KING ECO2S KFS2415-1-2S1-ECM - Heating

ECO2S KFS2415-1-2S1-ECM - Heating KING - Free user manual and instructions

Find the device manual for free ECO2S KFS2415-1-2S1-ECM KING in PDF.

📄 4 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice KING ECO2S KFS2415-1-2S1-ECM - page 1
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Electric Furnace
Brand KING
Model ECO2S KFS2415-1-2S1-ECM
Series KF / KFS
Installation Orientations Vertical upflow, downflow, horizontal
Minimum Clearance 1 inch
Power Supply 240 V single phase (480 V optional)
Heating Element Type Resistance coils, sequenced
Blower Motor 1/3 HP, multi-speed (low, medium, high)
Maximum Airflow 2120 CFM (at 0.1 in. static)
Control System Low voltage thermostat (24 VAC)
Circuit Breakers Built-in 60 A per circuit
Air Filter Size 1 in. × 16 in. × 20 in.
Dimensions (Case) 30.5 in. tall (width and depth vary by model)
Weight Approximately 74 to 85 lbs (depending on configuration)
Safety Features High limit control, circuit breakers, grounding terminal
Accessories Combustible floor base, cooling coil, electronic air cleaner

Frequently Asked Questions - ECO2S KFS2415-1-2S1-ECM KING

How do I install the furnace?
The furnace can be installed in vertical upflow, downflow, or horizontal position. For downflow, the Combustible Floor Base Accessory must be used. Ensure at least 1 inch clearance. Refer to the installation instructions for duct connections and electrical wiring.
What are the required clearances?
King furnaces require a minimum of 1 inch clearance for compact, space-saving installations.
How do I connect the thermostat?
Connect the thermostat to terminals R (24 VAC) and W for heating, and to R and G for cooling (fan only). For two-stage models, use terminals W1 and W2. A jumper wire from W1 to W2 may be needed for single-stage thermostats.
What is the heat anticipator setting?
For models KFS5 through KFS13, set the thermostat heat anticipator to 0.4 amps. For models KFS20 through KFS35, set it to 0.8 amps (or 8 amps? Actually 0.8 amps per sequencer). Adjust according to the number of sequencers.
Why does the furnace not start?
Possible causes: circuit breaker off, 24V transformer burned out, loose wire connections, or thermostat issues. Check that all circuit breakers are ON, and inspect wiring. Also ensure the thermostat is set to heat and the temperature is below the set point.
What filter size does the furnace use?
The furnace uses a 1-inch thick, 16-inch by 20-inch air filter. Replace it several times a year or when dirty.
Can the furnace be used with a cooling unit?
Yes, the furnace can be equipped with a cooling coil for summer cooling. Use a heat/cool thermostat and set the fan switch appropriately. For cooling, set the thermostat to COOL and the fan to ON.
What is the sequence of operation?
When the thermostat calls for heat, after about 30 seconds the first heating element and blower turn on. Subsequent elements turn on at 30-second intervals. When satisfied, the elements turn off in reverse order.
How do I set the blower speed?
The motor has three speed taps: red (low), blue (medium), and black (high). Connect the desired speed wire to the fan relay. Refer to the airflow delivery chart for CFM at different static pressures.
What should I do if the furnace cycles on high limit?
This may indicate dirty ducts, a dirty air filter, or a defective limit control. Clean or replace the filter, check ducts for blockages, and if the problem persists, replace the limit control. Also check that the manual reset button (if equipped) is not tripped.

User questions about ECO2S KFS2415-1-2S1-ECM KING

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Heating in PDF format for free! Find your manual ECO2S KFS2415-1-2S1-ECM - KING and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. ECO2S KFS2415-1-2S1-ECM by KING.

USER MANUAL ECO2S KFS2415-1-2S1-ECM KING

king Electric Furnace

Installation Instructions

KF and KFS Series

KING furnaces can be installed with a minimum of 1 inch clearance for compact, space saving installations in either vertical upflow, downflow or horizontal position.

When installed in the downtown position, the Combustible Floor Base Accessory must be used.

CHECK furnace to be sure blower wheel is free-turning, and that element assemblies are in place. Be sure titer is in proper position and not tom or damaged.

NOTE: the attached Underwriters Laboratories' label pertains to the furnace only. It does not cover any air cooler, condensing unit or air cleaner, which may be used with the furnace. The optional COU cabinets are designed for slip in addition of an evaporator coil at a later date. Approval of the complete system of air conditioning requires compliance with local ones.

