DAIKIN

EWAD820TZSRB2 - Air-conditioner DAIKIN - Free user manual and instructions

Find the device manual for free EWAD820TZSRB2 DAIKIN in PDF.

📄 85 pages English EN Download 💬 AI Question
Notice DAIKIN EWAD820TZSRB2 - page 7
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about EWAD820TZSRB2 DAIKIN

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Air-conditioner in PDF format for free! Find your manual EWAD820TZSRB2 - DAIKIN and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. EWAD820TZSRB2 by DAIKIN.

USER MANUAL EWAD820TZSRB2 DAIKIN

Air and Water cooled inverter chillers and heat pump

D-EOMZC00106-17EN

Air cooled:

  • EWAD TZ
  • EWAD TZ-B

Water cooled:

  • EWWD VZ
  • EWWH VZ

TABLE OF CONTENTS

1 SAFETY CONSIDERATIONS....7

1.1 General 7
1.2 Avoid electrocution....7
1.3 Safety Devices 7

1.3.1 General safety devices 7
1.3.2 Circuit safety devices....8
1.3.3 Component safety devices 8

1.4 Available sensors....9

1.4.1 Pressure transducers....9
1.4.2 Temperature sensors....9
1.4.3 Thermistors....9
1.4.4 Leak detectors 9

1.5 Available Controls 10

1.5.1 Evaporator pumps 10
1.5.2 Condenser pumps (W/C units only) 10
1.5.3 Compressors 10
1.5.4 Expansion Valve....10
1.5.5 Switchbox Pressurization fan for HFO units (W/C only).... 10

1.6 Customer Terminal Block Connections 10

1.6.1 Evaporator Flow Switch....11
1.6.2 Condenser Flow Switch (W/C units only).... 11
1.6.3 Double setpoint....11
1.6.4 Current limit (optional) 11
1.6.5 External Fault....11
1.6.6 Rapid Restart (optional)....11
1.6.7 Remote On-Off 11
1.6.8 General Alarm.... 11
1.6.9 Compressor Status.... 11
1.6.10 Circuit Alarm (optional) 11
1.6.11 Evaporator Pump Start 12
1.6.12 Condenser Pump Start (W/C units only)....12
1.6.13 Demand limit.... 12
1.6.14 Setpoint override....12
1.6.15 Pump VFD Signal (A/C units only)....12

2 GENERAL DESCRIPTION 13

2.1 Basic Information.... 13
2.2 Abbreviations used 13
2.3 Controller Operating Limits 13
2.4 Controller Architecture 14
2.5 Communication Modules 14

3 USING THE CONTROLLER.... 15

3.1 General Recommendation.... 15
3.2 Navigating 15
3.3 Passwords 16
3.4 Editing 16

3.5 Basic Control System Diagnostic.... 17
3.6 Controller maintenance.... 18
3.7 Optional Remote User Interface 18
3.8 Embedded Web Interface 19

4 MENU STRUCTURE....21

4.1 Main Menu 21
4.2 View/Set Unit 21

4.2.1 Thermostat Ctrl....21
4.2.2 Network Ctrl 22
4.2.3 Compressor Vfd Setup (A/C Units only) 22
4.2.4 Pumps 22
4.2.5 Condenser (W/C units only) 23
4.2.6 Press Fan (W/C units only) 23
4.2.7 Master/Slave 23

4.2.7.1 Data....24
4.2.7.2 Options....24
4.2.7.3 Thermostat Ctrl 25
4.2.7.4 Timers 25
4.2.7.5 Standby Chiller 25

4.2.8 Rapid Restart....25

4.2.9 Date/Time 25
4.2.10 Scheduler 26
4.2.11 Power Conservation 26
4.2.12 Controller IP setup....27
4.2.13 Daikin on Site....27
4.2.14 Menu Password 27

4.3 View/Set Circuit....28

4.3.1 Data 28
4.3.2 Compressor 29
4.3.3 Condenser (A/C only) 29
4.3.4 EXV 30
4.3.5 Economizer (A/C only) 30
4.3.6 Settings (A/C units only) 30
4.3.7 Variable VR....30

4.4 Active Setpoint 30
4.5 Evaporator LWT 31
4.6 Condenser LWT (W/C Units only) 31
4.7 Unit Capacity.... 31
4.8 Unit Mode 31
4.9 Unit Enable (A/C Units only) 32
4.10 Timers 32
4.11 Alarms....32
4.12 Commission Unit 32

4.12.1 Alarm Limits 32
4.12.2 Calibrate Sensors....33

4.12.2.1 Unit Calibrate Sensors 33

4.12.2.2 Circuit Calibrate Sensors....34

4.12.3 Manual Control 34

4.12.3.1 Unit 34

4.12.3.2 Circuit #1 (Circuit #2 if present) 35
4.12.4 Scheduled Maintenance 36

4.13 About this Chiller 36

5 WORKING WITH THIS UNIT 37

5.1 Unit Setup 37

5.1.1 Control Source 37
5.1.2 Available Mode Setting 37
5.1.3 Temperature Settings 38

5.1.3.1 LWT Setpoint Setting 38

5.1.3.2 Thermostat Control Settings.... 39

5.1.4 Alarm Settings 40
5.1.4.1 Pumps....40
5.1.5 Power Conservation 40

5.1.5.2 Current Limit (Optional) 41
5.1.5.3 Setpoint Reset....41
5.1.5.4 Setpoint Reset by OAT Reset (A/C units only) 41
5.1.5.5 Setpoint Reset by External 4-20 mA Signal 42
5.1.5.6 Setpoint Reset by Evaporator Return Temperature 42
5.1.5.7 Soft Load....43

5.1.6 Date/Time 43

5.1.6.1 Date, Time and UTC Settings 43
5.1.6.2 Quiet Mode Scheduling (A/C units only).... 43

5.1.7 Scheduler 44

5.2 Unit/Circuit Start-up....44

5.2.1 Unit Status....44
5.2.2 Prepare the unit to start 44

5.2.2.1 Unit Switch Enable (A/C units only) 44
5.2.2.2 Unit Switch Enable (W/C units only) 45
5.2.2.3 Keypad Enable 45
5.2.2.1 BMS Enable 45

5.2.3 Unit Start sequence 45
5.2.4 Circuit Status 46
5.2.5 Circuits start sequence 47
5.2.6 High Water Temperature Limit (A/C units only) 48
5.2.7 Low Evaporating Pressure....48
5.2.8 High Condensing Pressure 49
5.2.9 High Vfd Current....49
5.2.10 High Discharge Temperature....49

5.3 Condensation Control (A/C units only) 50

5.3.1 Fan Settings (A/C units only) 50
5.3.1.1 Fan VFD Settings....50

5.4 Condensation Control (W/C units only) 51

5 EXV Control 52
6 Economizer Control (A/C units only)....52
7 Liquid Injection Control 53
8 Variable Volume Ratio Control 53

6 ALARMS AND TROUBLESHOOTING....54

6.1 Unit Alerts 54

6.1.1 Bad Current Limit Input....54

6.1.2 Bad Demand Limit Input 54
6.1.3 Bad Leaving Water Temperature Reset Input....55
6.1.4 Condenser Pump #1 Failure (W/C units only)....55
6.1.5 Condenser Pump #2 Failure (W/C units only)....55
6.1.6 Energy Meter Communication Fail....56
6.1.7 Evaporator Pump #1 Failure 56
6.1.8 Evaporator Pump #2 Failure 56
6.1.9 External Event 57
6.1.10 Fan Alarm Module Communication Fail (A/C units only) 57
6.1.11 Heat Recovery Entering Water Temperature sensor fault (A/C units only) 57
6.1.12 Heat Recovery Leaving Water Temperature sensor fault (A/C units only)....58
6.1.13 Heat Recovery Water Temperatures inverted (A/C units only) 58
6.1.14 Rapid Recovery Module Communication Fail....58
6.1.15 Switch Box Temperature sensor fault (A/C units only)....59

6.2 Unit Pumpdown Stop Alarms 59

6.2.1 Condenser Entering Water Temperature (EWT) sensor fault....59
6.2.2 Condenser Leaving Water Temperature (LWT) sensor fault 59
6.2.3 Evaporator Entering Water Temperature (EWT) sensor fault 60
6.2.4 Evaporator Water Temperatures inverted....60
6.2.5 Outside Air Temperature (OAT) Lockout (A/C units only) 60
6.2.6 Outside Air Temperature sensor fault alarm (A/C units only)....61

6.3 Unit Rapid Stop Alarms.... 61

6.3.1 Condenser Water Freeze alarm (W/C units only) 61
6.3.2 Condenser Water Flow Loss alarm (W/C units only) 62
6.3.3 Emergency Stop 62
6.3.4 Evaporator Flow Loss alarm 62
6.3.5 Evaporator Leaving Water Temperature (LWT) sensor fault 63
6.3.6 Evaporator Water Freeze alarm....63
6.3.7 External alarm....63
6.3.8 Gas Leakage Alarm (W/C units only)....64
6.3.9 Heat Recovery Water Freeze Protect alarm (A/C units only)....64
6.3.10 OptionCtrlrCommFail (A/C units only)....64
6.3.11 Power Fault (only for A/C units with the UPS option)....64
6.3.12 PVM alarm (A/C units only)....65

6.4 Circuit Alerts....66

6.4.1 Economizer Pressure Sensor fault (A/C units only) 66
6.4.2 Economizer Temperature Sensor fault (A/C units only) 66
6.4.3 Failed Pumpdown....66
6.4.4 Fan Fault (A/C units only) 67
6.4.5 Gas Leakage Sensor fault (A/C units only) 67
6.4.6 CxCmp1 MaintCode01 (A/C units only) 67
6.4.7 CxCmp1 MaintCode02 (A/C units only) 68
6.4.8 Power Loss (A/C units only)....68

6.5 Circuit Pumpdown Stop Alarms 69

6.5.1 Discharge Temperature Sensor fault 69
6.5.2 Gas Leakage fault (A/C units only) 69
6.5.3 High Compressor Vfd Temperature fault (A/C units only)....69
6.5.4 Liquid Temperature Sensor fault (W/C units only) 70
6.5.5 Low Compressor Vfd Temperature fault (A/C units only)....70

6.5.6 Low Oil Level fault (W/C units only)....70
6.5.7 Low Discharge Superheat fault....71
6.5.8 Oil Pressure Sensor fault....71
6.5.9 Suction Temperature Sensor fault 71

6.6 Circuit Rapid Stop Alarms....72

6.6.1 Compressor Extension Communication Error (W/C units only) 72
6.6.2 EXV Driver Extension Communication Error (W/C units only) 72
6.6.3 Compressor VFD Fault 72
6.6.4 Compressor VFD OverTemp (A/C units only)....73
6.6.5 Condensing Pressure sensor fault....73
6.6.6 Economizer EXV Driver Error (A/C unit only)....73
6.6.7 Economizer EXV Motor Not Connected (A/C unit only) 74
6.6.8 Evaporating Pressure sensor fault....74
6.6.9 EXV Driver Error (A/C units only)....75
6.6.10 EXV Motor Not Connected (TZ B units only) 75
6.6.11 Fail Start Low Pressure 75
6.6.12 Fan VFD Over Current (A/C units only) 76
6.6.13 High Discharge Temperature Alarm 76
6.6.14 High Motor Current Alarm....76
6.6.15 High Motor Temperature Alarm 77
6.6.16 High Oil Pressure Differential Alarm 77
6.6.17 High Pressure alarm....77
6.6.18 Low Pressure alarm....78
6.6.19 Low Pressure Ratio Alarm....79
6.6.20 Maximum Number of Restart Alarm (A/C units only) 79
6.6.21 Mechanical High Pressure Alarm....80
6.6.22 Mechanical Low Pressure Alarm (W/C units only) 80
6.6.23 No Pressure At Start Alarm 81
6.6.24 No Pressure Change At Start Alarm 81
6.6.25 Overvoltage Alarm 81
6.6.26 Undervoltage Alarm 82
6.6.27 VFD Communication Failure....82

7 OPTIONS....83

7.1 Total Heat Recovery (Optional - A/C units only) 83
7.2 Energy Meter including Current Limit (Optional) 83
7.3 Rapid Restart (Optional) 84
7.4 Inverter Pump Kit (Optional) 84

1 SAFETY CONSIDERATIONS

1.1 General

Installation, start-up and servicing of equipment can be hazardous if certain factors particular to the installation are not considered: operating pressures, presence of electrical components and voltages and the installation site (elevated plinths and built-up up structures). Only properly qualified installation engineers and highly qualified installers and technicians, fully trained for the product, are authorized to install and start-up the equipment safely.

During all servicing operations, all instructions and recommendations, which appear in the installation and service instructions for the product, as well as on tags and labels fixed to the equipment and components and accompanying parts supplied separately, must be read, understood and followed.

Apply all standard safety codes and practices.

Wear safety glasses and gloves.

Use the proper tools to move heavy objects. Move units carefully and set them down gently.

1.2 Avoid electrocution

Only personnel qualified in accordance with IEC (International Electrotechnical Commission) recommendations may be permitted access to electrical components. It is particularly recommended that all sources of electricity to the unit be shut off before any work is begun. Shut off main power supply at the main circuit breaker or isolator.

IMPORTANT: This equipment uses and emits electromagnetic signals. Tests have shown that the equipment conforms to all applicable codes with respect to electromagnetic compatibility.

DAIKIN EWAD820TZSRB2 - Avoid electrocution - 1

RISK OF ELECTROCUTION: Even when the main circuit breaker or isolator is switched off, certain circuits may still be energized, since they may be connected to a separate power source.

DAIKIN EWAD820TZSRB2 - Avoid electrocution - 2

RISK OF BURNS: Electrical currents cause components to get hot either temporarily or permanently. Handle power cable, electrical cables and conduits, terminal box covers and motor frames with great care.

DAIKIN EWAD820TZSRB2 - Avoid electrocution - 3

ATTENTION: In accordance with the operating conditions the fans can be cleaned periodically. A fan can start at any time, even if the unit has been shut down.

1.3 Safety Devices

Each unit is equipped with safety devices of three different kinds:

1.3.1 General safety devices

Safeties of this level of severity will shut down all the circuits and stop the entire unit. When a general safety device will occur a manual intervention on the unit will be required in order to re-establish the normal operability of the machine. There are exceptions to this general rule in case of alarms linked to temporary abnormal conditions.

- Emergency Stop

A push button is placed on a door of the unit electrical panel. The button is highlighted by a red color in yellow background. A manual pressure of the emergency stop button stops all loads from rotating, thus preventing any accident which may occur. An alarm is also generated by the Unit Controller. Releasing the emergency stop button enables the unit, which may be restarted only after the alarm has been cleared on the controller.

DAIKIN EWAD820TZSRB2 - General safety devices - 1

The emergency stop causes all motors to stop, but does not switch off power to the unit. Do not service or operate on the unit without having switched off the main switch.

1.3.2 Circuit safety devices

Safety of this level of severity will shut down the circuit they protect. The remaining circuits will keep running.

1.3.3 Component safety devices

Safety of this level of severity will shut down a component against abnormal running condition that could create permanent damages to it. An overview of the protecting devices is listed below:

• Overcurrent/Overload Protections

Overcurrent/overload devices protect electrical motors used on compressors, fans and pumps in case of overload or short circuit. In case of inverter-driven motors, overload and overcurrent protection is integrated in the electronic drives. A further protection from short circuit is accomplished by fuses or circuit breakers installed upstream each load or group of loads.

• Overtemperature Protections

Compressor and fan electrical motors are also protected from overheating by thermistors immersed into motor windings. Should the winding temperature exceed a fixed threshold, the thermistors will trip and cause the motor to stop. High Temperature Alarm is recorded in the Unit Controller only in case of compressors. Alarm must be reset from the controller.

DAIKIN EWAD820TZSRB2 - Component safety devices - 1

Do not operate on a faulty fan before the main switch has been shut off. Overtemperature protection is auto-reset, therefore a fan may restart automatically if temperature conditions allow it.

- Phase reversal, under/over voltage, ground fault protections

When one of those alarms occurs the unit is immediately stopped or even inhibited to start. The alarms clear automatically once the problem is fixed. This auto clear logic allows the unit to automatically recover in case of temporary conditions where the supply voltage reaches the upper or lower limit set on the protection device. In the other two cases a manual intervention on the unit will be required in order to solve the problem. In case of a phase reversal alarm two phases requires to be inverted.

In the event of a power supply outage, the unit will restart automatically without the need for an external command. However, any faults active when the supply is interrupted are saved and may in certain cases prevent a circuit or unit from restarting.

DAIKIN EWAD820TZSRB2 - Component safety devices - 2

Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons.

- Flowswitch

The unit must be protected by a flowswitch. The flowswitch will stop the unit when the water flow becomes lower than the minimum allowed flow. When the water flow is restored the flow protection resets automatically. Exception is when the flowswitch opens with at least one compressor running, in this case the alarm shall be cleared manually.

- Freezing protection

Antifreeze protection prevents the water to freeze in the evaporator. It is automatically activated when the water temperature (entering or leaving) at the evaporator drops below the antifreeze limit. In freeze condition if the unit is in standby the evaporator pump will be activated to prevent freezing of the evaporator. If the freeze condition will activate when the unit is running all the unit will shut down in alarm while the pump will keep running. Alarm will automatically clear when the freeze condition will clear.

D-EOMZC00106-17EN

Operation Manual

8/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and heat pump

- Low pressure protection

If the circuit operates with a suction pressure lower than an adjustable limit for a certain time the circuit safety logic will shut down the circuit and generate an alarm. The alarm requires a manual action on the Unit Controller to be reset. Reset will take effect only if the suction pressure is no longer lower that the safety limit.

• High Pressure Protection

If the discharge pressure becomes too high and exceeds a limit which is linked with the operational envelop of the compressor the circuit safety logic will try to prevent the alarm or, if the corrective actions have no effect, it will shut down the circuit before the Mechanical High Pressure switch will open. This alarm required a manual action on the Unit Controller to be reset.

• Mechanical High Pressure Switch

Each circuit is equipped with at least one high pressure switch which tries to prevent the relief safety valve to open. When the discharge pressure becomes too high the Mechanical High Pressure switch will open and immediately stop the compressor cutting the power supply to the auxiliary relay. The alarm can be cleared as soon as the discharge pressure becomes normal again. The alarm must be reset on the switch itself and on the Unit Controller. The triggering pressure value cannot be changed.

- Relief Safety Valve

If the pressure becomes too high in the refrigerant circuit, the relief valve will open to limit the maximum pressure. If this happens switch off immediately the machine and contact your local service organization.

- Inverter fault

Each compressor can be equipped with its own inverter (integrated or external). The inverter can automatically monitor its status and inform the Unit Controller in case of faults or pre-alarm conditions. If this happen the Unit Controller will limit the compressor operation or eventually switch off the circuit in alarm. A manual action on the controller will be needed in order to clear the alarm.

1.4 Available sensors

1.4.1 Pressure transducers

Two types of electronic sensors are used to measure suction, discharge and oil pressure on each circuit. The range of each sensor is clearly indicated on the sensor casing. Discharge and oil pressures are monitored using a sensor of the same range.

1.4.2 Temperature sensors

The evaporator water sensors are installed in the entering and leaving side. An outdoor temperature sensor is mounted inside the chiller. Additionally each circuit installs a suction and discharge temperature sensors to monitor and control the superheated refrigerant temperatures.

On refrigerant-cooled inverters additional sensors immersed into the cooling plate measure the temperature of the drives.

1.4.3 Thermistors

Each compressor is equipped with PTC thermistors which are immersed into motor windings for motor protection. Thermistors trip to a high value in case the motor temperature reaches a hazardous temperature.

1.4.4 Leak detectors

As an option the unit can be equipped with leak detectors to sense the air in the compressor cabin and being able to identify a refrigerant leakage in that volume.

1.5 Available Controls

1.5.1 Evaporator pumps

The controller can regulate one or two evaporator pumps and takes care of automatic change-over between pumps. It's also possible to prioritize the pumps and temporarily disable one of the two. The controller is also able to control the pump speeds if the pumps are equipped with inverters.

1.5.2 Condenser pumps (W/C units only)

The controller can regulate one or two condenser pumps and takes care of automatic change-over between pumps. It's also possible to prioritize the pumps and temporarily disable one of the two.

1.5.3 Compressors

The controller can regulate one or two compressors installed on one or two independent refrigerant circuit (one compressor per circuit). All the safeties of each compressor will be managed by the controller. Embedded inverter safeties are handled by the inverter onboard electronic and only notified to the UC.

1.5.4 Expansion Valve

The controller can regulate an electronic expansion valve per each refrigerant circuit. Microtech® III embedded logic will always guarantee the best operation for the refrigerant circuit.

1.5.5 Switchbox Pressurization fan for HFO units (W/C only)

In case of water cooled units which are installed in machinery rooms it's required to pressurize the switchbox to avoid refrigerant accumulation that could lead to dangerous operations of the unit. To avoid this a pressurization fan will maintain a constant air circulation inside the switchbox. This fan will be always running when the internal temperature will exceed 23°C. Any drop in the delta pressure between the inside and the ambient will generate a stop of the unit to re-establish a safe condition for the users.

1.6 Customer Terminal Block Connections

The contacts below are available at the user's terminal block referred as MC24 or MC230 in the wiring diagram. The following table summarizes the connections at the user's terminal block.

DescriptionTerminals EWAD TZTerminals EWAD TZ BTerminals EWWD/H VZNotes
Evaporator Flow Switch (mandatory)708, 724708, 724708, 72424 Vdc digital input
Condenser Flow Switch--888, 89024 Vdc digital input
Double setpoint703, 728703,728703, 72824 Vdc digital input
Current limit enable884, 885885, 891-24 Vdc digital input
External Fault881,884881, 884542, 50124 Vdc digital input
Rapid Restart Enable (optional)764, 765-764, 76524 Vdc digital input
Back-up chiller (optional)764, 763--24 Vdc digital input
LOC/BMS selection (optional)894, 895881-1, 834894, 89524 Vdc digital input
On-Off Remote540, 541540, 541703, 749230 Vac digital input
Heat/Cool Remote--892, 893
Leak Detector Output--552, 553
General Alarm525, 526525, 526525, 526NO digital output (24...230 Vac ext supply)
Compressor #1 status512, 513512, 513-NO digital output (24...230 Vac ext supply)
Compressor #2 status514, 515514, 515-NO digital output (24...230 Vac ext supply)
Alarm Circuit #1 (optional)560, 561892, 896564, 565NO digital output (24...230 Vac ext supply)
Alarm Circuit #2 (optional)560, 562894, 899565, 566NO digital output (24...230 Vac ext supply)
Evaporator Pump #1 start806, 805501, 530527, 528NO digital output (24 Vdc internal supply)
Evaporator Pump #2 start806, 807501, 531559, 560NO digital output (24 Vdc internal supply)
Condenser Pump #1 start--550, 551NO digital output (24 Vdc internal supply)
Condenser Pump #2 start--559, 562NO digital output (24 Vdc internal supply)
Demand Limit (optional)888, 889888, 889887, 8894-20 mA analog input
Current Limit (optional)886, 890887, 886-4-20 mA analog input
Setpoint Override886, 887890, 886886, 8874-20 mA analog input
Pump VFD Signal (optional)882, 883--

D-EOMZC00106-17EN

Operation Manual

10/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and heat pump

1.6.1 Evaporator Flow Switch

Although the flow switch is offered as an optional, it is mandatory to install one and connect it to the digital input terminals in order to enable chiller operation only when a minimum flow is sensed.

DAIKIN EWAD820TZSRB2 - Evaporator Flow Switch - 1

Operating the unit by-passing the flow switch input or without an appropriate flow switch may damage the evaporator due to freezing. Operation of the flow switch must be checked prior to start up the unit.

1.6.2 Condenser Flow Switch (W/C units only)

Condenser flow switch is offered as an option but it's not mandatory to connect it to the digital input terminals. This input can be eventually closed by a jumper even if for a more reliable use it's suggested to mount it. If not installed, other protection will activate in order to protect the unit.

1.6.3 Double setpoint

This contact can be used to switch between two different LWT setpoints and, depending on the application, between different modes of operation.

Ice operation must be selected in case of ice storage application. In this case the UC will run the chiller in on/off mode, switching all the chiller off as soon as the setpoint is reached. In this case the unit will run to full capacity and then will switch off applying an ice delay different chiller starts.

1.6.4 Current limit (optional)

This optional feature enables a capacity control of the unit in order to limit the input current. The current limit feature is included in the Energy Meter option. The limiting signal will be compared with a limiting value set on the HMI. By default the current limit setpoint is selected through the HMI; an external 4-20 mA signal can be enabled to allow a remotely changeable setpoint.

