ENTES

DCV-11C - Voltmeter ENTES - Free user manual and instructions

Find the device manual for free DCV-11C ENTES in PDF.

📄 28 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice ENTES DCV-11C - page 1
Pick your language and provide your email: we'll send you a specifically translated version.
Product TypeDC Voltage Monitor
ModelDCV-11C
BrandENTES
Power Supply10-56 V DC
Power Consumption<4 VA (supply) + <1 VA (measuring)
Measuring Range±200 V DC
Accuracy0.5% ±1 digit (10% to 100% of full scale)
Display2.5-inch backlit LCD
Measurement Period1-600 seconds (adjustable)
Alarm Outputs2 programmable relays (NO, 5A, 1250 VA)
Alarm ModesHigh, Low, Range (High-Low), with hysteresis, delays, trip, latch
Security4-digit password protection
Input Resistance<2 MΩ
Operating Temperature-20 to 70 °C
Dimensions (Panel Cutout)48 x 96 mm (flush mount)
Weight0.240 kg
Enclosure ProtectionIP40 (front), IP00 (terminals)
Installation CategoryClass III
StandardsEN 61010-1, EN 61000-4-2, EN 61000-4-4, EN 61000-4-5, EN 61000-4-8, EN 61000-4-11
Wire Width2.5 mm²
Fuse1A F-type
LanguagesTurkish, English, German, French, Spanish
BacklightConfigurable (off, always on, 30s, 60s, 5min, 15min)
Contrast Adjustment0-15 steps

Frequently Asked Questions - DCV-11C ENTES

How do I reset the minimum and maximum measured voltage values?
Go to the RESET menu, select RESET MIN or RESET MAX, choose YES, and save when exiting the main menu.
How do I set an alarm threshold?
Enter the ALARMS menu, select ALARM1 or ALARM2, set ALRM STAT to ON, then configure ALRM TYPE (High, Low, Range), set HGH VALUE or LOW VALUE, and adjust hysteresis and delays as needed.
What power supply does the DCV-11C require?
The DCV-11C operates on 10-56 V DC (for models with '11' in the name). Models with '10' require 85-265 V AC/DC.
How do I change the display language?
Navigate to the LANGUAGE menu in the main menu. Select from Tr (Turkish), Eng (English), dE (German), ESP (Spanish), or FR (French). Press SET to confirm.
How do I enable password protection?
Go to SECURITY menu, then PASS ACTV. Enter the current password (default 0000), then set to ON. You can change the password in CHNG PASS.
What does the 'Trip' function do?
If TRIP is set to YES, when the measured voltage exceeds 1.5 times the set maximum (or drops below 0.5 times the set minimum), the alarm contact opens immediately without delay. This overrides normal on-delay settings.
How do I adjust the measurement period?
In the main menu, select PERIOD. Use the UP/DOWN buttons to set a value between 1 and 600 seconds. Press SET to save.
How should I connect the device for voltage measurement?
Connect the DC voltage source to the V+ and V- terminals of the 2-pin measuring input. Ensure all power is disconnected before wiring. See connection diagram in manual.
Does the DCV-11C have an analog output?
No, the DCV-11C model does not have analog output. Analog output is available only on DCV-10A/11A models. The DCV-11C has two alarm relay outputs instead.
How do I clean the device?
Clean only with a dry cloth. Do not use solvents or similar substances, as they may damage the device.

User questions about DCV-11C ENTES

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Voltmeter in PDF format for free! Find your manual DCV-11C - ENTES and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. DCV-11C by ENTES.

USER MANUAL DCV-11C ENTES

-Disconnect all power before connecting the device.

-Don't remove the front panel while the device is connected to the network.

-Don't clean the device with solvent or similar substances. Only clean with a dry cloth.

-Verify correct terminal connections when wiring.

-Electrical devices should be serviced only by your component seller.

-Device is for rack panel mounting only.

-Fuse which will be used must be F type and its current limit value must be 1A.

-No responsibility is assured by the manufacturer or any of its subsidiaries for any problems arising out of the disregard of these conditions.

SECURITY

ENTES DCV-11C - SECURITY - 1

Read the user manual completely before using the device.

The box is under dangerous high voltage. The device must be installed and serviced only by a qualified service personnel.

Displayed only when limit is crossed in opposite direction.

ENTES DCV-11C - SECURITY - 2

If a voltage higher than 200V or lower than -200V is applied to the measuring input of the device, a warning is displayed like the one on the left.

Is not displayed when limit is crossed in opposite direction.

Note: This manual is valid from Rev.2.00.00 firmware.

(Devices including INFO menu)

Warnings

  • Connect a button or a circuit breaker between the grid and the supply inputs of the device.
  • This button or circuit breaker must be in close proximity of the device.
  • This button or circuit breaker must be marked to indicate that it is used to separate the device from the grid.

Standards That Are Applied To The Device

EN 61010-1, EN 61000-4-2, EN 61000-4-4, EN 61000-4-5, EN 61000-4-8, EN 61000-4-11

Guarantee

The device has a 2 year guarantee. In case of a malfunction, repairs of the device must be done only by the authorised technical service or the guarantee will be void.

Index

  1. INTRODUCTION....4

1.1. APPLICATIONS....4
1.2. GENERAL FEATURES....4
1.3. FRONT PANEL 5
1.4. HARDWARE FEATURES....8

  1. USAGE OF DEVICE 8

2.1. MENU USAGE AND SETTINGS....8
2.2. MAIN MENUS....8

2.2.1. PERIOD SETTING MENU....10
2.2.2.ALARMS MENU....10
2.2.3. ANALOG OUTPUT SETTING MENU....18
2.2.4.RS-485 SERIAL COMMUNICATION SETTING MENU....20

2.2.5. RESET MENU 24
2.2.6. DISPLAY SETTING MENU 26
2.2.7. LANGUAGE SETTING MENU....27
2.2.8. FACTORY SETTING MENU....28
2.2.9. SECURITY SETTING MENU....29
2.2.10.INFO MENU....30

2.2.11. EXITING MAIN MENU 31

  1. INSTALLATION....31

3.1. DIMENSIONS AND INSTALLATION....31
3.2. CONNECTION DIAGRAM....32
3.3. PC CONNECTION....33
4. FACTORY DEFAULT VALUES 34
5. TECHNICAL FEATURES....36
6. REGISTER TABLE....38
7. MENU MAP 46

1. INTRODUCTION

1.1 APPLICATIONS:

You can achieve the following measurements and applications with the device.

- All measured parameters can be transferred via RS485 line with MODBUS protocol and menus can be set remotely. (DCV-10S/10CS/11S/11CS)

- With 2 programmable Alarm Relays, a range in which the monitored system voltage should resice can be determined and a warning signal can be created for the user with Alarm1 (C1) and Alarm2 (C2) contact outputs if this monitored voltage goes out of the determined range. (DCV-10C/10CS/11C/11CS) - With a programmable Analog Output, the device can be programmed to give a voltage or current output according to the measured voltage value. (DCV-10A/11A)

  • Measured maximum-minimum values can be monitored by using UP/DOWN buttons.
  • Settings can be accessed easily and read comfortably with the back-lit LCD feature.
  • Measurement results can be calculated in a desired time with an adjustable measurement period of 1-600 s.
  • The device provides flexible usage with wide supply voltage range. 85-265 V AC/DC (DCV-10/10A/10C/10S/10CS), 10-56V DC (DCV-11/11A/11C/11S/11CS)
  • The device settings can be protected from changes by unauthorized personnel by specifying a 4 digit user password.

1.2 GENERAL FEATURES

The device is designed to measure the voltage on a DC system.

1.3 FRONT PANEL

The device has a back-lit 2.5" LCD which contains two lines as numeric and alpha-numeric, warning symbols and notification signs. There are three buttons for programming the device. Explanations about the display and buttons are listed on the right side.

