CyberPower RB1270X4A - Battery

RB1270X4A - Battery CyberPower - Free user manual and instructions

Find the device manual for free RB1270X4A CyberPower in PDF.

📄 2 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice CyberPower RB1270X4A - page 1
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Sealed Lead-Acid Battery (VRLA)
Model RB1270X4A
Nominal Voltage 12V
Capacity (20hr rate) 7.2Ah
Dimensions (L x W x H) 5.94 x 2.56 x 3.70 inches (151 x 65 x 94 mm)
Weight 4.85 lbs (2.2 kg)
Terminal Type F1 (0.187 inch) and F2 (0.250 inch) compatible
Chemistry Lead-Acid, Absorbent Glass Mat (AGM)
Maintenance Valve-regulated, maintenance-free
Operating Temperature Charge: 32°F to 104°F (0°C to 40°C); Discharge: -4°F to 122°F (-20°C to 50°C)
Storage Temperature 32°F to 86°F (0°C to 30°C)
Max Charging Current 2.16A (0.3C)
Float Charging Voltage 13.5V to 13.8V at 77°F (25°C)
Cycle Charging Voltage 14.4V to 15.0V at 77°F (25°C)
Safety Features Overcharge protection, flame-retardant casing
Spare Parts & Repairability Battery is sealed and non-repairable; replace entire unit
Compliance UL, CE, RoHS certified
Typical Application UPS (Uninterruptible Power Supply) backup, emergency lighting, alarm systems
Expected Lifespan 3-5 years typical (depends on usage and environment)
Disposal Recycle at designated lead-acid battery recycling center

Frequently Asked Questions - RB1270X4A CyberPower

What is the voltage and capacity of the CyberPower RB1270X4A battery?
The battery is a 12V, 7.2Ah sealed lead-acid battery (AGM technology).
Can I use this battery in any CyberPower UPS?
It is designed as a direct replacement for CyberPower UPS models that use a 12V 7.2Ah battery. Check your UPS manual for compatible battery part numbers.
How do I install the RB1270X4A battery?
Disconnect the UPS from power, open the battery compartment, disconnect the old battery terminals, and replace with the new one, ensuring correct polarity (red to positive, black to negative).
How long does it take to charge this battery?
It typically charges fully in 4-6 hours with a standard UPS charger. Avoid overcharging; the UPS regulates the charge automatically.
What is the lifespan of the RB1270X4A battery?
Expected lifespan is 3-5 years, depending on temperature, discharge cycles, and quality of charging.
Can I replace the RB1270X4A with a higher capacity battery?
It is not recommended as the UPS charger is designed for a specific capacity. Using a higher capacity may cause undercharging or overheating.
How should I dispose of this battery when it fails?
Do not throw in trash. Recycle at a certified lead-acid battery recycling facility or return to a retailer with a battery take-back program.
What safety precautions should I take when handling the battery?
Wear protective gloves and eyewear. Avoid short-circuiting terminals. Keep away from sparks and flames. The battery contains sulfuric acid; if leakage occurs, neutralize with baking soda.
What does 'RB1270X4A' stand for?
It is a CyberPower model number: 'RB' for Rechargeable Battery, '12' for 12V, '70' for 7.0Ah (rounded), and 'X4A' for the specific form factor and terminal type.
Is the RB1270X4A battery maintenance-free?
Yes, it is a valve-regulated lead-acid (VRLA) AGM battery that does not require water topping or electrolyte checks.

User questions about RB1270X4A CyberPower

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Battery in PDF format for free! Find your manual RB1270X4A - CyberPower and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. RB1270X4A by CyberPower.

