CyberPower

HSTP3T30KEBCWOB - Inverter CyberPower - Free user manual and instructions

Find the device manual for free HSTP3T30KEBCWOB CyberPower in PDF.

📄 62 pages English EN Download 💬 AI Question
Notice CyberPower HSTP3T30KEBCWOB - page 3
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about HSTP3T30KEBCWOB CyberPower

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Inverter in PDF format for free! Find your manual HSTP3T30KEBCWOB - CyberPower and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. HSTP3T30KEBCWOB by CyberPower.

USER MANUAL HSTP3T30KEBCWOB CyberPower

HSTP3T10KE / KEBC / KEBCWOB

HSTP3T15KE / KEBC / KEBCWOB

HSTP3T20KE / KEBC / KEBCWOB

HSTP3T30KE / KEBC / KEBCWOB

HSTP3T40KE / KEBC / KEBCWOB

CyberPower Systems, Inc.

www.cyberpower.com

Safety Precautions

This manual contains information concerning the installation and operation of Tower UPS. Please carefully read this manual prior to installation.

The Tower UPS cannot be put into operation until it is commissioned by engineers approved by the manufacturer (or its agent). Not doing so could result in personnel safety risk, equipment malfunction and invalidation of warranty.

Safety Message Definition

Danger: Serious human injury or even death may be caused, if this requirement is ignored. Warning: Human injury or equipment damage may be caused, if this requirement is ignored.

Attention: Equipment damage, loss of data or poor performance may be caused, if this requirement is ignored.

Commissioning Engineer: The engineer who installs or operates the equipment should be well trained in electricity and safety and familiar with the operation, debug, and maintenance of the equipment.

Warning Label

The warning label indicates the possibility of human injury or equipment damage, and advises the proper step to avoid the danger. In this manual, there are three types of warning labels as below.

LabelsDescription
CyberPower HSTP3T30KEBCWOB - Warning Label - 1DangerSerious human injury or even death may be caused, if this requirement is ignored.
CyberPower HSTP3T30KEBCWOB - Warning Label - 2WarningHuman injury or equipment damage may be caused, if this requirement is ignored.
CyberPower HSTP3T30KEBCWOB - Warning Label - 3AttentionEquipment damage, loss of data or poor performance may be caused, if this requirement is ignored.

Safety Instruction

CyberPower HSTP3T30KEBCWOB - Safety Instruction - 1Danger✧ Performed only by commissioning engineers.✧ This UPS is designed for commercial and industrial applications only, and is not intended for any use in life-support devices or system.
CyberPower HSTP3T30KEBCWOB - Safety Instruction - 2Warning✧ Read all the warning labels carefully before operation, and follow the instructions.
CyberPower HSTP3T30KEBCWOB - Safety Instruction - 3✧ When the system is running, do not touch the surface with this label, to avoid any hurt of scald.
CyberPower HSTP3T30KEBCWOB - Safety Instruction - 4✧ ESD sensitive components inside the UPS, anti-ESD measure should be taken before handling.

Move & Install

CyberPower HSTP3T30KEBCWOB - Safety Instruction - 5 Danger✧ Keep the equipment away from heat source or air outlets.✧ In case of fire, use dry powder extinguisher only, any liquid extinguisher can result in electric shock.
CyberPower HSTP3T30KEBCWOB - Safety Instruction - 6 Warning✧ Do not start the system if any damage or abnormal parts founded.✧ Contacting the UPS with wet material or hands may be subject to electric shock.
CyberPower HSTP3T30KEBCWOB - Safety Instruction - 7 Attention✧ Use proper facilities to handle and install the UPS. Shielding shoes, protective clothes and other protective facilities are necessary to avoid injury.✧ During positioning, keep the UPS way from shock or vibration.✧ Install the UPS in proper environment, more detail in section 3.3.

Debug & Operate

CyberPower HSTP3T30KEBCWOB - Safety Instruction - 8 Danger✧ Make sure the grounding cable is well connected before connecting the power cables, the grounding cable and neutral cable must be in accordance with the local and national codes practice.✧ Before moving or re-connecting the cables, make sure to cut off all the input power sources, and wait for at least 10 minutes for internal discharge. Use a multi-meter to measure the voltage on terminals and ensure the voltage is lower than 36V before operation.
CyberPower HSTP3T30KEBCWOB - Safety Instruction - 9 Attention✧ The earth leakage current of load will be carried by RCCB or RCD.✧ Initial check and inspection should be performed after long time storing of UPS.

Maintenance & Replacement

CyberPower HSTP3T30KEBCWOB - Safety Instruction - 10 Danger✧ All the equipment maintenance and servicing procedures involving internal access need special tools and should be carried out only by trained personnel. The components that can only be accessed by opening the protective cover with tools cannot be maintained by user.✧ This UPS full complies with “IEC62040-1-1-General and safety requirements for use in operator access area UPS”. Dangerous voltages are present within the battery box. However, the risk of contact with these high voltages is minimized for non-service personnel. Since the component with dangerous voltage can only be touched by opening the protective cover with a tool, the possibility of touching high voltage component is minimized. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating proceduresin this manual.

Battery Safety

CyberPower HSTP3T30KEBCWOB - Safety Instruction - 11 Danger✧ All the battery maintenance and servicing procedures involving internal access need special tools or keys and should be carried out only by trained personnel.✧ When connected together, the battery terminal voltage will exceed 400Vdc and is potentially lethal.✧ Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all times. Particular attention should be paid to the recommendations concerning local environmental conditions and the provision of protective clothing, first aid and fire-fighting facilities.✧ Ambient tempera ture is a major factor in determining the battery capacity and life. The nominal operating temperature of battery is 20°C. Operating above this temperature will reduce the battery life. Periodically charge the battery according to the battery user manuals to ensure the back-up time of UPS.✧ Replace the batteries only with the same type and the same number, or it may cause explosion or poor performance.✧ When connecting the battery, follow the precautions for high-voltage operation before accepting and using the battery, check the appearance the battery. If the package is damaged, or the battery terminal is dirty, corroded or rusted or the shell is broken, deformed or has leakage, replace it with new product. Otherwise, battery capacity reduction, electric leakage or fire may be caused.● Before operating the battery, remove the finger ring, watch, necklace, bracelet and any other metal jewelry● Wear rubber gloves.● Eye protection should be worn to prevent injury from accidental electrical arcs.● Only use tools (e.g. wrench) with insulated handles.● The batteries are very heavy. Please handle and lift the battery with proper method to prevent any human injury or damage to the battery terminal.● Do not decompose, modify or damage the battery. Otherwise, battery short circuit, leakage or even human injury may be caused.● The battery contains sulfuric acid. In normal operation, all the sulfuric acid is attached to the separation board and plate in the battery. However, when the battery case is broken, the acid will leak from the battery. Therefore, be sure to wear a pair of protective glasses, rubber gloves and skirt when operating the battery. Otherwise, you may become blind if acid enters youreyes and your skin may be damaged by the acid.● At the end of battery life, the battery may have internal short circuit, drain of electrolytic and erosion of positive/negative plates. If this condition continues, the battery may have temperature out of control, swell or leak. Be sure to replace the battery before these phenomena happen.● If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations.● If electrolyte comes into contact with the skin, the affected area should be washed immediately with water.

Disposal

Warning◇ Dispose of used battery according to the local instructions

Contents

Chapter 1 Product Introduction....1

1.1 System Configuration....1

1.2 Operation Mode....1

1.2.1 Normal Mode....1

1.2.2 Battery Mode 2

1.2.3 Bypass Mode....2

1.2.4 Maintenance Mode (Manual Bypass) 2

1.2.5 ECO Mode....3

1.2.6 Auto-restart Mode....3

1.2.7 Frequency Converter Mode ....4

1.3 UPS Structure....4

1.3.1 UPS Configuration....4

1.3.2 UPS Outlook....4

Chapter 2 Installation Instruction....9

2.1 Location 9

2.1.1 Installation Environment....9

2.1.2 Site Selection....9

2.1.3 Size and Weight 9

2.2 Unloading and Unpacking....13

2.2.1 Moving and Unpacking of the Cabinet....13

2.3 Positioning....15

2.3.1 Positioning Cabinet 15

2.4 Battery 16

2.5 Cable Entry....16

2.6 Power Cables 17

2.6.1 Specifications 17

2.6.2 Specifications for Power Cables Terminal 17

2.6.3 Circuit Breaker....18

2.6.4 Connecting Power Cables....18

2.7 Control and Communication Cables 19

2.7.1 Dry Contact Interface 20

2.7.2 Communication Interface 25

Chapter 3 LCD Panel....26

3.1 Introduction....26

3.2 LCD panel for Cabinet....26

3.2.1 LED Indicator....26

3.2.2 Control and Operation Keys....27

3.2.3 LCD Screen 28

3.3 System Information Window 30

3.4 Menu Window....30

3.5 Event List....31

Chapter 4 Operations ......35

4.1 UPS Start-up 35

4.2 Procedure for Switching between Operation Modes 36

4.2.1 Switching the UPS into Battery Mode from Normal Mode 36

4.2.2 Switching the UPS into Bypass Mode from Normal Mode 36

4.2.3 Switching the UPS into Normal Mode from Bypass Mode 36

4.2.4 Switching the UPS into Maintenance Bypass Mode from Normal Mode......36

4.2.5 Switching the UPS into Normal Mode from Maintenance Bypass Mode.....37
4.3 Battery Maintenance .... 37
4.4 EPO 38
4.5 Installation of Parallel Operation System....39
4.5.1 Parallel system diagram....39
4.5.2 Parallel system setting ....41

Chapter 5 Maintenance ....44

5.1 Precautions....44
5.2 Instruction for Maintaining UPS....44
5.3 Instruction for Maintaining Battery string....44
5.3.1 Installation of internal battery 45

Chapter 6 Product Specification....51

6.1 Applicable Standards ....51
6.2 Environmental Characteristics ....51
6.3 Mechanical Characteristic....51
6.4 Electrical Characteristics....52
6.4.1 Electrical Characteristics (Input Rectifier)....52
6.4.2 Electrical Characteristics (Intermediate DC Link) 53
6.4.3 Electrical Characteristics (Inverter Output)....53
6.4.4 Electrical Characteristics (Bypass Mains Input)....54
6.5 Efficiency ....54
6.6 Display and Interface....54

Chapter 1 Product Introduction

1.1 System Configuration

The Tower UPS is configured by the following part: Rectifier, Charger, Inverter, Static Switch and Manual Bypass Switch. One or several battery strings should be installed to provide backup energy once the utility fails. The UPS structure is shown in Fig. 1-1.

