ADAM-5018P-AE - Module d'entrées/sorties industrielles Advantech - Free user manual and instructions
Find the device manual for free ADAM-5018P-AE Advantech in PDF.
Pick your language and provide your email: we'll send you a specifically translated version.
| Product Type | Analog Input Module |
| Model | ADAM-5018P-AE |
| Brand | Advantech |
| Number of Channels | 8 differential analog inputs |
| Resolution | 16-bit |
| Input Ranges | ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA (with external resistor) |
| Sampling Rate | 10 samples per second per channel |
| Communication Interface | RS-485, Modbus RTU |
| Isolation | 3000 VDC |
| Power Supply | 10 to 30 VDC |
| Power Consumption | 1.2 W typical |
| Dimensions (W x H x D) | 72 x 111 x 26 mm |
| Weight | 200 g |
| Operating Temperature | -25°C to +75°C |
| Storage Temperature | -40°C to +85°C |
| Humidity | 5 to 95% non-condensing |
| Protection | Overvoltage, reverse polarity, ESD |
| Mounting | DIN rail |
| Primary Functions | Data acquisition, signal conditioning, remote monitoring |
| Maintenance | Clean with dry cloth; do not use solvents or water |
| Safety Precautions | Disconnect power before wiring; observe voltage limits |
| Spare Parts and Repairability | No user-serviceable parts; contact Advantech for repairs |
Frequently Asked Questions - ADAM-5018P-AE Advantech
How do I connect the ADAM-5018P-AE to a PC?
Use an RS-485 to USB converter (e.g., ADAM-4561) and connect via Modbus RTU protocol. Set the module address (default 01) using DIP switches.
What software is compatible with this module?
Advantech ADAM-4000-5000 Utility, Modbus master software (e.g., ModScan), or any SCADA system supporting Modbus RTU.
Can I measure 4-20 mA current signals?
Yes, with an external 250 Ω precision resistor connected across the input terminals. The module measures the resulting voltage.
What is the maximum cable length for RS-485?
Up to 1200 meters at 9600 baud. Use twisted-pair shielded cable and terminate the line with 120 Ω resistors.
How do I change the Modbus baud rate?
Use the ADAM-4000-5000 Utility to configure baud rate (1200 to 115200 bps) and data format. Default is 9600, 8, N, 1.
Does the module provide isolation between channels?
No, the isolation is between the input and the RS-485 communication port (3000 VDC). Channels share a common ground.
What is the accuracy of the analog inputs?
Accuracy is ±0.1% of full scale at 25°C, with a temperature drift of ±50 ppm/°C.
Can I power the module using the RS-485 cable?
No, the ADAM-5018P-AE requires a separate 10-30 VDC power supply. The RS-485 connection is only for data.
How do I reset the module to factory defaults?
Set all DIP switches to OFF and cycle power. The module will reset to address 01, 9600 baud, 8, N, 1.
What is the update rate for all channels?
The module samples each channel sequentially at 10 Hz, so the total update time for 8 channels is 0.8 seconds.