USER MANUAL MAHM042CTA MRCOOL
The Signature Series is NOT designed for amateur installation. Installation SHOULD be performed by an authorized technician. Please read this manual carefully before installation and keep it for future reference.
Owner & Installation Manual

natural_image
Abstract black-and-white graphic of stylized bird-like shapes with curved and angular forms (no text or symbols)MRCOOL®
COMFORT MADE SIMPLE
Signature Series
MAHM*CTA AIR Handler
INSTALLATION INSTRUCTIONS
MAHM\*CTA Series Air Handler
This manual must be left with the homeowner for future reference.

This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.

natural_image
Exterior view of a gray industrial enclosure or cabinet with two small circular components on the side (no visible text or symbols)Table of Contents
MAH*C Unit Dimensions – Upflow – Inches (mm) .....2
Shipping and Packing List 3
General....3
Requirements 3
Installation Clearances 4
Installation 4
Condensate Drain....7
Duct System and Filters 8
Brazing Refrigerant Lines....9
Sealing the Unit 12
Electrical Connections....12
Air Flow – Cooling Blower Speed 16
Check-Out Procedures....18
Operation....18
Homeowner Maintenance....19
Repairing or Replacing Cabinet Insulation .....19
Professional Maintenance 20
Use of Air Handler During Construction....20
IMPORTANT INFORMATION FOR INSTALLER
This unit has a delay relay that delays the supply blower "ON" for 1 second and keeps the blower "ON" for 45 seconds on all fan and cooling demands. For more details, refer to page 18 for unit sequence of operation.

flowchart
graph LR
A["1 SECOND DELAY"] --> B["2"]
B --> C["3"]
C --> D["4"]
D --> E["OFF"]
B --> F["100% CFM"]
B --> G["COOLING DEMAND"]
C --> H["100% CFM"]
C --> I["45 SECS"]
Manufactured By
MRCOOL LLC
Hickory, KY 42051
*P507787-C*1
(P) 507787-01C
MAHM*CTA Unit Dimensions – Upflow – Inches (mm)

text_image
1 (25) 14-1/2 (368) C 1 (25) LINE VOLTAGE INLETS (Top and Left Side) TOP VIEW DETAIL OF PIPING PLATE 3/4 (19) SUCTION LINE LIQUID LINE 2-3/8 (60) 4-3/8 (111) 2-3/4 (70) 3-1/2 (89) 1-3/4 (44) 22 (559) CIRCUIT BREAKER COVER AIR FLOW LINE VOLTAGE INLETS (Top and Right Side) LOW VOLTAGE INLETS (Either Side) PIPING PLATE CONDENSATE DRAIN PIPING PLATE (3) (2-1/4 x 3-3/4) FILTER ACCESS SUCTION LINE LIQUID LINE 1-1/8 (29) D OPENING 1-1/8 (29) OPENING 1/2 (13) 20-3/8 (518) 1-1/8 (29)FRONT VIEW SIDE VIEW
| Dimensions | 018 024 030 | 036 / 042 048 060 | ||||||||||
| in. mm | in. mm | in. mm in. | mm in. mm | in. mm | ||||||||
| A 43-1/2 | 1105 45- | 1/2 1156 | 47 1194 53 | -5/8 1362 | 55 1397 | 59-3/4 15 | 18 | |||||
| B 18-1/2 | 470 18-1 | 2 470 18- | 1/2 470 21 | -1/2 546 | 21-1/2 546 | 21-1/2 546 | ||||||
| C 16-1/2 | 419 16-1 | 2 419 16- | 1/2 419 19 | -1/2 495 | 19-1/2 495 | 19-1/2 495 | ||||||
| D 16-1/4 | 413 16-1 | 4 413 16- | 1/4 413 19 | -1/4 489 | 19-1/4 489 | 19-1/4 489 | ||||||
Shipping and Packing List
Package 1 of 1 contains:
1 – Assembled air handler unit factory-equipped for upflow or horizontal air discharge application (includes upflow and horizontal drain pans and pre-installed air filter)
Check the air handler for shipping damage; if found, immediately contact the last carrier. Check the unit rating plate to confirm that delivered unit matches order.
NOTE: Special procedures are required for cleaning the all-aluminum coil in this unit. See Page 20 in this instruction for information.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
General
The MAHM*CTA series air handler with all-aluminum coil is designed for indoor installation only. As shipped, the unit is ready for installation in either upflow, horizontal left-hand or right-hand air discharge applications. Electric heat, downflow air discharge kits, air filters and other accessories are available and listed in the Product Specification for ordering.
This instruction is intended as a general guide and does not supersede local or national codes in any way. Consult authorities having jurisdiction before installation.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
Requirements
WARNING
Excessive Weight Hazard - Use two or more people when moving and installing the unit. Failure to do so can result in back or other type of injury.
IMPORTANT
MAHM*CTA units include a factory-installed check/expansion valve will provide optimal refrigerant control and system performance with outdoor units of varying capacities. These units must be installed as a part of a matched system as outlined in the MAHM*CTA Product Specification.
These instructions are intended as a general guide and do not supersede local or national codes in any way. Consult authorities having jurisdiction before installation.
Compliance with all local, state, or national codes pertaining to this type of equipment should be determined prior to installation. Read this instruction manual, as well as the instructions supplied in separate equipment, before starting the installation.
In addition to conforming to manufacturer's installation instructions and local municipal building codes, installation of air handler units (with or without optional electric heat), MUST conform with National Fire Protection Association (NFPA) standards: "Standard for Installation of Air Conditioning and Ventilation Systems" (NFPA No. 90A) and "Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems" (NFPA No. 90B).
All models are designed for indoor installation only. The installation of the air handler, field wiring, duct system, etc. must conform to the requirements of the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States, and any state laws, and local ordinances (including plumbing or waste water codes).
Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.
Install the conditioned air plenum, ducts and air filters (provided) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air-Conditioning Systems (latest edition).
The air handler is shipped from the factory completely assembled. The unit is provided with flanges for the connection of the duct system.
Do not remove the cabinet knockouts until it has been determined which knockouts will need to be removed for the installation.
Select the air discharge position which best suits the site conditions. Consider required clearances, space, routing requirements for refrigerant line, condensate disposal, filters, duct system, wiring, and accessibility for service. Refer to the rating plate on the air handler for specific information.

