USER MANUAL UATYQ50ABAY1 DAIKIN

Rooftop Packaged Unit

DAIKIN UATYQ50ABAY1 - Rooftop Packaged Unit - 1

text_image 24.2° 30.5° 20:30 PGD user interface

Models:

UATYQ20ABAY1

UATYQ25ABAY1

UATYQ30ABAY1

UATYQ45ABAY1

UATYQ50ABAY1

UATYQ55ABAY1

UATYQ65ABAY1

UATYQ75ABAY1

UATYQ90ABAY1

UATYQ110ABAY1

UATYQ115ABAY1

UATYQ20AFC2Y1

UATYQ25AFC2Y1

UATYQ30AFC2Y1

UATYQ45AFC2Y1

UATYQ50AFC2Y1

UATYQ55AFC2Y1

UATYQ65AFC2Y1

UATYQ75AFC2Y1

UATYQ90AFC2Y1

UATYQ110AFC2Y1

UATYQ115AFC2Y1

UATYQ20AFC3Y1

UATYQ25AFC3Y1

UATYQ30AFC3Y1

UATYQ45AFC3Y1

UATYQ50AFC3Y1

UATYQ55AFC3Y1

UATYQ65AFC3Y1

UATYQ75AFC3Y1

UATYQ90AFC3Y1

UATYQ110AFC3Y1

UATYQ115AFC3Y1

Operation manual

Rooftop Packaged Unit

English

DAIKIN UATYQ50ABAY1 - Models: - 1

DAIKIN UATYQ50ABAY1 - Models: - 2

natural_image Blank grid paper with uniform gray squares on white background (no text or symbols)

Contents

1 User Interface 4

2 Operating guide 5

2.1 Software menu 5
2.2 Main mask and menu 6
2.3 Switching ON/OFF he unit from keyboard 7
2.4 Temperature and air flow setpoint adjust 7
2.5 Clock menu and time slots setting 8
2.5.1 Time slots programming examples 9
2.6 Stop washing function (forced freecooling at unit start-up) 10
2.7 Summer/winter changeover from keyboard 11
2.8 Input/output visualization 12
2.10 Alarms

2.9 Change language and unit and software data visualization 14

15

This operation manual is dedicated to the end user of the unit and it contains a brief description of all free access functions of the unit control.

1 USER INTERFACE

The user interface is a LCD display with 4 rows, 20 columns and automatic backlight; the display has 6 function keys, that are used to navigate the software menu and to set the parameters.

DAIKIN UATYQ50ABAY1 - USER INTERFACE - 1

text_image 24.2° 30.5° 20:30 PGD user interface

The key functions are described in the following.

DAIKIN UATYQ50ABAY1 - USER INTERFACE - 2

This key, called "up arrow", allows to scroll up the masks and to modify the value of each mask field, increasing it.

DAIKIN UATYQ50ABAY1 - USER INTERFACE - 3

This key, called "down arrow", allows to scroll up the masks and to modify the value of each mask field, decreasing it.

DAIKIN UATYQ50ABAY1 - USER INTERFACE - 4

This key, called "Enter", confirms the selection done to access the menu branches and stores a parameter that has been modified.

DAIKIN UATYQ50ABAY1 - USER INTERFACE - 5

This key, called "alarm", allows to display active alarms and, in case, to reset them.

DAIKIN UATYQ50ABAY1 - USER INTERFACE - 6

This key, called "prg", allows to enter the software menu.

DAIKIN UATYQ50ABAY1 - USER INTERFACE - 7

This key, called "esc", allows to exit the displayed mask and to go back to the previous menu level.

The operating guide describes the main control functions.

2.1 Software menu

The software is organized with a menu that allows to access to different branches, each one containing one or more masks or screens, with different access levels: free, partially password-protected or completely password-protected.

Pressing the ^Prg key from any mask, the following menu loop is displayed:

ItalianoEnglishEspañol
ON/OFF unitàUnit ON/OFFON/OFF unidad
CostruttoreManufacturerConstructor
UtenteUserUsuar
SetpointSetpointP.Consig.
OrologioClockReloj
Ingressi/UsciteInput/OutputEntrad/Salidas
StoricoHistoryHistor.
ManutenzioneMaintenanceMantenimiento
Selezione unitàUnit selectionSelecc.unidad
Estate/InvernoSummer/WinterVer./Inv.

With arrow keys ↑ ↓ it is possible to scroll the menu; the selected one is highlighted and marked by an arrow on the left:

MenuQ0□ CostruttoreMenuQ0□ ManufacturerMenuQ0□ Constructor
→ Utente→ User→ Usuar
□ Setpoint□ Setpoint□ P.Consig

To enter the selected menu, press the "enter" key

DAIKIN UATYQ50ABAY1 - Software menu - 1

This is the masks tree with all sub-menus:

  • The ones reported in underlined letters are free access menu;
  • the ones reported in "italic letters" are partially password-protected menu;
  • the ones reported in bold letters are completely password-protected menu.

The access to the password-protected menu is reserved to Service technicians.

