JUNG TKASVAL114WW - Security Camera

TKASVAL114WW - Security Camera JUNG - Free user manual and instructions

Find the device manual for free TKASVAL114WW JUNG in PDF.

📄 24 pages English EN Download 💬 AI Question
Notice JUNG TKASVAL114WW - page 6
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about TKASVAL114WW JUNG

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Security Camera in PDF format for free! Find your manual TKASVAL114WW - JUNG and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. TKASVAL114WW by JUNG.

USER MANUAL TKASVAL114WW JUNG

DCM Video outdoor station

1 to 4-gang

TK ASV AL 114 WW

TK ASV AL 114

TK ASV ES 114

2 to 8-gang

TK ASV AL 128 WW

TK ASV AL 128

TK ASV ES 128

JUNG TKASVAL114WW - 1

text_image R. Kandt C. Bonventre M. Gebhardt J. Kohlhaas

Table of content

Safety instructions....3

Application / Brief description....4

Application....4

Brief description....4

Device overview....5

Wiring and installation....6

Wiring example 6-wire technique ....6

Connecting diagram 7

Possible connection for a door release relay....7

Installation....7

Commissioning 10

Acoustic and optical signals, pressing buttons 10

Setting the button layout ....11

Bell button programming....13

Basic principle 13

Programming a bell button 13

Programming a second indoor station to a bell button (parallel call)....14

Deleting the programming 16

Parameters 17

Settable parameters....17

Setting and blocking AS-address 17

Setting and cancelling a programming block....17

Light switching function 17

Automatic light switching 17

Light switching....17

Nameplate illumination 17

Setting parameters with DIP switches 18

Labelling the nameplate....20

Fault identification, indication and querying 20

Fault sources....20

Explanation of terms and definitions ....21

General notes on the wiring in DCM video systems 22

6-wire operation....22

Cleaning....23

Technical data 24

Acceptance of guarantee....24

Safety instructions

JUNG TKASVAL114WW - Safety instructions - 1

Assembly, installation, and commissioning must only be carried out by a qualified electrician!

For work on systems with 230 V AC mains current the safety requirements of DIN VDE 0100 must be observed.

When installing DCM BUS systems the general safety rules for telecommunication systems in accordance with VDE 0800 must be observed:

  • separate cabling for high and low voltage lines
  • minimum distance of 10 cm for joint cabling arrangements,
  • use of separators between high and low voltage lines in joint cable ducts,
  • use of standard telecommunication cables, e. g. J-Y (St) Y with 0.8 mm ^2 cross section
  • existing cables (modernisation) with different cross sections may be used whilst taking account of the loop resistance.

JUNG TKASVAL114WW - Safety instructions - 2

Suitable lightning prediction must ensure that a voltage of 32 V DC will not be exceeded at the DCM BUS wires a and b.

Application / Brief description

Application

  • hands-free operation with high audio quality (full duplex)
  • release door calls
  • Start a video image at the video indoor station by means of pressing a bell button
  • switching light

Brief description

  • Camera with a resolution of 1.3 MP, detected area of 130^ , automatic screen adjustment, automatic switch over between day and night, automatic backlight compensation, automatic white fader, camera cover made of break-proof material
  • full duplex operation in combination with comfort indoor station
  • half duplex operation in combination with standard indoor station
  • high audio quality due to active noise suppression (noise and line echo cancellation)
  • AEC (Acoustic Echo Cancellation), electronic method for acoustic echo reduction
    • automatic calibration of the ambient and network conditions
    • high-quality sound and great speaker dynamics
    • volume adjustable
    • covers for push-buttons can be combined variably, 1- to 4-gang or 2- to 8-gang
  • acknowledge tone for bell button
  • acoustic status indication if system is occupied (existing communication)
    • automatic call cut-off
    • durable energy saving LEDs for labelling illumination
  • fault analysis due to different flashing of the LED labelling illumination
  • fault differentiation due to acoustic feedback signal when pressing a bell button
  • weather-proof loudspeaker
    • solid, robust metal faceplate
  • stainless steel flush mounted housing, adjustable installation frame
  • integrated dismounting protection
  • bell button configured for switching light (basic settings)
  • bell button switches light depending on brightness (automatic light)
    • brightness threshold adjustable
  • programming possible without access to flats
  • connection: 6-wire-technique
    • electret capacitor microphone
  • audio and video stations can be combined in the same installation
  • inscription fields can be labelled with the JUNG labelling tool (www.jung-label.de)

