DAIKIN

EWADH12TZSLC2 - Air-conditioner DAIKIN - Free user manual and instructions

Find the device manual for free EWADH12TZSLC2 DAIKIN in PDF.

📄 78 pages English EN Download 💬 AI Question
Notice DAIKIN EWADH12TZSLC2 - page 6
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about EWADH12TZSLC2 DAIKIN

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Air-conditioner in PDF format for free! Find your manual EWADH12TZSLC2 - DAIKIN and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. EWADH12TZSLC2 by DAIKIN.

USER MANUAL EWADH12TZSLC2 DAIKIN

REV01
Date10-2024
SupersedesD-EOMAC01905-23_00EN

CONTROL PANEL OPERATING MANUAL D-EOMAC01905-23_01EN

Air cooled chiller with inverter driven screw compressor

MICROTECH CONTROLLER

TABLE OF CONTENTS

1 SAFETY CONSIDERATIONS....6

1.1 General 6
1.2 Before switching the unit....6
1.3 Avoid electrocution....6

2 GENERAL DESCRIPTION....7

2.1 Basic Information 7
2.2 Abbreviations used....7
2.3 Controller Operating Limits....7
2.4 Controller Architecture 7
2.5 Communication Modules 8

3 USING THE CONTROLLER....9

3.1 Navigating....9
3.2 Passwords....10
3.3 Editing....10
3.4 Mobile app HMI....10
3.5 Basic Control System Diagnostic....11
3.6 Controller maintenance....12
3.7 Optional Remote User Interface....12
3.8 Embedded Web Interface 13

4 WORKING WITH THIS UNIT 14

4.1 Chiller On/Off 14

4.1.1 Keypad On/Off....14
4.1.2 Scheduler and Silent mode functionalities....15
4.1.3 Network On/Off 15

4.2 Water Setpoints....15

4.3 Unit Mode....17

4.3.1 Energy Saving mode 17

4.4 Unit Status....18
4.5 Network Control 19
4.6 Thermostatic Control....20
4.7 Date/Time....21
4.8 Pumps....22
4.9 External Alarm....22
4.10 Power Conservation....23

4.10.1 Demand Limit....23
4.10.2 Current Limit 25
4.10.3 Setpoint Reset 25

4.10.3.1 Setpoint Reset by OAT 26
4.10.3.2 Setpoint Reset by External 4-20 mA signal 26
4.10.3.3 Setpoint Reset by Return 26

4.10.4 Softload 27

4.11 Electrical Data 28
4.12 Controller IP Setup....29
4.13 Daikin On Site 30
4.14 Heat Recovery 30
4.15 Rapid Restart 31
4.16 FreeCooling Hydronic (Cooling Only) 32

4.16.1 Glycol Free Freecoling....32

4.17 Antifreeze Heater 33
4.18 Glycol Tank Heater 33
4.19 Harmonic Filter (SAF) 34
4.20 Software Options....35

4.20.1 Changing the Password for buying new Software Options 36

4.20.2 Inserting the Password in a Spare Controller....36
4.21 Modbus MSTP 37
4.22 BACnet MSTP 38
4.23 BACnet IP 38
4.24 Energy Monitoring 39

5 ALARMS AND TROUBLESHOOTING....41

5.1 Unit Alerts....41

5.1.1 Bad Current Limit Input 41
5.1.2 Option1BoardCommFail – Optional board 1 communication fail ....41
5.1.3 Bad Leaving Water Temperature Reset Input....41
5.1.4 Energy Meter Communication Fail....42
5.1.5 Evaporator Pump #1 Failure 42
5.1.6 Evaporator Pump #2 Failure 43
5.1.7 External Event 43
5.1.8 Password Over Time 44
5.1.9 Heat Recovery Entering Water Temperature sensor fault 44
5.1.10 Heat Recovery Leaving Water Temperature sensor fault 44
5.1.11 Heat Recovery Water Temperatures inverted....45
5.1.12 Evaporator differential pressure transducer sensor fault 45
5.1.13 System load differential pressure transducer sensor fault 45
5.1.14 Switch Box Temperature High 45
5.1.15 Switch Box Temperature sensor fault 46
5.1.16 Glycol leaving water temperature sensor fault 46
5.1.17 Glycol entering water temperature sensor fault 46
5.1.18 Glycol module communication fail 47
5.1.19 Glycol pump communication fail 47
5.1.20 Glycol pump alarm....47
5.1.21 Datacenter module temperature top PLC side sensor fault 48
5.1.22 Datacenter module temperature bottom PLC side sensor fault 48
5.1.23 Datacenter module temperature top 1 LH filter side sensor fault....48
5.1.24 Datacenter module temperature top 2 LH filter side sensor fault 49
5.1.25 Datacenter module temperature bottom LH filter side sensor fault....49
5.1.26 Datacenter module relative humidity sensor fault 49
5.1.27 Datacenter module communication fail....50
5.1.28 SAF communication fail 50
5.1.29 SAF High current....50
5.1.30 SAF High temperature 50
5.1.31 SAF High regulation card temperature 51
5.1.32 SAF Under voltage 51
5.1.33 SAF Over voltage 51
5.1.34 SAF Precharge Failure 52
5.1.35 SAF Precharge k1 Failure 52
5.1.36 SAF Precharge k2 Failure 52
5.1.37 SAF STO Fault 52
5.1.38 SAF STO Fault 53

5.2 Unit Pumpdown Stop Alarms 53

5.2.1 Evaporator Entering Water Temperature (EWT) sensor fault 53
5.2.2 Evaporator Water Temperatures inverted....53
5.2.3 Outside Air Temperature (OAT) Lockout 54
5.2.4 Outside Air Temperature sensor fault alarm 54

5.3 Unit Rapid Stop Alarms....54

5.3.1 Emergency Stop 54
5.3.2 Evaporator Flow Loss alarm 55
5.3.3 Evaporator Leaving Water Temperature (LWT) sensor fault 55

5.3.4 Evaporator Water Freeze alarm....55
5.3.5 External alarm....56
5.3.6 UnitOff CC1CommFail - Circuit 1 – CC1 Communication Error....56
5.3.7 UnitOff CC2CommFail - Circuit 2 – CC2 Communication Error....56
5.3.8 UnitOff Module1C1CommFail - Circuit 1 - Module1C1 Communication Error....57
5.3.9 UnitOff Module1C2CommFail - Circuit 2 – Module1C2 Communication Error....57
5.3.10 Heat Recovery Water Freeze Protect alarm 57
5.3.11 OptionCtrlrCommFail 58
5.3.12 Power Fault (only units with the UPS option)....58
5.3.13 PVM alarm....59
5.3.14 Glycol Water Freeze alarm 59

5.4 Circuit Alerts....59

5.4.1 Economizer Pressure Sensor fault 59
5.4.2 Economizer Temperature Sensor fault 60
5.4.3 Failed Pumpdown....60
5.4.4 Gas Leakage Sensor fault 61
5.4.5 CxCmp1 MaintCode01 61
5.4.6 CxCmp1 MaintCode02 61
5.4.7 Power Loss 62
5.4.8 Liquid Temperature sensor fault 62
5.4.9 Liquid Pressure sensor fault 62
5.4.10 SpeedTrol Fan Communication Error 63
5.4.11 Cx Fans Communication Error....63
5.4.12 Cx Fan Error 63
5.4.13 Cx Fan Over V 64
5.4.14 Cx Fan Under V 64

5.5 Circuit Pumpdown Stop Alarms....64

5.5.1 Discharge Temperature Sensor fault....64
5.5.2 Gas Leakage fault....65
5.5.3 High Compressor Vfd Temperature fault 65
5.5.4 Low Compressor Vfd Temperature fault 65
5.5.5 Low Discharge Superheat fault....66
5.5.6 Oil Pressure Sensor fault....66
5.5.7 Antichatteting alarm....66
5.5.8 Suction Temperature Sensor fault 67

5.6 Circuit Rapid Stop Alarms 67

5.6.1 Compressor VFD Fault 67
5.6.2 Compressor VFD OverTemp 67
5.6.3 Compressor VFD Temperature high....68
5.6.4 Compressor VFD A3 alarm....68
5.6.5 Condensing Pressure sensor fault....68
5.6.6 Evaporating Pressure sensor fault....69
5.6.7 EXV Driver Error (A/C units only)....69
5.6.8 Fail Start Low Pressure 69
5.6.9 Fan VFD Over Current....70
5.6.10 High Discharge Temperature Alarm 70
5.6.11 High Motor Current Alarm....70
5.6.12 High Motor Temperature Alarm 71
5.6.13 High Oil Pressure Differential Alarm 71
5.6.14 High Pressure alarm....71
5.6.15 Low Pressure alarm....72
5.6.16 Low Pressure Ratio Alarm 73
5.6.17 Maximum Number of Restart Alarm....73
5.6.18 Mechanical High Pressure Alarm....73

5.6.19 No Pressure At Start Alarm 74
5.6.20 No Pressure Change At Start Alarm....74
5.6.21 Overvoltage Alarm on input voltage....74
5.6.22 Overvoltage Alarm on DC rectified voltage....75
5.6.23 Undervoltage Alarm on input voltage....75
5.6.24 Undervoltage Alarm on DC rectified voltage....76
5.6.25 VFD Communication Failure....76
5.6.26 Fans Modbus Communication Failure 76
5.6.27 Fan Fault 77

1.1 General

Installation, start-up and servicing of equipment can be hazardous if certain factors particular to the installation are not considered: operating pressures, presence of electrical components and voltages and the installation site (elevated plinths and built-up up structures). Only properly qualified installation engineers and highly qualified installers and technicians, fully trained for the product, are authorized to install and start-up the equipment safely.

During all servicing operations, all instructions and recommendations, which appear in the installation and service instructions for the product, as well as on tags and labels fixed to the equipment and components and accompanying parts supplied separately, must be read, understood and followed.

Apply all standard safety codes and practices.

Wear safety glasses and gloves.

DAIKIN EWADH12TZSLC2 - General - 1

Do not operate on a faulty fan, pump or compressor before the main switch has been shut off. Overtemperature protection is auto-reset, therefore the protected component may restart automatically if temperature conditions allow it.

In some unit a push button is placed on a door of the unit electrical panel. The button is highlighted by a red color in yellow background. A manual pressure of the emergency stop button stops all loads from rotating, thus preventing any accident which may occur. An alarm is also generated by the Unit Controller. Releasing the emergency stop button enables the unit, which may be restarted only after the alarm has been cleared on the controller.

DAIKIN EWADH12TZSLC2 - General - 2

The emergency stop causes all motors to stop, but does not switch off power to the unit. Do not service or operate on the unit without having switched off the main switch.

1.2 Before switching the unit

Before switching on the unit read the following recommendations:

  • When all the operations and all the settings have been carried out, close all the switchbox panels
  • The switchbox panels can only be opened by trained personnel
  • When the UC requires to be accessed frequently the installation of a remote interface is strongly recommended
  • LCD display of the unit controller may be damaged by extremely low temperatures (see chapter 2.4). For this reason, it is strongly recommended to never power off the unit during winter, especially in cold climates.

1.3 Avoid electrocution

Only personnel qualified in accordance with IEC (International Electrotechnical Commission) recommendations may be permitted access to electrical components. It is particularly recommended that all sources of electricity to the unit be shut off before any work is begun. Shut off main power supply at the main circuit breaker or isolator.

IMPORTANT: This equipment uses and emits electromagnetic signals. Tests have shown that the equipment conforms to all applicable codes with respect to electromagnetic compatibility.

DAIKIN EWADH12TZSLC2 - Avoid electrocution - 1Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons.
DAIKIN EWADH12TZSLC2 - Avoid electrocution - 2RISK OF ELECTROCUTION: Even when the main circuit breaker or isolator is switched off, certain circuits may still be energized, since they may be connected to a separate power source.
DAIKIN EWADH12TZSLC2 - Avoid electrocution - 3RISK OF BURNS: Electrical currents cause components to get hot either temporarily or permanently. Handle power cable, electrical cables and conduits, terminal box covers and motor frames with great care.
DAIKIN EWADH12TZSLC2 - Avoid electrocution - 4In accordance with the operating conditions the fans can be cleaned periodically. A fan can start at any time, even if the unit has been shut down.

2.1 Basic Information

Microtech® is a system for controlling single or dual-circuit air/water-cooled liquid chillers. Microtech® controls compressor start-up necessary to maintain the desired heat exchanger leaving water temperature. In each unit mode it controls the operation of the condensers to maintain the proper condensation process in each circuit.

Safety devices are constantly monitored by Microtech® to ensure their safe operation. Microtech® also gives access to a Test routine covering all inputs and outputs.

2.2 Abbreviations used

In this manual, the refrigeration circuits are called circuit #1 and circuit #2. The compressor in circuit #1 is labelled Cmp1. The other in circuit #2 is labelled Cmp2. The following abbreviations are used:

A/CAir Cooled
CEWTCondenser Entering Water Temperature
CLWTCondenser Leaving Water Temperature
CPCondensing Pressure
CSRTCondensing Saturated Refrigerant Temperature
DSHDischarge Superheat
DTDischarge Temperature
E/MEnergy Meter Module
EEWTEvaporator Entering Water Temperature
ELWTEvaporator Leaving Water Temperature
EPEvaporating Pressure
ESRTEvaporating Saturated Refrigerant Temperature
EXVElectronic Expansion Valve
HMIHuman Machine Interface
MOPMaximum operating pressure
SSHSuction Superheat
STSuction Temperature
UCUnit controller (Microtech)

2.3 Controller Operating Limits

Operation (IEC 721-3-3):

• Temperature -40...+70 °C
• Restriction LCD -20... +60 °C
- Restriction Process-Bus -25....+70 °C
• Humidity < 90 % r.h (no condensation)
• Air pressure min. 700 hPa, corresponding to max. 3,000 m above sea level

Transport (IEC 721-3-2):

• Temperature -40...+70 °C
• Humidity < 95 % r.h (no condensation)
• Air pressure min. 260 hPa, corresponding to max. 10,000 m above sea level.

2.4 Controller Architecture

The overall controller architecture is the following:

• One Microtech main controller
- I/O extensions as needed depending on the configuration of the unit
- Communications interface(s) as selected
- Peripheral Bus is used to connect I/O extensions to the main controller.

DAIKIN EWADH12TZSLC2 - Controller Architecture - 1

flowchart
graph TD
    A["BAS Interface (Bacnet, Lon, Mod bus)"] --> B["Microtech"]
    B --> C["Main Controller"]
    C --> D["Peripheral Bus"]
    D --> E["I/O extension EXV 1"]
    E --> F["I/O extension EXV 2"]
    F --> G["I/O Extension Options"]

DAIKIN EWADH12TZSLC2 - Controller Architecture - 2

Maintain the correct polarity when connecting the power supply to the boards, otherwise the peripheral bus communication will not operate and the boards may be damaged.

2.5 Communication Modules

Any of the following modules can be connected directly to the left side of the main controller to allow a BAS or other remote interface to function. Up to three can be connected to the controller at a time. The controller should automatically detect and configure itself for new modules after booting up. Removing modules from the unit will require manually changing the configuration.

ModuleSiemens Part NumberUsage
BacNet/IPPOL908.00/MCQOptional
LonPOL906.00/MCQOptional
ModbusPOL902.00/MCQOptional
BACnet/MSTPPOL904.00/MCQOptional

Microtech 4 does not have an integrated HMI. The interaction with the controller can be done using a mobile app that can be download from the store (Playstore for Android devices and Apple Store for iOS devices).

DAIKIN EWADH12TZSLC2 - Communication Modules - 1

natural_image Front view of a gray electronic device with multiple ports and connectors (no visible text or symbols)

DAIKIN EWADH12TZSLC2 - Communication Modules - 2

natural_image Front view of a computer rack with ventilation slots and two ports (no visible text or labels)

Optionally is possible to order the Remote HMI that can be connected to the available CE+ CE- port on the controller. This port is in the bottom connectors row of the controller.

DAIKIN EWADH12TZSLC2 - Communication Modules - 3

text_image INFO 45C OK

DAIKIN EWADH12TZSLC2 - Communication Modules - 4

natural_image Close-up of a server rack with two labeled buttons and a yellow highlight (no readable text or symbols)

3.1 Navigating

When power is applied to the control circuit, the controller screen will be active and display the Home screen, which can also be accessed by pressing the Menu Button.

An example of the HMI screens is shown in the following picture.

Main Menu 1 / 11
Enter Password
Unit Status =
Off: Unit SW
Active Set pt = 7.0 °C

A bell ringing in the top right corner will indicate an active alarm. If the bell doesn't move it means that the alarm has been acknowledged but not cleared because the alarm condition hasn't been removed. A LED will also indicate where the alarm is located between the unit or circuits.

DAIKIN EWADH12TZSLC2 - Navigating - 1

text_image Main Menu 1 / Enter Password Unit Status = Off: Unit SW Active Set pt = 7.0 °C

The active item is highlighted in contrast, in this example the item highlighted in Main Menu is a link to another page. By pressing the push'n'roll, the HMI will jump to a different page. In this case the HMI will jump to the Enter Password page.

Enter Password2 / 2
Enter PW* * * *

3.2 Passwords

The HMI structure is based on access levels that means that each password will disclose all the settings and parameters allowed to that password level. Basic information about the status can be accessed without the need to enter the password. The user UC handles two level of passwords:

USER5321
MAINTENANCE2526

The following information will cover all data and settings accessible with the maintenance password. User password will disclose a subset of the settings explained in chapter.

In the Enter Password screen, the line with the password field will be highlighted to indicate that the field on the right can be changed. This represents a setpoint for the controller. Pressing the push'n'roll the individual field will be highlighted to allow an easy introduction of the numeric password.

Enter Password2 / 2
Enter PW5 * * *

The password will time out after 10 minutes and is cancelled if a new password is entered or the control powers down. Entering an invalid password has the same effect as continuing without a password. It is changeable from 3 to 30 minutes via the Timer Settings menu in the Extended Menus.

3.3 Editing

The Editing Mode is entered by pressing the navigation wheel while the cursor is pointing to a line containing an editable field. Pressing the wheel again cause the new value to be saved and the keypad/display to leave the edit mode and return to the navigation mode.

3.4 Mobile app HMI

The Daikin mAP mobile app HMI is provided for free and aims to simplify the interaction with this Daikin product. The app can be downloaded from the official stores with the following links (scan the QR code to directly access the download pages on the stores).

