| Product type | Electronic timer module |
| Brand | Simpson |
| Model | TM2810141E |
| Dimensions | 90 x 70 x 60 mm |
| Weight | 150 g |
| Power supply | 24 V AC/DC |
| Maximum power consumption | 5 W |
| Operating temperature | -10 °C to +50 °C |
| Protection rating | IP20 |
| Main functions | On-delay, off-delay, programmable cycles, bistable mode |
| Timing range | 0.1 s to 99 h |
| Connection | Screw terminals (max 2.5 mm²) |
| Display | Status LED |
| Housing material | Self-extinguishing ABS plastic |
| Mounting | On DIN rail 35 mm |
| Maintenance and cleaning | Wipe with a dry, lint-free cloth; do not use solvents |
| Safety | Reverse polarity protection, overload protection, reinforced insulation |
| Spare parts and repairability | Not user-serviceable; contact Simpson after-sales service for any defects |
| General information | Compliant with CE directives; indoor use only |
Frequently Asked Questions - TM2810141E Simpson
How to connect the TM2810141E module?
Connect the 24 V AC/DC supply to terminals A1 and A2. The output contacts are marked 15-16 (NO) and 15-18 (NF). Respect polarity for DC.
How to set the timing?
Use the potentiometers or DIP switches (depending on the model) to adjust the timing. The range is from 0.1 second to 99 hours. Refer to the manual for exact combinations.
What to do if the module does not turn on?
First check the power supply: correct voltage at terminals A1-A2. If nothing lights up, the module may be faulty. Contact after-sales service.
What is the maximum contact current?
The contacts handle up to 5 A for resistive load (230 V AC) and 2 A for inductive load. Do not exceed these values.
Can I use this module outdoors?
No, the module is designed for indoor use (IP20). Protect it from moisture and dust.
How to reset the module?
Turn off the power for at least 10 seconds, then turn it back on. This resets the ongoing timings.
The module emits a humming sound. Is it normal?
A slight hum is normal for electromechanical relays. If it becomes loud or irregular, check the mounting and load.
What is the relay's lifespan?
Under normal conditions, the relay has a mechanical life of 10 million cycles and an electrical life of 100,000 cycles at full load.
How to mount the module on a DIN rail?
Clip the module onto the 35 mm DIN rail. To remove it, pull the lower clip with a screwdriver and tilt the module.
Where to find the detailed wiring diagram?
The wiring diagram is in the user manual downloadable from our website. It is also printed on the housing.
User questions about TM2810141E Simpson
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
No questions yet. Be the first to ask one.
Download the instructions for your Pressure washer in PDF format for free! Find your manual TM2810141E - Simpson and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. TM2810141E by Simpson.