UL
KING ECO2S KFS2415-1-2S1-ECM - Installation Instructions - 1

natural_image Line drawing of a rectangular industrial machine with ventilation grille and control panel (no text or symbols)

KING ECO2S KFS2415-1-2S1-ECM - Installation Instructions - 2

FIELD WIRING: King furnaces come equipped with 60 amp circuit breakers installed for protection of the furnace internal wiring only. They also serve as a connection means when required. A 240 volt single phase circuit must be brought to each circuit breaker in the furnace as shown in the wiring diagram. The terminals are identified as L1-L2, L3-4, L5-6 and L7-L8. The KW size of the furnace determines how many circuits are required. The furnace power and electrical rating table indicates how many circuits each model furnace requires, the size of the branch circuit protection at the distribution panel and the wire size required from distribution panel to the furnace. If there is any questions consult your local and national electric codes. All wiring used must be approved for 75°. NOTE: no wire may have more than 180 VAC potential to ground. This must be checked on installation to avoid motor damage. Unit must be grounded by connection of grounding wire from the distribution panel to the terminal provided in furnace. When the line voltage terminal block option is specified for single strike, wire wiring diagram for wire size and circuit protection requirements.

KING ELECTRIC MFG CO · 9131 10TH AVENUE SOUTH · SEATTLE, WA 98100 · PH: 206 702 0400 · FAX: 206 763 7738 · www.king-electric.com

66048 Rev. 2-7-20

KING ELECTRIC FURNACE

  1. Your King electric turbines has been designed to distribute healed air to your living quarters when connected to appropriate ducting.

  2. On models KFS & larger, your furnace operates under command of a low voltage wall thermostat.

  3. Horials KFS5 through KFS13 enjoy one sequencer relay and thus the thermosat heat antiisperator should be set at 0.4.

  4. Records KESPO, then KESSS company two thermal relays, thus the thermostat heat anticipator should be set at 0.8.

  1. With the thermostel set at 70°F and the temperature drops to about 69°F, the thermostel's internal switch closes its contacts. About 30

seconds later the first heating element and the blower lamp ON. After another 31 seconds the second heating element is turned ON.

continuing in 30 second intervals until at the heating elements in the surface are "ON"

  1. When the thermostat is satisfied the "ON" process is reversed with the last element 6. Lower turning "OFF" simultaneously

  2. The words of the means could be saline heart loss (rest wall, one max. double, etc.) are much a means comfortable with the thinnest cat in bar

or lower than 71°F. It will take some experience to find your comfort rate setting.

  1. Your King electric furnace may be equipped with a ceiling coil to accomplish summer cooling. It may also be

equipped with an electronic air cleaner to reduce dust, pollen and other household respiratory irritabilities.

  1. If your furnace does not have an electronic air cleaner you will need to replace the furnace filter, several times

sturing the year or whenever it becomes dirt clogged.

  1. The furnace cannot deliver warm air unless.

(a) all electric circuit breakers are turned "ON"

(b) your furnace there are clamped with dust and dust. Air is the vehicle for heat transfer, thus in order to deliver

warm air an equal amount of cold air must be draw back to the humosa

(c) your thermal heat anticipator is not wrong - see paragraph lines and four above.

(2) your cold air return registers are blocked with furniture, throw rugs, etc.

(e) your warm air registers are blocked with furniture, throw rugs, etc.

11 If your furnace is contained with a cooling unit, your "Outdoor Condensate Unit" must be turned "ON" when summer cooling is required and your

impossessed result for included in the 40th quarter, and the consensus information should be 60 at about 70% then 30% of total

(###)

(a) The heat end the model on Limacas with cooling gradients, has a HEAT/OFF & COOL position. The fan

suctico as an AUTOMATIC and ON position

Jal. For heating the suction switch must be moved to HFA7 position and the tan section should be set to AUTOMATU.

Let For continue set the session to COOL and the far section to ON. Thus, the far will run constantly with the outdoor condensing unit running

only when you the thermostat calls for cooling.

(a). You now want the fan to run continuously in either HEAT or COOLING. You will have a custom in ON.

(b) The C/C portion shots down both heat and cooling and also shuts off the lan

(4) In winter, don't leave home with the furnace heated OFF. Instead set your thermostat at about 40°F and leave the furnace return in the

HEAT requires to action the reversibility of fracture of the indoor plumbing

                                                                                                                                                                                  1. 90.

(2017)57(2): 156-51-12, worked with the electronic wire wire.