Device overview
JUNG TKASVAL114WW - Brief description - 1

text_image Faceplate Loudspeaker Camera and Light sensor Mounting hole Screw Inscription plate illumination Plug-in position for bell button Cover DIP switch Terminal description Terminals Cable entry Pluggable EEPROM-board Screw Microphone hole Bell button

Fig: TK ASV AL 114, without inscription plate

Wiring and installation

Wiring example 6-wire technique

The power supply units TK SV STG 60 REG + TK SV 2500 REG enable the connection of 8 indoor station + 8 parallel connected indoor station. Observe maximum output current!

JUNG TKASVAL114WW - Wiring example 6-wire technique - 1

flowchart
graph TD
    A["Video indoor station"] --> B["TKISA514A"]
    C["Video indoor station"] --> D["TKISA514A"]
    E["Video outdoor station"] --> F["G a b R P M V1 V2 TKASES114A"]
    G["Power supply & control unit"] --> H["AC 230 V~ 8VAC"]
    H --> I["Door release relay and illumination"]
    I --> J["AC 230 V~ >6Ω"]
    K["Floor bell button"] --> L["Ground"]
    M["Floor bell button"] --> N["Ground"]
    O["optional"] --> P["P"]
    Q["26VDC"] --> R["AC 230 V~"]
    S["AC 230 V~"] --> T["Ground"]

Connecting diagram Possible connection for a door release relay

Please use door release relay TK TR 24 EB.

Floating relay contact:

Max. AC 24 V, 2 A of external power supply

JUNG TKASVAL114WW - Connecting diagram Possible connection for a door release relay - 1

text_image 6 (a, b, P, M, V1, V2) TK ASV ES 114 A G a b R P M V1 V2 TKASES114A P R NC com H TKTR24EB >6 Ω

Installation

Flush mounted housing

  • Fasten the 4 delivered short hexagon screws (1) with a hexagon key.
  • Shut the unused cable entry holes with the delivered dummy plug.
  • Put the wires through the selected cable entry hole (2).
  • Connect the flush mounted housing into the wall. The edge of the housing has to be flush with the wall surface to enable, that the faceplate of the outdoor station fits flat on the wall.

Connection possibilities:

  • Connect the strap (3) of the housing with screws to the wall.
  • Attach with plaster by means of using plaster straps (4 metal sheets with holes, 4 screws and 4 nuts). These plaster straps can be connected on the reverse side of the housing to the housing straps (3).

JUNG TKASVAL114WW - Connection possibilities: - 1

text_image Technical diagram of a mechanical housing with numbered components and labeled parts

Flush mounted housing

Installation frame

The wall is plastered and the housing is installed flush with the plaster into the wall.

  • Unscrew the 4 hexagon screws until they stick out half length.
  • Put the wires through the cable entry hole of the installation frame (5).
  • Put the installation frame into the housing in that way, that the slots of the frame fit behind the screw heads.
  • Press the installation frame into the flush mounted housing and tighten the hexagon screws.