DC VOLTmeter Rx/Tx % PASSWORD 88888 C1 C2 MAX MIN MkWArh 13 15 9 DCV-10S

5

Usage of Front Panel and Buttons

  1. Up button

  2. Set button, for entry to menu and value entry

  3. Down button

  4. Indicates that the password protection is active.

  5. Indicates the existence of communication. It blinks during communication. (DCV-10S/10CS/11S/11CS)

  6. The line where measured parameters are displayed.

  7. Indicates the direction of the measured voltage.

  8. Indicates the notification messages or the menu where the user is.

  9. Units belonging to measurements and analog output parameters

10.Indicates that the contact or contacts are in a high fault state. (DCV-10C/10CS/11C/11CS)

11.Indicates that the contact or contacts are in a low fault state.(DCV-10C/10CS/11C/11CS)

  1. 1st Contact Output (DCV-10C/10CS/11C/11CS)

  2. 2nd Contact Output (DCV-10C/10CS/11C/11CS)

14&15. Indicates that the contacts are closed.(DCV -10C/10CS/11C/11CS)

6

Special Functions for Buttons

UP button: It helps you display maximum voltage value during measurement. In programming mode, it is used to switch device parameters. If lock function is active, it enables alarm output contacts when tension value exceeds the configured threshold. When the tension is between the set limits, alarm output contacts are not turned off (locked-hold). When pressed together with DOWN button (UP + DOWN), output switches are turned off.

SET button: 3 seconds. When you hold down this button, MAIN MENU mode is activated. It is used to switch from MAIN MENU to SUB MENUS and to save parameter changes.

DOWN button: It helps you display minimum voltage value during measurement. In programming mode, it is used to switch device parameters. If lock function is active, it enables alarm output contacts when tension value exceeds the configured threshold. When the tension is between the set limits, alarm output contacts are not turned off (locked-hold). When prassed together with UP button (UP + DOWN), output switches are turned off.

1.4 HARDWARE FEATURES

  • Voltage measurement connector (2-pin, V+, V-)
  • 0/2-10V, 0-4/20 mA Analog Output connector (3-pin, V, GND, I)(DCV-10A/11A)
  • RS-485 connector (4-Pin)(DCV-10S/10CS/11S/11CS)
  • 2 Relay connectors (4-pin)(DCV-10C/10CS/11C/11CS)
  • Supply input (2-pin) (85-265V AC/DC (DCV-10/10A/10C/10S/10CS), 10-56V DC (DCV-11/11A/11C/11S/11CS))

2- USAGE OF DEVICE:

2.1 MENU USAGE AND SETTINGS:

After the device is installed according to the connection diagram in the user manual, energize the device.(Refer to: Connection diagram) In order for the measurements and applications to be accurate, necessary adjustments must be made by using menus.

2.2 MAIN MENUS:

There are 11 main menus on the device for measurement and usage settings. The user can access MAIN MENUs by pressing the SET button for 3 seconds on measurement screen. By pressing the SET button on any MAIN MENU, SUB MENUs of the related MAIN MENU is entered.

MAIN MENU FLOW:

ENTES DCV-11C - MAIN MENUS: - 1

flowchart
graph TD
    A["024.00 V"] --> B["PERIOD 00.1"]
    B --> C["ALARM5"]
    C --> D["ANL6 OUT 00"]
    D --> E["RS 485"]
    E --> F["RESET"]
    F --> G["LANGUAGE ENG"]
    G --> H["DISPLAYSET"]
    H --> I["ESCRIPT"]
    I --> J["INFO"]
    J --> K["SECURITY"]
    K --> L["FCTRY SET"]
    L --> M["RESET"]
    M --> N["Only valid for DCV-10C/10CS/11C/11CS."]
    N --> O["Only valid for DCV-10A/11A."]
    O --> P["Only valid for DCV-10B/10CS/11S/11CS."]
    P --> Q["Only valid for DCV-10B/10CS/11S/11CS."]
    Q --> R["Only valid for DCV-10B/10CS/11S/11CS."]
    R --> S["Only valid for DCV-10B/10CS/11S/11CS."]
    S --> T["Only valid for DCV-10B/10CS/11S/11CS."]
    T --> U["Only valid for DCV-10B/10CS/11S/11CS."]
    U --> V["Only valid for DCV-10B/10CS/11S/11CS."]
    V --> W["Only valid for DCV-10B/10CS/11S/11CS."]
    W --> X["Only valid for DCV-10B/10CS/11S/11CS."]
    X --> Y["Only valid for DCV-10B/10CS/11S/11CS."]
    Y --> Z["Only valid for DCV-10B/10CS/11S/11CS."]
    Z --> AA["Only valid for DCV-10B/10CS/11S/11CS."]
    AA --> AB["Only valid for DCV-10B/10CS/11S/11CS."]
    AB --> AC["Only valid for DCV-10B/10CS/11S/11CS."]
    AC --> AD["Only valid for DCV-10B/10CS/11S/11CS."]
    AD --> AE["Only valid for DCV-10B/10CS/11S/11CS."]
    AE --> AF["Only valid for DCV-10B/10CS/11S/11CS."]
    AF --> AG["Only valid for DCV-10B/10CS/11S/11CS."]
    AG --> AH["Only valid for DCV-10B/10CS/11S/11CS."]
    AH --> AI["Only valid for DCV-10B/10CS/11S/11CS."]
    AI --> AJ["Only valid for DCV-10B/10CS/11S/11CS."]
    AJ --> AK["Only valid for DCV-10B/10CS/11S/11CS."]
    AK --> AL["Only valid for DCV-10B/10CS/11S/11CS."]
    AL --> AM["Only valid for DCV-10B/10CS/11S/11CS."]
    AM --> AN["Only valid for DCV-10B/10CS/11S/11CS."]
    AN --> AO["Only valid for DCV-10B/10CS/11S/11CS."]
    AO --> AP["Only valid for DCV-10B/10CS/11S/11CS."]
    AP --> AQ["Only valid for DCV-10B/10CS/11S/11CS."]
    AQ --> AR["Only valid for DCV-10B/10CS/11S/11CS."]
    AR --> AS["Only valid for DCV-10B/10CS/11S/11CS."]
    AS --> AT["Only valid for DCV-10B/10CS/11S/11CS."]
    AT --> AU["Only valid for DCV-10B/10CS/11S/11CS."]
    AU --> AV["Only valid for DCV-10B/10CS/11S/11CS."]
    AV --> AW["Only valid for DCV-10B/10CS/11S/11CS."]
    AW --> AX["Only valid for DCV-10B/10CS/11S/11CS."]
    AX --> AY["Only valid for DCV-10B/10CS/11S/ 585"]

2.2.1 "PERIOD" Period Setting Menu

After the device samples for a specified time, it displays the measurement result by calculating the mean value of those samples. You can set the sampling time in this menu. Period value can be entered between 1-600 seconds.

ENTES DCV-11C - "PERIOD" Period Setting Menu - 1

2.2.2 "ALARMS" Alarms Menu

DCV -10C/10CS/11C/11CS devices have two normally open (NO) contact outputs. Operating modes of the alarms are set in this menu. Each alarm can be set to one of six operating modes. These modes are high alarm, low alarm, high-low (range) alarm and their 3 inverted counterpart modes. This menu has 2 sub-menus.

"ALARM1", "ALARM2"

ENTES DCV-11C - "ALARMS" Alarms Menu - 1

flowchart
graph TD
    A["RL ARMS"] -->|SET| B["RL ARM 1"]
    B --> C["RL ARM 2"]
    C --> D["BAC to MENU"]
    D -->|SET| B
    B -->|↓| E["↓"]
    C -->|↓| F["↓"]
    D -->|↓| G["↓"]

"ALARM1"Alarm 1 Setting Menu

Operating mode of the relay on the device and the parameter according to that operating mode is set in this menu. All settings belonging to 1. Alarm relay is done in this menu. Settings belonging to 2. Alarm relay can be done in "ALARM2" menu. This menu has 1 sub-menu.