DAIKIN UATYQ50ABAY1 - Software menu - 2

flowchart
graph TD
    A["Main mask"] --> B["M. Main menu"]
    B --> C["N. Unit ON/OFF"]
    B --> D["Z. Manufacturer"]
    D --> E["V. Initialization"]
    D --> F["C. Configuration"]
    D --> G["G. Parameters"]
    D --> H["T. Timing"]
    D --> I["Drivers"]
    I --> J["F. System EVD param."]
    I --> K["Q. Autosetup"]
    I --> L["N. Advanced settings"]
    D --> M["Y. Plug-fan"]
    B --> N["P. User"]
    B --> O["S. Setpoint"]
    B --> P["K. Clock"]
    B --> Q["I. Input/Output"]
    B --> R["History"]
    B --> S["A. Maintenance"]
    B --> T["L. Unit selection"]
    B --> U["R. Summer/Winter"]

2.2 Main mask and menu

When the unit is powered, the main mask is displayed on the unit display, showing in its first row the indoor temperature setpoint on the left and the local address of the unit on the right, in bigger fonts the read indoor temperature and on the last row the unit status on the left and the current time on the right.

Set 27.0°C U0127.0°COFF DA TAST. 10:30Set 27.0°C U0127.0°COFF BY KEYB. 10:30Set 27.0°C U0127.0°COFF P/TECL. 10:30

↓ to display the unit working mode, the time slots activation, the dehumidification activation (not available), the setpoint compensation activation (where enabled).

Unità in ESTATE M2Fasce orarie □Deumidifica □Compensazione □Unit in SUMMER M2Time zone □Dehumidify □Compensation □Unid. en VERANO M2Franj.horar. □Deshumecta □Compensación □

to display if the unit is in defrost, in freecooling or in freeheating mode.

M3M3M3
Sbrinamento Defrost Desescharche
Freecooling Freecooling Freecooling
Freeheating Freeheating Freeheating

to display the unit active compressors.

Compressore 1 □ M4Compressor 1 □ M4Compresor 1 □ M4
Compressore 2 □Compressor 2 □Compresor 2 □
Compressore 3 □Compressor 3 □Compresor 3 □
Compressore 4 □Compressor 4 □Compresor 4 □

to display if high pressure alarm prevention function in summer mode is active, if the supply temperature limit is active and if the antifreeze function is enabled and active.

Prevent □ M5Limite mandata □Antigelo -Prevent □ M5Supply limit □Antifreeze -Prevenc □ M5Limite impuls. □Antihiel -

to display the delivery and return (if present) air fans working mode (manual or automatic).

Funzionamento M6ventilatori plug-fanMandata AutomaticoRipresa AutomaticoOperation M6Plug-fanDelivery AutomaticReturn AutomaticOperación M6Ventilad.Plug-fanImpulsión AutomaticoRetorno Automatico

to display if the condensate tray electrical heater is active.

Res.vasca cond. □M7Cond.tray heater □Res.tina cond. □

to display if the washing function (forced freecooling at unit start-up) is active.

M8Gest.lavaggio □M8Washing mng. □M8Gestion lavado □

to display if the low pressure alarm prevention function in winter mode is active for circuits 1 and 2.

Circuito 1M9Circuit 1M9Circuito 1M9
Prevent L.P. Prevent L.P. Prevent L.P.
Circuito 2Circuit 2Circuito 2
Prevent L.P. Prevent L.P. Prevent L.P.

2.3 Switching ON/OFF he unit from keyboard

Prg select "On/OFF unit" menu "Enter" "Enter" to switch ON/OFF the unit.

Stato unitàNOOFF DA TASTIERA ENTER per- ACCENDERE -Unit statusNOOFF BY KEYBOARDPress ENTER for- SWITCH ON -Estad unid. NOOFF POR TECLADO ENTER par- ENCEDER -

If time slots are active, the unit will start running only if it is programmed to be ON in that time slot.

If the unit ON/OFF switching from a supervisor system is enabled, the serial consent is necessary for the effective unit starting-up.

If the unit ON/OFF switching from digital input is enabled, the ON/OFF digital input must be closed for the effective unit starting-up.

If even only one of the previous starting-up systems does not give its consent, the unit will not start running.

2.4 Temperature and air flow setpoint adjust

Prg select "Setpoint" menu "Enter".

From S0 mask, the indoor temperature setpoint in summer mode (cooling) can be adjusted: press "enter" key adjust the setpoint value with arrow keys and press again to confirm the new value.

If time slots are active, the setpoint cannot be modified from this mask, but only from the specific mask of the Clock menu.

SetpointTemp.Est 27.0°CS0Temperature setpointSum 27.0°CS0P consig.Temp.Ver 27.0°CS0

from S1 mask, the indoor temperature setpoint in winter mode (heating) can be adjusted: press the key adjust the setpoint value with arrow keys and press again to confirm the new value.

If time slots are active, the setpoint cannot be modified from this mask, but only from the specific mask of the Clock menu.

Setpoint S1Temp.Inv 20.0°CTemperature S1setpointWin 20.0°CP consig. S1Temp.Inv 20.0°C

from S5 mask, the delivery air flow can be adjusted: press the key , adjust the setpoint value with arrow keys and press again to confirm the new value.

The real air flow can be read from next mask S6.