JUNG TKASVAL114WW - Installation frame - 1

natural_image Technical diagram of an electrical enclosure with internal wiring and mounting holes (no text or symbols)

Installation frame

Install faceplatePut the wires through the cable entry of the faceplate.Fasten the device with the delivered screws (1) and (2) into the installation frame.Put the bell button covers onto the plug-in position as required. Observe the top and bottom edge of the cover.Do not pinch the wires.First tighten the upper screw (1) after this the lower screw (2).JUNG TKASVAL114WW - Installation frame - 2
Connect the wiresTake off the connection block downwards.Attach the wires to the connection block in accordance with the terminal description.Plug on the connection block.Place the wires into the space under the connection block.Protruding wires disturb the installation of the inscription plate.JUNG TKASVAL114WW - Installation frame - 3Terminal descriptionIJUNG TKASVAL114WW - Installation frame - 4
Carry out the following steps before closing the device:commissioningcover configurationprogrammingadjusting parameterlabelling the inscription plate

Inscription field

- Put the labelled inscription foil (2) into the inscription field (1).

1 inscription field
2 inscription foil
3 gasket

- Close the opening with the gasket (3).

Pay attention of the gasket position.

Closing the device

  • Put the nameplate with the upper edge into the housing and snap the bottom edge into place.
  • The name plate should snap into place with a click.

Opening the device

  • Slide the opening tool into the slit under the nameplate until it engages.
  • Pull the opening tool out of the device together with the nameplate.

Opening tool

JUNG TKASVAL114WW - Opening the device - 1

text_image 3 2 ABC... 1 3 1

JUNG TKASVAL114WW - Opening the device - 2

natural_image Pure architectural diagram of a modern wall-mounted cabinet or enclosure with no text, numbers, or symbols

Commissioning

!JUNG TKASVAL114WW - Commissioning - 1 Please complete the full installation before you connect the system to the mains voltage!Do NOT connect V1 and V2 with the P-, M-, a- or b-wire. Even a connection for a quick moment will destroy the device.When connecting the video wires V1 (+) and V2 (-) observe polarity.If you can see a distorted image on the display, switch off the mains voltage and change the wires V1 and V2..

• Install all of the devices of the system completely.
- Check the a, b and P wires for short-circuit.
- Switch on the mains voltage.

The following functions are available without additional programming:

  • communication from the indoor stations to the outdoor station
  • door release function
  • light switching

Acoustic and optical signals, pressing buttons

Positive acknowledge toneJUNG TKASVAL114WW - Commissioning - 2Nameplate illumination On
Negative acknowledge tone (button already programmed)
Ring tone (from programming acknowledgement)
Prog2 tone (programming of the 2nd serial number begins)JUNG TKASVAL114WW - Commissioning - 3Nameplate illumination flashes: Programming mode0.5 s On / 0.5 s Off
NoProg tone (programming will be deleted if the button is released now)
ProgBlock toneJUNG TKASVAL114WW - Commissioning - 4Nameplate illumination flashes quickly: Parameter mode0.125 s On / 0.125 s Off
Occupied tone
Press button briefly (approx. 1s) and releaseJUNG TKASVAL114WW - Commissioning - 5Nameplate illumination pulse flashing: Fault mode0.175 s On / 0.825 s Off
Press button until ...
Release button

Setting the button layout

The button layout can be configured using the DIP switch.

To set the button layout, DIP switch 8 must be in the OFF position.

! If the button layout is not set for 1-gang and 2-gang buttons, there will be malfunctions during operation.

When the button layout is changed, all of the bell buttons have to be deleted. All bell buttons are assigned with the light switching function.

DIP switch cover

  • Open the device if necessary.
  • Remove the cover over the DIP switches.

JUNG TKASVAL114WW - DIP switch cover - 1

natural_image Diagram of a computer interface with labeled buttons and a key (no readable text or symbols)

Buttons

1-gang button

Button occupies 4 plug-in positions and covers 3 gaps.

2-gang button

Button occupies 2 plug-in positions and covers 1 gap.

4-gang button

Button occupies 1 plug-in position and does not cover any gap.

JUNG TKASVAL114WW - Buttons - 1

natural_image Blank white image with no visible content, text, or symbols

1-gang button

JUNG TKASVAL114WW - Buttons - 2
2-gang button

JUNG TKASVAL114WW - Buttons - 3
4-gang button

Button layout: Setting the DIP switches

Each DIP switch corresponds to one of the three or seven gaps between two plug-in positions.