ENTES DCV-11C - "ALARM1"Alarm 1 Setting Menu - 1

"ALRM STAT" Alarm Status Setting Menu

Alarm function of the relay is activated in this menu. If "OFF" option is selected in this menu, alarm parameters of the corresponding relay can't be accessed. If the alarm function will be used, "ALRM STAT" option must be set as "ON" in this menu. When alarm status is set as "ON", the 4 sub-menus of this menu become accessible. These menus are "CONTACT POS", "ALRM TYPE", "TRIP" and "LATCH" menus.

ENTES DCV-11C - "ALRM STAT" Alarm Status Setting Menu - 1

flowchart
graph TD
    A["ALRM STAT OFF"] --> B["SET"]
    B --> C["OR"]
    C --> D["OR"]
    D --> E["CONTACT POS OFF"]
    E --> F["TRIP NO"]
    F --> G["LATCH NO"]
    G --> H["ALRM TYPE HIGH"]
    H --> I["BRACH MENU SET"]
    I --> J["SET"]
    J --> K["OR"]
    K --> L["OR"]
    L --> M["OR"]
    M --> N["OR"]
    N --> O["OR"]
    O --> P["OR"]
    P --> Q["OR"]
    Q --> R["OR"]
    R --> S["OR"]
    S --> T["OR"]
    T --> U["OR"]
    U --> V["OR"]
    V --> W["OR"]
    W --> X["OR"]
    X --> Y["OR"]
    Y --> Z["OR"]

11

"CONTACT POS" Contact Position Setting Menu

The starting position of the alarm relay output is set in this menu. If this option is selected as "OFF", contact output starts as open when there isn't a fault condition. If this option is selected as "ON", contact output will be closed when there isn't a fault condition. It is set "OFF" as factory default.

ENTES DCV-11C - "CONTACT POS" Contact Position Setting Menu - 1

"TRIP"

If the measured voltage value becomes more than 1.5 times of set maximum voltage value when the "TRIP" function is selected as "YES", related alarm contact will open without a delay. In this case, up segment on the LCD and the dot in the C1 segment turn on. If the measured voltage value becomes less than 0.5 times of set minimum voltage value, related alarm contact will open without a delay. In this case, down segment on the LCD and the dot in the C1 segment turn on.

ENTES DCV-11C - "TRIP" - 1
12

"LATCH"

When the latch function is selected as "YES", a predefined alarm contact will open in case an alarm state arises. When the alarm state is resolved, the contact remains open (It latches). To close the alarm outputs after the alarm state is resolved, UP and DOWN button are pressed at the same time. When the latch function is selected as "NO", the opened alarm output will close after the predefined delay time.

ENTES DCV-11C - "LATCH" - 1

"ALRM TYPE" Alarm Type Setting Menu

Operating mode of the alarm is set in this menu. Alarm has 3 operating modes which are High, Low and Range (High-Low).

ENTES DCV-11C - "ALRM TYPE" Alarm Type Setting Menu - 1

flowchart
graph LRPH_TYPE_H 19H --> SET["SET"]
    SET --> RLPH_TYPE_LO["RLPH TYPE LO"]
    style RLPH_TYPE_H 19H fill:#f9f,stroke:#333
    style RLPH_TYPE_LO fill:#ccf,stroke:#333

When the alarm type is selected as High Alarm, first contact output opens after an on-delay time ("H ON DEL") if the measured voltage becomes more than the entered maximum voltage value ("HGH VALUE") and immediate opening option is inactive. In this case, up segment on the LCD and the dot in the C1 segment turn on. When the measured voltage drops below the set maximum value ("HGH VALUE") as much as the high hysteresis value ("HIGH HYS") and immediate opening option is inactive, first output contact closes after an off-delay time ("H OFF DEL"). In this case, up segment on the LCD and the dot in the C1 segment turn off.

When the alarm type is selected as Low Alarm, first contact output opens after an on-delay time ("L ON DEL") if the measured voltage becomes less than the entered minimum voltage value ("LOW VALUE") and immediate opening option is inactive. In this case, down segment on the LCD and the dot in the C1 segment turn on. When the measured voltage rises above the set minimum value ("LOW VALUE") as much as the low hysteresis value ("LOW HYS") and immediate opening option is inactive, first output contact closes after an off-delay time ("L OFF DEL"). In this case, down segment on the LCD and the dot in the C1 segment turn off.

When the alarm type is selected as High-Low Alarm (Range), "LOW VALUE" operates as low alarm and "HGH VALUE" operates as high alarm. While this alarm type is selected, minimum voltage value ("LOW VALUE") can't be entered higher than maximum voltage value ("HGH VALUE").

HIGH ALARM

"HGH VALUE"

The highest value that you want the measured current to reach is entered in this menu. A value between -200....200 can be entered.

ENTES DCV-11C - "HGH VALUE" - 1

"HIGH HYS"

In this menu display, you should set the percentage value of hysteresis current required to return the device to normal current (in case of high current warning). This value shall be between 0 and 20.

ENTES DCV-11C - "HIGH HYS" - 1

"H ON DEL"

It is the delay time for the high voltage alarm to activate. The value is entered as seconds. It can be entered between 000.0 and 999.9 seconds.

ENTES DCV-11C - "H ON DEL" - 1

"H OFF DEL"

It is the delay time for the high voltage alarm to deactivate. The value is entered as seconds. It can be entered between 000.0 and 999.9 seconds.

ENTES DCV-11C - "H OFF DEL" - 1

LOW ALARM

"LOW VALUE"

The lowest value that you want: the measured current to reach is entered in this menu. A value between -200.0....200.0 can be entered.

ENTES DCV-11C - "LOW VALUE" - 1

"LOW HYS"

In this menu display, you should set the percentage value of hysteresis current required to return the device to normal current (in case of low current warning). This value shall be between 0 and 20.

ENTES DCV-11C - "LOW HYS" - 1

"L ON DEL"

It is the delay time for the low voltage alarm to activate. The value is entered as seconds. It can be entered between 000.0 and 999.9 seconds.

ENTES DCV-11C - "L ON DEL" - 1

"LOFF DEL"

It is the delay time for the low voltage alarm to deactivate. The value is entered as seconds. It can be entered between 000.0 and 999.9 seconds.

ENTES DCV-11C - "LOFF DEL" - 1

2.2.3 "ANLG OUT" Analog Output Setting Menu

"ANLG OUT"

The device can give a voltage or current output with respect to the measured voltage according to your selection. Analog output value can be selected as 0-10V, 2-10V, 0-20mA or 4-20mA. The user can set the analog output type, turn off the analog output, learn the active analog output type or set the minimum and maximum values which the device will take into consideration when generating an analog output.

ENTES DCV-11C - "ANLG OUT" - 1

flowchart
graph TD
    A["ANL6 OUT 0-20mA"] -->|SET| B["ANL6 OUT 10"]
    B --> C["ANL6 OUT 0-20mA"]
    C -->|SET| D["HIGHEST 200V"]
    C -->|SET| E["LOWEST 000V"]
    C -->|SET| F["BACK MENU"]
    D --> G["ANL6 OUT 4-20mA"]
    E --> H["ANL6 OUT 0-80V"]
    F --> I["ANL6 OUT 2-80V"]
    G --> J["AnL6 OUT 10"]
    H --> K["AnL6 OUT 4-20mA"]
    I --> L["AnL6 OUT 0-80V"]

"HIGHEST"

The voltage value corresponding to the maximum value of the selected analog output type is set in this menu. This value can be entered between -200 and 200V.

