USER MANUAL FCAHG71GVEB DAIKIN
Installer and user reference guide
Split system air conditioners


FCAHG71GVEB
FCAHG100GVEB
FCAHG125GVEB
FCAHG140GVEB
Installer and user reference guide
Split system air conditioners
English
| CE.-DECLARATION/OCONFORMITE | CE.-DECLARATION-DE-CONFORMUIDACE | CE.-DECLARACADE-DE-CONFORMUIDACE | CE.-ERKLIERING OMAANWAR | CE.-ZUANA-OUSKLABERIDIST | CE.-IZUANA O SICLONDIST | CE.-ATTITIKES-DEKLARACILIA |
| CE.-KONFORMITATSENKLURUNG | CE.-DICHAZAZIONE-DI-CONFORMITA | CE.-SARBHEBIE-O-COOTBETCTBH | CE.-LIVOTUS-PRENDNIA/SUDEOSTA | CE.-NEGFELEGEG-EYALTKNZAT | CE.-VASTAVUSDELRASDIODION | CE.-ATISLIJ-BAS-DELARACILIA |
| CE.-DECLARATION/OCONFORMITE | CE.-JHADEN ZYNWOPQIKNE | CE.-OVERENSSTEVENELSESERKLIERING | CE.-PROHLASEN-O-SHOOE | CE.-DEKLARACIA-ZOOKOSCI | CE.-ZEINAPALWR-SA-C'SOTBETCTBME | CE.-YHYLASENE-CHOUY |
| CE.-KONFORMITETSVERKLARING | CE.-FORSAKRAHON-OVERENSTAMWELSE | CE.-FORSAKRAHON-OVERENSTAMWELSE | CE.-DECLARATIE DE CONFORMITATE | CE.-DECLARATIE DE CONFORMITATE | CE.-UYGUNLUX-BEYAN | CE.-UYGUNLUX-BEYAN |
FCAHG71GVEB, FCAHG100GVEB, FCAHG125GVEB, FCAHG140GVEB,
| 11. In some with respect to the following standard (or other normal vs. document), otherwise Ist there are used in accordance with our instructions:22. Cenklem fällenden Komteri (under term and termi formulikturen oder -documenten et charmentinier prechen und unter der Verwaltung, die) sie genauf, unserden Kewen eigengtend amien;33. Son somme a leste normale di autraki (documente) normal (%), suur lauare quile si steni lielle cormentamenti i nos sancima;44. Conform de ogende normale, of de lae di maer e handende documentar, sp. neceada che da se warden oestandere nonverreaming trane instructies;55. Ederan con conforme con (one) ####guative (normal) (or ####c documentar), normatnačia, esperne que sees disfalti de acero do con nusitise instructes;66. Sono conforme (all) sequente (standard), e a trol documentare i caniserve normale a pathe ob wegano uist i normaII alle rere strastru;77. Enapugnare (and i) ####seleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleleledelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelelee |
| 10. Esee an conformadome con (a), seguielte naontrata (no) uod#### (documenten) normal (%), sebeas que ewes sees in az dizos se secece os reze insurek instructions;11. Comercingem organometrical ciegegrime are a gyree inopermeate kup, posmaea, pura, yee na reze inopermeate komonee, uau na rezeypeaee, ovehindare ligeare standard, or a rodkadehini te## yed yede ##kou ##kow, foralid al deide adantato i nortali di ware inklater, represite a laze inlade, ovehindare mormamine inotih and fijler fialcens standard, oderi arra normamine document, under landshing at end sheringing le 1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1 -1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1-1.16. Tredite reke na aza sizvničnikacnak, pagyanyek ražo ralo duco merulinknak, bajah vokrde lae szenit hazsla;17. qasieja wyzny apoguaypugam nami i rich chch dianke remeu rontaminknak, and ahvarknai a byzovone sa goyeana zuznyar indrujejene;18. Sainl a cnomlun kura on umlankol (modemical standard) (sup) u##d documenta normal (sup), cu cerilci na co seceles si fiu lirkski in conformi kinu;19. Sipita noole;20. Akinha a norej mentared in deri ngom normal, podogom na da soj apogim jie a kladu zaiman muroti;21. na vissuava, kryse a sizvnični standa (zeg ve klaste normamine standarda, su nad caudasnila varzati tinei pashidnak;22. Uchertama na chetina chingame ciege prce poyne mehara ceymva, pyycevanne, ye ne ot certiast dornica sizvnični sizvnični;23. minha zemna rurnone standardis si araghi, kryse nurno sizvnični si ayj, kryse ne rcaqym pugal mays morydmu;24. ja fei klaste rizna tizvnični sizvnični, statut seklen standarden i ulan cenni tioni denul cenni;25. za p#saskodors (normal) (normal) (normal) (normal) (normal), za prcpokocci, da ta pozhajni i siste o saliin "savodori";26. Duraan taiti dama mora gola kullan masa kyp lae agadid standarder i norm bilatien bepeleke vularbur; |
| EN60335-2-40. |
| 01. folvcing the provisions of:12. genna del Vorschten der.23. conflamed u loti tipals des24. devemendring de leprogen van sm.35. egundere van de en.46. sconmene i verdeho van;57. je prigning nuir sambifana van38. se acuare van teveide em;9. i concomentive u sconmene van39. Note:as se ad. van die <Phi> and judged poeley by 06. Note:as se ad. van die <Phi> and judged poeley by 07. Note:as se ad. van die <Phi> and judged poeley by 08. Note:as se ad. van die <Phi> and judged poeley by 09. Note:as se ad. van die <Phi> and judged poeley by 10. Note:as se ad. van die <Phi> and judged poeley by 11. Note:as se ad. van die <Phi> and judged poeley by 12. Note:as se ad. van die <Phi> and judged poeley by 13. Note:as se ad. van die <Phi> and judged poeley by 14. Note:as se ad. van die <Phi> and judged poeley by 15. Note:as se ad. van die <Phi> and judged poeley by 16. Note:as se ad. van die <Phi> and judged poeley by 17. Note:as se ad. van die <Phi> and judged poeley by 18. Note:as se ad. van die <Phi> and judged poeley by 19. Note:as se ad. van die <Phi> and judged poeley by 20. Note:as se ad. van die <Phi> and judged poeley by 21. Note:as se ad. van die <Phi> and judged poeley by 22. Note:as se ad. van die <Phi> and judged poeley by 23. Note:as se ad. van die <Phi> and judged poeley by 24. Note:as se ad. van die <Phi> and judged poeley by 25. Note:as se ad. van die <Phi> and judged poeley by 26. Note:as se ad. van die <Phi> and judged poeley by 27. Note:as se ad. van die <Phi> and judged poeley by 28. Note:as se ad. van die <Phi> and judged poeley by 29. Note:as se ad. van die <Phi> and judged poeley by 30. Note:as se ad. van die <Phi> and judged poeley by 31. Note:as se ad. van die <Phi> and judged poeley by 32. Note:as se ad. van die <Phi> and judged poeley by 33. Note:as se ad. van die <Phi> and judged poeley by 34. Note:as se ad. van die <Phi> and judged poeley by 35. Note:as se ad. van die <Phi> and judged poeley by 36. Note:as se ad. van die <Phi> and judged poeley by 37. Note:as se ad. van die <Phi> and judged poeley by 38. Note:as se ad. van die <Phi> and judged poeley by 39. Note:as se ad. van die <Phi> and judged poeley by 40. Note:as se ad. van die <Phi> and judged poeley by 41. Note:as se ad. van die <Phi> and judged poeley by 42. Note:as se ad. van die <Phi> and judged poeley by 43. Note:as se ad. van die <Phi> and judged poeley by 44. Note:as se ad. van die <Phi> and judged poeley by 45. Note:as se ad. van die <Phi> and judged poeley by 46. Note:as se ad. van die <Phi> and judged poeley by 47. Note:as se ad. van die <Phi> and judged poeley by 48. Note:as se ad. van die <Phi> and judged poeley by 49. Note:as se ad. van die <Phi> and judged poeley by 50. Note:as se ad. van die <Phi> and judged poeley by 51. Note:as se ad. van die <Phi> and judged poeley by 52. Note:as se ad. van die <Phi> and judged poeley by 53. Note:as se ad. van die <Phi> and judged poeley by 54. Note:as se ad. van die <Phi> and judged poeley by 55. Note:as se ad. van die <Phi> and judged poeley by 56. Note:as se ad. van die <Phi> and judged poeley by 57. Note:as se ad. van die <Phi> and judged poeley by 58. Note:as se ad. van die <Phi> and judged poeley by 59. Note:as se ad. van die <Phi> and judged poeley by 60. Note:as se ad. van die <Phi> and judged poeley by 61. Note:as se ad. van die <Phi> and judged poeley by 62. Note:as se ad. van die <Phi> and judged poeley by 63. Note:as se ad. van die <Phi> and judged poeley by 64. Note:as se ad. van die <Phi> and judged poeley by 65. Note:as se ad. van die <Phi> and judged poeley by 66. Note:as se ad. van die <Phi> and judged poeley by 67. Note:as se ad. van die <Phi> and judged poeley by 68. Note:as se ad. van die <Phi> and judged poeley by 69. Note:as se ad. van die <Phi> and judged poeley by 70. Note:as se ad. van die <Phi> and judged poeley by 71. Note:as se ad. van die <Phi> and judged poeley by 72. Note:as se ad. van die <Phi> and judged poeley by 73. Note:as se ad. van die <Phi> and judged poeley by 74. Note:as se ad. van die <Phi> and judged poeley by 75. Note:as se ad. van die <Phi> and judged poeley by 76. Note:as se ad. van die <Phi> and judged poeley by 77. Note:as se ad. van die <Phi> and judged poeley by 78. Note:as se ad. van die <Phi> and judged poeley by 79. Note:as se ad. van die <Phi> and judged poeley by 80. Note:as se ad. van die <Phi> and judged poeley by 81. Note:as se ad. van die <Phi> and judged poeley by 82. Note:as se ad. van die <Phi> and judged poeley by 83. Note:as se ad. van die <Phi> and judged poeley by 84. Note:as se ad. van die <Phi> and judged poeley by 85. Note:as se ad. van die <Phi> and judged poeley by 86. Note:as se ad. van die <Phi> and judged poeley by 87. Note:as se ad. van die <Phi> and judged poeley by 88. Note:as se ad. van die <Phi> and judged poeley by 89. Note:as se ad. van die <Phi> and judged poeley by 90. Note:as se ad. van die <Phi> and judged poeley by 91. Note:as se ad. van die <Phi> and judged poeley by 92. Note:as se ad. van die <Phi> and judged poeley by 93. Note:as se ad. van die <Phi> and judged poeley by 94. Note:as se ad. van die <Phi> and judged poeley by 95. Note:as se ad. van die <Phi> and judged poeley by 96. Note:as se ad. van die <Phi> and judged poeley by 97. Note:as se ad. van die <Phi> and judged poeley by 98. Note:as se ad. van die <Phi> and judged poeley by 99. Note:as se ad. van die <Phi> and judged poeley by 100. Note:as se ad. van die <Phi> and judged poeley by 101. Note:as se ad. van die <Phi> and judged poeley by 102. Note:as se ad. van die <Phi> and judged poeley by 103. Note:as se ad. van die <Phi> and judged poeley by 104. Note:as se ad. van die <Phi> and judged poeley by 105. Note:as se ad. van die <Phi> and judged poeley by 106. Note:as se ad. van die <Phi> and judged poeley by 107. Note:as se ad. van die <Phi> and judged poeley by 108. Note:as se ad. van die <Phi> and judged poeley by 109. Note:as se ad. van die <Phi> and judged poeley by 110. Note:as se ad. van die <Phi> and judged poeley by 111. Note:as se ad. van die <Phi> and judged poeley by 112. Note:as se ad. van die <Phi> and judged poeley by 113. Note:as se ad. van die <Phi> and judged poeley by 114. Note:as se ad. van die <Phi> and judged poeley by 115. Note:as se ad. van die <Phi> and judged poeley by 116. Note:as se ad. van die <Phi> and judged poeley by 117. Note:as se ad. van die <Phi> and judged poeley by 118. Note:as se ad. van die <Phi> and judged poeley by 119. Note:as se ad. van die <Phi> and judged poeley by 120. Note:as se ad. van die <Phi> and judged poeley by 121. Note:as se ad. van die <Phi> and judged poeley by 122. Note:as se ad. van die <Phi> and judged poeley by 123. Note:as se ad. van die <Phi> and judged poeley by 124. Note:as se ad. van die <Phi> and judged poeley by 125. Note:as se ad. van die <Phi> and judged poeley by 126. Note:as se ad. van die <Phi> and judged poeley by 127. Note:as se ad. van die <Phi> and judged poeley by 128. Note:as se ad. van die <Phi> and judged poeley by 129. Note:as se ad. van die <Phi> and judged poeley by 130. Note:as se ad. van die <Phi> and judged poeley by 131. Note:as se ad. van die <Phi> and judged poeley by 132. Note:as se ad. van die <Phi> and judged poeley by 133. Note:as se ad. van die <Phi> and judged poeley by 134. Note:as se ad. van die <Phi> and judged poeley by 135. Note:as se ad. van die <Phi> and judged poeley by 136. Note:as se ad. van die <Phi> and judged poeley by 137. Note:as se ad. van die <Phi> and judged poeley by 138. Note:as se ad. van die <Phi> and judged poeley by 139. Note:as se ad. van die <Phi> and judged poeley by 140. Note:as se ad. van die <Phi> and judged poeley by 141. Note:as se ad. van die <Phi> and judged poeley by 142. Note:as se ad. van die <Phi> and judged poeley by 143. Note:as se ad. van die <Phi> and judged poeley by 144. Note:as se ad. van die <Phi> and judged poeley by 145. Note:as se ad. van die <Phi> and judged poeley by 146. Note:as se ad. van die <Phi> and judged poeley by 147. Note:as se ad. van die <Phi> and judged poeley by 148. Note:as se ad. van die <Phi> and judged poeley by 149. Note:as se ad. van die <Phi> and judged poeley by 150. Note:as se ad. van die <Phi> and judged poeley by 151. Note:as se ad. van die <Phi> and judged poeley by 152. Note:as se ad. van die <Phi> and judged poeley by 153. Note:as se ad. van die <Phi> and judged poeley by 154. Note:as se ad. van die <Phi> and judged poeley by 155. Note:as se ad. van die <Phi> and judged poeley by 156. Note:as se ad. van die <Phi> and judged poeley by 157. Note:as se ad. van die <Phi> and judged poeley by 158. Note:as se ad. van die <Phi> and judged poeley by 159. Note:as se ad. van die <Phi> and judged poeley by 160. Note:as se ad. van die <Phi> and judged poeley by 161. Note:as se ad. van die <Phi> and judged poeley by 162. Note:as se ad. van die <Phi> and judged poeley by 163. Note:as se ad. van die <Phi> and judged poeley by 164. Note:as se ad. van die <Phi> and judged poeley by 165. Note:as se ad. van die <Phi> and judged poeley by 166. Note:as se ad. van die <Phi> and judged poeley by 167. Note:as se ad. van die <Phi> and judged poeley by 168. Note:as se ad. van die <Phi> and judged poeley by 169. Note:as se ad. van die <Phi> and judged poeley by 170. Note:as se ad. van die <Phi> and judged poeley by 171. Note:as se ad. van die <Phi> and judged poeley by 172. Note:as se ad. van die <Phi> and judged poeley by 173. Note:as se ad. van die <Phi> and judged poeley by 174. Note:as se ad. van die <Phi> and judged poeley by 175. Note:as se ad. van die <Phi> and judged poeley by 176. Note:as se ad. van die <Phi> and judged poeley by 177. Note:as se ad. van die <Phi> and judged poeley by 178. Note:as se ad. van die <Phi> and judged poeley by 179. Note:as se ad. van die <Phi> and judged poeley by 180. Note:as se ad. van die <Phi> and judged poeley by 181. Note:as se ad. van die <Phi> and judged poeley by 182. Note:as se ad. van die <Phi> and judged poeley by 183. Note:as se ad. van die <Phi> and judged poeley by 184. Note:as se ad. van die <Phi> and judged poeley by 185. Note:as se ad. van die <Phi> and judged poeley by 186. Note:as se ad. van die <Phi> and judged poeley by 187. Note:as se ad. van die <Phi> and judged poeley by 188. Note:as se ad. van die <Phi> and judged poeley by 189. Note:as se ad. van die <Phi> and judged poeley by 190. Note:as se ad. van die <Phi> and judged poeley by 191. Note:as se ad. van die <Phi> and judged poeley by 192. Note:as se ad. van die <Phi> and judged poeley by 193. Note:as se ad. van die <Phi> and judged poeley by 194. Note:as se ad. van die <Phi> and judged poeley by 195. Note:as se ad. van die <Phi> and judged poeley by 196. Note:as se ad. van die <Phi> and judged poeley by 197. Note:as se ad. van die <Phi> and judged poeley by 198. Note:as se ad. van die <Phi> and judged poeley by 199. Note:as se ad. van die <Phi> and judged poeley by 200. Note:as se ad. van die <Phi> and judged poeley by 201. Note:as se ad. van die <Phi> and judged poeley by 202. Note:as se ad. van die <Phi> and judged poeley by 203. Note:as se ad. van die <Phi> and judged poeley by 204. Note:as se ad. van die <Phi> and judged poeley by 205. Note:as se ad. van die <Phi> and judged poeley by 206. Note:as se ad. van die <Phi> and judged poeley by 207. Note:as se ad. van die <Phi> and judged poeley by 208. Note:as se ad. van die <Phi> and judged poeley by 209. Note:as se ad. van die <Phi> and judged poeley by 210. Note:as se ad. van die <Phi> and judged poeley by 211. Note:as se ad. van die <Phi> and judged poeley by 212. Note:as se ad. van die <Phi> and judged poeley by 213. Note:as se ad. van die <Phi> and judged poeley by 214. Note:as se ad. van die <Phi> and judged poeley by 215. Note:as se ad. van die <Phi> and judged poeley by 216. Note:as se ad. van die <Phi> and judged poeley by 217. Note:as se ad. van die <Phi> and judged poeley by 218. Note:as se ad. van die <Phi> and judged poeley by 219. Note:as se ad. van die <Phi> and judged poeley by 220. Note:as se ad. van die <Phi> and judged poeley by 221. Note:as se ad. van die <Phi> and judged poeley by 222. Note:as se ad. van die <Phi> and judged poeley by 223. Note:as se ad. van die <Phi> and judged poeley by 224. Note:as se ad. van die <Phi> and judged poeley by 225. Note:as se ad. van die <Phi> and judged poeley by 226. Note:as se ad. van die <Phi> and judged poeley by 227. Note:as se ad. van die <Phi> and judged poeley by 228. Note:as se ad. van die <Phi> and judged poeley by 229. Note:as se ad. van die <Phi> and judged poeley by 230. Note:as se ad. van die <Phi> and judged poeley by 231. Note:as se ad. van die <Phi> and judged poeley by 232. Note:as se ad. van die <Phi> and judged poeley by 233. Note:as se ad. van die <Phi> and judged poeley by 234. Note:as se ad. van die <Phi> and judged poeley by 235. Note:as se ad. van die <Phi> and judged poeley by 236. Note:as se ad. van die <Phi> and judged poeley by 237. Note:as se ad. van die <Phi> and judged poeley by 238. Note:as se ad. van die <Phi> and judged poeley by 239. Note:as se ad. van die <Phi> and judged poeley by 240. Note:as se ad. van die <Phi> and judged poeley by 241. Note:as se ad. van die <Phi> and judged poeley by 242. Note:as se ad. van die <Phi> and judged poeley by 243. Note:as se ad. van die <Phi> and judged poeley by 244. Note:as se ad. van die <Phi> and judged poeley by 245. Note:as se ad. van die <Phi> and judged poeley by 246. Note:as se ad. van die <Phi> and judged poeley by 247. Note:as se ad. van die <Phi> and judged poeley by 248. Note:as se ad. van die <Phi> and judged poeley by 249. Note:as se ad. van die <Phi> and judged poeley by 250. Note:as se ad. van die <Phi> and judged poeley by 251. Note:as se ad. van die <Phi> and judged poeley by 252. Note:as se ad. van die <Phi> and judged poeley by 253. Note:as se ad. van die <Phi> and judged poeley by 254. Note:as se ad. van die <Phi> and judged poeley by 255. Note:as se ad. van die <Phi> and judged poeley by 256. Note:as se ad. van die <Phi> and judged poeley by 257. Note:as se ad. van die <Phi> and judged poeley by 258. Note:as se ad. van die <Phi> and judged poeley by 259. Note:as se ad. van die <Phi> and judged poeley by 260. Note:as se ad. van die <Phi> and judged poeley by 261. Note:as se ad. van die <Phi> and judged poeley by 262. Note:as se ad. van die <Phi> and judged poeley by 263. Note:as se ad. van die <Phi> and judged poeley by 264. Note:as se ad. van die <Phi |