If a button covers an gap, the switch must be set to ON.

If configured completely with 4-gang buttons, all DIP switches must be in the OFF position.

JUNG TKASVAL114WW - Button layout: Setting the DIP switches - 1

text_image OFF ON 1 ON 2 covered gap 3 OFF: gap not covered 4 5 6 7 8 not used Switch 8: OFF Define button layout

JUNG TKASVAL114WW - Button layout: Setting the DIP switches - 2

flowchart
graph TD
    A["Start"] --> B["Step 1"]
    B --> C["Step 2"]
    C --> D["Step 3"]
    D --> E["Step 4"]
    E --> F["Step 5"]
    F --> G["Step 6"]
    G --> H["Step 7"]
    H --> I["Step 8"]
    I --> J["End"]
    style A fill:#f9f,stroke:#333
    style J fill:#bbf,stroke:#333

Activating the button layout

  • To activate the new button layout, the buttons must be programmed as bell buttons (assignment of an indoor station).
  • If a 2-gang or 1-gang button is to be used as a light button, this button must first be programmed as a bell button and then deleted.

Fitting the button

- Fit the DCM buttons according to the configuration. Note the mechanical encoding of the buttons. Press lightly on the buttons to snap them in.

Bell button programming

Basic principle

  • All of the devices on the DCM BUS have a unique serial number.
  • When a bell button is programmed, the serial number of an indoor station is assigned and saved in the EEPROM of the outdoor station. 1 or 2 indoor stations (serial numbers) can be assigned and triggered with each bell button.
  • If no serial number is assigned to a bell button (state at delivery / serial number deleted), the light can be switched on by pressing this button.

Programming a bell button

Make sure that the indoor stations are connected to the DCM BUS and the mains voltage is switched on (the LED on the power supply and control unit is illuminated).

!

The button layout must be set before the bell buttons are programmed.

1

The programming must be deleted before a previously programmed bell button can be reprogrammed.

1Initiation
press briefly LED flashesOutdoor station in programming mode: flashes, programming mode of the system is switched on
2aBy means of communication button at the indoor station
Press communication button of the indoor station briefly (communica- tion is established with the outdoor station)Press button briefly ... positive acknowledge tones sounds at the outdoor and indoor stations 1)

1) If instead a programming block tone is audible, the outdoor station has been given a programming block. The programming block can only be cancelled using the commissioning software.

2bBy means of floor button (indoor station is not accessible)
Press floor bell button briefly two times in succession, a ring tone is sounded each timePress button briefly ... a positive acknowledge tone sounds at the outdoor station and a ring tone sounds at the indoor station
Repeat steps until all bell buttons have been programmed
3Finishing

1) If instead a programming block tone is audible, the outdoor station has been given a programming block. The programming block can only be cancelled using the commissioning software.

Programming a second indoor station to a bell button (parallel call)

The parallel call triggers 2 indoor station from one bell button of the outdoor station. The floor button only triggers the hard-wired indoor station.

To give the bell button and floor button the same functionality, the parallel function must be used. In this case several indoor stations respond both to the same bell button and to the same floor button. The parallel function must be set using the commissioning software.

Note: Repeated programming of an already programmed bell button always only changes the second serial number. If you wish to change the serial number that was programmed first, you have to delete both serial numbers and then reprogram both serial numbers again.
1Initiation
JUNG TKASVAL114WW - Programming a second indoor station to a bell button (parallel call) - 1JUNG TKASVAL114WW - Programming a second indoor station to a bell button (parallel call) - 2 JUNG TKASVAL114WW - Programming a second indoor station to a bell button (parallel call) - 3
press briefly LED flashes

2a By means of communication button at the indoor station
JUNG TKASVAL114WW - Programming a second indoor station to a bell button (parallel call) - 4