Example: When the analog output type is selected as 0 - 20 mA and "HIGHEST" value is set as 100V, current value on the analog output will be 20 mA when the measured voltage becomes 100V.

ENTES DCV-11C - "HIGHEST" - 1

"LOWEST"

The voltage value corresponding to the minimum value of the selected analog output type is set in this menu. This value can be entered between -200 and 200V.

Example: When the analog output type is selected as 0 - 20 mA and "LOWEST" value is set as 10V, current value on the analog output will be 0 mA when the measured voltage becomes 10V.

ENTES DCV-11C - "LOWEST" - 1

2.2.4 "RS-485" Serial Communication Setting Menu

All measured parameters can be transferred via RS485 line with MODBUS protocol and menus can be set remotely.

Note: Communication feature is available only on DCV-10S/10CS/11S/11CS models. In order for the communication to be accomplished; Address, Baudrate and Parity values must be entered to the device correctly. RS - 485 menu has 3 sub-menus. "ADDRESS", "BAUDRATE", "PARITY".

ENTES DCV-11C - "RS-485" Serial Communication Setting Menu - 1

flowchart
graph TD
    A["PS-485"] --> B["ADDRESS 001"]
    B --> C["BRUDRATE 9600"]
    C --> D["PARTY NONE"]
    D --> E["BACK MENU"]
    E --> F["SET"]
    F --> A

"ADDRESS" Address Setting

Address information can be entered between 1 and 247.

ENTES DCV-11C - "ADDRESS" Address Setting - 1

"BAUDRATE" Baudrate Settings

Enter one of the 2400 bps, 4800 bps, 9600 bps, 19200 bps, 38400 bps values as stated in the communication software.

ENTES DCV-11C - "ADDRESS" Address Setting - 2

flowchart
graph LR
    A["3AU/4ATE 9600"] -->|SET| B["3AU/4ATE 9500"]
    B -->|SET+0.00| C["3AU/4ATE 9600"]
    C -->|SET| D["Selected parameter is displayed"]

"PARITY" Parity Setting

Parity can be entered as none, odd or even.

ENTES DCV-11C - "ADDRESS" Address Setting - 3

flowchart
graph LR
    A["PARITY\nNONE"] -->|SET| B["PARITY\nNone\nEVEN"]
    B -->|SET| C["Selected parameter is displayed\nPARITY\nEVEN"]

21

MODBUS RTU PROTOCOL

Standart MODBUS RTU message is shown below.

TADDRESS8 BITFUNCTION8 BITDATA N × 8 BITCRCHCRCLT

The T times corresponds to a time in which data must not be exchanged on the communication bus to allow the connected devices to recognize the end of one message and the beginning of another. This time must be at least 3.5 characters at the selected baud rate. Adress range (1-247) is address of the connected device. The data field contains data sent to the slave by master or data sent to master by slave. CRC is a error check method by using MODBUS RTU protocol and consists of 2 bytes.

Modbus Functions:

03HREAD HOLD REGISTERS10HPRESET MULTIPLE REGISTERS
06HPRESET SINGLE REGISTER2BHREAD DEVICE INFO

22

Read Hold (03H) function is used for reading the measured parameter (intantenaous measurement value, minimum and maximum measurement values) and other setting values of the device. If any register other than this area has been tried to read, the device will send an error message. For example; below message can be sent to read the measured voltage value:

01DeviceAddress03Function00MSBAddress00LSBAddress00RegisternumberMSB01RegisternumberLSB84CRCMSB0A LSB

Preset Single Register (06H) function is used for change device settings and resetting the measured minimum/maximum values. For example; below message can be sent to set the period value to 100:

01DeviceAddress06Function80MSBAddress27LSBAddress00DataMSB64DataLSB11CRCMSBEA CRCLSB

Preset Multiple register (10H) function is used for changing more than one register value. For example; below message can be sent to set the contrast value to 10 and the period value to 100:

01DeviceAddress10Function80MSBAddr.26LSBAddr.00RegisternumberMSB02RegisternumberLSB04Bytecount00DataMSB0ADataLSB00DataMSB64DataLSB31CRCMSBB2CRCLSB

Read device info (2BH) function is used to learn the manufacturer name, the device code, hardware version and software version. The query packet to read the device info is as following: 01 2B 0E 01 00 70 77

2.2.5 "RESET" Reset Menu

Minimum and maximum values among measured voltage values are stored on the device. Reset menu is used in order to delete these values. There are 2 sub-menus under Reset menu: "RESET MIN", "RESET MAX". To see the measured minimum and maximum values, refer to the "Special Functions for Buttons" section of this user manual.

NOTE: Stored values are not affected from power outages. Measured minimum and maximum values are deleted after you select YES option under the value that you want to reset and approve the changes when you exit or a zero (0) value is written into the addresses that these values are stored.

ENTES DCV-11C - "RESET" Reset Menu - 1

flowchart
graph TD
    A["RESET"] --> B["RESET MIN"]
    B --> C["RESET MAX"]
    C --> D["BACK MENU"]
    D --> E["SET"]
    E --> A
    style A fill:#f9f,stroke:#333
    style B fill:#ccf,stroke:#333
    style C fill:#cfc,stroke:#333
    style D fill:#fcc,stroke:#333

"RESET MIN" Minimum Value Reset Menu

It is the menu where stored minimum voltage value is deleted.

ENTES DCV-11C - "RESET MIN" Minimum Value Reset Menu - 1

"RESET MAX" Maximum Value Reset Menu

It is the menu where stored maximum voltage value is deleted.

ENTES DCV-11C - "RESET MAX" Maximum Value Reset Menu - 1

2.2.6 "DISPLAYSET" Display Setting Menu

Settings about the device display are done in this menu. Display setting menu has 2 sub-menus: "BACKLIGHT", "CONTRAST".

ENTES DCV-11C - "DISPLAYSET" Display Setting Menu - 1

flowchart
graph TD
    A["DISPLAYSET"] --> B["BYCALTIGHT"]
    B --> C{YES}
    C --> D["CONTRAST"]
    D --> E["BYC MENU"]
    E --> F{IS}
    F --> G["Feedback to BYC"]
    G --> A

"BACKLIGHT" LCD Backlight Setting Menu

Backlight feature of the device is configured in this menu. Available choices are as following: "NO" Off. "YES" Continuously on. "30 s" On for 30 seconds, "60 s" On for 1 minute, "300 s" On for 5 minutes, "900 s" On for 15 minutes. Backlight turns off after the selected time if no button is pressed at the end of that time.

ENTES DCV-11C - "BACKLIGHT" LCD Backlight Setting Menu - 1

flowchart
graph LR
    A["30C V LIGHT YES"] -->|SET| B["30C V LIGHT"]
    B --> C["900 S"]
    B --> D["100 S"]
    C --> E["Selected parameter is displayed."]
    D --> E
    E --> F["30 S"]

"CONTRAST" Contrast Setting Menu

Contrast of the device display is set in this menu. It can be set to a value between "00" and "15".

ENTES DCV-11C - "CONTRAST" Contrast Setting Menu - 1

2.2.7 "LANGUAGE" Language Setting Menu

Language of the device is set in this menu. There are 5 language options as "Tr" Turkish, "Eng" English, "dE" German, "ESP" Spanish and "FR" French.

ENTES DCV-11C - "LANGUAGE" Language Setting Menu - 1

flowchart
graph LR
    A["输入"] --> B["SET"]
    B --> C["中间处理模块"]
    C --> D["SET"]
    D --> E["LANGUAGE ENG"]

27

2.2.8 "FCTRY SET" Factory Setting Menu

Factory settings are loaded in this menu. A 4 digit password is asked when entering this menu. If password protection is active, the password isn't asked again when entering this menu because it was entered during entering the main menu. If "YES" option is selected in this menu and "SAVE" confirmation is approved at the exit of main menu, factory settings are loaded (Refer to: Factory Default Values).