CyberPower HSTP3T30KEBCWOB - System Configuration - 1

flowchart
graph TD
    A["Battery"] --> B["Charger"]
    B --> C["Rectifier/Discharger"]
    C --> D["Inverter"]
    D --> E["Output Switch"]
    E --> F["Load"]
    G["Main Input"] --> C
    H["Bypass Input"] --> I["Static Switch"]
    I --> J["Manual Bypass"]
    J --> E

Fig.1-1 UPS Configuration

1.2 Operation Mode

The Tower UPS is an on-line, double-conversion UPS that permits operation in the following modes:

  • Normal mode
  • Battery mode
  • Bypass mode
  • Maintenance mode (manual bypass)
  • ECO mode
    • Auto-restart mode
    • Frequency Converter mode

1.2.1 Normal Mode

The inverter of power modules continuously supply the critical AC load. The rectifier/charger derives power from the AC mains input source and supplies DC power to the inverter while simultaneously FLOAT or BOOST charging its associated backup battery.

CyberPower HSTP3T30KEBCWOB - Normal Mode - 1

flowchart
graph TD
    A["Bypass Input"] --> B["Main Input"]
    B --> C["Rectifier/Discharger"]
    C --> D["Inverter"]
    D --> E["Output Switch"]
    E --> F["Load"]
    G["Battery"] --> H["Charger"]
    H --> D
    I["Static Switch"] --> D
    J["Manual Bypass"] --> A

Fig.1-2 Normal mode operation diagram

1.2.2 Battery Mode

Upon failure of the AC mains input power, the inverter of power modules, which obtain power from the battery, supply the critical AC load. There is no interruption in power to the critical load upon failure. After restoration of the AC mains input power, the "Normal mode" operation will continue automatically without the necessity of user intervention.

CyberPower HSTP3T30KEBCWOB - Battery Mode - 1

flowchart
graph TD
    A["Main Input"] --> B["Rectifier/Discharger"]
    C["Battery"] --> B
    B --> D["Inverter"]
    D --> E["Output Switch"]
    E --> F["Load"]
    G["Bypass Input"] --> H["Static Switch"]
    H --> I["Manual Bypass"]
    I --> D

Fig.1-3 Battery mode operation diagram

1.2.3 Bypass Mode

If the inverter overload capacity is exceeded under Normal mode, or if the inverter becomes unavailable for any reason, the static transfer switch will perform a transfer of the load from the inverter to the bypass source, with no interruption in power to the critical AC load. Should the inverter be asynchronous with the bypass, the static switch will perform a transfer of the load from the inverter to the bypass with power interruption to the load. This is to avoid large cross currents due to the paralleling of unsynchronized AC sources. This interruption is programmable but typically set to be less than 3/4 of an electrical cycle, e.g., less than 15ms (50Hz) or less than 12.5ms (60Hz). The action of transfer/re-transfer can also be done by the command through monitor.

CyberPower HSTP3T30KEBCWOB - Bypass Mode - 1

flowchart
graph TD
    A["Bypass Input"] --> B["Static Switch"]
    C["Main Input"] --> D["Rectifier/Discharger"]
    D --> E["inverter"]
    E --> F["Output Switch"]
    G["Battery"] --> H["Charger"]
    H --> I["Load"]
    J["Manual Bypass"] --> B
    J --> F
    B --> E

Fig.1-4 Bypass mode operation diagram

1.2.4 Maintenance Mode (Manual Bypass)

A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS becomes unavailable e.g. during a maintenance procedure. (See Fig.1-5).

CyberPower HSTP3T30KEBCWOB - Maintenance Mode (Manual Bypass) - 1

flowchart
graph TD
    A["Bypass Input"] --> B["Main Input"]
    B --> C["Rectifier/Discharger"]
    C --> D["Inverter"]
    D --> E["Output Switch"]
    E --> F["Load"]
    G["Battery"] --> H["Charger"]
    H --> C
    I["Manual Bypass"] --> D
    I --> E
    J["Main Bypass"] --> K["Output Switch"]
    K --> E

Fig.1-5 Maintenance mode operation diagram

CyberPower HSTP3T30KEBCWOB - Maintenance Mode (Manual Bypass) - 2

Danger

During Maintenance mode, dangerous voltages are present on the terminal of input, output and neutral, even with all the modules and the LCD turned off.

1.2.5 ECO Mode

To improve system efficiency, UPS rack system works in Bypass mode at normal time, and inverter is standby. When the utility fails, the UPS transfers to Battery Mode and the inverter provide powers to the loads.

CyberPower HSTP3T30KEBCWOB - ECO Mode - 1

flowchart
graph TD
    A["Bypass Input"] --> B["Static Switch"]
    C["Main Input"] --> D["Rectifier/Discharger"]
    D --> E["Inverter"]
    E --> F["Output Switch"]
    G["Battery"] --> H["Charger"]
    H --> I["Load"]
    J["Manual Bypass"] --> B
    J --> E
    B --> E

Fig.1-6 ECO Mode operation diagram

CyberPower HSTP3T30KEBCWOB - ECO Mode - 2

Note

There is a short interruption time (less than 10ms) when transfer from ECO mode to battery mode, it must be sure that the interruption has no effect on loads.

1.2.6 Auto-restart Mode

The battery may become exhausted following an extended AC mains failure. The inverter shuts down when the battery reaches the End of Discharge Voltage (EOD). The UPS may be programmed to "System Auto Start Mode after EOD". The system starts after a delay time when the AC main recovers. The mode and the delay time are programmed by the commissioning engineer.

1.2.7 Frequency Converter Mode

By setting the UPS to Frequency Converter mode, the UPS could present a stable output of fixed frequency (50 or 60Hz), and the bypass static switch is not available.

1.3 UPS Structure

1.3.1 UPS Configuration

The UPS configuration is provided in Table 1.1

Table1.1 UPS Configuration

ItemComponentsQuantityRemark
Standard Backup TypeCircuit Breakers5Standard
Dual Input1Standard
Parallel Card,1Optional
SNMP Card1Optional
Long Backup TypeCircuit Breakers4Standard
Dual Input1Standard
Parallel Card,1Optional
SNMP Card1Optional

1.3.2 UPS Outlook

The UPS outlook is shown as Fig.1-7 to Fig.1-13.

CyberPower HSTP3T30KEBCWOB - UPS Outlook - 1

text_image Technical diagram of a dual-chamber electronic device with labeled ports and internal components

Fig.1-7 10/15kVA System outlook (Long backup type)

CyberPower HSTP3T30KEBCWOB - UPS Outlook - 2

natural_image Technical line drawings of two server rack units with visible internal components and wheels (no text or symbols)

Fig.1-8 20/30kVA System outlook (Long backup type)

CyberPower HSTP3T30KEBCWOB - UPS Outlook - 3

natural_image Technical line drawings of two server rack units with internal compartments and control panels (no text or symbols)

Fig.1-9 20/30kVA System outlook (Standard backup type)

CyberPower HSTP3T30KEBCWOB - UPS Outlook - 4

text_image LED Buzzer LCD Operational button OberPower Ventilation Panel

Fig.1-10 10-40kVA front appearance

CyberPower HSTP3T30KEBCWOB - UPS Outlook - 5

text_image RS232 RS485 USB Parallel Board Dry Contact Protective Cover SNMP Maintenance CB Bypass Input CB Main input CB Output CB Connection terminal

Fig.1-11 10/15 kVA back appearance

CyberPower HSTP3T30KEBCWOB - UPS Outlook - 6

text_image SNP Dry Contact Parallel board USB Main input CB 232 485 Bypass Input CB Air vent Maintenance switch Output CB Protective cover Connection terminals

Fig.1-12 20/30kVA back appearance

CyberPower HSTP3T30KEBCWOB - UPS Outlook - 7

text_image SNMP Output CB Maintenance switch 232 485 USB Parallel board Dry contact Bypass Input CB Air vent Input CB Connection terminals

Fig.1-13 40kVA long type back appearance

CyberPower HSTP3T30KEBCWOB - UPS Outlook - 8

text_image SNMP Battery cold start USB Parallel board Dry contacts 232 485 Inbuilt battery CB Maintenacne bypass CB Output CB Bypass CB Input CB Connection terminals

Fig.1-13 40kVA standard type front appearance

CyberPower HSTP3T30KEBCWOB - UPS Outlook - 9

Note

The Standard product is configured with single input; the dual-input option is available, with an additional breaker for the main input

Chapter 2 Installation Instruction

2.1 Location

As each site has its requirements, the installation instructions in this section are to act as a guide for the general procedures and practices that should be observed by the installing engineer.

2.1.1 Installation Environment

The UPS is intended for indoor installation and uses forced convection cooling by internal fans. Please make sure there is enough space for the UPS ventilation and cooling.

Keep the UPS far away from water, heat and inflammable and explosive, corrosive material. Avoid installing the UPS in the environment with direct sunlight, dust, volatile gases, corrosive material and high salinity.

Avoid installing the UPS in the environment with conductive dirt.

The operating environment temperature for battery is 20^ C - 25^ C. Operating above 25^ C will reduce the battery life, and operation below 20^ C will reduce the battery capacity.

The battery will generate a little amount of hydrogen and oxygen at the end of charging; ensure the fresh air volume of the battery installation environment must meet EN50272-2001 requirements.

If external batteries are to be used, the battery circuit breakers (or fuses) must be mounted as close as possible to the batteries, and the connecting cables should be as short as possible.

2.1.2 Site Selection

Ensure the ground or installation platform can bear the weight of the UPS cabinet, batteries and battery rack.

No vibration and less than 5 degree inclination horizontally.

The equipment should be stored in a room so as to protect it against excessive humidity and heat sources.

The battery needs to be stored in dry and cool place with good ventilation. The most suitable storage temperature is 20^ C to 25^ C.

2.1.3 Size and Weight

The size of three dimensions for the UPS cabinet is shown in Fig. 2-1.

