be used with the devices

MB3170I/3270I Series

  1. ATEX Certificate number: DEMKO 19 ATEX 2232X
  2. IECEx number: IECEx UL 19.0058X
  3. Certification string: Ex nA IIC T4 Gc

Ambient Range : 0^ C ≤ Tamb ≤ 60^ C (For suffix without -T)

Ambient Range : -40^ ≤ Tamb ≤ 75^ (For suffix with -T)

  1. Standards covered:

ATEX: EN 60079-0:2012+A11:2013, EN 60079-15:2010

IECEx: IEC 60079-0 Ed.6; IEC 60079-15 Ed.4

  1. The conditions of safe usage:

  2. The equipment shall only be used in an area of at least pollution degree 2, as defined in IEC/EN 60664-1.

  3. The equipment shall be installed in an enclosure that provides a minimum ingress protection of IP 54 in accordance with IEC/EN 60079-0.
  4. Conductors suitable for Rated Cable Temperature ≥ 100^
  5. Input conductor with 28-12 AWG (max. 3.3 mm ^4 ) to be used with the devices

Address of manufacturer: No. 1111, Heping Rd., Bade Dist., Taoyuan City 334004, Taiwan