USER MANUAL RB1270X4A CyberPower

Intelligent LCD Series, AVR Series

MODEL: CP600LCD, CP825LCD, CP800AVR, CP685AVR-G, CP825AVR-G, CP685AVRLCD-G, CP825AVRLCD-G, AVRG750U, AVRG900U, AVRG750LCD, AVRG900LCD

CyberPower RB1270X4A - Intelligent LCD Series, AVR Series - 1

natural_image Three technical line drawings of a mechanical assembly or housing component, showing front, side, and top views with no visible text or symbols.
  1. Place the UPS on its top and remove the retaining screw (figure 1).
  2. Slide the battery compartment cover completely off of the unit (figure 2).
  3. Remove the battery from the compartment and disconnect the battery wires from the battery. Install the replacement battery by connecting the red wire to the positive (+) terminal and the black wire to the negative (-) terminal of the battery. (figure 3)
  4. Slide the battery compartment cover over the battery and tighten the retaining screw.
  5. Charge the unit for 4–8 hours to ensure the UPS performs expected runtimes.

MODEL: CP850AVRLCD, CP1000AVRLCD
CyberPower RB1270X4A - Intelligent LCD Series, AVR Series - 2

natural_image Three technical line drawings of a 3D mechanical component with no visible text or symbols
  1. Place the UPS on its side and locate the battery compartment cover on the bottom of the UPS. Remove the four (4) retaining screws and pull the battery compartment cover off the UPS (figure 1 & 2).
  2. Remove the battery from the compartment and disconnect the battery wires from the batteries. Install the replacement batteries by connecting the red wire and black wire to the same color wires from the battery pack. Put the battery pack into the compartment (figure 3).
  3. Slide the battery compartment cover over the battery and tighten the retaining screw. Charge the unit for 4 - 8 hours to ensure the UPS performs expected runtimes.

1

AVR Series

MODEL: CP900AVR, CP1200AVR, CP1500AVRT, CP1285AVRLCD, CP1350AVRLCD, CP1500AVRLCD

Technical diagram showing six steps of a device component assembly with numbered labels and directional arrows indicating movement.

  1. Place the UPS on its side to locate and remove the front panel retaining screws from the bottom of the UPS.
  2. Slide the cover (front panel) towards the bottom of the UPS.
  3. Remove it from the unit.
  4. Disconnect the cable located at the top of the cover.
  5. Disconnect the battery wires from the batteries.
  6. Remove the batteries from the compartment.
  7. Install the replacement batteries by connecting the red and black wires to the same color wires from the battery pack. Put the battery pack back into the compartment.
  8. Replace the battery compartment cover and tighten the retaining screw. Charge the unit for 4-8 hours to ensure the UPS performs expected runtimes.

Smart APP Intelligent LCD Series

MODEL: OR500LCDRM1U, OR700LCDRM1U, OR1000LCDRM1U, OR1500LCDRM1U

Diagram showing five steps of a device or folder assembly with labeled components and an inset magnified view.

  1. Remove the right side front panel.
  2. Remove the three retaining screws for the cable protection cover and remove the cover.
  3. Disconnect the black and red cable.
  4. Remove the one retaining screw holding the battery pack in place.
  5. Remove the battery pack.
  6. Install the new battery pack. Assemble the screws, cover, cable and front panel in the reverse order of the previous steps. Charge the unit for 4-8 hours to ensure the UPS performs expected runtimes.

MODEL: OR1500LCDRM2U, OR2200LCDRM2U, OR1500LCDRTXL2U, OR2200LCDRTXL2U
123 A 5 6

  1. Remove the right side front panel.
  2. Remove the three retaining screws for the cable protection cover and remove the cover.
  3. Remove the two retaining screws from the cable connectors.
  4. Disconnect the black and red cable.
  5. Remove the four retaining screws holding the battery pack in place.
  6. Remove the battery pack.
  7. Install the new battery pack. Assemble the screws, cover, cable and front panel in the reverse order of the previous steps. Charge the unit for 4-8 hours to ensure the UPS performs expected runtimes.

MODEL: CPS1500AVR
Diagram showing five views of a device with labeled components and an inset magnified view highlighting a cable or connector.

