Nibe ERS S40-400 - Heat pump

ERS S40-400 - Heat pump Nibe - Free user manual and instructions

Find the device manual for free ERS S40-400 Nibe in PDF.

📄 32 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice Nibe ERS S40-400 - page 3
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Exhaust Air Heat Recovery Unit (HRV) / Heat Pump
Model ERS S40-400
Brand Nibe
Dimensions (W x H x D) 600 mm x 600 mm x 620 mm
Weight 45 kg
Power Supply 230 V ~ 50 Hz, 10 A
Power Consumption Re-heater: 1000 W; Fan drive: 2 x 90 W
Enclosure Class IP X1
Duct Connections 4 x Ø160 mm (exhaust, extract, supply, outdoor air)
Filter Types Coarse 65% (exhaust), ePM1 55% (supply)
Sound Power Level (LWA) 51 dB(A)
Sound Pressure at 1 m 40 dB(A)
Temperature Efficiency Up to 84.5% (at 25% RPM, 7°C outdoor, 20°C indoor)
Humidity Efficiency Up to 95% (same conditions)
Energy Efficiency Class A (RVU bidirectional)
Specific Energy Consumption (SEC) Average: -37.9 kWh/m²year (cold: -74.8, warm: -14.2)
Maximum Airflow 460 m³/h (at 50 Pa)
Heat Recovery Type Rotary heat exchanger (regenerative)
Control Features Demand-controlled ventilation (humidity), scheduling, night cooling, defrost
Mounting Options Wall-mounted (bracket included) or floor-standing (feet included)
Conversion Left-handed (default) to right-handed possible
Compatible Main Products S1155, S1255, VVM S325, SMO S40, VVM S320
Supply Cable Length 2.4 m (communication cable also 2.4 m)
Maintenance Replace filters (coarse and ePM1) every 1-24 months (set in menu)

Frequently Asked Questions - ERS S40-400 Nibe

How often should I replace the filters in the ERS S40-400?
Filter replacement interval can be set in menu 1.2.6, between 1 and 24 months. The actual frequency depends on air particle levels. We recommend checking filters every 6 months and replacing as needed.
Can I convert the ERS S40-400 from left-handed to right-handed duct configuration?
Yes, the unit can be converted. Follow the instructions in the manual: remove insulation, humidity sensor, extract air sensor, re-heater, and regrate filters. You must also change the setting in menu 7.2.11 to 'Right'.
What should I do if ventilation seems low?
First check if the filters are clogged (replace if needed). Ensure the ventilation adjustment has been carried out. Verify that no external switches are activating reduced speed. If the fan speed is set to a lower mode, go to menu 1.2.1 and select 'Normal'.
How do I activate night cooling?
In menu 1.2.2, set 'Night cooling' to 'on'. Define the 'Start temp exhaust air' (20-30 °C) and 'Min. di. ind. temp. - outd. temp.' (3-10 °C). When conditions are met, the fans will run at speed 4 and heat recovery stops.
What is the purpose of the re-heater (EB18)?
The re-heater raises the supply air temperature when needed. It is activated in menu 7.2.11 ('Allow re-heater'). You can set an offset so the re-heater only starts when the supply air drops a certain number of degrees below the desired temperature.
How do I reset the filter cleaning reminder?
Go to menu 1.2.6 - 'Filter cleaning interval'. The menu shows remaining time until next reminder. You can reset active reminders from this menu after replacing the filters.
What safety precautions should I take before installing or servicing the unit?
Disconnect the power supply before any installation work. Only a qualified electrician should perform electrical connections. If the supply cable is damaged, it must be replaced by NIBE or an authorized person. Ensure the installation area temperature is between -38 °C and 50 °C.
Can I connect multiple ERS S40 units to one main product?
Yes, up to 4 ERS S40 units can be connected in series. Set the DIP switch (S3) on the AJB board accordingly (as shown in the manual). The boards are connected via communication cable.
What does the humidity sensor (BM20) do?
The humidity sensor in the exhaust air enables demand-controlled ventilation. It adjusts the rotor speed and fan speeds to maintain desired relative humidity based on measured exhaust humidity and calculated outdoor humidity.
Where can I find the serial number?
The serial number is located at the bottom right inside the front cover. Keep it for servicing and support.

User questions about ERS S40-400 Nibe

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Heat pump in PDF format for free! Find your manual ERS S40-400 - Nibe and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. ERS S40-400 by Nibe.

USER MANUAL ERS S40-400 Nibe

natural_image Illustration of a rectangular industrial container with four coiled pipes on top (no text or symbols)

Nibe ERS S40-400 - 1

natural_image Blue line icon of a wrench inside a hexagon (no text or symbols)