3P480520-3A
DAIKIN INDUSTRIES CZECH REPUBLIC s.r.o.
U Nové Hospody 1/1155, 301 00 Plzeň Skvrňany,
Czech Republic
Tetsuya Baba
Managing Director
Pilsen, 2nd of May 2017

Table of Contents
Table of Contents
1 General safety precautions 4
1.1 About the documentation .... 4
1.1.1 Meaning of warnings and symbols....4
1.2 For the user 4
1.3 For the installer....4
1.3.1 General 4
3.2.1 To unpack and handle the unit....9
3.2.2 To remove the accessories from the indoor unit..... 9
4 About the units and options 9
4.1 Overview: About the units and options....9
4.2 Identification 9
4.2.1 Identification label: Indoor unit 9
4.3 About the indoor unit 9
4.4 System layout.... 10
4.5 Combining units and options 10
4.5.1 Possible options for the indoor unit.... 10
5 Preparation 10
5.1 Overview: Preparation 10
5.2 Preparing installation site 10
5.2.1 Installation site requirements of the indoor unit ..... 10
5.3 Preparing refrigerant piping.... 11
5.3.1 Refrigerant piping requirements.... 11
5.3.2 Refrigerant piping insulation 12
5.4 Preparing electrical wiring 12
5.4.1 About preparing electrical wiring.... 12
6 Installation 12
6.1 Overview: Installation 12
6.2 Mounting the indoor unit.... 12
6.2.1 Precautions when mounting the indoor unit.... 12
6.2.2 Guidelines when installing the indoor unit.... 12
6.2.3 Guidelines when installing the drain piping.... 13
6.3 Connecting the refrigerant piping 15
6.3.1 About connecting the refrigerant piping 15
6.3.2 Precautions when connecting the refrigerant piping... 15
6.3.3 Guidelines when connecting the refrigerant piping.... 15
6.3.4 Pipe bending guidelines.... 16
6.3.5 To flare the pipe end.... 16
6.3.6 To braze the pipe end.... 16
6.3.7 To connect the refrigerant piping to the indoor unit .... 16
6.4 Connecting the electrical wiring.... 17
6.4.1 About connecting the electrical wiring.... 17
6.4.2 Precautions when connecting the electrical wiring ..... 17
6.4.3 Guidelines when connecting the electrical wiring ..... 17
6.4.4 Specifications of standard wiring components.... 17
6.4.5 To connect the electrical wiring on the indoor unit..... 17
7 Configuration 18
7.1 Field settings 18
8 Commissioning 20
8.1 Overview: Commissioning.... 20
8.2 Precautions when commissioning 20
8.3 Checklist before commissioning.... 20
8.4 To perform a test run 20
8.5 Error codes when performing a test run 21
9 Hand-over to the user 21
10 Disposal 21
11 Technical data 21
11.1 Piping diagram: Indoor unit 22
11.2 Wiring diagram 23
For the user 24
12 About the system 24
12.1 System layout 24
12.2 Information requirements for fan coil units 24
13 User interface 24
14 Before operation 24
15 Operation 25
15.1 Operation range 25
15.2 Operating the system 25
15.2.1 About operating the system 25
15.2.2 About pooling, heating, fan only, and automatic
operation 25
15.2.3 About the heating operation.... 25
15.2.4 To operate the system 25
15.3 Using the dry program 25
15.3.1 About the dry program 25
15 3 2 To use the dry program 25
15.4 Adjusting the air flow direction 26
15.4.1 About the air flow flap 26
16 Energy saving and optimum operation 26
17 Maintenance and service 26
17.1 Cleaning the air filter, suction grille, air outlet and outside
panels 27
17.1.1 To clean the air filter 27
17.1.2 To clean the suction grille 27
17.1.3 To clean the air outlet and outside panels 27
17.2 Maintenance after a long stop period 27
17.3 Maintenance before a long stop period 28
17.4 About the refrigerant 28
17.5 After-sales service and warranty 28
17.5.1 Warranty period 28
17.5.2 Recommended maintenance and inspection 28
17.5.3 Recommended maintenance and inspection cycles 28
17.5.4 Shortened maintenance and replacement cycles.... 29
18 Troubleshooting 29
18.1 Symptoms that are NOT system malfunctions 30
18.1.1 Symptom: The system does not operate 30
18.1.2 Symptom: The fan strength does not correspond to
the setting 30
18.1.3 Symptom: The fan direction does not correspond to
the setting 30
18.1.4 Symptom: White mist comes out of a unit (Indoor
unit) 30
18.1.5 Symptom: White mist comes out of a unit (Indoor
unit, outdoor unit) 30
18.1.6 Symptom: The user interface display reads "U4" or
"U5" and stops, but then restarts after a few minutes.. 30
18.1.7 Symptom: Noise of air conditioners (Indoor unit).... 30
18.1.8 Symptom: Noise of air conditioners (Indoor unit,
outdoor unit).... 30
1 General safety precautions
18.1.9 Symptom: Noise of air conditioners (Outdoor unit) .... 30
18.1.10 Symptom: Dust comes out of the unit 30
18.1.11 Symptom: The units can give off odours.... 30
18.1.12 Symptom: The outdoor unit fan does not spin .... 30
18.1.13 Symptom: The display shows "88" 30
18.1.14 Symptom: The compressor in the outdoor unit does not stop after a short heating operation .... 30
19 Relocation 30
20 Disposal 30
21 Glossary 31
1 General safety precautions
1.1 About the documentation
- The original documentation is written in English. All other languages are translations.
- The precautions described in this document cover very important topics, follow them carefully.
- The installation of the system, and all activities described in the installation manual and the installer reference guide must be performed by an authorized installer.
1.1.1 Meaning of warnings and symbols

DANGER
Indicates a situation that results in death or serious injury.

DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.

DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of extreme hot or cold temperatures.

DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.

WARNING
Indicates a situation that could result in death or serious injury.

WARNING: FLAMMABLE MATERIAL

CAUTION
Indicates a situation that could result in minor or moderate injury.

NOTICE
Indicates a situation that could result in equipment or property damage.

INFORMATION
Indicates useful tips or additional information.
| Symbol | Explanation |
| Before installation, read the installation and operation manual, and the wiring instruction sheet. | |
| Before performing maintenance and service tasks, read the service manual. | |
| For more information, see the installer and user reference guide. |
1.2 For the user
- If you are not sure how to operate the unit, contact your installer.
- This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.

WARNING
To prevent electric shocks or fire:
- Do NOT rinse the unit.
- Do NOT operate the unit with wet hands.
- Do NOT place any objects containing water on the unit.