Setpoint S5 Portata aria mandata 009000m3/hSetpoint S5 Delivery air flow 009000m3/hPConsig. S5 Flujo aire impuls. 009000m3/h

from S7 mask, displayed only for unit with return fans, the return air flow can be adjusted: press key, adjust the setpoint value with arrow keys and press again to confirm the new value. The real air flow can be read from next mask S8.

Setpoint S7Portata aria ripresa008500m3/hSetpoint S7Return air flow008500m3/hPConsig. S7Flujo aire returno008500m3/h

2.5 Clock menu and time slots setting

Prog select "Clock" menu .

DAIKIN UATYQ50ABAY1 - Clock menu and time slots setting - 1

Current time and date can be set from this mask, while the day is automatically updated.

OrologioKOClockKORelojKO
Ora10:30Hour10:30Hora10:30
Data01/01/18Date01/01/18Fech01/01/18
LunediMondayLunes

to enable and set time slots, input the Clock menu password and press the key ← ; the factory Clock menu password is 0001.

Inserire password0000K1Insert password0000K1Insertar password0000K1

down from this mask, the daily time slots can be enabled (second line) and switch off the unit outside the time slots (fourth line).

Abilita fasce K2 orarie giornaliere N Abilita off unità Fascie: NDaily time zone enable: Unit OFF by time zone enable:K2 NHabil.franjas horario laboral Habil. OFF unidad de franja:K2 N

set start and end time of the daily time slot.

Fasce orarie giornaliereK3Daily time zoneK3Fr. horarias diarioK3
Inizio08:00Start08:00Inicio08:00
Fine18:00Ending18:00Fin18:00

set the summer (cooling) indoor temperature setpoint inside the time slot (internal set, third line) and outside the time slot (external set, fourth line).

Fasce orarieK4Time zoneK4Fr. horariasK4
Funzionamento estivoSummer workingFuncionamento verano
Set interno27.0°CInternal set27.0°CSet interno27.0°C
Set esterno30.0°CExternal set30.0°CSet externo30.0°C

set the winter (heating) indoor temperature setpoint inside the time slot (internal set, third line) and outside the time slot (external set, fourth line).

Fasce orarie K5Funz.invernaleSet interno 20.0°CSet esterno 16.0°CTime zone K5Winter workingInternal set 20.0°CExternal set 16.0°CFr. horarias K5Func.inviernoSet interno 20.0°CSet externo 16.0°C

DAIKIN UATYQ50ABAY1 - Clock menu and time slots setting - 2

nable the weekly programming, if required.

Abilita OFF unità da fascia settimanaleK6 NUnit OFF by week time zone enableK6 NHabil. OFF unid. de franja semanalK6 N

DAIKIN UATYQ50ABAY1 - Clock menu and time slots setting - 3

at week days when the unit has to be in ON status (Y) or in OFF status (N).

Fasce orarie K7Lun N Mar N Mer NGio N Ven N Sab NDom NTime zone K7Mon N Tue N Wed NThu N Fri N Sat NSun NFr. Horarias K7Lun N Mar N Mie NJue N Vie N Sab NDom N

2.5.1 Time slots programming examples

To better explain the time slots programming, two examples are reported in the following.

Example n. 1

The unit has to operate every day:

• from 07:00 to 20:00 with summer setpoint 26.0°C and winter setpoint 21.0°C;
• from 20:00 to 07:00 with summer setpoint 30.0°C and winter setpoint 15.0°C.

Moreover, unit main fans must be always active.

Masks K2 to K6 have to be set as follows:

Abilita fasce K2 orarie giornaliere N Abilita off unità Fascie: NDaily time zone K2 enable: N Unit OFF by time zone enable: NHabil.franjas K2 horario laboral N Habil. OFF unidad de franja: N
Fasce orarie giornaliereK3Daily time zone K3Fr. horarias diarioK3
Inizio07:00Start07:00Inicio07:00
Fine20:00Ending20:00Fin20:00
Fasce orarie K4Funzionamento estivoSet interno 26.0°CSet esterno 30.0°CTime zone K4Summer workingInternal set 26.0°CExternal set 30.0°CFr. horarias K4Funcionamento veranoSet interno 26.0°CSet externo 30.0°C
Fasce orarie K5Funz.invernaleSet interno 21.0°CSet esterno 15.0°CTime zone K5Winter workingInternal set 21.0°CExternal set 15.0°CFr. horarias K5Func.inviernoSet interno 21.0°CSet externo 15.0°C
Abilita OFF unità da fascia settimanaleK6 NUnit OFF by week time zone enableK6 NHabil. OFF unid. de franja semanalK6 N

It is not required to set working days on mask K7, because weekly programming is disabled from mask K6.

Example n. 2

The unit has to operate from Monday to Friday, from 07:30 to 19:30, with summer setpoint 24.0°C and winter setpoint 20.5°C; moreover, unit fans must be switched OFF from 19:30 to 07:30 and the unit has to be completely switched OFF on Saturday and Sunday.