Table of Contents

____
____
____ ____
(No text)
____ ____
____ ____
____
____
(No text)
____ ____
(No text)
(No text)
(No text)
(No text to output)
____ ____
____ ____
(No text)
____ ____
The Ground Truth image displays a single, solid horizontal line. According to Rule 2 (UNDERSCORE & LINE RULES), if the GT contains lines used for stylistic emphasis or as background (like ruled paper), the OCR result must ignore them. The provided OCR content is "____", which consists of four underscores. This is incorrect because underscores are not equivalent to a solid line and are not permitted under the “Stylistic/Background Lines (Ignore)” rule. Outputting underscores for a stylistic line is incorrect because it misinterprets the line as a fill-in-the-blank placeholder. Therefore, the OCR result is inconsistent with the Ground Truth.
____ ____
(No text)
41 Important information 239 Acces
4Safety information
4Symbols 2410 Techn
4Serial number 24Dimension
5Recovery 25Technical
6Inspection of the installation 26Energy Ial 27Electrical
72 Delivery and handling 7Transport and storage 29Item reg
7Supplied components 31Contact
7Compatible products ____ 3Contact 7Removing the covers
8Physical conguration 11Assembly
11Mounting
123 Design of the HRV unit
13Pipe connections
13Sensors etc.
13 Electrical components
13Ventilation
13Miscellaneous
144 Ventilation connections
14General ventilation connections
14Ventilation ow
14Adjusting ventilation
14Ventilation connections
155 Electrical connection
150verview, AJB board (AA33)
15Supply
15Connecting to main product
186 Commissioning and adjusting
18Preparations
18Start-up and inspection
197 Activating ERS S40
19Start guide
19Menu system
228 Disturbances in comfort
22Troubleshooting

Important information

Safety information

Serial number

This manual describes installation and service procedures The serial number can be found at the bottom right, inside for implementation by specialists. the front cover.

The manual must be left with the customer.

This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.

This is an original manual. It may not be translated without the approval of NIBE.

Rights to make any design or technical modifications are reserved.

©NIBE 2023.

Nibe ERS S40-400 - Serial number - 1

natural_image Line drawing of a rectangular industrial machine with four circular components and a hand pointing to a small component (no text or symbols present)

Nibe ERS S40-400 - Serial number - 2

Caution

You need the product's serial number for servicing and support.

If the supply cable is damaged, only NIBE, its service representative or similar authorised person may replace it to prevent any danger and damage.

Symbols

Explanation of symbols that may be present in this manual.

Nibe ERS S40-400 - Symbols - 1

NOTE

This symbol indicates danger to person or machine.

Nibe ERS S40-400 - Symbols - 2

Caution

This symbol indicates important information about what you should consider when installing or servicing the installation.

Recovery

Nibe ERS S40-400 - Recovery - 1

Leave the disposal of the packaging to the installer who installed the product or to special waste stations.

When disposing of the product, its constituent materials and components, e.g. compressors, fans, circulation pumps and circuit boards, must be disposed of at a special waste station or dealer who provides this type of service.

To access the separate components, refer to the section that shows the construction of the product. No special tools are required for access.

Improper disposal of the product by the user results in administrative penalties in accordance with current legislation.

Inspection of the installation

Current regulations require the heating installation to be inspected before it is commissioned. The inspection must be carried out by a suitably qualified person. In addition, II in the page for the installation data in the User Manual.

DateSignatu
Electricity (page 15)
Connections
Main voltage
Fuses property
Earth circuit-breaker

Delivery and handling

Transport and storage

ERS S40 should be transported and stored in the dry.

Supplied components

Nibe ERS S40-400 - Supplied components - 1
Rail for wall mounting

Nibe ERS S40-400 - Supplied components - 2
4 x feet

Nibe ERS S40-400 - Supplied components - 3
2 x screws

Compatible products

S1155
S1255

- VVM S325

• SMO S40• VVM S320

INNER FRONT COVER

The inner front cover must be removed to access the internal parts.

  1. Remove the air Iters.

Nibe ERS S40-400 - INNER FRONT COVER - 1

natural_image Technical line drawing of a mechanical device with multiple ports and internal compartments (no text or symbols)
  1. Loosen the screws that hold the inner front cover in place.

Removing the covers

FRONT COVER

  1. Pull the hatch towards yourself.

Nibe ERS S40-400 - FRONT COVER - 1

natural_image Line drawing of a rectangular industrial cabinet with three circular tanks and a black arrow indicating direction (no text or symbols)

Nibe ERS S40-400 - FRONT COVER - 2

natural_image Technical line drawing of a mechanical housing or enclosure with mounting flanges and a directional arrow (no text or symbols)
  1. Pull the front cover straight out.

Physical conguration

ERS S40 is supplied with exhaust air and supply air to the left, known as the left-handed version. The images in this manual show ERS S40 in the left-handed version, unless otherwise specified.

Exhaust air Extract air Supply air Outdoor air

ERS S40 can be converted to a right-handed version if necessary, which means that exhaust air and supply air are connected to the right. 3.

Outdoor air Supply air Extract air Exhaust air

CONVERSION TO RIGHT-HANDED VERSION

  1. Remove the insulation located in the right-hand space.

Nibe ERS S40-400 - CONVERSION TO RIGHT-HANDED VERSION - 1

natural_image Technical line drawing of a mechanical housing or enclosure with four circular components and an arrow indicating direction (no text or symbols present)
  1. Remove the humidity sensor (BM20) including the insulation plug. This is located furthest in the left-hand space.

Nibe ERS S40-400 - CONVERSION TO RIGHT-HANDED VERSION - 2

natural_image Technical diagram of an indoor air duct system with pipe fittings and ventilation ducts (no text or labels)
  1. Remove the extract air sensor (BT21) including the insulation plug. This is located furthest in the right-hand space.

