CyberPower CR6U61001 - Wall box

CR6U61001 - Wall box CyberPower - Free user manual and instructions

Find the device manual for free CR6U61001 CyberPower in PDF.

📄 14 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice CyberPower CR6U61001 - page 3
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Uninterruptible Power Supply (UPS)
Model CR6U61001
Form Factor Rackmount / Tower convertible
Input Voltage 120 V AC
Output Capacity 1000 VA / 600 W
Number of Outlets 6 NEMA 5-15R
Battery Type Sealed Lead-Acid (SLA)
Battery Runtime (Full Load) Approximately 5 minutes
Battery Runtime (Half Load) Approximately 15 minutes
Dimensions (H x W x D) 3.4" x 17.2" x 17.5" (2U)
Weight 30 lbs
Input Cord NEMA 5-15P, 6 ft
Surge Protection 1200 Joules
Waveform Type Simulated Sine Wave
Interface Ports USB, Serial (RJ45)
Management Software PowerPanel Personal Edition
Warranty 3 Years (electronics & battery)
Cleaning Instructions Wipe with dry cloth; do not use liquids or solvents
Safety Features Surge protection, overload protection, short circuit protection
Spare Parts / Repairability Replacement battery available; user-replaceable

Frequently Asked Questions - CR6U61001 CyberPower

What is the typical runtime of the CyberPower CR6U61001?
At full load (600W), runtime is about 5 minutes. At half load (300W), runtime extends to approximately 15 minutes. Actual runtime varies based on connected equipment.
How do I replace the battery in the CR6U61001?
Turn off the UPS and unplug it. Remove the front bezel, slide out the battery compartment, disconnect the battery wires, and replace with a new battery (model CP600 or compatible). Reconnect and reassemble.
Is the CyberPower CR6U61001 rackmount or tower?
It is a convertible design: it can be mounted in a standard 19-inch rack (2U space) or used as a tower unit with included feet.
What software is available to manage the UPS?
CyberPower provides PowerPanel Personal Edition for local monitoring and shutdown. It can be downloaded from the CyberPower website.
Does the CR6U61001 provide pure sine wave output?
No, it provides simulated sine wave output, which is suitable for most electronics but may not be compatible with sensitive devices requiring pure sine wave.
What is the warranty period for this UPS?
The CyberPower CR6U61001 comes with a 3-year warranty covering both electronics and the battery.
How do I clean and maintain the UPS?
Always unplug the UPS before cleaning. Use a soft, dry cloth to wipe the exterior. Do not use any liquids, solvents, or abrasives.
Can I connect a laser printer to this UPS?
It is not recommended. Laser printers have high power surges that can exceed the UPS capacity. Use a surge protector instead.
What type of outlets does the CR6U61001 have?
It has 6 NEMA 5-15R outlets (standard 3-prong US outlets). Some outlets may be surge-only or battery backed up; check your model specifics.
How do I interpret the LED indicators?
Typically, a green LED indicates normal AC power, an amber LED indicates battery backup is active, and a red LED indicates fault or low battery. Consult the manual for exact patterns.

User questions about CR6U61001 CyberPower

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Wall box in PDF format for free! Find your manual CR6U61001 - CyberPower and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. CR6U61001 by CyberPower.

USER MANUAL CR6U61001 CyberPower

Wall Mount Enclosure

CRxU6 Series

Isometric line drawing of a server rack unit with ventilation grilles and mounting door (no text or symbols)

Table of Contents

Safety Instructions .... 1

Part Identification 2

Enclosure Components ......2

Hardware and Accessories....2

Initial Enclosure Setup.... 3

Door and Side Panel Locks ....3

Remove and Reverse Front Door....3

Relocate CyberPower Badge 4

Open and Remove Side Panels ....5

Adjusting Rack Angles....5

Mounting Depth 5

Dual Mounting Holes 6

Cable Access....7

Grounding 7

Enclosure Installation 8

Mounting on Wall 8

Caster Installation 9

Equipment Installation.... 10

Mounting Using Square Holes 10

Mounting Using Threaded Round Holes....11

Safety Instructions

CyberPower CR6U61001 - Safety Instructions - 1

Please read these instructions carefully before use.