MANUFACTURED HOUSING

DOWNFLOW INSTALLATION

  1. Select a suitable centralized location of the furnace: A Noel, alone or utility room.

  2. The role selection must be a key element that is an arbitrary and not in the initial department of one individual or planned institution of the share

Pecium

  1. Cut a 15" x 15" opening in the floor opening discharge opium for its location!

d. When the force is saturated for application into the finger corner. Suppose it is the floor with contact (at one point on each side).

  1. Cut the dust connector into the base opening and marking holes for cutting where the dust connectors mark out

  2. Domains the first component and act to the whole of working on place, and serve out part.

• 2017, the company was a major business center in the United States.

  1. 30000000000000000000000000000000000000000000000000000000000000000000

  2. It necessary out the line of dual connector so that it is below the top of linear base, approximately 1.

  3. The fact that the most recent 2016 data were obtained from the result of the results of the recent 2016 data and the time of death

(1) In addition, the resulting results of the _2 are not shown in particular with the present and present, respectively. The result is a negative coefficient estimate that from future

  1. Attach the duct connector to floor base using four (45-48) hex head 1/2" soft tapping screws.

  2. Present a black-farm house. The house alone does not be able to see the blue and of the brown house located. Decorated Star in

Wehren

  1. Make sure power is off on electrical circuits

  2. Dammum abses of humerus and labor stents abonded ulcers into an apicalcals, aminian annul plat and rivostatilina ac Instantine an alina

dagram.

  1. If needed, make sure any return air will lose a free air loss of not less than 195 square inches.

KING ECO2S KFS2415-1-2S1-ECM - DOWNFLOW INSTALLATION - 1

KFS Furnace Airflow Delivery Chart

Case SizeHP SpeedCFM (Static)
(0.1)(0.2)(0.3)(0.4)(0.5)(0.6)(0.7)(0.8)
Small Case 30.5" tall1/5Low1090980940890840820800760
Med126010901040980930890810780
High1370126012201170112010901080990
1/3Low17001680167016601650164016301620
Med18101800179017501740173017201710
High19601940193019101870186018501830
Large Case 30.5" tall1/5Low11601120109010501020990980850
Med131012301200115011201050990910
High1480141013901270124011801201040
1/3Low18601850184018301820181017901790
Med20001980196019401930192019101900
High21202100207020502030202020102000

Airflow delivery chart notes:

  1. CFM = cubic feet per minute

  2. Static = water column inches

  3. Performance based on air properties at sea level
  4. Includes factory provided air filter installed
  5. Includes electric heating coils installed, no power applied, no heat resistance
  6. Based on 230V, 5 speed motor.
  7. 480V motors are single speed only, use high speed for airflow delivery.

Double Motor Bracket (200mm) (100mm) Dr. Low Voltage Tenset of Block 5. Transformer Dual transformer is designed with a heavy high voltage range of 24V, thermalized for the external circuit. 6. Collector of The Dry Tail Sequence Exhausting heating demand based inductors always to monitor electrical systems in configuration with ICL and HCM standards. 7. Lighting Components Clock Heating, cyclic thermal- solarization, and any other power drain directly for the current load displacement by the external conventional circuit. 8. Surgeor for circuit breaker 3) 9. Power Supply For Field Only (Explorer Speed Order) 10. Ground Dig 11. Short 12. Air Force (Compressor or electric) 13. Air Force (Compressor or electric) 14. Air Force (Compressor or electric) 15. Air Force (Compressor or electric)

FES PART NUMBER DESCRIPTION

KFP-1000Holding Element: 5KW / 240V
KFP-1008AHolding Element: 5KW / 230V
KFP-1009DHolding Element: 5KW / 165A
KFP-1000CHolding Element: 5.2KW / 740V
KFP-1000GHolding Element: 5.2KW / 240V
KFP-1000EHolding Element: 4KW / 740V
KFP-1000FHolding Element: 4KW / 160V
2KFP-1001Line Unit Control - 0GT1C
3KFP-1009Circuit Breaker 80 Amp 10 (passing GE or SO2)
KFP-1009ACircuit Breaker 9 (Pine 50 Amp 50)
4KFP-1002Javel Terminal Block 10 KPS KH-18
KFP-1002AJavel Terminal Block 10 SF20 KFS-15
KFP-1002BJavel Terminal Block 30
5KFP-1004Low Voltage Transformer 24024
KFP-1004ALow Voltage Transformer 20024
KFP-1004BLow Voltage Transformer 2/7/24
KFP-1004CLow Voltage Transformer 49024

Plants note to provide & necessary information for the following: on body bits in packing and carrials for or standarding.

