Phoenix Contact

MACX MCR-EX-TC-I - Uncategorized Phoenix Contact - Free user manual and instructions

Find the device manual for free MACX MCR-EX-TC-I Phoenix Contact in PDF.

📄 58 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice Phoenix Contact MACX MCR-EX-TC-I - page 5
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Isolated Temperature Transducer with Ex Approval
Input Thermocouple Types J, K, T, R, S, B, E, N
Output Signal 4-20 mA (2-wire)
Supply Voltage 24 V DC (19.2 V to 30 V DC)
Power Consumption ≤ 1.5 W
Electrical Isolation 3-way isolation (input/output/power supply) with 2.5 kV test voltage
Accuracy ≤ 0.1% of span (typical)
Ambient Temperature Range -20°C to +60°C
Dimensions (W x H x D) 17.5 mm x 99 mm x 114.5 mm
Weight Approx. 150 g
Housing Material Polyamide (PA), UL 94 V0
Degree of Protection IP20
Mounting On 35 mm DIN rail per EN 60715
Ex Approval ATEX and IECEx for Zone 2 (II 3G Ex ec IIC T4 Gc)
Configuration Via DIP switches on device side
Cleaning Use a dry, lint-free cloth; do not use solvents
Repairability Device is not field-repairable; replace entire unit upon failure

Frequently Asked Questions - MACX MCR-EX-TC-I Phoenix Contact

What type of thermocouple can be connected to the MACX MCR-EX-TC-I?
The device supports standard thermocouple types J, K, T, R, S, B, E, and N. The range depends on the selected type.
What is the output signal of this transducer?
The output is a linear 4-20 mA current signal (2-wire) proportional to the measured temperature.
Is the MACX MCR-EX-TC-I suitable for use in hazardous areas?
Yes, it has ATEX and IECEx approval for use in Zone 2 (gas) applications, with certification Ex ec IIC T4 Gc.
What power supply is required?
The device operates on a 24 V DC supply (nominal), with an operating range of 19.2 to 30 V DC. Power consumption is ≤ 1.5 W.
How do I configure the input type and range?
Configuration is done via DIP switches located on the side of the device. The manual provides a table for selecting thermocouple type and temperature range.
What is the accuracy of the MACX MCR-EX-TC-I?
Typical accuracy is ≤ 0.1% of the configured span, with additional cold junction compensation error of about 1°C.
Can the device be mounted on a DIN rail?
Yes, it is designed for mounting on a standard 35 mm DIN rail per EN 60715.
What are the dimensions and weight?
Dimensions are 17.5 mm width, 99 mm height, 114.5 mm depth. Weight is approximately 150 g.
Does the device provide electrical isolation?
Yes, it features 3-way isolation between input, output, and power supply, with a test voltage of 2.5 kV.
How should I clean the device?
Use a dry, lint-free cloth. Do not use solvents or abrasive cleaners to avoid damaging the housing.

User questions about MACX MCR-EX-TC-I Phoenix Contact

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.