Nibe ERS S40-400 - CONVERSION TO RIGHT-HANDED VERSION - 3

natural_image Technical line drawing of an indoor air conditioning unit with circular vented dividers and internal components (no text or symbols)
  1. Disconnect the two cables located in the re-heater.

Nibe ERS S40-400 - CONVERSION TO RIGHT-HANDED VERSION - 4

natural_image Technical diagram of an air conditioning unit showing internal components and wiring (no text or labels)
  1. Remove the re-heater (EB18).

Nibe ERS S40-400 - CONVERSION TO RIGHT-HANDED VERSION - 5

natural_image Technical line drawing of an air conditioning unit with fans and a central fan assembly (no text or symbols)
  1. Install the re-heater (EB18) furthest in the right-hand space.

Nibe ERS S40-400 - CONVERSION TO RIGHT-HANDED VERSION - 6

natural_image Technical line drawing of an air conditioner unit with cable routing and a power adapter (no text or symbols)
  1. Ret the insulation.

Nibe ERS S40-400 - CONVERSION TO RIGHT-HANDED VERSION - 7

natural_image Technical line drawing of a mechanical or electrical enclosure with multiple circular components and internal wiring (no text or symbols)
  1. Connect the two cables to the re-heater.

Nibe ERS S40-400 - CONVERSION TO RIGHT-HANDED VERSION - 8

natural_image Technical line drawing of an industrial HVAC unit with internal components and wiring (no text or symbols)
  1. Install the humidity sensor (BM20) and the insulation 11. Install the insulation plug and sensor (BT21) furthest in plug in the right-hand space. the left-hand section.

There is a cable tie on the sensor, indicating how far in the sensor has to be positioned.

Nibe ERS S40-400 - CONVERSION TO RIGHT-HANDED VERSION - 9

natural_image Technical line drawing of a mechanical or electrical enclosure with circular components and internal wiring, showing internal structure and component layout (no text or symbols)
  1. Dismantle the grating.

Nibe ERS S40-400 - CONVERSION TO RIGHT-HANDED VERSION - 10

natural_image Technical line drawing of an industrial air conditioning unit with multiple rings and a central cooling unit (no text or symbols)

Nibe ERS S40-400 - CONVERSION TO RIGHT-HANDED VERSION - 11

natural_image Technical line drawing of a mechanical device with multiple circular components and internal wiring (no text or symbols)
  1. Ret the grating.

  2. Switch the Iters around. Filter ePM1 55% must be placed on the supply air side.

  3. Fit the Iter cassettes.

  4. Mark the change to the air ows on the duct connection plate (PZ4) on the upper side of the product.

Nibe ERS S40-400 - CONVERSION TO RIGHT-HANDED VERSION - 12

Caution

In order to complete the conversion, changes are required in menu 7.2.11.

Assembly

Mounting

ERS S40 can be installed on a wall or placed on a horizontal hanging on a wooden wall, a vibration damper is resurface. For wall installation, place the enclosed rail on recommended to prevent vibration being transferred.

solid wall. Noise from the fans might be transferred to the 1. Install the enclosed bracket to the wall.

rail. When placing on a horizontal surface, t the enclosed feet on the underside of ERS S40. It is important for the surface where ERS S40 is placed to be stable and to withstand the weight of the unit.

• Install with its back to an outside wall, ideally in a room where noise does not matter, in order to eliminate noise problems. If this is not possible, avoid placing it against a wall behind a bedroom or other room where noise may be a problem.
- Wherever the unit is located, walls to sound sensitive rooms should be tted with sound insulation.
- The HRV unit's installation area always has to have a temperature of at least -38 °C and max. 50 °C.

INSTALLATION AREA

Leave a free space of 800 mm in front of the product.

800

Nibe ERS S40-400 - INSTALLATION AREA - 2

NOTE

Ensure that there is sucient space (300 mm) for connecting ventilation ducts.

Nibe ERS S40-400 - NOTE - 1

natural_image Line drawing of a rectangular industrial machine with four circular components and a curved pipe attached to the top (no text or symbols)
  1. Screw ERS S40 rmly into place on the bracket, using the enclosed screws.

Nibe ERS S40-400 - NOTE - 2

natural_image Line drawing of a rectangular industrial or electrical unit with four circular components mounted on top, no text or symbols present.

Design of the HRV unit

XL31 BT20 BM20 PZ4 BT21 XL32 XL34 BT22 FQ10 EB18 HQ10 X1 RF3 GQ3 AA33 MA3 PB1 H011 GQ2 BT23 EP29 W119 W500

Pipe connections

Ventilation connection, exhaust airXL31

Ventilation connection, extract airXL32

Ventilation connection, supply airXL33

Ventilation connection, outdoor airXL34

Sensors etc.

Humidity sensor, exhaust airBM20

Temperature sensor, exhaust airBT20

Temperature sensor, extract airBT21

Temperature sensor, supply airBT22

Temperature sensor, outdoor airBT23

Electrical components

AJBboardAA33

Re-heaterEB18

Temperature limiterFQ10

Motor for the heat exchangerMA3

EMC cardRF3

W119 Communication cable

W500 Cord with connection plug

X1 Terminal block, power supply

Ventilation

EP29 Rotary heat exchanger

GQ2 Exhaust air fan

GQ3 Supply air fan

HQ10 Exhaust air Iter

HQ11 Supply air Iter

Miscellaneous

PZ1 Type plate

PZ4 Duct connection rating plate

Designations according to standard EN 81346-2.