6KFP-1005Sequator (R200 Series)
KFP-1006ASequator (R201 Series)
KF-1006BFaday, 28 Amp. RF/80A
KF-1006CFaday, 28 Amp. RF/80A
7KFP-1006Manual Direct Unit
KFP-1006AManual Pulse Busco
8KFP-1007Dual Speed Tin Relay, RB221F
9KFP-1008Low Voltage Terminal Block
10KFP-1009Ground Lug
11KFP-10101/5 HP 240V Motor
KFP-1010A1/5 HP 450V Motor
KFP-1010B1/5 HP 340V Motor
KFP-1010C1/5 HP 450V Motor
KFP-1010D1/5 HP 240V Motor
12KFP-1011Gridbox for 1/5 HP 240V/450V
13KFP-1012Boxer Small (kWV - 260KW)
KFP-1012ABoxer Large (350W - 350W)
14KFP-1013Al Filter 1" x 16" x 20"

KF/KFS 1-PHASE

CATALOG NO.KWDTU (W)VOLTSAmpa*Onion Position 1 V^st Well SizeRoasted of PressureMotorTemperature Rise, °CColared SizeWt (Wx.)
L/D 12L/D 14L/D 16L/D 18L/D 12L/D 14L/D 16L/D 18VoltsHPLowModHigh
KRS2005-1310,226814,430410120817542°11°20°Dm. A
KRS2405-1413,624016,720410124019595°15°10°Dm. A
KRS2005-1517,126824,04046126814020°16°10°Dm. A
KRS2405-124023,6304101240630
KRS405-143039,415414
KFS2006-1630,5268254040226819524°22°19°Dm. A
KRS2010-126848,06046
KRS2405-11034,124041,76046226815041°31°22°Dm. A
KRS485-149023,830410
KRS2415-1 KRS485-2111,836,224047,93048224015047°42°20°Dm. A
48023,94048
KRS2015-1 KRS2415-11551,826872,14060604046326813061°53°47°Dm. A
24052,9506060410
KRS485-149031,25046
KRS2416-1 KRS485-224062,040604046
49035,9506046
KRS2020-1 KRS2405-1 KRS2405-12068,326896,260604646426811567°73°63°Dm. B
26883,3606046
KRS2020-1 KRS2405-143041,75046
KRS2016-1 KRS2405-12068,326896,260604646426813057°51°47°Dm. B
26883,3606046
KRS485-149041,76046
KRS2425-1 KRS485-2132,678,826893,860604646424011057°53°47°Dm. B
45048,5604646
KRS2025-1 KRS2425-1 KRS485-12585,3268120,23060604104646526811572°62°51°Dm. B
240104,23060604104646
KRS2030-1 KRS2405-1 KRS485-143052,130604124646
KRS2030-1 KRS2405-1 KRS485-130102,4268144,2606060464646826814066°79°52°Dm. B
240150,0606060464646
KRS2035-1 KRS2405-1 KRS485-134,5117,7268149,750606047464646826814090°73°71°Dm. B
49071,540474646

KF/KFS 3-PHASE

Cableing NumberKWBTU (100)VOLTSAmpaCanal Production kcal/L Air Max Size mm/L Number of ComponentsMotorTemperature RiseCapillary SizeWt (lbs.)
VoltsHPLowMedHigh
KF5203-9KF5203-9830.720024.94040#6#832081#5372258258Dim A74
KF5203-9KF5203-911.2530.420031.24040#6#832081#5458417314Dim A74
KF52413-9KF52413-91240.924040628.914.44520#6#1032404061#5426448365Dim A74
KF52013-9KF52013-9KF52013-91550.220024040041.636.1605830#6#1032082404001#5616552479Dim A74
KF52416-9KF52416-917.2558.820040043.336.76840#6#10324050065706677565Dim A74
KF52026-922.575.820042.566#6620865647552468Dim B85
KF52424-9KF52424-92481.624040057.729.87540#6#862404001#5656617429Dim B85
KF52036-9KF52036-9KF52036-930162.420024043083.372.236.111059#6#862082404901#5969707627Dim B85
KF52436-9KF52436-934.5117.724045082.941.514060#6#262401501#5967827711Dim B85