CyberPower HSTP3T30KEBCWOB - Size and Weight - 1

Attention

Ensure there is at least 0.8m before the front of the cabinet so as to easily maintain and at least 0.5m behind for ventilation and cooling. The room reserved for the cabinet is shown in Fig. 2-4.

CyberPower HSTP3T30KEBCWOB - Attention - 1

text_image 461,7 530,5

CyberPower HSTP3T30KEBCWOB - Attention - 2

text_image 654.5 688.2

Fig.2-1-1 Size of the 10/15 kVA UPS of Long Backup Type (Unit : mm)

CyberPower HSTP3T30KEBCWOB - Attention - 3

text_image 641,2 714,2

CyberPower HSTP3T30KEBCWOB - Attention - 4

text_image 834.9 868.7

Fig.2-1-2 Size of the 10/15 kVA UPS of standard backup Type (Unit : mm)

CyberPower HSTP3T30KEBCWOB - Attention - 5

text_image 700.0 768.5

CyberPower HSTP3T30KEBCWOB - Attention - 6

text_image 684.7 733.2

Fig.2-2-1 Size of the 20/30kVA UPS of Long Backup Type (Unit : mm)

CyberPower HSTP3T30KEBCWOB - Attention - 7

text_image 1241.0 1333.5

CyberPower HSTP3T30KEBCWOB - Attention - 8

text_image 684,7 733,2

Fig.2-2-2 Size of the 20/30kVA UPS of Standard Backup Type (Unit : mm)
CyberPower HSTP3T30KEBCWOB - Attention - 9

text_image 700,4 768,9

CyberPower HSTP3T30KEBCWOB - Attention - 10

text_image 834,5 889,7

Fig.2-3-1 Size of the 40kVA UPS Long Backup Type (Unit : mm)

CyberPower HSTP3T30KEBCWOB - Attention - 11

text_image 1400 500

CyberPower HSTP3T30KEBCWOB - Attention - 12

natural_image Technical line drawing of a rectangular frame with dimension标注 (no text or symbols)

Fig.2-3-2 Size of the 40kVA UPS Standard Type (Unit: mm)

CyberPower HSTP3T30KEBCWOB - Attention - 13

text_image ≥500 ≥500 ≥800

Fig.2-4 Room reserved for the cabinet(Unit : mm)

The weight for the UPS cabinet is shown in Table 2.1

Table 2.1 Weight for the cabinet

ConfigurationWeight
10kVA/15kVA Standard Backup Type52kg(No Batteries Included)
10kVA/15kVA Long Backup Type31kg
20kVA/30kVA Standard Backup Type89kg(No Batteries Included)
20kVA/30kVA Long Backup Type50kg
40kVA Standard Backup Type140kg(No Batteries Included)
40kVA Long Backup Type61kg

2.2 Unloading and Unpacking

2.2.1 Moving and Unpacking of the Cabinet

The steps to move and unpack the cabinet are as follows :

  1. Check if any damages to the packing. (If any, contact to the carrier)
  2. Transport the equipment to the designated site by forklift, as shown in Fig.2-5.

CyberPower HSTP3T30KEBCWOB - Moving and Unpacking of the Cabinet - 1

natural_image Simple line drawing of a rectangular block mounted on a base with diagonal supports (no text or symbols)

Fig.2-5 Transport to the designated site

  1. Unpack the package (see Fig.2-6).

CyberPower HSTP3T30KEBCWOB - Moving and Unpacking of the Cabinet - 2

natural_image Technical line drawing of a vertical industrial or storage unit with internal components and mounting base (no text or symbols)

Fig.2-6 Disassemble the case

  1. Remove the protective foam around the cabinet.

CyberPower HSTP3T30KEBCWOB - Moving and Unpacking of the Cabinet - 3

natural_image Technical line drawing of a large industrial machine with cooling unit and conveyor belt (no text or symbols)

Fig.2-7 Remove the protective foam

  1. Check the UPS.

(a) Visually examine if there are any damages to UPS during transportation. If any, contact to the carrier.
(b) Check the UPS with the list of the goods. If any items are not included in the list, contact to our company or the local office.

  1. Dismantle the bolt that connects the cabinet and wooden pallet after disassembly.

  2. Move the cabinet to the installation position.

CyberPower HSTP3T30KEBCWOB - Moving and Unpacking of the Cabinet - 4

Attention

Be careful while removing to avoid scratching the equipment.

CyberPower HSTP3T30KEBCWOB - Attention - 1

Attention

The waste materials of unpacking should be disposed to meet the demand for environmental protection.

2.3 Positioning

2.3.1 Positioning Cabinet

The UPS cabinet has two ways of supporting itself: One is to support itself temporarily by the four wheels at the bottom, making it convenient to adjust the position of the cabinet; The other is by anchor bolts to support the cabinet permanently after adjusting the position of the cabinet. The supporting structure is shown in Fig. 2-8.

CyberPower HSTP3T30KEBCWOB - Positioning Cabinet - 1

text_image Anchor bolt Wheels Bracket

Fig.2-8 Supporting structure (Bottom view)

The steps to position the cabinet are as follows :

  1. Ensure the supporting structure is in good condition and the mounting floor is smooth and strong.
  2. Retract the anchor bolts by turning them counterclockwise using wrench, the cabinet is then supported by the four wheels.
  3. Adjust the cabinet to the right position by the supporting wheels.
  4. Put down the anchor bolts by turning them clockwise using wrench, the cabinet is then supported by the four anchor bolts.
  5. Ensure the four anchor bolts are in the same height and the cabinet is fixed and immovable.
  6. Positioning done.

CyberPower HSTP3T30KEBCWOB - Positioning Cabinet - 2

Attention

Auxiliary equipment is needed when the mounting floor is not solid enough to support the cabinet, which helps distribute the weight over a larger area. For instance, cover the floor with iron plate or increase the supporting area of the anchor bolts.

2.4 Battery

Three terminals (positive, neutral, negative) are drawn from the battery unit and connected to UPS system. The neutral line is drawn from the middle of the batteries in series (See Fig.2-9).

CyberPower HSTP3T30KEBCWOB - Battery - 1

text_image N BAT+ BAT- + N - + 1 - + 2 - ... + 20 - + - ... + - + 403921 40 batteries in series

Fig.2-9 Battery string wiring diagram

CyberPower HSTP3T30KEBCWOB - Battery - 2

Danger

The battery terminal voltage is of more than 200Vdc, please follow the safety instructions to avoid electric shock hazard.

Ensure the positive, negative, neutral electrode is correctly connected from the battery unit terminals to the breaker and from the breaker to the UPS system.

2.5 Cable Entry

Cables can enter the UPS cabinet from the side or from the bottom. Cable entry is made possible through a blanking plate fitted at the bottom of the equipment. The cable entry is shown in Fig.2-10.

CyberPower HSTP3T30KEBCWOB - Cable Entry - 1

text_image Technical schematic diagram of a server rack with labeled components and directional arrows indicating flow or movement.

Fig.2-10 Cable entry

2.6 Power Cables

2.6.1 Specifications

The UPS power cables are recommended in Table 2.2.

Table 2.2 Recommended cables for power cables

Contents10/15kVA20/30kVA40kVA
Main InputMain Input Current(A)18/28A35/55A70A
Cable Section (mm2)A61016
B61016
C61016
N61016
Main OutputMain Output Current(A)15/23A30/45A60A
Cable Section (mm2)A61016
B61016
C61016
N61016
Bypass Input (Optional)Bypass Input Current(A)15/23A30/45A60A
Cable Section (mm2)A61016
B61016
C61016
N61016
Battery InputBattery Input current(A)20/30A40/60A80A
Cable Section (mm2)+81625
-81625
N81625
PECable Section (mm2)PE 6 1016

CyberPower HSTP3T30KEBCWOB - Specifications - 1

Note

The recommended cable section for power cables are only for situations described below :

● Ambient temperature : 30°C.
- AC loss less than 3%, DC loss less than 1%, The length of the AC power cables are no longer than 50 m and the length of the DC power cables are no longer than 30 m.
● Currents listed in the table are based on the 208V system (Line-to-line voltage).
- The size of neutral lines should be 1.5\~1.7 times the value listed above when the predominant load is non-linear.

2.6.2 Specifications for Power Cables Terminal

Specifications for power cables connector are listed as Table 2.3.

Table 2.3 Requirements for terminal

PortConnectionBoltBolt ApertureTorque Moment
Mains inputCables crimped OT terminalM6 7mm4.9Nm
Bypass InputCables crimped OT terminalM6 7mm4.9Nm
Battery InputCables crimped OT terminalM6 7mm4.9Nm
OutputCables crimped OT terminalM6 7mm 4.9Nm
PECables crimped OT terminalM6 7mm 4.9Nm

2.6.3 Circuit Breaker

The circuit breakers (CB) for the system are recommended in Table 2.4.

Table 2.4 Recommended CB

Installed position10/15kVA20kVA30kVA40kVA
Battery CB32A,250Vdc50A,250Vdc63A,250Vdc100A,250Vdc

CyberPower HSTP3T30KEBCWOB - Circuit Breaker - 1

Attention

The CB with RCD (Residual Current Device) is not suggested for the system.

2.6.4 Connecting Power Cables

The steps of connecting power cables are as follows:

  1. Verify that all the switches of the UPS are completely open and the UPS internal maintenance bypass switch is open. Attach necessary warning signs to these switches to prevent unauthorized operation.
  2. Open the back door of the cabinet, remove the plastic cover. The input and output terminal, battery terminal and protective earth terminal are shown in Fig.2-11 &Fig 2.13.

CyberPower HSTP3T30KEBCWOB - Connecting Power Cables - 1

text_image PE BATT INPUT OUTPUT + 11 - mA bA mB bB mC bC 11 A B C 11

Fig.2-11 connections terminals for 10/15kVA
CyberPower HSTP3T30KEBCWOB - Connecting Power Cables - 2

text_image PE N C B A = N + OUTPUT BATTERY N bC mC bB mB bA mA

Fig.2-12 connections terminals for 20/30kVA

CyberPower HSTP3T30KEBCWOB - Connecting Power Cables - 3

text_image INPUT mA bA mB bB mC bC H OUTPUT BATT A B C H + H -

Fig.2-13 Connections terminals for 40kVA

  1. Connect the protective earth wire to protective earth terminal (PE).
  2. Connect the AC input supply cables to the Input terminal and AC output supply cables to the Output terminal.
  3. Connect the Battery cables to the Battery terminal.
  4. Check to make sure there is no mistake and re-install all the protective covers.