JUNG TKASVAL114WW - Programming a second indoor station to a bell button (parallel call) - 5

text_image Press button until a Prog2 tone and a NoProg tone and ... ... a positive acknowledge tone sounds at the out- door and a ring tone at the indoor stations¹)

Press communication button of the indoor station briefly (communication is established with the outdoor station)

JUNG TKASVAL114WW - Programming a second indoor station to a bell button (parallel call) - 6

2b By means of floor bell button (indoor station is not accessible)
JUNG TKASVAL114WW - Programming a second indoor station to a bell button (parallel call) - 7

flowchart
graph LR
    A["Press floor bell button"] --> B["+"]
    B --> C["Press button until a Prog2 tone and a NoProg tone and ..."]
    C --> D["... a positive acknowledge tone sounds at the outdoor station and a ring tone sounds at the indoor station 1)"]
    D --> E["release"]

Repeat steps until all ring tones have been programmed

3 Finishing
JUNG TKASVAL114WW - Programming a second indoor station to a bell button (parallel call) - 8

flowchart
graph LR
    A["Press briefly"] --> B["LED lights up"]
    B --> C["Outdoor station in idle mode\nProgramming mode of the system is switched off"]

1) If instead a programming block tone is audible, the outdoor station has been given a programming block. The programming block can only be cancelled using the commissioning software.

Deleting the programming

Before a bell button can be programmed, an existing programming has to be deleted.

1Initiation
JUNG TKASVAL114WW - Deleting the programming - 1JUNG TKASVAL114WW - Deleting the programming - 2JUNG TKASVAL114WW - Deleting the programming - 3press briefly LED flashes Outdoor station in programming mode: flashes, programming mode of the system is switched on
2Execution
if bell button programmed:JUNG TKASVAL114WW - Deleting the programming - 4 JUNG TKASVAL114WW - Deleting the programming - 5JUNG TKASVAL114WW - Deleting the programming - 6if bell button not programmed:Press until a delete tone sounds after 6 s1) release
3Finishing
JUNG TKASVAL114WW - Deleting the programming - 7JUNG TKASVAL114WW - Deleting the programming - 8JUNG TKASVAL114WW - Deleting the programming - 9press briefly LED lights up Outdoor station in idle modeProgramming mode of the system is switched off

1) If instead a programming block tone is audible, the outdoor station has been given a programming block. The programming block can only be cancelled using the commissioning software.

Parameters

Settable parametersFactory pre-settingCan be set with DIP switchCan be set with the commissioning software.
AS-addressnotblocked
Communication time 60 s x x
Door release time 3 s x
Acknowledge tone type Standard x
Acknowledge tone volume medium x
Voice volumemedium x
Programming block on/offoffx
Light switching function via the door release function of the indoor stations on/offoffx
Talking only after incoming door calloffx
Switching threshold for the automatic light function dependent on outdoor lightmediumx

Setting and blocking AS-address

For operation with multiple outdoor stations, a separate AS-address (0 - 63) must be set for each outdoor station. This produces an unambiguous assignment of the outdoor stations.

Setting and cancelling a programming block

When a programming block is set, no bell button programming can be performed. The programming block must be reset before reprogramming.

At the same time, when the programming block is cancelled, the light switching function and talking only after incoming door call are cancelled and the acknowledge tone is reset to the factory pre-setting.

Light switching function

Allows double assignment of the door release button to the indoor stations. When the light switching function is activated, door released is only actuated when existing communication is active. Without existing communication the light will be switched on. Thus the function button of the indoor stations remains available for other functions.

Automatic light switching

Brightness-dependent light switching when the bell button is triggered.

The function can be deactivated, adjusted in 6 brightness levels or switched independent of the brightness.

Light switching

The light can be switched on manually via non-programmed bell buttons or the function button of the indoor stations.

In the state of delivery the function button of the indoor station is assigned with this function.

