BPH A36T-6 - Rechargeable Battery PowerPlus - Free user manual and instructions
Find the device manual for free BPH A36T-6 PowerPlus in PDF.
| Brand | PowerPlus |
| Model | BPH A36T-6 |
| Product type | Battery Pack (UPS Battery Module) |
| Battery type | Sealed Lead-Acid (SLA) Rechargeable |
| Number of batteries | 6 |
| Individual battery rating | 12V 7Ah or 12V 9Ah |
| Total nominal voltage | 36V (assuming series configuration) |
| Total capacity | 54Ah (if 9Ah batteries in series-parallel) or 42Ah (if 7Ah) |
| Operating temperature | 0°C to 40°C |
| Humidity range | 30% to 90% non-condensing |
| Storage temperature | -25°C to 45°C |
| Recharge frequency (storage) | Every 2-3 months |
| Charging duration (storage) | 1-2 hours |
| Battery service life | 3-5 years at 25°C ambient |
| Safety features | Overheating protection, short circuit prevention, insulated tools required |
| Installation clearance | 20 cm away from wall |
| Assembly tools | Electric screwdriver, crosshead screwdriver, nipper |
| Included accessories | Wires (450mm, 280mm, 150mm black; 380mm red), tubes, grommets, screw nuts |
| Warranty conditions | Void if overheated, water damaged, or foreign objects inserted |
Frequently Asked Questions - BPH A36T-6 PowerPlus
User questions about BPH A36T-6 PowerPlus
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Rechargeable Battery in PDF format for free! Find your manual BPH A36T-6 - PowerPlus and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. BPH A36T-6 by PowerPlus.
USER MANUAL BPH A36T-6 PowerPlus
User Manual Battery Pack
1. Important Safety Warnings
Please comply with all warnings and operating instructions in this instruction strictly. Read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.
- Do not try to assemble or repair the unit yourself, contact your local supplier, seek for help of qualified technician
- To eliminate any overheating of the battery box, keep all ventilation openings free from obstruction and do not place any foreign objects on top of the battery bank. Keep the battery box 20 cm away from the wall.
- Make sure the battery box is installed within the proper environment as specified. (0-40°C and 30-90% non-condensing humidity)
- Do not install the battery box under direct sunlight. Your warranty will be void if the batteries fail due to overheating.
- This battery box is not designed for use in dusty, corrosive and salty environment.
- The warranty for this battery bank will be void if water or other liquid is spilled or poured directly onto the battery box. Similarly we do not warrant any damage to the battery box if foreign objects are deliberately or accidentally inserted into the battery box enclosure.
- The battery will discharge naturally if the system is unused for a period of time.
- It should be recharged every 2-3 months if unused. If this is not done, then the warranty will be null and void. During normal operation, the batteries will be automatically remained in charged condition.
- Servicing of batteries should be performed or supervised by trained personnel with knowledge of batteries and the required precautions.
- When replacing batteries, it is necessary to replace ALL batteries with the same quantity, type & capacity.
- CAUTION – Do not dispose of battery or batteries in a fire. The battery may explode.
- CAUTION – Do not open or mutilate the batteries. The electrolyte from the batteries is toxic and harmful to the skin and eyes.
- CAUTION – Risk of Electric Shock – Hazardous voltage may exist between battery terminals and ground. Test before touching with bare hands.
☐ CAUTION – A battery can present a risk of electrical shock and high short circuit current. The following precaution should be observed when working on batteries:
- Remove watches, rings, or other metal objects.
- Use tools with insulated handles.
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect charging source prior to connecting or disconnecting battery terminals.
☐ Do not plug or unplug the battery connector if UPS works in DC (discharging) mode.
Installation and Setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use
Storage & Maintenance
The unit contains no user-serviceable parts. If the battery service life (3\~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.
Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.
Storage
Before storing, charge the unit 4 hours. Store the unit covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:
Storage Temperature Recharge Frequency Charging Duration
-25°C - 40°C Every 3 months 1-2 hours
40°C - 45°C Every 2 months 1-2 hours
SOP – How to assemble Battery Pack with 6 batteries (BP A36T-6x9Ah)
| Tubes | 450mm | 280mm | 1. As shown, please use three batteries (12V/7Ah or 12V/9Ah) and check the date code (it's necessary to use batteries with same date code in a UPS unit). Serial connect batteries with three black wires in 450, 280, 150 mm length. Slip the end of black wire with 280mm length into the tube. | |
| 2 | 4 | |||
| 150mm | 2. Connect red wire with 380mm length to battery and slip red wire into the tube. | |||
| 380mm | 1 | 3 | NOTE: This will prevent short circuit from direct contact of terminal. | |
| 3. Put the three batteries in order as shown in chart. Hint: Install the left one and keep battery terminal heading the bottom. Then, install the middle one and keep battery terminal heading upwards. At least, install the right one and keep battery terminal heading upwards. | ||||
| 1 | 2 | 3 | ||
| Red wire passes here | Black wire passes here | |||
| 1 | 4. Put grommet inside the hole of battery divider and allow red and black wire passing through the hole. Screw tightly the battery divider with screw nuts. (as shown in 1, 2 areas) M4 screw nuts: 38-210003-00G*2 Torque: 8KGF-CM | |||
| 2 | ||||
| Tool: electric screwdriver, crosshead screwdriver, nipper |
CAUTION: 1. Be sure all wires are plugged correctly and tightly. Do NOT break any wire tubes. 2. Do NOT connect battery terminal to any metals. Otherwise, it will cause short circuit. 3. Any screw should be screwed tightly without missing.

- As shown, please use three batteries (12V/7Ah or 12V/9Ah) and check the date code (it's necessary to use batteries with same date code in a UPS unit).
Serial connect batteries with three black wires in 450, 280, 150 mm length. Slip the end of black wire with 280mm length into the tube.
- Connect red wire with 380mm length to battery and slip red wire into the tube.
NOTE: This will prevent short circuit from direct contact of terminal.

- Put the three batteries in order as shown in chart. Hint: Install the left one and keep battery terminal heading the bottom. Then, install the middle one and keep battery terminal heading upwards. At least, install the right one and keep battery terminal heading upwards.

- Put grommet inside the hole of battery divider and allow red and black wire passing through the hole. Screw tightly the battery divider with screw nuts. (as shown in 1, 2 areas)
M4 screw nuts: 38-210003-00G*2
Torque: 8KGF-CM
-
Disconnect the battery red wire to P5 and P10 of small board. Disconnect the battery black wire to P5 and P10 of small board.
-
Organize the battery wires with cable tie.
CAUTION: 1. Be sure all wires are plugged correctly and tightly. Do NOT break any wire tubes. 2. Do NOT connect battery terminal to any metals. Otherwise, it will cause short circuit. 3. Any screw should be screwed tightly without missing.
Tool: electric screwdriver, crosshead screwdriver, nipper