Note: mA, mB, mC standard for Main input phase A,B and C; bA, bB, bC standard for Bypass Input phase A,B and C.

CyberPower HSTP3T30KEBCWOB - Connecting Power Cables - 4

Attention

The operations described in this section must be performed by authorized electricians or qualified technical personnel. If you have any difficulties, contact the manufacturer or agency.

CyberPower HSTP3T30KEBCWOB - Attention - 1

Warning

  • Tighten the connections terminals to enough torque moment, refer to Table 2.3, and please ensure correct phase rotation.
  • The grounding cable and neutral cable must be connected in accordance with local and national codes.
  • When the cable holes does not goes through by cables, it should be filled by the hole stopper

2.7 Control and Communication Cables

The front panel of the bypass module provides dry contact interface (J2-J11) and communication interface (RS232, RS485, SNMP, Intelligent card interface and USB port), as it is shown in Fig.2-14.

CyberPower HSTP3T30KEBCWOB - Control and Communication Cables - 1

text_image Intelligent card slot COLD START R232 232 485 Dry Contact Parallel board USB

Fig.2-14 Dry contact & communication interface

2.7.1 Dry Contact Interface

Dry contact interface includes port J2-J11 and the functions of the dry contact are shown in Table 2.5.

Table 2.5 Functions of the port

Port Name Function
J2-1TEMP_BATDetection of battery temperature
J2-2TEMP_COMCommon terminal for temperature detection
J3-1ENV_TEMPDetection of environmental temperature
J3-2TEMP_COMCommon terminal for temperature detection
J4-1REMOTE_EPO_NCTrigger EPO when disconnect with J4-2
J4-2+24V_DRY+24V
J4-3+24V_DRY+24V
J4-4REMOTE_EPO_NOTrigger EPO when shorted with J4-3
J5-1+24V_DRY+24V
J5-2 GEN_CONNECTEDInput dry contact, function is settable,Default: interface for generator
J5-3GND_DRYGround for +24V
J6-1 BCB DriveOutput dry contact, function is settable.Default: Battery trip signal
J6-2 BCB_StatusInput dry contact, function is settable.Default: BCB Status and BCB Online, (Alert no battery when BCB Status is invalid).
J7-1GND_DRYGround for +24V
J7-2 BCB_OnlineInput dry contact, function is settable.Default: BCB Status and BCB Online (Alert no battery when BCB Status is invalid).
J8-1 BAT_LOW_ALARM_NCOutput dry contact (Normally closed), function is settable.Default: Low battery alarming
J8-2 BAT_LOW_ALARM_NOOutput dry contact (Normally open), function is settable.Default: Low battery alarming
J8-3BAT_LOW_ALARM_GNDCommon terminal for J8-1 and J8-2
J9-1GENERAL_ALARM_NCOutput dry contact, (Normally closed) function is settable.Default: Fault alarming
J9-2GENERAL_ALARM_NOOutput dry contact, (Normally open) function is settable.Default: Fault alarming
J9-3GENERAL_ALARM_GNDCommon terminal for J9-1 and J9-2
J10-1UTILITY_FAIL_NCOutput dry contact, (Normally closed) function is settable.Default: Utility abnormal alarming
J10-2UTILITY_FAIL_NOOutput dry contact, (Normally open) function is settable.Default: Utility abnormal alarming
J10-3UTILITY_FAIL_GNDCommon terminal for J10-1 and J10-2

CyberPower HSTP3T30KEBCWOB - Dry Contact Interface - 1

Note

The settable functions for each port can be set by the monitor software.

The default functions of each port are described as follows.

Battery Warning Output Dry Contact Interface

The input dry contact J2 and J3 can detect the temperature of batteries and environment respectively, which can be used in environment monitoring and battery temperature compensation.

Interfaces diagram for J2 and J3 are shown in Fig.2-15, the description of interface is in Table 2.6.

CyberPower HSTP3T30KEBCWOB - Battery Warning Output Dry Contact Interface - 1

Fig.2-15 J2 and J3 for temperature detecting

Table 2.6 Description of J2 and J3

PortNameFunction
J2-1TEMP_BATDetection of battery temperature
J2-2TEMP_COMCommon terminal
J3-1ENV_TEMPDetection of environmental temperature
J3-2TEMP_COMCommon terminal

CyberPower HSTP3T30KEBCWOB - Battery Warning Output Dry Contact Interface - 2

Note

Specified temperature sensor is required for temperature detection, please confirm with the manufacturer, or contact the local maintenance engineers when placing an order.

Remote EPO Input Port

J4 is the input port for remote EPO. It requires shorting NC and +24V and disconnecting NO and +24V during normal operation, and the EPO is triggered when opening NC and +24V or shorting the NO and +24V. The port diagram is shown in Fig.2-16, and port description is shown in Table 2.7.

CyberPower HSTP3T30KEBCWOB - Remote EPO Input Port - 1

Fig.2-16 Diagram of input port for remote EPO
Table 2.7 Description of input port for remote EPO

PortNameFunction
J4-1REMOTE_EPO_NCTrigger EPO when disconnect with J4-2
J4-2+24V_DRY+24V
J4-3+24V_DRY+24V
J4-4REMOTE_EPO_NOTrigger EPO when connect with J4-3

Generator Input Dry Contact

The default function of J5 is the interface for generator J5 Connect pin 2 of J5 with +24V power supply; it indicates that the generator has been connected with the system. The interface diagram is shown in Fig.2-17, and interface description is shown in Table 2.8.

CyberPower HSTP3T30KEBCWOB - Generator Input Dry Contact - 1

text_image +24V J5 GEN AUX-N.O. AUX-N.O. Generator

Fig.2-17 Diagram of status interface and connection of generator

Table 2.8 Description of status interface and connection of generator

PortNameFunction
J5-1+24V_DRY+24V
J5-2GEN_CONNECTEDConnection status of generator
J5-3GND_DRYPower ground for +24V

BCB Input Port

The default function of J6 and J7 are the ports of BCB. The port diagram is shown in Fig.2-18, and description is shown in Table 2.9.

CyberPower HSTP3T30KEBCWOB - BCB Input Port - 1

text_image +24V +24V J6 J7 G A B N H +24V

Fig.2-18 BCB Port

Table 2.9 Description of BCB port

PortNameFunction
J6-1 BCB_DRIVBCB contact drive, provides +24V voltage, 20mA drive signal
J6-2 BCB_StatusBCB contact status, connect with the normally open signal of BCB
J7-1GND_DRYPower ground for +24V
J7-2 BCB_OnlineBCB on-line input (normally open), BCB is on-line when the signal is connecting with J7-1

Battery Warning Output Dry Contact Interface

The default function of J8 is the output dry contact interface, which presents the battery warnings of low or excessive voltage, when the battery voltage is lower than set value, an auxiliary dry contact signal will be activated via the isolation of a relay. The interface diagram is shown in Fig.2-19, and description is shown in Table 2.10.

CyberPower HSTP3T30KEBCWOB - Battery Warning Output Dry Contact Interface - 1

text_image J8 N O A C F W B G D G

Fig.2-19 Battery warning dry contact interface diagram

Table2.10 Battery warning dry contact interface description

PortNameFunction
J8-1 BAT_LOW_ALARM_NCBattery warning relay (normally closed) will be open during warning
J8-2 BAT_LOW_ALARM_NOBattery warning relay (normally open) will be closed during warning
J8-3BAT_LOW_ALARM_GNDCommon terminal

General Alarm Output Dry Contact Interface

The default function of J9 is the general alarm output dry contact interface. When one or more warnings are triggered, an auxiliary dry contact signal will be active via the isolation of a relay. The interface diagram is shown in Fig.2-20, and description is shown in Table 2.11.

CyberPower HSTP3T30KEBCWOB - General Alarm Output Dry Contact Interface - 1

text_image J9 A B C D GND

Fig.2-20 Integrated warning dry contact interface diagram

Table2.11 General alarm dry contact interface description

PortNameFunction
J9-1 GENERAL_ALARM_NCIntegrated warning relay (normally closed) will be open during warning
J9-2 GENERAL_ALARM_NOIntegrated warning relay (normally open) will be closed during warning
J9-3GENERAL_ALARM_GNDCommon terminal

Utility Fail Warning Output Dry Contact Interface

The default function of J10 is the output dry contact interface for utility failure warning, when the utility fails, the system will send a utility failure warning information, and provide an auxiliary dry contact signal via the isolation of a relay. The interface diagram is shown in Fig.2-21, and description is shown in Table 2.12.

CyberPower HSTP3T30KEBCWOB - Utility Fail Warning Output Dry Contact Interface - 1

text_image J10 Zn Zn Zn

Fig.2-21 Utility failure warning dry contact interface diagram

Table 2.12 Utility failure warning dry contact interface description

PortNameFunction
J10-1 UTILITY_FAIL_NCMains failure warning relay(normally closed) will be open during warning
J10-2 UTILITY_FAIL_NOMains failure warning relay (normally open) will be closed during warning
J10-3UTILITY_FAIL_GNDCommon terminal

2.7.2 Communication Interface

RS232、RS485 and USB port: Provide serial data which can be used for commissioning and maintenance by authorized engineers or can be used for networking or integrated monitoring system in the service room.

SNMP: Used on site installation for communication (Optional).

Intelligent card interface: Extension dry contact interface (Optional).

Chapter 3 LCD Panel

3.1 Introduction

This chapter introduces the functions and operator instructions of the operator control and display panel in detail, and provides LCD display information, including LCD display types, detailed menu information, prompt window information and UPS alarm information.

3.2 LCD panel for Cabinet

The structure of operator control and display panel for cabinet is shown in Fig.3-1.

CyberPower HSTP3T30KEBCWOB - LCD panel for Cabinet - 1

text_image STATUS BYP EPO REC MY OUTPUT HOME ENTER CyberPower

Fig.3-1 Control and display panel for cabinet

The LCD panel for cabinet is divided into three functional areas : LED indicator, control and operation keys and LCD screen.