Nameplate illumination

Brightness-independent switching of the nameplate illumination

The state at delivery is always ON.

Setting parameters with DIP switches

1. Select parameter

Set DIP switches 1, 2 and 3, that the parameter to be changed has been selected.

2. Set value

Set switches 4, 5 and 6 in accordance with the desired value.

3. Activate parameter mode

Set switch 8 to ON.

Nameplate illumination flashes quickly (0.125 s On / 0.125 s Off).

4. Apply parameter

Pressing any bell button saves the desired value for the parameter being set. An acknowledge tone sounds as a confirmation.

5. Deactivate parameter mode

Set switch 8 to OFF.

Nameplate illumination: ON.

Note:

To set additional parameters, repeat steps

1 – 5. Otherwise continue with step 6.

6. Set the original button layout

After setting the parameters, reset the DIP switches according to the button layout.

JUNG TKASVAL114WW - Set the original button layout - 11 2 3
JUNG TKASVAL114WW - Set the original button layout - 2JUNG TKASVAL114WW - Set the original button layout - 3
JUNG TKASVAL114WW - Set the original button layout - 4JUNG TKASVAL114WW - Set the original button layout - 5
JUNG TKASVAL114WW - Set the original button layout - 6
JUNG TKASVAL114WW - Set the original button layout - 7JUNG TKASVAL114WW - Set the original button layout - 8
JUNG TKASVAL114WW - Set the original button layout - 9

DIP switch table for parameter setting

JUNG TKASVAL114WW - DIP switch table for parameter setting - 1

text_image ON 1 2 3 4 5 6 7 8
Parameter selection123Parameter
OFFOFFOFFTotal volume MIC/LSP (Vol)
ONOFFOFFAcknowledge volume (AVo)
OFFONOFFDoor release time (DRt)
ONONOFFCommunication time (Cot)
OFFOFFONAutomatic light switching threshold (ALT)
ONOFFONNameplate illumination threshold (NIT)
OFFONONnot assigned
ONONONnot assigned
Parameter value456VolAVoDRtCotALT
OFFOFFOFFMINMIN0.5s15sOFF
ONOFFOFF111s30s
OFFONOFF222s45s22
ONONOFF333s60s33
OFFOFFON444s75s44
ONOFFON555s90s55
OFFONON666s105s
ONONONMAXMAX7s135sONON
7not assigned
8DIP switch function
ONSet parameter
OFFDefine button layout

Abbreviations:

Vol Total volume of microphone / loudspeaker

AVo Volume of acknowledge tones

DRt Door release time for a connected door release relay, Art. No.: TKTR24EB

Cot Communication time until the existing communication is switched off automatically

ALT Switching threshold for the automatic light function

NIT Nameplate illumination threshold

Labelling the nameplate

Use the JUNG labelling tool to label the nameplates of your outdoor stations. You will find it at the following Internet address:

www.jung-label.de.

  1. In the "Template" field, select the ref.-number of your outdoor station, e.g. TK AS AL 114 A WW. Arrange the template to suit your requirements.
  2. Using a laser printer, print the nameplates on the supplied special foil, Ref. No.: TK 60 FO.
  3. Insert the foil into the nameplate.

! Use only the supplied foil to label the nameplates! Jung Ref.-No.: TK 60 FO.

Fault identification, indication and querying

  • Faults are signalled visually and acoustically (single fault tone and continuous flashing of the light strip).
  • The fault type can be queried by pressing any bell button, the fault tone is sounded again.