NOTICE
- Do NOT place any objects or equipment on top of the unit.
- Do NOT sit, climb or stand on the unit.
- Units are marked with the following symbol:

This means that electrical and electronic products may not be mixed with unsorted household waste. Do NOT try to dismantle the system yourself: the dismantling of the system, treatment of the refrigerant, of oil and of other parts must be done by an authorized installer and must comply with applicable legislation. Units must be treated at a specialized treatment facility for reuse, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. For more information, contact your installer or local authority.
• Batteries are marked with the following symbol:

This means that the batteries may not be mixed with unsorted household waste. If a chemical symbol is printed beneath the symbol, this chemical symbol means that the battery contains a heavy metal above a certain concentration. Possible chemical symbols are: Pb: lead (>0.004%). Waste batteries must be treated at a specialized treatment facility for reuse. By ensuring waste batteries are disposed of correctly, you will help to prevent potential negative consequences for the environment and human health.
1.3 For the installer
1.3.1 General
If you are not sure how to install or operate the unit, contact your dealer.

NOTICE
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
Installer and user reference guide
DAIKIN
FCAHG71-140GVEB
Split system air conditioners
4P482875-1-2017.03

WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).

CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,...) when installing, maintaining or servicing the system.

WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.

DANGER: RISK OF BURNING
- Do NOT touch the refrigerant piping, water piping or internal parts during and immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
- Do NOT touch any accidental leaking refrigerant.

WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.

CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.

NOTICE
- Do NOT place any objects or equipment on top of the unit.
- Do NOT sit, climb or stand on the unit.

NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods....
Also, at least, following information must be provided at an accessible place at the product:
- Instructions for shutting down the system in case of an emergency
• Name and address of fire department, police and hospital - Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
- Provide sufficient space around the unit for servicing and air circulation.
- Make sure the installation site withstands the unit's weight and vibration.
- Make sure the area is well ventilated. Do NOT block any ventilation openings.
- Make sure the unit is level.
Do NOT install the unit in the following places:
• In potentially explosive atmospheres.
- In places where there is machinery that emits electromagnetic waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
- In places where there is a risk of fire due to the leakage of flammable gases (example: thinner or gasoline), carbon fibre, ignitable dust.
- In places where corrosive gas (example; sulphurous acid gas) is produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
Instructions for equipment using R32 refrigerant
If applicable.

WARNING
- Do NOT pierce or burn.
- Do NOT use means to accelerate the defrosting process or to clean the equipment, other than those recommended by the manufacturer.
- Be aware that R32 refrigerant does NOT contain an odour.

WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well-ventilated room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater) and have a room size as specified below.

NOTICE
- Do NOT reuse joints which have been used already.
- Joints made in installation between parts of refrigerant system shall be accessible for maintenance purposes

WARNING
Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons.
Installation space requirements

NOTICE
- Pipework shall be protected from physical damage.
- Installation of pipework shall be kept to a minimum.

WARNING
If appliances contain R32 refrigerant, then the floor area of the room in which the appliances are installed, operated and stored must be larger than the minimum floor area defined in table below A (m²). This applies to:
- indoor units,
- outdoor units installed or stored indoors (example: winter garden, garage, machinery room),
- pipework in unventilated spaces.
To determine the minimum floor area
1 Determine the total refrigerant charge in the system (= factory refrigerant charge ① + ② additional refrigerant amount charged).
1 General safety precautions

2 Determine which graph or table to use.
- For indoor units: Is the unit ceiling-mounted, wall-mounted or floor-standing?
- For outdoor units installed or stored indoors, and field piping in unventilated spaces, this depends on the installation height:
| If the installation height is... Then use the graph or table for... | |
| <1.8 m Floor-standing units | |
| 1.8≤x<2.2 m Wall-mounted units | |
| ≥2.2 m Ceiling-mounted units | |
3 Use the graph or table to determine the minimum floor area.
A_(m^2)

line
| m (kg) | FLOOR-STANDING unit (m) | All-mounted unit (m) | Ceiling-mounted unit (m) | | ------ | ------------------------ | --------------------- | ------------------------- | | 1.2 | 0 | 0 | 0 | | 1.5 | 20 | 0 | 0 | | 2 | 40 | 0 | 0 | | 2.2 | 60 | 0 | 0 | | 2.6 | 80 | 0 | 0 | | 3 | 100 | 0 | 0 | | 3.2 | 120 | 0 | 0 | | 3.5 | 140 | 0 | 0 | | 3.8 | 160 | 0 | 0 | | 4 | 180 | 0 | 0 | | 4.2 | 200 | 0 | 0 | | 4.5 | 220 | 0 | 0 | | 5 | 240 | 0 | 0 | | 5.2 | 260 | 0 | 0 | | 5.5 | 280 | 0 | 0 | | 6 | 300 | 0 | 0 | | 6.2 | 320 | 0 | 0 | | 6.5 | 340 | 0 | 0 | | 6.8 | 360 | 0 | 0 | | 7 | 380 | 0 | 0 | | 7.2 | 400 | 0 | 0 | | 7.5 | 420 | 0 | 0 | | 7.8 | 440 | 0 | 0 | | 8 | 460 | 0 | 0 | | 8.2 | 480 | 0 | 0 | | 8.5 | 500 | 0 | 0 | | 8.8 | 520 | 0 | 0 | | 9 | 540 | 0 | 0 | | 9.2 | 560 | 0 | 0 | | 9.5 | 580 | 0 | 0 | | 9.8 | 600 | 0 | 0 | | 10 | 620 | 0 | 0 | | 11 | - | - | - | | 12 | - | - | - | | 13 | - | - | - | | 14 | - | - | - | | 15 | - | - | - | | 16 | - | - | - | | 17 | - | - | - | | 18 | - | - | - | | 19 | - | - | - | | 20 | - | - | - | | 21 | - | - | - | | 22 | - | - | - | | 23 | - | - | - | | 24 | - | - | - | | 25 | - | - | - | | 26 | - | - | - | | 27 | - | - | - | | 28 | - | - | - | | 29 | - | - | - | | 30 | - | - | - | | 31 | - | - | - | | 32 | - | - | - | | 33 | - | - | - | | 34 | - | - | - | | 35 | - | - | - | | 36 | - | - | - | | 37 | - | - | - | | 38 | - | - | - | | 39 | - | - | - | | 40 | - | - | - | | 41 | - | - | - | | 42 | - | - | - | | 43 | - | - | - | | 44 | - | - | - | | 45 | - | - | - | | 46 | - | - | - | | 47 | - | - | - | | 48 | - | - | - | | 49 | - | - | - | | 50 | - | - | - | | 51 | - | - | - | | 52 | - | - | - | | 53 | - | - | - | | 54 | - | - | - | | 55 | - | - | - | | 56 | - | - | - | | 57 | - | - | - | | 58 | - | - | - | | 59 | - | - | - | | 60 | - | - | - | | 61 | - | - | - | | 62 | - | - | - | | 63 | - | - | - | | 64 | - | - | - | | 65 | - | - | - | | 66 | - | - | - | | 67 | - | - | - | | 68 | - | - | - | | 69 | - | - | - | | 70 | - | - | - | | 71 | - | - | - | | 72 | - | - | - | | 73 | - | - | - | | 74 | - | - | - | | 75 | - | - | - | | 76 | - | - | - | | 77 | - | - | - | | 78 | - | - | - | | 79 }| Ceiling-mounted unit(a) |
| m (kg) — Amn (m2) |
| <1.224 —— |
| 1.2250-956 |
| 1.41-25 |
| 1.61-63 |
| 1.82-07 |
| 2.02-55 |
| 2.23-09 |
| 2.43-68 |
| 2.64-31 |
| 2.85-99 |
| 3.05-74 |
| 3.26-54 |
| 3.47-38 |
| 3.68-27 |
| 3.89-22 |
| 4.010-2 |
| 4.211-3 |
| 4.412-4 |
| 4.613-5 |
| 4.814-7 |
| 5.016-9 |
| 5.217-3 |
| 5.418-6 |
| 5.620-9 |
| 5.821-6 |
| 6.023-9 |
| 6.224-5 |
| 6.426-4 |
| 6.627-8 |
| 6.829-5 |
| 7.031-9 |
| 7.233-1 |
| 7.434-9 |
| 7.638-9 |
| 7.838-8 |
| 7.95640-5 |
| Wall-mounted unit ^[b] | |
| m (kg) — A _min (m ^2 ) | |
| <1.224— | |
| 1.2251.43- | |
| 1.41.87- | |
| 1.62.44- | |
| 1.83.09- | |
| 2.03.81- | |
| 2.24.61- | |
| 2.45.49- | |
| 2.66.44- | |
| 2.87.47- | |
| 3.08.58- | |
| 3.29.76- | |
| 3.414.0- | |
| 3.612.4- | |
| 3.813.0- | |
| 4.015.3- | |
| 4.216.8- | |
| 4.418.5- | |
| 4.620.2- | |
| 4.822.0- | |
| 5.023.0- | |
| 5.225.0- | |
| 5.427.0- | |
| 5.629.0- | |
| 5.832.1- | |
| 6.034.3- | |
| 6.236.6- | |
| 6.439.4- | |
| 6.644.6- | |
| 6.844.4- | |
| 7.046.7- | |
| 7.249.4- | |
| 7.452.2- | |
| 7.656.4- | |
| 7.858.0- | |
| 7.95664.0- |
| Floor-standing unit(1) | |
| m (kg) | A_min (m2) |
| <1.224— | |
| 1.22512.9 | |
| 1.416.8 | |
| 1.622.0 | |
| 1.827.8 | |
| 2.034.3 | |
| 2.241.6 | |
| 2.449.4 | |
| 2.658.0 | |
| 2.867.3 | |
| 3.077.2 | |
| 3.287.9 | |
| 3.499.2 | |
| 3.611.1 | |
| 3.812.4 | |
| 4.013.7 | |
| 4.215.1 | |
| 4.416.6 | |
| 4.618.2 | |
| 4.819.8 | |
| 5.021.5 | |
| 5.223.2 | |
| 5.426.0 | |
| 5.626.9 | |
| 5.828.0 | |
| 6.030.9 | |
| 6.233.0 | |
| 6.436.1 | |
| 6.637.4 | |
| 6.839.7 | |
| 7.042.0 | |
| 7.244.5 | |
| 7.447.0 | |
| 7.649.6 | |
| 7.852.2 | |
| 7.9569.8 | |
m Total refrigerant charge in the system
A_min Minimum floor area
(a) Ceiling-mounted unit (= Ceiling-mounted unit)
(b) Wall-mounted unit (= Wall-mounted unit)
(c) Floor-standing unit (= Floor-standing unit)
1.3.3 Refrigerant
If applicable. See the installation manual or installer reference guide of your application for more information.

NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.

NOTICE
Make sure the field piping and connections are not subjected to stress.

WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).

WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
- Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency.
- Toxic gas may be produced if refrigerant gas comes into contact with fire.

DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there is a leakage in the refrigerant circuit:
- Do NOT use the unit's automatic pump down function, with which you can collect all refrigerant from the system into the outdoor unit. Possible consequence: Self-combustion and explosion of the compressor because of air going into the operating compressor.
- Use a separate recovery system so that the unit's compressor does NOT have to operate.

WARNING
Always recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.

NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.

NOTICE
- To avoid compressor breakdown, do NOT charge more than the specified amount of refrigerant.
- When the refrigerant system is to be opened, refrigerant must be treated according to the applicable legislation.

WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
- In case re-charge is required, refer to the nameplate of the unit. It states the type of refrigerant and necessary amount.
- The unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant.
- Only use tools exclusively for the refrigerant type used in the system, this to ensure pressure resistance and prevent foreign materials from entering into the system.
- Charge the liquid refrigerant as follows:
| If Then | |
| A siphon tube is present (i.e., the cylinder is marked with "Liquid filling siphon attached") | Charge with the cylinder upright. |
| A siphon tube is NOT present Charge with the cylinder upside down. |
- Open refrigerant cylinders slowly.
- Charge the refrigerant in liquid form. Adding it in gas form may prevent normal operation.

CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is not closed immediately, remaining pressure might charge additional refrigerant. Possible consequence: Incorrect refrigerant amount.
1.3.4 Brine
If applicable. See the installation manual or installer reference guide of your application for more information.

WARNING
The selection of the brine MUST be in accordance with the applicable legislation.

WARNING
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area immediately and contact your local dealer.

WARNING
The ambient temperature inside the unit can get much higher than that of the room, e.g. 70°C. In case of a brine leak, hot parts inside the unit can create a hazardous situation.

WARNING
The use and installation of the application MUST comply with the safety and environmental precautions specified in the applicable legislation.
1.3.5 Water
If applicable. See the installation manual or installer reference guide of your application for more information.

NOTICE
Make sure water quality complies with EU directive 98/83 EC.
1.3.6 Electrical

DANGER: RISK OF ELECTROCUTION
- Turn OFF all power supply before removing the switch box cover, connecting electrical wiring or touching electrical parts.
- Disconnect the power supply for more than 1 minute, and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
- Do NOT touch electrical components with wet hands.
- Do NOT leave the unit unattended when the service cover is removed.

WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition. MUST be installed in the fixed wiring.
2 About the documentation

WARNING
- ONLY use copper wires.
- Make sure the field wiring complies with the applicable legislation.
- All field wiring must be performed in accordance with the wiring diagram supplied with the product.
- NEVER squeeze bundled cables and make sure they do not come in contact with the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
- Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
- Make sure to use a dedicated power circuit. NEVER use a power supply shared by another appliance.
- Make sure to install the required fuses or circuit breakers.
- Make sure to install an earth leakage protector. Failure to do so may cause electric shock or fire.
- When installing the earth leakage protector, make sure it is compatible with the inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.

NOTICE
Precautions when laying power wiring:
- Do not connect wiring of different thicknesses to the power terminal block (slack in the power wiring may cause abnormal heat).
- When connecting wiring which is the same thickness, do as shown in the figure below.



- For wiring, use the designated power wire and connect firmly, then secure to prevent outside pressure being exerted on the terminal board.
- Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head will damage the head and make proper tightening impossible.
- Over-tightening the terminal screws may break them.

WARNING
- After finishing the electrical work, confirm that each electrical component and terminal inside the electrical components box is connected securely.
- Make sure all covers are closed before starting up the unit.