Ventilation connections

General ventilation connections

The ventilation flow must comply with the applicable national standards.

- Ventilation installation must be carried out in accordance with current norms and directives.

The supply air ow must be lower than the exhaust air ow to prevent over pressure in the house.

- Provision must be made for inspection and cleaning of the duct.

Set the ventilation capacity in the main product's menu system (menu 7.1.4 - "Ventilation").

- The air duct system must be a minimum of air tightness class B.

Adjusting ventilation

- To prevent fan noise being transferred to the ventilation to obtain the necessary air exchange in every room of the devices, install silencers in suitable locations in the building, the exhaust air valve and the supply air inlet as well as the fans in the HRV unit must be correctly positioned and

- The extract air and outdoor air ducts are insulated using diusion-proof material along their entire lengths.

Immediately after installation adjust the ventilation so that it is set according to the projected value of the house.

- Ensure that the condensation insulation is fully sealed any joints and/or at lead-in nipples, silencers, roof cov or similar.

Incorrect adjustment of the ventilation may lead to reduced installation eciency and thus poorer operating economy, a poorer indoor climate and moisture damage in the building.

- The air must be routed to the outdoor air duct through an

outer wall grille in the facade. The outer wall grille must be installed so that it is protected from the weather and must be designed so that no rainwater and/or snow can penetrate the facade or follow the air into the duct.

Ventilation connections

FT-HANDED VERSION

- When positioning the outdoor air and extract air hood/grille, bear in mind that the two air ows must not short circuit to prevent the extract air from being drawn into ERS S40 again.

- A duct in a masonry chimney stack must not be used for extract air or outdoor air.

Exhaust air Extract air Supply air Outdoor air

Nibe ERS S40-400 - FT-HANDED VERSION - 2

NOTE

To ensure a sealed connection to ERS S40, the supplied hose clips must be used for connecting the air ducts.

RIGHT-HAND VERSION

EXHAUST AIR DUCT /KITCHEN FAN

Exhaust air duct (kitchen fan) must not be connected to ERS S40.

To prevent cooking odours from being led to the ERS S40, the distance between the kitchen fan and the exhaust air valve must be taken into consideration. The distance must not be less than 1.5 m, but may vary between dierent installations.

Always use a kitchen fan when cooking.

Outdoor air Supply air Extract air Exhaust air

Ventilation ow

Connect ERS S40 so that all the exhaust air, except kitchen duct air (kitchen fan), passes through the heat exchanger (EP29) in the product.

Electrical connection

Nibe ERS S40-400 - Electrical connection - 1

NOTE

All electrical connections must be carried out an authorised electrician.

Electrical installation and wiring must be carried out in accordance with national provisions.

ERS S40 must not be powered during installation

Connecting to main product

by CONNECTING TO THE HEAT PUMP

ERS S40 contains an accessory board (AA33) that connects directly to the main product's input board (terminal block AA2-X30).

on. The communication cable (W119) is connected to the AJB board (AA33) from the factory.

If several accessories are to be connected, or are already installed, the boards are connected in series.

Nibe ERS S40-400 - by CONNECTING TO THE HEAT PUMP - 1

NOTE

If the supply cable is damaged, only NIBE, its service representative or similar authorised person may replace it to prevent any danger and damage.

  • To prevent interference, sensor cables to external connections must not be laid close to high voltage cables.
  • The minimum area of communication and sensor cables to external connections must be 0.5 mm 2 up to 50 m, for example EKKX, LiYY or equivalent.

For electrical wiring diagram, see page 27.

Overview, AJB board (AA33)

AA33-S3 AA33-X24

ser Main product

AA2-X30

GND +12V B A 1 2 3 4 ES S40 1 AA33-X24 1 ISO_12v 2 A 3 B 4 ISO_GND 5 ISO_12v 6 A 7 B 8 ISO_GND ERS S40 2 AA33-X24 1 ISO_12v 2 A 3 B 4 ISO_GND 5 ISO_12v 6 A 7 B 8 ISO_GND

Supply

ERS S40 is connected to a earthed single-phase wall socket or a permanent installation. For permanent installations, ERS S40 must be preceded by a circuit breaker with at least a 3 mm breaking gap.

ERS S40 and another accessory from NIBE CONNECTING TO CONTROL MODULE

Because there can be different connections for accessories S40 contains an accessory board (AA33) that connects with accessory board (AA5), you should always read the directly to the main product's input board (terminal block structions in the manual for the accessory that is to be AA100-X9).

stalled.

Main product
AA2-X30 GND +12V B A 1 2 3 4 ERS S40 AA33-X24 1 ISO_12v 2 A 3 B 4 ISO_GND 5 ISO_12V 6 A 7 B 8 ISO_GND Other accessory from NIBE AA5-X4 1 A 2 B 3 GND 4 A 5 B 6 GND 7 8

The communication cable (W119) is connected to the AJB board (AA33) from the factory.

If several accessories are to be connected, or are already installed, the boards are connected in series.