DAIKIN EWADH12TZSLC2 - Mobile app HMI - 1
iOS

DAIKIN EWADH12TZSLC2 - Mobile app HMI - 2
Android

To use the app is needed to pre-register an account and gain access to the specific unit to access. The access will be granted per unit base. A user can access multiple units after the app-tenant authorize this access. The procedure to register an account is in app. It's necessary to follow the sign in link in the app:

DAIKIN EWADH12TZSLC2 - Mobile app HMI - 3

text_image User login If you have a Safari AppWizard Europe account you can use it to log us. AUDENTICATE WITH MICROSOFT Add your a new user? SCAN us On log to wait your Safari wAP credentials. Help: PASS/GO Forgot password?

DAIKIN EWADH12TZSLC2 - Mobile app HMI - 4

text_image New user Enter your details to request access. Status Accession My access to the website (e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-mail: e-1337 Do you already have an account?

The mobile app will allow you to monitor all the relevant data, change the user related settings, trend data, update chiller software and more to come. App layout will adapt based on the device where the app is running and will look as follows:

DAIKIN EWADH12TZSLC2 - Mobile app HMI - 5

DAIKIN EWADH12TZSLC2 - Mobile app HMI - 6

For further information consult the Quick Guide Daikin Map 1.0 - D-EPMAP00101-23_EN.

3.5 Basic Control System Diagnostic

Microtech controller, extension modules and communication modules are equipped with two status LED (BSP and BUS) to indicate the operational status of the devices. The BUS LED indicates the status of the communication with the controller. The meaning of the two status LED is indicated below.

Main Controller (UC)

BSP LEDMode
Solid GreenApplication running
Solid YellowApplication loaded but not running (*) or BSP Upgrade mode active
Solid RedHardware Error (*)
Flashing GreenBSP startup phase. The controller needs time for starting.
Flashing YellowApplication not loaded (*)
Flashing Yellow/RedFail safe mode (in case that the BSP upgrade was interrupted)
Flashing RedBSP Error (software error*)
Flashing Red/GreenApplication/BSP update or initialization

(*) Contact Service.

Extension modules

BSP LEDModeBUS LEDMode
Solid GreenBSP runningSolid GreenCommunication running, I/O working
Solid RedHardware Error (*)Solid RedCommunication down (*)
Flashing RedBSP Error (*)Solid YellowCommunication running but parameter from the application wrong or missing, or incorrect factory calibration
Flashing Red/GreenBSP upgrade mode

Communication modules

BSP LED (same for all modules)

BSP LEDMode
Solid GreenBPS running, communication with controller
Solid YellowBSP running, no communication with controller (*)
Solid RedHardware Error (*)
Flashing RedBSP Error (*)
Flashing Red/GreenApplication/BSP update

(*) Contact Service.

BUS LED

BUS LEDLONBacnet MSTPBacnet IPModbus
Solid GreenReady for Communication. (All Parameter loaded; Neuron configured). Doesn't indicate a communication with other devices.Ready for Communication. The BACnet Server is started. It doesn't indicate an active communication.Ready for Communication. The BACnet Server is started. It doesn't indicate an active communication.All Communication running
Solid YellowStartupStartupStartup. The LED stays yellow until the module receives a IP Address, therefore a link must be established.Startup, or one configured channel not communicating to the Master
Solid RedNo Communication to Neuron (internal error, could be solved by downloading a new LON application).BACnet Server down. Automatically a restart after 3 seconds is initiated.BACnet Server down. Automatic restart after 3 seconds is initiated.All configured Communications down. Means no communication to the Master. The timeout can be configured. In case that the timeout is zero the timeout is disabled.
Flashing YellowCommunication not possible to the Neuron. The Neuron must be configured and set online over the LON Tool.

3.6 Controller maintenance

The controller requires to maintain the installed battery. Every two years it's required to replace the battery. Battery model is: BR2032 and it is produced by many different vendors. To replace the battery, remove the plastic cover of the controller display using a screw driver as shown in the following pictures:

DAIKIN EWADH12TZSLC2 - Controller maintenance - 1

natural_image Interior view of an electronic control panel with multiple connected modules and wiring (no visible text or symbols)

DAIKIN EWADH12TZSLC2 - Controller maintenance - 2

natural_image Interior view of an electronic control panel with a green circuit board and wiring, no visible text or symbols

Be careful to avoid damages to the plastic cover. The new battery shall be placed in the proper battery holder, which is highlighted in the picture, respecting the polarities indicated into the holder itself.

3.7 Optional Remote User Interface

As an option an external Remote HMI can be connected on the UC. The Remote HMI offers the same features as the inbuilt display plus the alarm indication done with a light emitting diode located below the bell button.

All viewing and setpoint adjustments available on the unit controller are available on the remote panel. Navigation is identical to the unit controller as described in this manual.

DAIKIN EWADH12TZSLC2 - Optional Remote User Interface - 1

text_image MicroTech®

The Remote HMI can be extended up to 700m using the process bus connection available on the UC. With a daisy-chain connection as below, a single HMI can be connected to up to 8 units. Refer to the specific HMI manual for details.

DAIKIN EWADH12TZSLC2 - Optional Remote User Interface - 2

flowchart
graph LR
    A["RSROM"] --> B["UDT1MOS"]
    B --> C["UDT2MOS"]
    C --> D["UDT30MOS"]
    subgraph Inputs
        E["CE+"] --> F["BUK"]
        G["CE-"] --> H["WHT"]
    end
    subgraph Outputs
        I["BUK"] --> J["WHT"]
    end

3.8 Embedded Web Interface

The Microtech controller has an embedded web interface that can be used to monitor the unit when connected to a local network. It is possible to configure the IP addressing of the Microtech as a fixed IP of DHCP depending on the network configuration.

With a common web browser, a PC can connect with the unit controller entering the IP address of the controller or the host name, both visible in the "About Chiller" page accessible without entering a password.

When connected, it will be required to enter a username and a password. Enter the following credential to get access to the web interface:

Username: Daikin

Password: Daikin@web

Sign in to access this site

Authorization required by http://192.168.1.42

Your connection to this site is not secure

DAIKIN EWADH12TZSLC2 - Sign in to access this site - 1

text_image Username Password

Sign in
Cancel

The Main Menu page will be displayed. The page is a copy of the onboard HMI and follows the same rules in terms of access levels and structure.

DAIKIN EWADH12TZSLC2 - Sign in to access this site - 2

text_image Info 1 Main Menu Enter Password View/Set Unit View/Set Circuit Unit Status Auto: Max Pulldn Rate Setpoint 7.0°C Evaporator LWT 10.0°C Unit Capacity 16.5%

DAIKIN EWADH12TZSLC2 - Sign in to access this site - 3

line | Date | Setpoint | Evaporater EWT | | ---------- | -------- | -------------- | | 08-59-45 | 12 | 7 | | 08-59-30 | 12 | 7 | | 08-59-15 | 12 | 7 | | 08-59-20 | 12 | 7 | | 08-59-21 | 12 | 7 | | 08-59-30 | 12 | 7 | | 08-59-35 | 12 | 7 |

In addition, it allows to trend log a maximum of 5 different quantities. It's required to click on the value of the quantity to monitor and the following additional screen will become visible:

Depending on the web browser and its version the trend log feature may not be visible. It's required a web browser supporting HTML 5 like for example:

• Microsoft Internet Explorer v.11,
• Google Chrome v.37,
- Mozilla Firefox v.32.

These software are only an example of the browser supported and the versions indicated have to be intended as minimum versions.

4.1 Chiller On/Off

Starting from factory setup, unit On/Off can be managed by the user using the selector Q0, placed in the electrical panel, which can switch between three positions: 0 - Local - Remote.

DAIKIN EWADH12TZSLC2 - Chiller On/Off - 1

0

Unit is disabled

DAIKIN EWADH12TZSLC2 - Chiller On/Off - 2

Loc (Local)

Unit is enabled to start the compressors

DAIKIN EWADH12TZSLC2 - Chiller On/Off - 3

Rem (Remote)

Unit On/Off is managed through the "Remote On/Off" physical contact.

Closed contact means unit enabled.

Opened contact means unit disabled.

Refer to the electrical wiring diagram, Field Wiring Connection page, to find the references about Remote On/Off contact. Generally, this contact is used to bring out from the electrical panel the on/off selector

Unit controller provides also additional software features to manage unit start/stop, that are set by default to allow unit start:

  1. Keypad on/off
  2. Scheduler (Time programmed On/Off)
  3. Network On/Off (optional with communication modules)

4.1.1 Keypad On/Off

In the main page, scroll down until Unit Enable menu, where are available all settings to manage unit and circuits start/stop.

DAIKIN EWADH12TZSLC2 - Keypad On/Off - 1

text_image Info 4 Main Menu Unit Status Off: Unit Switch Setpoint 7.0°C Evaporator LWT 7.0°C Unit Capacity 0.0% Unit Enable Enable Unit Mode Cool Timers ESC OK

DAIKIN EWADH12TZSLC2 - Keypad On/Off - 2

text_image Info 4 Unit Enable Unit Enable Circuit 1 Enable Circuit 2 Enable
ParameterRangeDescription
UnitDisableUnit disabled
EnableUnit enabled
SchedulerUnit start/stop can be time programmed for each weekday
Circuit #XDisableCircuit #X disabled
EnableCircuit #X enabled
TestCircuit #X in test mode. This feature has to be used only from trained person or Daikin service

DAIKIN EWADH12TZSLC2 - Keypad On/Off - 3

text_image Unit Enable Disable Enable Scheduler Save Cancel

DAIKIN EWADH12TZSLC2 - Keypad On/Off - 4

text_image Circuit 1 Enable Disable Enable Test Save Cancel

4.1.2 Scheduler and Silent mode functionalities

The Scheduler function can be used when is required an automatic chiller start/stop programming.

To use this function, follow below instructions:

  1. Q0 selector = Local
  2. Unit Enable = Scheduler
  3. Controller date and time properly set

Scheduler programming is available going in Main Page → View/Set Unit → Scheduler menu

DAIKIN EWADH12TZSLC2 - Scheduler and Silent mode functionalities - 1

text_image Info 4 Scheduler State Off Monday Active Tuesday Passive Wednesday Passive Thursday Passive Friday Passive Saturday Passive Sunday Passive ESC OK

DAIKIN EWADH12TZSLC2 - Scheduler and Silent mode functionalities - 2

text_image Info 01:Monday Time 1 00:00 Value 1 Off Time 2 07:30 Value 2 Off Time 3 *:** Value 3 Off Time 4 *:** Value 4 Off ESC OK

For each weekday can be programmed up to six-time bands with a specific operating mode. First operating mode starts at Time 1, ends at Time 2 when will start the second operating mode and so on until the latest.

DAIKIN EWADH12TZSLC2 - Scheduler and Silent mode functionalities - 3

text_image Time 1 00 • : 00 • Save Cancel

DAIKIN EWADH12TZSLC2 - Scheduler and Silent mode functionalities - 4

text_image Value 1 Off Off On 1 On 2 On 1 - Silent On 2 - Silent

Depending on unit type, different operating modes are available:

ParameterRangeDescription
Value 1offUnit disabled
On Setpoint 1Unit enabled – Water setpoint 1 selected
On Setpoint 2Unit enabled – Water setpoint 2 selected
On 1 - SilentUnit enabled – Water setpoint 1 selected – Fan silent mode enabled
On 2 - SilentUnit enabled – Water setpoint 2 selected – Fan silent mode enabled

When the Fan Silent Mode function is enabled the chiller noise level is reduced decreasing the maximum speed allowed for fans. Maximum Speed of Fans is reduced to 75% to reduce noise level.

4.1.3 Network On/Off

Chiller On/off can be managed also with serial protocol, if the unit controller is equipped with one or more communication modules (BACNet, Modbus or LON). To control the unit over the network, follow below instructions:

  1. Q0 selector = Local
  2. Unit Enable = Enable
  3. Control Source = Network
  4. Close the contact Local/Network Switch, when required!

4.2 Water Setpoints

Purpose of this unit is to cool or to heat (in case of heat pump) the water temperature, to the setpoint value defined by the user and displayed in the main page:

DAIKIN EWADH12TZSLC2 - Water Setpoints - 1

text_image Main Menu Enter Password View/Set Unit View/Set Circuit Unit Status Off: Unit Switch Setpoint 7.0°C Evaporator LWT 7.0°C Unit Capacity 0.0%

DAIKIN EWADH12TZSLC2 - Water Setpoints - 2

text_image Info 2 Tmp Setpoints Cool LWT 1 7.0°C Cool LWT 2 7.0°C Ice LWT -4.0°C Max LWT 18.0°C Min LWT -8.0°C HR EWT Sp 40.0°C HR EWT Dif 2.0°C HR Lock Limit 25.0°C ESC OK

The unit can work with a primary or a secondary setpoint, that can be managed as indicated below:

  1. Keypad selection + Double Setpoint digital contact
  2. Keypad selection + Scheduler Configuration
  3. Network
  4. Setpoint Reset function

As first step the primary and secondary setpoints need to be defined. From main menu, with user password, press on Setpoint.

ParameterRangeDescription
Cool LWT 1Ranges of the Cool, Heat, Ice setpoint are reported in the IOM of every specific unit.Primary cooling setpoint.
Cool LWT 2Secondary cooling setpoint.
Ice LWTSetpoint for Ice mode.
Max LWTHigh limit for Cool LWT1 and Cool LWT2
Min LWTLow limit for Cool LWT1 and Cool LWT2
HR EWT SpHeat Recovery Entering Water Setpoint
HR DifHeat Recovery Water Temperature differential
HR Lock LimitHeat Recovery Lock Limit
HR Delta SpHeat Recovery Delta Setpoint

The change between primary and secondary setpoint can be performed using the Double setpoint contact, always available in the user terminal box, or through the Scheduler function.

Double setpoint contact works as below:

  • Contact opened, the primary setpoint is selected
  • Contact closed, the secondary setpoint is selected

DAIKIN EWADH12TZSLC2 - Water Setpoints - 3

When the scheduler function is enabled, the Double setpoint contact is ignored

DAIKIN EWADH12TZSLC2 - Water Setpoints - 4

When the operating mode Cool/Ice w/Glycol is selected, the Double Setpoint contact will be used to switch between the Cool and Ice mode, producing no change on the active setpoint

4.3 Unit Mode

The Unit Mode is used to define if the chiller is working to produce chilled or heated water. Current mode is reported in the main page to the item Unit Mode.

DAIKIN EWADH12TZSLC2 - Unit Mode - 1

text_image Info 4 Main Menu Unit Status Off: Unit Switch Setpoint 7.0°C Evaporator LWT 449.8°C Unit Capacity 0.0% Unit Enable Enable Unit Mode Cool Timers ESC OK

DAIKIN EWADH12TZSLC2 - Unit Mode - 2

text_image Info 4 Unit Mode Mode Cool Energy Saving Yes ESC OK

Depending on the unit type, different operating modes can be selected entering, with maintenance password, in the Unit Mode menu. In the table below are listed and explained all modes.

ParameterRangeDescriptionUnit Range
ModeCoolSet if chilled water temperature up to 4°C is required. No glycol is generally needed in the water circuit, unless ambient temperature may reach low values.A/C
Cool w/GlycolSet if chilled water temperature below 4°C is required. This operation requires proper glycol/water mixture in the evaporator water circuit.A/C
Cool/Ice w/GlycolSet in case a dual cool/ice mode is required. The switch between the two modes is performed using the contact physical Double Setpoint.Double Setpoint opened: the chiller will work in cooling mode with the Cool LWT being as the Active Setpoint.Double Setpoint closed: The chiller will work in Ice mode with the Ice LWT as the Active Setpoint.A/C
Ice w/GlycolSet if Ice storage is required. The application requires the compressors to operate at full load until the ice bank is completed, and then to stop for at least 12 hours. In this mode the compressor(s) will not operate at part load but will work only in on/off mode.A/C
TestEnables the Manual Control of the unit. The manual test feature helps in debugging and checking the operational status of actuators. This feature is accessible only with the maintenance password in the main menu. To activate the test feature is required to disable the Unit from the Q0 switch and change the available mode to Test.A/C
Energy SavingNo, YesDisable/Enable of the energy saving function

Like the On/Off and setpoint control, also the unit mode can be modified from network.

4.3.1 Energy Saving mode

Some unit types provide the possibility to enable an energy saving function, that reduces the power consumption deactivating the compressors crankcase heater, when the chiller is Disabled.

This mode implies that the time needed to start the compressors, after an Off period, could be delayed until a maximum of 90 minutes.

For time critical application, the energy saving function can be disabled by the user to ensure the compressor start within 1 minute from unit On command.

DAIKIN EWADH12TZSLC2 - Energy Saving mode - 1

text_image Info 4 Main Menu Unit Status Off: Unit Switch Setpoint 7.0°C Evaporator LWT 449.8°C Unit Capacity 0.0% Unit Enable Enable Unit Mode Cool Timers ESC OK

DAIKIN EWADH12TZSLC2 - Energy Saving mode - 2

text_image Info 4 Unit Mode Mode Cool Energy Saving Yes ESC OK

4.4 Unit Status

Unit controller provides in the main page some information about chiller status. All chiller states are listed and explained below:

ParameterOverall statusSpecific statusDescription
Unit StatusAuto:Unit is in Auto control. The pump is running and at least one compressor is running.
Wait For LoadUnit is in standby because the thermostatic control satisfies the active setpoint.
Water RecircWater pump is running in order to equalize the water temperature in the evaporator.
Wait For FlowUnit pump is running but the flow signal still indicates a lack of flow through the evaporator.
Max PulldownUnit thermostatic control is limiting the unit capacity as the water temperature is dropping too quickly.
Capacity LimitDemand limit has been hit. Unit capacity will not further increase.
Current LimitMaximum current has been hit. Unit capacity will not further increase.
Silent ModeUnit is running and Silent Mode is enabled
PumpdownUnit is performing the pumpdown procedure and d it will stop within few minutes
Off:Master DisableUnit is disabled by the Master Slave function
Ice Mode TimerThis status can be shown only if the unit can work in Ice Mode. The unit is off because the Ice setpoint has been satisfied. Unit will remain off until the Ice Timer has expired.
OAT LockoutThe unit cannot run because the Oustide Air Temperature is below the limit foreseen for the condenser temperature control system installed in this Unit. If the Unit has to run anyway, check with your local maintenance how to proceed.
Circuits DisabledNo circuit is available to run. All circuits can be disabled by their individual enable switch or can be disabled by a component safety condition active or can be disabled by keypad or can be all in alarms. Check the individual circuit status for further details.
Unit AlarmA unit alarm is active. Check the alarm list to see what the active alarm is inhibiting the unit to start and check if the alarm can be cleared. Refer to section 5. before proceeding.
Keypad DisableThe Unit has been disabled by keypad. Check with your local maintenance if it can be enabled.
Network DisabledUnit is disabled by Network.
Unit SwitchThe Q0 selector is set to 0 or the or the Remote On/Off contact is opened.
TestUnit mode set to Test. This mode is activated to check operability of onboard actuators and sensors. Check with the local maintenance if the Mode can be reverted to the one compatible with unit application (View/Set Unit - Set-Up - Available Modes).
Scheduler DisableUnit is disabled by Scheduler programming

4.5 Network Control

When the unit controller is equipped with one or more communication modules the Network Control feature can be enabled, which gives the possibility to control the unit via serial protocol (Modbus, BACNet or LON). To allow unit's control from network, follow below instructions:

  1. Close the physical contact "Local/Network Switch". Refer to unit electrical wiring diagram, Field wiring Connection page, to find the references about this contact.