NOTICE
Only applicable if the power supply is three-phase, and the compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
2 About the documentation
2.1 About this document
Target audience
Authorised installers + end users

INFORMATION
This appliance is intended to be used by expert or trained users in shops, in light industry, and on farms, or for commercial and household use by lay persons.
Documentation set
This document is part of a documentation set. The complete set consists of:
- General safety precautions:
• Safety instructions that you must read before installing - Format: Paper (in the box of the indoor unit)
- Indoor unit installation and operation manual:
• Installation and operation instructions - Format: Paper (in the box of the indoor unit)
• Installer and user reference guide:
- Preparation of the installation, good practices, reference data,...
• Detailed step-by-step instructions and background information for basic and advanced usage
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/product-information/
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
Technical engineering data
- A subset of the latest technical data is available on the regional Daikin website (publicly accessible).
- The full set of latest technical data is available on the Daikin extranet (authentication required).
For the installer
3 About the box
3.1 Overview: About the box
It contains information about:
- Unpacking and handling the units
- Removing the accessories from the units
Keep the following in mind:
- At delivery, the unit must be checked for damage. Any damage must be reported immediately to the carrier's claims agent.
Installer and user reference guide
DAIKIN
FCAHG71-140GVEB
Split system air conditioners 4P482875-1 - 2017.03
- Bring the packed unit as close as possible to its final installation position to prevent damage during transport.
3.2 Indoor unit
3.2.1 To unpack and handle the unit
Use a sling of soft material or protective plates together with a rope when lifting the unit. This to avoid damage or scratches to the unit.
Lift the unit by holding on to the hanger brackets without exerting any pressure on other parts, especially on refrigerant piping, drain piping and other resin parts.

natural_image
Isometric view of a 3D grid-based structure with four corner blocks and no visible text or symbols
natural_image
Isometric diagram of a mechanical assembly with layered components and directional arrows (no text or symbols)3.2.2 To remove the accessories from the indoor unit

text_image
a efdcb g 8×4×1×1×1×7× h j k 1× 1× 4× 1× i m 1× 1×a Paper pattern for installation (upper part of packing)
b General safety precautions
c Indoor unit installation and operation manual
d Installation guide
e Washers for hanger brackets
1 Screws (to temporarily attach the paper pattern for
installation to the indoor unit
d Cable ties
g Cubic ties
b Metal clamp
1. Insulation piece (drain pipe)
j Insulation piece (drain pipe) Sealing pads: Large (drain pipe), medium 1 (gas pipe).
medium 2 (liquid pipe), small (electrical wiring)
k Drain hose
1. Insulation piece: Small (liquid pipe)
m Insulation piece: Large (gas pipe)
4 About the units and options
4.1 Overview: About the units and options
This chapter contains information about:
- Combining outdoor and indoor units
- Combining the indoor unit with options

NOTICE
Do not wipe the controller operation panel with benzine, thinner, chemical dust cloth, etc. The panel may get discoloured or the coating peeled off. If it is heavily dirty, soak a cloth in water-diluted neutral detergent, squeeze it well and wipe the panel clean. Wipe it with another dry cloth.
4.2 Identification

NOTICE
When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models.
4.2.1 Identification label: Indoor unit
Location

natural_image
Technical line drawing of a mechanical assembly with no visible text or symbols4.3 About the indoor unit
Use the system in the following temperature and humidity ranges for safe and effective operation.
For combination with R410A outdoor unit, refer to the following table:
| Outdoor units | Cooling | Heating | |
| RZQG71-140 | Outdoor temperature | -15~50°C DB | -19~21°C DB -20~15.5°C WB |
| Indoor temperature | 18~37°C DB 12~28°C WB | 10~27°C DB | |
| RZQSG71-140 Outdoor | Outdoor temperature | -15~46°C DB | -14~21°C DB -15~15.5°C WB |
| Indoor temperature | 20~37°C DB 14~28°C WB | 10~27°C DB |
For combination with R32 outdoor unit, refer to the following table:
| Outdoor units | Cooling | Heating | |
| RZASG71-140 | Outdoor temperature | -15~46°C DB | -14~21°C DB -15~15.5°C WB |
| Indoor temperature | 20~37°C DB 14~28°C WB | 10~27°C DB | |
| Indoor humidity | ≤80% (a) | ||
5 Preparation
(a) To avoid condensation and water dripping out of the unit. If the temperature or the humidity is beyond these conditions, safety devices may be put in action and the air conditioner may not operate.
4.4 System layout
NOTICE
Design of the system must not be done at temperatures below -15^ .

text_image
Technical diagram of an appliance system with labeled components and wiring connectionsa Indoor unit
b Outdoor unit
c User interface
d Suction air
e Discharge air
f Refrigerant piping + interconnection cable
g Drain pipe
b Earth wiring
i Suction grille and air filter
4.5 Combining units and options
4.5.1 Possible options for the indoor unit
Make sure you have the following mandatory options:
- User interface: Wired or wireless
- Decoration panel: Standard or self-cleaning
5 Preparation
5.1 Overview: Preparation
This chapter describes what you have to do and know before going on-site.
It contains information about:
- Preparing the installation site
- Preparing the refrigerant piping
■ Preparing the electrical wiring
5.2 Preparing installation site
Do NOT install the unit in places often used as work place. In case of construction works (e.g. grinding works) where a lot of dust is created, the unit must be covered.
Choose the installation location with sufficient place for carrying the unit in and out of the site.
5.2.1 Installation site requirements of the indoor unit
INFORMATION
Also read the following requirements:
- General installation site requirements. See the "General safety precautions" chapter.
- Refrigerant piping requirements (length, height difference). See further in this "Preparation" chapter.
i INFORMATION
The sound pressure level is less than 70 dBA.
CAUTION
Appliance not accessible to the general public, install it in a secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment.
NOTICE
The equipment described in this manual may cause electronic noise generated from radio-frequency energy. The equipment complies to specifications that are designed to provide reasonable protection against such interference. However, there is no guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires keeping proper distances away from stereo equipment, personal computers, etc.

text_image
f e d ±1500 ±1500 ±1500 a b c (mm)a Earth leakage protector
b Fuse
c Outdoor unit
d Indoor unit
e User interface
f Personal computer or radio
In places with weak reception, keep distances of 3 m or more to avoid electromagnetic disturbance of other equipment and use conduit tubes for power and transmission lines.
- Fluorescent lights. When installing a wireless user interface in a room with fluorescent lights, mind the following to avoid interference:
• Install the wireless user interface as close as possible to the indoor unit.
• Install the indoor unit as far as possible from the fluorescent lights.
• Take care that in the event of a water leak, water cannot cause any damage to the installation space and surroundings.
5 Preparation
- Choose a location where the hot/cold air discharged from the unit or the operation noise, will NOT disturb anyone.
• Air flow. Make sure nothing blocks the air flow. - Drainage. Make sure condensation water can be evacuated properly.
- Paper pattern for installation (upper part of packing) (accessory). When selecting the installation location, use the paper pattern. It contains the dimensions of the unit and the required ceiling opening.
- Air flow directions. You can select different air flow directions. Choose the one best suited for the room. Also make sure the "Air flow direction" field setting corresponds with the actual situation (see Field settings).
Example:



a All-round air flow
b 4-way air flow (with closed corners) (optional blocking pad kit required)
c 3-way air flow (optional blocking pad kit required)
- Ceiling insulation. When conditions in the ceiling exceed 30^ and a relative humidity of 80% , or when fresh air is inducted into the ceiling, then additional insulation is required (minimum 10 mm thickness, polyethylene foam).
- Spacing. Mind the following requirements:

text_image
badac O A ≥1500 ≥2000 ≥4000 B (mm)A Minimum distance to the wall (see below)
B Minimum and maximum distance to the floor (see below)
C ≥298 mm: In case of installation with standard decoration
panel
≥348 mm: In case of installation with fresh air intake kit
≥378 mm: In case of installation with self-cleaning
decoration panel
a Indoor unit
b Lighting (the figure shows ceiling-mounted lighting, but
recessed lighting is also allowed)
c Air fan
d Static volume (example: table)
• A: Minimum distance to the wall. Depends on the air flow directions towards the wall.

a Air outlet and corners op
b Air outlet closed, corners open (optional blocking pad kit
required)
c Air outlet and corners closed (optional blocking pad kit
• B: Minimum and maximum distance to the floor:
- Minimum: 2.5 m to avoid accidental touching.
- Maximum: Depends on the air flow directions and the capacity class. Also make sure the "Ceiling height" field setting corresponds with the actual situation. See Field settings.
- Minimum: 2.5 m to avoid accidental touching.
- Maximum: Depends on the air flow directions and the capacity class. Also make sure the "Ceiling height" field setting corresponds with the actual situation. See Field settings.
| If air flow direction... | Then B | |
| FCAHG71 | FCAHG100~140 | |
| All-round | ≤3.5 m | ≤4.2 m |
| 4-way ^a | ≤4.0 m | ≤4.5 m |
| 3-way ^a | ≤3.5 m | ≤4.2 m |
(a) Optional blocking kit required
Do NOT install the unit in the following places:
- In places where a mineral oil mist, spray or vapour may be present in the atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may shorten the life of the unit: - Where the voltage fluctuates a lot
- In vehicles or vessels
- Where acidic or alkaline vapour is present
5.3 Preparing refrigerant piping
5.3.1 Refrigerant piping requirements

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
Refrigerant piping material
- Piping material: Phosphoric acid deoxidised seamless copper.
- Piping temper grade and thickness:
| Outer diameter (∅) | Temper grade | Thickness (t) ^10 | |
| 9.5 mm (3/8") | Annealed (O) | ≥0.8 mm | |
| 15.9 mm (5/8") | Annealed (O) | ≥1.0 mm |
(a) Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.
Refrigerant piping diameter
Use the same diameters as the connections on the outdoor units:
| L1 liquid piping | ∅9.5 mm |
| L1 gas piping | ∅15.9 mm |
Refrigerant piping length and height difference
The piping length and height difference must comply with the following requirements:

| Requirement | RZAG71 | RZAG100~140 |
| Minimum total one-way piping length | 3 m≤L1 | |
| Maximum total one-way piping length | L1≤55 m(75 m) ^a) | L1≤85 m(100 m) ^a) |
| Height difference between the indoor unit and the outdoor unit | H1≤30 m | |
(a) Parenthesised figure represents the equivalent length.
6 Installation
5.3.2 Refrigerant piping insulation
- Use polyethylene foam as insulation material:
• with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and 0.045 kcal/mh°C)
• with a heal resistance of at least 120°C
- Insulation thickness
| Ambient temperature | Humidity Minimum thickness |
| ≤30°C 75% to 80% RH 15 mm | |
| >30°C ≥80% RH 20 mm |
5.4 Preparing electrical wiring
5.4.1 About preparing electrical wiring

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.

WARNING
- If the power supply has a missing or wrong N-phase, equipment might break down.
- Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shock.
- Install the required fuses or circuit breakers.
- Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping, particularly on the high-pressure side.
- Do NOT use taped wires, stranded conductor wires, extension cords, or connections from a star system. They can cause overheating, electrical shock or fire.
- Do NOT install a phase advancing capacitor, because this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.

WARNING
- All wiring must be performed by an authorized electrician and must comply with the applicable legislation.
- Make electrical connections to the fixed wiring.
- All components procured on the site and all electrical construction must comply with the applicable legislation.

WARNING
ALWAYS use multicore cable for power supply cables.
6 Installation
6.1 Overview: Installation
This chapter describes what you have to do and know on-site to install the system.
Typical workflow
Installation typically consists of the following stages:
- Mounting the outdoor unit.
- Mounting the indoor unit (+ decoration panel).
- Mounting the outdoor unit.
Installer and user reference guide
DAIKIN
- Connecting the refrigerant piping.
- Checking the refrigerant piping.
- Charging refrigerant.
- Connecting the electrical wiring.
- Finishing the outdoor installation.
• Finishing the indoor installation.
6.2 Mounting the indoor unit
6.2.1 Precautions when mounting the indoor unit

INFORMATION
Also read the precautions and requirements in the following chapters:
- General safety precautions
- Preparation
6.2.2 Guidelines when installing the indoor unit

INFORMATION
Optional equipment. When installing optional equipment, also read the installation manual of the optional equipment. Depending on the field conditions, it might be easier to install the optional equipment first.
- In case of installation with a fresh air intake kit. Install the fresh air intake kit always before installing the unit.
- Decoration panel. Install the decoration panel always after installing the unit.
- Ceiling strength. Check whether the ceiling is strong enough to support the weight of the unit. If there is a risk, reinforce the ceiling before installing the unit.
- For existing ceilings, use anchors.
- For new ceilings, use sunken inserts, sunken anchors or other field supplied parts.