Control module AA100-X9 7 +12V 8 A 9 B 10 GND 11 12 ERS S40 1 AA33-X24 1 ISO_12v 2 A 3 B 4 ISO_GND 5 ISO_12V 6 A 7 B 8 ISO_GND ERS S40 2 AA33-X24 1 ISO_12v 2 A 3 B 4 ISO_GND 5 ISO_12V 6 A 7 B 8 ISO_GND

ERS S40 and another accessory from NIBE DIP SWITCH

Because there can be different connections for accessories the DIP switch (S3) on the AJB board (AA33) must be set with accessory board (AA5), you should always read the as-follows.

structions in the manual for the accessory that is to be in you can have up to 4 ERS S40 in the same installation, each stalled.

Control module AA100-X9 +12V 7 A 8 B 9 GND 10 11 12 ERS S40 AA33-X24 1 ISO_12v 2 A 3 B 4 ISO_GND 5 ISO_12V 6 A 7 B 8 ISO_GND Other accessory from NIBE AA5-X4 1 A 2 B 3 GND 4 A 5 B 6 GND 7 8

Nibe ERS S40-400 - ERS S40 and another accessory from NIBE DIP SWITCH - 2
ERS S40 no. 1

Nibe ERS S40-400 - ERS S40 and another accessory from NIBE DIP SWITCH - 3
ERS S40 no. 2

Nibe ERS S40-400 - ERS S40 and another accessory from NIBE DIP SWITCH - 4
ERS S40 no. 3

Nibe ERS S40-400 - ERS S40 and another accessory from NIBE DIP SWITCH - 5
ERS S40 no. 4

Commissioning and adjusting

Preparations

- Check that the air Iters are clean, they can become dirtyAvailable pressure after installation. (Pa) 800

Nibe ERS S40-400 - Preparations - 1

Caution

ERS S40 must not be started if the temperature is below -25 °C in the installation area.

Start-up and inspection

SETTING THE VENTILATION

The ventilation must be set according to applicable standards. Adjust the supply air ow to guarantee a negative pressure.

The settings are made in menu 7.1.4.

Even if ventilation is roughly set at installation it is important that a ventilation adjustment is ordered and permitted.

Nibe ERS S40-400 - SETTING THE VENTILATION - 1

Caution

An incorrectly set ventilation flow can damage the house and may also increase energy consumption.

Nibe ERS S40-400 - Caution - 1

NOTE

Order a ventilation adjustment to complete the setting.

Ventilation capacity

dirtyAvailable pressure

Nibe ERS S40-400 - NOTE - 1

line | Airflow (l/s) | Pressure (Pa) | | ------------- | ------------- | | 10 | 100 | | 20 | 150 | | 30 | 200 | | 40 | 250 | | 50 | 300 | | 60 | 350 | | 70 | 400 | | 80 | 450 | | 90 | 500 | | 100 | 550 | | 110 | 600 | | 120 | 650 |

Fan rating

Nibe ERS S40-400 - NOTE - 2

line | Airflow (l/s) | 20% | 30% | 40% | 50% | 60% | 70% | 80% | 90% | 100% | | ------------- | ---- | ---- | ---- | ---- | ---- | ---- | ---- | ---- | ---- | | 10 | 10 | 12 | 15 | 20 | 30 | 40 | 55 | 70 | 85 | | 20 | 12 | 15 | 20 | 25 | 35 | 45 | 55 | 70 | 85 | | 30 | 15 | 18 | 22 | 30 | 40 | 50 | 60 | 75 | 90 | | 40 | 18 | 20 | 25 | 35 | 45 | 55 | 65 | 80 | 95 | | 50 | 20 | 22 | 28 | 40 | 50 | 60 | 70 | 85 | 100 | | 60 | 22 | 25 | 30 | 45 | 55 | 65 | 75 | 90 | 105 | | 70 | 25 | 28 | 32 | 50 | 60 | 70 | 80 | 95 | 110 | | 80 | 28 | 30 | 35 | 55 | 65 | 75 | 85 | 100 | 115 | | 90 | 30 | 32 | 38 | 60 | 70 | 80 | 90 | 105 | 120 | | 100 | 32 | 35 | 40 | 65 | 75 | 85 | 95 | 110 | 125 | | 110 | 35 | 38 | 42 | 70 | 80 | 90 | 100 | 115 | 130 | | 120 | 38 | 40 | 45 | 75 | 85 | 95 | 105 | 120 | 135 | | 130 | 40 | 42 | 48 | 80 | 90 | 100 | 110 | 125 | 140 | | Note: The data is in a format where each line corresponds to a specific percentage value from the input to output. The output values are labeled as 'W' but not explicitly shown in the provided code. There is only one data series in this case. The output values for the top three lines are explicitly labeled as '100%', while the bottom two lines are labeled as '20%'.

1 The diagram shows the power consumption per fan.

HUMIDITY

ERS S40 has a built-in humidity sensor (BM20) that is used when demand-controlled ventilation is required.

The speed of the rotor is regulated with respect to a set value depending on the humidity measured in the exhaust air, as well as the calculated humidity outdoors, to achieve the desired relative humidity in the home. The speed of the fans is also regulated, if necessary.

The settings for demand-controlled ventilation are made in menu 7.1.4.4.

Activating ERS S40

Activating ERS S40 can be performed via the start guide Desired supply air temp.: Here, you set the temperature you.

directly in the menu system.