3.2.1 LED Indicator

There are 6 LEDs on the panel to indicate the operating status and fault. (See Fig.3-1). The description of indicators is shown in Table 3.1

Table 3.1 Status description of indicators

IndicatorsStateDescription
Rectifier indicatorSteady greenRectifier normal
Flashing greenRectifier normal for at least one module, mains normal
Steady redRectifier fault
Flashing redMains abnormal for at least one module
OffRectifier not operating
Battery indicatorSteady greenBattery charging
Flashing greenBattery discharging
Steady redBattery abnormal (battery failure, no battery or battery reversed) or battery converter abnormal (failure, over current or over temperature), EOD
Flashing redBattery low voltage
OffBattery and battery converter normal, battery not charging
Bypass indicatorSteady greenLoad supplied by bypass
Steady redBypass abnormal or out of normal range, or static bypass switch fault
Flashing redBypass voltage abnormal
OffBypass normal
Inverter indicatorSteady greenLoad supplied by inverter
Flashing greenInverter on, start, synchronization or standby (ECO mode) for at least one module
Steady redSystem output not supplied by inverter, inverter fault for at least one module.
Flashing redSystem output supplied by inverter, inverter fault for at least one module.
OffInverter not operating
Load indicatorSteady greenUPS output ON and normal
Steady redUPS overload time is out, or output short, or output no power supply
Flashing redOverload output of UPS
OffNo output of UPS
Status indicatorSteady greenNormal operation
Steady redFailure

There are two different types of audible alarm during UPS operation, as shown in Table 3.2.

Table 3.2 Description of audible alarm

AlarmDescription
Two short alarm with a long oneWhen system has general alarm (for example: AC fault),
Continuous alarmWhen system has serious faults (for example: fuse or hardware fault)

3.2.2 Control and Operation Keys

Control and operation keys include four keys. The functions description is shown in Table 3.3.

Table 3.3 Functions of Control and operation keys

Function KeyDescription
EPOLong press, cut off the load power (shut down the rectifier, inverter, static bypass and battery)
HOMEBack to home page
<Page up
>Page down
ENTERConfirm

CyberPower HSTP3T30KEBCWOB - Control and Operation Keys - 1

Attention

When bypass frequency is over track, there is interruption time(less than 10ms) for transferring from bypass to inverter.

3.2.3 LCD Screen

After the monitoring system starts self-test, the system enters the home page, following the welcome window. The home page is shown in Fig.3-2.

Home page consists of System Information Window, Menu Window and Current Command and Record Menu.

CyberPower HSTP3T30KEBCWOB - LCD Screen - 1

flowchart
graph TD
    A["IP"] --> B["Switch"]
    B --> C["="]
    C --> D["OP"]
    B --> E["+"]
    E --> F["Power icon"]
    B --> G["Computer monitor"]
    B --> H["Key key"]
    B --> I["Document icon"]
    B --> J["Speaker icon"]

Fig.3-2 Home page

The description of LCD icons is shown in Table 3.4.

Table 3.4 Description of LCD Icons

IconDescription
CyberPower HSTP3T30KEBCWOB - LCD Screen - 2Power On/Off button
CyberPower HSTP3T30KEBCWOB - LCD Screen - 3Parameters of Main & Bypass Input
CyberPower HSTP3T30KEBCWOB - LCD Screen - 4History log
CyberPower HSTP3T30KEBCWOB - LCD Screen - 5Function set(Fault Clear, Battery Test, Battery Maintenance, language set, Manual Transfer, etc.), System Configuration(For Service Engineer Only)
CyberPower HSTP3T30KEBCWOB - LCD Screen - 6Parameters of Battery, DC bus information, Temperature etc.
CyberPower HSTP3T30KEBCWOB - LCD Screen - 7Parameters of Output & Load
CyberPower HSTP3T30KEBCWOB - LCD Screen - 8Warning, S-code and System Information(Rated parameters, Version Information)
Mute Button

Select the icon, system enters the corresponding page; take the icon (Main Input) for example, as shown in Fig.3-3.

CyberPower HSTP3T30KEBCWOB - LCD Screen - 9I/P MAINCyberPower HSTP3T30KEBCWOB - LCD Screen - 10 NEXT
ABC
220.1 V220.1 V220.1 V
45.0 A45.0 A45.0 A
50.01 Hz50.01 Hz50.01 Hz
0.99 PF0.99 PF0.99 PF

Fig.3-3 Main input page

Select the icon of 📄, it will display the information of battery, as shown in Fig.3-4.

CyberPower HSTP3T30KEBCWOB - LCD Screen - 11BATTERYP.1CyberPower HSTP3T30KEBCWOB - LCD Screen - 12NEXT
Batt Volt240.0V240.0V
Batt Curr5.0A5.0A
Batt Number40
Dischag Times10
StatusBatt Boost

Fig 3-4 Battery Information

Select , to view the current status of the UPS ; Select , to turn off the buzzer raising from general alarms; Select , to view the system information and maintenance code;

Note

The LCD will go to sleep in 2 minutes during which time if there are no warnings or faults. Press any button to wake the screen up.

3.3 System Information Window

System Information Window displays the current time and UPS model, as is shown in the following Table 3.5.

Table 3.5 Description of System Information Window

ContentDescription
HSTP3T20KEUPS mode:3-phase in 3-phase out 20kVA,standard backup type
16:30Current time

3.4 Menu Window

The Menu Window displays the menu name of data window, while the data window displays the related contents of selected menu in menu window. Select UPS menu and data window to browse related parameters of UPS and set related functions. The details are given in Table 3.6.

Table.3.6 Description of UPS Menu

Menu nameMenu item Meaning
Main inputV phase(V)Voltage
I phase(A)Current
Freq.(Hz)Frequency
PFPower factor
Bypass inputV phase(V)Voltage
Freq. (Hz)Frequency
I phase(A)Current
PFPower factor
OutputV phase(V)Voltage
I phase(A)Current
Freq. (Hz)Frequency
PFPower factor
Load of UPSSout (kVA)Apparent Power
Pout (kW)Active Power
Qout (kVAR)Reactive Power
Load (%)Load percent
Battery dataEnvironmental TempEnvironmental Temp
Battery voltage(V)Positive and negative battery voltage
Battery current A)Positive and negative battery current
Battery Temp(°C)Battery Temperature
Remaining Time (Min.)Remained battery backup time
Battery capacity (%)Remained battery capacity
battery boost chargingBattery is working in boost charging mode
battery float chargingBattery is working in float charging mode
Battery disconnectedBattery is not connected
Current alarmDisplay all current alarm. The alarms are displayed on LCD
History logDisplay all history logs.
Function SettingsDisplay calibrationAdjust the accuracy of LCD display
Date format setMONTH-DATE-YEAR and YEAR-MONTH-DATE
formats can be selected
Date & TimeDate/Time set
Language setUser can set the language
Communication set/
Control password 1 setUser can modify control password 1
CommandBattery maintenance testThis test will lead to the battery being partly discharged to activate battery until battery voltage is low. Bypass must be in normal condition, the battery capacity should be above 25%.
Battery self-check testUPS transfer to battery discharge mode to test if the battery is normal. Bypass must be in normal condition, the battery capacity should be above 25%.
Stop testingManually Stop the test including maintenance test, capacity test
UPS system informationMonitoring software versionMonitoring software version
Rectified software versionRectifier software version
Inverted software versionInverter software version
Serial No.The serial NO set when delivered from the factory
Rated informationSystem rated information

3.5 Event List

The following Table3.7 gives events of UPS History Log
Table 3.7 List of History Log