A 50\~100 mm: In case of installation with standard panel 100\~150 mm: In case of installation with fresh air intake kit 430\~480 mm in case of installation with self cleaning
130\~180 mm, in case of installation with self-clearing decoration panel
a Ceiling slab
b Anchor
c Long nut or turnbuckle
d Suspension bolt
e Suspended ceiling
- Suspension bolts. Use M8\~M10 suspension bolts for installation. Attach the hanger bracket to the suspension bolt. Fix it securely using a nut and washer from the upper and lower sides of the hanger bracket.

text_image
710 (mm) 780 4x a1 b c b a2a1 Nut (field supply)
a2 Double nut (field supply)
FCAHG71\~140GVEB
Split system air conditioners
4P482875-1-2017.03
6 Installation
b Washer (accessories)
c Hanger bracket (attached to the unit)
- Paper pattern for installation (upper part of the packing). Use the paper pattern to determine the correct horizontal positioning. It contains the necessary dimensions and centers. You can attach the paper pattern to the unit.

a Centre of the unit
b Centre of the ceiling opening
c Paper pattern for installation (upper part of the packing)
d Screws (accessories)
• Ceiling opening and unit:
- Make sure the ceiling opening is within the following limits:
Minimum: 860 mm to be able to fit the unit.
Maximum: 910 mm to ensure enough overlap between the decoration panel and the suspended ceiling. If the ceiling opening is larger, add extra ceiling material.
- Make sure the unit and its hanger brackets (suspension) are centered within the ceiling opening.

text_image
a b c 710 d 840 e 860-910 f 960 f 960 (mm)a Drain piping
b Refrigerant piping
c Hanger bracket pitch (suspension)
d Unit
e Ceiling opening
f Decoration panel
| If A Then | ||
| B | C | |
| 860 mm(= min.) | 10 mm 45 mm | |
| 910 mm(= max.) | 35 mm 20 mm | |
A Ceiling opening
B Distance between the unit and the ceiling opening
C Overlap between the decoration panel and the suspended
ceiling
- Installation guide. Use the installation guide to determine the correct vertical position.

flowchart
graph TD
A["Start"] --> B["Step a"]
B --> C["Step b"]
C --> D["Step c"]
D --> E["Step d"]
E --> F["Step e"]
F --> G["End"]
A In case of installation with standard decoration panel
B In case of installation with fresh air intake kit
C In case of installation with self-cleaning decoration panel
a Suspended ceiling
b Installation guide (accessory)
c Unit
- Level. Make sure the unit is level at all 4 corners using a level or a water-filled vinyl tube.

text_image
a bb ca Level
b Vinyl tube
c Water level
NOTICE
Do NOT install the unit tilted. Possible consequence: If the unit is tilted against the direction of the condensate flow (the drain piping side is raised), the float switch might malfunction and cause water to drip.
6.2.3 Guidelines when installing the drain piping
Make sure condensation water can be evacuated properly. This involves:
- General guidelines
- Connecting the drain piping to the indoor unit
- Checking for water leaks
General guidelines
- Pipe length. Keep drain piping as short as possible.
- Pipe size. Keep the pipe size equal to or greater than that of the connecting pipe (vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter).
- Slope. Make sure the drain piping slopes down (at least 1/100) to prevent air from being trapped in the piping. Use hanging bars as shown.

a Hanging bar
O Allowed
X Not allowed

6 Installation
- Rising piping. If necessary to make the slope possible, you can install rising piping.
- Drain hose inclination: 0\~75 mm to avoid stress on the piping and to avoid air bubbles.
- Rising piping: ≤300 mm from the unit, ≤675 mm perpendicular to the unit.

text_image
a b 0-75 ≤300 1000~1500 ≤675 a b c d d (mm)a Metal clamp (accessory)
b Drain hose (accessory)
c Rising drain piping (vinyl pipe of 25 mm nominal diameter
and 32 mm outer diameter) (field supply)
d Hanging bars (field supply)
- Condensation. Take measures against condensation. Insulate the complete drain piping in the building.
- Combining drain pipes. You can combine drain pipes. Make sure to use drain pipes and T-joints with a correct gauge for the operating capacity of the units.

text_image
≥100 a ≤875 a T-joint (mm)To connect the drain piping to the indoor unit

NOTICE
Incorrect connection of the drain hose might cause leaks, and damage the installation space and surroundings.
1 Push the drain hose as far as possible over the drain pipe connection.
2 Tighten the metal clamp until the screw head is less than 4 mm from the metal clamp part.
3 Check for water leaks (see "To check for water leaks" on page 14).
4 Install the insulation piece (drain pipe).
5 Wind the large sealing pad (= insulation) around the metal clamp and drain hose, and fix it with cable ties.
6 Connect the drain piping to the drain hose.

text_image
1 a b 1
text_image
2-6 e 4 c 2 d 5 f 6 A A' ≤4 mm A-A' d b a 3a Drain pipe connection (attached to the unit)
b Drain hose (accessory)
c Metal clamp (accessory)
a Large sealing pad (accessory)
a Insulation piece (drain pins) (accessory)
f. Drain piping (field supply)
To check for water leaks
The procedure differs depending on whether electrical wiring is already finished. When electrical wiring is not finished yet, you need to temporarily connect the user interface and power supply to the unit.
When electrical wiring is not finished yet
1 Temporarily connect electrical wiring.
- Remove the switch box cover (a).
- Connect the user interface (b).
- Connect the power supply (1- 220-240 V 50/60 Hz) and earth (c).
- Reattach the switch box cover (a).

text_image
Technical diagram of a vehicle battery pack with labeled components and wiring connections2 Turn ON the power.
3 Start cooling operation (see "8.4 To perform a test run" on page 20).
4 Gradually pour approximately 1 l of water through the air discharge outlet, and check for leaks.

text_image
a b c d e 5×100 mma Plastic watering can
b Service drain outlet (with rubber plug). Use this outlet to
drain water from the drain pan.
c Drain pump location
d Drain pipe connection
e Drain pipe
5 Turn OFF the power.
6 Disconnect the electrical wiring.
- Remove the switch box cover.
- Disconnect the power supply and earth.
- Disconnect the user interface.
- Reattach the switch box cover.
6.3 Connecting the refrigerant piping
6.3.1 About connecting the refrigerant piping
Before connecting the refrigerant piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
- Connecting the refrigerant piping to the outdoor unit
- Connecting the refrigerant piping to the indoor unit
• Insulating the refrigerant piping -
Keeping in mind the guidelines for:
-
Pipe bending
- Flaring pipe ends
- Brazing
- Using the stop valves
6.3.2 Precautions when connecting the refrigerant piping

INFORMATION
Also read the precautions and requirements in the following chapters:
• General safety precautions
- Preparation

DANGER: RISK OF BURNING

CAUTION
- Do NOT use mineral oil on flared part.
- NEVER install a drier to this unit to guarantee its lifetime. The drying material may dissolve and damage the system.
^(1) Refer to the outdoor unit specifications for the type of refrigerant to be used.

NOTICE
Take the following precautions on refrigerant piping into account:
- Avoid anything but the designated refrigerant to get mixed into the refrigerant cycle (e.g. air).
- Only use R32 or R410A ^1 when adding refrigerant.
- Only use installation tools (e.g. manifold gauge set) that are exclusively used for R32 or R410A ^1 installations to withstand the pressure and to prevent foreign materials (e.g. mineral oils and moisture) from mixing into the system.
- Install the piping so that the flare is NOT subjected to mechanical stress.
- Protect the piping as described in the following table to prevent dirt, liquid or dust from entering the piping.
- Use caution when passing copper tubes through walls (see figure below).

natural_image
Four symbolic diagrams showing mechanical or electrical components with crossed and dashed lines, no text or labels present.| Unit Installation period Protection method | |
| Outdoor unit >1 month | Pinch the pipe |
| <1 month Pinch or tape the pipe | |
| Indoor unit Regardless of the period | |

INFORMATION
Do NOT open the refrigerant stop valve before checking the refrigerant piping. When you need to charge additional refrigerant it is recommended to open the refrigerant stop valve after charging.
6.3.3 Guidelines when connecting the refrigerant piping
Take the following guidelines into account when connecting pipes:
- Coat the flare inner surface with ether oil or ester oil when connecting a flare nut. Tighten 3 or 4 turns by hand, before tightening firmly.

• Always use 2 wrenches together when loosening a flare nut.
- Always use a spanner and torque wrench together to tighten the flare nut when connecting the piping. This to prevent nut cracking and leaks.

a Torque wrench
b Spanner
c Piping union
d Flare nut
6 Installation
| Piping size (mm) | Tightening torque (N·m) | Flare dimensions (A) (mm) | Flare shape (mm) |
| ∅9.5 33~39 | 12.8~13.2 | ![]() | |
| ∅15.9 63~75 | 19.3~19.7 |
6.3.4 Pipe bending guidelines
Use a pipe bender for bending. All pipe bends should be as gentle as possible (bending radius should be 30\~40 mm or larger).
6.3.5 To flare the pipe end

CAUTION
- Incomplete flaring may cause refrigerant gas leakage.
- Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.
- Use flare nuts that are included with the unit. Using different flare nuts may cause refrigerant gas leakage.
1 Cut the pipe end with a pipe cutter.
2 Remove burrs with the cut surface facing down so that the chips do not enter the pipe.

a Cut exactly at right angles. b Remove burrs.
3 Remove the flare nut from the stop valve and put the flare nut on the pipe.
4 Flare the pipe. Set exactly at the position as shown in the following illustration.

| Flare tool for R410A or R32 (clutch type) | Conventional flare tool | ||
| Clutch type (Ridgid-type) | Wing nut type (Imperial-type) | ||
| A 0~0 | 5 mm 1.0~1.5 mm 1 | 5~2.0 mm | |
5 Check that the flaring is properly made.

a Flare's inner surface must be flawless.
b The pipe end must be evenly flared in a perfect circle.
c Make sure the flare nut is fitted.
6.3.6 To braze the pipe end
The indoor unit and outdoor unit have flare connections. Connect both ends without brazing. If brazing should be needed, take the following into account:
- When brazing, blow through with nitrogen to prevent creation of large quantities of oxidised film on the inside of the piping. This film adversely affects valves and compressors in the refrigerating system and prevents proper operation.
- Set the nitrogen pressure to 20 kPa (0.2 bar) (just enough so it can be felt on the skin) with a pressure-reducing valve.
(2) Refer to the outdoor unit specifications for the type of refrigerant to be used.
Installer and user reference guide
DAIKIN

a Refrigerant piping
b Part to be brazed
c Taping
d Manual valve
e Pressure-reducing valve
f Nitrogen
- Do NOT use anti-oxidants when brazing pipe joints. Residue can clog pipes and break equipment.
- Do NOT use flux when brazing copper-to-copper refrigerant piping. Use phosphor copper brazing filler alloy (BCuP), which does not require flux. Flux has an extremely harmful influence on refrigerant piping systems. For instance, if chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will deteriorate the refrigerant oil.
6.3.7 To connect the refrigerant piping to the indoor unit

WARNING: FLAMMABLE MATERIAL
The R32 refrigerant (if applicable) in this unit is mildly flammable. ^2
- Pipe length. Keep refrigerant piping as short as possible.
- Flare connections. Connect refrigerant piping to the unit using flare connections.
• Insulation. Insulate the refrigerant piping on the indoor unit as follows:

text_image
A B a b c d b e f 1 3 2 g 4 1 3 2 g 4A Gas piping B Liquid piping
a Insulation material (field supply)
b Cable tie (accessory)
c Insulation pieces: Large (gas pipe), small (liquid pipe) (accessories)
d Flare nut (attached to the unit)
e Refrigerant pipe connection (attached to the unit)
f Unit
g Sealing pads: Medium 1 (gas pipe), medium 2 (liquid pipe) (accessories)
1 Turn up the seams of the insulation pieces.
2 Attach to the base of the unit.
3 Tighten the cable ties on the insulation pieces.
4 Wrap the sealing pad from the base of the unit to the top of the flare nut.

NOTICE
Make sure to insulate all refrigerant piping. Any exposed piping might cause condensation.
FCAHG71-140GVEB
Split system air conditioners 4P482875-1 - 2017.03
6.4 Connecting the electrical wiring
6.4.1 About connecting the electrical wiring
Typical workflow
Connecting the electrical wiring typically consists of the following stages:
1 Making sure the power supply system complies with the electrical specifications of the units.
2 Connecting the electrical wiring to the outdoor unit.
3 Connecting the electrical wiring to the indoor unit.
4 Connecting the main power supply.
6.4.2 Precautions when connecting the electrical wiring

INFORMATION
Also read the precautions and requirements in the following chapters:
• General safety precautions
- Preparation

DANGER: RISK OF ELECTROCUTION

WARNING
ALWAYS use multicore cable for power supply cables.

WARNING
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
6.4.3 Guidelines when connecting the electrical wiring
Keep the following in mind:
- If stranded conductor wires are being used, install a round crimp-style terminal on the tip. Place the round crimp-style terminal on the wire up to the covered part and fasten the terminal with the appropriate tool.

a Stranded conductor wire
b Round crimp-style terminal
- Use the following methods for installing wires:

text_image
Wire type Installation method Single core wire a Curled single core wire b Screw c Flat washer
text_image
Wire type Installation method Stranded conductor wire with round crimp-style terminal a Terminal b Screw c Flat washerTightening torques
| Wiring | Screw size | Tightening torque (N·m) |
| Interconnection cable (indoor+→outdoor) | M4 | 1.18~1.44 |
| User interface cable | M3.5 | 0.79~0.97 |
6.4.4 Specifications of standard wiring components
| Component | Specification |
| Interconnection cable (indoor, -outdoor) | Minimum cable section of 2.5 mm ^2 and applicable for 230 V |
| User interface cable | Vinyl cords with 0.75 to 1.25 mm ^2 sheath or cables (2-core wires)Maximum 500 m |
6.4.5 To connect the electrical wiring on the indoor unit

NOTICE
- Follow the wiring diagram (delivered with the unit, located at the inside of the service cover).
- For instructions on how to connect the decoration panel and the sensor kit, see the installation manual delivered with the panel or the kit.
- Make sure the electrical wiring does NOT obstruct proper reattachment of the service cover.
It is important to keep the power supply and the transmission wiring separated from each other. In order to avoid any electrical interference the distance between both wiring should always be at least 50 mm.