1.6.5 External Fault

This contact is available to report to the UC a fault or a warning from an external device. It could be an alarm coming from an external pump to inform the UC of the fault. This input can be configured as a fault (unit stop) or a warning (displayed on the HMI without any action on the chiller).

1.6.6 Rapid Restart (optional)

Purpose of the rapid restart feature is to let the unit restart in the shortest possible time after a power failure, and then recover in the shortest possible time (maintaining the reliability level of the normal operations) the capacity it had before the power failure. The rapid restart is enabled by the enable switch.

1.6.7 Remote On-Off

This unit can be started through a remote enable contact. The Q0 switch must be selected to "Remote".

1.6.8 General Alarm

In case of a unit alarm, this output is closed thus indicating a fault condition to an externally connected BMS.

1.6.9 Compressor Status

The digital output is closed when the related circuit is in run state.

1.6.10 Circuit Alarm (optional)

This option is included with the "Rapid Restart" option. The related digital contact is closed in case of alarm on a circuit.

1.6.11 Evaporator Pump Start

A 24 Vdc digital output (with internal supply) is enabled when a pump (#1 or #2) is required to start. The output can be used to start an external pump (either at fixed or variable speed). The output requires an external input or relay with less than 20 mA excitation current.

1.6.12 Condenser Pump Start (W/C units only)

A digital output is enabled when a pump (#1 or #2) is required to start. A pump will be required to start when a compressor will be called to start.

1.6.13 Demand limit

This optional function can be used to limit the unit capacity percentage to a changeable limit value. This limitation cannot be directly linked to a corresponding limitation of the unit current (50% demand limit can differ from 50% of the unit FLA).

The demand limit signal can be changed continuously between 4 and 20 mA. The Microtech III will convert this signal into a unit capacity limitation changing between minimum capacity and full capacity with a linear relationship. A signal between 0 and 4mA will correspond to a full unit capacity, in this way if nothing is connected to this input no limitation will be applied. The maximum limitation will never force a unit shutdown.

1.6.14 Setpoint override

This input allows to apply an offset on the Active Setpoint to adjust the operating point of the ELWT. This input can be used to maximize the comfort.

1.6.15 Pump VFD Signal (A/C units only)

The "Pump VFD Signal" terminals are available for pump inverter kit option when factory wired speed reference is required. These terminals are placed inside the main electrical panel. For more information about this option see 7.4.

2 GENERAL DESCRIPTION

2.1 Basic Information

Microtech® III is a system for controlling single or dual-circuit air/water-cooled liquid chillers. Microtech® III controls compressor start-up necessary to maintain the desired heat exchanger leaving water temperature. In each unit mode it controls the operation of the condensers to maintain the proper condensation process in each circuit.

Safety devices are constantly monitored by Microtech® III to ensure their safe operation. Microtech® III also gives access to a Test routine covering all inputs and outputs. All Microtech® III controls can work in accordance with three independent modes:

  • Local mode: the machine is controlled by commands from the user interface.
  • Remote mode: the machine is controlled by remote contacts (volt-free contacts).
  • Network mode: the machine is controlled by commands from a BAS system. In this case, a data communication cable is used to connect the unit to the BAS.

When the Microtech® III system operates autonomously (Local or Remote mode) it retains all of its own control capabilities but does not offer any of the features of the Network mode. In this case monitoring of the unit operational data is still allowed.

2.2 Abbreviations used

In this manual, the refrigeration circuits are called circuit #1 and circuit #2. The compressor in circuit #1 is labelled Cmp1. The other in circuit #2 is labelled Cmp2. The following abbreviations are used:

A/CAir Cooled
CEWTCondenser Entering Water Temperature
CLWTCondenser Leaving Water Temperature
CPCondensing Pressure
CSRTCondensing Saturated Refrigerant Temperature
DSHDischarge Superheat
DTDischarge Temperature
E/MEnergy Meter Module
EEWTEvaporator Entering Water Temperature
ELWTEvaporator Leaving Water Temperature
EPEvaporating Pressure
ESRTEvaporating Saturated Refrigerant Temperature
EXVElectronic Expansion Valve
HMIHuman Machine Interface
MOPMaximum operating pressure
SSHSuction SuperHeat
STSuction Temperature
UCUnit controller (Microtech III)
W/CWater Cooled

2.3 Controller Operating Limits

Operation (IEC 721-3-3):

• Temperature -40...+70 °C
• Restriction LCD -20... +60 °C
• Restriction Process-Bus -25....+70 °C
• Humidity < 90 % r.h (no condensation)
• Air pressure min. 700 hPa, corresponding to max. 3,000 m above sea level

Transport (IEC 721-3-2):

• Temperature -40...+70 °C
• Humidity < 95 % r.h (no condensation)

EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 13/85

• Air pressure min. 260 hPa, corresponding to max. 10,000 m above sea level.

2.4 Controller Architecture

The overall controller architecture is the following:

• One MicroTech III main controller
- I/O extensions as needed depending on the configuration of the unit
• Communications interface(s) as selected
- Peripheral Bus is used to connect I/O extensions to the main controller.

DAIKIN EWAD820TZSRB2 - Controller Architecture - 1

flowchart
graph TD
    A["BAS Interface (Bacnet, Lon, Mod bus)"] --> B["Microtech III Main Controller"]
    B --> C["Peripheral Bus"]
    C --> D["I/O extension EXV 1"]
    D --> E["I/O extension EXV 2"]
    E --> F["I/O Extension Options"]
Controller/Extension ModuleSiemens Part NumberAddressUsage
EWAD TZEWAD TZ BEWWD/H-VZ
Main ControllerPOL687.70/MCQPOL687.70/MCQPOL687.00/MCQn/aUsed on all configurations
Extension Module--POL965.00/MCQ2Used on all configurations
EEXV Module 1POL94U.00/MCQPOL98U.00/MCQPOL94U.00/MCQ3Used on all configurations
EEXV Module 2POL94U.00/MCQPOL98U.00/MCQ-4Used when configured for 2 circuits
Extension Module--POL965.00/MCQ4Used when configured for 2 circuits
EEXV Module 2--POL94U.00/MCQ5Used when configured for 2 circuits
Extension ModulePOL965.00/MCQ--5Used on all configurations
Rapid Restart ModulePOL945.00/MCQ-POL945.00/MCQ22Used with Rapid Restart option
HFO Module--POL945.00/MCQ27Used with HFO on W/C units

All boards are supplied from a common 24 Vac source. Extension boards can be directly powered by the Unit Controller. All boards can be also supplied by a 24Vdc source.

DAIKIN EWAD820TZSRB2 - Controller Architecture - 2

CAUTION: Maintain the correct polarity when connecting the power supply to the boards, otherwise the peripheral bus communication will not operate and the boards may be damaged.

2.5 Communication Modules

Any of the following modules can be connected directly to the left side of the main controller to allow a BAS or other remote interface to function. Up to three can be connected to the controller at a time. The controller should automatically detect and configure itself for new modules after booting up. Removing modules from the unit will require manually changing the configuration.

ModuleSiemens Part NumberUsage
BacNet/IPPOL908.00/MCQOptional
LonPOL906.00/MCQOptional
ModbusPOL902.00/MCQOptional
BACnet/MSTPPOL904.00/MCQOptional

D-EOMZC00106-17EN

Operation Manual

14/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

The control system consists of a unit controller (UC) equipped with a set of extension modules that implement additional features. All boards communicate via an internal peripheral bus with the UC. The Microtech III continuously manages the information received from the various pressure and temperature probes installed on the compressors and communicated to the unit. The UC incorporates a program that controls the unit.

The standard HMI consists of an inbuilt display (A) with 3 buttons (B) and a push'n'roll control (C).

DAIKIN EWAD820TZSRB2 - Communication Modules - 1

text_image UC A POUET TRACKS B C

The keypad/display (A) consists of a 5-line by 22 character display. The function of the three buttons (B) is described below:

Alarm status (from any page it links with the page with alarm list, alarm log and alarm snapshot if available)
Back to Main Page
Back to the previous level (it can be the Main Page)

The push'n'roll command (C) is used to scroll between the different menu pages, settings and data available on the HMI for the active password level. Rotating the wheel allows to navigate between lines on a screen (page) and to increase and decrease changeable values when editing. Pushing the wheel acts as an Enter Button and will jump from a link to the next set of parameters.

3.1 General Recommendation

Before switching on the unit read the following recommendations:

  • When all the operations and all the settings have been carried out, close all the switchbox panels
  • The switchbox panels can only be opened by trained personnel
  • When the UC requires to be accessed frequently the installation of a remote interface is strongly recommended
  • Evaporator, compressors and related inverters are protected from freezing by electrical heaters. These heaters are supplied through unit main supply and temperature controlled by thermostat or by the unit controller. Also the LCD display of the unit controller may be damaged by extremely low temperatures. For this reason, it is strongly recommended to never power off the unit during winter, especially in cold climates.

3.2 Navigating

When power is applied to the control circuit, the controller screen will be active and display the Home screen, which can also be accessed by pressing the Menu Button. The navigating wheel is the only navigating device necessary, although the MENU, ALARM, and BACK buttons can provide shortcuts as explained previously.

An example of the HMI screens is shown in the following picture.

DAIKIN EWAD820TZSRB2 - Navigating - 1

text_image M a i n M e n u 1 / 11 E n t e r P a s s w o r d U n i t S t a t u s = O f f : U n i t S W A c t i v e S e t p t = 7 . 0 ° C
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 15/85

A bell ringing in the top right corner will indicate an active alarm. If the bell doesn't move it means that the alarm has been acknowledged but not cleared because the alarm condition hasn't been removed. A LED will also indicate where the alarm is located between the unit or circuits.

M a i nM e n u1 /
E n t e rP a s s w o r d
U n i t S t a t u s =
O f f : U n i t S W
A c t i v e S e t p t =7.0 °C

The active item is highlighted in contrast, in this example the item highlighted in Main Menu is a link to another page. By pressing the push'n'roll, the HMI will jump to a different page. In this case the HMI will jump to the Enter Password page.

DAIKIN EWAD820TZSRB2 - Navigating - 2

text_image Enter Password 2 / 2 Enter PW * * * *

3.3 Passwords

The HMI structure is based on access levels that means that each password will disclose all the settings and parameters allowed to that password level. Basic informations about the status including the active alarm list, active setpoint and controlled water temperature can be accessed without the need to enter the password. The user UC handles two level of passwords:

USER5321
MAINTENANCE2526

The following information will cover all data and settings accessible with the maintenance password. User password will disclose a subset of the settings explained in chapter 4.

In the Enter Password screen, the line with the password field will be highlighted to indicate that the field on the right can be changed. This represents a setpoint for the controller. Pressing the push'n'roll the individual field will be highlighted to allow an easy introduction of the numeric password. By changing all fields, the 4 digits password will be entered and, if correct, the additional settings available with that password level will be disclosed.

DAIKIN EWAD820TZSRB2 - Passwords - 1

text_image Enter Password 2 / 2 Enter PW 5 * * *

The password will time out after 10 minutes and is cancelled if a new password is entered or the control powers down. Entering an invalid password has the same effect as continuing without a password.

Once a valid password has been entered, the controller allows further changes and access without requiring the user to enter a password until either the password timer expires or a different password is entered. The default value for this password timer is 10 minutes. It is changeable from 3 to 30 minutes via the Timer Settings menu in the Extended Menus.

3.4 Editing

The Editing Mode is entered by pressing the navigation wheel while the cursor is pointing to a line containing an editable field. Once in the edit mode pressing the wheel again causes the editable field to be highlighted. Turning the wheel clockwise while the editable field is highlighted causes the value to be increased. Turning the wheel counter-clockwise while the editable field is highlighted causes the value to be decreased. The faster the wheel is turned, the faster the value is increased or decreased. Pressing the wheel again cause the new value to be saved and the keypad/display to leave the edit mode and return to the navigation mode.

D-EOMZC00106-17EN

Operation Manual

16/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

A parameter with an "R" is read only; it is giving a value or description of a condition. An "R/W indicates a read and/or write opportunity; a value can be read or changed (providing the proper password has been entered).

Example 1: Check Status, for example -is the unit being controlled locally or by an external network? We are looking for the Unit Control Source. Since this a unit status parameter, start at Main Menu and select View/Set Unit and press the wheel to jump to the next set of menus. There will be an arrow at the right side of the box, indicating that a jump to the next level is required. Press the wheel to execute the jump. You will arrive at the Status/ Settings link. There is an arrow indicating that this line is a link to a further menu. Press the wheel again to jump to the next menu, Unit Status/Settings. Rotate the wheel to scroll down to Control Source and read the result.

Example 2: Change a Set point, the chilled water set point for example. This parameter is designated as Cool LWT Set point 1 and is a unit set parameter. From the Main Menu select View/Set Unit. The arrow indicated that this is link to a further menu. Press the wheel and jump to the next menu View/Set Unit and use the wheel to scroll down to Temperatures. This again has an arrow and is a link to a further menu. Press the wheel and jump to the Temperatures menu, which contains six lines of temperatures set points. Scroll down to Cool LWT 1 and press the wheel to jump to the item change page. Rotate the wheel to adjust the set point to the desired value. When this is done press the wheel again to confirm the new value. With the Back button it will be possible to jump back to the Temperatures menu where the new value will be displayed.

Example 3: Clear an Alarm. The presence of a new alarm is indicated with a Bell ringing on the top right of the display. If the Bell is frozen one or more alarm had been acknowledged but are still active. To view the Alarm menu from the Main Menu scroll down to the Alarms line or simply press the Alarm button on the display. Note the arrow indicating this line is a link. Press the wheel to jump to the next menu Alarms; there are two lines here: Alarm Active and Alarm Log. Alarms are cleared from the Active Alarm link. Press the wheel to jump to the next screen. When the Active Alarm list is entered scroll to the item AlmClr which is set to off by default. Change this value to on to acknowledge the alarms. If the alarms can be cleared then the alarm counter will display 0 otherwise it will display the number of alarm still active. When the alarms are acknowledged the Bell on the top right of the display will stop to ring if some of the alarms are still active or will disappear if all the alarms are cleared.

3.5 Basic Control System Diagnostic

MicroTech III controller, extension modules and communication modules are equipped with two status LED (BSP and BUS) to indicate the operational status of the devices. The BUS LED indicates the status of the communication with the controller. The meaning of the two status LED is indicated below.

Main Controller (UC)

BSP LEDMode
Solid GreenApplication running
Solid YellowApplication loaded but not running (*) or BSP Upgrade mode active
Solid RedHardware Error (*)
Flashing GreenBSP startup phase. The controller needs time for starting.
Flashing YellowApplication not loaded (*)
Flashing Yellow/RedFail safe mode (in case that the BSP upgrade was interrupted)
Flashing RedBSP Error (software error*)
Flashing Red/GreenApplication/BSP update or inizialization

(*) Contact Service.

Extension modules

BSP LEDModeBUS LEDMode
Solid GreenBSP runningSolid GreenCommunication running, I/O working
Solid RedHardware Error (*)Solid RedCommunication down (*)
Flashing RedBSP Error (*)Solid YellowCommunication running but parameter from the application wrong or missing, or uncorrect factory calibration
Flashing Red/GreenBSP upgrade mode

Communication modules

BSP LED (same for all modules)

BSP LEDMode
Solid GreenBPS running, communication with controller
Solid YellowBSP running, no communication with controller (*)
Solid RedHardware Error (*)
Flashing RedBSP Error (*)
Flashing Red/GreenApplication/BSP update

(*) Contact Service.

BUS LED

BUS LEDLONBacnet MSTPBacnet IPModbus
Solid GreenReady for Communication. (All Parameter loaded, Neuron configured). Doesn't indicate a communication with other devices.Ready for Communication. The BACnet Server is started. It doesn't indicate an active communicationReady for Communication. The BACnet Server is started. It doesn't indicate an active communicationAll Communication running
Solid YellowStartupStartupStartup. The LED stays yellow until the module receives a IP Address, therefore a link must be established.Startup, or one configured channel not communicating to the Master
Solid RedNo Communication to Neuron (internal error, could be solved by downloading a new LON application)BACnet Server down. Automatically a restart after 3 seconds are initiated.BACnet Server down. Automatic restart after 3 seconds is initiated.All configured Communications down. Means no communication to the Master. The timeout can be configured. In case that the timeout is zero the timeout is disabled.
Flashing YellowCommunication not possible to the Neuron. The Neuron must be configured and set online over the LON Tool.

3.6 Controller maintenance

The controller requires to maintain the installed battery. Every two years it's required to replace the battery. Battery model is: BR2032 and it is produced by many different vendors.

To replace the battery remove the plastic cover of the controller display using a screw driver as shown in the following pictures:

DAIKIN EWAD820TZSRB2 - Controller maintenance - 1

natural_image Close-up of a metallic electronic device with a knob and a pen inserted, placed on a white surface with red diagonal lines (no visible text or symbols)

DAIKIN EWAD820TZSRB2 - Controller maintenance - 2

natural_image Close-up of a white electronic device with a control panel and a hand holding a tool, placed on a blue surface (no visible text or symbols)

DAIKIN EWAD820TZSRB2 - Controller maintenance - 3

natural_image Close-up of a device panel with a circular inset showing a small mechanical component (no visible text or symbols)

Be careful to avoid damages to the plastic cover. The new battery shall be placed in the proper battery holder which is highlighted in the picture, respecting the polarities indicated into the holder itself.

3.7 Optional Remote User Interface

As an option an external Remote HMI can be connected on the UC. The Remote HMI offers the same features as the inbuilt display plus the alarm indication done with a light emitting diode located below the bell button.

D-EOMZC00106-17EN

Operation Manual

18/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and heat pump

The Remote can be ordered with the unit and shipped loose as a field installed option. It can also be ordered any time after chiller shipment and mounted and wired on the job as explained on the following page. The remote panel is powered from the unit and no additional power supply is required.

All viewing and setpoint adjustments available on the unit controller are available on the remote panel. Navigation is identical to the unit controller as described in this manual.

The initial screen when the remote is turned on shows the units connected to it. Highlight the desired unit and press the wheel to access it. The remote will automatically show the units attached to it, no initial entry is required.

DAIKIN EWAD820TZSRB2 - Optional Remote User Interface - 1

text_image MicroTech® III

The Remote HMI can be extended up to 700m using the process bus connection available on the UC. With a daisy-chain connection as below, a single HMI can be connected to up to 8 units. Refer to the specific HMI manual for details.

DAIKIN EWAD820TZSRB2 - Optional Remote User Interface - 2

flowchart
graph LR
    A["RESET RMT"] --> B["CLK"]
    B --> C["WNT"]
    C --> D["UXINT MDS"]
    D --> E["CLK"]
    E --> F["WNT"]
    F --> G["UXINT MDS"]
    G --> H["CLK"]
    H --> I["WNT"]
    I --> J["UXINT MDS"]
    J --> K["CLK"]
    K --> L["WNT"]

3.8 Embedded Web Interface

The MicroTech III controller has an embedded web interface that can be used to monitor the unit when connected to a local network. It is possible to configure the IP addressing of the MicroTech III as a fixed IP of DHCP depending on the network configuration.

With a common web browser a PC can connect with the unit controller entering the IP address of the controller or the host name, both visible in the "About Chiller" page accessible without entering a password.

When connected, it will be required to enter a user name and a password. Enter the following credential to get access to the web interface:

User Name: ADMIN

Password: SBTAdmin!

DAIKIN EWAD820TZSRB2 - Embedded Web Interface - 1

Air and Water cooled inverter chillers and heat pump

D-EOMZC00106-17EN

Operation Manual 19/85

The Main Menu page will be displayed. The page is a copy of the onboard HMI and follows the same rules in terms of access levels and structure.

DAIKIN EWAD820TZSRB2 - Embedded Web Interface - 2

text_image Main Menu Enter Password Unit Status= Off: Unit Not Cfgd Active Setpoint= 7.0°C MS Ctrl Tmp= 0.0°C Evaporator LWT= -273.1°C Unit Capacity= 0.0% Unit Mode= Cool

In addition it allows to trend log a maximum of 5 different quantities. It's required to click on the value of the quantity to monitor and the following additional screen will become visible:

DAIKIN EWAD820TZSRB2 - Embedded Web Interface - 3

line | Date | Press Ratio | Active Setpt | | ---------- | ----------- | ------------ | | 2014-10-17 | 2.99 | 7 |

Depending on the web browser and its version the trend log feature may not be visible. It's required a web browser supporting HTML 5 like for example:

• Microsoft Internet Explorer v.11,
- Google Chrome v.37,
- Mozilla Firefox v.32.

These software are only an example of the browser supported and the versions indicated have to be intended as minimum versions.

4 MENU STRUCTURE

All settings are divided in different menus. Each menu collects in a single page other sub-menus, settings or data related to a specific function (for example Power Conservation or Setup) or entity (for example Unit or Circuit). In any of the following pages, a grey box will indicate changeable values and the defaults.

4.1 Main Menu

Setpoint/Sub-MenuDefaultRangeDescription
Enter Password-Submenu to activate access levels
View/Set Unit-Submenu for unit data and settings
View/Set Circuit-Submenu for circuit data and settings
Unit Status=Off: Unit SwAutoOff: Ice Mode TmrOff: OAT Lockout (A/C units only)Off: All Cir DisabledOff: Unit AlarmOff: Keypad DisableOff: Master DisableOff: BAS DisableOff: Unit SwOff: Test ModeOff: Schedule DisableAuto: Noise ReductionAuto: Wait For LoadAuto: Evap Recirc (A/C units only)Auto: Water Recir (W/C units only)Auto: Wait For FlowAuto: PumpdnAuto: Max PulldnAuto: Unit Cap LimitAuto: Current LimitStatus of the Unit
Active Setpoint=7.0°C, ▶-Water temperature active setpoint + link to Setpoint page
MS Ctrl Tmp=-273.1°C, ▶-Master slave controlled temperature + link to Master Slave Data page
Evaporator LWT=-273.1°C, ▶-Evaporator leaving water temperature + link to Temperatures page
Condenser LWT=-273.1°C, ▶-Condenser leaving water temperature + link to Temperatures page (W/C units only)
Unit Capacity=0.0%, ▶-Unit capacity + link to Capacity page
Unit Mode=Cool, ▶-Unit Mode + link to Available modes page
Unit Enable=Enable, ▶-Unit Enable state + link to unit and circuits enable page
Timers-Submenu for unit timers
Alarms-Submenu for alarms; same function as Bell Button
Commission Unit-Submenu for commission unit
About Chiller-Application Info submenu

4.2 View/Set Unit

Setpoint/Sub-MenuDefaultRangeDescription
Thermostat Ctrl-Submenu for Thermostatic control
Network Ctrl-Submenu for Network control
Vfd Settings-Submenu Vfd installation settings (A/C units only)
Pumps-Submenu for pump settings
Condenser-Submenu for Condenser tower control (W/C units Only)
Master/Slave-Submenu for Master Slave data and settings
Rapid Restart-Submenu for Rapid Restart Option
Date/Time-Submenu Date, Time and Quiet Night mode schedule
Scheduler-Submenu for Time Scheduler
Power Conservation-Submenu Unit Limiting functions
Electrical Data-Submenu for electrical data
Ctrl IP Setup-Submenu for controller IP-address setup
Daikin on Site-Submenu for connection to Daikin cloud DoS
Menu Password-Submenu Disable Password for User level

4.2.1 Thermostat Ctrl

This page resumes all the parameters related to the unit thermostatic control.

EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 21/85
Setpoint/Sub-MenuDefaultRangeDescription
TZ/TZ BVZ
Start Up DT=2.7°C2.7°C0.0...5.0°COffset to start thermostat control
Shut Dn DT=1.0°C1.5°C0.0...1.7°COffset to standby
Stg Up DT=0.5°C0.5°C0.0...1.7°COffset to allow compressor starts
Stg Dn DT=1.0°C0.7°C0.0...1.7°COffset to force one compressor off
Stg Up Delay=5 min3 min0...60 minCompressor start interstage
Stg Dn Delay=3 min3 min3...30 minCompressor stop interstage
Strt Strt Dly=20min15min15...60 minCompressor Start to Start delay
Stop Strt Dly=5min3min3...20 minCompressor Stop to Start delay
Ice Cycle Dly=12h12h1...23hIce cycle delay
Lt Ld Stg Dn %=40%20%20...50%Circuit capacity threshold to stage down one compressor
Hi Ld Stg Up %=80%50%50...100%Circuit capacity threshold to stage up one compressor
Max Ckts Run=221...2Limit to the number of circuit to be used
C1 Sequence #=111...2Manual sequence of circuit #1
C2 Sequence #=111...2Manual sequence of circuit #2
Next Crkt On=00-Shows next circuit to be started up
Next Crkt Off=00-Shows next circuit number to be stopped

4.2.2 Network Ctrl

This page resumes all settings related to Network control.