String SequenceLCD Display Explanation
1 LoadOn UPS-Set Load On UPS
2Load On Bypass-SetLoad On Bypass
3No Load-SetNo Load (Output Power Lost)
4Battery Boost-SetCharger is Boosting Battery Voltage
5Battery Float-SetCharger is Floating Battery Voltage
6Battery Discharge-SetBattery is Discharging
7Battery Connected-SetBattery cables Connected
8Battery Not Connected-SetBattery cables Disconnected.
9Maintenance CB Closed-SetMaintenance CB is Closed
10Maintenance CB Open-SetMaintenance CB is Open
11EPO-SetEmergency Power Off
12 Less-SetValid Inverter capacity is less than the load capacity
13Less-ClearIncident above disappears
14Generator Input-SetGenerator as the AC Input Source
15Generator Input-ClearIncident above disappears
16Utility Abnormal-SetUtility (Grid) Abnormal
17Utility Abnormal-ClearIncident above disappears
18Bypass Sequence Error-SetBypass voltage Sequence is reverse
19Bypass Sequence Error-ClearIncident above disappears
20Bypass Volt Abnormal-SetBypass Voltage Abnormal
21Bypass Volt Abnormal-ClearIncident above disappears
22Bypass Module Fail-SetBypass Module Fail
23Bypass Module Fail-ClearIncident above disappears
24Bypass Overload-SetBypass Over load
25Bypass Overload-ClearIncident above disappears
26Bypass Overload Tout-SetBypass Over Load Timeout
27Byp Overload Tout-ClearIncident above disappears
28Byp Freq Over Track-SetBypass Frequency Over Track Range
29Byp Freq Over Track-ClearIncident above disappears
30Exceed Tx Times Lmt-SetTransfer times (from inverter to bypass) in 1 hour exceed the limit.
31Exceed Tx Times Lmt-ClearIncident above disappears
32Output Short Circuit-SetOutput shorted Circuit
33Output Short Circuit-ClearIncident above disappears
34Battery EOD-SetBattery End Of Discharge
35Battery EOD-ClearIncident above disappears
36Battery Test-SetBattery Test Starts
37Battery Test OK-SetBattery Test OK
38Battery Test Fail-SetBattery Test fails
39Battery Maintenance-SetBattery Maintenance Starts
40Batt Maintenance OK-SetBattery maintenance succeeds
41Batt Maintenance Fail-SetBattery maintenance fails
42Rectifier Fail-SetRectifier Fails
43 Rectifier Fail-ClearIncident above disappears
44Inverter Fail-SetInverter Fail
45Inverter Fail-ClearIncident above disappears
46Rectifier Over Temp.-SetRectifier Over Temperature
47Rectifier Over Temp.-ClearIncident above disappears
48Fan Fail-SetFan Fail
49Fan Fail-ClearIncident above disappears
50Output Overload-SetOutput Over Load
51Output Overload-ClearIncident above disappears
52Inverter Overload Tout-SetInverter Over Load Timeout
53INV Overload Tout-ClearIncident above disappears
54Inverter Over Temp.-SetInverter Over Temperature
55Inverter Over Temp.-ClearIncident above disappears
56On UPS Inhibited-SetInhibit system transfer from bypass to UPS (inverter)
57On UPS Inhibited-ClearIncident above disappears
58Manual Transfer Byp-SetTransfer to bypass manually
59Manual Transfer Byp-SetCancel to bypass manually
60Esc Manual Bypass-SetEscape transfer to bypass manually command
61Battery Volt Low-SetBattery Voltage Low
62Battery Volt Low-ClearIncident above disappears
63Battery Reverse-SetBattery pole (positive and negative are reverse)
64Battery Reverse-ClearIncident above disappears
65Inverter Protect-SetInverter Protect ( Inverter Voltage Abnormal or Power Back feed to DC Bus)
66Inverter Protect-ClearIncident above disappears
67Input Neutral Lost-SetInput Grid Neutral Lost
68Bypass Fan Fail-SetBypass Module Fan Fail
69Bypass Fan Fail-ClearIncident above disappears
70Manual Shutdown-SetManually Shutdown
71Manual Boost Charge-SetManually Battery Boost Charge
72Manual Float Charge-SetManually Battery Float Charge
73UPS Locked-SetInhibit to shut down the UPS
74Parallel Cable Error-SetParallel cable in error
75Parallel Cable Error-ClearIncident above disappears
76Lost N+X RedundantLost N+X Redundant
77N+X Redundant Lost-ClearIncident above disappears
78 EOD Sys InhibitedSystem is inhibited to supply after the battery is EOD (end of discharging)
79Power Share Fail-SetPower share is not in balance
80Power Share Fail-ClearIncident above disappears
81Input Volt Detect Fail-SetInput Voltage is abnormal
82Input Volt Detect Fail-ClearIncident above disappears
83Battery Volt Detect Fail-SetBattery Voltage is abnormal
84Batt Volt Detect Fail-ClearIncident above disappears
85Output Volt Fail-SetOutput Voltage is abnormal
86Output Volt Fail-ClearIncident above disappears
87Outlet Temp. Error-SetOutlet Temperature is abnormal
88Outlet Temp. Error-ClearIncident above disappears
89Input Curr Unbalance-SetInput current is not balance
90Input Curr Unbalance-ClearIncident above disappears
91DC Bus Over Volt-SetDC bus over Voltage
92DC Bus Over Volt-ClearIncident above disappears
93REC Soft Start Fail-SetRectifier soft start fails
94REC Soft Start Fail-ClearIncident above disappears
95Relay Connect Fail-SetRelay in open circuit
96Relay Connect Fail-ClearIncident above disappears
97Relay Short Circuit-SetRelay shorted
98Relay Short Circuit-ClearIncident above disappears
99No Inlet Temp. Sensor-SetThe inlet temperature sensor is not connected or abnormal
100No Inlet Temp Sensor-ClearIncident above disappears
101No Outlet Temp. Sensor-SetThe Outlet temperature sensor is not connected or abnormal
102No Outlet Temp. Sensor-ClearIncident above disappears
103Inlet Over Temp.-SetInlet over temperature
104Inlet Over Temp.-ClearIncident above disappears

Chapter 4 Operations

4.1 UPS Start-up

The UPS must be started up by commissioning engineer after the completeness of installation. The steps below must be followed :

  1. Ensure all the circuit breakers are open.
  2. Close the output circuit breaker (CB) and then the input CB and the system starts initializing. If the system has dual inputs, close both of the breakers.
  3. The LCD in front of the cabinet is lit up. The system enters the home page, as shown in Fig.3-2.

  4. Notice the energy bar in the home page, and pay attention to the LED indicators. The rectifier flashes indicating the rectifier is starting up. The LED indicators are listed below in Table 4.1.

Table 4.1 Rectifier starting up

IndicatorStatusIndicatorStatus
Rectifiergreen flashingInverteroff
BatteryredLoadoff
BypassoffStatusred
  1. After 30S, the rectifier indicator goes steady green, presenting the finishing of rectification and bypass static switch closes then the inverter is starting up. The LED indicators are listed below in Table.4.2.

Table 4.2 Inverter starting up

IndicatorStatusIndicatorStatus
RectifiergreenInvertergreen flashing
BatteryredLoadgreen
BypassgreenStatusred
  1. The UPS transfers from the bypass to inverter after the inverter goes normal. The LED indicators are listed below in Table 4.3.

Table 4.3 Supplying the load

IndicatorStatusIndicatorStatus
RectifiergreenInvertergreen
BatteryredLoadgreen
BypassoffStatusred
  1. The UPS is in Normal Mode. Close the battery circuit breakers and the UPS starts charging the battery. The LED indicators are listed below in Table 4.4.

Table 4.4 Normal mode

IndicatorStatusIndicatorStatus
RectifiergreenInvertergreen
BatterygreenLoadgreen
BypassoffStatusgreen
  1. The starting up done.

CyberPower HSTP3T30KEBCWOB - UPS Start-up - 1

Note

  • When the system starts, the stored setting will be loaded.
  • Users can browse all incidents during the process of the starting up by checking the menu Log.

4.2 Procedure for Switching between Operation Modes

4.2.1 Switching the UPS into Battery Mode from Normal Mode

The UPS transfers to Battery model immediately after input circuit breaker disconnects from the utility.

4.2.2 Switching the UPS into Bypass Mode from Normal Mode

Follow the path by selecting the icon of the system to Bypass Mode. and then select Manual Byp to transfer

CyberPower HSTP3T30KEBCWOB - Switching the UPS into Bypass Mode from Normal Mode - 1

Warning

Ensure the bypass is working normally before transferring to bypass mode. Or it may cause failure.

4.2.3 Switching the UPS into Normal Mode from Bypass Mode

Follow the path by selecting the icon of transfer to Normal Mode and then select Manual ESC, the system

CyberPower HSTP3T30KEBCWOB - Switching the UPS into Normal Mode from Bypass Mode - 1

Note

Normally, the system will transfer to the Normal mode automatically. This function is used when the frequency of the bypass is over track and when the system needs to transfer to Normal mode by manual.

4.2.4 Switching the UPS into Maintenance Bypass Mode from Normal Mode

These following procedures can transfer the load from the UPS inverter output to the maintenance bypass supply, which is used for maintaining the bypass module.

  1. Transfer the UPS into Bypass Mode following section 4.2.2.
  2. Open the battery breaker and close the maintenance bypass breaker. And the load is powered through maintenance bypass and static bypass.
  3. Open the input bypass and output breakers.
  4. The load is powered through maintenance bypass.

CyberPower HSTP3T30KEBCWOB - Switching the UPS into Maintenance Bypass Mode from Normal Mode - 1

text_image Screw for protective cover Protective cover Maintenance switch Maintenance switch

Fig.4-2 The cover of maintenance bypass breaker

CyberPower HSTP3T30KEBCWOB - Switching the UPS into Maintenance Bypass Mode from Normal Mode - 2

Waring

Once the cover on the maintenance bypass breaker is removed, the system will transfer to bypass mode automatically.

CyberPower HSTP3T30KEBCWOB - Waring - 1

Waring

Before making this operation, confirm the messages on LCD display to be sure that bypass supply is regular and the inverter is synchronous with it, so as not to risk a short interruption in powering the load.

CyberPower HSTP3T30KEBCWOB - Waring - 1

Danger

Even with the LCD turned off, the terminals of input and output may be still energized.

If you need to maintain the UPS, wait for 10 minutes to let the DC bus capacitor fully discharge before removing the cover.

4.2.5 Switching the UPS into Normal Mode from Maintenance Bypass Mode

These following procedures can transfer the load from the Maintenance Bypass Mode to inverter output.

  1. After finish of maintenance, close the output, bypass breakers and bypass static switch will be turned on in 30S after the LED screen goes on, the bypass indicator goes green and the load is powered through maintenance bypass and static bypass.
  2. Turn off the maintenance bypass switch and fix the protection cover, and then the load is powered through bypass static switch.

  3. Select the icon of

CyberPower HSTP3T30KEBCWOB - Switching the UPS into Normal Mode from Maintenance Bypass Mode - 1

to turn on the inverter.

  1. After 60S, the system transfers to Normal Mode.

CyberPower HSTP3T30KEBCWOB - Switching the UPS into Normal Mode from Maintenance Bypass Mode - 2

Waring

The system will stay on bypass mode until the cover of maintenance bypass breaker is fixed.

4.3 Battery Maintenance

If the battery is not discharged for a long time, it is necessary to test the condition of the battery.

Enter the menu 📄, as is shown in Fig.4-3 and select the icon MaintTest, the system transfers into the Battery mode for discharging. The system will discharge the batteries until the alarm of "Battery low voltage" is given Users can stop the discharging by the "Stop Test"

CyberPower HSTP3T30KEBCWOB - Battery Maintenance - 1

With the icon of BattTest, batteries will be discharged for about 30 seconds, and then re-transfer to normal mode.

BACK ⇌ FUNCTION ⇌ END
ManualByp/EscBatt. Test
Fault ClearMaint Test
Manual INVStop Test

Fig.4.3 Battery maintenance

4.4 EPO

The EPO button located in the operator control and display panel (with cover to avoid disoperation, see Fig.4-5) is designed to switch off the UPS in emergency conditions (e.g., fire, flood, etc.). To achieve this, just press the EPO button, and the system will turn off the rectifier, inverter and stop powering the load immediately (including the inverter and bypass output), and the battery stops charging or discharging.

If the input utility is present, the UPS control circuit will remain active; however, the output will be turned off. To completely isolate the UPS, users need to open the external mains input supply to the UPS.

CyberPower HSTP3T30KEBCWOB - EPO - 1

Warning

When the EPO is triggered, the load is not powered by the UPS. Be careful to use the EPO function.