* Does not include motor load, refer to Air Delivery Chart

REFRS ACCESSORIES

MAYDESCRIPTIONW
1970-01924% W/ Thermal, Temperature range of 50°C to 60°C3
2011-Balance to 125°C for a sample dry7
1975-019Per impeller heat exchanger (1000 mV) to 2000 mV8
1975-019 Per impeller heat exchanger (1000 mV) to 2000 mV65
1975-020Moole pressure testing method1
1975-021Moole pressure testing method for the identification institution7
1975-022Control for AC cooling tool by a performance transition. The test is tests8
1975-023Control for AC cooling tool by a performance transition. The test is tests85

KPIKPS BUILT-IN OPTIONS

AircraftDESCRIPTION
4-5Engineed controls
40Leaseless for 100 W/m 30KW, 1-Pole (Max + 5 PWR Off to 2-Pole for single power power 60kW)
LHPSubstrate 100 PWR Solar & Power for 30KW to 100KW Panels
LHPSubstrate 100 PWR Solar & Power for 30KW to 100KW Panels
251The design of 100% PWR Power panels
252The design of 100% PWR Power panels

CONVERSION OF TORQUE TO HORSEPOWER

The power requirements for the Direct Drive vanies in this section are stated in torque units of ounce-inches and ounce-to-feet.

The formula listed below may be used to convert

toque 20housepoint.

TORQUE IN OZ-IN

HP=Torque (oz-in) x RPM1006.420HP=Torque (oz-1) x RPM84,033
These tables show horsepower as calculated from the above to male. The torque and RPM values need for the calculations are the same as those used in the curves in the catalog.
AIR DELIVERY CHART
AIRS (W)Water tankLoneMeltHigh
FallsJap.500140210770250
40230300/4208.41.77755726006301020
13330300/4209.21.7110074212255001500
12330300/4203.61.21250520140011201700
New CokeFuelGasMilk

NOCOLPHEN, PCB DIRECT OUT

DATETUES (MM)Capped Value in $MM (MM)426407
40(20)192240278361426
8(2)152025722020
20160.261.971.140.213.250.280.430.501.57
20185.021.371.110.222.269.115.233.456.71
20202.010.260.320.183.280.20.154.420.48
20225.020.250.110.163.222.210.222.303.44
20240.274.832.120.148.37.369.098.711.31
2018VANOSGross Profit (in € million)
Current Value (in € million)
€20€10€65€501.901.521.231.071.452
5.26.07.5103.01.62.21.93.25
15205.756.305.805.141.381.221.071.011.56
1.230.650.780.721.091.311.020.911.273.78
10520.590.710.670.911.231.091.332.425.5
6420.540.680.550.761.071.071.421.091.53
8301.450.670.670.760.921.241.361.141.24

CONTROL CIRCUIT WIRING DIAGRAMS:
SINGLE LOW VOLTAGE I-TEMPERAT HEAT FAN RELAY YELLOW RED GREEN FURCED TERMINAL BLOCK SPAC Current Route Pure only way

Heat Anticipatory Setting

Model KF or XFB 5 first 18 = .4 amps

Model KFS 20 thru 35 = 8 amps

KING ECO2S KFS2415-1-2S1-ECM - CONVERSION OF TORQUE TO HORSEPOWER - 2

flowchart
graph TD
    A["Power Supply"] --> B["Transformer Block"]
    B --> C["Output"]
    D["Qing Supply"] --> B
    E["External Component"] --> B
    F["External Component"] --> B
    G["External Component"] --> B
    H["External Component"] --> B
    I["External Component"] --> B
    J["External Component"] --> B
    K["External Component"] --> B
    L["External Component"] --> B
    M["External Component"] --> B
    N["External Component"] --> B
    O["External Component"] --> B
    P["External Component"] --> B
    Q["External Component"] --> B
    R["External Component"] --> B
    S["External Component"] --> B
    T["External Component"] --> B
    U["External Component"] --> B
    V["External Component"] --> B
    W["External Component"] --> B
    X["External Component"] --> B
    Y["External Component"] --> B
    Z["External Component"] --> B