NOTICE
Be sure to keep the power line and transmission line apart from each other. Transmission wiring and power supply wiring may cross, but may not run parallel.
1 Remove the service cover.
2 User Interface cable: Route the cable through the frame, connect the cable to the terminal block, and fix the cable with a cable tie.
3 Interconnection cable (indoor→outdoor): Route the cable through the frame, connect the cable to the terminal block (make sure the numbers match with the numbers on the outdoor unit, and connect the earth wire), and fix the cable with a cable tie.
4 Divide the small sealing (accessory) and wrap it around the cables to prevent water from entering the unit. Seal all gaps to prevent small animals from entering the system.
7 Configuration

WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
5 Reattach the service cover.
- Pair type or multi-system. 1 user interface controls 1 indoor unit.

text_image
1~50 Hz 220-240 V c d b a P1 P2 1 2 3 e1- Simultaneous operation system. 1 user interface controls 2 indoor units (indoor units operate simultaneously)

text_image
1~50 Hz 220-240 V L N ⊕ c d b 1 2 3 L N ⊕ a P1 P2 ⊕ 1 2 3 1 2 3 P1 P2 e1- Group control. 1 user interface controls up to 16 indoor units (all indoor units operate according to the user interface).

text_image
变压器 c L N d b 1 2 3 L N L N 变压器 c L N d b 1 2 3 L N L N 变压器 c L N d b 1 2 3 L N L N 变压器 a P1 P2 1 2 3 e1 a P1 P2 1 2 3 a P1 P2 1 2 3 a P1 P2 1 2 3- 2 user interface control. (2 remote controllers control 1 indoor unit)

text_image
1-50 Hz 220-240 V L N c d b 1 2 3 L N a P1 P2 1 2 3 e2 e1a Interconnection cable
b Power supply cable
c Earth leakage circuit breaker
d Fuse
e1 Main user interface
e2 Optional user interface

text_image
c b 70-90 10-15 d e b a c 10-15 10-20 [mm]a Service cover (with wiring diagram on the back)
b Opening for cables
c Connection of interconnection cable (including earth)
d Cable tie
e Connection of user interface cable
7 Configuration
7.1 Field settings
Make the following field settings so that they correspond with the actual installation setup and with the needs of the user:
- Ceiling height
- Air flow direction
• Air volume when thermostat control is OFF
• Time to clean air filter
Setting: Ceiling height
This setting must correspond with the actual distance to the floor, capacity class and air flow directions.
- For 3-way and 4-way air flows (which require an optional blocking pad kit), see the installation manual of the optional blocking pad kit.
- For all-round air flow, use the table below.
7 Configuration
| If the distance to the floor is (m) Then | 4 | ||
| FCAHG71 FCAHG100~140 M C1 C2 | |||
| ≤2.7 ≤3.2 13 (23) 0 01 | |||
| 2.73.6 02 | |||
| 3.04.2 03.64.2 03.64.2 03.64.2 03.64.2 03.64.2 03.64.2 03.64.2 03.64.2 03.64.2 03.64.2 03.64.2 03.64.2 03.64.2 | |||
Setting: Air flow direction
This setting must correspond with the actual used air flow directions. See the installation manual of the optional blocking pad kit and the manual of the user interface.
Default: 01 (= all-round air flow)
Example:



a All-round air flow
b 4-way air flow (all air outlets open, 2 corners closed)
(optional blocking pad kit required)
c 3-way air flow (1 air outlet closed, all corners open)
(optional blocking pad kit required)
Setting: Air volume when thermostat control is OFF
This setting must correspond with the needs of the user. It determines the fan speed of the indoor unit during thermostat OFF condition.
1 If you have set the fan to operate, set the air volume speed:
| If you want | Then^a | ||||
| Outdoor unit | M | C1 | C2 | ||
| General | 3MX/4MX/5MX | ||||
| During cooling operation | LL^b | 12(22) | 6 | 01 | |
| Setup volume^b | 02 | ||||
| During heating operation | LL^s | Monitoring 1^s | 12(22) | 3 | 01 |
| Setup volume^s | Monitoring 2^s | 02 | |||
Setting: Time to clean air filter
This setting must correspond with the air contamination in the room. It determines the interval at which the TIME TO CLEAN AIR FILTER notification is displayed on the user interface. When using a wireless user interface, you must also set the address (see the installation manual of the user interface).
| If you want an interval of...(air contamination) | Then^4 | ||
| M C1 | C2 | ||
| ±2500 h (light) | 10 (20) | 0 01 | |
| ±1250 h (heavy) | 02 | ||
| No notification | 3 02 | ||
Individual setting in a simultaneous operation system
We recommend using the optional user interface to set the slave unit.
Perform the following steps:
2 Change the second code number to 02 to perform individual setting on the slave unit.
| If you want to set the slave unit as... | Then^4 | ||
| M C1 | C2 | ||
| Unified setting | 21(11) | 01 01 | |
| Individual setting | 02 | ||
3 Perform field setting for the master unit.
4 Turn off the main power supply switch.
5 Disconnect the remote controller from the master unit and connect it to the slave unit.
6 Change to individual setting.
7 Perform field setting for the slave unit.
8 Turn off the main power supply or, in case of more slave units, repeat the previous steps for all slave units.
9 Disconnect the user interface from the slave unit and reconnect it to the master unit.
It is not necessary to rewire the remote controller from the master unit if the optional user interface is used. (However, remove the wires attached to the user interface terminal board of the master unit)

text_image
1-50 Hz 220-240 V L N c d b 1 2 3 L N
A Master unit
B Slave unit
a Interconnection cable
b Power supply cable
c Earth leakage circuit breaker
d Fuse
e1 Main user interface
e2 Optional user interface
(4) Field settings are defined as follows:
- M: Mode number – First number: for group of units – Number between brackets: for individual unit
• C1: First code number
C2: Second code number - Default
(5) Fan speed:
- LL: Low fan speed
- Setup volume: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user interface.
- Monitoring 1, 2: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by Low fan speed (1) or by Setup volume (2).
FCAHG71\~140GVEB
Split system air conditioners
4P4B2875-1-2017.03
DAIKIN
Installer and user reference guide
8 Commissioning
8 Commissioning
8.1 Overview: Commissioning
This chapter describes what you have to do and know to commission the system after it is installed.
Typical workflow
Commissioning typically consists of the following stages: 1 Checking the "Checklist before commissioning". 2 Performing a test run for the system.
8.2 Precautions when commissioning

INFORMATION
During the first running period of the unit, the required power may be higher than stated on the nameplate of the unit. This phenomenon is caused by the compressor, that needs a continuous run time of 50 hours before reaching smooth operation and stable power consumption.

NOTICE
Before starting up the system, the unit MUST be energised for at least 6 hours to avoid compressor breakdown during startup.

NOTICE
NEVER operate the unit without thermistors and/or pressure sensors/switches. Burning of the compressor might result.

NOTICE
Do NOT operate the unit until the refrigerant piping is complete (when operated this way, the compressor will break).

NOTICE
Cooling operation mode. Perform the test run in cooling operation mode so that stop valves failing to open can be detected. Even if the user interface was set to heating operation mode, the unit will run in cooling operation mode during 2-3 minutes (although the user interface will display the heating icon), and then automatically switch to heating operation mode.

NOTICE
If you cannot operate the unit in test run, see "8.5 Error codes when performing a test run" on page 21.

WARNING
If the panels on the Indoor units are not installed yet, make sure to power OFF the system after finishing the test run. To do so, turn OFF operation via the user interface. Do NOT stop operation by turning OFF the circuit breakers.
8.3 Checklist before commissioning
Do NOT operate the system before the following checks are OK:
| You read the complete installation instructions, as described in the installer reference guide. | |
| The indoor units are properly mounted. | |
| In case a wireless user interface is used: The indoor unit decoration panel with infrared receiver is installed. | |
| The outdoor unit is properly mounted. |
| There are NO missing phases or reversed phases. | |
| The system is properly earthed and the earth terminals are tightened. | |
| The fuses or locally installed protection devices are installed according to this document, and have not been bypassed. | |
| The power supply voltage matches the voltage on the identification label of the unit. | |
| There are NO loose connections or damaged electrical components in the switch box. | |
| The insulation resistance of the compressor is OK. | |
| There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units. | |
| There are NO refrigerant leaks. | |
| The correct pipe size is installed and the pipes are properly insulated. | |
| The stop valves (gas and liquid) on the outdoor unit are fully open. |
8.4 To perform a test run
This task is only applicable when using the BRC1E52 or BRC1E53 user interface. When using any other user interface, see the installation manual or service manual of the user interface.

NOTICE
Do not interrupt the test run.

INFORMATION
Backlight. To perform an ON/OFF action on the user interface, the backlight does not need to be lit. For any other action, it needs to be lit first. The backlight is lit for ±30 seconds when you press a button.
1 Perform introductory steps.
| # | Action |
| 1 | Open the liquid stop valve (A) and gas stop valve (B) by removing the stem cap and turning counterclockwise with a hex wrench until it stops. |
| 2 | Close the service cover to prevent electric shocks. |
| 3 | Turn ON power for at least 6 hours before starting operation to protect the compressor. |
| 4 | On the user interface, set the unit to cooling operation mode. |
| # | Action | Result |
| 1 | Go to the home menu. |
2 Start the test run
Installer and user reference guide
DAIKIN
FCAHG71-140GVEB
Split system air conditioners 4P482875-1 - 2017.03
| # Action Result | |
2 Press at least 4 seconds. The Service Settings menu is displayed.![]() | |
3 Select Test Operation.![]() | |
4 Press. Test Operation is![]() | |
5 Press within 10 seconds. Test run starts.![]() |
3 Check operation for 3 minutes.
4 Check operation of the airflow direction.
| # Action Result | |
| 1 Press. | Air Volume DirectionAir Volume DirectionPosition D |
![]() | |
| 2 Select Position 0. | Air Volume DirectionAir Volume DirectionLow |
![]() | |
| 3 Change the position. If the airflow flap of the indoor unit moves, operation is OK. | |
![]() | If not, operation is not OK. |
| 4 Press. The home menu is | displayed. |
![]() | |
5 Stop the test run.
| # Action Result | |
1 Press at least 4 seconds. The Service Settings menu is displayed.![]() | |
2 Select Test Operation.![]() | Service Settings L2Offs ProductionInference ControlRide SidingS DemandWin Solutions DifferentialGroup AddressProduct Siding |
3 Press. The unit returns to normal![]() | operation, and the home menu is displayed. |
8.5 Error codes when performing a test run
If the installation of the outdoor unit has NOT been done correctly, the following error codes may be displayed on the user interface:
| Error code Possible cause | |
| Nothing displayed(the currently set temperature is not displayed) | The wiring is disconnected or there is a wiring error (between power supply and outdoor unit, between outdoor unit and indoor units, between indoor unit and user interface).The fuse on the outdoor or indoor unit PCB has blown. |
| E3, E4 or L8 | The stop valves are closed.The air inlet or air outlet is blocked. |
| E7 | There is a missing phase in case of three-phase power supply units.Note: Operation will be impossible. Turn OFF the power, recheck the wiring, and switch two of the three electrical wires. |
| L4 The air inlet or air outlet is blocked. | |
| U0 | The stop valves are closed. |
| U2 | There is a voltage imbalance.There is a missing phase in case of three-phase power supply units. Note:Operation will be impossible. Turn OFF the power, recheck the wiring, and switch two of the three electrical wires. |
| U4 or UF | The inter-unit branch wiring is not correct. |
| UA The outdoor and indoor unit are incompatible. | |
9 Hand-over to the user
Once the test run is finished and the unit operates properly, please make sure the following is clear for the user:
- Make sure that the user has the printed documentation and ask him/her to keep it for future reference. Inform the user that he can find the complete documentation on the url as earlier described in this manual.
- Explain the user how to properly operate the system and what to do in case of problems.
- Show the user what to do in relation to maintaining the unit.
10 Disposal

NOTICE
Do not try to dismantle the system yourself: the dismantling of the system, treatment of the refrigerant, oil and other parts must comply with applicable legislation. Units must be treated at a specialised treatment facility for reuse, recycling and recovery.
11 Technical data
- A subset of the latest technical data is available on the regional Daikin website (publicly accessible).
- The full set of latest technical data is available on the Daikin extranet (authentication required).
IN Installer and user reference guide
11 Technical data
11.1 Piping diagram: Indoor unit

text_image
c a ba Liquid pipe connection
b Gas pipe connection
c Heat exchanger
11.2 Wiring diagram
| Unified Wiring Diagram Legend | |||||
| For applied parts and numbering refer to the wiring diagram stover supplied on the unit. Part numbering is realized by Arabic numbers in ascending order for each part and is represented in the overview below by symbol ** in the part code. | |||||
| CIRCUIT BREAKER | ∅ | PROTECTIVE EARTH | |||
| CONNECTION | ∅ | PROTECTIVE EARTH (SCREW) | |||
| CONNECTOR | A | RECTIFIER | |||
| EARTH : RELAY CONNECTOR | |||||
| FIELD WIRING | SHORT CIRCUIT CONNECTOR | ||||
| FUSE : TERMINAL | |||||
| INDOOR UNIT : TERMINAL STRIP | |||||
| OUTDOOR UNIT : WIRE CLAMP | ○ ● | ||||
| BLK : BLACK | GRN : GREEN | PNK : PINK | WHF : WHITE | ||
| BLU : BLUE | CRY : GREY | PRP, PPL : PURPLE | YUV : YELLOW | ||
| BRN : BROWN | ORG : ORANGE | RED : RED | |||
| A/P | PRINTED CIRCUITBOARD | PS | SWITCHING POWER SUPPLY | ||
| BS* | PUSH BUTTON ON/OFF, OPERATION SWITCH | PTC* | THERMISTOR PTC | ||
| BZ, F'O | BUZZER | Q' | INSULATED GATE BIPOLAR TRANSISTOR (IGBT) | ||
| C* | CAPACITOR | QOI | EARTH LEAK CIRCUIT BREAKER | ||
| AC, ON', F', HV, HE, HL, IN', HR', MR', A, MR', B, S', U, V, W, X'A | CONNECTION CONNECTOR | QL | OVERLOAD PROTECTOR | ||
| D', V'O | DIODE | CM | THERMID SWITCH | ||
| DS* | DIODE BRIDGE | R* | RESISTOR | ||
| DS* | DIP SWITCH | RT | THERMISTOR | ||
| EH | HDATER | RC | RECEIVER | ||
| F'U, FU FOR CHARACTERISTICSREFER TO OR INSIDE YOUR UNIT: | FUSE | 5°C | LIMIT SWITCH | ||
| FG* | CONNECTOR (FRAME GROUND) | SL | FLOAT SWITCH | ||
| HT* | HARNESS | SNPH | PRESSURE SENSOR (HIGH) | ||
| HT', LED*, VL | PLOT LAMP, LIGHT EMITTING DIODE | SNPL | PRESSURE SENSOR (LOW) | ||
| HAP | LIGHT EMITTING DIODE (SERVICE MONITOR GREEN) | SPH, HPS* | PRESSURE SWITCH (HIGH) | ||
| HIGH VOLTAGE | HIGH VOLTAGE | SPL | PRESSURE SWITCH (LOW) | ||
| IES | INTELLIGENTE YE SENSOR | ST | THERMOSTAT | ||
| IRM* | INTELLIGENT POWER MODULE | SW, SW* | OPERATION SWITCH | ||
| KR, KCR, KFR, KHUR | MAGNETIC RELAY | SA* | SURGEARRESTOR | ||
| L | LME | SR*, WLU | SIGNAL RECOVER | ||
| L' | COL | SS* | SELECTORSWITCH | ||
| LR | REACTOR | SHEET METAL | TERMINAL STRIP FIXED PLATE | ||
| M* | STEPPER MOTOR | TR | TRANSFORMER | ||
| MC | COMPRESSOR MOTOR | TC, TRC | TRANSMITTER | ||
| MF | FAN MOTOR | V*, RV* | VARISTOR | ||
| MP | DRAIN PUMP MOTOR | WR | DIODEBRIDGE | ||
| MS | SWING MOTOR | WRC | WIRELESS REMOTE CONTROLLER | ||
| MR', MRCW', MRW', MRN* | MAGNETIC RELAY | X* | TERMINAL | ||
| N | NEUTRAL | XM | TERMINAL STRIP (BLOCK) | ||
| n=* | NUMBER OF PASSES THROUGH FERRITE CORE | YE | ELECTRONIC EXPANSION VALVE COIL | ||
| RAM | PULSE AMPLITUDE MODULATION | YR, Y/S | REVERSING SOLENOID VALVE COIL | ||
| PCB* | PRINTED CIRCUITBOARD | ZC | FERRITE CORE | ||
| PM* | POWER MODULE | ZF, ZF | NOISE FILTER | ||
12 About the system
For the user
12 About the system
The indoor unit of this split system air conditioner can be used for heating/cooling applications.