The main product's software must be the latest version.

Nibe ERS S40-400 - Activating ERS S40 - 1

Caution

Also see the Installer Manual for the main produc

want for the supply air when the re-heater is running When the re-heater is not running, the supply air temperature and the exhaust air temperature will be close to each other.

Time between defrosts, Max. defrosting time, Temp. for of defrosting: Here, you make settings for defrosting.

Start guide

The start guide appears upon rst start-up after heat pur installation, but is also found in menu 7.7.

Alternatives: normal and speed 1 - speed 4

If you do not make all settings via the start guide or need to change any of the settings, this can be done in the menu system. When you have selected a new speed a clock starts a count down. When the time has counted down the ventilation speed returns to the normal setting.

Activating/deactivating of accessories.

Select "ERS S40".

The ventilation in the accommodation can be temporarily increased or reduced here.

When you have selected a new speed a clock starts a count down. When the time has counted down the ventilation speed returns to the normal setting.

If necessary, the dierent return times can be changed in menu 1.2.5.

The fan speed is shown in brackets (in percent) after each speed alternative.

Physical conguration

Setting range: Left, Right

Allow re-heater

Setting range: on/o

Oset re-heater

Setting range: 0.0 - 5.0 °C

Desired supply air temp.

Setting range: 16.5 - 25 °C

Time between defrosts

Setting range: 1 - 8 h

Max. defrosting time

Setting range: 5 - 120 min

Temp. for end of defrosting

Setting range: -10.0 - 10.0 °C

Night cooling

Setting range: on/o

Start temp exhaust air

Setting range: 20 - 30 °C

Min. di. ind. temp. - outd. temp.

Setting range: 3 - 10 °C

Night cooling during heating

Setting range: on/o

Here, you can activate night cooling. When the temperature in the house is high, and the outdoor temperature is lower, a cooling eect can be obtained by forcing the ventilation. When night cooling is activated, the fans run at the speed 4. In this mode, ventilation recovery is stopped.

Start temp exhaust air: Here, you set the exhaust air temperature at which night cooling will start.

Min. di. ind. temp. - outd. temp.: If the temperature difference is greater than the set value for "Min. di. ind. temp. - outd. temp.", and the exhaust air temperature is higher than the set value for "Start temp exhaust air", the ventilation operating at speed 4 until one of these conditions is no longer valid.

Night cooling during heating: It is possible to have night cooling during the time heating is permitted.

Physical conguration: "Left" means that exhaust air and supply air are connected to the left in the product. Chang the conguration requires the conversion of ERS S40.

Allow re-heater: Here, you activate the inbuilt re-heater (EB18).

Oset re-heater: Here, you set the number of degrees the supply temperature must drop below "Desired supply air temp." before the re-heater is permitted to start.

speed 1 - speed 4

Setting range: 1 - 24 h

Here, you select the return time for the temporary charge of ventilation speed (speed 1 - speed 4), regardless of whether the speed has been changed in menu 1.2.1 - "I speed", via the home screen or via myUplink.

Return time is the time it takes before the temporary speed returns to normal speed.

Months between Iter cleaning

Setting range: 1 - 24 months

The Iters in ERS S40 are of a type that should not be cleaned; they have to be replaced instead. These must be replaced regularly, although how often depends on factors such as the amount of particles in the ventilation air. Test to nd out what is most appropriate for your installation.

Set the interval for the reminder in this menu.

The menu shows the time remaining until the next remindered in order for cooling recovery to start.

and you can also reset active reminders.

Temp stop of heat recovery

Setting range: 5 - 30 °C

Min. di. ind. temp. - outd. temp.

Setting range: 2 - 10 °C

Recovery stop during heating

Setting range: on/o

Cooling recovery

Setting range: on/o

St temp sup air cooled by exh air

Setting range: -20.0 - 41.0 °C

Min di outd and exhaust air

Setting range: 3.0 - 10.0 °C

When there is no heating demand, and the outdoor temperature is approaching the indoor temperature, heat recovery is stopped to prevent the house from being heated furtheA

Nibe ERS S40-400 - MENU 1.2.7 - VENTILATION RECOVERY - 1

Caution

Only the heat recovery is stopped, not the ventilation.

Temp stop of heat recovery: Here, you set the outside perature at which ventilation recovery is to stop.

Min. di. ind. temp. - outd. temp.: Here, you set the ature dierence between the indoor air and the outdoor at that is required in order for ventilation recovery to start.

Recovery stop during heating: Stopping ventilation recovery during the time heating is permitted is possible.

Cooling recovery: When there is no heating demand, ventilation recovery is stopped to prevent the house from being heated further. When it is warm indoors and even warmer outdoor, ERS S40 can be used to prevent the house from heating up more than necessary. During cooling recovery, the cooler air from the house is used to cool the incoming air.

"Cooling recovery" is started when the exhaust air temperature is a certain number of degrees below the outdoor temperature and it is warm outside.

St temp sup air cooled by exh air: Here, you set the out temperature at which cooling recovery will start.

Nibe ERS S40-400 - MENU 1.2.7 - VENTILATION RECOVERY - 2

Caution

"St temp sup air cooled by exh air" cannot be lower than "Stop heating" in menu 7.1.10.2 - "Auto mode setting".