  • The enclosure is a heavy object. Use of adequate mechanical means to move the enclosure to the desired location is highly recommended to minimize risk of injury or unit damage. For safety reasons, it is highly recommended to handle this unit between two or more people. Use caution when unpacking, moving, and installing the enclosure. Failure to follow may cause serious injury, or unit damage.
  • Handle the unit with care. Take precautions to avoid damaging the enclosure when unpacking, moving, repacking, or installing. Damage to the unit as a result of negligence is not covered under warranty.
  • Inspect the product and included accessories carefully before use. Do not use an enclosure with visible damage.
  • Before installing the enclosure, ensure that the wall or the floor is even and capable of supporting the total load being installed in the enclosure, including the enclosure itself. Do not mount the enclosure to the wall with equipment installed in it.
  • Do not stack enclosures and do not put any objects on the top of the enclosure.
  • Keep the enclosure in an appropriately ventilated space, and do not block the surrounding of the enclosure to ensure proper ventilation.
  • Install the enclosure in an indoor area, free of dust, extreme moisture and temperature changes, away from flammable objects, conductive contaminants, and exposure to direct sunlight.
  • Keep packaging materials if the enclosure will be reshipped. Do not ship the enclosure with any equipment installed. This can cause damage to the packaging material that can result in unit damage.

Part Identification

Enclosure Components

Technical diagram of a server rack cabinet with numbered components for identification

Technical line drawing of a server rack cabinet with labeled components (no text or symbols beyond labels)

(Model CR6U61001 is shown)

  1. Removable, Reversible, and Lockable Front Door
  2. Removable and Lockable Side Panels
  3. Vents
  4. Cable Access with Removable Covers
  5. Depth-Adjustable Rack Angles with Dual Mounting Holes
  6. Horizontal Rails
  7. Enclosure Mounting Keyholes
  8. Back Panel

Hardware and Accessories

CyberPower CR6U61001 - Hardware and Accessories - 1
Expansion Bolt (4)

CyberPower CR6U61001 - Hardware and Accessories - 2
Key (2)

CyberPower CR6U61001 - Hardware and Accessories - 3

12-24 Screw, Silver (30)

CyberPower CR6U61001 - 12-24 Screw, Silver (30) - 1
M6 Cage Nuts (30)

CyberPower CR6U61001 - 12-24 Screw, Silver (30) - 2
Cup Washer (30)

CyberPower CR6U61001 - 12-24 Screw, Silver (30) - 3
M6 Phillips-Head Screw, Black (30)

Initial Enclosure Setup

CyberPower CR6U61001 - Initial Enclosure Setup - 1

Setup the following configuration options shown in this section before mounting the enclosure on the wall.

Door and Side Panel Locks

The door and side panel locks are keyed-alike. The lock locations are shown below. Use the included keys to operate the locks.

NOTE: The enclosure is shipped with the door locked. To access the keys in the accessories bag, open a side panel by pushing the black retention tabs inward as shown on page 5. Side panels are shipped unlocked.

Technical line drawing of a server rack unit with two key keys and a close-up view of its internal components (no text or symbols present)

Remove and Reverse Front Door

  1. Pull on the spring loaded door pin hinges as shown below to remove the door from the enclosure.

Technical diagram of a server rack cabinet with labeled internal components and directional arrows indicating assembly or movement.

  1. Remove the door pin supporting washer from the bottom hinge and reinstall it on the opposite door pin hinge.

Mechanical assembly diagram showing a spring-loaded component with a downward arrow indicating force or direction (no text or symbols present)

  1. Rotate the front door and reinstall it on the opposite side sliding the door pin hinges into the hinge holes on the enclosure as shown below.

Diagram of an open server rack cabinet with internal components and a curved arrow indicating rotation (no text or symbols)

Relocate CyberPower Badge

To relocate the CyberPower badge, pull the two parts apart as shown below. To re-install the badge measure the vertical and horizontal distance from the edge of the door as shown below and push both parts together.

NOTE: Please press hard to make sure the badge has been firmly installed.

CyberPower CyberPower 3" (76mm) 9.84" (250mm)

Open and Remove Side Panels

Unlock the side panel and press the retention tabs simultaneously to release the side panel.

Technical line drawing of a server rack unit with mounting holes and ventilation ducts (no text or symbols)

Adjusting Rack Angles

Mounting Depth

The installed depth of the rack angles can be adjusted by unscrewing them from the horizontal mounting rails. Move the cage nuts behind the upper and lower horizontal rails to the desired depth as shown below. Depth of the rack angles can be adjusted in 3/4" (20mm) increments.

NOTE: Verify the rack angles are installed at the correct depth before installing equipment in the enclosure. You may remove the two rear rack angles if only installing two post mounting equipment.

Technical line drawing of a server rack cabinet with internal components and mounting holes, showing structural details (no text or symbols)

Dual Mounting Holes

The rack angles have dual mounting holes, square holes for use with cage nuts and #12-24 threaded round holes shown below.