Setpoint/Sub-MenuDefaultRangeDescription
TZ / TZ BVZ
Control Source=LocalLocalLocal, NetworkControl source selection: Local/BMS
Act Ctrl Src=LocalN/ALocal, NetworkActive control between Local/BMS
Netwrk En SP=DisableDisableEnable, DisableEnable unit command from BMS
Netwrk Mode SP=CoolCool-Cool, Ice, Heat (NA), Cool/Heat Recovery
Netwrk Cool SP=6.7°C6.7°C-Cooling setpoint from BMS
Netwrk Cap Lim=100%100%-Capacity limitation from BMS
Netwrk HR SP=45.0°CN/A-Heat recovery setpoint from BMS
Network Heat SP=N / A45.0°C-Heating setpoint from BMS (W/C Units only)
Netwrk Ice SP=-4.0°C-4.0°C-Ice setpoint from BMS
Netwrk Current SP=800A800A-Sepoint for current limitation from BMS
Remote Srv En=DisableDisableEnable, DisableRemote server enable

4.2.3 Compressor Vfd Setup (A/C Units only)

This page contains basics Vfd Settings. It will be possible to set the Modbus address of each inverter installed on compressors. This function is supposed to be activated in case of compressor replacement. The page will also contain the Modbus setup parameters like baud rate, parity etc.

Setpoint/Sub-MenuDefaultRangeDescription
Baud Rate=192004800, 9600, 19200, 38400Modbus communication speed
Parity=NoneNone, Odd, EvenParity
Two Stop Bits=NoNo, YesNumber of stop bits
485 Resistance=ActiveActive, PassiveRS485 Termination resistance
Set Inv1 Fltr=HoldHold, ExecCommand to enable communication filter on the compressor 1
Set Inv2 Fltr=HoldHold, ExecCommand to enable communication filter on the compressor 2

4.2.4 Pumps

This page contains the settings to define the operation of the primary/backup pumps, the running hours of each pump and all parameters to configure the behavior of the pump driven with an inverter.

Setpoint/Sub-MenuDefaultRangeDescription
TZ / TZBVZ
Evp Pmp Ctrl=#1 Only#1 Only#1 Only, #2 Only, Auto, #1 Primary, #2 PrimarySet number of Evaporator pumps operational and which priority.
Evap Recirc Tm=30s30s0...300sWater recirculating timer
Evap Pmp 1 Hrs=0h0hRunning Hours Evaporator Pump 1 (if present)
Evap Pmp 2 Hrs=0h0hRunning Hours Evaporator Pump 2 (if present)
Speed 1=80%N/A0-100%Speed when the input Double Speed Switch is open

D-EOMZC00106-17EN

Operation Manual

22/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

Setpoint/Sub-MenuDefaultRangeDescription
TZ / TZBVZ
Cnd Pump Ctrl=N/A#1 Only#1 Only, #2 Only, Auto, #1 Primary, #2 PrimarySet number of Condenser pumps operational and which priority.
Cond Pmp 1 Hrs=N/A0hRunning Hours Condenser Pump 1 (if present)
Cond Pmp 2 Hrs=N/A0hRunning Hours Condenser Pump 2 (if present)
Speed 2=60%N/A0-100%Speed when the input Double Speed Switch is close
Thermo Off Speed=50%N/A0-100%Speed when there are no compressors running
Plant PD=-N/A-Actual Plant Pressure Measurements
Plant PD Sp=0kPaN/A0-1000kPaPlant Pressure Drop Setpoint
Evap PD=-N/A-Actual Evaporator Pressure Drop Measurements
Min Evap PD=0kPaN/A0-1000kPaMinimum Evaporator Pressure Drop setpoint
Hysteresis0kPaN/A0-1000kPaHysteresis value for bypass value
Pump Speed=-N/A-Actual Pump Speed
Min Speed=0%N/A0-100%Minimum Pump Speed
Max Speed=100%N/A0-100%Maximum Pump Speed
Mode=AutoN/AAuto-ManualPump mode
Manual Speed=0%N/A0-100%Pump Manual Speed
Sns Scale=200kPaN/A0-2000kPaPlant Pressure Drop Sensor Scale
BypassOpenN/AOpen,CloseBypass valve state

4.2.5 Condenser (W/C units only)

This page contains basics settings for condensation control described in section 5.4.

Setpoint/Sub-MenuDefaultRangeDescription
Cond LWT-273.1°C-Present value of Condenser Leaving Water Temperature
Cond EWT-273.1°C-Present value of Condenser Entering Water Temperature
Cond Target25.0 °C19.0...55.0 °CTarget for Condenser Leaving Water Temperature
Cond Fan Spd0.0%0.0...100.0%Present value of Condenser Fan Speed
Tower Setpt 125.0 °C19.0...55.0 °CSetpoint for activation of Tower 1
Tower Setpt 127.0 °C26.0...55.0 °CSetpoint for activation of Tower 2
Tower Setpt 329.0 °C28.0...55.0 °CSetpoint for activation of Tower 3
Tower Setpt 431.0 °C30.0...55.0 °CSetpoint for activation of Tower 4
Tower Diff 11.5 °C0.1...5.0 °CDifferential for deactivation of Tower 1
Tower Diff 21.5 °C0.1...5.0 °CDifferential for deactivation of Tower 1
Tower Diff 31.5 °C0.1...5.0 °CDifferential for deactivation of Tower 1
Tower Diff 41.5 °C0.1...5.0 °CDifferential for deactivation of Tower 1
Min Vfd Sp10.0%0.0...49.0 %Setpoint for minimum percentage of Vfd Speed
Max Vfs Sp100.0%55.0...100.0%Setpoint for maximum percentage of Vfd Speed
PID Prop Gain10.00.0...50.0Proportional Gain of PID condensation controller
PID Der Time1s0...180sDerivative Time of PID condensation controller
PID Int Time600s0...600sIntegral Time of PID condensation controller
Vfd Manual Speed20.0%0.0...100.0%Setpoint for Vfd manual speed

4.2.6 Press Fan (W/C with HFO units only)

Setpoint/Sub-MenuDefaultRangeDescription
Internal FanEnableDisable, EnableEnable/Disable the pressurization fan internal to the unit switchbox.
Flamability Lim23.0 °C-Present value of Flammability limit

4.2.7 Master/Slave

All data and parameters available in this sub-menus are related to the Master Slave function. Refer to Master Slave manual for more details.

Setpoint/Sub-MenuDefaultRangeDescription
Data-Submenu Data. This link is available only on the Master unit
Options-Submenu Options. This link is available only on the Master unit
Thermostat Ctrl-Submenu Thermostat Ctrl. This link is available only on the Master unit
Timers-Submenu Timers. This link is available only on the Master unit
Standby Chiller-Submenu Standby Chiller. This link is available only on the Master unit
Disconnect UnitNoNo, YesParameter to disconnect the unit by the Master Slave system.
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 23/85

When this parameter is set to Yes the unit follows all local settings.

4.2.7.1 Data

In this menu are collected all main data related to Master Slave function.

Setpoint/Sub-MenuDefaultRangeDescription
Next On=--,Master, Slave 1, Slave 2, Slave 3Display next chiller that will be starts
Next Off=--,Master, Slave 1, Slave 2, Slave 3Display next chiller that will be stopped
Standby=--,Master, Slave 1, Slave 2, Slave 3Display the actual standby chiller
Switch Date-dd/mm/yyyyDisplay the day in which the standby chiller will be cycled
Switch Time-hh:mm:ssDisplay at which time of the switch day the standby chiller will be cycled
Plant Load=-0%...100%Display the actual plant load
Avg EWT--Display the actual average entering water temperature value
Common EWT--Display the actual common entering water temperature value
Mst State=-Off, On, Alarm, Comm ErrDisplay the actual state of the Master
SI1 State=-Off, On, Alarm, Comm ErrDisplay the actual state of the Slave 1
SI2 State=-Off, On, Alarm, Comm ErrDisplay the actual state of the Slave 2
SI3 State=-Off, On, Alarm, Comm ErrDisplay the actual state of the Slave 3
Mst Standalone=-No, YesDisplay if the standalone mode if active on the Master
SI1 Standalone-No, YesDisplay if the standalone mode if active on the Slave 1
SI2 Standalone-No, YesDisplay if the standalone mode if active on the Slave 2
SI3 Standalone-No, YesDisplay if the standalone mode if active on the Slave 3
Mst Load=-0%...100%Display the actual load of the Master
SI1 Load=-0%...100%Display the actual load of the Slave 1
SI2 Load=-0%...100%Display the actual load of the Slave 2
SI3 Load=-0%...100%Display the actual load of the Slave 3
Mst LWT=--Display the Master leaving water temperature
SI1 LWT=--Display the Slave1 leaving water temperature
SI2 LWT=--Display the Slave2 leaving water temperature
SI3 LWT=--Display the Slave3 leaving water temperature
Mst EWT=--Display the Master entering water temperature
SI1 EWT=--Display the Slave1 entering water temperature
SI2 EWT=--Display the Slave2 entering water temperature
SI3 EWT=--Display the Slave3 entering water temperature
Mst Hrs=--Master running hours
SI1 Hrs=--Slave 1 running hours
SI2 Hrs=--Slave 2 running hours
SI3 Hrs=--Slave 3 running hours
Mst Starts=--Master number of starts
SI1 Starts=--Slave 1 number of starts
SI2 Starts=--Slave 2 number of starts
SI3 Starts=--Slave 3 number of starts

4.2.7.2 Options

This menu allows to set main parameter of Master Slave function

Setpoint/Sub-MenuDefaultRangeDescription
Master Priority=11...4Start Up / Shut Down priority of the chiller MasterPriority = 1 → highest priorityPriority = 4 → lowest priority
Slave 1 Priority=11...4Start Up / Shut Down priority of the chiller Slave 1Priority = 1 → highest priorityPriority = 4 → lowest priority
Slave 2 Priority=11...4Start Up / Shut Down priority of the chiller Slave 2.Priority = 1 → highest priorityPriority = 4 → lowest priorityThis menu is visible only if the parameter M/S Num Of Unit has been configured at least with value 3
Slave 3 Priority=11...4Start Up / Shut Down priority of the chiller Slave 3.Priority = 1 → highest priorityPriority = 4 → lowest priorityThis menu is visible only if the parameter M/S Num Of Unit has been configured at least with value 4

D-EOMZC00106-17EN

Operation Manual

24/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

Setpoint/Sub-MenuDefaultRangeDescription
Master Enable=EnableEnable DisableThis parameter allows to enable or disable locally the Master Chiller
Control Mode=CompletePartial CompleteParameter to select the Partial or Complete control modePartial → On/Off controlComplete → On/Off + Capacity control
Control Tmp=LeavingEntering LeavingParameter to define the controlled temperatureEntering - Thermoregulations is based on the Average Entering Water Temperature (AEWT)Leaving - Thermoregulation is based on the Common Leaving Water Temperature (CLWT)

4.2.7.3 Thermostat Ctrl

This page resumes all thermostat control parameter of Master Slave.

Setpoint/Sub-MenuDefaultRangeDescription
Stage Up DT=2.7°C0.5...5.0°COffset respect the active setpoint for the unit startup.
Stage Dn DT =1.5°C0.5...5.0°COffset respect the active setpoint for the unit shutdown.
Dead Band =0.20.1 - Min(Stage UP DT, Stage Dn DT)Dead Band respect the active setpoint within which the load/unload command are no longer generated
Threshold=60%30...100%Threshold of load that have to reach all units running before start of a new chiller
Stage Up Time=5min0min...20minMinimum time between the start of two chillers
Stage Dn Time=5min0min...20minMinim time between the stop of two chillers
Min Evap Tmp=4.0-18...30°CMinimum Evaporator leaving water temperature

4.2.7.4 Timers

Setpoint/Sub-MenuDefaultRangeDescription
Stage Up Timer=--Current delay for new chiller stage up
Stage Dn Timer=--Current delay for new chiller stage down
Clear Timers=OffOff ResetThis command, visible only with service password, can be used to reset the Stage Up/Dn Timer.

4.2.7.5 Standby Chiller

This menu allows to configure the standby chiller

Setpoint/Sub-MenuDefaultRangeDescription
Standby Chiller=NoNo, Auto, Master, Slave 1, Slave 2, Slave 3Standby chiller selection
Cycling Type=TimeRun Hours, SequenceCycling type of standby chiller if previous parameter Standby Chiller is set as Auto
Interval Time=7 Days1...365Define the interval time (expressed in day) for the cycling of standby chiller
Switch Time=00:00:0000:00:00...23:59:59Define the time within the day when will be performed the switch of the standby chiller
Tmp Cmp=NoNo,YesEnabling of Temperature Compensation function
Tmp Comp Time=120 min0...600Time constant of Temperature Compensation function
Standby Reset=OffOff, ResetParameter to reset standby chiller cycling timer

4.2.8 Rapid Restart

This page shows if the function Rapid Restart is enabled by external contact and it allows to define the maximum black out time in order to recover quickly the unit load.

Setpoint/Sub-MenuDefaultRangeDescription
Rapid Restart=DisableEnable, DisableFeature enable if Rapid Restart is installed
Pwr Off Time=60s-Maximum black out time to enable Rapid Restart

4.2.9 Date/Time

This page will allow to adjust the time and date in the UC. This time and date will be used in the alarm log and to enable and disable the Quiet Mode. Additionally it's also possible to set the starting and ending date for the DayLight Saving time (DLS) if used. Quiet Mode is a feature that is used to reduce the chiller noise. This is

EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 25/85

done by applying the maximum setpoint reset to the cooling setpoint and increasing the condenser temperature target by an adjustable offset.

Setpoint/Sub-MenuDefaultRangeDescription
TZ / TZ BVZ
Actual Time=12:00:0012:00:00Set the time
Actual Date=01/01/201401/01/2014Set the date
UTC Diff=-60min-60minDifference with UTC
DLS Enable=YesYesNo, YesEnable DayLight Saving time
DLS Strt Month=MarMarDayLight Saving time start month
DLS Strt Week=2ndWeek2ndWeekDayLight Saving time start week
DLS End Month=NovNovNA, Jan...DecDayLight Saving time end month
DLS End Week=1stWeek1stWeek 1^st ... 5^th weekDayLight Saving time end week
Quiet Mode=DisableN/ADisable, EnableActivate Quiet Mode
QM Start Hr=21hN/A18...23hQuiet Mode start hour
QM Start Min=0minN/A0...59minQuiet Mode start minute
QM End Hr=6hN/A5...9hQuiet Mode end hour
QM End Min=0minN/A0...59minQuiet Mode end minute
QM Cond Offset=5°CN/A0.0...14.0°CQuiet Mode condenser target offset

On board real time clock settings are maintained thanks to a battery mounted on the controller. Make sure that the battery is replaced regularly each 2 years (see section 3.6).

4.2.10 Scheduler

This page allows to program the time scheduler

Setpoint/Sub-MenuDefaultRangeDescription
StateOffOff, On Setpoint 1, On Setpoint 2Actual state provided by the time scheduler
Monday-Link to Monday scheduler programming page
Tuesday-Link to Tuesday scheduler programming page
Wednesday-Link to Wednesday scheduler programming page
Thursday-Link to Thursday scheduler programming page
Friday-Link to Friday scheduler programming page
Saturday-Link to Saturday scheduler programming page
Sunday-Link to Sunday scheduler programming page

Table below reports the menu used to program daily time slots. Six time slots can be programmed by the user.

Setpoint/Sub-MenuDefaultRangeDescription
Time 1*:*0:00..23:59Define the starting time of 1^st time slot
Value 1OffOff, On Setpoint 1, On Setpoint 2Define the unit state during 1^st time slot
Time 2*:*0:00..23:59Define the starting time of 2^nd time slot
Value 2OffOff, On Setpoint 1, On Setpoint 2Define the unit state during 2^nd time slot
Time 3*:*0:00..23:59Define the starting time of 3^d time slot
Value 3OffOff, On Setpoint 1, On Setpoint 2Define the unit state during 3^d time slot
Time 4*:*0:00..23:59Define the starting time of 4^th time slot
Value 4OffOff, On Setpoint 1, On Setpoint 2Define the unit state during 4^th time slot
Time 5*:*0:00..23:59Define the starting time of 5^th time slot
Value 5OffOff, On Setpoint 1, On Setpoint 2Define the unit state during 5^th time slot
Time 6*:*0:00..23:59Define the starting time of 6^th time slot
Value 6OffOff, On Setpoint 1, On Setpoint 2Define the unit state during 6^th time slot

4.2.11 Power Conservation

This page resumes all the settings that allows chiller capacity limitations. Further explanations of the setpoint reset options can be found in the chapter 7.2.

Setpoint/Sub-MenuDefaultRangeDescription
TZ/TZ BVZ
Unit Capacity=100.0%100.0%
Demand Lim En=DisableDisableDisable, EnableDemand Limit Enable
Demand Limit=100.0%100.0%Demand Limit Mode - Active demand limitation
Unit Current=0.0AE/M OnlyCurrent Limit Mode (optional) - Unit current reading
Current Limit=800A800ACurrent Limit Mode (optional) - Active Current limit

D-EOMZC00106-17EN

Operation Manual

26/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

Flex Current Lm=DisableDisableDisable, EnableFlexible Current Limit Enable
Current Lim Sp=800A800A0...2000ACurrent Limit Mode (optional) - Current limit setpoint
Setpoint Reset=NoneNoneNone, 4-20mA, Return, OATSetpoint Reset Type (OAT reset
Max Reset=5.0°C5.0°C0.0...10.0°CSetpoint Reset Mode - Max Reset of water temp. setpoint
Start Reset DT=5.0°C5.0°C0.0...10.0°CSetpoint Reset Mode - Evaporator DT at which no reset is applied
Max Reset OAT=15.5°CN/A10.0...29.4°CSetpoint Reset Mode - OAT at which the max reset is applied
Strt Reset OAT=23.8°CN/A10.0...29.4°CSetpoint Reset Mode - OAT at wich 0°C reset is applied
Softload En=DisableDisableDisable, EnableSoft Load Mode Enable
Softload Ramp=20min20min1...60minSoft Load Mode - Duration of the Softload ramp
Starting Cap=40.0%40.0%20.0...100.0%Soft Load Mode - Starting capacity limit for Softload

4.2.12 Controller IP setup

The Microtech ^ III controller has an embedded web server showing a replica of the onboard HMI screens. To access to this additional web HMI can be required to adjust the IP settings to match the settings of the local network. This can be done in this page. Please contact your IT department for further information on how to set the following setpoints.

To activate the new settings a reboot of the controller is required, this can be done with the Apply Changes setpoint.

The controller also supports DHCP, in this case the name of the controller must be used.

Setpoint/Sub-MenuDefaultRangeDescription
Apply Changes=NoNo, YesWhen Yes, it save changes made on settings and reboot the controller
DHCP=OffOff, OnWhen On, Enable DHCP to automatically obtain an IP address
Act IP=-Active IP address
Act Msk=-Active Subnet mask
Act Gwy=-Active Gateway
Gvn IP=-Given IP address (it will become the active)
Gvn Msk=-Given Subnet mask
Gvn Gwy=-Given Gateway
PrimDNS-Primary DNS
SecDNS-Secondary DNS
Name-Controller Name
MAC-Controller MAC Address

Check with IT Department on how to set these properties in order to connect the Microtech III to the local network.

4.2.13 Daikin on Site

This menu allows to the user to enable the communication with Daikin cloud DoS (Daikin on Site). This option requires that the controller has access to internet. Please contact your service organization for more details.

Setpoint/Sub-MenuDefaultRangeDescription
Comm Start=OffOff, StartCommand to enable the communication
Comm State=--Communication state.The communication is established only if this parameter displays Connected
IPErrInitInitRegRegRegErrDescrConnected
Cntrlr ID=--Controller ID. This parameter is helpful to identify the specific controller in DoS
Remote Update=DisableDisable,EnableAllow the application update from Daikin on Site.

4.2.14 Menu Password

It is possible to keep the User level always active to avoid to enter the User password. To do this the Password Disable setpoint shall be set to On.

Setpoint/Sub-MenuDefaultRangeDescription
Pwd DisableOffOff, OnMenu for Circuit #1
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 27/85

4.3 View/Set Circuit

In this section it is possible to select between the available circuits and access data available for the circuit selected.

Setpoint/Sub-MenuDefaultRangeDescription
Circuit #1Menu for Circuit #1
Circuit #2Menu for Circuit #2

The submenus accessed for each circuit are identical but the content of each of them reflects the status of the corresponding circuit. In the following the submenus will be explained only once. If only one circuit is available the item Circuit #2 in the above table will be hidden and not accessible.

Each of the above links will jump to the following submenu:

Setpoint/Sub-MenuDefaultDescription
DataThermodynamic data
CompressorStatus of the compressor and electrical data
CondenserStatus of the condenser fan regulation (A/C Only)
EXVStatus of the expansion valve regulation
EconomizerStatus of the economizer (A/C Only)
SettingsSettings

In any of the above submenus each item shows a value and a link to another page. In that page the same data will be represented for both circuits as a reference as shown in the below example.

Setpoint/Sub-MenuDefaultDescription
Comp 1 Run Hours-Indication of the data represented
Circuit #1=0hData related to Circuit #1
Circuit #2=0hData related to Circuit #2

4.3.1 Data

In this page all relevant thermodynamic data are displayed.

Setpoint/Sub-MenuDefaultRangeDescription
Circuit Status=Status of the circuit
Off:VFD HeatingOff: ReadyOff: Stage Up DelayOff: Cycle TimerOff: BAS DisableOff: Keypad DisableOff: Circuit SwitchOff: Oil HeatingOff: AlarmOff: Test ModeEXV PreopenRun: PumpdownRun: NormalRun: Disch SH LowRun: Evap Press LowRun: Cond Press HighRun: High LWT LimitRun: High VFD AmpsRun: High VFD TempOff: Max Comp StartsOff: VFD HeatingOff: Maintenance
Capacity=0.0%Circuit capacity
Evap Pressure=220.0kPaEvaporating Pressure
Cond Pressure=1000.0kPaCondensing Pressure
Suction Temp=5.0°CSuction Temperature
Discharge Temp=45.0°CDischarge Temperature
Suction SH=5.0°CSuction Superheat
Discharge SH=23.0°CDischarge Superheat
Oil Pressure=1000.0kPaOil Pressure
Oil Pr Diff=0.0kPaOil Pressure differential
EXV Position=50%Expansion valve position
Econ Sv Output=OffEconomizer status

D-EOMZC00106-17EN

Operation Manual

28/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

Setpoint/Sub-MenuDefaultRangeDescription
Liq Inj=OffLiquid Injection status
Variable VR St=Off(VR2)VR2 or VR3 slide position status
Evap LWT=7.0°CEvaporator LWT
Evap EWT=12.0°CEvaporator EWT

4.3.2 Compressor

This page resumes all the relevant information about compressor. In this page a manual adjustment of the compressor capacity will be possible.

Setpoint/Sub-MenuDefaultRangeDescription
TZ / TZ BVZTZ / TZ BVZ
Start=Date and time of the last start
Stop=Date and time of the last stop
Run Hours=0h0hRunning hours of compressor
No. Of Starts=00Number of compressor starts
Cycle Time Rem=0s0sRemaining cycle time left
Clear Cycle TimeOffOffOff,OnCycle time clear command
Capacity=100%100%Compressor capacity
Act Speed=5400rmpN/ACompressor speed (depends on model)
Feedback CapN/A0.0%
Current=200.0AN/AInverter current
Percent RLA=85%N/APercentage over the Full Load current
Power Input=0kWN/APower Input
DC Voltage0VN/ADC-Link Voltage
Cap Control=AutoAutoAuto, ManStepAuto,ManStep,ManSpdCapacity Control Mode
Manual Cap=0.0%0.0%0.0...100.0%Manual capacity percentage
VFD Temp=0°CN/AVFD Temperature
Vfd Valve Life=100%N/AInverter cooling SV remaining cycles
Vfd Capct Life=100%N/AInverter capacitors remaining life
Start VFD Spd=1800rpmN/ACompressor start speed
Max VFD Spd=5400rpmN/ACompressor maximum speed

4.3.3 Condenser (A/C only)

This page resumes all the relevant data and settings to adjust the condenser pressure control to fit the specific requirements for the operating conditions.

Setpoint/Sub-MenuDefaultRangeDescription
# Fans Running=0Number of fans currently running
# Of Fans=6Total number of fans
Stg Up Error=0Error to stage up one fan
Stg Dn Error=0Error to stage down one fan
Cond Sat Temp=0Saturated condensing temperature
Cond Target=30.0°CSaturated condenser temperature target
VFD Target=30.0°CTarget for the VFD (only for Vfd and Speedtroll)
VFD Speed=0.0%Current VFD Speed
Fan VFD Enable=EnableDisable, EnableEnable or disable Fan speed regulation
Stg On Db 0=4.0°CDead band for fan stage up #1
Stg On Db 1=5.0°CDead band for fan stage up #2
Stg On Db 2=5.5°CDead band for fan stage up #3
Stg On Db 3=6.0°CDead band for fan stage up #4
Stg On Db 4=6.5°CDead band for fan stage up #5
Stg On Db 5=6.5°CDead band for fan stage up #6
Stg Off Db 2=10.0°CDead band for fan stage down #2*
Stg Off Db 3=8.0°CDead band for fan stage down #3
Stg Off Db 4=5.5°CDead band for fan stage down #4
Stg Off Db 5=4.0°CDead band for fan stage down #5
Stg Off Db 6=4.0°CDead band for fan stage down #6
VFD Max Speed=700rpm500...700 rpmVFD maximum speed
VFD Min Speed=175rpm100...700 rpmVFD minimum speed

* last fan running stage down uses a fixed limit not accessible from the HMI.

EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 29/85

DAIKIN EWAD820TZSRB2 - Condenser (A/C only) - 1

Fan settings are set to have a good and stable control of the condenser saturated temperature in almost all operating conditions. Improper modification of the default settings could affect performances and generate circuit alarms. This action must be performed only by trained persons.

4.3.4 EXV

This page resumes all the relevant information about the status of the EXV logic.

Setpoint/Sub-MenuDefaultRangeDescription
TZ / TZ BVZ
EXV State=ClosedClosedClosed, Pressure, SuperheatEXV State
Suction SH=6.0°C6.0°CSuction Superheat
Superht Target=6.0°C6.0°CSuction Superheat setpoint
Press TargetN/A-
Evap Pressure=220kPa220kPaEvaporating Pressure
EXV Position=50.0%50.0%Expansion valve opening

4.3.5 Economizer (A/C only)

This page resumes all the relevant information about the data and the status of the economizer

Setpoint/Sub-MenuDefaultRangeDescription
Economizer=WithWithout, WithSetting to enable or disable the Economizer
Econ State=RegulationOff,Preopen, SSH, Liq InjEconomizer State
Econ EXV Pos=0%Economizer EXV opening
Econ SH=6.0°CEconomizer Superheat
Econ SH Tar=6.0°CActual calculated Economizer superheat target
Min EcoSH Tar=6.0°CMinimum Economizer superheat target
Econ Press=500kPaEconomizer Pressure
Econ Sat Temp=24°CEconomizer Saturated Temperature
Econ Temp=30°CEconomizer Temperature
Econ En Cap=1200rpmMinimum compressor speed to enable Economizer

4.3.6 Settings (A/C units only)

This page resumes the settings of the circuit.

Setpoint/Sub-MenuDefaultRangeDescription
Pumpdn Press=100kPa70...280kPaPumpdown pressure limit
Pumpdn Time=120s0...180sPumpdown timeout limit
Service Pumpdn=OffOff,OnActivation of the function service pumpdown
Liq Inject Act=90°C80...100°CDischarge Temperature limit to enable the liquid injection
Var VR Act PR=3.81.5...5Pressure Ratio threshold to activate VR3 slide position

4.3.7 Variable VR

This page contains present data of variable VR control.

Setpoint/Sub-MenuDescription
Press RatioPresent value of compressor pressure ratio
VR PositionPresent position of VR slide

4.4 Active Setpoint

This link jumps to the page "Tmp Setpoint". This page resumes all chiller water temperature setpoints (limits and active setpoint will depend on the operating mode selected).

Setpoint/Sub-MenuDefaultRangeDescription
TZ/TZ BVZ
Cool LWT 1=7.0°C7.0°C4.0...15.0°C (cool mode)-8.0...15.0°C (cool w/ glycol mode)Primary cooling setpoint
Cool LWT 2=7.0°C7.0°C4.0...15.0°C (cool mode)-8.0...15.0°C (cool w/ glycol mode)Secondary cooling setpoint (see 3.6.3)
Ice LWT=-4.0°C-4.0°C-8.0...4.0°CIce setpoint (ice banking with on/off mode)
Max LWT=15.0°C15.0°C10.0...20.0°CHigh limit for Cool LWT1 and Cool LWT2
Min LWT=-8.0°C-8.0°C-15.0...-8.0°CLow limit for Cool LWT1 and Cool LWT2
HR EWT Stp=40.0°CN/A30.0...50.0°CHeat Recovery Entering Water Setpoint

D-EOMZC00106-17EN

Operation Manual

30/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

HR EWT Dif=2.0°CN/A1.0...10.0°CHeat Recovery Water Temperature differential

4.5 Evaporator LWT

This link jumps to the page "Temperatures". This page resumes all the relevant water temperatures.

Setpoint/Sub-MenuDefaultRangeDescription
TZ/TZ BVZ
Evap LWT=-273.1°C-273.1°C-Controlled water temperature
Evap EWT=-273.1°C-273.1°C-Return water temperature
Cond LWT=N/A-273.1°C-Condenser leaving water temperature
Cond EWT=N/A-273.1°C-Condenser entering water temperature
Evap Delta T=-273.1°C-273.1°C-Delta T across Evaporator
Cond Delta T=N/A-273.1°C-Delta T across Condenser
Pulldn Rate0.0°C/minN/A-Rate of decrease of the controlled temperature
Ev LWT SlopeN/A0.0°C/min-Rate of decrease of the controlled temperature
Cd LWT SlopeN/A0.0°C/min-Rate of decrease of the condenser leaving water temperature
Outside Air=-273.1°CN/A-Outside air temperature
Act Slope Lim.N/A1.7 °C/minMaximum slopes
Switch Box T=-273.1°CN/A-Switch Box temperature
Common LWT=-273.1°C-273.1°C-Master Slave Common supply water temperature
HR LWT=-273.1°CN/A-Heat Recovery Leaving Water Temperature
HR EWT=-273.1°CN/A-Heat Recovery Entering Water Temperature

4.6 Condenser LWT (W/C Units only)

This link jumps to the page "Temperatures". See section 4.5 for detailed page content.

4.7 Unit Capacity

This page displays the actual unit and circuit capacity

Setpoint/Sub-MenuDefaultRangeDescription
Unit=--Actual unit capacity
Circuit #1=--Actual circuit 1 capacity
Circuit #2=--Actual circuit 2 capacity

4.8 Unit Mode

This item shows the present Operating Mode and jumps to the page for unit mode selection.

Setpoint/Sub-MenuDefaultRangeDescription
TZ / TZ BVZ
Available Modes=CoolCool, Cool w/ Glycol, Cool/Ice w/ Glycol, Ice w/ Glycol, TestCool, Cool w/ Glycol, Cool/Ice w/ Glycol, Ice w/ Glycol, Heat/Cool, Heat/Cool w/Glycol, Heat/Ice w/Glycol, Pursuit, TestAvailable operating modes

Depending on selected mode among availables, the Unit Mode on the main menu will assume the corresponding value according to the following table:

Available mode selectedOperating Mode
TZ/TZ BVZ
C/H Switch = CoolC/H Switch = Heat
CoolCoolCoolN/A
Cool w/ Glycol
Cool/Ice w/ Glycol
Ice w/ GlycolIceIce
Heat/CoolN/ACoolHeat
Heat/Cool w/Glycol
Heat/Ice w/GlycolIce
PursuitPursuit
TestTestTest
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 31/85

4.9 Unit Enable (A/C Units only)

This page allows to enable or disable unit and circuits. For the unit it also possible enable the operation with time scheduler, while for circuit it is possible to enable the test mode.

Setpoint/Sub-MenuDefaultRangeDescription
UnitEnableEnable, Disable, SchedulerUnit enable command
Circuit #1EnableEnable, Disable, TestCircuit #1 enable command
Circuit #2EnableEnable, Disable, TestCircuit #2 enable command

4.10 Timers

This page indicates the remaining cycle timers for each circuit and the remaining staging timers. When the cycle timers are active any new start of a compressor is inhibited.

Setpoint/Sub-MenuDefaultRangeDescription
C1 Cycle Tm Left=0s-Circuit 1 cycle timer
C2 Cycle Tm Left=0s-Circuit 2 cycle timer
C1 Cycle Tmr Clr=OffOff, OnClear circuit 1 cycle timer
C2 Cycle Tmr Clr=OffOff, OnClear circuit 2 cycle timer
Stg Up Dly Rem=0s-Remaining delay to next compressor start
Stg Dn Dly Rem=0s-Remaining delay to next compressor stop
Clr Stg Delays=OffOff, OnClear remaining delays to next compressor start/stop
Ice Cycle Rem=0min-Remaining Ice cycle delay
Clr Ice DlyOffOff, OnClear remaining delay for Ice mode

4.11 Alarms

This link jumps to the same page accessible with the Bell button. Each of the items represents a link to a page with different information. The information shown depends on the abnormal operating condition that caused the activation of unit, circuit or compressor safeties. A detailed description of the alarms and how to handle will be discussed in the section 6.

Setpoint/Sub-MenuDefaultDescription
Alarm ActiveList of the active alarms
Alarm LogHistory of all the alarms and acknowledges
Event LogList of the events
Alarm SnapshotList of alarm snapshots with all the relevant data recorded at time the alarm occurred.

4.12 Commission Unit

Setpoint/Sub-MenuDefaultRangeDescription
Alarms Limits-Submenu for alarm limits definition
Calibrate Sensors-Submenus for Unit and Circuit sensor calibration
Manual Control-Submenus for Unit and Circuit manual control
Scheduled Maintenance-Submenu for scheduled maintenance

4.12.1 Alarm Limits

This page contains all alarm limits, including low pressure alarm prevention thresholds. In order to ensure proper operation they have to be set manually according to the specific application.

Setpoint/Sub-MenuDefaultRangeDescription
TZ / TZ BVZ
Low Press Hold=180.0kPa200.0kPa0...310.0 kPaLow pressure safety limit to stop capacity increase
Low Press Unld=160.0kPa190.0kPa0...250.0 kPaLow pressure alarm prevention
Hi Oil Pr Dly=30s30s10...180sDelay for the High oil pressure difference alarm
Hi Oil Pr Diff=250kPa250kPa0.0...415.0kPaPressure drop for a clogged filter
Hi Disch Temp=110.0°C110.0°CMaximum discharge temperature limit
Hi Cond Pr Dly=5s5sDelay on the High pressure alarm from transducer
Lo Pr Ratio Dly=90s90sDelay on the low pressure ratio alarm
OAT Lockout=4.0°C4.0°CAir temperature operational limit
Strt Time Lim=60sN/ATime limit for the low ambient start
Evap Flw Proof=15sN/AFlow proof delay
Evp Rec Timeout=3minN/ARecirculating timeout before the alarm is raised
Evap Water Frz=2.2°C2.2°C-18.0...6.0 °CFreeze protection limit
Water Flw Proof=N/A15s5...15sFlow proof delay

D-EOMZC00106-17EN

Operation Manual

32/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

Water Rec Timeout=N/A3min1...10minRecirculating timeout before the alarm is raised
Low DSH Limit=12.0°C12.0°CMinimum acceptable discharge superheat
Gas Conc Lim=200ppm200ppmMaximum gas concentration limit
HP Sw Test C#1OffOffOn, Off. Enables to check operation of the high pressure switch on #1.
HP Sw Test C#2OffOffOn, Off. Enables to check operation of the high pressure switch on #2.
Ext Fault Cfg=EventN/AEvent, AlarmDefinition of the unit behavior after switching of external alarm contact

DAIKIN EWAD820TZSRB2 - Alarm Limits - 1

The HP Sw Test shuts off all fans while compressor is running in order to raise condenser pressure until tripping of the high pressure switches. Beware that in case of high pressure switch failure the safety valves will trip and hot refrigerant will be ejected at high pressure!

DAIKIN EWAD820TZSRB2 - Alarm Limits - 2

Once tripped, the software will get back to normal operation. However, the alarm will not be reset until the high pressure switches are manually reset through the button included in the switch.

4.12.2 Calibrate Sensors

Setpoint/Sub-MenuDefaultRangeDescription
Unit-Submenu for Unit calibrate sensor
Circuit #1-Submenu for Circuit 1 calibrate sensor
Circuit #2-Submenu for Circuit 2 calibrate sensor

4.12.2.1 Unit Calibrate Sensors

This page allows a proper calibration of the unit sensors

Setpoint/Sub-MenuDefaultRangeDescription
Evap LWT=7.0°CEvaporator LWT current reading (includes the offset)
Evp LWT Offset=0.0°CEvaporator LWT calibration
Evap EWT=12.0°CEvaporator EWT current reading (includes the offset)
Evp EWT Offset=0.0°CEvaporator EWT calibration
Outside Air=35.0°COutside Air Temperature current reading (includes the offset)
OAT Offset=0.0°COutside Air Temperature calibration
HR Ewt=40.0°CHeat Recovery EWT current reading (includes the offset)
HR Ewt Offset=0.0°CHeat Recovery EWT calibration
HR Lwt=45.0°CHeat Recovery LWT current reading (includes the offset)
HR Ewt Offset=0.0°CHeat Recovery LWT calibration
Switch Box T40.0°CSwitch Box Temperature current reading (includes the offset)
HR Ewt Offset=0.0°CSwitch Box Temperature calibration
Common LWT8°CCommon LWT current reading Includes the offset
Comm LWT Offset=0.0°CCommon LWT calibration

4.12.2.2 Circuit Calibrate Sensors

This page allows to adjust the sensors and transducers readings.

Setpoint/Sub-MenuDefaultRangeDescription
Evap Pressure=Evaporator Pressure current reading (includes the offset)
Evp Pr Offset=0.0kPaEvaporator Pressure offset
Cond Pressure=Condenser Pressure current reading (includes the offset)
Cnd Pr Offset=0.0kPaCondenser Pressure offset
Oil Pressure=Oil Pressure current reading (includes the offset)
Oil Pr Offset=0.0kPaOil Pressure offset
Suction Temp=Suction Temperature current reading (includes the offset)
Suction Offset=0.0°CSuction Temperature offset
Discharge Temp=Discharge Temperature current reading (includes the offset)
Disch Offset=0.0°CDischarge Temperature offset
Econ Pressure=Economizer Pressure current reading (includes the offset)
Eco Pr Offset=0.0kPaEconomizer Pressure offset
Econ Temp=Economizer Temperature current reading (includes the offset)
Eco Tmp Offset=0.0°CEconomizer Temperature offset

DAIKIN EWAD820TZSRB2 - Circuit Calibrate Sensors - 1

Calibrations of the Evaporator Pressure and Suction Temperature are mandatory for the applications with negative water temperature setpoints. These calibrations have to be performed with proper gauge and thermometer.

An improper calibration of the two instruments may generate limitation of the operations, alarms and even damages to components.

4.12.3 Manual Control

This page contains links to other sub-pages where all the actuators can be tested, the raw values of the readings of each sensor or transducer can be checked, the status of all the digital inputs verified and the status of all the digital output checked.

Setpoint/Sub-MenuDefaultRangeDescription
UnitAcutators and sensors for the common parts (Unit)
Circuit #1Acutators and sensors for Circuit #1
Circuit #2Acutators and sensors for Circuit #2

4.12.3.1 Unit

This page contains all the test point, status of the digital inputs, status of the digital output and raw value of the analog inputs associated to the Unit. To activate the test point it's required to set the Available Modes to Test (see section 4.8) and this requires the Unit to be disabled.

Setpoint/Sub-MenuDefaultRangeDescription
Test Unit Alarm Out=OffOff/OnTest of the General Alarm relay output
Test C1 Alarm Out=OffOff/OnTest of the Circuit #1 Alarm relay output
Test C2 Alarm Out=OffOff/OnTest of the Circuit #2 Alarm relay output
Test Evap Pump 1=OffOff/OnTest of the Evaporator Pump #1
Test Evap Pump 2=OffOff/OnTest of the Evaporator Pump #2
Test HR Pmp=OffOff/OnTest of the Heat Recovery Pump
Test Bypass Vlv=OffOff/OnTest of the Bypass Valve
Test Pmp Spd=0%0-100%Test of the Evaporator Pump Speed
Input/Output ValuesOff/On
Unit Sw Inpt=OffOff/OnStatus of the Unit Switch
Estop Inpt=OffOff/OnStatus of the Emergency Stop button
PVM Inpt=OffOff/OnStatus of Phase Voltage monitor, Under-Over voltage protection or Ground Fault protection (check option installed)
Evap Flow Inpt=OffOff/OnStatus of the Evaporator Flow switch
Ext Alm Inpt=OffOff/OnStatus of the External Alarm input
CurrLm En Inpt=OffOff/OnStatus of the Current Limit enable switch (optional)
Dbl Spt Inpt=OffOff/OnStatus of the Double Setpoint switch
Dbl Speed Inpt=OffOff/OnStatus of the pump Double Speed Switch
RR Unlock Inpt=OffOff/OnStatus of the Rapid Restart enable switch (optional)
HR Switch Inpt=OffOff/OnStatus of the Heat Recovery Switch input
Loc Bas Inpt=OffOff/OnStatus of the Local Network Switch input

D-EOMZC00106-17EN

Operation Manual

34/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

Setpoint/Sub-MenuDefaultRangeDescription
Battery Inpt=OffOff/OnStatus of the Battery Mode input
Evp LWT Res=0Ohm340-300kOhmResistance of the Evaporator LWT sensor
Evp EWT Res=0Ohm340-300kOhmResistance of the Evaporator EWT sensor
OA Temp Res=0Ohm340-300kOhmResistance of the OAT sensor
HR Ewt Res=0Ohm340-300kOhmResistance of the Heat Recovery EWT sensor
HR Lwt Res=0Ohm340-300kOhmResistance of the Heat Recovery LWT sensor
SwBox Tmp Res=0Ohm340-300kOhmResistance of the Switch Box Temperature sensor
Common LWT Res=0Ohm340-300kOhmResistance of the Common LWT sensor
LWT Reset Curr=0mA3-21mACurrent input for the Setpoint Reset
Dem Lim Curr=0mA3-21mACurrent input for the Demand Limit
Flex Curr Lim=0mA3-21mACurrent input for the Flex Current Limit
Load PD Raw=0V-0mA0-10V/4-20mAVoltage/Current input for the Load Pressure Drop sensor
Evap PD Volt=0V0-10VVoltage Input for the Evaporator Pressure Drop sensor
Unit Alm Outpt=OffOff/OnStatus of the General Alarm relay
C1 Alm Outpt=OffOff/OnStatus of the Circuit #1 Alarm relay
C2 Alm Outpt=OffOff/OnStatus of the Circuit #2 Alarm relay
Evp Pmp1 Outpt=OffOff/OnStatus of the Evaporator Pump #1 relay
Evp Pmp2 Outpt=OffOff/OnStatus of the Evaporator Pump #2 relay
HR Pmp Outpt=OffOff/OnStatus of the Heat Recovery Pump relay
Bypass Vlv Outpt=0V0-10VStatus of the Bypass Valve
Pump Speed Outpt=0V0-10VVoltage signal for the pump VFD

4.12.3.2 Circuit #1 (Circuit #2 if present)

This page contains all the test point, status of the digital inputs, status of the digital output and raw value of the analog inputs associated to the Circuit #1 (or Circuit #2 if present and depending on the link followed). To activate the test point it's required to set the Available Modes to Test (see section 4.8) and this requires the Unit to be disabled.

Setpoint/Sub-MenuDefaultRangeDescription
Test Liq Inj=OffOff/OnTest of the Liquid Injection SV
Test Economizr=OffOff/OnTest of the Economizer SV
Test Fan 1=OffOff/OnTest of the Fan Output #1
Test Fan 2=OffOff/OnTest of the Fan Output #2
Test Fan 3=OffOff/OnTest of the Fan Output #3
Test Fan 4=OffOff/OnTest of the Fan Output #4
Test Fan 5=OffOff/OnTest of the Fan Output #5
Test Fan 6=OffOff/OnTest of the Fan Output #6
Test Var VR=OffOff/OnTest of VR3 slide position
Test VR Load=OffOff/OnTest of VR Load relay (VR3)
Test VR Unld=OffOff/OnTest of VR Unload relay (VR2)
Test VFD Speed=0%0-100%Test of the VFD for fans
Test EXV Pos=0%0-100%Test of the Expansion Valve movements
Test EcoEXV Pos=0%0-100%Test Of the Economizer Expansion Valve movements
Input/Output Values
Cir Sw Inpt=OffOff/OnStatus of the Circuit Enable switch
Mhp Sw Inpt=OffOff/OnStatus of the Mechanical High Pressure switch
Gas Leak Inpt=OffOff/OnStatus of the Gas Leak switch
Fan Alm Inpt=OffOff/OnStatus of the Fan Alarm Input
Evap Pr Inpt=0.0V0.4-4.6VInput voltage for the Evaporator Pressure
Cond Pr Inpt=0.0V0.4-4.6VInput voltage for the Condenser Pressure
Oil Pr Inpt=0.0V0.4-4.6VInput voltage for the Oil Pressure
Gas Leak Inpt=0.0V0.0-10.0VInput voltage for the Gas Leak sensor
Econ Pr Inpt=0.0V0.4-4.6VInput voltage for the Economizer Pressure
Econ Temp Res=0.0Ohm340-300kOhmResistance of the Economizer Temp sensor
Suct Temp Res=0.0Ohm340-300kOhmResistance of the Suction Temp sensor
Disc Temp Res=0.0Ohm340-300kOhmResistance of the Discharge Temp sensor
Strtr Outpt=OffOff/OnStatus of the Inverter start command
Liq Inj Outpt=OffOff/OnStatus of the Liquid Line SV relay
Econ Sv Outpt=OffOff/OnStatus of the Economizer SV relay
Fan 1 Outpt=OffOff/OnStatus of the Fan Output #1
Fan 2 Outpt=OffOff/OnStatus of the Fan Output #2
Fan 3 Outpt=OffOff/OnStatus of the Fan Output #3
Fan 4 Outpt=OffOff/OnStatus of the Fan Output #4
Fan Vfd Outpt=0.0V0-10.0VOutput voltage to the fan VFD
Variable VR StOff(VR2)Off(VR2)/On(VR3)Variable VR slide position (VR2, VR3)

4.12.4 Scheduled Maintenance

This page may contains the contact number of the Service organization taking care of this unit and the next maintenance visit schedule.

Setpoint/Sub-MenuDefaultRangeDescription
Next Maint=Jan 2015Schedule date for next maintenance
Support Reference=999-999-999Reference number or email of Service Org

4.13 About this Chiller

This page resumes all the information needed to identify the unit and the current software version installed. These information may be required in case of alarms or unit failure

Setpoint/Sub-MenuDefaultRangeDescription
ModelUnit model and code name
Unit S/N=Unit serial number
OV14-00001
BSP Ver=Firmware version
App Ver=Software version

5 WORKING WITH THIS UNIT

This section contains a guide on how to deal with the everyday usage of the unit. Next sections describe how to perform routine tasks on the unit, such as:

  • Unit Setup
  • Unit/Circuit start-up
  • Alarm handling
  • BMS Control
  • Battery replacement

5.1 Unit Setup

Before starting up the unit, some basic settings need to be set by the customer according to the application.

• Control Source (4.2.2)
• Available Modes (4.8)
• Temperature Settings (5.1.3)
• Alarm Settings (5.1.4)
- Pump Settings (5.1.5)
• Power Conservation (4.2.7)
- Date/Time (4.2.5)
- Scheduler (4.2.6)

5.1.1 Control Source

This function allows to select which source should be used for unit control. The following sources are available:

LocalUnit is enabled by local switches placed into the switchbox, chiller mode (cool, cool w/glycol, ice), LWT setpoint and capacity limit are determined by local settings in the HMI.
NetworkUnit is enable by a remote switch, chiller mode, LWT setpoint and capacity limit are determined by an external BMS. This function requires:Remote enable connection to a BMS (unit on/off switch must be in remote)Communication module and its connection to a BMS.

More parameters about network control can be found in 4.2.2.

5.1.2 Available Mode Setting

The following operating modes can be selected through the Available modes menu 4.8:

ModeDescriptionUnit Range
CoolSet if chilled water temperature up to 4°C is required. No glycol is generally needed in the water circuit, unless ambient temperature may reach low values.A/C and W/C
Cool w/GlycolSet if chilled water temperature below 4°C is required. This operation requires proper glycol/water mixture in the evaporator water circuit.A/C and W/C
Cool/Ice w/GlycolSet in case a dual cool/ice mode is required. This setting implies an operation with double setpoint which is activated through a customer supplied switch, according to the following logic:Switch OFF: The chiller will work in cooling mode with the Cool LWT 1 being as the Active SetpointSwitch ON: The chiller will work in ice mode with the Ice LWT as the Active Setpoint.A/C and W/C
Ice w/GlycolSet if ice storage is required. The application requires the compressors to operate at full load until the ice bank is completed, and then to stop for at least 12 hours. In this mode the compressor(s) will not operate at part load, but will work only in on/off mode.A/C and W/C

DAIKIN EWAD820TZSRB2 - Available Mode Setting - 1

The following modes allow to switch the unit between heat mode and one of the previous cool mode (Cool, Cool w/Glycol, Ice)

Heat/CoolSet in case a dual cool/heat mode is required. This setting implies an operation with double functioning which is activated through the Cool/Heat switch on the electric boxSwitch COOL: The chiller will work in cooling mode with the Cool LWT 1 as the Active Setpoint.Switch HEAT: The chiller will work in heat pump mode with the Heat LWT 1 as the Active Setpoint.W/C
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 37/85
ModeDescriptionUnit Range
Heat/Cool w/GlycolSet in case a dual cool/heat mode is required. This setting implies an operation with double functioning which is activated through the Cool/Heat switch on the electric boxSwitch COOL: The chiller will work in cooling mode with the Cool LWT 1 as the Active Setpoint.Switch HEAT: The chiller will work in heat pump mode with the Heat LWT 1 as the Active SetpointW/C
Heat/Ice w/GlycolSet in case a dual cool/heat mode is required. This setting implies an operation with double functioning which is activated through the Cool/Heat switch on the electric boxSwitch ICE: The chiller will work in cooling mode with the Ice LWT as the Active Setpoint.Switch HEAT: The chiller will work in heat pump mode with the Heat LWT 1 as the Active Setpoint.W/C
PursuitSet in case of double water control cool and contemporary heat. Evaporator leaving water temperature follows the Cool LWT 1 setpoint. Condenser leaving water temperature follows the Heat LWT 1 setpoint.W/C
TestEnables the Manual Control of the unit. The manual test feature helps in debugging and checking the operational status of sensors and actuators. This feature is accessible only with the maintenance password in the main menu. To activate the test feature is required to disable the Unit from the Q0 switch and change the available mode to Test (see section 5.2.2).A/C and W/C

5.1.3 Temperature Settings

Purpose of the unit is to keep the evaporator leaving water temperature as close as possible to a pre-set value, called Active Setpoint. The Active Setpoint is calculated by the unit controller based on the following parameters:

• Available Modes
- Double setpoint input
- Scheduler state
- LWT Setpoint
- Setpoint Reset
- Quiet Mode (A/C units only)

Operation mode and LWT setpoint can also be set via network if the appropriate control source has been selected.

5.1.3.1 LWT Setpoint Setting

Setpoint range is limited according to the selected operating mode. The controller includes:

  • two set points in heating mode (W/C units only))
  • one set point in ice mode

- two set points in cooling mode (either standard cool or cool w/glycol)

The above setpoints are activated according to Operating mode, Double Setpoint or Scheduler selection. If the Time Scheduler is enabled the Double Setpoint input state will be ignored by the controller.

The table below lists the LWT Setpoint being activated according to the operation mode, the double setpoint switch status and the scheduler state. The table also reports the defaults and the range allowed for each setpoint.

Operating ModeUnitsDouble Setpoint InputSchedulerLWT SetpointDefaultRange
CoolA/C W/COFFOff, On Setpoint 1Cool LWT 17.0°C4.0°C ÷ 15.0°C
ONOn Setpoint 2Cool LWT 27.0°C4.0°C ÷ 15.0°C
IceA/C W/CN/AN/AIce LWT-4.0°C-8.0°C ÷ 4.0°C
HeatW/COFFOff, On Setpoint 1Heat LWT 145.0°C30.0°C ÷ 60.0°C(*)
ONOn Setpoint 2Heat LWT 245.0°C30.0°C ÷ 60.0°C(*)

(*) 30.0°C ÷ 65.0 for HT unit type

The LWT setpoint can be overridden in case the setpoint reset (for details see chapter 5.1.5.3) or the quiet mode are activated (see chapter 5.1.6.2).

D-EOMZC00106-17EN

Operation Manual

38/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

DAIKIN EWAD820TZSRB2 - LWT Setpoint Setting - 1

Double Setpoint, Setpoint Reset and Quiet Mode are not operational in Ice Mode.

5.1.3.2 Thermostat Control Settings

Thermostat control settings, allows to set up the response to temperature variations and the precision of the thermostat control. Default settings are valid for most applications, however site specific conditions may require adjustments in order to have a smooth and precise temperature control or a quicker response of the unit.

The control will start the first circuit if the controlled temperature is higher (Cool Mode) or lower (Heat Mode) than the active setpoint (AS) of at least a Start Up DT (SU) value. Once circuit capacity exceeds the Hi Ld Stg Up % another circuit is switched on. When controlled temperature is within the deadband (DB) error from the active setpoint (AS), unit capacity will not be changed.

If the leaving water temperature decreases below (Cool Mode) or rises above (Heat Mode) the active setpoint (AS), unit capacity is adjusted to keep it stable. A further decreasing (Cool Mode) or increasing (Heat Mode) of the controlled temperature of the Shut Down DT offset (SD) can cause circuit shutdown.

In the Shutdown area the whole unit is switched off. In particular, a compressor will be shut down if it is required to unload below the Lt Ld Stg Dn % capacity.

Loading and unloading speeds are calculated by a proprietary PID algorithm. However, maximum the rate of water temperature decrease can be limited through the parameter Max Pulldn.

DAIKIN EWAD820TZSRB2 - Thermostat Control Settings - 1

Circuits are always started and stopped to guarantee the balancing of running hours and number or starts in multiple circuits units. This strategy optimizes the lifetime of compressors, inverters, capacitors and all the others circuit components.

DAIKIN EWAD820TZSRB2 - Thermostat Control Settings - 2

line | Phase | Temperature Level | | ---------------------- | ----------------- | | AS+S | High | | Capacity Load Up | Peak | | Capacity Unload | Low | | AS-SD | Baseline |

DAIKIN EWAD820TZSRB2 - Thermostat Control Settings - 3

line | Phase | Temperature Level | | ------------------ | ----------------- | | AS+S | - | | DB | - | | Capacity | Peak | | Capacity load up | Low | | AS-SU | - |

5.1.4 Alarm Settings

If glycol is present in the water circuits, factory defaults values for the Alarm Limits listed below must be adjusted:

ParameterDescription
Low Press HoldSet the minimum refrigerant pressure of the unit. It is generally recommended to set to a value whose saturated temperature is 8 to 10^ below the minimum active setpoint. This will allow a safe operation and a proper control of compressor suction superheat.
Low Press UnloadSet lower than the hold threshold enough to allow a suction pressure recovery from fast transients without unloading the compressor. A 20 kPa differential is generally appropriate for most applications.
Evap Water FrzStops the unit in case the leaving temperature falls below a given threshold. To allow a safe operation of the chiller, this setting must be adequate to the minimum temperature allowed by the mixture water/glycol present in the evaporator water circuit.
Cond Water Frz (W/C units only)Stops the unit in case the leaving temperature falls below a given threshold. To allow a safe operation of the chiller, this setting must be adequate to the minimum temperature allowed by the mixture water/glycol present in the condenser water circuit.

DAIKIN EWAD820TZSRB2 - Alarm Settings - 1

When glycol is used in the plant, always disconnect antifreeze electric heater.

5.1.4.1 Pumps

The UC can manages one or two water pumps for both evaporator and, for W/C units, condenser. Number of pumps and their priority can be set from the menu in 4.2.4.

The following options are available to control the pump(s):

#1 OnlySet to this in case of single pump or twin pump with only #1 operational (f.e. in case of maintenance on #2)
#2 OnlySet to this in case of twin pump with only #2 operational (f.e. in case of maintenance on #1)
AutoSet for automatic pump start management. At each chiller start, the pump with the least number of hours will be activated.
#1 PrimarySet to this in case of twin pump with #1 running and #2 as a backup
#2 PrimarySet to this in case of twin pump with #2 running and #1 as a backup

5.1.5 Power Conservation

Demand limit function allows the unit to be limited to a specified maximum load. Capacity limit level is defined with an external 4-20 mA signal and linear relationship. 4 mA indicate maximum capacity available whereas 20 mA indicates minimum capacity available.

With demand limit function is not possible shutdown the unit but only unload it until minimum admissible capacity. Demand limit related setpoints available through this menu are listed in the table below.

D-EOMZC00106-17EN

Operation Manual

40/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

DAIKIN EWAD820TZSRB2 - Power Conservation - 1

line | Demand Limit [mA] | Capacity Limit [%] | |---|---| | 4 | Maximum Capacity | | 20 | Minimum Capacity |
ParameterDescription
Unit CapacityDisplays current unit capacity
Demand Limit EnEnables demand limit
Demand LimitDisplays active demand limit

5.1.5.2 Current Limit (Optional)

Current limit function allows to control unit power consumption taking current drawn below a specific limit. Starting from the Current Limit Setpoint defined through the HMI or BAS communication, user can decrease the real limit using an external 4-20mA signal as indicate in the graph below. With 20 mA real current limit is set to Current Limit Setpoint, whereas with 4 mA signal the unit is unloaded until minimum capacity.

DAIKIN EWAD820TZSRB2 - Current Limit (Optional) - 1

line | Flexible Current Limit [mA] | Current Limit [A] | | --------------------------- | ----------------- | | 4 | 0 | | 20 | 20 |

5.1.5.3 Setpoint Reset

The setpoint reset function overrides the chilled water temperature selected through the interface, when certain circumstances occur. This feature helps in reducing energy consumption optimizing comfort as well. Three different control strategies can be selected:

  • Setpoint Reset by Outside Air Temperature (OAT)
  • Setpoint Reset by an external signal (4-20mA)
  • Setpoint Reset by Evaporator T (Return)

The following setpoints are available through this menu:

ParameterDescription
Setpoint ResetSet the Setpoint Reset mode (None, 4-20 mA, Return, OAT)
Max ResetMax Setpoint Reset (valid for all active modes)
Start Reset DTUsed on Setpoint Reset by Evaporator DT
Max Reset OATSee Setpoint Reset by OAT Reset
Strt Reset OATSee Setpoint Reset by OAT Reset

5.1.5.4 Setpoint Reset by OAT Reset (A/C units only)

The active setpoint is calculated applying a correction which is a function of ambient temperature (OAT). As temperature drops below the Start Reset OAT (SROAT), LWT setpoint is gradually increased until OAT

EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 41/85

reaches the Max Reset OAT value (MROAT). Beyond this value, the LWT setpoint is increased by the Max Reset (MR) value.

DAIKIN EWAD820TZSRB2 - Setpoint Reset by OAT Reset (A/C units only) - 1

line | OAT | A | | ------ | ----- | | MROAT | 1 | | SROAT | 0 |
ParameterDefaultRange
Max Reset (MR)5.0°C0.0°C ÷ 10.0°C
Max Reset OAT (MROAT)15.5°C10.0°C ÷29.4°C
Start Reset OAT(SROAT)23.8°C10.0°C ÷29.4°C
Active Setpoint (AS)
LWT Setpoint (LWT SP)Cool/Ice LWT

5.1.5.5 Setpoint Reset by External 4-20 mA Signal

The active setpoint is calculated applying a correction based on an external 4-20mA signal. 4 mA corresponds to 0°C correction, while 20 mA corresponds to a correction of the active setpoint as set in Max Reset (MR).

DAIKIN EWAD820TZSRB2 - Setpoint Reset by External 4-20 mA Signal - 1

line | Signal | AS | |--------|--------| | 0 | LWT SP | | 4mA | LWT SP | | 20mA | LWT SP + MR |
ParameterDefaultRange
Max Reset (MR)5.0°C0.0°C ÷ 10.0°C
Active Setpoint (AS)
LWT Setpoint (LWT SP)Cool/Ice LWT
Signal4-20mA External signal

5.1.5.6 Setpoint Reset by Evaporator Return Temperature

The active setpoint is calculated applying a correction that depends on the evaporator entering (return) water temperature. As evaporator T becomes lower than the SR T value, an offset to the LWT setpoint is increasingly applied, up to the MR value when the return temperature reaches the chilled water temperature.

DAIKIN EWAD820TZSRB2 - Setpoint Reset by Evaporator Return Temperature - 1

The Return Reset may affect negatively the chiller operation when operated with variable flow. Avoid to use this strategy in case of inverter water flow control.

D-EOMZC00106-17EN

Operation Manual

42/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

DAIKIN EWAD820TZSRB2 - Setpoint Reset by Evaporator Return Temperature - 2

line | SRΔT | AS | |------|----| | 0 | AS | | >SRΔT | 0 |
ParameterDefaultRange
Max Reset (MR)5.0°C0.0°C ÷ 10.0°C
Start Reset DT (SRΔT)5.0°C0.0°C ÷ 10.0°C
Active Setpoint (AS)
LWT Target (LWT SP)Cool/Ice LWT

5.1.5.7 Soft Load

Soft Loading is a configurable function used to ramp up the unit capacity over a given time period, usually used to influence building electrical demand by gradually loading the unit. The setpoints that control this function are:

ParameterDescription
Softload EnEnables soft loading
Softload RampDuration of the soft load ramp
Starting CapBegin capacity limit. Unit will increase capacity from this value to 100% over the time specified by the Softload Ramp setpoint.

5.1.6 Date/Time

5.1.6.1 Date, Time and UTC Settings

See 4.2.5.

5.1.6.2 Quiet Mode Scheduling (A/C units only)

The Quiet Mode can be used to reduce chiller noise in certain hours of the day when noise reduction is more important than cooling operation, like for example in night time. When Quiet Mode is activated, the LWT setpoint is increased by the maximum setpoint reset (MR) described in the chapter "Setpoint Reset", thus forcing a capacity limitation to the unit without losing control on chilled water temperature. Also, condenser temperature target is increased by a value set in "QM Cond Offset". In this way condenser fans are forced to reduce speed without losing control on condensation. Quiet mode is timer enabled.

DAIKIN EWAD820TZSRB2 - Quiet Mode Scheduling (A/C units only) - 1

The Quiet Mode may affect negatively chiller efficiency due to the increased condenser setpoint
DAIKIN EWAD820TZSRB2 - Quiet Mode Scheduling (A/C units only) - 2

line | Time | CP SP + CO | CP SP | LWT SP + MR | LWT SP | |-------|------------|-------|-------------|--------| | 0 | High | High | Low | Low | | QMS | High | High | Low | Low | | QME | High | High | Low | Low |
ParameterDefaultRange
Quiet ModeDisableDisable, Enable
QM Start Hr (QMS)21h0...24h
QM Start Min0min0...60min
QM End Hr (QME)6h0...24h
QM End Min0min0...60min
QM Cond Offset (CO)5°C0...10°C

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and heat pump

D-EOMZC00106-17EN

Operation Manual 43/85

5.1.7 Scheduler

Unit On/Off can be managed automatically through the function Time Scheduler enabled when the parameter Unit Enable is set to Scheduler 0. For each day of the week user can define six time slots and choose for each time slot one of following mode:

ParameterDescription
OffUnit Off
On Setpoint 1Unit On and Cool LWT 1 is the active setpoint
On Setpoint 2Unit On and Cool LWT 2 is the active setpoint

5.2 Unit/Circuit Start-up

In this section, starting and stopping sequence of the unit will be described. status will be briefly described to allow a better understanding of what is going on into the chiller control.

5.2.1 Unit Status

One of the texts strings listed in the table below will inform, on the HMI, about the Unit Status.

Overall StatusStatus textDescription
Off:Keypad DisableThe Unit has been disabled by keypad. Check with your local maintenance if it can be enabled.
Loc/Rem SwitchThe Local/Remote enable switch is set to disable. Turn it to Local to enable the unit to start its starting sequence.
BAS DisableUnit is disabled by BAS/BMS system. Check with the BAS company how to start the unit.
Master DisableUnit is disabled by the Master Slave function
Scheduler DisabledUnit is disabled by the time scheduler.
Unit AlarmA unit alarm is active. Check the alarm list to see what is the active alarm inhibiting the unit to start and check if the alarm can be cleared. Refer to section 6. before proceeding.
Test ModeUnit mode set to Test. This mode is activated to check operability of onboard actuators and sensors. Check with the local maintenance if the Mode can be reverted to the one compatible with unit application (View/Set Unit – Set-Up – Available Modes).
All Cir DisabledNo circuit is available to run. All circuits can be disabled by their individual enable switch or can be disabled by a component safety condition active or can be disabled by keypad or can be all in alarms. Check the individual circuit status for further details.
Ice Mode TmrThis status can be shown only if the unit can work in Ice Mode. The unit is off because the Ice setpoint has been satisfied. Unit will remain off until the Ice Timer has expired.
OAT Lockout (A/C units only)The unit cannot run because the Oustide Air Temperature is below the limit foreseen for the condenser temperature control system installed in this Unit. If the Unit has to run anyway check with your local maintenance how to proceed.
AutoUnit is in Auto control. The pump is running and at least one compressor is running.
Auto:Evap RecircUnit is running the evaporator pump to equalize the water temperature in the evaporator.
Wait For FlowUnit pump is running but the flow signal still indicate a lack of flow through the evaporator.
Wait For LoadUnit is in standby because the thermostat control satisfied the active setpoint.
Unit Cap LimitDemand limit has been hit. Unit capacity will not further increase.
Current LimitMaximum current has been hit. Unit capacity will not further increase.
Noise ReductionUnit is running with the Quiet Mode activated. Active setpoint may differ from what has been set as cooling setpoint.
Max PulldnUnit thermostat control is limiting the unit capacity because the water temperature is dropping at a rate that could exceed the active setpoint.
PumpdnUnit is shutting down.

5.2.2 Prepare the unit to start

The unit starts only if all the enable setpoints/signals are active:

  • Unit Switch Enable (signal) = Enable
  • Keypad Enable (setpoint) = Enable
    • BMS Enable (setpoint) = Enable

5.2.2.1 Unit Switch Enable (A/C units only)

Each unit is equipped with a Main selector installed outside the front panel of the unit switchbox. As shown in the pictures below, for TZ and TZ B units three different positions can be selected: Local, Disable, Remote:

D-EOMZC00106-17EN

Operation Manual

44/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

DAIKIN EWAD820TZSRB2 - Unit Switch Enable (A/C units only) - 1

Local With the Q0 switch in this position the unit is enabled. Pump will start if all other enable signals are set to enable and at least one compressor is available to run

DAIKIN EWAD820TZSRB2 - Unit Switch Enable (A/C units only) - 2

Disable With the Q0 switch in this position the unit is disabled. Pump will not start in normal operational condition. Compressor are kept disabled independently from the status of the individual enable switches.

DAIKIN EWAD820TZSRB2 - Unit Switch Enable (A/C units only) - 3

Remote With the Q0 switch in this position the unit can be enabled using the additional connections available on the connection terminals. A closed loop will identify an enable signal, this can come from a remote switch or a timer by example.

5.2.2.2 Unit Switch Enable (W/C units only)

Each unit is equipped with a Main selector installed outside the front panel of the unit switchbox. As shown in the pictures below, for VZ units, two different positions can be selected: Local, Disable:

DAIKIN EWAD820TZSRB2 - Unit Switch Enable (W/C units only) - 1

Local With the Q0 switch in this position the unit is enabled. Pump will start if all other enable signals are set to enable and at least one compressor is available to run

DAIKIN EWAD820TZSRB2 - Unit Switch Enable (W/C units only) - 2

Disable With the Q0 switch in this position the unit is disabled. Pump will not start in normal operational condition. Compressor are kept disabled independently from the status of the individual enable switches.

5.2.2.3 Keypad Enable

The Keypad enable setpoint is not accessible by user password level. If it is set to "Disable", contact your local maintenance service to check if it can be changed to Enable.

5.2.2.1 BMS Enable

The last enable signal is coming through the high level interface, that is from a Building Management System. The unit can be enabled/disabled from a BMS connected to the UC using a communication protocol. In order to control the unit over the network, the Control Source setpoint must be turned in "Network" (default is Local) and Network En Sp must be "Enable"(4.2.2). If disabled, check with your BAS company how the chiller is operated.

5.2.3 Unit Start sequence

As soon as the unit is ready to start and then its status turns to Auto, begins the main steps indicated in the following simplified flowchart:

EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 45/85

DAIKIN EWAD820TZSRB2 - Unit Start sequence - 1

flowchart
graph TD
    A["Start"] --> B{Decision}
    B --> C["Process"]
    C --> D{Decision}
    D --> E["Process"]
    E --> F{Decision}
    F --> G["End"]
    B -->|N| H["Loop Back"]
    D -->|N| I["Loop Back"]
    F -->|N| J["Loop Back"]

Is there any compressor available?

Start the Pump

Is Flow established?

Start Lead compressor

Is more capacity needed?

Start Lag compressor

Thermostat Capacity control

5.2.4 Circuit Status

One of the texts strings listed in the table below will inform, on the HMI, about the Circuit Status.

Overall StatusStatusDescription
Off:ReadyCircuit is off waiting for a stage up signal from thermostat control
Stage Up DelayCircuit is off waiting for the stage up delay to expire.
Cycle TimerCircuit is off waiting for the compressor cycle timer to expire
BAS DisableCircuit is off by BAS signal. Check with the BAS company how to start the unit.
Keypad DisableCircuit is off by the local or remote HMI. Check with your local maintenance if it can be enabled.
Circuit SwitchCircuit is off by Enable switch. Turn the Enable switch to 1 to allow the circuit start up procedure to start
Oil HeatingCircuit is off because the oil temperature is too low to guarantee a proper lubrication of compressor. Heating resistor is activated to eliminate this temporary condition. It's suggested to power up the unit in advance to avoid this limiting condition.
AlarmA circuit alarm is active. Check the alarm list to see what is the active alarm inhibiting the circuit to start and check if the alarm can be cleared. Refer to section 6.before proceeding.
Test ModeCircuit mode set to Test. This mode is activated to check operability of onboard circuit actuators and sensors. Check with the local maintenance if the Mode can be reverted to Enable.
Max Comp StartsCompressor starts exceed the maximum number of starts per hour.
VFD HeatingInverter on compressor cannot start because of low internal temperature. Heating resistor is activated to eliminate this temporary condition. It's suggested to power up the unit in advance to avoid this limiting condition.
MaintenanceA component needs to be replaced or maintained. Refer to section 6.before proceeding.
EXVPreopenEXV prepositioning before compressor starts.
Run:PumpdownCircuit is shutting down because of thermostat control or pumpdown alarm or because the enable switch has been turned to off.
NormalCircuit is running within the expected operational conditions.
Disch SH LowDischarge superheat is below the acceptable value. This is a temporary condition that should disappear after few minutes of operation.
Evap Press LowCircuit is running with low evaporator pressure. This could be due to a transitory condition or a lack of refrigerant. Check with the local maintenance if corrective actions are required. Circuit is protected by preventive logic.
Cond Press HighCircuit is running with high condenser pressure. This could be due to a transitory condition or high ambient temperature or problems with the condenser fans. Check with the local maintenance if corrective actions are required. Circuit will be protected by preventive logic.
High LWT LimitCircuit is running with a high water temperature. This is a temporary condition that will limit the maximum compressor capacity. Reduction of the water temperature will allow the compressor to reach the full capacity.
High VFD AmpsInverter current is higher than the maximum allowed current. Preventive logic will protect the inverter.

5.2.5 Circuits start sequence

To allow a circuit start up is required to enable the circuit using the enable switch located on the unit switchbox. Each circuit is equipped with a dedicated switch identified with Q1, Q2 (if available) or Q3 (if available). The enable position is indicated with a 1 on the label whereas the 0 position corresponds to disable.

The status of the circuit is indicated in the View/Set Circuit – Circuit #x – Status/Settings. The possible status will be described in the following table.

If the circuit is allowed to start, the starting sequence is initiated. Starting sequence is described in a simplified version with the further flowchart.

EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 47/85

DAIKIN EWAD820TZSRB2 - Circuits start sequence - 1

flowchart
graph TD
    A["Start"] --> B{Condition}
    B -->|N| C["Is the circuit required to start?"]
    B --> D["Valve preopening"]
    D --> E["Compressor start"]
    E --> F["Wait thermostat command"]
    F --> G{Condition}
    G -->|N| H["Adjust capacity"]
    G --> I["Shutdown signal for thermostat or alarm?"]
    I --> J["Pumpdown of circuit then switch compressor off"]
    H --> K["End"]
    J --> K

5.2.6 High Water Temperature Limit (A/C units only)

The only prevention that can activate at unit level will limit the maximum unit capacity to 80% when the leaving water temperature exceeds 25°C. This condition will be displayed at circuit level to indicate the capacity limitation.

SymptomCauseSolution
Unit maximum capacity equal to 80%Leaving Evaporator water temperature higher than 25°CWait until the water temperature drops below 25°C

5.2.7 Low Evaporating Pressure

When the circuit is running and the evaporating pressure drops below the safety limits (see section 4.12.1) the circuit control logic reacts at two different levels in order to recover the normal running conditions.

If the evaporating pressure drops below the Low Pressure Hold limit, compressor is inhibited to increase its running capacity. This condition is indicated on the controller display in the circuit status as "Run: Evap Press Low". The status is automatically cleared when the evaporating pressure rise above the Low Pressure Hold limit by 14 kPa.

If the evaporating pressure drops below the Low Pressure Unld limit, compressor is unloaded in order to recover the normal operating conditions. This condition is indicated on the controller display in the circuit status as "Run: Evap Press Low". The status is automatically cleared when the evaporating pressure rise above the Low Pressure Hold limit by 14 kPa.

See section 6.6.18 to troubleshoot this problem.

D-EOMZC00106-17EN

Operation Manual

48/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

5.2.8 High Condensing Pressure

When the circuit is running and the condensing pressure rises above the safety limits the circuit control logic reacts at two different levels in order to recover the normal running conditions.

The two different levels, called High Pressure Hold and High Pressure Unload limits, are calculated by the controller from the maximum condenser pressure allowed by the compressor envelope. This value depends from evaporating pressure as reported in the figure below.

If the condensing pressure rises above the High Pressure Hold limit, compressor is inhibited to increase its running capacity. This condition is indicated on the controller display in the circuit status as "Run: Cond Press High". The limit is calculated in terms of saturated condensing temperature; the status is automatically cleared when the saturated condensing temperature rises above the High Pressure Hold limit by 5.6°C.

If the condensing pressure rises above the High Pressure Unload limit, compressor is unloaded in order to recover the normal operating conditions. This condition is indicated on the controller display in the circuit status as "Run: Cond Press High". The status is automatically cleared when the saturated condensing temperature rises above the High Pressure Hold limit by 5.6°C. See section 6.6.17 to troubleshoot this problem.

DAIKIN EWAD820TZSRB2 - High Condensing Pressure - 1

other | Time (s) | Hi Press Trip | Hi Press Hold | Hi Press Unload | | -------- | ------------- | ------------- | --------------- | | 0 | Low | Low | Low | | Peak | High | High | High | | End | High | High | High |

5.2.9 High Vfd Current

When the compressor is running and its output current rises above the safety limits the circuit control logic reacts at two different levels in order to recover the normal running conditions. Safety limits are calculated by the controller based on the selected compressor type.

If the running current rises above the Running Current Hold limit (101% of RLA), compressor is inhibited to increase its running capacity. This condition is indicated on the controller display in the circuit status as "Run: High VFD Amps".

If the condensing pressure rises above the Running Current Unload limit (105% of RLA), compressor is unloaded in order to recover the normal operating conditions. This condition is indicated on the controller display in the circuit status as "Run: High VFD Amps". The status is automatically cleared when the running amps falls below the hold limit.

5.2.10 High Discharge Temperature

When the compressor is running and its discharge temperature rises above the safety limits the circuit control logic reacts at two different levels in order to recover the normal running conditions.

If the discharge temperature rises above the Discharge Temperature Hold limit (95°C), compressor is inhibited to increase its running capacity. This condition is indicated on the controller display in the circuit status as "Run: High Discharge Temp".

EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 49/85

If the discharge temperature rises above the Discharge Temperature Unload limit (100°C), compressor is unloaded in order to recover the normal operating conditions. This condition is indicated on the controller display in the circuit status as “Run: High Discharge Temp”. The status is automatically cleared when the discharge temperature falls below the hold limit.

5.3 Condensation Control (A/C units only)

Condensing Pressure is controlled in order to achieve best chiller efficiency within compressor envelope limits. Condenser pressure control is achieved through fan staging and/or fan speed control, when the unit is equipped with fan speed regulation option. See chapter 4.3.3 for more details.

In particular, when the chiller operates at a low ambient temperature, a minimum condenser saturated temperature is imposed, based on saturated evaporating temperature. This allows the compressor to operate within its envelope. This setpoint is further increased (see figure below) by a quantity which depends from outside ambient temperature and compressor load in achieve the best efficiency point, i.e. minimum energy consumption of compressor and fans.

DAIKIN EWAD820TZSRB2 - Condensation Control (A/C units only) - 1

line | Evap. Sat. Temp. | Cond. Sat. Temp. | | --------------- | ---------------- | | Min Cond Press | 0 | | 30% load | 0 | | 50% load | 0 |

5.3.1 Fan Settings (A/C units only)

The unit may be equipped with on/off fans, inverter fans or brushless fans. Based on the fan type, different settings are required to the chiller controller and/or to the inverters.

5.3.1.1 Fan VFD Settings

Units may be equipped optionally or as a standard with fan VFD control. Each circuit is organized with two steps, arranged as per the following table. The two stages are activated according to the same logic as described in the previous chapter.

DAIKIN EWAD820TZSRB2 - Fan VFD Settings - 1

Inverters used for fan control may be of two types, according to the number of fans which they control. Most parameters are valid for all, some other parameters (9900 series) are specific for the inverter and fan type used. For further details please refer to the instruction manual of the inverters included in the documentation of the unit.

Inverter parameter list - 1 fan control

ParameterDescriptionFan Type
AC900AC700
1611Param ViewLong ViewLong View
1002Ext commandsNOT SELNOT SEL
1301Min AI10%0%
1601Run EnableDI1DI1
1604Fault ResetDI1DI1

D-EOMZC00106-17EN

Operation Manual

50/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

2006UndervoltageEnableEnable
2101Start FunctionAUTOAUTO
2202Acceleration Time10 s10 s
2203Deceleration Time10 s10 s
2603IR compensation Volt10.510.5
2604IR comp. frequency50%50%
2606Switching Frequency8kHz8kHz
2609Noise SmoothingEnableEnable
2618FW voltage400 V400 V
3006Motor Thermal Time Constant350 s350 s
3104AR OvercurrentEnableEnable
3108AR External FaultDisableDisable
9906Motor In4.0 A2.7 A
9908Motor Speed900 rpm700 rpm
9909Motor Power1.2 kW0.7 kW

Inverter parameter list - 2 fan control

ParameterDescriptionFan Type
AC900AC700
1611Param ViewLong ViewLong View
1002Ext commandsNOT SELNOT SEL
1301Min AI10%0%
1601Run EnableDI1DI1
1604Fault ResetDI1DI1
2006UndervoltageEnableEnable
2101Start FunctionAUTOAUTO
2202Acceleration Time10 s10 s
2203Deceleration Time10 s10 s
2603IR compensation Volt10.510.5
2604IR comp. frequency50%50%
2606Switching Frequency8kHz8kHz
2609Noise SmoothingEnableEnable
2618FW voltage400 V400 V
3006Motor Thermal Time Constant350 s350 s
3104AR OvercurrentEnableEnable
3108AR External FaultDisableDisable
9906Motor In8.0 A5.4 A
9908Motor Speed900 rpm700 rpm
9909Motor Power2.4 kW1.4 kW

5.4 Condensation Control (W/C units only)

Condenser Entering Water Temperature is controlled in order to achieve best chiller efficiency within compressor envelope limits. To do this, application manages the outputs for the control of the following condensation devices:

- Tower fan #1...4 by mean of 4 on/off signals. Tower fan # state is on when Cond EWT is greater then the Cond EWT setpoint. Tower fan # state is off when Cond EWT is lower then Setpoint – Diff. The picture below represents an example of activation and deactivation sequence based on Cond EWT present value relation with set points and differentials listed in 4.2.5.

DAIKIN EWAD820TZSRB2 - Condensation Control (W/C units only) - 1

other | TCond | Towers Output | |-------|---------------| | 34 | Tower #1 | | 35 | Tower #2 | | 37 | Tower #3 | | 39 | Tower #4 |

EWAD TZ - EWAD TZ B EWWD VZ - EWWH VZ Air and Water cooled inverter chillers and heat pump
D-EOMZC00106-17EN Operation Manual 51/85

- 1 Vfd by mean of a modulating 0-10V signal generated through a PID controller. The following graph is an example of the modulating signal behavior in case of a PID control supposed to be purely proportional.

DAIKIN EWAD820TZSRB2 - Condensation Control (W/C units only) - 2

line | Cond In/Out Temp Set Point | Analog output max value (10 V) | Analog output min value (0 V) | | :--- | :--- | :--- | | 30 | 0 | 0 | | 40 | 100 | 100 | Regulation Band = 100/kP

5.5 EXV Control

As a standard, the unit is equipped with one electronic expansion valve (EXV) per circuit, moved by a stepper motor. The EXV controls the thermodynamic cicle (evaporator) in order to optimize evaporator efficiency and at the same time guarantee the proper operation of the circuit.

The controller integrates a PID algorithm which manages the dynamic response of the valve in order to keep a satisfactory quick and stable response to system parameter variations.

In Pressure control, the EXV is positioned to control the evaporator pressure and avoid that it can go above the MOP.

When the EXV transitions to the Superheat control, the superheat target is calculated to maximize the evaporator surface used to exchange heat with the other medium. This target is constantly updated, and averaged over a 10 second period.

Whenever the circuit is running, the EXV position is limited between 5% or 100% position.

Any time the circuit is in the Off or starts the shutdown procedure, the EXV shall be in the closed position. In this case additional closing steps are commanded to guarantee a proper recovery of the zero position.

Expansion valve driver is equipped with UPS module to safely close the expansion valve in case of power failure.

5.6 Economizer Control (A/C units only)

The circuit economizer will be activated if all the following conditions apply:

  • Circuit in Run state
  • Compressor speed > Econ En Spd
    • Circuit Pressure Ratio > Econ Act PR
  • Discharge Superheat >22^ (This condition is ignored with the EWAD TZ B)
    • Percent RLA < 95%

The economizer will be deactivated if one of the following conditions apply:

  • Circuit in Off state
  • Circuit Pressure Ratio < Econ Act PR - 0.3
  • Discharge Superheat < 17^ C (This condition is ignored with the EWAD TZ B)

D-EOMZC00106-17EN

Operation Manual

52/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

5.7 Liquid Injection Control

Liquid injection will be activated when the discharge temperature rises above a safety limit temperature to avoid compressor components overheating.

Liquid injection will be turned off when the discharge temperature decreases below the activation

5.8 Variable Volume Ratio Control

VVR (Variable Volume Ratio) slides in the compressor adapt discharge port geometry to achieve optimum compressor efficiency according to chiller operating conditions. The proper Compressor Volume Ratio is determined by the application basing on pressure ratio present value and obtained energizing slides to drive them in the needed position. Number of available volume ratios depends on compressor model.

6 ALARMS AND TROUBLESHOOTING

The UC protects the unit and the components from operating in abnormal conditions. Protections can be divided in preventions and alarms. Alarms can then be divided in pump-down and rapid stop alarms. Pump-down alarms are activated when the system or sub-system can perform a normal shutdown in spite of the abnormal running conditions. Rapid stop alarms are activated when the abnormal running conditions require an immediate stop of the whole system or sub-system to prevent potential damages.

The UC displays the active alarms in a dedicated page and keep an history of the last 50 entries divided between alarms and acknowledges occurred. Time and date for each alarm event and of each alarm acknowledge are stored.

The UC also stores alarm snapshot of each alarm occurred. Each item contains a snapshot of the running conditions right before the alarm has occurred. Different sets of snapshots are programmed corresponding to unit alarms and circuit alarms holding different information to help the failure diagnosis.

In the following sections it will also be indicated how each alarm can be cleared between local HMI, Network (by any of the high level interfaces Modbus, Bacnet or Lon) or if the specific alarm will clear automatically. The following symbols are used:

Allowed
Not allowed
Not foreseen

6.1 Unit Alerts

6.1.1 Bad Current Limit Input

This alarm is generated when the Flexible Current Limit option has been enabled and the input to the controller is out of the admitted range.

SymptomCauseSolution
Unit status is Run.Bell icon is moving on controller's display.Flexible Current Limit function cannot be used.String in the alarm list:BadCurrentLimitInputString in the alarm log:± BadCurrentLimitInputString in the alarm snapshotBadCurrentLimitInputFlexible current limit input out of range.For this warning out of range is considered to be a signal less than 3mA or more than 21mA.Check for values of input signal to the unit controller. It has to be in the allowed mA range.
Check for electrical shielding of wirings.
Check for right value of the unit's controller output in case input signal is into allowed range.
ResetNotes
Local HMINetworkAuto☐☐☑Automatically clears when the signal returns in the allowed range.

6.1.2 Bad Demand Limit Input

This alarm is generated when the Demand Limit option has been enabled and the input to the controller is out of the admitted range.

SymptomCauseSolution
Unit status is Run.Bell icon is moving on controller's display.Demand Limit function cannot be used.String in the alarm list:BadDemandLimitInputString in the alarm log:Demand limit input out of rangeFor this warning out of range is considered to be a signal less than 3mA or more than 21mA.Check for values of input signal to the unit controller. It has to be in the allowed mA range;
Check for electrical shielding of wirings.

D-EOMZC00106-17EN

Operation Manual

54/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

±BadDemandLimitInputString in the alarm snapshotBadDemandLimitInputCheck for right value of the unit's controller output in case input signal is into allowed range.
ResetNotes
Local HMINetworkAutoAutomatically clears when the signal returns in the allowed range.

6.1.3 Bad Leaving Water Temperature Reset Input

This alarm is generated when the Setpoint Reset option has been enabled and the input to the controller is out of the admitted range.

SymptomCauseSolution
Unit status is Run.Bell icon is moving on controller's display.LWT Reset function cannot be used.String in the alarm list:BadSetPtOverrideInputString in the alarm log:± BadSetPtOverrideInputString in the alarm snapshotBadSetPtOverrideInputLWT reset input signal is out of range.For this warning out of range is considered to be a signal less than 3mA or more than 21mA.Check for values of input signal to the unit controller. It has to be in the allowed mA range.
Check for electrical shielding of wirings.
Check for right value of the unit's controller output in case input signal is into allowed range.
ResetNotes
Local HMINetworkAuto☐☐☑Automatically clears when the signal returns in the allowed range.

6.1.4 Condenser Pump #1 Failure (W/C units only)

This alarm is generated if the pump is started but the flow switch is not able to close within the recirculate time. This can be a temporary condition or may be due to a broken flowswitch, the activation of circuit breakers, fuses or to a pump breakdown.

SymptomCauseSolution
Unit could be ON.Bell icon is moving on controller's display.Backup pump is used or stop of all circuits in case of pump #2 failure.String in the alarm list:CondPump1FaultString in the alarm log:± CondPump1FaultString in the alarm snapshotCondPump1FaultPump #1 may not be operating.Check for problem in electrical wiring of the pump #1.
Check that electrical breaker of pump #1 is tripped.
If fuses are used to protect the pump, check the integrity of fuses.
Check for problem in wiring connection between pump starter and unit controller.
Check the water pump filter and the water circuit for obstructions.
Flow Switch doesn't operate properlyCheck flow switch connection and calibration.
ResetNotes
Local HMINetworkAuto☑☑☐

6.1.5 Condenser Pump #2 Failure (W/C units only)

This alarm is generated if the pump is started but the flow switch is not able to close within the recirculate time. This can be a temporary condition or may be due to a broken flowswitch, the activation of circuit breakers, fuses or to a pump breakdown.

SymptomCauseSolution
Unit could be ON.Bell icon is moving on controller's display.Backup pump is used or stop of all circuits in case of pump #1 failure.String in the alarm list:CondPump2FaultPump #1 may not be operating.Check for problem in electrical wiring of the pump #1.
Check that electrical breaker of pump #1 is tripped.
If fuses are used to protect the pump, check the integrity of fuses.
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 55/85
String in the alarm log:±CondPump2FaultString in the alarm snapshotCondPump2FaultCheck for problem in wiring connection between pump starter and unit controller.
Check the water pump filter and the water circuit for obstructions.
Flow Switch doesn’t operate properlyCheck flow switch connection and calibration.
ResetNotes
Local HMINetworkAuto☑☑☐

6.1.6 Energy Meter Communication Fail

This alarm is generated in case of communication problems with the energy meter.

SymptomCauseSolution
Bell icon is moving on controller's display. String in the alarm list: EnergyMtrCommFail String in the alarm log: ± EnergyMtrCommFail String in the alarm snapshot EnergyMtrCommFailModule has no power supplyRefer to the datasheet of the specific component to see if it is correctly powered
Wrong cabling with the Unit ControllerCheck if the polarity of the connections is respected.
Modbus parameters not properly setReferring to the datasheet of the specific component to see if the modbus parameters are set correctly: Address = 20 Baud Rate =19200 kBs Parity = None Stop bits =1
Module is brokenCheck if the display shows something and the power supply is present.
ResetNotes
Local HMI Network Auto☐ ☐ ☑Automatically clears when the communication is re-established.

6.1.7 Evaporator Pump #1 Failure

This alarm is generated if the pump is started but the flow switch is not able to close within the recirculate time. This can be a temporary condition or may be due to a broken flowswitch, the activation of circuit breakers, fuses or to a pump breakdown.

SymptomCauseSolution
Unit could be ON.Bell icon is moving on controller's display.Backup pump is used or stop of all circuits in case of pump #2 failure.String in the alarm list:EvapPump1FaultString in the alarm log:± EvapPump1FaultString in the alarm snapshotEvapPump1FaultPump #1 may not be operating.Check for problem in electrical wiring of the pump #1.
Check that electrical breaker of pump #1 is tripped.
If fuses are used to protect the pump, check the integrity of fuses.
Check for problem in wiring connection between pump starter and unit controller.
Check the water pump filter and the water circuit for obstructions.
Flow Switch doesn't operate properlyCheck flow switch connection and calibration.
ResetNotes
Local HMINetworkAuto☑☑☐

6.1.8 Evaporator Pump #2 Failure

This alarm is generated if the pump is started but the flow switch is not able to close within the recirculate time. This can be a temporary condition or may be due to a broken flowswitch, the activation of circuit breakers, fuses or to a pump breakdown.

D-EOMZC00106-17EN

Operation Manual

56/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

SymptomCauseSolution
Unit could be ON.Bell icon is moving on controller's display.Backup pump is used or stop of all circuits in case of pump #1 failure.String in the alarm list:EvapPump2FaultString in the alarm log:± EvapPump2FaultString in the alarm snapshotEvapPump2FaultPump #2 may not be operating.Check for problem in electrical wiring of the pump #2.
Check that electrical breaker of pump #2 is tripped.
If fuses are used to protect the pump, check the integrity of fuses.
Check for problem in wiring connection between pump starter and unit controller.
Check the water pump filter and the water circuit for obstructions.
Flow Switch doesn't operate properlyCheck flow switch connection and calibration.
ResetNotes
Local HMI
Network
Auto

6.1.9 External Event

This alarm indicates that a device, whose operation is linked with this machine, is reporting a problem on the dedicated input.

SymptomCauseSolution
Unit status is Run.Bell icon is moving on controller's display.String in the alarm list:UnitExternalEventString in the alarm log:±UnitExternalEventString in the alarm snapshotUnitExternalEventThere is an external event that has caused the opening, for at least 5 seconds, of the digital input on the controller board.Check for reasons of external event and if it can be a potential problem for a correct chiller operation.
ResetNotes
Local HMINetworkAuto☐☐☑The alarm is automatically cleared when the problem is solved.
NOTE: What above applies in case of configuration of the external fault digital input as Event

6.1.10 Fan Alarm Module Communication Fail (A/C units only)

This alarm is generated in case of communication problems with the FAC module.

SymptomCauseSolution
Bell icon is moving on controller's display. String in the alarm list: FanMdlCommFail String in the alarm log: ± FanMdlCommFail String in the alarm snapshot FanMdlCommFailModule has no power supplyCheck the power supply from the connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is tightly inserted in the module
Module address is not properly setCheck if module's address is correct referring to the wiring diagram.
Module is brokenCheck if LED are on and both green. If BSP LED is solid red replace the module
Check if power supply is ok but LEDs are both off. In this case replace the module
ResetNotes
Local HMI Network Auto☑ ☑ ☐

6.1.11 Heat Recovery Entering Water Temperature sensor fault (A/C units only)

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpUnit status is Off.All circuits are stopped with a normal shutdown procedure.Bell icon is moving on controller's display. String in the alarm list:UnitAIHREwtSenString in the alarm log:± UnitAIHREwtSenString in the alarm snapshotUnitAIHREwtSenSensor is broken.D-EOMZC00106-17EN Operation Manual 57/85Check for sensor integrity according table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

6.1.12 Heat Recovery Leaving Water Temperature sensor fault (A/C units only)

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Heat Recovery is OffBell icon is moving on controller's display.String in the alarm list:UnitAIHRLvgSenString in the alarm log:± UnitAIHRLvgSenString in the alarm snapshotUnitAIHRLvgSenSensor is broken.Check for sensor integrity.according table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

6.1.13 Heat Recovery Water Temperatures inverted (A/C units only)

This alarm is generated any time that the heat recovery entering water temperature is lower than the leaving by 1^ C and at least one compressor is running.

SymptomCauseSolution
Bell icon is moving on controller's display.Bell icon is moving on controller's display.String in the alarm list:Unit HRInvAString in the alarm log:± Unit HRInvAString in the alarm snapshotUnit HRInvAIEntering and leaving water temperature sensors are inverted.Check cabling of the sensors on the unit controller.
Check offset of the two sensors with the water pump running
Entering and leaving water pipes are reversedCheck if the water flows in counter flow respect to refrigerant.
Water pump operate reverse.Check if the water flows in counter flow respect to refrigerant.
ResetNotes
Local HMINetworkAuto☑☑☐

6.1.14 Rapid Recovery Module Communication Fail

This alarm is generated in case of communication problems with the RRC module.

SymptomCauseSolution
Bell icon is moving on controller's display. String in the alarm list:Module has no power supplyCheck the power supply from the connector on the side of the module.

D-EOMZC00106-17EN

Operation Manual

58/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

RpdRcvryCommFailString in the alarm log:± RpdRcvryCommFailString in the alarm snapshotRpdRcvryCommFailCheck if LEDs are both green.
Check if the connector on the side is tightly inserted in the module
Module address is not properly setCheck if module's address is correct referring to the wiring diagram.
Module is brokenCheck if LED are on and both green. If BSP LED is solid red replace the module
Check if power supply is ok but LEDs are both off. In this case replace the module
ResetNotes
Local HMI
Network
Auto

6.1.15 Switch Box Temperature sensor fault (A/C units only)

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is OnBell icon is moving on controller's display.Bell icon is moving on controller's display.String in the alarm list:SwitchBoxTempSenString in the alarm log:± SwitchBoxTempSenString in the alarm snapshotSwitchBoxTempSenSensor is broken.Check for sensor integrity.according table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

6.2 Unit Pumpdown Stop Alarms

6.2.1 Condenser Entering Water Temperature (EWT) sensor fault

This alarm is generated any time the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is Off.All circuits are stopped with a normal shutdown procedure.Bell icon is moving on controller's display. String in the alarm list:UnitOffCndEntWTempSenString in the alarm log:± UnitOffCndEntWTempSenString in the alarm snapshotUnitOffcndEntWTempSenSensor is broken.Check for sensor integrity. according table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

6.2.2 Condenser Leaving Water Temperature (LWT) sensor fault

This alarm is generated any time the input resistance is out of an acceptable range.

EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 59/85
SymptomCauseSolution
Unit status is Off.All circuits are stopped with a normal shutdown procedure.Bell icon is moving on controller's display. String in the alarm list:UnitOffCndLvgWTempSenString in the alarm log:± UnitOffCndLvgWTempSenString in the alarm snapshotUnitOffcndLvgWTempSenSensor is broken.Check for sensor integrity.according table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

6.2.3 Evaporator Entering Water Temperature (EWT) sensor fault

This alarm is generated any time the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is Off.All circuits are stopped with a normal shutdown procedure.Bell icon is moving on controller's display. String in the alarm list:UnitOffEvpEntWTempSenString in the alarm log:± UnitOffEvpEntWTempSenString in the alarm snapshotUnitOffEvpEntWTempSenSensor is broken.Check for sensor integrity.according table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMI Network☑☑

6.2.4 Evaporator Water Temperatures inverted

This alarm is generated any time the entering water temperature is lower than the leaving by 1^ C and at least one compressor is running since 90 seconds.

SymptomCauseSolution
Unit status is Off.All circuits are stopped with a normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:UnitOffEvpWTempInvrdString in the alarm log:± UnitOffEvpWTempInvrdString in the alarm snapshotUnitOffEvpWTempInvrdEntering and leaving water temperature sensors are inverted.Check cabling of the sensors on the unit controller.
Check offset of the two sensors with the water pump running
Entering and leaving water pipes are reversedCheck if the water flows in counter flow respect to refrigerant.
Water pump operate reverse.Check if the water flows in counter flow respect to refrigerant.
ResetNotes
Local HMINetworkAuto☑☑☐

6.2.5 Outside Air Temperature (OAT) Lockout (A/C units only)

This alarm prevents the unit to start if the outside air temperature is too low. Purpose is to prevent low pressure trips at startup. The limit depends on the fan regulation that is installed on the unit. By default this value is set to 10^ C.

D-EOMZC00106-17EN

Operation Manual

60/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

SymptomCauseSolution
Unit Status is OAT Lockout.All circuits are stopped with a normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:StartInhbtAmbTempLoString in the alarm log:± StartInhbtAmbTempLoString in the alarm snapshotStartInhbtAmbTempLoOutside ambient temperature is lower than value set into unit's controller.Check the minimum outside ambient temperature value set into the unit's controller.
Check if this value is in accordance with chiller application, therefore check about the proper application and utilization of the chiller.
Improper operation of Outside Ambient Temperature sensor.Check for proper operation of OAT sensor according information about kOhm (kΩ) range related to temperature values.
ResetNotes
Local HMINetworkAuto☐☐☑It clears automatically with a 2.5°C of hysteresis.

6.2.6 Outside Air Temperature sensor fault alarm (A/C units only)

This alarm is generated any time the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is Off.All circuits are stopped with a normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:UnitOffAmbTempSenString in the alarm log:± UnitOffAmbTempSenString in the alarm snapshotUnitOffAmbTempSenSensor is broken.Check for sensor integrity.
Check correct sensors operation according table and allowed kOhm (kΩ) range.
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

6.3 Unit Rapid Stop Alarms

6.3.1 Condenser Water Freeze alarm (W/C units only)

This alarm is generated to indicate that the water temperature (entering or leaving) has dropped below a safety limit. Control tries to protect the heat exchanger starting the pump and letting the water circulate.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:UnitOffCondWaterTmpLoString in the alarm log:± UnitOffCondWaterTmpLoString in the alarm snapshotUnitOffCondWaterTmpLoWater flow too low.Increase the water flow.
Inlet temperature to the evaporator is too low.Increase the inlet water temperature.
Flow switch is not working or no water flow.Check the flow switch and the water pump.
Refrigerant temperature become too low (< -0.6°C).Check the water flow and filter. No good heat exchange condition into the evaporator.
Sensors readings (entering or leaving) are not properly calibratedCheck the water temperatures with a proper instrument and adjust the offsets
Wrong freeze limit setpointThe freeze limit has not been changed as a function of glycol percentage.
ResetNotes
Local HMINetworkAuto☑☒☐It's required to check if the condenser has any damage due to this alarm.
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 61/85

6.3.2 Condenser Water Flow Loss alarm (W/C units only)

This alarm is generated in case of flow loss to the chiller to protect the machine against Mechanical High Pressure trips.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:UnitOffCondWaterFlowString in the alarm log:± UnitOffCondWaterFlowString in the alarm snapshotUnitOffCondWaterFlowNo water flow sensed for 3 minutes continuously or water flow too low.Check the water pump filler and the water circuit for obstructions.
Check the flow switch calibration and adapt to minimum water flow.
Check if pump impeller can rotate freely and has no damages.
Check pumps protection devices (circuit breakers, fuses, inverters, etc.)
Check if water filter is clogged.
Check flow switch connections.
ResetNotes
Local HMINetworkAuto☑☑☐

6.3.3 Emergency Stop

This alarm is generated any time the Emergency Stop button is activated.

DAIKIN EWAD820TZSRB2 - Emergency Stop - 1

Before resetting the Emergency Stop button please verify that the harmful condition has been removed.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:UnitOffEmergencyStopString in the alarm log:± UnitOffEmergencyStopString in the alarm snapshotUnitOffEmergencyStopEmergency stop button has been pushed.Turning counterclockwise the emergency stop button, the alarm should be cleared.
ResetNotes
Local HMINetworkAuto☑☒☐Please see note on the top.

6.3.4 Evaporator Flow Loss alarm

This alarm is generated in case of flow loss to the chiller to protect the machine against freezing.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:UnitOffEvapWaterFlowString in the alarm log:± UnitOffEvapWaterFlowString in the alarm snapshotUnitOffEvapWaterFlowNo water flow sensed for 3 minutes continuously or water flow too low.Check the water pump filler and the water circuit for obstructions.
Check the flow switch calibration and adapt to minimum water flow.
Check if pump impeller can rotate freely and has no damages.
Check pumps protection devices (circuit breakers, fuses, inverters, etc.)
Check if water filter is clogged.
Check flow switch connections.
ResetNotes
Local HMINetworkAuto☑☑☐

D-EOMZC00106-17EN

Operation Manual

62/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

6.3.5 Evaporator Leaving Water Temperature (LWT) sensor fault

This alarm is generated any time that the input resistance is out of an acceptable range.

SymptomCauseSolution
Unit status is Off.All circuits are stopped with a normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:UnitOffLvgEntWTempSenString in the alarm log:± UnitOffLvgEntWTempSenString in the alarm snapshotUnitOffEvpLvgWTempSenSensor is broken.Check for sensor integrity.according table and allowed kOhm (kΩ) range.
Check correct sensors operation
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for absence of water or humidity on electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

6.3.6 Evaporator Water Freeze alarm

This alarm is generated to indicate that the water temperature (entering or leaving) has dropped below a safety limit. Control tries to protect the heat exchanger starting the pump and letting the water circulate.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:UnitOffEvapWaterTmpLoString in the alarm log:± UnitOffEvapWaterTmpLoString in the alarm snapshotUnitOffEvapWaterTmpLoWater flow too low.Increase the water flow.
Inlet temperature to the evaporator is too low.Increase the inlet water temperature.
Flow switch is not working or no water flow.Check the flow switch and the water pump.
Sensors readings (entering or leaving) are not properly calibrated.Check the water temperatures with a proper instrument and adjust the offsets
Wrong freeze limit setpoint.The freeze limit has not been changed as a function of glycol percentage.
ResetNotes
Local HMINetworkAuto☑☒☐It's required to check if the evaporator has any damage due to this alarm.

6.3.7 External alarm

This alarm is generated to indicate that an external device whose operation is linked with this unit operation. This external device could be a pump or an inverter.

SymptomCauseSolution
Unit status is Off.All circuits are switched off with the normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:UnitOffExternalAlarmString in the alarm log:± UnitOffExternalAlarmString in the alarm snapshotUnitOffExternalAlarmThere is an external event that has caused the opening, for at least 5 seconds, of the port on the controller board.Check causes of the external event or alarm.
Check electrical wiring from unit controller to the external equipment in case of any external events or alarms have been occurred.
ResetNotes
Local HMINetworkAuto☑☑☐
NOTE: What above applies in case of configuration of the external fault digital input as Alarm.
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 63/85

6.3.8 Gas Leakage Alarm (W/C units only)

This alarm is generated when the external leak detector(s) detects a refrigerant concentration higher that a threshold. To clear this alarm is required to clear the alarm either locally and, if needed, on the leak detector itself.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:UnitOffGasLeakageString in the alarm log:± UnitOffGasLeakageString in the alarm snapshotUnitOffGasLeakageRefrigerant leakageLocate the leakage with a sniffer and fix the leakage
Leak detector is not properly poweredCheck the power supply of the leak detector.
Leak detector is not properly connected to the controller.Check the connection of the detector with reference to the wiring diagram of the unit.
Leak detector is brokenReplace the leak detector.
Leak detector is not required/neededCheck the configuration on the unit controller and disable this option.
ResetNotes
Local HMINetworkAuto☑☑☐

6.3.9 Heat Recovery Water Freeze Protect alarm (A/C units only)

This alarm is generated to indicate that the heat recovery water temperature (entering or leaving) has dropped below a safety limit. Control tries to protect the heat exchanger starting the pump and letting the water circulate.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:UnitOff HRFreezeString in the alarm log:± UnitOff HRFreezeString in the alarm snapshotUnitOff HRFreezeWater flow too low.Increase the water flow.
Inlet temperature to the heat recovery is too low.Increase the inlet water temperature.
Sensors readings (entering or leaving) are not properly calibratedCheck the water temperatures with a proper instrument and adjust the offsets
ResetNotes
Local HMINetworkAuto☑☑

6.3.10 OptionCtrlCommFail (A/C units only)

This alarm is generated in case of communication problems with the AC module.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:OptionCtrlCommFailString in the alarm log:± OptionCtrlCommFailString in the alarm snapshotOptionCtrlCommFailModule has no power supplyCheck the power supply from the connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is tightly inserted in the module
Module address is not properly setCheck if module's address is correct referring to the wiring diagram.
Module is brokenCheck if LED are on and both green. If BSP LED is solid red replace the module
Check if power supply is ok but LEDs are both off. In this case replace the module
ResetNotes
Local HMI
Network
Auto

6.3.11 Power Fault (only for A/C units with the UPS option)

This alarm is generated when the main power is Off and the unit controller is powered by the UPS.

D-EOMZC00106-17EN

Operation Manual

64/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

DAIKIN EWAD820TZSRB2 - Power Fault (only for A/C units with the UPS option) - 1

Resolution of this fault requires a direct intervention on the power supply of this unit. Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons. In case of doubts contact your maintenance company.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately. Bell icon is moving on controller's display.String in the alarm list:Power FaultString in the alarm log:± Power FaultString in the alarm snapshotPower FaultLoss of one phase.Check voltage level on each of the phases.
Not correct sequence connection of L1,L2,L3.Check sequence of L1, L2, L3 connections according indication on chiller's electrical scheme.
Voltage level on the unit's panel is not in the allowed range (±10%).Check that voltage level on each phases is into the allowed range that is indicated on the chiller label.Is important to check the voltage level on each phases not only with chiller not running, but mainly with chiller running from minimum capacity up to full load capacity. That's because voltage drop can occur from a certain unit cooling capacity level, or because of certain working condition (i.e. high values of OAT);In these cases the issue can be related with the sizing of power cables.
There is a short-circuit on the unit.Check for correct electrical isolation condition of each unit's circuit with a Megger tester.
ResetNotes
Local HMINetworkAuto☑☑

6.3.12 PVM alarm (A/C units only)

This alarm is generated in case of problems with the power supply to the chiller.

DAIKIN EWAD820TZSRB2 - PVM alarm (A/C units only) - 1

Resolution of this fault requires a direct intervention on the power supply of this unit. Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons. In case of doubts contact your maintenance company.

SymptomCauseSolution
Unit status is Off.All circuits are stopped immediately. Bell icon is moving on controller's display.String in the alarm list:UnitOffPhaveVoltageString in the alarm log:± UnitOffPhaveVoltageString in the alarm snapshotUnitOffPhaveVoltageLoss of one phase.Check voltage level on each of the phases.
Not correct sequence connection of L1,L2,L3.Check sequence of L1, L2, L3 connections according indication on chiller's electrical scheme.
Voltage level on the unit's panel is not in the allowed range (±10%).Check that voltage level on each phases is into the allowed range that is indicated on the chiller label.Is important to check the voltage level on each phases not only with chiller not running, but mainly with chiller running from minimum capacity up to full load capacity. That's because voltage drop can occur from a certain unit cooling capacity level, or because of certain working condition (i.e. high values of OAT);In these cases the issue can be related with the sizing of power cables.
There is a short-circuit on the unit.Check for correct electrical isolation condition of each unit's circuit with a Megger tester.
ResetNotes
Local HMINetworkAuto☐☐☑

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and heat pump

D-EOMZC00106-17EN

Operation Manual 65/85

6.4 Circuit Alerts

6.4.1 Economizer Pressure Sensor fault (A/C units only)

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is On.Economizer is Off.Bell icon is moving on controller's display.String in the alarm list:Cx EcoPressSenString in the alarm log:± Cx EcoPressSenString in the alarm snapshotCx EcoPressSenSensor is broken.Check for sensor integrity.Check correct sensors operation according information about mVolt (mV) range related to pressure values in kPa.
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for correct installation of the sensor on refrigerant circuit pipe. The transducer must be able to sense the pressure through the valve's needle.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

6.4.2 Economizer Temperature Sensor fault (A/C units only)

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is On.Economizer is Off.Bell icon is moving on controller's display.String in the alarm list:Cx EcoTempSenString in the alarm log:± Cx EcoTempSenString in the alarm snapshotCx EcoTempSenSensor is shorted.Check for sensor integrity.
Check correct sensors operation according information about kOhm (kΩ) range related to temperature values.
Sensor is broken.Check if sensor is shorted with a resistance measurement.
Sensor is not good connected (open).Check for correct installation of the sensor on refrigerant circuit pipe.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according with electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

6.4.3 Failed Pumpdown

This alarm is generated to indicate that the circuit hadn't been able to remove all the refrigerant from the evaporator. It automatically clear as soon as the compressor stops just to be logged in the alarm history. It may not be recognized from BMS because the communication latency can give enough time for the reset. It may not even be seen on the local HMI.

SymptomCauseSolution
Circuit status is Off.No indications on the screenString in the alarm list:--EEXV is not closing completely, therefore there's “short-circuit” between high pressure side with low pressure side of the circuit.Check for proper operation and full closing position of EEXV. Sight glass should not show refrigerant flow after the valve is closed.

D-EOMZC00106-17EN

Operation Manual

66/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

String in the alarm log:± Cx Failed PumpdownString in the alarm snapshotCx Failed PumpdownCheck LED on the top of the valve, C LED should be solid green. If both LED are blinking alternately the valve motor is not properly connected.
Evaporating pressure sensor is not working properly.Check for proper operation of evaporating pressure sensor.
Compressor on circuit is internally damaged with a mechanical problems for example on internal check-valve, or on internal spirals or vanes.Check compressors on circuits.
ResetNotes
Local HMINetworkAuto☐☐☑

6.4.4 Fan Fault (A/C units only)

This alarm indicates that at least one of the fans could have some problems

SymptomCauseSolution
Circuit status is On.The compressor keep operating as normal.Bell icon is moving on controller's display.String in the alarm list:Cx FanAlmString in the alarm log:± Cx FanAlmString in the alarm snapshotCx FanAlmAt least one of the fan has some problemsIn case of on/off fan check the thermal magnetic circuit breaker of each fan. The fan could absorbs too much current
In case of fan with VFD check the alarm output of the and message error provided by each fan VFD
ResetNotes
Local HMINetworkAuto☑☑☐

6.4.5 Gas Leakage Sensor fault (A/C units only)

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is On.Bell icon is moving on controller's display.String in the alarm list:Cx GasLeakSenString in the alarm log:± Cx GasLeakSenString in the alarm snapshotCx GasLeakSenSensor is broken.Check for sensor integrity.Check correct sensors operation according information about mVolt (mV) range related to ppm values.
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for correct installation of the sensor.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

6.4.6 CxCmp1 MaintCode01 (A/C units only)

This alarm indicates that a component in the inverter may require verification or even a replacement.

EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 67/85
SymptomCauseSolution
Circuit status is On.The compressor keep operating as normal.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 MainCode01String in the alarm log:± CxCmp1 MainCode01String in the alarm snapshotCxCmp1 MainCode01The inverter cooling valve in the inverter, may require a verification or a replacement.Contact your service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto☑☑☐

6.4.7 CxCmp1 MaintCode02 (A/C units only)

This alarm indicates that a component in the inverter may require verification or even a replacement.

SymptomCauseSolution
Circuit status is On.The compressor keep operating as normal.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 MainCode02String in the alarm log:± CxCmp1 MainCode02String in the alarm snapshotCxCmp1 MainCode02The capacitors in the inverter, may require a verification or a replacement.Contact your service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto☑☑☐

6.4.8 Power Loss (A/C units only)

This alarm indicates that a short under voltage on main power supply, that does not turn off the unit, has occurred.

DAIKIN EWAD820TZSRB2 - Power Loss (A/C units only) - 1

Resolution of this fault requires a direct intervention on the power supply of this unit. Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons. In case of doubts contact your maintenance company.

SymptomCauseSolution
Circuit status is On.The controller brings the compressor to the minimum speed and then normal operation is recovered (default 1200rmp)Bell icon is moving on controller's display.String in the alarm list:Cx FanAlmString in the alarm log:± Cx FanAlmString in the alarm snapshotCx FanAlmChiller main power supply had a down peak which caused the trip.Check if main power supply is within the acceptable tolerance for this chiller
ResetNotes
Local HMINetworkAuto☑☑☐

D-EOMZC00106-17EN

Operation Manual

68/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

6.5 Circuit Pumpdown Stop Alarms

6.5.1 Discharge Temperature Sensor fault

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffDischTmpSenString in the alarm log:± CxCmp1 OffDischTmpSenString in the alarm snapshotCxCmp1 OffDischTmpSenSensor is shorted.Check for sensor integrity.
Check correct sensors operation according information about kOhm (kΩ) range related to temperature values.
Sensor is broken.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for correct installation of the sensor on refrigerant circuit pipe.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according with electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

6.5.2 Gas Leakage fault (A/C units only)

This alarm indicates a gas leakage in the compressor box.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the shutdown procedure performing a deep pumpdown of the circuit.Bell icon is moving on controller's display.String in the alarm list:Cx OffGasLeakageString in the alarm log:± Cx OffGasLeakageString in the alarm snapshotCx OffGasLeakageGas leakage in the compressors box (A/C units).Switch off the unit and perform a gas leakage test.
Gas Leakage in the plant room.Check if there are leakage on the unit with a detector eventually starting suction fans to change the air in the room.
Gas leakage sensor fault.Put the sensor in open air and check that the alarm can be cleared. In case replace the sensor or disable the option before getting a new part.
ResetNotes
Local HMINetworkAuto☑☑☐

6.5.3 High Compressor Vfd Temperature fault (A/C units only)

This alarm is generated to indicate that the Vfd temperature is too high to allow the compressor to run.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 VfdOverTempString in the alarm log:± CxCmp1 VfdOverTempString in the alarm snapshotCxCmp1 VfdOverTempCooling solenoid valve is not operating properly.Check electrical connection of the solenoid valve.
Check refrigerant charge. Low refrigerant charge can cause overheating of the Vfd electronic.
Check for obstructions in the pipe.
Vfd Heater not properly connected.Check if Vfd heater is switched off when the Vfd temperature increases.
Check if the contactor that commands the Vfd heater can switch properly.
ResetNotes
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 69/85
Local HMINetworkAuto☑☑☐

6.5.4 Liquid Temperature Sensor fault (W/C units only)

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffLiquidTempSenString in the alarm log:± CxCmp1 OffLiquidTempSenString in the alarm snapshotCxCmp1 OffLiquidTempSenSensor is shorted.Check for sensor integrity.
Check correct sensors operation according information about kOhm (kΩ) range related to temperature values.
Sensor is broken.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for correct installation of the sensor on refrigerant circuit pipe.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according with electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

6.5.5 Low Compressor Vfd Temperature fault (A/C units only)

This alarm is generated to indicate that the Vfd temperature is too low to allow the compressor to run safely.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 VfdLowTempString in the alarm log:± CxCmp1 VfdLowTempString in the alarm snapshotCxCmp1 VfdLowTempCooling solenoid valve is not operating properly. It's always open when compressor runs.Check electrical connection of the solenoid valve.
Check operation of the valve to see if it can close properly.
Check operating cycles of the valve. It has a limited number of cycles.
Vfd heater is not working.Check if the Vfd heater is powered.
Check if the Vfd heater is commanded on when Vfd temperature is low.
ResetNotes
Local HMINetworkAuto☑☒☐

6.5.6 Low Oil Level fault (W/C units only)

This alarm indicates that the oil level inside the oil separator has become too low to allow for a safe operation of the compressor.

This switch may not be installed on the unit because in regular operations the oil separation is always granted.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:Oil Level switch not operating correctly.Check the cabling between switch and controller feedback and power
Check if switch operates correctly.

D-EOMZC00106-17EN

Operation Manual

70/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

CxCmp1 OffOilLevelLoString in the alarm log:± CxCmp1 OffOilLevelLoString in the alarm snapshotCxCmp1 OffOilLevelLoCheck if digital input of the controller operates correctly.
Check the oil chargeVerify if there is enough oil inside the circuit.
ResetNotes
Local HMINetworkAuto☑☑☐

6.5.7 Low Discharge Superheat fault

This alarm indicates that the unit has worked for too long with low discharge super heat.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffDishSHLoString in the alarm log:± CxCmp1 OffDishSHLoString in the alarm snapshotCxCmp1 OffDishSHLoEEXV is not working correctly.It's not opening enough or it's moving in the opposite direction.Check if pump-down can be finished for pressure limit reached;
Check expansion valve movements.
Check connection to the valve driver on the wiring diagram.
Measure the resistance of each winding, it has to be different from 0 Ohm.
ResetNotes
Local HMINetworkAuto☑☑☑x 2 attempts (W/C only)

6.5.8 Oil Pressure Sensor fault

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is Off.The circuit is switched off with the normal shutdown procedure.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffOilFeedPSenString in the alarm log:± CxCmp1 OffOilFeedPSenString in the alarm snapshotCxCmp1 OffOilFeedPSenSensor is broken.Check for sensor integrity.Check correct sensors operation according information about mVolt (mV) range related to pressure values in kPa.
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for correct installation of the sensor on refrigerant circuit pipe. The transducer must be able to sense the pressure through the valve's needle.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMI
Network
Auto

6.5.9 Suction Temperature Sensor fault

This alarm is generated to indicate that the sensor is not reading properly.

SymptomCauseSolution
Circuit status is Off.Sensor is shorted.Check for sensor integrity.
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 71/85
The circuit is switched off with the normal shutdown procedure.Bell icon is moving on controller's display. String in the alarm list:CxCmp1 OffSuctTempSenString in the alarm log:± CxCmp1 OffSuctTempSenString in the alarm snapshotCxCmp1 OffSuctTempSenCheck correct sensors operation according information about kOhm (kΩ) range related to temperature values.
Sensor is broken.Check if sensor is shorted with a resistance measurement.
Sensor is not good connected (open).Check for correct installation of the sensor on refrigerant circuit pipe.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according with electrical scheme.
ResetNotes
Local HMI
Network
Auto

6.6 Circuit Rapid Stop Alarms

6.6.1 Compressor Extension Communication Error (W/C units only)

This alarm is generated in case of communication problems with the CCx module.

SymptomCauseSolution
Circuit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:Cx OffCmpCtrlrComFailString in the alarm log:± Cx OffCmpCtrlrComFailString in the alarm snapshotCx OffCmpCtrlrComFailModule has no power supplyCheck the power supply from the connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is tightly inserted in the module
Module address is not properly setCheck if module's address is correct referring to the wiring diagram.
Module is brokenCheck if LED are on and both green. If BSP LED is solid red replace the module
Check if power supply is ok but LEDs are both off. In this case replace the module
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.2 EXV Driver Extension Communication Error (W/C units only)

This alarm is generated in case of communication problems with the EEXVx module.

SymptomCauseSolution
Circuit status is Off.All circuits are stopped immediately.Bell icon is moving on controller's display.String in the alarm list:Cx OffEXVCtrlrComFailString in the alarm log:± Cx OffEXVCtrlrComFailString in the alarm snapshotCx OffEXVCtrlrComFailModule has no power supplyCheck the power supply from the connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is tightly inserted in the module
Module address is not properly setCheck if module's address is correct referring to the wiring diagram.
Module is brokenCheck if LED are on and both green. If BSP LED is solid red replace the module
Check if power supply is ok but LEDs are both off. In this case replace the module
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.3 Compressor VFD Fault

This alarm indicates an abnormal condition that forced the inverter to stop.

D-EOMZC00106-17EN

Operation Manual

72/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore,circuit is immediately stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffVfdFaultString in the alarm log:± CxCmp1 OffVfdFaultString in the alarm snapshotCxCmp1 OffVfdFaultInverter is operating in an unsafe condition and for this reason the inverter must be stopped.Check the alarm snapshot to identify the alarm code from the inverter. Contact your service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.4 Compressor VFD OverTemp (A/C units only)

This alarm indicates that the Inverter temperature has exceeded a safety limits and the inverter has to be stopped in order to avoid damages to components.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffVfdOverTempString in the alarm log:± CxCmp1 OffVfdOverTempString in the alarm snapshotCxCmp1 OffVfdOverTempInsufficient motor coolingCheck refrigerant charge.
Check if operational envelope of the unit is respected.
Check operation of the cooling solenoid valve
Motor temperature sensor could not operate properly.Check the readings of the motor temperature sensor and check the Ohmic value. A correct reading should be around hundreds of Ohm at ambient temperature.
Check the electrical connection of the sensor with the electronic board.
ResetNotes
Local HMI
Network
Auto

6.6.5 Condensing Pressure sensor fault

This alarm indicates that the condensing pressure transducer is not operating properly.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 CondPressSenString in the alarm log:± CxCmp1 CondPressSenString in the alarm snapshotCxCmp1 CondPressSenSensor is broken.Check for sensor integrity.Check correct sensors operation according information about mVolt (mV) range related to pressure values in kPa.
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for correct installation of the sensor on refrigerant circuit pipe. The transducer must be able to sense the pressure through the valve's needle.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.6 Economizer EXV Driver Error (A/C unit only)

This alarm indicates an abnormal condition of the Economizer EXV Driver.

EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 73/85
SymptomCauseSolution
Circuit is stopped if the discharge temperature reach the high limit value.Bell icon is moving on controller's display.String in the alarm list:Cx EcoEXVDrvErrorString in the alarm log:± Cx OffEcoEXVDrvErrorString in the alarm snapshotCx OffEcoEXVDrvErrorHardware ErrorContact your service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.7 Economizer EXV Motor Not Connected (A/C unit only)

This alarm indicates an abnormal condition of the Economizer EXV Driver.

SymptomCauseSolution
Circuit is stopped if the discharge temperature reach the high limit value.Bell icon is moving on controller's display.String in the alarm list:Cx EcoEXVMotorString in the alarm log:± Cx EcoEXVMotorString in the alarm snapshotCx EcoEXVMotorValve not connected.Referring to the wiring diagram check if the valve is correctly connected to the module.
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.8 Evaporating Pressure sensor fault

This alarm indicates that the evaporating pressure transducer is not operating properly.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 EvapPressSenString in the alarm log:± CxCmp1 EvapPressSenString in the alarm snapshotCxCmp1 EvapPressSenSensor is broken.Check for sensor integrity.Check correct sensors operation according information about mVolt (mV) range related to pressure values in kPa.
Sensor is shorted.Check if sensor is shorted with a resistance measurement.
Sensor is not properly connected (open).Check for correct installation of the sensor on refrigerant circuit pipe. The transducer must be able to sense the pressure through the valve's needle.
Check for absence of water or humidity on sensor electrical contacts.
Check for correct plug-in of the electrical connectors.
Check for correct sensors wiring also according electrical scheme.
ResetNotes
Local HMI
Network
Auto

D-EOMZC00106-17EN

Operation Manual

74/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

6.6.9 EXV Driver Error (A/C units only)

This alarm indicates an abnormal condition of the EXV Driver.

SymptomCauseSolution
Circuit status is Off.Circuit is immediately stopped.Bell icon is moving on controller's display.String in the alarm list:Cx OffEXVDrvErrorString in the alarm log:± Cx OffEXVDrvErrorString in the alarm snapshotCx OffEXVDrvErrorHardware ErrorContact your service organization to get the problem solved.
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.10 EXV Motor Not Connected (TZ B units only)

This alarm indicates an abnormal condition of the EXV Driver.

SymptomCauseSolution
Circuit status is Off.Circuit is immediately stopped.Bell icon is moving on controller's display.String in the alarm list:Cx OffEXVMotorString in the alarm log:± Cx OffEXVMotorString in the alarm snapshotCx OffEXVMotorValve not connected.Referring to the wiring diagram check if the valve is correctly connected to the module.
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.11 Fail Start Low Pressure

This alarm indicates that at the compressor start the evaporating pressure or condensing pressure is below a minimum fixed limit at compressor start.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:Cx OffStartFailEvpPrLoString in the alarm log:± Cx OffStartFailEvpPrLoString in the alarm snapshotCx OffStartFailEvpPrLoAmbient temperature is too low (A/C units)or water temperature is too low (W/C units)Check the operating envelope for this machine.
Circuit refrigerant charge is too lowCheck refrigerant charge.
Check for gas leakage with a sniffer.
ResetNotes
Local HMINetworkAuto☑☑☐
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 75/85

6.6.12 Fan VFD Over Current (A/C units only)

This alarm indicates that the Inverter current has exceeded a safety limits and the inverter has to be stopped in order to avoid damages to components.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffVfdOverCurrString in the alarm log:± CxCmp1 OffVfdOverCurrString in the alarm snapshotCxCmp1 OffVfdOverCurrThe ambient temperature is too high.Check the unit selection to see if the unit can operate at full load.
Check if all fans are operating properly and are able to keep the condensing pressure at the proper level.
Clean condenser coils to allow a lower condensing pressure.
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.13 High Discharge Temperature Alarm

This alarm indicates that the temperature at the discharge port of the compressor exceeded a maximum limit which may cause damages to the mechanical parts of the compressor.

DAIKIN EWAD820TZSRB2 - High Discharge Temperature Alarm - 1

When this alarm occurs compressor's crankcase and discharge pipes may become very hot. Be careful when getting in contact with the compressor and discharge pipes in this condition.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore or even unload, circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffDischTmpHiString in the alarm log:± CxCmp1 OffDischTmpHiString in the alarm snapshotCxCmp1 OffDischTmpHiLiquid Injection solenoid valve is not operating properly.Check the electrical connection between the controller and the liquid injection solenoid valve.
Check if the solenoid coil operates properly
Check if the digital output operates correctly.
Liquid injection orifice is small.Check if when the liquid injection solenoid is activated the temperature can be controlled between the limits.
Check that the liquid injection line is not obstructed by observing the discharge temperature when it is activated.
Discharge temperature sensor could not operate properly.Check for proper operation of the discharge temperature
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.14 High Motor Current Alarm

This alarm indicates that the compressor absorbed current is exceeding a predefined limit.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore or even unload, circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffMtrAmpsHiString in the alarm log:± CxCmp1 OffMtrAmpsHiString in the alarm snapshotCxCmp1 OffMtrAmpsHiThe ambient temperature is too high (A/C units) or condenser water temperature is higher than the limit set on the unit envelope (W/C units).Check the unit selection to see if the unit can operate at full load.
Check if all fans are operating properly and are able to keep the condensing pressure at the proper level (A/C units).
Clean condenser coils to allow a lower condensing pressure (A/C units).
Check if condenser pump is operating correctly, giving enough water flow (W/C units).

D-EOMZC00106-17EN

Operation Manual

76/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

Clean condenser water heat exchanger (W/C units).
The wrong compressor model has been selected.Check the compressor model for this unit.
ResetNotes
Local HMI Network Auto☑ ☑ ☐

6.6.15 High Motor Temperature Alarm

This alarm indicates that the motor temperature has exceeded the maximum temperature limit for safe operations.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore or even unload, circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffMotorTempHiString in the alarm log:± CxCmp1 OffMotorTempHiString in the alarm snapshotCxCmp1 OffMotorTempHiInsufficient motor cooling.Check refrigerant charge.
Check if operational envelope of the unit is respected.
Motor temperature sensor could not operate properly.Check the readings of the motor temperature sensor and check the Ohmic value. A correct reading should be around hundreds of Ohm at ambient temperature.
Check the electrical connection of the sensor with the electronic board.
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.16 High Oil Pressure Differential Alarm

This alarm indicates that the oil filter is clogged and needs to be replaced.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffOilPrDiffHiString in the alarm log:± CxCmp1 OffOilPrDiffHiString in the alarm snapshotCxCmp1 OffOilPrDiffHiOil filter is clogged.Replace oil filter.
Oil Pressure Transducer is reading incorrectly.Check Oil Pressure Transducer readings with a gauge.
Condensing Pressure Transducer is reading incorrectly.Check Condensing Pressure Transducer readings with a gauge.
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.17 High Pressure alarm

This alarm is generated in case the Condensing saturated temperature rise above the Maximum condensing saturated temperature and the control is not able to compensate to this condition. The maximum condenser saturated temperature is 68.5^ C but it can decrease when the evaporator saturated temperature become negative.

In case of water cooled chillers operating at high condenser water temperature, if the Condensing saturated temperature exceeds the Maximum condenser saturated temperature, the circuit is only switched off without any notification on the screen as this condition is considered acceptable in this range of operation.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore or even unload, circuit is stopped.One or more condenser fans do not operate properly (A/C units).Check if fans protections have been activated.
Check that the fans can turn freely.
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 77/85
Bell icon is moving on controller's display. String in the alarm list: CxCmp1 OffCndPressHi String in the alarm log: ± CxCmp1 OffCndPressHi String in the alarm snapshot CxCmp1 OffCndPressHiCheck that there is not any obstacle to the free ejection of the air blown.
Condenser pump may not be operating correctly (W/C units)Check if the pump can run and give the required water flow.
Dirty or partially blocked condenser coil (A/C units).Remove any obstacle; Clean the condenser coil using soft brush and blower.
Dirty condenser heat exchanger (W/C units)Clean the condenser heat exchanger.
Inlet air temperature of the condenser is too high (A/C units).The air temperature measured at the inlet of the condenser may not exceed the limit indicated in the operational range (working envelope) of the chiller.
Check the location where the unit is installed and check that there are no any short circuit of the hot-air blown from the fans of the same unit, or even from fans of next chillers (Check IOM for proper installation).
Entering water temperature at condenser is too high (W/C units).Check the cooling tower operation and settings.
Check the three way valve operation and settings.
One or more condenser fan turning in wrong direction (A/C units).Check for correct phases sequence (L1, L2, L3) in the electrical connection of the fans.
Excessive charge of refrigerant into the unit.Check liquid sub-cooling and suction super-heat to control indirectly the correct charge of refrigerant. If necessary recover all the refrigerant to weight the entire charge and to control if the value is in line with kg indication on unit label.
Condensing pressure transducer could not operate properly.Check for proper operation of the high pressure sensor.
Wrong unit configuration (W/C units).Check that the unit has been configured for high condenser temperature applications.
ResetNotes
Local HMI Network Auto☑ ☑

6.6.18 Low Pressure alarm

This alarm is generated in case the evaporating pressure drops below the Low Pressure Unload and the control is not able to compensate to this condition.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore or even unload, circuit is stopped immediately.Bell icon is moving on controller's display. String in the alarm list:CxCmp1 OffEvpPressLoString in the alarm log:± CxCmp1 OffEvpPressLoString in the alarm snapshotCxCmp1 OffEvpPressLoTransitory condition like a fan staging (A/C units).Wait until the condition is recovered by EXV control
Refrigerant charge is low.Check sight glass on liquid line to see if there is flash gas.
Measure sub-cooling to see if the charge is correct.
Protection limit not set to fit customer application.Check the evaporator approach and the corresponding water temperature to evaluate the low pressure hold limit.
High Evaporator Approach.Clean the evaporator
Check the quality of the fluid that flows into heat exchanger.
Check the glycol percentage and type (ethilenic or propilenic)
Water flow into water heat exchanger is too low.Increase the water flow.
Check that evaporator water pump is operating correctly providing the required water flow.
Evaporating pressure transducer is not working properly.Check the sensor for proper operation and calibrate the readings with a gauge.

D-EOMZC00106-17EN

Operation Manual

78/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

EEXV is not working correctly.It's not opening enough or it's moving in the opposite direction.Check if pump-down can be finished for pressure limit reached;
Check expansion valve movements.
Check connection to the valve driver on the wiring diagram.
Measure the resistance of each winding, it has to be different from 0 Ohm.
Water temperature is lowIncrease inlet water temperature.Check the low pressure safeties settings.
ResetA/C unitsW/C unitsNotes
Local HMI
Network
Auto

6.6.19 Low Pressure Ratio Alarm

This alarm indicates that the ratio between evaporating and condensing pressure is below a limit which depends on compressor speed and guarantees the proper lubrication to compressor.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffPrRatioLoString in the alarm log:± CxCmp1 OffPrRatioLoString in the alarm snapshotCxCmp1 OffPrRatioLoCompressor is not able to develop the minimum compression.Check fan setpoint and settings, it could be too low (A/C units).
Check compressor absorbed current and discharge superheat. Compressor can be damaged.
Check the correct operation of suction / delivery pressure sensors.
Check the internal relief valve didn't opened during previous operation (check the unit history).Note:If the difference between delivery and suction pressure exceed 22bar, the internal relief valve open and need to be replaced.
Inspect the gate rotors / screw rotor for possible damages.
Check if the cooling tower or three way valves are operating correctly and properly set.
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.20 Maximum Number of Restart Alarm (A/C units only)

This alarm indicates that for three consecutive times after the compressor start the evaporating pressure is under a minimum limit for too much time

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:Cx OffNbrRestartsString in the alarm log:± Cx OffNbrRestartsString in the alarm snapshotCx OffNbrRestartsAmbient temperature is too lowCheck the operating envelope for this machine.
ResetNotes
Local HMINetworkAuto☑☑☐
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 79/85

6.6.21 Mechanical High Pressure Alarm

This alarm is generated when the condenser pressure rises above the mechanical high pressure limit causing this device to open the power supply to all the auxiliary relays. This causes an immediate shutdown of compressor and all the other actuators in this circuit.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore or even unload, circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffMechPressHiString in the alarm log:± CxCmp1 OffMechPressHiString in the alarm snapshotCxCmp1 OffMechPressHiOne or more condenser fans do not operate properly(A/C units).Check if fans protections have been activated.
Check that the fans can turn freely.
Check that there is not any obstacle to the free ejection of the air blown.
Condenser pump may not be operating correctly (W/C units)Check if the pump can run and give the required water flow.
Dirty or partially blocked condenser coil (A/C units).Remove any obstacle;Clean the condenser coil using soft brush and blower.
Dirty condenser heat exchanger (W/C units)Clean the condenser heat exchanger.
Inlet air temperature of the condenser is too high (A/C units).The air temperature measured at the inlet of the condenser may not exceed the limit indicated in the operational range (working envelope) of the chiller (A/C units).
Check the location where the unit is installed and check that there are no any short circuit of the hot-air blown from the fans of the same unit, or even from fans of next chillers (Check IOM for proper installation).
One or more condenser fan turning in wrong direction.Check for correct phases sequence (L1, L2, L3) in the electrical connection of the fans.
Entering water temperature at condenser is too high (W/C units).Check the cooling tower operation and settings.
Check the three way valve operation and settings.
Mechanical high pressure switch is damaged or not calibrated.Check for proper operation of the high pressure switch.
ResetNotes
Local HMINetworkAuto☑☒☐Reset of this alarm requires a manual action on the high pressure switch.

6.6.22 Mechanical Low Pressure Alarm (W/C units only)

This alarm is generated when the evaporating pressure drops below the mechanical low pressure limit causing this device to open. This causes an immediate shutdown of compressor to prevent from freezing.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore or even unload, circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffMechPressLoString in the alarm log:± CxCmp1 OffMechPressLoString in the alarm snapshotCxCmp1 OffMechPressLoRefrigerant charge is low.Check sight glass on liquid line to see if there is flash gas.
Measure sub-cooling to see if the charge is correct.
High Evaporator Approach.Clean the evaporator
Check the quality of the fluid that flows into heat exchanger.
Check the glycol percentage and type (ethilenic or propilenic)
Water flow into water heat exchanger is too low.Increase the water flow.
Check that evaporator water pump is operating correctly providing the required water flow.
Evaporating pressure transducer is not working properly.Check the sensor for proper operation and calibrate the readings with a gauge.
EEXV is not working correctly.It's not opening enough or it's moving in the opposite direction.Check if pump-down can be finished for pressure limit reached;
Check expansion valve movements.

D-EOMZC00106-17EN

Operation Manual

80/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

Check connection to the valve driver on the wiring diagram.
Measure the resistance of each winding, it has to be different from 0 Ohm.
ResetNotes
Local HMI
Network
Auto

6.6.23 No Pressure At Start Alarm

This alarm is used to indicate a condition where the pressure at the evaporator or at the condenser is lower than 35kPa, so the circuit is potentially empty of refrigerant.

SymptomCauseSolution
Circuit status is Off.The compressor does not startBell icon is moving on controller's display.String in the alarm list:Cx OffNoPressAtStartString in the alarm log:± Cx OffNoPressAtStartString in the alarm snapshotCx OffNoPressAtStartEvaporator or condenser pressure are below 35kPaCheck transducers calibration with an appropriate gauge.
Check transducers cabling and readout.
Check refrigerant charge and set it to the proper value.
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.24 No Pressure Change At Start Alarm

This alarm indicates that the compressor is not able to start or to create a certain minimum variation of the evaporating or condensing pressures after start.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:Cx OffNoPressChgStartString in the alarm log:± Cx OffNoPressChgStartString in the alarm snapshotCx OffNoPressChgStartCompressor cannot startCheck if the start signal is properly connected to the inverter.
Compressor is turning in wrong direction.Check correct phases sequence to the compressor (L1, L2, L3) according to the electrical scheme.
Inverter is not properly programmed with the right direction of rotation
Refrigerant circuit is empty of refrigerant.Check circuit pressure and presence of refrigerant.
Not proper operation of evaporating or condensing pressure transducers.Check proper operation of evaporating or condensing pressure transducers.
ResetNotes
Local HMINetworkAuto☑☑☐

6.6.25 Overvoltage Alarm

This alarm indicates that chiller supply voltage exceeded the maximum limit which allows proper operations of the components. This is estimated looking at the DC voltage on the inverter which depends on course from the main power.

DAIKIN EWAD820TZSRB2 - Overvoltage Alarm - 1

Resolution of this fault requires a direct intervention on the power supply of this unit. Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons. In case of doubts contact your maintenance company.

EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 81/85
SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:Cx OffOverVoltageString in the alarm log:± Cx OffOverVoltageString in the alarm snapshotCx OffOverVoltageChiller main power supply had an up peak which caused the trip.Check if main power supply is within the acceptable tolerance for this chiller
Main power supply setting on the Microtech III is not suitable with the power supply in use (A/C units).Measure the power supply to the chiller and select the proper value on the Microtech III HMI.
ResetNotes
Local HMINetworkAuto☒☒☑The alarm clears automatically when the voltage is reduced to an acceptable limit.

6.6.26 Undervoltage Alarm

This alarm indicates that chiller supply voltage exceeded the minimum limit which allows proper operations of the components.

DAIKIN EWAD820TZSRB2 - Undervoltage Alarm - 1

Resolution of this fault requires a direct intervention on the power supply of this unit.

Direct intervention on the power supply can cause electrocution, burns or even death. This action must be performed only by trained persons. In case of doubts contact your maintenance company.

SymptomCauseSolution
Circuit status is Off.The circuit is stopped.Bell icon is moving on controller's display.String in the alarm list:Cx OffUnderVoltageString in the alarm log:± Cx OffUnderVoltageString in the alarm snapshotCx OffUnderVoltageChiller main power supply had a down peak which caused the trip.Check if main power supply is within the acceptable tolerance for this chiller
Main power supply setting on the Microtech III is not suitable with the power supply in use (A/C units).Measure the power supply to the chiller and select the proper value on the Microtech III HMI.
ResetNotes
Local HMINetworkAuto☒☒☑The alarm clears automatically when the voltage is increased to an acceptable limit.

6.6.27 VFD Communication Failure

This alarm indicates a communication problem with the inverter.

SymptomCauseSolution
Circuit status is Off.The compressor does not load anymore,circuit is immediately stopped.Bell icon is moving on controller's display.String in the alarm list:CxCmp1 OffVfdCommFailString in the alarm log:± CxCmp1 OffVfdCommFailString in the alarm snapshotCxCmp1 OffVfdCommFailRS485 network is not properly cabled.Check the continuity of the RS485 network with the unit off. There should be continuity from the main controller to the last inverter as indicated on the wiring diagram.
Modbus communication is not running properly.Check inverter addresses and addresses of all the additional devices in the RS485 network (for example the energy meter).All the addresses must be different.
Modbus interface card can be faultyCheck with your service organization to evaluate this possibility and eventually replace the board.
ResetNotes
Local HMINetworkAuto☑☑☑The alarm clears automatically when the communication is re-established.

D-EOMZC00106-17EN

Operation Manual

82/85

EWAD TZ - EWAD TZ B

EWWD VZ - EWWH VZ

Air and Water cooled inverter chillers and

heat pump

7 OPTIONS

7.1 Total Heat Recovery (Optional – A/C units only)

This chiller can handle a total heat recovery option. This feature will require an additional module and sensors to read the entering and leaving heat recovery water temperatures, command a heat recovery water pump.

The heat recovery is enabled through the Q8 switch installed on the unit and requires to adjust settings on the unit controller in order to make it work as needed. First of all the function needs to be enabled on the main controller in order to display all the settings related to this function. With reference to section 4.3.5 the heat recovery enable setpoint has to be chanded to Enable.

Setpoint/Sub-MenuDefaultRangeDescription
Apply Changes=NoNo, Yes
C1 # Of Fans=6Number of fans available.
Heat Recovery=EnableDisable, Enable

When this is done the controller will need to be reset by applying the changes.

After the reboot all the heat recovery data and settings will be displayed on the HMI. In the View/Set Unit – Temperatures the heat recovery entering and leaving water temperatures will be then visible.

HR LWT=-273.1°CHeat Recovery Leaving Water Temperature (displayed only if Heat Recovery set on)
HR EWT=-273.1°CHeat Recovery Entering Water Temperature (displayed only if Heat Recovery set on)

Additionally the Heat Recovery setpoint and differential will become visible and can be adjusted as needed:

Setpoint/Sub-MenuDefaultRangeDescription
HR EWT Stp40.0°C30.0...50.0°CHeat Recovery Entering Water Setpoint
HR EWT Dif2.0°C1.0...10.0°CHeat Recovery Water Temperature differential

7.2 Energy Meter including Current Limit (Optional)

An energy meter can be optionally installed on the unit. The energy meter is connected through Modbus to the unit controller, which can display all relevant electrical data such as:

• Line to Line Voltage (per phase and average)
• Line Current (per phase and average)
- Active Power
- Cos Phi
• Active Energy

More details are described in chapter 0. All these data can be also accessed from a BMS by connecting it to a communication module. See the communication module manual for details on the device and parameter settings.

Both the energy meter device and the unit controller need to be properly set. The instructions below detail how to set the energy meter. Refer to the specific instructions of the energy meter for more detail on the operation of the device.

Energy Meter Settings (Nemo D4-L / Nemo D4-Le)
Password (Down+Enter)1000
Connection3-2Ethree phase Aron System
Address020
Baud19.2kbps
ParNoneparity bit
Time Out3sec
Password 22001
CT ratiosee CT labelcurrent transformer ratio (i.e if CT is 600:5, set to 120)
VT ratio1no voltage transformers (unless 690V chiller)
EWAD TZ - EWAD TZ B EWWD VZ – EWWH VZ Air and Water cooled inverter chillers and heat pumpD-EOMZC00106-17EN Operation Manual 83/85

Once the energy meter has been configured, do the following steps in the unit controller:

  • From Main Menu, go to View/Set Unit → Commission Unit → Configuration → Unit
  • Set Energy Mtr = Nemo D4-L or Nemo D4-Le

The energy meter option integrates the current limit function, which allows the unit to limit its capacity in order not to exceed a pre-defined current setpoint. This setpoint can be set in the unit display or can be changed from an external 4-20 mA signal.

The current limit must be set according to the following instructions:

- From Main Menu, go to View/Set Unit → Power Conservation

The following settings related to current limit option are available into the menu:

Unit CurrentDisplays the unit current
Current LimitDisplays the active current limit (which can be given by an external signal if unit is in network mode)
Current Lim SpSet the current limit setpoint (if unit is in local mode)

7.3 Rapid Restart (Optional)

This chiller can activate a Rapid Restart (optional) sequence in reaction to a power failure. A digital contact is used to inform the controller that the feature is enabled. The feature is configured in the factory.

Rapid restart is activated under the following conditions:

  • The power failure exists for up to 180 seconds
  • The unit and circuit switches are ON.
  • No unit or circuit alarms exist.
  • The unit has been running in the normal Run state
  • The BMS Circuit Mode setpoint is set to Auto when the control source is Network

If the power failure is more than 180 seconds, the unit will start based on the setting of the Stop-to-Start cycle timer (minimum setting of 3 minutes) and load per standard unit without Rapid Restart.

When Rapid Restart is active, the unit will restart within 30 seconds of power restoration. The time to restore full load is less than 3 minutes.

7.4 Inverter Pump Kit (Optional)

The inverter pump kit includes one or two centrifugal pumps, each one driven by an inverter. Pumps can be driven by:

  • a customer supplied external speed reference wire to the inverter
  • a factory wired speed reference (see 1.6.15). In this case, a fixed flow control or a variable flow control can be set.

In any case, the pump inverter needs to be loaded with the appropriate set of parameters. A detailed description of the operator panel and inverter parameters is available in the inverter instruction manual included in the documentation of the unit.

The present publication is drawn up by of information only and does not constitute an offer binding upon Daikin Applied Europe S.p.A.. Daikin Applied Europe S.p.A. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content, and the products and services presented therein. Specification are subject to change without prior notice. Refer to the data communicated at the time of the order. Daikin Applied Europe S.p.A. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Applied Europe S.p.A..

DAIKIN APPLIED EUROPE S.p.A.

Air and Water cooled inverter chillers and heat pump

D-EOMZC00106-17EN

Operation Manual 85/85

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : DAIKIN

Model : EWAD820TZSRB2

Category : Air-conditioner