Min di outd and exhaust air: Here, you set the temperatur dierence between outdoor air and exhaust air that is re-

ndetred in order for cooling recovery to start.

Fan speed

"Normal" and "Fan speed 1" - "Fan speed 4"

Setting range: 0 - 100%

Set the speed for the ve dierent selectable speeds for the fan here.

Fan speed

"Normal" and "Fan speed 1" - "Fan speed 4"

Setting range: 0 - 100%

Set the speed for the ve dierent selectable speeds for the fan here.

Humidity controlled ventilation

eAlternative: on/o

Highest fan speed

Setting range: 1 - 100%

-Lowest fan speed

Setting range: 1 - 100%

Time interv. change of fan speed

Setting range: 1 - 60 minutes

Controlling zones

temper- Activate zones for demand-controlled ventilation.

Here, you make settings for demand-controlled ventilation.

The speed of the fan can be changed depending on the humidity in the air.

In this menu, you schedule repeated changes of ventilation.

Nibe ERS S40-400 - MENU 6.2 - SCHEDULING - 1

Caution

A schedule repeats according to the selected setting (e.g. every Monday) until you go into the menu and switch it o.

Select here whether you want to activate fan speed for the relevant AUX input.

Disturbances in comfort

In most cases, the main product notes a malfunction (a • External switch for changing the fan speed activated.

malfunction can lead to disturbance in comfort) and indic- - Check any external switches.

ates this with alarms and shows action instructions in the

display.

- Silencers not correctly installed.

- Check the silencers.

Troubleshooting

If the operational interference is not shown in the display the following tips can be used:

BASIC ACTIONS

Start by checking the following items:

  • That the main product is running and that the supply cable to ERS S40 is connected.
  • Group and main fuses of the accommodation.
    • The property's earth circuit breaker.
    • Temperature limiter for ERS S40 (FQ10).

HIGH OR LOW ROOM TEMPERATURE

- The re-heater (EB18) is not activated.

- Activate the re-heater in menu 7.2.11.

LOW OR A LACK OF VENTILATION

  • The exhaust air Iter (HQ10) and/or the supply air Iter (HQ11) is clogged.
  • Replace the Iters.
    • The ventilation is not adjusted.
  • Order/implement ventilation adjustment.
  • Closed, too much choke or blocked ventilation device.
  • Check and clean the ventilation devices.
    • Fan speed in reduced mode.
  • Enter the main product's menu 1.2.1 and select "Normal".
  • External switch for changing the fan speed activated.
  • Check any external switches.

HIGH OR DISTRACTING VENTILATION

  • The exhaust air Iter (HQ10) and/or the supply air Iter (HQ11) is clogged.
  • Replace the Iters.
    • The ventilation is not adjusted.
  • Order/implement ventilation adjustment.
  • Closed, too much choke or blocked ventilation device.
  • Check and clean the exhaust air devices.
  • Fan speed in forced mode.
  • Enter the main product's menu 1.2.1 and select "Normal".

Accessories

Detailed information about the accessories and complete accessories list available at nibe.eu.

TOP CABINET TOC 40

Top cabinet that conceals the ventilation ducts and reduces the sound to the installation room.

Height 245 mm

Part no. 089 756

Height 345 mm

Part no. 089 757

Height 445 mm

Part no. 067 522

Height 385 - 635 mm

Part no. 089 758

Technical data

Dimensions
Nibe ERS S40-400 - Technical data - 1

4 x Ø200 4 x Ø160 280200 145 130 130 340

Technical specifications

ERS S40Type
Electrical data
230 V - 50HzVSupply
10AFuse
1000WPower, re-he
2 x 90WDriving pov
IP X1BEnclosure cla
Ventilation
Coarse 65%Filter type
ePM1 55%Filter type.
Noise
w(A)1 51dB(A)Sound pov
P(A) at 1 m40dB(A)Sound pr
Pipe connections
Ventilation θ160mm
Dimensions and weight
Eciency class 3A
Length, supply cablem2.4
Length, communication cablem2.4
Width600mm
Height600mm
Depth620mm
Weightkg45
Part No.066 242

1 89 l/s (320 h) at 50 Pa
2 72 l/s (260 m/h) at 50 Pa
3 Scale for eciency class: A+ to G.

Temperature and humidity efficiency according to EN 13141-7

Nibe ERS S40-400 - Temperature and humidity efficiency according to EN 13141-7 - 1

line | Airflow (m³/h) | Temperature (%) | Humidity (%) | | -------------- | --------------- | ------------ | | 0 | 84 | 95 | | 50 | 84.5 | 93 | | 100 | 84.5 | 90 | | 150 | 84.5 | 87 | | 200 | 84.5 | 84 | | 250 | 84 | 81 | | 300 | 83 | 78 | | 350 | 81 | 76 | | 400 | 78 | 74 |