CyberPower HSTP3T30KEBCWOB - Warning - 1

text_image EPO STATUS BYP EPO REC MY OUTPUT HOME CyberPower ENTER

Fig .4-5 EPO Button

4.5 Installation of Parallel Operation System

4.5.1 Parallel system diagram

Up to four UPS could be paralleled, with a diagram as shown in Fig.4-6.

Power Supply
CyberPower HSTP3T30KEBCWOB - Parallel system diagram - 1

flowchart
graph TD
    subgraph UPS1
        UPS1_1["PS1"] --> UPS1_2["PS1"]
        UPS1_2 --> UPS1_3["PS1"]
        UPS1_3 --> UPS1_4["PS1"]
    end
    subgraph UPS2
        UPS2_1["PS2"] --> UPS2_2["PS2"]
        UPS2_2 --> UPS2_3["PS2"]
        UPS2_3 --> UPS2_4["PS2"]
        UPS2_4 --> UPS2_5["PS2"]
    end
    subgraph UPS3
        UPS3_1["PS3"] --> UPS3_2["PS3"]
        UPS3_2 --> UPS3_3["PS3"]
        UPS3_3 --> UPS3_4["PS3"]
        UPS3_4 --> UPS3_5["PS3"]
    end
    subgraph UPS4
        UPS4_1["PS4"] --> UPS4_2["PS4"]
        UPS4_2 --> UPS4_3["PS4"]
        UPS4_3 --> UPS4_4["PS4"]
        UPS4_4 --> UPS4_5["PS4"]
    end
    subgraph OutputPowerSupply
        PowerSupply["Output Power Supply"] --> LoadConnected["Load Connected"]
    end

Fig. 4-6 Parallel diagram

The parallel board is located at the back of the UPS cabinet, as is shown in Fig.4-7.

CyberPower HSTP3T30KEBCWOB - Parallel system diagram - 2

text_image A HOLD-80077 PANW (12.7) 30000000 LS 8008 LS 8009 LEATHS456 L3 8009 PREYT Zoom in A PARALLEL USB

Fig.4-7 Location of the Parallel board

All the parallel cables are designed to be shielded and double insulated, and are connected between the UPS to form a loop as shown below in Fig. 4-8.

CyberPower HSTP3T30KEBCWOB - Parallel system diagram - 3

text_image Technical diagram of four server rack-mounted electrical units with labeled internal components and connection lines

Fig.4-8 Parallel connection

4.5.2 Parallel system setting

Parallel system connection

For field installation, please connect the cables according to Fig.4-6 and Fig.4-8.

In order to assure that all units are equally utilized and to comply with relevant wiring rules, the following requirements apply:

  1. All units shall be of the same rating and must be connected to the same bypass source.
  2. The bypass and the main input sources must be referenced to the same neutral potential.
  3. Any RCD (Residual Current detecting device), if installed, must be of an appropriate setting and located upstream of the common neutral bonding point. Alternatively, the device must monitor the protective earth currents of the system. Refer to the High Leakage Current Warning in the first part of this manual.

  4. The outputs of all UPS must be connected to a common output bus.

Parallel system software setting

To change the parallel system setting, please follow the steps below.

  1. With the monitoring software from manufacturer, select the page of "Service Setting" as below,

CyberPower HSTP3T30KEBCWOB - Parallel system software setting - 1

text_image Home BypassData MainIpData OutputData BatteryData CabStatus UnitStatus HisLogDown SCodeDown RateSetting ServSetting DetectAdjust ControlCmd FwProgram System Setting Battery Setting Customization WarningSet DryContactSet System Mode Parallel United Number 3 System ID 0 Adjusted Output Voltage Frequency Slew Rate Frequency Synchronization Window LCD Time(Min) Default SaveAll Recover Set

Set "System Mode" to "Parallel", and set the "United Number" to the number of units in parallel. For the setting of system ID with a system of 3 units in parallel, for example, set the number from 0 to 2 for these 3 units accordingly.

Restart the UPS when finish the setting and press the button of "Set". Here the software setting is done. Ensure all the output parameters must be set the same.

Parallel system jumper setting

There are different settings of the jumpers on the parallel board and control board for different parallel system.

The location of connectors on parallel board is shown in Fig.4-11 and control board in Fig.4-12.

CyberPower HSTP3T30KEBCWOB - Parallel system jumper setting - 1

text_image H4 ON OFF X P/1 1 ● 2 ● P/2 1 ● 2 × P/3 1 × 2 × BAR CODE 1 J41 J33 J35 J37 J39 2 J42 J34 J36 J38 J40 J3 P3 J45 J46 J47 PS1409 TF1 REV.A1 2014-06-05 J47 J48 H1 H2 J21 H3 J31 J8

Fig.4-11 Connectors on Parallel board (PS1409_TF1)

CyberPower HSTP3T30KEBCWOB - Parallel system jumper setting - 2

text_image PS1203_CTREV A 2013-11-04 Zoom in jumper connectors

Fig.4-12 Connectors on Control board (PS1203_CT1)

  1. Parallel boards settings

A. For single UPS, no need parallel board. When a parallel board is installed, connectors of J33 to J42 should be shorted by the jumpers.
B. For 2 UPS in parallel, short the connectors of J33/J35/J37/J39/J41 by jumpers on each board, keep connectors of J34/J36/J38/J39/J42 open
C. For 3 or 4 UPS in parallel, keep connectors of J33-J42 open.

  1. Control boards settings

The control board is named as PS1203_CT1.

For single UPS, keep the J21-J25 shorted by jumpers

For parallel, keep all the connectors J21-J25 open. As is shown in Fig.4-12.

Note: The connectors not mentioned keep them untouched.

When all the connection and settings are finished, follow the steps below for the operation of parallel system setup.

  1. Close the output and input breaker of the first unit. Wait for the startup of bypass static switch and rectifier, about 90 seconds later; the system will transfer to normal mode. Check if there is any alarm on LCD and verify the output voltage is correct or not.
  2. Turn on the second unit as the same operation with the first one; the unit will join the parallel system automatically.
  3. Turn on the rest units one by one, and check the information on LCD.
  4. Verify the load sharing with a certain load applied.

Chapter 5 Maintenance

This chapter introduces UPS maintenance, including the maintenance instructions of power module and monitoring bypass module and the replacement method of dust filter.

5.1 Precautions

  1. Only certified engineers are authorized to maintain the UPS.
  2. The components or PCBs should be disassembled from top to bottom, so as to prevent any inclination from high gravity center of the cabinet.
  3. To ensure the safety before maintaining, measure the voltage between operating parts and the earth with multi-meter to ensure the voltage is lower than hazardous voltage, i.e. DC voltage is lower than 60Vdc, and AC maximum voltage is lower than 42.4Vac.
  4. Wait 10 minutes before opening the cover of the power module or the bypass after pulling out from the Cabinet.

5.2 Instruction for Maintaining UPS

For the maintenance of the UPS, please refer to chapter 4.2.4 for the instruction to transfer to maintenance bypass mode. After maintenance, re-transfer to normal mode according to chapter 4.2.5.

5.3 Instruction for Maintaining Battery string

For the Lead-Acid maintenance free battery, when maintenance the battery according to requirements, battery life can be prolonged. The battery life is mainly determined by the following factors:

  1. Installation. The battery should be placed in dry and cool place with good ventilation.
    Avoid direct sunlight and keep away from heat source. When installing, ensure the correct connection to the batteries with same specification.
  2. Temperature. The most suitable storage temperature is 20 °C to 25 °C . The battery life will be shortened if the battery is used under high temperature or in deep discharging status. Refer to product manual for details.
  3. Charging/discharging current. The best charging current for the lead-acid battery is 0.1C. The maximum current for the battery can be 0.3C. The suggested discharging current is 0.05C-3C.
  4. Charging voltage. In most of the time, the battery is in standby state. When the utility is normal, the system will charge the battery in boost mode (Constant voltage with maximum limited) to full and then transfers to the state of float charge.
  5. Discharge depth. Avoid deep discharging; which will greatly reduce the life time of the battery. When the UPS runs in battery mode with light load or no load for a long time, it will cause the battery to deep discharge.
  6. Check periodically. Observe if any abnormality of the battery, measure if the voltage of each battery are in balance. Discharge the battery periodically.

CyberPower HSTP3T30KEBCWOB - Instruction for Maintaining Battery string - 1

Warning

Daily inspection is very important!

Check and confirm the battery connection is tightened regularly, and make sure there is no abnormal heat generated from the battery.

CyberPower HSTP3T30KEBCWOB - Warning - 1

Warning

If a battery has leakage or is damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations.

The waste lead-acid battery is a kind of hazardous waste and is one of the major contaminants controlled by government.

Therefore, its storage, transportation, use and disposal must comply with the national or local regulations and laws about the disposal of hazardous waste and waste batteries or other standards.

According to the national laws, the waste lead-acid battery should be recycled and reused, and it is prohibited to dispose of the batteries in other ways except recycling. Throwing away the waste lead-acid batteries at will or other improper disposal methods will cause severe environment pollution, and the person who does this will bear the corresponding legal responsibilities.

5.3.1 Installation of internal battery

For 10kVA to 40kVA standard UPS, internal battery and the cables within the battery string are not provided as standard; if required, please contact your local agency.

For 10-15kVA UPS, 40 pieces of 7AH/9AH batteries can be installed.

For 20-30kVA UPS, 40 pieces of 12AH battery can be installed.

For 40kVA UPS, 80 pieces of 12Ah batteries can be installed.

For 10-15kVA UPS, there are 40 batteries of to be installed, which are divided into 4 layers. Fig.5-1 shows the installation of battery of the 10-15kVA standard UPS.

CyberPower HSTP3T30KEBCWOB - Installation of internal battery - 1

natural_image Technical line drawing of a multi-level electronic device chassis with visible internal components and mounting brackets (no text or labels)
  1. Dismantle the covers and crossbeams

CyberPower HSTP3T30KEBCWOB - Installation of internal battery - 2

natural_image Technical line drawing of a multi-level industrial storage unit with wheels and compartments (no text or symbols)
  1. Install battery and fix the crossbeams

CyberPower HSTP3T30KEBCWOB - Installation of internal battery - 3

text_image W49 W501 W502 W50 W51

3 · Connect the battery cable according to the series number

CyberPower HSTP3T30KEBCWOB - Installation of internal battery - 4

natural_image Line drawing of a rectangular industrial machine with wheels and side-mounted components (no text or symbols)

4 · Recover the cover
Fig.5-1 Installation of inner battery for 10/15K standard UPS

Fig.5-2 shows the installation of batteries for 20/30K standard UPS. There are 8 groups of batteries in series, with 5 cells for each group. The interconnection among groups is via cable with Anderson Socket.
CyberPower HSTP3T30KEBCWOB - Installation of internal battery - 5

text_image Technical diagram of a multi-level storage or warehouse system with numbered compartments and labeled sections L1, L2, L3.