Fault sources

Fault sourcesNameplate illumination indicationFault toneElimination
No EEPROMJUNG TKASVAL114WW - Fault identification, indication and querying - 1JUNG TKASVAL114WW - Fault identification, indication and querying - 2Insert EEPROM, switch mains voltage on again!
a and P wires interchangedJUNG TKASVAL114WW - Fault identification, indication and querying - 3Exchange a and P wires, device back to idle mode in a few seconds
"a" wire not connectedJUNG TKASVAL114WW - Fault identification, indication and querying - 4Connect a wire, device back to idle mode in a few seconds
Button sticks (pressed > approx. 20 s)Outdoor station in fault mode: flashesJUNG TKASVAL114WW - Fault identification, indication and querying - 5Release button, device back to idle mode in a few seconds

Explanation of terms and definitions

AS-addressEvery outdoor station is assigned with an outdoor station address. The address enables the differentiation between the various installed outdoor station. Selective communication or door release of e.g. main- or side entrance can be realised.
Ready for operationIncoming door call - You can hear a ring tone and the LED at the communication button flashes. You can activate a communication with the outdoor station by means of a short push of the communication button.
Hands-free operation (Full duplex)Simultaneous communication in both directions.
Door callYou release a door call at the assigned indoor station by means of pushing the bell button. A bell button can release a door call at two indoor stations (parallel call).
Internal call An indoorstation can call another assigned indoor station for an internal communication.
Automatic light switching Programming at the outdoor station.The light will be switched depending on the ambient brightness when you push the bell button of the outdoor station. The limited brightness value is adjustable.
Light switchingThe function button of the indoor station is assigned with the function "light switching" (factory setting). A bell button of the outdoor station will switch the light, if the bell button is not assigned to an indoor station.
Light switching function Programming at the power supply and control unit.This door release button of the indoor station can be assigned with a second function, when the light switching function is activated: You first have to push the communication button before you can release the door with the door release button. Without pushing the communication button you will switch the light with the door release button.
Parallel call A secondindoor station can be programmed to a bell button of the outdoor station.
Parallel functionMultiple indoor station can respond to one bell button of the outdoor station or the floor bell button. Each further indoor station respond just as the first indoor station.
Programming mode The system has to be in programming mode to assign the indoor stations to the desired bell buttons of the outdoor station.
Programming lock Protection against unauthorized programming. With active programming lock no bell button can be programmed.
Acknowledge tone Acoustical confirmation
Idle mode The device is ready for a door call or other operation.
Call diversionAn incoming door call will be forwarded from one indoor station to another indoor station. The call diversion has to be activated with the function button. The illuminated LED of the function button indicates the activated call diversion.
Talking mode A communication between indoor and outdoor station will be activated by means of pushing the communication button. Die LED of the communication button is illuminated.The LED of the communication button is flashing, when another indoor station is already communicating with the outdoor station.After elapsed talking time, activating the door release or pushing the communication button again, the device turns back into idle mode.
Talking only after incoming door callA communication between indoor and outdoor station can only be activated after an incoming door call.
Talking time The communication between indoor and outdoor station will be interrupted after a pre-defined talking time (60 s factory setting). The talking time is adjustable.
Control function Command for the control various relays in the door communication system.
Sub door callThe sub door call enables to assign 4 additional bell button of the outdoor station to the same indoor station. Each bell button can be assigned to a separate ring tone (e.g.: individual ring tones for each family member).
Automatic door releaseThe door release relay will be activated by means of pushing the bell button. The automatic door release can be activated/deactivated with the function button of the indoor station. The LED of the function button indicates the status.LED ON = automatic door release activatedLED OFF = automatic door release deactivated
Door release time The door release relay can be activated for an adjusted time.
Voice memo-functionRecord and play a voice memo (message) up to a length of 30 s.

General notes on the wiring in DCM video systems

6-wire operation

The 6-wire operation is the standard operation. A video system requires 2 separate ground potential (b und M).

The cabling depends on the building situation and will only be limited by the max. possible cable length.