  1. Remove the right side front panel.
  2. Remove the two retaining screws for the cable protection cover and remove the cover.
  3. Disconnect the black and red cable.
  4. Remove the four retaining screws holding the battery pack in place.
  5. Remove the battery pack.
  6. Install the new battery pack. Assemble the screws, cover, cable and front panel in the reverse order of the previous steps. Charge the unit for 4-8 hours to ensure the UPS performs expected runtimes.

Smart APP SINEWAVE Series

MODEL: PR750LCD
Diagram showing exploded view of a multi-case device with labeled components and internal components

  1. Remove the front panel of the UPS.
  2. Pull out both round knobs and remove the battery compartment cover completely off of the unit.
  3. Remove the batteries from the compartment.
  4. Disconnect the battery wires from the batteries.
  5. Install the replacement batteries by connecting the wire bundle (composed of one red wire and one black wire) to the connector from the battery pack. Put the batteries back into the compartment.
  6. Re-install the battery compartment cover and push both round knobs back into place. Put the front panel back on the UPS.
  7. Connect to AC power and charge the new batteries for up to 16 hours to insure a full charge.

MODEL: PR1000LCD
Diagram showing four steps of a computer or device installation, labeled 1 to 4 with Chinese characters indicating components.

  1. Remove the front panel of the UPS.
  2. Remove two screws from the battery compartment cover and slide the cover completely off of the unit.
  3. Remove the batteries from the compartment. Disconnect the battery wires from the batteries.
  4. Install the replacement batteries by connecting the wire bundle (composed of one red wire and one black wire) to the connector from the battery pack.
  5. Put the batteries back into the compartment. Re-install the battery compartment cover and tighten the retaining screws. Put the front panel back on the UPS.
  6. Connect to AC power and charge the new batteries for up to 16 hours to insure a full charge.

4

MODEL: PR1500LCD
CyberPower RB1270X4A - Smart APP SINEWAVE Series - 3

natural_image Exploded view diagram of four electronic devices with internal components (no text or labels)
  1. Remove the front panel of the UPS.
  2. Remove two screws from the battery compartment cover and slide the cover completely off of the unit.
  3. Remove the batteries from the compartment. Disconnect the battery wires from the batteries.
  4. Install the replacement batteries by connecting the wire bundle (composed of one red wire and one black wire) to the connector from the battery pack.
  5. Put the batteries back into the compartment. Re-install the battery compartment cover and tighten the retaining screws. Put the front panel back on the UPS.
  6. Connect to AC power and charge the new batteries for up to 16 hours to insure a full charge.

MODEL: PR2200LCD, PR3000LCD
Diagram showing four views of a laboratory or industrial equipment unit with labeled components and an inset close-up view.

  1. Remove the front panel of the UPS and two screws from the battery compartment cover and slide the cover completely off of the unit.
  2. Pull out the battery pack on the outside from the compartment. Disconnect the battery connector from the batteries.
  3. Before removing the battery pack on the inside, unlock the cable tie and pull out the battery wires. Disconnect the battery connector from the batteries.
  4. Install the replacement battery pack on the inside by connecting the wire bundle connector (composed of one red wire and one black wire) to the connector from the battery pack. Lock the battery wires back with the cable tie.
  5. Install the replacement batteries on the outside by connecting the wire bundle connector (composed of one red wire and one black wire) to the connector from the battery pack. Put the battery pack on the outside back into the compartment.
  6. Re-install the battery compartment cover and tighten the retaining screws and put the front panel back on the UPS.
  7. Connect to AC power and charge the new batteries for up to 16 hours to insure a full charge. Note: The battery pack on the outside has a fuse, while the battery pack on the inside does not.

5

MODEL: PR750LCDRM1U, PR1000LCDRM1U
Diagram showing six steps of file processing or storage with labeled components and arrows indicating movement.