NOTE: The enclosure is shipped with the rack angles in the square hole position.

#12-24 threaded round holes Square holes

To use the side with the threaded holes, unscrew the rack angles from the horizontal mounting rails. Switch the rack angles to the opposite side of the enclosure while ensuring that the rack unit numbers face outward. Screw the rack angles to the horizontal mounting rails. Keep the desired mounting depth when switching the rack angles.

Technical line drawings of a mechanical assembly with three views (top, front, side), showing structural components and directional arrows (no text or symbols)

Cable Access

Cables can be routed through the top or bottom cable openings of the enclosure. To access the cable opening, remove the two screws securing the cover as shown below.

Technical line drawing of a server rack unit with two microchip slots and mounting brackets (no text or symbols)

Grounding

CyberPower CR6U61001 - Grounding - 1

An individual grounding connection per enclosure is strongly recommended. Failure to follow may result in serious injury or death.

To connect the enclosure to the facility's ground, use the grounding nut in the enclosure. The grounding point is marked in the enclosure with the ground symbol shown below.

Pure electrical circuit symbol for a diode (no text or labels)

Enclosure Installation

CyberPower CR6U61001 - Enclosure Installation - 1

The enclosure is a heavy object. For safety reasons, it is highly recommended to handle this unit between two or more people. Failure to follow these instructions may cause serious injury, or unit damage.

Mounting on Wall

CyberPower CR6U61001 - Mounting on Wall - 1

Before installing the enclosure make sure that the wall is capable of supporting the total load being mounted in the enclosure, including the enclosure itself. Make sure the enclosure is properly mounted to the wall before installing equipment in the enclosure. Do not mount the enclosure with equipment installed in it.

Use the included expansion bolts, or other appropriate mounting hardware, to mount the enclosure to the wall as shown below.

Technical line drawing of a server rack unit with internal components and a magnified inset showing internal structure (no text or symbols)

The horizontal distance between keyholes, center to center, is 19.2" (488mm). The vertical distance between keyholes varies by model heights. Measure the vertical distance of the unit being installed before mounting the enclosure.

19.2"/488mm Variable

Caster Installation

CyberPower's Wall Mount Enclosures are compatible with an optional caster kit (CRA60002) shown below. Please contact your sales representative for ordering information.

NOTE: For installation information, please see the CRA60002 quick start guide.

Technical line drawing of a cabinet or enclosure with mounting hardware and internal components (no text or symbols)

Equipment Installation

CyberPower CR6U61001 - Equipment Installation - 1

  • Verify that the enclosure is securely mounted to the wall prior to installing any equipment.
  • It is strongly recommended to first install equipment in the bottom of the enclosure. Heavier equipment should be installed in the bottom of the enclosure.
  • If using sliding rails with installed equipment, use caution when pulling the equipment out of the enclosure as it can cause loading to shift and increase the hazard of tipping or failing. If multiple pieces of equipment use sliding rails only slide one piece of equipment out at once.

CyberPower's wall mount enclosures have dual-hole rails, square holes and #12-24 threaded round holes. To change the type of mounting holes that are facing forward please see the Adjusting Rack Angles section. Use the black cage nuts and black screws for square holes, and use the silver #12-24 screws for the round holes.

NOTE: Please review your equipment instructions carefully before installing in the enclosure.

Mounting Using Square Holes

  1. Install the included black M6 cage nuts from the back of the rack angles as shown below, and press the sides of the cage nuts to make sure they have been inserted properly.

6 5 4

6 5 4

CyberPower CR6U61001 - Mounting Using Square Holes - 3

To ensure proper and secure installation, cage nuts need to be installed horizontally as shown below. Installing cage nuts in the incorrect orientation can cause injury or equipment damage.

CyberPower CR6U61001 - Mounting Using Square Holes - 4

CyberPower CR6U61001 - Mounting Using Square Holes - 5

  1. Install the equipment by screwing the included black M6 screws and cup washers into the cage nuts as shown below.

6 5 4

Mounting Using Threaded Round Holes

Simply install the equipment by screwing the included silver #12-24 mounting screws into the threaded holes as shown below.

6 5 4

For warranty and additional information, please visit: www.cyberpower.com.

CyberPower®

Cyber Power Systems, Inc.

www.cyberpower.com

For USA and Canada:

4241 12th Ave East, Suite 400

Shakopee, MN 55379

Toll-free: (877) 297-6937

For all other regions:

Please visit our website for local contact information.