ENTES DCV-11C - "FCTRY SET" Factory Setting Menu - 1

flowchart
graph TD
    A["FCTRY SET"] --> B["Set"]
    B --> C{If password is inactive.}
    C -->|Yes| D["ENTR PRESS 0000"]
    C -->|No| E["SET"]
    D --> F{ENTR PRESS 0000}
    F --> G["Set"]
    G --> H{If password is wrong.}
    H --> I["ERROr"]
    G --> J{If password is correct.}
    J --> K["FCTRY SET"]
    K --> L{SET}
    L -->|Yes| M["END"]
    L -->|No| N["SETTINGS DONE"]
    M --> O["End"]
    N --> O

NOTE: When factory settings are loaded, language setting stays unchanged. The language will be the same as the on selected last.
28

2.2.9 "SECURITY" Security Setting Menu

Device password settings are done in this menu. There are 2 sub-menus under SECURITY menu. "PASS ACTV", "PASS CHNG". Password activation and changing operations are done under these menus. Factory default password is "0000".

ENTES DCV-11C - "SECURITY" Security Setting Menu - 1

flowchart
graph TD
    A["SECURITY"] -->|SET| B["NO"]
    B --> C["PASS ACTV"]
    C --> D["PASS CHNG"]
    D --> E["BACK MENU"]
    E -->|SET| A
    E -->|NO| F["↓"]
    F --> G["↓"]
    G --> H["↓"]
    H --> I["↓"]
    I --> J["↓"]
    J --> K["↓"]
    K --> L["↓"]
    L --> M["↓"]
    M --> N["↓"]
    N --> O["↓"]
    O --> P["↓"]
    P --> Q["↓"]
    Q --> R["↓"]
    R --> S["↓"]
    S --> T["↓"]
    T --> U["↓"]
    U --> V["↓"]
    V --> W["↓"]
    W --> X["↓"]
    X --> Y["↓"]
    Y --> Z["↓"]
    Z --> A

"PASS ACTV" Password Activation Menu

Password protection is activated or deactivated in this menu.

ENTES DCV-11C - "PASS ACTV" Password Activation Menu - 1

flowchart
graph LR
    A["PRSS ACTV PS IUE"] --> B["ENTR PASS 0000"]
    B --> C["ENTR PASS 0000"]
    C --> D["Selected parameter is displayed."]
    D --> E["PRSS ACTV ACEUE"]

29

"CHNG PASS" Change Password Menu

Password is changed in this menu.

ENTES DCV-11C - "CHNG PASS" Change Password Menu - 1

flowchart
graph TD
    A["CHNG PASS"] --> B["QL1 PASS"]
    B --> C["QL2 PASS"]
    C --> D["NEW PASS"]
    E["PRS CHNG3"] --> F["REENTER"]
    F --> G["QL1"]
    G --> H["QL2"]
    H --> I["NEW PASS"]
    J["SET"] --> K["000"]
    L["SET"] --> M["000"]
    N["SET"] --> O["000"]
    P["SET"] --> Q["111"]
    R["SET"] --> S["111"]

2.2.10 "INFO" Menu

This menu display shows software and hardware version as well as serial number of the device. It has 3 sub-menus.. "SOFT VER", "HARD VER", "SERI NO".

"SOFT VER"

This menu display shows the software version of the device.

"HARD VER"

This menu display shows the hardware version of the device.

"SERI NO"

This menu display shows the serial number of the device.

ENTES DCV-11C - "SERI NO" - 1

flowchart
graph TD
    A["INFO"] -->|SET| B["SOFT PER 2.00.00"]
    B --> C["HARPER PER 2.00.00"]
    C --> D["SERI NO 0000"]
    D --> E["BACK MENU"]
    E -->|←| F["↓"]
    F --> G["↔"]
    G --> H["↔"]
    H --> I["↔"]
    I --> J["↔"]
    J --> K["↔"]
    K --> L["↔"]
    L --> M["↔"]
    M --> N["↔"]
    N --> O["↔"]
    O --> P["↔"]
    P --> Q["↔"]
    Q --> R["↔"]
    R --> S["↔"]
    S --> T["↔"]
    T --> U["↔"]
    U --> V["↔"]
    V --> W["↔"]
    W --> X["↔"]
    X --> Y["↔"]
    Y --> Z["↔"]
    Z --> A

30

2.2.11 "ESCAPE" Exiting Main Menu

It is used to exit the main menu. If any changes has been made in the menus, a confirmation is asked to save those changes. If there are no changes, measurement results are displayed without a confirmation.

ENTES DCV-11C - "ESCAPE" Exiting Main Menu - 1

flowchart
graph LR
    A["ESCAPE"] --> B["SET"]
    B --> C["SR/VE"]
    C --> D{no}
    D -->|SET| E["Changes are saved."]
    D -->|SET| F["Changes are discarded."]
    E --> G["MEASUREMENT SCREEN 024.00 V"]
    F --> G

3. INSTALLATION

3.1. DIMENSIONS AND INSTALLATION

Dimensions
ENTES DCV-11C - DIMENSIONS AND INSTALLATION - 1

Panel Cutout Dimensions
ENTES DCV-11C - DIMENSIONS AND INSTALLATION - 2

Control Panel Area Dimensions
ENTES DCV-11C - DIMENSIONS AND INSTALLATION - 3

3.2. CONNECTION DIAGRAM
RELAY 1 RELAY 2 1 2 3 4 * V GNO A TR B A GNO 5 6 7 ** 8 9 10 11 *** RS-485 1A + 10-56VDC ***** + Vin --- - 14 15 16 Un ≈ 200V DC 1A 85-265 V AC/DC ****

* Only for DCV-10C/10CS/11C/11CS
** Only for DCV-10A/11A
*** Only for DCV-10S/10CS/11S/11CS
**** Only for DCV-10/10A/10C/10S/10CS
***** Only for DCV-11/11A/11C/11S/11CS

3.3. PC CONNECTION
ENTES DCV-11C - DIMENSIONS AND INSTALLATION - 5

flowchart
graph LR
    A["TR0 A GND"] --> B["Max. 1200 mt."]
    C["TR0 A GND"] --> D["Max. 1200 mt."]
    E["TR0 A GND"] --> F["Max. 1200 mt."]
    G["TR0 A GND"] --> H["Max. 1200 mt."]
    I["BS A GND"] --> J["PC"]
    K["DSV-10S/10CS-31, DCV-11S/11CS-31"] --> A
    L["DSV-10S/10CS-2, DCV-11S/11CS-2"] --> C
    M["DSV-19S/10CS-1, DCV-11S/11CS-1"] --> E
    N["DSV-19S/10CS-1"] --> F
    O["DSV-19S/10CS-1"] --> H
    P["DSV-19S/10CS-1"] --> I
    Q["DSV-19S/10CS-1"] --> L
    R["DSV-19S/10CS-1"] --> M
    S["DSV-19S/10CS-1"] --> N
    T["DSV-19S/10CS-1"] --> O
    U["DSV-19S/10CS-1"] --> P
    V["DSV-19S/10CS-1"] --> M
    W["DSV-19S/10CS-1"] --> N
    X["DSV-19S/10CS-1"] --> O
    Y["DSV-19S/10CS-1"] --> P
    Z["DSV-19S/10CS-1"] --> M
    AA["DSV-19S/10CS-1"] --> N
    AB["DSV-19S/10CS-1"] --> O
    AC["DSV-19S/10CS-1"] --> P
    AD["DSV-19S/10CS-1"] --> N
    AE["DSV-19S/10CS-1"] --> O
    AF["DSV-19S/10CS-1"] --> P
    AG["DSV-19S/10CS-1"] --> N
    AH["DSV-19S/10CS-1"] --> O
    AI["DSV-19S/10CS-1"] --> P
    AJ["DSV-19S/10CS-1"] --> N
    AK["DSV-19S/10CS-1"] --> O
    AL["DSV-19S/10CS-1"] --> P
    AM["DSV-19S/10CS-1"] --> N
    AN["DSV-19S/10CS-1"] --> O
    AO["DSV-19S/10CS-1"] --> P
    AP["DSV-19S/10CS-1"] --> N
    AQ["DSV-19S/10CS-1"] --> O
    AR["DSV-19S/10CS-1"] --> P
    AS["DSV-19S/10CS-1"] --> N
    AT["DSV-19S/10CS-1"] --> O
    AU["DSV-19S/10CS-1"] --> P
    AV["DSV-19S/10CS-1"] --> N
    AW["DSV-19S/10CS-1"] --> O
    AX["DSV-19S/10CS-1"] --> P
    AY["DSV-19S/10CS-3"]
    AZ["DSV-19S/10CS-3"]
    BA["DSV-19S/10CS-3"]