  • Consider the cable length: The loop resistance a-b and M-P shall not exceed a max. of 8 Ω (see table).
  • When loop resistance > 8 Ω: Extend the cable diameter by means of using multiple twisted pairs
    • line or star-shaped wiring
  • Do not install more then 20 Video indoor stations in one line. For systems with more then 20 video stations consider installation of video distributor (TK VV 2 REG or TK VV 2 U)
  • Up to 64 outdoor stations (max 16 Video outdoor stations) and unlimited indoor stations can be installed with the adequate power supply & control unit (avoid reverse polarity)

Table: Loop resistance

Wire length of a-b / M-P in mCross section0.6 mm 0.8 mm
Loop resistance in Ω
10 1.22 0.69
20 2.45 1.38
30 3.67 2.07
40 4.90 2.76
50 6.12 3.44
60 7.35 4.13
70 4.82
80 5.51
90 6.20
100 6.89

Principle of loop resistance Measuring loop resistance

Rule:

No door communication device shall have a longer distance from the power supply & control unit than 8 Ohm!

Rule:

Turn OFF 230 V / 50 Hz of the VS.

Connect a and b short circuit at the VS.

All other devices do not disturb the measuring process and remain connected.

JUNG TKASVAL114WW - Principle of loop resistance Measuring loop resistance - 1

flowchart
graph TD
    AS["AS"] -->|max. 8 Ohm| VS["VS"]
    VS -->|a-b/ M-P| AS
    VS -->|max. 8 Ohm| IS["IS"]
    IS -->|a-b/ M-P| VS

8 Ohm:

JUNG TKASVAL114WW - Principle of loop resistance Measuring loop resistance - 2

flowchart
graph TD
    AS["AS"] -->|a| VS["VS"]
    VS -->|b| IS["IS"]
    IS -->|b| Ohm["Ohm"]
    Ohm -->|c| IS
    IS -->|c| Ohm
    style AS fill:#f9f,stroke:#333
    style VS fill:#ccf,stroke:#333
    style IS fill:#cff,stroke:#333
    style Ohm fill:#ffc,stroke:#333

65 m wire length AS-VS (IS-VS) at a cross section of 0.6 mm

115 m wire length AS-VS (IS-VS) at a cross section of 0.8 mm

AS. Outdoor station

IS: Indoor station

VS: Power supply and control unit

Cleaning

JUNG TKASVAL114WW - Cleaning - 1

Avoid the penetration of water into this device!

Do not use any aggressive or abrasive cleaning supplies!

Please clean the device with a dry or slightly moist rag. Intense dirt can be removed with a mild cleaning supply.

Technical data

Supply voltage: +24 V DC ± 8 % (Power supply & control unit)

24 V (a-b) / 26 V (P-b) in idle state

Dimensions, 1 to 4-gang (W x H x D):

Front plate 178.5 x 226 x 4 mm (Material incl. gasket)

DCM UP flush box 134 x 183 x 40 mm

Dimensions, 2 to 8-gang (W x H x D):

Front plate 178.5 x 314 x 4 mm (Material incl. gasket)

DCM flush box 134 x 271 x 40 mm

Labelling field (W x H):

1 to 4-gang 71 x 85 mm

2 to 8-gang 71 x 173 mm

Input current: I(a) = 0,1 mA, I(P) = 26 mA in idle state

Max. input current: I(amax) = 14 mA, I(Pmax) = 150 mA

Protection level: IP44, according to DIN EN 50486

Admissible ambient temperature: -20 °C ... +50 °C

Operation humidity: 0 to 80 % r. h.

Installation height: Recommended 1.50 m

Acceptance of guarantee

We accept the guarantee in accordance with the corresponding legal provisions.

Please return the unit postage paid to our central service department giving a brief description of the fault:

ALBRECHT JUNG GMBH & CO. KG

Service-Centre

Kupferstr. 17-19

44532 Lünen

Germany

Service-Line:0 23 55 . 80 65 51

Fax: 0 23 55.80 61 89

The €-sign is a free trade sign addressed exclusively to the authorities and does not include any warranty of any properties.

Technical subjects to change.

EN_PI_TKASxx

A Art0030823 1v04AP.doc

02/2010

0024099700

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : JUNG

Model : TKASVAL114WW

Category : Security Camera