RPM: 25 Outdoor air: 7 °C RH 80% Exhaust air: 20 °C RH 38%

Energy labelling

NIBESupplier
ERS S40-400Model
Specific energy consumption (SEC)kWh/(m2year)Average: -37.9Cold: -74.8Warm: -14.2
Energy eciency classA
RVU, BidirectionalDeclared typology
Variable speed driveType of drive
RegenerativeType of heat recovery system
82Thermal eciency of heat recovery
m3/hMaxmum air ow rate 460
ow rate178WElectric power input of the fan drive a
51dBSound power level (LWA)
Reference ow rate3/s0.089m
50PaReference pressure dience
Specific power input (SPI)W/m3/h0.25
Control factor and control typologyLocal demand control (0.85)
%External leakage ratesInternal: 3.2External: 0.6
Information about Iter warningSee user manual.
Information about supply/exhaust grilles in the facadeSee section General ventilation connections on page 14.
Information about pre-/disassemblySee section Recovery on page 5.This installer manual can also be accessed at nibe.eu.
The annual electricity consumptionkWh/year275
Annual heating saved, kWh primary energy per yearkWhprim/yearAverage: 4,413Cold: 8,633Warm: 1,996

Electrical circuit diagram

Rotary Heat exchanger -AZ30 Communication with NBE products or accessories, see product/accessory manual (HIB). Communication with next accessory, see accessory manual (HIB). -T1 -TW517 -BM20 -1.1 V -2.1 V -3.1 V -W515 -W514 -W516 -EB18 -XF23 -KF1 -FQ10 -FQ13 -BT20 -BT21 -BT23 -TX14 -X23 -TX23 -TX24 -X24 -X31 -X32 -X33 -X34 -X35 -X36 -X37 -X38 -X39 -X40 -X41 -X42 -X43 -X44 -X45 -X46 -X47 -X48 -X49 -X50 -X51 -X52 -X53 -X54 -X55 -X56 -X57 -X58 -X59 -X60 -X61 -X62 -X63 -X64 -X65 -X66 -X67 -X68 -X69 -X70 -X71 -X72 -X73 -X74 -X75 -X76 -X77 -X78 -X79 -X80 -X81 -X82 -X83 -X84 -X85 -X86 -X87 -X88 -X89 -X90 -TW510 -W511 -W512 -TW503 -TW504 -W505 -TW501/2.7C -W502/2.3D -TW502/2.3D WIRING DIAGRAM ERS S40-400 ELSHEMA ERS S40-400 Dimension 230V 50Hz Material Quality/Specification Mass (kg) Revision note Rev by Rev Checked by Rev date (YYYY-MM-DD) Status Designer Checked by Date (YYYY-MM-DD) NIBE AB MARKARYO SWEDEN WIRING DIAGRAM ERS S40-400 ELSHEMA ERS S40-400 Plant Format Next sheet Sheet 1 Location Drawing no Rev 051262 7

Nibe ERS S40-400 - Electrical circuit diagram - 2

Item register

A

Accessories, 23

Adjusting ventilation, 14

Assembly, 11

C

Commissioning and adjusting, 18 Preparations, 18

D

Delivery and handling, 7

Assembly, 11

Installation, 11

Installation area, 11

Physical conguration

Left-handed version, 8

Right-handed version, 8

Removing the covers, 7

Supplied components, 7

Transport and storage, 7

Design of the HRV unit, 12

Dimensions and ventilation connections, 14

Disturbances in comfort, 22

Troubleshooting, 22

E

Electrical connection, 15

Connecting to main product, 15

DIP switch, 17

Energy labelling, 26

Exhaust air duct, 14

G

General ventilation connections, 14

I

Important information, 4

Recycling, 5

Inspection of the installation, 6

Installation area, 11

L

Left-handed version, 8

M

Menu system, 19

Mounting, 11

P

Physical conguration

Left-handed version, 8

Right-handed version, 8

Pipe and ventilation connections

Exhaust air duct, 14

Program settings, 19

R

Recycling, 5

Removing the covers, 7

Right-hand version, 8

s

Safety information

Inspection of the installation, 6

Serial number, 4

Start guide, 19

Start-up and inspection

Setting the ventilation, 18

Supplied components, 7

T

The design of the exhaust air module

List of components, 13

Transport and storage, 7

Troubleshooting, 22

V

Ventilation connections, 14

Adjusting ventilation, 14

Dimensions and ventilation connections, 14

General ventilation connections, 14

Ventilation ows, 14

Ventilation ow, 14

Contact information

DENMARKCZECH REPUBLICAUSTRIA

NIBE Energy Systems France SAS

Zone industrielle RD 28

NIBE Energy Systems Ltd

3C Broom Business Park,

Bridge Way, S41 9QG Chestereld

Tel: +44 (0)330 311 2201

info@nibe.co.uk

nibe.co.uk

NIBE-BIAWAR Sp. z o.o.

Al. Jana Pawla II 57, 15-703 BialystoBox 14

Tel: +48 (0)85 66 28 490 Hannabadsvägen 5, 285 21 MarkarydTel. +41 (0)58 252 21 00

biawar.com.pl Tel: +46 (0)

Tel: +46 (0)433-27 30 00 info@nibe.ch

info@nibe.se nibe.ch

nibe.se

For countries not mentioned in this list, contact NIBE Sweden or check nibe.eu for more information.

NIBE Energy Systems

Hannabadsvägen 5

Box 14

SE-285 21 Markaryd

info@nibe.se

nibe.eu

This is a publication from NIBE Energy Systems. All product illustrations, facts and data are on the available information at the time of the publication's approval.

NIBE Energy Systems makes reservations for any factual or printing errors in this publication