WARNING
Danger of explosion. Keep flammable materials and vapors, such as gasoline, away from air handler. Place air handler so that heating elements are at least 18 inches (46 cm) above the floor for a garage installation. Failure to follow these instructions can result in death, explosion or fire.
IMPORTANT
Excessive condensation may occur if the unit is installed in a warm, humid place. When the unit is installed in an unconditioned space, apply sealant around electrical wires, refrigerant piping and condensate lines at the point where they enter the cabinet.
Apply sealant on the inside of the cabinet at the point where the electrical wires exit through the conduit opening. This will also keep warm and moist unconditioned air out of the air handler cabinet where it will form condensate on the cooler control box and electrical controls.
IMPORTANT
This unit is approved for installation clearance to combustible material as stated on the unit rating plate. Accessibility and service clearances must take precedence over combustible material clearances.
The air handler must be installed so that free access is allowed to the coil/filter compartment and blower/control compartment.
- During cooling operation, excessive sweating may occur if the air handler is installed in a warm and humid space.
-
If installed in an unconditioned space, sealant should be applied around the electrical wires, refrigerant tubing, and condensate lines where they enter the cabinet.
-
Electrical wires should be sealed on the inside where they exit the conduit opening. Sealant is required to prevent air leakage into, and condensate from forming inside of, the air handler, the control box, and on the electrical controls.
- This unit is approved for installation clearance to combustible material as stated on the unit rating plate. Accessibility and service clearances must take precedence over combustible material clearances.
- The air handler must be installed so that free access is allowed to the coil/filter compartment and blower/control compartment.
Installation Clearances
Non-Ducted Return Closet Installation
The air handler can be installed in a closet with a false bottom to form a return air plenum. It may also be installed with a return air plenum under the air handler.
Louvers or return air grilles are field-supplied. Local codes may limit application of systems without a ducted return to single-story buildings.
When a MAHM*CTA unit is installed in a closet with a louvered return opening, the minimum open area for the louvers will be:
• 320 square inches for -018 and -024 models;
• 360 square inches for -030 and -036 models;
• 450 square inches for -042 thru -060 models
If the free area is not known, assume a 25% free area for wood or a 75% free area for metal louvers or grilles. Using the louver dimensions and the 25% or 75% assumption, determine if the open area meets the minimum open area listed above.
If a return air plenum is used, the return air grille should be immediately in front of the opening in the plenum to allow for the free flow of return air. When not installed in front of the opening, there must be adequate clearance around the air handler to allow for the free flow of return air.
Installation
Each unit consists of a blower assembly, refrigerant coil, and controls in an insulated galvanized steel factory-finished enclosure. Knockouts are provided for electrical wiring entrance.
For ease in installation, it is best to make any necessary coil configuration changes before setting air handler in place.
Refrigerant Metering Device
MAHM'CTA units are equipped with a factory-installed check/expansion valve or an RFC device.
Upflow Application
- The air handler must be supported on the bottom only and set on solid floor or field-supplied support frame. Securely attach the air handler to the floor or support frame.
- If installing a unit in an upflow application, remove the horizontal drain pan.
NOTE: The horizontal drain pan is not required in upflow air discharge installations; its removal provides the best efficiency and air flow. - Place the unit in the desired location and slope unit. Connect return and supply air plenums as required using sheet metal screws.
- Install units that have no return air plenum on a stand that is at least 14" from the floor. This will allow proper air return.

text_image
UP-FLOW / DOWN-FLOW DRAIN PAN HORIZONTAL DRAIN PAN (MUST BE REMOVED)Figure 1. Upflow Configuration
Horizontal Applications

IMPORTANT
When removing the coil, there is a possibility of danger of equipment damage and personal injury. Be careful when removing the coil assembly from a unit installed in right- or left-hand applications. The coil may tip into the drain pan once it is clear of the cabinet. Support the coil when removing it.
NOTE: When the unit is installed in horizontal applications, a secondary drain pan is recommended. Refer to local codes.
NOTE: This unit may be installed in left-hand or right-hand air discharge horizontal applications. Adequate support must be provided to ensure cabinet integrity. Ensure that there is adequate room to remove service and access panels if installing in the horizontal position.
Right-Hand Discharge
- Determine which plugs are required for drain line connections.
- With access door removed, remove drain line plugs to install drain lines.
- Set unit so that it is sloped toward the upflow drain pan end of the unit and level from front to back of unit (see Figure 6).
- The horizontal configuration is shown in Figure 2.

text_image
AIR FLOW Drains RIGHT-HAND DRAINS PLUGSFigure 2. Right-Hand Discharge Configuration
- If the unit is suspended, the entire length of the cabinet must be supported. If you use a chain or strap, use a piece of angle iron or sheet metal attached to the unit (either above or below) to support the length of the cabinet. Use securing screws no longer than 1/2 inch to avoid damaging the coil or filter. See Figure 3. Use sheet metal screws to connect the return and supply air plenums as required.

text_image
ANGLE IRON OR SHEET METAL MAXIMUM 1/2" LONG SCREW AIR FLOW WEIV FRONT WEND ELECTRICAL INLET CLEAR- ANCE 4 IN. (102 MM)Figure 3. Suspending Horizontal Unit
Left-Hand Air Discharge
For horizontal left-hand air discharge, the following field modifications are required.
- Remove access panels and the corrugated padding between the blower and coil assembly. Discard the corrugated padding.
- Pull the coil assembly from unit. Pull off the horizontal drain pan.
- Remove the drain plugs from back drain holes on horizontal drain pan and reinstall them on front holes.
IMPORTANT
After removal of drain pan plug(s), check drain hole(s) to verify that drain opening is fully open and free of any debris. Also check to make sure that no debris has fallen into the drain pan during installation that may plug up the drain opening.
- Rotate drain pan 180° front-to-back and install it on the opposite side of the coil.
- Remove screws from top cap.
- Remove plastic plug from left hole on coil front end seal and reinstall plug in back hole.

text_image
TOP CAP ROTATED TO CORRECT POSITION CABINET SUPPORT TOP CAP SCREWS 90° BEND DRAIN PAN REINSTALLED HERE DRAIN PLUGS REINSTALLED HERE REMOVED FROM HERE COIL SHOWN IN UPLOAD POSITION FOR EASY CONVERSION TOP CAP 90° BEND ALIGN HOLES WITH HOLES IN COIL END PLATE. STARTING WITH THE ROUND HOLES ON THIS END. BACK COIL END SEALFigure 4. Field Modification for Left-Hand Discharge
- Rotate top cap 180° front-to-back and align with unused screw holes. Holes must align with front and back coil end plates. The top cap has a 45° bend on one side and a 90° bend on the other. The 90° bend must be on the same side as the horizontal drain pan as illustrated in Figure 4.