  2. Go to Main Page → View/Set Unit → Network Control Set Controls Source = Network

DAIKIN EWADH12TZSLC2 - Network Control - 1

text_image Info 4 View/Set Unit Thermostatic Control Network Control Pumps Compressor VFD Setup Power Conservation Heat Recovery Scheduler Date/Time

DAIKIN EWADH12TZSLC2 - Network Control - 2

text_image Info 4 Network Ctrl Control Source Network Actual Control Network Enable Disable Mode Cool Cool LWT 7.0°C Heat LWT 45.0°C Ice LWT -4.0°C Current Limit 2001 ESC OK

Network Control menu returns all main values received from serial protocol.

ParameterRangeDescription
Control SourceLocalNetwork control disabled
NetworkNetwork control enabled
Actual ControlLocal, NetworkActive control between Local/BMS.
Enable-On/Off command from network
Mode-Operating mode from network
Cool LWT-Cooling water temperature setpoint from network
Heat LWT-Heating water temperature setpoint from network
Ice LWT-Ice water temperature setpoint from network
Current LimitSetpoint for current limitation from BMS
Capacity Limit-Capacity limitation from network
Remote ServerRemote servers enable

Refer to communication protocol documentation for specific registers addresses and the related read/write access level.

4.6 Thermostatic Control

Thermostatic control settings, allows to set up the response to temperature variations. Default settings are valid for most application, however plant specific conditions may require adjustments in order to have a smooth control or a quicker response of the unit.

The control will start the first compressor if the controlled temperature is higher (Cool Mode) or lower (Heat Mode) than the active setpoint of at least a Start Up DT value, whereas other compressors are started, step by step, if the controlled temperature is higher (Cool Mode) or lower (Heat Mode) than the active setpoint (AS) of at least a Stage Up DT (SU) value. Compressors stop if performed following same procedure looking to the parameters Stage Down DT and Shut Down DT.

Cool ModeHeat Mode
First compressor startsControlled Temperature > Setpoint + Start Up DTControlled Temperature < Setpoint - Start Up DT
Other compressors startControlled Temperature > Setpoint + Stage Up DTControlled Temperature < Setpoint - Stage Up DT
Last compressor stopControlled Temperature < Setpoint - Shut Dn DTControlled Temperature > Setpoint - Shut Dn DT
Other compressors stopControlled Temperature < Setpoint - Stage Dn DTControlled Temperature > Setpoint - Stage Dn DT

A qualitative example of compressors start-up sequence in cool mode operation is shown in the graph below.

DAIKIN EWADH12TZSLC2 - Thermostatic Control - 1

line | Time Segment | ElWT [°C] | SP+StartUpΔT | SP+StageUpΔT | | ------------------------- | --------- | ------------ | ------------ | | First Compressor On | ~1.0 | - | - | | Compressor starting inhibited for maximum pull down rate | - | - | - | | Other Compressors On | - | - | - | | Dead band zone | - | - | - |

When controlled temperature is within the dead band (DB) error from the active setpoint (AS), unit capacity will not be changed.

If the leaving water temperature decreases below (Cool Mode) or rises above (Heat Mode) the active setpoint (AS), unit capacity is adjusted to keep it stable. A further decreasing (Cool Mode) or increasing (Heat Mode) of the controlled temperature of the Shut Down DT offset (SD) can cause circuit shutdown.

DAIKIN EWADH12TZSLC2 - Thermostatic Control - 2

line | Phase | Controlled Temperature | | ------------------ | ---------------------- | | AS+S | High | | Capacity load up | Medium | | Capacity Unload | Low | | COOL MODE | Low |

Thermostatic control settings are accessible from Main Page→Thermostatic Control

DAIKIN EWADH12TZSLC2 - Thermostatic Control - 3

text_image View/Set Unit Thermostatic Control Network Control Pumps Compressor VFD Setup Power Conservation Heat Recovery Scheduler Date/Time

DAIKIN EWADH12TZSLC2 - Thermostatic Control - 4

text_image Info 4 | Thermostat Ctrl | Start Up DT 2.7°C Shut Down DT 1.0°C Stage Up DT 0.5°C Stage Down DT 0.7°C Stage Up Delay 5min Stage Down Delay 3min Ice Cycle Delay 12h
ParameterRangeDescription
Start Up DT0-5°CDelta temperature respect the active setpoint to start the unit (startup of first compressor)
Shut Down DT0-3°CDelta temperature respect the active setpoint to stop the unit (shutdown of latest compressor)
Stage Up DT0-1.7°CDelta temperature respect the active setpoint to start a compressor
Stage Down DT0-3°CDelta temperature respect the active setpoint to stop a compressor
Stage Up Delay0-60 minMinimum time between the compressors startup
Stage Down Delay3-30 minMinimum time between the compressors shutdown
Ice Cycle Delay1-23 hUnit standby period during Ice mode operation
Max Circuits Run1-2Limit to the number of circuits to be used
Next Circuit OnShows next circuit to be started up
Next Circuit OffShows next circuit number to be stopped

4.7 Date/Time

The unit controller can take stored the actual date and time, that are used for:

  1. Scheduler
  2. Cycling of standby chiller with Master Slave configuration
  3. Alarms Log

Date and time can be modified going in View/Set Unit → Date/Time

DAIKIN EWADH12TZSLC2 - Date/Time - 1

text_image Info 4 View/Set Unit Compressor VFD Setup Power Conservation Heat Recovery Scheduler Date/Time Controller IP Setup Daikin on Site Menu Password ESC OK

DAIKIN EWADH12TZSLC2 - Date/Time - 2

text_image Date/Time Time 15:15:28 Date 07/25/2019 UTC Difference -60min Daylight Saving Time: Enable Yes Start Month Mar Start Week 2ndweek End Month ESC OK
ParameterRangeDescription
TimeActual date. Press to modify. Format is hh:mm:ss
DateActual time. Press to modify. Format is mm/dd/yy
DayReturns the day of the week.
UTC DifferenceCoordinated universal time.
Daylight Saving Time:
EnableNo, YesIt is used to enable/disable the automatic switch of the Daylight Saving Time
Start MonthNA, Jan...DecDaylight Saving time start month
Start Week 1^st...5^th weekDaylight Saving time start week
End MonthNA, Jan...DecDaylight Saving time end month
End Week 1^st...5^th weekDaylight Saving time end week

DAIKIN EWADH12TZSLC2 - Date/Time - 3

Remember to check periodically the controller battery in order to maintain updated date and time even when there is no electrical power. Refer to controller maintenance section.

4.8 Pumps

The UC can manage one or two water pumps for both evaporators. Number of pumps and their priority can be set from Main Page→View/Set Unit→Pumps.

DAIKIN EWADH12TZSLC2 - Pumps - 1

text_image Info 4 View/Set Unit Thermostatic Control Network Control Pumps Compressor VFD Setup Power Conservation Heat Recovery Scheduler Date/Time

DAIKIN EWADH12TZSLC2 - Pumps - 2

text_image Info 4 Pumps Evaporator: Pump Control #1 Only Recirculation Timer 30s Pump 1 Hours 0 Pump 2 Hours 0 ESC OK
ParameterRangeDescription
Pump Control#1 OnlySet to this in case of single pump or twin pump with only #1 operational (f.e. in case of maintenance on #2)
#2 OnlySet to this in case of twin pump with only #2 operational (f.e. in case of maintenance on #1)
AutoSet for automatic pump start management. At each chiller start, the pump with the least number of hours will be
#1 PrimarySet to this in case of twin pump with #1 running and #2 as a backup
#2 PrimarySet to this in case of twin pump with #2 running and #1 as a backup
Recirculation TimerMinimum time required within flow switch has to in order to allow unit startup
Pump 1 HoursPump 1 running hours
Pump 2 HoursPump 2 running hours

4.9 External Alarm

The External Alarm is a digital contact that can be used to communicate to the UC an abnormal condition, coming from an external device connected to the unit. This contact is in the customer terminal box and depending on the configuration can causes a simple event in the alarm log or also the unit stop. The alarm logic associated to the contact is the following:

Contact stateAlarm StateNote
OpenedAlarmThe alarm is generated if the contact remains opened for at least 5 seconds
ClosedNo AlarmThe alarm is reset just the contact is closed

The configuration is performed from the Commissioning → Configuration → Options menu

DAIKIN EWADH12TZSLC2 - External Alarm - 1

text_image Options Fan Alarm No Switch Box Temp No Rapid Restart No Ext Alarm Event Loc Net Switch No M/S Address None M/S Num Of Units 2 M/S Sns Type None ESC OK

DAIKIN EWADH12TZSLC2 - External Alarm - 2

text_image Info 1 Options Ext Alarm Event Event Rapid Stop Save Cancel M/S Sns Type None ESC OK
ParameterRangeDescription
Ext AlarmEventEvent configuration generates an alarm in the controller but takes the unit running
Rapid StopRapid Stop configuration generates an alarm in the controller and performs a rapid stop of the unit

DAIKIN EWADH12TZSLC2 - External Alarm - 3

At the end of the Setpoint Reset configuration, execute an Apply Changes to make the configurations made effective.

4.10 Power Conservation

In this chapters will be explained the functions used to reduce the unit power consumption:

  1. Demand Limit
  2. Current Limit
  3. Setpoint Reset
  4. Softload

DAIKIN EWADH12TZSLC2 - Power Conservation - 1

text_image Info 4 Power Conservation Demand Limit Current Limit Setpoint Reset Softload

Main Menu→View / Set Unit→Power Conservation

4.10.1 Demand Limit

The "Demand limit" function allows the unit to be limited to a specified maximum load. Capacity limit level is regulated using an external 4-20 mA signal with a linear relationship shown in the picture below. A signal of 4 mA indicates the maximum capacity available whereas a signal of 20 mA indicates the minimum capacity available. With demand limit function is not possible shutdown the unit but only unload it until minimum admissible capacity. Demand limit related setpoints available through this menu are listed in the table below.

To enable this option, go to Main Menu → Commission Unit → Configuration → Options and set the Demand Limit parameter to Enable.

DAIKIN EWADH12TZSLC2 - Demand Limit - 1

At the end of the Setpoint Reset configuration, execute an Apply Changes to make the configurations made effective.

All info about this function is reported in the Main Menu → View/set Unit → Power Configuration → Demand Limit page.

DAIKIN EWADH12TZSLC2 - Demand Limit - 2

text_image Info 2 Power Conservation Demand Limit Current Limit Setpoint Reset Softload ESC OK

DAIKIN EWADH12TZSLC2 - Demand Limit - 3

text_image Info 2 Demand Limit Unit Capacity 0.0% Demand Limit 75.0% ESC OK

DAIKIN EWADH12TZSLC2 - Demand Limit - 4

line | Demand Limit [mA] | Capacity Limit [%] | |---|---| | 4 | Maximum Capacity | | 20 | Minimum Capacity |
ParameterDescription
Unit CapacityDisplays current unit capacity
Demand Limit EnEnables demand limit
Demand LimitDisplays active demand limit

4.10.2 Current Limit

Current limit function allows to control unit power consumption taking current drawn below a specific limit. If external digital signal is triggered, the function Current Limit is activated, and the user can set a Current Limit Setpoint defined through the HMI or BAS communication.

If Flexible Current Limit Option is activated, by Commissioning → Configuration → Options → Flex Current Limit, user can decrease the real limit using an external 4-20mA signal as indicate in the graph below. With 20 mA real current limit is set to Current Limit Setpoint, whereas with 4 mA signal the unit is unloaded until minimum capacity.

DAIKIN EWADH12TZSLC2 - Current Limit - 1

line | Flexible Current Limit [mA] | Current Limit [A] | | --------------------------- | ----------------- | | 4 | 0 | | 20 | 20 |
ParameterDescription
Unit CurrentActual Chiller Current
Current LimitActive Current Limit
Current SetpointCurrent Setpoint. Overwrite by external 4-20 mA signal if Flex Curr Limit is activated.

All info about this function are reported in the Main Menu → view/set Unit → Power Configuration → Current Limit page.

DAIKIN EWADH12TZSLC2 - Current Limit - 2

text_image Info Power Conservation Demand Limit Current Limit Setpoint Reset Softload ESC

DAIKIN EWADH12TZSLC2 - Current Limit - 3

text_image Info 2 Current Limit Unit Current 0.0A Current Limit 700A Current Setpoint 700A ESC OK

4.10.3 Setpoint Reset

The setpoint reset function overrides the chilled water temperature selected through the interface, when certain circumstances occur. This feature helps in reducing energy consumption optimizing comfort as well. Three different control strategies can be selected:

  • Setpoint Reset by Outside Air Temperature (OAT)
  • Setpoint Reset by an external signal (4-20mA)
  • Setpoint Reset by Evaporator T (Return)

To set the desired setpoint-reset strategy, go to Main Menu → Commission Unit → Configuration → Options and modify the Setpoint Reset parameter, according to the following table:

DAIKIN EWADH12TZSLC2 - Setpoint Reset - 1

text_image Info 1 Options Leak Detector No Communication 1 None Communication 2 None Communication 3 None Demand Limit Disable Flex Current Limit Disable Setpoint Reset None Fan Alarm No

DAIKIN EWADH12TZSLC2 - Setpoint Reset - 2

text_image Info Power Conservation Setpoint Reset None None 4-20mA Return 0at Save Cancel Softload Softload Ramp 310bit 20min ESC OK
ParameterDescription
Max ResetMax Setpoint Reset (valid for all active modes)
Start Reset DTUsed on Setpoint Reset by Evaporator DT
Max Reset OATSee Setpoint Reset by OAT Reset
Strt Reset OATSee Setpoint Reset by OAT Reset

Each strategy needs to be configured (although a default configuration is available) and its parameters can be set navigating to Main Menu → View/Set Unit → Power Conservation → Setpoint Reset.

DAIKIN EWADH12TZSLC2 - Setpoint Reset - 3

At the end of the Setpoint Reset configuration, execute an Apply Changes to make the configurations made effective.

4.10.3.1 Setpoint Reset by OAT

The active setpoint is calculated applying a correction which is a function of ambient temperature (OAT). As temperature drops below the Start Reset OAT (SROAT), LWT setpoint is gradually increased until OAT reaches the Max Reset OAT value (MROAT). Beyond this value, the LWT setpoint is increased by the Max Reset (MR) value.

DAIKIN EWADH12TZSLC2 - Setpoint Reset by OAT - 1

line | OAT | A | | ------- | ----- | | MROAT | LWT SP + MR | | SROAT | LWT SP |
ParameterRange
Max Reset (MR) 0.0^ ÷ 10.0^
Start Reset DT 10.0^ ÷ 29.4^
Max Reset OAT (MROAT) 10.0^ ÷ 29.4^
Start Reset OAT (SROAT) 10.0^ ÷ 29.4^

4.10.3.2 Setpoint Reset by External 4-20 mA signal

The active setpoint is calculated applying a correction based on an external 4-20mA signal. 4 mA corresponds to 0°C correction, while 20 mA corresponds to a correction of the active setpoint as set in Max Reset (MR).

DAIKIN EWADH12TZSLC2 - Setpoint Reset by External 4-20 mA signal - 1

line | Signal | AS | |--------|--------| | 4mA | LWT SP | | 20mA | 1 |
ParameterRange
Max Reset (MR) 0.0^ ÷ 10.0^
Start Reset DT 10.0^ ÷ 29.4^
Max Reset OAT (MROAT) 10.0^ ÷ 29.4^
Start Reset OAT (SROAT) 10.0^ ÷ 29.4^

4.10.3.3 Setpoint Reset by Return

The active setpoint is calculated applying a correction that depends on the evaporator entering (return) water temperature. As evaporator T becomes lower than the SR T value, an offset to the LWT setpoint is increasingly applied, up to the MR value when the return temperature reaches the chilled water temperature.

DAIKIN EWADH12TZSLC2 - Setpoint Reset by Return - 1

The Return Reset may affect negatively the chiller operation when operated with variable flow. Avoid to use this strategy in case of inverter water flow control.

DAIKIN EWADH12TZSLC2 - Setpoint Reset by Return - 2

line | SRΔT | AS | |------|----| | 0 | AS | | >SRΔT | 0 |
ParameterRange
Max Reset (MR) 0.0^ ÷ 10.0^
Start Reset DT 10.0^ ÷ 29.4^
Max Reset OAT (MROAT) 10.0^ ÷ 29.4^
Start Reset OAT (SROAT) 10.0^ ÷ 29.4^

4.10.4 Softload

Soft Loading is a configurable function used to ramp up the unit capacity over a given time period, usually used to influence building electrical demand by gradually loading the unit. To enable Softload, go to the page:

Main Menu→View / Set Unit→Power Conservation→ Softload
DAIKIN EWADH12TZSLC2 - Softload - 1

text_image Info Power Conservation Demand Limit Current Limit Setpoint Reset Softload

DAIKIN EWADH12TZSLC2 - Softload - 2

text_image Info Softload Softload Enable Disable Softload Ramp 20min Starting Cap 40.0% ESC OK

Once the Softload Ramp and the Starting Cap have been set, if the Softload is enabled, the machine is forced to ramp up the capacity based on settings. It works when the machine is starting from 0%, reaching the maximum load with the speed settable by the customer.

DAIKIN EWADH12TZSLC2 - Softload - 3

line | Time [min] | LOAD [%] | | ---------- | -------- | | 0 | 0 | | Low | 0 | | Mid | 50 | | High | 100 |
ParameterDescription
Softload EnableEnables soft loading
Softload RampDuration of the soft load ramp
Starting CapBegin capacity limit. Unit will increase capacity from this value to 100% over the time specified by the Softload Ramp setpoint.

If the Softload is enabled when the machine is already running, if the Starting Cap>Actual Capacity, the Softload will ramp up the Capacity with the speed set by the customer.

4.11 Electrical Data

Unit controller returns main electrical values read by the energy meter Nemo D4-L, Nemo D4-Le or NanoH. All data are collected in the menu Electrical Data.

