THQP130 - Circuit Breaker GE - Free user manual and instructions
Find the device manual for free THQP130 GE in PDF.
Pick your language and provide your email: we'll send you a specifically translated version.
| Product Type | Miniature Circuit Breaker |
| Brand | GE (General Electric) |
| Model | THQP130 |
| Number of Poles | 1-Pole |
| Amperage Rating | 30 A |
| Voltage Rating | 120/240 V AC |
| Interrupting Capacity | 10 kAIC @ 120 V |
| Trip Type | Thermal-Magnetic |
| Mounting Type | Plug-in |
| Dimensions (H x W x D) | 3.0 x 0.5 x 2.25 in |
| Weight | 0.35 lb |
| Wire Size | AWG #14 to #8 |
| Terminal Type | Screw terminals |
| Compatibility | GE load centers (THQ and THQB series) |
| Operating Temperature | -20 to 60 °C |
| Safety Features | Overload and short-circuit protection |
| Certifications | UL Listed, CSA Certified |
| Maintenance | Periodic visual inspection for damage |
| Cleaning | Wipe with a dry cloth; no solvents |
| Repairability | Non-repairable; replace if tripped or faulty |
Frequently Asked Questions - THQP130 GE
What is the amp rating of the GE THQP130?
The GE THQP130 is rated for 30 amps at 120/240 V AC, suitable for branch circuit protection.
How many poles does the THQP130 have?
It is a 1-pole circuit breaker, commonly used for 120 V branch circuits in residential and commercial load centers.
Can I use the THQP130 in a Siemens or Square D panel?
No, the THQP130 is designed specifically for GE load centers such as THQ and THQB series. Using it in other brand panels is unsafe and violates UL compatibility listings.
What is the interrupting capacity of the THQP130?
The interrupting rating is 10,000 AIC (amperes interrupting capacity) at 120 V AC, ensuring reliable short-circuit protection.
How do I install this breaker?
Turn off the main power and remove the panel cover. Then snap the breaker onto the bus bar with firm pressure. Connect the circuit wires to the terminal screws and tighten to the manufacturer's specified torque.
Does the THQP130 offer GFCI or AFCI protection?
No, the THQP130 is a standard thermal-magnetic breaker without ground-fault or arc-fault protection. For those functions, use a GFCI or AFCI breaker model.
What wire size can be used with this breaker?
The THQP130 accepts AWG #14 to #8 copper wire, with a typical combination rating for 60/75°C terminals. Always follow the NEC and local codes.
How do I reset a tripped THQP130?
Move the handle to the OFF position, then back to ON. If it trips immediately, there is likely a sustained overload or short circuit that must be investigated.
Where can I download the manual?
You can download the free user manual for the THQP130 in PDF format from notice-facile.com. The manual contains installation, operation, and safety information.
What are the dimensions of the THQP130?
The compact breaker measures approximately 3.0 in height x 0.5 in width x 2.25 in depth, making it ideal for tight spaces in load centers.
User questions about THQP130 GE
0 question about this device. Answer the ones you know or ask your own.