text_image
DOWN-FLOW RAIL FRONT EDGE OF HORIZONTAL DRAIN PANFigure 5. Left-Hand Discharge Configuration
NOTE: Be very careful when reinstalling the screws into the coil end plate engaging holes. Misaligned screws may damage the coil.
- From the upflow position, flip cabinet 90° to the left and set into place. Replace blower assembly. Secure coil in place by bending down the tab on the cabinet support rail as illustrated.
- Install the horizontal shield (-060 model) on the front edge of the horizontal drain pan as illustrated in Figure 5.
NOTE: For horizontal applications in high humidity areas, remove the downflow rail closest to the drain pan. To remove rail, remove screw from rail at back of unit and at cabinet support rail. Remove downflow rail then replace screws. Also, seal around the exiting drain pipe, liquid and suction lines to prevent infiltration of humid air.
- Knock out drain seal plate from access door. Secure plate to cabinet front flange with screw provided.
- Flip access door and replace it on the unit.
- Set unit so that it is sloped 1/4" toward the drain pan end of the unit. Connect return and supply air plenums as required using sheet metal screws.
- If suspending the unit, it must be supported along the entire length of the cabinet. If using chain or strap, use a piece of angle iron or sheet metal attached to the unit (either above or below) so that the full length of the cabinet is supported. Use securing screws no longer than 1/2" to avoid damage to coil or filter, as illustrated in Figure 3. Connect return and supply air plenums as required using sheet metal screws.
Downflow Application
NOTE: If downflow application is required, separately order kit number 83M57 and install per kit's instructions. Also use metal or class I supply and return air plenums. Use the installation instruction provided with the downflow kit.
IMPORTANT
If electric heat section with circuit breakers (ECBA25) is installed in a MAHM*CTA unit in a downflow application, the circuit breakers must be rotated 180° to the UP position. See ECBA25 installation instructions for more details.
Condensate Drain

IMPORTANT
On units of this type, where the blower "draws" rather than "blows" air through the coil, traps must be installed in the condensate drain lines (primary and auxiliary, if used). Traps prevent the blower from drawing air through the drain lines into the air supply.

IMPORTANT
A field-fabricated secondary drain pan, with a drain pipe to the outside of the building, is required in all installations over a finished living space or in any area that may be damaged by overflow from the main drain pan. In some localities, local codes may require a secondary drain pan for any horizontal installation.
Sloping The Unit
Make sure the unit is sloped (similar to the slope shown in Figure 6) so that the drain pan will empty completely without water standing in the pan.
THIS CORNER SHOULD BE 5/8" (+/- 1/8") HIGHER THAN DRAIN CORNER

text_image
LEVEL PLANE DRAIN CORNER LEVEL PLANEFigure 6. Sloping the Unit for Proper Drainage

flowchart
graph TD
A["ABOVE FINISHED SPACE?"] --> B{NO}
B --> C{YES}
C --> D["AIR HANDLER DRAIN PAN"]
D --> E["MAIN DRAIN"]
E --> F["CUT TO REQUIRED LENGTH"]
F --> G["PROVIDED PIPE NIPPLE 2"]
G --> H["SIDE VIEW"]
H --> I["FOR NEGATIVE PRESSURE COILS (BLOWER AFTER COIL) TRAPS ARE REQUIRED ON ALL DRAIN LINES CONNECTED TO COIL."]
I --> J["TRAP DEPTH"]
J --> K["TO APPROVED DRAIN"]
K --> L["DRAIN LINE SHOULD SLOPE A MINIMUM OF ONE INCH PER 10 FEET (25MM PER 3 METERS)."]
M["CONTENTS"] --> N["PART # X3169"]
N --> O["COMPACT OVERFLOW SWITCH WITH 3/4" FEMALE SLIP INLET AND MALE ADAPTER, TWO PART DESIGN FOR USE WHERE OBSTRUCTIONS PREVENT DIRECT THREADING"]
P["VEENT MUST EXTEND ABOVE HEIGHT OF COIL DRAIN PAN BY TWO INCHES (51MM)"] --> Q["1" X 3/4" X 3/4" REDUCING TEE WITH PLUG"]
Q --> R["MAIN DRAIN"]
R --> S["CUT TO REQUIRED LENGTH"]
S --> T["PROVIDED PIPE NIPPLE 2"]
T --> U["SIDE VIEW"]
U --> V["FOR NEGATIVE PRESSURE COILS (BLOWER AFTER COIL) TRAPS ARE REQUIRED ON ALL DRAIN LINES CONNECTED TO COIL."]
Figure 7. Typical Main and Overflow Drain
Install Condensate Drain
The air handler is provided with 3/4" NPT condensate drain connections.

IMPORTANT
On some pans, the primary and secondary drain holes have knockouts.
Confirm primary and secondary drains are open.
- MAHM*CTA units are equipped with a drain pan, which includes green (main drain) and red (secondary drain) plugs. Unscrew the plugs to remove them before inserting condensate drain fittings.

