Energy-400 D90 - Energy meter Vemer - Free user manual and instructions
Find the device manual for free Energy-400 D90 Vemer in PDF.
| Product Type | Three-phase static energy meter, direct connection, class 1 |
| Brand | Vemer |
| Model | Energy-400 D90 |
| Dimensions (Width) | 7 DIN modules (126 mm) |
| Dimensions (Height x Depth) | 90 mm x 70 mm (typical) |
| Weight | Approximately 200 g |
| Power Supply Voltage | 3x230/400 V (-15%/+10%) |
| Operating Frequency | 50/60 Hz |
| Maximum Current (Continuous) | 100 A (class 1) |
| Minimum Start-up Current | 10 mA |
| Power Consumption | <2.5 VA |
| Operating Temperature Range | -10 °C to +45 °C |
| Relative Humidity | 10% to 90% non-condensing |
| Display Type | LCD, 7+5 digits |
| Precision Class | 1 (EN 62053-21) |
| Pulse Output | Opto-insulated, 9-24 VDC, 30 mA max, 100 ms duration |
| Protection Degree | IP20 (enclosure), IP51 (front) |
| Color | RAL 7035 gray |
| Standards | EN 62053-21, EN 61010-1, EN 62052-11 |
| Connection Type | Direct insertion, max conductor 25 mm² |
| Installation | DIN rail mount in electrical panel |
| Safety | Installation by qualified operator; overcurrent protection upstream required |
| Maintenance | Clean with dry cloth; no user-serviceable parts |
Frequently Asked Questions - Energy-400 D90 Vemer
User questions about Energy-400 D90 Vemer
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Energy meter in PDF format for free! Find your manual Energy-400 D90 - Vemer and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. Energy-400 D90 by Vemer.
USER MANUAL Energy-400 D90 Vemer
4-wire (3 phases plus neutral) or 3-wire (without neutral)
DESCRIPTION

MAXIMUM MEASUREMENT ERROR

line
| Time | Value | |------|-------| | 0.5 A | 1.5% | | 1 A | 0% | | 10 A | -1% | | 100 A | -1.5% |(1) Indetermined error zone
User Manual
DIRECT CONNECTION ENERGY METER
Read all instructions carefully
■ Static meter with direct insertion to measure the the consumption of active energy in three-phase systems with precision class 1 (EN 62053-21).
SAFETY INSTRUCTIONS
To guarantee correct installation, observe the following instructions:
1) The appliance must be installed by a qualified operator
2) The appliance must be installed in an electrical panel which, after installation, leaves terminals inaccessible.
3) A protection device against over-currents must be installed in the electrical system
upstream of the energy meter
4) Connect the instruments as shown in the diagrams opposite
5) Before making contact with terminals, ensure that conductors to be connected to the
appliance are not live
Code
Code VN08
IN50
Description
Three-phase energy meter
TECHNICAL SPECIFICATIONS
• NPower supply voltage: N3x230 (400) V (-15%/+10%)
• Operating frequency: N50/60 H
- Basic cu
• Maximum current: NI
• Maximum overload in continuos use maintaining class 1: 100A
• Minimum start-up current
• Consumption: N<2,5 VA
• Operating temperature:
• Relative humidity:
- Connection type:
=10A
MAX = 90 A
use maintaining class 1: 100A
mA
[Non-Text]
-10 ÷ +45 °C
10% ÷ 90% non-condensing
direct for current conductors with galvanic isolation between
voltage and current terminals. By direct insertion of the
current conductor vertically into the case
maximum diameter of lead 25 sqmm
maximum diameter of through cable 12.5 mm
optoinsulated, open-conector type pulse duration 100 ms + 15%
pulse duration 100 ms ± 15%
pulse voltage 9÷24 VDC ± 10% switchable output current 30 mA max
switchable output
green = power on
rod - flashing at 10Wh frequency
yellow = wrong connection
class 1 (EN 62053-21)
LCD 7 + 5 digit
10 Wh from 000.00 kWh to 999.99 kWh
100Wh from 1000.0 kWh to 9999.9 kWh
0.1 kWh from 000000.0 kWh to 999999.9 kWh
1 kWh from 1000000 kWh to 9999999 kWh
4KV between output pulse and all other terminals
4kV between accessible parts (front) and all other terminals
7 DIN, RAL 7035 gray
IP20/IP51 on the front.
DEVICE DESCRIPTION
1) Display box of total energy
2) Display box of partial energy
3) Green LED: when lit it indicates power is on
4) Red LED: every flash corresponds to an energy count of 10Wh
5) Yellow LED: when lit it indicates wrong connection
6) Optoinsulated pulse output
8) Perforations for direct connection of wires to be metered
OPERATION
- When the energy meter is turned on the main page is displayed, representing the total energy count on the 7-digit upper block and the partial energy count on the 5-digit lower block. The resolution of each meter is automatically updated as soon as the scale-end is reached. If the YELLOW LED stays on after the implement was powered, check the installation for connection errors (cfr. "Connection errors") section.
- To display the total energy reading only, press the "Sel" key: this meter cannot be set to zero
- To display the partial energy reading, press the “Sel” key again: this meter is zeroed automatically as soon as the end of the scale is reached (9999.9 kWh); it can also be set to zero manually anytime by holding the “Sel” key pressed for more than 4 seconds
- To return to the main page reading both meters (total and partial), press the “Sel” key again.


Total reading

Partial reading
- Backlighting is enabled by default: it is switched on each time a key is pressed and stays on for 30 seconds after the last key was pressed. In order to enable/disable backlight while on the main page, hold "Sel" key pressed for at least 4 seconds: ON/OFP backlight status will be displayed for a couple of seconds, after which the main page will return.

Backlight status
CONNECTION ERRORS
During the first 3 minutes after power-up, a connection check-up is automatically carried out to detect any connection errors: the implement will light up the YELLOW LED if the energy at one or more phases appears to be negative.
In this case, for further details on the actual error type go to the total energy page and hold the "Sel" key down for longer than 4 seconds, until the "tESt" reading appears.
Wrong connection is indicated by a negative energy reading (E1 and/or E2 and/or E3) followed by the "Error" message.

PHASE 1 error
E1 is negative

PHASE 2 error
E2 is negative

PHASE 3 error
E.3 is negative

PHASE 1 and 2 error
E1 and E2 are negative

PHASE 1 and 3 error
E1 and E3 are negative

PHASE 2 and 3 error
E2 and E3 are negative
TEST

PHASE 1, 2 and 3 error
E1, E2 and E3 are
negative
The test can be performed anytime by simply repeating the above steps.
Warning: to restore correct meter operation after an error reading has been displayed, switch the meter off, check connection of phases (sequence of phases R, S, T) and current; then power the meter up.
REFERENCE STANDARDS
Conformity to European Community directives:
2006/95/EC (Low Voltage)
2004/108/EC (E.M.C.)
is declared according to the following standards:
■ Safety: EN 61010-1
■ Electromagnetic compatibility: EN 62052-11 and EN62053-21