Fig.5-2-1 Cable interconnection of the battery string

Layer 1. The positive of the battery 1# is connected to battery breaker CB4-2, via the cable labeled L1, and the negative of battery 40# is connected to CB4-6, via the cable labeled L2, as shown in Fig.5-2-2.

CyberPower HSTP3T30KEBCWOB - Installation of internal battery - 6

text_image L1 L2 L3 1 2 3 4 5 6 7 8 9 10 L1 L2 L3

Fig.5-2-2 Cable connection of Lay 1

Layer 2. The positive of the battery 6# is connected to the negative of battery 5#, via the cable labeled L4, and the negative of battery 35# is connected to the positive of battery 36#, via the cable labeled L4, as shown in Fig.5-2-3.

CyberPower HSTP3T30KEBCWOB - Installation of internal battery - 7

Fig.5-2-3 Cable connection of Lay 2

Layer 3. The positive of the battery 11# is connected to the negative of battery 10#, via the cable labeled L4, and the negative of battery 30# is connected to the positive of battery 31#, via the cable labeled L4, as shown in Fig.5-2-4.

CyberPower HSTP3T30KEBCWOB - Installation of internal battery - 8

text_image L4 15 14 13 12 11 26 27 28 29 30 L4 L4

Fig.5-2-4 Cable connection of Lay 3

Layer 4. The positive of the battery 16# is connected to the negative of battery 15#, via the cable labeled L4, and the negative of battery 25# is connected to the positive of battery 26#, via the cable labeled L4. The negative of 20# and the positive of 21#, which are defined as the battery neutral, are connected to CB4-4, as shown in Fig.5-2-5.

CyberPower HSTP3T30KEBCWOB - Installation of internal battery - 9

text_image L4 L4 16 17 18 19 20 21 23 22 24 25 L5

Fig.5-2-5 Cable connection of Lay 4
Fig.5-2 Installation of inner battery for 20, 30K standard UPS

For 40kVA the battery bank has four layers. Each lay has four packages with 5 batteries contained in one package. Fig5-3 shows the connection of each layer.

CyberPower HSTP3T30KEBCWOB - Installation of internal battery - 10

Fig. 5-3 battery connection of each layer

After the connected as shown in Fig 5-3, connect the connectors as following as zoomed in Fig 5-4

Terminal+: W01-1 and W01-2

Terminal N: W03-1, W03-2, W03-4, W03-4

Terminal-: W02-1 and W02-2

CyberPower HSTP3T30KEBCWOB - Installation of internal battery - 11

text_image Technical schematic diagram of a server rack with labeled components and a magnified cross-section view.

Fig. 5-4 Battery terminal connection

After connect the terminal, recover the cover as shown in the following Fig. 5-5

CyberPower HSTP3T30KEBCWOB - Installation of internal battery - 12

natural_image Technical line drawing of an electrical cabinet with multiple internal compartments and fans (no text or symbols)

Fig. 5-5, Recover the cover

CyberPower HSTP3T30KEBCWOB - Installation of internal battery - 13

Warning

Make sure the polarity of the battery is correct according to the diagrams above.

Test and confirm the battery voltage before connecting to the main circuit.

Chapter 6 Product Specification

This chapter provides the specifications of the product, including environmental characteristics mechanical characteristics and electrical characteristics.

6.1 Applicable Standards

The UPS has been designed to conform to the following European and international standards:

Table 6.1 Compliance with European and International Standards

ItemNormative reference
General safety requirements for UPS used in operator access areasEN50091-1-1/IEC62040-1-1/AS 62040-1-1
Electromagnetic compatibility (EMC) requirements for UPSEN50091-2/IEC62040-2/AS 62040-2 (C3)
Method of specifying the performance and test requirements of UPSEN50091-3/IEC62040-3/AS 62040-3 (VFI SS 111)

CyberPower HSTP3T30KEBCWOB - Applicable Standards - 1

Note

The above mentioned product standards incorporate relevant compliance clauses with generic IEC and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/ AS61000 series) and construction (IEC/EN/AS60146 series and 60950).

CyberPower HSTP3T30KEBCWOB - Note - 1

Warning

This product conform the EMC requirements for UPS in Category C3 and it is not suitable for medical equipment.

6.2 Environmental Characteristics

Table 6.2 Environmental Characteristics

ItemUnitRequirements
Acoustic noise level at 1 meterdB58dB @ 100% load, 55dB @ 45% load
Altitude of Operation m≤1000,load derated 1% per 100m from 1000m and 2000m
Relative Humidity%0-95 ,Non condensing
Operating Temperature °C0-40,Battery life is halved for every 10°C increase above 20°C
UPS Storage Temperature°C -40-70

6.3 Mechanical Characteristic

Table 6.3 Mechanical Characteristics for Cabinet

ModelUnit10/15KE10/15KEBC10/15KEBCWOB
Dimension W×D×Hmm250*660*530250*840*715250*840*715
Weightkg3116452
ColorN/ABLACK,RAL 7021
Protection LevelIEC (60529)N/A IP20
ModelUnit20/30KE20/30KEBC20/30KEBCWOB
Dimension W×D×Hmm250*680*770350*738*1335350*738*1335
Weightkg5024789
ColorN/ABLACK,RAL 7021
Protection Level IEC (60529)N/A IP20
ModelUnit40KE40KEBC40KEBCWOB
Dimension W×D×Hmm250*836*770500*840*1400500*840*1400
Weightkg61456140
ColorN/ABLACK,RAL 7021
Protection Level IEC (60529)N/A IP20

6.4 Electrical Characteristics

6.4.1 Electrical Characteristics (Input Rectifier)

Table 6.5 Rectifier AC input Mains)

ItemUnitParameter
Grid System\3 Phases + Neutral + Ground
Rated AC Input VoltageVac380/400/415 (three-phase and sharing neutral with the bypass input)
Rated FrequencyVac50/60Hz
Input voltage range Vac304~478Vac (Line-Line),full load228V~304Vac (Line-Line),load decrease linearly according to the min phase voltage
Input Frequency rangeHz40~70
Input Power factorPF>0.99
THDITHDI%<3% (full Linear Load)

Table 6.6 Battery

ItemsUnitParameters
Battery bus voltageVdcRated: ±240V
Quantity of lead-acid cellsNominal40=[1 battery(12V)],240=[1 battery(2V)]
Float charge voltageV/cell (VRLA)2.25V/cell(selectable from 2.2V/cell ~2.35V/cell)Constant current and constant voltage charge mode
Temperature compensationmV/°C/cl3.0(selectable:0~5.0)
Ripple voltage%≤1
Ripple current%≤5
Equalized charge voltageVRLA2.4V/cell(selectable from : 2.30V/cell~2.45V/cell)Constant current and constant voltage charge mode
Final discharging voltageV/cell (VRLA)1.65V/cell(selectable from: 1.60V/cell~1.750V/cell)@0.6C discharge current1.75V/cell (selectable from: 1.65V/cell~1.8V/cell)@0.15C discharge current(EOD voltage changes linearly within the set range according to discharge current)
Battery Charge V/cell2.4V/cell(selectable from : 2.3V/cell~2.45V/cell)Constant current and constant voltage charge mode
Battery Charging Power Max CurrentkW10%* UPS capacity (selectable from : 1~20% * UPS capacity)

6.4.3 Electrical Characteristics (Inverter Output)

Table 6.7 Inverter Output (To critical load)

ItemUnitValue
Rated capacitykVA10/15/20/30/40
Rated AC voltageVac380/400/415 (Line-Line)
Rated FrequencyHz50/60
Frequency RegulationHz 50/60Hz±0.1%
Voltage precision%±1.5(0~100% linear load)
Overload \110%, 60min;125%,10min;150%,1min;>150%,200ms
Synchronized RangeHz Settable, ±0.5Hz ~ ±5Hz, default ±3Hz
Synchronized Slew RateHz Settable, 0.5Hz/S ~ 3Hz/S, default 0.5Hz/S
Output Power FactorPF 0.9
Transient Response%<5% for step load (20% - 80% -20%)
Transient recovery< 30ms for step load (20% - 100% -20%)
Output Voltage THDu<1% from 0% to 100% linear load<6% full non-linear load according to IEC/EN62040-3

6.4.4 Electrical Characteristics (Bypass Mains Input)

Table 6.8 Bypass Mains Input

Item UnitValue
Rated AC voltageVac380/400/415(three-phase four-wire and sharing neutral with the bypass)
Overload%125% Long term operation;125%~130% for 10min;130%~150% for 1min;150%~400% for 1s;>400%,less than 200ms
Current rating of neutral cableA 1.7×ln
Rated frequencyHz 50/60
Switch time (between bypass and inverter)ms Synchronized transfer: 0ms
Bypass voltage range%Settable, default -20%~+15%Upper limit: +10%, +15%, +20%, +25%Lower limit: -10%, -15%, -20%, -30%, -40%
Bypass frequency range%Hz Settable, ±1Hz, ±3Hz, ±5Hz
Synchronized RangeHzSettable ±0.5Hz~±5Hz, default ±3Hz

6.5 Efficiency

Table 6.9 Efficiency

Rated power(kVA)Unit10/15kVA20/30kVA40kVA
Overall efficiency
Normal mode(dual conversion)% >95>95 >96
Battery discharging efficiency (battery at nominal voltage 480Vdc and full-rated linear load)
Battery mode%>94.5>95>96

6.6 Display and Interface

Table 6.10 Display and Interface

DisplayLED + LCD
InterfaceStandard:RS232, RS485Option: SNMP ,Dry Contact
Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : CyberPower

Model : HSTP3T30KEBCWOB

Category : Inverter