  1. Remove the right side front panel.
  2. Remove the two retaining screws for the cable protection cover and remove the cover.
  3. Disconnect the black and red cable.
  4. Remove the one retaining screw holding the battery pack in place.
  5. Remove the battery pack.
  6. Install the new battery pack. Assemble the screws, cover, cable and front panel in the reverse sequence of the above steps. Charge the unit for 4-8 hours to ensure the UPS performs expected runtimes.

MODEL: PR1500SWRM2U, PR2200SWRM2U
Diagram showing six different electronic device configurations with labeled parts and a magnified inset highlighting a component detail.

  1. Remove the right side front panel.
  2. Remove the two retaining screws for the cable protection cover and remove the cover.
  3. Disconnect the black and red cable.
  4. Remove the four retaining screws holding the battery pack in place.
  5. Remove the battery pack.
  6. Install the new battery pack. Assemble the screws, cover, cable and front panel in the reverse order of the previous steps. Charge the unit for 4-8 hours to ensure the UPS performs expected runtimes.

6

MODEL: PR1000LCDRT2U, PR1000LCDRTXL2U, PR1500LCDRT2U, PR2200LCDRT2U, PR3000SWRM2U
Diagram showing six sequential steps of a device or electronic component with labeled parts and a magnified inset detail.

  1. Remove the right side front panel.
  2. Remove the three retaining screws for the cable protection cover and remove the cover.
  3. Remove the two retaining screws from the cable connectors.
  4. Disconnect the black and red cable.
  5. Remove the four retaining screws holding the battery pack in place.
  6. Remove the battery pack.
  7. Install the new battery pack. Assemble the screws, cover, cable and front panel in the reverse order of the previous steps. Charge the unit for 4-8 hours to ensure the UPS performs expected runtimes.

MODEL: PR1000LCDRTXL2Ua, PR1500LCDRTXL2U, PR2200LCDRTXL2U, PR3000LCDRT2U, PR3000LCDRTXL2U
1 2 3 4 5 6

  1. Remove the six retaining screws, and remove the front panel from the UPS.
  2. Remove the two retaining screws for the cable protection cover and remove the cover.
  3. Remove the two retaining screws from the cable connectors.
  4. Disconnect the black and red cable.
  5. Remove the three retaining screws holding the battery pack in place.
  6. Remove the battery pack.
  7. Install the new battery pack. Assemble the screws, cover, cable and front panel in the reverse order of the previous steps. Charge the unit for 4-8 hours to ensure the UPS performs expected runtimes.

CyberPower RB1270X4A - Smart APP SINEWAVE Series - 9

PFC SINEWAVE Series

MODEL: PR5000LCDRTXL5U, PR6000LCDRTXL5U
CyberPower RB1270X4A - PFC SINEWAVE Series - 1

flowchart
graph TD
    A["Raw Material Input"] --> B["Material Release"]
    B --> C{Material Breakout}
    C -->|Yes| D["Process Unit"]
    C -->|No| E["Product Output"]
    D --> F["Final Assembly"]
    E --> F
  1. Remove the front panel.
  2. Remove the two retaining screws of the cable protection cover and remove the cover.
  3. Pull the plastic sticker out slowly to remove the battery module.
  4. Put the new battery modules back into the compartment
  5. Tighten the screws and replace the cable protection cover and the front panel.

MODEL: CP850PFCLCD, CP1000PFCLCD
CyberPower RB1270X4A - PFC SINEWAVE Series - 2

natural_image Four technical line drawings of a device housing with internal components and mounting points (no text or symbols)
  1. Turn the UPS on its side. Remove the retaining screw located on the bottom of the UPS.
  2. Slide the battery compartment cover completely off of the unit.
  3. Remove the batteries from the compartment.
  4. Disconnect the battery wires from the batteries.
  5. Install the replacement batteries by connecting the red wire (+) and black wire (-) to the same color connectors from the battery pack. Put the batteries back into the compartment.
  6. Slide back the battery compartment cover and tighten the retaining screw. Recharge the UPS for 8-16 hours to fully charge the battery