KING ECO2S KFS2415-1-2S1-ECM - CONVERSION OF TORQUE TO HORSEPOWER - 3

flowchart
graph TD
    A["20VAC"] --> B["60VAC"]
    B --> C["20VAC"]
    C --> D["60VAC"]
    D --> E["20VAC"]
    E --> F["60VAC"]
    F --> G["20VAC"]
    G --> H["60VAC"]
    H --> I["20VAC"]
    I --> J["60VAC"]
    J --> K["20VAC"]
    K --> L["60VAC"]
    L --> M["20VAC"]
    M --> N["60VAC"]
    N --> O["20VAC"]
    O --> P["60VAC"]
    P --> Q["20VAC"]
    Q --> R["60VAC"]
    R --> S["20VAC"]
    S --> T["60VAC"]
    T --> U["20VAC"]
    U --> V["60VAC"]
    V --> W["20VAC"]
    W --> X["60VAC"]
    X --> Y["20VAC"]
    Y --> Z["60VAC"]
    Z --> AA["20VAC"]
    AA --> AB["60VAC"]
    AB --> AC["20VAC"]
    AC --> AD["60VAC"]
    AD --> AE["20VAC"]
    AE --> AF["60VAC"]
    AF --> AG["20VAC"]
    AG --> AH["60VAC"]
    AH --> AI["20VAC"]
    AI --> AJ["60VAC"]
    AJ --> AK["20VAC"]
    AK --> AL["60VAC"]
    AL --> AM["20VAC"]
    AM --> AN["60VAC"]
    AN --> AO["20VAC"]
    AO --> AP["60VAC"]
    AP --> AQ["20VAC"]
    AQ --> AR["60VAC"]
    AR --> AS["20VAC"]
    AS --> AT["60VAC"]
    AT --> AU["20VAC"]
    AU --> AV["60VAC"]
    AV --> AW["20VAC"]
    AW --> AX["60VAC"]
    AX --> AY["20VAC"]

CONTROL WIRING: Connect thermostat to terminals R and W for treating, and to R and G for cool air only. This can be done with a single stage heat cool thermostat or a single stage heat only thermostat and a separate fan only switch to control the fan relay (optional) installed on furnaces. Some models of furnace have two stage operation (optional) and are provided with terminals W1 and W2. If a single stage thermostat is used if should be connected to terminals R and W1 and a fumor wire installed form terminals W1 to W2; see enclosed control circuit wiring diagram. Some models of furnace have the 24 VAC power available between terminal C and R for use with external air conditioning blower relay option.

OPERATION: When control thermostat is turned up to demand heat the blower and heating elements should be energized. Furnaces with sequences installed will have up to 30 seconds delay in start-up. Heat-cool thermostats when turned to cool position should bring on the blower only for cooling air.

TROUBLE SHOOTER

TROUBLEPOSSRIF CAUSELREMEDY
Furne too thin, Blanche cold air• Thermosat heat anticipator sat too low • CFM of motor sat too high • Change of motor size from original• Replace with adheselike anticipated thermocor • Lower CFM of motor Red Wire - Low Speed Blue Wire - Medium Speed Stock Wire - High Speed • KFS6 - 18 should have 1/2HP motor, KFS16-05 should have a 1/2HP motor (2 & 3/4 HP motors are optional)
Furnace short oaths before Thermosat cells for oil• Thermosat anticipator sat too low • Intermittent upswing of thermosat or its wires • Heat element burned out • Circuit breaker off • Motor overheating• Adjust to .04 amps for each sequencer in furnace • Repair or replace Thermosat • Replace • Real • Replace
Furnace will not start• Slot wire not connected • Circuit breaker off • 24 Volt transformer burned out • Tire connection off or broken wires • Reset button slipped • Wrong Voltage• Repair • Real • Replace • Repair or Replace • Real • Check your power source
Motor will not stop• Detective sequencer or contractor• Replace
Furnace goes off on high limit• Dirty ducks • Dirty air water • Detective sequencer • Detective limit control • Power failure• Clean • Replace • Replace • Replace • Reset manual limit power button (10'320-05)
Furnace blower making too much air noise• Air filter dirty • Too small of duct • Too small plasium chamber • Not enough coil air• Replace • Enlange or replace • Replace • Replace
Vibration noise• Slower assembly hose • Lack of insulation• Secure motor and blower cage • Wrap furnace & duds with insulation
Furnace has a buzzing sound when not in use• Low voltage transformer defective or flame• Replace or lighton
Furnace continues to heat silks room is up to set temperature - does not cool off• Defective sequencer • Defective thermostat • Slot wires to ground • Motor wires to ground • Thermosat accidentally shunted & molecules are walked• Replace • Replace • Repair • Replace -- Make sure all connections are light

NOTE: When converting from oil, gas, etc., to sputate, replace your old low voltage thermostat that has a fixed-hat inhibitor with one that has an adjustable heat inhibitor.

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : KING

Model : ECO2S KFS2415-1-2S1-ECM

Category : Heating