Masks K2 to K7 have to be set as follows:

Abilita fasce K2 orarie giornaliere N Abilita off unità Fascie: NDaily time zone K2 enable: N Unit OFF by time zone enable: NHabil.franjas K2 horario laboral N Habil. OFF unidad de franja: N
Fasce orarie giornaliereK3Daily time zone K3Fr. horarias diarioK3
Inizio07:30Start07:30Inicio07:30
Fine19:30Ending19:30Fin19:30
Fasce orarie K4Funzionamento estivoSet interno 24.0°CSet esterno 30.0°CTime zone K4Summer workingInternal set 24.0°CExternal set 30.0°CFr. horarias K4Funcionamento veranoSet interno 24.0°CSet externo 30.0°C
Fasce orarie K5Funz.invernaleSet interno 20.5°CSet esterno 15.0°CTime zone K5Winter workingInternal set 20.5°CExternal set 15.0°CFr. horarias K5Func.inviernoSet interno 20.5°CSet externo 15.0°C
Abilita OFF unità da fascia settimanaleK6 SUnit OFF by week time zone enableK6 YHabil. OFF unid. de franja semanalK6 S
Fascia oraria K7Lun S Mar S Mer SGio S Ven S Sab NDom NTime zone K7Mon Y Tue Y Wed YThu Y Fri Y Sat NSun NFr. Horarias K7Lun S Mar S Mie SJue S Vie S Sab NDom N

DAIKIN UATYQ50ABAY1 - Example n. 2 - 1

In case the "Unit OFF by time slot" function is enabled in mask K2, the external set in mask K4 can be whatever value, because it is not considered by the unit thermoregulation due to the fact that unit is switched OFF.

2.6 Stop washing function (forced freecooling at unit start-up)

Unit with freecooling dampers and washing function enabled.

Main mask → press "Enter" to stop washing function.

2.7 Summer/winter changeover from keyboard

The unit must be switched OFF and the summer/winter changeover from keyboard must be enabled.

Prg Select "Summer/Winter" menu "Enter"

Unità in - ESTATE - ENTER per - INVERNO -R0Unit in - SUMMER - Press ENTER for - WINTER -R0Unid. en - VERANO - ENTER par - INVIERNO -R0

"Enter" to change unit working mode.

If the changeover from digital input is enabled, mask R0 is not visualized.

If the automatic changeover is enabled, the changeover from winter mode to summer mode is done automatically when the indoor air temperature rises above the summer setpoint, while the changeover from summer mode to winter mode is done automatically when the indoor air temperature falls below the winter setpoint. In any case, the automatic changeover is done with the unit in ON status, so the control will first stop all active devices (compressors, electrical heaters, etc.), except main fans, and it will restart them automatically when the changeover is done, following the thermal load request.

DAIKIN UATYQ50ABAY1 - Summer/winter changeover from keyboard - 1

In order to have the automatic summer/winter changeover working properly, winter setpoint must be lower than summer setpoint; if not, the control will activate an alarm that will stop the unit; this alarm will be automatically reset when the summer and winter setpoint are properly set.

2.8 Input/output visualization

Prg select "Input/Output" menu .

DAIKIN UATYQ50ABAY1 - Input/output visualization - 1

The mask displays intake air temperatures internal and external.

Sonda temperatura I0Temperature probe I0Sonda temperatura I0
Interna00.0°CIntake00.0°CInterna00.0°C
Esterna00.0°CExternal00.0°CExterna00.0°C

the mask displays the supply air temperature.

Sonda temperatura IlMandata 00.0°CTemperature probe IlSupply 00.0°CSonda temperatura IlImpuls. 00.0°C

the mask displays circuit 1 and 2 refrigerant pressures.

SondaI3ProbeI3SondaI3
Pressione 100.0BarPressure 100.0BarPresión 100.0Bar
Pressione 200.0BarPressure 200.0BarPresión 200.0Bar

The mask displays the CO _2 or VOC concentration, read by the air quality probe, if present.

Sonda I5qualità ariaCO2 0000ppmAir quality probe I5CO2 0000ppmSonda I5calidad aireCO2 0000ppm

the masks display the digital input statuses: C = closed, O = open.

Ingressi digitali I8Digital input I8Entradas digital. I8
01:CCC07:CCC01:CCC07:CCC01:CCC07:CCC
04:CCC10:CCC04:CCC10:CCC04:CCC10:CCC
Ingressi digitali I913:CCC 16:CCCDigital input I913:CCC 16:CCCEntradas digital. I913:CCC 16:CCC

the mask displays the compressor statuses.

Compressor 1 OFF IaCompressor 1 OFF IaCompressor 1 OFF Ia
Compressor 2 OFFCompressor 2 OFFCompressor 2 OFF
Compressor 3 OFFCompressor 2 OFFCompressor 3 OFF
Compressor 4 OFFCompressor 4 OFFCompressor 4 OFF

the mask displays the statuses of the external fans and of the 4-way reversing valves of circuit 1 and 2.

Vent.cond.1OFF IbCond.fan 1OFF IbVent.cond.1OFF Ib
Vent.cond.2OFFCond.fan 2OFFVent.cond.2OFF
Valv.inv.1OFFRev.valve 1OFFValv.inv.1OFF
Valv.inv.2OFFRev.valve 2OFFValv.inv.2OFF

DAIKIN UATYQ50ABAY1 - Input/output visualization - 2

e mask displays the main fan status.

Vent.princ. OFF IcMain fan OFF IcVent.princ. OFF Ic

DAIKIN UATYQ50ABAY1 - Input/output visualization - 3

e mask displays the electrical heater statuses, if present.