NOTICE
Do not use the system for other purposes. In order to avoid any quality deterioration, do not use the unit for cooling precision instruments, food, plants, animals or works of art.

NOTICE
For future modifications or expansions of your system:
A full overview of allowable combinations (for future system extensions) is available in technical engineering data and should be consulted. Contact your installer to receive more information and professional advice.
12.1 System layout

text_image
Technical diagram of a solar panel installation with labeled components and wiring connectionsa Indoor unit
b Outdoor unit
e User interface
d Suetion air
a Suction all
e Discharge an
4 Refrigerating + interconnection cable
† Refrigerant piping + interconnection cable
g Drain pipe
h Earth wiring
I Suction grille and air filter
12.2 Information requirements for fan coil units
| Item Symbol Value Unit | |||
| Cooling capacity (sensible) P | p_elec | A | kW |
| Cooling capacity (latent) P | p_elec | B | kW |
| Heating capacity P | p_elec,h | C | kW |
| Total electric power input | P_elec | D | kW |
| Item Symbol Value Unit | |||
| Sound power level (per speed setting, if applicable) | Lm/s | E | dB |
| Contact details:DAIKIN INDUSTRIES CZECH REPUBLIC s.r.o. U Nové Hospody 1/1155, 301 00 Plzeň Skvrňany, Czech Republic | |||
| A | B | C | D | E | |
| FCAHG125 | 7.83 | 4.27 | 13.50 | 0.25 | 61 |
| FCAHG140 | 8.68 | 4.72 | 15.50 | 0.25 | 61 |
13 User interface

CAUTION
Never touch the internal parts of the controller.
Do not remove the front panel. Some parts inside are dangerous to touch and appliance problems may happen. For checking and adjusting the internal parts, contact your dealer.
This operation manual will give a non-exhaustive overview of the main functions of the system.
For more information about the user interface, see the operation manual of the installed user interface.
14 Before operation

WARNING
This unit contains electrical and hot parts.

WARNING
Before operating the unit, be sure the installation has been carried out correctly by an installer.

CAUTION
It is not good for your health to expose your body to the air flow for a long time.

CAUTION
To avoid oxygen deficiency, ventilate the room sufficiently if equipment with burner is used together with the system.

CAUTION
Do not operate the system when using a room fumigation-type insecticide. This could cause the chemicals to become deposited in the unit, which could endanger the health of those who are hypersensitive to chemicals.
This operation manual is for the following systems with standard control. Before initiating operation, contact your dealer for the operation that corresponds to your system type and mark. If your installation has a customised control system, ask your dealer for the operation that corresponds to your system.
Operation modes:
• Heating and cooling (air to air).
• Fan only operation (air to air).
15 Operation
15.1 Operation range
Use the system in the following temperature and humidity ranges for safe and effective operation.
For combination with R410A outdoor unit, refer to the following table:
| Outdoor units Cooling Heating | |||
| RZQG71-140 Outdoor temperature | -15~50°C DB | -19~21°C DB-20~15.5°C WB | |
| Indoor temperature | 18~37°C DB12~28°C WB | ||
| RZQSG71-140 Outdoor temperature | -15~46°C DB | -14~21°C DB-15~15.5°C WB | |
| Indoor temperature | 20~37°C DB14~28°C WB | ||
For combination with R32 outdoor unit, refer to the following table:
| Outdoor units | Cooling Heating | ||
| RZASG71~140 | Outdoor temperature | -15~46°C DB | 14~21°C DB -15~15.5°C WB |
| Indoor temperature | 20~37°C DB 14~28°C WB | 10~27°C DB | |
| Indoor humidity ≤80% | (a) | ||
(a) To avoid condensation and water dripping out of the unit. If the temperature or the humidity is beyond these conditions, safety devices may be put in action and the air conditioner may not operate.
15.2 Operating the system
15.2.1 About operating the system
- To protect the unit, turn on the main power switch 6 hours before operation.
- If the main power supply is turned off during operation, operation will restart automatically after the power turns back on again.
15.2.2 About cooling, heating, fan only, and automatic operation
- The air flow rate may adjust itself depending on the room temperature or the fan may stop immediately. This is not a malfunction.
15.2.3 About the heating operation
It may take longer to reach the set temperature for general heating operation than for cooling operation.
The following operation is performed in order to prevent the heating capacity from dropping or cold air from blowing.
Defrost operation
In heating operation, freezing of the outdoor unit's air cooled coil increases over time, restricting the energy transfer to the outdoor unit's coil. Heating capability decreases and the system needs to go into defrost operation to be able to deliver enough heat to the indoor units.
The indoor unit will stop fan operation, the refrigerant cycle will reverse and energy from inside the building will be used to defrost the outdoor unit coil.
The indoor unit will indicate defrost operation on the display
Hot start
In order to prevent cold air from blowing out of an indoor unit at the start of heating operation, the indoor fan is automatically stopped. The display of the user interface shows 🐃/➀ It may take some time before the fan starts. This is not a malfunction.

INFORMATION
- The heating capacity drops when the outside temperature falls. If this happens, use another heating device together with the unit. (When using together with appliances that produce open fire, ventilate the room constantly). Do not place appliances that produce open fire in places exposed to the air flow from the unit or under the unit.
- It takes some time to heat up the room from the time the unit is started since the unit uses a hot-air circulating system to heat the entire room.
- If the hot air rises to the ceiling, leaving the area above the floor cold, we recommend that you use the circulator (the indoor fan for circulating air). Contact your dealer for details.
15.2.4 To operate the system
1 Press the operation mode selector button on the user interface several times and select the operation mode of your choice.
* Cooling operation
Heating operation
Fan only operation
2 Press the ON/OFF button on the user interface.
Result: The operation lamp lights up and the system starts operating.
15.3 Using the dry program
15.3.1 About the dry program
- The function of this program is to decrease the humidity in your room with minimal temperature decrease (minimal room cooling).
- The micro computer automatically determines temperature and fan speed (cannot be set by the user interface).
- The system does not go into operation if the room temperature is low (<20°C).
15.3.2 To use the dry program
To start
1 Press the operation mode selector button on the user interface several times and select (program dry operation).
2 Press the ON/OFF button of the user interface.
Result: The operation lamp lights up and the system starts operating.
To stop
3 Press the ON/OFF button on the user interface once again.
Result: The operation lamp goes out and the system stops operating.

NOTICE
Do not turn off power immediately after the unit stops, but wait for at least 5 minutes.

16 Energy saving and optimum operation
15.4 Adjusting the air flow direction
Refer to the operation manual of the user interface.
15.4.1 About the air flow flap

Double flow+multi-flow units
For the following conditions, a micro computer controls the air flow direction which may be different from the display.
| Cooling Heating | |
| When the room temperature is lower than the set temperature. | When starting operation.When the room temperature is higher than the set temperature.At defrost operation. |
| When operating continuously at horizontal air flow direction.When continuous operation with downward air flow is performed at the time of cooling with a ceiling-suspended or a wall-mounted unit, the micro computer may control the flow direction, and then the user interface indication will also change. | |
The air flow direction can be adjusted in one of the following ways:
- The air flow flap itself adjusts its position.
- The air flow direction can be fixed by the user.
• Automatic and desired position

WARNING
Never touch the air outlet or the horizontal blades while the swing flap is in operation. Fingers may become caught or the unit may break down.

NOTICE
- The movable limit of the flap is changeable. Contact your dealer for details. (only for double-flow, multi-flow, corner, ceiling-suspended and wall-mounted).
- Avoid operating in the horizontal direction . . . may cause dew or dust to settle on the ceiling or flap.
16 Energy saving and optimum operation
Observe the following precautions to ensure the system operates properly.
- Adjust the air outlet properly and avoid direct air flow to room inhabitants.
- Adjust the room temperature properly for a comfortable environment. Avoid excessive heating or cooling.
- Prevent direct sunlight from entering a room during cooling operation by using curtains or blinds.
- Ventilate often. Extended use requires special attention to ventilation.
- Keep doors and windows closed. If the doors and windows remain open, air will flow out of your room causing a decrease in the cooling or heating effect.
- Be careful not to cool or heat too much. To save energy, keep the temperature setting at a moderate level.
- Never place objects near the air inlet or the air outlet of the unit. It may cause deterioration in the effect or stop the operation.
- Turn off the main power supply switch to the unit when the unit is not used for longer periods of time. If the switch is on, it consumes electricity. Before restarting the unit, turn on the main power supply switch 6 hours before operation to ensure smooth running.
- When the display shows (time to clean the air filter), clean the filters (see "17.1.1 To clean the air filter" on page 27).
- Keep the indoor unit and user interface at least 1 m away from televisions, radios, stereos, and other similar equipment. Failing to do so may cause static or distorted pictures.
- Do not place items under the indoor unit, they may be damaged by water.
- Condensation may form if the humidity is above 80% or if the drain outlet gets blocked.
17 Maintenance and service

NOTICE
Never inspect or service the unit by yourself. Ask a qualified service person to perform this work. However, as end user, you may clean the air filter, suction grille, air outlet and outside panels.

WARNING
Never replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out. Use of wire or copper wire may cause the unit to break down or cause a fire.

CAUTION
Do not insert fingers, rods or other objects into the air inlet or outlet. Do not remove the fan guard. When the fan is rotating at high speed, it will cause injury.

CAUTION
Pay attention to the fan.
It is dangerous to inspect the unit while the fan is running.
Be sure to turn off the main switch before executing any maintenance task.

CAUTION
After a long use, check the unit stand and fitting for damage. If damaged, the unit may fall and result in injury.

NOTICE
Do not wipe the controller operation panel with benzine, thinner, chemical dust cloth, etc. The panel may get discoloured or the coating peeled off. If it is heavily dirty, soak a cloth in water-diluted neutral detergent, squeeze it well and wipe the panel clean. Wipe it with another dry cloth.

CAUTION
Before accessing terminal devices, make sure to interrupt all power supply.

NOTICE
When cleaning the heat exchanger, make sure to remove the switch box, fan motor, drain pump and float switch. Water or detergent might deteriorate the insulation of electronic components and result in burnout of these components.
17.1 Cleaning the air filter, suction grille, air outlet and outside panels
17.1.1 To clean the air filter
When to clean the air filter:
- Rule of thumb: Clean every 6 months. If the air in the room is extremely contaminated, increase the cleaning frequency.
- Depending on the settings, the user interface can display the TIME TO CLEAN AIR FILTER notification. Clean the air filter when the notification is displayed.
- If the dirt becomes impossible to clean, change the air filter (= optional equipment).
How to clean the air filter:

NOTICE
Do NOT use water of 50°C or higher. Possible consequence: Discoloration and deformation.
1 Open the suction grille.

natural_image
Technical line drawing of a mechanical component with no visible text or symbols2 Remove the air filter.

natural_image
Three-step diagram showing a door handle, lock mechanism, and cleaning steps (no text or symbols)3 Clean the air filter. Use a vacuum cleaner or wash with water. If the air filter is very dirty, use a soft brush and neutral detergent.

natural_image
Two technical illustrations of a vacuum cleaner connected to a solar panel, with no visible text or symbols.4 Dry the air filter in the shadow.
5 Reattach the air filter and close the suction grille.
6 Turn ON the power.
7 Press the FILTER SIGN RESET button.
Result: The TIME TO CLEAN AIR FILTER notification disappears from the user interface.
17.1.2 To clean the suction grille

NOTICE
Do NOT use water of 50°C or higher. Possible consequence: Discoloration and deformation.
1 Open the suction grille.

natural_image
Technical line drawing of a mechanical component with a highlighted section and directional arrow (no text or symbols)2 Remove the suction grille.

natural_image
Three technical diagrams showing mechanical assembly and component alignment (no text or symbols)3 Remove the air filter.

natural_image
Three-step diagram showing hand positioning, folding a panel, and projecting an arrow (no text or symbols)4 Clean the suction grille. Wash with a soft bristle brush, and water or neutral detergent. If the suction grille is very dirty, use a typical kitchen cleaner, leave it on for 10 min, then wash it with water.
5 Reattach the air filter and suction grille, and close the suction grille.
17.1.3 To clean the air outlet and outside panels

WARNING
Do NOT let the indoor unit get wet. Possible consequence: Electric shock or fire.