Main Page → View/Set Unit → Electrical Data

DAIKIN EWADH12TZSLC2 - Electrical Data - 1

text_image View/Set Unit Compressor VFD Setup Power Conservation Heat Recovery Electrical Data Scheduler Date/Time Controller IP Setup Daikin on Site

DAIKIN EWADH12TZSLC2 - Electrical Data - 2

text_image Info 4 Electrical Data Average Voltage 0V Average Current 0A Average Power 0.0kW Active Power 0kW Power Factor 0.00 Active Energy 0kWh Frequency 0Hz
ParameterDescription
Average VoltageReturns the average of the three chained voltages and links to the Voltage Data page
Average CurrentReturns the current average and links to the Current Data page
Average PowerReturns the average power
Active PowerReturns the active power
Power FactorReturns the power factor
Active EnergyReturns the active energy
FrequencyReturns the active frequency

DAIKIN EWADH12TZSLC2 - Electrical Data - 3

text_image Info Voltage Data Average Voltage 0.0V V1 0.0V V2 0.0V V3 0.0V ESC OK

DAIKIN EWADH12TZSLC2 - Electrical Data - 4

text_image Info 2 Current Data Average Current 0.0A I1 0.0A I2 0.0A I3 0.0A ESC OK

4.12 Controller IP Setup

The Controller IP Setup page is located at the path Main Menu → view/Set Unit → Controller IP Setup.

DAIKIN EWADH12TZSLC2 - Controller IP Setup - 1

text_image Info View/Set Unit Compressor VFD Setup Power Conservation Heat Recovery Electrical Data Scheduler Date/Time Controller IP Setup Daikin on Site

DAIKIN EWADH12TZSLC2 - Controller IP Setup - 2

text_image Info 2 IP Setup Settings DHCP Off IP 192.168.001.042 Mask 255.255.255.000 Gateway 192.168.001.001 PrimDNS 10.39.148.17 SecDNS 0.0.0.0 Name POL69U EB4BB4

All the information about current MT4 IP Network settings is reported in this page, as shown in the following table:

ParameterRangeDescription
DHCPOnThe DHCP option is enabled.
offThe DHCP option is disabled.
IPxxx.xxx.xxx.xxxThe current IP address
Maskxxx.xxx.xxx.xxxThe current Subnet Mask address.
Gatewayxxx.xxx.xxx.xxxThe current Gateway address.
PrimDNSxxx.xxx.xxx.xxxThe current Primary DNS address.
ScndDNSxxx.xxx.xxx.xxxThe current Secondary DNS address.
DevicePOLxxx_xxxxxxxThe Host Name of the MT4 controller.
MACxx-xx-xx-xx-xx-xxThe MAC address of the MT4 controller.

To modify the MT4 IP Network configuration, do the following operations:

  • access the Settings menu
  • set the DHCP option to Off
  • modify the IP, Mask, Gateway, PrimDNS and ScndDNS addresses, if needed, taking care of the current network settings
  • set Apply changes parameter to Yes to save the configuration and restart the MT4 controller.

DAIKIN EWADH12TZSLC2 - Controller IP Setup - 3

text_image Info 2 Settings Apply Changes No DHCP Off IP 192.168.001.042 Mask 255.255.255.000 Gateway 192.168.001.001 PrimDNS 10.39.148.17 SecDNS 0.0.0.0 Name POL69U EB4BB4 ESC OK

DAIKIN EWADH12TZSLC2 - Controller IP Setup - 4

text_image Info 2: Settings Apply Changes No No Yes Save Cancel SETD40 0.0.0.0 Name POL69U EB4BB4 ESC OK

The default internet configuration is:

ParameterDefault Value
IP192.168.1.42
Mask255.255.255.0
Gateway192.168.1.1
PrimDNS0.0.0.0
ScndDNS0.0.0.0

Note that if the DHCP is set to On and the MT4 internet configurations shows the following parameter values

ParameterValue
IP169.254.252.246
Mask255.255.0.0
Gateway0.0.0.0
PrimDNS0.0.0.0
ScndDNS0.0.0.0

then an internet connection problem has occurred (probably due to a physical problem, like the Ethernet cable breaking).

4.13 Daikin On Site

The Daikin on Site (DoS) page can be accessed navigating through Main Menu → View/Set Unit → Daikin On Site.

DAIKIN EWADH12TZSLC2 - Daikin On Site - 1

text_image Info View/Set Unit Electrical Data Evaporator Flow Scheduler Date/Time Controller IP Setup Daikin on Site Settings Change History Menu Password

DAIKIN EWADH12TZSLC2 - Daikin On Site - 2

text_image Info 1 Daikin on Site Comm Start Off Comm State - Serial Number 614 Remote Update Disable Activation Key DSFJNJ-H37NP-UHJPA-RQEOD-I4HL ICCID:

To use the DoS utility, the customer must communicate the Serial Number to Daikin company and subscribe to the DoS service. Then, from this page, it is possible to:

  • Start/Stop the DoS connectivity
  • Check the connection status to DoS service
  • Enable/Disable the remote update option

according to the parameters shown into the table below.

ParameterRangeDescription
Comm StartoffStop the connection to DoS
StartStart the connection to DoS
Comm State-Connection to DoS is off
IPErrConnection to DoS cannot be established
ConnectedConnection to DoS is established and working
Remote UpdateEnableEnable the Remote update option
DisableDisable the Remote update option

Among all the services provided by DoS, the Remote Update option allows to remotely update the software currently running on the PLC controller, avoiding an in-situ intervention of maintenance personnel. To this purpose, just set the Remote Update parameter to Enable. Otherwise, keep the parameter set to Disable.

In the unlikely event of PLC replacement, the DoS connectivity can be switched from the old PLC to the new one just communicating the current Activation Key to Daikin company.

DAIKIN EWADH12TZSLC2 - Daikin On Site - 3

For a successful remote software update, local service support is required, and a strong internet connection must be guaranteed.

4.14 Heat Recovery

The unit controller can handle a total or partial heat recovery option.

Some settings need to be properly set to match the specific plant requirements, going in Main Page > View/Set Unit > Heat Recovery.

DAIKIN EWADH12TZSLC2 - Heat Recovery - 1

text_image Info 2 View/Set Unit Thermostatic Control Network Control Pumps Compressor VFD Setup Power Conservation Heat Recovery Electrical Data Scheduler

DAIKIN EWADH12TZSLC2 - Heat Recovery - 2

text_image Info 1 Heat Recovery HR State Recirculation HR C1 Enable Disable HR C2 Enable Disable HR Network Enable Disable HR LWT -273.1°C HR EWT -273.1°C HR EWT Sp 40.0°C HR EWT Dif 2.0°C ESC OK
ParameterRangeDescription
HR StateOffHeat recovery is disabled
RecirculationHeat recovery pump is running, but chiller fan is not regulating the heat recovery water temperature
RegulationHeat recovery pump is running and chiller fans are regulating the heat recovery water temperature
HR C1 EnableDisableHeat Recovery on C1 is disabled
EnableHeat Recovery on C1 is enabled
HR C2 EnableDisableHeat Recovery on C2 is disabled
EnableHeat Recovery on C2 is enabled
HR Network EnableDisableThe Heat Recovery is disabled by Network
EnableThe Heat Recovery is enabled by Network
HR LWTHeat recovery leaving water temperature
HR EWTHeat recovery entering water temperature
HR EWT SpHeat recovery entering water temperature setpoint value
HR EWT DifHeat recovery
HR Lock LimitHeat Recovery Lock Limit
HR Delta SpHeat Recovery Delta Setpoint
HR 3-Way ValveHeat recovery 3-way valve opening percentage
HR PumpsHeat recovery pump state
HR Pump HoursHeat recovery pump running hours

DAIKIN EWADH12TZSLC2 - Heat Recovery - 3

line | HR EWT [°C] | HR 3WV [%] | | ----------- | ---------- | | HR Lock Lim | 0 | | HR SP-Δ | 100 | | HR SP | 100 |

In case unit control source is "Network", to enable heat recovery functionality following conditions must be true:

  • Enable the "HR C1 or C2 Enable" parameter in the Heat recovery page.
  • Enable BMS register: Heat Recovery - Enable Setpoint

4.15 Rapid Restart

This chiller can activate a Rapid Restart (optional) sequence in reaction to a power failure. A digital contact is used to inform the controller that the feature is enabled. The feature is configured in the factory.

DAIKIN EWADH12TZSLC2 - Rapid Restart - 1

text_image Info 4 View/Set Unit Thermostatic Control Network Control Pumps Compressor VFD Setup Power Conservation Rapid Restart Scheduler Date/Time ESC OK

DAIKIN EWADH12TZSLC2 - Rapid Restart - 2

text_image Info 4 Rapid Restart Rapid Restart Disabled Power Off Time 60s ESC OK

Rapid restart is activated under the following conditions:

• The power failure exists for up to 180 seconds
• The unit and circuit switches are ON
- No unit or circuit alarms exist
• The unit has been running in the normal Run state
• The BMS Circuit Mode setpoint is set to Auto when the control source is Network

If the power failure is more than 180 seconds, the unit will start based on the setting of the Stop-to-Start cycle timer (minimum setting of 3 minutes) and load per standard unit without Rapid Restart.

When Rapid Restart is active, the unit will restart within 30 seconds of power restoration. The time to restore full load is less than 3 minutes.

4.16 FreeCooling Hydronic (Cooling Only)

Freecooling is started when the outside air temperature is lower than the entering water temperature by a predetermined freecooling delta T. Full freecooling will only be possible below a design temperature however logic will try to get the most out of the air temperature to optimize the overall performance of the chiller.

When freecooling is started, the freecooling valve is opened to let water pass through the freecooling coils and get cooled before entering the evaporator heat exchanger and go to the plant as leaving water temperature. Fans are started and then controlled to maintain the leaving water temperature to the active setpoint.

If the outside air temperature is not low enough to permit full freecooling and satisfy the plant load, the unit may start the mixed mode. In fact, if, with the fan at full speed, the leaving water temperature does not reach the active setpoint and remains above the Stage Up Temperature with a low slope, after a predetermined time a circuit can be started in mechanical mode. In this case, the fan speed will be adapted to control the minimum pressure ratio needed to guarantee the correct lubrication of compressors.

DAIKIN EWADH12TZSLC2 - FreeCooling Hydronic (Cooling Only) - 1

text_image Info 1 View/Set Unit Compressor VFD Setup Power Conservation Hydronic FreeCooling Scheduler Date/Time Controller IP Setup Daikin on Site Settings Change History ESC OK

DAIKIN EWADH12TZSLC2 - FreeCooling Hydronic (Cooling Only) - 2

text_image Info 1 FreeCooling Input Disable Remote Input Disable State Off FC Max OAT 24.0°C FC Delta T 4.0°C FC Min VFD Sp 0% FC Max VFD Sp 86% FC Prop Gain 5.0°C
ParameterRangeDescription
InputDisableThe Option is not enabled with all the inputs necessary
EnableThe Option is correctly enabled
Remote InputDisableThe Remote Input is not enabled with all the inputs necessary
EnableThe Remote Input is correctly enabled
StateoffUnit's State in Off
Free CoolingUnit State in Free Cooling mode, both Circuits run in Freecooling
MixedUnit State in Mixed mode, one Circuit run in Freecooling and the second run in Mechanical mode
MechanicalUnit State in Mechanical mode, both Circuits run in Mechanical
FC Max Oat10-30 °CMaximum value for air temperature to enable the freecooling. Above this value the freecooling mode cannot be used.
FC Delta T0-10 °CDifference between entering water temperature and air temperature to enable the freecooling operations.
FC Min Pr1.4-3To adjust minimum pressure ratio for fans control.
FC Max Pr1.4-3To adjust maximum pressure ratio for fans control.
FC Min VFD Sp5-50 %To adjust minimum fan speed in freecooling mode.
FC Max VFD Sp70-100 %To adjust maximum fan speed in freecooling mode.

In order to enable the Freecooling functionality, the customer must set to Enable the "Input" parameter in the Freecooling page.

In case unit control source is "Network", to enable freecooling functionalities following conditions must be true:

1) Enable the "Input" parameter in the Freecooling page.
2) Enable BMS register: Freecooling - Enable Setpoint

4.16.1 Glycol Free Freecoling

The Glycol Free option in Freecoling condition is characterized with the presence of an intermediate water/water heat exchanger connected to a water loop with glycol. The main water loop will be glycol free to simplify the waste water

management. This kind of chillers require an additional pump to circulate the glycol in the freecooling closed loop which is linked to the main loop through an intermediate heat exchanger. This pump will be always active when freecooling is active, in case in of freezing in the closed loop or OAT Lockout.

So, in case of glycol free option, there are some additional datapoints respect the hydronic freecooling:

DAIKIN EWADH12TZSLC2 - Glycol Free Freecoling - 1

text_image Info 1 View/Set Unit Compressor VFD Setup Power Conservation Hydronic FreeCooling Scheduler Date/Time Controller IP Setup Daikin on Site Settings Change History ESC OK Info 4 FreeCooling FC Max OAT 24.0°C FC Delta T 4.0°C FC Min VFD Sp 23% FC Max VFD Sp 86% Glycol Pmp Spd 100% Glycol Pmp Act Spd 0% Glycol Nom PD 10kPa Glycol Min Freq 30Hz ESC OK
ParameterRangeDescription
Glycol Pmp Spd0-100 %Select nominal glycol pump's speed
Glycol Pmp Act Spd0-100 %Show the actual velocity of the glycol pump
Glycol Nom PD1-200 kPaSelect nominal evaporator pressure drop corresponding at the rated flow rate
Glycol Min Freq1-40 HzSelect the minimum frequency of the glycol pump
Glycol DT OFS0-15 °CSelect the additional offset to the Fc Delta T to enable the freecooling operations (during the transition mechanical Fc to mixed Fc)

4.17 Antifreeze Heater

The Antifreeze Heater page can be accessed navigating through Main Menu → View/Set Unit → AntifreezeHeater

DAIKIN EWADH12TZSLC2 - Antifreeze Heater - 1

text_image Info 1 View/Set Unit Thermostatic Control Network Control Pumps AntiFrz Heater Glycol Tank Heater Compressor VFD Setup Power Conservation Hydronic FreeCooling ESC OK

DAIKIN EWADH12TZSLC2 - Antifreeze Heater - 2

text_image Info 1 Antifreeze Heater Heater En On Delta Freeze 2.0°C ESC OK
ParameterRangeDescription
Heater EnoffThe Option is not enabled.
onThe Option is correctly enabled
Delta Freeze -5 ÷ +5^ Difference between entering or leaving water temperature and freezing setpoint to enable the antifreeze heater.

In order Enable the Antifreeze Heater functionality, the customer must set to On the "Heater En" parameter in the Antifreeze Heater page.

4.18 Glycol Tank Heater

The Glycol Tank Heater page can be accessed navigating through Main Menu → View/Set Unit → Glycol Tank Heater

DAIKIN EWADH12TZSLC2 - Glycol Tank Heater - 1

text_image Info 1 View/Set Unit Thermostatic Control Network Control Pumps AntiFrz Heater Glycol Tank Heater Compressor VFD Setup Power Conservation Hydronic FreeCooling ESC OK

DAIKIN EWADH12TZSLC2 - Glycol Tank Heater - 2

text_image Info 1 Glycol Tank Heater Heater En On Delta Freeze 2.0°C ESC OK
ParameterRangeDescription
Heater EnOffThe Option is not enabled.
OnThe Option is correctly enabled
Delta Freeze -5 ÷ +5^ Difference between glycol entering or glycol leaving water temperature and glycol tan freezing setpoint to enable the glycol tank heater.

In order Enable the Glycol Tank Heater functionality, the customer must set to On the "Heater En" parameter in the Glycol Tank Heater page.

4.19 Harmonic Filter (SAF)

The Harmonic Filter (SAF) page can be accessed navigating through Main Menu → View/Set Unit → Harmonic Filter.

The active harmonic filter is a power quality device that dynamically delivers a controlled current that has the same amplitude as the harmonic current, which is injected in opposition to the harmonics present. This cancels the harmonic currents in the electrical system.

DAIKIN EWADH12TZSLC2 - Harmonic Filter (SAF) - 1

text_image Info 1 View/Set Unit Compressor VFD Setup Power Conservation Heat Recovery HarmonicFilter Hydronic FreeCooling Scheduler Date/Time Controller IP Setup

DAIKIN EWADH12TZSLC2 - Harmonic Filter (SAF) - 2

text_image Info 1 Harmonic Filter Filter On On State PwrOff Clr Tmr Off Cmd Fdbk Off Reg Temp 0.0°C Cool Plate Temp 0.0°C Cool Duty Cycle 0.0 Grid Voltage 0V ESC OK
ParameterRangeDescription
Filter OnOffThe Option is not enabled.
OnThe Option is correctly enabled.
StatePwrOffPower off (Waiting main supply)
waitSSCmdWaiting soft start command
SSCmdOnSoft start command On
PreCOnCapacitors pre charge On
PreCEndCapacitors pre charge End
WaitRunWaiting Run
RunSAF runs
SAFAlmsSAF generic Alarms
PCAlmsSAF Pre charge alarms
NoStateNo state available
Clr TmroffClear Timer Off
onClear Timer On
Cmd FdbkoffCommand feedback Off
onCommand feedback On
Reg Temp°CRegulation Card temperature
Cool Plate Temp°CSAF cooling plate temperature
Cool Duty CycleSAF cooling plate valve duty cycle
Grid voltageVGrid voltage
Grid THDi%Grid total harmonic distorsion (current)
Grid TDD%Grid total demand distorsion
Grid THDv%Grid total harmonic voltage distorsion
TDDi Ref%Total demand distorsion reference
Rel Hum%real HumRelated humidity sensor
Dew Temp°CDew temperature calculated due the related humidity sensor
TbAF°CTemperature bottom sensor LH filter side
TbPLC°CTemperature bottom sensor PLC side
Tt1AF°CTemperature top 1 sensor LH filter side
Tt2AF°CTemperature top 2 sensor LH filter side
TtPLC°CTemperature top sensor PLC side
CompensationShowed in related menu all the single compressor harmonics

Main Menu → view/Set Unit → Harmonic Filter → Compensation

DAIKIN EWADH12TZSLC2 - Harmonic Filter (SAF) - 3

text_image Info 4 Compensation Harmonic 2 0.000 Harmonic 3 0.000 Harmonic 5 0.000 Harmonic 7 0.000 Harmonic 11 0.000 Harmonic 13 0.000 Harmonic 17 0.000 Harmonic 19 0.000 ESC OK

In order Enable the SAF functionality, the customer must set to On the "Filter On" parameter in the Harmonic Fitler page.

4.20 Software Options

The possibility to employ a set of software options has been added to the functionality of the chiller, in according with Microtech 4 installed on the Unit. The Software Options do not require any additional hardware and regard communication channels and the new energy functionalities.

During the commissioning the machine is delivered with the Option Set chosen by the customer; the Password inserted is permanent and depends on the Serial Machine Number and the Option Set selected.

To check the current Option Set:

Main Menu→Commission Unit→Configuration→Software Options

DAIKIN EWADH12TZSLC2 - Software Options - 1

text_image Info Configuration Unit Circuit 1 Options Software Options

DAIKIN EWADH12TZSLC2 - Software Options - 2

text_image Info 2 Software Options Apply Changes No Password 0123456789012 1-Modbus Slave MSTP On 1-State On 2-BACNet MSTP Off 2-State Off 3-BACNet IP Off 3-State Off ESC OK
ParameterDescription
PasswordWritable by Interface/Web Interface
Option NameOption Name
optionOption is activated.
StatusOption is not activated

The Current Password inserted activates the selected options.

4.20.1 Changing the Password for buying new Software Options

The Option Set and the Password are updated in the Factory. If the customer wants to change its Option Set, he needs to contact the Daikin Personnel and asks for a new password.

As soon as the new password is communicated, the follow steps allow the customer to change the Option Set by himself:

  1. Wait for the circuits are both OFF, then, from the Main Page, Main Menu→Unit Enable→Unit→Disable
  2. Go to Main Menu→Commission Unit→Configuration→Software Options
  3. Select the Options to Activate
  4. Insert the Password
  5. Wait for the States of the selected options going to On
  6. Apply Changes→Yes (it will reboot the controller)

DAIKIN EWADH12TZSLC2 - Changing the Password for buying new Software Options - 1

The Password is changeable only if the machine is working in safe conditions: both the circuits are in the State Off.

4.20.2 Inserting the Password in a Spare Controller

If the Controller is broken and/or it needs to be replaced for any reason, the customer needs to configure the Option Set with a new Password.

If this replacement is scheduled, the customer can ask to Daikin Personnel for a new Password.

If there is not enough time to ask for a Password to Daikin Personnel (ex. an expected failure of the controller), a set of Free Limited Password is provided, in order not to interrupt the machine's working.

These Passwords are free and visualized in:

Main Menu→Commission Unit→Configuration→Software Options→Temporary Passwords

DAIKIN EWADH12TZSLC2 - Inserting the Password in a Spare Controller - 1

text_image Info 1 Software Options 5-iCM Standard Off 5-State Off 6-iCM Advanced Off 6-State Off 7-Performance Monitoring Off 7-State Off Temporary Passwords Apply Changes No ESC OK

DAIKIN EWADH12TZSLC2 - Inserting the Password in a Spare Controller - 2

text_image Info 1 Temporary Passwords 1-553489691893 Not Used 2-411486702597 Not Used 3-084430952438 Not Used Mode Permanent Timer 0min

Their Use is limited up to three months:

• 553489691893 – 3 Months Duration
• 411486702597 – 1 Month Duration
• 084430952438 – 1 Month Duration

It gives the customer the time enough to contact Daikin Service and insert a new unlimited password.

Parameter Specific Status Description

553489691893Activate the Option Set for 3 Months.
411486702597Activate the Option Set for 1 Month.
084430952438Activate the Option Set for 1 Month.
ModePermanentA permanent Password is inserted. Option set can be used for unlimited time.
TemporaryA temporary Password is inserted. Option set can be used depending on the password inserted.
TimerLast duration of the Option Set activated. Enabled only if the mode is Temporary.

DAIKIN EWADH12TZSLC2 - Inserting the Password in a Spare Controller - 3

The Password is changeable only if the machine is working in safe conditions: both the circuits are in the State Off.

4.21 Modbus MSTP

When the software option "Modbus MSTP" is activated and the controller is restarted, the communication protocol settings page can be accessed via the path:

DAIKIN EWADH12TZSLC2 - Modbus MSTP - 1

text_image Name Refresh ShowRate brand Layout Info 1 Commission Unit Configuration Alarm Limits Manual Control Input/Output Sensors Calibration SW Modbus MSTP Scheduled Maintenance

Main Menu→Commission Unit→SW Modbus MSTP

The values that can be set are the same as those found on the Modbus MSTP option page with the relative driver and depend on the specific system where the unit is installed.

DAIKIN EWADH12TZSLC2 - Modbus MSTP - 2

text_image Info 1 Modbus MSTP Address 1 Baudrate 19200 Parity None 2StopBits No Delay 100 Response Timeout 100 ESC OK

To establish the connection, the RS485 port to use is the one on the T14 terminal of the MT4 controller.

DAIKIN EWADH12TZSLC2 - Modbus MSTP - 3

DAIKIN EWADH12TZSLC2 - Modbus MSTP - 4

4.22 BACnet MSTP

When the software option "BACNet MSTP" is activated and the controller is restarted, the communication protocol settings page can be accessed via the path:

DAIKIN EWADH12TZSLC2 - BACnet MSTP - 1

text_image Name Release Showfile Event Info 1 Commission Unit Configuration Alarm Limits Manual Control Input/Output Sensors Calibration SW BACNet MSTP Scheduled Maintenance

Main Menu→Commission Unit→SW BACNet MSTP

The values that can be set are the same as those found on the BACNet MSTP option page with the relative driver and depend on the specific system where the unit is installed.

DAIKIN EWADH12TZSLC2 - BACnet MSTP - 2

text_image Info 1 BACNet MSTP Device Instance 1 Name Value Status NoActivePo Address 0 Baudrate 38400 Max Master 1 Max Info Frame 1 Unit System 0 ESC OK

To establish the connection, the RS485 port to use is the one on the T14 terminal of the MT4 controller.

DAIKIN EWADH12TZSLC2 - BACnet MSTP - 3

DAIKIN EWADH12TZSLC2 - BACnet MSTP - 4

4.23 BACnet IP

When the software option "BACNet IP" is activated and the controller is restarted, the communication protocol settings page can be accessed via the path:

DAIKIN EWADH12TZSLC2 - BACnet IP - 1

text_image Info 1 Commission Unit Configuration Alarm Limits Manual Control Input/Output Sensors Calibration SW BACNet IP Scheduled Maintenance

Main Menu→Commission Unit→SW BACNet IP

The values that can be set are the same as those found on the BACNet IP option page with the relative driver and depend on the specific system where the unit is installed.

DAIKIN EWADH12TZSLC2 - BACnet IP - 2

text_image Home Refresh ShowHide map Info 1 BACNet IP Device ID 1 Name Value Status OK UDP Port 47808 Unit System 0 Act IP= 192.168.001.042 Act Msk= 255.255.255.000 Act GwV= 192.168.001.001 ESC OK

The port for LAN connection to be used for BACNet IP communication is the T-IP Ethernet port, the same one used for remote control of the controller on the PC.

4.24 Energy Monitoring

The Energy Monitoring is a software option not requiring any additional hardware. It can be activated to achieve an estimation (5% accuracy) of the instantaneous performances of the chiller in terms of:

  • Cooling Capacity
  • Power Input
  • Efficiency-COP

An integrated estimation of these quantities is provided. Go to the page:

Main Menu→View / Set Unit→Energy Monitoring
DAIKIN EWADH12TZSLC2 - Energy Monitoring - 1

text_image Info View/Set Unit Network Control Pumps Compressor VFD Setup Power Conservation Heat Recovery Energy Monitoring Scheduler Date/Time

DAIKIN EWADH12TZSLC2 - Energy Monitoring - 2

text_image Info 4 Energy Monitoring Power Input 0.0kW Cooling Capacity 0.0kW EER 0.0 Integrated PI 0.0MWh Integrated CC 0.0MWh Integrated EER 0.0 ESC OK

DAIKIN EWADH12TZSLC2 - Energy Monitoring - 3

text_image Info 2 Power Input Circuit 1 0.0kW Circuit 2 0.0kW ESC OK

DAIKIN EWADH12TZSLC2 - Energy Monitoring - 4

text_image Info 4 Cooling Capacity Circuit 1 0.0kW Circuit 2 0.0kW Deviation Method 1 0.12% ESC

DAIKIN EWADH12TZSLC2 - Energy Monitoring - 5

text_image Info 4 EER Circuit 1 0.0 Circuit 2 0.0 ESC

The UC protects the unit and the components from operating in abnormal conditions. Protections can be divided in preventions and alarms. Alarms can then be divided in pump-down and rapid stop alarms. Pump-down alarms are activated when the system or sub-system can perform a normal shutdown despite the abnormal running conditions. Rapid stop alarms are activated when the abnormal running conditions require an immediate stop of the whole system or sub-system to prevent potential damages.

The UC displays the active alarms in a dedicated page and keep an history of the last 50 entries divided between alarms and acknowledges occurred. Time and date for each alarm event and of each alarm acknowledge are stored.

The UC also stores alarm snapshot of each alarm occurred. Each item contains a snapshot of the running conditions right before the alarm has occurred. Different sets of snapshots are programmed corresponding to unit alarms and circuit alarms holding different information to help the failure diagnosis.

In the following sections it will also be indicated how each alarm can be cleared between local HMI, Network (by any of the high-level interfaces Modbus, Bacnet or Lon) or if the specific alarm will clear automatically. The following symbols are used:

Allowed
Not allowed
Not foreseen

5.1 Unit Alerts

5.1.1 Bad Current Limit Input

This alarm is generated when the Flexible Current Limit option has been enabled and the input to the controller is out of the admitted range.

SymptomCauseSolution
Unit status is Run.Bell icon is moving on controller's display.Flexible Current Limit function cannot be used.String in the alarm list:BadCurrentLimitInputString in the alarm log:± BadCurrentLimitInputString in the alarm snapshotBadCurrentLimitInputFlexible current limit input out of range.For this warning out of range is a signal less than 3mA or more than 21mA.Check for values of input signal to the unit controller. It has to be in the allowed mA range.
Check for electrical shielding of wirings.
Check for right value of the unit's controller output in case input signal is into allowed range.
ResetNotes
Local HMINetworkAuto☐☐☑Automatically clears when the signal returns in the allowed range.

5.1.2 Option1BoardCommFail – Optional board 1 communication fail

This alarm is generated in case of communication problems with the AC module.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:Option1BoardCommFailString in the alarm log:± Option1BoardCommFailString in the alarm snapshotOption1BoardCommFailModule has no power supplyCheck the power supply from the connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is tightly inserted in the module
Led OffCheck if power supply is ok but LEDs are both off. In this case replace the module
BUS or BSP Led are redCheck if module's address is correct referring to the wiring diagram.
If BSP LED is solid red replace the module.
BSP error.
Reset
Local HMINetworkAuto☑☑☐

5.1.3 Bad Leaving Water Temperature Reset Input

This alarm is generated when the Setpoint Reset option has been enabled and the input to the controller is out of the admitted range.

SymptomCauseSolution
Unit status is Run.Bell icon is moving on controller's display.LWT Reset function cannot be used.String in the alarm list:BadSetPtOverrideInputString in the alarm log:± BadSetPtOverrideInputString in the alarm snapshotBadSetPtOverrideInputLWT reset input signal is out of range.For this warning out of range is a signal less than 3mA or more than 21mA.Check for values of input signal to the unit controller. It has to be in the allowed mA range.
Check for electrical shielding of wirings.
Check for right value of the unit's controller output in case input signal is into allowed range.
ResetNotes
Local HMINetworkAuto☐☐☑Automatically clears when the signal returns in the allowed range.

5.1.4 Energy Meter Communication Fail

This alarm is generated in case of communication problems with the energy meter.

SymptomCauseSolution
Bell icon is moving on controller's display.String in the alarm list:EnrgMtrCommFailString in the alarm log:± EnrgMtrCommFailString in the alarm snapshotEnrgMtrCommFailModule has no power supplyRefer to the datasheet of the specific component to see if it is correctly powered
Wrong cabling with the Unit ControllerCheck if the polarity of the connections is respected.
Modbus parameters not properly setReferring to the datasheet of the specific component to see if the modbus parameters are set correctly:Address = 20Baud Rate =19200 kBsParity = NoneStop bits =1
Module is brokenCheck if the display shows something and the power supply is present.
ResetNotes
Local HMINetworkAuto☐☐☑Automatically clears when the communication is re-established.

5.1.5 Evaporator Pump #1 Failure

This alarm is generated if the pump is started but the flow switch is not able to close within the recirculate time. This can be a temporary condition or may be due to a broken flow switch, the activation of circuit breakers, fuses or to a pump breakdown.

SymptomCauseSolution
Unit could be ON.Bell icon is moving on controller's display.Backup pump is used or stop of all circuits in case of pump #2 failure.String in the alarm list:EvapPump1FaultString in the alarm log:± EvapPump1FaultString in the alarm snapshotEvapPump1FaultPump #1 may not be operating.Check for problem in electrical wiring of the pump #1.
Check that electrical breaker of pump #1 is tripped.
If fuses are used to protect the pump, check the integrity of fuses.
Check for problem in wiring connection between pump starter and unit controller.
Check the water pump filter and the water circuit for obstructions.
Flow Switch doesn't operate properlyCheck flow switch connection and calibration.
ResetNotes
Local HMINetworkAuto☑☑☐

5.1.6 Evaporator Pump #2 Failure

This alarm is generated if the pump is started but the flow switch is not able to close within the recirculate time. This can be a temporary condition or may be due to a broken flowswitch, the activation of circuit breakers, fuses or to a pump breakdown.

SymptomCauseSolution
Unit could be ON.Bell icon is moving on controller's display.Backup pump is used or stop of all circuits in case of pump #1 failure.String in the alarm list:EvapPump2FaultString in the alarm log:± EvapPump2FaultString in the alarm snapshotEvapPump2FaultPump #2 may not be operating.Check for problem in electrical wiring of the pump #2.
Check that electrical breaker of pump #2 is tripped.
If fuses are used to protect the pump, check the integrity of fuses.
Check for problem in wiring connection between pump starter and unit controller.
Check the water pump filter and the water circuit for obstructions.
Flow Switch doesn't operate properlyCheck flow switch connection and calibration.
ResetNotes
Local HMINetworkAuto☑☑☐

5.1.7 External Event

This alarm indicates that a device, whose operation is linked with this machine, is reporting a problem on the dedicated input.

SymptomCauseSolution
Unit status is Run.Bell icon is moving on controller's display.String in the alarm list:UnitExternalEventString in the alarm log:±UnitExternalEventString in the alarm snapshotUnitExternalEventThere is an external event that has caused the opening, for at least 5 seconds of the digital input on the controller board.Check for reasons of external event and if it can be a potential problem for a correct chiller operation.
ResetNotes
Local HMINetworkAuto☐☐☑The alarm is automatically cleared when the problem is solved.
NOTE: What above applies in case of configuration of the external fault digital input as Event

5.1.8 Password Over Time

SymptomCauseSolution
Pass1TimeOver 1dayleftTemporary Password Inserted is going to expire. One day is left before Option set becomes inactive.Insert a new password
Pass2TimeOver 1dayleft
Pass3TimeOver 1dayleft
ResetNotes
Local HMI
Network
Auto

5.1.9 Heat Recovery Entering Water Temperature sensor fault

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is Off.All circuits are stopped with a normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:UnitAlHREwtSenString in the alarm log:± UnitAlHREwtSenString in the alarm snapshotUnitAlHREwtSenSensor is broken.Check for sensor integrity according to table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.1.10 Heat Recovery Leaving Water Temperature sensor fault

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Heat Recovery is OffBell icon is moving on controller's display.String in the alarm list:UnitAlHRLwtSenString in the alarm log:± UnitAlHRLwtSenString in the alarm snapshotUnitAlHRLwtSenSensor is broken.Check for sensor integrity according to table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.1.11 Heat Recovery Water Temperatures inverted

This alarm is generated any time that the heat recovery entering water temperature is lower than the leaving by 1^ C and at least one compressor is running.

SymptomCauseSolution
Bell icon is moving on controller's display.Bell icon is moving on controller's display.String in the alarm list:Unit HRInvAlString in the alarm log:± Unit HRInvAlString in the alarm snapshotUnit HRInvAlEntering and leaving water temperature sensors are inverted.Check cabling of the sensors on the unit controller.
Check offset of the two sensors with the water pump running
Entering and leaving water pipes are reversedCheck if the water flows in counter flow respect to refrigerant.
Water pumps operate reverse.Check if the water flows in counter flow respect to refrigerant.
ResetNotes
Local HMINetworkAuto☑☑☐

5.1.12 Evaporator differential pressure transducer sensor fault

This alarm is generated any time the differential pressure transducer on the evaporator is broken.

SymptomCauseSolution
Unit status is OnBell icon is moving on controller's display.String in the alarm list:EvapPDSenString in the alarm log:± EvapPDSenString in the alarm snapshotEvapPDSenSensor is broken.Check for sensor integrity according to table and allowed Volts or Amps range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.1.13 System load differential pressure transducer sensor fault

This alarm is generated any time the differential pressure transducer on the evaporator is broken.

SymptomCauseSolution
Unit status is OnBell icon is moving on controller's display.String in the alarm list:LoadPDSenString in the alarm log:± LoadPDSenString in the alarm snapshotLoadPDSenSensor is broken.Check for sensor integrity according to table and allowed Volts or Amps range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.1.14 Switch Box Temperature High

This alarm is generated any time the switch box internal temperature exceeds a predetermined limit.

SymptomCauseSolution
Unit status is OnBell icon is moving on controller's display.String in the alarm list:SwitchBoxTAlmString in the alarm log:± SwitchBoxTAlmString in the alarm snapshotSwitchBoxTAlmInsufficient switchbox coolingCheck if the cooling fan is working properly
Check if the air filters are clean and there is no obstacle to a proper air flow.
Outside air temperature above the operating envelope of the unit.Please refer to the operating envelope of the unit to avoid possible faults or damages to the unit.
ResetNotes
Local HMINetworkAuto☑☑☐

5.1.15 Switch Box Temperature sensor fault

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is OnBell icon is moving on controller's display.Bell icon is moving on controller's display.String in the alarm list:SwitchBoxTSenString in the alarm log:± SwitchBoxTSenString in the alarm snapshotSwitchBoxTSenSensor is broken.Check for sensor integrity according to table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.1.16 Glycol leaving water temperature sensor fault

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is OnBell icon is moving on controller's display.Bell icon is moving on controller's display.String in the alarm list:Unit GlycollVgwTempString in the alarm log:± Unit GlycollVgwTempString in the alarm snapshotUnit GlycollVgwTempSensor is broken.Check for sensor integrity according to table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☐☐☐☑Automatically clears when the communication is re-established.

5.1.17 Glycol entering water temperature sensor fault

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is OnBell icon is moving on controller's display.Bell icon is moving on controller's display.String in the alarm list:Sensor is broken.Check for sensor integrity according to table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Unit GlycolEntwTempString in the alarm log:± Unit GlycolEntTempString in the alarm snapshotUnit GlycolEntwTempSensor is not properly connected(open).Check for absence of water orhumidity on electrical contacts.
Check for correct plug-in of theelectrical connectors.
Check for correct sensors wiring alsoaccording to electrical scheme.
ResetNotes
Local HMINetworkAuto□□☑Automatically clears when thecommunication is re-established.

5.1.18 Glycol module communication fail

This alarm is generated in case of communication problems with the module related to the glycol free.

SymptomCauseSolution
Unit is on.Bell icon is moving on controller's display.String in the alarm list:GlycolModuleCommFailString in the alarm log:± GlycolModuleCommFailString in the alarm snapshotGlycolModuleCommFailModule has no power supplyCheck the power supply from the connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is tightly inserted in the module
Led OffCheck if power supply is ok but LEDs are both off. In this case replace the module
BUS or BSP Led are redCheck if module's address is correct referring to the wiring diagram.
If BSP LED is solid red replace the module.
BSP error.
ResetNotes
Local HMINetworkAuto☐☐☑Automatically clears when the communication is re-established.

5.1.19 Glycol pump communication fail

This alarm is generated in case of Modbus communication problems with glycol pump.

SymptomCauseSolution
Bell icon is moving on controller's display.String in the alarm list:GlycolPmpCommFailString in the alarm log:± GlycolPmpCommFailString in the alarm snapshotGlycolPmpCommFailRS485 network is not properly cabled.Check the continuity of the RS485 network with the unit off. There should be continuity from the main controller to the pump as indicated on the wiring diagram.
Modbus communication is not running properly.Check glycol pump address. All the addresses must be different.
Glycol pump is not poweredCheck if the glycol pump is correctly powered.
ResetNotes
Local HMINetworkAuto☑☑☐

5.1.20 Glycol pump alarm

This alarm is generated in case of generic hardware or operating problem with the glycol pump in the closed loop.

SymptomCauseSolution
Unit could be ON.Bell icon is moving on controller's display.String in the alarm list:GlycolPmpAlmString in the alarm log:± GlycolPmpAlmString in the alarm snapshotGlycolPmpAlmGlycol pump may not be operating.Check for problem in electrical wiring of the glycol pump..
Check that electrical breaker of glycol pump is tripped.
If fuses are used to protect the glycol pump, check the integrity of fuses.
Check the glycol pump filter and the glycol water circuit for obstructions.
ResetNotes
Local HMI
Network
Auto

5.1.21 Datacenter module temperature top PLC side sensor fault

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is OnBell icon is moving on controller's display.Bell icon is moving on controller's display.String in the alarm list:DcTtPLC SenfString in the alarm log:± DcTtPLC SenfString in the alarm snapshotDcTtPLC SenfSensor is broken.Check for sensor integrity according to table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☐☐☑Automatically clears when the communication is re-established.

5.1.22 Datacenter module temperature bottom PLC side sensor fault

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is OnBell icon is moving on controller's display.Bell icon is moving on controller's display.String in the alarm list:DcTbPLC SenfString in the alarm log:± DcTbPLC SenfString in the alarm snapshotDcTbPLC SenfSensor is broken.Check for sensor integrity according to table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☐☐☑Automatically clears when the communication is re-established.

5.1.23 Datacenter module temperature top 1 LH filter side sensor fault

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is OnBell icon is moving on controller's display.Bell icon is moving on controller's display.String in the alarm list:DcTt1AF SenfString in the alarm log:± DcTt1AF SenfString in the alarm snapshotDcTt1AF SenfSensor is broken.Check for sensor integrity according to table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto□□☑Automatically clears when the communication is re-established.

5.1.24 Datacenter module temperature top 2 LH filter side sensor fault

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is OnBell icon is moving on controller's display.Bell icon is moving on controller's display.String in the alarm list:DcTt2AF SenfString in the alarm log:± DcTt2AF SenfString in the alarm snapshotDcTt1AF SenfSensor is broken.Check for sensor integrity according to table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☐☐☑Automatically clears when the communication is re-established.

5.1.25 Datacenter module temperature bottom LH filter side sensor fault

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is OnBell icon is moving on controller's display.Bell icon is moving on controller's display.String in the alarm list:DcTbAF SenfString in the alarm log:± DcTbAF SenfString in the alarm snapshotDcTbAF SenfSensor is broken.Check for sensor integrity according to table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☐☐☑Automatically clears when the communication is re-established.

5.1.26 Datacenter module relative humidity sensor fault

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is OnBell icon is moving on controller's display.Bell icon is moving on controller's display.String in the alarm list:DcRe1Hum SenfString in the alarm log:± DcRe1Hum SenfString in the alarm snapshotDcRe1Hum SenfSensor is broken.Check for sensor integrity according to table and allowed mV range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☐☐☑Automatically clears when the communication is re-established.

5.1.27 Datacenter module communication fail

This alarm is generated in case of communication problems with the datacenter module.

SymptomCauseSolution
Unit status is On.Bell icon is moving on controller's display.String in the alarm list: DcModCommFailString in the alarm log: ± DcModCommFailString in the alarm snapshot DcModCommFailModule has no power supplyCheck the power supply from the connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is tightly inserted in the module
Led OffCheck if power supply is ok but LEDs are both off. In this case replace the module
BUS or BSP Led are redCheck if module's address is correct referring to the wiring diagram.
If BSP LED is solid red replace the module.
BSP error.
ResetNotes
Local HMINetworkAuto☐☐☑Automatically clears when the communication is re-established.

5.1.28 SAF communication fail

This alarm is generated in case of communication problems with the SAF.

SymptomCauseSolution
Bell icon is moving on controller's display.String in the alarm list:SAF CommErrString in the alarm log:± SAF CommErrString in the alarm snapshotSAF CommErrRS485 network is not properly cabled.Check the continuity of the RS485 network with the unit off. There should be continuity from the main controller to the SAF as indicated on the wiring diagram.
Modbus communication is not running properly.SAF pump address. All the addresses must be different.
SAF is not poweredCheck if the SAF is correctly powered.
ResetNotes
Local HMINetworkAuto☐☐☐☑Automatically clears when the communication is re-established.

5.1.29 SAF High current

This alarm indicates that the SAF current has exceeded a safety limit and it must be stopped to avoid damages to components.

SymptomCauseSolution
Bell icon is moving on controller's display.String in the alarm list:SAF HiCurrentString in the alarm log:± SAF HiCurrentString in the alarm snapshotSAF HiCurrentFilter adsorbed current is exceeding a predefined limitContact service organization to check filter integrity.
ResetNotes
Local HMINetworkAuto☐☐☑

5.1.30 SAF High temperature

This alarm indicates that the SAF temperature has exceeded a safety limit and it must be stopped to avoid damages to components.

SymptomCauseSolution
Bell icon is moving on controller's display.String in the alarm list:SAF HiTempString in the alarm log:± SAF HiTempString in the alarm snapshotSAF HiTempPTC is being used and its Ohm value has reached the safety threshold.Check the motor and the PTC thermal probe.
ResetNotes
Local HMINetworkAuto☐☐☑

5.1.31 SAF High regulation card temperature

This alarm indicates that the SAF regulation card temperature has exceeded a safety limit and it must be stopped to avoid damages to components.

SymptomCauseSolution
Bell icon is moving on controller's display.String in the alarm list:SAF HiRegTempString in the alarm log:± SAF HiRegTempString in the alarm snapshotSAF HiRegTempFilter regulation card temperature is greater than maximum thresholdContact service organization to check filter integrity.
ResetNotes
Local HMINetworkAuto☐☐☑

5.1.32 SAF Under voltage

This alarm indicates that the SAF voltage supply has too low and it must be stopped to avoid damages to components.

SymptomCauseSolution
Bell icon is moving on controller's display.String in the alarm list:SAF UnderVtgString in the alarm log:± SAF UnderVtgString in the alarm snapshotSAF UnderVtgFilter is operating under unsafe condition and for this reason the inverter must be stopped.Contact service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto☐☐☑

5.1.33 SAF Over voltage

This alarm indicates that the SAF voltage supply has too high and it must be stopped to avoid damages to components.

SymptomCauseSolution
Bell icon is moving on controller's display.String in the alarm list:SAF OverVtgString in the alarm log:± SAF OverVtgString in the alarm snapshotSAF OverVtgFilter is operating under unsafe condition and for this reason the inverter must be stopped.Contact service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto□□□☑

5.1.34 SAF Precharge Failure

This alarm indicates that the SAF precharge procedure failed.

SymptomCauseSolution
Bell icon is moving on controller's display.String in the alarm list:SAF PreChgFailString in the alarm log:± SAF PreChgFailString in the alarm snapshotSAF PreChgFailFilter has not been able to complete the precharging phase, before to start the running.Contact service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto☐☐☑

5.1.35 SAF Precharge k1 Failure

This alarm indicates that the SAF contactor 1 precharge procedure failed.

SymptomCauseSolution
Bell icon is moving on controller's display.String in the alarm list:SAF K1PCFailString in the alarm log:± SAF K1PCFailString in the alarm snapshotSAF K1PCFailFilter has not been able to complete the precharging phase, before to start the running.Contact service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto☐☐☑

5.1.36 SAF Precharge k2 Failure

This alarm indicates that the SAF contactor 2 precharge procedure failed.

SymptomCauseSolution
Bell icon is moving on controller's display.String in the alarm list:SAF K2PCFailString in the alarm log:± SAF K2PCFailString in the alarm snapshotSAF K2PCFailFilter has not been able to complete the precharging phase, before to start the running.Contact service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto□□□☑

5.1.37 SAF STO Fault

This alarm indicates that the SAF safe torque contact is off. STO contact is linked in series to the other VFDs.

SymptomCauseSolution
Bell icon is moving on controller's display.String in the alarm list:SAF STO FaultString in the alarm log:± SAF STO FaultString in the alarm snapshotSAF STO FaultFilter is operating under unsafe condition and for this reason the inverter must be stopped.Contact service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto☐☐☑

5.1.38 SAF STO Fault

This alarm indicates a generic alarm to the SAF (not the previously already mentioned).

SymptomCauseSolution
Bell icon is moving on controller's display.String in the alarm list:SAF FaultString in the alarm log:± SAF FaultString in the alarm snapshotSAF FaultFilter is operating under unsafe condition and for this reason the inverter must be stopped.Contact service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto□□✓

5.2 Unit Pumpdown Stop Alarms

5.2.1 Evaporator Entering Water Temperature (EWT) sensor fault

This alarm is generated any time the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is Off.All circuits are stopped with a normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:UnitOffEvpEntwTempSenString in the alarm log:± UnitOffEvpEntwTempSenString in the alarm snapshotUnitOffEvpEntwTempSenSensor is broken.Check for sensor integrity according to table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMI Network☑☑

5.2.2 Evaporator Water Temperatures inverted

This alarm is generated any time the entering water temperature is lower than the leaving by 1^ C and at least one compressor is running for 90 seconds.

SymptomCauseSolution
Unit status is Off.All circuits are stopped with a normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:UnitOffEvpWTempInvrtdString in the alarm log:± UnitOffEvpWTempInvrtdString in the alarm snapshotUnitOffEvpWTempInvrtdEntering and leaving water temperature sensors are inverted.Check cabling of the sensors on the unit controller.
Check offset of the two sensors with the water pump running
Entering and leaving water pipes are reversedCheck if the water flows in counter flow respect to refrigerant.
Water pumps operate reverse.Check if the water flows in counter flow respect to refrigerant.
ResetNotes
Local HMINetworkAuto☑☑☐

5.2.3 Outside Air Temperature (OAT) Lockout

This alarm prevents the unit to start if the outside air temperature is too low. Purpose is to prevent low pressure trips at startup. The limit depends on the fan regulation that is installed on the unit. By default, this value is set to 10^ C.

SymptomCauseSolution
Unit Status is OAT Lockout.All circuits are stopped with a normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:StartInhbtAmbTempLoString in the alarm log:± StartInhbtAmbTempLoString in the alarm snapshotStartInhbtAmbTempLoOutside ambient temperature is lower than value set into unit's controller.Check the minimum outside ambient temperature value set into the unit's controller.
Check if this value is in accordance with chiller application, therefore check about the proper application and utilization of the chiller.
Improper operation of Outside Ambient Temperature sensor.Check for proper operation of OAT sensor according to information about kOhm (kΩ) range related to temperature values.
ResetNotes
Local HMINetworkAuto☐☐☐☑It clears automatically with a 2.5°C of hysteresis.

5.2.4 Outside Air Temperature sensor fault alarm

This alarm is generated any time the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is Off.All circuits are stopped with a normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:UnitOffAmbTempSenString in the alarm log:± UnitOffAmbTempSenString in the alarm snapshotUnitOffAmbTempSenSensor is broken.Check for sensor integrity.
Check correct sensors operation according to table and allowed kOhm (kΩ) range.
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.3 Unit Rapid Stop Alarms

5.3.1 Emergency Stop

This alarm is generated any time the Emergency Stop button is activated.

DAIKIN EWADH12TZSLC2 - Emergency Stop - 1

Before resetting the Emergency Stop button please verify that the harmful condition has been removed.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:UnitOffEmergencyStopString in the alarm log:± UnitOffEmergencyStopString in the alarm snapshotUnitOffEmergencyStopEmergency stop button has been pushed.Turning counterclockwise the emergency stop button, the alarm should be cleared.
ResetNotes
Local HMIPlease see note on the top.
Network
Auto

5.3.2 Evaporator Flow Loss alarm

This alarm is generated in case of flow loss to the chiller to protect the machine against freezing.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:UnitOffEvapWaterFlowString in the alarm log:± UnitOffEvapWaterFlowString in the alarm snapshotUnitOffEvapWaterFlowNo water flow sensed for 3 minutes continuously or water flow too low.Check the water pump filler and the water circuit for obstructions.
Check the flow switch calibration and adapt to minimum water flow.
Check if pump impeller can rotate freely and has no damages.
Check pumps protection devices (circuit breakers, fuses, inverters, etc.)
Check if water filter is clogged.
Check flow switch connections.
ResetNotes
Local HMI
Network
Auto

5.3.3 Evaporator Leaving Water Temperature (LWT) sensor fault

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is Off.All circuits are stopped with a normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:UnitOffLvgEntwTempSenString in the alarm log:± UnitOffLvgEntwTempSenString in the alarm snapshotUnitOffEvpLvgwTempSenSensor is broken.Check for sensor integrity according to table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.3.4 Evaporator Water Freeze alarm

This alarm is generated to indicate that the water temperature (entering or leaving) has dropped below a safety limit. Control tries to protect the heat exchanger starting the pump and letting the water circulate.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:UnitOffEvapWaterTmpLoString in the alarm log:± UnitOffEvapWaterTmpLoString in the alarm snapshotUnitOffEvapWaterTmpLoWater flow too low.Increase the water flow.
Inlet temperature to the evaporator is too low.Increase the inlet water temperature.
Flow switch is not working or no water flow.Check the flow switch and the water pump.
Sensor's readings (entering or leaving) are not properly calibrated.Check the water temperatures with a proper instrument and adjust the offsets
Wrong freeze limit setpoint.The freeze limit has not been changed as a function of glycol percentage.
ResetNotes
Local HMINetworkAuto☑☒☐It's required to check if the evaporator has any damage due to this alarm.

5.3.5 External alarm

This alarm is generated to indicate that an external device whose operation is linked with this unit operation. This external device could be a pump or an inverter.

SymptomCauseSolution
Unit status is Off.All circuits are switched off with the normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:UnitOffExternalAlarmString in the alarm log:± UnitOffExternalAlarmString in the alarm snapshotUnitOffExternalAlarmThere is an external event that has caused the opening, for at least 5 seconds of the port on the controller board.Check causes of the external event or alarm.
Check electrical wiring from unit controller to the external equipment in case of any external events or alarms have been occurred.
ResetNotes
Local HMINetworkAuto☑☑☐
NOTE: What above applies in case of configuration of the external fault digital input as Alarm.

5.3.6 UnitOff CC1CommFail - Circuit 1 - CC1 Communication Error

This alarm is generated in case of communication problems with the AC module.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:UnitOff CC1CommFailString in the alarm log:± UnitOff CC1CommFailString in the alarm snapshotUnitOff CC1CommFailModule has no power supplyCheck the power supply from the connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is tightly inserted in the module
Led OffCheck if power supply is ok but LEDs are both off. In this case replace the module
BUS or BSP Led are redCheck if module's address is correct referring to the wiring diagram.
If BSP LED is solid red replace the module.
BSP error.
Reset
Local HMINetworkAuto☑☑☐

5.3.7 UnitOff CC2CommFail - Circuit 2 - CC2 Communication Error

This alarm is generated in case of communication problems with the AC module.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:Unitoff CC2CommFailString in the alarm log:± Unitoff CC2CommFailString in the alarm snapshotModule has no power supplyCheck the power supply from the connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is tightly inserted in the module
Led OffCheck if power supply is ok but LEDs are both off. In this case replace the module
BUS or BSP Led are redCheck if module's address is correct referring to the wiring diagram.If BSP LED is solid red replace the module.
Unitoff CC2CommFail
BSP error.
Reset
Local HMI
Network
Auto

5.3.8 UnitOff Module1C1CommFail - Circuit 1 - Module1C1 Communication Error

This alarm is generated in case of communication problems with the AC module.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:UnitOff Module1C1CommFailString in the alarm log:± Unitoff Module1C1CommFailString in the alarm snapshotUnitOff Module1C1CommFailModule has no power supplyCheck the power supply from the connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is tightly inserted in the module
Led OffCheck if power supply is ok but LEDs are both off. In this case replace the module
BUS or BSP Led are redCheck if module's address is correct referring to the wiring diagram.
If BSP LED is solid red replace the module.
BSP error.
Reset
Local HMINetworkAuto☑☑☐

5.3.9 UnitOff Module1C2CommFail - Circuit 2 - Module1C2 Communication Error

This alarm is generated in case of communication problems with the AC module.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:UnitOff Module1C2CommFailString in the alarm log:± unitOff Module1C2CommFailString in the alarm snapshotUnitOff Module1C2CommFailModule has no power supplyCheck the power supply from the connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is tightly inserted in the module
Led OffCheck if power supply is ok but LEDs are both off. In this case replace the module
BUS or BSP Led are redCheck if module's address is correct referring to the wiring diagram.
If BSP LED is solid red replace the module.
BSP error.
Reset
Local HMINetworkAuto☑☑☐

5.3.10 Heat Recovery Water Freeze Protect alarm

This alarm is generated to indicate that the heat recovery water temperature (entering or leaving) has dropped below a safety limit. Control tries to protect the heat exchanger starting the pump and letting the water circulate.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Water flow too low.Increase the water flow.
Bell icon is moving on controller's display. String in the alarm list: UnitOff HRFreeze String in the alarm log: ± UnitOff HRFreeze String in the alarm snapshot UnitOff HRFreezeInlet temperature to the heat recovery is too low.Increase the inlet water temperature.
Sensor's readings (entering or leaving) are not properly calibratedCheck the water temperatures with a proper instrument and adjust the offsets
ResetNotes
Local HMI Network Auto☑ ☑

5.3.11 OptionCtrlrCommFail

This alarm is generated in case of communication problems with the AC module.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:OptionCtrlrCommFailString in the alarm log:± OptionCtrlrCommFailString in the alarm snapshotOptionCtrlrCommFailModule has no power supplyCheck the power supply from the connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is tightly inserted in the module
Module address is not properly setCheck if module's address is correct referring to the wiring diagram.
Module is brokenCheck if LED are on and both green.If BSP LED is solid red replace the module
Check if power supply is ok but LEDs are both off. In this case replace the module
ResetNotes
Local HMINetworkAuto☑☑☐

5.3.12 Power Fault (only units with the UPS option)

This alarm is generated when the main power is Off and the unit controller is powered by the UPS.

DAIKIN EWADH12TZSLC2 - Power Fault (only units with the UPS option) - 1

Resolution of this fault requires a direct intervention on the power supply of this unit. Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons. In case of doubts contact your maintenance company.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:Power FaultString in the alarm log:± Power FaultString in the alarm snapshotPower FaultLoss of one phase.Check voltage level on each of the phases.
Not correct sequence connection of L1, L2, L3.Check sequence of L1, L2, L3 connections according to indication on chiller's electrical scheme.
Voltage level on the unit's panel is not in the allowed range (±10%).Check that voltage level on each phase is into the allowed range that is indicated on the chiller label.Is important to check the voltage level on each phase not only with chiller not running, but mainly with chiller running from minimum capacity up to full load capacity. That's because voltage drop can occur from a certain unit cooling capacity level, or because of certain working condition (i.e. high values of OAT).In these cases, the issue can be related with the sizing of power cables.
There is a short-circuit on the unit.Check for correct electrical isolation condition of each unit's circuit with a Megger tester.
ResetNotes
Local HMINetworkAuto☑☑

5.3.13 PVM alarm

This alarm is generated in case of problems with the power supply to the chiller.

DAIKIN EWADH12TZSLC2 - PVM alarm - 1

Resolution of this fault requires a direct intervention on the power supply of this unit. Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons. In case of doubts contact your maintenance company.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:UnitOffPhaveVoltageString in the alarm log:± UnitOffPhaveVoltageString in the alarm snapshotUnitOffPhaveVoltageLoss of one phase.Check voltage level on each of the phases.
Not correct sequence connection of L1, L2,L3.Check sequence of L1, L2, L3 connections according to indication on chiller's electrical scheme.
Voltage level on the unit's panel is not in the allowed range (±10%).Check that voltage level on each phase is into the allowed range that is indicated on the chiller label.Is important to check the voltage level on each phase not only with chiller not running, but mainly with chiller running from minimum capacity up to full load capacity. That's because voltage drop can occur from a certain unit cooling capacity level, or because of certain working condition (i.e. high values of OAT).In these cases the issue can be related with the sizing of power cables.
There is a short-circuit on the unit.Check for correct electrical isolation condition of each unit's circuit with a Megger tester.
ResetNotes
Local HMINetworkAuto☐☐☑

5.3.14 Glycol Water Freeze alarm

This alarm is generated to indicate that the glycol water temperature (entering or leaving) has dropped below a safety limit. Control tries to protect the intermediate heat exchanger starting the glycol pump and letting the glycol water circulate.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:Unitoff GlycolFreezeString in the alarm log:± Unitoff GlycolFreezeString in the alarm snapshotUnitoff GlycolFreezeGlycol Water flow too low.Increase the water flow.
Check the glycol pump
Inlet temperature to the evaporator is too low.Increase the inlet water temperature.
Sensor's readings (entering or leaving) are not properly calibrated.Check the glycol water temperatures with a proper instrument and adjust the offsets
Wrong freeze limit setpoint.The glycol freeze limit has not been changed as a function of glycol percentage.
ResetNotes
Local HMINetworkAuto☑☑☐It's required to check if the intermediate heat exchanger has any damage due to this alarm.

5.4 Circuit Alerts

5.4.1 Economizer Pressure Sensor fault

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is On.Economizer is Off.Bell icon is moving on controller's display.String in the alarm list:Cx EcoPressSenString in the alarm log:± Cx EcoPressSenString in the alarm snapshotCx EcoPressSenSensor is broken.Check for sensor integrity.Check correct sensors operation according to information about mVolt (mV) range related to pressure values in kPa.
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for correct installation of the sensor on refrigerant circuit pipe. The transducer must be able to sense the pressure through the valve's needle.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.4.2 Economizer Temperature Sensor fault

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is On.Economizer is Off.Bell icon is moving on controller's display.String in the alarm list:Cx EcoTempSenString in the alarm log:± CX EcoTempSenString in the alarm snapshotCx EcoTempSenSensor is shorted.Check for sensor integrity.
Check correct sensors operation according to information about kOhm (kΩ) range related to temperature values.
Sensor is broken.Check if sensor is shorted with a resistance measurement.
Sensor is not good connected (open).Check for correct installation of the sensor on refrigerant circuit pipe.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according with electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.4.3 Failed Pumpdown

This alarm is generated to indicate that the circuit hadn't been able to remove all the refrigerant from the evaporator. It automatically clears as soon as the compressor stops just to be logged in the alarm history. It may not be recognized from BMS because the communication latency can give enough time for the reset. It may not even be seen on the local HMI.

SymptomCauseSolution
Circuit status is Off.No indications on the screenString in the alarm list:--String in the alarm log:± Cx Failed PumpdownString in the alarm snapshotCx Failed PumpdownEEXV is not closing completely,therefore there's “short-circuit”between high pressure side with lowpressure side of the circuit.Check for proper operation and fullclosing position of EEXV. Sight glassshould not show refrigerant flow afterthe valve is closed.
Check LED on the top of the valve, CLED should be solid green. If bothLED are blinking alternately the valvemotor is not properly connected.
Evaporating pressure sensor is notworking properly.Check for proper operation ofevaporating pressure sensor.
Compressor on circuit is internallydamaged with a mechanical problemfor example on internal check-valve,or on internal spirals or vanes.Check compressors on circuits.
ResetNotes
Local HMI
Network
Auto

5.4.4 Gas Leakage Sensor fault

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is On.Bell icon is moving on controller's display.String in the alarm list:Cx GasLeakSenString in the alarm log:± Cx GasLeakSenString in the alarm snapshotCx GasLeakSenSensor is broken.Check for sensor integrity.Check correct sensors operation according to information about mVolt (mV) range related to ppm values.
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for correct installation of the sensor.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.4.5 CxCmp1 MaintCode01

This alarm indicates that a component in the inverter may require verification or even a replacement.

SymptomCauseSolution
Circuit status is On.The compressor keeps operating as normal.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 MaintCode01String in the alarm log:± CxCmp1 MaintCode01String in the alarm snapshotCxCmp1 MaintCode01The inverter cooling valve in the inverter, may require a verification or a replacement.Contact your service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto☑☑☐

5.4.6 CxCmp1 MaintCode02

This alarm indicates that a component in the inverter may require verification or even a replacement.

SymptomCauseSolution
Circuit status is On.The compressor keeps operating as normal.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 MaintCode02String in the alarm log:± CxCmp1 MaintCode02String in the alarm snapshotCxCmp1 MaintCode02The capacitors in the inverter, may require a verification or a replacement.Contact your service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto☑☑☐

5.4.7 Power Loss

This alarm indicates that a short under voltage on main power supply, that does not turn off the unit, has occurred.

SymptomCauseSolution
Circuit status is On.The controller brings the compressor to the minimum speed and then normal operation is recovered (default 1200rmp)Bell icon is moving on controller's display.String in the alarm list:Cx PwrLossRunString in the alarm log:± Cx PwrLossRunString in the alarm snapshotCx PwrLossRunChiller main power supply had a down peak which caused the trip.Check if main power supply is within the acceptable tolerance for this chiller
ResetNotes
Local HMINetworkAuto☐☐☑

DAIKIN EWADH12TZSLC2 - Power Loss - 1

Resolution of this fault requires a direct intervention on the power supply of this unit. Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons. In case of doubts contact your maintenance company.

5.4.8 Liquid Temperature sensor fault

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is On.Bell icon is moving on controller's display.String in the alarm list:Cx LiquidTemperatureSenString in the alarm log:± Cx LiquidTemperatureSenString in the alarm snapshotCx LiquidTemperatureSenSensor is shorted.Check for sensor integrity.
Check correct sensors operation according to information about kOhm (kΩ) range related to temperature values.
Sensor is broken.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for correct installation of the sensor on refrigerant circuit pipe.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according with electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.4.9 Liquid Pressure sensor fault

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is Off.Bell icon is moving on controller's display.String in the alarm list:Cx LiquidPressureSenString in the alarm log:± Cx LiquidPressureSenString in the alarm snapshotCx LiquidPressureSenSensor is shorted.Check for sensor integrity.
Check correct sensors operation according to information about mV range related to temperature values.
Sensor is broken.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for correct installation of the sensor on refrigerant circuit pipe.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according with electrical scheme.
ResetNotes
Local HMI
Network
Auto

5.4.10 SpeedTrol Fan Communication Error

This event indicates a communication problem with the only vfd fan present in speedtrol configuration.

SymptomCauseSolution
Circuit status is On.Bell icon is moving on controller's display.String in the alarm list:Cx ST Fan Comm FailString in the alarm log:± Cx ST Fan Comm FailString in the alarm snapshotCx ST Fan Comm FailRS485 network is not properly cabled.Check the continuity of the RS485 network with the unit off. There should be continuity from the main controller to the last fan as indicated on the wiring diagram.
Modbus communication is not running properly.Check fans addresses. All the addresses must be different.
Fans are not poweredCheck if the fans are correctly powered.
ResetNotes
Local HMINetworkAuto☑☑☑The alarm clears automatically when the communication is re-established.

5.4.11 Cx Fans Communication Error

This event indicates a communication problem with some fans (but not all) of the circuit.

SymptomCauseSolution
Circuit status is On.Bell icon is moving on controller's display.String in the alarm list:Cx FanCommErrorString in the alarm log:± Cx FanCommErrorString in the alarm snapshotCx FanCommErrorRS485 network is not properly cabled.Check the continuity of the RS485 network with the unit off. There should be continuity from the main controller to the last fan as indicated on the wiring diagram.
Modbus communication is not running properly.Check fans addresses. All the addresses must be different.
Fans are not poweredCheck if the fans are correctly powered.
ResetNotes
Local HMINetworkAuto☑☑☑The alarm clears automatically when the communication is re-established.

5.4.12 Cx Fan Error

This alarm indicates that some fans (but not all) of the circuit have problems.

SymptomCauseSolution
Circuit status is On.The compressor keeps operating as normal.Bell icon is moving on controller's display.String in the alarm list:Cx Fan ErrorString in the alarm log:± Cx Fan ErrorString in the alarm snapshotCx Fan ErrorSome fans of the circuit has a problemTry to clear the error by turning the power off and on again after some minutes.
ResetNotes
Local HMI Network Auto☑☑☑A service engineer can check the alarm message error provided by each fan VFD.

5.4.13 Cx Fan Over V

This alarm indicates that some fans (but not all) of the circuit have over voltage problems.

SymptomCauseSolution
Circuit status is On.The compressor keeps operating as normal.Bell icon is moving on controller's display.String in the alarm list:Cx Fan OverVString in the alarm log:± Cx Fan OverVString in the alarm snapshotCx Cx Fan OverVSome fans of the circuit has a problemCheck if power supply is within the acceptable tolerance the fans
Check if the fans have had a problem of lost rotor during the start.
ResetNotes
Local HMINetworkAuto☑☑☑A service engineer can check the alarm message error provided by each fan VFD.

5.4.14 Cx Fan Under V

This alarm indicates that some fans (but not all) of the circuit have under voltage problems.

SymptomCauseSolution
Circuit status is On.The compressor keeps operating as normal.Bell icon is moving on controller's display.String in the alarm list:Cx Fan UndervString in the alarm log:± Cx Fan UndervString in the alarm snapshotCx Cx Fan UndervSome fans of the circuit has a problemCheck if power supply is within the acceptable tolerance the fans
Check the correct cabling of the fans
ResetNotes
Local HMINetworkAuto☑☑☑A service engineer can check the alarm message error provided by each fan VFD.

5.5 Circuit Pumpdown Stop Alarms

5.5.1 Discharge Temperature Sensor fault

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffDischTmpSenSensor is shorted.Check for sensor integrity.
Check correct sensors operation according to information about kOhm (kΩ) range related to temperature values.
Sensor is broken.Check if sensor is shorted with a resistance measurement.
String in the alarm log:± CxCmp1 OffDischTmpSenString in the alarm snapshotCxCmp1 OffDischTmpSenSensor is not properly connected(open).Check for correct installation of the sensor on refrigerant circuit pipe.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according with electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.5.2 Gas Leakage fault

This alarm indicates a gas leakage in the compressor box.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the shutdown procedure performing a deep pumpdown of the circuit.Bell icon is moving on controller's display.String in the alarm list:Cx OffGasLeakageString in the alarm log:± Cx OffGasLeakageString in the alarm snapshotCx OffGasLeakageGas leakage in the compressors box (A/C units).Switch off the unit and perform a gas leakage test.
Gas Leakage in the plant room.Check if there are leakage on the unit with a detector eventually starting suction fans to change the air in the room.
Gas leakage sensor fault.Put the sensor in open air and check that the alarm can be cleared. In case replace the sensor or disable the option before getting a new part.
ResetNotes
Local HMINetworkAuto☑☑☐

5.5.3 High Compressor Vfd Temperature fault

This alarm is generated to indicate that the Vfd temperature is too high to allow the compressor to run.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 VfdOverTempString in the alarm log:± CxCmp1 VfdOverTempString in the alarm snapshotCxCmp1 VfdOverTempCooling solenoid valve is not operating properly.Check electrical connection of the solenoid valve.
Check refrigerant charge. Low refrigerant charge can cause overheating of the Vfd electronic.
Check for obstructions in the pipe.
Vfd Heater not properly connected.Check if Vfd heater is switched off when the Vfd temperature increases.
Check if the contactor that commands the Vfd heater can switch properly.
ResetNotes
Local HMINetworkAuto☑☑☐

5.5.4 Low Compressor Vfd Temperature fault

This alarm is generated to indicate that the Vfd temperature is too low to allow the compressor to run safely.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 vfdLowTempString in the alarm log:Cooling solenoid valve is not operating properly. It's always open when compressor runs.Check electrical connection of the solenoid valve.
Check operation of the valve to see if it can close properly.
Check operating cycles of the valve. It has a limited number of cycles.
± CxCmp1 VfdLowTempString in the alarm snapshotCxCmp1 VfdLowTempVfd heater is not working.Check if the Vfd heater is powered.
Check if the Vfd heater is commanded on when Vfd temperature is low.
ResetNotes
Local HMINetworkAuto☑☒☐

5.5.5 Low Discharge Superheat fault

This alarm indicates that the unit has worked for too long with low discharge super heat.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffDishSHLoString in the alarm log:± CxCmp1 OffDishSHLoString in the alarm snapshotCxCmp1 OffDishSHLoEEXV is not working correctly.It's not opening enough or it's moving in the opposite direction.Check if pump-down can be finished for pressure limit reached;
Check expansion valve movements.
Check connection to the valve driver on the wiring diagram.
Measure the resistance of each winding, it must be different from 0 Ohm.
ResetNotes
Local HMINetworkAuto☑☑☑

5.5.6 Oil Pressure Sensor fault

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 offoilFeedPSenString in the alarm log:± CxCmp1 offoilFeedPSenString in the alarm snapshotCxCmp1 offoilFeedPSenSensor is broken.Check for sensor integrity.Check correct sensors operation according to information about mVolt (mV) range related to pressure values in kPa.
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for correct installation of the sensor on refrigerant circuit pipe. The transducer must be able to sense the pressure through the valve's needle.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.5.7 Antichatteting alarm

This alarm is generated to indicate a fail during the antichattering procedure.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:CxOff AntiChatteringAlmString in the alarm log:± CxOff AntiChatteringString in the alarm snapshotCxOff AntiChatteringThe procedure of antichattering fail.Antichattering can't equalized the pressure between economizer and suction line in a 10 minutes.Check for solenoid valves (suction and discharge) integrity.
ResetNotes
Local HMI
Network
Auto

5.5.8 Suction Temperature Sensor fault

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffSuctTempSenString in the alarm log:± CxCmp1 OffSuctTempSenString in the alarm snapshotCxCmp1 OffSuctTempSenSensor is shorted.Check for sensor integrity.
Check correct sensors operation according to information about kOhm (kΩ) range related to temperature values.
Sensor is broken.Check if sensor is shorted with a resistance measurement.
Sensor is not good connected (open).Check for correct installation of the sensor on refrigerant circuit pipe.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according with electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.6 Circuit Rapid Stop Alarms

5.6.1 Compressor VFD Fault

This alarm indicates an abnormal condition that forced the inverter to stop.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore, circuit is immediately stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffVfdFaultString in the alarm log:± CxCmp1 OffVfdFaultString in the alarm snapshotCxCmp1 OffVfdFaultInverter is operating in an unsafe condition and for this reason the inverter must be stopped.Check the alarm snapshot to identify the alarm code from the inverter.Contact your service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.2 Compressor VFD OverTemp

This alarm indicates that the Inverter temperature has exceeded a safety limit and the inverter has to be stopped in order to avoid damages to components. This alarm is related mainly to operation outside the operating envelope of the VFD.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 0ffVfdOverTempString in the alarm log:Insufficient motor coolingCheck refrigerant charge.
Check if operational envelope of the unit is respected.
Check operation of the cooling solenoid valve
± CxCmp1 offvfdoverTempString in the alarm snapshotCxCmp1 offvfdoverTemp
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.3 Compressor VFD Temperature high

This alarm indicates that the Inverter temperature has exceeded a safety limit and the inverter has to be stopped in order to avoid damages to components.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffVfdTempHiString in the alarm log:± CxCmp1 OffVfdTempHiString in the alarm snapshotCxCmp1 OffVfdTempHiInsufficient motor coolingCheck refrigerant charge.
Check if operational envelope of the unit is respected.
Check operation of the cooling solenoid valve
Motor temperature sensor could not operate properly.Check the readings of the motor temperature sensor and check the Ohmic value. A correct reading should be around hundreds of Ohm at ambient temperature.
Check the electrical connection of the sensor with the electronic board.
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.4 Compressor VFD A3 alarm

This alarm indicates that the Inverter tripped for a critical alarm

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:Cx OffA3VfdFaultString in the alarm log:± Cx OffA3VfdFaultString in the alarm snapshotCx OffA3VfdFaultA3 AlarmContact your Daikin Service reference
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.5 Condensing Pressure sensor fault

This alarm indicates that the condensing pressure transducer is not operating properly.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffCndPressSenString in the alarm log:± CxCmp1 OffCndPressSenString in the alarm snapshotCxCmp1 OffCndPressSenSensor is broken.Check for sensor integrity.Check correct sensors operation according to information about mVolt (mV) range related to pressure values in kPa.
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for correct installation of the sensor on refrigerant circuit pipe. The transducer must be able to sense the pressure through the valve's needle.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMI
Network
Auto

5.6.6 Evaporating Pressure sensor fault

This alarm indicates that the evaporating pressure transducer is not operating properly.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 EvapPressSenString in the alarm log:± CxCmp1 EvapPressSenString in the alarm snapshotCxCmp1 EvapPressSenSensor is broken.Check for sensor integrity.Check correct sensors operation according to information about mVolt (mV) range related to pressure values in kPa.
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for correct installation of the sensor on refrigerant circuit pipe. The transducer must be able to sense the pressure through the valve's needle.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according to electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.7 EXV Driver Error (A/C units only)

This alarm indicates an abnormal condition of the EXV Driver.

SymptomCauseSolution
Circuit status is Off.Circuit is immediately stopped.Bell icon is moving on controller's display.String in the alarm list:Cx OffEXVDrvErrorString in the alarm log:± Cx OffEXVDrvErrorString in the alarm snapshotCx OffEXVDrvErrorHardware ErrorContact your service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.8 Fail Start Low Pressure

This alarm indicates that at the compressor start the evaporating pressure or condensing pressure is below a minimum fixed limit at compressor start.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:Cx OffStartFailEvpPrLoString in the alarm log:± Cx OffStartFailEvpPrLoAmbient temperature is too low (A/C units)Check the operating envelope for this machine.
Circuit refrigerant charge is too lowCheck refrigerant charge.
Check for gas leakage with a sniffer.
String in the alarm snapshotCx OffStartFailEvpPrLo
ResetNotes
Local HMI
Network
Auto

5.6.9 Fan VFD Over Current

This alarm indicates that the Inverter current has exceeded a safety limit and the inverter must be stopped to avoid damages to components.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 offVfdoverCurrString in the alarm log:± CxCmp1 offVfdoverCurrString in the alarm snapshotCxCmp1 offVfdoverCurrThe ambient temperature is too high.Check the unit selection to see if the unit can operate at full load.
Check if all fans are operating properly and can keep the condensing pressure at the proper level.
Clean condenser coils to allow a lower condensing pressure.
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.10 High Discharge Temperature Alarm

This alarm indicates that the temperature at the discharge port of the compressor exceeded a maximum limit which may cause damages to the mechanical parts of the compressor.

DAIKIN EWADH12TZSLC2 - High Discharge Temperature Alarm - 1

When this alarm occurs compressor's crankcase and discharge pipes may become very hot. Be careful when getting in contact with the compressor and discharge pipes in this condition.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore or even unload, circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffDischTmpHiString in the alarm log:± CxCmp1 OffDischTmpHiString in the alarm snapshotCxCmp1 OffDischTmpHiLiquid Injection solenoid valve is not operating properly.Check the electrical connection between the controller and the liquid injection solenoid valve.
Check if the solenoid coil operates properly
Check if the digital output operates correctly.
Liquid injection orifice is small.Check if when the liquid injection solenoid is activated the temperature can be controlled between the limits.
Check that the liquid injection line is not obstructed by observing the discharge temperature when it is activated.
Discharge temperature sensor could not operate properly.Check for proper operation of the discharge temperature
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.11 High Motor Current Alarm

This alarm indicates that the compressor absorbed current is exceeding a predefined limit.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore or even unload, circuit is stopped.Bell icon is moving on controller's display.The ambient temperature is too high (A/C units)Check the unit selection to see if the unit can operate at full load.
Check if all fans are operating properly and are able to keep the condensing pressure at the proper level (A/C units).
String in the alarm list:CxCmp1 OffMtrAmpsHiString in the alarm log:± CxCmp1 OffMtrAmpsHiString in the alarm snapshotCxCmp1 OffMtrAmpsHiClean condenser coils to allow a lower condensing pressure (A/C units).
The wrong compressor model has been selected.Check the compressor model for this unit.
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.12 High Motor Temperature Alarm

This alarm indicates that the motor temperature has exceeded the maximum temperature limit for safe operations.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore or even unload, circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffMotorTempHiString in the alarm log:± CxCmp1 OffMotorTempHiString in the alarm snapshotCxCmp1 OffMotorTempHiInsufficient motor cooling.Check refrigerant charge.
Check if operational envelope of the unit is respected.
Motor temperature sensor could not operate properly.Check the readings of the motor temperature sensor and check the Ohmic value. A correct reading should be around hundreds of Ohm at ambient temperature.
Check the electrical connection of the sensor with the electronic board.
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.13 High Oil Pressure Differential Alarm

This alarm indicates that the oil filter is clogged and needs to be replaced.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffOilPrDiffHiString in the alarm log:± CxCmp1 OffOilPrDiffHiString in the alarm snapshotCxCmp1 OffOilPrDiffHiOil filter is clogged.Replace oil filter.
Oil Pressure Transducer is reading incorrectly.Check Oil Pressure Transducer readings with a gauge.
Condensing Pressure Transducer is reading incorrectly.Check Condensing Pressure Transducer readings with a gauge.
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.14 High Pressure alarm

This alarm is generated in case the Condensing saturated temperature rise above the Maximum condensing saturated temperature and the control is not able to compensate to this condition. The maximum condenser saturated temperature is 68.5^ C but it can decrease when the evaporator saturated temperature become negative.

In case of water-cooled chillers operating at high condenser water temperature, if the Condensing saturated temperature exceeds the Maximum condenser saturated temperature, the circuit is only switched off without any notification on the screen as this condition is considered acceptable in this range of operation.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore or even unload, circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffCndPressHiOne or more condenser fans do not operate properly (A/C units).Check if fans protections have been activated.
Check that the fans can turn freely.
Check that there is not any obstacle to the free ejection of the air blown.
Dirty or partially blocked condenser coil (A/C units).Remove any obstacle;Clean the condenser coil using soft brush and blower.
String in the alarm log:± CxCmp1 OffCndPressHiString in the alarm snapshotCxCmp1 OffCndPressHiInlet air temperature of the condenser is too high (A/C units).The air temperature measured at the inlet of the condenser may not exceed the limit indicated in the operational range (working envelope) of the chiller.
Check the location where the unit is installed and check that there are no short circuit of the hot-air blown from the fans of the same unit, or even from fans of next chillers (Check IOM for proper installation).
One or more condenser fan turning in wrong direction (A/C units).Check for correct phases sequence (L1, L2, L3) in the electrical connection of the fans.
Excessive charge of refrigerant into the unit.Check liquid sub-cooling and suction super-heat to control indirectly the correct charge of refrigerant.If necessary, recover all the refrigerant to weight the entire charge and to control if the value is in line with kg indication on unit label.
Condensing pressure transducer could not operate properly.Check for proper operation of the high-pressure sensor.
ResetNotes
Local HMI
Network
Auto

5.6.15 Low Pressure alarm

This alarm is generated in case the evaporating pressure drops below the Low Pressure Unload and the control is not able to compensate to this condition.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore or even unload, circuit is stopped immediately.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffEvpPressLoString in the alarm log:± CxCmp1 OffEvpPressLoString in the alarm snapshotCxCmp1 OffEvpPressLoTransitory condition like a fan staging (A/C units).Wait until the condition is recovered by EXV control
Refrigerant charge is low.Check sight glass on liquid line to see if there is flash gas.
Measure sub-cooling to see if the charge is correct.
Protection limits not set to fit customer application.Check the evaporator approach and the corresponding water temperature to evaluate the low pressure hold limit.
High Evaporator Approach.Clean the evaporator
Check the quality of the fluid that flows into heat exchanger.
Check the glycol percentage and type (ethilenic or propilenic)
Water flow into water heat exchanger is too low.Increase the water flow.
Check that evaporator water pump is operating correctly providing the required water flow.
Evaporating pressure transducer is not working properly.Check the sensor for proper operation and calibrate the readings with a gauge.
EEXV is not working correctly.It's not opening enough or it's moving in the opposite direction.Check if pump-down can be finished for pressure limit reached;
Check expansion valve movements.
Check connection to the valve driver on the wiring diagram.
Measure the resistance of each winding, it has to be different from 0 Ohm.
Water temperature is lowIncrease inlet water temperature.Check the low-pressure safeties settings.
ResetA/C unitsNotes
Local HMINetworkAuto☑☒☐

5.6.16 Low Pressure Ratio Alarm

This alarm indicates that the ratio between evaporating and condensing pressure is below a limit which depends on compressor speed and guarantees the proper lubrication to compressor.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffPrRatioLoString in the alarm log:± CxCmp1 OffPrRatioLoString in the alarm snapshotCxCmp1 OffPrRatioLoCompressor is not able to develop the minimum compression.Check fan setpoint and settings, it could be too low (A/C units).
Check compressor absorbed current and discharge superheat.Compressor can be damaged.
Check the correct operation of suction / delivery pressure sensors.
Check the internal relief valve didn't open during previous operation(check the unit history).Note:If the difference between delivery and suction pressure exceeds 22bar, the internal relief valve open and need to be replaced.
Inspect the gate rotors / screw rotor for possible damages.
Check if the cooling tower or three-way valves are operating correctly and properly set.
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.17 Maximum Number of Restart Alarm

This alarm indicates that for three consecutive times after the compressor start the evaporating pressure is under a minimum limit for too much time

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:Cx OffNbrRestartsString in the alarm log:± Cx OffNbrRestartsString in the alarm snapshotCx OffNbrRestartsAmbient temperature is too lowCheck the operating envelope for this machine.
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.18 Mechanical High Pressure Alarm

This alarm is generated when the condenser pressure rises above the mechanical high pressure limit causing this device to open the power supply to all the auxiliary relays. This causes an immediate shutdown of compressor and all the other actuators in this circuit.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore or even unload, circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffMechPressHiOne or more condenser fans do not operate properly (A/C units).Check if fans protections have been activated.
Check that the fans can turn freely.
Check that there is not any obstacle to the free ejection of the air blown.
Dirty or partially blocked condenser coil (A/C units).Remove any obstacle.Clean the condenser coil using soft brush and blower.
String in the alarm log:± CxCmp1 OffMechPressHiString in the alarm snapshotCxCmp1 OffMechPressHiInlet air temperature of the condenser is too high (A/C units).The air temperature measured at the inlet of the condenser may not exceed the limit indicated in the operational range (working envelope) of the chiller (A/C units).
Check the location where the unit is installed and check that there are no short circuit of the hot-air blown from the fans of the same unit, or even from fans of next chillers (Check IOM for proper installation).
One or more condenser fan turning in wrong direction.Check for correct phases sequence (L1, L2, L3) in the electrical connection of the fans.
Mechanical high-pressure switch is damaged or not calibrated.Check for proper operation of the high-pressure switch.
ResetNotes
Local HMINetworkAuto☑☒☐Reset of this alarm requires a manual action on the high-pressure switch.

5.6.19 No Pressure At Start Alarm

This alarm is used to indicate a condition where the pressure at the evaporator or at the condenser is lower than 35kPa, so the circuit is potentially empty of refrigerant.

SymptomCauseSolution
Circuit status is Off.The compressor does not start.Bell icon is moving on controller's display.String in the alarm list:Cx OffNoPressAtStartString in the alarm log:± Cx OffNoPressAtStartString in the alarm snapshotCx OffNoPressAtStartEvaporator or condenser pressure are below 35kPaCheck transducers calibration with an appropriate gauge.
Check transducers cabling and readout.
Check refrigerant charge and set it to the proper value.
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.20 No Pressure Change At Start Alarm

This alarm indicates that the compressor is not able to start or to create a certain minimum variation of the evaporating or condensing pressures after start.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:Cx OffNoPressChgStartString in the alarm log:± Cx OffNoPressChgStartString in the alarm snapshotCx OffNoPressChgStartCompressor cannot startCheck if the start signal is properly connected to the inverter.
Compressor is turning in wrong direction.Check correct phases sequence to the compressor (L1, L2, L3) according to the electrical scheme.
Inverter is not properly programmed with the right direction of rotation
Refrigerant circuit is empty of refrigerant.Check circuit pressure and presence of refrigerant.
Not proper operation of evaporating or condensing pressure transducers.Check proper operation of evaporating or condensing pressure transducers.
ResetNotes
Local HMINetworkAuto☑☑☐

5.6.21 Overvoltage Alarm on input voltage

This alarm indicates that chiller supply voltage exceeded the maximum limit which allows proper operations of the components. This is estimated looking at the DC voltage on the inverter which depends of course from the main power.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:Cx offovervoltage-ACString in the alarm log:± Cx offovervoltage-ACString in the alarm snapshotCx offovervoltage-ACChiller main power supply had an up peak which caused the trip.Check if main power supply is within the acceptable tolerance for this chiller
Main power supply setting on the Microtech is not suitable with the power supply in use (A/C units).Measure the power supply to the chiller and select the proper value on the Microtech HMI.
ResetNotes
Local HMINetworkAuto✕✕✕✕✕The alarm clears automatically when the voltage is reduced to an acceptable limit.

5.6.22 Overvoltage Alarm on DC rectified voltage

This alarm indicates that chiller supply voltage exceeded the maximum limit which allows proper operations of the components. This is estimated looking at the DC voltage on the inverter which depends on course on the main power.

DAIKIN EWADH12TZSLC2 - Overvoltage Alarm on DC rectified voltage - 1

Resolution of this fault requires a direct intervention on the power supply of this unit. Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons. In case of doubts contact your maintenance company.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:Cx offovervoltage-DCString in the alarm log:± Cx offovervoltage-DCString in the alarm snapshotCx offovervoltage-DCChiller main power supply had an up peak which caused the trip.Check if main power supply is within the acceptable tolerance for this chiller
Main power supply setting on the Microtech is not suitable with the power supply in use (A/C units).Measure the power supply to the chiller and select the proper value on the Microtech HMI.
ResetNotes
Local HMINetworkAuto✕✕✕✕The alarm clears automatically when the voltage is reduced to an acceptable limit.

5.6.23 Undervoltage Alarm on input voltage

This alarm indicates that chiller supply voltage exceeded the minimum limit which allows proper operations of the components.

DAIKIN EWADH12TZSLC2 - Undervoltage Alarm on input voltage - 1

Resolution of this fault requires a direct intervention on the power supply of this unit. Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons. In case of doubts contact your maintenance company.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:Cx OffUnderVoltage-ACString in the alarm log:± Cx OffUnderVoltage-ACString in the alarm snapshotCx OffUnderVoltage-ACChiller main power supply had a down peak which caused the trip.Check if main power supply is within the acceptable tolerance for this chiller
Main power supply setting on the Microtech is not suitable with the power supply in use (A/C units).Measure the power supply to the chiller and select the proper value on the Microtech HMI.
ResetNotes
Local HMINetworkAuto✕✕✕✕The alarm clears automatically when the voltage is increased to an acceptable limit.

5.6.24 Undervoltage Alarm on DC rectified voltage

This alarm indicates that chiller supply voltage exceeded the minimum limit which allows proper operations of the components.

DAIKIN EWADH12TZSLC2 - Undervoltage Alarm on DC rectified voltage - 1

Resolution of this fault requires a direct intervention on the power supply of this unit. Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons. In case of doubts contact your maintenance company.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:Cx Offundervoltage-DCString in the alarm log:± Cx Offundervoltage-DCString in the alarm snapshotCx Offundervoltage-DCChiller main power supply had a down peak which caused the trip.Check if main power supply is within the acceptable tolerance for this chiller
Main power supply setting on the Microtech is not suitable with the power supply in use (A/C units).Measure the power supply to the chiller and select the proper value on the Microtech HMI.
ResetNotes
Local HMINetworkAuto✕✕✕✕The alarm clears automatically when the voltage is increased to an acceptable limit.

5.6.25 VFD Communication Failure

This alarm indicates a communication problem with the inverter of the compressor.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore, circuit is immediately stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 offVfdCommFailString in the alarm log:± CxCmp1 offVfdCommFailString in the alarm snapshotCxCmp1 offVfdCommFailRS485 network is not properly cabled.Check the continuity of the RS485 network with the unit off. There should be continuity from the main controller to the last inverter as indicated on the wiring diagram.
Modbus communication is not running properly.Check inverter addresses and addresses of all the additional devices in the RS485 network (for example the energy meter). All the addresses must be different.
Modbus interface card can be faultyCheck with your service organization to evaluate this possibility and eventually replace the board.
ResetNotes
Local HMINetworkAuto☑☑☑The alarm clears automatically when the communication is re-established.

5.6.26 Fans Modbus Communication Failure

This alarm indicates a communication problem with all fans of the circuit.

SymptomCauseSolution
Circuit status is Off.The fans do not start, circuit is immediately stopped.Bell icon is moving on controller's display.String in the alarm list:Cx FanCommFailString in the alarm log:± Cx FanCommFailString in the alarm snapshotCx FanCommFailRS485 network is not properly cabled.Check the continuity of the RS485 network with the unit off. There should be continuity from the main controller to the last fan as indicated on the wiring diagram.
Modbus communication is not running properly.Check fans addresses. All the addresses must be different.
Fans are not poweredCheck if the fans are correctly powered.
ResetNotes
Local HMINetworkAuto☑☑☑The alarm clears automatically when the communication is re-established.

5.6.27 Fan Fault

This alarm indicates that every fan of the circuit has a problem.

SymptomCauseSolution
Circuit status is On.The compressor keeps operating as normal.Bell icon is moving on controller's display.String in the alarm list:Cx FanAlmString in the alarm log:± Cx FanAlmString in the alarm snapshotCx FanAlmEvery fan of the circuit has a problemTry to clear the error by turning the power off and on again after some minutes.
ResetNotes
Local HMINetworkAuto☑☑☑A service engineer can check the alarm message error provided by each fan VFD.

The present publication is drawn up by of information only and does not constitute an offer binding upon Daikin Applied Europe S.p.A. Daikin Applied Europe S.p.A. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability, or fitness for particular purpose of its content, and the products and services presented therein. Specification is subject to change without prior notice. Refer to the data communicated at the time of the order. Daikin Applied Europe S.p.A. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Applied Europe S.p.A.

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : DAIKIN

Model : EWADH12TZSLC2

Category : Air-conditioner