CyberPower RB1270X4A - PFC SINEWAVE Series - 3

MODEL: CP1350PFCLCD
Technical diagram showing four stages of a device housing assembly with labeled components and directional arrows

  1. Turn the UPS on its side. Remove the front panel retaining screws located on the bottom of the UPS.
  2. Slide the battery compartment cover (front panel) completely off of the unit.
  3. Remove the batteries from the compartment.
  4. Disconnect the battery wires from the batteries.
  5. Install the replacement batteries by connecting the red wire (+) and black wire (-) to the same color connectors from the battery pack. Put the batteries back into the compartment.
  6. Slide back the battery compartment cover and tighten the retaining screws. Recharge the UPS for 8-16 hours to fully charge the battery.

MODEL: CP1500PFCLCD
CyberPower RB1270X4A - PFC SINEWAVE Series - 5

natural_image Technical line drawings of four different electronic component assemblies (no text or symbols)
  1. Turn the UPS on its side. Remove the front panel retaining screws located on the bottom of the UPS.
  2. Slide the battery compartment cover (front panel) completely off of the unit.
  3. Remove the batteries from the compartment.
  4. Disconnect the battery wires from the batteries.
  5. Install the replacement batteries by connecting the wire bundle (composed of one red wire and one black wire) to the connector from the battery pack. Put the batteries back into the compartment.
  6. Slide back the battery compartment cover and tighten the retaining screws. Recharge the UPS for 8-16 hours to fully charge the battery.

CyberPower RB1270X4A - PFC SINEWAVE Series - 6

FTTx Series

MODEL: OR1500PFCRT2U, OR2200PFCRT2U
128 4 5 6

  1. Remove the right side front panel.
  2. Remove the three retaining screws for the cable protection cover and remove the cover.
  3. Remove the two retaining screws from the cable connectors.
  4. Disconnect the black and red cable.
  5. Remove the four retaining screws holding the battery pack in place.
  6. Remove the battery pack.
  7. Install the new battery pack. Assemble the screws, cover, cable and front panel in the reverse order of the previous steps. Charge the unit for 4-8 hours to ensure the UPS performs expected runtimes.

MODEL: CSN27U12V-NA2, CSN27U12V-NA3, CSN27U12V-NA3-G, CSN27U12V-XL
CyberPower RB1270X4A - FTTx Series - 2

natural_image Technical line drawings of three different electronic devices or enclosures (no text or symbols visible)
  1. Remove the battery cover.
  2. Disconnect battery cable connector to remove battery.
  3. Replace with new battery and re-connect the battery connector.
  4. Make sure battery is fixed properly in the compartment and close the battery cover.

MODEL: DTC36U12V-NA3-G
CyberPower RB1270X4A - FTTx Series - 3

natural_image Three-step diagram showing a device with labeled components and directional arrows (no text or symbols)
  1. Slide off the battery cover at the back of the DTC36U12V unit.
  2. Remove the battery from the enclosure.
  3. Disconnect both battery cable connectors.
  4. Install the new battery by connecting the red lead to the positive
    terminal and the black lead to the negative terminal.
  5. Slide the battery back into the normal operation.
  6. Replace battery cover to resume normal operation.

MODEL: CS24C12V2-E
123

  1. Remove the case screw.
  2. Open the battery cover.
  3. Loosen the battery strap.
  4. Disconnect battery cable connector to remove battery.
  5. Replace with new battery and re-connect the battery connector
  6. Tighten the battery strip
  7. Close the battery cover and lock the case screw.

CyberPower®

Cyber Power Systems, Inc.

www.cyberpower.com

For USA and Canada:

4241 12th Ave East, Suite 400

Shakopee, MN 55379

Toll-free: (877) 297-6937

For all other regions:

Please visit our website for local contact information.

CyberPower RB1270X4A - For all other regions: - 1