text_image
UNSCREW PLUGS AND CONNECT PROPERLY SIZED FIELD-PROVIDED FITTINGS AND DRAIN LINES. DRAIN PAN GREEN MAIN DRAIN PLUG RED SECONDARY DRAIN PLUGFigure 8. Drain Line Connections
- Install properly sized, field-provided connection fittings and connect primary drain line to the main drain pan connection.
NOTE: When installing drain line connection fittings to the drain pan, hand tighten the fitting and use a thread sealant. Over-tightening the fittings can split connections on the drain pan.
-
If the secondary drain line is to be used, remove the plug or the knockout and route the drain line so that water draining from the outlet will be easily noticed by the homeowner. Refer to local codes for drain trap requirements on the secondary drain line.
-
Check again to ensure drain ports and drain pan are free of all debris.
-
Plug and check any unused drain pan openings for tightness. Torque plugs to 30 in. lb. to prevent water leaks or seepage from the drain pan.
-
Install a 2" trap in the main (primary) drain lines as close to the unit as practical (see Figure 7). Make sure the top of the trap is below the connection to the drain pan to allow complete drainage of the pan.
NOTE: Horizontal runs must have an anti-siphon air vent (standpipe) installed ahead of the horizontal run. See Figure 7. An extremely long horizontal run may require an oversized drain line to eliminate air traps.
NOTE: Do not operate air handler without a trap in the main (primary) drain. The condensate drain is on the negative pressure side of the blower; therefore, air being pulled through the condensate line will not allow positive drainage without a proper trap.
- Route the drain line to the outside or to an appropriate drain. Drain lines must be installed so they do not block service access to the front of the air handler. A 24" clearance is required for filter, coil, or blower removal and service access.
NOTE: Check local codes before connecting the drain line to an existing drainage system. Insulate the drain lines where sweating could cause water damage.
Test Condensate Drain
Test the drain pan and drain line after installation:
- Pour several quarts of water into drain pan. Use enough water to fill both the drain trap and the line.
- Check the installed drain pan. Drain pan must be draining completely. Drain line fittings must not be leaking. Water must be draining from the end of the primary drain line.
- Correct any leaks found.
Duct System and Filters
Duct System
The air handler is provided with flanges for the connection of the supply plenum.
Supply and return duct system must be adequately sized to meet the system's air requirements and static pressure capabilities. The duct system should be insulated with a minimum of 1" thick insulation with a vapor barrier in conditioned areas or 2" minimum in unconditioned areas.
Supply plenum should be the same size as the flanged opening provided around the blower outlet and should extend at least 3 ft. from the air handler before turning or branching off plenum into duct runs. The plenum forms an extension of the blower housing and minimizes air expansion losses from the blower.
Filters
A filter is provided. Table 1 lists the filter size for each unit.
| Model Filter Size + in. |
| -018, -024, -030 15" x 20" x 1" |
| -036, -042, -048, -060 18" x 20" x 1" |
Table 1. Unit Air Filter Size Chart
IMPORTANT
If a high efficiency filter is being installed as part of this system to ensure better indoor air quality, the filter must be properly sized. High efficiency filters have a higher static pressure drop than standard efficiency glass/foam filters. If the pressure drop is too great, system capacity and performance may be reduced. The pressure drop may also cause the limit to trip more frequently during the winter and the indoor coil to freeze in the summer, resulting in an increase in the number of service calls. Before using any filter with this system, check the specifications provided by the filter manufacturer against the data given in the appropriate Product Specifications. Additional information is provided in Service and Application Note ACC002 (August 2000).
Installing Duct System
Connect supply air duct to the flange on top of the air handler. If an isolation connector is used, it must be nonflammable.
Field-Fabricated Return Air Duct Flange for Horizontal Applications
A return air duct system is recommended, but not factory-provided. If the unit is installed in a confined space or closet, run a full-size return connection to a location outside the closet.
Cabinet and Duct Flange

text_image
CABINET DOOR FLANGE 1-1/2 (38) DUCT FLANGE 3/4 (19) 3/4 (19) "A" 1-1/2(38) BRAKE DOWN 90 DEGREES 1/2 (13) 1/4 (6) DIA. 2-HOLES 3/4 (19) BOTTOM OF CABINET DUCT ADAPTER 1-1/2 (38)| UNIT SIZE | "A" |
| -018, -024,-030 | 18-3/8" |
| -036, -042,-048, -060 | 21-1/2" |
Figure 9. Cabinet and Duct Flange
Brazing Refrigerant Lines
Refrigerant lines must be connected by a qualified technician in accordance with established procedures.
IMPORTANT
Refrigerant lines must be clean, dry, refrigerant-grade copper lines. Air handler coils should be installed only with specified line sizes for approved system combinations.
Handle the refrigerant lines gently during the installation process. Sharp bends or kinks in the lines will cause a restriction.
Do not remove the caps from the lines or system connection points until connections are ready to be completed.
WARNING
Polyol ester (POE) oils used with HFC-410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
WARNING

Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture. Check the high and low pressures before applying heat.
WARNING

When using a high pressure gas such as nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well-ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
IMPORTANT
To prevent the build-up of high levels of nitrogen when purging, it must be done in a well-ventilated area. Purge low-pressure nitrogen (1 to 2 psig) through the refrigerant piping during brazing. This will help to prevent oxidation and the introduction of moisture into the system.
NOTE: Recommended line length is 50' or less. If more than 50' line set is required, contact MRCOOL.
-
Route the suction and liquid lines from the fittings on the indoor coil to the fittings on the outdoor unit. Run the lines in a direct path, avoiding unnecessary turns and bends.
-
Make sure that the suction line is insulated over the entire exposed length and that neither suction nor liquid lines are in direct contact with floors, walls, duct system, floor joists, or other piping.
-
To avoid damaging the rubber grommets in the cabinet while brazing, slide the rubber grommets over the refrigerant lines until they are away from the heat source.
NOTE: Place wet rags against piping plate and around suction line connections.
-
Connect the suction and liquid lines to the evaporator coil. Take care to protect the cabinet and internal components as detailed in Figure 10.
-
Braze using an alloy of silver or copper and phosphorus with a melting point above 1,100°F (593°C).
NOTE: Do not use soft solder.
- Allow refrigerant pipes to cool to room temperature.
NOTE: Make sure to route copper refrigerant tubing away from sharp edges and make sure that it does not touch other metal surfaces. This prevents damage caused by vibration or metal-on-metal contact.
- Reinstall the rubber grommets into the refrigerant piping panel.
NOTE: Make sure expansion valve capillary tube is not touching metal edges or copper tubing.
- Make sure outdoor unit has been placed according to the Installation Instructions and is connected to the refrigerant lines
PLEASE READ IMPORTANT ISSUES CONCERNING BRAZING OPERATIONS IN THE BRAZING REFRIGERANT LINES SECTION BEFORE PROCEEDING.
NOTE - REFER TO OUTDOOR UNIT INSTALLATION INSTRUCTIONS FOR REFRIGERANT PIPING SIZE REQUIREMENTS.
NOTE - Use silver alloy brazing rods with five or six percent minimum silver alloy for copper-to-copper brazing, 45 percent alloy for copper-to-brass and copper-to-steel brazing.
A REMOVE ACCESS PANEL
B REMOVE RUBBER PLUG FROM BOTH LIQUID AND SUCTION LINES
NOTE - MAHM*CTA SERIES UNITS USE NITROGEN OR DRY AIR AS A HOLDING CHARGE. IF THERE IS NO PRESSURE WHEN THE RUBBER PLUGS ARE REMOVED, CHECK THE COIL FOR LEAKS BEFORE INSTALLING.
C EITHER REMOVE OR PUSH PIPE WRAPPING BACK THROUGH HOLE IN PIPING PLATE BEFORE LINE SET CONNECTION AND BRAZING.
D CONNECT PIPES
NOTE - REFRIGERANT LINE SETS SHOULD BE ROUTED TO ALLOW FILTER ACCESSIBILITY.

natural_image
Simple line drawing of a mechanical assembly with cylindrical components and wires, no text or symbols present.F PLACE A WET RAG AGAINST PIPING PLATE AND AROUND THE SUCTION LINE CONNECTION.
G BRAZE CONNECTION. ALLOW PIPE TO COOL BEFORE REMOVING WET RAG FROM CTXV SENSING BULB AND PIPING PANEL AREA.
H REPEAT PREVIOUS PROCEDURE FOR LIQUID LINE.

natural_image
Cross-sectional diagram of a mechanical device showing internal components and wiring (no text or labels)PIPING PLATE
E CONNECT GAUGES AND START NITROGEN FLOW
FLOW REGULATED NITROGEN (AT 1 TO 2 PSIG) THROUGH THE REFRIGERATION GAUGE SET INTO THE VALVE STEM PORT CONNECTION ON THE OUTDOOR UNIT LIQUID LINE SERVICE VALVE AND OUT OF THE VALVE STEM PORT CONNECTION ON THE SUCTION SERVICE VALVE.

natural_image
Close-up of a pressure regulator with two gauges and tubing (no visible text or symbols)

natural_image
Line drawing of a mechanical assembly or installation with a tool inserted into a panel (no text or symbols)REFER TO INSTRUCTIONS PROVIDED WITH OUTDOOR UNIT FOR LEAK TESTING, EVACUATING AND CHARGING PROCEDURES
Figure 10. Brazing Connections
Sealing the Unit
Seal the unit so that warm air is not allowed into the cabinet. Warm air introduces moisture, which results in water blow-off problems. This is especially important when the unit is installed in an unconditioned area.
If installed in an unconditioned space, sealant should be applied around the electrical wires, refrigerant tubing, and condensate lines where they enter the cabinet.
WARNING
There must be an airtight seal between the bottom of the air handler and the return air plenum. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the air handler cabinet to ensure a tight seal. Return air must not be drawn from a room where this air handler or any gas-fueled appliance (i.e., water heater), or carbon monoxide-producing device (i.e., wood fireplace) is installed.
IMPORTANT
Use duct tape and/ or Permagum to seal closed any space around the holes where the drain lines exit the cabinet. Warm air must not be allowed to enter through any gaps or holes in the cabinet.
Electrical Connections
WARNING

Electric shock hazard! - Disconnect all power supplies before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electric shock.
WARNING
Run 24V Class II wiring only through specified low voltage opening. Run line voltage wiring only through specified high voltage opening. Do not combine voltage in one opening.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be properly grounded in accordance with national and local codes.

Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
WARNING
Electric Shock Hazard.
Can cause injury or death.

Foil-faced insulation has conductive characteristics similar to metal. Be sure there are no electrical connections within 1/2" of the insulation. If the foil-faced insulation comes in contact with electrical voltage, the foil could provide a path for current to pass through to the outer metal cabinet. While the current produced may not be enough to trip existing electrical safety devices (e.g., fuses or circuit breakers), the current can be enough to cause an electrical shock hazard that could cause personal injury or death.
- Wiring must conform to the current National Electric Code ANSI/NFPA No. 70, or Canadian Electric Code Part I, CSA Standard C22.1, and local building codes. Refer to following wiring diagrams. See unit nameplate for minimum circuit ampacity and maximum over-current protection size.
- Electrical wiring, disconnect means and over-current protection are to be supplied by the installer. Refer to the air handler rating plate for maximum over-current protection, minimum circuit ampacity, as well as operating voltage. Select the proper supply circuit conductors in accordance with tables 310-16 and 310-17 in the National Electric Code, ANSI/NFPA No. 70 or tables 1 through 4 in the Canadian Electric Code, Part I, CSA Standard C22.1.
- The power supply must be sized and protected according to the specifications supplied on the product.
-
This air handler is factory-configured for 240 volt, single phase, 60 cycles. For 208-volt applications, see "208 Volt Conversion" later in this section.
-
Separate openings have been provided for 24V low voltage and line voltage. Refer to the dimension illustration of specific location.
- This unit is provided with holes for conduit. Use provided caps to seal holes not used.
- Typical unit wiring (as well as wiring of optional field-installed electric heat) is given in Figure 14. Refer to the instructions provided with the electric heat section for proper installation.
WARNING
USE COPPER CONDUCTORS ONLY
- Disconnect all power supplies.
- Remove the air handler access panel.
- Route the field supply wires to the air handler electrical connection box.
- Use UL-listed wire nuts to connect the field supply conductors to the unit black and yellow leads, and the ground wire to ground terminal marked GND.
- Replace the air handler access panel.

text_image
TOP SIDEFigure 11. Electrical Connections (Upflow Configuration)
NOTE: To avoid the possibility of moisture damage to the control in some right-hand discharge configurations, the control panel can be relocated to the end panel as shown in Figure 12.

text_image
TOP SIDEFigure 12. Control Panel Relocated to End Panel (Left-Hand Horizontal Configuration)
208 Volt Conversion
- Disconnect all power supplies.
- Remove the air handler access panel.
- Using the wiring diagram located on the unit access panel as a reference, move the 2 connected black transformer leads from the 240 volt terminal on the transformer to the 208 volt terminal on the transformer.
WARNING

Electrically ground air handler. Connect ground wire to ground terminal marked "GND". Failure to do so can result in death or electrical shock.
208 / 240 VOLT TRANSFORMER

text_image
PRIMARY SECONDARY 240 Volts 208 VoltsFigure 13. Converting Unit from 240VAC to 208VAC

text_image
PART NO. 537980-01 WIRING DIAGRAM - ELECTRIC HEAT 20KW 12.5KW & 15KW 7.5KW & 10KW 5KW HEATERS USED 5 KW = HTR1 7.5 & 10 KW = HTR1 & HTR2 15 KW = HTR1,HTR2 & HTR3 20 KW = HTR1,HTR2,HTR3 & HTR4 TB = TERMINAL BLOCK CB = CIRCUIT BREAKER SEQ = SEQUENCER GND = GROUND LUG PRI LS= LIMIT SWITCH SEC L= LIMIT SWITCH HTR = HEATER ELEMENT POWER (FACTORY WIRED) POWER (FIELD WIRED) CONTROL (FACTORY WIRED) CONTROL (FIELD WIRED) CONTROL CIRCUIT WIRING TO BE 24 VOLT, N.E.C. CLASS 2 THREE POLE SEQUENCER PLUG PIN ON OFF LOCATION 1-20 40-110 20-63 1-30 20-62 1-30 TWO POLE SEQUENCER TIMING - SEC ON OFF 30-90 1-30 30-90 1-30 TD = TIME DELAY (OPT.) TR = TRANSFORMER BR = BLOWER RELAY MTR = BLOWER MOTOR CAP = MOTOR CAPACITOR GND = GROUND CONNECTION WIRING DIAGRAM: NO HEAT WIRE NUTS BY OTHERS L1 L2 OR SUPPLY VOLTAGE 1 BLK 14 RED(LO) 4 BLK(HB) 3 BLK MTR 2 GRN/WH T 14 RED(LO) 4 BLK(HB) 3 BLK MTR 2 GRN/WH T 14 RED(LO) 4 BLK(HB) 3 BLK MTR 2 GRN/WH T 14 RED(LO) 4 BLK(HB) 3 BLK MTR 2 GRN/WH T 14 RED(LO) 4 BLK(HB) 3 BLK MT R 14 RED(LO) 4 BLK(HB) 3 BLK MT R 14 RED(LO) 4 BLK(HB) 3 BLK MT R 14 RED(LO) 4 BLK(HB) 3 BLK MT R 14 RED(LO) 4 BLK(HB) 3 BLK MT R 14 RED(LO) 4 BLK(HB) 3 BLK MT T R 14 RED(LO) 4 BLK(HB) 3 BLK MT R 14 RED(LO) 4 BLK(HB) 3 BLK MT R 14 RED(LO) 4 BLK(HB) 3 BLK MT R 14 RED(LO) 4 BLK(HB) 3 BLK MT R 14 RED(LO) 4 BLK(HB) 3 BLK MTR 2 GRN/WH T 14 RED(LO) 4 BLK(HB) 3 BLK MT R 14 RED(LO) 4 BLK(HB) 3 BLK MT R 14 RED(LO) 4 BLK(HB) 3 BLK MT R 14 RED(LO) 4 BLK(HBB) THERMOSTAT BY OTHERSFACTORY SPEED SET TO MEDIUM (BLUE)

text_image
ELECTRIC HEAT PSC LABEL WIRING DIAGRAM Supersodes 0319 Form No. 537980-01 © 2011 Ufro U.S.A.Figure 14. Typical Wiring Diagram MAHM*CTA Air Handler with Electric Heat – PSC (018, 024, 030, 036, 042 models)

| ELECTRIC HEAT | |
| CONSTANT TORQUE LABEL WIRING DIAGRAM | |
| Superseries | |
| 041B | Form No. 537981-01 |
Figure 15. Typical Wiring Diagram MAHM*CTA Air Handler with Electric Heat – CT (048 and 060 models)

flowchart
Air and heat pump system diagram showing connections between air handler, heater, and cooling-only applications with electric heat application.Figure 16. Low Voltage Connections (3-Speed PSC Motor) – Field Wiring
Air Flow – Cooling Blower Speed
The cooling blower speed is factory configured to provide correct air flow for an outdoor unit that matches the cooling capacity rating of the air handler.
If the outdoor unit is smaller than the maximum cooling capacity rating for the air handler, the cooling blower speed may need to be changed. Refer to blower performance chart in Table 2.

text_image
WARNING Electric shock hazard! - Disconnect all power supplies before servicing. Replace all parts and panels before operating. Failure to do so can result in death or electrical shock.Change Blower Speed
- Disconnect all power supplies.
- Remove the air handler access panel.
- Locate pin number 2 on the blower relay. Two black wires are connected to this terminal pin. One connects to pin number 5 on the blower relay, one connects to an in-line splice connecting to a blue wire.
- Select the required blower motor speed. Connect red-LO or black-HI and plug it into the 4-pin blower relay harness connector.
NOTE: Reuse the factory-installed wire nut on the unused wires. - Replace all panels.
- Reconnect power.
BLOWER RELAY
NOTE - Refer to wiring diagram located on the unit access panel, this figure and blower performance (table 2).
- All air data measured external to unit with 1 inch non-pleated air filter in place.
• All factory settings are medium speed. - All data given while air handler is operating with a dry DX coil.
- All downflow applications run on high speed when utilizing electric heat.

text_image
AY 3 6 4 5 BLOWER RELAY HARNESS BLUE (MED) 2 PLASTIC CAPS RED (L0) BLACK (HI) GND BRN/MHT BRN MTR BLUE RED BLK YEL 4-PIN BLOWER CONNECTOR YELLOW (COM)Figure 17. Changing Blower Speed
NOTE: To change blower speed on Constant Torque -048 and -060 units, remove the wire from terminal Y1 on the strip and install on either of the speeds not being used (Brown TAP 2 or Black TAP 5).
| Air Handler Model | Blower Speed | .10" WC | .20" WC | .30" WC | .40" WC | .50" WC |
| -018 | LOW 538 525 503 471 418 | |||||
| MED 688 670 639 603 548 | ||||||
| HIGH 919 881 855 788 710 | ||||||
| -024 | LOW 677 673 657 629 592 | |||||
| MED 1011 979 942 803 742 | ||||||
| HIGH 1106 1045 | 999 917 857 | |||||
| -030 | LOW 871 870 853 812 769 | |||||
| MED | 1078 | 1057 | 1024 987 936 | |||
| HIGH 1311 1261 | 1214 1154 1086 | |||||
| -036 | LOW | 1020 972 956 909 806 | ||||
| MED | 1276 | 1240 1191 | 1148 1086 | |||
| HIGH | 1559 | 1521 | 1446 | 1395 | 1327 | |
| -042 | LOW | 1300 | 1273 | 1250 | 1211 | 1155 |
| MED | 1527 | 1493 | 1452 | 1390 | 1345 | |
| HIGH | 1816 | 1756 | 1693 | 1605 | 1528 | |
| -048 | LOW | 1257 | 1212 | 1157 | 1116 | 1053 |
| MED LOW | 1486 | 1448 1411 1364 | 1330 | |||
| MED | 1721 | 1675 | 1630 | 1594 | 1553 | |
| MED HIGH | 1721 | 1675 | 1630 | 1594 | 1553 | |
| HIGH | 1840 | 1794 | 1754 | 1721 | 1681 | |
| -060 | LOW | 1098 | 1049 | 1001 926 831 | ||
| MED LOW | 1624 | 1594 | 1565 | 1520 | 1492 | |
| MED | 1815 | 1783 | 1758 | 1730 | 1685 | |
| MED HIGH | 1903 | 1869 | 1837 | 1809 | 1764 | |
| HIGH | 1981 | 1957 | 1923 | 1893 | 1861 | |
| Blower Performance (CFM vs. ESP inches H20)Cooling speeds should not be reduced below factory setting.All units with electric heat approved at 0.5" maximum and medium blower speed minimum.All downflow applications run on high speed when utilizing electric heat. | ||||||
Table 2. MAHM*CTA Blower Performance (3-Speed PSC) – 240V (CFM @ ESP. – in. W. C.)
Check-Out Procedures
NOTE: Refer to outdoor unit installation instructions for system start-up instructions and refrigerant charging instructions.
Pre-Start-Up Checks
- Is the air handler properly and securely installed?
- If horizontally configured, is the unit sloped up to 5/8 inch toward drain lines?
- Will the unit be accessible for servicing?
- Has an auxiliary pan been provided under the unit with separate drain for units installed above a finished ceiling or in any installation where condensate overflow could cause damage?
- Have ALL unused drain pan ports been properly plugged?
- Has the condensate line been properly sized, run, trapped, pitched, and tested?
- Is the duct system correctly sized, run, sealed, and insulated?
- Have all cabinet openings and wiring been sealed?
- Is the indoor coil factory-installed TXV or RFC properly sized for the outdoor unit being used?
- Have all unused parts and packaging been disposed of?
• Is the filter clean, in place, and of adequate size?
• Is the wiring neat, correct, and in accordance with the wiring diagram? - Is the unit properly grounded and protected (fused)?
- Is the thermostat correctly wired and in a good location?
- Are all access panels in place and secure?
Check Blower Operation
- Set thermostat to FAN ON. The indoor blower should come on.
Check Cooling Operation
- Set thermostat to force a call for cooling (approximately 5^ F lower than the indoor ambient temperature).
- The outdoor unit should come on immediately and the indoor blower should start between 30 - 60 seconds later.
- Check the air flow from a register to confirm that the system is moving cooled air.
- Set the thermostat 5°F higher than the indoor temperature. The indoor blower and outdoor unit should cycle off.
Check Electric Heat (If Used)
- Set thermostat to call for auxiliary heat (approximately 5^ F above ambient temperature). The indoor blower and auxiliary heat should come on together. Allow a minimum of 3 minutes for all sequencers to cycle on.
- Set the thermostat so that it does not call for heat. Allow up to 5 minutes for all sequencers to cycle off.
Operation
Time Delay Relay
Blower time delay operation:
- When cooling demand is initiated, there is a 1 second motor-on delay.
- After the motor-on delay expires, motor ramps up to 100% and runs at 100% until cooling demand is satisfied.
- Once demand is met, motor runs at 100% for 45 seconds.
- Motor ramps down to stop.

flowchart
graph LR
A["1 SECOND DELAY"] --> B["2"]
B --> C["3"]
C --> D["4"]
D --> E["OFF"]
B --> F["COOLING DEMAND"]
F --> G["45 SECS"]
style A fill:#f9f,stroke:#333
style B fill:#ccf,stroke:#333
style C fill:#cfc,stroke:#333
style D fill:#fcc,stroke:#333
style E fill:#ffc,stroke:#333
Figure 18. Blower Time Delay
Cooling (Cooling Only or Heat Pump)
When the thermostat calls for cooling, 24 volts is put on the blower time-delay relay coil and then the indoor blower relay energizes. The normally open contacts close, causing the indoor blower motor to operate. The circuit between R and Y is completed, closing the circuit to the contactor in the outdoor unit, starting the compressor and outdoor fan motor.
On heat pumps, circuit R and O energizes the reversing valve, switching the valve to the cooling position. (The reversing valve remains energized as long as the thermostat selector switch is in the COOL position.)
At the completion of the cooling demand the indoor blower and outdoor unit should cycle off. Air handler should cycle off 45 seconds after the outdoor unit shuts off.
Heating (Electric Heat Only)
When the thermostat calls for heat, the circuit between R and W is completed, and the heat sequencer is energized. A time delay follows before the heating elements and the indoor blower motor come on. Units with a second heat sequencer can be connected with the first sequencer to W on the thermostat sub-base, or they may also be connected to a second stage on the sub-base.
Heating (Heat Pump)
When the thermostat calls for heating, 24 volts is applied to the blower time-delay relay coil. Then, normally open contacts close, causing the indoor blower motor to operate. The circuit between R and Y is completed, closing the circuit to the contactor in the outdoor unit, starting the compressor and outdoor fan motor.
If the room temperature continues to decrease, the circuit between R and W1 is completed by the second-stage heat room thermostat. Circuit R-W1 energizes a heat sequencer. The completed circuit will energize supplemental electric heat (if applicable). Units with a second heat sequencer can be connected with the first sequencer to W1 on the thermostat. They may also be connected to a second heating stage W2 on the thermostat sub-base.
Emergency Heat (Heating Heat Pump)
If the selector switch on the thermostat is set to the emergency heat position, the heat pump will be locked out of the heating circuit, and all heating will be electric heat (if applicable). A jumper should be placed between W2 and E on the thermostat sub-base so that the electric heat control will transfer to the first-stage heat on the thermostat. This will allow the indoor blower to cycle on and off with the electric heat when the fan switch is in the AUTO position.
Homeowner Maintenance

IMPORTANT
Do not operate system without a filter. A filter is required to protect the coil, blower, and internal parts from excessive dirt and dust. The filter is placed in the return duct by the installer.
- Inspect air filters at least once a month and replace or clean as required. Dirty filters are the most common cause of inadequate heating or cooling performance.
- Replace disposable filters. Cleanable filters can be cleaned by soaking in mild detergent and rinsing with cold water.
• Install new/clean filters with the arrows on the side pointing in the direction of air flow. Do not replace a cleanable (high velocity) filter with a disposable (low velocity) filter unless return air system is properly sized for it. - If water should start coming from the secondary drain line, a problem exists which should be investigated and corrected. Contact a qualified service technician.
Repairing or Replacing Cabinet Insulation

IMPORTANT
DAMAGED INSULATION MUST BE REPAIRED OR REPLACED before the unit is put back into operation. Insulation loses its insulating value when wet, damaged, separated or torn.
Matte- or foil-faced insulation is installed in indoor equipment to provide a barrier between outside air conditions (surrounding ambient temperature and humidity) and the varying conditions inside the unit. If the insulation barrier is damaged (wet, ripped, torn or separated from the cabinet walls), the surrounding ambient air will affect the inside surface temperature of the cabinet.
The temperature/humidity difference between the inside and outside of the cabinet can cause condensation on the inside or outside of the cabinet which leads to sheet metal corrosion and, subsequently, component failure.
Repairing Damaged Insulation
Areas of condensation on the cabinet surface are an indication that the insulation is in need of repair.
If the insulation in need of repair is otherwise in good condition, the insulation should be cut in an X pattern, peeled open, glued with an appropriate all-purpose glue and placed back against the cabinet surface, being careful to not overly compress the insulation so the insulation can retain its original thickness. If such repair is not possible, replace the insulation. If using foil-faced insulation, any cut, tear, or separations in the insulation surface must be taped with a similar foil-faced tape.

text_image
GLUE - Make sure there is full coverage of glue on the metal or insulation so there are no areas where air pockets may form which can lead to sweating. 1. CUT INSULATION IN X PATTERN 2. APPLY GLUE 3. PRESS GLUED TABS AGAINST CABINETFigure 19. Repairing Insulation
Professional Maintenance
NOTICE
Failure to follow instructions will cause damage to the unit.
This unit is equipped with an aluminum coil. Aluminum coils may be damaged by exposure to solutions with a pH below 5 or above 9. The aluminum coil should be cleaned using potable water at a moderate pressure (less than 50psi). If the coil cannot be cleaned using water alone, it is recommended to use a coil cleaner with a pH in the range of 5 to 9. The coil must be rinsed thoroughly after cleaning.
In coastal areas, the coil should be cleaned with potable water several times per year to avoid corrosive buildup (salt).
Use of Air Handler During Construction
It is not recommended to use this air handler unit during any phase of construction. Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit.
Air handler units may be used for heating (heat pumps) or cooling of buildings under construction, if the following conditions are met:
- A room thermostat must control the air handler. The use of fixed jumpers is not allowed.
• Air filter must be installed in the system and must be maintained during construction.
• Air filter must be replaced upon construction completion. - The air handler evaporator coil, supply fan assembly and duct system must be thoroughly cleaned following final construction clean-up.
- All air handler operating conditions must be verified according to these installation instructions.
Installing Contractor's Name
Installing Contractor's Phone
Job Address
Installing Date
Air Handler Model #

flowchart
graph TD
A["1 Duct System"] --> B["8 Temperature"]
A --> C["5 Duct Static"]
A --> D["RETURN AIR"]
B --> E["Supply Air"]
C --> E
D --> E
E --> F["Thermostat 9"]
E --> G["Disconnect Switch"]
G --> H["Line Voltage 3"]
E --> I["2 Integrated Control"]
E --> J["6 Blower Motor Amps"]
E --> K["7 Electric Heat Amps"]
E --> L["4 Drain Line"]
① DUCT SYSTEM
SUPPLY AIR DUCT
Sealed
□ Insulated (if necessary)
□ Registers Open and Unobstructed
RETURN AIR DUCT
Sealed
Filter Installed and Clean
□ Registers Open and Unobstructed
② INTEGRATED CONTROL
☐ Jumpers Configured Correctly (if applicable)
□ Appropriate Links in Place (if applicable)
③ VOLTAGE CHECK
□ Supply Voltage ____
□ Low Voltage ____
Electrial Connections Tight
④ DRAIN LINE
□ Leak Free
☐ Explained Operation of System to Homeowner
Technician's Name: Date Start-Up & Performance Check Completed
⑤ TOTAL EXTERNAL STATIC (dry coil)
dry coil wet coil
Supply External Static ____ ____
Return External Static ____ ____
Total External Static = ____ ____
⑥ ELECTRIC HEAT AMPS
⑦ INDOOR BLOWER AMPS
INDOOR BLOWER CFM
⑧ TEMPERATURE DROP (Cooling Mode)
Return Duct Temperature ____
Supply Duct Temperature -
Temperature Drop = ____
⑧ TEMPERATURE RISE (Heating Mode)
Return Duct Temperature ____
Supply Duct Temperature - ____
Temperature Rise = ____
⑨ THERMOSTAT
□ Adjusted and Programmed
☐ Operation Explained to Owner
Figure 20. Start-Up and Performance Checklist (Upflow Configuration)
Installing Contractor's Name ____ Installing Contractor's Phone ____ Job Address ____
Installing Date ____ Air Handler Model # ____

flowchart
graph TD
A["① Duct System"] --> B["② Integrated Control"]
B --> C["Filter"]
C --> D["RETURN AIR"]
D --> E["④ Drain Line"]
E --> F["⑤ Duct Static"]
F --> G["Temperature"]
G --> H["⑧ Electric Heat Amps"]
H --> I["⑦ Blower motor Amps"]
I --> J["SUPPLY AIR"]
K["⑨ Thermostat"] --> L["Line Voltage"]
M["⑩ Disconnect Switch"] --> L
L --> N["① Duct System"]
① DUCT SYSTEM SUPPLY AIR DUCT
Sealed
□ Insulated (if necessary)
☐ Registers Open and Unobstructed RETURN AIR DUCT
Sealed
☐ Filter Installed and Clean
□ Registers Open and Unobstructed
② INTEGRATED CONTROL
☐ Jumpers Configured Correctly (if applicable)
□ Appropriate Links in Place (if applicable)
③ VOLTAGE CHECK
□ Supply Voltage ____
□ Low Voltage ____
Electrial Connections Tight
④ DRAIN LINE
□ Leak Free
⑤ TOTAL EXTERNAL STATIC (dry coil) dry coil wet coil
Supply External Static ____ ____
Return External Static ____ ____
Total External Static = ____ ____
⑥ ELECTRIC HEAT AMPS____
⑦ INDOOR BLOWER AMPS____ INDOOR BLOWER CFM____
⑧ TEMPERATURE DROP (Cooling Mode) Return Duct Temperature ____ Supply Duct Temperature – ____ Temperature Drop = ____
⑧ TEMPERATURE RISE (Heating Mode) Return Duct Temperature ____ Supply Duct Temperature – ____ Temperature Rise = ____
⑨ THERMOSTAT
□ Adjusted and Programmed
☐ Operation Explained to Owner
☐ Explained Operation of System to Homeowner
Technician's Name: Date Start-Up & Performance Check Completed
Figure 21. Start-Up and Performance Checklist (Horizontal Configuration)

natural_image
Abstract black-and-white graphic of stylized animal-like shapes with curved and angular forms (no text or symbols)MRCOOL®
COMFORT MADE SIMPLE
Signature Series
MAHM\*CTA Air Handler
ELECTRICIAN and/or HVAC TECHNICIAN:
LICENSE #:
INSTALLATION DATE:
INSTALLATION LOCATION:
SERIAL NUMBER:
The design and specifications of this product and/or manual are subject to change without prior notice. Consult with the sales agency or manufacturer for details.