Resistenza 1 OFF IdResistenza 2 OFFHeater 1OFF IdResistenc. 1OFF Id
Heater 2OFFResistenc. 2OFF

DAIKIN UATYQ50ABAY1 - Input/output visualization - 4

e mask displays the opening percentages of the external air damper and of the hot water valve, if present.

Serr.esterna 000% IeValvola caldo 000%Ext.damper 000% IeHeat Valve 000%Comp.externa 000% IeVàlvula calor 000%

DAIKIN UATYQ50ABAY1 - Input/output visualization - 5

e mask displays the opening percentage of the recirculation damper, if present.

Ie2Ie2Ie2
Serr.ricircolo000%Recirc.damper000%Comp.recircu.000%

DAIKIN UATYQ50ABAY1 - Input/output visualization - 6

e mask displays the running percentage of external fans of circuit 1 and 2.

Vent.cond.1 000% If | Vent.cond.2 000% |Cond.fan1 | Cond.fan2 |000% If 000% |Vent.cond.1 000% If | Vent.cond.2 000% |

DAIKIN UATYQ50ABAY1 - Input/output visualization - 7

e mask displays the running percentage of delivery and return fans (if present).

Vent.Plug-fanITPlug-fanITVent.Plug-fanIT
SegnaleSignalSeñal
Mandata000%Delivery000%Impuls.000%
Ripresa000%Return000%Retorno000%

DAIKIN UATYQ50ABAY1 - Input/output visualization - 8

the mask displays the air pressures read from the air pressure transducer of supply and return air flow; please say that this pressure is measured on fan nozzle and is not related in any way to the available static pressure.

Vent.Plug-fan IuSegnale sonde press.Mandata 00000PaRipresa 00000PaPlug-fan IuSignal pres.probeDelivery 00000PaReturn 00000PaVent.Plug-fan IuSeñal sondas press.Impuls. 00000PaRetorno 00000Pa

DAIKIN UATYQ50ABAY1 - Input/output visualization - 9

the masks display the evaporation temperature, the defrost calculated setpoint and the defrost starting tdown of circuits 1 and 2.

SbrinamentoIvlDefrostIvlDescongelationIvl
T.evap.:-xx.x°CEvap.T.:-xx.x°CT.evap.:-xx.x°C
Set sbrin.:-xx.x°CDefr.set.:-xx.x°CSet desc.:-xx.x°C
Countdown:xxx sCountdown:xxx sCountdown:xxx s
SbrinamentoIv2DefrostIv2DescongelationIv2
T.evap.:-xx.x°CEvap.T.:-xx.x°CT.evap.:-xx.x°C
Set sbrin.:-xx.x°CDefr.set.:-xx.x°CSet desc.:-xx.x°C
Countdown:xxx sCountdown:xxx sCountdown:xxx s

the mask displays the NO11 auxiliary output status and the condensate tray electrical heater status.

IzUscita aus.NO11: OFFRes.vasca cond.: OFFIzAux.output NO11: OFFCond.tray heater:OFFIzSalida aux.NO11: OFFRes. tina cond.: OFF

2.9 Change language and unit and software data visualization

↓ "Maintenance" menu "Enter"

From this mask the control language can be changed, choosing from those available. Press "Enter" change the language.

Lingua corrente AxITALIANOpremere tastoENTER per cambiareCurrent language: AxENGLISHpress ENTER tochange languageIdioma actual AXESPAÑOLpulsar teclaENTER para cambiar

the mask displays the following unit data: serial number, factory testing date and factory tester identification code.

Dati unità AyMatricola: 12345678Data coll.: 01/01/18Collaudatore: 0653Unit data AySerial n.: 12345678Test data: 01/01/18Tester: 0653Datos unidad AyN.de serie: 12345678Data ens.: 01/01/18Ensayador: 0653

the mask displays the software code, version and release date and the unit model.

the mask displays the control board bios and boot versions and release dates.

A1A1A1
Bios:6.4408/12/17Bios:6.4408/12/17Bios:6.4408/12/17
Boot:5.0230/03/13Boot:5.0230/03/13Boot:5.0230/03/13

the mask displays the control board model and type.

Hardware installato Scheda :pCO5+ Tipo :LARGEA2Installed pCO board Board :pCO5+ Type :LARGEA2Hardware instalado Tarjeta:pCO5+ Tipo :LARGEA2

the mask displays the unit working hours.

the mask displays the working hours of compressors 1 and 2.

Ore funzionamento A4Working hours A4Horas func. A4
Comp.1000000hCompressor 1 000000hComp.1000000h
Comp.2000000hCompressor 2 000000hComp.2000000h

DAIKIN UATYQ50ABAY1 - Change language and unit and software data visualization - 1

e mask displays the working hours of compressors 3 and 4.

Ore funzionamento A5Working hours A5Horas func. A5
Comp.3000000hCompressor 3000000hComp.3000000h
Comp.4000000hCompressor 4000000hComp.4000000h

2.10 Alarms

When an alarm is triggered, the red "Alarm" key is on and the alarm digital output is activated.

By pressing the "Alarm" key, the last alarm is displayed; the other active alarms can be scrolled with arrow keys.

This is an example of an alarm mask:

AL70DAIKIN UATYQ50ABAY1 - Alarms - 1Sonda B9 guasta o disconnessaAL70DAIKIN UATYQ50ABAY1 - Alarms - 2B9 probe broken or disconnectedAL70DAIKIN UATYQ50ABAY1 - Alarms - 3Sonda B9 averia o desconect.

Each alarm is identified by a code "ALxx" and the alarm cause is described in the mask. To reset an active alarm, press and hold for at least 2 seconds the "Alarm" key; if the alarm has been successfully reset, the alarm mask disappears and, if no other alarms are active, the red "Alarm" key is switched OFF. An alarm can be reset only if the condition that has activated the alarm is not present anymore.

DAIKIN UATYQ50ABAY1 - Alarms - 4

The manual reset of an alarm must be done only after checking the alarm cause and solving the problem that has activated the alarm.

The improper reset of an alarm can cause serious damages to the unit or to its components.

On alarm history menu, last 150 alarms are stored. When the memory is full and another alarm is activated, the oldest alarm is overwritten.

In the following, the full alarm list is reported with the main possible causes, some troubleshooting hints, the reset mode, the action on the unit and on its components.

The alarm reset mode is reported on the "RESET" column:

  • A = automatic: when the alarm condition disappears, the alarm is automatically reset;
  • AC = automatic controlled: the alarm is automatically reset for a limited number of attempts in a certain time, after that the reset becomes manual;
  • M = manual reset from display or from supervisor: the alarm must be manually reset by display as described above or by the supervisor reset variable; for each alarm with manual reset, the reset day and time are stored on the alarm history.

In the "OFF UNIT" column, it is reported if the alarm stops the whole unit or not:

• Yes = the alarm stops the unit;
- No = the alarm does not stop the unit, but only the concerned devices

CODEDESCRIPTION MAINCAUSES CHECKS AND TROUBLESHOOTING RESETUNIT OFFITEMS OFF
AL01Overload Compressor 1Intervention of the thermal protection compressor 1Check working conditions.M NoCompressor 1
Check cabling, terminals and circuit breaker of the motor.
Check adsorbed current.
Check compressor discharge temperature.
AL02Overload Compressor 2Intervention of the thermal protection compressor 2Check working conditions.M NoCompressor 2
Check cabling, terminals and circuit breaker of the motor.
Check adsorbed current.
Check compressor discharge temperature.
AL03High pressure Circuit 1High pressure alarm from circuit 1 (high pressure switch)Check condensing pressure.MNoAll compressors circuit 1
Check refrigerant charge.
Check condensing fan/s operation
Check the presence of warm condensing air recycling.
Check condensing coil cleaning and eventually clean it.
Reset the high pressure switch before resetting the alarm in the controller.
Check the correct intervention set for the high-pressure switch.
AL04High pressure Circuit 2High pressure alarm from circuit 2 (high pressure switch)Check working conditions.MNoAll compressors circuit 2
Check condensing pressure.
Check refrigerant charge.
Check condensing fan/s operation
Check the presence of warm condensing air recycling.
Check condensing coil cleaning and eventually clean it.
Reset the high pressure switch before resetting the alarm in the controller.
Check the correct intervention setting for the high-pressure switch.
AL05Antifreeze alarm Digitalinput 1 open Check working conditions. A (2) NoCompressors (only cooling mode)
AL06High temp threshold exceededIndoor temperature exceeds the max value setCheck working conditions. A No None
AL07Low temp threshold exceededIndoor temperature is lower than the min value setCheck working conditions. A (2) No None
AL08Low pressure Circuit 1 in summerLow pressure alarm circuit 1 from the low-pressure switch (cooling mode)Check working conditions.MNoAll compressors circuit 1
Check evaporation pressure.
Check refrigerant charge
Check evaporation fans.
Check the correct intervention of the low-pressure switch.
AL09Low pressure Circuit 2 in summerLow pressure alarm circuit 2 from the low pressure switch (cooling mode)Check working conditions.MNoAll compressors circuit 2
Check evaporation pressure.
Check refrigerant charge
Check evaporation fans.
Check the correct intervention of the low-pressure switch.
AL10Low pressure Circuit 1 in winterLow pressure alarm circuit 1 from the low pressure switch (heating mode)Check working conditions.MNoAll compressors circuit 1
Check evaporation pressure.
Check refrigerant charge
Check evaporation fans.
Check the correct intervention of the low-pressure switch.
AL11Low pressure Circuit 2 in winterLow pressure alarm circuit 2 from the low-pressure switch (heating mode)Check working conditions.MNoAll compressors circuit 2
Check evaporation pressure.
Check refrigerant charge
Check evaporation fans.
Check the correct intervention of the low-pressure switch.
AL12Compressor 1 maintenanceIt has been exceeded Compressor 1 operating hours threshold.Check the compressor working conditions.M (1) No None
AL13Compressor 2 maintenanceIt has been exceeded Compressor 2 operating hours threshold.Check the compressor working conditions.M (1) No None
CODEDESCRIPTION MAINCAUSES CHECKS AND TROUBLESHOOTING RESETUNIT OFFITEMS OFF
AL14Unit MaintenanceIt has been exceeded unit operating hours threshold.Unit check up. Perform the ordinary maintenance operations.M (1) NoNo None
AL15Main fan overload/interblockThermal protection ventilation fanCheck working conditions.M YesAll
Check fans motor cabling, terminals and adsorbed current.
Check thermal overload switch.
AL16Filter dirtyThe pressure drop across the filter measured by the differential pressure switch is higher than the set valueClean or replace the air filters. MNo None
Calibration of the differential pressure switch for clogged filters.M
AL17Not used - - - - -
AL18Flow-switch alarmThe differential air pressure switch detects a pressure (airflow) lower than the set pointCheck working conditions (airflow and pressure).M YesAll
Check working operation of the ventilation fans.
Check air distribution system.
Check the correct intervention of the airflow switch.
AL19Clock broken or not presentThe clock board is defectiveReboot the controller; if alarm persists, replace the main board.MNoNone, hourly programming not operating
AL20Summer setpoint < winter setpointSummer set point is lower than winter set point or winter set point is higher than summer set point and automatic changeover is enabledCheck for the correct temperature set point (cooling and heating modes).AYes All
AL21B1 probe broken or disconnectedThe reading of the probe B1 (supply airflow differential pressure probe) exceeds the operative rangeCheck working conditions.MNoAll components and fuctions directly related to the probe
Check in the controller for the correct probe reading range .
Check the correct reading of the probe and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic input of the main board.
AL22B2 probe broken or disconnectedThe reading of the probe B2 (return airflow differential pressure probe) exceeds the operative rangeCheck working conditions.MNoAll components and fuctions directly related to the probe
Check in the controller for the correct probe reading range .
Check the correct reading of the probe and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic inputof the main board.
AL23B6 probe broken or disconnectedThe reading of the probe B6 (condensing pressure circuit 2) exceeds the rangeCheck working conditions.MNoAll components and fuctions directly related to the probe
Check in the controller for the correct probe reading range .
Check the correct reading of the probe and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic input of the main board.
CODEDESCRIPTION MAINCAUSES CHECKS AND TROUBLESHOOTING RESETUNIT OFFITEMS OFF
AL24B7 probe broken or disconnectedThe reading of the probe B7 (indoor air humidity) exceeds the rangeCheck working conditions.MNoAll components and fuctions directly related to the probe
Check in the controller for the correct probe reading range .
Check the correct reading of the probe and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic input of the main board.
AL25B4 probe broken or disconnectedThe reading of the probe B4 (supply air temperature) exceeds the rangeCheck working conditions.MNoAll components and fuctions directly related to the probe
Check in the controller for the correct probe reading range .
Check the correct reading of the probe and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic input of the main board.MNoAll components and fuctions directly related to the probe
AL26B3 probe broken or disconnectedThe reading of the probe B3 (condensing pressure circuit 1) exceeds the rangeCheck working conditions.
Check in the controller for the correct probe reading range .
Check the correct reading of the probe and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic input of the main board.
AL27B8 probe broken or disconnectedThe reading of the probe B8 (Outdoor air temperature) exceeds the rangeCheck working conditions.MNoAll components and fuctions directly related to the probe
Check in the controller for the correct probe reading range .
Check the correct reading of the probe and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic input of the main Board.
AL28B5 probe broken or disconnectedThe reading of the probe B5 (return air temperature) exceeds the rangeCheck working conditions.MNoAll components and fuctions directly related to the probe
Check in the controller for the correct probe reading range .
Check the correct reading of the probe and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic input of the main Board.
AL29Heater 1 overloadThe circuit breaker of the heater group 1 tripsCheck working conditions (airflow and temperature).M NoHeater group 1Check cabling and terminals
heaters and adsorbed current.
Check thermal switch.
AL30Heater 2 overloadThe circuit breaker of the heater group 2 tripsCheck working conditions (airflow and temperature).M NoHeater group 2Check cabling and terminals
heaters and adsorbed current.
Check thermal switch.
AL31Generic serious alarm by DIN . System offThe serious alarm digital input (DIN) is openCheck external control. M Yes All
AL32Generic alarm by dig. input System still onThe generic alarm digital input is openCheck external control. M No None
AL33Compressor 3 OverloadIntervention of the thermal protection compressor 3Check working conditions.M NoCompressor 3
Check cabling, terminals and circuit breaker of the motor.
Check adsorbed current.
Check compressor discharge temperature.
AL34Compressor 4 OverloadIntervention of the thermal protection compressor 4Check working conditions.M NoCompressor 4
Check cabling, terminals and circuit breaker of the motor.
Check adsorbed current.
Check compressor discharge temperature.
AL35Compressor 3 maintenanceIt has been exceeded compressor 3 operating hours threshold.Check the working conditions of the compressor.M (1) NoNone
AL36Compressor 4 maintenanceIt has been exceeded compressor 4 operating hours threshold.Check the working conditions of the compressor.M (1) NoNone
AL37-65Not used - - - - -
AL66WARNING Circuit 1 in PreventCondensing pressure circuit 1 is higher than prevention value (cooling mode)Evaporation pressure circuit 1 is lower than prevention value (heating mode)Check working conditions.A (2) NoOne compressor of circuit 1
Check condensing pressure.
Check condensing fans and coil.
Check condensing coil air flow.
Check refrigerant charge
AL67WARNING Circuit 2 in PreventCondensing pressure circuit 2 is higher than prevention value (cooling mode)Evaporation pressure circuit 2 is lower than prevention value (heating mode)Check working conditions.A (2) NoOne compressor of circuit 2
Check condensing pressure.
Check condensing fans and coil.
Check condensing coil air flow.
Check refrigerant charge
AL68Differential probe supplyThe value measured from the supplyn air differential pressure probe for the return is outside the allowed range.Check airflow.A (2) NoNone
Check airflow distribution system.
Check supply differential pressure switch and its own connection hoses.
AL69Differential probe returnThe value measured from the return air differential pressure probe for the return is outside the allowed range.Check airflow.A (2) NoNone
Check airflow distribution system.
Check supply differential pressure switch and its own connection hoses.
AL70B9 probe broken or disconnectedThe reading of the probe B9 (indoor air CO2 or VOC) exceeds the rangeCheck working conditions.MNoAll components and fuctions directly related to the probe
Check in the controller for the correct probe reading range.
Check the correct reading of the probe and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic input of the main board.
AL71B10 probe broken or disconnectedThe reading of the probe B10 (outdoor air relative humidity) exceeds the rangeCheck working conditions.MNoAll components and fuctions directly related to the probe
Check in the controller for the correct probe reading range.
Check the correct reading of the probe and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic input of the main board.
CODEDESCRIPTION MAINCAUSES CHECKS AND TROUBLESHOOTING RESETUNIT OFFITEMS OFF
AL72Board 2 Lan disconnectedInterrupted communication between main and expansion boardsCheck for correct power supply to the expansion board.MNo
Check for the connection between main and expansion boards.
Communication setup.
AL73B1 slave probe broke or disconnectedThe reading of the probe B1 of expansion board exceeds the rangeCheck working conditions.MNo
Check in the controller for the correct probe reading range .
Check the correct reading of the probe and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic input of the main board
AL74Circuit 1 High pressure from transd.in cooling Tent.: x/yHigh pressure alarm of cooling circuit 1 in cooling (summer) mode from pressure transducer.The attempt "x" of the maximum number "y" of attempts is displayed; when the maximum number of attempts is reached, the alarm reset becomes manual.Check working conditions.AC No
Check condensing pressure.
Check condensing fans and coil.
Check condensing coil air flow.
Check refrigerant charge.
Check pressure probe.
AL75Circuit 2 High pressure from transd.in cooling Tent.: x/yHigh pressure alarm of cooling circuit 2 in cooling (summer) mode from pressure transducer.The attempt "x" of the maximum number "y" of attempts is displayed; when the maximum number of attempts is reached, the alarm reset becomes manual.Check working conditions.AC No
Check condensing pressure.
Check condensing fans and coil.
Check condensing coil air flow.
Check refrigerant charge.
Check pressure probe.
AL76Circuit 1 Low pressure from transd.in heating Tent.: x/yLow pressure alarm of cooling circuit 1 in heating (winter) mode from pressure transducer. The attempt "x" of the maximum number "y" of attempts is displayed; when the maximum number of attempts is reached, the alarm reset becomes manual."Check working conditions.AC No
Check evaporating pressure.
Check evaporating fans and coil.
Check evaporating coil air flow.
Check refrigerant charge.
Check pressure probe.
AL77Circuit 2 Low pressure from transd.in heating Tent.: x/yLow pressure alarm of cooling circuit 2 in heating (winter) mode from pressure transducer. The attempt "x" of the maximum number "y" of attempts is displayed; when the maximum number of attempts is reached, the alarm reset becomes manual."Check working conditions.AC No
Check evaporating pressure.
Check evaporating fans and coil.
Check evaporating coil air flow.
Evaporation pressure of circuit 1 in heating (winter) mode is lower than the low pressure prevention valueCheck working conditions.A (2) No
Check evaporating pressure.
Check evaporating fans and coil.
Check evaporating coil air flow.
CODEDESCRIPTION MAINCAUSES CHECKS AND TROUBLESHOOTING RESETUNIT OFFITEMS OFF
AL79WARNING Circuit 2 in low pressure preventionEvaporation pressure of circuit 2 in heating (winter) mode is lower than the low pressure prevention valueCheck working conditions.A (2) NoA compressor of circuit 2
Check evaporating pressure.
Check evaporating fans and coil.
Check evaporating coil air flow.
Check refrigerant charge

(1) Maintenance alarms must be reset from masks Ac-Ad-Ae of the Maintenance menu and they cannot be reset by pressing the Alarm key
(2) The alarm is reset automatically, but to clear the alarm visualization it is necessary to press and hold the Alarm key for at least 2 seconds.

DAIKIN UATYQ50ABAY1 - Alarms - 5

DAIKIN UATYQ50ABAY1 - Alarms - 6

natural_image Blank grid paper with uniform gray squares on white background (no text or symbols)

DAIKIN UATYQ50ABAY1 - Alarms - 7

DAIKIN UATYQ50ABAY1 - Alarms - 8

natural_image Blank grid paper with uniform gray squares on white background (no text or symbols)
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : DAIKIN

Model : UATYQ50ABAY1

Category : Air-conditioner