📄 55 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice IFM PG1707 - page 4
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Electronic Pressure Sensor
Measuring Range 0 to 100 bar (relative)
Output Signal 4-20 mA analog + IO-Link
Supply Voltage 18-32 V DC (SELV/PELV)
Protection Rating IP67
Process Connection G1/4 internal thread
Electrical Connection M12x1 connector, 4-pin
Operating Temperature -25 to +80 °C
Housing Material Stainless steel 316L
Display 3-digit LED, red/green
Switching Function NO/NC programmable, hysteresis
Accuracy ±0.5% of full scale
Dimensions Length 80 mm, Ø 30 mm
Weight Approx. 120 g
Power Consumption < 1 W
Installation Any position, zero point adjustment
Maintenance Wipe with damp cloth, no glass cleaner
Spare Parts Seals, connectors available
Repair Factory repair service, replaceable
Compliance CE, RoHS, EMC 100-4-2/3

Frequently Asked Questions - PG1707 IFM

How do I set the switching output on the PG1707?
Press the MODE button to enter the menu, then use the arrow keys to select SP1 (set point 1) and adjust the value with the arrow keys. Confirm with ENTER.
What is the maximum pressure I can measure with the PG1707?
The PG1707 has a measuring range of 0-100 bar. Do not exceed 150 bar overload pressure to avoid damage.
How should I wire the M12 connector?
Pin 1 = V+ (18-32 V DC), Pin 2 = 4-20 mA output, Pin 3 = GND, Pin 4 = IO-Link. Use a shielded cable for best performance.
What happens if the sensor is exposed to overpressure?
The sensor can withstand up to 150 bar without damage. Above that, the internal diaphragm may rupture, so install a pressure relief valve if necessary.
Can I use the PG1707 in food and beverage applications?
No, the standard PG1707 is not designed for hygienic applications. It lacks the required EHEDG certification. Use IFM’s PG21xx series for food grade.
How do I perform a zero point calibration?
Vent the pressure port to atmospheric pressure, press MODE and hold for 3 seconds to enter calibration mode, then select ZERO. The display will show 0.0.
What does the LED display show?
The 3-digit display shows the current pressure value in bar. During setup it shows the parameter code and value. A green backlight indicates normal operation, red indicates an alarm.
Is the PG1707 compatible with IO-Link masters?
Yes, it supports IO-Link 1.1. Connect Pin 4 to an IO-Link master and configure parameters remotely using IODD software.
How do I clean the PG1707?
Use a soft damp cloth with mild soap or isopropyl alcohol. Do not use abrasive cleaners or immerse the sensor. Dry with a lint-free cloth.
What should I do if the output signal is not stable?
Check for electromagnetic interference from nearby motors or cables. Ensure the shield is connected and the supply voltage is stable. Also verify the process connection is not leaking.

User questions about PG1707 IFM

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Uncategorized in PDF format for free! Find your manual PG1707 - IFM and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. PG1707 by IFM.

USER MANUAL PG1707 IFM

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : IFM

Model : PG1707

Category : Uncategorized