NOTICE
- Do NOT use gasoline, benzene, thinner polishing powder or liquid insecticide. Possible consequence: Discoloration and deformation.
- Do NOT use water or air of 50°C or higher. Possible consequence: Discoloration and deformation.
- Do NOT scrub firmly when washing the blade with water. Possible consequence: The surface sealing peels off.
Clean with a soft cloth. If it is difficult to remove stains, use water or neutral detergent.
17.2 Maintenance after a long stop period
E.g., at the beginning of the season.
- Check and remove everything that might be blocking inlet and outlet vents of indoor units and outdoor units.
- Clean air filters and casings of indoor units (see "17.1.1 To clean the air filter" on page 27 and "17.1.3 To clean the air outlet and outside panels" on page 27).
- Turn on the power at least 6 hours before operating the unit in order to ensure smoother operation. As soon as the power is turned on, the user interface display appears.
17 Maintenance and service
17.3 Maintenance before a long stop period
E.g., at the end of the season.
- Let the indoor units run in fan only operation for about half a day in order to dry the interior of the units. Refer to "15.2.2 About cooling, heating, fan only, and automatic operation" on page 25 for details on fan only operation.
- Turn off the power. The user interface display disappears.
- Clean air filters and casings of indoor units (see "17.1.1 To clean the air filter" on page 27 and "17.1.3 To clean the air outlet and outside panels" on page 27).
17.4 About the refrigerant
This product contains fluorinated greenhouse gases. Do NOT vent gases into the atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675
Refrigerant type: R410A
Global warming potential (GWP) value: 2087.5

NOTICE
In Europe, the greenhouse gas emissions of the total refrigerant charge in the system (expressed as tonnes CO_2 -equivalent) is used to determine the maintenance intervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions: GWP value of the refrigerant × Total refrigerant charge [in kg] / 1000
Please contact your installer for more information.

WARNING: FLAMMABLE MATERIAL
The R32 refrigerant (if applicable) in this unit is mildly flammable. ^6
(a) Refer to the outdoor unit specifications for the type of refrigerant to be used.

WARNING
- Do NOT pierce or burn refrigerant cycle parts.
- Do NOT use cleaning materials or means to accelerate the defrosting process other than those recommended by the manufacturer.
- Be aware that the refrigerant inside the system is odourless.

WARNING
R410A is a non-combustible refrigerant, and R32 is a mildly flammable refrigerant; they normally don't leak. If the refrigerant leaks in the room and comes in contact with fire from a burner, a heater, or a cooker, this may result in a fire (in case of R32), or the formation of a harmful gas.
Turn off any combustible heating devices, ventilate the room, and contact the dealer from where you purchased the unit.
Do not use the unit until a service person confirms that the part from which the refrigerant leaked has been repaired.
17.5 After-sales service and warranty
17.5.1 Warranty period
- This product includes a warranty card that was filled in by the dealer at the time of installation. The completed card has to be checked by the customer and stored carefully.
- If repairs to the product are necessary within the warranty period, contact your dealer and keep the warranty card at hand.
17.5.2 Recommended maintenance and inspection
Since dust collects when using the unit for several years, performance of the unit will deteriorate to some extent. As taking apart and cleaning interiors of units requires technical expertise and in order to ensure the best possible maintenance of your units, we recommend to enter into a maintenance and inspection contract on top of normal maintenance activities. Our network of dealers has access to a permanent stock of essential components in order to keep your unit in operation as long as possible. Contact your dealer for more information.
When asking your dealer for an intervention, always state:
• The complete model name of the unit.
• The manufacturing number (stated on the nameplate of the unit).
• The installation date.
• The symptoms or malfunction, and details of the defect.

WARNING
- Do not modify, disassemble, remove, reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire. Contact your dealer.
- In case of accidental refrigerant leaks, make sure there are no naked flames. The refrigerant itself is entirely safe and non-toxic. R410A is a non-combustible refrigerant, and R32 is a mildly flammable refrigerant but they will generate a toxic gas when they accidentally leak into a room where combustible air from fan heaters, gas cookers, etc. is present. Always have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation.
17.5.3 Recommended maintenance and inspection cycles
Be aware that the mentioned maintenance and replacement cycles do not relate to the warranty period of the components.
| Component | Inspection cycle | Maintenance cycle (replacements and/or repairs) |
| Electric motor | 1 year | 20,000 hours |
| PCB | 25,000 hours | |
| Heat exchanger | 5 years | |
| Sensor (thermistor, etc.) | 5 years | |
| User interface and switches | 25,000 hours | |
| Drain pan | 8 years | |
| Expansion valve | 20,000 hours | |
| Solenoid valve | 20,000 hours |
The table assumes the following conditions of use:
(6) Refer to the outdoor unit specifications for the type of refrigerant to be used.
Installer and user reference guide
DAIKIN
FCAHG71-140GVEB
Split system air conditioners
4P482875-1-2017.03
- Normal use without frequent starting and stopping of the unit. Depending on the model, we recommend not starting and stopping the machine more than 6 times/hour.
• Operation of the unit is assumed to be 10 hours/day and 2,500 hours/year.

NOTICE
• The table indicates main components. Refer to your maintenance and inspection contract for more details.
- The table indicates recommended intervals of maintenance cycles. However, in order to keep the unit operational as long as possible, maintenance work may be required sooner. Recommended intervals can be used for appropriate maintenance design in terms of budgeting maintenance and inspection fees. Depending on the content of the maintenance and inspection contract, inspection and maintenance cycles may in reality be shorter than listed.
17.5.4 Shortened maintenance and replacement cycles
Shortening of "maintenance cycle" and "replacement cycle" needs to be considered in following situations:
The unit is used in locations where:
• Heat and humidity fluctuate out of the ordinary.
- Power fluctuation is high (voltage, frequency, wave distortion, etc.) (the unit cannot be used if power fluctuation is outside the allowable range).
- Bumps and vibrations are frequent.
- Dust, salt. harmful gas or oil mist such as sulphurous acid and hydrogen sulfide may be present in the air.
- The machine is started and stopped frequently or operation time is long (sites with 24 hour air-conditioning).
Recommended replacement cycle of wear parts
| Component Inspection cycle | Maintenance cycle (replacements and/or repairs) | |
| Air filter 1 year 5 years | ||
| High efficiency filter | 1 year | |
| Fuse | 10 years | |
| Pressure containing parts | In case of corrosion, contact your local dealer. | |

NOTICE
• The table indicates main components. Refer to your maintenance and inspection contract for more details.
- The table indicates recommended intervals of replacement cycles. However, in order to keep the unit operational as long as possible, maintenance work may be required sooner. Recommended intervals can be used for appropriate maintenance design in terms of budgeting maintenance and inspection fees. Contact your dealer for details.

INFORMATION
Damage due to taking apart or cleaning interiors of units by anyone other than our authorised dealers may not be included in the warranty.
18 Troubleshooting
If one of the following malfunctions occur, take the measures shown below and contact your dealer.

WARNING
Stop operation and shut off the power if anything unusual occurs (burning smells etc.).
Leaving the unit running under such circumstances may cause breakage, electric shock or fire. Contact your dealer.
The system must be repaired by a qualified service person:
| Malfunction | Measure |
| If a safety device such as a fuse, a breaker or an earth leakage breaker frequently actuates or the ON/OFF switch does not properly work. | Turn off the main power switch. |
| If water leaks from the unit. | Stop the operation. |
| The operation switch does not work well. | Turn off the power. |
| If the user interface display indicates the unit number, the operation lamp flashes and the malfunction code appears. | Notify your installer and report the malfunction code. |
If the system does not properly operate except for the above mentioned cases and none of the above mentioned malfunctions is evident, investigate the system according to the following procedures.
| Malfunction | Measure |
| If the system does not operate at all. | Check if there is no power failure. Wait until power is restored. If power failure occurs during operation, the system automatically restarts immediately after power is restored.Check if no fuse has blown or breaker is activated. Change the fuse or reset the breaker if necessary. |
| The system operates but cooling or heating is insufficient. | Check if air inlet or outlet of outdoor or indoor unit is not blocked by obstacles. Remove any obstacles and make sure the air can flow freely.Check if the air filter is not clogged (see "17.1.1 To clean the air filter" on page 27).Check the temperature setting.Check the fan speed setting on your user interface.Check for open doors or windows. Close doors and windows to prevent wind from coming in.Check if there are too many occupants in the room during cooling operation. Check if the heat source of the room is excessive.Check if direct sunlight enters the room. Use curtains or blinds.Check if the air flow angle is proper. |
If after checking all above items, it is impossible to fix the problem yourself, contact your installer and state the symptoms, the complete model name of the unit (with manufacturing number if possible) and the installation date (possibly listed on the warranty card).
19 Relocation
18.1 Symptoms that are NOT system malfunctions
The following symptoms are NOT system malfunctions:
18.1.1 Symptom: The system does not operate
- The air conditioner does not start immediately after the ON/OFF button on the user interface is pressed. If the operation lamp lights, the system is in normal condition. To prevent overloading of the compressor motor, the air conditioner starts 5 minutes after it is turned ON again in case it was turned OFF just before. The same starting delay occurs after the operation mode selector button was used.
- If "Under Centralized Control" is displayed on the user interface, pressing the operation button causes the display to blink for a few seconds. The blinking display indicates that the user interface cannot be used.
- The system does not start immediately after the power supply is turned on. Wait one minute until the micro computer is prepared for operation.
18.1.2 Symptom: The fan strength does not correspond to the setting
The fan speed does not change even if the fan speed adjustment button in pressed. During heating operation, when the room temperature reaches the set temperature, the outdoor unit goes off and the indoor unit changes to whisper fan speed. This is to prevent cold air blowing directly on occupants of the room. The fan speed will not change if the button is pressed.
18.1.3 Symptom: The fan direction does not correspond to the setting
The fan direction does not correspond with the user interface display. The fan direction does not swing. This is because the unit is being controlled by the micro computer.
18.1.4 Symptom: White mist comes out of a unit (Indoor unit)
- When humidity is high during cooling operation. If the interior of an indoor unit is extremely contaminated, the temperature distribution inside a room becomes uneven. It is necessary to clean the interior of the indoor unit. Ask your dealer for details on cleaning the unit. This operation requires a qualified service person.
- Immediately after the cooling operation stops and if the room temperature and humidity are low. This is because warm refrigerant gas flows back into the indoor unit and generates steam.
18.1.5 Symptom: White mist comes out of a unit (Indoor unit, outdoor unit)
When the system is changed over to heating operation after defrost operation. Moisture generated by defrost becomes steam and is exhausted.
18.1.6 Symptom: The user interface display reads "U4" or "U5" and stops, but then restarts after a few minutes
This is because the user interface is intercepting noise from electric appliances other than the air conditioner. The noise prevents communication between the units, causing them to stop. Operation automatically restarts when the noise ceases.
18.1.7 Symptom: Noise of air conditioners (Indoor unit)
- A "zeen" sound is heard immediately after the power supply is turned on. The electronic expansion valve inside an indoor unit starts working and makes the noise. Its volume will reduce in about one minute.
- A continuous low "shah" sound is heard when the system is in cooling operation or at a stop. When the drain pump is in operation, this noise is heard.
- A "pishi-pishi" squeaking sound is heard when the system stops after heating operation. Expansion and contraction of plastic parts caused by temperature change make this noise.
18.1.8 Symptom: Noise of air conditioners (Indoor unit, outdoor unit)
- A continuous low hissing sound is heard when the system is in cooling or defrost operation. This is the sound of refrigerant gas flowing through both indoor and outdoor units.
- A hissing sound which is heard at the start or immediately after stopping operation or defrost operation. This is the noise of refrigerant caused by flow stop or flow change.
18.1.9 Symptom: Noise of air conditioners (Outdoor unit)
When the tone of operating noise changes. This noise is caused by the change of frequency.
18.1.10 Symptom: Dust comes out of the unit
When the unit is used for the first time in a long time. This is because dust has gotten into the unit.
18.1.11 Symptom: The units can give off odours
The unit can absorb the smell of rooms, furniture, cigarettes, etc., and then emit it again.
18.1.12 Symptom: The outdoor unit fan does not spin
During operation. The speed of the fan is controlled in order to optimise product operation.
18.1.13 Symptom: The display shows "88"
This is the case immediately after the main power supply switch is turned on and means that the user interface is in normal condition. This continues for 1 minute.
18.1.14 Symptom: The compressor in the outdoor unit does not stop after a short heating operation
This is to prevent refrigerant from remaining in the compressor. The unit will stop after 5 to 10 minutes.
19 Relocation
Contact your dealer for removing and reinstalling the total unit. Moving units requires technical expertise.
20 Disposal
This unit uses hydrofluorocarbon. Contact your dealer when discarding this unit.
NOTICE
Do not try to dismantle the system yourself: the dismantling of the system, treatment of the refrigerant, oil and other parts must comply with applicable legislation. Units must be treated at a specialised treatment facility for reuse, recycling and recovery.
21 Glossary
Dealer
Sales distributor for the product.
Authorized installer
Technical skilled person who is qualified to install the product.
User
Person who is owner of the product and/or operates the product.
Applicable legislation
All international, European, national and local directives, laws, regulations and/or codes that are relevant and applicable for a certain product or domain.
Service company
Qualified company which can perform or coordinate the required service to the product.
Installation manual
Instruction manual specified for a certain product or application, explaining how to install, configure and maintain it.
Operation manual
Instruction manual specified for a certain product or application, explaining how to operate it.
Maintenance instructions
Instruction manual specified for a certain product or application, which explains (if relevant) how to install, configure, operate and/or maintain the product or application.
Accessories
Labels, manuals, information sheets and equipment that are delivered with the product and that need to be installed according to the instructions in the accompanying documentation.
Optional equipment
Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation.