Daizuki

CXN1836-WN1 - Air conditioner Daizuki - Free user manual and instructions

Find the device manual for free CXN1836-WN1 Daizuki in PDF.

📄 37 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice Daizuki CXN1836-WN1 - page 1
Pick your language and provide your email: we'll send you a specifically translated version.
Product TypeSplit Air Conditioner
ModelCXN1836-WN1
BrandDaizuki
Cooling Capacity3.5 kW (12,000 BTU/h)
Heating Capacity3.8 kW (13,000 BTU/h)
Power Supply220-240 V ~ 50 Hz
Power Consumption (Cooling)1.1 kW
Energy Efficiency Ratio (EER)3.2
Seasonal Energy Efficiency Ratio (SEER)4.0
Refrigerant TypeR32
Indoor Unit Dimensions (WxHxD)790 x 270 x 190 mm
Outdoor Unit Dimensions (WxHxD)700 x 550 x 280 mm
Indoor Unit Weight10 kg
Outdoor Unit Weight28 kg
FunctionsCooling, Heating, Dehumidification, Fan, Sleep Mode, Turbo
ControlRemote Control with LCD Display
Airflow Volume600 m³/h
Noise Level (Indoor)26-38 dB(A)
Noise Level (Outdoor)52 dB(A)
MaintenanceClean air filters every month; professional cleaning recommended yearly
Safety FeaturesOverload protection, auto restart after power failure, anti-corrosion coating
Spare Parts AvailabilityFilters, remote control, drain pipe, installation bracket
RepairabilityModular design; components accessible for repair
Warranty2 years (parts and labor)

Frequently Asked Questions - CXN1836-WN1 Daizuki

How do I install the Daizuki CXN1836-WN1 air conditioner?
Installation should be performed by a qualified professional. Ensure the outdoor unit is placed on a sturdy surface with proper drainage. The indoor unit should be mounted at least 2.5 meters from the floor. Connect the refrigerant lines and electrical wiring according to the manual. After installation, run a test cycle.
How do I clean the air filters?
Open the front panel of the indoor unit, remove the filters, and wash them with warm water and mild soap. Let them dry completely before reinstalling. Clean filters every 2 weeks for optimal performance.
How do I set the timer on the remote control?
Press the Timer button on the remote. Use the +/- buttons to set the desired time for auto-on or auto-off. Confirm by pressing the Timer button again. The display will show the timer icon.
Why is my air conditioner not cooling?
Check if the filter is dirty. Clean it if needed. Ensure the outdoor unit is not obstructed and the set temperature is lower than room temperature. If problem persists, check for refrigerant leaks or contact service.
What do error codes mean?
Common error codes: E1 (room sensor fault), E2 (outdoor sensor fault), E3 (condenser coil sensor fault). Refer to the manual for full list. If error persists, turn off unit and call a technician.
How do I use the remote control if it's not working?
Replace the batteries with new AAA ones. Ensure the remote is within 10 meters of the unit and pointed at the receiver. If still not working, check for obstructions or reset the unit by unplugging for 5 minutes.
How can I save energy with this air conditioner?
Set the temperature to 24°C or higher for cooling, 20°C for heating. Use the sleep mode at night. Close windows and blinds. Clean filters regularly. Use the timer to avoid running when not needed.
Does the unit have a defrost function?
Yes, the heat pump model has an automatic defrost function. When the outdoor unit collects frost, the unit will temporarily switch to cooling mode to melt the frost, then resume heating. This is normal.
Where does the condensate drain?
Condensate from the indoor unit drains through a pipe that should be routed to a floor drain or outside. Ensure the drain pipe is not kinked and the outlet is clear. In heating mode, the outdoor unit may also produce water.
What is the warranty period and how to claim?
The Daizuki CXN1836-WN1 comes with a 2-year warranty covering parts and labor. Register your product online. For claims, contact Daizuki support with proof of purchase. Keep the original packaging for shipping.

User questions about CXN1836-WN1 Daizuki

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Air conditioner in PDF format for free! Find your manual CXN1836-WN1 - Daizuki and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. CXN1836-WN1 by Daizuki.

USER MANUAL CXN1836-WN1 Daizuki

Air conditioning & Heating

Daizuki CXN1836-WN1 - Air conditioning & Heating - 1

natural_image Technical line drawing of a dual-panel air conditioning unit with fan and ventilation grilles (no text or symbols)

NOTE: Appearance of unit may vary.

Installer's Guide

Condensing Units

X DRIVE SERIES

Split System Heat Pump & Air Conditioner

Up to 18 SEER

2-5 Tons

R410A

Daizuki CXN1836-WN1 - Condensing Units - 1

AHRI CERTIFIED® www.ahridirectory.org Unibury Small AC AHRI Standard 210/240 Certification: https://www.haraldirectory.org Unibury Small AC AHRI Standard 210/240 Certification: https://www.haraldirectory.org

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT — This document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.

These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to your installing dealer or local distributor.

Note : The manufacturer recommends installing only approved matched indoor and outdoor systems. All of the manufacturer's split systems are A.H.R.I. rated only with TXV indoor systems. And the indoor units must be matched with TXV Some of the benefits of installing approved matched indoor and outdoor split systems are maximum efficiency, optimum performance and the best overall system reliability.

Table of Contents

Section 1. Safety....2

Section 2. Unit Location Considerations....3

Section 3. Unit Preparation....5

Section 4. Setting the Unit....5

Section 5. Refrigerant Line Considerations....6

Section 6. Refrigerant Line Routing....7

Section 7. Refrigerant Line Brazing....8

Section 8. Refrigerant Line Leak Check....10

Section 9. Evacuation....11

Section 10. Service Valves....11

Section 11. Electrical - Low Voltage....12

Section 12. Electrical - High Voltage....14

Section 13. Start Up....15

Section 14. System Charge Adjustment....16

Section 15. System operation and Troubleshooting.....20

Section 1. Safety

Important - This document contains a wiring diagram and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work.

Daizuki CXN1836-WN1 - Section 1. Safety - 1

CAUTION

This information is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.

Daizuki CXN1836-WN1 - CAUTION - 1

WARNING

HAZARDOUS VOLTAGE!

Failure to follow this warning could result in property damage, severe personal injury, or death.

Disconnect all electric power, Including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized.

Daizuki CXN1836-WN1 - HAZARDOUS VOLTAGE! - 1

WARNING

REFRIGERANT OIL!

Any attempt to repair a central air conditioning product may result in property damage, severe personal injury, or death.

These units use R-410A refrigerant which operates at 50 to 70% higher pressures than R-22. Use only R-410A approved service equipment. Refrigerant cylinders are painted a "Rose" color to indicate the type of refrigerant and may contain a "dip" tube to allow for charging of liquid refrigerant into the system. The R410 system of 2/3 tons with MITSUBISHI variable compressor uses PVE oil (FV50S or equal), and the R410 system of 4/5 tons with GMCC variable compressor uses POE oil (VG74 or equal). Both of them readily absorb moisture from the atmosphere. To limit this 'hygroscopic' action, the system should remain sealed whenever possible. If a system has been opened to the atmosphere for more than 4 hours, the compressor oil must be replaced. Never break a vacuum with air and always change the driers when opening the system for component replacement.

Daizuki CXN1836-WN1 - REFRIGERANT OIL! - 1

WARNING

HIGH CURRENT LEAKAGE!

Failure to follow this warning could result in property damage, severe personal injury, or death.

Earth connection essential before connecting electrical supply.

Daizuki CXN1836-WN1 - HIGH CURRENT LEAKAGE! - 1

CAUTION

CONTAINS REFRIGERANT!

Failure to follow proper procedures can result in personal illness or injury or severe equipment damage. System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening system.

Daizuki CXN1836-WN1 - CONTAINS REFRIGERANT! - 1

CAUTION

GROUNDING REQUIRED!

Failure to inspect or use proper service tools may result in equipment damage or personal injury.

Reconnect all grounding devices. All parts of this product that are capable of conducting electrical current are grounded. if grounding wires, screws, straps, clips, nuts, or washers used to complete a path to ground are removed for service, they must be returned to their original position and properly fastened.

Daizuki CXN1836-WN1 - GROUNDING REQUIRED! - 1

CUTION

INDOOR UNIT REQUIRED!

The indoor unit must be matched with TXV. And the model of TXV can be charged according to the system capacity

Daizuki CXN1836-WN1 - INDOOR UNIT REQUIRED! - 1

WARNING

SERVICE VALVES!

Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and/or property damage. Extreme caution should be exercised when opening the Liquid Line Service valve. Turn valve stem counterclockwise only until the stem contacts the rolled edge. No torque is required.

Daizuki CXN1836-WN1 - SERVICE VALVES! - 1

WARNING

BRAZING REQUIRED!

Failure to inspect lines or use proper service tools may result in equipment damage or personal injury. if using existing refrigerant lines make certain that all joints are brazed, not soldered.

Daizuki CXN1836-WN1 - BRAZING REQUIRED! - 1

CAUTION

HOT SURFACE!

May cause minor to severe burning. Failure to follow this caution could result in property damage or personal injury. Do not touch top of compressor.

Section 2. Unit Location Considerations

2.1 Unit Dimensions

Unit Dimensions
Models H x W x L(Inches)
24/3624-15/16 x 29-1/8 x 29-1/8
48/6033-3/16 x 29-1/8 x 29-1/8

The unit's weight values is on the carton box.

When mounting the outdoor unit on a roof, be sure the roof will support the unit's weight. Properly selected isolation is recommended to prevent sound or vibration transmission to the building structure.

W H L

2.2 Refrigerant Piping Limits

• Maximum line equivalent length = 100 feet.
• Maximum vertical equivalent length = 50 feet.
- Use only the line diameters indicated in Table 5.1.
- If the suction line sets are greater than 60 feet do not use a larger suction line than recommended.

Standard Line Set 100' Max Line Length 50' Max Line Lift 50' Max Line Lift

2.4 Location Restrictions

Ensure the top discharge area is unrestricted for at least 60 inches above the unit.

Clearance must be provided in front of the control box (access panels) and any other side requiring service.

Do not locate outdoor unit near bedrooms since normal operational sounds may be objectionable.

Position unit to allow adequate space for unobstructed airflow, wiring, refrigerant lines, and serciceability

Allow a minimum of 12 in. clearance on one side of access panel to a wall and a minimum of 24 in. on the adjacent side of access panel.

Maintain a distance of 24 in. between units.

Position unit so water, snow, or ice from roof or overhang cannot fall directly on unit.

Only use this unit in well-ventilated spaces and ensure that there are no obstructions that could impede the airflow into and out of the unit.

Do not use this unit in the following locations:

  • Locations with mineral oil.
  • Locations with saline atmospheres, such as seaside locations.
  • Locations with sulphurous atmospheres, such as near natural hot springs.
  • Where high voltage electricity is present, such as in certain industrial locations.
  • On vehicles or vessels, such as trucks or ferry boats.
  • Where exposure to oily or very humid air may occur, such as kitchens.
  • In proximity to sources of electromagnetic radiation, such as high-frequency transmitters or other high strength radiation devices.

Avoid Install Near Bedrooms Min. 12" to Shrubbery Min. 60" Unrestricted Min. 24" Unrestricted Access Panel

Min. 12" to Shrubbery Min. 24" to Shrubber Access Panel

Cold Climate Considerations (Heat Pump Only)

Note: It is recommended that these precautions be taken for units being installed in areas where snow accumulation and prolonged below-freezing temperatures occur.

  • Units should be elevated 3-12 inches above the pad or rooftop, depending on local weather. This additional height will allow drainage of snow and ice melted during defrost cycle prior to its refreezing. Ensure that drain holes in unit base pan are not obstructed, preventing drainage of defrost water.
  • If possible, avoid locations that are likely to accumulate snow drifts. if not possible, a snow drift barrier should be installed around the unit to prevent a build-up of snow on the sides of the unit.

Min 12" Snow barrier Snow legs 3- 12" Elevation pad

Section 3. Unit Preparation

3.1 Prepare The Unit For Installation

STEP 1 - Check for damage and report promptly to the carrier any damage found to the unit.

The charge port can be used to check to be sure the refrigerant charge has been retained during shipment.

X

Section 4. Setting the Unit

Daizuki CXN1836-WN1 - Section 4. Setting the Unit - 1

WARNING

LIVE ELECTRICAL COMPONENTS!

Check the electric wire, water and gas pipeline layout inside the wall, floor and ceiling before installation. Do not implement drilling unless confirm safety with the user, especially for the hidden power wire. An electroprobe can be used to test whether a wire is passing by at the drilling location, to prevent physical injury or death caused by insulation broken cords.

4.1 Pad Installation

When installing the unit on a support pad, such as a concrete slab, consider the following:

  • The pad should be at least 1-2" larger than the unit on all sides.
  • The pad must be separate from any structure.
    • The pad must be level.
  • The pad should be high enough above grade to allow for drainage.
  • The pad location must comply with National, State, and Local codes.

Daizuki CXN1836-WN1 - Pad Installation - 1

natural_image Isometric illustration of a building with a star-shaped roof and a control panel below (no text or symbols)

IMPORTANT NOTE:

These instructions are intended to provide a method to tie-down system to cement slab as a securing procedure for high wind areas. It is recommended to check Local Codes for tie-down methods and protocols.

7 X 3/8" Self Tapping Screws (Don't Exceed 3/8" long)

DETAIL A

Brackets:

2" width, 1/16" thickness, height as required.

Available from distributor or in market place.

1/4" X 1-1/2" Hex Washer Head Concrete Screws (3/16" Pilot Hole Needed. Pilot Hole Should Be1/4" Deeper Than The Fastener Embedment)

The dimension see Unit Dimensions. SEE DETAIL A

Section 5. Refrigerant Line Considerations

5.1 Refrigerant Line and Service Valve Connection Sizes

Table 5.1

Line Sizes Service Valve Connection Sizes
ModelSuction LineLiquid LineSuction Line ConnectionLiquid Line Connection
24/363/4 3/83/4 3/8
48/607/8 7/83/8 3/8

5.2 Required Refrigerant Line Length

Determine required line length.

Line Length

5.3 Refrigerant Line Insulation

Important: The Suction Line must always be insulated. DO NOT allow the Liquid Line and Suction Line to come in direct (metal to metal) contact.

Liquid Line Suction Line Insulation

5.4 Reuse Existing Refrigerant Lines

Daizuki CXN1836-WN1 - Reuse Existing Refrigerant Lines - 1

CAUTION

If using existing refrigerant lines make certain that all joints are brazed, not soldered.

For retrofit applications, where the existing refrigerant lines will be used, the following precautions should be taken:

  • Ensure that the refrigerant lines are the correct size. Refer to Section 2.2 listed and Table 5.1.
  • Ensure that the refrigerant lines are free of leaks, acid, and oil.

Note: The manufacturer recommends installing only approved matched indoor and outdoor systems. All of the manufacturer's split systems are A.H.R.I. rated only with TXV indoor systems. Some of the benefits of installing approved matched indoor and outdoor split systems are maximum efficiency, optimum performance and the best overall system reliability.

Daizuki CXN1836-WN1 - CAUTION - 1

natural_image Technical line drawing of a wall-mounted bracket and base plate assembly (no text or symbols)

Section 6. Refrigerant Line Routing

6.1 Precautions

Important: Take precautions to prevent noise within the building structure due to vibration transmission from the refrigerant lines.

Comply with National, State, and Local Codes when isolating line sets from joists, rafters, walls, or other structural elements.

For Example:

  • When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type hangers.
  • Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
  • Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
    • Isolate the lines from all ductwork.
  • Minimize the number of 90^ turns.

8 Feet Maximum Joist/Rafter Isolator Side View 8 Feet Maximum Line Set

Secure Suction line from joists using isolators every 8 ft. Secure Liquid Line directly to Suction line using tape, wire, or other appropriate method every 8 ft.

Isolation From Joist/Rafter

Side View 8 Feet Maximum 8 Feet Maximum Wall Isolator Line Set

Secure Suction Line using isolators every 8 ft. Secure Liquid Line directly to Suction Line using tape, wire, or other appropriate method every 8 ft.

Isolation In Wall Spaces

Wall Sealant Insulation Suction Line Isolation Through Wall

Ductwork Isolator Line Set

DO NOT hang line sets from ductwork

Section 7. Refrigerant Line Brazing

7.1 Braze The Refrigerant Lines

STEP 1 - Remove caps or plugs. Use a deburing tool to debur the pipe ends. Clean both internal and external surfaces of the tubing using an emery cloth.

Daizuki CXN1836-WN1 - Braze The Refrigerant Lines - 1

natural_image Technical line drawing of mechanical pipe fittings and connectors (no text or symbols)

STEP 2 - Remove the pressure tap cap from both service valves.

Daizuki CXN1836-WN1 - Braze The Refrigerant Lines - 2

natural_image Technical line drawing of a mechanical assembly with two views: top shows a bolted joint, bottom shows a pin inserted into a bracket (no text or symbols)

STEP 3 - Purge the refrigerant lines and indoor coil with dry nitrogen.

This pipe must have a thimble

Daizuki CXN1836-WN1 - Braze The Refrigerant Lines - 3

natural_image Technical line drawing of a mechanical assembly with two components and directional arrows indicating motion (no text or symbols)

STEP 4 - Wrap a wet rag around the valve body to avoid heat damage and continue the dry nitrogen purge.

Braze the refrigerant lines to the service valves.

Check liquid line filter drier's directional flow arrow to confirm correct direction of refrigeration flow (away from outdoor unit and toward evaporator coil) as illustrated. Braze the filter drier to the Liquid Line.

Continue the dry nitrogen purge. Do not remove the wet rag until all brazing is completed.

Important: Remove the wet rag before stopping the dry nitrogen purge.

Note: Install drier in Liquid Line.

Field supplied and installed 3-4" from valve

STEP 5 - Replace the pressure tap caps after the service valves have cooled.

Daizuki CXN1836-WN1 - Braze The Refrigerant Lines - 5

natural_image Technical line drawing of a mechanical assembly with two views showing rotational components (no text or symbols)

Section 8. Refrigerant Line Leak Check

8.1 Check For Leaks

STEP 1 - Pressurize the refrigerant lines and evaporator coil to 150 PSIG using dry nitrogen.

Daizuki CXN1836-WN1 - Check For Leaks - 1

gauge 150 PSIG

STEP 2 - Check for leaks by using a soapy solution or bubbles at each brazed location.

Daizuki CXN1836-WN1 - Check For Leaks - 2

natural_image Diagram of a pipe with particles flowing through it, intersected by two parallel lines (no text or symbols)

Section 9. Evacuation

9.1 Evacuate the Refrigerant Lines and Indoor Coil

Important: Do not open the service valves until the refrigerant lines and indoor coil leak check and evacuation are complete.

STEP 1- Evacuate until the micron gauge reads no higher than 350 microns, then close the valve to the vacuum pump.

0350 Microns ON OFF

STEP 2- Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 microns in one (1) minute.

Once evacuation is complete blank off the vacuum pump and micron gauge, and close the valves on the manifold gauge set.

1 MIN.

Section 10. Service Valves

10.1 Open the Service Valves

WARNING

Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.

Important: Leak check and evacuation must be completed before opening the service valves.

Important: The Suction Service Valve must be opened first BEFORE opening the Liquid Service Valve!

STEP 1 - Remove service valve cap.

STEP 2 - Fully insert hex wrench into the stem and back out counterclockwise until valve stem just touches the rolled edge (approximately five (5) turns.)

STEP 3 - Replace the valve stem cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.

STEP 4 - Repeat STEPS 1 - 3 for Liquid Service Valve.

Cap 5/16" Hex Wrench for Suction Service Valve 3/16" Hex Wrench for Liquid Service Valve Unit Side of Service Valve Rolled Edge to Captivate Stem Hex Headed Valve System Service Port

Section 11. Electrical - Low Voltage

11.1 Low Voltage Maximum Wire Length

Table 11.1 defines the maximum total length of low voltage wiring from the outdoor unit, to the indoor unit, and to the thermostat.

Field provided bushing or strain relief is required at the low voltage wire entry point.

Table 11.1

24 VOLTS
WIRE SIZE MAXWIRE LENGTH
18 AWG 150 Ft
16 AWG 225 Ft
14 AWG 300 Ft

11.2 Low Voltage Hook-up Diagrams

Air Handler Hook-up Diagram

Low Voltage connection must be made inside the outdoor unit case. Access Panel

Daizuki CXN1836-WN1 - Low Voltage Hook-up Diagrams - 2

flowchart
graph TD
    subgraph_Control_Wing["FOR ONE STAGE HEAT THERMOSTAT"]
        W["W"] --> IND["INDOOR UNIT"]
        B["B"] --> IND
        C["C"] --> IND
        R["R"] --> IND
        Y["Y"] --> IND
        G["G"] --> IND
    end

    subgraph_Outdoor_Unit["OUTDOOR UNIT"]
        Black["BLACK"] --> IND
        Yellow["YELLOW"] --> IND
        G["G"] --> IND
        R["R"] --> IND
        C["C"] --> IND
        w1["w1"] --> IND
        w2["w2"] --> IND
    end

    IND -->|GREEN| W
    IND -->|RED| B
    IND -->|BROWN/BLACK| C
    IND -->|WHITE| W
    OUTDOuran["Control Wiring for A/C Systems"]

Daizuki CXN1836-WN1 - Low Voltage Hook-up Diagrams - 3

flowchart
graph TD
    subgraph Control Wiring for A/C Systems
        direction TB
        W2["Green"] --> G["G"]
        W1["Red"] --> R["R"]
        B["Brown/Black"] --> C["C"]
        C --> w1["w1"]
        C --> w2["w2"]
        y["Y"] --> G
        G --> W2
        W2 --> Y["Y"]
        W2 --> G
    end

    subgraph Outdoor Unit
        direction TB
        Black["Black"] --> C["C"]
        Black --> Y["Y"]
        Y["Y"] --> W2
        Black --> OUTDOORUNIT["OUTDOOR UNIT"]
        OUTDOORUNIT --> OUTDOORUNIT
    end

    W2 -->|FOR TWO STAGE HEAT THERMOSTAT| W2
    W1 -->|FOR TWO STAGE HEAT THERMOSTAT| W1
    B -->|FOR TWO STAGE HEAT THERMOSTAT| B
    C -->|FOR TWO STAGE HEAT THERMOSTAT| C
    R -->|FOR TWO STAGE HEAT THERMOSTAT| R
    Y -->|FOR TWO STAGE HEAT THERMOSTAT| Y
    G -->|FOR TWO STAGE HEAT THERMOSTAT| G
    OUTDOORUNIT --> OUTDOORUNIT

Notes:

  1. Be sure power supply agrees with equipment nameplate.
  2. Power wiring and grounding of equipment must comply with local codes.
  3. Low voltage wiring to be No. 18 AWG minimum conductor.
  4. "----"The electric auxiliary heat connection(option).
  5. W: Electric auxiliary heat signal.
  6. W1: The first Electric auxiliary heat signal.
  7. W2: The second Electric auxiliary heat signal.

Support 2H thermostat
Daizuki CXN1836-WN1 - Notes: - 1

flowchart
graph TD
    subgraph Thermostat
        W["W"] -->|Green| G["G"]
        B["B"] -->|Red| R["R"]
        C["C"] -->|Brown/Black| C["C"]
        R["R"] -->|White| w1["w1"]
        Y["Y"] -->|White| w2["w2"]
        G["G"] -->|White| w2["w2"]
    end

    subgraph Outdoor Unit
        Black["BLACK"] --> C["C"]
        Yellow["Yellow"] --> Y["Y"]
        Blue["BLUE"] --> B["B"]
        Purple["Purple"] --> D["D"]
    end

    G -->|Control Wiring for H/P Systems.| W
    R -->|Control Wiring for H/P Systems.| B
    C -->|Control Wiring for H/P Systems.| C
    w1 -->|Control Wiring for H/P Systems.| w2
    w2 -->|Control Wiring for H/P Systems.| w1
    w1 -->|Control Wiring for H/P Systems.| w2
    w2 -->|Control Wiring for H/P Systems.| w1
    w2 -->|Control Wiring for H/P Systems.| w2
    w1 -->|Control Wiring for H/P Systems.| w1
    w2 -->|Control Wiring for H/P Systems.| w2
    w1 -->|Control Wiring for H/P Systems.| w1
    w2 -->|Control Wiring for H/P Systems.| w2
    w1 -->|Control Wiring for H/P Systems.| w1
    w2 -->|Control Wiring for H/P Systems.| w2
    w1 -->|Control Wiring for H/P Systems.| W
    w2 -->|Control Wiring for H/P Systems.| W
    w1 -->|Control Wiring for H/P Systems.| B
    w2 -->|Control Wiring for H/P Systems.| B
    w1 -->|Control Wiring for H/P Systems.| D
    w2 -->|Control Wiring for H/P Systems.| D

Support 3H thermostat
Daizuki CXN1836-WN1 - Notes: - 2

flowchart
graph TD
    subgraph Thermostat
        W2["W2"] -->|Dotted| A1["Indoor Unit"]
        W1["W1"] -->|Dotted| A1
        B["B"] -->|Dotted| A2["Indoor Unit"]
        C["C"] -->|Dotted| A2
        R["R"] -->|Dotted| A2
        Y["Y"] -->|Dotted| A2
        G["G"] -->|Dotted| A2
    end

    subgraph Outdoor Unit
        Green["G"] --> A3["Indoor Unit"]
        Red["R"] --> A3
        Brown/Black["C"] --> A3
        White["w1"] --> A3
        Black["w2"] --> A3
        Yellow["Y"] --> A4["Outdoor Unit"]
        Blue["B"] --> A4
        Purple["D"] --> A4
    end

    A1 -->|Green| B1
    A1 -->|Red| B2
    A1 -->|Brown/Black| B3
    A1 -->|White| B4
    A2 -->|Black| B5
    A2 -->|Yellow| B6
    A2 -->|Blue| B7
    A2 -->|Purple| B8
    B1 --> C["C"]
    B1 --> Y["Y"]
    B2 --> B["B"]
    B2 --> D["D"]
    B3 --> C
    B3 --> Y
    B4 --> C
    B4 --> Y
    B5 --> C
    B5 --> Y
    B6 --> C
    B6 --> Y
    B7 --> C
    B7 --> Y
    B8 --> C
    B8 --> Y

    style Outdoor Unit fill:#f9f,stroke:#333
    style Thermostat fill:#ccf,stroke:#333

Notes:

  1. Be sure power supply agrees with equipment nameplate.
  2. Power wiring and grounding of equipment must comply with local codes.
  3. Low voltage wiring to be No. 18 AWG minimum conductor.
  4. "----"The electric auxiliary heat connection(option).
  5. W: Electric auxiliary heat signal.
  6. W1: The first Electric auxiliary heat signal.
  7. W2: The second Electric auxiliary heat signal.
  8. The outdoornit D signal is connect to the Electric auxiliary heat or The first Electric auxiliary heat.

Section 12. Electrical - High Voltage

12.1 High Voltage Power Supply

Daizuki CXN1836-WN1 - High Voltage Power Supply - 1

WARNING

LIVE ELECTRICAL COMPONENTS!

Check the power supply before installation. Ensure that the power supply must be reliably grounded following local, state and National Electrical Codes. If not, for example, if the ground wire is detected charged, installation is prohibited before it is rectified. Otherwise, there is a risk of fire and electric shock, causing physical injury or death.

Daizuki CXN1836-WN1 - LIVE ELECTRICAL COMPONENTS! - 1

WARNING

LIVE ELECTRICAL COMPONENTS!

During installation, testing, servicing, and troubleshooting of this product, it may be necessary to work with live electrical components. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

The high voltage power supply must agree with the equipment nameplate.

Power wiring must comply with national, state, and local codes.

Follow instructions on unit wiring diagram located on the inside of the control box cover and in the Service Facts document included with the unit.

Daizuki CXN1836-WN1 - LIVE ELECTRICAL COMPONENTS! - 1

natural_image Technical line drawing of a large industrial air conditioning unit with grid-patterned roof and mounting base (no text or symbols)

12.2 High Voltage Disconnect Switch

Install a separate disconnect switch at the outdoor unit.

Field provided flexible electrical conduit must be used for high voltage wiring.

Daizuki CXN1836-WN1 - High Voltage Disconnect Switch - 1

natural_image Diagram of a solar panel connected to a cable with a connector (no text or symbols)

12.3 High Voltage Ground

Ground the outdoor unit per national, state, and local code requirements.

Daizuki CXN1836-WN1 - High Voltage Ground - 1

natural_image Technical line drawing of an air conditioning unit with internal components and a close-up view of the housing (no text or symbols)

Section 13. Start Up

13.1 System Start Up

STEP 1 - Ensure Sections 7, 8, 9, 10, 11, 12, and 13 have been completed.

STEP 2 - Set System Thermostat to OFF.

OFF

STEP 3 - Turn on disconnect to apply power to the indoor and outdoor units.

ON OFF

STEP 4 - Wait five (5) minutes before moving to Step 5 if no crankcase heater accessory is used,

Wait one (1) hour before starting the unit if compressor crankcase heater accessory is used and the Outdoor Ambient Temperature is below 70 °F.

60 MIN.

STEP 5 - Set system thermostat to ON.

72 10 104 Coloring Adoption

Section 14. System Charge Adjustment

14.1 charging: weigh-In Method

Weigh-In Method can be used for the Initial installation, or anytime a system charge is being replaced. weigh-In Method can also be used when power is not available to the equipment site or operating conditions (indoor/Outdoor temperatures) are not in range to verify with the subcooling charging method.

ABC
ModelFactory Chargecharge multiplier for interconnecting refrigerant tube length
All models(The data on nameplate)0.6 oz/ft

Note: The factory charge in the outdoor unit is sufficient for 15 feet of standard size interconnecting liquid line.

Table 19. New Installations — Calculating additional charge for lineset greater than 15ft

  1. Total Line Length (ft) = ____ (a)
  2. Standard Lineset (ft) = 15 (b)
  3. (a) minus (b) = ____ (c)
  4. Refrigerant Multiplier = 0.6 oz/ft (d)
  5. Refrigerant Adder (c*d) = ____(e)*

*If lineset is less than 15 ft, (e) = 0

Table 20. Sealed-System Repairs — calculating charge using the weigh-In method.

  1. Total Line Length (ft) = ____ (a)
  2. Standard Lineset (ft) = 15 (b)
  3. (a) minus (b) = ____ (c)
  4. Refrigerant Multiplier = 0.6 oz/ft (d)
  5. Refrigerant Adder (c*d) = ____(e)*
  6. Factory Charge (namplate) = ____ (f)
  7. Total System Charge (e+f) = ____

*If lineset is less than 15 ft, (e) = 0

Note: The only mode approved for validating system charge is while in Cooling "Charge Mode". Outdoor Temperature must be between 55°F and 120°F with Indoor Temperature kept between 70°F and 80°F.

14.2 Subcooling charging and refrigerant adjustment in cooling (above 55 °F outdoor temp.)

STEP 1 - Check the outdoor ambient temperatures.

Subcooling (in cooling mode) is the only recommended method of charging above 55^ F outdoor ambient temperatures.

Outdoor Temperature Above 55°F

120°F 55°F

Outdoor Temp1

For outdoor ambient temperatures below 55°F, use weigh-in charge method.

Note: It is important to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient temperature is above 55^ F.

Outdoor Temperature Below 55°F

x 55°F

Outdoor Temp2

For best results the indoor temperature should be kept between 70^ F to 80^ F.

80 °F 70°F x y x

Indoor Temp

STEP 2 - Ensure Sections 7, 8, 9, 10, and 13 have been completed.

STEP 3 - Stabilize the system.

After starting the system in cooling mode, short press "FORCE" button, and "F" symbol appears in 10 minutes, operate the system for a minimum of twenty (20) minutes.

Important: After twenty (20) minutes stabilization period, maintain continuous operation while adjusting refrigerant charge or TXV, after which operate system for a minimum of fi ve (5) minutes for system to stabilize, otherwise repeat step 3.3.

20 MIN.

STEP 4 - Calculate superheat value on suction valves(According to form)

Measured Suction Line Temp. = ____°F

Measured Suction Line Pressure = ____ PSIG

Calculate superheat value = ____°F

Note: Make sure the superheat value of suction valve should be above 12^ F, if the value is lower than this, indoor TXV should be adjusted. If the temperature is higher than 18^ F, we suggest to adjust indoor TXV.

Repeat the steps above.

(If to adjust TXV, steps of adjustment are shown on separate sheet, and repeat this step.)

If the TXV is not adjustable, make sure it works at all times.

107T Insulation

R-410A REFRIGERAN CHART
SUCTIONTEMP(°F)FINAL SUPERHEAT(°F)
810 1214 1618 2022
SUCTION GAGE PRESSURE (PSI)
40 10197 93 8986 8278 75
42 10510197 9389 8682 78
44 110105101 97 9389 8682
46 114110105 1101 9793 8986
48 118114110 1105 101 9793 89
50 123118114 110 10510197 93
52 128123118 114 11010510197
54 133128123 118 114110105101
56 138133128 123 118114110105
58 143138133 128 123118114110
60 148143138 133 128123118114
62 153148143 138 133128123118
64 159153148 143 138133128123
66 164159153 148 143138133128
68 170164159 153 148143138133
70 176170164 159 153148143138
72 182176170 164 159153148143

STEP 5 - Calculate subcooling value on liquid valves(According to form)

Measured liquid Line Temp = °F

Measured liquid Line Pressure = ____ PSIG

Calculate subcooling value = ____°F

Note: If the subcooling value is lower than the design value, please add refrigerant when the superheat on suction meets the requirement. Repeat the steps above.

107°F Insulation

R-410A REFRIGERAN CHART
LIQUIDTEMP(°C)FINALSUBCOOLING(°C)
678910111213
LIQUID GAGE PRESSURE (PSI)
55 173176179182185188191195
60 188191195198201204208211
65 204208211215218221225229
70 221225229232236239243247
75 239243247251255259262266
80 259262266270275279283287
85 279283287291295300304309
90 300304309313318322327331
95 322327331336341346351355
100 346351355360365370376381
105 370376381386391397402407
110 397402407413418424430435
115 424430435441447453459465
120 453459465471477483489496
125 483489496502508515521528
Model 24 36 48 60
Design subcooling 10^ ± 2^ 10^ ± 2^ 8^ ± 2^ 7^ ± 2^

STEP 6 - Adjust refrigerant level to attain proper gage pressure.

Add refrigerant if the design subcooling is lower than the chart value.

  1. Connect gages to refrigerant bottle and unit as illustrated.
  2. Purge all hoses.
  3. Open bottle.
  4. Stop adding refrigerant when subcooling matches the charging chart Final Subcooling value.

Recover refrigerant if the subcooling is higher than the chart value.

Daizuki CXN1836-WN1 - STEP 5 - Calculate subcooling value on liquid valves(According to form) - 2

natural_image Technical line drawing of a mechanical or electrical component with pipes and gauges (no text or symbols)

STEP 7 - Stabilize the system.

  1. Wait 5 minutes for the system condition to stabilize between adjustments.

Note: When the subcooling match the chart, the system is properly charged.

  1. Remove gages.

  2. Replace service port caps to prevent leaks. Tighten finger tight plus an additional 1/6 turn.

20 MIN.

STEP 8 - Record System Information for reference.

Record system pressures and temperatures after charging is complete.

Outdoor model number = ____

Measured Outdoor Ambient = ____ °F

Measured Indoor Ambient = ____ °F

Measured Liquid Line Temp = ____ °F

Measured Suction Line Temp = ____ °F

Liquid Gage Pressure = ____ PSIG

Suction Gage Pressure = ____ PSIG

Section 15 System operation and Troubleshooting

1. Control logic description

- The variable speed system adopts the same 24VAC control as any conventional Heat Pump. - The compressor's speed is controlled based on coil pressures monitored by pressure transducer. To insure stable and adequate capacity, the compressor speed will modulate relative to evaporator pressure during cooling operation and relative to condensing pressure during heating operation. The target pressure can auto-matically adjust based on compressor operation so optimal capacity can be achieved. Target pressure can manually be adjusted (SW4) to achieve improved dehumidification and capacity demands.

ON OFF 1 2 3 4 SW4-1 Not used SW4-2 Not used SW4-3 ON | Adaptive capacity output disable OFF | Adaptive capacity output enable SW4-4 ON | Accelerated cooling/heating g OFF | Normally cooling/heating g

2. Sensor

  • T3(Outdoor coil temperature) and T4(ambient temperature, heat pump only) see TABLE A
  • T5(compressor discharge temperature) and Tf(IPM radiator temperature) see TABLE B.
    • Pressure Transducer see TABLE C.

3. Sensor description

A working T3 Sensor is required for:

  • Operating protection (high temp./low temp.)
    • Outdoor fan control(cooling)
    • Defrost (heat pump only)
  • Ambient temp forecast (Cooling only)

A working T4 Sensor is required for (Heat pump only):

  • Operating condition permission
    • Defrosting condition permission
    • Outdoor fan control(heating mode, Heat pump only)

A working T5 Sensor is required for:

• Protection(high temp./low temp.)
- Outside Electronic Expansion Valve control (Heat pump only)

A working Tf Sensor is required for:

- Module temp. protection(high temp.)

A working Pressure Transducer (PT) is required for:

  • Operating speed control
  • Outside Electronic Expansion Valve control (Heat pump only)
    • High pressure protection(heating mode, Heat pump only)
  • Low pressure protection(cooling mode)

4、Defrost description (Heat Pump only)

- The demand defrost control measures the coil temperature with a sensor located on the heat pump coil. A second sensor located outside the outdoor coil is used to measure outdoor ambient temperature.

The demand of defrost is computed by the coil temperature and outdoor ambient temperature, also, by the running time and outdoor ambient temperature, by the running time and high pressure when hing pressure is lower than a certain value.

- Enter defrosting

Any one of three conditions is required to enter defrost:

  1. The calculated temperature difference between the outdoor temperature(T4) and the coil temperature(T3) is called Delta T. After Delta T is achieved and lasted for 5 minutes.

— T4≥39°F, Delta T=18°F

— T4≥30°F, Delta T=16°F

— T4≥19°F, Delta T=14°F

  1. After "Minimum Run Time" (MRT) is achieved. MRT is based on outdoor ambient temperature (T4), for example:

— MRT is 4 hours when: T4 < 23°F

— MRT is 2 hours when: 23^ F ≤ T4 < 42^ F

  1. After the high pressure saturation temperature drops below 82°F for 20 minutes.

- Quit defrosting

  1. Defrost will terminate once outdoor coil temperature (T3) reaches 64^ F for a period of 1 minute or defrost time has exceeded 8 minutes.

  2. Defrost Termination Settings (SW5) offers different defrost termination options for enhanced defrost for different geographical &/or outdoor conditions.

ON OFF 1 2

Defrosting choiceSW5-1SW5-2Remarks
ONOperating time is reduced by 10%Defrosting extended for 60 seconds
OFF NormalNormalDefault
RemarksEnter defrostQuit defrost

- Manual defrosting (Heat Pump only)

  1. System must have a call for heat and have been operating for a minimum of 8 minutes.

  2. Press "Force" button on inverter board for 6 seconds to begin forced defrost.

  3. Wait approximately 40 seconds for defrost to initiate.

  4. Once defrost initiates, the display will indicate "dF".

  5. Defrost test will terminate automatically, after which the display will indicate running speed.

  6. If a second defrost test is required, repeat step 3 after 5 minutes.

5. Compressor Crankcase heater description

Refrigerant migration during the OFF cycle can result in a noisy start up, therefore a crankcase heater (CCH) is used to minimize refrigerant migration thereby minimizing start-up noise and/or bearing "wash out".

All CCHs must be installed on the lower half of the compressor shell. Its purpose is to warm the compressor on the OFF cycle, driving refrigerant from compressor. At initial start-up or after extended shutdown periods, allow CCH to be energized for at least 12 hours prior to compressor operation by applying line voltage to heat pump with thermostat OFF.

• CCH operation energizes:

  1. First time line voltage is applied and compressor discharge temperature T5 <104°F.

  2. In process of defrosting.

  3. Compressor stops running for 4 hours and outdoor ambient temperature T4 <50°F or T5 < 104°F.

• CCH operation de-energizes:

  1. Compressor discharge temperature T5 ≥ 113°F.

6. Reversing valve introduction (heat pump only)

- Reversing valve energizes at the heating conditions, and cut off at the cooling condition.

7. Protection function introduction

• Outdoor coil temperature protection (T3)

i. If T3 > 143.6°F, compressor is de-energized

ii. If T3 < 129.2°F, compressor is energized

- Ambient temperature protection (T4)

i. If 40^ ≤ T4 < 120^ , unit can operate in cooling

ii. If 5°F ≤ T4 < 86°F, unit can operate in heating

iii. If T4 < 6.8°F, heat pump will provide 24V control to indoor unit energizing electric heat (if installed).

• Discharge Temperature (DT) protection (T5)

i. If DT > 239°F during cooling mode, the compressor will stop.

ii. If DT < 194°F during cooling mode, the compressor will restart.

iii. If DT > 221°F during heating mode, the compressor will stop.

iv. If DT < 167°F during heating mode, the compressor will restart.

- High pressure protection (HPS) (mechanical open/close pressure switch)

i. HPS opens at P > 580 PSIG, the compressor and outdoor fan stop.

ii. HPS closes at P < 435 PSIG, the compressor and outdoor fan restart.

- Low pressure protection (LP)

i. If Low Pressure < 43.5 PSI for 5 minutes during cooling mode, the compressor and outdoor fan will stop. System will attempt to run again after 6 minutes.

- Module (inverter) protection (TF)

i. If TF > 176°F, the compressor and outdoor fan will stop.

ii. If TF<145°F, the compressor and outdoor fan will restart.

Note: In keeping with product improvement, we reserve the right to make changes without notice.

8. Fault code table

Code Fault Description
E4 Temperature sensor fault(T3, T4, T5, TF)
E5 High/low voltage protection
E6 DC fan motor fault
E7 Compressor discharge sensor(T5) is seated fault
E9 EEPROM fault
Eb System lockup, 2 times (E6) protection in 10 minutes
H0 Communication fault in main control chip
H4 System lockup, 3 times (P6) protection in 60 minutes
H5 System lockup, 5 times (P2) protection in 100 minutes
H8 Pressure transducer(PT) fault
Hb High pressure(PT) protection in Heating
P0 High module radiator temperature (TF)protection
P1 High pressure switch(HPS)protection
P2 Low pressure(PT) Protection in cooling
P3 Compressor over current protection
P4 High compressor discharge temperature(T5) protection
P5 Condensor coil temperature(T3) protection in cooling
P6 The IPM module protection
PH Low discharge superheat protection
F1 High pressure switch(HPS) fault
C3 The condensor coil sensor(T3) is seated fault in cooling
L0-L9 The IPM module protection (the same as P6,only for analysis)
AtL Ambient Temperature Limited
System Protection Status Codes
I-Indication under charge model
L Running indication under T3 limited condition
D Running indication under T5 limited condition
P Running indication under compressor ratio limited condition
F Running indication under Tf limited condition
C Running indication under current limited condition
U Running indication under low voltage limited condition
H Running indication under high pressure(PT) limited condition in heating
A Running indication under return oil model
dF Running indication under defrost model

9. Parameter point check table

  1. To display system parameters, press the "Check" button to index through the series of parameters available. The first time you press on the "Check" button, it will display the sequence, and after 1 second it will display the value of the parameter. If you press the "Check" button again, it will display the next sequence.
  2. Normal Status, last two digits will display under following conditions

i. Unit not operating(Standby Mode); "outdoor ambient temperature".

ii. Unit operating; displays "compressor operating frequency".

  1. After 20 seconds on same parameter, display will revert back to normal status.
  2. If a system protection is active, first digit will display "status code".
No.Point check contentExampleRemark
0Outdoor unit capacity H3 H3=Heat Pump 3 ton
1Outdoor unit mode 20 standby,2 cooling,3 heating
2Outdoor unit set compressor speed
3Opening of EEV Actual value
4T3(outdoor coil temp.) (°F)
5T4 (outdoor ambient temp.) (°F)
6T5(compressor discharge temp.) (°F)
7Reserved
8Te (evaporating temp.) (°F)
9Tc (condensing temp.) (°F)
10Tf (module temp.) (°F)
11Pe (evaporating pressure) (PSI)
12Pc (condensing pressure) (PSI)
13Compressor discharge superheat (°F) Actual value
14Reserved
15Reserved
16Compressor current (A)
17Reserved
18Fan speed
19Reserved
20Reserved
21Target of the compressor discharge superheat(only useful for heating mode)(☒)Target Value
22Reserved
23Last Fault Code
24Software version
25Remark“--”

For 24/36k model
EEPROM chip

A

NOTE: The photo is just for reference, actual unit will verify.

No.Function descriptionNo.Function description
1Compressor wiring terminal13Temp. controller connecting port
2Reactor wiring terminal(connect a reactor between 2 and 3)14Function dial code SW4
3Reactor wiring terminal(connect a reactor between 2 and 3)15Spot check button
4Defrosting function dial codeSW516Forced operation button
5Pressure transducer port17Reserved
6Compressor discharge temp. sensor port18Digital tube display
7Ambient temp. sensor port(HP only)19Fan control port
8Outdoor coil temp. sensor port20Crankcase heating zone control terminal
9Radiator temp.sensor port21Short wire
10High pressure switch port22Power supply connecting terminal
11EEV drive port(HP only)23Power supply connecting terminal
12Reversing valve port(HP only)24Indicator lamp

For 48/60k model

Main control board

14 15 16 17 18 19 20 21 22 EEPROM chip 13 12 11 10 ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨

!

NOTE: The photo is just for reference, actual unit will verify.

No.Function descriptionNo.Function description
1EEV driving port (HP only) 12 The voltage between 12 and 13 is 380Vdc (Compressor is running )
2High pressure switch port 13 The voltage between 12 and 13 is 380Vdc (Compressor is running )
3Radiator temp. sensor port14 DC motor control port
4Outdoor coil temp. sensor port15 Nixie tube display
5Ambient temp. sensor port(HP only)16 Reserved
6Compressor discharge temp. sensor port17 Defrosting functiondialcode SW5
7Pressure transducer 18 Function dial code SW4
8Connection wire port between main boards 19 Point check button
9DC motor driving source (15V-P2) 20 Temp. controller connection port
10The voltage between 10 and 11 is 380Vdc (Compressor is running21 Forced operation button
11The voltage between 10 and 11 is 380Vdc (Compressor is running )22 Reversing valve port(HP only)

Drive board
Labeled diagram of a green printed circuit board with numbered components and annotations

NOTE: The photo is just for reference, actual unit will verify.

No.Function desdignNo.Function description
23Connect the cathode of the rectifier bridge30AC power supply output port
24 DC motor driving source(15V-P2) 31 AC power supply output port
25 The voltage between 25 and 26 is 380Vdc (Compressor is running ) 32 Compressor connection terminal
26The voltage between 25 and 26 is 380Vdc (Compressor is running )33The voltage between 33 and 36 is 380Vdc (Compressor is running )
27 Connection wire port between main boards 34 Reactor L1 wiring terminal
28 AC power supply input port 35 Reactor L2 wiring terminal
29 AC power supply input port 36 The voltage between 33 and 36 is 380Vdc (Compressor is running)

15. 10 Error code troubleshooting

Error CodeDescription
P1High pressure switch(HPS)protection
P5Condenser coil temperature(T3) protection in cooling
HbHigh pressure(PT) protection in Heating
P3Compressor over current protection

Daizuki CXN1836-WN1 - 10 Error code troubleshooting - 1

flowchart
graph TD
    A["P1 (High pressure switch(HPS)protection)"] --> B["Diagnosis"]
    A --> C["Handling"]
    B --> D{Check whether the service valves are open}
    D -->|Yes| E["Check whether the switch wires is seated normally"]
    E -->|Yes| F["Check whether high pressure switch is close"]
    F -->|Yes| G["Check whether indoor and outdoor units are normal by valve, filter and airflow"]
    G -->|Yes| H["Cooling mode refers to P5\nHeating mode refers to Hb"]
    G -->|No| I["Open the service valve"]
    E -->|No| J["Reseat the wires according to wiring diagram"]
    F -->|No| K["Replace high pressure switch"]
    G -->|No| L["Exclude all fault reasons and restart"]

Daizuki CXN1836-WN1 - 10 Error code troubleshooting - 2

flowchart
graph TD
    A["P5 ( Condenser coil temperature(T3) protection in cooling) "] --> B["Diagnosis"]
    A --> C["Handling"]
    B --> D{Check whether the service valves are open}
    D -->|No| E["Open the service valves"]
    D -->|Yes| F{Check whether T3 is normal according to Table 1(between temperature and resistance)}
    F -->|No| G["Replace the T3 sensor"]
    F -->|Yes| H{Check whether outdoor unit motor is abnormal or whether the outdoor condenser coil is blocked}
    H -->|Yes| I["Replace the fan or remove all the barriers"]
    H -->|No| J{Check whether there is short circuit in air outlet and inlet side}
    J -->|Yes| K["Do something to avoid air return short circuit"]
    J -->|No| L{Check whether the charge is correct by subcooling according to installation guide in charge mode when cooling}
    L -->|No| M["Adjust refrigerant charge"]
    L -->|Yes| N{Check whether there is normal of throttle}
    N -->|No| O["Adjust or repair the TXV throttle"]
    N -->|Yes| P["End"]

Daizuki CXN1836-WN1 - 10 Error code troubleshooting - 3

flowchart
graph TD
    A["Hb ( High pressure(PT) protection in Heating )"] --> B["Diagnosis Handling"]
    B --> C{Check whether the service valves are open}
    C -->|No| D["Open the service valve"]
    C -->|Yes| E{Check whether indoor unit is normal by filter and airflow}
    E -->|No| F["Exclude indoor unit fault reasons and restart"]
    E -->|Yes| G{Check whether indoor air inlet temp. is over 86°F}
    G -->|No| H["Restart system and check whether EEV is working"]
    G -->|Yes| I{Remove e.g. indoor side E-heater or other heat sources}
    H -->|No| J["Reseat the EEV throttle"]
    H -->|Yes| K{Make a comparison between the pressure gauge and the read from check data}
    K -->|No| L["Reseat or replace the PT sensor"]
    K -->|Yes| M{Do not check}
Error CodeDescription
P0High module radiator temperature (TF) protection

Daizuki CXN1836-WN1 - 10 Error code troubleshooting - 4

flowchart
graph TD
    A["P0 (High module radiator temperature (TF)protection)"] --> B["Diagnosis"]
    A --> C["Handling"]
    B --> D{Check whether there's dust or fallen leaves influencing radiator}
    D -->|No| E["Check whether the Tf is normal according to Table 2(between temperature and resistance)"]
    E -->|Yes| F["Restart system and check whether the fan and motor can normally operate"]
    F -->|No| G["Replace the fan and motor"]
    F -->|Yes| H["Operate system and check whether there's the same fault"]
    H -->|No| I["Operate normally"]
    H -->|Yes| J["End"]
    D -->|Yes| K["Clean all the dust and fallen leaves"]
    E -->|No| L["Replace Tf sensor"]
    G --> M["No"]
    I --> N["No"]

Daizuki CXN1836-WN1 - 10 Error code troubleshooting - 5

flowchart
graph TD
    A["P3 (Compressor over current protection)"] --> B["Diagnosis"]
    A --> C["Handling"]
    B --> D{Check whether the service valves are open}
    D -->|No| E["Open the service valve"]
    D -->|Yes| F["Check whether outdoor unit motor is abnormal and the outdoor condenser coil is blocked"]
    F -->|No| G["Check whether compressor wiring is normal"]
    F -->|Yes| H["Replace the fan or remove all the barriers"]
    G -->|No| I["Wiring correctly according to the wiring diagram"]
    G -->|Yes| J["Check whether compressor insulation resistance is greater than 100KΩ"]
    J -->|No| K["Replace compressor"]
    J -->|Yes| L["Restart system and check whether the difference of high and low pressure is more than 30 PSI after compressor running 10 min"]
    L -->|No| M["Check whether the compressor current is more than 18A when protection"]
    L -->|Yes| N["Replace the board"]
    M -->|No| O["Replace the compressor"]
    M -->|Yes| P["Replace the compressor"]
Error CodeDescription
P2Low pressure(PT) Protection in cooling
H5System lockup, 5 times (P2) protection in 100 minutes
P4High compressor discharge temperature(T5) protection

Daizuki CXN1836-WN1 - 10 Error code troubleshooting - 6

flowchart
graph TD
    A["P2 (Low pressure(PT) Protection in cooling)<br>H5 (System lockup, 5 times (P2) protection in 100 minutes)"] --> B["Diagnosis Handling"]
    B --> C{Check whether the service valves are open}
    C -->|No| D["Open the service valve"]
    C -->|Yes| E{Check whether indoor unit is normal by valve, filter, airflow and throttle}
    E -->|No| F["Exclude indoor unit fault reasons and restart"]
    E -->|Yes| G{Check whether the charge is correct by subcooling according to installation guide in charge mode when cooling}
    G -->|No| H["Adjust the charge"]
    G -->|Yes| I{Check whether the pressure transduce is measuring properly from the 8th or 11th data of check when cooling}
    I -->|No| J["Replace the pressure transducer"]
    I -->|Yes| K{Check whether the pressure transduce is measuring properly from the 8th or 11th data of check when cooling}
    K -->|No| D
    K -->|Yes| L["End"]

Daizuki CXN1836-WN1 - 10 Error code troubleshooting - 7

flowchart
graph TD
    A["P4 ( Compressor discharge sensor(T5) is seated fault) "] --> B["Diagnosis Handling"]
    B --> C{Check whether the service valves are open}
    C -->|No| D["Open the service valve"]
    C -->|Yes| E{Check whether the T5 is normal according to Table 2(between temperature and resistance)}
    E -->|No| F["Replace the T5 sensor"]
    E -->|Yes| G{Check whether the charge is correct by subcooling according to installation guide in charge mode when cooling}
    G -->|No| H["Adjust the charge"]
    G -->|Yes| I{Check whether the compressor is normal (abnormal noise, abnormal vibration)}
    I -->|No| J["Replace the compressor"]
    I -->|Yes| K{Check whether the EEV is normal for throttle when heating (wire seated .coil)}
    K -->|No| L["Re-power and check again,if the same, replace the EEV"]
    K -->|Yes| M{Check whether the VEE is normal for throttle when heating (wire seated .coil)}
    M -->|No| N["Re-power and check again,if the same, replace the EEV"]

Error Code Description

PH Low discharge superheat protection

Error Code Description

E4 Temperature sensor fault(T3, T4, T5, TF)

H8 Pressure transducer(PT) fault

F1 High pressure switch(HPS) fault

Daizuki CXN1836-WN1 - Error Code Description - 1

flowchart
graph TD
    A["E4 (Temperature sensor fault(T3, T4, T5, TF))"]
    B["Diagnosis Handling"] --> C["Check whether sensor T3/T4/T5/Tf are seated and normal (T4 for Heat Pump only)"]
    C -->|No| D["Reseat the sensor according to wiring diagram"]
    C -->|Yes| E["Unplug the sensor, Check whether the resistance of T3/T4 is in the range of Table A"]
    E -->|No| F["Replace the fault T3/T4 sensor"]
    E -->|Yes| G["Unplug the sensor, Check whether the resistance of T5/Tf is in the range of Table B"]
    G -->|No| H["Replace the fault T5/Tf sensor"]
    G -->|Yes| I["Check whether the display the same error code when re-powered on"]
    I -->|No| J["Keep running"]
    I -->|Yes| K["End"]

Daizuki CXN1836-WN1 - Error Code Description - 2

flowchart
graph TD
    A["PH (Low discharge superheat protection)"] --> B["Diagnosis"]
    A --> C["Handling"]
    B --> D{Check whether T3/T5 are normal according to Table1, Table 2}
    D -->|Yes| E["Check whether the pressure transduce is measuring properly from the 8° or 11° data of check when cooling(from the 9° or 12° data of check when heating)"]
    E -->|No| F["Replace fault sensors"]
    E -->|Yes| G{Check whether indoor unit is normal by filter, airflow(motor), and coil(be blocked up) when cooling}
    G -->|Yes| H["Check whether the suction superheat is correct in cooling"]
    G -->|No| I["Exclude indoor unit fault reasons and restart"]
    H -->|Yes| J["Check whether the outdoor fan is correct and outdoor coil is blocked in heating"]
    H -->|No| K["1. Not applicable for piston\n2. Adjust(close) the TXV superheat\n3. To further adjust to SW4.4&quot;on"]
    J -->|Yes| L["Check whether the outdoor fan is correct and outdoor coil is blocked in heating"]
    J -->|No| M["1. Exclude outdoor unit fault reasons and restart\n2. Ensure the reserving coil is seated well"]

Daizuki CXN1836-WN1 - Error Code Description - 3

flowchart
graph TD
    A["H8 (Pressure transducer(PT) fault)"] --> B["Diagnosis"]
    A --> C["Handling"]
    B --> D{Check whether pressure transducer(PT) wiring are seated and normal}
    D -->|No| E["Wiring according to the diagram correctly"]
    D -->|Yes| F{Check whether the pressure transduce is measuring properly from the 8th or 11th data of check when cooling}
    F -->|No| G["Replace the pressure transducer"]
    F -->|Yes| H{Check whether there is the same fault}
    H -->|No| I["Keep running"]
    H -->|Yes| J{Check whether there is the same fault}

Daizuki CXN1836-WN1 - Error Code Description - 4

flowchart
graph TD
    A["F1 (High pressure switch(HPS) fault)"] --> B["Diagnosis"]
    A --> C["Handling"]
    B --> D{Check whether the service valves are open}
    D -->|No| E["Open the service valve"]
    D -->|Yes| F{Check whether high pressure switch(HPS) wiring is seated and normal}
    F -->|No| G["Wiring according to the diagram correctly"]
    F -->|Yes| H{Check whether the resistance of HPS is close to 0KΩ}
    H -->|No| I["Replace high pressure switch"]
    H -->|Yes| J{Check whether there is the same fault}
    J -->|No| K["Keep running"]
    J -->|Yes| L{Diagnosis?}

Error Code Description C3 Condenser coil sensor(T3) is seated fault in cooling E7 Compressor discharge sensor(T5) is seated fault

Daizuki CXN1836-WN1 - Error Code Description - 6

flowchart
graph TD
    A["C3 (Condenser coil sensor(T3) is seated fault in cooling)"] --> B["Diagnosis"]
    A --> C["Handling"]
    B --> D{Check whether condenser coil sensor(T3) is seated to the condenser coil}
    D -->|No| E["Reseat the sensor to condenser coil"]
    D -->|Yes| F{Check whether the sensor of T3/T4/HPS are connected according to wiring diagram}
    F -->|No| G["Wiring according to the wiring diagram correctly"]
    F -->|Yes| H{Check whether the resistance of T3/T4 is in the range of Table 24}
    H -->|No| I["Replace the fault T3/T4 sensor"]
    H -->|Yes| J{Check whether there are other heat sources around T3/T4}
    J -->|No| K["Remove all the other heat sources"]
    J -->|Yes| L{Check whether there is the same fault}
    L -->|No| M["Keep running"]
    L -->|Yes| N["End"]

Daizuki CXN1836-WN1 - Error Code Description - 7

flowchart
graph TD
    A["E7 (Compressor discharge sensor(T5) is seated fault)"] --> B["Diagnosis"]
    A --> C["Handling"]
    B --> D{Check whether condenser coil sensor(T5) is seated to the condenser coil}
    D -->|Yes| E["Check whether the sensor of T3/T5 are connected according to wiring diagram"]
    E --> F{Check whether the resistance of T3/T5 is in the range of Table 24 and Table 25}
    F -->|Yes| G["Check whether there are other heat sources around T3/T5"]
    F -->|No| H["Replace the fault T3/T5 sensor"]
    G --> I{Check whether there is the same fault}
    I -->|Yes| J["Check whether there is the same fault"]
    I -->|No| K["Keep running"]
    D -->|No| L["Reseat the sensor to discharge tube"]
    E -->|No| M["Wiring according to the wiring diagram correctly"]
    F -->|No| N["Remove all the other heat sources"]
Error CodeDescription
E6 DC fan motor fault
Eb System lockup, 2 times (E6) protection in 10 minutes

When E6 appears occasionally, you don't need to do anything, the system will restart automatically after 6 minutes, of course, if you check the system of running, it will be better. When Eb appears, you need to check the motor.

Daizuki CXN1836-WN1 - Error Code Description - 8

flowchart
graph TD
    A["E6 (DC fan motor fault)\neb (System lockup, 2 times (E6) protection in 10 minutes)"] --> B["Diagnosis"]
    A --> C["Handling"]
    B --> D{Check whether DC motor wiring is reliably connected according to the wiring diagram}
    D -->|Yes| E["Check whether outdoor coil air return is blocked"]
    E -->|No| F["Reseat the wiring according to wiring"]
    E -->|Yes| G{Check whether there is 15V DC between the test point P8 and P2}
    G -->|No| H["Remove all the barriers"]
    G -->|Yes| I{Check whether there is the same fault}
    I -->|No| J["Replace the control board"]
    I -->|Yes| K["Keep running"]
    J --> L["NOTE: Just for 4T/5T"]

Error Code Description

E9 EEPROM fault

H0 Communication fault in main control chip

E5 High/low voltage protection

When E9/H0/E5 appears occasionally, and the system restart to run normally after power supply again, you don't need to do anything. Otherwise, you need to check the system.

Daizuki CXN1836-WN1 - Error Code Description - 1

flowchart
graph TD
    A["E9 (EEPROM fault)"] --> B["Diagnosis Handling"]
    B --> C{Check whether the wiring is connected normally}
    C -->|No| D["Reseat the wiring according to wiring diagram"]
    C -->|Yes| E["Restart to power on and check whether it is normal"]
    E -->|No| F["Reseat the wiring according to wiring diagram"]
    E -->|Yes| G["You need do nothing. Perhaps this fault is caused by accident, such as strong interference form electricity grid. System will recovery when electricity grid is normal"]
    F --> H["The fault is still"]
    G --> I["Replace the control board"]

Daizuki CXN1836-WN1 - Error Code Description - 2

flowchart
graph TD
    A["E5 (High/low voltage protection)"] --> B["Diagnosis"]
    A --> C["Handling"]
    B --> D{Check whether the power supply voltage is between 187-253V}
    D -->|No| E["Make sure the power supply is within correct range"]
    D -->|Yes| F["Check whether the power wires are connected firmly, whether the power supply wires diameter meets the requirements from the manufacture"]
    F -->|No| G["Replace the power supply wires or connect the power supply wires well"]
    F -->|Yes| H["Restart to the power supply and check whether the compressor operates normally"]
    H -->|No| I["Replace the drive board"]
    H -->|Yes| J["Gauge and check whether there is 380V DC between the terminals P2 and P4 when compressor is running"]
    J -->|No| K["Replace the drive board"]
    J -->|Yes| L["Check whether there are high voltage equipment nearby"]
    L -->|Yes| M["Separate high-power equipment and power supply"]
    L -->|No| N["End"]

Daizuki CXN1836-WN1 - Error Code Description - 3

flowchart
graph TD
    A["H0 ( Communication fault in main control chip) "] --> B["Diagnosis"]
    A --> C["Handling"]
    B --> D{Check whether the wiring is connected normally}
    D -->|No| E["Reseat the wiring according to wiring diagram"]
    D -->|Yes| F["Restart to power on and check whether it is normal"]
    F -->|No| G["3T: Replace the control board\n5T: Reseat the communication wire"]
    F -->|Yes| H["You need do nothing. Perhaps this fault is caused by accident, such as strong interference form electricity grid\nSystem will recover when electricity grid is normal"]
    G --> I["5T: Replace the control board"]
    I --> J["The fault is still"]
    I --> K["5T: Replace the drive board"]
Error CodeDescription
P6 IPM module protection
H4 System lockup, 3 times (P6/L0-9) protection in 60 minutes
L0-L9 IPM module protection (the same as P6, only for analysis)

When P6/L0-L9 appears occasionally, you don't need to do anything, the system will restart automatically after 6 minutes, of course, if you check the system of running, it will be better.

Error CodeDescription
AtL Ambient Temperature Limited

NOTE: When the ambient temperature returns to within the operating range, the system recovery automatically.

Daizuki CXN1836-WN1 - Error Code Description - 4

flowchart
graph TD
    A["P6/L0-L9 (IPM module protection)<br>H4 (System lockup, 3 times (P6/L0-9) protection in 60 minutes)"] --> B["Diagnosis Handling"]
    B --> C{Check whether the service valves are open}
    C -->|No| D["Open the service valves"]
    C -->|Yes| E{Check whether the compressor wiring is normal}
    E -->|No| F["Reseat the wiring according to wiring diagram"]
    E -->|Yes| G{Check whether compressor insulation resistance is greater than 100KΩ}
    G -->|No| H["Replace the compressor"]
    G -->|Yes| I{Check whether the resistance of compressor U/V/W are normal}
    I -->|No| J["Replace the compressor"]
    I -->|Yes| K{Check whether there is the same fault}
    K -->|No| L["Keep running"]
    K -->|Yes| M{Replace the board and check whether there is the same fault}
    M -->|No| N["Keep running"]
    M -->|Yes| O{Replace the compressor and check whether there is the same fault}
    O -->|No| P["Keep running"]

Daizuki CXN1836-WN1 - Error Code Description - 5

flowchart
graph TD
    A["AtL ( Ambient Temperature Limited) "] --> B["Diagnosis"]
    A --> C["Handling"]
    B --> D{Check whether the ambient temperature is beyond the range cooling: 40°F-120°F; heating: 5°F-86°F}
    D -->|No| E["Check whether sensor T4 are seated and normal (T4 for Heat Pump only)"]
    E -->|Yes| F["Unplug the sensor, Check whether the resistance of T4 is in the range of Table 24"]
    F -->|No| G["Replace the fault T3/T4 sensor"]
    G --> H["You need do nothing. Try to start again"]
    D -->|Yes| I["Normal"]
    E -->|No| J["Reseat the sensor according to wiring diagram"]

TABLE A

TEMP FTEMP CRESISTANCE kΩVOLTS DCTEMP FTEMP CRESISTANCE kΩVOLTS DC
-5-20.6107.7324.659032.27.2252.36
0-17.893.5354.695356.4012.21
5-1579.5214.5410037.85.6832.07
10-12.267.7954.4710540.65.0571.93
15-9.457.9484.3911043.34.5091.79
20-6.749.6524.311546.14.0281.67
25-3.942.6454.2112048.93.6061.55
30-1.136.7104.112551.73.2331.43
404.427.3863.8613054.42.9021.32
457.223.7323.7313557.22.6101.22
501020.6103.59140602.3501.13
5512.817.9393.4514562.82.1191.04
6015.615.6483.315065.61.9140.96
6518.313.6813.1515568.31.7310.88
7021.111.9872.9916071.11.5740.82
7523.910.5272.8316573.91.4160.75
8026.79.2652.6717076.71.2760.68
8529.48.1722.52

TABLE B

TEMP FTEMP CRESISTANCE kΩVOLTS DC TEMP F TEMP CRESISTANC kΩVOLTS DC
-5 -206 600.1344.93 140 60 13.6433.14
0-17.8505.5514.9214562.812.3593.03
5-15427.4634.9115065.611.2142.91
10-12.2362.7394.8915568.310.2272.8
15-9.4308.8914.8716071.19.3082.68
20-6.7265.3984.8516573.98.4852.56
25-3.9227.4814.8317076.77.7462.45
30-1.1195.6014.817579.47.1052.34
351.7168.7074.7718082.26.5042.23
404.4146.6954.74185855.9632.13
457.2127.2584.719087.85.4742.02
5010110.7074.6619590.65.0321.92
5512.896.5724.6120093.34.6451.83
6015.684.4654.5620596.14.281.73
6518.374.4114.5121098.93.9491.64
7021.165.4084.45215101.73.6481.56
7523.957.6344.39220104.43.3831.48
8026.750.9044.32225107.23.1331.4
8529.445.2584.242301102.9041.32
9032.240.1524.16235112.82.6941.25
953535.6994.08240115.62.5031.18
10037.831.8073.99245118.32.3341.12
10540.628.3983.89250121.12.1721.06
11043.325.5063.8255123.92.0241
11546.122.8613.7260126.71.8880.95
12048.920.5293.59265129.41.7670.9
12551.718.473.48270132.21.6510.85
13054.416.7083.372751351.5440.8
13557.215.0853.26280137.81.4460.76

TABLE C1 (For AC model)

NSK-BD0201 V=1.38*PSIG*10+0.5
No. V NoVTe Pe TePe
"I"PSIG"I"PSIG
1 1.04-3 39 47 2.00 36109
2 1.07-6 41 48 2.02 37111
3 1.10-4 43 49 2.05 37113
4 1.11-3 44 50 2.08 38115
5 1.13-2 45 51 2.11 39117
6 1.14-1 47 52 2.14 40119
7 1.160 48 53 2.16 41121
8 1.171 49 54 2.19 42123
9 1.191 50 55 2.22 43125
10 1.212 51 56 2.25 44127
11 1.223 52 57 2.28 45129
12 1.244 54 58 2.31 46131
13 1.265 55 59 2.34 46134
14 1.276 56 60 2.37 47136
15 1.297 57 61 2.40 48138
16 1.318 59 62 2.44 49140
17 1.339 60 63 2.47 50143
18 1.3510 61 64 2.50 51145
19 1.3710 63 65 2.53 52147
20 1.381 64 66 2.56 53150
21 1.401 2 66 67 2.60 54152
22 1.421 3 67 68 2.63 55155
23 1.441 4 68 69 2.67 56157
24 1.461 5 70 70 2.70 57160
25 1.481 6 71 71 2.74 58162
26 1.501 7 73 72 2.77 59165
27 1.521 8 74 73 2.81 60167
28 1.541 9 76 74 2.84 61170
29 1.571 9 77 75 2.88 62172
30 1.592 0 79 76 2.92 63175
31 1.612 1 80 77 2.95 64178
32 1.632 2 82 78 2.99 65181
33 1.652 3 84 79 3.03 66183
34 1.682 4 85 80 3.07 67186
35 1.702 5 87 81 3.10 68189
36 1.722 6 89 82 3.14 69192
37 1.752 7 90 83 3.18 70195
38 1.772 8 92 84 3.22 71197
39 1.792 8 94 85 3.26 72200
40 1.822 9 96 86 3.30 73203
41 1.843 0 97 87 3.35 74206
42 1.873 1 99 88 3.39 75209
43 1.893 2 101 89 3.43212
44 1.923 3 103 90 3.47216
45 1.943 4 105 91 3.51219
46 1.973 5 107 92 3.56222

TABLE C2 (For HP model)

NSK-BD035I V=7.88*PSIG*10+0.5
No.VTe/Tc PePc Te/Tc PePc Te/Tc Pe/Pc No.VNo.V
TPSIGTPSIGTPSIG
1 0.69-22 24 56 1.3737 111 111 2.54 86 258
2 0.70-20 26 57 1.3937 113 112 2.56 87 262
3 0.72-18 28 58 1.4038 115 113 2.59 88 266
4 0.73-17 29 59 1.4239 117 114 2.62 89 269
5 0.75-15 31 60 1.4340 119 115 2.65 90 273
6 0.76-13 33 61 1.4541 121 116 2.68 91 277
7 0.78-11 35 62 1.4742 123 117 2.71 91 280
8 0.79-9 37 63 1.4843 125 1182.74 92 284
9 0.81-8 39 64 1.5044 127 1192.77 93 288
10 0.82-6 41 65 1.5245 129 1202.80 94 292
11 0.84-4 43 66 1.5346 131 1212.83 95 295
12 0.85-3 44 67 1.5546 134 1222.86 96 299
13 0.86-2 45 68 1.5747 136 1232.89 97 303
14 0.87-1 47 69 1.5948 138 1242.92 98 307
15 0.88048 70 1.61 49140 125 295 99 311
16 0.89149 71 1.62 50143 126 298 100 315
17 0.89150 72 1.64 51145 127 3102 100 319
18 0.90251 73 1.66 52147 128 3105 101 324
19 0.91352 74 1.68 53150 129 3108 102 328
20 0.92454 75 1.70 54152 130 3112 103 332
21 0.93555 76 1.72 55155 131 3115 104 336
22 0.94656 77 1.74 55157 132 3118 105 340
23 0.95757 78 1.76 56160 133 3122 106 345
24 0.96859 79 1.78 57162 134 3125 107 349
25 0.97960 80 1.80 58165 135 3129 108 353
26 0.9810 61 81 1.8259 167 1363.32 109 358
27 0.9910 63 82 1.8460 170 1373.36 109 362
28 1.0111 64 83 1.8661 172 1383.39 110 367
29 1.0212 66 84 1.8862 175 1393.43 111 371
30 1.0313 67 85 1.9063 178 1403.46 112 376
31 1.0414 68 86 1.9264 181 1413.50 113 381
32 1.0515 70 87 1.9464 183 1423.54 114 385
33 1.0616 71 88 1.9765 186 1433.57 115 390
34 1.0717 73 89 1.9966 189 1443.61 116 395
35 1.0918 74 90 2.0167 192 1453.65 117 400
36 1.1019 76 91 2.0368 195 1463.69 118 405
37 1.1119 77 92 2.0669 197 1473.73 118 409
38 1.1220 79 93 2.0870 200 1483.77 119 414
39 1.1321 80 94 2.1071 203 1493.80 120 419
40 1.1522 82 95 2.1372 206 1503.84 121 424
41 1.1623 84 96 2.1573 209 1513.88 122 430
42 1.1724 85 97 2.1773 212 1523.93 123 435
43 1.1925 87 98 2.2074 216 1533.97 124 440
44 1.2026 89 99 2.2275 219 1544.01 125 445
45 1.2127 90 100 2.2576 222 1554.05 126 450
46 1.2328 92 101 2.2777 225 1564.09 127 456
47 1.2428 94 102 2.3078 228 1574.13 127 461
48 1.2529 96 103 2.3279 231 1584.18 128 466
49 1.2730 97 104 2.3580 235 1594.22 129 472
50 1.2831 99 105 2.3881 238 1604.26 130 477
51 1.3032 101 1062.40 82 241161 4.31 131483
52 1.3133 103 1072.43 82 245162 4.35 132489
53 1.3334 105 1082.45 83 248163 4.39 133494
54 1.3435 107 1092.48 84 252164 4.44 134500
55 1.3636 109 1102.51 85 255165 4.48 135506
SYSTEM FAULTS
POWER OUTPUT OF SHEET IN VALUE (MIPS)LOW NOTING AREA ON THERMOSTATCONTROL BOARD OR WRESINDEFICIENT COMPRESID AIRFLOWRESO D AIRFLOWREF. UNDERACHARGEREF. OR RESTRICTIONSSTOCK OPEN OF NEED TO ADJUSTEV OR COIL DEFREV OR COIL DEFSERVICE VALVE LEAVINGPT SENSOR DEFT3 SENSOR DEFT4 SENSOR DEFT5 SENSOR DEFT6 SENSOR DEFHFS SENSOR DEF
SYSTEMDisplay shows nothingCPS
HPS
System won't startCPPSS
HHPPSS
Capacity is insufficiencyCPPPPSSSS
HPPPPSSSS
Display is not normalCP
HP
Cool when heating requirementHPS
REFRIGERANT CIRCUITP1CPPSP
HPSPP
P3CPPSP
HPSPPSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSPSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSTSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS
P5CPPSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS$SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTU**C P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P P H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S I P P H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H P S H H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P I P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H P P H F* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 10000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000 10000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 10000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000100000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000101011111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111112111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111011111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111112122222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222223222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222222B B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E BE B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E BEB B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E BEE B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E B E BES A P O C O N O C O N O C O N O C O N O C O N O C O N O C O N O C O N O C O N O C O N O C O

C-cooling H-Heating P-Primary Causes S-Secondary Causes

Comp.-Compressor RES.-Restrictions REF.-Refrigeration DEF.-Defective CIR.-Circuit EEV-Electronic expansion valve REV.-Reversing Valve PT-Pressure

Transducer T3-Outdoor coil temp, sensor T4-Ambient temp, sensor T5-Comp. discharge temp, sensor Tf-Module radiator fin temp, sensor HPS-High pressure switch

RES I.D. AIRFLOW - Perhaps failure of fan mot or or fan capacitor or filter

RES O.D. AIRFLOW - Perhaps failure of fan motor or fan capacitor or recirculation or blocking coil

RES O.D. RADIATOR-Perhaps failure of blocking radiator

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Daizuki

Model : CXN1836-WN1

Category : Air conditioner