ENTES DCV-11C - DIMENSIONS AND INSTALLATION - 6

flowchart
graph LR
    A["DCV-10S/10CS -247. DCV-11S/11CS -247."] --> B["REPEATER"]
    B --> C["DCV-10S/10CS -31. DCV-11S/10CS -31. DCV-10S/10CS -2. DCV-10S/10CS -1. DCV-11S/11CS -2. DCV-11S/11CS -1."]
    C --> D["PC"]
    E["Max 1200 mL"] --> F["Max 1200 mL"]
    G["DCV-10S/10CS -247. DCV-11S/11CS -247."] --> H["DCV-10S/10CS -31. DCV-10S/10CS -2. DCV-10S/10CS -1. DCV-11S/11CS -2. DCV-11S/11CS -1."]

4. FACTORY DEFAULT VALUES:

Alarms:(DCV-10C/10CS/11C/11CS)

  1. Alarm:

Alarm Status

Latch

Trip

Contact Position (Output Inverse)

Alarm Type

High Alarm Value

Low Alarm Value

High Alarm Hysteresis

Low Alarm Hysteresis

High Alarm On Delay (d_on_time)

High Alarm Off Delay (d_off_time)

Low Alarm On Delay (d_on_time)

Low Alarm Off Delay (d_off_time)

2.Alarm:

Alarm Status

Latch

Trip

Contact Position (Output Inverse)

Alarm Type

High Alarm Value

Low Alarm Value

High Alarm Hysteresis

: Passive

: Off

: Off

: Off

: High Alarm

: 100V

: 10V

: 10

: 5

: 20s

: 10s

: 20s

: 10s

广力云智慧零售收银系统

: Passive

: Off

: Off

: Off

: High Alarm

: 100V

: 10V

: 10

Low Alarm Hysteresis: 5
High Alarm On Delay (d_on_time): 20s
High Alarm Off Delay (d_off_time): 10s
Low Alarm On Delay (d_on_time): 20s
Low Alarm Off Delay (d_off_time): 10s
RS 485: (DCV-10S/10CS/11S/11CS)
Address: 1
Baudrate: 9600
Parity: None
Analog Output: (DCV-10A/11A)
Analog Output: 0 - 20 mA
Assign Hi: 200V
Assign Lo: 0V
Period: 1 (second)
Display
Backlight: On
Contrast: 15
Security
Password Protection: Off
Password: 0

5. TECHNICAL FEATURES:

Operating Voltage (Un)

Frequency

Supply Input Power Consumption

Measuring Input Power Consumption

Measuring Input Resistance (Rin)

Measuring Voltage Range

Accuracy

Relay Outputs (2 pieces)

Communication

Baudrate

Address

Parity

Analog Output

Analog Voltage Output

Load Resistance

Update Period

Analog Current Output

Load Resistance

Update Period

Accuracy

Period

:85-265V AC/DC (DCV-10/10A/10C/10S/10CS).

10-56V DC (DCV-11/11A/11C/11S/11CS)

:50/60 Hz (DCV-10/10A/10C/10S/10CS)

:<4 VA

:<1 VA

:<2M

:+/- 200V

:0.5% ±1 Digit [(10% - 100%) x full scale] **

:2 NO, 5A 1250 VA (DCV-10C/10CS/11C/11CS)

:MODEUS RTU (RS-485) Programmable.(DCV-10S/10CS/11S/11CS)

:2400-38400

:1-247

:None, Odd, Even

:(DCV-10A/11A)

:0-10 V or 2-10 V

:>=1K2 Ohm

:100ms (milliseconds).

:0-20 mA or 4-20 mA

:<= 500ohm

:100ms (milliseconds).

+0.01% ES

:1 - 600 seconds

Ambient Temperature : -20 ... 70°C

Display :2.5 inches Backlit LCD

Dimensions :PR-20

Device Protection Class :Double Insulation - Class II (☐)

Casing Protection Class :IP 40

Terminal Protection Class :IP 00

Wire Width (For Terminals) :2.5mm2

Casing Material : Nonflammable

Installation Type :Flush Mounting ( PR-20 )

Weight :0.240 kg

Installation Class :Class III

Panel Cutout Dimensions :48X96 mm (PR-20)

** Measurement accuracy may change when measured waveform is not pure DC. (Measuring error may increase to 5% for half-wave and full-wave rectified AC signals. Capacitive filter usage is suggested to increase the precision for measuring such signals.) It is recommended to use "Capactive filter" in order to improve accuracy of measurements.

  1. REGISTER TABLE:
Bit Register Table
Address (HEX)DescriptionWRRangeUnitMultiplierFormat
0x0000DC Voltage ValueR+/- 20000V0,01signed int
0x0001Max. Measurement ValueR/W+/- 20000V0,01signed int
0x0002Min. Measurement ValueR/W+/- 20000V0,01signed int
0x8000Shunt Current *R/W1 – 10000A1unsigned int
0x8001Shunt Voltage *R/W50-150mV1unsigned int
0x8002Alarm 1 ActivationR/W0 – 1-1unsigned int
0 → Alarm 1 inactive
1 → Alarm 1 active
0x8003Alarm 1 Latch FunctionR/W0-1-1unsigned int
0 → Latch Inactive
1 → Latch Active
0x8004Alarm 1 Trip FunctionR/W0-1-1unsigned int
0 → Trip Inactive
1 → Trip Active

* Only valid for DCA-10/10A/10C/10S/10CS/11/11A/11C/11S/11CS.

Address (HEX)DescriptionWRRangeUnitMultiplierFormat
0x8005Alarm 1 Contact PositionR/W0-1-1unsigned int
0 ----> Normal
1 ----> Inverted
0x8006Alarm 1 Alarm TypeR/W0-2-1unsigned int
0 ----> High Protection Active
1 ----> Low Protection Active
2 ----> Range Protection Active
0x8007Alarm 1 High Warning ValueR/W+/- 20000v0,1long int
0x8009Alarm 1 Low Warning ValueR/W+/- 20000v0,1long int
0x800BAlarm 1 High HysteresisR/W0-20%1unsigned int
0x800CAlarm 1 Low HysteresisR/W0-20%1unsgined int
0X800DAlarm 1 High Alarm ON DelayR/W0-9999second0,1unsigned int
0x800EAlarm 1 High Alarm OFF DelayR/W0-9999second0,1unsigned int
Address (HEX)DescriptionWRRangeUnitMultiplierFormat
0x800FAlarm 1Low AlarmON DelayR/W0-9999saniye0,1unsigned int
0x8010Alarm 1Low AlarmOFF DelayR/W0-9999saniye0,1unsigned int
0x8011Alarm 2ActivationR/W0-1-1unsigned int
0 --> Protection Inactive
1 --> Protection Active
0x8012Alarm 2Latch FunctionR/W0-1-1unsigned int
0 --> Latch Inactive
1 --> Latch Active
0x3013Alarm 2Trip FunctionR/W0-1-1unsigned int
0 --> Trip Inactive
1 --> Trip Active
0x3014Alarm 2Contact PositionR/W0-1-1unsigned int
0 --> Normal
1 --> Inverted
0x3015Alarm 2Alarm TypeR/W0-2-1unsigned int
0 --> High Protection Active
1 --> Low Protection Active
2 --> Range Protection Active
Addres (HEX)DescriptionW/RRangeUnitMultiplierFormat
0x8016Alarm 2High Warning ValueR/W+/- (Shunt Current)v1long int
0x8018Alarm 2Low Warning ValueR/W+/- (Shunt Current)v1long int
0x8001AAlarm 2High HysteresisR/W0-20%1ungined int
0x8001BAlarm 2Low HysteresisR/W0-20%1ungined int
0x8001CAlarm 2High AlarmON DelayR/W0-9999second0,1unsigned int
0x8001DAlarm 2High AlarmOFF DelayR/W0-9999second0,1unsigned int
0x8001EAlarm 2Low AlarmON DelayR/W0-9999second0,1unsigned int
0x8001FAlarm 2Low AlarmOFF DelayR/W0-9999second0,1unsigned int
Address (HEX)DescriptionW / RAlarm StatusUnitMultiplierFormat
0x8020Alarm1 StatusR0: Alarm doesn't count1: High Alarm2: Low Alarm-1unsigned int
0x8021Alarm2 StatusR0: Alarm doesn't count1: High Alarm2: Low Alarm-1unsigned int
Address (HEX)DescriptionW/RRangeUnitMultiplierFormat
0x8022Analog Output Type/RangeR/W0-4-1unsigned int
0 OUTPUT INACTIVE
1 OUTPUT TYPE VOLT RANGE = 0-10 V
2 OUTPUT TYPE VOLT RANGE = 2-10 V
3 OUTPUT TYPE CURRENT RANGE = 0-20 mA
4 OUTPUT TYPE CURRENT RANGE = 4-20 mA
0x8023Assign HiR/W+/- 20000v0,1long int
0x8025Assign LoR/W+/- 20000v0,1long int
0x8027Comm. AddressR/W1-247-1unsigned int
0x8026Baud RateR/W0--4bps1unsigned int
0--2400
1--4800
2--9600
3--19200
4--38400
0x8029ParityR/W0-2-1unsigned int
0-->None,1-->Ost,2-->Even
0x802APass. ProtectionR/W0-->Off -1-->On-1unsigned int
0x802BPasswordR/W0-9999-1unsigned int
Address (HEX)DescriptionW/RRangeUnitMultiplierFormat
0x802CBacklight StatusR/W0~4-1unsigned int
0→Backlight Off
1→Backlight On continuously
2→Backlight On for 30 seconds
3→Backlight On for 1 minute
4→Backlight On for 5 minutes
5→Backlight On for 15 minutes
0x802DContrastR/W0-15
0x802EAverage PeriodR/W1~600second1unsigned int
0x802FLanguageR/W0~4-1unsigned int
0:TR 1:ENG 2:DE 3:FR 4:ESP
32 Bit Register Table
Address (HEX)DescriptionWRRangeUnitMultiplierFormat
0x4J00DC Current ValueR+/- 10000000A0,001long int
0x4J02Max. Measurement ValueR/W+/- 10000000A0,001long int
0x4J04Min. Measurement ValueR/W+/- 10000000A0,001long int

Note: When these addresses are read on a DCV Series device, 0 (zero) value will be read.

EC00DEVICE IDR0xB601-0xB604-1unsigned int
EC01DEVICE ID && VERSION NOR0x0111 - 0x01FF-1unsigned int
EC02SERIAL NOR0x0000 - 0xFFFF-1unsigned int
EC03-1unsigned int
EC04SOFTWARE VERSIONR-1unsignedlong
EC06HARDWARE VERSIONR-1unsignedlong
EC08MODBUS TABLE VERSIONR-1unsignedlong
EC0APRODUCTION DATER-1unix time
EC0CCALIBRATION DATER-1unix time
DEVICE IDDEVICE TYPEDEVICE IDDEVICE TYPEDEVICE IDDEVICE TYPEDEVICE IDDEVICE TYPE
B60101DCA-1CB60201DCV-10B60301DCA-11B60401DCV-11
B60102DCA-10AB60202DCV-10AB60302DCA-11AB60402DCV-11A
B60103DCA-10SB60203DCV-10SB60303DCA-11SB60403DCV-11S
B60104DCA-10CB60204DCV-10CB60304DCA-11CB60404DCV-11C
B60105DCA-10CSB60205DCV-10CSB60305DCA-11CSB60405DCV-11CS
Supported Modbus Functions:
03HREAD HOLD REGISTERS
06HPRESET SINGLE REGISTER
10HPRESET MULTIPLE REGISTERS
2BHREAD DEVICE INFO
Data TypeSize
signed int16 bit
unsigned int16 bit
long int32 bit
unsigned long32 bit

When a reading operation from addresses that are not present on the device is done, 0 (zero) value will be read. When a writing operation to addresses that are not present on the device is done, no writing is done and no error code is returned.

  1. MENU MAP
    ENTES DCV-11C - Period - 1
flowchart
graph TD
    A["024.00"] --> B{is displayed if password is active}
    B --> C["0000"]
    C --> D{0000?}
    D --> E["0000"]
    E --> F{errOr}
    F --> G["001"]
    G --> H{PERIOD 001?}
    H --> I["050"]
    I --> J{PERIOD 050?}
    J --> K["Last entered value is displayed."]
    K --> L["001"]
    L --> M{If password is inactive}
    M --> N["0000"]
    N --> O{If password is correct}
    O --> P["0000"]
    P --> Q["ERROr"]
    Q --> R["001"]
    R --> S["PERIOD 050"]
    S --> T["001"]
    T --> U["PERIOD 050"]

ENTES DCV-11C - Period - 2

flowchart
graph TD
    A["RLRMS"] --> B["RLRMS 1"]
    A --> C["RLRMS 2"]
    A --> D["BRC+NEW"]
    B --> E["OFF"]
    C --> F["OFF"]
    D --> G["H 19H"]
    E --> H["Selected parameter is displayed."]
    F --> I["Selected parameter is displayed."]
    G --> J["High Value 100"]
    G --> K["Low Value 0.10"]
    G --> L["High Value 100"]
    G --> M["Low Value 0.10"]
    G --> N["High Value 0.20.0"]
    G --> O["Low Value 0.10"]
    H --> P["354 KOS 05"]
    I --> Q["3 BICHE 5 020.0"]
    J --> R["3 JONHE 5 0.10.0"]
    K --> S["BRC MENU 020.0"]
    L --> T["BRC MENU 0.10.0"]
    M --> U["BRC MENU 0.10.0"]
    N --> V["BRC MENU 0.10.0"]
    O --> W["BRC MENU 0.10.0"]
    P --> X["LATCH 70"]
    Q --> Y["LATCH 70"]
    R --> Z["LATCH 70"]
    S --> AA["LATCH 70"]
    T --> AB["LATCH 70"]
    U --> AC["LATCH 70"]
    V --> AD["LATCH 70"]
    W --> AE["LATCH 70"]
    X --> AF["LATCH 70"]
    Y --> AG["LATCH 70"]
    Z --> AH["LATCH 70"]
    AA --> AI["LATCH 70"]
    AB --> AJ["LATCH 70"]
    AC --> AK["LATCH 70"]
    AD --> AL["LATCH 70"]
    AE --> AM["LATCH 70"]
    AF --> AN["LATCH 70"]
    AG --> AO["LATCH 70"]
    AH --> AP["LATCH 70"]
    AI --> AQ["LATCH 70"]
    AJ --> AR["LATCH 70"]
    AK --> AS["LATCH 70"]
    AL --> AT["LATCH 70"]
    AM --> AU["LATCH 70"]
    AN --> AV["LATCH 70"]
    AO --> AW["LATCH 70"]
    AP --> AX["LATCH 70"]
    AQ --> AY["LATCH 70"]
    AR --> AZ["LATCH 70"]
    AS --> BA["LATCH 70"]
    AT --> BB["LATCH 70"]
    AU --> BC["LATCH 70"]
    AV --> BD["LATCH 70"]
    AW --> BE["LATCH 70"]
    AX --> BF["LATCH 70"]
    AY --> BG["LATCH 70"]
    AZ --> BH["LATCH 70"]

ENTES DCV-11C - Period - 3

flowchart
graph TD
    A["Input"] --> B["0-20 mA"]
    B --> C["RALE OUT 0-20 mA"]
    C --> D["RALE OUT 4-20 mA"]
    D --> E["RALE OUT 8-10 v"]
    E --> F["RALE OUT 2-10 v"]
    F --> G["HIGHEST 100 v"]
    G --> H["Last entered value is displayed."]
    H --> I["HIGHEST 200 v"]
    I --> J["LIGHEST 000 v"]
    J --> K["BRICH MENU"]
    K --> L["Output"]
    style A fill:#f9f,stroke:#333
    style B fill:#ccf,stroke:#333
    style C fill:#cfc,stroke:#333
    style D fill:#fcc,stroke:#333
    style E fill:#cff,stroke:#333
    style F fill:#ffc,stroke:#333
    style G fill:#fcf,stroke:#333
    style H fill:#cff,stroke:#333
    style I fill:#fcf,stroke:#333
    style J fill:#cff,stroke:#333
    style K fill:#ffc,stroke:#333
    style L fill:#cfc,stroke:#333

49

ENTES DCV-11C - Period - 4

flowchart
graph TD
    A["PS485"] --> B["ADDRESS 001"]
    B --> C["RJDRATE 9600"]
    C --> D["PROPTY none"]
    D --> E["BRL & MENU"]
    E --> F["Only valid for DCV-90S/10CS/11S/11CS."]
    B --> G["RJDRATE 001"]
    G --> H["Last second permutation is displayed."]
    C --> I["RJDRATE 9600"]
    I --> J["Last second permutation is displayed."]
    D --> K["PROPTY none"]
    K --> L["Last second permutation is displayed."]
    E --> M["BRL & MENU"]
    M --> N["Last second permutation is displayed."]

50

ENTES DCV-11C - Period - 5

flowchart
graph TD
    A["RESET"] --> B["RESET HIN"]
    B --> C["RESET HFE"]
    C --> D["BPL+HOU"]
    D --> E["AND"]
    E --> F["RESET HIN"]
    F --> G["RESET HFE"]
    G --> H["BPL+HOU"]
    H --> I["AND"]
    I --> J["RESET HIN"]
    J --> K["RESET HFE"]
    K --> L["BPL+HOU"]
    L --> M["AND"]
    M --> N["RESET HIN"]
    N --> O["RESET HFE"]
    O --> P["BPL+HOU"]
    P --> Q["AND"]
    Q --> R["RESET HIN"]
    R --> S["RESET HFE"]
    S --> T["BPL+HOU"]
    T --> U["AND"]
    U --> V["RESET HIN"]
    V --> W["RESET HFE"]
    W --> X["BPL+HOU"]
    X --> Y["AND"]
    Y --> Z["RESET HIN"]
    Z --> AA["RESET HFE"]
    AA --> AB["BPL+HOU"]
    AB --> AC["AND"]
    AC --> AD["RESET HIN"]
    AD --> AE["RESET HFE"]
    AE --> AF["BPL+HOU"]
    AF --> AG["AND"]
    AG --> AH["RESET HIN"]
    AH --> AI["RESET HFE"]
    AI --> AJ["BPL+HOU"]
    AJ --> AK["AND"]
    AK --> AL["RESET HIN"]
    AL --> AM["RESET HFE"]
    AM --> AN["BPL+HOU"]
    AN --> AO["AND"]
    AO --> AP["RESET HIN"]
    AP --> AQ["RESET HFE"]
    AQ --> AR["BPL+HOU"]
    AR --> AS["AND"]
    AS --> AT["RESET HIN"]
    AT --> AU["RESET HFE"]
    AU --> AV["BPL+HOU"]
    AV --> AW["AND"]
    AW --> AX["RESET HIN"]
    AX --> AY["RESET HFE"]
    AY --> AZ["BPL+HOU"]
    AZ --> BA["AND"]
    BA --> BB["RESET HIN"]
    BB --> BC["RESET HFE"]
    BC --> BD["BPL+HOU"]
    BD --> BE["AND"]
    BE --> BF["RESET HIN"]
    BF --> BG["RESET HFE"]
    BG --> BH["BPL+HOU"]
    BH --> BI["AND"]
    BI --> BJ["RESET HIN"]
    BJ --> BK["RESET HFE"]
    BK --> BL["BPL+HOU"]
    BL --> BM["AND"]
    BM --> BN["RESET HIN"]
    BN --> BO["RESET HFE"]
    BO --> BP["BPL+HOU"]
    BP --> BQ["AND"]
    BQ --> BR["RESET HIN"]
    BR --> BS["RESET HFE"]
    BS --> BT["BPL+HOU"]
    BT --> BU["AND"]
    BU --> BV["RESET HIN"]
    BV --> BW["RESET HFE"]
    BW --> BX["BPL+HOU"]
    BX --> BY["AND"]
    BY --> BZ["RESET HIN"]
    BZ --> CA["RESET HFE"]
    CA --> CB["BPL+HOU"]

ENTES DCV-11C - Period - 6

flowchart
graph TD
    A["LYNGURSE"] --> B["If password is inactive"]
    B --> C{000?}
    C -->|Yes| D["ETUP PRESS"]
    C -->|No| E{000?}
    E -->|Yes| F["ETUP PRESS"]
    E -->|No| G["If password is active"]
    G --> H{00?}
    H -->|Yes| I["SET: N65"]
    H -->|No| J["done"]
    I --> K["SET: N65"]
    J --> L["End"]
    style A fill:#f9f,stroke:#333
    style K fill:#ccf,stroke:#333
    style L fill:#ccf,stroke:#333

ENTES DCV-11C - Period - 7

flowchart
graph TD
    A["SECURITY"] --> B["PRSS RECY NO"]
    B --> C["PRSS CHNG"]
    C --> D["BRE MENU"]
    D --> E["INIT PRSS 0000"]
    E --> F["ENTP PRSS 0000"]
    F --> G["ERROr"]
    G --> H{If password is wrong.}
    H -->|Yes| I["OK"]
    H -->|No| J["Error"]
    I --> K["PRSS RECY"]
    J --> L["Selected parameter is displayoc."]
    K --> M["INFO"]
    L --> N["SOFT VER 2.00.00"]
    N --> O["HARDYER 2.00.00"]
    O --> P["SERIAL NJ 00001"]
    P --> Q["BRE MENU"]
    Q --> R["ESCRIPT"]
    R --> S["SAVE"]
    S --> T{Changes are saved.}
    T -->|Yes| U["OK"]
    T -->|No| V["Change to discarded"]
    V --> W["120.00v"]
    W --> X["53"]
    X --> Y["If password is correct."]
    Y --> Z["OLI PRSS 0000"]
    Z --> AA["OLI PRSS 0000"]
    AA --> AB["ORRIN"]
    AB --> AC["ORRIN"]
    AC --> AD["ORRIN"]
    AD --> AE["1111"]
    AE --> AF["ORRIN"]
Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : ENTES

Model : DCV-11C

Category : Voltmeter